BI379615
BUCYRUS-ERIE ® 380-W WAL INO D AOLINE
SERIAL NUMBER __ TEMPORARY BUCYRUS-ERIE COMPANY General Offices: Soum Milwaukee, Wisconsin, U.S.A.
CARE, I T liCE n OPERATI AIUAL
MACHINE
• Thank you very much for reading the preview of the manual.
• You can download the complete manual from: www.heydownloads.com by clicking the link below
• Please note: If there is no response to CLICKING the link, please download this PDF first and then click on it.
CLICK HERE TO DOWNLOAD THE COMPLETE MANUAL
CLICK HERE TO DOWNLOAD THE COMPLETE MANUAL
BI379615 (
The master switch contacts shown in series with voltage limit control windings open the circuit when the master switch is in the neutral position. If the excavator is swinging and the master switch is returned to the neutral position, (1) the voltage limit circuit is bypassed and (2) the reference calls for zero armature current. The current feedback signal will cause the regulator to regulate zero armature current and "free wheeling" of the swing will be obtained. Stopping is accomplished by moving the master switch in the opposite direction calling for reverse armature current.
Rheostats SRH and 6RH provide for adjustment of no load volts in the swing left and swing right directions, respectively. When the master switch is rapidly reversed the contacts in the voltage limit circuit prevent current flow while in the plugging quadrant. Otherwise, the voltage limit signal would add to the reference signal and produce large armature current peaks.
Thermister THER connected in parallel with 3RS provides temperature compensation. Its effect is discussed in the voltage regulator section.
BI379615 111 I BUCYRUS-ERIE 1111 §Ill
®
FU 230v AC ± 10% X (17) 2 RH REG 1 A FCM (15) + 2 RS 2A 3 RH (18) (16.1 I : 6 RH ·-----I I I 5 RH (A2) GEN. SER. FLO. 1 RH (C) GREG : FROM BIAS POWER MODULE (62v) I + I I (19) REFERENCE (20) Figure 4.2-37 4-87I (A1) MOT MOT. COMM. FLO. (A2) +
The bias windings are used to "set" the operating point of each exciter. With no current flowing in the reference and feedback windings the resistor in series with the bias windings determines the exciter output. Since the controlling amplistat turns full on with no current flowing in any of the control windings, the bias winding is connected to produce negative ampere turns. Increasing the resistance in series with bias windings causes a corresponding increase in exciter output. Once the bias resistor is set to produce the desired output voltage, normally referred to as "overlap volts", the exciter will operate about this point. That is, the exciter output will increase above "overlap volts" for a positive signal and decrease for a negative signal. The proper adjustment of ''overlap" volts is important to machine operation. Insufficient overlap volts can cause a dead band around the master switch neutral position, resulting in no change in generator output when the master switch is moved slightly off the neutral position. Excessive overlap voltage increases field heating and can overtemperature the generator field coils.
Bias rheostats 8RH and 9RH are provided for adjustment of overlap voltage. These have been adjusted at the factory to produce equal volts across each generator field. This value of voltage is approximately 3-5 volts, and should be checked under field conditions. 4-88
BI379615 + GEN. VOLTS VL
VOLTS BIAS
CHARACTERISTICS - GEN.
LOAD
-GEN. AMPS
VOLTS
VOLTAGE
/CURRENT REGULATION STALL
Figure 4.2-38 BIAS
LIMIT
AMPS MAX. MASTER SWITCH POS.
/ \. (
BIAS POWER MODULE (IC3506Al09E8)
The D-C voltage necessary for current and voltage limit bias and for amplistat bias (overlap adjustment) is obtained from the Bias Power Module. It consists basically of a step-down transformer, full wave rectifier bridge, zener diode, and the associating filter circuits. The circuitry for this Module is as shown in Figure 4.2-39.
As mentioned earlier, a zener diode is a semi-conductor device that conducts like an ordinary diode in the forward direction, but will also conduct in the reverse direction if the reverse voltage across the diode exceeds its rated value. The voltage across the zener diode will remain substantially constant as long as the current through it is within its prescribed range.
The secondary voltage of the transformer is rectified by the bridge to produce 88 volts d-e between terminals 3 and 5. Resistor 4RS and the bias circuits, representing the load, are connected to the Module as indicated. The value of 4RS has been selected to limit zener diode current to a safe value and still allow regulation.
The Module must maintain a constant voltage output under two types of varying conditions - changes in a-c voltage, or changes in load current. A change in a-c voltage changes zener current, and will vary the current through 4RS, and consequently the voltage across it. However, both zener voltage and load voltage will remain constant because of the characteristics.
If the load current should change, the zener will absorb or supply this required change in current, while the voltage across 4RS will remain constant.
BI379615 I BUCYRUS-ERIE E:3l
BPM I (1 l 115v I I
(5)
(3)
+88v1
I I I I I 4 RS ,BIAS CIRCUITS 1 I I_ --· I I I I I
Figure 4.2-39
4-89 ®
MAGNETICS
Dragline control circuits normally include several contactors and relays which are used to establish motor field strength, and perform sequencing functions. Other relays may "look at" the generator out- ( puts and modify the regulator reference signals and volt-amp characteristics under certain conditions. These devices are shown on the diagram and the reader should become familiar with their operation before making any adjustments on the control equipment.
