Palantir Pavilion
Occupant Load Determination
Promenade 86,7270 Davos, Switzerland Construction Type: Type III (SIPs Shell and Wood Framing) Building Classification: Business & Assembly Gross Floor Area (NFPA 101 3.3.21.2.1.): 3,967 sq ft
-. --
-. --
-. --. --
Fire and Life Safety Plan 4
Coat Closet
Coffee Bar
5
6
7
8
9
Meeting Room A3
Meeting Room
A3
ø 5' - 0"
Longest Path of Egress Travel: 72' 11"
ø 5' - 0"
5' - 5 1/4"
A3
Entry
1 hr
Large Phone Room A3
Storage Accs
4' - 4 1/4"
Demo Space A3
ø 5' - 0"
Phone Room A3
Restroom
6' - 3 3/4"
Isolated Lounge Area A3
N/A
Large Meeting Room A3
ø 5' - 0" UP
B
1 hr
Floating Seating (Day)/Invite Only Event (Night)
A3
A 1
A1-Plan FireSafety 1/8" = 1'-0"
1
2
3
4
5
6
7
8
9
10 FIRE/LIFE SAFETY SHEET NOTES: ENSURE MINIMUM LIGHT LEVELS AND BACK UP POWER SUPPLY FOR EXIT LIGHTS
D
COORDINATE FIRE SAFETY WITH MECHANICAL AND HVAC REQUIREMENTS ELECTRICAL, PLUMBING, AND ARCHITECTURAL DRAWINGS.
Phone Room A3 Food Prep/Circulation A2
Team Workspace B1
1 hr ø 5' - 0" 9' - 9 1/4"
6' - 0"
ø 5' - 0"
C
REFER TO A0.02 REGARDING FURTHER ADA AND EGRESS DETAILS. INSTALL PANIC HARDWARE ON ALL EXTERIOR DOORS.
Overall 2502 SF 31274.21 CF
Restroom N/A
Hang Out A3
Communication Hub Accs
Life Safety Plan Legend Main Evacuation Secondary Evacuation Longest Path Sprinkler Smoke Detector Exit Signs
Longest Path of Egress Travel: 70' 10-1/8"
UP
B
Meeting Area A3
1 hr
SD
Fire Extinguisher 1hr
A 2
A1 A1 A1 A1 A1 A1 A1 A1 A1 A1 A1 A1 A0 A0 A0 A0 A0 A0 A0
Factor (Day)
Load (Day)
Factor (Night) Load (Night) Egress Width Total
A3 A3 A3 Accs Accs A3
77 SF 90 SF 49 SF 43 SF 34 SF 468 SF
7 7 7 300 300 15
12 13 7 1 1 32
7 7 7 300 300 7
12 13 7 1 1 67
0' - 4 3/8" 0' - 4 5/8" 0' - 2 1/2" 0' - 0 3/8" 0' - 0 3/8" 2' - 0 1/8"
A3 A2 A3 A3 A3 A3 A3 A3 A3 A3 N/A N/A A3 A3 A2 Accs A3 B1 N/A
304 SF 271 SF 92 SF 17 SF 75 SF 51 SF 74 SF 58 SF 114 SF 80 SF 43 SF 392 SF 279 SF 299 SF 331 SF 39 SF 41 SF 230 SF 75 SF 3626 SF
15 15 15 15 15 15 15 15 15 15 0 0 15 15 200 300 15 100 0
21 19 7 2 6 4 5 4 8 6
7 15 15 15 15 15 15 15 15 15 0 0 15 15 200 300 15 100 0
44 19 7 2 6 4 5 4 8 6
1' - 3 7/8" 0' - 6 7/8" 0' - 2 1/2" 0' - 0 3/4" 0' - 2 1/8" 0' - 1 1/2" 0' - 1 3/4" 0' - 1 1/2" 0' - 2 7/8" 0' - 2 1/8"
19 20 2 1 3 3
0' - 6 7/8" 0' - 7 1/4" 0' - 0 3/4" 0' - 0 3/8" 0' - 1 1/8" 0' - 1 1/8"
254
7' - 7 1/4"
19 20 2 1 3 3 196
10
3' - 0"
C
Meeting Room A3
A3
3' - 5 1/2"
6' - 8 1/2"
ø 5' - 0"
Open Lounge Area
ø 5' - 0"
A2
Entry Vestibule A3
A3
7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25
Entry Vestibule Entry Concierge Coat Closet Storage Floating Seating (Day)/Invite Only Event (Night) Demo Space Coffee Bar Meeting Room Phone Room Open Lounge Area Large Phone Room Meeting Room Meeting Room Large Meeting Room Isolated Lounge Area Restroom Transition/Circulation Hang Out Meeting Area Food Prep/Circulation Communication Hub Phone Room Team Workspace Restroom
Area
CoverSheet Notes/Symbols CodeReference A1 Plans A0 Plans A1 RCP A0 RCP Mechanical/HVAC Electrical/PowerComm Plumbing Furniture Plan Finish Plans Detail_Contour Construction Detail_Wall System Conditions Detail_Stairs Detail_Millwork_Coffee Detail_FirePlace Detail_Lighting Fixtures Detail_Entry OPEN
A0.00 A0.01 A0.02 A1.00 A1.01 A1.02 A1.03 A1.04 A1.05 A1.06 A1.07 A1.08 A5.00 A5.01 A5.02 A5.03 A5.04 A5.06 A5.07 z OPEN
design team: xie maggie hill lilli geen
consulting: allison gaskins marla smith
Project Description
1 hr
Concierge
A1 A1 A1 A1 A1 A1
Occu.
Site Diagram 1" = 60'-0"
6' - 0"
Accs
1 2 3 4 5 6
Room
Code Analysis
3
D
Lvl.
