KS1 Digital Control Panel Introduction Note: The generator set will stop if the controller is disconnected, resets, or the DC power supply fails. In manual or automatic mode with the voltage-free contact closed, the generator set will restart automatically when the connection is restored.
Data Programmed Variables
Time (seconds)
Pre-heating time
15
Cool down time
60
Heating time (input contactor)
20
Maximum cranking time
5
Time between cranking attempts
10
Maximum number of cranking attempts
5
Stopped time (for excitation)
10
BPA (Low oil pressure) alarm delay
15
ATA (High coolant temperature) Checkup delay
15
AUX alarm delay
15
4
9803-9980-1
4