EXHAUST FAN SCHEDULE MOTOR MANUFACTURER AND MODEL
TYPE
CFM
CEILING
ESP IN (WG)
FAN RPM
HP (WATTS)
VOLT
PH
HZ
WEIGHT (LBS)
192
120
1
60
16
ANCHOR. DETAIL
-
-
SHEET NUMBER REMARKS
PROVIDE BACKDRAFT DAMPER
M-001
SHEET TITLE
GYM FACULTY RESTROOM 219
LOREN COOK GC-190
EF 2
GYM FACULTY RESTROOM 210
LOREN COOK GC-190
CEILING
EF 3
GYM MEN'S LOCKER ROOM 216
LOREN COOK 1656CB
ROOF VENTILATOR
2,800
5/8
1,215
3/4
120
1
60
106
11 M-504
16.5"
PROVIDE BACKDRAFT DAMPER AND MANUFACTURER ROOF CURB
MB-111
GYMNASIUM MECHANICAL FLOOR PLAN
EF 4
GYM WOMEN'S LOCKER ROOM 207
LOREN COOK 1656CB
ROOF VENTILATOR
2,800
5/8
1,215
3/4
120
1
60
106
11 M-504
16.5"
PROVIDE BACKDRAFT DAMPER AND MANUFACTURER ROOF CURB
MB-131
GYMNASIUM MECHANICAL ROOF PLAN
EF 5
GYM MEN'S RESTROOM 222
LOREN COOK 100C2B
ROOF VENTILATOR
600
45
11 M-504
10"
PROVIDE BACKDRAFT DAMPER AND MANUFACTURER ROOF CURB
M-301
EF 6
GYM WOMEN'S RESTROOM 206
LOREN COOK 100C2B
ROOF VENTILATOR
600
0.5
1,600
1/6
120
1
60
45
11 M-504
10"
PROVIDE BACKDRAFT DAMPER AND MANUFACTURER ROOF CURB
M-501
DETAILS
EF 7
GYM MEN'S SHOWER 221
LOREN COOK 80C2B
ROOF VENTILATOR
400
0.5
1,260
1/6
120
1
60
45
11 M-504
10"
PROVIDE BACKDRAFT DAMPER AND MANUFACTURER ROOF CURB
M-502
DETAILS
EF 8
GYM WOMEN'S SHOWER 208
LOREN COOK 80C2B
ROOF VENTILATOR
400
45
11 M-504
10"
PROVIDE BACKDRAFT DAMPER AND MANUFACTURER ROOF CURB
M-503
EF 9
MPR STAFF RESTROOM 118
LOREN COOK GC-190
CEILING
200
0.25
1,500
192
120
1
60
16
-
-
PROVIDE BACKDRAFT DAMPER
M-504
DETAILS
EF 10
MPR JANITOR ROOM 121
LOREN COOK GC-190
CEILING
200
0.25
1,500
192
120
1
60
16
-
-
PROVIDE BACKDRAFT DAMPER
M-505
DETAILS
EF 11
MPR BOY'S RESTROOM 127
LOREN COOK 100C2B
ROOF VENTILATOR
500
0.5
1,400
1/6
120
1
60
45
11 M-504
10"
PROVIDE BACKDRAFT DAMPER AND MANUFACTURER ROOF CURB
EF 12
MPR GIRL'S RESTROOM 128
LOREN COOK 100C2B
ROOF VENTILATOR
500
0.5
1,400
1/6
120
1
60
45
11 M-504
10"
PROVIDE BACKDRAFT DAMPER AND MANUFACTURER ROOF CURB
EF 13
MPR KITCHEN 114
LOREN COOK
UPBLAST ROOF EXHAUST
2,540
1.5
1,435
1
460
3
60
136
2 M-505
18"
PROVIDE BACKDRAFT DAMPER
EF 14
GYM LAUNDRY 214
LOREN COOK GC-140
CEILING
100
1/8
1,200
70
120
1
60
15
-
-
PROVIDE BACKDRAFT DAMPER
0.25
1,500
ON-OFF SWITCH
T
THERMOSTAT
