Ohanian Residence

Page 1

COORDINATE THE LOCATION OF ALL DIFFUSER, REGISTER, GRILLES WITH THE ARCHITECTURAL PLAN.

7.

ALL SHEET METAL DUCTWORK SHALL BE NEW GALVANIZED SHEET METAL DUCT GAUGES, CONSTRUCTION, SUPPORT, AND INSTALLATION SHALL BE IN ACCORDANCE WITH THE CALIFORNIA MECHANICAL CODE 2010

8.

9.

BALANCE AND ADJUST ALL DIFFUSERS, REGISTERS, ETC. FOR OPTIMUM AIRDISTRIBUTION AND MINIMUM NOISE. SUBMIT A CERTIFIED AIR BALANCE REPORTTO THE MECHANICAL ENGINEER FOR APPROVAL. BALANCING OF THE SYSTEMS SHALL BE PERFORMED BY AN INDEPENDENT CERTIFIED TEST AND BALANCING AGENCY WHIC SPECIALIZES IN THE BALANCING AND TESTING OF HEATING, VENTILATING ANDAIR CONDITIONING SYSTEMS.

HP

VOLT

PH

HZ

OPER. WEIGHT

1/2

208

1

60

170

CARRIER 58MVB-060-14

LOWER FLOOR

FAU 2

CARRIER 58MVB-060-14

MASTER BEDROOM

FAU 3

CARRIER 58MVB-080-20

MASTER BED, BEDROOM 4

1600

0.5

46.5

75

1

208

1

60

FAU 4

CARRIER 58MVB-080-20

KITCHEN, FAMILY ROOM

2000

0.5

56

75

1

208

1

60

FAU 5

CARRIER 58MVB-080-20

2ND FLR MAIN

1200 1200

2000

0.5 0.5

0.5

35

57

35

56

56

75

1/2

1

208

1

208

1

60

60

11. CEILING DIFFUSERS SHALL BE ANEMOSTAT RMD-S OR APPROVED EQUAL MODULAR WIH OBD.

UNIT

REMARKS

MANUFACTURER AMB. TEMP AND MODEL

COMPRESSOR NO

RLA

COND. COIL FACE ROW FPI (SQ.FT)

FAN MOTOR

COND. FAN

MCA NO.

RPM

FLA

HP

VOLT

PH

HZ

MOCP

OPER. WEIGHT

CU 1

CARRIER 24ANA136

95

1

16.7

22.63

25

1

1

800

1.2

1/12

208

1

60

22

35

191

16X25X3/4

CU 2

CARRIER 24ANA136

95

1

16.7

22.63

25

1

1

800

1.2

1/12

208

1

60

22

35

191

204

20X25X3/4

CU 3

CARRIER 24ANA148

95

1

21.8

25.15

25

1

1

800

1.2

1/4

208

1

60

28.4

40

231

204

20X25X3/4

PRIVDE CONDENSING PUMP

CU 4

CARRIER 24ANA160

95

1

26.4

25.15

20

2

1

800

1.2

1/4

208

1

60

34.2

50

272

20X25X3/4

PRIVDE CONDENSING PUMP

CU 5

CARRIER 24ANA160

170

204

16X25X3/4

PRIVDE CONDENSING PUMP

95

1

26.4

25.15

20

2

1

800

1.2

1/4

208

1

60

34.8

50

S

TEMPERATURE SENSOR

T

THERMOSTAT

REMARKS

UNIT

SERVICE

TYPE

CFM

ESP IN (WG)

FAN RPM

CAPACITY

CD

CEILING DIFFUSER

SECTION THRU RECTANGULAR SUPPLY DUCT

CFM

CUBIC FEET PER MINUTE

SECTION THRU RECTANGULAR RETURN DUCT

CG

CEILING GRILLE

CHS

CHILLED WATER SUPPLY

CHR

CHILLED WATER RETURN

CONC

CONCRETE

COND

CONDENSATE

DUCT DROP IN DIRECTION OF FLOW

CONN

CONNECTION

CEILING DIFFUSER W/DIRECTION OF THROW INDICATED, (3-WAY BLOW SHOWN)

CONT

CONTINUATION

CR

CEILING REGISTER

D

DRAIN

DB

DRY BULB

DL

DOOR LOUVER

STATIC PRESSURE DAMPER COMBINATION FIRE/SMOKE DAMPER

DN

DOWN

DTR

DOWN THRU ROOF

FLEXIBLE CONNECTION, (F.C.)

