Mechanical Permit set example

Page 1


NOTETOGENERALCONTRACTOR,SUBCONTRACTORSANDSUPPLIERS: TheGeneralContractorandallSubcontractorsandMaterialSuppliersshallreviewandbefamiliarwith alldrawingsassociatedwiththisprojectincludingthearchitectural,civil,structural,plumbing, mechanical,andelectricaldrawings.Specificrequirementsdepictedononedrawingpageorinone portionofthedrawingsshallbeapplicabletoalldrawingpagesandallportionsofthedrawings.Should aconflictordiscrepancybediscoveredinthedrawingsduringthebiddingornegotiationphase,the GeneralContractor,SubcontractororMaterialSuppliershallimmediatelynotifytheArchitectand requestadditionalinformationandclarification.FailuretodosowillnotrelievetheGeneralContractor, SubcontractororMaterialSupplierfromtherequirementsofallportionsofthedrawings.

DIFFUSERDESIGNATIONANDCFM

NATURALGASPIPING CONDENSATEPIPING

MANUALVOLUMEDAMPER

MOTORIZEDDAMPER

BIPOLARIONIZATIONUNIT

THERMOSTAT

TEMPERATURESENSOR

COMBINATIONCARBONMONOXIDE NITROGENDIOXIDESENSOR

HUMIDITYSENSOR

REFRIGERANTMONITORINGDEVICE R

STANDARD4-WAYBLOWSUPPLYDIFFUSER

3-WAYBLOWSUPPLYDIFFUSER

2-WAYBLOWSUPPLYDIFFUSER

1-WAYBLOWSUPPLYDIFFUSER

LINEARDIFFUSER

ENERGYREQUIREMENTS:

MAINTRUNKAND BRANCHDUCTTAKEOFF, WITHVOLUMEDAMPER

TRANSFERGRILLE

ROOFEXHAUSTFAN (RD)RADIATIONDAMPER (FD)FIREDAMPER (SD)SMOKEDAMPER (FSD)FIRE/SMOKE DAMPER (--)FSDIF

THECONTRACTORSHALLFURNISHANDINSTALLALLMATERIALANDEQUIPMENTINSTRICTACCORDANCEWITHAPPLICABLECODESANDSTANDARDS,ANDPER MANUFACTURER'SDIRECTIONS.INSTALLATIONSHALLCOMPLYWITHANSI/ACCASTANDARD5. 2. THEGENERALCONTRACTORANDALLSUBCONTRACTORSANDMATERIALSUPPLIERSSHALLREVIEWANDBEFAMILIARWITHALLDRAWINGSASSOCIATEDWITHTHIS PROJECTINCLUDINGTHEARCHITECTURAL,CIVIL,STRUCTURAL,PLUMBING,MECHANICAL,ANDELECTRICALDRAWINGS.SPECIFICREQUIREMENTSDEPICTEDONONE DRAWINGPAGEORINONEPORTIONOFTHEDRAWINGSSHALLBEAPPLICABLETOALLDRAWINGPAGESANDALLPORTIONSOFTHEDRAWINGS.SHOULDACONFLICT ORDISCREPANCYBEDISCOVEREDINTHEDRAWINGSDURINGTHEBIDDINGORNEGOTIATIONPHASE,THEGENERALCONTRACTOR,SUBCONTRACTORORMATERIAL SUPPLIERSHALLIMMEDIATELYNOTIFYTHEARCHITECTANDREQUESTADDITIONALINFORMATIONANDCLARIFICATION.FAILURETODOSOWILLNOTRELIEVETHE GENERALCONTRACTOR,SUBCONTRACTORORMATERIALSUPPLIERFROMTHEREQUIREMENTSOFALLPORTIONSOFTHEDRAWINGS.

