EXHAUST FAN SCHEDULE

SHEET INDEX MOTOR

MANUFACTURER AND MODEL

TYPE

CFM

ESP IN (WG)

FAN RPM

HP (WATTS)

VOLT

PH

HZ

WEIGHT (LBS)

ANCHOR. DETAIL

REMARKS

SHEET TITLE

M-001

LEGENDS, NOTES, AND SCHEDULES

EF 1

TOILET 159

LOREN COOK GC-160

CEILING

140

0.25

1,500

113

120

1

60

15

-

-

PROVIDE BACKDRAFT DAMPER

M-110

MECHANICAL FIRST FLOOR PLAN

EF 2

TOILET 207

LOREN COOK GC-160

CEILING

140

0.25

1,500

113

120

1

60

15

-

-

PROVIDE BACKDRAFT DAMPER

M-111

MECHANICAL SECOND FLOOR PLAN

EF 3

JANITOR 209

LOREN COOK GC-180

CEILING

200

0.25

1,500

192

120

1

60

16

-

-

EF 4

TOILETS 106, 108, 109

LOREN COOK 80C2B

ROOF VENTILATOR

400

0.5

1,260

1/6

120

1

60

30

12 M-500

EF 5

TOILETS 136, 137

LOREN COOK 80C2B

ROOF VENTILATOR

300

0.5

1,239

1/6

120

1

60

30

EF 6

MEN'S RESTROOM 133

LOREN COOK 120C2B

ROOF VENTILATOR

750

0.5

1,151

1/6

120

1

60

EF 7

WOMEN'S 134, 212 AND MEN'S RESTROOMS 211

LOREN COOK 180C3B

ROOF VENTILATOR

1,600

0.5

742

1/4

120

1

60

S

ON-OFF SWITCH

T

THERMOSTAT

ABV ABOVE BEL BELOW BTU BRITISH THERMAL UNIT CAP CAPACITY CD CEILING DIFFUSER CFM CUBIC FEET PER MINUTE CG CEILING GRILLE CONC CONCRETE COND CONDENSATE CONN CONNECTION CONT CONTINUATION CR CEILING REGISTER D DRAIN DB DRY BULB DL DOOR LOUVER DN DOWN DTR DOWN TRHU ROOF EA EXHAUST AIR (E) EXISTING ENT ENTERING F.A. FACE AREA F FARENHEIT FLA FULL LOAD AMPS FPI FINS PER INCH FPM FEET PER MINUTE FLEX FLEXIBLE GALV GALVANIZED GA GAUGE HP HORSEPOWER IN INCH ISOL ISOLATOR LBS POUNDS LVG LEAVING EMS ENERGY MANAGEMENT SYSTEM M.A. MIXED AIR MAX MAXIMUM MBH 1000 BTU'S PER HOUR (N) NEW MIN MINIMUM MOD MODULATING DAMPER MVD MANUAL VOLUME DAMPER NTS NOT TO SCALE OPER. WT. OPERATING WEIGHT OPG OPENING OSA OUTSIDE AIR PD PRESSURE DROP PH PHASE PRESS PRESSURE POC POINT OF CONNECTION PSI POUNDS PER SQUARE INCH RA RETURN AIR RAR RETURN AIR REGISTER REQ'D REQUIRED RLA RATED LOAD AMPS RPM REVOLUTIONS PER MINUTE Ø ROUND DUCT SA SUPPLY AIR SP STATIC PRESSURE SF SQUARE FEET SWR SIDEWALL REGISTER SL SOUND LINED TEMP TEMPERATURE T'STAT THERMOSTAT TYP TYPICAL UTR UP THRU ROOF V VOLT VTR VENT THRU ROOF W/ WITH WB WET BULB W.G. WATER GAUGE

SECTION THRU RECTANGULAR SUPPLY DUCT SECTION THRU RECTANGULAR RETURN DUCT SECTION THRU RECTANGULAR EXHAUST DUCT

PROVIDE BACKDRAFT DAMPER

M-130

MECHANICAL ROOF PLAN

10"

PROVIDE BACKDRAFT DAMPER AND MANUFACTURER ROOF CURB

M-310

BUILDING SECTIONS

12 M-500

10"

PROVIDE BACKDRAFT DAMPER AND MANUFACTURER ROOF CURB

M-500

DETAILS

55

12 M-500

10"

