Indoor unit (R410A) 0CVP0-01A


Indoor unit (R410A) 0CVP0-01A General Information


Indoor unit • Introduction • General Information • Indoor Units • Dip Switch & Group Control Setting


Introduction 1. Preface

is the most favored choice when there is a need for precise air conditioning of relatively big projects extending from Multi-Room structure to big commercial places. We have a big line up, that offers wider flexibility of model selection. Equipped with inverter technology and long piping installation, the product matches well if one talk about optimum power consumption in high rise buildings. Add on capacity feature makes it easy to upgrade the existing capacity at any time. With the growing concern about environment preservation, comes with R410A refrigerant which is environment friendly and thus our system is a high technology and environment friendly product.

Unique refrigerant flow and electronic circuit control gives this system an unique capability to work in extreme/abnormal working conditions making our customer feel great about their decision of selecting LG as their first choice. This publication provides a detailed and in depth information about the design and installation of . We hope that with this information you would become an expert of your

system.

Air-Conditioning Company

General Information

R410A Model


General Information

2. Step by Step (1)

(2)

System Selection Process

Calculate or obtain the maximum heat load for the area(s) to be air conditioned

Decide the indoor unit specifications Decide the outdoor unit specifications Capacity coefficient factor Decide the air velocity and temperature distributions

(3)

(4)

Selection of refrigerant pipe joints and headers

Selection of the control system Control wiring method Description of devices

(5)

Electrical wiring Electric characteristics Field wiring

!

Caution

1. Air conditioners should not be installed in areas where corrosive gas such as acid gas or alkaline gas is produced. 2. If the outdoor unit is installed close to the sea shore, direct exposure to the sea breeze should be avoided and choose an outdoor unit with anti-corrosion treatment.


Indoor unit General Information 1. Model Names 2. External Appearance 3. Nomenclature 4. Indoor Unit Capacity Index


1. Model Names Chassis 5k Name (1.6)

General information Indoor unit

Category

9k (2.8)

12k (3.6)

15k (4.5)

ARNU18G ARNU24G S5*2 S5*2

S5 ARNU07G ARNU09G ARNU12G ARNU15G SE*2 SE*2 SE*2 SE*2

SE Mirror ART COOL

ARNU18G ARNU24G S8*2 S8*2

S8

Gallery

ARNU07G ARNU09G ARNU12G SF*2 SF*2 SF*2 ARNU07G ARNU09G ARNU12G GTU*2 GTU*2 GTU*2

SF TU

1 Way

ARNU18G ARNU24G TT*2 TT*2 ARNU18G ARNU24G TL*2 TL*2

TT 2 Way Ceiling

TL TR

Cassette

ARNU05 ARNU07G ARNU09G ARNU12G GTR*2 TR*2 TR*2 TR*2 ARNU15 ARNU18G GTQ*2 TQ*2

TQ 4 Way

Capacity(Btu/h(kW)) 18k 24k 28k 36k 42k 48k 76k 96k (5.6) (7.1) (8.2) (10.6) (12.3) (14.1) (22.4) (28.0)

ARNU07G ARNU09G ARNU12G ARNU15G SE*2 SE*2 SE*2 SE*2

SE

Wall Mounted (General)

7k (2.2)

ARNU24G ARNU28G TP*2 TP*2

TP

ARNU36G TN*2

TN

ARNU42G ARNU48G TM*2 TM*2

TM BH High Static Ceiling Concealed Duct

ARNU07G ARNU09G ARNU12G ARNU15G ARNU18G ARNU24G BHA2 BHA2 BHA2 BHA2 BHA2 BHA2 ARNU28G ARNU36G ARNU42G BGA2 BGA2 BGA2

BG

ARNU48G BRA2

BR

URNU76G URNU96G B8A2 B8A2

B8 B1 Low Static

ARNU07 GB1G2

ARNU09 GB1G2

ARNU12 GB1G2

ARNU15 GB1G2 ARNU18 GB2G2

B2 B3 Built In

ARNU07G ARNU09G ARNU12G ARNU15G B3G2 B3G2 B3G2 B3G2 ARNU18G ARNU24G B4G2 B4G2

B4 Ceiling & Floor

VE

Ceiling Suspended

VJ CE

With Case

ARNU09G ARNU12G VEA2 VEA2 ARNU18G ARNU24G VJA2 VJA2 ARNU07G ARNU09G ARNU12G ARNU15G CEA2 CEA2 CEA2 CEA2 ARNU18G ARNU24G CFA2 CFA2

CF

Floor Standing

Without Case Console

CE

ARNU07G ARNU09G ARNU12G ARNU15G CEU2 CEU2 CEU2 CEU2 ARNU18G ARNU24G CFU2 CFU2

CF QA BR

Fresh Air Intake Unit

ARNU24 GB2G2

ARNU07G ARNU09G ARNU12G ARNU15G QAA2 QAA2 QAA2 QAA2 ARNU48G BRZ2

B8

❈ *ART COOL- SE/S8( * R:Mirror, V:Silver, B : Blue), SF(* E:Red, V:Silver, G:Gold , 1: Kiss (Photo changeable)) *Wall Mounted- A: Basic, L:Plasma, *Ceiling Cassette- A: Basic, C:Plasma

1 _ General Information

URNU76 URNU96 GB8Z2 GB8Z2


2. External Appearance Ceiling Concealed Duct - High Static

ARNU07GTU*2 ARNU09GTU*2 ARNU12GTU*2

ARNU07GBHA2 ARNU09GBHA2 ARNU12GBHA2 ARNU15GBHA2 ARNU18GBHA2 ARNU24GBHA2 ARNU28GBGA2

ARNU18GTT*2 ARNU24GTT*2

* A:Basic, C:Plasma

Ceiling Cassette- 4Way ARNU05GTR*2 ARNU07GTR*2 ARNU09GTR*2 ARNU12GTR*2 ARNU15GTQ*2 ARNU18GTQ*2

ARNU24GTP*2 ARNU28GTP*2 ARNU36GTN*2 ARNU42GTM*2 ARNU48GTM*2 * A:Basic, C:Plasma

Ceiling Concealed Duct - Low Static ARNU07GB1G2 ARNU15GB1G2 ARNU09GB1G2 ARNU18GB2G2 ARNU12GB1G2 ARNU24GB2G2

Ceiling Concealed Duct – Built-in ARNU07GB3G2 ARNU09GB3G2 ARNU12GB3G2

ARNU15GB3G2 ARNU18GB4G2 ARNU24GB4G2

ARNU36GBGA2 ARNU42GBGA2 ARNU48GBRA2 URNU76GB8A2 URNU96GB8A2

Wall Mounted ARNU07GSE*2 ARNU09GSE*2 ARNU12GSE*2

ARNU15GSE*2 ARNU18GS5*2 ARNU24GS5*2 * A:Basic, L:Plasma

ART COOL Gallery ARNU07GSF*2 ARNU09GSF*2 ARNU12GSF*2 * E:Red V:Silver G:Gold 1: Kiss (Photo changeable)

Floor Standing With case ARNU07GCEA2 ARNU09GCEA2 ARNU12GCEA2

ARNU15GCEA2 ARNU18GCFA2 ARNU24GCFA2

ART COOL Mirror

Without case

ARNU07GSE*2 ARNU09GSE*2 ARNU12GSE*2

ARNU07GCEU2 ARNU09GCEU2 ARNU12GCEU2

ARNU15GSE*2 ARNU18GS8*2 ARNU24GS8*2 * R:Mirror, V:Silver, B:Blue

ARNU15GCEU2 ARNU18GCFU2 ARNU24GCFU2

Ceiling & Floor Console

ARNU09GVEA2 ARNU12GVEA2

Ceiling Suspended ARNU18GVJA2 ARNU24GVJA2

Ceiling Cassette -2Way ARNU18GTL*2 ARNU24GTL*2

ARNU07GQAA2 ARNU09GQAA2 ARNU12GQAA2 ARNU15GQAA2

Fresh Air Intake Unit ARNU48GBRZ2 URNU76GB8Z2 URNU96GB8Z2

* A:Basic, C:Plasma

General Information _ 2

General information Indoor unit

Ceiling Cassette- 1Way


General information Indoor unit

3. Nomenclature ARN

U

07

G

TU

A

2 Serial Number Combinations of functions A:Basic function L:Neo Plasma(Wall Mounted) C:Plasma(Ceiling Cassette) G: Low Static U : Floor Standing without Case ART COOL Type Panel Color SE/S8 - R:Mirror V:Silver B:Blue SF - E:Red V:Silver G:Gold 1: Kiss (Photo changeable) Q : Console Z : Fresh Air Intake Unit Chassis Name Electrical Ratings 2:1Ø, 220V, 60Hz 6:1Ø, 220 - 240V, 50Hz G:1Ø, 220 - 240V, 50Hz / 1Ø, 220V, 60Hz Total Cooling Capacity in Btu/h EX) 5,000 Btu/h Class ➝ '05' 18,000 Btu/h Class ➝ '18' Combination of Inverter Type and Cooling Only or Heat Pump N: AC Inverter and H/P V: AC Inverter and C/O U: DC Inverter and H/P and C/O System with Indoor Unit using R410A ❈ LGETA:U Ex) URN

3 _ General Information


4. Indoor Unit Capacity Index INDOOR UNIT CAPACITY INDEX 5k

7k

9k

12k

15k

18k

24k

28k

36k

42k

48k

76k

96k

Capacity Index

1.6

2.2

2.8

3.6

4.5

5.6

7.1

8.2

10.6

12.3

14.1

22.4

28.0

â?ˆ Capacity Index is same as the capacity(kW).

General Information _ 4

General information Indoor unit

Unit Capacity (Btu/h)


5 _ General Information

General information Indoor unit


Indoor unit Ceiling Cassette 1-Way Ceiling Cassette 2-Way Ceiling Cassette 4-way Ceiling Concealed Duct(High Static) Ceiling Concealed Duct(Low Static) Ceiling Concealed Duct(Built in) Wall Mounted ART COOL Mirror ART COOL Gallery Ceiling & Floor/Ceiling Suspended Floor Standing Console Fresh Air Intake Unit Dip Switch & Group Control Setting


Indoor unit Ceiling Cassette 1-Way 1. List of functions 2. Specifications 3. Dimensions 4. Piping Diagrams 5. Wiring Diagrams 6. Capacity Tables 7. Air Velocity and Temperature Distribution 8. Electric Characteristics 9. Sound Levels 10. Installation 11. Accessories


1. List of functions Category

Air flow

Air purifying

Installation

Convenience

Individual control

Special function kit

Air supply outlet Airflow direction control(left & right) Airflow direction control(up & down) Auto swing(left & right) Auto swing(up & down) Airflow steps(fan/cool/heat) Chaos swing Chaos wind(auto wind) Jet cool(Power wind) Swirl wind Deodorizing filter Plasma air purifier Prefilter(washable / anti-fungus) Drain pump E.S.P. control Electric heater(operation) High ceiling operation Hot start Self diagnosis Soft dry operation Auto changeover Auto cleaning Auto operation(artificial intelligence) Auto restart operation Child lock Forced operation Group control Sleep mode Timer(on/off) Timer(weekly) Two thermistor control Wide wired remote controller Deluxe wired remote controller Simple wired remote controller Wired remote controller(for hotel use) Wireless remote controller(simple) Wireless LCD remote control Zone control CTIE Electro thermostat

ARNU07GTU*2, ARNU09GTU*2, ARNU12GTU*2 ARNU18GTT*2, ARNU24GTT*2 1 Auto O 4/5/4 X O O X Option O O O X O O O O O(Heat recovery) X O(Heat pump or Cooling only) O O O O O O O O Accessory Accessory Accessory Accessory X Accessory -

O : Applied X : Not applied – : No relation Option : Model name & price are different according to options, and assembled in factory with main unit. Accessory : Installed at field, ordered and purchased separately by the corresponding model name, supplied with separate package. * Some functions can be limited by remote controller.

Ceiling Cassette 1-Way _ 1

Indoor Units

Reliability

Function


2. Specifications * Model Name A:Basic, C:Plasma Type Model Cooling Capacity

Heating Capacity

Unit kW kcal/h Btu/h kW kcal/h Btu/h

Casing Body Dimensions (WxDxH) Front Panel

Indoor Units

Coil

Fan

Rows x Columns x FPI Face Area Type Motor Output x Number Running Current Air Flow Rate(H / M / L)

mm inch mm inch m3 W A CMM cfm

Drive Motor type Temperature Control Sound Absorbing Thermal Insulation Material Safety Device Liquid Side mm(inch) Pipe Connections Gas Side mm(inch) Drain Pipe(Internal Dia.) mm(inch) Net Weight Body kg(lbs) Noise Level(Sound Press, 1.5m, H / M / L) dB(A) Power Supply Refrigerant Control Power cable Transmission cable Panel Color Panel Name(Accessory)

Ø, V, Hz

1Way Ceiling Cassette ARNU07GTU*2 ARNU09GTU*2 ARNU12GTU*2 2.2 2.8 3.6 1,900 2,400 3,100 7,500 9,600 12,300 2.5 3.2 4.0 2,200 2,800 3,400 8,500 10,900 13,600 Galvanized Steel Plate Galvanized Steel Plate Galvanized Steel Plate 860 x 450 x 132 860 x 450 x 132 860 x 450 x 132 33.8 x 17.7 x 5.2 33.8 x 17.7 x 5.2 33.8 x 17.7 x 5.2 1100 x 500 x 34 1100 x 500 x 34 1100 x 500 x 34 43.3 x 19.7 x 1.3 43.3 x 19.7 x 1.3 43.3 x 19.7 x 1.3 2 x 12 x 18 2 x 12 x 18 2 x 12 x 18 0.16 0.16 0.16 Cross Flow Fan Cross Flow Fan Cross Flow Fan 30 30 30 0.18 0.18 0.18 8.2 / 7.3 / 6.4 9.2 / 8.6 / 8.2 10 / 9.2 / 8.2 289.5 / 257.7 / 225.9 324.7 / 303.6 / 289.5 353 / 324.8 / 289.5 Direct Direct Direct BLDC BLDC BLDC Microprocessor, Thermostat for cooling and heating Microprocessor, Thermostat for cooling and heating Microprocessor, Thermostat for cooling and heating Foamed polystrene Foamed polystrene Foamed polystrene Fuse Fuse Fuse Ø6.35(1/4) Ø6.35(1/4) Ø6.35(1/4) Ø12.7(1/2) Ø12.7(1/2) Ø12.7(1/2) 25(1) 25(1) 25(1) 14.7(32.4) 14.7(32.4) 14.7(32.4) 32 / 29 / 25 35 / 34 / 32 38 / 35 / 32 1, 220-240, 50 1, 220-240, 50 1, 220-240, 50 1, 220, 60 1, 220, 60 1, 220, 60 EEV EEV EEV CV1.5 x 3C CV1.5 x 3C CV1.5 x 3C CVV-SB 1.0~1.5 x 2C CVV-SB 1.0~1.5 x 2C CVV-SB 1.0~1.5 x 2C White White White PT-UUC(Grill), PT-UUD(Panel)

Notes:1. Capacities are based on the following conditions: Cooling • Indoor temp. 27°C[80.6°F]DB/ 19°C[66.2°F]WB • Outdoor temp. 35°C[95°F]DB/ 24°C[75.2°F]WB • Interconnecting Piping Length 7.5m • Level Difference of Zero Heating • Indoor temp. 20°C[68°F]DB/ 15°C[59°F]WB • Outdoor temp. 7°C[44.6°F]DB/ 6°C[42.8°F]WB • Interconnecting Piping Length 7.5m • Level Difference of Zero 2. Capacities are Net Capacities 3. Due to our policy of innovation some specifications may be changed without prior notification 4. To be added for more available Models 5. EEV : Electronic Expansion Valve 6. Anechoic chamber conversion value is measured at 1.5 m downward from unit centre. The values depends on the ambient conditions and values are normally higher in actual operation.

2 _ Ceiling Cassette 1-Way

Conversion Formula kcal/h= kW x 860 Btu/h = kW x 3412 cfm = m3/min x 35.3 l/s = CMM x 1000/60


2. Specifications * Model Name A:Basic, C:Plasma Type Model Cooling Capacity

Heating Capacity

Unit kW kcal/h Btu/h kW kcal/h Btu/h

Casing Body Dimensions (WxDxH) Front Panel Coil

m3 W A CMM cfm

Drive Motor type Temperature Control Sound Absorbing Thermal Insulation Material Safety Device Liquid Side mm(inch) Pipe Connections Gas Side mm(inch) Drain Pipe(Internal Dia.) mm(inch) Net Weight Body kg(lbs) Noise Level(Sound Press, 1.5m, H / M / L) dB(A) Power Supply Refrigerant Control Power cable Transmission cable Panel Color Panel Name(Accessory)

Ø, V, Hz

Notes:1. Capacities are based on the following conditions: Cooling • Indoor temp. 27°C[80.6°F]DB/ 19°C[66.2°F]WB • Outdoor temp. 35°C[95°F]DB/ 24°C[75.2°F]WB • Interconnecting Piping Length 7.5m • Level Difference of Zero Heating • Indoor temp. 20°C[68°F]DB/ 15°C[59°F]WB • Outdoor temp. 7°C[44.6°F]DB/ 6°C[42.8°F]WB • Interconnecting Piping Length 7.5m • Level Difference of Zero 2. Capacities are Net Capacities 3. Due to our policy of innovation some specifications may be changed without prior notification 4. To be added for more available Models 5. EEV : Electronic Expansion Valve 6. Anechoic chamber conversion value is measured at 1.5 m downward from unit centre. The values depends on the ambient conditions and values are normally higher in actual operation.

Conversion Formula kcal/h= kW x 860 Btu/h = kW x 3412 cfm = m3/min x 35.3 l/s = CMM x 1000/60

Ceiling Cassette 1-Way _ 3

Indoor Units

Fan

Rows x Columns x FPI Face Area Type Motor Output x Number Running Current Air Flow Rate(H / M / L)

mm inch mm inch

1Way Ceiling Cassette ARNU18GTT*2 ARNU24GTT*2 5.6 7.1 4,800 6,100 19,100 24,200 6.3 7.1 5,400 6,100 21,500 24,200 Galvanized Steel Plate Galvanized Steel Plate 1180 x 450 x 132 1180 x 450 x 132 13.3 x 17.7 x 5.2 46.5 x 17.7 x 5.2 1420 x 500 x 34 1420 x 500 x 34 55.9 x 19.7 x 1.3 55.9 x 19.7 x 1.3 2 x 12 x 18 2 x 12 x 18 0.24 0.24 Cross Flow Fan Cross Flow Fan 30 30 0.30 0.30 13.3 / 12.1 / 10.9 14.6 / 13.3 / 11.5 515.4 / 427.1 / 384.8 575.4 / 469.5 / 406 Direct Direct BLDC BLDC Microprocessor, Thermostat for cooling and heating Microprocessor, Thermostat for cooling and heating Foamed polystrene Foamed polystrene Fuse Fuse Ø6.35(1/4) Ø9.52(3/8) Ø12.7(1/2) Ø15.88(5/8) 25(1) 25(1) 18.7(41.23) 18.7(41.23) 40 / 37 / 35 43 / 40 / 36 1, 220-240, 50 1, 220-240, 50 1, 220, 60 1, 220, 60 EEV EEV CV1.5 x 3C CV1.5 x 3C CVV-SB 1.0~1.5 x 2C CVV-SB 1.0~1.5 x 2C White White PT-UTC(Grill), PT-UTD(Panel)


1,100 881(Air outlet Hole)

1012

861

88

106.8 206.6 275.8 57.4 96.5 168.3

4 _ Ceiling Cassette 1-Way 500 34

27

Air suction grill Air discharge grill

3 4

(unit : mm)

Unit size(7k, 9k, 12k):ø12.7

Unit size(7k, 9k, 12k):ø6.35

Descripition

CHASSIS CODE: TU

2. Unit shall be grounded in accordance with the local regulations or applicable national codes.

1. Unit should be installed in compliance with the installation manual in the product box.

Note

Gas pipe connection

2

76, Seongsan-dong, Changwon City, Gyeongnam, 641-713, Korea

(Panel Name: PT-UUC)

320.5

453

Liquid pipe connection

Name

ARNU07GTU*2 ARNU09GTU*2 ARNU12GTU*2

Ceiling Cassette 1-way

1

Number

Indoor Units

3. Dimensions


Ceiling Cassette 1-Way _ 5

109.5

1012

1100

88

109.5

453 320.5

34

500

106.8 206.3 275.8 96.5 168.3 57.4

453 354.3

46.5

861

Air discharge grill

4

Unit size(7k, 9k, 12k):ø12.7

Unit size(7k, 9k, 12k):ø6.35

Descripition

(unit : mm)

CHASSIS CODE: TU

2. Unit shall be grounded in accordance with the local regulations or applicable national codes.

1. Unit should be installed in compliance with the installation manual in the product box.

Note

Air suction grill

3

Gas pipe connection

76, Seongsan-dong, Changwon City, Gyeongnam, 641-713, Korea

(Panel Name: PT-UUD)

27

Liquid pipe connection

1

Name

ARNU07GTU*2 ARNU09GTU*2 ARNU12GTU*2

2

Number

Indoor Units

117

Ceiling Cassette 1-way

3. Dimensions


247.5 180.6 65.3

453.8

173.8 96.1 91 20.6 57.4 31.7

6 _ Ceiling Cassette 1-Way

1,201(Air Outlet Hole)

1,420

1332

1176.4 65.1

500 34

453.8

4

CHASSIS CODE: TT

2. Unit shall be grounded in accordance with the local regulations or applicable national codes.

1. Unit should be installed in compliance with the installation manual in the product box.

Note

Air suction grill Air discharge grill

3

Unit size(18k):ø12.7, (24k):ø15.88

Gas pipe connection

2

76, Seongsan-dong, Changwon City, Gyeongnam, 641-713, Korea

(Panel Name: PT-UTC)

(unit : mm) Descripition

Liquid pipe connection Unit size(18k):ø6.35, (24k):ø9.52

Name

ARNU18GTT*2 ARNU24GTT*2

Ceiling Cassette 1-way

1

Number

Indoor Units

3. Dimensions


Ceiling Cassette 1-Way _ 7

109.5

1332

1420

Ø14 15.2

65.3

453.8 247.5 180.6

173.8 97.1 91

500

57.4 31.7 20.6

46.5

34

65.1

22.3

57 132

1176.4

109.5

335

453.8

Air discharge grill

CHASSIS CODE: TT

2. Unit shall be grounded in accordance with the local regulations or applicable national codes.

1. Unit should be installed in compliance with the installation manual in the product box.

Note

4

Air suction grill

3

76, Seongsan-dong, Changwon City, Gyeongnam, 641-713, Korea

(Panel Name: PT-UTD)

96.5

Gas pipe connection

Unit size(18k):ø12.7, (24k):ø15.88

Liquid pipe connection Unit size(18k):ø6.35, (24k):ø9.52

Descripition

(unit : mm)

2

Name

ARNU18GTT*2 ARNU24GTT*2

1

Number

Indoor Units

44

Ceiling Cassette 1-way

3. Dimensions


4. Piping Diagrams

Heat Exchanger

EEV

Filter

:Cooling :Heating

Th2

Th3 C.F.F.

Filter

Indoor Units

Th1

lndoor unit

Refrigerant pipe connection port diameter [Unit: mm(inch)]

Model

Gas

Liquid

Ø12.7(1/2)

Ø6.35(1/4)

Ø15.88(5/8)

Ø9.52(3/8)

ARNU07GTU*2 ARNU09GTU*2 ARNU12GTU*2 ARNU18GTT*2 ARNU24GTT*2

LOC.

Description

Th1

Room thermistor

Th2

Pipe in thermistor

Th3

Pipe out thermistor

8 _ Ceiling Cassette 1-Way


5. Wiring Diagrams TU, TT Chassis

LOCATION POINT Fan motor output Drain pump output Communication Display EEV Output Step motor Float switch input Suction pipe sensor Discharge pipe sensor Room sensor Remote controller Dry contact Option pwb. Communication Step motor

Dip Switch Setting SW3 GROUP

Off Master

On Slave

SW4

DRY CONTACT

Variable

Auto

SW5

EXTRA 1

Off

On

FUNCTION Motor output of BLDC AC output for drain pump Connection between indoor and outdoor Display of indoor status EEV Control output Step motor output Float switch sensing Pipe in thermistor Pipe out thermistor Room air thermistor Remote control line Dry contact line Communication between main and option Communication between indoor and outdoor Step motor output

Remarks Group Control setting using Wired Remote Controller Old Dry Contact Mode Setting 1. Variable : Auto/Manual Mode can be chosen by Wide wired remote controller or Wireless remote controller (When shipped from Factory → Manual Mode) 2. Auto : For Dry Contact, it is always Auto mode. 1. Duct model -. OFF : Default(not operate continuosly ) -. ON : Fan operate continuosly 2. Cassette Model : No Function 3. Ceiling Suspended Model -. OFF : Ceiling(default) -. ON : Floor

CAUTION For Multi V Model, Dip Switch 1,2,6,7,8 must be set OFF That dip switch is used for the other model.

Ceiling Cassette 1-Way _ 9

Indoor Units

CONNECTOR NUMBER CN-MOTOR1 CN-D/PUMP CN-485 CN-DISP CN-EEV CN-VANE2 CN-FLOAT CN-PIPE/IN CN-PIPE/OUT CN-ROOM CN-REMO CN-CC CN-OPTION CN-COM CN-VANE1


6. Capacity Tables 6.1 Cooling Capacity

Capacity Index

Indoor Units

2.2

2.8

3.6

Outdoor air temp. (DB, °C) 10 12 14 16 18 20 21 23 25 27 29 31 33 35 37 39 10 12 14 16 18 20 21 23 25 27 29 31 33 35 37 39 10 12 14 16 18 20 21 23 25 27 29 31 33 35 37 39

Cooling capacity

20 14 TC SHC kW kW

23 16 TC SHC kW kW

Indoor air temp. (DB/WB, °C) 26 27 28 18 19 20 TC SHC TC SHC TC SHC kW kW kW kW kW kW

1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4

1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9

2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4

1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1

Notes: TC: Total Capacity(kW)

10 _ Ceiling Cassette 1-Way

1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3

1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5

2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6

1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6

SHC: Sensible Heat Capacity(kW)

2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8

1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6

30 22 TC SHC kW kW 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3

1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8

32 24 TC SHC kW kW 2.9 2.9 2.8 2.8 2.7 2.7 2.7 2.6 2.6 2.6 2.5 2.5 2.5 2.4 2.4 2.3 3.7 3.6 3.6 3.5 3.5 3.4 3.4 3.4 3.3 3.3 3.2 3.2 3.1 3.1 3.0 3.0 4.7 4.7 4.6 4.6 4.5 4.4 4.4 4.3 4.3 4.2 4.2 4.1 4.0 4.0 3.9 3.8

1.7 1.6 1.6 1.6 1.6 1.6 1.5 1.5 1.5 1.5 1.5 1.4 1.4 1.4 1.4 1.4 2.1 2.1 2.1 2.0 2.0 2.0 2.0 1.9 1.9 1.9 1.9 1.8 1.8 1.8 1.8 1.7 2.7 2.7 2.7 2.6 2.6 2.5 2.5 2.5 2.5 2.4 2.4 2.4 2.3 2.3 2.3 2.2


6. Capacity Tables

Capacity Index

5.6

10 12 14 16 18 20 21 23 25 27 29 31 33 35 37 39 10 12 14 16 18 20 21 23 25 27 29 31 33 35 37 39

Notes: TC: Total Capacity(kW)

20 14 TC SHC kW kW

23 16 TC SHC kW kW

3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8

4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7

5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6

3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1

3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5

3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9

5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1

3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0

6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6

4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1

30 22 TC SHC kW kW 6.7 6.7 6.7 6.7 6.7 6.7 6.7 6.7 6.7 6.7 6.7 6.7 6.7 6.7 6.7 6.7 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5

4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3

32 24 TC SHC kW kW 7.4 7.3 7.2 7.1 7.0 6.9 6.8 6.7 6.6 6.6 6.5 6.4 6.3 6.2 6.1 6.0 9.3 9.2 9.1 9.0 8.8 8.7 8.7 8.5 8.4 8.3 8.2 8.1 7.9 7.8 7.7 7.6

4.2 4.1 4.1 4.0 4.0 3.9 3.9 3.8 3.8 3.7 3.7 3.6 3.6 3.5 3.5 3.4 5.3 5.2 5.2 5.1 5.0 5.0 4.9 4.9 4.8 4.7 4.7 4.6 4.5 4.4 4.4 4.3

SHC: Sensible Heat Capacity(kW)

Ceiling Cassette 1-Way _ 11

Indoor Units

7.1

Outdoor air temp. (DB, °C)

Indoor air temp. (DB/WB, °C) 26 27 28 18 19 20 TC SHC TC SHC TC SHC kW kW kW kW kW kW


6. Capacity Tables 6.2 Heating Capacity Outdoor air temp. Capacity Index DB(°C) WB(°C)

Indoor Units

2.2

2.8

3.6

-19.8 -18.8 -16.7 -14.7 -12.6 -10.5 -9.5 -8.5 -7.0 -5.0 -3.0 0.0 3.0 5.0 7.0 9.0 11.0 13.0 15.0 -19.8 -18.8 -16.7 -14.7 -12.6 -10.5 -9.5 -8.5 -7.0 -5.0 -3.0 0.0 3.0 5.0 7.0 9.0 11.0 13.0 15.0 -19.8 -18.8 -16.7 -14.7 -12.6 -10.5 -9.5 -8.5 -7.0 -5.0 -3.0 0.0 3.0 5.0 7.0 9.0 11.0 13.0 15.0

-20.0 -19.0 -17.0 -15.0 -13.0 -11.0 -10.0 -9.1 -7.6 -5.6 -3.7 -0.7 2.2 4.1 6.0 7.9 9.8 11.8 13.7 -20.0 -19.0 -17.0 -15.0 -13.0 -11.0 -10.0 -9.1 -7.6 -5.6 -3.7 -0.7 2.2 4.1 6.0 7.9 9.8 11.8 13.7 -20.0 -19.0 -17.0 -15.0 -13.0 -11.0 -10.0 -9.1 -7.6 -5.6 -3.7 -0.7 2.2 4.1 6.0 7.9 9.8 11.8 13.7

Heating capacity Indoor air temp. (DB, °C)

16

18

20

21

22

24

TC

TC

TC

TC

TC

TC

kW

kW

kW

kW

kW

kW

1.7 1.7 1.8 1.9 2.0 2.1 2.2 2.2 2.3 2.4 2.5 2.6 2.8 2.8 2.9 2.9 2.9 2.9 2.9 2.1 2.2 2.3 2.5 2.6 2.7 2.8 2.8 2.9 3.0 3.2 3.4 3.6 3.6 3.7 3.7 3.7 3.7 3.7 2.7 2.8 2.9 3.1 3.2 3.4 3.4 3.5 3.6 3.8 4.0 4.2 4.4 4.5 4.6 4.6 4.6 4.6 4.6

1.7 1.7 1.8 1.9 2.0 2.1 2.2 2.2 2.3 2.4 2.5 2.6 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.1 2.2 2.3 2.4 2.6 2.7 2.8 2.8 2.9 3.0 3.2 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 2.7 2.8 2.9 3.0 3.2 3.4 3.4 3.5 3.6 3.8 4.0 4.2 4.3 4.3 4.3 4.3 4.3 4.3 4.3

1.7 1.7 1.8 1.7 1.8 1.9 1.9 2.0 2.0 2.1 2.2 2.3 2.4 2.5 2.5 2.5 2.5 2.5 2.5 2.1 2.2 2.3 2.2 2.3 2.4 2.5 2.5 2.6 2.7 2.8 3.0 3.1 3.2 3.2 3.2 3.2 3.2 3.2 2.7 2.8 2.9 2.7 2.9 3.0 3.1 3.2 3.3 3.4 3.5 3.7 3.9 4.0 4.0 4.0 4.0 4.0 4.0

1.7 1.7 1.8 1.9 2.0 2.1 2.2 2.2 2.2 2.3 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.1 2.2 2.3 2.4 2.6 2.7 2.8 2.8 2.8 3.0 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 2.6 2.8 2.9 3.0 3.2 3.4 3.4 3.5 3.6 3.7 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9

1.7 1.7 1.8 1.9 2.0 2.1 2.2 2.2 2.2 2.3 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.1 2.2 2.3 2.4 2.6 2.7 2.8 2.8 2.8 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 2.6 2.7 2.9 3.0 3.2 3.4 3.4 3.5 3.6 3.7 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8

1.7 1.7 1.8 1.9 2.0 2.1 2.1 2.1 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.1 2.2 2.3 2.4 2.6 2.7 2.7 2.7 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.6 2.7 2.9 3.0 3.2 3.4 3.4 3.4 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5

Notes: TC: Total Capacity(kW)

12 _ Ceiling Cassette 1-Way


6. Capacity Tables Heating capacity Outdoor air temp. Capacity Index DB(°C) WB(°C)

5.6

-20.0 -19.0 -17.0 -15.0 -13.0 -11.0 -10.0 -9.1 -7.6 -5.6 -3.7 -0.7 2.2 4.1 6.0 7.9 9.8 11.8 13.7 -20.0 -19.0 -17.0 -15.0 -13.0 -11.0 -10.0 -9.1 -7.6 -5.6 -3.7 -0.7 2.2 4.1 6.0 7.9 9.8 11.8 13.7

16

18

20

21

22

24

TC

TC

TC

TC

TC

TC

kW

kW

kW

kW

kW

kW

4.2 4.3 4.6 4.9 5.1 5.4 5.4 5.5 5.7 6.0 6.2 6.6 7.0 7.1 7.2 7.2 7.2 7.2 7.2 4.8 4.9 5.2 5.5 5.8 6.0 6.1 6.2 6.5 6.7 7.0 7.5 7.9 8.0 8.2 8.2 8.2 8.2 8.2

4.2 4.3 4.6 4.8 5.1 5.4 5.4 5.5 5.7 6.0 6.2 6.6 6.7 6.7 6.7 6.7 6.7 6.7 6.7 4.8 4.9 5.2 5.4 5.8 6.0 6.1 6.2 6.5 6.7 7.0 7.5 7.6 7.6 7.6 7.6 7.6 7.6 7.6

4.2 4.3 4.6 4.3 4.5 4.8 4.9 5.0 5.1 5.4 5.5 5.8 6.2 6.3 6.3 6.3 6.3 6.3 6.3 4.8 4.9 5.2 4.9 5.1 5.4 5.5 5.6 5.8 6.0 6.2 6.6 6.9 7.1 7.1 7.1 7.1 7.1 7.1

4.2 4.3 4.6 4.8 5.0 5.4 5.4 5.5 5.6 5.8 6.1 6.1 6.1 6.1 6.1 6.1 6.1 6.1 6.1 4.7 4.9 5.2 5.4 5.7 6.0 6.1 6.2 6.3 6.6 6.8 6.9 6.9 6.9 6.9 6.9 6.9 6.9 6.9

4.2 4.3 4.6 4.8 5.0 5.3 5.4 5.5 5.6 5.8 5.9 5.9 5.9 5.9 5.9 5.9 5.9 5.9 5.9 4.7 4.8 5.2 5.4 5.7 6.0 6.1 6.2 6.3 6.6 6.7 6.7 6.7 6.7 6.7 6.7 6.7 6.7 6.7

4.2 4.3 4.5 4.8 5.0 5.3 5.4 5.4 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 4.7 4.8 5.1 5.4 5.7 6.0 6.0 6.1 6.2 6.2 6.2 6.2 6.2 6.2 6.2 6.2 6.2 6.2 6.2

Notes: TC: Total Capacity(kW)

Ceiling Cassette 1-Way _ 13

Indoor Units

7.1

-19.8 -18.8 -16.7 -14.7 -12.6 -10.5 -9.5 -8.5 -7.0 -5.0 -3.0 0.0 3.0 5.0 7.0 9.0 11.0 13.0 15.0 -19.8 -18.8 -16.7 -14.7 -12.6 -10.5 -9.5 -8.5 -7.0 -5.0 -3.0 0.0 3.0 5.0 7.0 9.0 11.0 13.0 15.0

Indoor air temp. (DB, °C)


7. Air Velocity and Temperature Distribution(Reference Data) ARNU07GTU*2 Cooling

Heating

Discharge angle: 50°

Discharge angle: 60° Air velocity [m/s]

0.1

2m

2.0

2m

0.5

1

2. 5

0.1

0.5

22

.5

0.5

0. 1

3

0.1

0.1

0.5

1

0.5

1.5

1.0 3.5. 43 .0 5

Air velocity [m/s]

1.0

0.1

1.0

05

0. 5

0.5

1m

1.0

1

0.5

1m

0.1 1.0

1.5

0.5

0.5

0.5

0.5

1 0.

