Cat EMCP 3.1 3.2 3.3 Generator Set Control Application & Installation Manual - PDF DOWNLOAD

Page 19

13

3.5

Wiring Requirements

50 Foot Requirements Component

Wire Type of Wire Size (AWG) Three-Wire Sensors 16 Shielded twisted triad cable is recommended. For (when applicable. Not used on all systems)

Two-Wire Components (Magnetic Speed Sensors and some data links)

Engine Solenoids (Air Shutoff) Power

(1)

Connections(1)

Deutsch DT type of connectors are recommended. If Spring Spade or Ring Terminals are used, the connection between the 16 or 18 Shielded twisted pair cable is recommended. For conduits terminals inside facilities, use the 123-2376 Electrical Cable or the and the wire 3E-4594 Electrical Cable. For the engine harness, use the should be 6V-2744 Wire. The cable must be resistant to fuel and oil. crimped and The cable must have a temperature range of minus 40º C soldered. (40º F) to plus 125º C (257º F). conduits inside facilities, use Belden 8618. For the engine harness, use the 4G-2556 Shielded Cable. The cable must be resistant to fuel and oil. The cable must have a temperature range from minus 40º C (40º F) to plus 125º C (257º F).

10

Stranded wire normally used on engine harnesses. The cable must be resistant to fuel and oil. The cable must have a temperature range of minus 40º C (40º F) to plus 125º C (257º F).

The number of connections must be kept to a minimum.

The leads of the cable should have Spring Spade Terminals or Ring Terminals. The Connection between the wire and the terminal should be crimped and soldered.


Turn static files into dynamic content formats.

Create a flipbook
Issuu converts static files into: digital portfolios, online yearbooks, online catalogs, digital photo albums and more. Sign up and create your flipbook.