Sheet #
1hr
Wall/Door Ratings
OCCUPANCY COUNTS FLOOR A0: Area: 1442 sq ft Occupant Load: Business-1 and Assembly-3 (see chart) FLOOR A1: Area: 2451 sq ft Occupant Load: Business-1 and Assembly-3 (see chart) EXIT ACCESS MEANS OF EGRESS SIZING (2012 IBC SECTION 1005): The total width of means of egress in inches shall not be less than the total occupant load served multiplied by the factors listed in sections 1005.3.1 and 1005.3.2 and not less than the minimums specified for egress components. Multiple means of egress shall be sized such that the loss of any one means of egress shall not reduce the available capacity to less than 50 percent of the required capacity. EGRESS WIDTH PER OCCUPANT SERVED: Occupancies other than h-1, h-2, h-3, h-4, and i-2 (without automatic sprinkler system and emergency voice/alarm communication system) stairways 0.3 and other egress components 0.2 (inches per occupant) OTHER EGRESS COMPONENTS (2012 IBC SECTION 1005.3.2): Exit width doors required for occupancies without automatic sprinkler and emergency voice/alarm systems: 12 x 0.3=3.6" Exit width doors provided are (72”/door x 1 doors + 36"/door x 2 door)= 144” “32” min door opening per 2012 IBC sec 1008.1.1 DOOR ENCROACHMENT (2012 IBC 1005.7): Doors opening into the path of egress travel shall not reduce the required width to less than one-half during the course of the swing. When fully open, the door shall not project more than 7 inches into the required width. EXIT OR EXIT ACCESS DOORWAYS REQUIRED (2012 IBC 1015.1 AND TABLE 1015.1): Two exits or exit access doorways from any space shall be provided where one of the following conditions exists: 1.1. the occupant load of the space exceeds the following: occupancy group B = 49 occupants. (49 x100 = 4,900 SF) 1.2. the common path of egress travel exceeds the limitations of section 1014.3. 1.3. where required by sections 1015.3, 1015.4, 1015.5, or 1015.6. EXIT ACCESS TRAVEL DISTANCE (2012 IBC TABLE 1016.2): occupancy B – 200’-0” without automatic sprinkler system. AISLES (2012 IBC 1017.3): In group B and M occupancies, the minimum clear aisle width shall be determined by section 1005.1 for the occupant load served, but shall not be less than 36". exception** non-public aisles serving less than 50 people, and not required to be accessible by chapter 11 need to exceed 28" in width. CORRIDOR WIDTH (2012 IBC 1018.2): The minimum corridor width specified in table 1018.2 shall be as determined in section 1005.1. The typical width is 44" min. minimum width is 36" for areas with a required occupant capacity of less than 50. PER SECTION 1005.1: Tenant space = min 44” 12 x 0.2= 2.4" (floor 1) DEAD END CORRIDOR (2012 IBC 1018.4): Where more than one exit or exit access doorway is required, the exit access shall be arranged such that no dead ends in corridors exceed 20’-0” in length. MINIMUM NUMBER OF EXITS (2012 IBC SECTION 1021.2): Occupant load 1-500 (1st floor) = 3 exits per floor Occupant load 1-500 (1st floor) = 3 exits per floor
5 day Pavilion Construction PROJECT NAME Palantir Pavilion Promenade 86,7270 Davos, Switzerland OWNER Palantir Technologies JURISDICTION FOR STUDIO: Travis County, City of Austin OCCUPANCY Construction Type: Type III (SIPs Shell and Wood Framing) Building Occupancy: Business & Assembly FULLY SPRINKLERED: Yes
Applicable Building Code (Local Amendments May Apply) 2012 International Building Code 2011 International Electrical Code 2012 International Mechanical Code 2012 International Plumbing Code 2006 International Fire Code 2009 International Energy Conservation Code 2012 TAS- State of Texas Accessibility Standards
palantir pavillion promenade 86, 7270 davos
3
2
Sheet Name
Room Occupancy Load Schedule #
1
Index of Drawings
Fire/Life Safety BUILDING CHARACTERISTICS Occupied Levels Below Grade: Level A0 Unoccupied Levels Below Grade: N/A Occupied Levels Above Grade: Level A1 Unoccupied Levels Above Grade: N/A BUILDING AREA Gross Floor Area (NFPA 101 3.3.21.2.1.): 3,967 sq ft Net Floor Area (NFPA 101-3.3.21.2.2/IBC Section 202: 3893 sq ft Occupiable Area (NFPA 101-3.3.21.7): 3893 sq ft BUILDING HEIGHT ABOVE GRADE (IBC Section 502.1 for Definition): 14' 0" HIGH RISE BUILDING: No ATRIUM: No FIRE PROTECTION SYSTEMS: Automatic Sprinkler System (IBC 903): Yes Alternate Automatic Fire-Extinguishing Systems (IBC 904): No Stand Pipe System (IBC 905): No Portable Fire Extinguishers (IBC 906): Yes Fire Alarm and Detection System (IBC 907): Yes Emergency Alarm System (IBD 908): No Smoke Control Systems (IBC 909): No Smoke and Heat Vents (IBC 910): No Fire Command Center (IBC 911): No Fire Department Connections (IBC 912): No Fire Pumps (IBC 913): No Emergency Responder Safety Features: Yes Emergency Responder Radio Coverage: No HAZARD OF CONTENTS (NFPA 101-Chapter 6.2.2): Enter One of Following; General PARKING REQUIREMENTS: N/A TRASH AND DUMPSTER SCREENING REQUIREMENTS: N/A
startup:
01/01/2015
scale:
As indicated
A0-Plan FireSafety 1/8" = 1'-0"
A0.00