PROVIDE BACKDRAFT DAMPER AND MANUFACTURER ROOF CURB

M-510

VIBRATION ISOLATOR DETAILS

90

12 M-500

18"

PROVIDE BACKDRAFT DAMPER AND MANUFACTURER ROOF CURB

M-511

VIBRATION ISOLATOR DETAILS

M-520

EMS DIAGRAMS

FLEXIBLE CONNECTION R

SERVICE

SHEET NUMBER

DUCT RISE IN DIRECTION OF FLOW

D

UNIT

FAN WHEEL DIA. IN (MIN)

MECHANICAL LEGENDS & ABBREVIATIONS

DUCT DROP IN DIRECTION OF FLOW MANUAL VOLUME DAMPER (MVD) AUTOMACTIC FIRE DAMPER (AFD) MODULATING DAMPER (MOD) BACKDRAFT DAMPER (BDD) STATIC PRESSURE DAMPER

SOUND TRAP SCHEDULE DESIGNATION ST 1-1

MFG MODEL

UNIT SIZE (INCHES)

P.D. (IN. W.G.)

125

250

500

1000

2000

4000

8000

VEL. FPM

PRICE RLX60/2F

18x14

0.23

14

28

42

48

48

37

21

914

1,600

PRICE RMX60/4G

26X12

0.15

16

31

43

51

45

27

13

738

5

112

ON RETURN AIR DUCTWORK

CFM

ST 2-1

DECIBELS

1,600

LENGTH (FT)

OPER. WT. (LBS)

ST 2-2

ST 3-1

ST 4-1

ST 5-1

2,400

PRICE RMX60/4G

28x14

0.22

13

27

40

47

45

28

15

882

5

124

ON SUPPLY AIR DUCTWORK

ST 3-2

ST 4-2

ST 5-2

1,680

PRICE RMX60/1F

36X12

0.17

14

25

42

51

50

34

21

800

5

162

ON RETURN AIR DUCTWORK

3,000

PRICE RLX60/1F

36X14

0.35

14

32

45

50

51

46

26

857

5

176

ON RETURN AIR DUCTWORK

6,000

PRICE RLX60/1F

40X20

PRICE RLX60/1F

48X16

ST 9-1

ST 10-1

ST 9-2

6,000 ST 10-2

4,065

ST 10-3

1,875

PRICE RLX60/1F

36X18

PRICE RMX60/4G

24X16

0.79

11

0.79

14

1.5

14

1.5

13

26

33

32

27

41

45

46

51

51

45

51

50

40

51

47

45

48

45

46

28

30

5

1,260

25

26

ENERGY COMPLIANCE FORMS

SD SMOKE DETECTOR

M-531

ENERGY COMPLIANCE FORMS

BD

BYPASS DAMPER

SOUND LINED (SL) DUCT W/ INTERNAL INSULATION. DUCT SIZES SHOWN ARE NET INSIDE DIMENSION

MEP COMPONENT ANCHORAGE NOTE: ALL MECHANICAL, PLUMBING, AND ELECTRICAL COMPONENTS SHALL BE ANCHORED AND INSTALLED PER THE DETAILS ON THE DSA APPROVED CONSTRUCTION DOCUMENTS. WHERE NO DETAIL IS INDICATED, THE FOLLOWING COMPONENTS SHALL BE ANCHORED OR BRACED TO MEET THE FORCE AND DISPLACEMENT REQUIREMENTS PRESCRIBED IN THE 2010 CBC, SECTIONS 1615A.1.12 THROUGH 1615A.1.22 AND ASCE 7-05 CHAPTER 6 AND 13. 1. ALL PERMANENT EQUIPMENT AND COMPONENTS. 2. TEMPORARY OR MOVABLE EQUIPMENT THAT IS PERMANENTLY ATTACHED (E.G HARD WIRED) TO THE BUILDING UTILITY SERVICES SUCH AS ELECTRICITY, GAS, OR WATER. 3. MOVABLE EQUIPMENT WHICH IS STATIONED IN ONE PLACE FOR MORE THAN 8 HOURS AND HEAVIER THAN 400 POUNDS ARE REQUIRED TO BE ANCHORED WITH TEMPORARY ATTACHMENTS.