ABV ABOVE BEL BELOW BTU BRITISH THERMAL UNIT CAP CAPACITY CD CEILING DIFFUSER CFM CUBIC FEET PER MINUTE CG CEILING GRILLE CONC CONCRETE COND CONDENSATE CONN CONNECTION CONT CONTINUATION CR CEILING REGISTER D DRAIN DB DRY BULB DL DOOR LOUVER DN DOWN DTR DOWN TRHU ROOF EA EXHAUST AIR (E) EXISTING ENT ENTERING F.A. FACE AREA F FARENHEIT FLA FULL LOAD AMPS FPI FINS PER INCH FPM FEET PER MINUTE FLEX FLEXIBLE GALV GALVANIZED GA GAUGE HP HORSEPOWER IN INCH ISOL ISOLATOR LBS POUNDS LVG LEAVING EMS ENERGY MANAGEMENT SYSTEM M.A. MIXED AIR MAX MAXIMUM MBH 1000 BTU'S PER HOUR (N) NEW MIN MINIMUM MOD MODULATING DAMPER MVD MANUAL VOLUME DAMPER NTS NOT TO SCALE OPER. WT. OPERATING WEIGHT OPG OPENING OSA OUTSIDE AIR PD PRESSURE DROP PH PHASE PRESS PRESSURE POC POINT OF CONNECTION PSI POUNDS PER SQUARE INCH RA RETURN AIR RAR RETURN AIR REGISTER REQ'D REQUIRED RLA RATED LOAD AMPS RPM REVOLUTIONS PER MINUTE Ø ROUND DUCT SA SUPPLY AIR SP STATIC PRESSURE SF SQUARE FEET SWR SIDEWALL REGISTER SL SOUND LINED TEMP TEMPERATURE T'STAT THERMOSTAT TYP TYPICAL UTR UP THRU ROOF V VOLT VTR VENT THRU ROOF W/ WITH WB WET BULB W.G. WATER GAUGE
LEGENDS, NOTES, AND SCHEDULES
EF 1
200
S
MA-111
SECTION THRU RECTANGULAR SUPPLY DUCT
MULTI-PURPOSE MECHANICAL FLOOR PLAN
SECTION THRU RECTANGULAR RETURN DUCT 200
0.25
1,500
192
1
120
60
16
-
-
MA-131
PROVIDE BACKDRAFT DAMPER
MULTI-PURPOSE MECHANICAL ROOF PLAN SECTION THRU RECTANGULAR EXHAUST DUCT
0.5
0.5
1,600
1/6
1,260
1/6
1
120
1
120
60
60
CU 1
FC 2
CU 2
FC 3
CU 3
AUTOMACTIC FIRE DAMPER (AFD) MODULATING DAMPER (MOD)
DETAILS
M
M-506
COMBINATION FIRE/SMOKE DAMPER
SD SMOKE DETECTOR BD
BYPASS DAMPER
ENERGY COMPLIANCE FORMS SOUND TRAP
M-507
ENERGY COMPLIANCE FORMS
M-508
SOUND LINED (SL) DUCT W/ INTERNAL INSULATION. DUCT SIZES SHOWN ARE NET INSIDE DIMENSION
ENERGY COMPLIANCE FORMS
MEP COMPONENT ANCHORAGE NOTE: ALL MECHANICAL, PLUMBING, AND ELECTRICAL COMPONENTS SHALL BE ANCHORED AND INSTALLED PER THE DETAILS ON THE DSA APPROVED CONSTRUCTION DOCUMENTS. WHERE NO DETAIL IS INDICATED, THE FOLLOWING COMPONENTS SHALL BE ANCHORED OR BRACED TO MEET THE FORCE AND DISPLACEMENT REQUIREMENTS PRESCRIBED IN THE 2010 CBC, SECTIONS 1615A.1.12 THROUGH 16A.1.22 AND ASCE 7-05 CHAPTER 6 AND 13. FLEXIBLE DUCT TO CEILING DIFFUSER OR REGISTER
1. ALL PERMANENT EQUIPMENT AND COMPONENTS. 2. TEMPORARY OR MOVABLE EQUIPMENT THAT IS PERMANENTLY ATTACHED (E.G HARD WIRED) TO THE BUILDING UTILITY SERVICES SUCH AS ELECTRICITY, GAS, OR WATER. 3. MOVABLE EQUIPMENT WHICH IS STATIONED IN ONE PLACE FOR MORE THAN 8 HOURS AND HEAVIER THAN 400 POUNDS ARE REQUIRED TO BE ANCHORED WITH TEMPORARY ATTACHMENTS.
