EXHAUST FAN SCHEDULE
SHEET INDEX MOTOR
MANUFACTURER AND MODEL
TYPE
CFM
ESP IN (WG)
FAN RPM
HP (WATTS)
VOLT
PH
HZ
WEIGHT (LBS)
ANCHOR. DETAIL
REMARKS
SHEET TITLE
M-001
LEGENDS, NOTES, AND SCHEDULES
EF 1
TOILET 159
LOREN COOK GC-160
CEILING
140
0.25
1,500
113
120
1
60
15
-
-
PROVIDE BACKDRAFT DAMPER
M-110
MECHANICAL FIRST FLOOR PLAN
EF 2
TOILET 207
LOREN COOK GC-160
CEILING
140
0.25
1,500
113
120
1
60
15
-
-
PROVIDE BACKDRAFT DAMPER
M-111
MECHANICAL SECOND FLOOR PLAN
EF 3
JANITOR 209
LOREN COOK GC-180
CEILING
200
0.25
1,500
192
120
1
60
16
-
-
EF 4
TOILETS 106, 108, 109
LOREN COOK 80C2B
ROOF VENTILATOR
400
0.5
1,260
1/6
120
1
60
30
12 M-500
EF 5
TOILETS 136, 137
LOREN COOK 80C2B
ROOF VENTILATOR
300
0.5
1,239
1/6
120
1
60
30
EF 6
MEN'S RESTROOM 133
LOREN COOK 120C2B
ROOF VENTILATOR
750
0.5
1,151
1/6
120
1
60
EF 7
WOMEN'S 134, 212 AND MEN'S RESTROOMS 211
LOREN COOK 180C3B
ROOF VENTILATOR
1,600
0.5
742
1/4
120
1
60
S
ON-OFF SWITCH
T
THERMOSTAT
ABV ABOVE BEL BELOW BTU BRITISH THERMAL UNIT CAP CAPACITY CD CEILING DIFFUSER CFM CUBIC FEET PER MINUTE CG CEILING GRILLE CONC CONCRETE COND CONDENSATE CONN CONNECTION CONT CONTINUATION CR CEILING REGISTER D DRAIN DB DRY BULB DL DOOR LOUVER DN DOWN DTR DOWN TRHU ROOF EA EXHAUST AIR (E) EXISTING ENT ENTERING F.A. FACE AREA F FARENHEIT FLA FULL LOAD AMPS FPI FINS PER INCH FPM FEET PER MINUTE FLEX FLEXIBLE GALV GALVANIZED GA GAUGE HP HORSEPOWER IN INCH ISOL ISOLATOR LBS POUNDS LVG LEAVING EMS ENERGY MANAGEMENT SYSTEM M.A. MIXED AIR MAX MAXIMUM MBH 1000 BTU'S PER HOUR (N) NEW MIN MINIMUM MOD MODULATING DAMPER MVD MANUAL VOLUME DAMPER NTS NOT TO SCALE OPER. WT. OPERATING WEIGHT OPG OPENING OSA OUTSIDE AIR PD PRESSURE DROP PH PHASE PRESS PRESSURE POC POINT OF CONNECTION PSI POUNDS PER SQUARE INCH RA RETURN AIR RAR RETURN AIR REGISTER REQ'D REQUIRED RLA RATED LOAD AMPS RPM REVOLUTIONS PER MINUTE Ø ROUND DUCT SA SUPPLY AIR SP STATIC PRESSURE SF SQUARE FEET SWR SIDEWALL REGISTER SL SOUND LINED TEMP TEMPERATURE T'STAT THERMOSTAT TYP TYPICAL UTR UP THRU ROOF V VOLT VTR VENT THRU ROOF W/ WITH WB WET BULB W.G. WATER GAUGE
SECTION THRU RECTANGULAR SUPPLY DUCT SECTION THRU RECTANGULAR RETURN DUCT SECTION THRU RECTANGULAR EXHAUST DUCT
PROVIDE BACKDRAFT DAMPER
M-130
MECHANICAL ROOF PLAN
10"
PROVIDE BACKDRAFT DAMPER AND MANUFACTURER ROOF CURB
M-310
BUILDING SECTIONS
12 M-500
10"
PROVIDE BACKDRAFT DAMPER AND MANUFACTURER ROOF CURB
M-500
DETAILS
55
12 M-500
10"
PROVIDE BACKDRAFT DAMPER AND MANUFACTURER ROOF CURB
M-510
VIBRATION ISOLATOR DETAILS
90
12 M-500
18"
PROVIDE BACKDRAFT DAMPER AND MANUFACTURER ROOF CURB
M-511
VIBRATION ISOLATOR DETAILS
M-520
EMS DIAGRAMS
FLEXIBLE CONNECTION R
SERVICE
SHEET NUMBER
DUCT RISE IN DIRECTION OF FLOW
D
UNIT
FAN WHEEL DIA. IN (MIN)
MECHANICAL LEGENDS & ABBREVIATIONS
DUCT DROP IN DIRECTION OF FLOW MANUAL VOLUME DAMPER (MVD) AUTOMACTIC FIRE DAMPER (AFD) MODULATING DAMPER (MOD) BACKDRAFT DAMPER (BDD) STATIC PRESSURE DAMPER
SOUND TRAP SCHEDULE DESIGNATION ST 1-1
MFG MODEL
UNIT SIZE (INCHES)
P.D. (IN. W.G.)