FLEXIBLE DUCT TO CEILING DIFFUSER OR REGISTER

THE ATTACHMENT OF THE FOLLOWING MECHANICAL AND ELECTRICAL COMPONENTS SHALL BE POSITIVELY ATTACHED TO THE STRUCTURE, BUT NEED NOT BE DETAILED ON THE PLANS. THE PROJECT INSPECTOR WILL VERIFY THAT THESE ITEMS HAVE BEEN POSITIVELY ATTACHED. THESE COMPONENTS SHALL HAVE FLEXIBLE CONNECTIONS PROVIDED BETWEEN THE COMPONENT AND ASSOCIATED DUCTWORK, PIPING, AND CONDUIT.

ON RETURN AIR DUCTWORK

124

COMBINATION FIRE/SMOKE DAMPER

SOUND TRAP

ON RETURN AIR DUCTWORK

162

5

738

M-530

ON SUPPLY AIR DUCTWORK

213

5

857

15

213

5

1,125

M

ON SUPPLY AIR DUCTWORK

ST 1-2

ST 6-1

EMS DIAGRAMS

REMARKS

110

5

M-521

ON RETURN AIR DUCTWORK

SINGLE LINE RIGID SHEET METAL DUCTWORK

A. COMPONENTS WEIGHTING LESS THAN 400 POUNDS AND HAVE A CENTER OF MASS LOCATED 4 FEET OR LESS ABOVE THE ADJACENT FLOOR OR ROOF LEVEL THAT DIRECTLY SUPPORT THE COMPONENT. B. COMPONENTS WEIGHTING LESS THAN 20 POUNDS, OR INTHE CASE OF DISTRIBUTED SYSTEMS LESS THAN 5 POUNDS PER FOOT, WHICH ARE SUSPENDED FROM A ROOF OR FLOOR OR HUNG FROM A WALL.

NOTES: PROVIDE DUCT TRANSITION FROM SOUND TRAPS TO RELATED DUCTWORK AS NEEDED

FOR THOSE ELEMENTS THAT DO NOT REQUIRE DETAILS ON THE APPORVED DRAWINGS, THE INSTALLATION SHALL BE SUBJECT TO THE APPROVAL OF THE STRUCTURAL ENGINEER OF RECORD AND THE DSA DISTRICT STRUCTURAL ENGINEER

PIPING, DUCTWORK, AND ELECTRICAL DISTRIBUTION SYSTEM BRACING NOTE

M

FURNISHED & INSTALLED BY MECHANICAL CONTRACTOR

E

FURNISHED & INSTALLED BY ELECTRICAL CONTRACTOR

ME

FURNISHED & INSTALLED BY MECHANICAL CONTRACTOR, WIRED BY ELECTRICAL CONTRACTOR

EM

FURNISHED BY ELECTRICAL CONTRACTOR, INSTALLED BY MECHANICAL CONTRACTOR, WIRED BY ELECTRICAL CONTRACTOR

CC

CLOSING COIL IN MAGNETIC STARTER

SW

SWITCH

CSDA Architects, Inc. 4061 Glencoe Ave, Suite B Marina del Rey, CA 90292 design@csdarchitects.com T:310.821.9200 F:310.821.9201

ARCHITECT STAMP

CONSULTANT

CREATIVE DESIGN

CONSULTING ENGINEERS 336 NORTH CENTRAL AVE SUITE 10B GLENDALE, CA 91203 TEL: (818) 507-7522

CONSULTANT STAMP

NOT FOR CONSTRUCTION USE

AUTHORITY APPROVAL IDENTIFICATION STAMP DIVISION OF THE STATE ARCHITECT

04-112249

PIPING, DUCTWORK, AND ELECTRICAL DISTRIBUTION SYSTEMS SHALL BE BRACED TO COMPLY WITH THE FORCES AND DISPLACEMENTS PRESCRIBED IN ASCE 7-05 SECTION 13.3 AS DEFINED IN ASCE 7-05 SECTION 13.6.8, 13.6.7, 13.6.5.6, AND 2010 CBC, SECTIONS 1615A.1.20, 1615A.1.21 AND 1615A.1.22. THE BRACING AND ATTACHMENTS TO THE STRUCTURE SHALL COMPLY WITH ONE OF THE OSHPD PREAPPROVALS WITH AN OPA #, AS MODIFIED TO SATISFY ANCHORAGE REQUIREMENTS OF ACI 318, APPENDIX D.