1.5

1.5

5 0.

0.1

0.5

1

0.5 1

4m

0.5

3m

2m

1m

0

5m

Temperature [°C]

4m

0.5 0.5

3m

01

2m

0

1m

0

Temperature [°C] 32 14

30

30

16 20

31

32

33

34

2m

31

36

3 37 8

32

24

22

31

35

34

26

32

2m

36

31

28

28

35

34

30

28

26

24

4327

32

30

41 3 396

32

1m

35

37 36

24

1m 34

28

26

30

33

28

36

24

32

28

30

26

4m

3m

28

26

28

30

5m

2m

31

0 5m

0

1m

35

4m

36

35

34

3m

2m

0

1m

0

ARNU09GTU*2 Cooling

Heating

Discharge angle: 50°

Discharge angle: 60°

Air velocity [m/s]

Air velocity [m/s] 2.5 0.5

3.0

2. 0 0.5

1.0 1.5

0.5

1.0

1.0

0.5

1

1

0.5

0.5

5 0.

1m

1.5

1m

0.5

01

1

0.5

1.5

0.5

0.5

2m

0.1

1

2

1.0

1.5

2m

0.1

0.1

5 0. 0.5

0.1

1.5 1.5

2. 5 3 .5 5 1.

0.5

0.1

1

3

0.1

0.5

1 0.5

4m

0.5

0

3m

2m

1m

0

5m

Temperature [°C]

4m

1.0 0.5

01

3m

2m

0

1m

0

Temperature [°C]

32

31 32

2284 20

32

38

18

30

32

35

30

22

32

43 38326354 9

5m

36

33 37 36 33

30

32

22

2m 36

26 28

26

31

2m

28

24

1m

36

33

34 35 37

34

3231

24

30

28

1m

4m

28

3m

26

26 30 28

2m

1m

32

0 0

33

32

26

30

5m

36

31

24

34

35

28

28

Indoor Units

0.1

0

0.5

0.5

5m

1

5m

4m

36

35

34

3m

2m

0 1m

0

Note: The standard setup height is 2.7m. Shown here is the measurement distribution at the ceiling height of 2.7m

14 _ Ceiling Cassette 1-Way


7. Air Velocity and Temperature Distribution(Reference Data) ARNU12GTU*2 Cooling

Heating

Discharge angle: 50°

Discharge angle: 60° Air velocity [m/s] 1.0

0.1

2. 5

0.5

1.0

1. 0. 05

2m 1.5

1m

0.5

0.1

0.1

0. 5

0.1

0.1

2

0.5

1.5

0.5

1

5 0.

1.50.5

1.5

1

1

0.5

0. 5

5 1. 0.5

2. 0

0.5

1 0.

2m

05

0.1

1.5

11.5 .0 2. 420.5 .0

2 11 .5

Air velocity [m/s]

1m

1.0

3m

2m

1.0

0

1m

0

01

5m

4m

0

3m

2m

1m

0

Temperature [°C]

32

32

32

32

28

31

32

37 41

30

3 4064

Temperature [°C]

0.5

1

4m

05

1

0.5

5 0.

5m

0.5

1.0

1.0

1.5

0.5

0.5

0.5

30

33

2m

2m

33

37 32

4m

36

35

34 36

31

24

26

34

24

28

3m

36

33

5m

26

30

1m

37

28

28

38

24

28

22

32

30

28

3635

28

31

26

28

30

1m

26

34

39

31

26

0

2m

5m

0

1m

37

35

34

32

4m

3536

3m

2m

0

1m

0

ARNU18GTT*2 Cooling

Heating

Discharge angle: 50°

Discharge angle: 60°

Air velocity [m/s]

Air velocity [m/s] 1

0.53

1

.5

5

01.5 43.5

2

2

2 1.5

1

2. 5

2m

2m

1

0.5

1

0.5 0.5

1

1.5

1.5

0.5

1.5 2

0.5

0.5

5 0.

0.5 0.5

1 0.5

5 0.

2. 5

0.5

.5 1 4

1.5

1m

1.5

1

1m

1

1

0.5

0.5

0.5

0.5

1 .5

0.5

0.5

4m

3m

0 2m

1m

0

0 5m

Temperature [°C]

4m

3m

2m

1m

0

Temperature [°C]

32

32

32

32

3364

30

30 39 40

30

32

26

22

2m 33

31

34

35

24

34

30

28 33

4m

3m

36

33

26

34

24

2826

5m

1m

36

28

36

37

1m

36

32

24

24

31

2628

28

2m

35 33

30

32

32 1 4

38

22

18 28

35

202

8

31

34

5m

31

0

0 2m

1m

0

5m

4m

3m

2m

1m

0

Note: The standard setup height is 2.7m. Shown here is the measurement distribution at the ceiling height of 2.7m

Ceiling Cassette 1-Way _ 15

Indoor Units

26


7. Air Velocity and Temperature Distribution(Reference Data) ARNU24GTT*2 Cooling

Heating

Discharge angle: 50째

Discharge angle: 60째

Air velocity [m/s]

Air velocity [m/s] 2. 5

1.5

1

2m

2 1.5

1.5

0.5

0.5

0.5

1m

05

0.5

1 1.5

0 .5

1.5 0.5

0.5

0.5

0. 1.55

1 5 0.

2m

1

2

0. 5

2

0.5

32

.5 4.5

5 0.

1 1. 52

0.5

1

1

2

3.5

1m

1

1

0.5

1.5

1

1

1

1.5

1

0.5 1

1

0.5

5m

4m

0.5

3m

2m

1

0

1m

0

0 5m

Temperature [째C]

4m

3m

2m

1m

0

Temperature [째C]

32

32

32 161

36

2

32

40

32333

26 22

30

2m

2m 38

22

31

28

28

4

39

32

20

28

36

36 37

36

33

36

1m

24

35

30

33

34

31

28

28

32

1m

34

26

35

37

24

33

24 4

28

28

26

34

31

30

Indoor Units

31

30

30 24

35

30

28

5m

4m

3m

0

0 2m

1m

0

5m

4m

3m

2m

1m

0

Note: The standard setup height is 2.7m. Shown here is the measurement distribution at the ceiling height of 2.7m

16 _ Ceiling Cassette 1-Way


8. Electric Characteristics Units

Power Supply

Input(W)

MFA

kW

FLA

1.23

15

0.03

0.18

40

40

1.23

15

0.03

0.18

40

40

1.23

15

0.03

0.18

40

40

1.38

15

0.03

0.30

70

70

TT

1.38

15

0.03

0.30

70

70

ARNU07GTU*2

TU

1.23

15

0.03

0.18

40

40

ARNU09GTU*2

TU

1.23

15

0.03

0.18

40

40

ARNU12GTU*2

TU

1.23

15

0.03

0.18

40

40

ARNU18GTT*2

TT

1.38

15

0.03

0.30

70

70

ARNU24GTT*2

TT

1.38

15

0.03

0.30

70

70

Model

Type

ARNU07GTU*2

TU

ARNU09GTU*2

TU

ARNU12GTU*2

TU

ARNU18GTT*2

TT

ARNU24GTT*2

Hz

50

Volts

220-240

60

220

Voltage Range MCA

IFM

Max:264 Min:198

Max:242 Min:198

Cooling Heating

Indoor Units

Symbols: MCA : Minimum Circuit Amperes (A) MFA : Maximum Fuse Amperes(see note 5) kW : Fan Motor Rated Output(kW) FLA : Full Load Amperes(A) IFM : Indoor Fan Motor Note : 1. Voltage Range Units are suitable for use on electrical system where voltage supplied to unit terminals is not below or above the listed range limits. 2. Maximum allowable voltage unbalance between phase is 2%. 3. MCA/MFA MCA = 1.25 x FLA MFA ≤ 4 x FLA ( Next lower standard fuse rating. Minimum 15A) 4. Select wire size based on the larger value on the MCA. 5. Instead of fuse, use Circuit Breaker.

Ceiling Cassette 1-Way _ 17


9. Sound Levels Overall Notes: - Sound measured at 1.5m away from the center of the unit. - Data is valid at free field condition - Data is valid at nominal operating condition - Reference accoustic pressure OdB = 20μPa - Sound level will vary depending on a range of factors such as the construction(acoustic absorption coefficient) of particular room in which the equipment is installed.

1.5m Microphone

Sound Levels dB(A) H M L

Model

Indoor Units

ARNU07GTU*2 ARNU09GTU*2 ARNU12GTU*2 ARNU18GTT*2 ARNU24GTT*2

32 35 38 40 43

29 34 35 37 40

25 32 32 35 36

Sound Pressure Level ARNU09GTU*2

ARNU12GTU*2 XP

WP

WP

WP

nc MVU

VP nc MVP nc MUU

UP

nc MUP nc MTU

TP

nc MTP nc MSU

SP

nc MSP

RP

nc MRU

a’˜‰”… h…’‰Ž‡@ tˆ’…“ˆŒ„

ncMVP ncMUU

UP ncMUP ncMTU

TP ncMTP

nc MQU

QRU

RUP

UPP

QPPP

RPPP

TPPP

XPPP

oƒ”–…@bŽ„@c…Ž”…’@f’…‘•…Žƒ™@HhšI

18 _ Ceiling Cassette 1-Way

ncMSU

SP

ncMSP

ncMRU

RP

nc MRP

QP VS

ncMVU

VP

QP

a’˜‰”… h…’‰Ž‡ tˆ’…“ˆŒ„ VS

oƒ”–…@bŽ„@s•Ž„@p’…““•’…@l…–…Œ@H„b@’…@RPµp@I

XP

oƒ”–…@bŽ„@s•Ž„@p’…““•’…@l…–…Œ@H„b@’…@RPµp@I

oƒ”–…@bŽ„@s•Ž„@p’…““•’…@l…–…Œ@H„b@’…@RPµp@I

ARNU07GTU*2 XP

NC-65

VP NC-60 NC-55

UP NC-50 NC-45

TP NC-40

NC-30

QRU

RUP

UPP

QPPP

RPPP

TPPP

oƒ”–…@bŽ„@c…Ž”…’@f’…‘•…Žƒ™@HhšI

XPPP

NC-25

RP

ncMRP ncMQU

NC-35

SP

QP

Approximate Hearing Threshold VS

NC-20 NC-15

QRU

RUP

UPP

QPPP

RPPP

TPPP

oƒ”–…@bŽ„@c…Ž”…’@f’…‘•…Žƒ™@HhšI

XPPP


9. Sound Levels ARNU24GTT*2

80

80

70

70

NC-65 60 NC-60 NC-55

50

NC-50 NC-45

40

NC-40 NC-35

30

NC-30

NC-25

20 Approximate Hearing Threshold

NC-65 60 NC-60

NC-50

125

250

500

1000

2000

4000

Octave Band Center Frequency (Hz)

8000

NC-45

40

NC-40 NC-35

30

NC-30

20

10

NC-25 Approximate Hearing Threshold 63

NC-20

125

250

500

1000

2000

4000

NC-15 8000

Indoor Units

10

NC-55

50

NC-20 NC-15

63

oƒ”–…@bŽ„@s•Ž„@p’…““•’…@l…–…Œ@H„b@’…@RPµp@I

oƒ”–…@bŽ„@s•Ž„@p’…““•’…@l…–…Œ@H„b@’…@RPµp@I

ARNU18GTT*2

Octave Band Center Frequency (Hz)

Ceiling Cassette 1-Way _ 19


10. Installation • Please read this instruction sheet completely before installing the product. • When the power cord is damaged, replacement work shall be performed by authorized personnel only. • Installation work must be performed in accordance with the national wiring standards by authorized personnel only.

Outlet

TEM P

Remote Controlle

Indoor Units

r

Inlet

Required Parts • Connecting cable • Pipes: Gas side Liquid side • Hanging Bolt (W 3/8 or M10 length 650mm) • Insulated drain hose • Additional Drain hose

Wired remote controller

Required Tools • Level • Screw driver • Electric drill • Hole core drill • Flaring Tool set • Torque Wrenches • Hexagonal Wrench • Gas-leak detector • Thermometer

20 _ Ceiling Cassette 1-Way

Ceiling board

500 or more

300 or less

500 or more

Above 2500 3300 or less

Ceiling Ceiling board

1000 or more

• There should not be any heat source or steam near the unit. • There should not be any obstacles to the air circulation. • A place where air circulation in the room will be good. • A place where drainage can be easily obtained. • A place where noise prevention is taken into consideration. • Do not install the unit near the door way. • Ensure the spaces indicated by arrows from the wall, ceiling, or other obstacles. • The indoor unit must have the maintenance space.

200 or more

10.1 Selection of the best location

Unit:mm Floor


10. Installation 10.2 Ceiling opening dimensions and hanging bolt location 1,385 1,285

50

50

354 466

1,180

448

306

40

600

400

• The dimensions of the paper model for installation are the same as those of the ceiling opening dimensions.

40

Ceiling 250

TT Chassis

Level gauge

1,065 965

50

50

250

354 466

448

860

TU Chassis

• Select and mark the position for fixing bolts and piping hole. • Decide the position for fixing bolts slightly tilted to the drain direction after considering the direction of drain hose. • Drill the hole for anchor bolt on the wall.

(unit: mm)

Ceiling board

NOTE: • Avoid the following installation location. 1. Such places as restaurants and kitchen where considerable amount of oil steam and flour is generated. These may cause heat exchange efficiency reduction, or water drops, drain pump mal-function. In these cases, take the following actions; • Make sure that ventilation fan is enough to cover all noxious gases from this place. • Ensure enough distance from the cooking room to install the air conditioner in such a place where it may not suck oily steam. Air conditioner

Take enough distance Use the ventilation fan for smoke-collecting hood with sufficient capacity. Cooking table

2. Avoid installing air conditioner in such places where cooking oil or iron powder is generated. 3. Avoid places where inflammable gas is generated. 4. Avoid place where noxious gas is generated. 5. Avoid places near high frequency generators.

Ceiling Cassette 1-Way _ 21

Indoor Units

• This air-conditioner uses a drain pump. • Install the unit horizontally using a level gauge. • During the installation, care should be taken not to damage electric wires.

40

400

CAUTION

306

40

600


10. Installation Ceiling

Nut (W3/8 or M10)

70mm

Keep the length of the bolt from the bracket to 40mm

Hanging bolt (W3/8 or M10)

Flat washer for M10 (accessory) Ceiling board

Spring washer (M10)

Flat washer for M10 (accessory) Nut (W3/8 or M10)

Air conditioner body

Set screw of paper model (4 pieces)

Paper model for installation

Open the ceiling board along the outer edge of the paper model

Indoor Units

Adjust the same height

• The following parts are local purchasing. ① Hanging bolt - W 3/8 or M10 ② Nut - W 3/8 or M10 ③ Spring washer - M10 ④ Plate washer - M10

Ceiling board

CAUTION • Tighten the nut and bolt to prevent the unit from falling.

10.3 Wiring Connection • Connect the wires to the terminals on the control board individually according to the outdoor unit connection. • Ensure that the color of the wires of outdoor unit and the terminal No. are the same as those of indoor unit respectively. [Multi V III Heat Pump Model] Terminal block of indoor unit 1(L)

2(N)

3

SODU B

SODU A

IDU B

IDU A

INT B

INT A

4

Indoor power input

[Except Multi VIII Heat Pump Model] Terminal block of outdoor unit Terminal block of indoor unit 1(L)

2(N)

3

4

Outdoor unit Indoor unit

SODU SODU IDU IDU INTERNET DRY1 DRY2 GND 12V

Indoor power input

WARNING Make sure that the screws of the terminal are not loose.

22 _ Ceiling Cassette 1-Way

Central controller


10. Installation 10.4 Installation of Decoration Panel (Panel Type) Before installing the decoration panel, always remove the paper template.

The decoration panel has its installation direction. 1. Open the air outlet vane, and extract side covers. 2. Remove the air inlet panel from the decoration panel.

3. Hook decoration panel to indoor unit, using hooks attached at the backside of both side of decoration panel. 4. Arrange wires not to get caught between decoration panel and indoor unit. 5. Screw 7 fixing screws. (7,9,12kBtu : 6 screws) 6. Connect the vane motor connector ,display connector and air inlet panel connector. 7. Install the air inlet panel (including the air filter) and side covers. Air conditioner unit

Indoor Units

Mesh Control box cover

Side cover Robot kit Decorative panel fixing screws (hexagon M6 screws) (tightening about 20mm)

Air inlet panel

Decorative panel Air outlet vane

CAUTION

Install certainly the decoration panel. Cool air leakage causes sweating. ⇨讀 Waterdrops fall.

Good example

Bad example Air conditioner unit Cool air leakage (no good) Ceiling board Decorative panel

Air conditioner unit Ceiling board Decorative panel

Fit the insulator (this part) and be careful for cool air leakage

Ceiling Cassette 1-Way _ 23


10. Installation 10.5 Installation of Decoration Panel(Grille Type) Before installing the decoration panel, always remove the paper template.

The decoration panel has its installation direction. 1. Open the air outlet vane, and extract side covers. 2. Remove the air inlet grille from the decoration panel.

3. Hook decoration panel to indoor unit, using hooks attached at the backside of both side of decoration panel. 4. Arrange wires not to get caught between decoration panel and indoor unit. 5. Screw 7 fixing screws. (7,9,12kBtu : 6 screws) 6. Connect the vane motor connector and display connector. (Plasma connector for plasma model)

Indoor Units

7. Install the air inlet grille (including the air filter) and side covers.

Air conditioner unit

Mesh Control box cover

Side cover Plasma filter (applied only to plasma model) Decorative panel fixing screws (hexagon M6 screws) (tightening about 20mm) Air inlet grille

Decorative panel Air inlet grille

CAUTION

Install certainly the decoration panel. Cool air leakage causes sweating. ⇨讀 Waterdrops fall.

Good example

Bad example Air conditioner unit Cool air leakage (no good) Ceiling board Decorative panel

Fit the insulator (this part) and be careful for cool air leakage

24 _ Ceiling Cassette 1-Way

Air conditioner unit Ceiling board Decorative panel


10. Installation 10.6 Indoor Unit Drain Piping • Drain piping must have down-slope (1/50 to 1/100): be sure not to provide up-and-down slope to prevent reversal flow. • During drain piping connection, be careful not to exert extra force on the drain port on the indoor unit. • The outside diameter of the drain connection on the indoor unit is 32mm. Piping material: Polyvinyl chloride pipe 25mm and pipe fittings

Upward routing not allowed

Pipe clamp Indoor unit

Maintenance drain port

• Be sure to install heat insulation on the drain piping. 1/50~1/100

Heat insulation material: Polyethylene foam with thickness more than 8 mm.

Max 700mm

Drain test

Feed water

Flexible drain hose (accessory) Main drain pipe

Drain pump

Drain port

Glue the joint

Drain hose connection Use the clip (accessory)

• Connect the main drain pipe to the exterior and leave it provisionally until the test comes to an end. • Feed water to the flexible drain hose and check the piping for leakage. • Be sure to check the drain pump for normal operating and noise when electrical wiring is complete. • When the test is complete, connect the flexible drain hose to the drain port on the indoor unit.

Drain pan

CAUTION Max 300mm Metal clamp Flexible drain hose

Hanger bracket 1/50~1/100 slope Max 700mm

The supplied flexible drain hose should not be curved, neither screwed. The curved or screwed hose may cause a leakage of water.

Hanger distance 1~15m

Insulation

Ceiling Cassette 1-Way _ 25

Indoor Units

The air conditioner uses a drain pump to drain water. Use the following procedure to test the drain pump operation:


10. Installation

Indoor Units

CAUTION After the confirmation of the above conditions, prepare the wiring as follows: 1) Never fail to have separate power specially for the air conditioner. As for the method of wiring, follow the circuit diagram pasted on the inside of control box cover. 2) Provide a circuit breaker switch between power source and the unit. 3) The screw which fasten the wiring in the casing of electrical fittings are liable to come loose from vibrations to which the unit is subjected during the course of transportation. Check them and make sure that they are all tightly fastened. (If they are loose, it could give rise to burn-out of the wires.) 4) Confirm the Specification of power source 5) Confirm that electrical capacity is sufficient. 6) Be sure that the starting voltage is maintained at more than 90 percent of the rated voltage marked on the name plate. 7) Confirm that the cable thickness is as specified in the power sources specification. (Particularly note the relation between cable length and thickness.) 8) Do not install the leakage breaker in a place which is wet or moist. Water or moist may cause short circuit. 9) The following troubles would be caused by voltage drop-down. • Vibration of a magnetic switch, damage on the contact point there of, fuse breaking, disturbance to the normal function of a overload protection device. • Proper starting power is not given to the compressor.

WIRED REMOTE CONTROLLER INSTALLATION • Since the room temperature sensor is in the remote controller, the remote controller box should be installed in a place away from direct sunlight, high humidity and direct supply of cold air to maintain proper space temperature. Install the remote controller about 5ft(1.5m) above the floor in an area with good air circulation at an average temperature.

Do not install the remote controller where it can be affected by: - Drafts, or dead spots behind doors and in corners. - Hot or cold air from ducts. - Radiant heat from sun or appliances. - Concealed pipes and chimneys. - Uncontrolled areas such as an outside wall behind the remote controller. - This remote controller is equipped with a seven segment LED. display. For proper display of the remote controller LED's, the remote controller should be installed properly as shown in Fig.1. (The standard height is 1.2~1.5 m from floor level.)

TEMP

yes

Remote Controller

no

TEMP

Remote Controller

5feet (1.5meters)

TEMP

Controller Remote

no

no

Fig.1 Typical locations for remote controller

26 _ Ceiling Cassette 1-Way


11. Accessories Name

Drain hose

Clamp metal

Quantity

1 EA

2 EA

Washer for hanging bracket 8 EA

Plastic band

Insulation for fitting

4 EA

1 SET

Shape

for gas pipe

for liquid pipe

Paper pattern for installation

Installation and Owner's manual

Quantity

1EA

1EA

Shape

CAUTION • Use only those accessories (Standard or optional) which have designated specifications.

Ceiling Cassette 1-Way _ 27

Indoor Units

Name


Indoor unit Ceiling Cassette 2-Way 1. List of functions 2. Specifications 3. Dimensions 4. Piping Diagrams 5. Wiring Diagrams 6. Capacity Tables 7. Air Velocity and Temperature Distribution 8. Electric Characteristics 9. Sound Levels 10. Installation 11. Accessories


1. List of functions Category

Air flow

Air purifying

Installation

Convenience

Individual control

Special function kit

Air supply outlet Airflow direction control(left & right) Airflow direction control(up & down) Auto swing(left & right) Auto swing(up & down) Airflow steps(fan/cool/heat) Chaos swing Chaos wind(auto wind) Jet cool(Power wind) Swirl wind Deodorizing filter Plasma air purifier Prefilter(washable / anti-fungus) Drain pump E.S.P. control Electric heater(operation) High ceiling operation Hot start Self diagnosis Soft dry operation Auto changeover Auto cleaning Auto operation(artificial intelligence) Auto restart operation Child lock Forced operation Group control Sleep mode Timer(on/off) Timer(weekly) Two thermistor control Wide wired remote controller Deluxe wired remote controller Simple wired remote controller Wired remote controller(for hotel use) Wireless remote controller(simple) Wireless LCD remote control Zone control CTIE Electro thermostat

ARNU18GTL*2, ARNU24GTL*2 2 Auto O 4/5/4 X O O X Option O O O X O O O O O(Heat recovery) X O(Heat pump or Cooling only) O O O O O O O O Accessory Accessory Accessory Accessory X Accessory -

O : Applied X : Not applied – : No relation Option : Model name & price are different according to options, and assembled in factory with main unit. Accessory : Installed at field, ordered and purchased separately by the corresponding model name, supplied with separate package.

Ceiling Cassette 2-way _ 1

Indoor Units

Reliability

Function


2. Specifications * Model Name A:Basic, C:Plasma Type Model Cooling Capacity

Heating Capacity

Unit kW kcal/h Btu/h kW kcal/h Btu/h

Casing Body Dimensions (WxDxH) Front Panel

Indoor Units

Coil

Fan

Rows x Columns x FPI Face Area Type Motor Output x Number Running Current Air Flow Rate(H / M / L)

mm inch mm inch m3 W A CMM cfm

Drive Motor type Temperature Control Sound Absorbing Thermal Insulation Material Safety Device Liquid Side mm(inch) Pipe Connections Gas Side mm(inch) Drain Pipe(Internal Dia.) mm(inch) Net Weight Body kg(lbs) Noise Level(Sound Press, 1.5m, H / M / L) dB(A) Power Supply Refrigerant Control Power cable Transmission cable Panel Color Panel Name(Accessory)

Ø, V, Hz

2Way Ceiling Cassette ARNU18GTL*2 5.6 4,800 19,100 6.3 5,400 21,500 Galvanized Steel Plate 830 x 550 x 225 32.6 x 21.6 x 8.9 1,050 x 640 x 28.5 41.3 x 25.2 x 1.1 2 x 11 x 20 0.13 Cross Flow Fan 20 x 2 0.18 x 2 13 / 12 / 10 459 / 424 / 353 Direct BLDC Microprocessor, Thermostat for cooling and heating Foamed polystrene Fuse Ø6.35(1/4) Ø12.7(1/2) 25(1) 22(48.5) 40 / 36 / 32 1, 220-240, 50 1, 220, 60 EEV CV1.5 x 3C CVV-SB 1.0~1.5 x 2C Morning fog PT-HL*

Notes:1. Capacities are based on the following conditions: Cooling • Indoor temp. 27°C[80.6°F]DB/ 19°C[66.2°F]WB • Outdoor temp. 35°C[95°F]DB/ 24°C[75.2°F]WB • Interconnecting Piping Length 7.5m • Level Difference of Zero Heating • Indoor temp. 20°C[68°F]DB/ 15°C[59°F]WB • Outdoor temp. 7°C[44.6°F]DB/ 6°C[42.8°F]WB • Interconnecting Piping Length 7.5m • Level Difference of Zero 2. Capacities are Net Capacities 3. Due to our policy of innovation some specifications may be changed without prior notification 4. To be added for more available Models 5. EEV : Electronic Expansion Valve 6. Anechoic chamber conversion value is measured at 1.5 m downward from unit centre. The values depends on the ambient conditions and values are normally higher in actual operation.

2 _ Ceiling Cassette 2-way

Conversion Formula kcal/h= kW x 860 Btu/h = kW x 3412 cfm = m3/min x 35.3 l/s = CMM x 1000/60


2. Specifications * Model Name A:Basic, C:Plasma Type Model Cooling Capacity

Heating Capacity

Unit kW kcal/h Btu/h kW kcal/h Btu/h

Casing Body Dimensions (WxDxH) Front Panel Coil

m3 W A CMM cfm

Drive Motor type Temperature Control Sound Absorbing Thermal Insulation Material Safety Device Liquid Side mm(inch) Pipe Connections Gas Side mm(inch) Drain Pipe(Internal Dia.) mm(inch) Net Weight Body kg(lbs) Noise Level(Sound Press, 1.5m, H / M / L) dB(A) Power Supply Refrigerant Control Power cable Transmission cable Panel Color Panel Name(Accessory)

Ø, V, Hz

Notes:1. Capacities are based on the following conditions: Cooling • Indoor temp. 27°C[80.6°F]DB/ 19°C[66.2°F]WB • Outdoor temp. 35°C[95°F]DB/ 24°C[75.2°F]WB • Interconnecting Piping Length 7.5m • Level Difference of Zero Heating • Indoor temp. 20°C[68°F]DB/ 15°C[59°F]WB • Outdoor temp. 7°C[44.6°F]DB/ 6°C[42.8°F]WB • Interconnecting Piping Length 7.5m • Level Difference of Zero 2. Capacities are Net Capacities 3. Due to our policy of innovation some specifications may be changed without prior notification 4. To be added for more available Models 5. EEV : Electronic Expansion Valve 6. Anechoic chamber conversion value is measured at 1.5 m downward from unit centre. The values depends on the ambient conditions and values are normally higher in actual operation.

Conversion Formula kcal/h= kW x 860 Btu/h = kW x 3412 cfm = m3/min x 35.3 l/s = CMM x 1000/60

Ceiling Cassette 2-way _ 3

Indoor Units

Fan

Rows x Columns x FPI Face Area Type Motor Output x Number Running Current Air Flow Rate(H / M / L)

mm inch mm inch

2Way Ceiling Cassette ARNU24GTL*2 7.1 6,100 24,200 8.0 6,900 27,300 Galvanized Steel Plate 830 x 550 x 225 32.6 x 21.6 x 8.9 1,050 x 640 x 28.5 41.3 x 25.2 x 1.1 2 x 11 x 20 0.13 Cross Flow Fan 20 x 2 0.18 x 2 17 / 15 / 13 601 / 530 / 459 Direct BLDC Microprocessor, Thermostat for cooling and heating Foamed polystrene Fuse Ø9.52(3/8) Ø15.88(5/8) 25(1) 22(48.5) 42 / 38 / 34 1, 220-240, 50 1, 220, 60 EEV CV1.5 x 3C CVV-SB 1.0~1.5 x 2C Morning fog PT-HL*


3

4

144.2

921(Air Outlet Hole) 1,050

893

931.2 830 34 1

4-R15

482 550

2 205.5 69.2

35.6

162.4 640 28.5

4 _ Ceiling Cassette 2-way 177.1 225

6.5

92

206.5 69.2

Air discharge grill

Air suction grill

Gas pipe connection

Liquid pipe connection

Name

(unit : mm)

Unit size(24k):ø15.88

Unit size(18k):ø12.7

Unit size(24k):ø9.52

Unit size(18k):ø6.35

Descripition

ARNU18GTL*2 ARNU24GTL*2

Ceiling Cassette 2-way

76, Seongsan-dong, Changwon City, Gyeongnam, 641-713, Korea

CHASSIS CODE: TL

2. Unit shall be grounded in accordance with the local regulations or applicable national codes.

1. Unit should be installed in compliance with the installation manual in the product box.

Note

4

3

2

1

Number

Indoor Units

3. Dimensions


4. Piping Diagrams

Heat Exchanger

EEV

Filter

:Cooling :Heating

Th2

Th3 C.F.F.

Filter Th1

lndoor unit

[Unit: mm(inch)]

Model

Gas

Liquid

ARNU18GTL*2

Ø12.7(1/2)

Ø6.35(1/4)

ARNU24GTL*2

Ø15.88(5/8)

Ø9.52(3/8)

LOC.

Description

Th1

Room thermistor

Th2

Pipe in thermistor

Th3

Pipe out thermistor

Ceiling Cassette 2-way _ 5

Indoor Units

Refrigerant pipe connection port diameter


5. Wiring Diagrams

Indoor Units

TL Chassis

CONNECTOR NUMBER CN-POWER CN-MOTOR1 CN-MOTOR2 CN-D/PUMP CN-485 CN-DISP CN-EEV CN-VANE2 CN-FLOAT CN-PIPE/IN CN-PIPE/OUT CN-ROOM CN-REMO

SPEC AC Power supply Fan motor output Fan motor output Drain pump output Communication Display EEV Output Step motor Float switch input Suction pipe sensor Discharge pipe sensor Room sensor Remote controller

Dip Switch Setting SW3 GROUP

Off Master

On Slave

SW4

DRY CONTACT

Variable

Auto

SW5

EXTRA 1

Off

On

DESCRIPTION AC Power line input for indoor controller Motor output of BLDC Motor output of BLDC AC output for drain pump Connection between indoor and outdoor Display of indoor status EEV Control output Step motor output Float switch sensing Pipe in thermistor Pipe out thermistor Room air thermistor Remote control line Remarks Group Control setting using Wired Remote Controller Old Dry Contact Mode Setting 1. Variable : Auto/Manual Mode can be chosen by Wide wired remote controller or Wireless remote controller (When shipped from Factory → Manual Mode) 2. Auto : For Dry Contact, it is always Auto mode. 1. Duct model -. OFF : Default(not operate continuosly ) -. ON : Fan operate continuosly 2. Cassette Model : No Function 3. Ceiling Suspended Model -. OFF : Ceiling(default) -. ON : Floor

CAUTION For Multi V Model, Dip Switch 1,2,6,7,8 must be set OFF That dip switch is used for the other model.

