The JCB Digital Control Panel Controller has an alarm list, which stores the details of both active and inactive alarms. There are different classes of alarms programmed within the JCB Digital Control Panel, some critical alarms such as ‘Emergency Stop’ will cause the set to shutdown, sound an audible alarm and will prevent restart, until the issue has been resolved and the alarm cleared from the list. Other less critical alarms, such as battery under/over voltage generate an alarm message and an audible alarm, but do not cause shutdown or prevent starting.

Accessing List

The alarm list is accessible from the ‘top level’ screen by pressing soft key !

Access Alarms

The alarm list displays all the alarm messages that have not been acknowledged and cleared. The first line contains the alarm message while the second line provides date and time when the alarm was present. If the ! Symbol is also displayed then the alarm is currently active, and cannot be cleared. An alarm must be acknowledged before it can be cleared, when an alarm has been acknowledged the indicator light stops flashing and the horn is reset (or auto resets). To highlight different alarms in the list use the and soft keys, to acknowledge a highlighted alarm press and to clear an acknowledged alarm press again. To return to the top level screen press

Acknowledge an Alarm

Reset an Acknowledged Alarm

Navigate Up or Down Through Alarm List

Return to ‘Top Level Screen’ OR