661 Loram Way Home Inspection

Page 1

FOCUS INSPECTION AUTHORITY

(949) 945-0111

focusinspectionauthority@gmail.com

https://focusinspectionauthority.com/

RESIDENTIAL INSPECTION - R/R

661 Loran Way Tustin, CA 92782

Scott Woodburn MAY 15, 2024

Inspector

Randall Meadows

InterNACHI CMI #131727 CPI #19012717 (949) 945-0111

focusinspectionauthority@g mail com

Inspector

Abraham Bravo

InterNACHI CPI#20080414 (949) 945-0111

focusinspectionauthority@g mail com

Inspector

Greg Estrada InterNACHI CPI #21122734 (949) 945-0111

focusinspectionauthority@g mail com

Agent

Scott Woodburn EXP Realty (949) 433-7803

scott@zteamreg com

661 Loran Way Scott Woodburn FOCUS Inspection Authority Page 1 of 139
661 Loran Way Scott Woodburn FOCUS Inspection Authority Page 2 of 139
CONTENTS 1: Inspection Details 2: Roof 3: Attic, Insulation & Ventilation 4: Exterior 5: Foundation & Under Floor Structure 6: Plumbing Main 7: Electrical Main 8: Cooling System 9: Cooling System 2 10: Heating System 11: Heating System 2 12: Water Heater/Hot Water System 13: Garage 14: Interior Details 15: Laundry Room 16: Living Room 17: Dining Room 18: Fireplace 19: Fireplace 2 exterior 20: Kitchen & Built-in Appliances 21: Hallways/Trac Areas 22: Home Bar 23: Steps/Stairway/Railings 24: Bedroom 1 25: Bedroom 2 26: Bedroom 3 27: Bedroom 4 28: Oce/Loft 8 19 26 28 43 47 51 54 58 62 65 67 70 76 78 80 81 83 88 91 99 101 103 104 108 110 113 114
TABLE OF

29: Bathroom 1

30: Oce/Loft - Upstairs

31: Bathroom 2

32: Bathroom 3

33: 1/2-1/3 Bath

34: Bathroom 4

35: Thermal Camera Walkthrough

36: Environmental Concerns

37: Final Check List

38: Closing Remarks

661 Loran Way Scott Woodburn FOCUS Inspection Authority Page 3 of 139
Standards of Practice 117 120 122 126 128 130 132 134 136 137 139

MAINTENANCE ITEM

SUMMARY

RECOMMENDATION SAFETY HAZARD

2.2.1 Roof - Coverings: Tree Too Close

2 2 2 Roof - Coverings: Tiles Cracked/Slipped/Missing

2 2 3 Roof - Coverings: Debris on Roof

2.2.4 Roof - Coverings: Discoloration

2 4 1 Roof - Penetrations/Plumbing Vents: Roof Vent Pipe Mastic Cracking/Deteriorating

2 6 1 Roof - Roof Drainage Systems: Gutters/Downspouts Debris

2.7.1 Roof - Chimneys: Chimney Caulking Needed

4.2.1 Exterior - Siding, Flashing & Trim: Siding Discoloration of Stucco

4 2 2 Exterior - Siding, Flashing & Trim: Siding Material Deciency - Minor

4.2.3 Exterior - Siding, Flashing & Trim: Siding Styrofoam Pop Out Deciency

4.2.4 Exterior - Siding, Flashing & Trim: Exterior House/Coach Lights Loose/Damaged/Missing/Not Sealed

4 2 5 Exterior - Siding, Flashing & Trim: Siding Stucco Spalling

4.2.6 Exterior - Siding, Flashing & Trim: Siding Texture Anomaly

4.2.7 Exterior - Siding, Flashing & Trim: Siding Wood Rot/Deterioration/Weathering

4 2 8 Exterior - Siding, Flashing & Trim: Open Penetrations

4.4.1 Exterior - Eaves, Sots & Fascia: Vine Intrusion Into Sot Attic Vents/Openings

4.4.2 Exterior - Eaves, Sots & Fascia: Wasp Nest

4 5 1 Exterior - Exterior Doors and Windows: Door/Window Screen Damaged

4.7.1 Exterior - Driveways & Walkways: Concrete Spalling - Minor

4.7.2 Exterior - Driveways & Walkways: Loose / cracking/ Missing Brick or Stone

4 7 3 Exterior - Driveways & Walkways: Patio Typical Settlement Cracks - Minor

4 7 4 Exterior - Driveways & Walkways: Walkway Cracking - Minor

4.7.5 Exterior - Driveways & Walkways: Mortar/Grout/Caulking

4 7 6 Exterior - Driveways & Walkways: Eorescence

4 8 1 Exterior - Decks, Patios, Balconies, Porches & Steps: Paint Deciency Noted

4.8.2 Exterior - Decks, Patios, Balconies, Porches & Steps: Wood Water Sealant Required

4.9.1 Exterior - Fence/Gate/Walls: Minor Settling Cracks/Separation Privacy Wall

4 10 1 Exterior - Vegetation, Grading, & Drainage: Negative Grading

661 Loran Way Scott Woodburn FOCUS Inspection Authority Page 4 of 139
57 41 16

4.10.2 Exterior - Vegetation, Grading, & Drainage: Drain Cover Broken

4 10 3 Exterior - Vegetation, Grading, & Drainage: Overgrowth of Trees/Vegetation Against Side of Structure

4.11.1 Exterior - Exterior Lighting Fixtures, Switches & Receptacles: Cover Plates Loose/Damaged/Missing

5.2.1 Foundation & Under Floor Structure - Slab Foundation: Foundation Cracks - Minor

5.2.2 Foundation & Under Floor Structure - Slab Foundation: Foundation Stem-Wall spalling or Cracks/Damage

5.2.3 Foundation & Under Floor Structure - Slab Foundation: Parge Coat Deciency on Foundation Stem Wall

7 1 1 Electrical Main - Main Panel: Main Panel Cover Deciency

7.4.1 Electrical Main - Branch Wiring Circuits, Breakers, Fuses & Junction Boxes: Loose Breaker

8.2.1 Cooling System - Cooling Equipment: Insulation Missing or Damaged

8 2 2 Cooling System - Cooling Equipment: Older Unit R-22 Refrigerant

8 2 3 Cooling System - Cooling Equipment: Plastic Platform Deciency

9.2.1 Cooling System 2 - Cooling Equipment: Insulation Missing or Damaged

9 2 2 Cooling System 2 - Cooling Equipment: Older Unit R-22 Refrigerant

9 2 3 Cooling System 2 - Cooling Equipment: Vegetation Too Close

9.2.4 Cooling System 2 - Cooling Equipment: Plastic Platform Deciency

10.4.1 Heating System - Distribution Systems: Ductwork Touching Deciency

12 2 1 Water Heater/Hot Water System - Equipment: No Drip/Catch Pan

12.2.2 Water Heater/Hot Water System - Equipment: Open Gaps in Wall Penetrations

12.2.3 Water Heater/Hot Water System - Equipment: Water Heater High Temp

13 5 1 Garage - Walls & Firewalls: Moisture Intrusion/Damaged/Stained Drywall

13.9.1 Garage - Garage Door Opener: Garage Door Safety Side Sensors Deciency

13.9.2 Garage - Garage Door Opener: Garage Door Opener Deciency

13 9 3 Garage - Garage Door Opener: Garage Door Safety Side Sensors Not Functioning

13.10.1 Garage - Lighting Fixtures, Switches & Receptacles: Cover Plates Loose/Damaged/Missing

14 6 1 Interior Details - Smoke/Carbon Monoxide Detectors: Smoke and or Carbon Monoxide Detector Deciency

15 11 1 Laundry Room - GFCI & AFCI: GFCI Protection Not Present/Found

16.7.1 Living Room - Cabinets & Countertops: Cabinet Doors/Drawers Need Adjustment or Repair

17.5.1 Dining Room - Walls: Minor Corner/Drywall Cracks

17 5 2 Dining Room - Walls: Wall Damage

18.2.1 Fireplace - Vents, Flues & Chimneys: Creosote Buildup Noted

18.4.1 Fireplace - Damper Doors: Flue Lock/Damper Stop

19 3 1 Fireplace 2 exterior - Lintels, Hearth and Hearth Extension: Cracked

20.2.1 Kitchen & Built-in Appliances - Kitchen Sink, Faucets, Plumbing: Caulking Deciency

20 3 1 Kitchen & Built-in Appliances - Kitchen Cabinets & Countertops: Countertop Cracked/Chipped/Damaged

20 3 2 Kitchen & Built-in Appliances - Kitchen Cabinets & Countertops: Cabinet Hardware Deciency

661 Loran Way Scott Woodburn FOCUS Inspection Authority Page 5 of 139

20.3.3 Kitchen & Built-in Appliances - Kitchen Cabinets & Countertops: Cabinet Thermofoil Peeling

20.3.4 Kitchen & Built-in Appliances - Kitchen Cabinets & Countertops: General Ware

20 5 1 Kitchen & Built-in Appliances - Dishwasher: Door Hinge Diciency

20 8 1 Kitchen & Built-in Appliances - Oven: Oven Fan Deciency

20.9.1 Kitchen & Built-in Appliances - Refrigerator: Ice/ Water Dispenser Deciency

20.9.2 Kitchen & Built-in Appliances - Refrigerator: Damaged Covering

21 9 1 Hallways/Trac Areas - Smoke Detectors: Not Functioning Properly

21.10.1 Hallways/Trac Areas - Carbon Monoxide Detectors: No Carbon Monoxide Alarm

22.2.1 Home Bar - Sink, Faucets, Plumbing: Previous Plumbing Leak Damage Observed

22 6 1 Home Bar - GFCI & AFCI: Inaccessible

24.3.1 Bedroom 1 - Windows: General Wear

24.3.2 Bedroom 1 - Windows: General Settling Crack on Sill

24 4 1 Bedroom 1 - Floors: Carpet Buckling

24.5.1 Bedroom 1 - Walls: Base Board/Crown Molding Damage/Loose

24.9.1 Bedroom 1 - Smoke Detectors: Not Functioning Properly

24 10 1 Bedroom 1 - Carbon Monoxide Detectors: No Carbon Monoxide Alarm

25.3.1 Bedroom 2 - Windows: General Wear

25.9.1 Bedroom 2 - Smoke Detectors: Not Functioning Properly

25 10 1 Bedroom 2 - Carbon Monoxide Detectors: No Carbon Monoxide Alarm

26.3.1 Bedroom 3 - Windows: General Wear

26.4.1 Bedroom 3 - Floors: Stains/Discoloration

26 8 1 Bedroom 3 - Lighting Fixtures, Switches & Receptacles: Light Inoperable/Not Luminating

26 9 1 Bedroom 3 - Smoke Detectors: Not Functioning Properly

26.10.1 Bedroom 3 - Carbon Monoxide Detectors: No Carbon Monoxide Alarm

27 10 1 Bedroom 4 - Carbon Monoxide Detectors: No Carbon Monoxide Alarm

28 5 1 Oce/Loft - Walls: Wall Damage

28.8.1 Oce/Loft - Lighting Fixtures, Switches & Receptacles: Light Inoperable/Not Luminating

28.8.2 Oce/Loft - Lighting Fixtures, Switches & Receptacles: Open Ground

28 10 1 Oce/Loft - Carbon Monoxide Detectors: No Carbon Monoxide Alarm

29.2.1 Bathroom 1 - Sink, Faucets, Plumbing: Sink Stopper Deciency

29.5.1 Bathroom 1 - Tub/Shower: Mildew/Caulking Deciency

29 5 2 Bathroom 1 - Tub/Shower: Bung Needed

29.9.1 Bathroom 1 - Floors: Cracked Floor Tiles

29.12.1 Bathroom 1 - Lighting Fixtures, Switches & Receptacles: Light Inoperable/Not Luminating

30 4 1 Oce/Loft - Upstairs - Floors: Soft Spots

30.5.1 Oce/Loft - Upstairs - Walls: Minor Wall/Corner Cracks

30.8.1 Oce/Loft - Upstairs - Lighting Fixtures, Switches & Receptacles: Light Inoperable/Not Luminating

30 9 1 Oce/Loft - Upstairs - Smoke Detectors: Not Functioning Properly

31 5 1 Bathroom 2 - Tub/Shower: Mildew/Caulking Deciency

31.5.2 Bathroom 2 - Tub/Shower: Tub Diverter Deciency

31.10.1 Bathroom 2 - Walls: Wall Damage

661 Loran Way Scott Woodburn FOCUS Inspection Authority Page 6 of 139

31.12.1 Bathroom 2 - Lighting Fixtures, Switches & Receptacles: Cover Plates Loose/Damaged/Missing

32.3.1 Bathroom 3 - Cabinets & Countertops: Bathroom Cabinet Damaged

32 5 1 Bathroom 3 - Tub/Shower: General Grout/Caulking Deciency

32 5 2 Bathroom 3 - Tub/Shower: Tub Diverter Deciency

33.8.1 1/2-1/3 Bath - Walls: Wall Damage

34.2.1 Bathroom 4 - Sink, Faucets, Plumbing: Loose Hardware

34 4 1 Bathroom 4 - Toilet: Inoperable

34.5.1 Bathroom 4 - Tub/Shower: General Grout/Caulking Deciency

34.7.1 Bathroom 4 - Doors: Door Hardware Deciency

36 2 1 Environmental Concerns - Rodent/Pest/WDO Concerns: Evidence of Microbial Growth Observed

661 Loran Way Scott Woodburn FOCUS Inspection Authority Page 7 of 139

1: INSPECTION DETAILS

section-MDkyYzFkYTEtNWQ5My00ZjQwLThhOTYtYTJiYTNiMTQ4NGIy

1.1 General Property Overview X

1.2 All Terms and Limitations X

1 3 InterNachi Guarantee X

General Property Overview: Type of Structure & Overview

Detached, Single Family, 2 Story, Slab on Grade Foundation, Wood Frame

General Property Overview: Occupancy Furnished, Occupied, Utilities On

General Property Overview: Home Square Footage 3100 Structure Sqft:

General Property Overview: In Attendance

Client's Agent

General Property Overview: Time On Site 2.5 Hours

General Property Overview: Lot Square Footage 3100 Lot Sqft:

General Property Overview: Inspected By: Randall Meadows, Abraham Bravo, Greg Estrada

General Property Overview: Style Traditional

General Property Overview: Year Built 2006 Year

General Property Overview: Temperature (approximate) 70 Fahrenheit (F)

General Property Overview: Weather Conditions Clear

General Property Overview: Direction House Faces North

Throughout this report, the terms "right" and "left" are used to describe the inspected property and/or any reportable conditions as viewed from the front entry

General Property Overview: Older Structure Built To Older Standards

Structure is built to older standards: The structure is built to older standards, including wood framing methods, seismic reinforcement, foundation system, plumbing system, electrical system and HVAC system that may not be up to todays standards of eciency This inspection is not a code inspection, however please understand that an older structure that was built to older standards and codes is only required to comply with current codes when a major remodel or replacement of a major system is performed Some older homes may not have had there major systems upgraded which means these systems may be originally installed when the the building was built making them the same age as the building. Upgrading older systems is always recommended. We recommend requesting full disclosure regarding any additions or system replacements/upgrades from seller

661 Loran Way Scott Woodburn FOCUS Inspection Authority Page 8 of 139
IN NI NP D
IN = Inspected NI = Not Inspected NP = Not Present D = Deciencies Information

General Property Overview: Overall Findings Pre-Purchase Inspections

Informational, Please Read:

All homes need periodic repairs and maintenance every year, both expected and unexpected. We recommend you budget for these items, in addition to elective repairs and immediate repairs Be sure to read the entire report to identify potentially expensive future repairs, safety issues, and upgrades. The report is intended to give you an idea of the overall condition and types of repairs needed, rather than a comprehensive list of all defects in your home You may notice additional defects that have not been addressed during the inspection or reected in the inspection report once you move in.

It is not uncommon for systems to fail between the inspection, purchase and move in, especially in a vacant house. On your nal walkthrough, be sure to run all the appliances again and check to make sure the HVAC is operating adequately. Look for new leaks in the ceilings upstairs, below all baths, under sinks and along interior and exterior wall lines Test all the plumbing xtures again to verify no leaks have started and all drains are still operational since the inspection.

Home Warranty Recommended:

We recommend purchasing a one year warranty based on the age of some of the mechanical systems and the likelihood for future repairs or replacements If systems are in need of repair at this time of inspection or are very old, we strongly recommend service before settlement/purchase to help prevent the warranty company from calling it a pre-existing condition and denying coverage

All Terms and Limitations: General Exterior/Interior Home Inspection Terms

GENERALIST INSPECTION: A property inspector is a Generalist and the inspection is conducted along generalist guidelines The generalist job is to note material defects in the subject property being inspecting When he/she observes and nds one or more problems in a system of the property that aects its performance he/she may then refer the entire system over to a specialist in that eld for a further detailed investigation The specialist is expected to conduct a more detailed examination on that system from his specialist sphere of knowledge and training to determine all the problems with the system and the related costs of repairs The specialist is inspecting from a depth of knowledge and experience that the generalist does not have "The home inspector is not a specialist" in this specic system It is expected that when a licensed contractor who specializes in this SYSTEM inspects the complete system, he/she may nd more conditions than the home inspector. This is the reason the home inspector recommends further evaluation and a complete inspection of this SYSTEM by a qualied licensed professional

NOT A WARRANTY: The Home Inspection and the Home Inspection Report DO NOT constitute and shall not be considered to be a WARRANTY, either expressed or implied, concerning the present or future condition of the Property

As written in the inspection contract "CLIENTS DUTY" Client agrees to read the entire written report when it is received and promptly call Inspector with any questions or concerns they may have with the report. The written report shall be the nal and exclusive ndings of Inspector Client acknowledges that Inspector is a generalist and that further investigation of a reported condition by a qualied licensed specialist may provide additional information which can aect Clients purchase decision. We recommend that the client obtain further evaluation of reported conditions by qualied licensed professional before removing any inspection contingency period and prior to the close of escrow Further information is listed under the General Limitations entry in this section.

OBSERVATION KEY & TERMS OF THE INSPECTION REPORT:

Minor Issues/Maintenance Items/DIY (colored in blue), Marginal Issues/Deciencies/Needs Attention (in orange), and Signicant Issues/Safety Concern (in red) Safety Hazards or Concerns will be listed in the Red or Orange categories depending on their perceived danger, but should always be addressed ASAP.

SERVICEABLE: It is the inspectors opinion that this system is doing the job for which it was intended and exhibits normal wear and tear

MINOR OR DEFERRED MAINTENANCE / MONITOR: (BLUE) It is the inspectors opinion that the system or item although minor, may be in need of, or will require maintenance repairs in the future as a normal course of home care The owner or potential owner should monitor this system with that intent. OR, this mark may also be use to alert the owner or potential owner of the current condition of a system or item, perhaps a minor cosmetic issue but worth noting.

DEFICIENCY / RECOMMENDATION / NEEDS ATTENTION: (Orange) It is the inspectors opinion that this SYSTEM is in need of further investigation and/or repairs, or appears to be at the end of its serviceable life. The inspector has made the client aware of this situation by recommending "FURTHER EVALUATION BY LICENSED PROFESSIONAL" It is now the "Clients" responsibility to take appropriate action concerning the SYSTEMS mentioned with the appropriate licensed professional before the end of the inspection contingency period and prior to the close of escrow

SIGNIFICANT AND/OR SAFETY CONCERN / NOT ACCEPTABLE: (RED) It is the inspectors opinion that this SYSTEM is either a SAFETY CONCERN or not functioning properly The inspector has made the client aware of this situation by recommending "FURTHER EVALUATION BY LICENSED PROFESSIONAL" in this home inspection report and it is now the "Clients Duty" to take appropriate action concerning the SYSTEMS with the appropriate qualied licensed professional before the end of the inspection contingency period and prior to the close of escrow.

661 Loran Way Scott Woodburn FOCUS Inspection Authority Page 9 of 139

All Terms and Limitations: Attic Inspection Terms and Limitations

Informational: Attic space limited access/visual inspection: Attic's area visually inspected however there are many visual obstacles in attics, Insulation can prevent visual inspection of drywall/plaster, ceiling joists, wiring, plumbing, lighting etc Insulation can also prevent inspector from being able to move about attic because the insulation covers the ceiling joists not giving the inspector something secure to walk or crawl on. Some attic heights are to low to enter and visual inspection can only be done from access hatch If access to attic is blocked and entry cannot be made for visual inspection, this will be noted in the Section Limitation

All Terms and Limitations: GFCI/AFCI Terms and Limitations

All GFCI electrical outlets in the kitchen and bathrooms, garage, laundry room, and exterior locations were checked for proper connection by GFCI Receptacle Testing Device and found to be in proper serviceable condition at the time of inspection, unless otherwise noted in report.

AFCI’s if present, were also checked for proper function. All were found serviceable at time of inspection, unless otherwise noted in report.

Informational: GFCI (Ground Fault Circuit Interrupter): The National Electrical Code now requires extra protection for outlets in specic areas of the home, such as kitchens, baths, utility rooms, laundry rooms, garages and outdoors Ground-fault circuit interrupters (GFCIs)- which are identiable by their TEST and RESET buttons-are generally required in proximity to wet locations If your wiring has not been upgraded with GFCIs you're not protected Absence of GFCI receptacles will be noted in this report. Recommend immediate upgrade by qualied licensed electrician if GFCI is Not present

All Terms and Limitations: Electrical Inspection Terms and Limitations

Fatal Shock Hazard Warning: Inspecting electrical components and systems risks death by electrocution as well as serious burns or other injuries to the inspector or to others. Do not attempt these tasks unless you are properly trained and equipped.