6 _ Ceiling Cassette 2-way


6. Capacity Tables 6.1 Cooling Capacity

Capacity Index

20 14 TC SHC kW kW

23 16 TC SHC kW kW

Indoor air temp. (DB/WB, °C) 26 27 28 18 19 20 TC SHC TC SHC TC SHC kW kW kW kW kW kW

30 22 TC SHC kW kW

32 24 TC SHC kW kW

10

3.8

3.2

4.5

3.6

5.2

3.9

5.6

3.9

6.0

4.0

6.7

4.2

7.4

4.2

12

3.8

3.2

4.5

3.6

5.2

3.9

5.6

3.9

6.0

4.0

6.7

4.2

7.3

4.1

14

3.8

3.2

4.5

3.6

5.2

3.9

5.6

3.9

6.0

4.0

6.7

4.2

7.2

4.1

16

3.8

3.2

4.5

3.6

5.2

3.9

5.6

3.9

6.0

4.0

6.7

4.2

7.1

4.0

18

3.8

3.2

4.5

3.6

5.2

3.9

5.6

3.9

6.0

4.0

6.7

4.2

7.0

4.0

20

3.8

3.2

4.5

3.6

5.2

3.9

5.6

3.9

6.0

4.0

6.7

4.2

6.9

3.9

21

3.8

3.2

4.5

3.6

5.2

3.9

5.6

3.9

6.0

4.0

6.7

4.2

6.8

3.9

23

3.8

3.2

4.5

3.6

5.2

3.9

5.6

3.9

6.0

4.0

6.7

4.2

6.7

3.8

25

3.8

3.2

4.5

3.6

5.2

3.9

5.6

3.9

6.0

4.0

6.6

4.2

6.6

3.8

27

3.8

3.2

4.5

3.6

5.2

3.9

5.6

3.9

6.0

4.0

6.4

4.1

6.6

3.7

29

3.8

3.2

4.5

3.6

5.2

3.9

5.6

3.9

6.0

4.0

6.4

4.0

6.5

3.7

31

3.8

3.2

4.5

3.6

5.2

3.9

5.6

3.9

6.0

4.0

6.3

3.9

6.4

3.6

33

3.8

3.2

4.5

3.6

5.2

3.9

5.6

3.9

6.0

4.0

6.2

3.9

6.3

3.6

35

3.8

3.2

4.5

3.6

5.2

3.9

5.6

3.9

6.0

4.0

6.0

3.8

6.2

3.5

37

3.8

3.2

4.5

3.6

5.2

3.9

5.6

3.9

5.8

3.9

5.9

3.7

6.1

3.5

39

3.8

3.2

4.5

3.6

5.2

3.9

5.6

3.9

5.7

3.9

5.8

3.7

6.0

3.4

Outdoor air temp. (DB, °C)

Notes: TC: Total Capacity(kW)

SHC: Sensible Heat Capacity(kW)

Ceiling Cassette 2-way _ 7

Indoor Units

5.6

Cooling capacity


6. Capacity Tables Cooling capacity

Indoor Units

Capacity Index

7.1

20 14 TC SHC kW kW

23 16 TC SHC kW kW

Indoor air temp. (DB/WB, °C) 26 27 28 18 19 20 TC SHC TC SHC TC SHC kW kW kW kW kW kW

30 22 TC SHC kW kW

32 24 TC SHC kW kW

10

4.8

4.1

5.7

4.5

6.6

4.9

7.1

5.0

7.6

5.1

8.5

5.3

9.3

5.3

12

4.8

4.1

5.7

4.5

6.6

4.9

7.1

5.0

7.6

5.1

8.5

5.3

9.2

5.2

14

4.8

4.1

5.7

4.5

6.6

4.9

7.1

5.0

7.6

5.1

8.5

5.3

9.1

5.2

16

4.8

4.1

5.7

4.5

6.6

4.9

7.1

5.0

7.6

5.1

8.5

5.3

9.0

5.1

18

4.8

4.1

5.7

4.5

6.6

4.9

7.1

5.0

7.6

5.1

8.5

5.3

8.8

5.0

20

4.8

4.1

5.7

4.5

6.6

4.9

7.1

5.0

7.6

5.1

8.5

5.3

8.7

5.0

21

4.8

4.1

5.7

4.5

6.6

4.9

7.1

5.0

7.6

5.1

8.5

5.3

8.7

4.9

23

4.8

4.1

5.7

4.5

6.6

4.9

7.1

5.0

7.6

5.1

8.5

5.3

8.5

4.9

25

4.8

4.1

5.7

4.5

6.6

4.9

7.1

5.0

7.6

5.1

8.4

5.3

8.4

4.8

27

4.8

4.1

5.7

4.5

6.6

4.9

7.1

5.0

7.6

5.1

8.2

5.1

8.3

4.7

29

4.8

4.1

5.7

4.5

6.6

4.9

7.1

5.0

7.6

5.1

8.1

5.1

8.2

4.7

31

4.8

4.1

5.7

4.5

6.6

4.9

7.1

5.0

7.6

5.1

8.0

5.0

8.1

4.6

33

4.8

4.1

5.7

4.5

6.6

4.9

7.1

5.0

7.6

5.1

7.8

4.9

7.9

4.5

35

4.8

4.1

5.7

4.5

6.6

4.9

7.1

5.0

7.6

5.1

7.7

4.8

7.8

4.4

37

4.8

4.1

5.7

4.5

6.6

4.9

7.1

5.0

7.4

5.0

7.5

4.7

7.7

4.4

39

4.8

4.1

5.7

4.5

6.6

4.9

7.1

5.0

7.2

4.9

7.4

4.6

7.6

4.3

Outdoor air temp. (DB, °C)

Notes: TC: Total Capacity(kW)

8 _ Ceiling Cassette 2-way

SHC: Sensible Heat Capacity(kW)


6. Capacity Tables 6.2 Heating Capacity Outdoor air temp. Capacity Index DB(°C) WB(°C)

Indoor air temp. (DB, °C) 16

18

20

21

22

24

TC

TC

TC

TC

TC

TC

-19.8 -20.0

kW 4.2

kW 4.2

kW 4.2

kW 4.2

kW 4.2

kW 4.2

-18.8 -19.0

4.3

4.3

4.3

4.3

4.3

4.3

-16.7 -17.0

4.6

4.6

4.6

4.6

4.6

4.5

-14.7 -15.0

4.9

4.8

4.3

4.8

4.8

4.8

-12.6 -13.0

5.1

5.1

4.5

5.0

5.0

5.0

-10.5 -11.0

5.4

5.4

4.8

5.4

5.3

5.3

-9.5 -10.0

5.4

5.4

4.9

5.4

5.4

5.4

-8.5

-9.1

5.5

5.5

5.0

5.5

5.5

5.4

-7.0

-7.6

5.7

5.7

5.1

5.6

5.6

5.5

-5.0

-5.6

6.0

6.0

5.4

5.8

5.8

5.5

-3.0

-3.7

6.2

6.2

5.5

6.1

5.9

5.5

0.0

-0.7

6.6

6.6

5.8

6.1

5.9

5.5

3.0

2.2

7.0

6.7

6.2

6.1

5.9

5.5

5.0

4.1

7.1

6.7

6.3

6.1

5.9

5.5

7.0

6.0

7.2

6.7

6.3

6.1

5.9

5.5

9.0

7.9

7.2

6.7

6.3

6.1

5.9

5.5

11.0

9.8

7.2

6.7

6.3

6.1

5.9

5.5

13.0 11.8

7.2

6.7

6.3

6.1

5.9

5.5

15.0 13.7

7.2

6.7

6.3

6.1

5.9

5.5

Notes: TC: Total Capacity(kW)

Ceiling Cassette 2-way _ 9

Indoor Units

5.6

Heating capacity


6. Capacity Tables Heating capacity

Indoor Units

Outdoor air temp. Capacity Index DB(°C) WB(°C)

7.1

Indoor air temp. (DB, °C) 16

18

20

21

22

24

TC

TC

TC

TC

TC

TC

-19.8 -20.0

kW 5.4

kW 5.4

kW 5.4

kW 5.3

kW 5.3

kW 5.3

-18.8 -19.0

5.5

5.5

5.5

5.5

5.4

5.4

-16.7 -17.0

5.8

5.8

5.8

5.8

5.8

5.8

-14.7 -15.0

6.2

6.1

5.5

6.1

6.1

6.1

-12.6 -13.0

6.5

6.5

5.8

6.4

6.4

6.4

-10.5 -11.0

6.8

6.8

6.0

6.8

6.7

6.7

-9.5 -10.0

6.9

6.9

6.2

6.9

6.9

6.8

-8.5

-9.1

7.0

7.0

6.3

7.0

7.0

6.8

-7.0

-7.6

7.3

7.3

6.5

7.1

7.1

7.0

-5.0

-5.6

7.6

7.6

6.8

7.4

7.4

7.0

-3.0

-3.7

7.9

7.9

7.0

7.7

7.5

7.0

0.0

-0.7

8.4

8.4

7.4

7.8

7.5

7.0

3.0

2.2

8.9

8.6

7.8

7.8

7.5

7.0

5.0

4.1

9.0

8.6

8.0

7.8

7.5

7.0

7.0

6.0

9.2

8.6

8.0

7.8

7.5

7.0

9.0

7.9

9.2

8.6

8.0

7.8

7.5

7.0

11.0

9.8

9.2

8.6

8.0

7.8

7.5

7.0

13.0 11.8

9.2

8.6

8.0

7.8

7.5

7.0

15.0 13.7

9.2

8.6

8.0

7.8

7.5

7.0

Notes: TC: Total Capacity(kW)

10 _ Ceiling Cassette 2-way


7. Air Velocity and Temperature Distribution(Reference Data) ARNU24GTL*2 Cooling

Heating

Discharge angle: 40째

Discharge angle: 60째

Air velocity [m/s]

Air velocity [m/s] 2.7m

2.0

2.5

3.0

3.0

2.5

2m

2.0

1.5

1.5

1.0

1.0

0.5

4m

2.7m 2.5 2.0 1.5

1m

2m

1m

0m

1m

2m

0m 4m

3m

Temperature [째C]

0.5

4m

3m

2m

20

20

2.7m 21

22

0m

32 31

2m

23

1m

2m

0m 4m

3m

24

1m

28 26

1m

0m

1m

2m

3m

0m 4m

4m

27

3m

2m

1m

29

2.7m

32 31

30

24

2m

0.5

1m

2m

30 27

28

29 28

0m

1m

28 27

1m

26

2m

3m

0m 4m

Ceiling Cassette 2-way _ 11

Indoor Units

21

23

3m

1m

1.0

Temperature [째C]

22

4m

2m

1.5

1.0

0.5

3m

2.5 2.0


8. Electric Characteristics Units Model

Type

ARNU18GTL*2

TL

ARNU24GTL*2

TL

ARNU18GTL*2

TL

ARNU24GTL*2

TL

Power Supply Hz

Volts

50

220-240

60

220

Voltage Range MCA

IFM

Input(W)

MFA

kW

FLA

Cooling Heating

Max:264

0.52

15

0.04

0.41

70

70

Min:198

0.52

15

0.04

0.41

70

70

Max:242

0.52

15

0.04

0.41

70

70

Min:198

0.52

15

0.04

0.41

70

70

Symbols:

Indoor Units

MCA : Minimum Circuit Amperes (A) MFA : Maximum Fuse Amperes(see note 5) kW : Fan Motor Rated Output(kW) FLA : Full Load Amperes(A) IFM : Indoor Fan Motor Note : 1. Voltage Range Units are suitable for use on electrical system where voltage supplied to unit terminals is not below or above the listed range limits. 2. Maximum allowable voltage unbalance between phase is 2%. 3. MCA/MFA MCA = 1.25 x FLA MFA ≤ 4 x FLA ( Next lower standard fuse rating. Minimum 15A) 4. Select wire size based on the larger value on the MCA. 5. Instead of fuse, use Circuit Breaker.

12 _ Ceiling Cassette 2-way


9. Sound Levels Overall Notes: - Sound measured at 1.5m away from the center of the unit. - Data is valid at free field condition - Data is valid at nominal operating condition - Reference accoustic pressure OdB = 20μPa - Sound level will vary depending on a range of factors such as the construction(acoustic absorption coefficient) of particular room in which the equipment is installed.

1.5m Microphone

Sound Levels dB(A)

Model

H

M

L

ARNU18GTL*2

40

36

32

ARNU24GTL*2

42

38

34

ARNU24GTL*2

80

80

70

70

NC-65 60 NC-60 NC-55

50

NC-50 NC-45

40

NC-40 NC-35

30

NC-30

20

10

NC-25 Approximate Hearing Threshold 63

Octave Band Sound Pressure Level (dB re 20μPa )

Octave Band Sound Pressure Level (dB re 20μPa )

ARNU18GTL*2

NC-65 60 NC-60

NC-15 250

500

1000

2000

4000

Octave Band Center Frequency (Hz)

8000

NC-55

50

NC-50 NC-45

40

NC-40 NC-35

30

NC-30

20

NC-20

125

Indoor Units

Sound Pressure Level

10

NC-25 Approximate Hearing Threshold 63

NC-20 NC-15 125

250

500

1000

2000

4000

8000

Octave Band Center Frequency (Hz)

Ceiling Cassette 2-way _ 13


10. Installation • Please read the instruction sheets completely before installing the product. • When the power cord is damaged, replacement work shall be performed by authorized personnel only. • Installation work must be performed in accordance with the national wiring standards by authorized personnel only.

TEMP

Remote Controller

Air Intake Air Outlet

Required Parts • Connecting cable • Pipes: Gas side Liquid side • Hanging Bolt (W 3/8 or M10 length 650mm) • Insulated drain hose • Additional Drain hose

Required Tools • Level • Screw driver • Electric drill • Hole core drill • Flaring Tool set • Torque Wrenches • Hexagonal Wrench • Gas-leak detector • Thermometer

14 _ Ceiling Cassette 2-way

50 or more

Ceiling Board

50 or more

30 or less

Ceiling Ceiling Board

Above 200 300 or less

• There should not be any heat source or steam near the unit. • There should not be any obstacles to the air circulation. • A place where air circulation in the room will be good. • A place where drainage can be easily obtained. • A place where noise prevention is taken into consideration. • Do not install the unit near the door way. • Ensure the spaces indicated by arrows from the wall, ceiling, or other obstacles. • The indoor unit must have sufficient maintenance space.

20 or more

10.1 Selection of the best location

100 or more

Indoor Units

Anti-bacteria filter

Unit:cm Floor


10. Installation 10.2 Ceiling opening dimensions and hanging bolt location • The dimensions of the paper pattern for installation are the same as those of the ceiling opening dimensions. Ceiling board

Ceiling Level gauge

CAUTION

NOTE: • Avoid the following installation location. 1. Such places as restaurants and kitchen where considerable amount of oil steam and flour is generated. These may cause heat exchange efficiency reduction, or water drops, drain pump mal-function. In these cases, take the following actions; • Make sure that ventilation fan is enough to cover all noxious gases from this place. • Ensure enough distance from the cooking room to install the air conditioner in such a place where it may not suck oily steam.

Air conditioner

Take enough distance Use the ventilation fan for smoke-collecting hood with sufficient capacity. Cooking table

2. Avoid installng air conditioner in such places where cooking oil or iron powder is generated. 3. Avoid places where inflammable gas is generated. 4. Avoid place where noxious gas is generated. 5. Avoid places near high frequency generators.

Ceiling Cassette 2-way _ 15

Indoor Units

• This air-conditioner uses a drain pump. • Install the unit horizontally using a level gauge. • During the installation, care should be taken not to damage electric wires.

• Select and mark the position for fixing bolts and piping hole. • Decide the position for fixing bolts slightly tilted to the drain direction after considering the direction of drain hose. • Drill the hole for anchor bolt on the wall.


10. Installation Ceiling

Nut (W3/8 or M10)

90mm

Keep the length of the bolt from the bracket to 40mm

Hanging bolt (W3/8 or M10)

Flat washer for M10 False (accessory) ceiling board

Air Conditioner body

Flat washer for M10 (accessory) Nut (W3/8 or M10)

Set screw of paper pattern (4 pieces)

Paper pattern for installation

Open the ceiling board along the outer edge of the paper pattern

Indoor Units

Adjust the same height

• The following parts are locally purchased. ① Hanging Bolt - W 3/8 or M10 ② Nut - W 3/8 or M10 ③ Spring Washer - M10 ④ Plate Washer - M10

False ceiling board

CAUTION • Tighten the nut and bolt to prevent the unit from falling.

10.3 Wiring Connection Connect the wires to the terminals on the control board individually according to the outdoor unit connection. • Ensure that the color of the wires of outdoor unit and the terminal No. are the same as those of indoor unit respectively. [Multi V III Heat Pump Model]

Terminal Block Indoor 1(L)

2(N)

3

SODU B

IDU B

SODU A

IDU A

INT B

INT A

4

INDOOR POWER INPUT

[Except Multi VIII Heat Pump Model]

Terminal Block Indoor 1(L)

2(N)

3

SODU

4

B

A

INDOOR POWER INPUT

WARNING Make sure that the screws of the terminal are not loose.

16 _ Ceiling Cassette 2-way

INTERNET DRY1 DRY2 GND 12V

IDU -

-

B

A

-

-

-

-

Outdoor Unit


10. Installation 10.4 Installation of Decoration Panel Before installing the decoration panel, always remove the paper template.

The decoration panel has its installation direction.

1. Temporarily fix two decoration panel fixing screws (hexagon M5 screw) on the unit body. (Tighten by amount 10mm in length.) The fixing screws (hexagon M5 screw) are included in the indoor unit box. 2. Remove the air inlet grille from the decoration panel. (Remove the hook for the air inlet grille cord.) 3. Hook the decoration panel key hole ( ) on the screws fixed in step above, and slide the panel so that the screws reach the key hole edge. 4. Retighten completely two temporarily fixed screws and other two screws. (Total 4 screws) 5. Connect the louver motor connector and display connector. 6. After tightening these screws, install the air inlet grille (including the air filter). Air conditioner unit

Indoor Units

Decorative panel fixing screws (hexagon M6 screws) Temporary fitting at 2 poles (Tightening about 10mm)

Piping side

Control box cover Cover

Plasma filter

Louver motor

Key holes

Decorative panel fixing screws (Hexagon M6 screw)

Decorative panel Push

Ratch pull

Inlet Grille

CAUTION Install the decoration panel otherwise cool air leakage causes condensation. ⇨讀 Water drops fall.

Correct method

Wrong method Air conditioner unit Cool air leakage (no good) Ceiling board Decoration panel

Air conditioner unit Ceiling board Decoration panel

Fit the insulator (this part) and be careful for cool air leakage

Ceiling Cassette 2-way _ 17


10. Installation 10.5 Indoor Unit Drain Piping • Drain piping must have down-slope (1/50 to 1/100): Make sure not to provide up-and-down slope to prevent reversal flow. • During drain piping connection, be careful not to exert extra force on the drain port on the indoor unit. • The outside diameter of the drain connection on the indoor unit is 32mm.

Upward routing not allowed

Pipe clamp Indoor unit

Maintenance drain port

Piping material: Polyvinyl chloride pipe inner diameter Ø 25mm and pipe fittings 1/50~1/100

• Make sure to install heat insulation on the drain piping.

MAX 700mm

Heat insulation material: Polyethylene foam with thickness more than 8 mm.

The air conditioner uses a drain pump to drain water. Use the following procedure to test the drain pump operation:

Feed water

Flexible drain hose (accessory) Main drain pipe

Drain Pump

Drain port

Glue the joint

Drain hose connection Use the clip (accessory)

• Connect the main drain pipe to the exterior and leave it provisionally until the test comes to an end. • Feed water to the flexible drain hose and check the piping for leakage. • Make sure to check the drain pump for normal operating and noise when electrical wiring is complete. • When the test is complete, connect the flexible drain hose to the drain port on the indoor unit.

Drain pan

CAUTION The supplied flexible drain hose should not be strained. A strained hose may cause leakage of water.

Max 300mm

Hanger distance 1~15m

Metal clamp Flexible drain hose Insulation

18 _ Ceiling Cassette 2-way

Hanger Bracket 1/50~1/100 slope Max 700mm

Indoor Units

Drain test


10. Installation CAUTION

HAND OVER Teach the customer the operation and maintenance procedures, using the operation manual. (air filter cleaning, temperature control, etc.)

WIRED REMOTE CONTROLLER INSTALLATION • Since the room temperature sensor is in the remote controller, the remote controller box should be installed in a place away from direct sunlight, high humidity and direct supply of cold air to maintain proper space temperature. Install the remote controller about 5ft(1.5m) above the floor in an area with good air circulation at an average temperature.

Do not install the remote controller where it can be affected by: - Drafts, or dead spots behind doors and in corners. - Hot or cold air from ducts. - Radiant heat from sun or appliances. - Concealed pipes and chimneys. - Uncontrolled areas such as an outside wall behind the remote controller. - This remote controller is equipped with a seven segment LED. display. For proper display of the remote controller LED's, the remote controller should be installed properly as shown in Fig.1. (The standard height is 1.2~1.5 m from floor level.)

TEMP

yes

Remote Controller

no

TEMP

Controller Remote

TEMP

Remote Controller

5feet (1.5meters)

no

no

Fig.1 Typical locations for remote controller

Ceiling Cassette 2-way _ 19

Indoor Units

After the confirmation of the above conditions, prepare the wiring as follows: 1) Never fail to have separate power specially for the air conditioner. As for the method of wiring, follow the circuit diagram pasted on the inside of control box cover. 2) Provide a circuit breaker switch between power source and the unit. 3) The screw which fasten the wiring in the casing of electrical fittings are liable to come loose from vibrations to which the unit is subjected during the course of transportation. Check them and make sure that they are all tightly fastened. (If they are loose, it could give rise to burn-out of the wires.) 4) Confirm the specification of power source 5) Confirm that electrical capacity is sufficient. 6) Be sure that the starting voltage is maintained at more than 90 percent of the rated voltage marked on the name plate. 7) Confirm that the cable thickness is as specified in the power sources specification. (Particularly note the relation between cable length and thickness.) 8) Do not install the leakage breaker in a place which is wet or moist. Water or moist may cause short circuit. 9) The following troubles would be caused by voltage drop-down. • Vibration of a magnetic switch, damage on the contact point there of, fuse breaking, disturbance to the normal function of a overload protection device. • Proper starting power is not given to the compressor.


11. Accessories Standard Accessories Name

Clamp metal

Drain hose

Insulation for fitting

Quantity

2 EA

1 EA

1 set

Washer for hanging bracket 8 EA

Clamp (Tie Wrap) 4 EA

Bolt

(Other)

4 EA • Paper pattern for installation • Owner's manual • Installation manual

Shape

for gas pipe

for liquid pipe

Indoor Units

• Screws for fixing panels are attached to decoration panel.

CAUTION • Use only those accessories (Standard or optional) which have designated specifications.

20 _ Ceiling Cassette 2-way


Indoor unit Ceiling Cassette 4-way 1. List of functions 2. Specifications 3. Dimensions 4. Piping Diagrams 5. Wiring Diagrams 6. Capacity Tables 7. Air Velocity and Temperature Distribution 8. Electric Characteristics 9. Sound Levels 10. Installation 11. Accessories


1. List of functions Category

Air flow

Indoor Units

Air purifying

Installation

Reliability

Convenience

Individual control

Special function kit

Function Air supply outlet Airflow direction control(left & right) Airflow direction control(up & down) Auto swing(left & right) Auto swing(up & down) Airflow steps(fan/cool/heat) Chaos swing Chaos wind(auto wind) Jet cool(Power wind) Swirl wind Deodorizing filter Plasma air purifier Prefilter(washable / anti-fungus) Drain pump E.S.P. control Electric heater(operation) High ceiling operation Hot start Self diagnosis Soft dry operation Auto changeover Auto cleaning Auto operation(artificial intelligence) Auto restart operation Child lock Forced operation Group control Sleep mode Timer(on/off) Timer(weekly) Two thermistor control Elevation Grill Wide wired remote controller Deluxe wired remote controller Simple wired remote controller Wired remote controller(for hotel use) Wireless remote controller(simple) Wireless LCD remote control Zone control CTIE Electro thermostat

ARNU05GTR*2, ARNU07GTR*2, ARNU09GTR*2, ARNU12GTR*2 ARNU15GTQ*2, ARNU18GTQ*2, ARNU24GTP*2, ARNU28GTP*2 ARNU36GTN*2, ARNU42GTM*2, ARNU48GTM*2 4 Auto O 4/5/4 X O O O X Option O O X X O O O O O(Heat recovery) X O(Heat pump or Cooling only) O O O O O O O O Accessory (TM,TN,TP only) Accessory Accessory Accessory Accessory X Accessory -

O : Applied X : Not applied – : No relation Option : Model name & price are different according to options, and assembled in factory with main unit. Accessory : Installed at field, ordered and purchased separately by the corresponding model name, supplied with separate package. * Plasma kit and Elevation Grille are not applicable at the same time

1 _ Ceiling Cassette 4-way


2. Specifications * Model Name A:Basic, C:Plasma Type Model Cooling Capacity

Heating Capacity

Unit kW kcal/h Btu/h kW kcal/h Btu/h

Casing Body Dimensions(WxDxH) Front Panel Coil

m3 W A CMM cfm

Drive Motor type Temperature Control

Sound Absorbing Thermal Insulation Material Safety Device Liquid Side mm(inch) Pipe Connections Gas Side mm(inch) Drain Pipe(Internal Dia.) mm(inch) Net Weight Body kg(lbs) Packaged kg(lbs) Noise Level(Sound Press, 1.5m, H / M / L) dB(A) Power Supply Refrigerant Control Power cable Transmission cable Panel Color Panel Name(Accessory)

Ø, V, Hz mm2 mm2

4 Way Ceiling Cassette ARNU07GTR*2 ARNU09GTR*2 2.2 2.8 1,900 2,400 7,500 9,600 2.5 3.2 2,200 2,800 8,500 10,900 Galvanized Steel Plate Galvanized Steel Plate 570 x 570 x 214 570 x 570 x 214 22.4 x 22.4 x 8.4 22.4 x 22.4 x 8.4 700 x 700 x 30 700 x 700 x 30 27.5 x 27.5 x 1.2 27.5 x 27.5 x 1.2 1 x 8 x 18 2 x 8 x 18 0.21 0.21 Turbo Fan Turbo Fan 43 x 1 43 x 1 0.2 0.2 7.5 / 7.0 / 6.6 8.0 / 7.5 / 7.1 265 / 247 / 212 283 / 265 / 251 Direct Direct BLDC BLDC Microprocessor, Microprocessor, Thermostat for cooling Thermostat for cooling and heating and heating Foamed polystrene Foamed polystrene Fuse Fuse Ø6.35(1/4) Ø6.35(1/4) Ø12.7(1/2) Ø12.7(1/2) 25(1) 25(1) 13.1(28.9) 14.2(31.3) 15.4(33.9) 16.5(36.3) 29 / 27 / 26 30 / 29 / 27 1, 220-240, 50 1, 220-240, 50 1, 220, 60 1, 220, 60 EEV EEV CV1.5 x 3C CV1.5 x 3C CVV-SB 1.0~1.5 x 2C CVV-SB 1.0~1.5 x 2C Morning fog Morning fog PT-UQC

Notes:1. Capacities are based on the following conditions: Cooling • Indoor temp. 27°C[80.6°F]DB/ 19°C[66.2°F]WB • Outdoor temp. 35°C[95°F]DB/ 24°C[75.2°F]WB • Interconnecting Piping Length 7.5m • Level Difference of Zero Heating • Indoor temp. 20°C[68°F]DB/ 15°C[59°F]WB • Outdoor temp. 7°C[44.6°F]DB/ 6°C[42.8°F]WB • Interconnecting Piping Length 7.5m • Level Difference of Zero 2. Capacities are net capacities 3. Due to our policy of innovation some specifications may be changed without prior notification 4. To be added for more available Models 5. EEV : Electronic Expansion Valve 6. Anechoic chamber conversion value is measured at 1.5 m downward from unit centre. The values depends on the ambient conditions and values are normally higher in actual operation.

Conversion Formula kcal/h= kW x 860 Btu/h = kW x 3412 cfm = m3/min x 35.3 l/s = CMM x 1000/60

Ceiling Cassette 4-way _ 2

Indoor Units

Fan

Rows x Columns x FPI Face Area Type Motor Output x Number Running Current Air Flow Rate(H / M / L)

mm inch mm inch

ARNU05GTR*2 1.6 1,400 5,500 1.8 1,500 6,100 Galvanized Steel Plate 570 x 570 x 214 22.4 x 22.4 x 8.4 700 x 700 x 30 27.5 x 27.5 x 1.2 1 x 8 x 18 0.21 Turbo Fan 43 x 1 0.2 7.5 / 7.0 / 6.6 265 / 247 / 212 Direct BLDC Microprocessor, Thermostat for cooling and heating Foamed polystrene Fuse Ø6.35(1/4) Ø12.7(1/2) 25(1) 13.1(28.9) 15.4(33.9) 29 / 27 / 26 1, 220-240, 50 1, 220, 60 EEV CV1.5 x 3C CVV-SB 1.0~1.5 x 2C Morning fog


2. Specifications * Model Name A:Basic, C:Plasma Type Model Cooling Capacity

Heating Capacity

Unit kW kcal/h Btu/h kW kcal/h Btu/h

Casing Body Dimensions(WxDxH) Front Panel

Indoor Units

Coil

Fan

Rows x Columns x FPI Face Area Type Motor Output x Number Running Current Air Flow Rate(H / M / L)

mm inch mm inch m3 W A CMM cfm

Drive Motor type Temperature Control

Sound Absorbing Thermal Insulation Material Safety Device Liquid Side mm(inch) Pipe Connections Gas Side mm(inch) Drain Pipe(Internal Dia.) mm(inch) Net Weight Body kg(lbs) Packaged kg(lbs) Noise Level(Sound Press, 1.5m, H / M / L) dB(A) Power Supply Refrigerant Control Power cable Transmission cable Panel Color Panel Name(Accessory)

Ø, V, Hz mm2 mm2

ARNU12GTR*2 3.6 3,100 12,300 4.0 3,400 13,600 Galvanized Steel Plate 570 x 570 x 214 22.4 x 22.4 x 8.4 700 x 700 x 30 27.5 x 27.5 x 1.2 2 x 8 x 18 0.21 Turbo Fan 43 x 1 0.2 8.7 / 8.0 / 7.0 307 / 283 / 247 Direct BLDC Microprocessor, Thermostat for cooling and heating Foamed polystrene Fuse Ø6.35(1/4) Ø12.7(1/2) 25(1) 14.2(31.3) 16.5(36.3) 32 / 30 / 27 1, 220-240, 50 1, 220, 60 EEV CV1.5 x 3C CVV-SB 1.0~1.5 x 2C Morning fog

4 Way Ceiling Cassette ARNU15GTQ*2 ARNU18GTQ*2 4.5 5.6 3,900 4,800 15,400 19,100 5.0 6.3 4,300 5,400 17,100 21,500 Galvanized Steel Plate Galvanized Steel Plate 570 x 570 x 256 570 x 570 x 256 22.4 x 22.4 x 10.1 22.4 x 22.4 x 10.1 700 x 700 x 30 700 x 700 x 30 27.5 x 27.5 x 1.2 27.5 x 27.5 x 1.2 2 x 10 x 18 2 x 10 x 18 0.27 0.27 Turbo Fan Turbo Fan 43 x 1 43 x 1 0.2 0.2 11.0 / 10.0 / 9.3 11.2 / 11.0 / 10.0 388 / 353 / 328 396 / 388 / 353 Direct Direct BLDC BLDC Microprocessor, Microprocessor, Thermostat for cooling Thermostat for cooling and heating and heating Foamed polystrene Foamed polystrene Fuse Fuse Ø6.35(1/4) Ø6.35(1/4) Ø12.7(1/2) Ø12.7(1/2) 25(1) 25(1) 15.5(34.2) 15.5(34.2) 18.0(39.7) 18.0(39.7) 36 / 34 / 32 37 / 35 / 34 1, 220-240, 50 1, 220-240, 50 1, 220, 60 1, 220, 60 EEV EEV CV1.5 x 3C CV1.5 x 3C CVV-SB 1.0~1.5 x 2C CVV-SB 1.0~1.5 x 2C Morning fog Morning fog PT-UQC

Notes:1. Capacities are based on the following conditions: Cooling • Indoor temp. 27°C[80.6°F]DB/ 19°C[66.2°F]WB • Outdoor temp. 35°C[95°F]DB/ 24°C[75.2°F]WB • Interconnecting Piping Length 7.5m • Level Difference of Zero Heating • Indoor temp. 20°C[68°F]DB/ 15°C[59°F]WB • Outdoor temp. 7°C[44.6°F]DB/ 6°C[42.8°F]WB • Interconnecting Piping Length 7.5m • Level Difference of Zero 2. Capacities are net capacities 3. Due to our policy of innovation some specifications may be changed without prior notification 4. To be added for more available Models 5. EEV : Electronic Expansion Valve 6. Anechoic chamber conversion value is measured at 1.5 m downward from unit centre. The values depends on the ambient conditions and values are normally higher in actual operation.