AIRFLOW RETURNOREXHAUST SUPPLYAIRFLOW EXHAUSTGRILLE RETURNOR

LOUVEREDDOOR(SEE ARCHITECTURAL DRAWINGS)

1"DOORUNDERCUT

DUCTMOUNTEDSMOKE DETECTOR

CONDENSATEPUMP CD

MECHANICALSYSTEMS,SERVICESYSTEMSANDEQUIPMENT

METHODOFCOMPLIANCE

CLIMATEZONE

THERMALZONE

WINTERDRYBULB

SUMMERDRYBULB

INTERIORDESIGNCONDITIONS

WINTERDRYBULB

SUMMERDRYBULB

RELATIVEHUMIDITY

BUILDINGHEATINGLOAD(MBH)

BUILDINGCOOLINGLOAD(MBH)

MECHANICALSPACINGCONDITIONINGSYSTEM

DESCRIPTIONOFUNIT

HEATINGEFFICIENCY COOLINGEFFICIENCY

HEATOUTPUTOFUNIT

COOLINGOUTPUTOFUNIT

TOTALBOILEROUTPUT.IFOVERSIZED,STATEREASON.

TOTALCHILLEROUTPUT.IFOVERSIZED,STATEREASON.

LISTEQUIPMENTEFFICIENCIES

EQUIPMENTSCHEDULESWITHMOTORS(MECHANICALSYSTEMS)

MOTORHORSEPOWER NUMBEROFPHASES

SEESCHEDULES

SEESCHEDULES

SEESCHEDULES

SEESCHEDULES SEESCHEDULES

SEESCHEDULES

SEESCHEDULES

SEESCHEDULES

SEESCHEDULES

3. THECONTRACTORSHALLSECUREANDPAYFORALLNECESSARYPERMITS,LICENSE,INSPECTIONS,APPROVALS,ANDFEES.

4.THECONTRACTORSHALLPROVIDEAWRITTENGUARANTEETHATSHALLWARRANTALLWORKMANSHIPANDMATERIALSFORONEYEARFROMDATEOFFINAL ACCEPTANCEBYTHEOWNER.ANYBREAKDOWNOCCURRINGINTHEFIRSTYEARSHALLBEATNOEXPENSETOTHEOWNER.ALLREFRIGERATIONCOMPRESSORS SHALLHAVEAFIVEYEAR(PARTSONLY)WARRANTY,ANDALLNATURALGASHEATEXCHANGERSSHALLHAVEATENYEAR(PARTSONLY)WARRANTY.

5.DRAWINGSARESCHEMATIC,NOTALLRISESANDDROPSARESHOWN.DONOTSCALEDRAWINGSFORMEASUREMENTS.DRAWINGSTHATHAVENOTRECEIVEDPERMIT APPROVALFROMAUTHORITYHAVINGJURISDICTIONSHOULDNOTBEUSEDFORFINALORGUARANTEEDPRICING.ANYPRICINGBASEDONUNAPPROVEDDRAWINGS SHOULDBENOTEDASPROVISIONAL.CONTRACTORACCEPTSALLRESPONSIBILITYFORGUARANTEEDPRICINGBASEDONUNAPPROVEDDRAWINGS.

6. WHENEXISTINGEQUIPMENTISREUSEDCONTRACTORSHALLENSUREEQUIPMENTISISGOODWORKINGORDERANDSHALLREPORTTOTHEOWNERANYREPAIRS REQUIREDTOBRINGEQUIPMENTTOGOODWORKINGORDERPRIORTOTURNOVER.

7. TRADESARETOCOORDINATETHEIRWORKWITHALLOTHERTRADESTOAVOIDCONFLICTS.GENERALLY,DUCTWORKSHALLBEKEPTASHIGHASPOSSIBLE. MECHANICALCONTRACTORSHALLREVIEWENTIRESETOFCONTRACTDOCUMENTSINCLUDINGBUTNOTNECESSARILYLIMITEDTOALLARCHITECTURAL,STRUCTURAL, MECHANICAL,ELECTRICAL,PLUMBINGANDENTIREPROJECTMANUAL.MECHANICALCONTRACTORSHALLACKNOWLEDGEANDINCLUDEINTHESCOPEOFWORK (CONTRACT)ALLCONDITIONSPERTINENTTOTHECOMPLETIONOFTHEMECHANICALWORK.MECHANICALCONTRACTORSHALLFULLYCOORDINATEMECHANICALWORK WITHTHEINSTALLATIONOFWORKBYALLOTHERTRADESANDMAKENECESSARYFIELDADJUSTMENTSASREQUIREDTOACCOMMODATETHEMECHANICAL INSTALLATION.ALLOFTHEABOVESHALLBEINCLUDEDINTHESCOPEOFWORKATNOADDITIONALCOSTTOTHEOWNER.

