Generator Circuit Breaker Status (Open / Closed
Immediate Stopping OR
There is also at least one emergency stop button in the system which will cause immediate shutdown of the generating set, the user should be aware of the position of these switches within their own system. Once pressed the ESTOP will shut down the set immediately. The Genset will not restart until the button has been reset and the alarm has been cleared from the alarm list; refer to section ‘Alarm List’ for information on resetting alarms.
Manual ATP7 Operation (when configured for MCB/GCB application)
When the system is configured with an ATP7 for load transfer on mains failure (see application modes ‘ATP7 application’) the JCB Digital Control Panel provides the ability to manually transfer load to and from the generating set even while the mains supply is still present. This manual operation of the ATP7 is achieved while in MANUAL mode. To transfer load from the mains to the generating set Manual Mode ) To enter MANUAL mode
OPERATION
Toggles GCB open/Closed][)
Toggles MCB open/Closed] To transfer load to the Generating set (only possible while Genset is running) the Mains Circuit Breaker must first be toggled open by pressing soft key, closing the Generator Circuit Breaker (GCB) (toggle soft key) will then transfer the mains load to the Generating set. Transferring load back to the mains is achieved by first toggling open the GCB and closing the MCB.