3 _ Ceiling Cassette 4-way

Conversion Formula kcal/h= kW x 860 Btu/h = kW x 3412 cfm = m3/min x 35.3 l/s = CMM x 1000/60


2. Specifications * Model Name A:Basic, C:Plasma Type Model

4 Way Ceiling Cassette ARNU24GTP*2 ARNU28GTP*2 ARNU36GTN*2 Cooling Capacity 7.1 8.2 10.6 6,100 7,100 9,100 24,200 28,000 36,200 Heating Capacity 8.0 9.2 11.9 6,900 8,000 10,200 27,300 31,500 40,600 Casing Galvanized Steel Plate Galvanized Steel Plate Galvanized Steel Plate Dimensions Body mm 840 x 840 x 204 840 x 840 x 204 840 x 840 x 246 (WxDxH) inch 33.0 x 33.0 x 8.0 33.0 x 33.0 x 8.0 33.0 x 33.0 x 9.7 Front Panel mm 950 x 950 x 25 950 x 950 x 25 950 x 950 x 25 inch 37.4 x 37.4 x 1 37.4 x 37.4 x 1 37.4 x 37.4 x 1 Coil Rows x Columns x FPI 2 x 8 x 19 2 x 8 x 19 2x10x19 Face Area m3 0.40 0.40 0.57 Fan Type Turbo Fan Turbo Fan Turbo Fan Motor Outputx Number W 30 30 135 Running Current A 0.15 0.15 0.56 Air Flow Rate(H / M / L) CMM 17 / 15 / 13 19 / 16 / 14 25 / 21 / 19 cfm 600 / 529 / 459 671 / 565 / 494 883 / 742 / 671 Drive Direct Direct Direct Motor type BLDC BLDC BLDC Temperature Control Microprocessor, Thermostat for cooling and heating Sound Absorbing Thermal Insulation Material Foamed polystrene Foamed polystrene Foamed polystrene Safety Device Fuse Fuse Fuse Pipe Liquid Side mm(inch) Ø9.52(3/8) Ø9.52(3/8) Ø9.52(3/8) Connections Gas Side mm(inch) Ø15.88(5/8) Ø15.88(5/8) Ø15.88(5/8) Drain Pipe(Internal Dia.) mm(inch) 25(1) 25(1) 25(1) Net Weight Body kg(lbs) 20.8(45.8) 20.8(45.8) 23.5(51.8) Noise Level (Sound Press, 1.5m, H / M / L) dB(A) 36 / 34 / 31 39 / 35 / 33 43 / 40 / 37 Power Supply 1, 220-240, 50 1, 220-240, 50 1, 220-240, 50 Ø, V, Hz 1, 220, 60 1, 220, 60 1, 220, 60 Refrigerant Control EEV EEV EEV Power cord CV2.0 X 3C CV2.0 X 3C CV2.0 X 3C Transmission cable CVV-SB 1.0~1.5 X 2C CVV-SB 1.0~1.5 X 2C CVV-SB 1.0~1.5 X 2C Panel Color Morning fog Morning fog Morning fog Panel Name(Accessory) PT-UMC Elevation Grill(Accessory) PTEGM0 Unit kW kcal/h Btu/h kW kcal/h Btu/h

1. Capacities are based on the following conditions: Cooling • Indoor temp. 27°C[80.6°F]DB/ 19°C[66.2°F]WB • Outdoor temp. 35°C[95°F]DB/ 24°C[75.2°F]WB • Interconnecting Piping Length 7.5m • Level Difference of Zero Heating • Indoor temp. 20°C[68°F]DB/ 15°C[59°F]WB • Outdoor temp. 7°C[44.6°F]DB/ 6°C[42.8°F]WB • Interconnecting Piping Length 7.5m • Level Difference of Zero 2. Capacities are net capacities 3. Due to our policy of innovation some specifications may be changed without prior notification 4. To be added for more available Models 5. EEV : Electronic Expansion Valve 6. Anechoic chamber conversion value is measured at 1.5 m downward from unit centre. The values depends on the ambient conditions and values are normally higher in actual operation.

Conversion Formula kcal/h= kW x 860 Btu/h = kW x 3412 cfm = m3/min x 35.3 l/s = CMM x 1000/60

Ceiling Cassette 4-way _ 4

Indoor Units

Notes:-


2. Specifications * Model Name A:Basic, C:Plasma Type Model Cooling Capacity

Heating Capacity

Casing Dimensions (WxDxH)

Body Front Panel

Indoor Units

Coil Fan

Rows x Columns x FPI Face Area Type Motor Outputx Number Running Current Air Flow Rate(H / M / L)

Unit kW kcal/h Btu/h kW kcal/h Btu/h mm inch mm inch m3 W A CMM cfm

Drive Motor type Temperature Control Sound Absorbing Thermal Insulation Material Safety Device Pipe Liquid Side mm(inch) Connections Gas Side mm(inch) Drain Pipe(Internal Dia.) mm(inch) Net Weight Body kg(lbs) Noise Level (Sound Press, 1.5m, H / M / L) dB(A) Power Supply Ø, V, Hz Refrigerant Control Power cord Transmission cable Panel Color Panel Name(Accessory) Elevation Grill(Accessory)

4 Way Ceiling Cassette ARNU42GTM*2 ARNU48GTM*2 12.3 14.1 10,600 12,100 42,000 48,100 13.8 15.9 11,000 13,200 43,800 51,200 Galvanized Steel Plate Galvanized Steel Plate 840 x 840 x 288 840 x 840 x 288 33.0 x 33.0 x 11.3 33.0 x 33.0 x 11.3 950 x 950 x 25 950 x 950 x 25 37.4 x 37.4 x 1 37.4 x 37.4 x 1 2 x 12 x 19 2 x 12 x 19 0.57 0.57 Turbo Fan Turbo Fan 135 135 0.56 0.56 30 / 27 / 24 31 / 29 / 27 1,059 / 954 / 848 1,059 / 1,024 / 954 Direct Direct BLDC BLDC Microprocessor, Thermostat for cooling and heating Foamed polystrene Foamed polystrene Fuse Fuse Ø9.52(3/8) Ø9.52(3/8) Ø15.88(5/8) Ø15.88(5/8) 25(1) 25(1) 25.6(56.4) 25.6(56.4) 44 / 41 / 38 46 / 43 / 41 1, 220-240, 50 1, 220-240, 50 1, 220, 60 1, 220, 60 EEV EEV CV2.0 X 3C CV2.0 X 3C CVV-SB 1.0~1.5 X 2C CVV-SB 1.0~1.5 X 2C Morning fog Morning fog PT-UMC PTEGM0

Notes:1. Capacities are based on the following conditions: Cooling • Indoor temp. 27°C[80.6°F]DB/ 19°C[66.2°F]WB • Outdoor temp. 35°C[95°F]DB/ 24°C[75.2°F]WB • Interconnecting Piping Length 7.5m • Level Difference of Zero Heating • Indoor temp. 20°C[68°F]DB/ 15°C[59°F]WB • Outdoor temp. 7°C[44.6°F]DB/ 6°C[42.8°F]WB • Interconnecting Piping Length 7.5m • Level Difference of Zero 2. Capacities are net capacities 3. Due to our policy of innovation some specifications may be changed without prior notification 4. To be added for more available Models 5. EEV : Electronic Expansion Valve 6. Anechoic chamber conversion value is measured at 1.5 m downward from unit centre. The values depends on the ambient conditions and values are normally higher in actual operation.

5 _ Ceiling Cassette 4-way

Conversion Formula kcal/h= kW x 860 Btu/h = kW x 3412 cfm = m3/min x 35.3 l/s = CMM x 1000/60


Ceiling Cassette 4-way _ 6

6

A

CEILING OPENING

700

473

380(Air outlet hole)

700 B

376(Inlet Grille)

22.5

5

4

523 59.5 84.5

3

A ARROW VIEW

30 19 142.5

2 1

79 53 48

128 570

165

461 570

517

Power supply connection Air discharge grill Air suction grill

3 4 5 6

(unit : mm)

VP25(Φ32)

Unit size(5k, 7k, 9k, 12k):ø12.7

Unit size(5k, 7k, 9k, 12k):ø6.35

Descripition

B ARROW VIEW

500mm or more*

• REQUIRED SPACE

500mm or more*

CHASSIS CODE: TR

500mm or more*

500mm or more*

2. Unit shall be grounded in accordance with the local regulations or applicable national codes.

1. Unit should be installed in compliance with the installation manual in the product box.

Note

Gas pipe connection Drain pipe connection

2

Liquid pipe connection

Name

1

Number

ARNU05GTR*2 ARNU07GTR*2 ARNU09GTR*2 ARNU12GTR*2

Ceiling Cassette 4-way

76, Seongsan-dong, Changwon City, Gyeongnam, 641-713, Korea

Branch Duct Connection

63

69

517 214 34.5

4R20

5

570

Indoor Units

R3

3. Dimensions


A

CEILING OPENING

700

473

380(Air outlet hole)

B

6

376(Inlet Grille) 22.5

5

4

59.5

523

30 19 142.5

2 1

3

A ARROW VIEW

125 95.5

4R20

79 48 570

165

461 570

517

5

174

R3

517

Power supply connection Air discharge grill Air suction grill

3 4 5 6 Note

Gas pipe connection Drain pipe connection

2

Liquid pipe connection

Name

1

Number

(unit : mm)

VP25(Φ32)

Unit size(15k, 18k):Ø12.7

Unit size(15k, 18k):Ø6.35

Descripition

ARNU15GTQ*2 ARNU18GTQ*2

Ceiling Cassette 4-way

76, Seongsan-dong, Changwon City, Gyeongnam, 641-713, Korea

500mm or more*

• REQUIRED SPACE

500mm or more*

CHASSIS CODE: TQ

500mm or more*

500mm or more*

2. Unit shall be grounded in accordance with the local regulations or applicable national codes.

1. Unit should be installed in compliance with the installation manual in the product box.

B ARROW VIEW

Branch Duct Connection

63

68

570

256

7 _ Ceiling Cassette 4-way 76 94

Indoor Units

3. Dimensions

700


Ceiling Cassette 4-way _ 8

31

475

71

B ARROW VIEW

35

Ceiling opening

870-920(CEILING OPENING SPACE) 786(SUSPENSION POSITION)

500(Air outlet Hole) 737 950

614(Inlet Grille) 682(SUSPENSION POSITION)

ø70

OUTDOOR AIR INTAKE (DIRECT CONNECTION)

B

62

669(SUSPENSION POSITION) 420 393

13-ø 3, 3 Hole

26

71

300 OR LESS

420

950

25 870-920(CEILING OPENING SPACE)

6

2

A

65 40

5

671 108 60

1

840

165

350

53.5

60 82 99

4

3 Branch Duct Connection

80

840

787

787

804

204

BRANCH DUCT CONNECTION

684 840 92

VP25(Φ32)

Unit size(24k, 28k):ø15.88

Unit size(24k, 28k):ø9.52

92

10 350

50

92

165

92

500mm or more*

BRANCH DUCT CONNECTION

500mm or more*

CHASSIS CODE: TP

500mm or more*

500mm or more*

• REQUIRED SPACE

2. Unit shall be grounded in accordance with the local regulations or applicable national codes.

A ARROW VIEW

165

(unit : mm) Descripition

1. Unit should be installed in compliance with the installation manual in the product box.

Note

Air suction grill

4

Air discharge grill

Drain pipe connection Power supply connection

3

6

Gas pipe connection

2

5

Liquid pipe connection

Name

1

Number

ARNU24GTP*2 ARNU28GTP*2

Ceiling Cassette 4-way

76, Seongsan-dong, Changwon City, Gyeongnam, 641-713, Korea

13-ø 3, 3 Hole

79

204 154 79 41.5

32 50 50

Indoor Units

4-R20

3. Dimensions


13-ø 3, 3 Hole

35

71

B

ø70

OUTDOOR AIR INTAKE (DIRECT CONNECTION)

B ARROW VIEW

31

475

Ceiling opening

786(SUSPENSION POSITION)

870-920(CEILING OPENING SPACE)

682(SUSPENSION POSITION)

500(Air outlet Hole) 737 950

614(Inlet Grille) 25

2

870-920(CEILING OPENING SPACE)

6

110

1

A

60 840

165

350

103 141

246

3

4

Branch Duct Connection

53.5

80

840

78

5

420

300 OR LESS 80

669(SUSPENSION POSITION) 420 393

44

71

950 40 107

246 195 100 52

BRANCH DUCT CONNECTION 43 60

4-R20

13-ø 3, 3 Hole

100

9 _ Ceiling Cassette 4-way 60

165

10 350

92

165

92 BRANCH DUCT CONNECTION

500mm or more*

500mm or more*

CHASSIS CODE: TN

500mm or more*

500mm or more*

• REQUIRED SPACE

2. Unit shall be grounded in accordance with the local regulations or applicable national codes.

A ARROW VIEW

92

VP25(Φ32)

Unit size(36k):ø15.88

Unit size(36k):ø9.52

Descripition

(unit : mm)

1. Unit should be installed in compliance with the installation manual in the product box.

Note

76, Seongsan-dong, Changwon City, Gyeongnam, 641-713, Korea

92

5

Air suction grill

Air discharge grill

4 6

Drain pipe connection Power supply connection

3

Gas pipe connection

2

Name Liquid pipe connection

ARNU36GTN*2

Ceiling Cassette 4-way

1

Number

Indoor Units

3. Dimensions


Ceiling Cassette 4-way _ 10

6

75

31

475

ø70

B

OUTDOOR AIR INTAKE (DIRECT CONNECTION)

B ARROW VIEW

35

71

Ceiling opening

682(SUSPENSION POSITION) 110

870-920(CEILING OPENING SPACE) 786(SUSPENSION POSITION)

300 OR LESS

420

614(Inlet Grille)

25 870-920(CEILING OPENING SPACE)

500(Air outlet Hole) 737 950

2

A

1 100 84

669(SUSPENSION POSITION) 420 393

13-ø 3, 3 Hole

71

288 165

237 350

53.5

Branch Duct Connection

3

4 76 60

136 13-ø 3, 3 Hole

BRANCH DUCTCONNECTION

60

840

Air suction grill

5 6

(unit : mm)

VP25(Φ32)

Unit size(42k, 48k):ø15.88

Unit size(42k, 48k):ø9.52

Descripition

10 350

92

165

92

500mm or more*

CHASSIS CODE: TM

500mm or more*

500mm or more*

• REQUIRED SPACE

500mm or more*

BRANCH DUCT CONNECTION

2. Unit shall be grounded in accordance with the local regulations or applicable national codes.

1. Unit should be installed in compliance with the installation manual in the product box.

A ARROW VIEW

165

92

Air discharge grill

4

76, Seongsan-dong, Changwon City, Gyeongnam, 641-713, Korea

92

Power supply connection

3

Note

Gas pipe connection Drain pipe connection

2

Liquid pipe connection

Name

ARNU42GTM*2 ARNU48GTM*2

Ceiling Cassette 4-way

1

Number

100

5

Indoor Units

4-R20

3. Dimensions

950


4. Piping Diagrams

Heat Exchanger

:Cooling :Heating

EEV Filter

Th3

Th2 Turbo Fan

Filter

lndoor unit

Indoor Units

Th1

Refrigerant pipe connection port diameter [Unit: mm(inch)]

Model

Gas

Liquid

ARNU05GTR*2

Ø12.7(1/2)

Ø6.35(1/4)

ARNU07GTR*2

Ø12.7(1/2)

Ø6.35(1/4)

ARNU09GTR*2

Ø12.7(1/2)

Ø6.35(1/4)

ARNU12GTR*2

Ø12.7(1/2)

Ø6.35(1/4)

ARNU15GTQ*2

Ø12.7(1/2)

Ø6.35(1/4)

ARNU18GTQ*2

Ø12.7(1/2)

Ø6.35(1/4)

ARNU24GTP*2

Ø15.88(5/8)

Ø9.52(3/8)

ARNU28GTP*2

Ø15.88(5/8)

Ø9.52(3/8)

ARNU36GTN*2

Ø15.88(5/8)

Ø9.52(3/8)

ARNU42GTM*2

Ø15.88(5/8)

Ø9.52(3/8)

ARNU48GTM*2

Ø15.88(5/8)

Ø9.52(3/8)

LOC.

Description

Th1

Room thermistor

Th2

Pipe in thermistor

Th3

Pipe out thermistor

11 _ Ceiling Cassette 4-way


5. Wiring Diagrams TR/TQ Chassis

LOCATION POINT AC Power supply Fan motor output Drain pump output Communication Display EEV Output Step motor Float switch input Suction pipe sensor Discharge pipe sensor Room sensor Remote controller Dry contact Air clean

Dip Switch Setting SW3 GROUP

Off Master

On Slave

SW4

DRY CONTACT

Variable

Auto

SW5

EXTRA 1

Off

On

FUNCTION AC Power line input for indoor controller Motor output of BLDC AC output for drain pump Connection between indoor and outdoor Display of indoor status EEV Control output Step motor output Float switch sensing Pipe in thermistor Pipe out thermistor Room air thermistor Remote control line Dry contact line Air cleaner control Remarks Group Control setting using Wired Remote Controller Old Dry Contact Mode Setting 1. Variable : Auto/Manual Mode can be chosen by Wide wired remote controller or Wireless remote controller (When shipped from Factory → Manual Mode) 2. Auto : For Dry Contact, it is always Auto mode. 1. Duct model -. OFF : Default(not operate continuosly ) -. ON : Fan operate continuosly 2. Cassette Model : No Function 3. Ceiling Suspended Model -. OFF : Ceiling(default) -. ON : Floor

CAUTION For Multi V Model, Dip Switch 1,2,6,7,8 must be set OFF That dip switch is used for the other model.

Ceiling Cassette 4-way _ 12

Indoor Units

CONNECTOR NUMBER CN-POWER CN-MOTOR1 CN-D/PUMP CN-485 CN-DISP CN-EEV CN-VANE2 CN-FLOAT CN-PIPE/IN CN-PIPE/OUT CN-ROOM CN-REMO CN-CC CN-AIRC


5. Wiring Diagrams

Indoor Units

TM/TN/TP Chassis

CONNECTOR NUMBER CN-POWER CN-MOTOR1 CN-D/PUMP CN-485 CN-DISP CN-EEV CN-VANE1 / VANE2 CN-FLOAT CN-PIPE/IN CN-PIPE/OUT CN-ROOM CN-REMO CN-CC CN-AIRC

LOCATION POINT AC Power supply Fan motor output Drain pump output Communication Display EEV Output Step motor Float switch input Suction pipe sensor Discharge pipe sensor Room sensor Remote controller Dry contact Air clean

Dip Switch Setting SW3 GROUP

Off Master

On Slave

SW4

DRY CONTACT

Variable

Auto

SW5

EXTRA 1

Off

On

FUNCTION AC Power line input for indoor controller Motor output of BLDC AC output for drain pump Connection between indoor and outdoor Display of indoor status EEV Control output Step motor output Float switch sensing Pipe in thermistor Pipe out thermistor Room air thermistor Remote control line Dry contact line Air cleaner control Remarks Group Control setting using Wired Remote Controller Old Dry Contact Mode Setting 1. Variable : Auto/Manual Mode can be chosen by Wide wired remote controller or Wireless remote controller (When shipped from Factory → Manual Mode) 2. Auto : For Dry Contact, it is always Auto mode. 1. Duct model -. OFF : Default(not operate continuosly ) -. ON : Fan operate continuosly 2. Cassette Model : No Function 3. Ceiling Suspended Model -. OFF : Ceiling(default) -. ON : Floor

CAUTION For Multi V Model, Dip Switch 1,2,6,7,8 must be set OFF That dip switch is used for the other model.

13 _ Ceiling Cassette 4-way


6. Capacity Tables 6.1 Cooling Capacity

Capacity Index

1.6

2.8

10 12 14 16 18 20 21 23 25 27 29 31 33 35 37 39 10 12 14 16 18 20 21 23 25 27 29 31 33 35 37 39 10 12 14 16 18 20 21 23 25 27 29 31 33 35 37 39

Notes: TC: Total Capacity(kW)

20 14 TC SHC kW kW

23 16 TC SHC kW kW

Indoor air temp. (DB/WB, °C) 26 27 28 18 19 20 TC SHC TC SHC TC SHC kW kW kW kW kW kW

30 22 TC SHC kW kW

1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9

1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3

1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6

1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4

1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7

1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8

1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0

1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8

1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0

1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0

1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1

1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2

32 24 TC SHC kW kW 2.1 2.1 2.1 2.0 2.0 2.0 2.0 1.9 1.9 1.9 1.8 1.8 1.8 1.8 1.7 1.7 2.9 2.9 2.8 2.8 2.7 2.7 2.7 2.6 2.6 2.6 2.5 2.5 2.5 2.4 2.4 2.3 3.7 3.6 3.6 3.5 3.5 3.4 3.4 3.4 3.3 3.3 3.2 3.2 3.1 3.1 3.0 3.0

1.3 1.3 1.3 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.1 1.1 1.1 1.1 1.1 1.1 1.8 1.7 1.7 1.7 1.7 1.6 1.6 1.6 1.6 1.6 1.5 1.5 1.5 1.5 1.5 1.4 2.1 2.1 2.1 2.1 2.0 2.0 2.0 2.0 1.9 1.9 1.9 1.9 1.8 1.8 1.8 1.7

SHC: Sensible Heat Capacity(kW)

Ceiling Cassette 4-way _ 14

Indoor Units

2.2

Outdoor air temp. (DB, °C)

Cooling capacity


6. Capacity Tables Cooling capacity

Capacity Index

Indoor Units

3.6

4.5

5.6

Outdoor air temp. (DB, °C) 10 12 14 16 18 20 21 23 25 27 29 31 33 35 37 39 10 12 14 16 18 20 21 23 25 27 29 31 33 35 37 39 10 12 14 16 18 20 21 23 25 27 29 31 33 35 37 39

20 14 TC SHC kW kW

23 16 TC SHC kW kW

Indoor air temp. (DB/WB, °C) 26 27 28 18 19 20 TC SHC TC SHC TC SHC kW kW kW kW kW kW

30 22 TC SHC kW kW

2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8

2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5

3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2

4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 6.7 6.7 6.7 6.7 6.7 6.7 6.7 6.7 6.7 6.7 6.7 6.7 6.7 6.7 6.7 6.7

2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2

Notes: TC: Total Capacity(kW)

15 _ Ceiling Cassette 4-way

2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6

2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9

3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6

2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9

SHC: Sensible Heat Capacity(kW)

3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0

2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0

2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2

32 24 TC SHC kW kW 4.7 4.7 4.6 4.6 4.5 4.4 4.4 4.3 4.3 4.2 4.2 4.1 4.0 4.0 3.9 3.8 5.9 5.8 5.8 5.7 5.6 5.5 5.5 5.4 5.3 5.3 5.2 5.1 5.0 5.0 4.9 4.8 7.4 7.3 7.2 7.1 7.0 6.9 6.8 6.7 6.6 6.6 6.5 6.4 6.3 6.2 6.1 6.0

2.7 2.6 2.6 2.6 2.5 2.5 2.5 2.5 2.4 2.4 2.4 2.3 2.3 2.2 2.2 2.2 3.5 3.5 3.4 3.4 3.3 3.3 3.3 3.2 3.2 3.1 3.1 3.0 3.0 2.9 2.9 2.8 4.2 4.1 4.1 4.0 4.0 3.9 3.9 3.8 3.8 3.7 3.7 3.6 3.6 3.5 3.5 3.4


6. Capacity Tables Cooling capacity

20 14 TC SHC kW kW

23 16 TC SHC kW kW

Indoor air temp. (DB/WB, °C) 26 27 28 18 19 20 TC SHC TC SHC TC SHC kW kW kW kW kW kW

30 22 TC SHC kW kW

Capacity Index

Outdoor air temp. (DB, °C)

7.1

10 12 14 16 18 20 21 23 25 27 29 31 33 35 37 39

4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8

4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2

5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7

4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6

6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6

5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0

7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1

5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1

7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.4 7.2

5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.1 5.0

8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.4 8.2 8.1 8.0 7.8 7.7 7.5 7.4

5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.4 5.3 5.2 5.1 5.1 5.0 4.9 4.8

9.3 9.2 9.1 9.0 8.8 8.7 8.7 8.5 8.4 8.3 8.2 8.1 7.9 7.8 7.7 7.6

5.4 5.4 5.3 5.2 5.2 5.1 5.1 5.0 4.9 4.9 4.8 4.7 4.6 4.6 4.5 4.4

8.2

10 12 14 16 18 20 21 23 25 27 29 31 33 35 37 39

5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5

4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9

6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6

5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4

7.7 7.7 7.7 7.7 7.7 7.7 7.7 7.7 7.7 7.7 7.7 7.7 7.7 7.7 7.7 7.7

5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8 5.8

8.2 8.2 8.2 8.2 8.2 8.2 8.2 8.2 8.2 8.2 8.2 8.2 8.2 8.2 8.2 8.2

5.9 5.9 5.9 5.9 5.9 5.9 5.9 5.9 5.9 5.9 5.9 5.9 5.9 5.9 5.9 5.9

8.7 8.7 8.7 8.7 8.7 8.7 8.7 8.7 8.7 8.7 8.7 8.7 8.7 8.7 8.5 8.4

6.1 6.1 6.1 6.1 6.1 6.1 6.1 6.1 6.1 6.1 6.1 6.1 6.1 6.1 5.9 5.8

9.8 9.8 9.8 9.8 9.8 9.8 9.8 9.8 9.7 9.4 9.3 9.2 9.0 8.9 8.7 8.5

6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.3 6.1 6.1 5.9 5.8 5.7 5.6 5.5

10.8 10.6 10.5 10.4 10.2 10.1 10.0 9.9 9.7 9.6 9.5 9.3 9.2 9.0 8.9 8.8

6.3 6.2 6.1 6.1 6.0 5.9 5.8 5.8 5.7 5.6 5.5 5.4 5.4 5.3 5.2 5.1

10.6

10 12 14 16 18 20 21 23 25 27 29 31 33 35 37 39

7.2 7.2 7.2 7.2 7.2 7.2 7.2 7.2 7.2 7.2 7.2 7.2 7.2 7.2 7.2 7.2

6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3 6.3

8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5

6.9 6.9 6.9 6.9 6.9 6.9 6.9 6.9 6.9 6.9 6.9 6.9 6.9 6.9 6.9 6.9

9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9

7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5

10.6 10.6 10.6 10.6 10.6 10.6 10.6 10.6 10.6 10.6 10.6 10.6 10.6 10.6 10.6 10.6

7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6

11.3 11.3 11.3 11.3 11.3 11.3 11.3 11.3 11.3 11.3 11.3 11.3 11.3 11.3 11.0 10.8

7.9 7.9 7.9 7.9 7.9 7.9 7.9 7.9 7.9 7.9 7.9 7.9 7.9 7.9 7.7 7.5

12.7 12.7 12.7 12.7 12.7 12.7 12.7 12.7 12.5 12.2 12.1 11.9 11.7 11.4 11.2 11.0

8.2 8.2 8.2 8.2 8.2 8.2 8.2 8.2 8.1 7.9 7.8 7.7 7.6 7.4 7.3 7.1

13.9 13.7 13.6 13.4 13.2 13.0 12.9 12.8 12.6 12.4 12.2 12.0 11.8 11.7 11.5 11.3

8.1 8.0 7.9 7.8 7.7 7.6 7.6 7.5 7.3 7.3 7.1 7.0 6.9 6.8 6.7 6.6

SHC: Sensible Heat Capacity(kW)

Ceiling Cassette 4-way _ 16

Indoor Units

Notes: TC: Total Capacity(kW)

32 24 TC SHC kW kW


6. Capacity Tables Cooling capacity

Capacity Index

Indoor Units

12.3

14.1

Outdoor air temp. (DB, °C) 10 12 14 16 18 20 21 23 25 27 29 31 33 35 37 39 10 12 14 16 18 20 21 23 25 27 29 31 33 35 37 39

20 14 TC SHC kW kW

23 16 TC SHC kW kW

Indoor air temp. (DB/WB, °C) 26 27 28 18 19 20 TC SHC TC SHC TC SHC kW kW kW kW kW kW

8.3 8.3 8.3 8.3 8.3 8.3 8.3 8.3 8.3 8.3 8.3 8.3 8.3 8.3 8.3 8.3 9.5 9.5 9.5 9.5 9.5 9.5 9.5 9.5 9.5 9.5 9.5 9.5 9.5 9.5 9.5 9.5

9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 11.3 11.3 11.3 11.3 11.3 11.3 11.3 11.3 11.3 11.3 11.3 11.3 11.3 11.3 11.3 11.3

11.5 11.5 11.5 11.5 11.5 11.5 11.5 11.5 11.5 11.5 11.5 11.5 11.5 11.5 11.5 11.5 13.2 13.2 13.2 13.2 13.2 13.2 13.2 13.2 13.2 13.2 13.2 13.2 13.2 13.2 13.2 13.2

7.3 7.3 7.3 7.3 7.3 7.3 7.3 7.3 7.3 7.3 7.3 7.3 7.3 7.3 7.3 7.3 8.3 8.3 8.3 8.3 8.3 8.3 8.3 8.3 8.3 8.3 8.3 8.3 8.3 8.3 8.3 8.3

Notes: TC: Total Capacity(kW)

17 _ Ceiling Cassette 4-way

8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 9.2 9.2 9.2 9.2 9.2 9.2 9.2 9.2 9.2 9.2 9.2 9.2 9.2 9.2 9.2 9.2

8.7 8.7 8.7 8.7 8.7 8.7 8.7 8.7 8.7 8.7 8.7 8.7 8.7 8.7 8.7 8.7 10.0 10.0 10.0 10.0 10.0 10.0 10.0 10.0 10.0 10.0 10.0 10.0 10.0 10.0 10.0 10.0

12.3 12.3 12.3 12.3 12.3 12.3 12.3 12.3 12.3 12.3 12.3 12.3 12.3 12.3 12.3 12.3 14.1 14.1 14.1 14.1 14.1 14.1 14.1 14.1 14.1 14.1 14.1 14.1 14.1 14.1 14.1 14.1

8.9 8.9 8.9 8.9 8.9 8.9 8.9 8.9 8.9 8.9 8.9 8.9 8.9 8.9 8.9 8.9 10.2 10.2 10.2 10.2 10.2 10.2 10.2 10.2 10.2 10.2 10.2 10.2 10.2 10.2 10.2 10.2

SHC: Sensible Heat Capacity(kW)

13.1 13.1 13.1 13.1 13.1 13.1 13.1 13.1 13.1 13.1 13.1 13.1 13.1 13.1 12.8 12.5 15.0 15.0 15.0 15.0 15.0 15.0 15.0 15.0 15.0 15.0 15.0 15.0 15.0 15.0 14.7 14.4

9.1 9.1 9.1 9.1 9.1 9.1 9.1 9.1 9.1 9.1 9.1 9.1 9.1 9.1 8.9 8.7 10.5 10.5 10.5 10.5 10.5 10.5 10.5 10.5 10.5 10.5 10.5 10.5 10.5 10.5 10.2 10.0

30 22 TC SHC kW kW

32 24 TC SHC kW kW

14.7 14.7 14.7 14.7 14.7 14.7 14.7 14.7 14.5 14.1 14.0 13.8 13.5 13.3 13.0 12.8 16.9 16.9 16.9 16.9 16.9 16.9 16.9 16.9 16.6 16.2 16.1 15.8 15.5 15.2 14.9 14.7

16.2 15.9 15.8 15.6 15.3 15.1 15.0 14.8 14.6 14.4 14.2 14.0 13.7 13.5 13.4 13.1 18.5 18.3 18.1 17.8 17.6 17.3 17.2 17.0 16.7 16.5 16.3 16.0 15.8 15.5 15.3 15.1

9.5 9.5 9.5 9.5 9.5 9.5 9.5 9.5 9.4 9.2 9.1 8.9 8.8 8.6 8.4 8.3 10.9 10.9 10.9 10.9 10.9 10.9 10.9 10.9 10.8 10.5 10.4 10.2 10.0 9.9 9.7 9.5

9.4 9.3 9.2 9.1 9.0 8.8 8.8 8.6 8.5 8.4 8.3 8.2 8.0 7.9 7.8 7.7 10.8 10.7 10.6 10.4 10.3 10.1 10.1 9.9 9.8 9.6 9.5 9.4 9.2 9.1 8.9 8.8


6. Capacity Tables 6.2 Heating Capacity Outdoor air temp. Capacity Index DB(°C) WB(°C)

1.6

2.8

-20.0 -19.0 -17.0 -15.0 -13.0 -11.0 -10.0 -9.1 -7.6 -5.6 -3.7 -0.7 2.2 4.1 6.0 7.9 9.8 11.8 13.7 -20.0 -19.0 -17.0 -15.0 -13.0 -11.0 -10.0 -9.1 -7.6 -5.6 -3.7 -0.7 2.2 4.1 6.0 7.9 9.8 11.8 13.7 -20.0 -19.0 -17.0 -15.0 -13.0 -11.0 -10.0 -9.1 -7.6 -5.6 -3.7 -0.7 2.2 4.1 6.0 7.9 9.8 11.8 13.7

Indoor air temp. (DB, °C) 16

18

20

21

22

24

TC

TC

TC

TC

TC

TC

kW

kW

kW

kW

kW

kW

1.2 1.2 1.3 1.4 1.5 1.5 1.5 1.6 1.6 1.7 1.8 1.9 2.0 2.0 2.1 2.1 2.1 2.1 2.1 1.7 1.7 1.8 1.9 2.0 2.1 2.2 2.2 2.3 2.4 2.5 2.6 2.8 2.8 2.9 2.9 2.9 2.9 2.9 2.1 2.2 2.3 2.5 2.6 2.7 2.8 2.8 2.9 3.0 3.2 3.4 3.6 3.6 3.7 3.7 3.7 3.7 3.7

1.2 1.2 1.3 1.4 1.5 1.5 1.5 1.6 1.6 1.7 1.8 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.7 1.7 1.8 1.9 2.0 2.1 2.2 2.2 2.3 2.4 2.5 2.6 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.1 2.2 2.3 2.4 2.6 2.7 2.8 2.8 2.9 3.0 3.2 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4