8. CONTRACTORSHALLCOORDINATEELECTRICALCHARACTERISTICSANDREQUIREMENTSOFALLMECHANICALEQUIPMENTWITHELECTRICALDRAWINGSPRIORTO ORDERINGEQUIPMENTORSUBMITTINGSHOPDRAWINGSANDSHALLFURNISHEQUIPMENTWIREDFORVOLTAGESSHOWNTHEREIN.

9. CONTRACTORSHALLCOORDINATETHEINSTALLATIONOFMECHANICALEQUIPMENT,DUCTWORK,ETC.TOFITWITHINTHESPACEALLOWEDBYTHEARCHITECTURAL ANDSTRUCTURALCONDITIONS.CONTRACTORSHALLFIELDVERIFYEXISTINGCONDITIONSPRIORTOORDERINGANYEQUIPMENTORMATERIALS.ALLSUSPENDED MATERIALSANDEQUIPMENTSHALLBEINDIVIDUALLYSUPPORTEDFROMTHEBUILDINGSTRUCTURE.DONOTSUSPENDITEMSFROMTHECEILINGORITSSUPPORT SYSTEM.

10.CUTTINGOROTHERWISEALTERINGANYSTRUCTURALMEMBERSSHALLNOTBEPERMITTEDWITHOUTWRITTENPERMISSIONFROMTHESTRUCTURALENGINEEROF RECORD.

11.CONTRACTORSHALLKEEPASETOFMARKEDUPPRINTSWITHANYFIELDCHANGESMADEDURINGCONSTRUCTIONTOCREATEAN"AS-BUILT"SETOFPRINTSTOBE TURNEDOVERTOTHEOWNERATTHECOMPLETIONOFTHEPROJECT.NOTEPERENERGYCODESECTIONDESIGNSETPOINTSOFEQUIPMENTATAMAXIMUMOFNO LOWERTHAN75°INCOOLINGANDNOHIGHERTHAN72°INHEATING.

12.INTHEEVENTCONTRACTORSUBSTITUTESALTERNATEMANUFACTURERSTHENCONTRACTORSHALLCOORDINATEALLASPECTSOFSUBSTITUTEDEQUIPMENTWITH ALLTRADESINCLUDINGBUTNOTLIMITEDTOGASSERVICE,ELECTRICALSERVICE,STRUCTURALLOADSANDOPENINGS,ETC.

13.PROVIDEACCESSPANELSINCEILINGSANDWALLSTOALLOWACCESSTOVALVES,TRAPS,DAMPERS,CLEANOUTS,CONTROLS,ETC.MINIMUMACCESSSIZE12"x12", UNLESSLIMITEDBYPHYSICALCONSTRAINTS.

14.ALLCONDENSATEDRAINPIPINGSHALLBETYPELHARDDRAWNCOPPER,ASTMB-88,WITHTYPEDWVFITTINGS,ASMEB16.23,ORSCHEDULE40PVC,ASTMD1785,WITH TYPEDWVFITTINGS,ASTMD2672.COPPERDRAINPIPEANDFITTINGSSHALLBEJOINEDUSING95-5SILVERSOLDER,ANDPVCPIPEANDFITTINGSSHALLBEJOINED USINGSOLVENTCEMENT.PROVIDETRAPWITHCLEANOUTANDUNIONS.SLOPECONDENSATEDRAINLINESAMINIMUMOF1/8"PERFOOTAWAYFROMTHEMECHANICAL EQUIPMENT.PROVIDEAUXILIARYWATERLEVELMONITORINGDEVICESPERSECTION307.2.3.UNLESSOTHERWISENOTEDROUTECONDENSATEATFULLSIZEOF EQUIPMENTCONNECTIONFROMEQUIPMENTTODRYWELLORSITESTORM.INCASESWHERENEITHERISAVAILABLEDISCHARGETONEARESTMOPSINKORUTILITY SINK.PROVIDECONDENSATEPUMPASREQUIREDBYFIELDCONDITIONS.

