Sample Asbestos Report

Page 1

Asbestos Re-Inspection Report A Building, A Hospital Site, Any Town Hospital NHS Trust

Prepared for: Mr A N Other Project Manager Any Town Hospital NHS Trust A Hospital Any Town AN1 0WQ

February 2010

Prepared by: Mr Kevin Hume Oakleaf Technical Services Ltd. 7 Brookfield Moulton Park Northampton NN3 6WL


Oakleaf Technical Services Ltd. 0845 293 7571

Issue 2

Contents Item

Page

Introduction

3

Method of Survey

4

Risk Assessment

5

Survey Information

6

Section 1 Asbestos Material Risk Summary Report Section 2 Asbestos Register Sheets Section 3 No Access Report Section 4 Site Drawings Section 5 Removal and Clearance Information

A Building, A Hospital February 2010

Asbestos Survey Page 2 of 7


Oakleaf Technical Services Ltd. 0845 293 7571

Issue 2

Introduction Further to a request made by Mr A N Other of Any Town Hospital NHS Trust, Oakleaf Technical Services Ltd has completed a re-inspection of previously identified asbestos materials (ACMs) in A Block. A survey report (produced by Aspect Contracts Ltd) was provided by the Trust and used as the base for the re-inspections. All asbestos information has been checked and updated to provide the Trust with accurate and compliant risk assessments. Any caveats from the original reports are still important and should be considered when managing asbestos on the site. The inspections were completed in August of 2010. At the time of the survey, the building was occupied and fully functional. Access to the site was arranged by Mr A N Other who coordinated with local building users and the Estates team. For details of the asbestos contained within this building, see section 1 and 2 of this report.

A Building, A Hospital February 2010

Asbestos Survey Page 3 of 7


Oakleaf Technical Services Ltd. 0845 293 7571

Issue 2

Method of Survey The building was inspected in a professional and methodical manner, using the drawings and existing survey reports provided by the Trust. Access to the site was arranged through Mr A N Other. The survey was carried out in accordance with the Oakleaf Technical Services Ltd in house asbestos survey procedure. This procedure is based upon and meets the requirements of HSG 264 Asbestos: The survey guide. Where possible, all areas of asbestos identified in the previous report have been accessed and their current condition recorded. Material risk assessments for all asbestos containing materials (ACMs) have been produced, to show current levels of damage and subsequent treatments. Recommendations of future actions for each asbestos containing material (ACM) have been provided. Any actions taken must be in full accordance with the Control of Asbestos Regulations 2006 (CAR 2006).

A Building, A Hospital February 2010

Asbestos Survey Page 4 of 7


Oakleaf Technical Services Ltd. 0845 293 7571

Issue 2

Risk Assessment The risk assessment method used is the HSE approved ‘materials risk assessment’, as described in the HSE document HSG 264. This is used to assess all ACMs on a like for like basis, using an algorithm that for each ACM looks at:

Product type – Cement roof sheets or gaskets etc. Extent of damage/deterioration – High or low etc. Surface treatment – Painted, exposed etc. Asbestos type – Chrysotile etc.

Each of these parameters is awarded a score, with the scores then combined to give the final material risk assessment score of between 2 and 12. Materials that do not contain asbestos are not given a score. ACMs with a score of 10 or more should be regarded as high risk with a significant potential to release fibres if disturbed. ACMs with a score between 7 and 9 are regarded as medium risk items. ACMs with a score between 5 and 6 are regarded as low risk items. ACMs with a score of 4 and below are regarded as very low risk items.

A Building, A Hospital February 2010

Asbestos Survey Page 5 of 7


Oakleaf Technical Services Ltd. 0845 293 7571

Issue 2

Survey Information Sealed voids; partitions; cavity walls; behind cladding; behind Asbestos Containing Materials (ACMs); under floorboards; safes/fire cabinets; plant and equipment; above solid ceilings, where to gain access would have caused destruction, have not been surveyed. The extent of the survey did not include items on the surface of or within the ground beneath or adjacent to the survey area. The grounds of the building and inaccessible areas such as under floor ducts, tunnels and sewers have not been assessed. Confined spaces of any kind will not have been accessed. This is not a contaminated land survey. This also applies for re-locatable items held in storage facilities (for example, asbestos gloves in boxes or draws). Representative checks will have been made above suspended ceiling grids where access is available, i.e. where the ceiling tiles were not sealed with paint or fixed with screws/nails. Loft and roof spaces will have only been surveyed where safe access was available. If crawl boards or secure flooring were not present, the area would have been deemed to be unsafe. Flooded basements, pipe runs, troughs or other areas that were covered with water could not be fully assessed. These areas may contain asbestos that is not identified in the survey. Fuse boxes will not have been opened up as they remain ‘live’ and would constitute a safety hazard. Some older type fuse boxes have been known to contain chrysotile asbestos rope used as fuse insulation. It will be necessary to presume that these contain asbestos and investigate the areas with the help of an electrician before any future works are carried out. Fixed items of plant, heaters, services or equipment will not have been surveyed internally, as surveyors are not qualified to shut down, dismantle and restart these items. The survey was limited to the accessible external casings of these items. Oakleaf Technical Services Ltd make every effort to fully survey buildings and rooms, but cannot be held responsible for asbestos products located behind or underneath stored items. This is particularly important in areas of excessive or untidy storage. As a qualified engineer was not present on site, the lift shafts have not been fully inspected. The inspection will have been limited to gaps in-between the lift doors and the lift shaft were lifts are present. Within a survey, Oakleaf Technical Services Ltd will not have removed insulation or its coverings, such as metal or plaster cladding. The inspection will have been carried out where the underlying pipe was visible (normally at areas of damage, flanges or gaskets) and the outer casing of boilers, pipes and other plant machinery.

