KS1 Digital Control Panel Introduction Note: The generator set will stop if the controller is disconnected, resets, or the DC power supply fails. In manual or automatic mode with the voltage-free contact closed, the generator set will restart automatically when the connection is restored.

Data Programmed Variables

Time (seconds)

Pre-heating time

15

Cool down time

60

Heating time (input contactor)

20

Maximum cranking time

5

Time between cranking attempts

10

Maximum number of cranking attempts

5

Stopped time (for excitation)

10

BPA (Low oil pressure) alarm delay

15

ATA (High coolant temperature) Checkup delay

15

AUX alarm delay

15

4

9803-9980-1