Electrical System is a "LIMITED VISUAL AND NON-INVASIVE INSPECTION of the SYSTEMS of the structure that are REASONABLY ACCESSIBLE." Features are operated with normal controls. The general wiring, switches, outlets and xtures are randomly checked in accessible areas Wiring in the main box is inspected by removing cover if accessible and safe for inspector to remove. While some observations may be code related, this inspection does not determine if the system complies with code The inspection does not determine electrical capacity, determine over current capacity for any item including appliances or compare circuit breaker capacity to installed appliance rating. Also excluded are interior or exterior low voltage wiring landscape lighting or any lighting outside the footprint of the building is not inspected. Light bulbs are not removed or changed during an inspection. It is common for homes to have extra wall switches that serve no purpose, these switches may be for future upgrades such as ceiling fans or they may be connected to a switched wall receptacle typically used to plug in a lamp. The current home owner is the best person to ask regarding wall switches and there purpose This inspection does not certify or warrant the system to be free of risk of re, electrocution, personal injury or death. Any recommendations about electrical throughout this report should be immediately further evaluated before the end of your inspection contingency period and the close of escrow by a qualied licensed professional electrician.

A representative number of (outlets) receptacles and switches are tested at time of inspection, occupied homes limit testing of many receptacles and switches because personal items and or furnishings are blocking or concealing them. You may nd a (outlet) receptacle or switch that is inoperative or damaged when storage and furnishings have been removed when you move in. In the event you nd a defective or damaged switch or receptacle you should contact a qualied licensed electrical professional immediately for repair or replacing Fixtures, Switches and Receptacle Information: Switches and xtures were tested for serviceability. A representative number of receptacles throughout the home were tested with a polarity tester to conrm proper wiring. No wiring deciencies were reported by the tester unless otherwise noted in this report.

While we do not evaluate cable, alarm, or media boxes, we do recommend that you call the service provider for further evaluation on the application of this component

GFCI/AFCI: GFCI (Ground Fault Circuit Interrupter): The National Electrical Code now requires extra protection for outlets in specic areas of the home, such as kitchens, baths, utility rooms, laundry rooms, garages and outdoors Ground-fault circuit interrupters (GFCIs)- which are identiable by their TEST and RESET buttons-are generally required in proximity to wet locations If your wiring has not been upgraded with GFCIs you're not protected Absence of GFCI receptacles will be noted in this report. Recommend immediate upgrade by qualied licensed electrician if GFCI is Not present

AFCI’s if present, were also checked for proper function. All were found serviceable at time of inspection, unless otherwise noted in report.

Note: Any alarm systems, electronic keypads; remote control devices; low-voltage interior speakers, intercom systems; low-voltage or 'solar' powered exterior landscape lighting; telephone and cable TV; and all local electric company equipment or components were not tested; which are beyond the scope of a professional home inspection

661 Loran Way Scott Woodburn FOCUS Inspection Authority Page 10 of 139

All Terms and Limitations: Plumbing Inspection Terms and Limitations

Plumbing Inspection Description: PLUMBING SYSTEM is a "LIMITED VISUAL AND NON-INVASIVE INSPECTION of the SYSTEMS of the home that are REASONABLY ACCESSIBLE." While some plumbing observation may be code related, this inspection does not determine if the system complies with code Main water supply shut o valve and any other valves such as angle stop valves by toilets and under sinks are not turned on or o by inspector or tested although we will mention if we observe corrosion or potential leak issues with these valves Plumbing supply and waste lines are inspected only where they are accessible and visible while operating accessible xtures and drains Performance of the water ow can vary during dierent times of the day and performance of the drain during actual usage is undetermined

Be Advised: It is recommended to have any underground drain/sewer lines examined by sewer camera inspection (Additional Inspection Service) to visually inspect the condition of the pipes and identify any blockages, root intrusions or breaks A sewer main line inspection is not included in the scope of this general home inspection and is specically excluded unless you ordered this additional inspection. Determining if a building is connected to city sewer or a septic tank is specically excluded from this general home inspection and will not be commented on

Limitations:Evaluation of plumbing is limited to what is able to be viewed. Although we identify certain types of plumbing material, we are not able to see all enclosed plumbing supply pipes

The following plumbing components are specically excluded from this general inspection: inaccessible supply or waste lines such as vertical runs in walls, underground pipes in a slab foundation or a inaccessible crawl space, the interior of pipes for mineral or corrosive clogging, water hammering, solar equipment or water temperature, and the condition of shower pans or if a shower will leak when used No water testing of any type is performed The gas system is not tested for leaks and any underground or hidden gas lines are specically excluded from this report. Gas Seismic valves are not evaluated for correct size or connection, or function Determining the operation of sewer ejection systems is excluded from this inspection and it should be examined by a qualied licensed specialist.

All Terms and Limitations: HVAC System Inspection Terms and Limitations

Heating and Cooling System: HVAC SYSTEM Is a "LIMITED VISUAL AND NON-INVASIVE INSPECTION of the SYSTEMS of the structure that are REASONABLY ACCESSIBLE " (HVAC) is short for Heating Ventilation And Air Conditioning Observations may be code related, this inspection does not determine if the system complies with code Weather permitting the systems is operated with normal controls (Thermostat). In order not to damage the system, the air conditioners are not activated if the out door temperatures below 65 degrees the day before inspection Gas furnaces are not checked for carbon monoxide leakage or re risks. There are carbon monoxide and re detection devices, which can be purchased and installed, which we strongly recommend Air ducts and registers are randomly checked for airow, Heat exchangers are specically excluded from the inspection as they are visually obstructed by design of the system and a complete inspection requires special tools and disassembly, which is beyond the scope of this inspection The following items are outside the scope of the inspection; balance of the air ow, capacity or velocity of the air ow, humidiers, air duct cleanliness, the ability of the system to heat or cool evenly, the presence of toxic or hazardous material or asbestos, system refrigerant levels, cooling or heating capacity to determine if its sucient size for the building Window AC units are not built in and are not inspected or commented

Informational: The average ecient life of a residential heating and cooling system that has been properly maintained is 15 years After 15 years the unit will still operate, but it's operating eciency slowly dwindles When the system is between 15-20 years of age the system can lose up to 40% of its eciency.

NOTE: The air conditioning side of system typical serviceable life expectancy is 15-20 years, the heating side of system typical serviceable life expectancy is 20-30 yrs These conditions may vary from home to home because of deferred maintenance of systems which is common in most homes HVAC systems require annual service by a qualied licensed HVAC professional.

Be Advised: (Example) If your property was inspected in the summer months and the AC was working at the time of inspection however the furnace had deciencies and you were recommended to have HVAC system further evaluated (Or Vice-Versa) I recommend you have the entire system further evaluated immediately by a qualied licensed professional before the end of your inspection contingency period and the close of escrow

661 Loran Way Scott Woodburn FOCUS Inspection Authority Page 11 of 139

All Terms and Limitations: Garage Inspection Terms and Limitations

General inspection was made of the garage and existing components including electrical, plumbing, lights, walls, ceiling, doors according to SOP. Components were all serviceable at time of inspection unless otherwise noted below.

Garage Information: Inspection of the garage typically includes examination of the following:

General structure; oor, wall and ceiling surfaces; operation of all accessible conventional doors and door hardware; overhead door condition and operation including manual and automatic safety component operation and switch placement; proper electrical condition including Ground Fault Circuit Interrupter (GFCI) protection; interior and exterior lighting; stairs and stairways; proper rewall separation from living space; and proper oor drainage

LIMITATIONS:

Garage Fire Wall Ratings: The inspector does not determine the adequacy of rewall ratings. Requirements for ventilation in garages vary between municipalities

All Terms and Limitations: Kitchen Inspection Terms and Limitations

Kitchen Comments & Limitations: The KITCHEN SYSTEM is a "LIMITED VISUAL AND NON-INVASIVE INSPECTION of the SYSTEMS of the structure that are REASONABLY ACCESSIBLE " The Built-In kitchen appliances are visually inspected and operated by using their normal user controls that one would use to turn on to determine if the appliance is functional Appliance components such as timers, clocks, thermostats, self-cleaning functions, cooking functions are not tested specically and oven temperature is not tested for accuracy, Refrigerators or there related components are not inspected such as ice makers or the waterline to the refrigerator, Insta-hot systems or any type of water puriers are not inspected and are specically excluded. Non built in appliances such as counter top microwaves or portable dishwashers are outside the scope of the home inspection and are specically excluded Built-in kitchen cabinets, countertops and ooring are also visually inspected. Cosmetic and aesthetic conditions shall NOT be considered or commented on

Informational: Most kitchen appliances have a life expectancy range of 8-15 years under normal living conditions and depending on how well the home is maintained If the inspector comments that a specic appliance is an older model you can expect to repair or replace it in near future as it has likely reached the end of its life expectancy. As appliances get older they become less ecient and may not perform as intended

Searching for recalls on appliances or other products is outside the scope of this home inspection. If you would like information about recalls you can visit the Consumer Product Safety Commission

The Following are specically excluded from this home inspection report: Appliance components such as timers, clocks, thermostats, self-cleaning functions, cooking functions are not tested specically and oven temperature is not tested for accuracy, Refrigerators or there related components are not inspected such as ice makers or the waterline to the refrigerator or temperature accuracy, Insta-hot systems or any type of water puriers are not inspected and are specically excluded. Non built in appliances such as counter top microwaves or portable dishwashers are also excluded

The sink waste disposal inspection is minimal, the disposal is tested using normal operating controls only The home Inspector cannot predict the remaining life of the garbage disposal or determine how well the garbage disposal will perform If the inspector has noted the disposal is leaking/cracked or inoperative the disposal will require replacing

661 Loran Way Scott Woodburn FOCUS Inspection Authority Page 12 of 139

All Terms and Limitations: Laundry Room Inspection Terms and Limitations

The laundry area is inspected for presence of proper venting of dryer, presence of proper wiring of electrical connections, gas lines and ttings, and presence of proper drainage to laundry tub or wall drain. All of the above are serviceable unless otherwise noted on report.

Laundry Area/Closet/Room and Facilities: Operation of clothes washer and dryer are excluded from this general home inspection Inspector does NOT inspect the following, including but not limited to, the dryer or washing machine, the plumbing lines or any of their connections, including connections to the laundry faucets, the operation of any valves, determining the exact ow rate, if any, the volume, pressure, temperature or adequacy of the water supply in the laundry room. We recommend that you test your own water supply in the laundry room, both hot and cold, prior to nal close of escrow, since this component is excluded from our inspections

NOTE: Recommend that the lint vent be cleaned annually to avoid buildup of lint and potential re hazard.

General Info: We recommend to replace your old rubber washing lines. Replacement of washer hoses is probably one of our leading recommendations to reduce the potential for loss We recommend the stainless steel braided lines As rubber ages, it loses its exibility After being subjected to water hammer over and over for many years, the rubber washing machine hose is eventually going to fail, with potential for heavy water damage Here are a few suggestions to lower the risk of your washing machine hoses suddenly bursting

1 Turn o the water supply when not in use Washing machine manufacturers actually tell you to do this in their installation instructions.

2 Replace your old rubber hoses regularly At least very ve years

3 Install an emergency shuto kit You can purchase an emergency shuto kit, such as the type sold by Floodstop, which will almost surely prevent any type of catastrophic leak These devices come with a water sensor, so if a leak is detected, an alarm goes o and the water supply valves automatically close These kits are battery powered, and according to the web site, can be installed in about 10 minutes

4 Install stainless steel braided hoses This is the simple advice that we usually give during home inspections Stainless steel braided hoses are much more resistant to bursting, and they're fairly inexpensive. You can buy a pair on Amazon for under $17 Link below

Amazon Link Braided Hose

Best Laundry Hoses

All Terms and Limitations: Bathroom Terms and Limitations

Informational: The BATHROOM SYSTEM is a "LIMITED VISUAL AND NON-INVASIVE INSPECTION of the SYSTEMS of the structure that are REASONABLY ACCESSIBLE." Bathrooms are inspected in a cursory fashion, however each accessible xture is operated to test its function and visually inspected to determine its current condition Determining whether shower pans, tub/shower surrounds are watertight or have any hidden rot or other damage is beyond the scope of this inspection and is specically excluded It is very important to maintain all grouting and caulking in the bath areas. Minor grout or caulking imperfections can allow water to get into the wall or oor areas and cause damage. Proper ongoing maintenance is always required whenever there is contact of water with various materials Determining if toilets or shower heads are in compliance with current water conservation laws is outside the scope of this home inspection

All Terms and Limitations: Water Heater Inspection and Limitations

Water heater information and limitations: The Water heater(s) was visually inspected in order to ensure proper installation and that no leaks, rust, or corrosion were present. The temperature of the water was also checked to ensure the water heater was functioning properly The recommended temperature for a water heater is at least 120 degrees F to kill microbes and no higher than 130 degrees F to prevent scalding. Any defects are noted below.

Evaluation of and determining the adequacy or completeness of the following items are not included in this inspection: water recirculation pumps; solar water heating systems; Energy Smart or energy saver controls; catch pan drains Any comments made regarding these items are as a courtesy only Note that the inspector does not provide an estimate of remaining life on water heaters, does not determine if water heaters are appropriately sized, or perform any evaluations that require a pilot light to be lit or a shut-o valve to be operated

661 Loran Way Scott Woodburn FOCUS Inspection Authority Page 13 of 139

All Terms and Limitations: Smoke Detector/Carbon Monoxide Detector Inspection Terms

Smoke detectors were tested and found in working condition at time of inspection unless otherwise noted below

Beginning July 1, 2014, California Senate Bill 745 requires that all solely battery-operated smoke alarms and combination smoke and carbon monoxide alarms installed in California must contain a non-replaceable, non-removable (Lithium) battery that is capable of powering the smoke alarm for a minimum of 10 years. The requirement does not apply to any alarms that are hard-wired

NOTE: The NFPA states - Smoke detectors/alarms should be located inside each bedroom, outside each sleeping area and on every level of the home, including the basement On levels without bedrooms, install alarms in the living room (or den or family room) or near the stairway to the upper level, or in both locations.

Carbon monoxide detectors/Alarm were tested and found in working condition at time of inspection unless otherwise noted below.

NOTE: At a minimum, industry experts recommend a CO alarm be installed on each level of the home -- ideally on any level with fuel burning appliances and outside of sleeping areas Additional CO alarms are recommended 5-20 feet from sources of CO such as a furnace, water heater or replace. Alarms can alert you to a problems only after smoke or carbon monoxide reach their sensors

Where to place them: Because carbon monoxide is slightly lighter than air and also because it may be found with warm, rising air, detectors should be placed on a wall at least 5 feet above the oor The detector may also be placed on the ceiling. Do not place the detector right next to or over a replace or ame-producing appliance. Choose locations free of obstructions, where the alarm will stay clean and protected from adverse environmental conditions Do not place the unit in dead air spaces or next to a window or door.

All Terms and Limitations: Stairway Inspection Terms and Limitations

Interior stairway inspected. Stairway checked for proper rise, tread, hand railing, and baluster separation. We found this component to be serviceable at time of inspection unless otherwise noted in report

InterNACHI is so certain of the integrity of our members that we back them up with our $25,000 Honor Guarantee.

InterNACHI will pay up to $25,000 USD for the cost of replacement of personal property lost during an inspection and stolen by an InterNACHI-certied member who was convicted of or pleaded guilty to any criminal charge resulting from the member's taking of the client's personal property

For details, please visit www nachi org/honor

All Terms and Limitations

661 Loran Way Scott Woodburn FOCUS Inspection Authority Page 14 of 139
Info Image
InterNachi Guarantee: InterNachi $25,000 Honor Guarantee
Limitations
GENERAL LIMITATION: HAZARDOUS MATERIALS AND INDOOR AIR QUALITY

Hazardous Materials Limitations: Informational Limitations: Hazardous building materials are OUTSIDE the scope of a home inspection. This includes building materials that are now suspected of posing a risk to health such as phenol-formaldehyde and urea-formaldehyde based insulation, berglass insulation and vermiculite insulation The Inspector does not identify asbestos roong, siding, wall, ceiling or oor nishes, insulation or reproong. We do not look for lead or other toxic metals in such things as pipes, paint or window coverings. The Inspection does not deal with environmental hazards such as the past use of insecticides, fungicides, herbicides or pesticides. The Home Inspector does not look for, or comment on, the past use of chemical termite treatments in or around the property.

Indoor Air Quality: Informational Limitations: WE DO NOT COMMENT ON THE QUALITY OF AIR IN A BUILDING. The Inspector does not try to determine if there are irritants, pollutants, contaminants, or toxic materials in or around the building The Inspection does not include spores, fungus, mold or mildew that may be present Be Advised: that whenever there is water damage noted in the report, there is a possibility that mold or mildew may be present, unseen behind a wall, oor, cabinet or ceiling. If anyone in your family suers from allergies or heightened sensitivity to quality of air, we strongly recommend that you consult a qualied Environmental Consultant professional who can test for toxic materials, mold and allergens at an additional cost before the end of your inspection contingency period and the close of escrow.

All Terms and Limitations GENERAL LIMITATIONS

661 Loran Way Scott Woodburn FOCUS Inspection Authority Page 15 of 139

General Limitations

Inspector is not required to:

(A) inspect:

(i) items other than those listed within these standards of practice;

(ii) elevators;

(iii) detached buildings, decks, docks, fences, or waterfront structures or equipment; (iv) anything buried, hidden, latent, or concealed; (v) sub-surface drainage systems;

(vi) automated or programmable control systems, automatic shut-o, photoelectric sensors, timers, clocks, metering devices, signal lights, lightning arrestor system, remote controls, security or data distribution systems, solar panels, outdoor kitchens, gas grills (built-in or free standing), refrigerators (built-in or free standing), wine coolers, ice makers or smart home automation components; or

(vii) concrete atwork such as; driveways, sidewalks, walkways, paving stones or patios;

(B) report:

(i) past repairs that appear to be eective and workmanlike except as specically required by these standards;

(ii) cosmetic or aesthetic conditions; or

(iii) wear and tear from ordinary use;

(C) determine:

(i) insurability, warrantability, suitability, adequacy, compatibility, capacity, reliability, marketability, operating costs, recalls, counterfeit products, product lawsuits, life expectancy, age, energy eciency, vapor barriers, thermostatic performance, compliance with any code, listing, testing or protocol authority, utility sources, or manufacturer or regulatory requirements except as specically required by these standards;

(ii) the presence or absence of pests, termites, or other wood-destroying insects or organisms;

(iii) the presence, absence, or risk of asbestos, lead-based paint, MOLD, mildew, corrosive or contaminated drywall Chinese Drywall or any other environmental hazard, environmental pathogen, carcinogen, toxin, mycotoxin, pollutant, fungal presence or activity, or poison;

(iv) types of wood or preservative treatment and fastener compatibility; or (v) the cause or source of a conditions;

(D) anticipate future events or conditions, including but not limited to:

(i) decay, deterioration, or damage that may occur after the inspection;

(ii) deciencies from abuse, misuse or lack of use;

(iii) changes in performance of any component or system due to changes in use or occupancy; (iv) the consequences of the inspection or its eects on current or future buyers and sellers; (v) common household accidents, personal injury, or death;

(vi) the presence of water penetrations; or

(vii) future performance of any item;

(E) operate shut-o, safety, stop, pressure or pressure-regulating valves or items requiring the use of codes, keys, combinations, or similar devices;

(F) designate conditions as safe;

(G) recommend or provide engineering, architectural, appraisal, mitigation, physical surveying, realty, or other specialist services;

(H) review historical records, installation instructions, repair plans, cost estimates, disclosure documents, or other reports;

(I) verify sizing, eciency, or adequacy of the ground surface drainage system;

(J) verify sizing, eciency, or adequacy of the gutter and downspout system;

(K) operate recirculation or sump pumps;

(L) remedy conditions preventing inspection of any item;

(M) apply open ame or light a pilot to operate any appliance;

(N) turn on decommissioned equipment, systems or utility services; or

(O) provide repair cost estimates, recommendations, or re-inspection services

661 Loran Way Scott Woodburn FOCUS Inspection Authority Page 16 of 139

THE CLIENT, BY ACCEPTING THIS PROPERTY INSPECTION REPORT OR RELYING UPON IT IN ANY WAY, EXPRESSLY AGREES TO THE SCOPE OF INSPECTION, GENERAL LIMITATIONS AND INSPECTION AGREEMENT INCLUDED IN THIS INSPECTION REPORT.

This inspection report is made for the sole purpose of assisting the purchaser to determine his and/or her own opinion of feasibility of purchasing the inspected property and does not warrant or guarantee all defects to be found If you have any questions or are unclear regarding our ndings, please call our oce prior to the expiration of any time limitations such as option periods

949-945-0111

This report contains technical information If you were not present during this inspection, please call the oce to arrange for a consultation with your inspector If you choose not to consult with the inspector, this inspection company cannot be held liable for your understanding or misunderstanding of the reports content.

The contents of this report are for the sole use of the client named above and no other person or party may rely on this report for any reason or purpose whatsoever without the prior written consent of the inspector who authored the report. Any person or party who chooses to rely on this report for any reason or purpose whatsoever without the express written consent of the inspector does so at their own risk and by doing so without the prior written consent of the inspector waives any claim of error or deciency in this report.

This report is not intended to be used for determining insurability or warrantability of the structure and may not conform to the guidelines for property insurability. This report is not to be used by or for any property and/or home warranty company.

The digital pictures within this report are a representative sample of inaccessible areas, deciencies or damages in place and should not be considered to show all of the inaccessible areas, deciencies or damages observed There will be inaccessible areas, deciencies or damages not represented with digital imaging.

All Terms and Limitations

LAWN IRRIGATION SYSTEMS EXCLUDED FROM GENERAL HOME INSPECTION

Exterior Grounds Note: Lawn irrigation systems and components are outside the scope of this general home inspection and are not tested or operated and are specically excluded from this inspection. If you have questions or concerns regarding the operation of this system it is recommended to contact a qualied licensed contractor for further evaluation.

All Terms and Limitations OCCUPIED/FURNISHED HOME

661 Loran Way Scott Woodburn FOCUS Inspection Authority Page 17 of 139
LIMITATIONS

Informational Limitations: If your home is occupied or furnished during the time of inspection, it can limit the inspectors visual inspection in regards to oors, walls, windows or doors due to storage and furnishings as well as closet's and cupboards Floors and walls may have damage that is concealed to inspector because home is occupied Exterior walls can have the same visible limitations caused by storage commonly found at a occupied home. The garage is commonly lled with excessive storage so walls and oors are typically covered and can not be seen by inspector. You may nd issues with walls, oors or cabinets when the home is emptied. Recommend contacting a professional right away to further evaluate any material defects found.