A Building, A Hospital February 2010

Asbestos Survey Page 6 of 7


Oakleaf Technical Services Ltd. 0845 293 7571

Issue 2

General Comments: Where drawings have been provided by the client, Oakleaf Technical Services Ltd does not accept liability for recording errors due to inaccurate drawings. The results in the survey report relate to prevailing conditions on site at the time of survey. Alterations to the building or to its use and occupancy may affect the accessibility of ACMs contained within. In these circumstances, the report should be reviewed in accordance with HSG227 ‘A comprehensive guide to Managing Asbestos in Premises’. Due to the limitations described above, the survey information should not therefore be solely relied on when undertaking building works. Before any building works, refurbishment or re-wiring etc are undertaken a fully invasive demolition or refurbishment survey must be carried out in the location of the works to ensure that workers are not put at risk.

A Building, A Hospital February 2010

Asbestos Survey Page 7 of 7


Section 1: Asbestos Material Risk Summary Report

Section 1 Oakleaf Technical Services 0845 293 7571


Asbestos Material Risk Summary Report Site: A Hospital Site Block: A Building Accessibility Score

Qty

Materials Risk Score

1

1

3 m2

2 (Very Low)

Chrysotile

1

2

<1 m2

2 (Very Low)

0

Chrysotile

1

1

3 m2

2 (Very Low)

0

0

Chrysotile

1

1

3 m2

2 (Very Low)

1

0

0

Chrysotile

1

1

3 m2

2 (Very Low)

1

0

0

Chrysotile

1

1

3 m2

2 (Very Low)

Floor tiles - Floor

1

0

0

Chrysotile

1

1

4 m2

2 (Very Low)

1/Villa 3 - R14

Floor tiles - Floor

1

0

0

Chrysotile

1

1

4 m2

2 (Very Low)

Identified

1/Villa 3 - R18

Floor tiles - Floor

1

0

0

Chrysotile

1

1

4 m2

2 (Very Low)

Identified

0/Villa 3 - R18

Floor tiles - Floor

1

0

0

Chrysotile

1

1

3 m2

2 (Very Low)

Sample Ref

Inspection

9

Identified

0/Villa 1 - R11

Floor tiles - Floor

1

0

0

Chrysotile

10

Identified

0/Villa 1 - R16

Floor tiles - Floor

1

0

0

9

Identified

0/Villa 1 - R17

Floor tiles - Floor

1

0

9

Identified

0/Villa 1 - R21

Floor tiles - Floor

1

9

Identified

0/Villa 1 - R5

Floor tiles - Floor

5

Identified

0/Villa Floor tiles - Floor 3Cupboar d4

4

Identified

1/Villa 3 - R13

4

Identified

4 5

Section 1 Oakleaf Technical Services 0845 293 7571

Flr/Room Description

Product Damage Treatmt

1651/9

Asbestos Type

Priotity Risk Score

Section 1: Page 2 of 4


Asbestos Material Risk Summary Report Site: A Hospital Site Block: A Building Accessibility Score

Qty

Materials Risk Score

1

1

4 m2

2 (Very Low)

Chrysotile

1

1

3 m2

2 (Very Low)

0

Chrysotile

1

1

4 m2

2 (Very Low)

0

0

Chrysotile

1

1

4 m2

2 (Very Low)

1

0

0

Chrysotile

1

1

3 m2

2 (Very Low)

Floor tiles - Floor

1

0

0

Chrysotile

1

1

4 m2

2 (Very Low)

0/Villa 3 - R8

Floor tiles - Floor

1

0

0

Chrysotile

1

1

3 m2

2 (Very Low)

Identified

1/Villa 3 - R9

Floor tiles - Floor

1

0

0

Chrysotile

1

1

4 m2

2 (Very Low)

5

Identified

0/Villa 3 - R9

Floor tiles - Floor

1

0

0

Chrysotile

1

1

3 m2

2 (Very Low)

8

Identified

0/Villa 1 - Ext

Cement boarding Canopy

1

0

1

Chrysotile

1

1

6 m2

3 (Very Low)

11

Identified

0/Villa 1 - R8

Cistern - Toilet cistern

1

0

0

Amosite

2

2

1 m2

3 (Very Low)