272

DUCT RISE IN DIRECTION OF FLOW

MOTOR VOLT

PH

HZ

BACKDRAFT DAMPER, (BDD)

REMARKS

EF 1

POWDER ROOMS AND BATHROOMS

LOREN COOK GC-162

CEILING

100

0.25

1,200

103

120

1

60

15

PROVIDE BACKDRAFT DAMPER

SOUND LINED (SL)DUCT W/INTERNAL INSULATION DUCT SIZES SHOWN ARE NET INSIDE DIMENSION.

EA

EXHAUST AIR

(E)

EXISTING

EF 2

MASTER BATHROOM

LOREN COOK GC-182

CEILING

200

0.25

1,400

185

120

1

60

16

PROVIDE BACKDRAFT DAMPER

SOUND TRAP (ST)

ENT

ENTERING

TURNING VANES

EXH

EXHAUST

F.A.

FACE AREA

F

FAHRENHEIT

FLA

FULL LOAD AMPS

FPI

FINS PER INCH

SINGLE LINE RIGID SHEET METAL DUCTWORK

FPM

FEET PER MINUTE

M

FURNISHED & INSTALLED BY MECH. CONTRACTOR

FLEX

FLEXIBLE

GALV.

GALVANIZED

E

FURNNISHED & INSTALLED BY ELECT. CONTRACTOR

GA

GAUGE

HWS

HOT WATER SUPPLY

12. SIDEWALL SUPPLY REGISTERS SHALL BE DOUBLE DEFLECTION GRILLE WITH OPOSED BLADE DAMPER ATTACHED, TWO SETS OF INDIVIDUALLY ADJUSTABLE LOUVER, ANEMOSTAT S2HO

FLEXIBLE DUCT TO CEILING DIFFUSER OR REGISTER

13. EXHAUST AIR AND RETURN AIR REGISTERS SHALL BE ANEMOSTAT S3HOD, HORIZONTAL FACE BARS SET AN ANGLE OF 45-DEGREES WITH OBD AND FLEXIBLE DUCT ADAPTOR. 14. FLEXIBLE CONNECTION SHALL BE PROVIDED FOR ALL DUCT WORK ATTACHED TO AIR MOVING EQUIPMENT MOUNTED ON OR SUSPENDED FROM VIBRATION ISOLATIONS. FLEXIBLE CONNECTIONS SHALL BE CODE APPROVED NEOPRENE COATED GLASS TYPE FABRIC. 15. THE ELECTRICAL AND PLUMBING CONTRACTORS SHALL PROVIDE FLEXIBLE CONNECTIONS AT ALL MECHANICAL EQUIPMENT MOUNTED ON VIBRATION ISOLATORS AND OR SUSPENDED FROM VIBRATION HANGER.

BELOW

CAP

MODULATING DAMPER, (MOD)

HP (WATTS)

BEL

BRITISH THERMAL UNIT

AUTOMATIC FIRE DAMPER, (AFD)

WEIGHT (LBS)

ABOVE

BTU

SECTION THRU RECTANGULAR EXHAUST DUCT

EXHAUST FAN SCHEDULE MANUFACTURER AND MODEL

ABV

RECTANGULAR DUCT W/SIZE OF SIDE SHOWN INDICATED FIRST

MANUAL VOLUME DAMPER, (MVD)

AS-BUILT RECORD PRINTS MUST BE PROVIDED PRIOR TO JOB COMPLETION.

10. PROVIDE ALL TRANSITIONS AS REQUIRED FROM MAIN DUCT OR BRANCHES TO DIFFUSERS, REGISTERS, OR GRILLES. PROVIDE MVD FOR EACH BRANCH.