When an ITEM is NOT ACCESSIBLE = This item was NOT accessible and therefore NOT inspected The inspector makes no representations of whether or not such an item was functioning as intended or not. The INSPECTOR is not responsible for items that can not be examined. An example of why something would not be accessible would be blockage by furniture or personal items, locked or concealment. If critical to the home purchase decision, we recommend subsequent follow-up by a licensed and qualied tradesperson or a re-inspection by the Home Inspector (Re-Inspection fee applies) prior to closing when the property is vacant and more visible

If a Component is OBSTRUCTED FROM VIEW: = This item was obstructed from view and therefore NOT inspected. The inspector makes no representations of whether or not such an item was present or present and functioning as intended or not The INSPECTOR is not responsible for items that can not be examined because it was obstructed from view

This can occur more so in an occupied home then one that is vacant. Many times, moving boxes, displaced personal items and general disorder that accompanies a move can conceal, hide and prevent an INSPECTOR from discovering defects in attics, garages, cabinets and closets. A less obvious example of why something would be obstructed from view would be in the attic due to insulation or other coverings or restricted access due to low head space for safe passage

661 Loran Way Scott Woodburn FOCUS Inspection Authority Page 18 of 139

2.6

2.7

661 Loran Way Scott Woodburn FOCUS Inspection Authority Page 19 of 139
AB General: Roof
Hip Overview Front Left Middle Back Right Right
General Overview Photos 2:
IN NI NP D
General X 2.2 Coverings
X 2 3 Roof Slope and Pitch 2.4 Penetrations/Plumbing Vents
5 Flashings
General: INSP
Type/Style Gable,
General:
ROOF
2.1
X
2
X
Roof Drainage Systems
Chimneys
8 Skylights
Solar Panels IN = Inspected NI = Not Inspected NP = Not Present D = Deciencies Information section-NDM4YWZlNjctYzU4NS00MDAwLWJkZTYtOTEwZWNiYjcyMzUy
2
2.9

General: Inspection Method

Drone

Roong System Comments: The ROOFING SYSTEM is a "LIMITED VISUAL AND NON-INVASIVE INSPECTION of the SYSTEMS of the structure that are REASONABLY ACCESSIBLE." It has been inspected at a time when it was not raining. Since one of the purposes of the roof is to repel water this could not be observed and veried as occurring in all cases Therefore the roof has not been tested under wet conditions and how it performs in these conditions is unknown

NOTE: This visual roof inspection is not intended as a warranty or an estimate on the remaining life of the roof; and portions of the roof may not be visible due to solar panel array if present at time of inspection No warranty is made that roof system will not leak when it is under a wet condition.

RECOMMENDED MAINTENANCE: Roong requires periodic maintenance where pipe stacks penetrate roof top and where metal ashings are present between walls and roof as well as where chimneys penetrate roof Over time the sun dries out the sealant and causes it to crack creating open seams which can allow moisture intrusion into structure. In addition, roof tiles can crack, become loose or slide overtime due to wind, debris or maintenance walks Checking the condition of these areas on a annual basis is recommended and especially after high wind storms

Coverings: Material

Concrete, Tile

How old is my Roof ? is the most commonly asked question.

The inspector or roong professional can only guess the age of the roof at best, unfortunately roong materials do not come with data tags indicating the age or date of installation

The most accurate way is to nd out the date of the roong permit if there is one, but not all jurisdictions require building permits for roof replacement and sometimes the homeowner has the roof replaced without a permit Or ask for disclosure from the seller or current owner if they know when the roof was installed.

Coverings: Ceramic/Clay/Concrete Roof Tiles

Information Only: Ceramic/Concrete roof tiles are a perfect option for low slope and pitched roofs. Highly durable, roof tiles have the lowest life cycle cost and they stand the test of time more than any other roong material

Excellent re resistance properties make clay/concrete roof tiles a very popular choice In general, a cared for and well maintained tile roof can last 50 years, although there are buildings in Europe whose tile roofs have lasted for centuries Tile roofs exceed all other types of roong materials for longevity

Roof Slope and Pitch: Roof Slope and Pitch

INFORMATIONAL: Please note that, according to the International Standards of Practice for Performing a General Home Inspection, the inspector is not required to measure the slope of the roof. Therefore, the information provided in this section is courtesy only.

Both pitch and slope indicate the incline of a roof, expressed as a proportion of the vertical to the horizontal. Picture provided

The slope of a roof aects how roof systems are installed, including dictating which type of roof-covering material can be applied, Therefore, understanding the slope of a roof may be valuable information for the home owner or perspective buyer.

Penetrations/Plumbing Vents: General Photos

661 Loran Way Scott Woodburn FOCUS Inspection Authority Page 20 of 139

Penetrations/Plumbing Vents: Roof Penetrations/Plumbing Vent Pipes

Roof Penetrations, such as Furnace, Plumbing Vents and Stove Vents, were inspected by drone close up and appeared to be serviceable at time of inspection unless otherwise noted below.

Plumbing Vent Pipes: The plumbing vent, also known as a vent stack, helps regulate the air pressure in your plumbing system. Just as drain pipes remove water and waste from your home, the plumbing vent pipe also known as a plumbing air vent removes gas and odors It also allows fresh air into the plumbing system to help water ow smoothly through the drain pipes. However, no water runs through the plumbing vent pipe. It is a vertical pipe attached to a drain line and runs through the roof of your home The vent stack is the pipe leading to the main roof vent. It channels the exhaust gases to the vent and helps maintain proper atmospheric pressure in the waste system. Vent pipes were inspected and found in serviceable condition at time of inspection unless otherwise noted below

Flashings: Material

Aluminum

Roof Flashing Information & Limitations : LMT - Visible portions of the ashings were inspected looking for signicant deciencies (drip edge, sidewall, headwall, counter, step, etc - as applicable). Typically most areas of ashings are not visible as they are covered by the roof covering material and/or the wall cladding (as applicable), and these areas are excluded from this inspection. Therefore functionality has to be determined by looking for moisture intrusion on ceilings where the ashing was presumed to be in place, or on the roof decking from within the attic (as accessible) No reportable conditions were observed at visible portions, at the time of inspection, unless otherwise noted in this report.

Roof Drainage Systems: General Photos

Roof Drainage Systems: Roof Drainage Inspection Terms and Limitations

Roof drainage system was inspected from the roof or with use of drone. Inspector looks for proper drainage, debris, and/or damage This component was found serviceable at the time of inspection, unless otherwise noted below

661 Loran Way Scott Woodburn FOCUS Inspection Authority Page 21 of 139

Chimneys: General Photos

Chimneys: Chimney Above Roof & Cap/Rain Covering

The Inspector observed the condition of the visible portions of the chimney that extended above the roof at the time of inspection. Inspection of this portion of the chimney includes evaluation of the following: chimney exterior; cap; spark arrestor; visible ue; cricket; and location on the roof

All appeared to be in serviceable condition at time of inspection unless otherwise noted below.

Skylights: Skylight Present

One or more skylights were present in the residence All appeared to be serviceable at time of inspection unless otherwise noted.

Solar Panels: Solar Panels Present

Inspection and operation of solar panels is outside of the scope of practice for our home inspector. These panels are usually inspected and/or replaced, and at times maintained by a solar panel company upon request as it is a specialty install and the panels carry their own warranty separate from other roof coverings. Observations on this item may be provided by the inspector if an irregularity in the panels are noticed Maintenance of Solar Panels - The dustier your area, the more frequent inspection is recommended This ensures that dirt, grime, bird droppings and debris do not block the sun from ecient absorption by the panels

Limitations

General

GENERAL ROOF LIMITATIONS

661 Loran Way Scott Woodburn FOCUS Inspection Authority Page 22 of 139

Roof limitations: The following items or areas are not included in this inspection: areas that could not be traversed or viewed clearly due to lack of access; solar roong components. Any comments made regarding these items are made as a courtesy only Note that the inspector does not provide an estimate of remaining life on the roof surface material, nor guarantee that leaks have not occurred in the roof surface, skylights or roof penetrations in the past. Regarding roof leaks, only active leaks, visible evidence of possible sources of leaks, and evidence of past leaks observed during the inspection are reported on as part of this inspection. The inspector does not guarantee or warrant that leaks will not occur in the future. Complete access to all roof and attic spaces during all seasons and during prolonged periods of all types of weather conditions (e g high wind and rain, melting snow) would be needed to do so Occupants should monitor the condition of roong materials in the future For older roofs, recommend that a professional inspect the roof surface, ashings, appurtenances, etc. annually and maintain/repair as might be required. If needed, the roofer should enter attic space(s). Regarding the roof drainage system, unless the inspection was conducted during and after prolonged periods of heavy rain, the inspector was unable to determine if gutters, downspouts and extensions perform adequately or are leak-free.

This is a visual-only inspection of the roof-covering materials It does not include an inspection of the entire system. There are components of the roof that are not visible or accessible at all, including the underlayment, decking, fastening, ashing, age, shingle quality, manufacturer installation recommendations, etc.

Deciencies

2 2 1 Coverings

TREE TOO CLOSE

Tree and or tree branches were overhanging the roof or in contact with the roof which may cause accelerated wear and aging of roong material and provide potential entry for vermin Recommend correction, removal or trimming of tree and or tree branches away from roof and roong material as regular maintenance

2.2.2 Coverings

TILES CRACKED/SLIPPED/MISSING

RIGHT LOWER FIELD

Roof had cracked/broken, missing and/or slipped tiles. Recommend a qualied roof contractor repair or replace to prevent moisture intrusion.

2 2 3

Coverings

DEBRIS ON ROOF

Accumulation of debris on roof was noticed in one or more areas Debris can contribute to moisture accumulation and potential roof leaks as well as obstructing rain gutters for proper ow and drainage. We recommend that debris be cleared o roong material on a regular maintenance basis.

661 Loran Way Scott Woodburn FOCUS Inspection Authority Page 23 of 139
Maintenance Item
Recommendation
Back Maintenance Item

2.2.4 Coverings DISCOLORATION THROUGHOUT

Roof covering was discolored in one or more areas, which can be caused by moisture, moss build-up, rust or soot or a previous repair material used on the roof tiles. Recommend a qualied roong contractor evaluate and remedy with a roof cleaning agent if indicated.

Here is a helpful article on common roof stains

2 4 1 Penetrations/Plumbing Vents ROOF VENT PIPE MASTIC CRACKING/DETERIORATING

THROUGHOUT

Observed one or more roof vent collars/pipes with cracks along mastic that attaches the pipe to the ashing boot. Recommend to be resealed as maintenance to prevent any water intrusion. Recommendation

2 6 1 Roof Drainage Systems GUTTERS/DOWNSPOUTS

DEBRIS

THROUGHOUT

Debris has accumulated in the gutters and/or at downspouts Recommend cleaning and re-sloping of gutters to facilitate water ow and proper drainage. There is potential for damage to the structure if gutters are not cleared and maintained each year.

Here is a DIY resource for cleaning your gutters

661 Loran Way Scott Woodburn FOCUS Inspection Authority Page 24 of 139
Maintenance Item
Maintenance Item

2.7.1 Chimneys

CHIMNEY CAULKING NEEDED

Observed Chimney ashing needing mastic and/or caulking for proper seal.

Recommendation

Contact a qualied professional. Recommendation

661 Loran Way Scott Woodburn FOCUS Inspection Authority Page 25 of 139

General: INSP

3: ATTIC, INSULATION & VENTILATION

Fixtures, Switches & Receptacles

Ventilation: Ventilation Type Low Prole Roof Vents

Attic & Insulation: Insulation

Blown Attic & Insulation: R-value

R-Value provided is estimate only

Ventilation: Attic Dryer Vent Duct Material

Dryer Vent Duct Not In Attic

Concealed ducting must be metal (galvanized or aluminum) duct

Exhaust Systems: Exhaust Fans Fan Only

661 Loran Way Scott Woodburn FOCUS Inspection Authority Page 26 of 139
AB
Type
32
IN NI NP D
IN = Inspected NI = Not Inspected NP = Not Present D = Deciencies
3.1 General X 3.2 Attic & Insulation X 3 3 Ventilation X 3.4 Exhaust Systems X 3 5 Lighting
Information section-ZWE1MmY2NzEtNjI0MC00ODNlLTk4NTMtY2EwMWY0ZGZlMjVl

Attic & Insulation: General Attic Structure

Rafters/Stick

Trusses: Prefabricated wooden structure that integrates a triangular webbing of structural members to provide support for the roof above while tying the outside walls of the house together. 2x4s are most commonly used in trusses

Rafters: A traditional means of framing roofs, known as stick framing Each rafter is built on the job site using dimensional lumber Every piece is measured, cut, and fastened together to form the rafter Rafters commonly use 2x8s, 2x10s and 2x12s

661 Loran Way Scott Woodburn FOCUS Inspection Authority Page 27 of 139 General:
General Overview Photos
Rafters Vs Trusses

4: EXTERIOR

661 Loran Way Scott Woodburn FOCUS Inspection Authority Page 28 of 139 General: INSP GE Siding, Flashing & Trim: Siding Style Panels, Trowel Finish, Smooth Trowel Driveways & Walkways: Driveways and Walkways Material Brick, Concrete
Patios, Balconies, Porches & Steps: General Photos
Patios, Balconies, Porches & Steps: Material Concrete, Wood, Stucco
Decks,
Decks,
IN NI NP D 4.1 General X 4.2 Siding, Flashing & Trim X X 4 3 Exterior Water/Gas Plumbing X X 4.4 Eaves, Sots & Fascia X X 4 5 Exterior Doors and Windows X X 4.6 Gutters and Downspouts X 4.7 Driveways & Walkways X X 4 8 Decks, Patios, Balconies, Porches & Steps X X 4.9 Fence/Gate/Walls X X 4 10 Vegetation, Grading, & Drainage X X 4.11 Exterior Lighting Fixtures, Switches & Receptacles X X 4.12 Exterior GFCI & AFCI X 4 13 Chimneys X 4.14 BBQ/Fire Pit X 4 15 Pool/Spa/Jacuzzi X IN = Inspected NI = Not Inspected NP = Not Present D = Deciencies Information section-OWUxOTA1NTUtODFjMy00YWUyLWExNTMtYzk5NTAxZDI0N2Q5

General: Exterior Terms

Exterior information: The exterior of a home requires constant general maintenance and cleaning An inspection is visual and non-evasive only and therefore not every square inch can been seen or inspected. It is up to the home owner to keep up on regular maintenance Some maintenance items include but are not limited to caulking/sealing of siding, trim, windows, and doors, keeping gutters cleaned, washing the home, proper draining of downspouts etc.. When it comes to caulking/sealing, this is something that should be monitored and repaired or replaced as necessary There are many areas of the home that require caulk/sealant Caulk/sealant will dry out overtime due to constant temperature changes in the weather. If not properly maintained these are areas that can let water into the home and begin to deteriorate the structure While there could be areas listed in your report that need caulked or sealed, be advised that it might not be every area of the home that needs it. Some maintenance items can be done DIY and others might need to be done by qualied contractors

The exterior of your home is slowly deteriorating and aging The sun, wind, rain and temperatures are constantly aecting it. Your job is to monitor the buildings exterior for its condition and weathertightness.

Check the condition of all exterior materials and look for developing patterns of damage or deterioration

During a heavy rainstorm (without lightning), grab an umbrella and go outside Walk around your house and look around at the roof and property A rainstorm is the perfect time to see how the roof, downspouts and grading are performing. Observe the drainage patterns of your entire property, as well as the property of your neighbor. The ground around your house should slope away from all sides Downspouts, surface gutters and drains should be directing water away from the foundation.

Siding, Flashing & Trim: Siding Material

Stucco, Wood Trim, Wood, Brick

The wall siding and/or wall cladding were inspected looking for signicant damage, presence of proper ashings, and potential water entry points, etc. No reportable deciencies were visibly present at the time of inspection unless otherwise noted in this report.

Siding, Flashing & Trim: Wood Siding and/or Trim Information

Wood Siding and Trim Information : FYI - Wood siding or wood trim was present on this home, and wood components require diligent maintenance including caulking and sealing/painting as a part of routine maintenance to prevent water related damage. No deciencies were found unless otherwise noted below.

Siding, Flashing & Trim: Stucco Siding Information

Your home has a Stucco Exterior Cladding: Stucco or Portland Cement Plaster, is a low-cost, strong, and durable nish. It can be used in a wide variety of climates. It is versatile and can be applied to concrete, concrete masonry, brick, wood frame, or steel frame It is re resistant and color retentive The stucco plaster is usually applied as a twoor three-part coating directly onto masonry, or over wood or metal lath to a wood frame structure. It does require maintenance watch, especially with contraction and expansion of new home applications We inspected for excessive cracking or chipping of the stucco between 1/16-1/8" width as well as any sign of spalling of the cladding. We found that the stucco was in serviceable condition unless otherwise noted below.

661 Loran Way Scott Woodburn FOCUS Inspection Authority Page 29 of 139

Eaves, Sots & Fascia: Eaves, Sots and Fascia

Visual

Sot / Fascia Information: The sot and fascia was inspected at visible portions looking for any water damage or other signicant defects. No reportable conditions were visibly present at the time of inspection unless otherwise noted in this report.

Limitation NOTE: There are limitations to our inspection of all of the eaves, sot, and facia. It's impossible to inspect those areas closely during a home inspection due to the height and locations A home inspection is not an exhaustive evaluation. Our inspection of the exterior was limited as the inspector was not able to reach and access closely every part of the eaves, sot, and fascia However, all areas that were observed were in serviceable condition at time of inspection, Except if otherwise noted below.

Exterior Doors and Windows: Exterior Doors and Windows

Wood, Vinyl Slidding Door

Exterior Doors: All exterior doors were inspected by looking for damage, lack of proper ashing, deciencies with their operation, etc No reportable deciencies were present at the time of inspection unless otherwise noted in this report.

Exterior

Doors and Windows: Door & Window Exteriors

Exterior Doors & Windows Information: The exterior components of the windows (trim, ashing, weep holes, etc ) and doors were inspected looking for damage, lack of proper ashing, clearance from grade, etc. No reportable deciencies were visibly present at the time of inspection unless otherwise noted in this report.

Gutters and Downspouts: Gutter Material

Aluminum, Metal, French

Information About Roof Drainage:

Their are many reasons why gutters and downspouts are necessary for proper roof drainage If the soil around the foundation is soaked from roof drainage water, we can assume that at least some of that moisture will nd its way into the basement, crawl space or the concrete oor Some of this moisture will then be absorbed by the air in the home If this occurs in the winter time, we can assume that the warmed air in the home will absorb a great deal of moisture (warm air can absorb more moisture than cold air). If this moisture saturated air nds itself into some spaces with cold surfaces - and it will, then some of this moisture will condense against these cold surfaces This can happen at windows, attic plywood and inside exterior walls, etc.

A good gutter & downspout system helps to control the amount of water and moisture that gets into a structure. And that, in combination with various types of venting system, can prevent the damage from trapped moisture It is also important to keep the gutters and down spouts clear from debris which may not allow roof water from reaching drainage on the ground Buildings surrounded by large trees that may overhanging/touching the buildings roof should be trimmed back as this can lead to poor roof drainage

661 Loran Way Scott Woodburn FOCUS Inspection Authority Page 30 of 139

Gutters and Downspouts: Gutters & Downspouts Inspected

Gutters Information: The gutters were inspected looking for proper securement, debris in the channel, standing water, damage, etc. Leaking gutters can not be diagnosed if an active rain was not occurring at the time of inspection, and if leaks are noticed after taking ownership of the property, sealing or repairs may be needed at seams or endcaps No deciencies were visibly present at the time of inspection unless otherwise noted in this report.

Downspouts Information: The downspouts were inspected to ensure they were diverting rainwater away from the structure. Testing for blockages in downspouts or drainpipes is beyond the scope of a home inspection, as is locating their termination point No deciencies were present at visible portions at the time of inspection, unless otherwise noted in this report.

Recommend Maintaining Gutters: It is recommended to periodically clean debris from the guttering channels to prevent downspouts from clogging Clogs in downspouts can allow the gutters to overow; damaging roof sheathing, fascia boards, and saturating grounds at the foundation.

Driveways & Walkways: General Photos

Driveways & Walkways: Concrete Surfaces: Concrete Flatwork Information

Concrete, Flatwork or Hardscape Information: Concrete atwork or hardscape that adjoined the structure was inspected looking for excessive cracking, ensuring it sloped away from the structure, and for any other signicant defects. No reportable conditions were visibly present at the time of inspection if not otherwise noted in this report.

Decks, Patios, Balconies, Porches & Steps: Appurtenance/Accessory

Patio, Pergola covering, BBQ Area

Items noted under this section appeared serviceable with no major visual defects observed at the time of inspection unless otherwise noted

Decks, Patios, Balconies, Porches & Steps: Patio Information

Patio: The patio area was inspected looking for signicant defects No signicant deciencies were present at the time of inspection unless otherwise noted in this report.

661 Loran Way Scott Woodburn FOCUS Inspection Authority Page 31 of 139

Fence/Gate/Walls: General Photos

Fence/Gate/Walls: Fence, Wall and Gates Information

Gates and Fencing and or Walls were inspected and appear to be in serviceable condition, except if noted below.

Vegetation, Grading, & Drainage: General Photos

661 Loran Way Scott Woodburn FOCUS Inspection Authority Page 32 of 139

Vegetation, Grading, & Drainage: Grading, Slope, Lot Drainage

Grading / Lot Drainage: The grading around the home was inspected to determine that it was designed to allow rainwater to adequately drain away from the structure. The soil is recommended to slope away from the home, with a 6 inch drop in elevation, in the rst 10 feet away from the structure (5% grade) When the 5% grade can not be achieved, swales or drains should be used as needed to properly divert rainwater runo. Any at or low areas around the home should be backlled and sloped away from the foundation, to prevent potential moisture inltration into areas below grade No reportable deciencies were observed at the time of inspection unless otherwise noted in this report.

Grading and Slope Illustration

Lot Slope Illustration

Exterior Lighting Fixtures, Switches & Receptacles: Receptacle Information

Fixtures, Switches and Receptacle Information: Switches and xtures were tested for serviceability. A representative number of receptacles throughout the home were tested with a polarity tester to conrm proper wiring. No wiring deciencies were reported by the tester unless otherwise noted in this report.