Sample Ref

Inspection

4

Identified

1/Villa 3 - R19

Floor tiles - Floor

1

0

0

Chrysotile

5

Identified

0/Villa 3 - R2

Floor tiles - Floor

1

0

0

4

Identified

1/Villa 3 - R4

Floor tiles - Floor

1

0

4

Identified

1/Villa 3 - R5

Floor tiles - Floor

1

5

Identified

0/Villa 3 - R6

Floor tiles - Floor

4

Identified

1/Villa 3 - R8

5

Identified

4

Section 1 Oakleaf Technical Services 0845 293 7571

Flr/Room Description

Product Damage Treatmt

1651/9

Asbestos Type

Priotity Risk Score

Section 1: Page 3 of 4


Asbestos Material Risk Summary Report Site: A Hospital Site Block: A Building Sample Ref

Inspection

Flr/Room Description

7

Identified

0/Villa 2 - Ext

13

Identified

14

Asbestos Type

Accessibility Score

Qty

Materials Risk Score

1

0

1

Chrysotile

1

1

4 m2

3 (Very Low)

0/Pigger Cement sheeting - Roof y

1

1

1

Chrysotile

1

1

45 m2

4 (Very Low)

Strongly presumed

1/Villa 1 - Ext

Cement Cowl - Roof

1

1

1

Chrysotile

1

0

<1 m2

4 (Very Low)

3

Identified

1/Villa 1 -Loft

Insulation - Insulation on tank

3

2

2

Amosite

2

3

3 m2

9 (Medium)

1

Identified

1/Villa 1 -Loft

Insulation - Residue on tank

2

3

2

Amosite

2

3

4 m2

9 (Medium)

2

Identified

1/Villa 1 -Loft

Debris - Debris on floor

3

3

3

Amosite

2

2

80 m2

11 (High)

Section 1 Oakleaf Technical Services 0845 293 7571

Cement boarding Canopy

Product Damage Treatmt

1651/9

Priotity Risk Score

Section 1: Page 4 of 4


Section 2: Asbestos Register Sheets

Section 2 Oakleaf Technical Services 0845 293 7571


Asbestos Register Sheet Site: A Hospital Site Block: A Building Sample Ref:

12

Floor:

0

RoomNo:

Kitchen

No Photo Available

Description: Bitumen Pad - Under sink Extent: Inspection:

Identified

Last Inspection Date:

08/09/2010

Next Inspection Date:

Asbestos Risk Assessment Material Score

Priority Score

Product Type:

0

Normal Occupant Activity

Damage:

0

Likelihood of Disturbance

Treatment:

0

Human Exposure Potential

Asbestos Type:

0

Maintenance Activity

Material Risk Score:

0

Priority Risk Score:

0

Recommendation No action required. Comments

No Asbestos Detected. No Action Required.

Section 2 Oakleaf Technical Services 0845 293 7571

Report Number: 1651/9 Section 2: Page 1 of 29


Asbestos Register Sheet Site: A Hospital Site Block: A Building Sample Ref:

6

Floor:

1

RoomNo:

Loft

No Photo Available

Description: Debris - Debris inside tank Extent: Inspection:

Identified

Last Inspection Date:

08/09/2010

Next Inspection Date:

Asbestos Risk Assessment Material Score

Priority Score

Product Type:

0

Normal Occupant Activity

Damage:

0

Likelihood of Disturbance

Treatment:

0

Human Exposure Potential

Asbestos Type:

0

Maintenance Activity

Material Risk Score:

0

Priority Risk Score:

0

Recommendation No action required. Comments

No Asbestos Detected. No Action Required.

Section 2 Oakleaf Technical Services 0845 293 7571

Report Number: 1651/9 Section 2: Page 2 of 29


Asbestos Register Sheet Site: A Hospital Site Block: A Building Sample Ref:

13

Floor:

0

RoomNo:

Piggery

No Photo Available

Description: Cement sheeting - Roof 45 m2

Extent: Inspection:

Identified

Last Inspection Date:

30/06/2010

Next Inspection Date:

30/06/2011

Asbestos Risk Assessment Material Score

Priority Score

Product Type:

1

Cement

Normal Occupant Activity

Damage:

1

Low Damage

Likelihood of Disturbance

Treatment:

1

Asbestos Cement

Human Exposure Potential

Asbestos Type:

1

Chrysotile

Maintenance Activity

Material Risk Score:

4

Very Low

Priority Risk Score:

0

Recommendation Remove and Clean. Comments Little used building to the rear of the site.