FILTER

ME

FURNISHED & INSTALLED BY MECH. CONTRACTOR, WIRED BY ELECT. CONTRACTOR

HWR

HOT WATER RETURN

EM

FURNISHED BY ELECT. CONTRACTOR, INSTALLED BY MECH. CONTRACTOR WIRED BY ELECT. CONTRACTOR

HP

HORSEPOWER

IN

INCH

ISOL

ISOLATOR

LBS

POUNDS

LVG

LEAVING

EMS

ENERGY MANAGEMENT SYSTEM

21. CONTRACTOR TO THOROUGHLY CLEAN ALL PORTIONS OF THEIR WORK, REMOVE ALL DEBRIS AND LEAVE INSTALLATION IN PERFECT CONDITION READY FOR USE.

M.A.

MIXED AIR

MAX

MAXIMUM

22. CONDENSER REFRIGERANT PIPING IN THE STRUCTURE SHALL BE INSTALLED SO AS NOT TOUCH STRUCTURE, FRAMING, OR WALL SURFACES. INSTALL FOAM RUBBER CUSHIONS AT PENETRATIONS TO SEPERATE PIPING FROM STRUCTURE.

MBH

1000 BTU'S PER HOUR

MIN

MINIMUM

MOD

MODULATING DAMPER

23. DUCT INSTALLATION: FOR THERMAL INSULATION, INSULATE ALL SUPPLY AND RETURN AIR DUCT WORK AND PLENUM WITH 2" THICK FIBERGLASS INSULATION WRAPPED AROUND WITH 2" OVERLAP AND WIRED ON #18 GALVANIZED WIRE @ 12" O.C. NRC RATING SHALL BE AT LEAST .80 AT FREQUENCIES ABOVE 1000. ALL DUCTS SHALL HAVE JOINTS AND SEAMS SEALED. FOR SOUND INSULLATION, INSULATE INTERIOR OF SUPPLY AND RETURN AIR PLENUMS WITH MIN. 1" THICK SOUND INTERIOR OF SUPPLY AND RETURN AIR PLENUMS WITH MIN. 1" THICK SOUND ABSORBING INSULATION TO REDUCE NOISE. INSTALL SOUND STRAPS IN PLENUM AND INSULATE BLOWER COMPARTMENT WHERE RETURN AIR REGISTERS ARE IN CLOSE PROXIMITY TO UNITS.

MVD

MANUAL VOLUME DAMPER

NTS

NOT TO SCALE

OPER. WT. OPERATING WEIGHT

24. LABEL ALL EQUIPMENT (AC) TO INDICATE THE SPACE NAME THAT IT IS SERVING.

16. ALL AIR CONDINTIONING FILTERS SHALL BE REPLACED PRIOR ON DAY OF BALANCING. 17. ALL EQUIPMENT TO BE INSTALLED IN ACCORDANCE WITH THE MANUFACTURER'S INSTRUCTION 18. AFFIX MAINTENANCE LABELS TO MECHANICAL EQUIPMENT AND PROVIDE THE OWNER WITH MAINTENANCE AND PARTS MANUALS., LABEL ALL EQUIPMENT WITH THE NAME OF SPACE IT SERVES.

CC

CLOSING COIL IN MAGNETIC STARTER

19. SEAL ALL DUCT JOINTS WITH AN APPROVED TYPE MASTIC.

SW

SWITCH

20. ALL DUCTS PENETRATING THE ROOF SHALL HAVE APPROVED FLASHING AND COUNTER-FLASHING AND BE WEATHER PROOFED.

25. DUCT SYSTEM SHOWN ON THE PLANS ARE SIZED IN ACCORDANCE WITH ASHRAE EQUAL FRICTION METHOD (CHAPTER 35,2005 ASHRAE HANDBOOK). 26. DUCT MATERIAL AND GAGES, PER THE FOLLOWING TABLES: i. TABLE 6-6A & 6-6B DUCT INSTALLATION ii. TABLE 6-7 DUCT SUPPORT a. VERTICAL DUCTS b. HORIZONTAL DUCTS c. HORIZONTAL-DUCTS-TRAPEZE-TYPE SUPPORTS iii. TABLE 6-8 CONSTRUCTION DETAILS FOR ROUND & FLAT-OVAL DTUCTS (LOW, MED, & HI PRESSURE)