4 M-502
SINGLE LINE RIGID SHEET METAL DUCTWORK
THE ATTACHMENT OF THE FOLLOWING MECHANICAL AND ELECTRICAL COMPONENTS SHALL BE POSITIVELY STTACHED TO THE STRUCTURE, BUT NEED NOT BE DETAILED ON THE PLANS. THE PROJECT INSPECTOR WILL VERIFY THAT THESE ITEMS HAVE BEEN POSITIVELY ATTACHED. THESE COMPONENTS SHALL HAVE FLEXIBLE CONNECTIONS PROVIDED BETWEEN THE COMPONENT AND ASSOCIATED DUCTWORK, PIPING, AND CONDUIT.
FOR THOSE ELEMENTS THAT DO NOT REQUIRE DETAILS ON THE APPORVED DRAWINGS, THE INSTALLATION SHALL BE SUBJECT TO THE APPROVAL OF THE MECHANICAL/ELECTRICAL ENGINEER.
MITSUBISHI INDOOR WALL MOUNTED COOLING ONLY UNIT MODEL PKA-A18HA, 390 CFM, COOLING CAPACITY 18MBH, 13.0 SEER, 208V-1PH-60HZ, MCA = 1, MOCP = 15, OPERATING WEIGHT = 35 14 LBS. BREAKER SIZE 15 AMP. PROVIDE WITH CONDENSING PUMP. M-504
LOREN COOK GRAVITY VENTILATOR MODEL PR EXHAUST SIZE 8, 500 CFM @ 0.15" S.P.. PROVIDE WITH MANUFACTURER ROOF CURB
GV 2
LOREN COOK GRAVITY VENTILATOR MODEL PR INTAKE SIZE 8, 500 CFM @ 0.15" S.P.. PROVIDE WITH MANUFACTURER ROOF CURB
E
FURNISHED & INSTALLED BY ELECTRICAL CONTRACTOR FURNISHED & INSTALLED BY MECHANICAL CONTRACTOR, WIRED BY ELECTRICAL CONTRACTOR
EM
FURNISHED BY ELECTRICAL CONTRACTOR, INSTALLED BY MECHANICAL CONTRACTOR, WIRED BY ELECTRICAL CONTRACTOR
CC
CLOSING COIL IN MAGNETIC STARTER
SW
SWITCH
Z1-1 1000
MUA 1
AND
MANUFACTURER
MUA 2
MODEL
REZNOR
MUA 3
GYM MEN'S, WOMEN'S LOCKER
REZNOR
MPR KITCHEN
RDH-200
CFM
ESP
HP
VOLT
INPUT
OUTPUT
HP
VOLT
QTY.