INSTALLATION
PRELIMINARY INSPECTION
1. Visually inspect the equipment for shipment damages.
2. If equipment is to be stored before use, provide adequate protection against the elements and other contaminating conditions.
3. If the equipment has been stored or unused for prolonged periods, be sure all equipment is dry and clean before energizing.
4. Manually move all mechanical devices to check for binding or misalignment.
5. Check to assure all interconnecting wires and remote devices agree with the elementary diagram.
6. Check terminals for loose connections, electrical clearance, etc.
7. Make sure all contacts are clean, and properly positioned.
8. Check generator fields for proper ohms and grounds. In checking for grounds avoid subjecting the control equipment to voltages which might cause damage to the semi-conductor components.
9. Check thermistor ohms and assure thermistor is properly insulated from armature circuit.
NOTE
Thermistor settings on elementary diagrams are given in ohms at 2soc.
10. Insure that the voltage and current feedback signals are being extracted from the proper points on the motors and generators.
11. Assure adequate electrical, thermal, andmechanical clearances have been maintained.
12. Establish effective communication means between control panels and operator's cab, prior to actual tuna up of equipment.
13. Check that all resistors have been set according to elementary diagram.
BI379615
4-90
TEMPORARY MAINTENANCE
Periodic inspection and maintenance is important to assure continuous machine operation at peak performance. Control operations may exceed a thousand times a day and regular inspections are important so replacements or repairs can be made before a failure occurs. Costly downtime can be reduced by following three basic rules.
1. Prepare a productive-maintenance program consisting of item to be checked and recorded at each scheduled inspection. Sometimes frequent inspections are desirable on new equipment. The interval between inspections can then be increased at the user's discretion as he becomes more familiar with the equipment and particular operating conditions.
2. Keep on hand renewal and repair parts.
3. Much time and trouble can be saved by buying renewal parts made by the manufacturer who originally supplied the You are then certain such renewal-parts will-conform with specifications of the original parts.
The suggested frequency of inspection recommended in the accompanying chart is based on average conditions. The actual frequency should be adjusted for each application as experience indicates.
WEEKLY INSPECTION
WHAT TO INSPECT
Static components
WHAT TO INSPECT FOR
Collections of dirt or gum
Excessive heating of parts - evidenced by discoloration of metal parts, charred insulation, or odor
Corrosion of metal parts
Frayed, broken, or loose connections
Magnetic and Mechanically Operated Devices
Control Circuit Voltage
Collections of dirt or gum
Excessive heating of parts - evidenced by discoloration of metal- parts' charred insulation; or odor
Freedom of moving parts (no binding or stickinq)
Corrosion of metal parts
Remaining wear allowance on contacts
Proper contact pressure
4-91
BI379615
WEEKLY INSPECTION (Continued)
WHAT TO INSPECT
Magnetic and Mechanically Operated Devices (cont'd.)
WHAT TO INSPECT FOR
Brush wear on rheostats and Variacs
Loose connections
Conditions of flexible shunts
Conditions of arc chutes or barriers
Worn or broken mechanical parts
Excessive arcing in opening circuits
Loose set screws on shafts and couplings
Evidence of dripping water or liquids falling on control
Condition of control-circuit contacts
Wear or roughness on sliding contacts
Lubricate contacts where recommended
Condition of wheels and linings (on brakes)
Operation - including proper functioning of timing devices, sequencing of devices, and operation of protectivelimit switches, etc.
Arc Chutes or Barriers
If they are almost burned through, replace. This will prevent the heat of the arc from burning out polepieces or shorting the next phase.
Flexible Shunts
Corrosion
Damage from wear
Flex or twist slightly to make sure they are in good condition.
Interlocks
TROUBLESHOOTING
Make sure they are properly adjusted.
A preventive maintenance program will help reduce costly downtime. Should trouble occur, the following tips will help get inoperative equipment back into service in a hurry.
1. Become familiar with each circuit and the operation of each new component as it is installed.
2. Keep the elementary diagram handy. This is the most valuable tool the manufacturer can furnish for use in trouble shooting.
3. Keep portable instruments handy for checking voltage, current, resistance, etc. 4-92
BI379615
TEMPORARY 4. Have on hand adequate spare parts to replace failed components.
The information contained in the "reference measurements" chart provides sufficient data to quickly determine if many of the circuits and components are functioning properly. The chart should be filled out when the equipment is put into service so the information will be readily available.
After operating properly, should the drive become inoperative, or its performance change, care should be exercised during trouble shooting in order not to get the drive out of adjustment. Generally, the difficulty stems from a loose connection, broken wire, or failed component and can be corrected without making additional adjustments to the control. Considerable time will be saved if the difficulty can be corrected without changing the component settings necessitating returning the drive. The following chart when used with "reference measurements" provides a means for isolating the malfunction.
