BEAM SMOKE SPECIALIST DEVICES
FIRE ALARMS, PANELS & DETECTORS
Firebeam - 2
2
YEARS
EN54
Features The firebeam specialist detection system is reliable and easy to maintain, and more importantly it will reduce the risk of expensive false alarms and misalignment faults. Beam detectors offer a cost effective solution for protecting large open spaces. One single unit installed on a wall can detect smoke over areas far greater than that of traditional point detectors.
Ideal For Protecting Areas Such As: • Warehouses • Theatres • Sport centres
• Places of worship • Atriums • Supermarkets
Mid Range Distance Kits (70-140 Metres) Designed to cover distances between 70 and 140 metres, the Fire Beam Mid Range Kit is a clear acrylic plate with 3 extra reflectors attached.
Product Code
Long Range Distance Kit (140-160 Metres)
F/CHBM/SA/2
Self adjusting beam detector 7 - 70m range
Designed to cover distances between 140 and 160 metres, the Fire Beam Long Range Kit is a clear acrylic plate with 8 extra reflectors attached. Simply add the Single Reflector that is provided with the standard Fire Beam into the spare space on the plate using the screws provided. Firebeam is designed to fully comply with EN 54 part 12. and exceeds European standards, in particular BS5839 part 1.
F/CHBM/70/KIT/2
70 - 140m range kit for CHBM/SA/2
F/CHBM/140/KIT/2
140 -160m range kit for CHBM/SA/2
F/CHBM/ADAPTER
Unistrut Adapter for CHBM/SA/2
Description
Self Adjusting Beams
Anti-Fog Kits SP/CHBM/70KIT
Anti-Fog 70-140m range kit for CHBM/SA/2
SP/CHBM/140/KIT
Anti-Fog 140-160m range kit for CHBM/SA/2
Distance & Position Guidelines A roof is considered flat unless the height of the apex is greater then 0.6m. If the roof is fl at fi rebeam system can be placed anywhere under the roof between 0.3m and 0.6m below the roof, up to a maximum height of 40m from the fl oor. Firebeam has a detection area of 7.5m either side of the beam. If the roof is considered to have an apex, place the fi rebeam system 0.3m to 0.6m down from the top of the apex, up to a maximum height of 40m from the fl oor. The maximum protected area either side of the beam can be extended by 1% for every degree of roof pitch, see the example.
0.3m – 0.6m
Extra coverage due to apex angle 10°
40m max 2.7m min
0.3 – 0.6m
15 + (15 x 10%) = 15m + 1.5m = 16.5m
8.25m
8.25m
16.5m detection area
Field of view should be a 50cm radius from the centre or the beam Wall
Flat roof 0.3 – 0.6m
Min 0.5m
Wall
You should always position the beam at least 0.5m away from any protrusion
15m detection area Please note: For further information on this specilaist range contact our sales team on 0845 884 7000.