Section 2 Oakleaf Technical Services 0845 293 7571

Report Number: 1651/9 Section 2: Page 3 of 29


Asbestos Register Sheet Site: A Hospital Site Block: A Building Sample Ref:

8

Floor:

0

RoomNo:

Villa 1 - Ext

No Photo Available

Description: Cement boarding - Canopy 6 m2

Extent: Inspection:

Identified

Last Inspection Date:

30/06/2010

Next Inspection Date:

30/06/2011

Asbestos Risk Assessment Material Score

Priority Score

Product Type:

1

Cement

Normal Occupant Activity

Damage:

0

Good Condition

Likelihood of Disturbance

Treatment:

1

Asbestos Cement

Human Exposure Potential

Asbestos Type:

1

Chrysotile

Maintenance Activity

Material Risk Score:

3

Very Low

Priority Risk Score:

0

Recommendation Label and Manage. Comments Soffits above entrance to Villa 1.

Section 2 Oakleaf Technical Services 0845 293 7571

Report Number: 1651/9 Section 2: Page 4 of 29


Asbestos Register Sheet Site: A Hospital Site Block: A Building Sample Ref:

14

Floor:

1

RoomNo:

Villa 1 - Ext

No Photo Available

Description: Cement Cowl - Roof <1 m2

Extent: Inspection:

Strongly presumed

Last Inspection Date:

30/06/2010

Next Inspection Date:

30/06/2011

Asbestos Risk Assessment Material Score

Priority Score

Product Type:

1

Cement

Normal Occupant Activity

Damage:

1

Low Damage

Likelihood of Disturbance

Treatment:

1

Asbestos Cement

Human Exposure Potential

Asbestos Type:

1

Chrysotile

Maintenance Activity

Material Risk Score:

4

Very Low

Priority Risk Score:

0

Recommendation Manage Only. Comments High level cowl on roof.

Section 2 Oakleaf Technical Services 0845 293 7571

Report Number: 1651/9 Section 2: Page 5 of 29


Asbestos Register Sheet Site: A Hospital Site Block: A Building Sample Ref:

9

Floor:

0

RoomNo:

Villa 1 - R11

No Photo Available

Description: Floor tiles - Floor 3 m2

Extent: Inspection:

Identified

Last Inspection Date:

30/06/2010

Next Inspection Date:

30/06/2011

Asbestos Risk Assessment Material Score

Priority Score

Product Type:

1

Reinforced Composite

Normal Occupant Activity

Damage:

0

Good Condition

Likelihood of Disturbance

Treatment:

0

Composite Material

Human Exposure Potential

Asbestos Type:

1

Chrysotile

Maintenance Activity

Material Risk Score:

2

Very Low

Priority Risk Score:

0

Recommendation Manage Only. Comments Asbestos floor tiles and bitumen adhesive in cupboard.

Section 2 Oakleaf Technical Services 0845 293 7571

Report Number: 1651/9 Section 2: Page 6 of 29


Asbestos Register Sheet Site: A Hospital Site Block: A Building Sample Ref:

10

Floor:

0

RoomNo:

Villa 1 - R16

No Photo Available

Description: Floor tiles - Floor <1 m2

Extent: Inspection:

Identified

Last Inspection Date:

30/06/2010

Next Inspection Date:

30/06/2011

Asbestos Risk Assessment Material Score

Priority Score

Product Type:

1

Reinforced Composite

Normal Occupant Activity

Damage:

0

Good Condition

Likelihood of Disturbance

Treatment:

0

Composite Material

Human Exposure Potential

Asbestos Type:

1

Chrysotile

Maintenance Activity

Material Risk Score:

2

Very Low

Priority Risk Score:

0

Recommendation Manage Only. Comments Asbestos floor tiles.

Section 2 Oakleaf Technical Services 0845 293 7571

Report Number: 1651/9 Section 2: Page 7 of 29


Asbestos Register Sheet Site: A Hospital Site Block: A Building Sample Ref:

9

Floor:

0

RoomNo:

Villa 1 - R17

No Photo Available

Description: Floor tiles - Floor 3 m2

Extent: Inspection:

Identified

Last Inspection Date:

30/06/2010

Next Inspection Date:

30/06/2011

Asbestos Risk Assessment Material Score

Priority Score

Product Type:

1

Reinforced Composite

Normal Occupant Activity

Damage:

0

Good Condition

Likelihood of Disturbance

Treatment:

0

Composite Material

Human Exposure Potential

Asbestos Type:

1

Chrysotile

Maintenance Activity

Material Risk Score:

2

Very Low

Priority Risk Score:

0

Recommendation Manage Only. Comments Asbestos floor tiles and bitumen adhesive in cupboard.

Section 2 Oakleaf Technical Services 0845 293 7571

Report Number: 1651/9 Section 2: Page 8 of 29


Asbestos Register Sheet Site: A Hospital Site Block: A Building Sample Ref:

9

Floor:

0

RoomNo:

Villa 1 - R21

No Photo Available

Description: Floor tiles - Floor 3 m2

Extent: Inspection:

Identified

Last Inspection Date:

30/06/2010

Next Inspection Date:

30/06/2011

Asbestos Risk Assessment Material Score

Priority Score

Product Type:

1

Reinforced Composite

Normal Occupant Activity

Damage:

0

Good Condition

Likelihood of Disturbance

Treatment:

0

Composite Material

Human Exposure Potential

Asbestos Type:

1

Chrysotile

Maintenance Activity

Material Risk Score:

2

Very Low

Priority Risk Score:

0

Recommendation Manage Only. Comments Asbestos floor tiles and bitumen adhesive in cupboard.