SIZE
2,800
1.2
2
460V-3PH
200 MBH
162 MBH
1/50
120V-1PH
1
6" CELDEK
1,145
1.4
2
460V-3PH
200 MBH
162 MBH
CONSULTING ENGINEERS 336 N. CENTRAL AVE. SUITE 10B GLENDALE, CA 91203 TEL: (818) 507-7522 FAX: (818) 507-9879
CONSULTANT STAMP
NOT FOR CONTRUCTION USE
FLS
SS
AC NUMBER ZONE NUMBER ZONE CFM
AC NUMBER BD-1 1000
DAMPER CFM
SCHOOL DISTRICT:
VICTOR VALLEY UNION HIGH SCHOOL DISTRICT 16350 MOJAVE DR, VICTORVILLE, CA 92392 SCHOOL ADDRESS:
HOOK JR HIGH SCHOOL NEW FACILITIES
OPER. WEIGHT INCLUD. CURB (LBS.)
2,340
CREATIVE DESIGN
AC DATE
COPIES OF THE MANUAL SHALL BE AVAILABLE ON THE JOBSITE PRIOR TO THE START OF HANGING AND BRACING OF THE PIPE, DUCTWORK, AND ELECTRICAL DISTRIBUTION SYSTEMS.
PUMP MOTOR
FILTERS
SERVICE
RDH-200
CONSULTANT
04-112177
MAKE-UP AIR UNIT UNIT
ARCHITECT STAMP
IDENTIFICATION STAMP DIVISION OF THE STATE ARCHITECT
THE BRACING AND ATTACHMENTS TO THE STRUCTURE SHALL COMPLY WITH ONE OF THE OSHPD PRE-APPROVALS WITH AN OPA #, SUCH AS MASON INDUSTRIES (OPA 349), OR ISAT (OPA 485) AS MODIFIED TO SATISFY ANCHORAGE REQUIREMENTS OF ACI 318, APPENDIX D.
HEATING CAPACITY
design@csdarchitects.com T:310.821.9200 F:310.821.9201
AUTHORITY APPROVAL
THE STRUCTURAL ENGINEER OF RECORD SHALL VERIFY THE ADEQUACY OF THE STRUCTURE TO SUPPORT THE HANGER AND BRACE LOADS.
SUPPLY FAN & MOTOR
CSDA Architects, Inc. 4061 Glencoe Ave, Suite B Marina del Rey, CA 90292
BYPASS DAMPER
PIPING, DUCTWORK, AND ELECTRICAL DISTRIBUTION SYSTEMS SHALL BE BRACED TO COMPLY WITH THE FORCES AND DISPLACEMENTS PRESCRIBED IN ASCE 7-05 SECTION 13.3 AS DEFINED IN ASCE 705 SECTION 13.6.8, 13.6.7, 13.6.6, AND 2010 CBC, SECTIONS 1615A.1.20, 1615A.1.21 AND 1615A.1.22.
GV 1
FURNISHED & INSTALLED BY MECHANICAL CONTRACTOR
ZONE
PIPING, DUCTWORK, AND ELECTRICAL DISTRIBUTION SYSTEM BRACING NOTE
4 M-502
M
ME
A. COMPONENTS WEIGHTING LESS THAN 400 POUNDS AND HAVE A CENTER OF MASS LOCATED 4 FEET OR LESS ABOVE THE ADJACENT FLOOR OR ROOF LEVEL THAT DIRECTLY SUPPORT THE COMPONENT. B. COMPONENTS WEIGHTING LESS THAN 20 POUNDS, OR INTHE CASE OF DISTRIBUTED SYSTEMS LESS THAN 5 POUNDS PER FOOT, WHICH ARE SUSPENDED FROM A ROOF OR FLOOR OR HUNG FROM A WALL.