125
250
500
1000
2000
4000
8000
VEL. FPM
PRICE RLX60/2F
18x14
0.23
14
28
42
48
48
37
21
914
1,600
PRICE RMX60/4G
26X12
0.15
16
31
43
51
45
27
13
738
5
112
ON RETURN AIR DUCTWORK
CFM
ST 2-1
DECIBELS
1,600
LENGTH (FT)
OPER. WT. (LBS)
ST 2-2
ST 3-1
ST 4-1
ST 5-1
2,400
PRICE RMX60/4G
28x14
0.22
13
27
40
47
45
28
15
882
5
124
ON SUPPLY AIR DUCTWORK
ST 3-2
ST 4-2
ST 5-2
1,680
PRICE RMX60/1F
36X12
0.17
14
25
42
51
50
34
21
800
5
162
ON RETURN AIR DUCTWORK
3,000
PRICE RLX60/1F
36X14
0.35
14
32
45
50
51
46
26
857
5
176
ON RETURN AIR DUCTWORK
6,000
PRICE RLX60/1F
40X20
PRICE RLX60/1F
48X16
ST 9-1
ST 10-1
ST 9-2
6,000 ST 10-2
4,065
ST 10-3
1,875
PRICE RLX60/1F
36X18
PRICE RMX60/4G
24X16
0.79
11
0.79
14
1.5
14
1.5
13
26
33
32
27
41
45
46
51
51
45
51
50
40
51
47
45
48
45
46
28
30
5
1,260
25
26
ENERGY COMPLIANCE FORMS
SD SMOKE DETECTOR
M-531
ENERGY COMPLIANCE FORMS
BD
BYPASS DAMPER
SOUND LINED (SL) DUCT W/ INTERNAL INSULATION. DUCT SIZES SHOWN ARE NET INSIDE DIMENSION
MEP COMPONENT ANCHORAGE NOTE: ALL MECHANICAL, PLUMBING, AND ELECTRICAL COMPONENTS SHALL BE ANCHORED AND INSTALLED PER THE DETAILS ON THE DSA APPROVED CONSTRUCTION DOCUMENTS. WHERE NO DETAIL IS INDICATED, THE FOLLOWING COMPONENTS SHALL BE ANCHORED OR BRACED TO MEET THE FORCE AND DISPLACEMENT REQUIREMENTS PRESCRIBED IN THE 2010 CBC, SECTIONS 1615A.1.12 THROUGH 1615A.1.22 AND ASCE 7-05 CHAPTER 6 AND 13. 1. ALL PERMANENT EQUIPMENT AND COMPONENTS. 2. TEMPORARY OR MOVABLE EQUIPMENT THAT IS PERMANENTLY ATTACHED (E.G HARD WIRED) TO THE BUILDING UTILITY SERVICES SUCH AS ELECTRICITY, GAS, OR WATER. 3. MOVABLE EQUIPMENT WHICH IS STATIONED IN ONE PLACE FOR MORE THAN 8 HOURS AND HEAVIER THAN 400 POUNDS ARE REQUIRED TO BE ANCHORED WITH TEMPORARY ATTACHMENTS.