Section 2 Oakleaf Technical Services 0845 293 7571

Report Number: 1651/9 Section 2: Page 9 of 29


Asbestos Register Sheet Site: A Hospital Site Block: A Building Sample Ref:

9

Floor:

0

RoomNo:

Villa 1 - R5

No Photo Available

Description: Floor tiles - Floor 3 m2

Extent: Inspection:

Identified

Last Inspection Date:

30/06/2010

Next Inspection Date:

30/06/2011

Asbestos Risk Assessment Material Score

Priority Score

Product Type:

1

Reinforced Composite

Normal Occupant Activity

Damage:

0

Good Condition

Likelihood of Disturbance

Treatment:

0

Composite Material

Human Exposure Potential

Asbestos Type:

1

Chrysotile

Maintenance Activity

Material Risk Score:

2

Very Low

Priority Risk Score:

0

Recommendation Manage Only. Comments Asbestos floor tiles and bitumen adhesive in cupboard.

Section 2 Oakleaf Technical Services 0845 293 7571

Report Number: 1651/9 Section 2: Page 10 of 29


Asbestos Register Sheet Site: A Hospital Site Block: A Building Sample Ref:

11

Floor:

0

RoomNo:

Villa 1 - R8

No Photo Available

Description: Cistern - Toilet cistern 1 m2

Extent: Inspection:

Identified

Last Inspection Date:

30/06/2010

Next Inspection Date:

30/06/2011

Asbestos Risk Assessment Material Score

Priority Score

Product Type:

1

Reinforced Composite

Normal Occupant Activity

Damage:

0

Good Condition

Likelihood of Disturbance

Treatment:

0

Composite Material

Human Exposure Potential

Asbestos Type:

2

Amosite

Maintenance Activity

Material Risk Score:

3

Very Low

Priority Risk Score:

0

Recommendation Manage Only. Comments Low level toilet cistern.

Section 2 Oakleaf Technical Services 0845 293 7571

Report Number: 1651/9 Section 2: Page 11 of 29


Asbestos Register Sheet Site: A Hospital Site Block: A Building Sample Ref:

1

Floor:

1

RoomNo:

Villa 1 -Loft

No Photo Available

Description: Insulation - Residue on tank 4 m2

Extent: Inspection:

Identified

Last Inspection Date:

30/06/2010

Next Inspection Date:

30/06/2011

Asbestos Risk Assessment Material Score

Priority Score

Product Type:

2

Insulation Board

Normal Occupant Activity

Damage:

3

High Damage

Likelihood of Disturbance

Treatment:

2

Unsealed AIB/Encapsul

Human Exposure Potential

Asbestos Type:

2

Amosite

Maintenance Activity

Material Risk Score:

9

Medium

Priority Risk Score:

0

Recommendation Remove and Clean. Comments Asbestos debris found on water tank. Access to this area must be prohibited until clearance certificates are available.

Section 2 Oakleaf Technical Services 0845 293 7571

Report Number: 1651/9 Section 2: Page 12 of 29


Asbestos Register Sheet Site: A Hospital Site Block: A Building Sample Ref:

2

Floor:

1

RoomNo:

Villa 1 -Loft

No Photo Available

Description: Debris - Debris on floor 80 m2

Extent: Inspection:

Identified

Last Inspection Date:

30/06/2010

Next Inspection Date:

30/06/2011

Asbestos Risk Assessment Material Score

Priority Score

Product Type:

3

Thermal Insulation

Normal Occupant Activity

Damage:

3

High Damage

Likelihood of Disturbance

Treatment:

3

Unsealed Lagging and

Human Exposure Potential

Asbestos Type:

2

Amosite

Maintenance Activity

Material Risk Score:

11

High

Priority Risk Score:

0

Recommendation Remove and Clean. Comments Insulation debris found within the lift space. Access to this area must be prohibited until clearance certificates are available.

Section 2 Oakleaf Technical Services 0845 293 7571

Report Number: 1651/9 Section 2: Page 13 of 29


Asbestos Register Sheet Site: A Hospital Site Block: A Building Sample Ref:

3

Floor:

1

RoomNo:

Villa 1 -Loft

No Photo Available

Description: Insulation - Insulation on tank 3 m2

Extent: Inspection:

Identified

Last Inspection Date:

30/06/2010

Next Inspection Date:

30/06/2011

Asbestos Risk Assessment Material Score

Priority Score

Product Type:

3

Thermal Insulation

Normal Occupant Activity

Damage:

2

Medium Damage

Likelihood of Disturbance

Treatment:

2

Unsealed AIB/Encapsul

Human Exposure Potential

Asbestos Type:

2

Amosite

Maintenance Activity

Material Risk Score:

9

Medium

Priority Risk Score:

0

Recommendation Remove and Clean. Comments Asbestos insulation has been applied to the water tank. Access to this area must be prohibited until clearance certificates are available.