BBQ/Fire Pit: Gas BBQ/Fire Pit

Your home has built-in gas accessories such as a built in Gas BBQ and/or Gas Fire Pit. While it appeared that these accessories were serviceable at time of inspection, we do not operate GAS BBQs or Fire Pits as this is beyond our Standards of Practice and for insurance purposes. We recommend that the appropriate service provider be contacted prior to use especially if they have not been in use for an extended period of time Your local gas company can also be contacted to provide a safety check of external gas lines, connections and accessories.

Deciencies

661 Loran Way Scott Woodburn FOCUS Inspection Authority Page 33 of 139
SIDING DISCOLORATION OF STUCCO Maintenance Item
4 2 1 Siding, Flashing & Trim

Observe discoloration of stucco in one or more places. This can be due to various reasons including, UV Light discoloration that usually happens over time, previous repairs, lack of rain gutters or landscape sprinkler system If found under patio or eaves, discoloration may be due to previous roof or plumbing leak or drip edge deciencies. Recommend request of disclosure and repair or repaint and/or correction of potential cause of anomaly or moisture discoloration found on cladding by qualied contractor. This is usually considered a cosmetic issue unless further evaluation shows a cause due to material deciency of additional components

4 2 2 Siding, Flashing & Trim SIDING MATERIAL DEFICIENCYMINOR

Siding showed minor cracking (mostly hairline), chipping, aking and/or separation of material in one or more places. This may be a result of original application, normal settling, temperature changes, contraction and expansion of the home, or normal wear. Recommend repairing, correcting, and cracks and/or chips should be repaired when they reach between 1/16 and 1/8 inch in width

4 2 3 Siding, Flashing & Trim SIDING STYROFOAM POP OUT DEFICIENCY

Some damage and/or premature discoloration/color fade/paint blister or inadequate nish coverage was observed in your Styrofoam pop out features in one or more locations around corners, doors and/or windows Damaged or Unnished Styrofoam features can deteriorate faster due to UV and Weather conditions if not maintained or repaired when damaged Recommend maintenance repair in noted locations. Recommendation

4 2 4 Siding, Flashing & Trim EXTERIOR HOUSE/COACH LIGHTS LOOSE/DAMAGED/MISSING/NOT SEALED

Observed one or more exterior house/coach lights that were Loose/Damaged, Missing or not sealed correctly and should be re-secured, and properly sealed at top and side penetration or replaced if needed.

661 Loran Way Scott Woodburn FOCUS Inspection Authority Page 34 of 139
Maintenance Item Maintenance Item

SPALLING

Observed spalling stucco or parge coating in one or more areas of the home This may be due to excessive moisture intrusion at the area noted; possibly due to sprinkler heads directed at the siding Recommend repair of spalling stucco or parge coat as needed for maintenance and redirecting any source of water that has aected this component. Direct sprinklers away from the structure.

Observed siding texture anomaly. Texture variations due to previous repair is a cosmetic issue and not necessarily a structural concern unless other factors determine dierently. We bring this to your attention for information only and recommend that buyer request disclosure of reason for the condition of this component

661 Loran Way Scott Woodburn FOCUS Inspection Authority Page 35 of 139
4 2 5 Siding, Flashing & Trim SIDING STUCCO Back Right Back Right Left Front
Maintenance Item
Right 4 2 6 Siding, Flashing & Trim SIDING TEXTURE ANOMALY
Maintenance Item

4 2 7 Siding, Flashing & Trim SIDING WOOD

ROT/DETERIORATION/WEATHERING

Recommendation

Observed one or more areas of wood rot or deterioration or weathering of wood siding and/or wood trim components inn noted locations Recommend that these areas as seen in the representative pictures be evaluated further for repair, painting or replacement.

4

2

8 Siding, Flashing & Trim OPEN PENETRATIONS

Observed one or more open gaps or penetrations that need to be sealed properly to avoid moisture or pest intrusion Recommend a qualied contractor to seal all exterior penetrations appropriately

Recommendation

Contact a qualied professional

4

4 1

Eaves,

VINE INTRUSION INTO SOFFIT ATTIC VENTS/OPENINGS

Observed Vine Growth into the fascia and sot components which may extend to the interior of the attic from sot vent openings This allows moisture and vermin into the home and poses a high maintenance issue. Recommend removing vines and other vegetation o the cladding to avoid intrusion into the sot vent holes and other components Best to remove all vegetation growth from structure

661 Loran Way Scott Woodburn FOCUS Inspection Authority Page 36 of 139
Right Back Left Back Recommendation Sots & Fascia Maintenance Item 4 4 2 Eaves, Sots & Fascia WASP NEST Maintenance Item

Observed one or more wasp nests. Recommend a qualied exterminator evaluate and remove.

4 5 1 Exterior Doors and Windows DOOR/WINDOW SCREEN DAMAGED

Observe one or more door or window screens with damage noted areas. Recommend repair for proper function

Recommendation

Contact a qualied professional.

4 7 1 Driveways & Walkways CONCRETE SPALLING - MINOR

Observed some minor concrete spalling in noted location. This appears mainly to be cosmetic in nature at this time We recommend monitoring this particular component and repairing as needed

4 7 2 Driveways & Walkways LOOSE / CRACKING/ MISSING BRICK OR STONE

Observed Missing cracking / Damaged Brick/Stone in driveway or walkway. This may be mostly cosmetic, but recommend repair to prevent any further deterioration issues

661 Loran Way Scott Woodburn FOCUS Inspection Authority Page 37 of 139
Maintenance Item
Maintenance Item
Maintenance
Item

4 7 3 Driveways

& Walkways

PATIO TYPICAL SETTLEMENT CRACKS - MINOR

Patio - Typical Settlement Cracks: Typical or Normal settlement / shrinkage cracks were present on the patio concrete slab (under 1/4" wide) These can be caused by the composition of the concrete mix used when the slab was poured, the lack of expansion or relief joints, or standard settlement At a minimum these cracks should be monitored and/or sealed with a masonry sealant to prevent further damage from freezing rain water in winter months. If a concern, have a concrete contractor to evaluate further.

4 7 4 Driveways & Walkways WALKWAY CRACKING - MINOR

Minor cosmetic cracks observed less that 1/4" without vertical lift or oset. Recommend monitor and/or patch/seal.

4 7 5 Driveways & Walkways MORTAR/GROUT/CAULKING

Observed that one or more component Tiles, bricks or stones showed deterioration of mortar, grout or caulking at noted locations. Recommend maintenance repair of this component.

Recommendation

Contact a qualied professional

661 Loran Way Scott Woodburn FOCUS Inspection Authority Page 38 of 139
Item
Maintenance
Maintenance Item
Recommendation

4.7.6 Driveways & Walkways EFFLORESCENCE

Eorescence is a crystalline or powdery deposit of salts often visible on the surface of concrete, brick, stucco, or natural stone surfaces. It occurs when water leaves behind salt deposits on the masonry Surface

Recommendation

Contact a qualied professional Recommendation

4.8.1 Decks, Patios, Balconies, Porches & Steps PAINT DEFICIENCY NOTED

Area of sealer and paint aking or deciency at noted location. This is a maintenance item. Recommend repainting noted areas

4 8 2 Decks, Patios, Balconies, Porches & Steps WOOD WATER SEALANT REQUIRED

Wood is showing signs of weathering and/or water damage

Recommend water sealant/weatherproong be applied.

Here is a helpful article on staining & sealing your deck.

661 Loran Way Scott Woodburn FOCUS Inspection Authority Page 39 of 139
Maintenance Item
Recommendation 4 9 1 Fence/Gate/Walls MINOR SETTLING CRACKS/SEPARATION PRIVACY WALL Maintenance Item

Observed Minor cracking/material separation on Privacy Wall along expansion joints and/or mortar joints. This is normal as settling occurs. Cracks that are outside of or not following expansion joints should have maintenance re-pointing repair provided at these aected areas although this appears to be mostly cosmetic at the time of inspection

4 10 1 Vegetation, Grading, & Drainage NEGATIVE GRADING

Grading is sloping towards the home in one or more areas. This could lead to water intrusion and foundation issues Recommend qualied landscaper or contractor regrade or provide proper drainage so water ows away from home This may require installation of a Swale System, Yard Drains, Drain Boxes, French Drains, scoring of cement components or other adjustments

Here is a helpful article discussing negative grading.

4.10.2 Vegetation, Grading, & Drainage DRAIN COVER BROKEN

Observed one or more drain covers that are broken or missing. Recommend replacement. Easy x.

661 Loran Way Scott Woodburn FOCUS Inspection Authority Page 40 of 139
Recommendation
Maintenance Item

4 10 3 Vegetation, Grading, & Drainage OVERGROWTH OF TREES/VEGETATION AGAINST SIDE OF STRUCTURE

Observed trees/vegetation in need of trimming away from structure Overgrowth against the structure may facilitate entry of moisture or vermin into the structure or deterioration of siding. Recommend the trimming of shrubs and trees away from the structure.

Tree roots may also begin to become an issue as they grow and possibly penetrate into foundation. Recommend correction.

4 11 1 Exterior Lighting Fixtures, Switches & Receptacles COVER PLATES LOOSE/DAMAGED/MISSING

One or more receptacles or light switches have a damaged, loose or missing cover plate. Recommend resecuring, repair or replacement.

661 Loran Way Scott Woodburn FOCUS Inspection Authority Page 41 of 139
Maintenance Item
Safety Hazard

(click here to view on web)

661 Loran Way Scott Woodburn FOCUS Inspection Authority Page 42 of 139
Video

5: FOUNDATION & UNDER FLOOR STRUCTURE

5.1 General X

5.2 Slab Foundation X X

5 3 Crawlspace X

5.4 Basement X

= Inspected

Information

General: INSP

GE

General: Inspection Method

Visual

Limitations section-MmM2NzY1MjAtMDczMy00MzU4LWJiOTUtMmU4YTI3NGJkNGVl

General: Foundation Type/Style Slab on Grade

Slab Foundation: Material Slab on Grade, Concrete

Foundation Floor Structure Comments and Limitations: Foundation SYSTEM and or Floor Framing SYSTEM is a "LIMITED VISUAL AND NON-INVASIVE INSPECTION of the SYSTEMS of the structure that are REASONABLY ACCESSIBLE " The conditions observed at the time of the inspection and are the opinion of the inspector The inspection does not determine the potential of the structure to experience future problems, geological conditions or the potential of the underlying soils to experience movement or water ow or whether the soil is stable If any form of prior structural movement has been disclosed, you should expect future movements and possible repairs. The inspection does not calculate crawl space ventilation capacities, deck and balcony capacity, retaining wall eectiveness, construction material type, quality or capacity. It does not address the existence of prior repairs, the potential of future repairs, failure analysis, documentation of all possible movement or cracks in oor slabs covered by oor furnishings It is typical for concrete oor slabs to have some cracks because of the normal drying process of the concrete plus the stress occurring by settlement and seismic activity

Foundation Information:

Notice: This inspection is one of rst impression and the inspector was not provided with any historical information pertaining to the structural integrity of the inspected real property This is a limited cursory and visual survey of the accessible general conditions and circumstances present at the time of this inspection. Opinions are based on general observations made without the use of specialized tools or procedures unless otherwise noted Therefore, the opinions expressed are one of apparent conditions and not of absolute fact and are only good for the date and time of this inspection

The inspection of the foundation may show it to be providing adequate support for the structure or having movement typical to this region, at the time of the inspection. This does not guarantee the future life or failure of the foundation. The Inspector is not a structural engineer. This inspection is not an engineering report or evaluation and should not be considered one, either expressed or implied. If any cause of concern is noted on this report, or if you want further evaluation, you should consider an evaluation by an engineer of your choice

General GENERAL FOUNDATION AND FLOOR STRUCTURE LIMITATIONS

661 Loran Way Scott Woodburn FOCUS Inspection Authority Page 43 of 139
IN NI NP D
IN
NI
= Not Inspected NP = Not Present D = Deciencies

Foundation SYSTEM and or Floor Framing SYSTEM is a "LIMITED VISUAL AND NON-INVASIVE INSPECTION of the SYSTEMS of the structure that are REASONABLY ACCESSIBLE." The conditions observed at the time of the inspection and are the opinion of the inspector The inspection does not determine the potential of the structure to experience future problems, geological conditions or the potential of the underlying soils to experience movement or water ow or whether the soil is stable. If any form of prior structural movement has been disclosed, you should expect future movements and possible repairs. The inspection does not calculate crawl space ventilation capacities, deck and balcony capacity, retaining wall eectiveness, construction material type, quality or capacity. It does not address the existence of prior repairs, the potential of future repairs, failure analysis, documentation of all possible movement or cracks in oor slabs covered by oor furnishings It is typical for concrete oor slabs to have some cracks because of the normal drying process of the concrete plus the stress occurring by settlement and seismic activity.

Slab Foundation

SLAB ON GRADE LIMITATIONS

Concrete Slab Information and Limitations If Present: Building constructed on top of a concrete slab over earth, with no crawl space underneath Concrete is known to typically develop cracks due to expansion & contraction and or poor compaction of soil below, poor drainage adjacent to structure can also contribute to slab or foundation issues so it is expected some cracking would be found if the concrete were exposed to view by removing interior ooring. By the nature of slab construction the structure would be bolted to this concrete slab per the building standards at the time of construction. Bolting is typically not visible in slab construction as it is inside the wood frame walls that are covered with drywall and siding

A concrete slab is a common structural element of modern buildings. Horizontal slabs of steel reinforced concrete, typically between 4 and 20 inches (100 and 500 millimeters) thick, are most often used to construct oors in residential structures, while thinner slabs are also used for exterior driveways and walkways

NOTE: Full interior slab was not visible at the time of inspection due to tile, carpet or other oor coverings unless otherwise noted below.

NOTE: Conditions of any utilities within or under a slab-on-grade, such as water/gas plumbing or ductwork are not within the scope of a professional home inspection

Crawlspace RAISED FOUNDATION

LIMITATIONS

Raised Foundation Information and Limitations If present : The crawl space limited visual inspection: There are many obstacles present under a home with a raised foundation Some crawl space Access points were not built large enough for a person to enter which is common in older buildings over 50 years old, Minimum Access Opening Size is( 24" wide x 16" Tall) for the average size person to enter. Floor support beams in crawl space are some times lower than minimum requirement of (12" between bottom of beam and soil oor) making access under beams impossible. Also low hanging plumbing & low hanging electrical wires also prevent access in some areas ( this is typically a sign of poor installation of plumbing and wiring) Many times a large amount of debris is present under homes from prior repairs or remodeling that makes it unsafe for inspector, this debris should be removed, large water leaks and ponding water under home will also prevent the inspector from entering for safety reasons.

Deciencies

5.2.1 Slab Foundation

FOUNDATION CRACKS - MINOR

661 Loran Way Scott Woodburn FOCUS Inspection Authority Page 44 of 139
Maintenance Item

Minor cracking was noted at the foundation. This is common as concrete ages and shrinkage surface cracks are normal. This does not appear to be a structural issue at this time Recommend monitoring for more serious shifting/displacement Here is an informational article on foundation cracks.

5 2 2 Slab Foundation FOUNDATION STEM-WALL SPALLING OR CRACKS/DAMAGE

Foundation stem-wall or one or more CMU foundation wall spalling or cracks were observed in the noted areas. Recommend spot repair with Mortar/Epoxy.

5

PARGE COAT DEFICIENCY ON FOUNDATION STEM WALL

Recommendation

Observed area of parge coat deciency on stem wall, at noted area of the foundation This does not appear to be a structural issue but should be repaired to prevent further deciency or deterioration At times this may also be due to moisture intrusion onto the stem wall from sprinklers, negative grading, or lack of gutter application.

661 Loran Way Scott Woodburn FOCUS Inspection Authority Page 45 of 139
Right Back Front Front Front
Recommendation
2 3 Slab Foundation Back Left
661 Loran Way Scott Woodburn FOCUS Inspection Authority Page 46 of 139
Back Right Back Right Left Front

6: PLUMBING MAIN

661 Loran Way Scott Woodburn FOCUS Inspection Authority Page 47 of 139 General: INSP GE
Water
Drain and Waste
Drain Size 3" Cleanouts Drain and Waste Systems: Material ABS
Water Main Shut-o Device: General Overview Photo
Main Shut-o Device: Water Pressure It is recommended that water pressure be between 40 psi and 80 psi
Systems:
IN NI NP D
General X 6.2 Water Main Shut-o Device X
3 Water Supply and Distribution Systems X 6.4 Drain and Waste Systems X 6 5 Gas Main Shut-o Device X 6.6 Dryer Vent Termination X 6.7 Fire Sprinkler System 6 8 Sump Pump X 6.9 Septic Tank IN = Inspected NI = Not Inspected NP = Not Present D = Deciencies Information section-ZGM4NTY3ODctYTI3MS00OGMwLWFkODItNjRkZjE5YzM3NjJl
6.1
6

Gas Main Shut-o Device: General

Dryer Vent Termination: Location

Roof

Water Main Shut-o Device: Location Right Side of Garage

Informational: It is important to know where your main water supply shut o valve is located. In the event of a water leak inside the home you should turn o the main water valve immediately and then call a licensed plumbing professional. It is strongly recommended you familiarize yourself with the location of the shut o valve, some water mains have multiple handles in a small area, if this is present at your water main i recommend you label the correct valve for ease of locating it in the event of a water leak emergency Do not block the valve with storage of furniture or allow overgrowth of plants for easy access

Note: If the inspector could not locate the water main it is recommended you request disclosure from seller before the end of your inspection contingency period

Water Supply and Distribution Systems: Water Supply Material

Not All Supply Lines Are Visible, Copper

NOTE: Supply system pipe is the line delivering water from the potable source to the building.

Water Supply and Distribution Systems: Distribution Material

Not All Distribution Lines are Visable, Copper

NOTE: Water-distribution pipe line is located inside a building and delivers potable water to the xtures While we do not open walls to determine this information, we usually can locate and identify material used at the Shut-O Valves that supply sinks and toilets, at the water heater supply lines, or exposed plumbing in the attic space

Water Supply and Distribution Systems: Water Source

Public *

NOTE: If the inspector was able to make access to the public meter at the time of inspection, pictures will be provided. Pictures of the meter reading at the time of inspection, may help to indicate if there is a potential water leak on the property. On some properties, this may not be accessible to the inspector.

Water Supply and Distribution Systems: Copper Pipes

We observed that you’re home construction used copper piping While copper pipe and ttings were common in construction until the late 2000-2010, many professional plumbers now use exible PEX for all new construction and in repairs and extensions to existing copper systems Due to increased chloramine in the water today, we encourage you to replace any copper pipe that shows possible corrosion or patina as a proactive measure against leaking.

661 Loran Way Scott Woodburn FOCUS Inspection Authority Page 48 of 139
Photo
Overview

Drain and Waste Systems: Sewer Lateral Line NOT inspected

NOTE: A Sewer Lateral Line Inspection was NOT requested by the Client Please note that our comments regarding your sewer and or drain lines are from visual only inspection. We always recommend a Sewer Lateral Line Inspection for new homes, and older homes over 20 yrs of age, due to the nature of our Southern California soil, propensity for contraction and expansion, settling and root intrusions. If you decide to have a sewer line camera inspection after your home inspection and prior to your close of escrow, please give us a call as we provide this service to our clients at a reduced rate

Gas Main Shut-o Device: Location Right Side of Home

Informational: It is important to know where your main fuel (GAS) supply shut o valve is located In the event of a Gas leak in or around the home you should turn o the main fuel valve immediately and then call the gas company or a licensed plumbing professional It is strongly recommended you familiarize yourself with the location of the main fuel shut o valve typically located at the gas meter Do not block the valve with storage of furniture for easy access

Note: This valve is NOT easy to turn without the proper gas valve wrench I recommend you purchase one when you close escrow and store it near the main fuel shut o typically located at the GAS Meter. This type of wrench can be purchased at amazon, home depot etc

Gas Shut O Wrench Sample

Dryer Vent Termination: General Overview Photo

If Dryer Vent terminates on the roof, it may not be as readily accessible for a photo

661 Loran Way Scott Woodburn FOCUS Inspection Authority Page 49 of 139
Gas Shut O at Meter Sample

Dryer

Vent Termination: Dryer Vent Maintenance Reminder

DRYER MAINTENANCE REMINDER Info Only: Excessive lint accumulation around the dryer vent exhaust cover can cause the damper to stick open from lint. This can be a potential re hazard and will also allow for air leakage and pest intrusion The exhaust vent was fairly clean at the time of inspection, however we recommend that you have the dryer duct and terminal cleaned yearly or as needed.

Here's a helpful article on this topic, click here:

Keeping Your Dryer Clean and Safe

661 Loran Way Scott Woodburn FOCUS Inspection Authority Page 50 of 139

7: ELECTRICAL MAIN

7.1 Main Panel X X

7.2 Sub Panel X

7 3 Service Entrance Conductors X

7.4 Branch Wiring Circuits, Breakers, Fuses & Junction Boxes X X

7 5 Main GFCI Reset(s) X

Main Panel: INSP

AB, Other

Main Panel: Main Panel Manufacturer Cutler Hammer, Eaton

Branch Wiring Circuits, Breakers, Fuses & Junction Boxes: Wiring Method

Romex/NM Nonmetallic Sheathed

Main Panel: Main Panel Location Right

Main Panel: Panel Type Circuit Breaker

Main Panel: Panel Capacity 200 AMP

Service Entrance Conductors: Electrical Service Conductors Below Ground

Branch Wiring Circuits, Breakers, Fuses & Junction Boxes: Unused Breaker In Box

Observed unused breaker in box Unknown use

Main GFCI Reset(s): Main GFCI Reset Location(s) Multiple Locations, 1/2-1/3 Bathroom

1/2-1/3 Bath

661 Loran Way Scott Woodburn FOCUS Inspection Authority Page 51 of 139
IN NI NP D
IN = Inspected NI = Not Inspected NP = Not Present D = Deciencies
section-NDM0YTFjYjktZGVmZS00MzNlLTkwYjEtOGQ5YjAyNzIwY2Nl
Information

Main Panel: Main Panel Photos

Main Panel: Main Panel Shut O

Note Picture Location of Your Main Power Shut O

Note Location

Branch Wiring Circuits, Breakers, Fuses & Junction Boxes: Branch Wire 15 and 20 AMP Copper

Branch Wiring Information: The branch wiring was inspected at visible portions looking for any signicant deciencies or defects that could be a re and/or safety hazard; including but not limited to: connections made outside of a junction box, wiring terminations, open junction boxes, damage, the wiring material, improper support, etc The majority of branch feeders are not visible due to being behind wall and ceiling coverings, insulation, etc. No signicant deciencies were visibly present at the time of inspection unless otherwise noted in this report

Deciencies

7 1 1 Main Panel MAIN PANEL COVER DEFICIENCY

Recommendation

Observed at time of inspection, main panel cover was dicult to remove due to access invitation Recommend further valuation by qualied electrician.