FLEXIBLE DUCT TO CEILING DIFFUSER OR REGISTER
THE ATTACHMENT OF THE FOLLOWING MECHANICAL AND ELECTRICAL COMPONENTS SHALL BE POSITIVELY ATTACHED TO THE STRUCTURE, BUT NEED NOT BE DETAILED ON THE PLANS. THE PROJECT INSPECTOR WILL VERIFY THAT THESE ITEMS HAVE BEEN POSITIVELY ATTACHED. THESE COMPONENTS SHALL HAVE FLEXIBLE CONNECTIONS PROVIDED BETWEEN THE COMPONENT AND ASSOCIATED DUCTWORK, PIPING, AND CONDUIT.
ON RETURN AIR DUCTWORK
124
COMBINATION FIRE/SMOKE DAMPER
SOUND TRAP
ON RETURN AIR DUCTWORK
162
5
738
M-530
ON SUPPLY AIR DUCTWORK
213
5
857
15
213
5
1,125
M
ON SUPPLY AIR DUCTWORK
ST 1-2
ST 6-1
EMS DIAGRAMS
REMARKS
110
5
M-521
ON RETURN AIR DUCTWORK
SINGLE LINE RIGID SHEET METAL DUCTWORK
A. COMPONENTS WEIGHTING LESS THAN 400 POUNDS AND HAVE A CENTER OF MASS LOCATED 4 FEET OR LESS ABOVE THE ADJACENT FLOOR OR ROOF LEVEL THAT DIRECTLY SUPPORT THE COMPONENT. B. COMPONENTS WEIGHTING LESS THAN 20 POUNDS, OR INTHE CASE OF DISTRIBUTED SYSTEMS LESS THAN 5 POUNDS PER FOOT, WHICH ARE SUSPENDED FROM A ROOF OR FLOOR OR HUNG FROM A WALL.
NOTES: PROVIDE DUCT TRANSITION FROM SOUND TRAPS TO RELATED DUCTWORK AS NEEDED
FOR THOSE ELEMENTS THAT DO NOT REQUIRE DETAILS ON THE APPORVED DRAWINGS, THE INSTALLATION SHALL BE SUBJECT TO THE APPROVAL OF THE STRUCTURAL ENGINEER OF RECORD AND THE DSA DISTRICT STRUCTURAL ENGINEER
PIPING, DUCTWORK, AND ELECTRICAL DISTRIBUTION SYSTEM BRACING NOTE
M
FURNISHED & INSTALLED BY MECHANICAL CONTRACTOR
E
FURNISHED & INSTALLED BY ELECTRICAL CONTRACTOR
ME
FURNISHED & INSTALLED BY MECHANICAL CONTRACTOR, WIRED BY ELECTRICAL CONTRACTOR
EM
FURNISHED BY ELECTRICAL CONTRACTOR, INSTALLED BY MECHANICAL CONTRACTOR, WIRED BY ELECTRICAL CONTRACTOR
CC
CLOSING COIL IN MAGNETIC STARTER
SW
SWITCH
CSDA Architects, Inc. 4061 Glencoe Ave, Suite B Marina del Rey, CA 90292 design@csdarchitects.com T:310.821.9200 F:310.821.9201
ARCHITECT STAMP
CONSULTANT
CREATIVE DESIGN
CONSULTING ENGINEERS 336 NORTH CENTRAL AVE SUITE 10B GLENDALE, CA 91203 TEL: (818) 507-7522
CONSULTANT STAMP
NOT FOR CONSTRUCTION USE
AUTHORITY APPROVAL IDENTIFICATION STAMP DIVISION OF THE STATE ARCHITECT
04-112249
PIPING, DUCTWORK, AND ELECTRICAL DISTRIBUTION SYSTEMS SHALL BE BRACED TO COMPLY WITH THE FORCES AND DISPLACEMENTS PRESCRIBED IN ASCE 7-05 SECTION 13.3 AS DEFINED IN ASCE 7-05 SECTION 13.6.8, 13.6.7, 13.6.5.6, AND 2010 CBC, SECTIONS 1615A.1.20, 1615A.1.21 AND 1615A.1.22. THE BRACING AND ATTACHMENTS TO THE STRUCTURE SHALL COMPLY WITH ONE OF THE OSHPD PREAPPROVALS WITH AN OPA #, AS MODIFIED TO SATISFY ANCHORAGE REQUIREMENTS OF ACI 318, APPENDIX D.
