101
Reset Crank Attempt Counter $0404 (1028) - 1 register (2 bytes) long - Write Resets the accumulated number of crank attempts made by the engine. Write $AA55 followed by $55AA within 1 second to reset the counter to zero.
Reset Successful Start Counter $0405 (1029) - 1 register (2 bytes) long - Write Resets the accumulated number of successful starts of the engine. Write $AA55 followed by $55AA within 1 second to reset the counter to zero.
Reset kW Hour Meter $0406 (1030) - 1 register (2 bytes) long - Write Resets the total kilowatt-hours that have been exported by the generator. Write $AA55 followed by $55AA within 1 second to reset the meter to zero.
Reset kVAr Hour Meter $0407 (1031) - 1 register (2 bytes) long - Write Resets the total kilovar-hours that have been exported by the generator. Write $AA55 followed by $55AA within 1 second to reset the meter to zero.
Reset Service Interval Counter $0408 (1032) - 1 register (2 bytes) long - Write Resets the countdown until the next service inspection is required. This is usually performed at the end of a service call. Write $AA55 followed by $55AA within 1 second to reset the counter to zero. This is usually performed at the end of a service call. Event System The EMCP 3 displays both internal events and those transmitted over the J1939 data link. Over SCADA, the status of the warning and shutdown lamps on the display can be viewed, and events can be acknowledged. Events can be acknowledged individually or as a group, and the event count can be read. Details of both EMCP 3 and supported optional module events can be read over SCADA.
Acknowledge All Events Command $0130 (304) - 1 register (2 bytes) long - Write SCADA command to acknowledge all events, similar to pressing the Alarm Acknowledge key on the control. Each time a TRUE is written to this register, all of the events are momentarily acknowledged. Resolution
Offset
Data Range
1 / bit
0
0 to 1
Bit Definitions: 00 = FALSE 01 = TRUE