4 M-502
MITSUBISHI OUTDOOR UNIT MODEL PUY-A18NHA, 208V-1PH-60HZ, MCA = 13, MOCP = 20, OPERATING WEIGHT = 97 LBS. FOR ANCHORAGE DETAILS SEE
BUILDING SECTIONS
STATIC PRESSURE DAMPER
MITSUBISHI SLIM INDOOR UNIT COOLING ONLY MODEL PLA-A24BA, COOLING CAPACITY 24 MBH, 13.4 SEER, 230V-1PH-60HZ, MCA=1, MOCP= 15,, OPERATING WEIGHT=53 LBS. PROVIDE WITH OPTIONAL CONDENSATION PUMP, REMOTE TEMPERATURE SENSOR AND REMOTE CONTROLLER. PROVIDE WITH CONDENSING PUMP. MITSUBISHI OUTDOOR UNIT MODEL PAY-A24NHA, 230V-1PH-60HZ, MCA=18, MOCP=30, OPERATING WEIGHT=163 LBS. FOR ANCHORAGE DETAILS SEE
DUCT DROP IN DIRECTION OF FLOW
BACKDRAFT DAMPER (BDD)
MITSUBISHI INDOOR WALL MOUNTED COOLING ONLY UNIT MODEL PKA-A30KA, 530 CFM, COOLING CAPACITY 30MBH, 13.0 SEER, 208V1PH-60HZ, MCA = 1, MOCP = 15, OPERATING WEIGHT = 53 LBS. 13 BREAKER SIZE 30 AMP. PROVIDE WITH CONDENSING PUMP. M-504 MITSUBISHI OUTDOOR UNIT MODEL PUY-A30NHA, 208V-1PH-60HZ, MCA = 25, MOCP = 40, OPERATING WEIGHT = 163 LBS. FOR ANCHORAGE DETAILS SEE
DUCT RISE IN DIRECTION OF FLOW
MANUAL VOLUME DAMPER (MVD)
EQUIPMENT SCHEDULE FC 1
FLEXIBLE CONNECTION R
SERVICE
FAN WHEEL DIA. IN (MIN)
D
UNIT
MECHANICAL LEGENDS & ABBREVIATIONS
SHEET INDEX
1/50
120V-1PH
1
6" CELDEK
1,145
15000 HOOK BLVD. VICTORVILLE, CA 92394
ANCHOR. DETAIL
REMARKS
2 M-502
PROVIDE WITH BLOWER, FURNACE, EVAPORATIVE COOLER AND DOWN TURN SA PLENUM
3 M-502
PROVIDE WITH BLOWER, FURNACE, EVAPORATIVE COOLER AND DOWN TURN SA PLENUM
KEY PLAN
B A
PACKAGED AIR CONDITIONING UNIT SCHEDULE COOLING CAP UNIT
MANUFACTURER
CFM
TOTAL
SENSIBLE
EWB TEMP. ºF
ESP IN (WG)
ENT COND TEMP ºF
SEER
OUTDOOR FAN
EER INPUT MBH OUT MBH
ROWS
FPI
FACE AREA
ROWS
FPI
FACE AREA
NO.
SIZE
RPM
BHP
NO.
SIZE
RPM
BHP
COMP NO.1 RLA
COMP NO.2 RLA
OFM (FLA) IFM (FLA) EACH EACH
V
PHASE
HZ
MCA
MOCP
FILTERS (INCHES)
OPER. WEIGHT INCLUD. CURB (LBS.)
ACCESSORIES INTEGRATED
GYM OFFICE
48HCFA04
1,200
0.8
35.2
27.5
67º
105º
15
12.5
115
93
3
15
5.5
2
17
12.7
1
10X10
1,175
1.2
1
22"DIAM.
825
1/8
5.8
-
0.5
2.1
460
3
60
13.1
15
(2)16X25X2 (1)20X24X1
890
1
3
4
5
6
AC 2
CARRIER
MPR MUSIC/DRAMA
48HCFA06
2,000
1.0
57.5
40.25
67º
105º
15.6
13
150
120
4
15
7.3
2
17
21.3
1
10X10
1,466
2.4
1
22"DIAM.
