from CAT Roof Support Щитовая крепь 5501650-2X1414-1500 Инструкция по эксплуатации Manual – PDF DOWNLOAD
Umbrella Lock is active here and X shlds to the left.
#123 ULOCK > 6 More
Umbrella Lock is active here and X shlds to the right.
#123 ULOCK !!!
Umbrella Lock is active; this is the center shield.
#123 ULOCK Overlap
This shield is in two umbrella lock zones; zones cannot be cleared or moved from this shield.
#123 Maint. Lock !!!
Maintenance Lock is active, centered on this shield.
#123 Maint. Lock #
Maintenance Lock is active, started & centered from the indicated shield.
#123 Sol Driver Error
Solenoid driver has indicated a fault. Clear Solenoid Driver error to correct using Ekey and Enter. If it happens again, replace solenoid driver, cable or PMC-R.
#123 No Solenoid Drvr
No solenoid driver detected! Connect solenoid driver to clear this display. If one is connected, replace cable, driver, or PMC-R.
#123 Stuck Key!
A key is stuck on PMC-R keyboard. Replace PMC-R.
#123 Soft Locked!
Because a neighbor shield lockout button is pressed, this shield is soft locked - not allowed to activate any solenoids.
#123 LOCKED
Large black lockout button is pressed on this PMC-R. No functions can occur on this shield; no functions are allowed on neighbor shields.
#123 QUICKSTOP #100
Large red quickstop button is pressed somewhere on face. No shield functions are allowed until button is pulled back out.
#123 ! SLAVE ! - ##122
This shield is in slave mode - being controlled by the indicated shield.