15.SUBMITTALS: ASAMINIMUM,THECONTRACTORSHALLPROVIDESUBMITTALSFORALLITEMSSCHEDULEDONTHEDRAWINGS,UNLESSDIRECTEDOTHERWISE.

16.MECHANICALEQUIPMENTSHALLBEINSTALLEDINACCORDANCEWITHTHEMANUFACTURER'SRECOMMENDATIONS.

17.OUTSIDEAIRFORAIRCONDITIONINGUNITSSHALLBEAMINIMUMOF10FEETFROMEXHAUSTFANS,EXHAUSTOPENINGSANDPLUMBINGVENTS.

18.ALLDUCTDIMENSIONSSHOWNAREINSIDECLEARDIMENSIONS.

19.ALLSUPPLYANDRETURNDUCTWORKSHALLBECONSTRUCTEDANDINSTALLEDINACCORDANCEWITHTHELATESTSMACNAANDASHRAESTANDARDS.DUCTWORK SHALLBEFABRICATEDOFGALVANIZEDSTEELFORAPRESSURERATINGOF(-)2"WGFORRETURNAND(+)2"WGFORSUPPLYDUCTWORK.ALLEXHAUSTDUCTWORK SHALLCONSTRUCTEDANDINSTALLEDINACCORDANCEWITHTHELATESTSMACNAANDASHRAESTANDARDS.EXHAUSTDUCTWORKSHALLBEFABRICATEDOF GALVANIZEDSTEELFORAPRESSURERATINGOF1"WGINEXCESSOFTHESYSTEMFANTOTALSTATICPRESSURERATINGATDESIGNFLOWRATE,UNLESSNOTED OTHERWISE.

20.SUPPORTDUCTWORKFROMBUILDINGSTRUCTUREINACCORDANCEWITHSMACNASTANDARDS.

MINIMUMEFFICIENCY NUMBEROFPOLES

SEESCHEDULES

SEESCHEDULES

DESIGNER'SSTATEMENT:

COMPLIESWITHTHEMECHANICALSYSTEMS,SERVICESYSTEMSANDEQUIPMENT TOTHEBESTOFMYKNOWLEDGEANDBELIEF,THEDESIGNOFTHISBUILDING

REQUIRMENTSOFTHEN.C.S.ENERGYCODE.

TITLE: NAME: SIGNED: MOTORTYPE

BrandonRDillard

MechanicalEngineerP.E.

21.RADIUSEDDUCTWORKELBOWSSHALLHAVEACENTERLINERADIUSOF1.5TIMESTHEDUCTWIDTH(ORDIAMETER)UNLESSNOTEDOTHERWISE.

22.ALLMITEREDELBOWS(RECTANGULARANDROUND)SHALLHAVEDOUBLETHICKNESSTURNINGVANESINSTALLEDUNLESSNOTEDOTHERWISEONDRAWINGS.

23.SECURELYSEALALLJOINTSLONGITUDINALANDTRANSVERSESEAMSANDCONNECTIONSINDUCTWORKUSINGWELDMENTS,MECHANICALFASTENERSWITHSEALSOR GASKETSORMASTICS,MESHANDMASTICSEALINGSYSTEMSORTAPES.TAPESANDMASTICSMUSTBELISTEDANDLABELEDINACCORDANCEWITHUL181AORUL181B.

24.DUCTCONNECTIONSTOFANSANDOTHERAIRDISTRIBUTIONEQUIPMENTSHALLBEMADEUSINGMECHANICALFASTENERSWITHSEALS,MASTICSORGASKETS.ALL MECHANICALEQUIPMENTSHALLBEPROVIDEDWITHVIBRATIONISOLATIONBETWEENEQUIPMENTANDBUILDINGSTRUCTURE.