1,100
1/4
7.0
7.0
0.9
3.4
460
3
60
13.1
15
(4)16X16X2 (1)20X24X1
797
1
2
3
4
5
AC 3
CARRIER
MPR MUSIC/DRAMA
48HCFD07
2,400
1.0
71.2
55.3
67º
105º
-
12
150
120
3
15
8.9
2
17
20.5
1
15X15
949
3.4
460
3
60
13.1
15
(4)16X20X2 (1)20X36X1
1,275
1
2
3
4
AC 4
CARRIER
MPR KITCHEN
48HCFA07
2,400
1.0
71.2
55.3
67º
105º
-
12
150
120
3
15
8.9
2
17
20.5
1
15X15
949
3.4
460
3
60
13.1
15
(4)16X20X2 (1)20X36X1
1,275
1
2
3
AC 5
CARRIER
MPR STAGE 117
48HCFD07
2,400
1.0
71.2
55.3
67º
105º
-
12
150
120
3
15
8.9
2
17
20.5
1
15X15
949
3.4
460
3
60
13.1
15
(4)16X20X2 (1)20X36X1
1,275
1
2
3
CARRIER
MPR SERVING ROOM 127
48HCFD08
3,000
1.0
88.2
70.1
67º
105º
-
12
224
184
4
15
11.1
2
17
25.1
1
15X15
1,084
2.4
2
22"DIAM.
1,100
1/4
6.1
6.1
0.8
2.6
460
3
60
21.1
25
(4)20X20X2 (1)20X24X1
1,350
1
2
3
4
5
CARRIER
MPR MAIN ROOM 125
48HCFD12
4,000
1.4
111.9
86.9
67º
105º
-
11.5
250
205
4
15
22
2
17
21.4
2
15X15
863
3.3
3
22"DIAM.
1,100
1/4
7.7
7.7
3.1
4.4
460
3
60
27.8
35
(6)20X25X2 (4)16X25X1
1,500
1
2
3
4
CARRIER
GYM 101
48HCFD24
8,000
1.6
237.1
182.2
67º
105º
-
12
400
324
4
15
26
2
17
29.6
2
18X15 15X11
1,176
8.7
4
22"DIAM.
1,100
1/4
18.6
14.7
0.9
6.4
460
3
60
53.8
60
(9)16X25X2 (4)16X25X1
3,250
1
2
3
4
AC 9 AC 11
2.9
2.9
2.9
2
2
2
22"DIAM.
22"DIAM.
1,100
1,100
22"DIAM.
1,100
TIME GUARD II CONTROL CIRCUIT
1/4
1/4
1/4
9.7
9.7
9.7
9.7
9.7
9.7
0.8
0.8
0.8
REMARKS
ANCHORAGE
7
1 M-501
6
7
2 M-501
5
6
7
3 M-501
4
5
6
7
3 M-501
4
5
6
7
3 M-501
6
7
3 M-501
5
6
7
4 M-501
5
6
7
1 M-502
05/04/12 11/30/11 10/21/11 09/16/11 MARK: DATE: DRAWN BY: CHK'D BY:
DSA BACKCHECK DSA SUBMITTAL 50% CD'S DD SUBMITTAL DESCRIPTION: PP VO
COPYRIGHT:CSDA ARCHITECTS 2011 SHEET TITLE
LEGENDS, NOTES, & SCHEDULES ORIGINAL SCALE
ACCESSORIES NOTES: 1
ELECTRICAL
CARRIER
AC 8 AC 10
MODEL
INDOOR FAN
CONDENSER COIL
EVAPORATOR COIL
AC 1
AC 6 AC 7
SERVICE AREA
HEATING CAPACITY
0
2
100% DRY-BULB TYPE ECONOMIZER
3
100% BAROMETRIC RELIEF
4
MODULATING POWER EXHAUST
5
CO2 SENSOR
6
POWERED CONVENIENCE OUTLET
7
THE AIR-MOVING EQUIPMENT IS SERVED BY A TOTAL COVERAGE SMOKE-DETECTION SYSTEM PER CMC SECTION 609.0 EXCEPTION 1
1"
Project Number JOB NO.: SHEET NUMBER:
M-001
2"