FLS
AC DATE
ZONE
SS
AC NUMBER ZONE NUMBER
Z1-1 1000
ZONE CFM
COPIES OF THE MANUAL SHALL BE AVAILABLE ON THE JOBSITE PRIOR TO THE START OF HANGING AND BRACING OF THE PIPE, DUCTWORK, AND ELECTRICAL DISTRIBUTION SYSTEMS.
BYPASS DAMPER
THE STRUCTURAL ENGINEER OF RECORD SHALL VERIFY THE ADEQUACY OF THE STRUCTURE TO SUPPORT THE HANGER AND BRACE LOADS.
BD-1 1000
AC NUMBER
SCHOOL DISTRICT:
DAMPER CFM
VICTOR VALLEY UNION HIGH SCHOOL DISTRICT 16350 MOJAVE DRIVE VICTORVILLE, CA 92395 SCHOOL ADDRESS:
VICTOR VALLEY HIGH SCHOOL - NEW ADMINISTRATION & LIBRARY BUILDING
SPLIT SYSTEM COOLING UNIT SCHEDULE INDOOR UNIT COOLING CAPACITY (MBH)
SEER
290
12
15.2
1
0.33
208
1
ELECTRICAL ROOM 107
570
24
17
1
0.36
208
ELECTRICAL ROOM 124
635
34.2
14
1
0.57
208
MANUFACTURER AND MODEL
SERVICE
FC 1
MITSUBISHI PKA-A12HA4
ELECTRICAL ROOM 155
FC 2
MITSUBISHI PKA-A24KA4
FC 3
MITSUBISHI PKA-A36KA4
UNIT
OUTDOOR UNIT
CFM
MCA
FLA
V
OPER. WEIGHT
ANCHOR. DETAIL
60
29
2 M-511
1
1
60
46
2 M-511
1
60
46
2 M-511
PH
HZ
OPER. WEIGHT
ANCHOR. DETAIL
60
82
1 M-511
1
60
165
1 M-511
1
60
165
1 M-511
MANUFACTURER AND MODEL
MCA
CU 1
MITSUBISHI PKY-A12NHA4
13
15
208
1
1
CU 2
MITSUBISHI PKA-A24NHA4
18
30
208
1
CU 3
MITSUBISHI PKA-A36NHA4
25
40
208
REMARKS
UNIT
MOCP
V
PH
HZ
REMARKS
16500 MOJAVE DRIVE VICTORVILLE, CA 92395 KEY PLAN
NOTES: 1
PROVIDE WITH CONDENSING PUMP
PACKAGED AIR CONDITIONING UNIT SCHEDULE COOLING CAP UNIT
MANUFACTURER
SERVICE AREA
MODEL
CFM
HEATING CAPACITY
ESP IN (WG) TOTAL
SENSIBLE
EWB TEMP. ºF
ENT COND TEMP ºF
SEER
INDOOR FAN
CONDENSER COIL
EVAPORATOR COIL
OUTDOOR FAN
EER INPUT MBH OUT MBH
ROWS
FPI
FACE AREA
ROWS
FPI
FACE AREA
NO.
SIZE
RPM
BHP
NO.
SIZE
RPM
BHP
COMP NO.1 RLA
COMP NO.2 RLA
OFM (FLA) IFM (FLA) EACH EACH
FILTERS (INCHES)
V
PHASE
HZ
MCA
MOCP
OPER. WEIGHT INCLUD. CURB
ACCESSORIES INTEGRATED
REMARKS
ANCHORAGE
AC 1
CARRIER
CORRIDOR 217
48HCFD05
1,600
1.0
47.7
37
67º
105º
15.6
13
120
96
3
15
7.3
2
17
23.1
1
10X10
1,208
2.9
1
22"DIAM.
1,100
1/4
6.2
-
0.9
2.7
460
3
60
10.8
15
(4)16X20X2 (1)20X36X1
910
1
2
3
4
5
6
7
1 M-510
AC 2
CARRIER
TEXTBOOK 213
48HCFD05
1,600
1.0
47.7
37
67º
105º
15.6
13
120
96
3
15
7.3
2
17
23.1
1
10X10
1,208
2.9
1
22"DIAM.
