Note: The generator set will stop if the controller is disconnected, resets, or the DC power supply fails. In manual or automatic mode with the voltage-free contact closed, the generator set will restart automatically when the connection is restored.
Programmed Variables Time (seconds) Pre-heating time 15 Cool down time 60 Heating time (input contactor) 20 Maximum cranking time 5 Time between cranking attempts 10 Maximum number of cranking attempts 5 Stopped time (for excitation) 10 BPA (Low oil pressure) alarm delay 15 ATA (High coolant temperature) Checkup delay 15
AUX alarm delay 15 Introduction