Changing the Transmitter Settings continued
Changing the process variable(s)
When assigning process variables, the primary mA output is referred to as the primary variable (PV) and the secondary mA output is referred to as the secondary variable (SV). Note: Milliamp output 2 is not available with Series 1000 transmitters. The available process variables for the PV and SV are: • Mass flow • Volume flow • Temperature • Density • Drive Signal You can change the PV and SV with HART Communicator, the display, or ProLink II software.
With a HART Communicator To assign process variables as the PV and SV with a HART Communicator: 1. Press 4, 3, 1, 1. 2. Select “PV is.” 3. Select a process variable (see list above). 4. Press F4 “ENTER.” 5. Press the “Left Arrow.” 6. Press 2. 7. Select “SV is.” 8. Press F4 “ENTER.” 9. Press the Left Arrow. 10. Select a process variable (see list above). 11. Press F4 “ENTER.” 12. Press F2 “SEND.”
68
Series 1000 and 2000 Transmitters with Intrinsically Safe Outputs