1,100
1/4
6.2
-
0.9
2.7
460
3
60
10.8
15
(4)16X20X2 (1)20X36X1
910
1
2
3
4
5
6
7
1 M-510
AC 3
CARRIER
CLASSROOM 214
48HCFD07
2,400
1.0
71.2
55.3
67º
105º
-
12
150
120
3
15
8.9
2
17
20.5
1
15X15
949
2.9
2
22"DIAM.
1,100
1/4
9.7
9.7
0.8
3.4
460
3
60
13.1
15
(4)16X20X2 (1)20X36X1
1,275
1
2
3
4
5
6
7
2 M-510
AC 4
CARRIER
CLASSROOM 215
48HCFD07
2,400
1.0
71.2
55.3
67º
105º
-
12
150
120
3
15
8.9
2
17
20.5
1
15X15
949
2.9
2
22"DIAM.
1,100
1/4
9.7
9.7
0.8
3.4
460
3
60
13.1
15
(4)16X20X2 (1)20X36X1
1,275
1
2
3
4
5
6
7
2 M-510
AC 5
CARRIER
CLASSROOM 216
48HCFD07
2,400
1.0
71.2
55.3
67º
105º
-
12
150
120
3
15
8.9
2
17
20.5
1
15X15
949
2.9
2
22"DIAM.
1,100
1/4
9.7
9.7
0.8
3.4
460
3
60
13.1
15
(4)16X20X2 (1)20X36X1
1,275
1
2
3
4
5
6
7
2 M-510
AC 6
CARRIER
MUSEUM 100
48HCFD08
3,000
1.0
88.2
70.1
67º
105º
-
12
224
184
4
15
11.1
2
17
25.1
1
15X15
1,084
2.4
2
22"DIAM.
1,100
1/4
6.1
6.1
0.8
2.6
460
3
60
21.1
25
(4)20X20X2 (1)20X24X1
1,350
1
2
3
4
5
6
7
2 M-510
AC 7
AC 8
CARRIER
FIRST FLOOR NORTH OFFICES
48HCFD24
7,000
1.6
232.6
170.4
67º
105º
-
12
400
324
4
15
26
2
17
29.6
2
18X15 15X11
1,176
8.7
4
22"DIAM.
1,100
1/4
18.6
14.7
0.9
6.4
460
3
60
53.8
60
(9)16X25X2 (4)16X25X1
3,250
1
2
3
4
5
6
7
3 M-510
AC 9
AC 10
CARRIER
SECOND FLOOR LIBRARY
48HCFD24
7,000
1.6
232.6
170.4
67º
105º
-
12
400
324
4
15
26
2
17
29.6
2
18X15 15X11
1,176
8.7
4
22"DIAM.
1,100
1/4
18.6
14.7
0.9
6.4
460
3
60
53.8
60
(9)16X25X2 (4)16X25X1
3,250
1
2
3
4
5
6
7
3 M-510
CARRIER
FIRST FLOOR WEST OFFICES
2
18X15 15X11
60
(9)16X25X2 (4)16X25X1
7
4 M-510
AC 11
48HCFD28
9,000
1.6
284.4
210.8
67º
105º
-
11.2
400
324
4
15
26
2
17
34.3
1,010
8.7
6
ACCESSORIES NOTES: 1
ELECTRICAL
TIME GUARD II CONTROL CIRCUIT
2
100% DRY-BULB TYPE ECONOMIZER
3
100% BAROMETRIC RELIEF
4
MODULATING POWER EXHAUST
5
CO2 SENSOR
6
POWERED CONVENIENCE OUTLET
7
THE AIR-MOVING EQUIPMENT IS SERVED BY A TOTAL COVERAGE SMOKEDETECTION SYSTEM COMPLYING WITH THE CALIFORNIA FIRE CODE
22"DIAM.
1,100
1/4
18.6
18.6
0.9
9.7
460
3
60
63.6
3,470
1
2
3
4
5
6
06/11/12 DSA BACKCHECK 12/29/11 DSA SUBMITTAL MARK: DATE: DESCRIPTION: DRAWN BY: PP CHK'D BY: VO COPYRIGHT: CSDA ARCHITECTS 2011 SHEET TITLE
LEGENDS, NOTES, AND SCHEDULES ORIGINAL SCALE 0
1"
JOB NO.: SHEET NUMBER:
M-001