FLS

AC DATE

ZONE

SS

AC NUMBER ZONE NUMBER

Z1-1 1000

ZONE CFM

COPIES OF THE MANUAL SHALL BE AVAILABLE ON THE JOBSITE PRIOR TO THE START OF HANGING AND BRACING OF THE PIPE, DUCTWORK, AND ELECTRICAL DISTRIBUTION SYSTEMS.

BYPASS DAMPER

THE STRUCTURAL ENGINEER OF RECORD SHALL VERIFY THE ADEQUACY OF THE STRUCTURE TO SUPPORT THE HANGER AND BRACE LOADS.

BD-1 1000

AC NUMBER

SCHOOL DISTRICT:

DAMPER CFM

VICTOR VALLEY UNION HIGH SCHOOL DISTRICT 16350 MOJAVE DRIVE VICTORVILLE, CA 92395 SCHOOL ADDRESS:

VICTOR VALLEY HIGH SCHOOL - NEW ADMINISTRATION & LIBRARY BUILDING

SPLIT SYSTEM COOLING UNIT SCHEDULE INDOOR UNIT COOLING CAPACITY (MBH)

SEER

290

12

15.2

1

0.33

208

1

ELECTRICAL ROOM 107

570

24

17

1

0.36

208

ELECTRICAL ROOM 124

635

34.2

14

1

0.57

208

MANUFACTURER AND MODEL

SERVICE

FC 1

MITSUBISHI PKA-A12HA4

ELECTRICAL ROOM 155

FC 2

MITSUBISHI PKA-A24KA4

FC 3

MITSUBISHI PKA-A36KA4

UNIT

OUTDOOR UNIT

CFM

MCA

FLA

V

OPER. WEIGHT

ANCHOR. DETAIL

60

29

2 M-511

1

1

60

46

2 M-511

1

60

46

2 M-511

PH

HZ

OPER. WEIGHT

ANCHOR. DETAIL

60

82

1 M-511

1

60

165

1 M-511

1

60

165

1 M-511

MANUFACTURER AND MODEL

MCA

CU 1

MITSUBISHI PKY-A12NHA4

13

15

208

1

1

CU 2

MITSUBISHI PKA-A24NHA4

18

30

208

1

CU 3

MITSUBISHI PKA-A36NHA4

25

40

208

REMARKS

UNIT

MOCP

V

PH

HZ

REMARKS

16500 MOJAVE DRIVE VICTORVILLE, CA 92395 KEY PLAN

NOTES: 1

PROVIDE WITH CONDENSING PUMP

PACKAGED AIR CONDITIONING UNIT SCHEDULE COOLING CAP UNIT

MANUFACTURER

SERVICE AREA

MODEL

CFM

HEATING CAPACITY

ESP IN (WG) TOTAL

SENSIBLE

EWB TEMP. ºF

ENT COND TEMP ºF

SEER

INDOOR FAN

CONDENSER COIL

EVAPORATOR COIL

OUTDOOR FAN

EER INPUT MBH OUT MBH

ROWS

FPI

FACE AREA

ROWS

FPI

FACE AREA

NO.

SIZE

RPM

BHP

NO.

SIZE

RPM

BHP

COMP NO.1 RLA

COMP NO.2 RLA

OFM (FLA) IFM (FLA) EACH EACH

FILTERS (INCHES)

V

PHASE

HZ

MCA

MOCP

OPER. WEIGHT INCLUD. CURB

ACCESSORIES INTEGRATED

REMARKS

ANCHORAGE

AC 1

CARRIER

CORRIDOR 217

48HCFD05

1,600

1.0

47.7

37

67º

105º

15.6

13

120

96

3

15

7.3

2

17

23.1

1

10X10

1,208

2.9

1

22"DIAM.

1,100

1/4

6.2

-

0.9

2.7

460

3

60

10.8

15

(4)16X20X2 (1)20X36X1

910

1

2

3

4

5

6

7

1 M-510

AC 2

CARRIER

TEXTBOOK 213

48HCFD05

1,600

1.0

47.7

37

67º

105º

15.6

13

120

96

3

15

7.3

2

17

23.1

1

10X10

1,208

2.9

1

22"DIAM.