SD

SMOKE DETECTOR

OPG

OPENING

OSA

OUTSIDE AIR

PD

PRESSURE DROP

PH

PHASE

PRESS

PRESSURE

POC

POINT OF CONNECTION

PSI

POUNDS PER SQUARE INCH

RA

RETURN AIR

RAR

RETURN AIR REGISTER

REQ'D

REQUIRED

RL

REFRIGERATION LIQUID LINE

RLA

RATED LOAD AMPS

RPM

REVOLUTIONS PER MINUTE

RS

REFRIGERATION SUCTION LINE

CONSULTING ENGINEERS 336 NORTH CENTRAL AVE SUITE 10B GLENDALE, CA 91203 TEL: (818) 507-7522

6.

FAN MOTOR

ROUND DUCT SA

SUPPLY AIR

SP

STATIC PRESSURE

SF

SQUARE FEET

SWR

SIDEWALL REGISTER

SL

SOUND LINED

TEMP

TEMPERATURE

T'STAT

THERMOSTAT

TYP

TYPICAL

UTR

UP THRU ROOF

V

VOLT

W/

WITH

WB

WET BULB

W.G.

WATER GAUGE

(E)

EXISTING

(N)

NEW

Date

4/12/2013

Scale

AS NOTED

Drawn

PP

Job

7068

5253 HORIZON DRIVE MALIBU, CA

COORDINATE THE SIZE, LOCATION, @ SERVICE REQUIREMENTS OF ALL MECHANICAL EQUIPMENT & DUCTWORK WITH THE GENERAL, PLUMBING, ELEC.CONTROL, & FIRE PROTECTION CONTRACTOR PRIOR TO THE START OF CONSTRUCTION. REPORT ALL UNRESOLVED CONFLICTS TO THE ARCHITECT.

COOLING HEATING ESP. (IN WG.) CAPACITY CAPACITY (MBH) (MBH)

CREATIVE DESIGN

5.

THE MECHANICAL CONTRACTOR SHALL OBTAIN & PAY FOR ALL PERMITS, LICENSES & INSPECTIONS REQUIRED TO COMPLETE THIS JOB.

CFM

OHANIAN RESIDENCE

4.

THE MECHANICAL CONTRACTOR SHALL GUARANTEE ALL EQUIPMENT, APPARATUS, ACCESSORIES (I.E., THE ENTIRE INSTALLATION) AS FURNISHED BY HIM FOR A PERIOD OF ONE YEAR.

FAU 1

SERVICE

NOT FOR CONSTRUCTION USE

3.

THE INSTALLATION SHALL COMPLY WITH & BE INSTALLED IN ACCORDANCE WITH ALL LEGALLY CONSTITUTED AUTHORITIES & CODES HAVING JURISDICTION. ALSO ALL THE REQUIREMENTS OF LANDLORD.

MANUFACTURER AND MODEL

UNIT

JOB TITLE

2.

THE MECHANICAL CONTRACTOR SHALL FURNISH ALL MATERIAL, LABOR, EQUIPMENT APPURTENANCES, AND ALL CONTRACTUAL EXPENSES REQUIRED FOR THE COMPLETE INSTALLATION OF THE MECHANICAL SYSTEM TO THE SATISFACTION OF THE OWNER, ARCHITECT, AND MECHANICAL ENGINEER.

OUTDOOR UNIT

INDOOR UNIT

LEGENDS, NOTES, AND SCHEDULES

1.

LEGEND & ABBREVIATIONS

SHEET TITLE

HVAC GENERAL NOTES

SPLIT SYSTEM COOLING UNIT SCHEDULE

Sheet