Input/Output Signals of the AML (AML-L B) System (GR-120N-1)

CN 2 connector

Pin No. Name

13 CNTL 1P

Signal names and functions

Signal name: Right swing proportional control valve output

Current controlled by the AML is output from the AML to the right swing proportional control valve when the right swing is stopped by automatic swing stop. However, in the following conditions, the automatic swing stop does not activate.

(1) Swing stop/override switch is set to “OVERRIDE”.

(2) Outriggers are not extended.

(3) AML emergency switch is set to “Emergency” and the PTO switch is set to “OVERRIDE”.

Output voltage: Square wave 0 to 24V

Crane condition that causes the automatic swing stop

The moment ratio exceeds 100% due to right swing while the extension widths of four outriggers are different.

The moment ratio reaches 90% or more (not 100%) while the boom lift with the jib mounted is performed.

When the jib set pin is out of inserted condition, the AML assumes that the jib is mounted.

The crane operation exceeds the right swing limit when the swing stop limit is registered.

14 CNTL 1N Signal name: Ground terminal for right swing proportional control valve

Input voltage: DC0V

Signal name: Left swing proportional control valve output

Current controlled by the AML is output from the AML to the left swing proportional control valve when the left swing is stopped by automatic swing stop. However, in the following conditions, the automatic swing stop is not activated.

(1) Swing stop/override switch is set to “OVERRIDE”.

(2) Outriggers are not extended.

(3) AML emergency switch is set to “Emergency” and the PTO switch is set to “OVERRIDE”.

15 CNTL 2P

Output voltage: Square wave 0 to 24V

Crane condition that causes the automatic swing stop

The moment ratio exceeds 100% due to left swing while the extension widths of four outriggers are different.

The moment ratio reaches 90% or more (not 100%) while the boom lift with the jib mounted is performed.

When the jib set pin is out of inserted condition, the AML assumes that the jib is mounted.

The crane operation exceeds the left swing limit when the swing stop limit is registered.

Signal name: Ground terminal for left swing proportional control valve

Input voltage: DC0V

16 CNTL 2N