Recommendation

Contact a qualied professional.

7 4 1 Branch Wiring Circuits, Breakers, Fuses & Junction Boxes LOOSE BREAKER

Recommendation

661 Loran Way Scott Woodburn FOCUS Inspection Authority Page 52 of 139

Observed one or more breakers loose in main or sub panel. If connecting wires are not properly attached or if the breaker itself is not securely mounted, it can become loose over time This can create safety issues and even lead to electrical res if left unaddressed Recommend correction.

Recommendation

Contact a qualied professional.

661 Loran Way Scott Woodburn FOCUS Inspection Authority Page 53 of 139

Cooling Equipment: Energy Source/Type

8: COOLING SYSTEM

Cooling Equipment: Manufacture

Cooling Equipment: Location Left Side of Home

Cooling Equipment: Cooling Type/Style Split, Central

Cooling Equipment: Cooling

661 Loran Way Scott Woodburn FOCUS Inspection Authority Page 54 of 139
INSP AB, Other
General:
Carrier
Electric
Distribution System: Conguration Central, Split
System Approximate Age Year - 2009
IN NI NP D 8.1 General X 8.2 Cooling Equipment X X 8 3 Normal Operating Controls 8.4 Distribution System X 8 5 Cool Temperature Readings IN = Inspected NI = Not Inspected NP = Not Present D = Deciencies Information section-NDZiNWNlZDYtZjdmZi00MzY5LWIzZGMtOWQ5ZDZkMDA0MTk5

Cooling Equipment: SEER Rating

14 SEER

Video

(click here to view on web)

Modern standards call for at least 13 SEER rating for new install Read more on energy ecient air conditioning at Energy.gov.

How do I nd the SEER rating on my AC unit? (Seasonal Energy Eciency Ratio)

The manufacturer typically provides the number, and there are several ways to nd it: Look for the yellow and black rating sticker Found on the side of the condenser, it clearly states the system's SEER rating Look for an information sheet axed to the front of the air handler, the interior unit.

Cooling Equipment: Multiple AC Units Installed in Home

Multiple AC Units Installed - Informational: Multiple units allow for an easier time balancing the desired temperature in your home Generally, one area of your home will be warmer or more dicult to cool than another In a two-story home, the upstairs area is often warmer, as warm air rises Having multiple AC units in your home can help balance out the temperature. However, it's also important to note that multiple units double your chances of a system failure and increase your overall cost of repairs over time

661 Loran Way Scott Woodburn FOCUS Inspection Authority Page 55 of 139 General:
General Photo & Video

Cool Temperature Readings: Extreme Temperature - No Temperatures Taken

Due to the outside and/or interior temperature being lower that 65*, the AC unit was not tested for cooling as this has the potential for damage to the unit. We recommend that the AC portion of your HVAC system be tested and serviced prior to extended use when temperatures are above 65*

Deciencies

8 2 1 Cooling Equipment INSULATION

MISSING OR DAMAGED

Missing or damaged lineset insulation on AC refrigerant line can cause energy loss and condensation. A typical residential AC unit has two copper lines that both exit the building exterior and run to the outside condenser unit. Only one of these copper pipes, the cold line, should be insulated This is called the “suction” pipe or line and is typically the larger of the two pipes

8 2 2 Cooling Equipment

661 Loran Way Scott Woodburn FOCUS Inspection Authority Page 56 of 139
Recommendation
OLDER UNIT R-22 REFRIGERANT Maintenance Item

Suspect that your Air Conditioning System uses R-22 refrigerant. This can no longer be sold due to environmental hazards. Newer HVAC systems use R410-A that does not harm the environment

Recommend that you budget for replacement When this system stope working, it will be beyond economic repair. You can nd the refrigerant information in the data plate on the side of your condenser.

NOTE: On January 1, 2010, the Environmental Protection Agency (EPA) implemented a ban on the production and import of R22, except for continuing servicing needs of existing equipment. The EPA also banned the manufacture and installation of new R22 AC or heat pump systems.

8 2 3 Cooling Equipment

PLASTIC PLATFORM DEFICIENCY

At time of inspection AC condenser was on a plastic platform. This is usually only for a temporary footing. Plastic platforms are inclined to shift and sink in wet soil aecting the unit in maintaining level. Recommend concrete footing for more permanent stabilization

Recommendation

Contact a qualied professional

661 Loran Way Scott Woodburn FOCUS Inspection Authority Page 57 of 139
Maintenance Item

Cooling Equipment: Energy

Source/Type Electric

9: COOLING SYSTEM 2

Cooling Equipment: Manufacture

Cooling Equipment: Location Left Side of Home

Cooling Equipment: Cooling Type/Style Central, Split

Cooling Equipment: Cooling System Approximate Age Year - 2009

661 Loran Way Scott Woodburn FOCUS Inspection Authority Page 58 of 139
AB, Other
General: INSP
Carrier
Normal Operating Controls: Thermostat Distribution System: Conguration Central, Split
IN NI NP D 9.1 General X 9.2 Cooling Equipment X X 9 3 Normal Operating Controls X 9.4 Distribution System X 9 5 Cool Temperature Readings X IN = Inspected NI = Not Inspected NP = Not Present D = Deciencies Information
section-YjM4OWIwNDktMDc3MC00MjQzLTg2ODctMWVlYWQwNGE5N2Vh

Cooling Equipment: SEER Rating 14

Video

(click here to view on web)

Modern standards call for at least 13 SEER rating for new install Read more on energy ecient air conditioning at Energy.gov.

How do I nd the SEER rating on my AC unit? (Seasonal Energy Eciency Ratio)

The manufacturer typically provides the number, and there are several ways to nd it: Look for the yellow and black rating sticker Found on the side of the condenser, it clearly states the system's SEER rating Look for an information sheet axed to the front of the air handler, the interior unit.

Cooling Equipment: Multiple AC Units Installed in Home

Multiple AC Units Installed - Informational: Multiple units allow for an easier time balancing the desired temperature in your home Generally, one area of your home will be warmer or more dicult to cool than another In a two-story home, the upstairs area is often warmer, as warm air rises Having multiple AC units in your home can help balance out the temperature. However, it's also important to note that multiple units double your chances of a system failure and increase your overall cost of repairs over time

661 Loran Way Scott Woodburn FOCUS Inspection Authority Page 59 of 139 General: General Photo & Video

Cool Temperature Readings: Extreme Temperature - No Temperatures Taken

Due to the outside and/or interior temperature being lower that 65*, the AC unit was not tested for cooling as this has the potential for damage to the unit. We recommend that the AC portion of your HVAC system be tested and serviced prior to extended use when temperatures are above 65*

Deciencies

9 2 1 Cooling Equipment INSULATION

MISSING OR DAMAGED

Missing or damaged lineset insulation on AC refrigerant line can cause energy loss and condensation. A typical residential AC unit has two copper lines that both exit the building exterior and run to the outside condenser unit. Only one of these copper pipes, the cold line, should be insulated This is called the “suction” pipe or line and is typically the larger of the two pipes

9 2 2 Cooling Equipment

661 Loran Way Scott Woodburn FOCUS Inspection Authority Page 60 of 139
Recommendation
OLDER UNIT R-22 REFRIGERANT Maintenance Item

Suspect that your Air Conditioning System uses R-22 refrigerant. This can no longer be sold due to environmental hazards. Newer HVAC systems use R410-A that does not harm the environment. Recommend that you budget for replacement When this system stope working, it will be beyond economic repair You can nd the refrigerant information in the data plate on the side of your condenser.

NOTE: On January 1, 2010, the Environmental Protection Agency (EPA) implemented a ban on the production and import of R22, except for continuing servicing needs of existing equipment. The EPA also banned the manufacture and installation of new R22 AC or heat pump systems

9 2 3 Cooling Equipment VEGETATION TOO CLOSE

Vegetation was too close to the compressor, which can limit heat dissipation and limit eectiveness It is recommended to leave at least three feet of space between the AC unit and your plants Never put plants on top of your AC unit as well As a general, it's best to err on the side of caution when it comes to putting things near your air conditioner. Recommend cutting back vegetation to avoid overheating compressor.

9 2 4 Cooling Equipment PLASTIC PLATFORM DEFICIENCY

At time of inspection AC condenser was on a plastic platform. This is usually only for a temporary footing. Plastic platforms are inclined to shift and sink in wet soil aecting the unit in maintaining level. Recommend concrete footing for more permanent stabilization.

Recommendation

Contact a qualied professional

661 Loran Way Scott Woodburn FOCUS Inspection Authority Page 61 of 139
Recommendation Maintenance Item

General: INSP

10: HEATING SYSTEM

Equipment: Location of Furnace/AirHandler Attic

Equipment: Manufacture

Equipment: Heating System

Approximate Age

Equipment: Heat Type

Equipment: Energy Source Gas

661 Loran Way Scott Woodburn FOCUS Inspection Authority Page 62 of 139
AB
Carrier
Forced
Air
Year - 2005
IN NI NP D
X 10.2 Equipment X
Normal Operating Controls X
Distribution Systems X X 10 5 Heat Temperature Readings X IN = Inspected NI = Not Inspected NP = Not Present D = Deciencies
10.1 General
10 3
10.4
Information section-ZjRkZmRlYzgtZTcyMi00NGNiLWE5ZjItMDBjMDZkODIzZmU3

General: General Photos & Video

Video

(click here to view on web)

Equipment: AFUE Rating

80

AFUE (Annual fuel utilization eciency) is a metric used to measure furnace eciency in converting fuel to energy. A higher AFUE rating means greater energy eciency 90% or higher meets the Department of Energy's Energy Star program standard.

GENERAL INFORMATION:

To nd your current furnace AFUE rating – The rating should be on your furnace's faceplate If it's not, then look for the model or serial number of the furnace, which should be on the furnace or on the compressor outside. Use that model or serial number on the manufacturer's website to nd the furnace's AFUE rating

A standard eciency furnace provides 80% annual fuel utilization eciency (AFUE). In this type of furnace, 20% of the energy produced by natural gas is expelled as exhaust These days, 95% AFUE is a common rating among new gaspowered furnaces. So a 95% furnace is more ecient than an 80% furnace.

A 20 or 25 year old furnace may have an eciency rating of about 60% Instead of warming your house, 40% of the heat generated through combustion of natural gas goes up the ue and out the chimney High eciency furnaces of today on average have an eciency rating of 90-95%

661 Loran Way Scott Woodburn FOCUS Inspection Authority Page 63 of 139 Normal Operating Controls: Thermostat Distribution Systems: Ductwork Insulated

Heat Temperature Readings: Temperature Reading at Register

Temperature reading at register in one or more rooms We look for adequate airow as well as a minimum temperature variance of 10°-15° between intake return and room registers.

Deciencies

10 4 1 Distribution Systems DUCTWORK TOUCHING DEFICIENCY

Recommendation

When ductwork is touching it forms a very cold spot at that location and condensation may accumulate Ductwork located in an attic or crawlspace should be hung and separated properly so that the insulation can perform properly. We recommend evaluation of this component, and correction as indicated.

Recommendation

Contact a qualied professional.

661 Loran Way Scott Woodburn FOCUS Inspection Authority Page 64 of 139
Base Reading 2nd Floor Heat Reading

11: HEATING SYSTEM 2

Equipment: Location of Furnace/AirHandler

661 Loran Way Scott Woodburn FOCUS Inspection Authority Page 65 of 139 General: INSP AB
Manufacture Carrier Equipment: Heat Type Forced Air, Gas-Fired Heat
Equipment:
Attic
Age Year - 2005
Energy Source Gas
Equipment: Heating System Approximate
Equipment:
IN NI NP D 11.1 General X 11.2 Equipment X 11 3 Normal Operating Controls X 11.4 Distribution Systems X 11 5 Heat Temperature Readings X IN = Inspected NI = Not Inspected NP = Not Present D = Deciencies Information section-MDEwZWM2YzQtNzllYS00NDJmLTg1NWItZjZmNzJmNzZhYTJm

Equipment: AFUE Rating

80

AFUE (Annual fuel utilization eciency) is a metric used to measure furnace eciency in converting fuel to energy. A higher AFUE rating means greater energy eciency 90% or higher meets the Department of Energy's Energy Star program standard.

GENERAL INFORMATION:

To nd your current furnace AFUE rating – The rating should be on your furnace's faceplate If it's not, then look for the model or serial number of the furnace, which should be on the furnace or on the compressor outside. Use that model or serial number on the manufacturer's website to nd the furnace's AFUE rating

A standard eciency furnace provides 80% annual fuel utilization eciency (AFUE). In this type of furnace, 20% of the energy produced by natural gas is expelled as exhaust These days, 95% AFUE is a common rating among new gaspowered furnaces. So a 95% furnace is more ecient than an 80% furnace.

A 20 or 25 year old furnace may have an eciency rating of about 60% Instead of warming your house, 40% of the heat generated through combustion of natural gas goes up the ue and out the chimney. High eciency furnaces of today on average have an eciency rating of 90-95%

Heat Temperature Readings: Temperature Reading at Register

Temperature reading at register in one or more rooms We look for adequate airow as well as a minimum temperature variance of 10°-15° between intake return and room registers

661 Loran Way Scott Woodburn FOCUS Inspection Authority Page 66 of 139 Normal Operating Controls: Thermostat Distribution Systems: Ductwork Insulated
General: General Photos & Video
Base Reading 1st Floor Heat Reading
Video (click here to view on web)

12: WATER HEATER/HOT WATER SYSTEM

section-MGFjYzlhYzMtODg3MS00MDlmLWIzZTQtNWZlODA2NjVjZjk4

12.1 General X 12.2 Equipment

Information

General: INSP

RM, Other

Equipment: Capacity

50 gallons

General: General Overview Photo

Equipment: Type/Style Tank

Equipment: Water Heater

Approximate Age

YEAR - 2018

Equipment: Location Garage

Equipment: Energy Source Gas

661 Loran Way Scott Woodburn FOCUS Inspection Authority Page 67 of 139
IN NI NP D
X X IN = Inspected NI = Not Inspected NP = Not Present D = Deciencies

Equipment: Manufacturer

AO Smith

It is recommended to ush & service your water heater annually for optimal performance Water temperature should be set to at least 120 degrees F to kill microbes and no higher than 130 degrees F to prevent scalding. Here is a nice maintenance guide from Lowe's to help

Equipment: Water Temperature Tested

Informational: Water temperature at one or more locations in the home was tested 120°F is the temperature safety recommendation for home water heaters. Most experts agree that anything below 120° may create a risk for bacteria to develop inside the water heater from stagnant water, such as Legionella that causes legionnaires disease

Equipment: Conventional Tank Water Heater

Information Regarding Conventional (Tank) Water heater: The life expectancy of a conventional water heater depends on several factors, manufacturers warranty, maintenance of tank and usage A typical life expectancy of a conventional water heater is between 6-15 years. The inspector can not determine when a water heater will fail. The warranty of the unit can give you a time line of when you may expect to replace it and when it may have reached the end of its life expectancy. If the tank is leaking it would need immediate replacement. Recommend requesting service record of water heater from seller, if seller has no record or knowledge of servicing tank i recommend you have it serviced soon by a qualied professional

Deciencies

12 2 1 Equipment

NO DRIP/CATCH PAN

Recommendation

No drip pan and associated pan drainage was present Recommend installation by a qualied plumber

661 Loran Way Scott Woodburn FOCUS Inspection Authority Page 68 of 139

12 2 2 Equipment

OPEN GAPS IN WALL PENETRATIONS

Safety Hazard

Observed open gaps in wall penetrations in the water heater surround or closet (This is considered as a Fire Wall) All Drywall cracks or openings should be sealed properly with either a drywall repair application and/or with re stop at open penetrations. Recommend sealing gaps at wall or ceiling penetrations. Safety.

12 2 3 Equipment

WATER HEATER HIGH TEMP

Hazard

Water temperature setting at water heater is over 125°. This may pose a safety hazard as scalding water is 130° Recommend decreasing water temperature at hot water thermostat unless specically needed.

See additional information at the following site:

https://www.mrrooter.com/about/blog/2018/april/what-temperatureshould-a-hot-water-heater-be-se/

661 Loran Way Scott Woodburn FOCUS Inspection Authority Page 69 of 139
Water Heater Drip Pan Safety
661 Loran Way Scott Woodburn FOCUS Inspection Authority Page 70 of 139 General: General Overview Photo General: INSP RM Floors: Floor Overview Pic Cabinets & Countertops: Cabinet Type/Style Wood Cabinets & Countertops: Countertop Type/Style None Garage Door: Material Metal, Non-insulated
IN NI NP D 13.1 General X 13.2 Doors X 13 3 Windows X 13.4 Floors X 13 5 Walls & Firewalls X X 13.6 Ceiling X 13.7 Cabinets & Countertops X 13 8 Garage Door X 13.9 Garage Door Opener X X 13 10 Lighting Fixtures, Switches & Receptacles X 13.11 GFCI & AFCI X 13.12 Fire Door X 13 13 Pool Safety Door X IN = Inspected NI = Not Inspected NP = Not Present D = Deciencies Information section-OTlmMzA4MjQtM2RlZi00NWFiLWI4ZmItNjk5NTgzNDliY2I3
13: GARAGE

General: Limitation of Inspection Due to Storage Boxes

The inspector was limited in his observations and ability to inspect this component due to the storage of items that blocked access and the view of the walls, ceilings and oors of the garage We bring this to your attention as a limitation of inspection. It is possible that after storage items are removed or cleared out, other deciencies may be observed

Doors: Exterior Occupant Side Door

Since occupant door to garage is exterior only, it does not have a requirement for re door rating We did test the garage occupant entry side door for proper opening and closing, weatherstripping, locking device and general condition of the door. These components were found functional and serviceable at time of inspection unless otherwise noted below in this report.

661 Loran Way Scott Woodburn FOCUS Inspection Authority Page 71 of 139 Garage
General Overview Photo
Door Opener:

Doors: Door Blocked

Side garage door was blocked by storage We are unable to inspect this component

Walls & Firewalls: Walls and Fire Walls

Walls Information: The walls appeared to be in satisfactory condition at the time of inspection No deciencies were observed at visible portions unless otherwise noted in this report.

Fire Wall Separation: Current standards require that walls adjacent to living areas in a garage are covered with 1/2" drywall for proper separation of garage to living space Homes built prior to 2006 (year dependent on local municipality) may not have this protection, but upgrades are recommended for safety.

Garage Ventilation: Currently, residential garages are not required to have ventilation under ANSI/ASHRAE Standard 62.2. However, the EPA does recommend active ventilation to help get rid of toxic fumes and carbon monoxide. Even though it's not legally required, it's still a good idea to have some sort of ventilation in your garage Garage ventilation is a growing concern today among homeowners. Not ventilating your garage can be extremely dangerous. Your car exhaust releases many toxic fumes, and without proper ventilation, these fumes can get trapped within the walls of your garage creating a health hazard.

Another reason you may want to ventilate your garage is to control the buildup of heat. Because of the lack of air space in a garage, things can get extremely stuy We add the above comments to our report for your information only.

661 Loran Way Scott Woodburn FOCUS Inspection Authority Page 72 of 139
Ceiling: Overview picture

Garage Door: General Overview Photo

Garage Door: Style/Type Automatic, Sectional, Overhead

Garage Door: Overhead Door Introduction: Inspection of overhead garage doors typically includes examination for presence, serviceable condition and proper operation of the following components:

- door condition;

- mounting brackets;

- automatic opener;

- automatic reverse;

- photo sensors;

- switch placement;

- track & rollers; and

- manual disconnect

Garage Door Opener: Garage Door Inspection Terms

The garage door opener was tested and was serviceable at time of inspection. Safety sensors were also tested and serviceable at time of inspection unless otherwise noted below.

Garage Door Opener Information

The garage door opener(s) were inspected by depressing the wall mounted transmitter and observing the openers functionality (remote transmitters are not tested). No reportable conditions were present at the time of inspection unless otherwise noted in this report.

Garage Door Opener: Auto-Reverse Disclaimer:

Garage doors are not tested by the Inspector using specialized equipment and this inspection will not conrm compliance with manufacturer's specications This inspection is performed according to the Inspector's judgment from past experience. You should adjust your expectations accordingly. If you wish to ensure that the garage door automatic-reverse feature complies with the manufacturer's specications, you should have it inspected by a qualied garage door contractor.

Manual Release Handle/Cord Tested: This is a means of manually detaching the door from the door opener in case of emergency or power loss. The handle should be colored red so that it can be seen easily The handle should be easily accessible and no more than 6 feet above the garage oor The handle should not be in contact with the top of a vehicles

661 Loran Way Scott Woodburn FOCUS Inspection Authority Page 73 of 139

Garage Door Opener: Garage Door Opener Emergency Manual Release

Manual Release Handle/Cord Tested: This is a means of manually detaching the door from the door opener in case of emergency or power loss.

The handle should be colored red so that it can be seen easily. The handle should be easily accessible and no more than 6 feet above the garage oor The handle should not be in contact with the top of a vehicles This component was serviceable at time of inspection UNLESS OTHERWISE NOTED BELOW

Fire Door: Fire Door Inspection Terms

The door from the garage to the home was tested for meeting safety and re standards. This door must be self closing and latching and re rated Meeting safety standards If there is deciency, it will be noted below and should be corrected at your earliest opportunity.