FUSE PROTECTION
The fuse used on the SCR Exciter has been specially selected for its fast blow characteristic. A fast blow fuse is necessary to protect the SCR's and concentional rectifiers. Further, the fast blow fuse also protects the rotating equipment in the event of Exciter malfunction.. The fast-blow fuses should not be replaced with ordinary fuses of the same current rating.
SYMPTOM Drive will not start
Incorrect drive speed
CHECK
REFER TO:
Mechanical Operation Adjustinginstructions Generator running
SCR exciter supply voltage
Overlap voltage
Master switch output
Reference current available
Brakes released
Motor field volts
DC Exciter
Motor field volts
Armature field volts
Generator no-load volts 4-93
BI379615
SYMPTOM
Incorrect generator voltage
CHECK
Master switch output
Reference signal
miliamperes
Overlap voltage
Voltage feedback signal
Proper control of exciter output
REFER TO:
Overtravel limit switch
Incorrect overlap volts
Incorrect stall torque (current)
Master switch output
Reference signal milliamperes
Overlap voltages
Commutating field voltages
Current limit bias voltages
Current feedback signal
Temperature compensation and thermistor ohms
Current limit diodes
Motor field current
Incorrect overlap volts
Excessive stall torque (current) variation with temperature
Improper adjustments of thermistor circuit. If stall current decreases with increasing temperature, increase resistance in parallel with thermistor. Also decrease resistance in series with thermistor to maintain same bridge current, or adjust tapped resistor for constant bridge output voltage.
Stall current variation
Excessive armature current with master switch in neutral
Reference field current (should be zero)
Current in current or voltage limit control fields
Current-limit/voltage limit diodes
Overlap voltage
Generator residual voltages 4-94
Incorrect overlap volts
Generator instructions
BI379615
(
\
• Thank you very much for reading the preview of the manual.
• You can download the complete manual from: www.heydownloads.com by clicking the link below
• Please note: If there is no response to CLICKING the link, please download this PDF first and then click on it.
CLICK HERE TO DOWNLOAD THE COMPLETE MANUAL
CLICK HERE TO DOWNLOAD THE COMPLETE MANUAL
SYMPTOM
Incorrect overlap voltages
CHECK
Zero voltage or current limit field miliamperes
Zero reference field miliamperes
Bias voltage
Bias currents to each amplistat
Exciter operation
REFER TO:
Exciter instructions
Excessive generator sparking
Stall current
No load volts
Excessive plugging peaks
Generator conditions
Excessive plugging peaks
Stall current oscillating at 5 - 14 cps
Generator voltage relays
Rate capacitors in reference circuit
Will also be observed in exciter and generator outputs. Improper adjustment of resistor-capacitor anti-hunt networks. Vary resistant and capacitance to obtain desired performance. May also be caused by insufficient resistance in series with current control fields.
BI379615 I ill _T_E_M_P_O_RA_R_Y___ __"U"_C-'-"J!t"__::m:::_e>=-n.T---=l.v.I::..:...::.....A..___::J.'V=--....:10":::;..;:.A..:.=.:::III:a=--------- BUCYRUS-ERIE Ei1l
4-95 ®
BI379615 ( ( \
SECTION 3
ELECTRICAL ADJUSTMENTS
DIESEL WITH AC SWING CONTROL
BI379615 TEMPORARY x 1V &-r:et."1:70"'JL" xc::» 1V' 1\I.I:..A.1V"':7.A. X.
4-97
BI379615 ( (
380-W DRAGLINE (LOT 1)
ELECTRICAL SHOP TEST
DIESEL A-C CONTROL
THE PURPOSE OF THESE TESTS IS TO VERIFY THAT THE ELECTRICAL SYSTEM HAS BEEN PROPERLY CONNECTED TO REDUCE COSTLY DELAYS DURING FIELDS 1START-UP.
TABLE OF CONTENTS
I.
II. "380-W STARTING SEQUENCE AND SHUTDOWN"
JEF 2/1.4/77
III. AUXILIARY
IV. TORQUE CONVERTER
V. "CALIBRATION AND ADJUSTNENT PRECEDURE FOR ELECTRONIC_ GOVERJ.JOR" TWIN DISC INC. #221091, 2/22/77
VI. MOTION CONTROL SWING
BI379615
. X-2882
BI379615
The 380-W Walking Dragline is the first of a series of small mining machines which are designed with ease of assembly and disassembly as one of the major features. This not only decreases erection time, but allows a machine to be readily di5assembled and moved to another location.
All electrical connections which cross shipping sections are plug connected to eliminate field wiring requirements and to aid in disassembly. Refer to cable and connection tabulation drawing for a breakdo\m of all plug connected cables. This tabulation can be used for a check-off list or erection and disa-ssembly. (See mechanical for a breakdown of shipping section.)
BI379615
380-W L Introduction
-1-
X-2882
• Thank you very much for reading the preview of the manual.
• You can download the complete manual from: www.heydownloads.com by clicking the link below
• Please note: If there is no response to CLICKING the link, please download this PDF first and then click on it.
CLICK HERE TO DOWNLOAD THE COMPLETE MANUAL
CLICK HERE TO DOWNLOAD THE COMPLETE MANUAL