1.2 1.2 1.3 1.2 1.3 1.4 1.4 1.4 1.5 1.5 1.6 1.7 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.7 1.7 1.8 1.7 1.8 1.9 1.9 2.0 2.0 2.1 2.2 2.3 2.4 2.5 2.5 2.5 2.5 2.5 2.5 2.1 2.2 2.3 2.2 2.3 2.4 2.5 2.5 2.6 2.7 2.8 3.0 3.1 3.2 3.2 3.2 3.2 3.2 3.2

1.2 1.2 1.3 1.4 1.4 1.5 1.5 1.6 1.6 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.8 1.9 2.0 2.1 2.2 2.2 2.2 2.3 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.1 2.2 2.3 2.4 2.6 2.7 2.8 2.8 2.8 3.0 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1

1.2 1.2 1.3 1.4 1.4 1.5 1.5 1.6 1.6 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.8 1.9 2.0 2.1 2.2 2.2 2.2 2.3 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.1 2.2 2.3 2.4 2.6 2.7 2.8 2.8 2.8 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0

1.2 1.2 1.3 1.4 1.4 1.5 1.5 1.5 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.7 1.7 1.8 1.9 2.0 2.1 2.1 2.1 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.1 2.2 2.3 2.4 2.6 2.7 2.7 2.7 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8

Notes: TC: Total Capacity(kW)

Ceiling Cassette 4-way _ 18

Indoor Units

2.2

-19.8 -18.8 -16.7 -14.7 -12.6 -10.5 -9.5 -8.5 -7.0 -5.0 -3.0 0.0 3.0 5.0 7.0 9.0 11.0 13.0 15.0 -19.8 -18.8 -16.7 -14.7 -12.6 -10.5 -9.5 -8.5 -7.0 -5.0 -3.0 0.0 3.0 5.0 7.0 9.0 11.0 13.0 15.0 -19.8 -18.8 -16.7 -14.7 -12.6 -10.5 -9.5 -8.5 -7.0 -5.0 -3.0 0.0 3.0 5.0 7.0 9.0 11.0 13.0 15.0

Heating capacity


6. Capacity Tables Heating capacity Outdoor air temp. Capacity Index DB(°C) WB(°C)

Indoor Units

3.6

4.5

5.6

-19.8 -18.8 -16.7 -14.7 -12.6 -10.5 -9.5 -8.5 -7.0 -5.0 -3.0 0.0 3.0 5.0 7.0 9.0 11.0 13.0 15.0 -19.8 -18.8 -16.7 -14.7 -12.6 -10.5 -9.5 -8.5 -7.0 -5.0 -3.0 0.0 3.0 5.0 7.0 9.0 11.0 13.0 15.0 -19.8 -18.8 -16.7 -14.7 -12.6 -10.5 -9.5 -8.5 -7.0 -5.0 -3.0 0.0 3.0 5.0 7.0 9.0 11.0 13.0 15.0

-20.0 -19.0 -17.0 -15.0 -13.0 -11.0 -10.0 -9.1 -7.6 -5.6 -3.7 -0.7 2.2 4.1 6.0 7.9 9.8 11.8 13.7 -20.0 -19.0 -17.0 -15.0 -13.0 -11.0 -10.0 -9.1 -7.6 -5.6 -3.7 -0.7 2.2 4.1 6.0 7.9 9.8 11.8 13.7 -20.0 -19.0 -17.0 -15.0 -13.0 -11.0 -10.0 -9.1 -7.6 -5.6 -3.7 -0.7 2.2 4.1 6.0 7.9 9.8 11.8 13.7

Indoor air temp. (DB, °C) 16

18

20

21

22

24

TC

TC

TC

TC

TC

TC

kW

kW

kW

kW

kW

kW

2.7 2.8 2.9 3.1 3.2 3.4 3.4 3.5 3.6 3.8 4.0 4.2 4.4 4.5 4.6 4.6 4.6 4.6 4.6 3.4 3.5 3.7 3.9 4.1 4.3 4.3 4.4 4.6 4.8 5.0 5.3 5.6 5.6 5.8 5.8 5.8 5.8 5.8 4.2 4.3 4.6 4.9 5.1 5.4 5.4 5.5 5.7 6.0 6.2 6.6 7.0 7.1 7.2 7.2 7.2 7.2 7.2

2.7 2.8 2.9 3.0 3.2 3.4 3.4 3.5 3.6 3.8 4.0 4.2 4.3 4.3 4.3 4.3 4.3 4.3 4.3 3.4 3.5 3.7 3.8 4.1 4.3 4.3 4.4 4.6 4.8 5.0 5.3 5.4 5.4 5.4 5.4 5.4 5.4 5.4 4.2 4.3 4.6 4.8 5.1 5.4 5.4 5.5 5.7 6.0 6.2 6.6 6.7 6.7 6.7 6.7 6.7 6.7 6.7

2.7 2.8 2.9 2.7 2.9 3.0 3.1 3.2 3.3 3.4 3.5 3.7 3.9 4.0 4.0 4.0 4.0 4.0 4.0 3.4 3.5 3.7 3.4 3.6 3.8 3.9 4.0 4.1 4.3 4.4 4.6 4.9 5.0 5.0 5.0 5.0 5.0 5.0 4.2 4.3 4.6 4.3 4.5 4.8 4.9 5.0 5.1 5.4 5.5 5.8 6.2 6.3 6.3 6.3 6.3 6.3 6.3

2.6 2.8 2.9 3.0 3.2 3.4 3.4 3.5 3.6 3.7 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.3 3.5 3.7 3.8 4.0 4.3 4.3 4.4 4.4 4.6 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.2 4.3 4.6 4.8 5.0 5.4 5.4 5.5 5.6 5.8 6.1 6.1 6.1 6.1 6.1 6.1 6.1 6.1 6.1

2.6 2.7 2.9 3.0 3.2 3.4 3.4 3.5 3.6 3.7 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.3 3.4 3.7 3.8 4.0 4.2 4.3 4.4 4.4 4.6 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.2 4.3 4.6 4.8 5.0 5.3 5.4 5.5 5.6 5.8 5.9 5.9 5.9 5.9 5.9 5.9 5.9 5.9 5.9

2.6 2.7 2.9 3.0 3.2 3.4 3.4 3.4 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.3 3.4 3.6 3.8 4.0 4.2 4.3 4.3 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.2 4.3 4.5 4.8 5.0 5.3 5.4 5.4 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5

Notes: TC: Total Capacity(kW)

19 _ Ceiling Cassette 4-way


6. Capacity Tables Heating capacity Outdoor air temp. Capacity Index DB(°C) WB(°C)

7.1

10.6

16

18

20

21

22

24

TC

TC

TC

TC

TC

TC

kW

kW

kW

kW

kW

kW

-19.8 -18.8 -16.7 -14.7 -12.6 -10.5 -9.5 -8.5 -7.0 -5.0 -3.0 0.0 3.0 5.0 7.0 9.0 11.0 13.0 15.0 -19.8 -18.8 -16.7 -14.7 -12.6 -10.5 -9.5 -8.5 -7.0 -5.0 -3.0 0.0 3.0 5.0 7.0 9.0 11.0 13.0 15.0

-20.0 -19.0 -17.0 -15.0 -13.0 -11.0 -10.0 -9.1 -7.6 -5.6 -3.7 -0.7 2.2 4.1 6.0 7.9 9.8 11.8 13.7 -20.0 -19.0 -17.0 -15.0 -13.0 -11.0 -10.0 -9.1 -7.6 -5.6 -3.7 -0.7 2.2 4.1 6.0 7.9 9.8 11.8 13.7

5.4 5.5 5.8 6.2 6.5 6.8 6.9 7.0 7.3 7.6 7.9 8.4 8.9 9.0 9.2 9.2 9.2 9.2 9.2 6.2 6.3 6.7 7.1 7.5 7.8 7.9 8.1 8.4 8.7 9.1 9.7 10.2 10.4 10.6 10.6 10.6 10.6 10.6

5.4 5.5 5.8 6.1 6.5 6.8 6.9 7.0 7.3 7.6 7.9 8.4 8.6 8.6 8.6 8.6 8.6 8.6 8.6 6.2 6.3 6.7 7.0 7.5 7.8 7.9 8.1 8.4 8.7 9.1 9.7 9.8 9.8 9.8 9.8 9.8 9.8 9.8

5.4 5.5 5.8 5.5 5.8 6.0 6.2 6.3 6.5 6.8 7.0 7.4 7.8 8.0 8.0 8.0 8.0 8.0 8.0 6.2 6.3 6.7 6.3 6.6 7.0 7.1 7.3 7.5 7.8 8.1 8.5 9.0 9.2 9.2 9.2 9.2 9.2 9.2

5.3 5.5 5.8 6.1 6.4 6.8 6.9 7.0 7.1 7.4 7.7 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 6.1 6.3 6.7 7.0 7.4 7.8 7.9 8.1 8.2 8.5 8.9 8.9 8.9 8.9 8.9 8.9 8.9 8.9 8.9

5.3 5.4 5.8 6.1 6.4 6.7 6.9 7.0 7.1 7.4 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 6.1 6.3 6.7 7.0 7.4 7.7 7.9 8.1 8.2 8.5 8.6 8.6 8.6 8.6 8.6 8.6 8.6 8.6 8.6

5.3 5.4 5.8 6.1 6.4 6.7 6.8 6.8 7.0 7.0 7.0 7.0 7.0 7.0 7.0 7.0 7.0 7.0 7.0 6.1 6.3 6.6 7.0 7.4 7.7 7.8 7.9 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0

-19.8 -18.8 -16.7 -14.7 -12.6 -10.5 -9.5 -8.5 -7.0 -5.0 -3.0 0.0 3.0 5.0 7.0 9.0 11.0 13.0 15.0

-20.0 -19.0 -17.0 -15.0 -13.0 -11.0 -10.0 -9.1 -7.6 -5.6 -3.7 -0.7 2.2 4.1 6.0 7.9 9.8 11.8 13.7

8.0 8.2 8.7 9.2 9.6 10.1 10.2 10.5 10.8 11.3 11.8 12.5 13.2 13.4 13.7 13.7 13.7 13.7 13.7

8.0 8.2 8.7 9.0 9.6 10.1 10.2 10.5 10.8 11.3 11.8 12.5 12.7 12.7 12.7 12.7 12.7 12.7 12.7

8.0 8.2 8.7 8.2 8.6 9.0 9.2 9.4 9.7 10.1 10.4 11.0 11.6 11.9 11.9 11.9 11.9 11.9 11.9

7.9 8.2 8.7 9.0 9.5 10.1 10.2 10.5 10.6 11.0 11.5 11.5 11.5 11.5 11.5 11.5 11.5 11.5 11.5

7.9 8.1 8.7 9.0 9.5 10.0 10.2 10.5 10.6 11.0 11.2 11.2 11.2 11.2 11.2 11.2 11.2 11.2 11.2

7.9 8.1 8.6 9.1 9.5 10.0 10.1 10.2 10.4 10.4 10.4 10.4 10.4 10.4 10.4 10.4 10.4 10.4 10.4

Notes: TC: Total Capacity(kW)

Ceiling Cassette 4-way _ 20

Indoor Units

8.2

Indoor air temp. (DB, °C)


6. Capacity Tables Heating capacity Outdoor air temp. Capacity Index DB(°C) WB(°C)

Indoor air temp. (DB, °C) 16

18

20

21

22

24

TC

TC

TC

TC

TC

TC

kW

kW

kW

kW

kW

12.3

-20.0 -19.0 -17.0 -15.0 -13.0 -11.0 -10.0 -9.1 -7.6 -5.6 -3.7 -0.7 2.2 4.1 6.0 7.9 9.8 11.8 13.7

9.2 9.5 10.1 10.6 11.2 11.7 11.9 12.1 12.6 13.1 13.7 14.5 15.3 15.5 15.9 15.9 15.9 15.9 15.9

9.2 9.5 10.1 10.5 11.2 11.7 11.9 12.1 12.6 13.1 13.7 14.5 14.8 14.8 14.8 14.8 14.8 14.8 14.8

9.2 9.5 10.1 9.5 10.0 10.4 10.7 10.9 11.3 11.7 12.1 12.8 13.5 13.8 13.8 13.8 13.8 13.8 13.8

9.1 9.5 10.1 10.5 11.0 11.7 11.9 12.1 12.2 12.8 13.3 13.4 13.4 13.4 13.4 13.4 13.4 13.4 13.4

9.1 9.4 10.1 10.5 11.0 11.6 11.9 12.1 12.2 12.8 13.0 13.0 13.0 13.0 13.0 13.0 13.0 13.0 13.0

9.1 9.4 9.9 10.5 11.0 11.6 11.7 11.8 12.1 12.1 12.1 12.1 12.1 12.1 12.1 12.1 12.1 12.1 12.1

14.1

-19.8 -18.8 -16.7 -14.7 -12.6 -10.5 -9.5 -8.5 -7.0 -5.0 -3.0 0.0 3.0 5.0 7.0 9.0 11.0 13.0 15.0

-20.0 -19.0 -17.0 -15.0 -13.0 -11.0 -10.0 -9.1 -7.6 -5.6 -3.7 -0.7 2.2 4.1 6.0 7.9 9.8 11.8 13.7

10.7 11.0 11.6 12.2 12.9 13.5 13.7 14.0 14.5 15.1 15.7 16.7 17.7 17.9 18.3 18.3 18.3 18.3 18.3

10.7 11.0 11.6 12.1 12.9 13.5 13.7 14.0 14.5 15.1 15.7 16.7 17.0 17.0 17.0 17.0 17.0 17.0 17.0

10.7 11.0 11.6 10.9 11.5 12.0 12.3 12.6 13.0 13.5 13.9 14.7 15.5 15.9 15.9 15.9 15.9 15.9 15.9

10.5 11.0 11.6 12.1 12.7 13.5 13.7 14.0 14.1 14.7 15.3 15.4 15.4 15.4 15.4 15.4 15.4 15.4 15.4

10.5 10.8 11.6 12.1 12.7 13.4 13.7 14.0 14.1 14.7 14.9 14.9 14.9 14.9 14.9 14.9 14.9 14.9 14.9

10.5 10.8 11.4 12.1 12.7 13.4 13.5 13.6 13.9 13.9 13.9 13.9 13.9 13.9 13.9 13.9 13.9 13.9 13.9

Indoor Units

kW -19.8 -18.8 -16.7 -14.7 -12.6 -10.5 -9.5 -8.5 -7.0 -5.0 -3.0 0.0 3.0 5.0 7.0 9.0 11.0 13.0 15.0

Notes: TC: Total Capacity(kW)

21 _ Ceiling Cassette 4-way


7. Air Velocity and Temperature Distribution(Reference Data) ARNU05GTR*2, ARNU07GTR*2, ARNU09GTR*2 Cooling

Heating

Discharge angle: 40°

Discharge angle: 50°

Air velocity [m/s]

Air velocity [m/s] 2.7m

2.7m 2.0

2.0

2.0

1.5 1.0

1.5 1.0

2m

2.0 1.5

1.5 1.0

2.5m

1.5m

0m

1.5m

0m 2.5m

1.0 0.5

0.5

1m

0.5

0.5

2.5m

2m

1.5m

1m

0m

1.5m

0m 2.5m

Temperature [°C]

Temperature [°C]

2.7m

2.7m 2m

18

18 20

20

22

21

21 2m 27

18

24

27

18 24

24

1m

22

33

1m

24

2.5m

1.5m

0m

1.5m

0m 2.5m

2.5m

1.5m

0m

1.5m

0m 2.5m

ARNU12GTR*2 Cooling

Heating

Discharge angle: 40°

Discharge angle: 50° Air velocity [m/s]

Air velocity [m/s]

2.7m

2.7m 2.0

2.0 1.5

2.0

2m 1.5

2.0 1.5

1.0 1.0

1.0

0.5

2.5m

2m

1.5 1.0

0.5

1m

1m

0.5

0.5

1.5m

0m

1.5m

0m 2.5m

2.5m

1.5m

0m

0m 2.5m

1.5m

Temperature [°C]

Temperature [°C]

2.7m

2.7m 18

33

18

20

2m

20

22

33

30 24

22

2m

30

27

27

24

21

21

1m

1m 24

2.5m

1.5m

24

0m

1.5m

0m 2.5m

2.5m

1.5m

0m

1.5m

0m 2.5m

Ceiling Cassette 4-way _ 22

Indoor Units

33


7. Air Velocity and Temperature Distribution(Reference Data) ARNU15GTQ*2 Cooling

Heating

Discharge angle: 40°

Discharge angle: 50°

Air velocity [m/s]

Air velocity [m/s]

2.7m

2.7m 2.0

2.0

2.0 1.5

1.0

1m

1m

0m

1m

2m

4m

0m

4m

3m

2m

1m

0m

1m

2m

3m

4m

2.7m

2.7m 18

18 20

20

33

33

2m

2m 22

22

21

24

24

1m

27

24

24

3m

21

1m 27

4m

0m

Temperature [°C]

Temperature [°C]

Indoor Units

0.5

0.5

3m

1m

1.0

1.0

0.5

2m

1.5

1.5

0.5 3m

2m

2m 1.5

1.0

4m

2.0

2m

1m

0m

1m

2m

3m

4m

0m

4m

3m

2m

1m

0m

1m

2m

3m

4m

0m

ARNU18GTQ*2 Cooling

Heating

Discharge angle: 40°

Discharge angle: 50°

Air velocity [m/s]

Air velocity [m/s]

2.7m

2.7m 2.0

2.0

2.0

1.5

2m

1.0

4m

3m

2m

1.5

1.5 1m

1.0

0.5 0m

1m

3m

4m

0m

4m

3m

2m

1m

1.0

0.5

2m

2m

1.5

1.0

0.5 1m

2.0

0.5

1m

0m

1m

2m

3m

4m

Temperature [°C]

Temperature [°C]

2.7m

2.7m 18 20

18

22

33

20

2m

2m

2m

30

21

22

24

3m

33

30

1m

4m

0m

21 24

27

27

1m

24

24

1m

0m

1m

2m

23 _ Ceiling Cassette 4-way

3m

4m

0m

4m

3m

2m

1m

0m

1m

2m

3m

4m

0m


7. Air Velocity and Temperature Distribution(Reference Data) ARNU24GTP*2 Cooling

Heating

Discharge angle: 40°

Discharge angle: 50°

Air velocity [m/s]

Air velocity [m/s]

2.7m

2.7m 2.0

2.0

2m

2m 2.0

1.5

3m

1.0

1.0

1.0 4m

1m

1.5

2m

1m

0m

1m

3m

4m

0m

4m

2m

0.5

1m

0m

1m

2m

3m

4m

0m

Temperature [°C] 2.7m

2.7m

18 20 22

2m

24

2m

1m

0m

1m

2m

3m

4m

0m

4m

2m

3m

1m

24

24

27

23

24

30 22

22

1m 23

33

33 30

2m

1m

27

0m

1m

2m

3m

4m

0m

ARNU28GTP*2 Cooling

Heating

Discharge angle: 40°

Discharge angle: 50°

Air velocity [m/s]

Air velocity [m/s]

2.7m 2.0

2m

2.0

1.0

1.0

1.0

2m

2m 1.5

1m

1.5

1.0 3m

2.7m

3.0 2.0

1.5

1m

1.5

4m

3.0 2.0

2.5

2.5

1m

0m

1m

2m

3m

4m

0m

0.5

4m

3m

2m

0.5

1m

0m

1m

2m

3m

4m

Temperature [°C]

Temperature [°C]

2.7m

2.7m 18

33

18

33

2m

2m 21 22

22 23

4m

3m

2m

0m

23

1m

0m

1m

2m

3m

4m

0m

30

24

1m

30

1m

27

4m

3m

2m

21

24

1m

0m

27 1m

2m

3m

4m

0m

Ceiling Cassette 4-way _ 24

Indoor Units

18 20 22

3m

3m

1m

1.0

0.5

2m

Temperature [°C]

4m

2.0


7. Air Velocity and Temperature Distribution(Reference Data) ARNU36GTN*2 Cooling

Heating

Discharge angle: 40°

Discharge angle: 50°

Air velocity [m/s]

Air velocity [m/s]

3.0 2.5 2.0

2.7m

3.0 2.5 2.0

2m 1.5

1.5 1.0 5m

4m

3m

1m

1m

2m

0m

1m

2m

3m

4m

Indoor Units

1.0

3m

2m

1m

2.7m

0m

1m

2m

3m

4m

0m 5m

22

23

1m

0m

2m

1m

2m

3m

4m

0m 5m

30

24 22

1m 23

2m

33

2m

20

22

2.7m

33

18

20

3m

4m

1m

Temperature [°C]

18

4m

5m

2m

2.0

1.0

0m 5m

2.7m

3.5 3.0 2.5

2.0

1.0

Temperature [°C]

5m

3.5 3.0 2.5

30

27

5m

4m

3m

2m

1m

24 22

1m

4m

0m 5m

27

0m

1m

2m

3m

ARNU42GTM*2 Cooling

Heating

Discharge angle: 40°

Discharge angle: 50°

Air velocity [m/s]

Air velocity [m/s]

3.2m

3.2m 4.0

4.0

4.0 3.0

3.0

3.0

2m

3.0

4.0

2m

1m

5m

4m

3m

1m 2.0

2.0 1.0

2.0 1.0 2m

1m

0m

1m

2m

2.0

1.0

3m

4m

0m 5m

5m

4m

3m

2m

1.0

1m

0m

1m

2m

3m

4m

Temperature [°C]

Temperature [°C] 3.2m

3.2m

2m

20

33

33

18

18

24

20

22

22

4m

3m

2m

1m

0m

1m

2m

25 _ Ceiling Cassette 4-way

3m

22 27

24

24

30

22

1m

4m

0m 5m

5m

4m

2m

24 30

5m

0m 5m

3m

2m

1m

1m

27

0m

1m

2m

3m

4m

0m 5m


7. Air Velocity and Temperature Distribution(Reference Data) ARNU48GTM*2 Cooling

Heating

Discharge angle: 40째

Discharge angle: 50째

Air velocity [m/s]

Air velocity [m/s]

3.2m 4.0

1.0 4m

3m

2m

1m

0m

1m

2m

2m

3.0

3.0

1m

2.0 1.0

2.0

4.0

2m

3.0

3.0

5m

3.2m 4.0

4.0

1m 2.0

2.0

1.0

3m

4m

0m 5m

4m

5m

3m

2m

1m

1.0

0m

1m

2m

3m

4m

0m 5m

Temperature [째C]

Temperature [째C]

3.2m 33

2m

20

20

33

2m 22

24

22

24

1m 22 24

5m

4m

24

3m

2m

1m

1m

0m

1m

2m

3m

30

30 27

22

4m

0m 5m

5m

4m

3m

2m

1m

27

0m

1m

2m

3m

4m

0m 5m

Ceiling Cassette 4-way _ 26

Indoor Units

3.2m 18

18


8. Electric Characteristicss Units

Indoor Units

Model

Type

Power Supply Hz

Volts

Voltage Range MCA

IFM

Input(W)

MFA

kW

FLA

Cooling Heating

ARNU05GTR*2

TR

0.25

15

0.043

0.2

30

30

ARNU07GTR*2

TR

0.25

15

0.043

0.2

30

30

ARNU09GTR*2

TR

0.25

15

0.043

0.2

30

30

ARNU12GTR*2

TR

0.25

15

0.043

0.2

30

30

ARNU15GTQ*2

TQ

0.25

15

0.043

0.2

30

30

ARNU18GTQ*2

TQ

0.25

15

0.043

0.2

30

30

0.22

15

0.03

0.17

33

33

50

220-240

MAX : 264 MIN:198

ARNU24GTP*2

TP

ARNU28GTP*2

TP

0.22

15

0.03

0.17

33

33

ARNU36GTN*2

TN

0.81

15

0.135

0.64

144

144

ARNU42GTM*2

TM

0.81

15

0.135

0.64

144

144

ARNU48GTM*2

TM

0.81

15

0.135

0.64

144

144

ARNU05GTR*2

TR

0.25

15

0.043

0.2

30

30

ARNU07GTR*2

TR

0.25

15

0.043

0.2

30

30

ARNU09GTR*2

TR

0.25

15

0.043

0.2

30

30

ARNU12GTR*2

TR

0.25

15

0.043

0.2

30

30

ARNU15GTQ*2

TQ

0.25

15

0.043

0.2

30

30

ARNU18GTQ*2

TQ

0.25

15

0.043

0.2

30

30

ARNU24GTP*2

TP

0.22

15

0.03

0.17

33

33

ARNU28GTP*2

TP

0.22

15

0.03

0.17

33

33

ARNU36GTN*2

TN

0.81

15

0.135

0.64

144

144

ARNU42GTM*2

TM

0.81

15

0.135

0.64

144

144

ARNU48GTM*2

TM

0.81

15

0.135

0.64

144

144

60

220

MAX : 242 MIN:198

Symbols: MCA : Minimum Circuit Amperes (A) MFA : Maximum Fuse Amperes(see note 5) kW : Fan Motor Rated Output(kW) FLA : Full Load Amperes(A) IFM : Indoor Fan Motor Note : 1. Voltage Range Units are suitable for use on electrical system where voltage supplied to unit terminals is not below or above the listed range limits. 2. Maximum allowable voltage unbalance between phase is 2%. 3. MCA/MFA MCA = 1.25 x FLA MFA ≤ 4 x FLA ( Next lower standard fuse rating. Minimum 15A) 4. Select wire size based on the larger value on the MCA. 5. Instead of fuse, use Circuit Breaker.

27 _ Ceiling Cassette 4-way


9. Sound Levels Overall Notes: - Sound measured at 1.5m below the center of the unit. - Data is valid at free field condition - Data is valid at nominal operating condition - Reference accoustic pressure OdB = 20μPa - Sound level will vary depending on a range of factors such as the construction(acoustic absorption coefficient) of particular room in which the equipment is installed.

Ceiling 1.5m

Model H 29 29 30 32 36 37

Model H 36 39 43 44 46

ARNU24GTP*2 ARNU28GTP*2 ARNU36GTN*2 ARNU42GTM*2 ARNU48GTM*2

Sound Level dB(A) L M 34 31 35 33 40 37 41 38 43 41

Indoor Units

ARNU05GTR*2 ARNU07GTR*2 ARNU09GTR*2 ARNU12GTR*2 ARNU15GTQ*2 ARNU18GTQ*2

Sound Level dB(A) L M 26 27 26 27 27 29 27 30 32 34 34 35

Sound Pressure Level ARNU07GTR*2

ARNU09GTR*2 80

70

70

70

NC-65

60

NC-60 NC-55

50

NC-50 NC-45

40

NC-40 NC-35

30

NC-30 20

10

NC-25 Approximate Hearing Threshold 63

NC-60

125 250 500 1000 2000 4000 Octave Band Center Frequency (Hz)

NC-55

50

NC-50 NC-45

40

NC-40 NC-35

30

NC-30 20

NC-20 NC-15 8000

NC-65

60

10

NC-25 Approximate Hearing Threshold 63

Octave Band Sound Pressure Level (dB re 20μPa )

80

Octave Band Sound Pressure Level (dB re 20μPa )

Octave Band Sound Pressure Level (dB re 20μPa )

ARNU05GTR*2 80

NC-60

125 250 500 1000 2000 4000 Octave Band Center Frequency (Hz)

NC-55

50

NC-50 NC-45

40

NC-40 NC-35

30

NC-30 20

NC-20 NC-15 8000

NC-65

60

10

NC-25 Approximate Hearing Threshold 63

NC-20

125 250 500 1000 2000 4000 Octave Band Center Frequency (Hz)

NC-15 8000

Ceiling Cassette 4-way _ 28


9. Sound Levels ARNU12GTR*2

80

ARNU15GTQ*2

NC-65 NC-60 NC-55

50

NC-50 NC-45

40

NC-40 NC-35

30

NC-30

Approximate Hearing Threshold

10

63

NC-60 50

NC-50 NC-45

40

NC-40 NC-35

30

NC-30

NC-20 NC-15 125 250 500 1000 2000 4000 Octave Band Center Frequency (Hz)

NC-55

NC-25

20

NC-25

20

NC-65

60

10

Approximate Hearing Threshold 63

8000

125

ARNU24GTP*2

NC-60 NC-55 NC-50 NC-45 NC-40 NC-35

30

NC-30 20

10

Octave Band Sound Pressure Level (dB re 20μPa )

Octave Band Sound Pressure Level (dB re 20μPa )

NC-65

40

63

250

500

NC-15 1000 2000 4000 8000

4000

NC-65

60

NC-60 NC-55

50

NC-50 NC-45

40

NC-40 NC-35

30

NC-30 NC-25 Approximate Hearing Threshold 63

NC-55 NC-50 NC-45 NC-40 NC-35 NC-30 NC-25 Approximate Hearing Threshold 63

Octave Band Sound Pressure Level (dB re 20μPa )

NC-60

20

250

500

63

125

250

500

NC-15 1000 2000 4000 8000

NC-60

NC-15 1000 2000 4000 8000

Octave Band Center Frequency (Hz)

29 _ Ceiling Cassette 4-way

NC-55

50

NC-50 NC-45

40

NC-40 NC-35

30

NC-30 NC-25

20

10

Approximate Hearing Threshold 63

125

NC-20

250

500

NC-15 1000 2000 4000 8000

Octave Band Center Frequency (Hz)

125

250

500

1000

2000

4000

NC-15 8000

NC-65 NC-60 NC-55

50

NC-50 NC-45

40

NC-40 NC-35

30

NC-30 NC-25

20

10

Approximate Hearing Threshold 63

125

NC-20

250

500

NC-15 1000 2000 4000 8000

Octave Band Center Frequency (Hz)

NC-65

60

NC-20

60

NC-20

70

NC-20

125

10

NC-25 Approximate Hearing Threshold

ARNU36GTN*2

ARNU48GTM*2

NC-65

30

NC-30

Octave Band Center Frequency (Hz)

Octave Band Center Frequency (Hz)

70

40

NC-35

30

20

NC-15 8000

80

50

NC-40

70

ARNU42GTM*2 Octave Band Sound Pressure Level (dB re 20μPa )

2000

NC-45

40

70

10

80

60

NC-50

80

Octave Band Center Frequency (Hz)

10

1000

NC-55

50

80

NC-20

125

500

20

NC-25 Approximate Hearing Threshold

NC-60

ARNU28GTP*2

70

50

250

NC-65

60

Octave Band Center Frequency (Hz)

80

60

70

NC-20

Octave Band Sound Pressure Level (dB re 20μPa )

60

Octave Band Sound Pressure Level (dB re 20μPa )

80

70

Octave Band Sound Pressure Level (dB re 20μPa )

Octave Band Sound Pressure Level (dB re 20μPa )

70

Indoor Units

ARNU18GTQ*2

80


10. Installation • Please read this instruction sheet completely before installing the product. • When the power cord is damaged, replacement work shall be performed by authorized personnel only. • Installation work must be performed in accordance with the national wiring standards by authorized personnel only.

Anti-bacteria filter

Indoor Units

Air Intake

TEM P

Remote Controll

er

Air Outlet Wired Remote Controller(Optional)

Required Parts

Required Tools

• Connecting cable • Pipes: Gas side Liquid side • Hanging Bolt (W 3/8 or M10 length 650mm) • Insulated drain hose • Additional Drain hose

• Level • Screw driver • Electric drill • Hole core drill • Flaring Tool set • Torque Wrenches • Hexagonal Wrench • Gas-leak detector • Thermometer

Ceiling Board

50 or more

30 or less

50 or more

Above 250 360 or less

Ceiling Ceiling Board

100 or more

• There should not be any heat source or steam near the unit. • There should not be any obstacles to the air circulation. • A place where air circulation in the room will be good. • A place where drainage can be easily obtained. • A place where noise prevention is taken into consideration. • Do not install the unit near the door way. • Ensure the spaces indicated by arrows from the wall, ceiling, or other obstacles. • The indoor unit must have sufficient maintenance space.

30 or more

10.1 Selection of the best location

Unit:cm Floor

Ceiling Cassette 4-way _ 30


10. Installation 10.2 Ceiling opening dimensions and hanging bolt location • The dimensions of the paper pattern for installation are the same as those of the ceiling opening dimensions.

Ceiling Ceiling board

Level gauge

TQ/TR Chassis

TM/TN/TP Chassis

585~660(Ceiling opening)

875(Ceiling opening)

461

Unit:mm

CAUTION • This air-conditioner uses a drain pump. • Install the unit horizontally using a level gauge. • During the installation, care should be taken not to damage electric wires.

875(Ceiling opening)

684(Hanging bolt)

840 Unit size 840 Unit size

671

517

570

585~660(Ceiling opening)

787(Hanging bolt)

570 319

523

Indoor Units

517

Unit:mm

• Select and mark the position for fixing bolts and piping hole. • Decide the position for fixing bolts slightly tilted to the drain direction after considering the direction of drain hose. • Drill the hole for anchor bolt on the wall.

NOTE: • Avoid the following installation location. 1. Such places as restaurants and kitchen where considerable amount of oil steam and flour is generated. These may cause heat exchange efficiency reduction, or water drops, drain pump mal-function. In these cases, take the following actions; • Make sure that ventilation fan is enough to cover all noxious gases from this place. • Ensure enough distance from the cooking room to install the air conditioner in such a place where it may not suck oily steam. Air conditioner

Take enough distance Use the ventilation fan for smoke-collecting hood with sufficient capacity. Cooking table

2. Avoid installng air conditioner in such places where cooking oil or iron powder is generated. 3. Avoid places where inflammable gas is generated. 4. Avoid place where noxious gas is generated. 5. Avoid places near high frequency generators.

31 _ Ceiling Cassette 4-way


10. Installation Ceiling

Nut (W3/8 or M10)

Flat washer for M10 (accessory) Ceiling board

150mm

Keep the length of the bolt from the bracket to 40mm

Hanging bolt (W3/8 or M10)

Air Conditioner body

Ceiling board Keep the length of 15~18mm between the air conditioner bottom surface and the ceiling surface

Flat washer for M10 (accessory) Nut (W3/8 or M10)

Set screw of paper model (4 pieces) Open the ceiling board along the outer edge of the paper model

Paper model for installation

• The following parts are locally purchased. ① Hanging Bolt - W 3/8 or M10 ② Nut - W 3/8 or M10 ③ Spring Washer - M10 ④ Plate Washer - M10

CAUTION

10.3 Wiring Connection Connect the wires to the terminals on the control board individually according to the outdoor unit connection. • Ensure that the color of the wires of outdoor unit and the terminal No. are the same as those of indoor unit respectively.