25.SUPPLYAIRANDRETURNAIRDUCTWORKSHALLBEINSULATEDWITHAMINIMUM2"THICK,3/4LB.PERCUBICFOOT,FIBERGLASSDUCTWRAP,WITHFOILFACEDVAPOR BARRIERANDANINSTALLEDTHERMALRESISTANCEOF6.0(RVALUE).ALTERNATEINSULATIONFORRECTANGULARSUPPLYANDRETURNDUCTSHALLBEANINTERIOR DUCTLININGWITHAMINIMUM1-1/2"THICK,1.5LB.PERCUBICFOOTDUCTLINER.DUCTLINERSHALLCONTAINANANTI-MICROBIALAGENTWITHINTHEDUCTLINING ITSELF.MINIMUM"R"VALUESHALLBER-6.3.INCREASEDUCTSHEETMETALSIZEASREQUIREDTOMEETINSIDECLEARDIMENSIONSGIVENONDRAWINGS.

26.ALLDUCTINSULATIONSHALLMEETTHEMINIMUMREQUIREMENTSOFU.L.181FORFLAMESPREADANDSMOKEDEVELOPMENT,ANDSHALLBEU.L.LISTED.

27.TRANSFERDUCTSSHALLBEINTERNALLYLINEDTOAIDINCANCELINGNOISETRANSFER.

28.EXHAUSTDUCTWORKSHALLBEINSULATEDUNLESSNOTEDOTHERWISE.

29.EXPOSEDDUCTWORKSHALLBEINTERNALLYLINEDANDWHENROUNDSHALLBESPIRALCONSTRUCTION.STANDINGSEAMROUNDDUCTWORKSHALLNOTBE ALLOWEDWHENVISIBLE.INTERNALINSULATIONEXPOSEDTOAIRSTREAMSHALLBECLOSEDCELLELASTOMERICMATERIAL

30.COORDINATELOCATIONSOFGRILLES,REGISTERSANDDIFFUSERSWITHARCHITECTURALREFLECTEDCEILINGPLAN.LOCATIONSSHOWNAREAPPROXIMATE,ADJUST LOCATIONSINTHEFIELDASREQUIREDBYCONSTRUCTIONCONSTRAINTS.

31.PROVIDEEACHSUPPLYAIROUTLETORDIFFUSERWITHITSOWNBALANCINGDEVICE.DEVICESCANBELOCATEDINDUCTWORKORSUPPLYAIRDEVICEITSELF.

32.ALLMANUALBALANCINGDAMPERSSHALLHAVEALOCKINGQUADRANT.

33.FLEXIBLEDUCTWORKSHALLBECLASSIFIEDUNDERUL181.PROVIDEAMINIMUMOFFEETINLENGTHANDAMAXIMUMOF10FEETINLENGTH,SUPPORTEDWITH3" GALVANIZEDSHEETMETALSTRAPSAT4FEETCENTERS(MAX).FLEXIBLEDUCTRUNOUTSSHALLBEROUNDDUCTWORKREINFORCEDWITHAWIREHELIXAND INSULATEDWITH1-1/2"THICKFIBERGLASS(WITHA6.0"R"VALUEMINIMUM)COVEREDWITHFLAMEPROOFVAPORBARRIEROFALUMINUMMETALIZEDPOLYESTERFILM LAMINATEDTOGLASSMESH.DUCTSHALLBEATCO'SUPC#036VALUFLEXCLASS1AIRDUCTOREQUAL.CONNECTIONSTODUCTMAINSSHALLBEMADEWITHFITTINGS PROVIDEDWITHTWISTRINGS,BUTTERFLYDAMPERS,LOCKINGHANDQUADRANTS,ANDINSULATIONGUARDS.

34.CONTRACTORSHALLFURNISH,ROUTE,ANDINSTALLCONTROLWIRINGFORALLMECHANICALSYSTEMS.FORSYSTEMSWITHMULTIPLECOMPONENTSCONTRACTORIS RESPONSIBLEFORALLWIRINGBETWEENCOMPONENTS.