Section 2 Oakleaf Technical Services 0845 293 7571

Report Number: 1651/9 Section 2: Page 14 of 29


Asbestos Register Sheet Site: A Hospital Site Block: A Building Sample Ref:

7

Floor:

0

RoomNo:

Villa 2 - Ext

No Photo Available

Description: Cement boarding - Canopy 4 m2

Extent: Inspection:

Identified

Last Inspection Date:

30/06/2010

Next Inspection Date:

30/06/2011

Asbestos Risk Assessment Material Score

Priority Score

Product Type:

1

Cement

Normal Occupant Activity

Damage:

0

Good Condition

Likelihood of Disturbance

Treatment:

1

Asbestos Cement

Human Exposure Potential

Asbestos Type:

1

Chrysotile

Maintenance Activity

Material Risk Score:

3

Very Low

Priority Risk Score:

0

Recommendation Manage Only. Comments Soffits above entrance to Villa 2 have been painted and labelled.

Section 2 Oakleaf Technical Services 0845 293 7571

Report Number: 1651/9 Section 2: Page 15 of 29


Asbestos Register Sheet Site: A Hospital Site Block: A Building Sample Ref:

5

Floor:

0

RoomNo: Villa 3 - Cupboard 4

No Photo Available

Description: Floor tiles - Floor 3 m2

Extent: Inspection:

Identified

Last Inspection Date:

30/06/2010

Next Inspection Date:

30/06/2011

Asbestos Risk Assessment Material Score

Priority Score

Product Type:

1

Reinforced Composite

Normal Occupant Activity

Damage:

0

Good Condition

Likelihood of Disturbance

Treatment:

0

Composite Material

Human Exposure Potential

Asbestos Type:

1

Chrysotile

Maintenance Activity

Material Risk Score:

2

Very Low

Priority Risk Score:

0

Recommendation Manage Only. Comments Asbestos floor tiles to cupboard.

Section 2 Oakleaf Technical Services 0845 293 7571

Report Number: 1651/9 Section 2: Page 16 of 29


Asbestos Register Sheet Site: A Hospital Site Block: A Building Sample Ref:

4

Floor:

1

RoomNo:

Villa 3 - R13

No Photo Available

Description: Floor tiles - Floor 4 m2

Extent: Inspection:

Identified

Last Inspection Date:

30/06/2010

Next Inspection Date:

30/06/2011

Asbestos Risk Assessment Material Score

Priority Score

Product Type:

1

Reinforced Composite

Normal Occupant Activity

Damage:

0

Good Condition

Likelihood of Disturbance

Treatment:

0

Composite Material

Human Exposure Potential

Asbestos Type:

1

Chrysotile

Maintenance Activity

Material Risk Score:

2

Very Low

Priority Risk Score:

0

Recommendation Manage Only. Comments Asbestos floor tiles to cupboard.

Section 2 Oakleaf Technical Services 0845 293 7571

Report Number: 1651/9 Section 2: Page 17 of 29


Asbestos Register Sheet Site: A Hospital Site Block: A Building Sample Ref:

4

Floor:

1

RoomNo:

Villa 3 - R14

No Photo Available

Description: Floor tiles - Floor 4 m2

Extent: Inspection:

Identified

Last Inspection Date:

30/06/2010

Next Inspection Date:

30/06/2011

Asbestos Risk Assessment Material Score

Priority Score

Product Type:

1

Reinforced Composite

Normal Occupant Activity

Damage:

0

Good Condition

Likelihood of Disturbance

Treatment:

0

Composite Material

Human Exposure Potential

Asbestos Type:

1

Chrysotile

Maintenance Activity

Material Risk Score:

2

Very Low

Priority Risk Score:

0

Recommendation Manage Only. Comments Asbestos floor tiles to cupboard.

Section 2 Oakleaf Technical Services 0845 293 7571

Report Number: 1651/9 Section 2: Page 18 of 29


Asbestos Register Sheet Site: A Hospital Site Block: A Building Sample Ref:

5

Floor:

0

RoomNo:

Villa 3 - R18

No Photo Available

Description: Floor tiles - Floor 3 m2

Extent: Inspection:

Identified

Last Inspection Date:

30/06/2010

Next Inspection Date:

30/06/2011

Asbestos Risk Assessment Material Score

Priority Score

Product Type:

1

Reinforced Composite

Normal Occupant Activity

Damage:

0

Good Condition

Likelihood of Disturbance

Treatment:

0

Composite Material

Human Exposure Potential

Asbestos Type:

1

Chrysotile

Maintenance Activity

Material Risk Score:

2

Very Low

Priority Risk Score:

0

Recommendation Manage Only. Comments Asbestos floor tiles to cupboard.