Indoor cord Remote control cord power cord

• TR/TQ Chassis [Multi V III Heat Pump Model]

Terminal Block Indoor 1(L)

2(N)

3

[Except Multi VIII Heat Pump Model] SODU B

SODU A

IDU B

IDU A

INT B

INT A

Terminal Block Indoor

4

1(L)

INDOOR POWER INPUT

2(N)

3

SODU

4

B

A

Outdoor Unit

INTERNET DRY1 DRY2 GND 12V

IDU -

-

B

A

-

-

-

-

INDOOR POWER INPUT

• TM/TN/TP Chassis [Multi V III Heat Pump Model]

[Except Multi VIII Heat Pump Model]

Terminal Block Indoor

Terminal Block Indoor

1(L) 2(N) 3(L) 4(N)

5(A) 5(B) RD

POWER INPUT

SODU B

SODU A

IDU B

IDU A

INT B

INT A

YL BK

TO AIR FRESH KIT

Terminal Block Indoor

Terminal Block Indoor

SODU

1(L) 2(N) 3(L) 4(N)

5(A) 5(B) RD

B

POWER INPUT

YL BK

A

IDU B

INTERNET DRY1 DRY2 GND 12V A

B

A

-

-

-

-

Outdoor Unit

TO AIR FRESH KIT

WARNING Make sure that the screws of the terminal are not loose.

Ceiling Cassette 4-way _ 32

Indoor Units

• Tighten the nut and bolt to prevent the unit from falling.


10. Installation 10.4 Installation of Decoration Panel Before installing the decoration panel, always remove the paper template.

The decoration panel has its installation direction.

1. Temporarily fix two decoration panel fixing screws (hexagon M5 screw) on the unit body. (Tighten by amount 10mm in length.) The fixing screws (hexagon M5 screw) are included in the indoor unit box. 2. Remove the air inlet grille from the decoration panel. (Remove the hook for the air inlet grille cord.) 3. Hook the decoration panel key hole ( ) on the screws fixed in step above, and slide the panel so that the screws reach the key hole edge. 4. Retighten completely two temporarily fixed screws and other two screws. (Total 4 screws) 5. Connect the louver motor connector and display connector. 6. After tightening these screws, install the air inlet grille (including the air filter). Piping side

Indoor Units

Air conditioner unit

Control box cover Decoration panel fixing screws (hexagon M5 screws) Temporally fitting at 2 places (Tightening about 10mm)

Louver motor

Decoration panel

Display Lead wire for louver motor and display

Decoration panel fixing screws (Hexagon M5 screw)

CAUTION Install certainly the decoration panel. Cool air leakage causes sweating.

Inlet Grille

Good example

⇨讀 Water drops fall.

Bad example Air conditioner unit

Ceiling board Decoration panel Fit the insulator (this part) and be careful for cool air leakage

33 _ Ceiling Cassette 4-way

Air conditioner unit Air

Cool air leakage (no good) Ceiling board Decoration panel


10. Installation 10.5 Indoor Unit Drain Piping • Drain piping must have down-slope (1/50 to 1/100): be sure not to provide up-and-down slope to prevent reversal flow. • During drain piping connection, be careful not to exert extra force on the drain port on the indoor unit. • The outside diameter of the drain connection on the indoor unit is 32mm. Piping material: Polyvinyl chloride pipe inner diometes Ø 25mm and pipe fittings

Upward routing not allowed

Pipe clamp Indoor unit

Maintenance drain port

• Be sure to install heat insulation on the drain piping.

1/50~1/100

Heat insulation material: Polyethylene foam with thickness more than 8 mm.

MAX 700mm

Drain test The air conditioner uses a drain pump to drain water. Use the following procedure to test the drain pump operation: Flexible drain hose (accessory) Main drain pipe

Drain Pump

Drain port

Glue the joint

Drain hose connection Use the clip (accessory)

• Connect the main drain pipe to the exterior and leave it provisionally until the test comes to an end. • Feed water to the flexible drain hose and check the piping for leakage. • Be sure to check the drain pump for normal operating and noise when electrical wiring is complete. • When the test is complete, connect the flexible drain hose to the drain port on the indoor unit.

Drain pan

The supplied flexible drain hose should not be strained. A strained hose may cause leakage of water.

Max 300mm

Hanger distance 1~15m

Metal clamp Flexible drain hose

Hanger Bracket 1/50~1/100 slope

Max 700mm

CAUTION

Insulation

CAUTION After the confirmation of the above conditions, prepare the wiring as follows: 1) Never fail to have separate power specially for the air conditioner. As for the method of wiring, follow the circuit diagram pasted on the inside of control box cover. 2) Provide a circuit breaker switch between power source and the unit. 3) The screw which fasten the wiring in the casing of electrical fittings are liable to come loose from vibrations to which the unit is subjected during the course of transportation. Check them and make sure that they are all tightly fastened. (If they are loose, it could give rise to burn-out of the wires.) 4) Confirm the specification of power source 5) Confirm that electrical capacity is sufficient. 6) Be sure that the starting voltage is maintained at more than 90 percent of the rated voltage marked on the name plate. 7) Confirm that the cable thickness is as specified in the power sources specification. (Particularly note the relation between cable length and thickness.) 8) Do not install the leakage breaker in a place which is wet or moist. Water or moist may cause short circuit. 9) The following troubles would be caused by voltage drop-down. • Vibration of a magnetic switch, damage on the contact point there of, fuse breaking, disturbance to the normal function of a overload protection device. • Proper starting power is not given to the compressor.

HAND OVER Teach the customer the operation and maintenance procedures, using the operation manual (air filter cleaning, temperature control, etc.).

Ceiling Cassette 4-way _ 34

Indoor Units

Feed water


10. Installation WIRED REMOTE CONTROLLER INSTALLATION • Since the room temperature sensor is in the remote controller, the remote controller box should be installed in a place away from direct sunlight, high humidity and direct supply of cold air to maintain proper space temperature. Install the remote controller about 5ft(1.5m) above the floor in an area with good air circulation at an average temperature.

Do not install the remote controller where it can be affected by:

Indoor Units

- Drafts, or dead spots behind doors and in corners. - Hot or cold air from ducts. - Radiant heat from sun or appliances. - Concealed pipes and chimneys. - Uncontrolled areas such as an outside wall behind the remote controller. - This remote controller is equipped with a seven segment LED. display. For proper display of the remote controller LED's, the remote controller should be installed properly as shown in Fig.1. (The standard height is 1.2~1.5 m from floor level.)

TEMP

yes

Remote Controller

no

TEMP

Remote Controller

5feet (1.5meters)

TEMP

Controller Remote

no

no

Fig.1 Typical locations for remote controller

35 _ Ceiling Cassette 4-way


11. Accessories Standard Accessories Name

Drain hose

Clamp metal

Quantity

1 EA

2 EA

Shape

Washer for hanging backet 8 EA

Clamp (Tie Wrap)

Insulation for fitting

4 EA

1 SET

for gas pipe

Bolt

(Other)

4 EA • Paper pattern for installation • Owner's manual • Installation manual

for liquid pipe

Indoor Units

CAUTION • Use only those accessories (Standard or optional) which have designated specifications.

Ceiling Cassette 4-way _ 36


Indoor unit Ceiling Concealed Duct (High Static) 1. List of functions 2. Specifications 3. Dimensions & Gravity point 4. Piping Diagrams 5. Wiring Diagrams 6. Capacity Tables 7. External Static Pressure(E.S.P) & Air Flow 8. Electric Characteristics 9. Sound Levels 10. Installation 11. Accessories


1. List of functions Category

Air flow

Air purifying

Reliability

Convenience

Individual control

Special function kit

Air supply outlet Airflow direction control(left & right) Airflow direction control(up & down) Auto swing(left & right) Auto swing(up & down) Airflow steps(fan/cool/heat) Chaos swing Chaos wind(auto wind) Jet cool(Power wind) Swirl wind Deodorizing filter Plasma air purifier Prefilter(washable / anti-fungus) Drain pump E.S.P. control Electric heater(operation) High ceiling operation Hot start Self diagnosis Soft dry operation Auto changeover Auto cleaning Auto operation(artificial intelligence) Auto restart operation Child lock Forced operation Group control Sleep mode Timer(on/off) Timer(weekly) Two thermistor control Wide wired remote controller Deluxe wired remote controller Simple wired remote controller Wired remote controller(for hotel use) Wireless remote controller(simple) Wireless LCD remote control Zone control CTIE Electro thermostat

ARNU07GBHA2, ARNU09GBHA2, ARNU12GBHA2, ARNU15GBHA2, ARNU18GBHA2, ARNU24GBHA2, ARNU28GBGA2 , ARNU36GBGA2, ARNU42GBGA2, ARNU48GBRA2, URNU76GB8A2, URNU96GB8A2 1 3/3/3 X X O O O X O O O O(Heat recovery) X O(Heat pump or Cooling only) O O O O O O O Accessory Accessory Accessory Accessory X Accessory Accessory -

O : Applied X : Not applied – : No relation Option : Model name & price are different according to options, and assembled in factory with main unit. Accessory : Installed at field, ordered and purchased separately by the corresponding model name, supplied with separate package.

Ceiling Concealed Duct(High Static) _ 1

Indoor Units

Installation

Function


2. Specifications Type Model Cooling Capacity

Heating Capacity

Unit kW kcal/h Btu/h kW kcal/h Btu/h

Casing Dimensions(WxDxH) Body

mm inch

Rows x Columns x FPI Face Area m3 Type Motor Output x Number W Running Current A Air Flow Rate(H / M / L) CMM (High Mode-factory set) cfm Fan External Static Pressure mmAq(Pa) Air Flow Rate(H / M / L) CMM (Standard Mode) cfm External Static Pressure mmAq(Pa) Drive Motor type Temperature Control Sound Absorbing Thermal Insulation Material Air Filter Safety Device Liquid Side mm(inch) Pipe Connections Gas Side mm(inch) Drain Pipe(Internal Dia.) mm(inch) Net Weight kg(lbs) Noise Level(Sound Press, 1.5m, H / M / L) dB(A)

Indoor Units

Coil

Power Supply Refrigerant Control Power cable Transmission cable

Ø, V, Hz mm2 mm2

ARNU07GBHA2 2.2 1,900 7,500 2.5 2,200 8,500 Galvanized Steel Plate 882 x 450 x 260 34.7 x 17.7 x 10.2 2 x 10 x 21 0.15 Sirocco Fan 118 0.92 8.5 / 7.5 / 6.0 300 / 265 / 212 8(78) 8.5 / 8.0 / 7.5 300 / 282 / 265 6(59) Direct BLDC Microprocessor, Thermostat for cooling and heating Foamed polystrene Fuse Ø6.35(1/4) Ø12.7(1/2) 25(1) 26(57.4) 34 / 33 / 32 1, 220-240, 50 1, 220, 60 EEV CV1.5 x 3C CVV-SB 1.0~1.5 x 2C

Ceiling Concealed Duct -High Static ARNU09GBHA2 ARNU12GBHA2 2.8 3.6 2,400 3,100 9,600 12,300 3.2 4.0 2,800 3,400 10,900 13,600 Galvanized Steel Plate Galvanized Steel Plate 882 x 450 x 260 882 x 450 x 260 34.7 x 17.7 x 10.2 34.7 x 17.7 x 10.2 2 x 10 x 21 2 x 10 x 21 0.15 0.15 Sirocco Fan Sirocco Fan 118 118 0.92 0.92 10.0 / 8.5 / 7.5 12.0 / 10.0 / 8.5 353 / 300 / 265 424 / 353 / 300 8(78) 8(78) 8.5 / 8.0 / 7.5 11.0 / 8.5 / 7.5 300 / 282 / 265 388 / 300 / 265 6(59) 6(59) Direct Direct BLDC BLDC Microprocessor, Thermostat for cooling and heating Microprocessor, Thermostat for cooling and heating Foamed polystrene Foamed polystrene Fuse Fuse Ø6.35(1/4) Ø6.35(1/4) Ø12.7(1/2) Ø12.7(1/2) 25(1) 25(1) 26(57.4) 26(57.4) 35 / 34 / 33 37 / 35 / 34 1, 220-240, 50 1, 220-240, 50 1, 220, 60 1, 220, 60 EEV EEV CV1.5 x 3C CV1.5 x 3C CVV-SB 1.0~1.5 x 2C CVV-SB 1.0~1.5 x 2C

Notes:1. Capacities are based on the following conditions: Cooling • Indoor temp. 27°C[80.6°F]DB/ 19°C[66.2°F]WB • Outdoor temp. 35°C[95°F]DB/ 24°C[75.2°F]WB • Interconnecting Piping Length 7.5m • Level Difference of Zero Heating • Indoor temp. 20°C[68°F]DB/ 15°C[59°F]WB • Outdoor temp. 7°C[44.6°F]DB/ 6°C[42.8°F]WB • Interconnecting Piping Length 7.5m • Level Difference of Zero 2. Capacities are net capacities 3. Due to our policy of innovation some specifications may be changed without prior notification 4. To be added for more available Models 5. EEV : Electronic Expansion Valve 6. Noise Level is Standard Mode (for actual High Mode(factory set) condition, Noise Level may exceed the standard level by 1.5dB(A)) 7. Anechoic chamber conversion value is measured at 1.5 m downward from unit centre. The values depends on the ambient conditions and values are normally higher in actual operation.

2 _ Ceiling Concealed Duct(High Static)

ARNU15GBHA2 4.5 3,900 15,400 5.0 4,300 17,100 Galvanized Steel Plate 882 x 450 x 260 34.7 x 17.7 x 10.2 2 x 10 x 21 0.15 Sirocco Fan 118 0.92 13.5 / 12.0 / 8.5 477 / 424 / 300 8(78) 13.5 / 12.0 / 11.0 477 / 424 / 388 6(59) Direct BLDC Microprocessor, Thermostat for cooling and heating Foamed polystrene Fuse Ø6.35(1/4) Ø12.7(1/2) 25(1) 26(57.4) 39 / 38 / 37 1, 220-240, 50 1, 220, 60 EEV CV1.5 x 3C CVV-SB 1.0~1.5 x 2C

Conversion Formula kcal/h= kW x 860 Btu/h = kW x 3412 cfm = m3/min x 35.3 l/s = CMM x 1000/60


2. Specifications Type Model Cooling Capacity

Heating Capacity

Unit kW kcal/h Btu/h kW kcal/h Btu/h

Casing Dimensions(WxDxH) Body

mm inch

Power Supply Refrigerant Control Power cable Transmission cable

Ø, V, Hz mm2 mm2

Notes:1. Capacities are based on the following conditions: Cooling • Indoor temp. 27°C[80.6°F]DB/ 19°C[66.2°F]WB • Outdoor temp. 35°C[95°F]DB/ 24°C[75.2°F]WB • Interconnecting Piping Length 7.5m • Level Difference of Zero Heating • Indoor temp. 20°C[68°F]DB/ 15°C[59°F]WB • Outdoor temp. 7°C[44.6°F]DB/ 6°C[42.8°F]WB • Interconnecting Piping Length 7.5m • Level Difference of Zero 2. Capacities are net capacities 3. Due to our policy of innovation some specifications may be changed without prior notification 4. To be added for more available Models 5. EEV : Electronic Expansion Valve 6. Noise Level is Standard Mode (for actual High Mode(factory set) condition, Noise Level may exceed the standard level by 1.5dB(A)) 7. Anechoic chamber conversion value is measured at 1.5 m downward from unit centre. The values depends on the ambient conditions and values are normally higher in actual operation.

Conversion Formula kcal/h= kW x 860 Btu/h = kW x 3412 cfm = m3/min x 35.3 l/s = CMM x 1000/60

Ceiling Concealed Duct(High Static) _ 3

Indoor Units

Rows x Columns x FPI Face Area m3 Type Motor Output x Number W Running Current A Air Flow Rate(H / M / L) CMM (High Mode-factory set) cfm Fan External Static Pressure mmAq(Pa) Air Flow Rate(H / M / L) CMM (Standard Mode) cfm External Static Pressure mmAq(Pa) Drive Motor type Temperature Control Sound Absorbing Thermal Insulation Material Air Filter Safety Device Liquid Side mm(inch) Pipe Connections Gas Side mm(inch) Drain Pipe(Internal Dia.) mm(inch) Net Weight kg(lbs) Noise Level(Sound Press, 1.5m, H / M / L) dB(A) Coil

Ceiling Concealed Duct(High Static) ARNU18GBHA2 ARNU24GBHA2 ARNU28GBGA2 5.6 7.1 8.2 4,800 6,100 7,100 19,100 24,200 28,000 6.3 8.0 9.2 5,400 6,900 8,000 21,500 27,300 31,500 Galvanized Steel Plate Galvanized Steel Plate Galvanized Steel Plate 882 x 450 x 260 882 x 450 x 260 1,182 x 450 x 298 34.7 x 17.7 x 10.2 34.7 x 17.7 x 10.2 46.5 x 17.7 x 11.7 3 x 10 x 21 3 x 10 x 21 3 x 12 x 21 0.15 0.15 0.26 Sirocco Fan Sirocco Fan Sirocco Fan 118 118 390 0.92 0.92 2.30 15.5 / 13.5 / 12.4 18.3 / 16.9 / 15.5 25.9 / 24.1 / 21.8 547 / 477 / 438 646 / 597 / 547 915 / 851 / 770 8(78) 8(78) 10(98) 15.3 / 13.6 / 10.3 19.0 / 16.4 / 14.5 25.3 / 21.8 / 17.6 540 / 480 / 364 671 / 579 / 512 893 / 770 / 622 6(59) 6(59) 8(78) Direct Direct Direct BLDC BLDC BLDC Microprocessor, Thermostat for cooling and heating Microprocessor, Thermostat for cooling and heating Microprocessor, Thermostat for cooling and heating Foamed polystrene Foamed polystrene Foamed polystrene Fuse Fuse Fuse Ø6.35(1/4) Ø9.52(3/8) Ø9.52(3/8) Ø12.7(1/2) Ø15.88(5/8) Ø15.88(5/8) 25(1) 25(1) 25(1) 26.5(58.4) 26.5(58.4) 38.0(83.8) 42.5 / 41 / 37 45 / 43 / 41 44 / 42 / 40 1, 220-240, 50 1, 220-240, 50 1, 220-240, 50 1, 220, 60 1, 220, 60 1, 220, 60 EEV EEV EEV CV1.5 x 3C CV1.5 x 3C CV1.5 x 3C CVV-SB 1.0~1.5 x 2C CVV-SB 1.0~1.5 x 2C CVV-SB 1.0~1.5 x 2C


2. Specifications Type Model Cooling Capacity

Heating Capacity

Ceiling Concealed Duct(High Static) Unit kW kcal/h Btu/h kW kcal/h Btu/h

Casing Dimensions(WxDxH) Body

mm inch

Rows x Columns x FPI Face Area m3 Type Motor Output x Number W Running Current A Air Flow Rate(H / M / L) CMM (High Mode-factory set) cfm Fan External Static Pressure mmAq(Pa) Air Flow Rate(H / M / L) CMM (Standard Mode) cfm External Static Pressure mmAq(Pa) Drive Motor type Temperature Control Sound Absorbing Thermal Insulation Material Air Filter Safety Device Liquid Side mm(inch) Pipe Connections Gas Side mm(inch) Drain Pipe(Internal Dia.) mm(inch) Net Weight kg(lbs) Noise Level(Sound Press, 1.5m, H / M / L) dB(A)

Indoor Units

Coil

Power Supply Refrigerant Control Power cable Transmission cable

Ø, V, Hz mm2 mm2

ARNU36GBGA2 ARNU42GBGA2 ARNU48GBRA2 10.6 12.3 14.1 9,100 10,600 12,100 36,200 42,000 48,100 11.9 13.8 15.9 10,200 11,000 13,200 40,600 43,800 51,200 Galvanized Steel Plate Galvanized Steel Plate Galvanized Steel Plate 1,182 x 450 x 298 1,182 x 450 x 298 1,230 x 590 x 380 46.5 x 17.7 x 11.7 46.5 x 17.7 x 11.7 48.4 x 23.2 x 15 3 x 12 x 21 3 x 12 x 21 3 x 13 x 19 0.26 0.26 0.38 Sirocco Fan Sirocco Fan Sirocco Fan 390 390 390 2.30 2.30 2.40 32.3 / 29.0 / 25.3 34.5 / 32.3 / 30.7 44.8 / 40.6 / 33.3 1,141 / 1,024 / 894 1,218 / 1,141 / 1,084 1,582 / 1,434 / 1,176 10(98) 10(98) 14(137) 28.4 / 25.3 / 21.8 32.0 / 28.4 / 27.2 44.4 / 39.5 / 33.5 1,003 / 894 / 770 1,130 / 1,003 / 961 1,568 / 1,395 / 1,183 8(78) 8(78) 10(98) Direct Direct Direct BLDC BLDC BLDC Microprocessor, Thermostat for cooling and heating Microprocessor, Thermostat for cooling and heating Microprocessor, Thermostat for cooling and heating Foamed polystrene Foamed polystrene Foamed polystrene Fuse Fuse Fuse Ø9.52(3/8) Ø9.52(3/8) Ø9.52(3/8) Ø15.88(5/8) Ø15.88(5/8) Ø15.88(5/8) 25(1) 25(1) 25(1) 38(83.8) 38(83.8) 53(117) 46 / 44 / 42 48 / 46 / 45 45 / 43 / 41 1, 220-240, 50 1, 220-240, 50 1, 220-240, 50 1, 220, 60 1, 220, 60 1, 220, 60 EEV EEV EEV CV1.5 x 3C CV1.5 x 3C CV1.5 x 3C CVV-SB 1.0~1.5 x 2C CVV-SB 1.0~1.5 x 2C CVV-SB 1.0~1.5 x 2C

Notes:1. Capacities are based on the following conditions: Cooling • Indoor temp. 27°C[80.6°F]DB/ 19°C[66.2°F]WB • Outdoor temp. 35°C[95°F]DB/ 24°C[75.2°F]WB • Interconnecting Piping Length 7.5m • Level Difference of Zero Heating • Indoor temp. 20°C[68°F]DB/ 15°C[59°F]WB • Outdoor temp. 7°C[44.6°F]DB/ 6°C[42.8°F]WB • Interconnecting Piping Length 7.5m • Level Difference of Zero 2. Capacities are net capacities 3. Due to our policy of innovation some specifications may be changed without prior notification 4. To be added for more available Models 5. EEV : Electronic Expansion Valve 6. Noise Level is Standard Mode (for actual High Mode(factory set) condition, Noise Level may exceed the standard level by 1.5dB(A)) 7. Anechoic chamber conversion value is measured at 1.5 m downward from unit centre. The values depends on the ambient conditions and values are normally higher in actual operation.

4 _ Ceiling Concealed Duct(High Static)

Conversion Formula kcal/h= kW x 860 Btu/h = kW x 3412 cfm = m3/min x 35.3 l/s = CMM x 1000/60


2. Specifications Type Model

Ceiling Concealed Duct(High Static) URNU76GB8A2 URNU96GB8A2 22.4 28 Cooling Capacity 19,300 24,100 76,400 95,900 25.2 31.5 Heating Capacity 21,700 27,100 86,000 107,500 Casing Galvanized Steel Plate Galvanized Steel Plate mm 1,562 x 688 x 460 1,562 x 688 x 460 Dimensions(WxDxH) Body inch 61.5 x 27.1 x 18.1 61.5 x 27.1 x 18.1 Rows x Columns x FPI 3 x 21 x 19 3 x 21 x 19 Coil Face Area m3 0.59 0.59 Type Sirocco Fan Sirocco Fan Motor Output x Number W 375 x 2 375 x 2 Running Current A 4.50 4.50 Air Flow Rate(H / M / L) CMM 60.0 / 50.0 / 50.0 72.0 / 64.0 / 64.0 (High Mode-factory set) cfm 2,119 / 1,766 / 1,766 2542 / 2,260 / 2,260 Fan External Static Pressure mmAq(Pa) 22(216) 22(216) Air Flow Rate(H / M / L) CMM 64.0 / 50.0 / 50.0 76.0 / 64.0 / 64.0 (Standard Mode) cfm 2,260 / 1,766 / 1,766 2,684 / 2,260 / 2,260 External Static Pressure mmAq(Pa) 15(147) 15(147) Drive Direct Direct Motor type BLDC BLDC Temperature Control Microprocessor, Thermostat for cooling and heating Microprocessor, Thermostat for cooling and heating Sound Absorbing Thermal Insulation Material Foamed polystrene Foamed polystrene Air Filter Safety Device Fuse Fuse Liquid Side mm(inch) Ø9.52(3/8) Ø9.52(3/8) Pipe Connections Gas Side mm(inch) Ø19.05(3/4) Ø22.2(7/8) Drain Pipe(Internal Dia.) mm(inch) 25(1) 25(1) Net Weight kg(lbs) 87(192) 87(192) Noise Level(Sound Press, 1.5m, H / M / L) dB(A) 50 / 48 / 48 52 / 50 / 50 1, 220-240, 50 1, 220-240, 50 Power Supply Ø, V, Hz 1, 220, 60 1, 220, 60 Refrigerant Control EEV EEV Power cable mm2 CV1.5 x 3C CV1.5 x 3C Transmission cable mm2 CVV-SB 1.0~1.5 x 2C CVV-SB 1.0~1.5 x 2C Unit kW kcal/h Btu/h kW kcal/h Btu/h

Conversion Formula kcal/h= kW x 860 Btu/h = kW x 3412 cfm = m3/min x 35.3 l/s = CMM x 1000/60

Ceiling Concealed Duct(High Static) _ 5

Indoor Units

Notes:1. Capacities are based on the following conditions: Cooling • Indoor temp. 27°C[80.6°F]DB/ 19°C[66.2°F]WB • Outdoor temp. 35°C[95°F]DB/ 24°C[75.2°F]WB • Interconnecting Piping Length 7.5m • Level Difference of Zero Heating • Indoor temp. 20°C[68°F]DB/ 15°C[59°F]WB • Outdoor temp. 7°C[44.6°F]DB/ 6°C[42.8°F]WB • Interconnecting Piping Length 7.5m • Level Difference of Zero 2. Capacities are net capacities 3. Due to our policy of innovation some specifications may be changed without prior notification 4. To be added for more available Models 5. EEV : Electronic Expansion Valve 6. Noise Level is Standard Mode (for actual High Mode(factory set) condition, Noise Level may exceed the standard level by 1.5dB(A)) 7. Anechoic chamber conversion value is measured at 1.5 m downward from unit centre. The values depends on the ambient conditions and values are normally higher in actual operation.


5

7.

R3

60

114

450

260

47

355

158

20

175

75

21

49

64

24

243

5

428

6

882

212

882

87 750

932

745

243

119

65

108

30

115

4

450 47

133 127 106

6 _ Ceiling Concealed Duct(High Static)

450

219 119

1 2

100

50

70

260

29

51

3

123 140

48 52 165

31

Air suction

6

Unit size(7k,9k,12k,18k):ø6.35 Unit size(24k):ø9.52 Unit size(7k,9k,12k,18k):ø12.7 Unit size(24k):ø15.88

Descripition

(unit : mm)

Gravity point

CHASSIS CODE: BH

2. Unit shall be grounded in accordance with the local regulations or applicable national codes.

1. Unit should be installed in compliance with the installation manual in the product box.

Note

Air discharge

5

Drain pipe connection Power supply connection

3 4

Gas pipe connection

Liquid pipe connection

Name

2

1

Number

ARNU07GBHA2 ARNU09GBHA2 ARNU12GBHA2 ARNU15GBHA2 ARNU18GBHA2 ARNU24GBHA2

Ceiling Concealed Duct (High Static)

76, Seongsan-dong, Changwon City, Gyeongnam, 641-713, Korea

101

Indoor Units

3. Dimensions & Gravity point

355

224


Ceiling Concealed Duct(High Static) _ 7

ø1

00

60

152

224

20

298

220

23

186

450

232

49

565

243

5

6

1,182

232

1,182

87 830

1,230

243

232

115

108

29

75

87

355 450 158 113

219 136

1,043

1

100

50

2 261

165

3

122 140

47 53

32

Note

(unit : mm)

Unit size(28k,36k,42k):ø15.88

Unit size(28k,36k,42k):ø9.52

Descripition

Gravity point

CHASSIS CODE: BG

2. Unit shall be grounded in accordance with the local regulations or applicable national codes.

1. Unit should be installed in compliance with the installation manual in the product box.

Air suction

Air discharge

5 6

Power supply connection

4

Drain pipe connection

Gas pipe connection

2 3

Liquid pipe connection

1

Name

ARNU28GBGA2 ARNU36GBGA2 ARNU42GBGA2

Ceiling Concealed Duct (High Static)

76, Seongsan-dong, Changwon City, Gyeongnam, 641-713, Korea

102 51

Number

Indoor Units

4

3. Dimensions & Gravity point


R6

0

60

198

312

380

50

215

5

621

279

6

1,230

1,004

241

118 1,004

1,284 1,230

279 215

120

114

4

2

90

1

135 190 260

115

101 83

Name

Air discharge Air suction

4 5 6

Unit size(48k):ø15.88

Unit size(48k):ø9.52

Descripition

(unit : mm)

Gravity point

CHASSIS CODE: BR

2. Unit shall be grounded in accordance with the local regulations or applicable national codes.

1. Unit should be installed in compliance with the installation manual in the product box.

Note

Power supply connection

3

76, Seongsan-dong, Changwon City, Gyeongnam, 641-713, Korea

3

Gas pipe connection Drain pipe connection

2

Liquid pipe connection

1

Number 26

ARNU48GBRA2

Ceiling Concealed Duct (High Static)

72 123 221 122 144

1,092

477 590 56 168

25

303

32

140

590

8 _ Ceiling Concealed Duct(High Static) 185 174

302 293

Indoor Units

3. Dimensions & Gravity point


Ceiling Concealed Duct(High Static) _ 9

460

460

688

293

5

329

819

6 1,622

1,562

320

1,220

1,562

329

115

688 30

222

560 64

290 161

20

440

318

1,396

358

68

18

109

58

122 60 70 64

397

Air suction

(unit : mm)

Unit size(76k):ø19.05 Unit size(96k):ø22.2

Unit size(76k,96k):ø9.52

Descripition

Gravity point

CHASSIS CODE: B8

2. Unit shall be grounded in accordance with the local regulations or applicable national codes.

1. Unit should be installed in compliance with the installation manual in the product box.

Note

6

5

Air discharge

Drain pipe connection Power supply connection

3 4

Gas pipe connection

2

Name Liquid pipe connection

3

1

Number

70 120

2

URNU76GB8A2 URNU96GB8A2

Ceiling Concealed Duct (High Static)

76, Seongsan-dong, Changwon City, Gyeongnam, 641-713, Korea

1

40 99 1

Indoor Units

4

3. Dimensions & Gravity point


4. Piping Diagrams

Heat Exchanger

:Cooling :Heating

EEV Filter

Th3

Th2 Sirocco Fan

Indoor Units

Th1

Filter

lndoor unit

Refrigerant pipe connection port diameter [Unit: mm(inch)]

MODEL

GAS

LIQUID

ARNU07GBHA2

Ø12.7(1/2)

Ø6.35(1/4)

ARNU09GBHA2

Ø12.7(1/2)

Ø6.35(1/4)

ARNU12GBHA2

Ø12.7(1/2)

Ø6.35(1/4)

ARNU15GBHA2

Ø12.7(1/2)

Ø6.35(1/4)

ARNU18GBHA2

Ø12.7(1/2)

Ø6.35(1/4)

ARNU24GBHA2

Ø15.88(5/8)

Ø9.52(3/8)

ARNU28GBGA2

Ø15.88(5/8)

Ø9.52(3/8)

ARNU36GBGA2

Ø15.88(5/8)

Ø9.52(3/8)

ARNU42GBGA2

Ø15.88(5/8)

Ø9.52(3/8)

ARNU48GBRA2

Ø15.88(5/8)

Ø9.52(3/8)

URNU76GB8A2

Ø19.05(3/4)

Ø9.52(3/8)

URNU96GB8A2

Ø22.2(7/8)

Ø9.52(3/8)

LOC.

Description

Th1

Room thermistor

Th2

Pipe in thermistor

Th3

Pipe out thermistor

10 _ Ceiling Concealed Duct(High Static)


5. Wiring Diagrams BH Chassis

LOCATION POINT AC Power supply Fan motor output Drain pump output Communication EEV Output Float switch input Suction pipe sensor Discharge pipe sensor Room sensor Remote controller Zontroller RF Remote controller Dry contact

Dip Switch Setting SW3 GROUP

Off Master

On Slave

SW4

DRY CONTACT

Variable

Auto

SW5

EXTRA 1

Off

On

FUNCTION AC Power line input for indoor controller Motor output of BLDC AC output for drain pump Connection between indoor and outdoor EEV Control output Float switch sensing Pipe in thermistor Pipe out thermistor Room air thermistor Remote control line Zone control line RF Remote control line Dry contact line Remarks Group Control setting using Wired Remote Controller Old Dry Contact Mode Setting 1. Variable : Auto/Manual Mode can be chosen by Wide wired remote controller or Wireless remote controller (When shipped from Factory → Manual Mode) 2. Auto : For Dry Contact, it is always Auto mode. 1. Duct model -. OFF : Default(not operate continuosly ) -. ON : Fan operate continuosly 2. Cassette Model : No Function 3. Ceiling Suspended Model -. OFF : Ceiling(default) -. ON : Floor

CAUTION For Multi V Model, Dip Switch 1,2,6,7,8 must be set OFF That dip switch is used for the other model.