1,100

1/4

6.2

-

0.9

2.7

460

3

60

10.8

15

(4)16X20X2 (1)20X36X1

910

1

2

3

4

5

6

7

1 M-510

AC 3

CARRIER

CLASSROOM 214

48HCFD07

2,400

1.0

71.2

55.3

67º

105º

-

12

150

120

3

15

8.9

2

17

20.5

1

15X15

949

2.9

2

22"DIAM.

1,100

1/4

9.7

9.7

0.8

3.4

460

3

60

13.1

15

(4)16X20X2 (1)20X36X1

1,275

1

2

3

4

5

6

7

2 M-510

AC 4

CARRIER

CLASSROOM 215

48HCFD07

2,400

1.0

71.2

55.3

67º

105º

-

12

150

120

3

15

8.9

2

17

20.5

1

15X15

949

2.9

2

22"DIAM.

1,100

1/4

9.7

9.7

0.8

3.4

460

3

60

13.1

15

(4)16X20X2 (1)20X36X1

1,275

1

2

3

4

5

6

7

2 M-510

AC 5

CARRIER

CLASSROOM 216

48HCFD07

2,400

1.0

71.2

55.3

67º

105º

-

12

150

120

3

15

8.9

2

17

20.5

1

15X15

949

2.9

2

22"DIAM.

1,100

1/4

9.7

9.7

0.8

3.4

460

3

60

13.1

15

(4)16X20X2 (1)20X36X1

1,275

1

2

3

4

5

6

7

2 M-510

AC 6

CARRIER

MUSEUM 100

48HCFD08

3,000

1.0

88.2

70.1

67º

105º

-

12

224

184

4

15

11.1

2

17

25.1

1

15X15

1,084

2.4

2

22"DIAM.

1,100

1/4

6.1

6.1

0.8

2.6

460

3

60

21.1

25

(4)20X20X2 (1)20X24X1

1,350

1

2

3

4

5

6

7

2 M-510

AC 7

AC 8

CARRIER

FIRST FLOOR NORTH OFFICES

48HCFD24

7,000

1.6

232.6

170.4

67º

105º

-

12

400

324

4

15

26

2

17

29.6

2

18X15 15X11

1,176

8.7

4

22"DIAM.

1,100

1/4

18.6

14.7

0.9

6.4

460

3

60

53.8

60

(9)16X25X2 (4)16X25X1

3,250

1

2

3

4

5

6

7

3 M-510

AC 9

AC 10

CARRIER

SECOND FLOOR LIBRARY

48HCFD24

7,000

1.6

232.6

170.4

67º

105º

-

12

400

324

4

15

26

2

17

29.6

2

18X15 15X11

1,176

8.7

4

22"DIAM.

1,100

1/4

18.6

14.7

0.9

6.4

460

3

60

53.8

60

(9)16X25X2 (4)16X25X1

3,250

1

2

3

4

5

6

7

3 M-510

CARRIER

FIRST FLOOR WEST OFFICES

2

18X15 15X11

60

(9)16X25X2 (4)16X25X1

7

4 M-510

AC 11

48HCFD28

9,000

1.6

284.4

210.8

67º

105º

-

11.2

400

324

4

15

26

2

17

34.3

1,010

8.7

6

ACCESSORIES NOTES: 1

ELECTRICAL

TIME GUARD II CONTROL CIRCUIT

2

100% DRY-BULB TYPE ECONOMIZER

3

100% BAROMETRIC RELIEF

4

MODULATING POWER EXHAUST

5

CO2 SENSOR

6

POWERED CONVENIENCE OUTLET

7

THE AIR-MOVING EQUIPMENT IS SERVED BY A TOTAL COVERAGE SMOKEDETECTION SYSTEM COMPLYING WITH THE CALIFORNIA FIRE CODE

22"DIAM.

1,100

1/4

18.6

18.6

0.9

9.7

460

3

60

63.6

3,470

1

2

3

4

5

6

06/11/12 DSA BACKCHECK 12/29/11 DSA SUBMITTAL MARK: DATE: DESCRIPTION: DRAWN BY: PP CHK'D BY: VO COPYRIGHT: CSDA ARCHITECTS 2011 SHEET TITLE

LEGENDS, NOTES, AND SCHEDULES ORIGINAL SCALE 0

1"

JOB NO.: SHEET NUMBER:

M-001