35.INSTALLTHERMOSTATSAT4'-0"A.F.F.UNLESSNOTEDOTHERWISE.THERMOSTATLOCATIONSSHALLBECOORDINATEDWITHFINALLOCATIONSOFWALL-MOUNTED ARCHITECTURALANDELECTRICALEQUIPMENT.FINALLOCATIONSMUSTBEAPPROVEDBYTHEARCHITECTANDOWNER.THERMOSTATSSHALLNOTBEINSTALLEDON EXTERIORWALLSIFINTERIORWALLSAREAVAILABLEWITHINSPACESERVEDBYTHERMOSTAT.SHOULDTHETHERMOSTATREQUIREINSTALLATIONONANEXTERIOR WALLANINSULATEDBACKINGPLATEMUSTBEPROVIDEDTOPREVENTFALSEREADINGSBYTHETHERMOSTAT.

36.MECHANICALCONTRACTORSHALLPROVIDEACOMPLETETESTANDBALANCEREPORTOFTHEHVACSYSTEMSPREPAREDBYANINDEPENDENTTESTANDBALANCE CONTRACTOR.ACOPYOFTHETESTANDBALANCEREPORTSHALLBETRANSMITTEDTOTHELOCALCODEOFFICIALSASREQUIRED.THETESTANDBALANCEREPORT SHALLINCLUDECOILLEAVINGTEMPERATURE,OUTSIDEAIRTEMPERATURE,RETURNAIRTEMPERATURE,ANDBOTHOUTDOORANDINDOORHUMIDITYREADINGS.

37.CONTRACTORSHALLPROVIDEACOMPLETECOMMISSIONINGREPORTOFTHEHVACSYSTEMSPREPAREDBYANINDEPENDENTCOMMISSIONINGCONSULTANTAS REQUIREDBYTHEENERGYCONSERVATIONCODEINEFFECT.ACOPYOFTHECOMMISSIONINGREPORTSHALLBETRANSMITTEDTOTHELOCALCODEOFFICIALSAS REQUIRED.

38.ALLPENETRATIONSTHROUGHEXTERIORWALLS&ROOFSHALLBEFLASHED&COUNTERFLASHEDINAWATERPROOFMANNER.(COLORTOMATCHEXTERIOR).

39.CONTRACTORSHALLVERIFYLOCATIONOFALLPENETRATIONSFORRELIEFHOODS,OUTSIDEAIRHOODS,LOUVERS,ANDWALLCAPSWITHARCHITECT&OWNERPRIOR TOINSTALLATION.

40.PENETRATIONSOFRATEDWALLS,PARTITIONSANDFLOORSOFNON-COMBUSTIBLECONSTRUCTIONSHALLBEFIRESTOPPEDWITHNONCOMBUSTIBLEMATERIALS. PENETRATIONSOFNONRATEDWALLS,PARTITIONSANDFLOOROFCOMBUSTIBLECONSTRUCTIONSHALLBEFIRESTOPPEDWITHMATERIALSEQUIVALENTTOTWO INCHESOFWOOD.FIRESTOPPINGSHALLCOMPLYWITHASTME-814.CONTRACTORSHALLCOORDINATEPENETRATIONSWITHARCHITECTURALPLANSANDSHALL PROVIDEFIREDAMPERSATEVERYPENETRATIONOFARATEDWALLANDSMOKEDAMPERSWHEREARCHITECTURALRATINGSREQUIREINCLUDINGTHEPENETRATION OFCORRIDORENCLOSURES.WHEREBOTHAFIREANDSMOKEDAMPERAREREQUIREDACOMBINATIONFIRESMOKEDAMPERMAYBEPROVIDED.PROVIDERADIATION DAMPERSFORALLAIRDEVICESPENETRATINGARATEDCEILING.LISTINGOFDAMPERSSHALLMEETOREXCEEDRATINGOFASSEMBLYWHEREINSTALLED.

41.REFRIGERANTPIPING,NOTSHOWNONPLANS,SHALLBESIZED&INSTALLEDINACCORDANCEWITHTHEMANUFACTURER'SRECOMMENDATIONS,INSTALLATION INSTRUCTIONSANDLOCALCODES.