Deciencies

13 5 1 Walls & Firewalls

DRYWALL

Garage walls showed signs of previous moisture intrusion. At time of inspection moisture meter showed wet material. Recommend disclosure by previous owner of cause of previous moisture intrusion and remediation and repair of damaged drywall.

13 9 1 Garage Door Opener

661 Loran Way Scott Woodburn FOCUS Inspection Authority Page 74 of 139
Fire Door: General Overview Photo Video (click here to view on web)
MOISTURE INTRUSION/DAMAGED/STAINED
Maintenance Item
DEFICIENCY Safety Hazard
GARAGE DOOR SAFETY SIDE SENSORS

As a general rule, Garage door sensor should be mounted not more than 6 inches above the oor. This is a safety precaution so that people or animals do not get trapped under the door as it closes Recommend correction in the height of sensor to meet safety standard. Easy x.

13 9 2 Garage Door Opener GARAGE DOOR OPENER DEFICIENCY

Recommendation

Garage door opening device is malfunctioning, not opening or closing properly. Recommend further evaluation by garage door technician.

Recommendation

Contact a qualied professional.

13 9 3 Garage Door Opener GARAGE

DOOR SAFETY SIDE SENSORS NOT FUNCTIONING

Observed at time of inspections, the garage door, safety side sensors were not functioning properly This is a safety issue and should be repaired

Recommendation

Contact a qualied professional. Safety Hazard

13 10 1 Lighting Fixtures, Switches & Receptacles COVER PLATES LOOSE/DAMAGED/MISSING

Recommendation

One or more receptacles or light switches have a damaged, loose or missing cover plate. Recommend repair or replacement.

661 Loran Way Scott Woodburn FOCUS Inspection Authority Page 75 of 139

14: INTERIOR DETAILS

section-M2MzODFlNzgtNDk4NS00YTQ4LWI4N2EtZThiMzFjM2U4ZmFi

14.1 Doors X

14.2 Windows X

14 3 Floors X

14.4 Walls X

14 5 Ceilings X

14.6 Smoke/Carbon Monoxide Detectors

Information

Windows: Window Manufacturer ABC Floors: Floor Type/Style Tile, Carpet

Ceilings: Ceiling Type/Style

Gypsum Board, Drywall

Doors: Door Type/Style

Wood, Solid Wood, Hollow Core, Glass Sliding Doors

Walls: Wall Type/Style

Drywall, Gypsum Board

Types of doors found in the interior of the residence are presented for information only For a description of types of doors found, you can visit the following website listed below. The selection of types of doors found above may not be a complete listing of all doors found in the residence Doors are inspected for proper opening and closing, damage, deciency in their operation, hardware deciency, etc. No reportable deciencies were present at the time of inspection unless otherwise noted in this report.

https://legaleaglecontractors.com/choosing-right-interior-doors/

Windows: Window Type/Style

Drop-down, Sliders, Picture, Double Pane

Information on Windows:

Single Pane/Glazed Window: Single-pane/glazed with clear glass allows the highest transfer of energy (i e heat loss or heat gain depending on local climate conditions) while permitting the highest daylight transmission. (this type of window is the least energy ecient)

Double Pane/Glazed Window: A typical clear, double-pane/glazed unit has two lites or pieces of glass with the inner and outer layers of glass both being clear and separated by an air gap Double glazing, compared to single glazing, cuts heat loss in half due to the insulating air space between the glass layers. In addition to reducing the heat ow, a double-glazed unit with clear glass will allow the transmission of high visible light and high solar heat gain

Triple Pane/Glazed Window: This window is suited for buildings located in very cold climates Both Low-E coatings in this product have high solar heat and visible light transmittance, which is ideal for passive solar design The use of three layers, however, results in lower solar heat gain relative to double glazing with high-solar-gain Low-E.

661 Loran Way Scott Woodburn FOCUS Inspection Authority Page 76 of 139
IN NI NP D
IN = Inspected NI = Not Inspected NP = Not Present D = Deciencies

14 6 1 Smoke/Carbon Monoxide Detectors SMOKE AND OR CARBON

MONOXIDE DETECTOR DEFICIENCY

We did NOT nd either one or more Smoke Detectors and/or CO2 Detectors in the required places as noted in this report. Recommend correction of this component.

Recommendation

Contact a qualied professional.

661 Loran Way Scott Woodburn FOCUS Inspection Authority Page 77 of 139 Deciencies
Hazard
Safety

15: LAUNDRY ROOM

Information section-MmQxNzUzYTgtYmNmMC00ZGFhLThiNzYtYzZiYjY3NDJhZjUz

15.1 General X

15.2 Laundry Room Equipment X

15 3 Sink, Faucets, Plumbing X

15.4 Cabinets & Countertops X

15 5 Doors X

15.6 Windows X

15.7 Floors X

15 8 Walls X

15.9 Ceilings X

15 10 Lighting Fixtures, Switches & Receptacles X

15.11 GFCI & AFCI X X IN = Inspected NI = Not Inspected NP = Not Present D = Deciencies

General: INSP GE

Laundry Room Equipment: Dryer Power Source 110 Volt, 220 Electric, Gas

Cabinets & Countertops: Cabinet Type/Style Wood

Cabinets & Countertops: Countertop Type/Style

None

661 Loran Way Scott Woodburn FOCUS Inspection Authority Page 78 of 139
IN NI NP D

General: General Overview Photo

Please Note LIMITATIONS:

The laundry area is a LIMITED inspection. We inspect for presence of proper venting of dryer, presence of proper wiring of electrical connections, gas lines and ttings, and presence of proper drainage to laundry tub or wall drain All of the above appear serviceable at time of inspection unless otherwise noted on report.

Laundry Area/Closet/Room and Facilities: We do NOT TEST for proper drainage, and do NOT TEST the dryer vent or gas lines, Do NOT disconnect plumbing lines or connections for testing purposes. Operation of clothes washer and dryer are excluded from this general home inspection Inspector does NOT inspect the following, including but not limited to, the dryer or washing machine, their plumbing lines or any of their connections, including connections to the laundry faucets, the operation of any valves, determining the exact ow rate, if any, the volume, pressure, temperature or adequacy of the water supply in the laundry room to the washing machine. Due to the limitations of our inspection for this component, we recommend that you test your own water supply, both hot and cold, to the washing machine using a catch bucket or other device, prior to nal close of escrow, since this component is specically excluded from our inspections

Deciencies

15 11 1 GFCI & AFCI GFCI PROTECTION NOT PRESENT/FOUND

GFCI protection was not present/found in this location, at the time of inspection GFCI protection is recommended to be present for the exterior, garage, basement, laundry area, and crawl space receptacles for safety, as well as ALL kitchen and bathroom receptacles. We recommend repairs or upgrades as needed to ensure GFCI protection is present at all recommended locations for safety and recommended work to be performed by a licensed electrician

661 Loran Way Scott Woodburn FOCUS Inspection Authority Page 79 of 139
Safety Hazard

16: LIVING ROOM

Deciencies section-YWI0YTU1MjAtMjhmMC00NDZkLWFjYTAtNjcwYmFkNWI5ZGRl

16 7 1 Cabinets & Countertops

CABINET DOORS/DRAWERS NEED ADJUSTMENT OR REPAIR

Needs Attention: One or more cabinet doors or drawers need adjustment or repair, it is common for doors and drawers to come loose over time and is typically a minor repair that can be performed by a qualied professional or DIY. Recommendation

661 Loran Way Scott Woodburn FOCUS Inspection Authority Page 80 of 139
None
General: General Overview Photo Cabinets & Countertops: Cabinet Type/Style Laminate, Wood Cabinets & Countertops: Countertop Type/Style
IN NI NP D
General X 16.2 Doors X 16 3 Windows X 16.4 Floors X 16 5 Walls X
Ceilings X 16.7 Cabinets & Countertops X X 16 8 Lighting Fixtures, Switches & Receptacles X IN = Inspected NI = Not Inspected NP = Not Present D = Deciencies
16.1
16.6
Information

Deciencies

17: DINING ROOM

CRACKS

Observed minor cracks at the corners of doors, windows or ceilings at walls at noted locations. Appeared to be the result of long-term settling. Some settling is not unusual in a home of this age and these cracks are not a structural concern. Recommend maintenance repair of this component Cosmetic

661 Loran Way Scott Woodburn FOCUS Inspection Authority Page 81 of 139 General:
General Overview Photo
IN NI NP D 17.1 General X 17.2 Doors X 17
Windows X 17.4 Floors
17
Walls
Ceilings
Cabinets
Countertops
17
Lighting
Switches
IN = Inspected NI = Not Inspected NP = Not Present D = Deciencies
3
X
5
X X 17.6
X 17.7
&
X
8
Fixtures,
& Receptacles X
Information
section-MzQ5OTdlMjAtOTkzZS00MTNmLTkyYjctN2YzNDAxYTU2ZGIy
Walls MINOR
17 5 1
CORNER/DRYWALL
Maintenance Item 17 5 2 Walls WALL DAMAGE Maintenance Item

Observed wall damage at noted location. Recommend a qualied handyman or drywall contractor repair.

661 Loran Way Scott Woodburn FOCUS Inspection Authority Page 82 of 139

18: FIREPLACE

18.1 General X 18.2 Vents, Flues & Chimneys X X 18 3 Lintels, Hearth and Hearth Extension X 18.4 Damper Doors X X

5 Frame, Firewall & Clean Out X

General: General Overview Photo General: INSP RM, Other Frame, Firewall & Clean Out: Type/Style Frame and Fire Box Serviceable

661 Loran Way Scott Woodburn FOCUS Inspection Authority Page 83 of 139
IN NI NP D
IN = Inspected NI = Not Inspected NP = Not Present D = Deciencies
18
Information section-Y2I0ZGZiZDMtNDliMi00YTEwLTkxYjYtODFmYTJiOWY4NzQy

General: Fireplace Type/Style Gas

Pilot lights and replaces are not lit. Our insurance and standards of practice prevent our company from lighting any pilot lights or gas operated replaces.

NOTE: According to InterNACHI SOP for home inspectors, the scope of the inspection for a replace and chimney is limited to readily accessible and visible portions of the replace and chimney. The inspection is not all-inclusive or technically exhaustive The inspection involves a visual-only examination of the readily accessible portions of the chimney exterior, interior, accessible portions of the appliance, and the chimney connection.

It is recommended that all replaces, fuel-burning stoves, and chimneys be inspected by a certied chimney sweep prior to their rst use, and not less than annually.

NOTE: Be advised The National Fire Protection Association (NFPA) recommends a Level 2 Chimney Inspection by a qualied licensed chimney professional with the transfer of real estate This extensive and invasive inspection may reveal concealed defects inside replace box, chimney ue etc This type of specialist inspection is outside the scope of this general home inspection and is specically excluded because home inspector is NOT a qualied licensed chimney specialist contractor and does not posses the specialty tools/equipment needed to perform this type of inspection of chimney or replace.

Most home owners consider their replaces and chimneys to be indestructible parts of their home that require little or no maintenance While masonry work is generally as close to maintenance-free as you can get, replaces and chimneys are more than just works of masonry: they may be part of your homes heating system, which must eectively exhaust fumes from your replace thru the chimney

Relatively minor but regular maintenance eorts can help your chimney operate safely for an indenite period of time. In the U S , many people are poorly informed about the importance of basic chimney maintenance This lack of understanding causes a substantial number of preventable deaths and injuries each year.

Beyond the safety issue, neglect of chimneys leads to very expensive major repairs that would not be necessary if the chimney were properly maintained.

The three most serious problems that result from poorly maintained chimneys/replaces are:

Carbon monoxide poisoning

Chimney res

Premature failure of the replace and chimney

It is beyond the scope of this home inspection to determine the condition of the chimney as this requires observing the inside of the ue for cracks, gaps between ue pieces etc. This is typically performed by a qualied licensed chimney specialist using a video scope It is recommended to hire a chimney specialist for further inspection of chimney/replace before the end of your inspection contingency period or before the close of escrow

Links below provide more information regarding chimney and replace safety

Video Link for Level 2 Chimney & Fireplace Inspections

(CSIA) website Link; Chimney Safety Institute Of America Home Owner Resource

General: Manufactured Gas Fireplace

Not a Wood FP - Because wood burns much hotter than natural gas or propane, it can easily destroy the internal workings of your gas replace. - House re. The powerful heat may radiate into the walls surrounding your replace and spark a serious house re

Vents, Flues & Chimneys: Chimney, Flue and Vent Inspection Terms

Visually inspected these components. Serviceable at time of inspection unless otherwise noted below.

A ue is simply a passage for conveying exhaust gases from an appliance to the outdoors. A ue may be a duct, pipe, vent, or chimney

661 Loran Way Scott Woodburn FOCUS Inspection Authority Page 84 of 139

Lintels, Hearth and Hearth Extension: Lintel & Hearth Inspection Terms

Visually inspected these components Serviceable at time of inspection unless otherwise noted below

The replace lintel or lintel bar is a horizontal beam that runs across the length of the replace and supports the chimney The hearth extension is the non-combustible material in front of and at the sides of the replace opening Hearth and hearth extensions are designed to prevent sparks from leaving the replace and igniting nearby combustibles These components were inspected and found to be serviceable at time of inspection unless otherwise noted below.

Damper Doors: Damper Door Inspection Terms

Inspected this component and found it serviceable at the time of inspection unless otherwise noted below Dampers are made to seal the chimney when res aren't being run, so that the cold air stays out and your home stays warm Dampers send smoke away Before your re gets going, be sure to open the damper, so that all of the smoke escapes through the chimney. Dampers generally are pull to open and push to close. Much like a dresser drawer, Pull to open the drawer, push to close the drawer

Frame, Firewall & Clean Out: Frame, Firewall and Clean Out Inspection Terms

Inspected these components if present, and found them serviceable at the time of inspection unless otherwise noted below

Many Wood Stoves and some older Fireplaces have a cleanout This is a metal door on the ue that's at least a foot lower than the lowest combustion area A missing cleanout door where a wood stove is installed is a re hazard, and it can also allow a buildup of ash that impairs ventilation

Deciencies

18 2 1 Vents, Flues & Chimneys

CREOSOTE BUILDUP NOTED

Recommendation

Observed a layer of creosote dust in the chimney ue. If there is too much buildup inside the chimney, it can hinder the escape of smoke from the re and impact how well the re starts and burns and can also cause a re inside the chimney. Recommend qualied chimney sweep company provide a Level 2 inspection and/or clean prior to use.

661 Loran Way Scott Woodburn FOCUS Inspection Authority Page 85 of 139

18 4 1 Damper Doors

FLUE LOCK/DAMPER STOP

Fireplace needs u lock or damper stop/C-clamp Due to the application of gas logs, the damper should have a C-clamp or damper stop to inhibit it from closing completely. Gas logs within a replace can emit carbon monoxide for up to one hour after use. This is the reason why a C-clamp or damper stop should be installed so that carbon monoxide buildup will not occur within the home after use a gas log replace Recommend correction

661 Loran Way Scott Woodburn FOCUS Inspection Authority Page 86 of 139
Sample Image Safety Hazard
661 Loran Way Scott Woodburn FOCUS Inspection Authority Page 87 of 139

19: FIREPLACE 2 EXTERIOR

section-NzRkODkzZGMtMjVkYy00OWY5LWExMjAtZTAzZThhZTY2Mjc3

19.1 General X 19.2 Vents, Flues & Chimneys X

19 3 Lintels, Hearth and Hearth Extension X X 19.4 Damper Doors X 19 5 Frame, Firewall & Clean Out X

General: General Overview Photo General: INSP GE Frame, Firewall & Clean Out: Type/Style Frame and Fire Box Serviceable, Not able to Inspect Due to Limitations, Closed System

661 Loran Way Scott Woodburn FOCUS Inspection Authority Page 88 of 139
IN NI NP D
IN = Inspected NI = Not Inspected NP = Not Present D = Deciencies
Information

General: Fireplace Type/Style

Wood, Gas

Pilot lights and replaces are not lit. Our insurance and standards of practice prevent our company from lighting any pilot lights or gas operated replaces.

NOTE: According to InterNACHI SOP for home inspectors, the scope of the inspection for a replace and chimney is limited to readily accessible and visible portions of the replace and chimney. The inspection is not all-inclusive or technically exhaustive The inspection involves a visual-only examination of the readily accessible portions of the chimney exterior, interior, accessible portions of the appliance, and the chimney connection.

It is recommended that all replaces, fuel-burning stoves, and chimneys be inspected by a certied chimney sweep prior to their rst use, and not less than annually.

NOTE: Be advised The National Fire Protection Association (NFPA) recommends a Level 2 Chimney Inspection by a qualied licensed chimney professional with the transfer of real estate This extensive and invasive inspection may reveal concealed defects inside replace box, chimney ue etc This type of specialist inspection is outside the scope of this general home inspection and is specically excluded because home inspector is NOT a qualied licensed chimney specialist contractor and does not posses the specialty tools/equipment needed to perform this type of inspection of chimney or replace.

Most home owners consider their replaces and chimneys to be indestructible parts of their home that require little or no maintenance While masonry work is generally as close to maintenance-free as you can get, replaces and chimneys are more than just works of masonry: they may be part of your homes heating system, which must eectively exhaust fumes from your replace thru the chimney

Relatively minor but regular maintenance eorts can help your chimney operate safely for an indenite period of time. In the U S , many people are poorly informed about the importance of basic chimney maintenance This lack of understanding causes a substantial number of preventable deaths and injuries each year.

Beyond the safety issue, neglect of chimneys leads to very expensive major repairs that would not be necessary if the chimney were properly maintained.

The three most serious problems that result from poorly maintained chimneys/replaces are:

Carbon monoxide poisoning

Chimney res

Premature failure of the replace and chimney

It is beyond the scope of this home inspection to determine the condition of the chimney as this requires observing the inside of the ue for cracks, gaps between ue pieces etc. This is typically performed by a qualied licensed chimney specialist using a video scope It is recommended to hire a chimney specialist for further inspection of chimney/replace before the end of your inspection contingency period or before the close of escrow

Links below provide more information regarding chimney and replace safety

Video Link for Level 2 Chimney & Fireplace Inspections

(CSIA) website Link; Chimney Safety Institute Of America Home Owner Resource

Gas was turned o

General: Manufactured Gas Fireplace

Not a Wood FP - Because wood burns much hotter than natural gas or propane, it can easily destroy the internal workings of your gas replace. - House re. The powerful heat may radiate into the walls surrounding your replace and spark a serious house re

661 Loran Way Scott Woodburn FOCUS Inspection Authority Page 89 of 139

Vents, Flues & Chimneys: Chimney, Flue and Vent Inspection Terms

Visually inspected these components Serviceable at time of inspection unless otherwise noted below

A ue is simply a passage for conveying exhaust gases from an appliance to the outdoors. A ue may be a duct, pipe, vent, or chimney

Lintels, Hearth and Hearth Extension: Lintel & Hearth Inspection Terms

Visually inspected these components Serviceable at time of inspection unless otherwise noted below

The replace lintel or lintel bar is a horizontal beam that runs across the length of the replace and supports the chimney The hearth extension is the non-combustible material in front of and at the sides of the replace opening Hearth and hearth extensions are designed to prevent sparks from leaving the replace and igniting nearby combustibles These components were inspected and found to be serviceable at time of inspection unless otherwise noted below.

Damper Doors: Damper Door Inspection Terms

Inspected this component and found it serviceable at the time of inspection unless otherwise noted below

Dampers are made to seal the chimney when res aren't being run, so that the cold air stays out and your home stays warm. Dampers send smoke away. Before your re gets going, be sure to open the damper, so that all of the smoke escapes through the chimney Dampers generally are pull to open and push to close Much like a dresser drawer, Pull to open the drawer, push to close the drawer

Frame, Firewall & Clean Out: Frame, Firewall and Clean Out Inspection Terms

Inspected these components if present, and found them serviceable at the time of inspection unless otherwise noted below.

Many Wood Stoves and some older Fireplaces have a cleanout This is a metal door on the ue that's at least a foot lower than the lowest combustion area. A missing cleanout door where a wood stove is installed is a re hazard, and it can also allow a buildup of ash that impairs ventilation

Deciencies

19 3 1 Lintels, Hearth and Hearth Extension CRACKED

Maintenance Item

Observed one or more cracks at 1/16" or wider around replace hearth and/or mantel This component may be aected by heat expansion and contraction, settling or may have been damaged in some other way. Although mostly cosmetic in nature, we recommend repair by a material specialist and/or resealing to avoid further damage.

661 Loran Way Scott Woodburn FOCUS Inspection Authority Page 90 of 139

20: KITCHEN & BUILT-IN APPLIANCES

661 Loran Way Scott Woodburn FOCUS Inspection Authority Page 91 of 139 General: INSP RM Kitchen Cabinets & Countertops: Cabinetry Material Thermofoil Engineered Wood Kitchen Cabinets & Countertops: Countertop Material Marble
IN NI NP D
General X 20.2 Kitchen Sink, Faucets, Plumbing X X 20 3 Kitchen Cabinets & Countertops X X 20.4 Garbage Disposal X 20 5 Dishwasher X X 20.6 Exhaust Hood X 20.7 Cooktop X 20 8 Oven X X 20.9 Refrigerator X X 20 10 Built-in Microwave X 20.11 Doors X 20.12 Windows X 20 13 Walls X 20.14 Floors X 20 15 Ceilings X 20.16 Lighting Fixtures, Switches & Receptacles X 20.17 GFCI & AFCI X IN = Inspected NI = Not Inspected NP = Not Present D = Deciencies Information section-ODJlYzhlNTQtODU5Ni00YzgyLTgwNTQtYWQyMzM0NDQyZmFk
20.1

Garbage Disposal: General Photo and Video

Exhaust Hood: General Photos and Video

Exhaust Hood: Exhaust Type/Style

Ceiling Mount

661 Loran Way Scott Woodburn FOCUS Inspection Authority Page 92 of 139
Cooktop: General Photos and Video Oven: General Photos and Video Oven: Oven Energy Source Gas Built-in Microwave: General Photos and Video General: General Overview Photo

Kitchen Sink, Faucets, Plumbing: General Photos

Kitchen Sink, Faucets, Plumbing: Sink/Plumbing

Visual inspection was made of the kitchen sink, faucet and plumbing by operating the faucet valves and faucet looking for any leaks or signs of signicant deciencies. The supply and drain pipes were inspected looking for leaks, improper installation, and other deciencies Condition was serviceable at time of inspection unless otherwise noted below.