Ceiling Concealed Duct(High Static) _ 11

Indoor Units

CONNECTOR NUMBER CN-POWER CN-MOTOR1 CN-D/PUMP CN-COM CN-EEV CN-FLOAT CN-PIPE/IN CN-PIPE/OUT CN-ROOM CN-REMO CN-ZON CN-DISPLAY CN-CC


5. Wiring Diagrams

Indoor Units

BG Chassis

CONNECTOR NUMBER CN-POWER CN-MOTOR1 CN-MOTOR2 CN-D/PUMP CN-COM CN-EEV CN-FLOAT CN-PIPE/IN CN-PIPE/OUT CN-ROOM CN-REMO CN-ZON CN-DISPLAY CN-CC

LOCATION POINT AC Power supply Fan motor output Fan motor output Drain pump output Communication EEV Output Float switch input Suction pipe sensor Discharge pipe sensor Room sensor Remote controller Zontroller RF Remote controller Dry contact

Dip Switch Setting SW3 GROUP

Off Master

On Slave

SW4

DRY CONTACT

Variable

Auto

SW5

EXTRA 1

Off

On

FUNCTION AC Power line input for indoor controller Motor output of BLDC Motor output of BLDC AC output for drain pump Connection between indoor and outdoor EEV Control output Float switch sensing Pipe in thermistor Pipe out thermistor Room air thermistor Remote control line Zone control line RF Remote control line Dry contact line Remarks Group Control setting using Wired Remote Controller Old Dry Contact Mode Setting 1. Variable : Auto/Manual Mode can be chosen by Wide wired remote controller or Wireless remote controller (When shipped from Factory → Manual Mode) 2. Auto : For Dry Contact, it is always Auto mode. 1. Duct model -. OFF : Default(not operate continuosly ) -. ON : Fan operate continuosly 2. Cassette Model : No Function 3. Ceiling Suspended Model -. OFF : Ceiling(default) -. ON : Floor

CAUTION For Multi V Model, Dip Switch 1,2,6,7,8 must be set OFF That dip switch is used for the other model.

12 _ Ceiling Concealed Duct(High Static)


5. Wiring Diagrams BR Chassis

LOCATION POINT AC Power supply Fan motor output Fan motor output Drain pump output Communication EEV Output Float switch input Suction pipe sensor Discharge pipe sensor Room sensor Remote controller Zontroller RF Remote controller Dry contact

Dip Switch Setting SW3 GROUP

Off Master

On Slave

SW4

DRY CONTACT

Variable

Auto

SW5

EXTRA 1

Off

On

FUNCTION AC Power line input for indoor controller Motor output of BLDC Motor output of BLDC AC output for drain pump Connection between indoor and outdoor EEV Control output Float switch sensing Pipe in thermistor Pipe out thermistor Room air thermistor Remote control line Zone control line RF Remote control line Dry contact line Remarks Group Control setting using Wired Remote Controller Old Dry Contact Mode Setting 1. Variable : Auto/Manual Mode can be chosen by Wide wired remote controller or Wireless remote controller (When shipped from Factory → Manual Mode) 2. Auto : For Dry Contact, it is always Auto mode. 1. Duct model -. OFF : Default(not operate continuosly ) -. ON : Fan operate continuosly 2. Cassette Model : No Function 3. Ceiling Suspended Model -. OFF : Ceiling(default) -. ON : Floor

CAUTION For Multi V Model, Dip Switch 1,2,6,7,8 must be set OFF That dip switch is used for the other model.

Ceiling Concealed Duct(High Static) _ 13

Indoor Units

CONNECTOR NUMBER CN-POWER CN-MOTOR1 CN-MOTOR2 CN-D/PUMP CN-COM CN-EEV CN-FLOAT CN-PIPE/IN CN-PIPE/OUT CN-ROOM CN-REMO CN-ZON CN-DISPLAY CN-CC


5. Wiring Diagrams

Indoor Units

B8 Chassis

CONNECTOR NUMBER CN-POWER CN-MOTOR1, CN-MOTOR2 CN-D/PUMP CN-COM CN-EEV CN-FLOAT CN-PIPE/IN CN-PIPE/OUT CN-ROOM CN-REMO CN-CC CN-DISPLAY CN-OPTION CN-ZONE

LOCATION POINT AC Power supply Fan motor output Drain pump output Communication EEV Output Float switch input Suction pipe sensor Discharge pipe sensor Room sensor Remote controller Dry contact RF Remocon Option PCB Zone controller

Dip Switch Setting SW3 GROUP

Off Master

On Slave

SW4

DRY CONTACT

Variable

Auto

SW5

EXTRA 1

Off

On

FUNCTION AC Power line input for indoor controller Motor output of BLDC AC Output for drain pump Connection between indoor and outdoor EEV Control output Float switch sensing Pipe in thermistor Pipe out thermistor Room thermistor Remote control line Dry contact line RF Remocon receiver Option PCB connector Zone controller line Remarks Group Control setting using Wired Remote Controller Old Dry Contact Mode Setting 1. Variable : Auto/Manual Mode can be chosen by Wide wired remote controller or Wireless remote controller (When shipped from Factory → Manual Mode) 2. Auto : For Dry Contact, it is always Auto mode. 1. Duct model -. OFF : Default(not operate continuosly ) -. ON : Fan operate continuosly 2. Cassette Model : No Function 3. Ceiling Suspended Model -. OFF : Ceiling(default) -. ON : Floor

CAUTION For Multi V Model, Dip Switch 1,2,6,7,8 must be set OFF That dip switch is used for the other model.

14 _ Ceiling Concealed Duct(High Static)


6. Capacity Tables 6.1 Cooling Capacity

Cooling capacity

20 14 TC SHC kW kW

23 16 TC SHC kW kW

Indoor air temp. (DB/WB, °C) 26 27 28 18 19 20 TC SHC TC SHC TC SHC kW kW kW kW kW kW

2.2

10 12 14 16 18 20 21 23 25 27 29 31 33 35 37 39

1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5

1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4

1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8

1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5

2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1

1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7

2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2

1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7

2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3

1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7

2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6

1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8

2.9 2.9 2.8 2.8 2.7 2.7 2.7 2.6 2.6 2.6 2.5 2.5 2.5 2.4 2.4 2.3

1.8 1.8 1.8 1.7 1.7 1.7 1.7 1.7 1.6 1.6 1.6 1.6 1.5 1.5 1.5 1.5

2.8

10 12 14 16 18 20 21 23 25 27 29 31 33 35 37 39

1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9

1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8

2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3

2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0

2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6

2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1

2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8

2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2

3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0

2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2

3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4

2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3

3.7 3.6 3.6 3.5 3.5 3.4 3.4 3.4 3.3 3.3 3.2 3.2 3.1 3.1 3.0 3.0

2.3 2.3 2.2 2.2 2.2 2.1 2.1 2.1 2.1 2.0 2.0 2.0 2.0 1.9 1.9 1.9

3.6

10 12 14 16 18 20 21 23 25 27 29 31 33 35 37 39

2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4

2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3

2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9

2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5

3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4

2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7

3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6

2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8

3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8

2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9

4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3

3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0

4.7 4.7 4.6 4.6 4.5 4.4 4.4 4.3 4.3 4.2 4.2 4.1 4.0 4.0 3.9 3.8

3.0 2.9 2.9 2.8 2.8 2.8 2.7 2.7 2.7 2.6 2.6 2.6 2.5 2.5 2.4 2.4

Capacity Index

Outdoor air temp. (DB, °C)

32 24 TC SHC kW kW

SHC: Sensible Heat Capacity(kW)

Ceiling Concealed Duct(High Static) _ 15

Indoor Units

Notes: TC: Total Capacity(kW)

30 22 TC SHC kW kW


6. Capacity Tables Cooling capacity

20 14 TC SHC kW kW

23 16 TC SHC kW kW

Indoor air temp. (DB/WB, °C) 26 27 28 18 19 20 TC SHC TC SHC TC SHC kW kW kW kW kW kW

30 22 TC SHC kW kW

4.5

10 12 14 16 18 20 21 23 25 27 29 31 33 35 37 39

3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0

2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8

3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6

3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1

4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2

3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4

4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5

3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5

4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8

3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6

5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4

3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7

5.9 5.8 5.8 5.7 5.6 5.5 5.5 5.4 5.3 5.3 5.2 5.1 5.0 5.0 4.9 4.8

3.7 3.6 3.6 3.6 3.5 3.5 3.4 3.4 3.3 3.3 3.2 3.2 3.1 3.1 3.1 3.0

5.6

10 12 14 16 18 20 21 23 25 27 29 31 33 35 37 39

3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8

3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4

4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5

3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7

5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2

4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0

5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6

4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1

6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 5.8 5.7

4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.1 4.0

6.7 6.7 6.7 6.7 6.7 6.7 6.7 6.7 6.6 6.4 6.4 6.3 6.2 6.0 5.9 5.8

4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.3 4.2 4.2 4.1 4.0 4.0 3.9 3.8

7.4 7.3 7.2 7.1 7.0 6.9 6.8 6.7 6.6 6.6 6.5 6.4 6.3 6.2 6.1 6.0

4.4 4.3 4.3 4.2 4.1 4.1 4.1 4.0 3.9 3.9 3.8 3.8 3.7 3.6 3.6 3.5

7.1

10 12 14 16 18 20 21 23 25 27 29 31 33 35 37 39

4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8

4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3

5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7

4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7

6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6

5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1

7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1

5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2

7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.4 7.2

5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.2 5.1

8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.4 8.2 8.1 8.0 7.8 7.7 7.5 7.4

5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.5 5.4 5.3 5.2 5.1 5.0 4.9 4.8

9.3 9.2 9.1 9.0 8.8 8.7 8.7 8.5 8.4 8.3 8.2 8.1 7.9 7.8 7.7 7.6

5.5 5.5 5.4 5.3 5.2 5.2 5.1 5.1 5.0 4.9 4.8 4.8 4.7 4.6 4.6 4.5

Indoor Units

Capacity Index

Outdoor air temp. (DB, °C)

Notes: TC: Total Capacity(kW)

SHC: Sensible Heat Capacity(kW)

16 _ Ceiling Concealed Duct(High Static)

32 24 TC SHC kW kW


6. Capacity Tables Cooling capacity

20 14 TC SHC kW kW

23 16 TC SHC kW kW

Indoor air temp. (DB/WB, °C) 26 27 28 18 19 20 TC SHC TC SHC TC SHC kW kW kW kW kW kW

30 22 TC SHC kW kW

32 24 TC SHC kW kW

8.2

10 12 14 16 18 20 21 23 25 27 29 31 33 35 37 39

5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5

5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0

6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6

5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5

7.7 7.7 7.7 7.7 7.7 7.7 7.7 7.7 7.7 7.7 7.7 7.7 7.7 7.7 7.7 7.7

6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0

8.2 8.2 8.2 8.2 8.2 8.2 8.2 8.2 8.2 8.2 8.2 8.2 8.2 8.2 8.2 8.2

6.1 6.1 6.1 6.1 6.1 6.1 6.1 6.1 6.1 6.1 6.1 6.1 6.1 6.1 6.1 6.1

8.7 8.7 8.7 8.7 8.7 8.7 8.7 8.7 8.7 8.7 8.7 8.7 8.7 8.7 8.5 8.4

6.2 6.2 6.2 6.2 6.2 6.2 6.2 6.2 6.2 6.2 6.2 6.2 6.2 6.2 6.1 6.0

9.8 9.8 9.8 9.8 9.8 9.8 9.8 9.8 9.7 9.4 9.3 9.2 9.0 8.9 8.7 8.5

6.5 6.5 6.5 6.5 6.5 6.5 6.5 6.5 6.4 6.3 6.2 6.1 6.0 5.9 5.8 5.7

10.8 10.6 10.5 10.4 10.2 10.1 10.0 9.9 9.7 9.6 9.5 9.3 9.2 9.0 8.9 8.8

6.5 6.4 6.3 6.2 6.1 6.0 6.0 5.9 5.8 5.8 5.7 5.6 5.5 5.4 5.3 5.3

10 12 14 16 18 20 21 23 25 27 29 31 33 35 37 39 10 12 14 16 18 20 21 23 25 27 29 31 33 35 37 39

7.2 7.2 7.2 7.2 7.2 7.2 7.2 7.2 7.2 7.2 7.2 7.2 7.2 7.2 7.2 7.2 8.3 8.3 8.3 8.3 8.3 8.3 8.3 8.3 8.3 8.3 8.3 8.3 8.3 8.3 8.3 8.3

6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 6.4 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5

8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9

7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 8.3 8.3 8.3 8.3 8.3 8.3 8.3 8.3 8.3 8.3 8.3 8.3 8.3 8.3 8.3 8.3

9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 9.9 11.5 11.5 11.5 11.5 11.5 11.5 11.5 11.5 11.5 11.5 11.5 11.5 11.5 11.5 11.5 11.5

7.7 7.7 7.7 7.7 7.7 7.7 7.7 7.7 7.7 7.7 7.7 7.7 7.7 7.7 7.7 7.7 9.0 9.0 9.0 9.0 9.0 9.0 9.0 9.0 9.0 9.0 9.0 9.0 9.0 9.0 9.0 9.0

10.6 10.6 10.6 10.6 10.6 10.6 10.6 10.6 10.6 10.6 10.6 10.6 10.6 10.6 10.6 10.6 12.3 12.3 12.3 12.3 12.3 12.3 12.3 12.3 12.3 12.3 12.3 12.3 12.3 12.3 12.3 12.3

7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8 9.1 9.1 9.1 9.1 9.1 9.1 9.1 9.1 9.1 9.1 9.1 9.1 9.1 9.1 9.1 9.1

11.3 11.3 11.3 11.3 11.3 11.3 11.3 11.3 11.3 11.3 11.3 11.3 11.3 11.3 11.0 10.8 13.1 13.1 13.1 13.1 13.1 13.1 13.1 13.1 13.1 13.1 13.1 13.1 13.1 13.1 12.8 12.5

8.1 8.1 8.1 8.1 8.1 8.1 8.1 8.1 8.1 8.1 8.1 8.1 8.1 8.1 7.9 7.7 9.4 9.4 9.4 9.4 9.4 9.4 9.4 9.4 9.4 9.4 9.4 9.4 9.4 9.4 9.2 9.0

12.7 12.7 12.7 12.7 12.7 12.7 12.7 12.7 12.5 12.2 12.1 11.9 11.7 11.4 11.2 11.0 14.7 14.7 14.7 14.7 14.7 14.7 14.7 14.7 14.5 14.1 14.0 13.8 13.5 13.3 13.0 12.8

8.4 8.4 8.4 8.4 8.4 8.4 8.4 8.4 8.3 8.1 8.0 7.9 7.8 7.6 7.5 7.3 9.8 9.8 9.8 9.8 9.8 9.8 9.8 9.8 9.7 9.4 9.3 9.2 9.0 8.8 8.7 8.5

13.9 13.7 13.6 13.4 13.2 13.0 12.9 12.8 12.6 12.4 12.2 12.0 11.8 11.7 11.5 11.3 16.2 15.9 15.8 15.6 15.3 15.1 15.0 14.8 14.6 14.4 14.2 14.0 13.7 13.5 13.4 13.1

8.4 8.2 8.2 8.0 7.9 7.8 7.8 7.7 7.5 7.5 7.3 7.2 7.1 7.0 6.9 6.8 9.7 9.6 9.5 9.3 9.2 9.1 9.0 8.9 8.8 8.6 8.5 8.4 8.3 8.1 8.0 7.9

10.6

12.3

Notes: TC: Total Capacity(kW)

SHC: Sensible Heat Capacity(kW)

Ceiling Concealed Duct(High Static) _ 17

Indoor Units

Capacity Index

Outdoor air temp. (DB, °C)


6. Capacity Tables Cooling capacity

Capacity Index

Indoor Units

14.1

22.4

28.0

Outdoor air temp. (DB, °C) 10 12 14 16 18 20 21 23 25 27 29 31 33 35 37 39 10 12 14 16 18 20 21 23 25 27 29 31 33 35 37 39 10 12 14 16 18 20 21 23 25 27 29 31 33 35 37 39

Notes: TC: Total Capacity(kW)

20 14 TC SHC kW kW

23 16 TC SHC kW kW

Indoor air temp. (DB/WB, °C) 26 27 28 18 19 20 TC SHC TC SHC TC SHC kW kW kW kW kW kW

9.5 9.5 9.5 9.5 9.5 9.5 9.5 9.5 9.5 9.5 9.5 9.5 9.5 9.5 9.5 9.5 15.1 15.1 15.1 15.1 15.1 15.1 15.1 15.1 15.1 15.1 15.1 15.1 15.1 15.1 15.1 15.1 18.9 18.9 18.9 18.9 18.9 18.9 18.9 18.9 18.9 18.9 18.9 18.9 18.9 18.9 18.9 18.9

11.3 11.3 11.3 11.3 11.3 11.3 11.3 11.3 11.3 11.3 11.3 11.3 11.3 11.3 11.3 11.3 18.0 18.0 18.0 18.0 18.0 18.0 18.0 18.0 18.0 18.0 18.0 18.0 18.0 18.0 18.0 18.0 22.5 22.5 22.5 22.5 22.5 22.5 22.5 22.5 22.5 22.5 22.5 22.5 22.5 22.5 22.5 22.5

13.2 13.2 13.2 13.2 13.2 13.2 13.2 13.2 13.2 13.2 13.2 13.2 13.2 13.2 13.2 13.2 21.0 21.0 21.0 21.0 21.0 21.0 21.0 21.0 21.0 21.0 21.0 21.0 21.0 21.0 21.0 21.0 26.2 26.2 26.2 26.2 26.2 26.2 26.2 26.2 26.2 26.2 26.2 26.2 26.2 26.2 26.2 26.2

8.7 8.7 8.7 8.7 8.7 8.7 8.7 8.7 8.7 8.7 8.7 8.7 8.7 8.7 8.7 8.7 12.9 12.9 12.9 12.9 12.9 12.9 12.9 12.9 12.9 12.9 12.9 12.9 12.9 12.9 12.9 12.9 16.1 16.1 16.1 16.1 16.1 16.1 16.1 16.1 16.1 16.1 16.1 16.1 16.1 16.1 16.1 16.1

9.6 9.6 9.6 9.6 9.6 9.6 9.6 9.6 9.6 9.6 9.6 9.6 9.6 9.6 9.6 9.6 14.3 14.3 14.3 14.3 14.3 14.3 14.3 14.3 14.3 14.3 14.3 14.3 14.3 14.3 14.3 14.3 17.8 17.8 17.8 17.8 17.8 17.8 17.8 17.8 17.8 17.8 17.8 17.8 17.8 17.8 17.8 17.8

10.4 10.4 10.4 10.4 10.4 10.4 10.4 10.4 10.4 10.4 10.4 10.4 10.4 10.4 10.4 10.4 15.5 15.5 15.5 15.5 15.5 15.5 15.5 15.5 15.5 15.5 15.5 15.5 15.5 15.5 15.5 15.5 19.3 19.3 19.3 19.3 19.3 19.3 19.3 19.3 19.3 19.3 19.3 19.3 19.3 19.3 19.3 19.3

14.1 14.1 14.1 14.1 14.1 14.1 14.1 14.1 14.1 14.1 14.1 14.1 14.1 14.1 14.1 14.1 22.4 22.4 22.4 22.4 22.4 22.4 22.4 22.4 22.4 22.4 22.4 22.4 22.4 22.4 22.4 22.4 28.0 28.0 28.0 28.0 28.0 28.0 28.0 28.0 28.0 28.0 28.0 28.0 28.0 28.0 28.0 28.0

10.6 10.6 10.6 10.6 10.6 10.6 10.6 10.6 10.6 10.6 10.6 10.6 10.6 10.6 10.6 10.6 15.7 15.7 15.7 15.7 15.7 15.7 15.7 15.7 15.7 15.7 15.7 15.7 15.7 15.7 15.7 15.7 19.6 19.6 19.6 19.6 19.6 19.6 19.6 19.6 19.6 19.6 19.6 19.6 19.6 19.6 19.6 19.6

SHC: Sensible Heat Capacity(kW)

18 _ Ceiling Concealed Duct(High Static)

15.0 15.0 15.0 15.0 15.0 15.0 15.0 15.0 15.0 15.0 15.0 15.0 15.0 15.0 14.7 14.4 23.8 23.8 23.8 23.8 23.8 23.8 23.8 23.8 23.8 23.8 23.8 23.8 23.8 23.8 23.8 23.8 29.8 29.8 29.8 29.8 29.8 29.8 29.8 29.8 29.8 29.8 29.8 29.8 29.8 29.8 29.8 29.8

10.9 10.9 10.9 10.9 10.9 10.9 10.9 10.9 10.9 10.9 10.9 10.9 10.9 10.9 10.6 10.4 16.1 16.1 16.1 16.1 16.1 16.1 16.1 16.1 16.1 16.1 16.1 16.1 16.1 16.1 16.1 16.1 20.2 20.2 20.2 20.2 20.2 20.2 20.2 20.2 20.2 20.2 20.2 20.2 20.2 20.2 20.2 20.2

30 22 TC SHC kW kW

32 24 TC SHC kW kW

16.9 16.9 16.9 16.9 16.9 16.9 16.9 16.9 16.6 16.2 16.1 15.8 15.5 15.2 14.9 14.7 26.8 26.8 26.8 26.8 26.8 26.8 26.8 26.8 26.8 26.8 26.8 26.8 26.8 26.8 26.8 26.8 33.5 33.5 33.5 33.5 33.5 33.5 33.5 33.5 33.5 33.5 33.5 33.5 33.5 33.5 33.5 33.5

18.5 18.3 18.1 17.8 17.6 17.3 17.2 17.0 16.7 16.5 16.3 16.0 15.8 15.5 15.3 15.1 29.4 29.0 28.7 28.3 27.9 27.5 27.4 27.0 26.6 26.2 25.8 25.4 25.0 24.6 24.3 23.9 36.8 36.3 35.9 35.4 34.9 34.4 34.2 33.7 33.2 32.8 32.3 31.8 31.3 30.8 30.4 29.9

11.4 11.4 11.4 11.4 11.4 11.4 11.4 11.4 11.2 10.9 10.8 10.7 10.5 10.3 10.1 9.9 16.9 16.9 16.9 16.9 16.9 16.9 16.9 16.9 16.9 16.9 16.9 16.9 16.9 16.9 16.9 16.9 21.1 21.1 21.1 21.1 21.1 21.1 21.1 21.1 21.1 21.1 21.1 21.1 21.1 21.1 21.1 21.1

11.3 11.1 11.0 10.8 10.7 10.5 10.5 10.3 10.2 10.0 9.9 9.7 9.6 9.4 9.3 9.2 16.7 16.5 16.3 16.1 15.9 15.6 15.5 15.3 15.1 14.9 14.7 14.4 14.2 14.0 13.8 13.6 20.9 20.6 20.4 20.1 19.8 19.5 19.4 19.1 18.9 18.6 18.3 18.1 17.8 17.5 17.3 17.0


6. Capacity Tables 6.2 Heating Capacity Outdoor air temp. Capacity Index DB(°C) WB(°C)

Heating capacity

Indoor air temp. (DB, °C) 16

18

20

21

22

24

TC

TC

TC

TC

TC

TC

kW

kW

kW

kW

kW

2.2

-20.0 -19.0 -17.0 -15.0 -13.0 -11.0 -10.0 -9.1 -7.6 -5.6 -3.7 -0.7 2.2 4.1 6.0 7.9 9.8 11.8 13.7

1.7 1.7 1.8 1.9 2.0 2.1 2.2 2.2 2.3 2.4 2.5 2.6 2.8 2.8 2.9 2.9 2.9 2.9 2.9

1.7 1.7 1.8 1.9 2.0 2.1 2.2 2.2 2.3 2.4 2.5 2.6 2.7 2.7 2.7 2.7 2.7 2.7 2.7

1.7 1.7 1.8 1.7 1.8 1.9 1.9 2.0 2.0 2.1 2.2 2.3 2.4 2.5 2.5 2.5 2.5 2.5 2.5

1.7 1.7 1.8 1.9 2.0 2.1 2.2 2.2 2.2 2.3 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4

1.7 1.7 1.8 1.9 2.0 2.1 2.2 2.2 2.2 2.3 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4

1.7 1.7 1.8 1.9 2.0 2.1 2.1 2.1 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2

2.8

-19.8 -18.8 -16.7 -14.7 -12.6 -10.5 -9.5 -8.5 -7.0 -5.0 -3.0 0.0 3.0 5.0 7.0 9.0 11.0 13.0 15.0

-20.0 -19.0 -17.0 -15.0 -13.0 -11.0 -10.0 -9.1 -7.6 -5.6 -3.7 -0.7 2.2 4.1 6.0 7.9 9.8 11.8 13.7

2.1 2.2 2.3 2.5 2.6 2.7 2.8 2.8 2.9 3.0 3.2 3.4 3.6 3.6 3.7 3.7 3.7 3.7 3.7

2.1 2.2 2.3 2.4 2.6 2.7 2.8 2.8 2.9 3.0 3.2 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4

2.1 2.2 2.3 2.2 2.3 2.4 2.5 2.5 2.6 2.7 2.8 3.0 3.1 3.2 3.2 3.2 3.2 3.2 3.2

2.1 2.2 2.3 2.4 2.6 2.7 2.8 2.8 2.8 3.0 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1

2.1 2.2 2.3 2.4 2.6 2.7 2.8 2.8 2.8 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0

2.1 2.2 2.3 2.4 2.6 2.7 2.7 2.7 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8

3.6

-19.8 -18.8 -16.7 -14.7 -12.6 -10.5 -9.5 -8.5 -7.0 -5.0 -3.0 0.0 3.0 5.0 7.0 9.0 11.0 13.0 15.0

-20.0 -19.0 -17.0 -15.0 -13.0 -11.0 -10.0 -9.1 -7.6 -5.6 -3.7 -0.7 2.2 4.1 6.0 7.9 9.8 11.8 13.7

2.7 2.8 2.9 3.1 3.2 3.4 3.4 3.5 3.6 3.8 4.0 4.2 4.4 4.5 4.6 4.6 4.6 4.6 4.6

2.7 2.8 2.9 3.0 3.2 3.4 3.4 3.5 3.6 3.8 4.0 4.2 4.3 4.3 4.3 4.3 4.3 4.3 4.3

2.7 2.8 2.9 2.7 2.9 3.0 3.1 3.2 3.3 3.4 3.5 3.7 3.9 4.0 4.0 4.0 4.0 4.0 4.0

2.6 2.8 2.9 3.0 3.2 3.4 3.4 3.5 3.6 3.7 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9

2.6 2.7 2.9 3.0 3.2 3.4 3.4 3.5 3.6 3.7 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8

2.6 2.7 2.9 3.0 3.2 3.4 3.4 3.4 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5

Notes: TC: Total Capacity(kW)

Ceiling Concealed Duct(High Static) _ 19

Indoor Units

kW -19.8 -18.8 -16.7 -14.7 -12.6 -10.5 -9.5 -8.5 -7.0 -5.0 -3.0 0.0 3.0 5.0 7.0 9.0 11.0 13.0 15.0


6. Capacity Tables Heating capacity

Outdoor air temp. Capacity Index DB(°C) WB(°C)

Indoor air temp. (DB, °C) 16

18

20

21

22

24

TC

TC

TC

TC

TC

TC

kW

kW

kW

kW

kW

4.5

-20.0 -19.0 -17.0 -15.0 -13.0 -11.0 -10.0 -9.1 -7.6 -5.6 -3.7 -0.7 2.2 4.1 6.0 7.9 9.8 11.8 13.7

3.4 3.5 3.7 3.9 4.1 4.3 4.3 4.4 4.6 4.8 5.0 5.3 5.6 5.6 5.8 5.8 5.8 5.8 5.8

3.4 3.5 3.7 3.8 4.1 4.3 4.3 4.4 4.6 4.8 5.0 5.3 5.4 5.4 5.4 5.4 5.4 5.4 5.4

3.4 3.5 3.7 3.4 3.6 3.8 3.9 4.0 4.1 4.3 4.4 4.6 4.9 5.0 5.0 5.0 5.0 5.0 5.0

3.3 3.5 3.7 3.8 4.0 4.3 4.3 4.4 4.4 4.6 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8

3.3 3.4 3.7 3.8 4.0 4.2 4.3 4.4 4.4 4.6 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7

3.3 3.4 3.6 3.8 4.0 4.2 4.3 4.3 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4

5.6

-19.8 -18.8 -16.7 -14.7 -12.6 -10.5 -9.5 -8.5 -7.0 -5.0 -3.0 0.0 3.0 5.0 7.0 9.0 11.0 13.0 15.0

-20.0 -19.0 -17.0 -15.0 -13.0 -11.0 -10.0 -9.1 -7.6 -5.6 -3.7 -0.7 2.2 4.1 6.0 7.9 9.8 11.8 13.7

4.2 4.3 4.6 4.9 5.1 5.4 5.4 5.5 5.7 6.0 6.2 6.6 7.0 7.1 7.2 7.2 7.2 7.2 7.2

4.2 4.3 4.6 4.8 5.1 5.4 5.4 5.5 5.7 6.0 6.2 6.6 6.7 6.7 6.7 6.7 6.7 6.7 6.7

4.2 4.3 4.6 4.3 4.5 4.8 4.9 5.0 5.1 5.4 5.5 5.8 6.2 6.3 6.3 6.3 6.3 6.3 6.3

4.2 4.3 4.6 4.8 5.0 5.4 5.4 5.5 5.6 5.8 6.1 6.1 6.1 6.1 6.1 6.1 6.1 6.1 6.1

4.2 4.3 4.6 4.8 5.0 5.3 5.4 5.5 5.6 5.8 5.9 5.9 5.9 5.9 5.9 5.9 5.9 5.9 5.9

4.2 4.3 4.5 4.8 5.0 5.3 5.4 5.4 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5

7.1

-19.8 -18.8 -16.7 -14.7 -12.6 -10.5 -9.5 -8.5 -7.0 -5.0 -3.0 0.0 3.0 5.0 7.0 9.0 11.0 13.0 15.0

-20.0 -19.0 -17.0 -15.0 -13.0 -11.0 -10.0 -9.1 -7.6 -5.6 -3.7 -0.7 2.2 4.1 6.0 7.9 9.8 11.8 13.7

5.4 5.5 5.8 6.2 6.5 6.8 6.9 7.0 7.3 7.6 7.9 8.4 8.9 9.0 9.2 9.2 9.2 9.2 9.2

5.4 5.5 5.8 6.1 6.5 6.8 6.9 7.0 7.3 7.6 7.9 8.4 8.6 8.6 8.6 8.6 8.6 8.6 8.6

5.4 5.5 5.8 5.5 5.8 6.0 6.2 6.3 6.5 6.8 7.0 7.4 7.8 8.0 8.0 8.0 8.0 8.0 8.0

5.3 5.5 5.8 6.1 6.4 6.8 6.9 7.0 7.1 7.4 7.7 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8

5.3 5.4 5.8 6.1 6.4 6.7 6.9 7.0 7.1 7.4 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5

5.3 5.4 5.8 6.1 6.4 6.7 6.8 6.8 7.0 7.0 7.0 7.0 7.0 7.0 7.0 7.0 7.0 7.0 7.0

Indoor Units

kW -19.8 -18.8 -16.7 -14.7 -12.6 -10.5 -9.5 -8.5 -7.0 -5.0 -3.0 0.0 3.0 5.0 7.0 9.0 11.0 13.0 15.0

Notes: TC: Total Capacity(kW)

20 _ Ceiling Concealed Duct(High Static)


6. Capacity Tables Heating capacity

Outdoor air temp. Capacity Index DB(°C) WB(°C)

Indoor air temp. (DB, °C) 16

18

20

21

22

24

TC

TC

TC

TC

TC

TC

kW

kW

kW

kW

kW

8.2

-20.0 -19.0 -17.0 -15.0 -13.0 -11.0 -10.0 -9.1 -7.6 -5.6 -3.7 -0.7 2.2 4.1 6.0 7.9 9.8 11.8 13.7

6.2 6.3 6.7 7.1 7.5 7.8 7.9 8.1 8.4 8.7 9.1 9.7 10.2 10.4 10.6 10.6 10.6 10.6 10.6

6.2 6.3 6.7 7.0 7.5 7.8 7.9 8.1 8.4 8.7 9.1 9.7 9.8 9.8 9.8 9.8 9.8 9.8 9.8

6.2 6.3 6.7 6.3 6.6 7.0 7.1 7.3 7.5 7.8 8.1 8.5 9.0 9.2 9.2 9.2 9.2 9.2 9.2

6.1 6.3 6.7 7.0 7.4 7.8 7.9 8.1 8.2 8.5 8.9 8.9 8.9 8.9 8.9 8.9 8.9 8.9 8.9

6.1 6.3 6.7 7.0 7.4 7.7 7.9 8.1 8.2 8.5 8.6 8.6 8.6 8.6 8.6 8.6 8.6 8.6 8.6

6.1 6.3 6.6 7.0 7.4 7.7 7.8 7.9 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0

10.6

-19.8 -18.8 -16.7 -14.7 -12.6 -10.5 -9.5 -8.5 -7.0 -5.0 -3.0 0.0 3.0 5.0 7.0 9.0 11.0 13.0 15.0

-20.0 -19.0 -17.0 -15.0 -13.0 -11.0 -10.0 -9.1 -7.6 -5.6 -3.7 -0.7 2.2 4.1 6.0 7.9 9.8 11.8 13.7

8.0 8.2 8.7 9.2 9.6 10.1 10.2 10.5 10.8 11.3 11.8 12.5 13.2 13.4 13.7 13.7 13.7 13.7 13.7

8.0 8.2 8.7 9.0 9.6 10.1 10.2 10.5 10.8 11.3 11.8 12.5 12.7 12.7 12.7 12.7 12.7 12.7 12.7

8.0 8.2 8.7 8.2 8.6 9.0 9.2 9.4 9.7 10.1 10.4 11.0 11.6 11.9 11.9 11.9 11.9 11.9 11.9

7.9 8.2 8.7 9.0 9.5 10.1 10.2 10.5 10.6 11.0 11.5 11.5 11.5 11.5 11.5 11.5 11.5 11.5 11.5