Section 2 Oakleaf Technical Services 0845 293 7571

Report Number: 1651/9 Section 2: Page 19 of 29


Asbestos Register Sheet Site: A Hospital Site Block: A Building Sample Ref:

4

Floor:

1

RoomNo:

Villa 3 - R18

No Photo Available

Description: Floor tiles - Floor 4 m2

Extent: Inspection:

Identified

Last Inspection Date:

30/06/2010

Next Inspection Date:

30/06/2011

Asbestos Risk Assessment Material Score

Priority Score

Product Type:

1

Reinforced Composite

Normal Occupant Activity

Damage:

0

Good Condition

Likelihood of Disturbance

Treatment:

0

Composite Material

Human Exposure Potential

Asbestos Type:

1

Chrysotile

Maintenance Activity

Material Risk Score:

2

Very Low

Priority Risk Score:

0

Recommendation Manage Only. Comments Asbestos floor tiles to cupboard.

Section 2 Oakleaf Technical Services 0845 293 7571

Report Number: 1651/9 Section 2: Page 20 of 29


Asbestos Register Sheet Site: A Hospital Site Block: A Building Sample Ref:

4

Floor:

1

RoomNo:

Villa 3 - R19

No Photo Available

Description: Floor tiles - Floor 4 m2

Extent: Inspection:

Identified

Last Inspection Date:

30/06/2010

Next Inspection Date:

30/06/2011

Asbestos Risk Assessment Material Score

Priority Score

Product Type:

1

Reinforced Composite

Normal Occupant Activity

Damage:

0

Good Condition

Likelihood of Disturbance

Treatment:

0

Composite Material

Human Exposure Potential

Asbestos Type:

1

Chrysotile

Maintenance Activity

Material Risk Score:

2

Very Low

Priority Risk Score:

0

Recommendation Manage Only. Comments Asbestos floor tiles to cupboard.

Section 2 Oakleaf Technical Services 0845 293 7571

Report Number: 1651/9 Section 2: Page 21 of 29


Asbestos Register Sheet Site: A Hospital Site Block: A Building Sample Ref:

5

Floor:

0

RoomNo:

Villa 3 - R2

No Photo Available

Description: Floor tiles - Floor 3 m2

Extent: Inspection:

Identified

Last Inspection Date:

30/06/2010

Next Inspection Date:

30/06/2011

Asbestos Risk Assessment Material Score

Priority Score

Product Type:

1

Reinforced Composite

Normal Occupant Activity

Damage:

0

Good Condition

Likelihood of Disturbance

Treatment:

0

Composite Material

Human Exposure Potential

Asbestos Type:

1

Chrysotile

Maintenance Activity

Material Risk Score:

2

Very Low

Priority Risk Score:

0

Recommendation Manage Only. Comments Asbestos floor tiles to cupboard.

Section 2 Oakleaf Technical Services 0845 293 7571

Report Number: 1651/9 Section 2: Page 22 of 29


Asbestos Register Sheet Site: A Hospital Site Block: A Building Sample Ref:

4

Floor:

1

RoomNo:

Villa 3 - R4

No Photo Available

Description: Floor tiles - Floor 4 m2

Extent: Inspection:

Identified

Last Inspection Date:

30/06/2010

Next Inspection Date:

30/06/2011

Asbestos Risk Assessment Material Score

Priority Score

Product Type:

1

Reinforced Composite

Normal Occupant Activity

Damage:

0

Good Condition

Likelihood of Disturbance

Treatment:

0

Composite Material

Human Exposure Potential

Asbestos Type:

1

Chrysotile

Maintenance Activity

Material Risk Score:

2

Very Low

Priority Risk Score:

0

Recommendation Manage Only. Comments Asbestos floor tiles to cupboard.

Section 2 Oakleaf Technical Services 0845 293 7571

Report Number: 1651/9 Section 2: Page 23 of 29


Asbestos Register Sheet Site: A Hospital Site Block: A Building Sample Ref:

4

Floor:

1

RoomNo:

Villa 3 - R5

No Photo Available

Description: Floor tiles - Floor 4 m2

Extent: Inspection:

Identified

Last Inspection Date:

30/06/2010

Next Inspection Date:

30/06/2011

Asbestos Risk Assessment Material Score

Priority Score

Product Type:

1

Reinforced Composite

Normal Occupant Activity

Damage:

0

Good Condition

Likelihood of Disturbance

Treatment:

0

Composite Material

Human Exposure Potential

Asbestos Type:

1

Chrysotile

Maintenance Activity

Material Risk Score:

2

Very Low

Priority Risk Score:

0

Recommendation Manage Only. Comments Asbestos floor tiles to cupboard.

Section 2 Oakleaf Technical Services 0845 293 7571

Report Number: 1651/9 Section 2: Page 24 of 29


Asbestos Register Sheet Site: A Hospital Site Block: A Building Sample Ref:

5

Floor:

0

RoomNo:

Villa 3 - R6

No Photo Available

Description: Floor tiles - Floor 3 m2

Extent: Inspection:

Identified

Last Inspection Date:

30/06/2010

Next Inspection Date:

30/06/2011

Asbestos Risk Assessment Material Score

Priority Score

Product Type:

1

Reinforced Composite

Normal Occupant Activity

Damage:

0

Good Condition

Likelihood of Disturbance

Treatment:

0

Composite Material

Human Exposure Potential

Asbestos Type:

1

Chrysotile

Maintenance Activity

Material Risk Score:

2

Very Low

Priority Risk Score:

0

Recommendation Manage Only. Comments Asbestos floor tiles to cupboard.