Garbage Disposal: Garbage Disposal Overview Photo

Disposal Was serviceable at time of inspection unless otherwise noted below.

The sink waste disposal inspection is minimal. Garbage disposal was inspected by activating it at normal controls only and ensuring the motor ran, while also looking for leaks from the unit, an exposed power cord, heavy rust, or other deciencies The unit is not tested to determine if it can eectively "grind" food waste The home Inspector cannot predict the remaining life of the garbage disposal or determine how well the garbage disposal will perform. If the inspector has noted the disposal is leaking/cracked or inoperative the disposal will require replacing

Dishwasher: General Photos and Video

Dishwasher: Manufacture

Kitchenaid

The dishwasher was operated by running a wash cycle, and was functional at the time of inspection No leaks or water was present at the base of the unit at the completion of the cycle. The unit's eciency of cleaning dishes is not tested for No deciencies were observed with the unit unless otherwise noted in this report.

661 Loran Way Scott Woodburn FOCUS Inspection Authority Page 93 of 139

Exhaust Hood: Manufacture KitchenAid

The kitchen exhaust fan was inspected by operating normal controls, checking for proper operation The fan's type (recirculating or exterior) will also be reported on. No deciencies were observed at the time of inspection unless otherwise noted in this report.

Cooktop: Cooktop Manufacture Kitchenaid

The oven was operated by placing into "Bake" mode, and heat was produced from the element(s) Temperature calibration, "clean" options, and other functions are not tested for You are recommended to seek further evaluation of additional functions if desired/needed No indications of deciencies were observed at the time of inspection, unless otherwise noted in this report.

All cooktop heating elements were turned to "High", and were functional at the time of inspection. No deciencies were observed at the time of inspection unless otherwise noted in this report.

Cooktop Energy Source Gas

661 Loran Way Scott Woodburn FOCUS Inspection Authority Page 94 of 139
Cooktop: Video (click here to view on web)

Oven: Oven Manufacture

Kitchenaid

The oven was operated by placing into "Bake" mode, and heat was produced from the element(s) Temperature calibration, "clean" options, and other functions are not tested for. You are recommended to seek further evaluation of additional functions if desired/needed No indications of deciencies were observed at the time of inspection, unless otherwise noted in this report

All cooktop heating elements were turned to "High", and were functional at the time of inspection No deciencies were observed at the time of inspection unless otherwise noted in this report.

Refrigerator: General Photos

Refrigerator: Manufacture

Sub-Zero

Refrigerators are generally not included in a Home Inspection as they are considered transient, "unattached" items They are also not moved to look at the condition of the oor under them, or the cabinetry around them. Therefore their water line and power receptacle are not visible and excluded from this inspection If the refrigerator is a concern, I recommend having it evaluated by an appliance repair company or other qualied person prior to closing. Any observations or comments provided by the inspector on this item is a courtesy

661 Loran Way Scott Woodburn FOCUS Inspection Authority Page 95 of 139

Built-in Microwave: Manufacturer Kitchenaide

NOTE: Inspection is of microwave is minimal, and is tested using normal operating controls only The home Inspector cannot predict the remaining life of the microwave or determine how well the unit will perform. If the inspector has noted a deciency at the time of inspection or the unit is inoperative he will recommend replacing

Video

Deciencies

20 2 1 Kitchen Sink, Faucets, Plumbing CAULKING DEFICIENCY

Observed caulking deciency in noted area. Recommend proper application of caulking to avoid Moisture intrusion into substrate of counter and cabinets

Recommendation

Contact a qualied professional.

20 3 1 Kitchen Cabinets & Countertops COUNTERTOP CRACKED/CHIPPED/DAMAGED

Countertop had one or more cracks or chips and/or notable damage in need of spot repair. Recommend qualied countertop contractor evaluate and repair as needed.

Here is a helpful article on repairing cracks, chips & ssures

20 3 2 Kitchen Cabinets & Countertops CABINET HARDWARE DEFICIENCY

One or more cabinets were missing hardware or was not functioning properly Recommend correction of this component at noted locations.

661 Loran Way Scott Woodburn FOCUS Inspection Authority Page 96 of 139
(click here to view on web) Maintenance Item Maintenance Item Maintenance Item

20 3 3 Kitchen Cabinets & Countertops CABINET THERMOFOIL PEELING

Observed peeling or damage of the thermofoil covering at one more places on the cabinets. Thermofoil should be repaired when peeling occurs to avoid further damage. Thermal foil cabinets can also be refaced if indicated. Thermofoil is sensitive to heat and steam.

20 3 4 Kitchen Cabinets & Countertops GENERAL WARE

General ware and tear are noted in the cabinet and/or countertop components We bring this to your attention for information purposes

Recommendation

Contact a qualied professional.

20.5.1 Dishwasher DOOR HINGE DIFICIENCY

Dish washer door does not open or close properly. Signs of normal wear and tear and requires maintenance or replacement.

20 8 1 Oven OVEN FAN DEFICIENCY

Observed that oven fan does not engage or is noisy when oven is in use. Recommend for the evaluation of this component for proper compliance.

Recommendation

Contact a qualied professional.

661 Loran Way Scott Woodburn FOCUS Inspection Authority Page 97 of 139
Maintenance Item
Maintenance Item Maintenance Item Recommendation

20.9.1 Refrigerator ICE/ WATER DISPENSER DEFICIENCY

Maintenance Item

Observe that refrigerator ice and water dispenser it was nonoperable at time of inspection

20 9 2 Refrigerator DAMAGED COVERING

Noted damage or missing covering of refrigerator face Request disclosure this component Maintenance Item

661 Loran Way Scott Woodburn FOCUS Inspection Authority Page 98 of 139

21: HALLWAYS/TRAFFIC AREAS

21.1 General X 21.2 Doors X

21 3 Windows X

21.4 Floors X

21 5 Walls X

21.6 Ceilings X

21.7 Cabinets & Countertops X

21 8 Lighting Fixtures, Switches & Receptacles X

21.9 Smoke Detectors X X

10 Carbon Monoxide Detectors X X

Elevator X

Information

General: General Overview Photo

Deciencies section-ZmUzNzA2MGEtODM5OS00OTA0LWJlMzUtMzA4YzE3OTZhNTI1

21.9.1 Smoke Detectors NOT FUNCTIONING PROPERLY

Smoke detector found in the noted location is connected, but not functioning properly. Recommend replacement. Safety Hazard

661 Loran Way Scott Woodburn FOCUS Inspection Authority Page 99 of 139
1st Floor
IN NI NP D
21.11
IN = Inspected NI = Not Inspected NP = Not Present D = Deciencies
21

NO CARBON MONOXIDE ALARM

At a minimum, industry experts recommend a CO alarm be installed on each level of the home -- ideally on any level with fuel burning appliances and outside of sleeping areas Additional CO alarms are recommended 5-20 feet from sources of CO such as a furnace, water heater or replace. Alarms can alert you to a problem only after smoke or carbon monoxide reach their sensors. Choose locations free of obstructions, where the alarm will stay clean and protected from adverse environmental conditions Do not place the unit in dead air spaces or next to a window or door Safety

No carbon monoxide alarm found installed in this location. We recommend that CO alarms be placed on every level of your home. It is recommended that CO alarms also be located outside of sleeping areas and common rooms for extra safety

661 Loran Way Scott Woodburn FOCUS Inspection Authority Page 100 of 139
Carbon
21.10.1
Monoxide Detectors
Hazard

22: HOME BAR

section-YjYzNTMzYjUtNzlhZS00Mjg4LThmZWYtNGQ2Y2FiYjE3YTk1

22.1 General X

22.2 Sink, Faucets, Plumbing

22 3 Cabinets & Countertops X

22.4 Refrigerator/Wine Cooler X

22 5 Lighting Fixtures, Switches & Receptacles

22.6 GFCI & AFCI

Information

General: General Overview Photo General: INSP AB

Cabinets & Countertops: Countertop Material Composite

Sink, Faucets, Plumbing: Sink Overview Photo

Cabinets & Countertops: Cabinetry Material Laminate, Wood

Visual inspection was made of the kitchen sink, faucet and plumbing by operating the faucet valves and faucet looking for any leaks or signs of signicant deciencies The supply and drain pipes were inspected looking for leaks, improper installation, and other deciencies Condition was serviceable at time of inspection unless otherwise noted below

Deciencies

661 Loran Way Scott Woodburn FOCUS Inspection Authority Page 101 of 139
IN NI NP D
IN = Inspected NI = Not Inspected NP = Not Present D = Deciencies

22.2.1 Sink, Faucets, Plumbing PREVIOUS PLUMBING LEAK DAMAGE OBSERVED

Recommendation

Observed there was a previous plumbing leak with resulting damage. Moisture meter showed dry material at time of inspection. Recommend getting disclosure on this issue.

22 6 1 GFCI & AFCI INACCESSIBLE

Recommendation

What time of inspection no GFCI it was easily accessible due to storage. Recommend further evaluation and correction if needed. Recommendation

Contact a qualied professional.

661 Loran Way Scott Woodburn FOCUS Inspection Authority Page 102 of 139

23: STEPS/STAIRWAY/RAILINGS

23 3 Ceilings X 23.4 Railings X 23 5 Doors X

23.6 Windows X

23.7 Cabinets & Countertops X

23 8 Floors X

23.9 Lighting Fixtures, Switches & Receptacles X

General: General Overview Photo

661 Loran Way Scott Woodburn FOCUS Inspection Authority Page 103 of 139
IN NI NP D
23.1 General X 23.2 Walls X
IN = Inspected NI = Not Inspected NP = Not Present D = Deciencies
section-NGEyN2I4ODItMTMyNy00ZTM1LWI5MzYtMjZlYTAyMmRjOTQ5
Information

24: BEDROOM 1

Deciencies

24 3 1 Windows

One or more windows appears to have general damage/wear, but are operational. Recommend a window professional clean, lubricate, adjust and/or caulk as necessary

661 Loran Way Scott Woodburn FOCUS Inspection Authority Page 104 of 139
General: General Overview Photo
IN NI NP D 24.1 General X 24.2 Doors X 24 3 Windows X X 24.4 Floors X X 24 5 Walls X X 24.6 Ceilings X X 24.7 Cabinets & Countertops X 24 8 Lighting Fixtures, Switches
Receptacles X 24.9 Smoke Detectors X X 24 10 Carbon Monoxide Detectors X X IN = Inspected NI = Not Inspected NP = Not Present D = Deciencies Information
&
section-YTEwODk0MzMtNDIzZS00MWE1LWExMjItYTg4ZGNmMjYwNzJl
GENERAL WEAR
Maintenance Item

24 3 2 Windows

GENERAL SETTLING CRACK ON SILL

General settling cracks on windowsill. Recommend re-caulking and painting.

Recommendation

Contact a qualied professional

CARPET BUCKLING

Observed carpet buckling in one or more areas in noted locations. There are a number of reasons why carpet may develop ripples or buckles. It may be due to installer error, carpet not being properly acclimated prior to install, excessive moisture in the air, dragging heavy furniture over the carpet, or other reasons. We recommend that the carpet be re-stretched in aected areas using power stretcher to resolve buckled areas Without re-stretching the carpet to proper installation, damage can be caused to buckled areas

661 Loran Way Scott Woodburn FOCUS Inspection Authority Page 105 of 139
Throughout bedroom windows
Maintenance Item
24 4 1 Floors
Maintenance Item

24 5 1 Walls

BASE BOARD/CROWN MOLDING DAMAGE/LOOSE

Observed damage or gaps in baseboard or crown molding at one or more locations Recommend repair or replacement

Smoke detector found in the noted location is connected, but not functioning properly. Recommend replacement.

661 Loran Way Scott Woodburn FOCUS Inspection Authority Page 106 of 139
Maintenance Item
FUNCTIONING PROPERLY
24 9 1 Smoke Detectors NOT
Safety Hazard
10 1 Carbon Monoxide Detectors NO CARBON MONOXIDE ALARM Maintenance Item
24

NOTE, FYI - No carbon monoxide alarm found installed in this location. We recommend that CO alarms be placed on every level of your home and especially outside of sleeping areas (which is usually now required) For extra safety, (although not required), CO alarms may also be in every bedroom, sleeping area and common rooms especially if there is a fossil fuel burning heater, appliance, or replace associated with or close to this space.

At a minimum, industry experts recommend a CO alarm be installed on each level of the home -- ideally on any level with fuel burning appliances and outside of sleeping areas. Additional CO alarms are recommended 5-20 feet from sources of CO such as a furnace, water heater or replace. Alarms can alert you to a problem only after smoke or carbon monoxide reach their sensors. Choose locations free of obstructions, where the alarm will stay clean and protected from adverse environmental conditions Do not place the unit in dead air spaces or next to a window or door.

661 Loran Way Scott Woodburn FOCUS Inspection Authority Page 107 of 139

25: BEDROOM 2

section-ODg4MWEzNjctMjFjNS00YjBkLWI4ZWItZWE1NzBkMDYzYTdk

25.1 General X

25.2 Doors X

25 3 Windows X X

25.4 Floors X

25 5 Walls X

25.6 Ceilings X

25.7 Cabinets & Countertops X

25 8 Lighting Fixtures, Switches & Receptacles X

25.9 Smoke Detectors X X

25 10 Carbon Monoxide Detectors

Information

General: General Overview Photo

Deciencies

25 3 1 Windows GENERAL WEAR

Recommendation

One or more windows appears to have general damage/wear, but are operational. Recommend a window professional clean, lubricate, adjust and/or caulk as necessary

25 9 1 Smoke Detectors

661 Loran Way Scott Woodburn FOCUS Inspection Authority Page 108 of 139
IN NI NP D
IN = Inspected NI = Not Inspected NP = Not Present D = Deciencies
X X
NOT FUNCTIONING PROPERLY Safety Hazard

Smoke detector found in the noted location is connected, but not functioning properly. Recommend replacement.

25 10 1 Carbon Monoxide Detectors NO CARBON MONOXIDE ALARM

NOTE, FYI - No carbon monoxide alarm found installed in this location. We recommend that CO alarms be placed on every level of your home and especially outside of sleeping areas (which is usually now required). For extra safety, (although not required), CO alarms may also be in every bedroom, sleeping area and common rooms especially if there is a fossil fuel burning heater, appliance, or replace associated with or close to this space

At a minimum, industry experts recommend a CO alarm be installed on each level of the home -- ideally on any level with fuel burning appliances and outside of sleeping areas Additional CO alarms are recommended 5-20 feet from sources of CO such as a furnace, water heater or replace Alarms can alert you to a problem only after smoke or carbon monoxide reach their sensors. Choose locations free of obstructions, where the alarm will stay clean and protected from adverse environmental conditions. Do not place the unit in dead air spaces or next to a window or door

661 Loran Way Scott Woodburn FOCUS Inspection Authority Page 109 of 139
Maintenance Item

26: BEDROOM 3

One or more windows appears to have general damage/wear, but are operational. Recommend a window professional clean, lubricate, adjust and/or caulk as necessary

661 Loran Way Scott Woodburn FOCUS Inspection Authority Page 110 of 139
General: General Overview Photo
IN NI NP D
General X 26.2 Doors X 26 3 Windows X X 26.4 Floors X X 26 5 Walls X
Ceilings X 26.7 Cabinets & Countertops X 26 8 Lighting Fixtures, Switches
Receptacles X X 26.9 Smoke Detectors X X 26 10 Carbon Monoxide Detectors X X IN = Inspected NI = Not Inspected NP = Not Present D = Deciencies Information
section-N2RkMjkwZjgtYzNjOS00YWFhLWFjYjItOTg2NmQ3NzljYTRj 26
Windows GENERAL WEAR
26.1
26.6
&
Deciencies
3 1
26 4 1 Floors STAINS/DISCOLORATION Recommendation
Recommendation

Observed some staining or discoloration in ooring material. Recommend a thorough cleaning or further evaluation by qualied professional.

26.8.1 Lighting Fixtures, Switches & Receptacles LIGHT INOPERABLE/NOT LUMINATING

One or more lights are not operating in the following locations. New light bulb possibly needed or new light xture.

Smoke detector found in the noted location is connected, but not functioning properly Recommend replacement

661 Loran Way Scott Woodburn FOCUS Inspection Authority Page 111 of 139
Maintenance Item
NOT
26 9 1 Smoke Detectors
FUNCTIONING PROPERLY
Safety Hazard
NO CARBON MONOXIDE ALARM
26 10 1 Carbon Monoxide Detectors
Maintenance Item

NOTE, FYI - No carbon monoxide alarm found installed in this location. We recommend that CO alarms be placed on every level of your home and especially outside of sleeping areas (which is usually now required) For extra safety, (although not required), CO alarms may also be in every bedroom, sleeping area and common rooms especially if there is a fossil fuel burning heater, appliance, or replace associated with or close to this space.

At a minimum, industry experts recommend a CO alarm be installed on each level of the home -- ideally on any level with fuel burning appliances and outside of sleeping areas. Additional CO alarms are recommended 5-20 feet from sources of CO such as a furnace, water heater or replace. Alarms can alert you to a problem only after smoke or carbon monoxide reach their sensors. Choose locations free of obstructions, where the alarm will stay clean and protected from adverse environmental conditions Do not place the unit in dead air spaces or next to a window or door.

661 Loran Way Scott Woodburn FOCUS Inspection Authority Page 112 of 139

27: BEDROOM 4

Doors X 27 3 Windows X 27.4 Floors X 27 5 Walls X

27.6 Ceilings X

27.7 Cabinets & Countertops X 27 8 Lighting Fixtures, Switches & Receptacles X

Smoke Detectors X

10 Carbon Monoxide Detectors X X

General: General Overview Photo

Deciencies

27.10.1 Carbon Monoxide Detectors NO CARBON MONOXIDE ALARM

NOTE, FYI - No carbon monoxide alarm found installed in this location. We recommend that CO alarms be placed on every level of your home and especially outside of sleeping areas (which is usually now required). For extra safety, (although not required), CO alarms may also be in every bedroom, sleeping area and common rooms especially if there is a fossil fuel burning heater, appliance, or replace associated with or close to this space

At a minimum, industry experts recommend a CO alarm be installed on each level of the home -- ideally on any level with fuel burning appliances and outside of sleeping areas. Additional CO alarms are recommended 5-20 feet from sources of CO such as a furnace, water heater or replace. Alarms can alert you to a problem only after smoke or carbon monoxide reach their sensors Choose locations free of obstructions, where the alarm will stay clean and protected from adverse environmental conditions Do not place the unit in dead air spaces or next to a window or door.

661 Loran Way Scott Woodburn FOCUS Inspection Authority Page 113 of 139
IN NI NP D
27.2
27.1 General X
IN = Inspected NI = Not Inspected NP = Not Present D = Deciencies
27.9
27
Information
section-MTY3NTkxNTItNjhkMC00NWExLThhNmUtMDViZWRmOTc0ZTYw
Maintenance Item

28: OFFICE/LOFT

Deciencies

661 Loran Way Scott Woodburn FOCUS Inspection Authority Page 114 of 139 General: General Overview Photo
IN NI NP D 28.1 General X 28.2 Doors X 28 3 Windows X 28.4 Floors X 28 5 Walls X X 28.6 Ceilings X 28.7 Cabinets & Countertops X
8 Lighting Fixtures, Switches & Receptacles X X 28.9 Smoke Detectors X 28 10 Carbon Monoxide Detectors X X IN = Inspected NI = Not Inspected NP = Not Present D = Deciencies Information
28
section-ZmI3MGQwOTMtMGMyNi00OGFhLThlZWMtYzBhNmFjYTgxOGU5 28 5 1 Walls WALL DAMAGE NEAR FRONT DOOR Maintenance Item

Wall damage at noted areas. Recommend a qualied handyman or drywall contractor repair.

28 8 1 Lighting Fixtures, Switches & Receptacles LIGHT INOPERABLE/NOT LUMINATING

One or more lights are not operating in the following locations. New light bulb possibly needed or new light xture.

28 8 2 Lighting Fixtures, Switches & Receptacles OPEN GROUND

Suspect one or more outlets with open ground indicated. Open ground with three prong receptacle indicates that the receptacle is not connected to an equipment grounding conductor This is unsafe and increases the chance of arching, sparks and electrical re. Recommend immediate attention by a licensed electrician. Safety Hazard

28.10.1 Carbon Monoxide Detectors NO CARBON MONOXIDE ALARM

661 Loran Way Scott Woodburn FOCUS Inspection Authority Page 115 of 139
Maintenance Item
Maintenance
Item

NOTE, FYI - No carbon monoxide alarm found installed in this location. We recommend that CO alarms be placed on every level of your home and especially outside of sleeping areas (which is usually now required) For extra safety, (although not required), CO alarms may also be in every bedroom, sleeping area and common rooms especially if there is a fossil fuel burning heater, appliance, or replace associated with or close to this space.

At a minimum, industry experts recommend a CO alarm be installed on each level of the home -- ideally on any level with fuel burning appliances and outside of sleeping areas. Additional CO alarms are recommended 5-20 feet from sources of CO such as a furnace, water heater or replace Alarms can alert you to a problem only after smoke or carbon monoxide reach their sensors Choose locations free of obstructions, where the alarm will stay clean and protected from adverse environmental conditions. Do not place the unit in dead air spaces or next to a window or door.

661 Loran Way Scott Woodburn FOCUS Inspection Authority Page 116 of 139

29.6

29: BATHROOM 1

661 Loran Way Scott Woodburn FOCUS Inspection Authority Page 117 of 139
Cabinet Type/Style Wood Cabinets
Countertop Type/Style Quartz General: General Overview Photo
Cabinets & Countertops:
& Countertops:
IN NI NP D
General X
X X
Cabinets
X
29.1
29.2 Sink, Faucets, Plumbing
29 3
& Countertops
X
Tub/Shower X X
29.4 Toilet
29 5
Spa/Jacuzzi X
Doors X
8 Windows X
Floors X X 29 10 Ceilings X 29.11 Walls X 29.12 Lighting
X X 29 13 GFCI
AFCI X IN = Inspected NI = Not Inspected NP = Not Present D = Deciencies Information section-YjU4ODg3YmItYTIzMi00YzE2LTg4YjUtMTU0YTY3OWNkYThl
29.7
29
29.9
Fixtures, Switches & Receptacles
&

Sink, Faucets, Plumbing: Sink/Plumbing Overview Photo

Visual inspection was made of the kitchen sink, faucet and plumbing by operating the faucet valves and faucet looking for any leaks or signs of signicant deciencies. The supply and drain pipes were inspected looking for leaks, improper installation, and other deciencies Condition was serviceable at time of inspection unless otherwise noted below.