42.KITCHENHOODEXHAUSTDUCTSHALLBE16GAUGECARBONSTEELOFFACTORYFABRICATEDSTAINLESSSTEEL.ALLJOINTSANDSEAMSSHALLBECONSTRUCTED WITHACONTINUOUSLIQUID-TIGHTEXTERNALWELD.ALLDUCTWORKSHALLBEINSTALLEDPERSECTION506OFTHEMECHANICALCODE.PROVIDECLEANOUTSAT EVERYCHANGEOFDIRECTIONINTHEEXHAUSTDUCTANDPERSPACINGREQUIREMENTSINDICATEDINSECTION506.

43.CONTRACTORSHALLPREPAREALLEXPOSEDDUCT,GRILLES,PIPING,ANDUNITSFORPAINTING.GCWILLBERESPONSIBLEFORPAINTING.

44.AIRHANDLERSWITHAIRFLOWSGREATERTHANOREQUALTO2000CFMORTHATSHAREACOMMONOUTSIDEAIRORRETURNDUCTSHALLBEFURNISHEDWITHSMOKE DETECTORSLOCATEDINTHESUPPLYANDRETURNSECTIONSFORALLUNITS.

NOTE: ANYINSTALLATIONTHATISNOTCOMPLETEDBYJANUARY1,2025SHALL COMPLYWITHNEWASHRAESTANDARD15-2022ANDUTILIZEEITHERR-32OR R-454BANDALLASSOCIATEDSAFETYPRECAUTIONSREQUIREDFORANA2L TYPEREFRIGERANTSHALLBETAKENPERNEWEPAREGULATIONS.IF INSTALLATIONISNOTEXPECTEDTOBECOMPLETEDPRIORTOTHISTIMETHE CONTRACTORSHALLCOORDINATEWITHARCHITECTANDENGINEEROF RECORDTODETERMINEIFVENTILATEDREFRIGERANTCHASESARE REQUIREDFORTHEPROJECTAPPLICATION.

KEYEDNOTESTHISSHEET

12"OUTSIDEAIRDUCTUPTOGREENHECKGRS-12OR EQUALONROOF.PROVIDEWITHMOTORIZED DAMPERSONOUTSIDEAIRDUCTTOROOF. ROUTECONDENSATEATFULLSIZEOFEQUIPMENT CONNECTIONOUTSIDEBUILDINGTOSITESTORMOR DRYWELL.COORDINATEEXACTLOCATIONWITHSITE CIVIL. ROUTEFLUE/COMBUSTIONAIRDUCTSUPTO MANUFACTURER'SAPPROVEDDISCHARGE ACCESSORYONTHEROOF.SIZEANDINSTALLPER MANUFACTURER'SLITERATURE.MAINTAINAMINIMUM OF10'-0"CLEARANCEFROMALLOUTSIDEAIR INTAKES. PLACENEWOUTDOORUNITSINPLACEOFEXISTING OUTDOORUNITSSERVINGTHISSPACE.FIELD COORDINATEEXACTLOCATION.

NOTETOGENERALCONTRACTOR,SUBCONTRACTORSANDSUPPLIERS:

TheGeneralContractorandallSubcontractorsandMaterialSuppliersshallreviewandbefamiliarwith alldrawingsassociatedwiththisprojectincludingthearchitectural,civil,structural,plumbing, mechanical,andelectricaldrawings.Specificrequirementsdepictedononedrawingpageorinone portionofthedrawingsshallbeapplicabletoalldrawingpagesandallportionsofthedrawings.Should conflictordiscrepancybediscoveredinthedrawingsduringthebiddingornegotiationphase,the GeneralContractor,SubcontractororMaterialSuppliershallimmediatelynotifytheArchitectand requestadditionalinformationandclarification.FailuretodosowillnotrelievetheGeneralContractor, SubcontractororMaterialSupplierfromtherequirementsofallportionsofthedrawings.

1

Turn static files into dynamic content formats.

Create a flipbook
Issuu converts static files into: digital portfolios, online yearbooks, online catalogs, digital photo albums and more. Sign up and create your flipbook.