Section 2 Oakleaf Technical Services 0845 293 7571

Report Number: 1651/9 Section 2: Page 25 of 29


Asbestos Register Sheet Site: A Hospital Site Block: A Building Sample Ref:

5

Floor:

0

RoomNo:

Villa 3 - R8

No Photo Available

Description: Floor tiles - Floor 3 m2

Extent: Inspection:

Identified

Last Inspection Date:

30/06/2010

Next Inspection Date:

30/06/2011

Asbestos Risk Assessment Material Score

Priority Score

Product Type:

1

Reinforced Composite

Normal Occupant Activity

Damage:

0

Good Condition

Likelihood of Disturbance

Treatment:

0

Composite Material

Human Exposure Potential

Asbestos Type:

1

Chrysotile

Maintenance Activity

Material Risk Score:

2

Very Low

Priority Risk Score:

0

Recommendation Manage Only. Comments Asbestos floor tiles to cupboard.

Section 2 Oakleaf Technical Services 0845 293 7571

Report Number: 1651/9 Section 2: Page 26 of 29


Asbestos Register Sheet Site: A Hospital Site Block: A Building Sample Ref:

4

Floor:

1

RoomNo:

Villa 3 - R8

No Photo Available

Description: Floor tiles - Floor 4 m2

Extent: Inspection:

Identified

Last Inspection Date:

30/06/2010

Next Inspection Date:

30/06/2011

Asbestos Risk Assessment Material Score

Priority Score

Product Type:

1

Reinforced Composite

Normal Occupant Activity

Damage:

0

Good Condition

Likelihood of Disturbance

Treatment:

0

Composite Material

Human Exposure Potential

Asbestos Type:

1

Chrysotile

Maintenance Activity

Material Risk Score:

2

Very Low

Priority Risk Score:

0

Recommendation Manage Only. Comments Asbestos floor tiles to cupboard.

Section 2 Oakleaf Technical Services 0845 293 7571

Report Number: 1651/9 Section 2: Page 27 of 29


Asbestos Register Sheet Site: A Hospital Site Block: A Building Sample Ref:

5

Floor:

0

RoomNo:

Villa 3 - R9

No Photo Available

Description: Floor tiles - Floor 3 m2

Extent: Inspection:

Identified

Last Inspection Date:

30/06/2010

Next Inspection Date:

30/06/2011

Asbestos Risk Assessment Material Score

Priority Score

Product Type:

1

Reinforced Composite

Normal Occupant Activity

Damage:

0

Good Condition

Likelihood of Disturbance

Treatment:

0

Composite Material

Human Exposure Potential

Asbestos Type:

1

Chrysotile

Maintenance Activity

Material Risk Score:

2

Very Low

Priority Risk Score:

0

Recommendation Manage Only. Comments Asbestos floor tiles to cupboard.

Section 2 Oakleaf Technical Services 0845 293 7571

Report Number: 1651/9 Section 2: Page 28 of 29


Asbestos Register Sheet Site: A Hospital Site Block: A Building Sample Ref:

4

Floor:

1

RoomNo:

Villa 3 - R9

No Photo Available

Description: Floor tiles - Floor 4 m2

Extent: Inspection:

Identified

Last Inspection Date:

30/06/2010

Next Inspection Date:

30/06/2011

Asbestos Risk Assessment Material Score

Priority Score

Product Type:

1

Reinforced Composite

Normal Occupant Activity

Damage:

0

Good Condition

Likelihood of Disturbance

Treatment:

0

Composite Material

Human Exposure Potential

Asbestos Type:

1

Chrysotile

Maintenance Activity

Material Risk Score:

2

Very Low

Priority Risk Score:

0

Recommendation Manage Only. Comments Asbestos floor tiles to cupboard.

Section 2 Oakleaf Technical Services 0845 293 7571

Report Number: 1651/9 Section 2: Page 29 of 29


Section 3: No Access Areas Report

Section 3 Oakleaf Technical Services 0845 293 7571


Asbestos No Access Areas Report Site: A Hospital Site Block: A Building Floor:

RoomNo:

Comments:

Recommendations:

Ext

High level access.

Further Investigation.

0

Villa 1 R7

Access could still not be gained into the cupboard.

Further Investigation.

1

Loft Villa 3

Limited access; loft space.

Further Investigation.

Section 3 Oakleaf Technical Services 0845 293 7571

Section 3: Page 2 of 2



Issuu converts static files into: digital portfolios, online yearbooks, online catalogs, digital photo albums and more. Sign up and create your flipbook.