Deciencies

29 2 1 Sink, Faucets, Plumbing SINK STOPPER DEFICIENCY

Sink stopper was not operational at time of inspection or was showing signs of deciency. Recommend correction.

29 5 1 Tub/Shower MILDEW/CAULKING DEFICIENCY

Observed microbial growth/mildew in noted pictured areas. Mildew/microbial growth usually doesn’t penetrate surfaces but grows on top of at surfaces and can collect in places like grout between your bathroom tiles, or underneath caulking around shower enclosures. While mildew is not as dangerous to your health as certain types of toxic mold, nor is it damaging to your home, mildew should be taken seriously and be removed as quickly as possible in order to prevent adverse aects and cosmetic damage to your home Recommend thoroughly cleaning the noted areas with household cleaner and scrub brush. Replace or reapply caulking or grout as indicated.

661 Loran Way Scott Woodburn FOCUS Inspection Authority Page 118 of 139
Maintenance Item Recommendation

29 5 2 Tub/Shower BUFFING NEEDED

Observed one or more locations where bung of this component may be required for proper nish

Recommendation

Contact a qualied professional

29.9.1 Floors CRACKED FLOOR TILES

Recommendation

Observed one or more cracked, chipped or damaged oor tiles. Recommend replacement or repair.

29 12 1 Lighting Fixtures, Switches & Receptacles LIGHT INOPERABLE/NOT LUMINATING

One or more lights are not operating in the following locations New light bulb possibly needed or new light xture.

661 Loran Way Scott Woodburn FOCUS Inspection Authority Page 119 of 139
Maintenance Item Maintenance Item

30: OFFICE/LOFT - UPSTAIRS

section-ZjMyMTBiNzEtMTU2OS00MTAwLTg3MWUtOGQxNGUxYzAyNTlk

30.1 General X 30.2 Doors X

30 3 Windows X

30.4 Floors X X

30 5 Walls X X

30.6 Ceilings X

30.7 Cabinets & Countertops X

30 8 Lighting Fixtures, Switches & Receptacles X X 30.9 Smoke Detectors X X 30 10 Carbon Monoxide Detectors X

Information

General: General Overview Photo

Deciencies

30.4.1 Floors SOFT SPOTS

Recommendation

Observed one or more areas of ooring that had soft spots or a slight deection with irregular sub oor support resulting in creaking/squeaking. Recommend further evaluation to resecure suboor panels to oor joists

Recommendation

Contact a qualied professional

30 5 1 Walls

661 Loran Way Scott Woodburn FOCUS Inspection Authority Page 120 of 139
IN NI NP D
IN = Inspected NI = Not Inspected NP = Not Present D = Deciencies
MINOR WALL/CORNER CRACKS Maintenance Item

Minor cracks at the corners of doors and windows and walls. Appeared to be the result of settling or separation of material. Some settling is not unusual, not a structural concern

30 8 1 Lighting Fixtures, Switches & Receptacles LIGHT INOPERABLE/NOT LUMINATING

Recommendation

One or more lights are not operating in the following locations New light bulb possibly needed or new light xture.

30 9 1 Smoke Detectors NOT FUNCTIONING PROPERLY

Smoke detector found in the noted location is connected, but not functioning properly Recommend replacement

661 Loran Way Scott Woodburn FOCUS Inspection Authority Page 121 of 139
Safety Hazard

31: BATHROOM 2

31.1 General X

31.2 Sink, Faucets, Plumbing X

31 3 Cabinets & Countertops X

31.4 Toilet X

31 5 Tub/Shower X X

31.6 Spa/Jacuzzi X

31.7 Doors X

31 8 Windows

Floors

31 10 Walls

Ceilings X

31.12 Lighting Fixtures, Switches & Receptacles X X 31 13 GFCI & AFCI X

Cabinets & Countertops: Cabinet

Type/Style

Thermofoil Manufactured Wood, Wood

Cabinets & Countertops: Countertop Type/Style Corian

661 Loran Way Scott Woodburn FOCUS Inspection Authority Page 122 of 139
IN NI NP D
X
X 31.9
X X 31.11
IN
NI =
NP =
D = Deciencies Information
= Inspected
Not Inspected
Not Present
section-YzkyNWVlMTgtZDJkMC00OGJhLTlmMzktMjkwYTJmNTBmNjU3

General: General Overview Photo

Sink, Faucets, Plumbing: Sink/Plumbing Overview Photo

Visual inspection was made of the kitchen sink, faucet and plumbing by operating the faucet valves and faucet looking for any leaks or signs of signicant deciencies. The supply and drain pipes were inspected looking for leaks, improper installation, and other deciencies Condition was serviceable at time of inspection unless otherwise noted below.

Deciencies

31 5 1 Tub/Shower

MILDEW/CAULKING DEFICIENCY

Recommendation

Observed microbial growth/mildew in noted pictured areas Mildew/microbial growth usually doesn’t penetrate surfaces but grows on top of at surfaces and can collect in places like grout between your bathroom tiles, or underneath caulking around shower enclosures. While mildew is not as dangerous to your health as certain types of toxic mold, nor is it damaging to your home, mildew should be taken seriously and be removed as quickly as possible in order to prevent adverse aects and cosmetic damage to your home Recommend thoroughly cleaning the noted areas with household cleaner and scrub brush. Replace or reapply caulking or grout as indicated.

31 5 2 Tub/Shower

TUB DIVERTER DEFICIENCY

Observed tub diverter not functioning properly This should be repaired or replaced

Recommendation

661 Loran Way Scott Woodburn FOCUS Inspection Authority Page 123 of 139

Video (click here to view on web)

31 10 1 Walls WALL DAMAGE

Recommendation

Wall had damage at noted locations Recommend a qualied handyman or drywall contractor repair.

31 12 1 Lighting Fixtures, Switches & Receptacles

COVER PLATES LOOSE/DAMAGED/MISSING

Safety Hazard

One or more receptacles or light switches or electrical wall box have a damaged, loose or missing cover plate Recommend proper cover, repair or replacement

661 Loran Way Scott Woodburn FOCUS Inspection Authority Page 124 of 139

Video

(click here to view on web)

661 Loran Way Scott Woodburn FOCUS Inspection Authority Page 125 of 139

32: BATHROOM 3

32.1 General X

32.2 Sink, Faucets, Plumbing X X

32 3 Cabinets & Countertops X X

32.4 Toilet X

32 5 Tub/Shower X X

32.6 Spa/Jacuzzi X

32.7 Doors X

32 8 Windows X

32.9 Floors X

32 10 Walls X

32.11 Ceilings X

32.12 Lighting Fixtures, Switches & Receptacles X

13 GFCI & AFCI

General: General Overview Photo Cabinets & Countertops: Cabinet Type/Style Laminate, Wood Cabinets & Countertops: Countertop Type/Style Composite

Sink, Faucets, Plumbing: Sink/Plumbing Overview Photo

Visual inspection was made of the kitchen sink, faucet and plumbing by operating the faucet valves and faucet looking for any leaks or signs of signicant deciencies. The supply and drain pipes were inspected looking for leaks, improper installation, and other deciencies Condition was serviceable at time of inspection unless otherwise noted below.

661 Loran Way Scott Woodburn FOCUS Inspection Authority Page 126 of 139
IN NI NP D
32
X IN = Inspected NI = Not Inspected NP = Not Present D = Deciencies Information Deciencies
section-MTA1ZGI2YzctYzZlNi00MzYzLWI5MGYtMTYxMzNhYjk1NDlh

32.3.1 Cabinets & Countertops

BATHROOM CABINET DAMAGED

Bathroom Cabinet Deciency - Repair recommended.

32 5 1 Tub/Shower

GENERAL GROUT/CAULKING DEFICIENCY

Observed grout cracks and or caulking deciencies in one or more areas as noted Recommend reapplication of maintenance grout and or caulking. Maintenance grout and caulk help to prevent moisture intrusion‘s.

32 5 2 Tub/Shower

TUB DIVERTER DEFICIENCY

Observed tub diverter not functioning properly This should be repaired or replaced

Video (click here to view on web)

661 Loran Way Scott Woodburn FOCUS Inspection Authority Page 127 of 139
Recommendation
Maintenance Item
Recommendation

33: 1/2-1/3 BATH

33.1 General X

33.2 Sink, Faucets, Plumbing X X

33 3 Cabinets & Countertops X

33.4 Toilet X

33 5 Doors X

33.6 Windows X

33.7 Floors X

33 8 Walls X

33.9 Ceilings X

33 10 Lighting Fixtures, Switches & Receptacles X 33.11 GFCI & AFCI X

Information

Sink, Faucets, Plumbing: Sink/Plumbing Overview Photo

General: General Overview Photo Cabinets & Countertops: Cabinet Type/Style None Cabinets & Countertops: Countertop Type/Style Porcelain

Visual inspection was made of the kitchen sink, faucet and plumbing by operating the faucet valves and faucet looking for any leaks or signs of signicant deciencies The supply and drain pipes were inspected looking for leaks, improper installation, and other deciencies. Condition was serviceable at time of inspection unless otherwise noted below.

Deciencies section-NjZkNWExYjItZTBiMC00Mzc1LTliNWUtZTQ3NzRkY2NlMGFl

661 Loran Way Scott Woodburn FOCUS Inspection Authority Page 128 of 139
IN NI NP D
IN = Inspected NI = Not Inspected NP = Not Present D = Deciencies

33.8.1 Walls

WALL DAMAGE

Maintenance Item

Wall had damage at noted locations. Recommend a qualied handyman or drywall contractor repair.

661 Loran Way Scott Woodburn FOCUS Inspection Authority Page 129 of 139

34: BATHROOM 4

section-YTg4MjExMTAtMmE1My00M2VkLWI1MzctNzc4YmFmNjkzOTNk

34.1 General X

34.2 Sink, Faucets, Plumbing X

34 3 Cabinets & Countertops X

34.4 Toilet

34 8 Windows X

34.9 Floors X

34 10 Walls X

34.11 Ceilings X

34.12 Lighting Fixtures, Switches & Receptacles X 34 13 GFCI & AFCI X

Cabinets & Countertops: Cabinet Type/Style Laminate, Wood

General: General Overview Photo

General: Storage Limitation

Cabinets & Countertops: Countertop Type/Style Composite

At time of inspection, there’s a limitation for full inspection due to storage. Recommend further evaluation.

661 Loran Way Scott Woodburn FOCUS Inspection Authority Page 130 of 139
IN NI NP D
X
X X
X X
34 5 Tub/Shower
X
34.6 Spa/Jacuzzi X 34.7 Doors X
IN = Inspected NI = Not Inspected NP = Not Present D = Deciencies
Information

34 2 1 Sink, Faucets, Plumbing LOOSE HARDWARE

Observed loose hardware. Recommend correction.

Recommendation

34 4 1 Toilet INOPERABLE

Recommendation

Observe that toilet, tub or shower or not operable at time of inspection

Homeowner has mentioned toilet has been leaking The water was shut o at the time of inspection Recommend further evaluation and correction.

Recommendation

Contact a qualied professional.

34 5 1 Tub/Shower GENERAL GROUT/CAULKING DEFICIENCY

Observed grout cracks and or caulking deciencies in one or more areas as noted Recommend re-application of maintenance grout and or caulking. Maintenance grout and caulk help to prevent moisture intrusion‘s.

34 7 1 Doors DOOR HARDWARE DEFICIENCY

Observed door hardware was loose or not functioning properly. Recommend repair or replacement.

661 Loran Way Scott Woodburn FOCUS Inspection Authority Page 131 of 139 Deciencies
Maintenance Item Maintenance Item

35: THERMAL CAMERA WALKTHROUGH

section-ZDY3OTc2MTktYjNkZC00MDNhLWEzNGYtOTMwOWQ0YjU1OGU5

35.1 General X

35.2 Electrical X

35 3 Roof X

35.4 Plumbing X

35 5 Insulation X

35.6 Interior Walls/Doors/Windows X

General: INSP

General: Thermal Camera General Information

Your inspector performed a gas leak check and limited thermal camera walkthrough inspection upon completion of your home inspection. If a gas leak was detected at any of the gas appliances or main, it will be noted below. Although thermal imaging goes beyond the SOP for a general home inspection, using a visual thermal imaging scan may help your inspector detect small anomalies related to heat, whether they be too hot or too cold, such as:

Plumbing leaks or clogs — Using infrared imaging, inspectors might be able to spot the location of a clog or leak before the homeowner or plumber knocks holes in walls to nd it.

Water damage — The thermal imaging scan should reveal a temperature dierence between wet and dry areas in a home’s walls, ceilings, and oors This is because moisture adds thermal mass to an area, causing it to hold onto heat longer than its drier surroundings. Suspected plumbing leaks, moisture intrusion or water damage will also be veried by a moisture meter to determine accuracy of the scan. A thermal imaging device is not a moisture meter. A thermal imaging camera will detect the heat from excess moisture in an area, but your inspector will conrm those results using a non-penetrating moisture meter

Missing or damaged insulation — Since insulation’s role is to insulate heat in the home, a thermal scan should show any spots where the material is missing or no longer doing its job.

Electrical issues — An infrared scan can help locate hotspots indicating overloaded circuits, old circuit breakers, electrical faults, and overheated electrical equipment

IMPORTANT LIMITATION NOTE: It should be noted that thermal imaging may not reveal all potential anomalies related to the limited thermal scan performed, and DOES NOT allow your inspector to “see through walls ” That’s because even though thermal imaging technology feels like something out of a futuristic sci- movie, it’s important to remember that thermal imaging is not the same as x-ray vision It’s a visual, surface-level inspection that simply translates heat into the visible spectrum Thermal imaging helps us to get an idea of unseen issues; however, the only issues that may show up are ones that relate to heat discrepancies. It should be noted, that a thermal imaging scan isn’t a catch-all and shouldn’t be treated as such.

661 Loran Way Scott Woodburn FOCUS Inspection Authority Page 132 of 139
FYI
RM
- Sample Images
IN NI NP D
IN = Inspected NI = Not Inspected NP = Not Present D = Deciencies Information

General: Thermal Camera Findings

Thermal review: Any deciency or anomaly found during thermal scan at time of inspection will be noted below If no photos are shown then thermal walkthrough showed no deciencies.

661 Loran Way Scott Woodburn FOCUS Inspection Authority Page 133 of 139

36: ENVIRONMENTAL CONCERNS

36.1

Information

General: Odors Present

Discernable Odors

General: General Comments

General: Fungal/Microbial Growth

Microbial Growth Noted Further Evaluation Recommended

Pest/Insect Information: WDO-Termite Inspection Recommended

General: Rodent/Pest/WDO

Due to Age of Structure Further Evaluation Recommended

Inspecting for, and reporting on the presence of WDO activity (wood destroying organisms) including but not limited to; termites, powder post beetles, carpenter ants, carpenter bees, etc is beyond the scope of a home inspection, is excluded by our Standards of Practice, and is excluded from this inspection. It is highly recommended that you have a WDO-Termite inspection prior to the end of your inspection contingency period Any comments made in this report in regards to any such activity was done as a courtesy only, should not be viewed as an all-inclusive listing of activity, and requires further evaluation by a licensed pest control company.

Rodent / Pest Concerns: Rodent/Pest Information

Inspecting for pests, rodents, termites, etc. is outside the scope of a home inspection. A thorough inspection was not performed in order to determine their presence and/or or any damage done by them We are not qualied or licensed pest inspectors, therefore hiring an actual professional pest inspection company is advised. However, as a courtesy, any evidence or damage caused by mice, squirrels, wood destroying organisms, etc. is listed below.

Odors Present: Odors Information

If any odors are noticed in the home I will include them in this section with recommendations made as needed If no additional information is included in this report in respect to odors, then no discernible odors were present or noticed in the home at the time of inspection

Fungal Growth, Microbial Growth/Mold Information: Fungal Growth and Mold Information

In accordance with the standards of practice reporting on the presence of mold is excluded from a home inspection. If I see obvious signs of fungal or microbial growth, I will recommend further evaluation and testing as a courtesy, but these individual references should not be construed as an all-inclusive listing of areas of fungal growth present. Furthermore, the removal of personal belongings or any remodeling or repairs that may take place in the future may reveal fungal growth or mold that was not visible at the time of inspection. If mold is a concern, you are advised to have a mold inspection and indoor air quality testing conducted by a certied mold inspector or industrial hygienist prior to the end of your inspection contingency period.

Please NOTE: We Pair with 3West Environmental in San Clemente, for Mold, Asbestos, Lead and Air Quality Testing. For appointments, they can be reached at 310-400-0195. www.3westenviro.com

Deciencies

Recommendation

GARAGE

661 Loran Way Scott Woodburn FOCUS Inspection Authority Page 134 of 139
IN NI NP D
General X 36.2 Rodent/Pest/WDO Concerns X X IN = Inspected NI = Not Inspected NP = Not Present D = Deciencies
OF MICROBIAL GROWTH OBSERVED
section-OTExZDdlZTgtN2M2NC00NWQ5LWFkNGYtNjg2MWYzYzQ0MWFj 36 2 1 Rodent/Pest/WDO Concerns EVIDENCE

Evidence of microbial or fungal growth (potential mold) observed in the following noted areas. Recommend further evaluation by a qualied professional

Noted area had noticeable indication of potential microbial growth due to previous moisture or leak. At times, these areas are prone to microbial growth. Although our moisture meter showed that the area was dry at time of inspection, we recommend that further evaluation be made and remediation of the aected area be done. Please NOTE: We are NOT able to determine type of mold without taking test swabs for laboratory evaluation. This would provide you with the TYPE of mold or fungus that has been discovered. Therefore, we recommend further evaluation of this area and appropriate corrective measures. We also recommend disclosure of corrections made of the areas of potential moisture intrusion prior to corrective measures to assure that further moisture intrusion is no longer a threat.

Microbial growth testing may help to assist you in further evaluating the extent of potential repairs that may be needed in these areas As noted in our general information, we do oer further mold testing and also pair with 3West Environmental for Mold Testing on extensive cases. We can also oer referrals or recommendations for Mold Remediation Companies as needed. Some areas of noted microbial growth may be candidate for a simple (DIY) local application of of a mold cleaning agent, such as Benefect Botanical Decon 30 or Multipurpose Vinegar We DO NOT recommend Bleach for cleaning mold If you need further information, please let us know.

Recommendation

Contact a qualied mold inspection professional.

661 Loran Way Scott Woodburn FOCUS Inspection Authority Page 135 of 139

37: FINAL CHECK LIST

section-MzY3YzNmN2QtYWMzMS00OGQwLTljNmEtOWZhMWNmMDBhZTVm

37.1 General X

Information

General: Upon Completion

Realtor and Client Last at

Property

661 Loran Way Scott Woodburn FOCUS Inspection Authority Page 136 of 139
IN NI NP D
IN = Inspected NI = Not Inspected NP = Not Present D = Deciencies

38: CLOSING REMARKS

38.1 General X

661 Loran Way Scott Woodburn FOCUS Inspection Authority Page 137 of 139
IN NI NP D
IN = Inspected NI = Not Inspected NP = Not Present D = Deciencies
Information section-NmU2MDVkMmItMzA0Mi00NTZhLWJmNzItZGE0NGViYzliNDgw

General: Closing Remarks

We hope you found the general home inspection process and the inspection report useful and informational regarding the systems of your home. You have hired us to perform a limited visual inspection of the subject property to let you know the current condition of the home and its systems It is important that you understand the results of our ndings. We strongly recommend you read the entire inspection report including the limitations and standards of practice Often home buyers have unrealistic expectations of what the general home inspection process covers, the limitations tab may contain certain systems or components pertaining to the subject property that are outside the scope of this general home inspection (and will not be inspected or commented on) by the inspector These systems or components should be inspected by a qualied licensed professional before the end of your inspection contingency period or the close of escrow to insure they are working as intended.

Be Advised: If Repair/Replace or Recommend Further Evaluation is written in any of the SYSTEMS throughout this Inspection Report it is recommended that you contact a qualied licensed professional contractor and or specialist in that particular area to evaluate this deciency and the identied system to provide repair/replacement options and probable costs prior to the end of your inspection contingency period and or the close of escrow A specialist may nd more defects that are outside the scope of the general home inspector

FOCUS Home Inspection Authority (FHIA) does not provide estimates for repairs for any systems of the building, (FHIA) can not determine what a contractor may charge to repair or replace any SYSTEM or component. There are hundreds of licensed contractors that may give dierent cost estimates, (FHIA) recommends you get several quotes from qualied licensed professional contractors only. Here are a few links to 3rd party repair cost estimators not aliated with FHIA to help assist you with estimated costs for repairs

Click Here For Fixr.com

Click Here For RepairPricer com

We trust the above comments will be of assistance to you If you have any questions regarding our inspection report or the property, or are in need of further clarication on the content of this report, please don't hesitate to contact us.

If you feel that we did a good job in providing you with a valuable service and thorough report, we would greatly appreciate you leaving us a Five Star Review with your kind comments on one of the following review sites: Google, HomeAdvisor or on the Better Business Bureau website at bbb org Below you will nd the immediate links to all three review sites.

Your recommendation is the highest compliment!

"Your Satisfaction Is Our FOCUS."

Thank you so much for your support!

Focus Home Inspection Authority 949-945-0111

FocusInspectionAuthority.com

Click Here For Google Review Link

Click Here For bbb.org Review Link

Click Here For HomeAdvisor Review Link

661 Loran Way Scott Woodburn FOCUS Inspection Authority Page 138 of 139
Certied Master Inspector Certied Professional Inspector

STANDARDS OF PRACTICE

661 Loran Way Scott Woodburn FOCUS Inspection Authority Page 139 of 139 section-sop