7.9 8.1 8.7 9.0 9.5 10.0 10.2 10.5 10.6 11.0 11.2 11.2 11.2 11.2 11.2 11.2 11.2 11.2 11.2

7.9 8.1 8.6 9.1 9.5 10.0 10.1 10.2 10.4 10.4 10.4 10.4 10.4 10.4 10.4 10.4 10.4 10.4 10.4

12.3

-19.8 -18.8 -16.7 -14.7 -12.6 -10.5 -9.5 -8.5 -7.0 -5.0 -3.0 0.0 3.0 5.0 7.0 9.0 11.0 13.0 15.0

-20.0 -19.0 -17.0 -15.0 -13.0 -11.0 -10.0 -9.1 -7.6 -5.6 -3.7 -0.7 2.2 4.1 6.0 7.9 9.8 11.8 13.7

9.2 9.5 10.1 10.6 11.2 11.7 11.9 12.1 12.6 13.1 13.7 14.5 15.3 15.5 15.9 15.9 15.9 15.9 15.9

9.2 9.5 10.1 10.5 11.2 11.7 11.9 12.1 12.6 13.1 13.7 14.5 14.8 14.8 14.8 14.8 14.8 14.8 14.8

9.2 9.5 10.1 9.5 10.0 10.4 10.7 10.9 11.3 11.7 12.1 12.8 13.5 13.8 13.8 13.8 13.8 13.8 13.8

9.1 9.5 10.1 10.5 11.0 11.7 11.9 12.1 12.2 12.8 13.3 13.4 13.4 13.4 13.4 13.4 13.4 13.4 13.4

9.1 9.4 10.1 10.5 11.0 11.6 11.9 12.1 12.2 12.8 13.0 13.0 13.0 13.0 13.0 13.0 13.0 13.0 13.0

9.1 9.4 9.9 10.5 11.0 11.6 11.7 11.8 12.1 12.1 12.1 12.1 12.1 12.1 12.1 12.1 12.1 12.1 12.1

Notes: TC: Total Capacity(kW)

Ceiling Concealed Duct(High Static) _ 21

Indoor Units

kW -19.8 -18.8 -16.7 -14.7 -12.6 -10.5 -9.5 -8.5 -7.0 -5.0 -3.0 0.0 3.0 5.0 7.0 9.0 11.0 13.0 15.0


6. Capacity Tables Heating capacity

Outdoor air temp. Capacity Index DB(°C) WB(°C)

Indoor air temp. (DB, °C) 16

18

20

21

22

24

TC

TC

TC

TC

TC

TC

kW

kW

kW

kW

kW

14.1

-20.0 -19.0 -17.0 -15.0 -13.0 -11.0 -10.0 -9.1 -7.6 -5.6 -3.7 -0.7 2.2 4.1 6.0 7.9 9.8 11.8 13.7

10.7 11.0 11.6 12.2 12.9 13.5 13.7 14.0 14.5 15.1 15.7 16.7 17.7 17.9 18.3 18.3 18.3 18.3 18.3

10.7 11.0 11.6 12.1 12.9 13.5 13.7 14.0 14.5 15.1 15.7 16.7 17.0 17.0 17.0 17.0 17.0 17.0 17.0

10.7 11.0 11.6 10.9 11.5 12.0 12.3 12.6 13.0 13.5 13.9 14.7 15.5 15.9 15.9 15.9 15.9 15.9 15.9

10.5 11.0 11.6 12.1 12.7 13.5 13.7 14.0 14.1 14.7 15.3 15.4 15.4 15.4 15.4 15.4 15.4 15.4 15.4

10.5 10.8 11.6 12.1 12.7 13.4 13.7 14.0 14.1 14.7 14.9 14.9 14.9 14.9 14.9 14.9 14.9 14.9 14.9

10.5 10.8 11.4 12.1 12.7 13.4 13.5 13.6 13.9 13.9 13.9 13.9 13.9 13.9 13.9 13.9 13.9 13.9 13.9

22.4

-19.8 -18.8 -16.7 -14.7 -12.6 -10.5 -9.5 -8.5 -7.0 -5.0 -3.0 0.0 3.0 5.0 7.0 9.0 11.0 13.0 15.0

-20.0 -19.0 -17.0 -15.0 -13.0 -11.0 -10.0 -9.1 -7.6 -5.6 -3.7 -0.7 2.2 4.1 6.0 7.9 9.8 11.8 13.7

16.9 17.4 18.4 19.4 20.4 21.4 21.7 22.2 22.9 23.9 25.0 26.5 28.0 28.4 29.0 29.0 29.0 29.0 29.0

16.9 17.4 18.4 19.2 20.4 21.4 21.7 22.2 22.9 23.9 25.0 26.5 27.0 27.0 27.0 27.0 27.0 27.0 27.0

16.9 17.4 18.4 17.3 18.2 19.1 19.5 19.9 20.6 21.5 22.1 23.4 24.6 25.2 25.2 25.2 25.2 25.2 25.2

16.6 17.4 18.4 19.2 20.2 21.4 21.7 22.2 22.4 23.3 24.3 24.4 24.4 24.4 24.4 24.4 24.4 24.4 24.4

16.6 17.1 18.4 19.2 20.2 21.2 21.7 22.2 22.4 23.3 23.7 23.7 23.7 23.7 23.7 23.7 23.7 23.7 23.7

16.6 17.1 18.1 19.2 20.2 21.2 21.4 21.6 22.0 22.0 22.0 22.0 22.0 22.0 22.0 22.0 22.0 22.0 22.0

28.0

-19.8 -18.8 -16.7 -14.7 -12.6 -10.5 -9.5 -8.5 -7.0 -5.0 -3.0 0.0 3.0 5.0 7.0 9.0 11.0 13.0 15.0

-20.0 -19.0 -17.0 -15.0 -13.0 -11.0 -10.0 -9.1 -7.6 -5.6 -3.7 -0.7 2.2 4.1 6.0 7.9 9.8 11.8 13.7

21.1 21.7 23.0 24.3 25.5 26.8 27.1 27.7 28.7 29.9 31.2 33.1 35.0 35.4 36.2 36.2 36.2 36.2 36.2

21.1 21.7 23.0 23.9 25.5 26.8 27.1 27.7 28.7 29.9 31.2 33.1 33.7 33.7 33.7 33.7 33.7 33.7 33.7

21.1 21.7 23.0 21.6 22.7 23.8 24.4 24.9 25.7 26.8 27.6 29.2 30.8 31.5 31.5 31.5 31.5 31.5 31.5

20.8 21.7 23.0 23.9 25.2 26.8 27.1 27.7 28.0 29.1 30.3 30.5 30.5 30.5 30.5 30.5 30.5 30.5 30.5

20.8 21.4 23.0 23.9 25.2 26.5 27.1 27.7 28.0 29.1 29.6 29.6 29.6 29.6 29.6 29.6 29.6 29.6 29.6

20.8 21.4 22.7 24.0 25.2 26.5 26.8 27.0 27.6 27.6 27.6 27.6 27.6 27.6 27.6 27.6 27.6 27.6 27.6

Indoor Units

kW -19.8 -18.8 -16.7 -14.7 -12.6 -10.5 -9.5 -8.5 -7.0 -5.0 -3.0 0.0 3.0 5.0 7.0 9.0 11.0 13.0 15.0

Notes: TC: Total Capacity(kW)

22 _ Ceiling Concealed Duct(High Static)


7. External Static Pressure (E.S.P) & Air Flow ARNU07GBHA2, ARNU09GBHA2, ARNU12GBHA2 ARNU15GBHA2, ARNU18GBHA2, ARNU24GBHA2 Setting Value 70 80 90 100 110 120 130 140 145 150

(Unit: CMM)

Static Pressure(mmAq(Pa)) 3(29)

4(39)

5(49)

6(59)

7(69)

8(78)

9(88)

10(98)

12(118)

4.1 7.6 10.7 13.4 15.9 18.6 19.8 22.3 23.2 24.3

8.1 11.2 13.2 16.2 18.8 21.1 22.2 23.1

6.3 9.6 12.6 15.2 18.0 20.3 21.4 22.3

4.9 7.5 10.3 12.8 15.3 17.7 19.1 21.1

4.0 7.7 11.1 14.2 17.1 18.4 19.8

5.5 9.1 12.4 15.5 16.9 18.3

6.7 10.4 13.7 15.3 16.8

5.3 8.8 12.6 13.8 15.2

5.7 9.7 11.8 13.0

Setting Value 70 80 90 100 110 120 130 140 143 150 160

(Unit: CMM)

Static Pressure(mmAq(Pa)) 5(49)

6(59)

7(69)

8(78)

9(88)

10(98)

12(118)

14(137)

16(157)

4.0 12.1 17.0 21.4 25.8 30.0 36.0 37.5 41.0 42.4

6.9 15.5 19.6 24.0 28.5 32.1 33.9 38.0 41.6

4.13 11.01 17.53 21.8 26.93 30.41 32.1 36.0 38.2

6.2 14.0 19.8 25.3 29.0 30.7 34.5 36.1

4.2 11.6 17.9 23.4 27.4 28.8 32.1 35

6.6 14.6 21.8 25.9 27.2 30.1 34.6

12.1 18.1 21.6 23.0 26.3 31.1

14.6 17.8 20.1 22.4 26.8

11.3 14.5 16.8 18.2 23.3

ARNU48GBRA2 Setting Value 91 96 101 106 111 116 121 126

(Unit: CMM) Static Pressure(mmAq(Pa)) 5(49)

6(59)

8(78)

46.5 49.9 52.1 51.4 53.6 62.3 67.0 68.2

43.7 46.1 50.2 51.2 53.7 61.0 64.8 67.5

38.2 43.0 47.9 50.4 52.9 60.3 64.1 66.2

10(98) 12(118) 14(137) 15(147) 16(157) 17(168) 18(176) 20(196) 31.3 33.5 39.5 44.4 49.9 55.7 58.2 65.1

23.2 31.1 37.4 43.1 48.3 50.8 52.2 64.3

14.0 18.4 27.3 33.3 40.6 44.8 50.8 57.4

9.0 13.7 25.2 32.1 40.2 42.6 50.3 54.4

3.7 9.0 17.8 28.9 32.8 40.1 45.7 51.2

2.6 8.9 21.0 31.5 37.6 44.6 50.4

6.1 17.9 27.2 32.5 38.8 46.0

8.3 17.5 27.6 32.2 43.5

Note: 1. The above table shows the correlation between the air rates and E.S.P.

Ceiling Concealed Duct(High Static) _ 23

Indoor Units

ARNU28GBGA2, ARNU36GBGA2, ARNU42GBGA2


7. External Static Pressure (E.S.P) & Air Flow URNU76GB8A2, URNU96GB8A2 (Unit: CMM)

Indoor Units

Setting Value

Static Pressure(mmAq(Pa)) 6(59)

9(88)

12(118)

15(147)

18(177)

20(196)

22(216)

23(226)

25(245)

60

40.5

-

-

-

-

-

-

-

-

65

52.7

-

-

-

-

-

-

-

-

70

63.7

47.1

-

-

-

-

-

-

-

75

71.1

56.9

44.7

-

-

-

-

-

-

80

76.3

69.7

55.2

-

-

-

-

-

-

85

83.3

78.6

67.4

55.9

-

-

-

-

-

91

89.7

87.1

78.9

67.6

54.2

-

-

-

-

95

93.4

91.4

86.1

77.0

66.4

50.6

30.0

-

-

100

93.4

91.4

88.3

84.9

75.9

69.5

60.8

43.1

-

105

93.2

91.3

88.3

84.9

81.1

77.4

69.2

67.9

51.3

Note: 1. The above table shows the correlation between the air rates and E.S.P.

24 _ Ceiling Concealed Duct(High Static)


7. External Static Pressure (E.S.P) & Air Flow ARNU07GBHA2, ARNU09GBHA2, ARNU12GBHA2 ARNU15GBHA2, ARNU18GBHA2, ARNU24GBHA2 Capacity

High (factory set) 7k Standard High (factory set) 9k Standard High (factory set) Standard High (factory set) 15k Standard High (factory set) 18k Standard High (factory set) Standard

Hl Mid Low Hl Mid Low Hl Mid Low Hl Mid Low Hl Mid Low Hl Mid Low Hl Mid Low Hl Mid Low HI Mid Low HI Mid Low HI Mid Low HI Mid Low

120 117 115 110 107 105 125 120 117 110 107 105 130 125 120 115 110 105 135 130 120 123 120 115 140 135 130 130 125 110 150 145 140 145 135 128

8(78) 6(59) 8(78) 6(59) 8(78) 6(59) 8(78) 6(59) 8(78) 6(59) 8(78) 6(59)

CMM 8.5 7.5 6 8.5 8 7.5 10 8.5 7.5 8.5 8 7.5 12 10 8.5 11 8.5 7.5 13.5 12 8.5 13.5 12 11 15.5 13.5 12.4 15.3 13.6 10.3 18.3 16.9 15.5 19 16.4 14.5

Lower Limit of External Static Pressure(mmAq(Pa))

Upper Limit of External Static Pressure(mmAq(Pa))

6(59)

12(118)

4(39)

8(78)

6(59)

12(118)

4(39)

8(78)

6(59)

12(118)

4(39)

8(78)

6(59)

12(118)

4(39)

8(78)

6(59)

12(118)

4(39)

8(78)

6(59)

12(118)

4(39)

8(78)

ARNU28GBGA2, ARNU36GBGA2, ARNU42GBGA2 Capacity

28k

High (factory set) Standard

36k

Standard Set value ESP(mmAq(Pa))

Mode

High (factory set) Standard High (factory set)

42k Standard

HI Mid Low HI Mid Low HI Mid Low HI Mid Low HI Mid Low HI Mid Low

140 136 130 130 124 116 151 145 139 138 130 124 157 154 151 145 138 134

10(98) 8(78) 10(98) 8(78) 10(98) 8(78)

CMM 25.9 24.1 21.8 25.3 21.8 17.6 32.3 29 25.3 28.4 25.3 21.8 34.5 32.3 30.7 32 28.4 27.2

Lower Limit of External Static Pressure(mmAq(Pa))

Upper Limit of External Static Pressure(mmAq(Pa))

8(78)

16(157)

6(59)

10(98)

8(78)

14(137)

6(59)

10(98)

8(78)

12(118)

6(59)

10(98)

Ceiling Concealed Duct(High Static) _ 25

Indoor Units

12k

24k

Standard Set value ESP(mmAq(Pa))

Mode


7. External Static Pressure (E.S.P) & Air Flow ARNU48GBRA2 Capacity

Standard Set value ESP(mmAq(Pa))

Mode High (factory set)

48k Standard

HI Mid Low HI Mid Low

116 111 106 106 101 96

14(137) 10(98)

CMM 44.8 40.6 33.3 44.4 39.5 33.5

Lower Limit of External Static Pressure(mmAq(Pa))

Upper Limit of External Static Pressure(mmAq(Pa))

10(98)

20(196)

7(67)

14(137)

URNU76GB8A2, URNU96GB8A2

Indoor Units

Capacity

76k

High (factory set) Standard

96k

Standard Set value ESP(mmAq(Pa))

Mode

High (factory set) Standard

HI Mid Low HI Mid Low HI Mid Low HI Mid Low

102 98 98 86 83 83 105 102 102 94 89 89

22(216) 15(147) 22(216) 15(147)

26 _ Ceiling Concealed Duct(High Static)

CMM 60 50 50 64 50 50 72 64 64 76 64 64

Lower Limit of External Static Pressure(mmAq(Pa))

Upper Limit of External Static Pressure(mmAq(Pa))

12(118)

25(245)

12(118)

25(245)

12(118)

25(245)

12(118)

25(245)


8. Electric Characteristics Units

Power Supply

Input(W)

kW

FLA

1.32

15

0.118

1.06

150

150

BH

1.32

15

0.118

1.06

150

150

ARNU12GBHA2

BH

1.32

15

0.118

1.06

150

150

ARNU15GBHA2

BH

1.32

15

0.118

1.06

150

150

ARNU18GBHA2

BH

1.32

15

0.118

1.06

150

150

ARNU24GBHA2

BH

Max:264

1.32

15

0.118

1.06

150

150

ARNU28GBGA2

BG

Min:198

3.31

15

0.39

2.65

450

450

ARNU36GBGA2

BG

3.31

15

0.39

2.65

450

450

ARNU42GBGA2

BG

3.31

15

0.39

2.65

450

450

ARNU48GBRA2

BR

3.45

15

0.39

2.76

450

450

URNU76GB8A2

B8

6.47

15

0.75

5.18

800

800

URNU96GB8A2

B8

6.47

15

0.75

5.18

800

800

ARNU07GBHA2

BH

1.32

15

0.118

1.06

150

150

ARNU09GBHA2

BH

1.32

15

0.118

1.06

150

150

ARNU12GBHA2

BH

1.32

15

0.118

1.06

150

150

ARNU15GBHA2

BH

1.32

15

0.118

1.06

150

150

ARNU18GBHA2

BH

1.32

15

0.118

1.06

150

150

ARNU24GBHA2

BH

Max:242

1.32

15

0.118

1.06

150

150

ARNU28GBGA2

BG

Min:198

3.31

15

0.39

2.65

450

450

ARNU36GBGA2

BG

3.31

15

0.39

2.65

450

450

ARNU42GBGA2

BG

3.31

15

0.39

2.65

450

450

ARNU48GBRA2

BR

3.45

15

0.39

2.76

450

450

URNU76GB8A2

B8

6.47

15

0.75

5.18

800

800

URNU96GB8A2

B8

6.47

15

0.75

5.18

800

800

Type

ARNU07GBHA2

BH

ARNU09GBHA2

Symbols: MCA : Min, Circuit Amps(A) MFA : Max. Fuse Amps(see note 5) kW : Fan Motor Rated Output(kW) FLA : Full Load Amps(A) IFM : Indoor Fan Motor

Hz

50

60

Volts

220-240

220

Cooling Heating

Note : 1. Voltage range Units are suitable for use on electrical systems where voltage supplied to unit terminals is not below or above the listed range limits, 2. Maximum allowable voltage unbalance between phases is 2% 3. MCA/MFA MCA=1.25 x FLA MFA≤ 4 x FLA (Next lower standard fuse rating. Min. 15A) 4. Select wire size based on the MCA 5. Instead of fuse, use Circuit Breaker.

Ceiling Concealed Duct(High Static) _ 27

Indoor Units

MFA

Model

Voltage Range MCA

IFM


9. Sound Levels Overall

DISCHARGE

SUCTION

DUCT

DUCT 1.5m

2m

Indoor Units

Model

1m 1m

Sound Level dB(A)

Notes: - Sound measured at 1.5m away from the center of the unit. - Data is valid at free field condition - Data is valid at nominal operating condition - Reference accoustic pressure OdB = 20μPa - Sound level will vary depending on a range of factors such as the construction(acoustic absorption coefficient) of particular room in which the equipment is installed.

Sound Level dB(A)

Model

ARNU07GBHA2

H 34

M 33

L 32

ARNU28GBGA2

H 44

M 42

L 40

ARNU09GBHA2

35

34

33

ARNU36GBGA2

46

44

42

ARNU12GBHA2

37

35

34

ARNU42GBGA2

48

46

45

ARNU15GBHA2

39

38

37

ARNU48GBRA2

45

43

41

ARNU18GBHA2

42.5

41

37

URNU76GB8A2

50

48

48

ARNU24GBHA2

45

43

41

URNU96GB8A2

52

50

50

Sound Pressure Level ARNU09GBHA2

ARNU12GBHA2 80

70

70

70

NC-65

60

NC-60 NC-55

50

NC-50 NC-45

40

NC-40 NC-35

30

NC-30 20

10

NC-25 Approximate Hearing Threshold 63

NC-60 NC-55

50

NC-50 NC-45

40

NC-40 NC-35

30

NC-30 20

NC-20

NC-15 125 250 500 1000 2000 4000 8000 Octave Band Center Frequency (Hz)

NC-65

60

10

NC-25 Approximate Hearing Threshold 63

NC-65

60

NC-60 NC-55

50

NC-50 NC-45

40

NC-40 NC-35

30

NC-30 20

NC-20

NC-15 125 250 500 1000 2000 4000 8000 Octave Band Center Frequency (Hz)

28 _ Ceiling Concealed Duct(High Static)

Octave Band Sound Pressure Level (dB re 20μPa )

80

Octave Band Sound Pressure Level (dB re 20μPa )

Octave Band Sound Pressure Level (dB re 20μPa )

ARNU07GBHA2 80

10

NC-25 Approximate Hearing Threshold 63

NC-20

NC-15 125 250 500 1000 2000 4000 8000 Octave Band Center Frequency (Hz)


9. Sound Levels ARNU15GBHA2

ARNU18GBHA2

NC-60 NC-55

50

NC-50 NC-45

40

NC-40 NC-35

30

NC-30 NC-25

20 Approximate Hearing Threshold 63

70

250

500

NC-65

60

NC-60 NC-55

50

NC-50 NC-45

40

NC-40 NC-35

30

NC-30 20

NC-20

125

80

NC-15 1000 2000 4000 8000

10

NC-25 Approximate Hearing Threshold 63

NC-50

NC-40

NC-30 20

10

NC-60 NC-55 NC-50 NC-45

40

NC-40 NC-35

30

NC-30 NC-25 Approximate Hearing Threshold 63

250

500

NC-15 1000 2000 4000 8000

NC-60 NC-55

50

NC-50 NC-45

40

NC-40 NC-35

30

NC-30 20

NC-55

50

NC-50 NC-45

40

NC-40 NC-35

30

NC-30 NC-25

20 Approximate Hearing Threshold 63

Octave Band Sound Pressure Level (dB re 20μPa )

NC-60

125

250

500

Octave Band Center Frequency (Hz)

500

NC-15 1000 2000 4000 8000

NC-60 NC-55

50

NC-50 NC-45

40

NC-40 NC-35

30

NC-30

10

NC-25 Approximate Hearing Threshold 63

125

NC-60 NC-55

50

NC-50 NC-45

40

NC-40 NC-35

30

NC-30 20

10

NC-25 Approximate Hearing Threshold 63

125

250

500

Octave Band Center Frequency (Hz)

500

NC-15 1000 2000 4000 8000

70

NC-65

60

NC-60 NC-55

50

NC-50 NC-45

40

NC-40 NC-35

30

NC-30 NC-25

20

NC-20 NC-15 1000 2000 4000 8000

250

URNU96GB8A2

80

NC-65

60

NC-20

Octave Band Center Frequency (Hz)

URNU76GB8A2

70

NC-20 NC-15 1000 2000 4000 8000

250

NC-65

60

NC-20

125

80

NC-65

60

NC-15 1000 2000 4000 8000

70

Octave Band Center Frequency (Hz)

ARNU48GBRA2

500

20

NC-25 Approximate Hearing Threshold 63

80

250

ARNU42GBGA2

NC-65

Octave Band Center Frequency (Hz)

70

125

80

60

10

NC-20

Octave Band Center Frequency (Hz)

70

NC-20

125

NC-25 Approximate Hearing Threshold 63

Octave Band Sound Pressure Level (dB re 20μPa )

NC-65

50

NC-35

30

Octave Band Sound Pressure Level (dB re 20μPa )

70

60

NC-45

40

ARNU36GBGA2 Octave Band Sound Pressure Level (dB re 20μPa )

Octave Band Sound Pressure Level (dB re 20μPa )

500

NC-55

50

80

20

Octave Band Sound Pressure Level (dB re 20μPa )

NC-60

Indoor Units

ARNU28GBGA2

10

250

NC-15 1000 2000 4000 8000

NC-65

60

Octave Band Center Frequency (Hz)

80

10

70

NC-20

125

Octave Band Center Frequency (Hz)

Octave Band Sound Pressure Level (dB re 20μPa )

NC-65

60

Octave Band Sound Pressure Level (dB re 20μPa )

Octave Band Sound Pressure Level (dB re 20μPa )

70

10

ARNU24GBHA2

80

80

10

Approximate Hearing Threshold 63

NC-20

125

250

500

NC-15 1000 2000 4000 8000

Octave Band Center Frequency (Hz)

Ceiling Concealed Duct(High Static) _ 29


10. Installation • Please read this instruction sheet completely before installing the product. • When the power cord is damaged, replacement work shall be performed by authorized personnel only. • Installation work must be performed in accordance with the national wiring standards by authorized personnel only.

Air outlet vents

Air filters

Air intake vents TEMP

Indoor Units

Wired LCD Remote Control

Remote Controller

Required Parts

Required Tools

• Connecting cable • Pipes: Gas side Liquid side • Hanging Bolt (W 3/8 or M10 length 650mm) • Insulated drain hose • Additional Drain hose

• Level • Screw driver • Electric drill • Hole core drill • Flaring Tool set • Torque Wrenches • Hexagonal Wrench • Gas-leak detector • Thermometer

10.1 Selection of the best location Install the air conditioner in the location that satisfies the following conditions. • The place shall easily bear a load exceeding four times the indoor unitʼs weight. • The place shall be able to inspect the unit as the figure. • The place where the unit shall be leveled. • The place shall allow easy water drainage.(Suitable dimension “H” is necessary to get a slope to drain as figure.) • The place shall easily connect with the outdoor unit. • The place where the unit is not affected by an electrical noise. • The place where air circulation in the room will be good . • There should not be any heat source or steam near the unit. • The servicing inspection hole in the ceiling should be as large as the product • The selection of the servicing hole should be approved by the customer

30 _ Ceiling Concealed Duct(High Static)

[Inspection Hole Standard] Number of Inspection hole

Distance between False ceiling & Actual ceiling

1

More than 100cm

2

20cm to 100cm

Hole size should be more than the size of IDU.

Less than 20cm

Remarks Sufficient space in the ceiling for servicing. Insufficient space. Difficult for servicing Minimum height for motor replacement.


10. Installation 10.2 Ceiling dimension and hanging bolt location

BH/BG/BR Chassis

C E

■ Installation of Unit Install the unit above the ceiling correctly.

A B

CASE 1

D

POSITION OF SUSPENSION BOLT

F

(G)

I

• Apply a joint-canvas between the unit and duct to absorb unnecessary vibration. • Apply a filter Accessory at air return hole. • Refer to the Dimensions. (Unit:mm) Dimension

B

C

D

E

F

(G)

H

I

932

882

355

47

450

30

87

750

158

BG

1232

1182

355

47

450

30

87

830

186

BR

1282 1230

477

56

590

30

H

BH

Drainage hole

Indoor Units

A Chassis

B8 Chassis

120 1006 294

(Unit:mm) Dimension

A

B

C

D

E

F

G

H

I

J

K

L

Chassis

B8

1680 1565 1160 330 460 580 700 1400 1635 390 445 15

• Install the unit leaning to a drainage hole side as a figure for easy water drainage.

CASE 2 POSITION OF CONSOLE BOLT • A place where the unit will be leveled and that can support the weight of the unit. • A place where the unit can withstand its vibration. • A place where service can be easily performed.

M10 Nut

X4

M10 washer

X4

M10 washer

X4

M10 Nut

X8

Ceiling Concealed Duct(High Static) _ 31


10. Installation NOTE: • Throughly study the following installation locations: 1. In such places as restaurants and kitchens, considerable amount of oil steam and flour adhere to the fan, the fin of the heat exchanger, resulting in heat exchange reduction, spraying, dispersing of water drops, etc. In these cases, take the following actions: • Make sure that the ventilation fan for smoke-collecting hood on a cooking table has sufficient capacity so that it draws oily steam which should not flow into the suction of the air conditioner. • Make enough distance from a cooking room to install the air conditioner in such a place where it may not suck in oil steam. 2. Avoid installing air conditioner in such circumstances where cutting oil mist or iron powder is in suspension in factories, etc. 3. Avoid places where inflammable gas is generated, flows in, is stored or vented. 4. Avoid places where sulfurous acid gas or corrosive gas is generated. 5. Avoid places near high frequency generators. • Select and mark the position for fixing bolts. • Drill the hole for set anchor on the face of ceiling.

• Insert the set anchor and washer onto the suspension bolts for locking the suspension bolts on the ceiling. • Mount the suspension bolts to the set anchor firmly. • Secure the installation plates onto the suspension bolts (adjust level roughly) using nuts, washers and spring washers.

Indoor Units

Old building

New building

1 Set anchor 2 Plate washer 3 Spring washer

CAUTION

4 Nut 5 Suspension bolts

Tighten the nut and bolt to prevent unit falling.

10.3 Connecting Cables between Indoor Unit and Outdoor Unit Connect the wires to the terminals on the control board individually according to the outdoor unit connection. • Ensure that the color of the wires of outdoor unit and the terminal No. are the same as those of indoor unit respectively [Multi V III Heat Pump Model]

Terminal Block Indoor 1(L)

2(N)

3

SODU B

IDU B

SODU A

IDU A

INT B

INT A

4

INDOOR POWER INPUT

[Except Multi VIII Heat Pump Model]

Terminal Block Indoor 1(L)

2(N)

3

SODU

4

B

A

INTERNET DRY1 DRY2 GND 12V

IDU -

-

B

A

-

-

-

-

Outdoor Unit

INDOOR POWER INPUT

WARNING Make sure that the screws of the terminal are not loose.

Clamping of cables 1) Arrange 2 power cables on the control panel. 2) First, fasten the steel clamp with a screw to the inner boss of control panel. 3) For the cooling model, fix the other side of the clamp with a screw strongly. For the heat pump model, put the 0.75mm2 cable(thinner cable) on the clamp and tighten it with a plastic clamp to the other boss of the control panel.

32 _ Ceiling Concealed Duct(High Static)


10. Installation THERMAL INSULATION

All thermal insulation must comply with local requirement.

INDOOR UNIT BH/BG/BR Chassis

Union for liquid pipe

Thermal insulator for refrigerant pipe (Local supply) Thermal insulator for piping(Local supply)

Refrigerant pipe and thermal insulator(Local supply) Hose clamp for thermal insulator (Local supply)

B8

Thermal insulator for refrigerant pipe (Local supply) Union for gas pipe

Overlap with thermal insulator for piping. Hose clamp for thermal insulator(Local supply) Make sure that there is no clearance here.

Union for gas pipe

Hose crip for thermal insulator (Local supply) Refrigerant pipe and therma insulator(Local supply)

Union for liquid pipe

10.4 Checking the Drainage 1) Checking the Drainage

BH/BG/BR Chassis

1. Remove the Air Filter.

B8

2. Check the drainage. • Spray one or two glasses of water on the evaporator. • Ensure that water flows through drain hose of indoor unit without any leakage.

Ceiling Concealed Duct(High Static) _ 33

Indoor Units

Thermal insulator for refrigerant pipe (Local supply)


10. Installation 10.5 Indoor Unit Drain Piping • Drain piping must have down-slope (1/50 to 1/100): be sure not to provide up-and-down slope to prevent reversal flow. • During drain piping connection, be careful not to exert extra force on the drain port on the indoor unit. • The outside diameter of the drain connection on the indoor unit is 32mm.

Upward routing not allowed

Pipe clamp Indoor unit

Maintenance drain port

Piping material: Polyvinyl chloride pipe inner diometes Ø 25mm and pipe fittings • Be sure to install heat insulation on the drain piping.

1/50~1/100 MAX 700mm

Heat insulation material: Polyethylene foam with thickness more than 8 mm.

The air conditioner uses a drain pump to drain water. Use the following procedure to test the drain pump operation: Feed water

Drain Pump

Flexible drain hose (accessory)

• Connect the main drain pipe to the exterior and leave it provisionally until the test comes to an end. Main drain pipe • Feed water to the flexible drain hose and check the piping for leakage. Drain • Be sure to check the drain pump for normal operation and port Glue the joint noise when electrical wiring is complete. Drain hose connection Use the clip (accessory) • When the test is complete, connect the flexible drain hose to the drain port on the indoor unit.

Drain pan

CAUTION The supplied flexible drain hose should not be strained. A strained hose may cause leakage of water.

Max 300mm

Hanger distance 1~15m

Hanger Bracket 1/50~1/100 slope

Metal clamp Flexible drain hose

Max 700mm

Indoor Units

Drain test

Insulation

Flexible drain hose Flexible drain hose Flexible drain hose

34 _ Ceiling Concealed Duct(High Static)


10. Installation 10.6 Ground drain piping a) It is standard work practice to make connections to the main pipe from above. The pipe down from the combination should be as large as possible.

Face the vent pipe opening facing downward to keep foreign matter from penetrating the system Face piping downward

b) The pipe work should be kept as short as possible and the number of indoor units per group kept to a minimum.

10.7 Use of an auxiliary drain hose(flexible) a) To connect drain pipe to the drain socket on the indoor unit, an auxiliary flexible drain hose should be used. auxiliary flexible drain hose allows that the drain pipe can be connected to the socket without breaking by excessive strain. Auxiliary drain hose

Thermal insulation (drain pipe area)

Metal clamp

Metal clamp Thermal insulation(bend area) Drain pan

â?ˆ Important points - The drain pipe should be at least equal in size to that of the indoor unit. - The drain pipe is thermally insulated to prevent the formation of condensation inside the pipe. - The drain up mechanism should be fitted before the indoor unit is installed and when the electricity has been connected some water should be added to the drain pan and the drain pump to check and see if it is functioning correctly. - All connections should be secure. (Special care is needed with PVC pipe) - Insulate auxiliary drain hose with thermal insulation band.

Ceiling Concealed Duct(High Static) _ 35

Indoor Units

Vent pipe


10. Installation WIRED REMOTE CONTROLLER INSTALLATION • Since the room temperature sensor is in the remote controller, the remote controller box should be installed in a place away from direct sunlight, high humidity and direct supply of cold air to maintain proper space temperature. Install the remote controller about 5ft(1.5m) above the floor in an area with good air circulation at an average temperature.

Do not install the remote controller where it can be affected by:

Indoor Units

- Drafts, or dead spots behind doors and in corners. - Hot or cold air from ducts. - Radiant heat from sun or appliances. - Concealed pipes and chimneys. - Uncontrolled areas such as an outside wall behind the remote controller. - This remote controller is equipped with a seven segment LED. display. For proper display of the remote controller LED's, the remote controller should be installed properly as shown in Fig.1. (The standard height is 1.2~1.5 m from floor level.)

TEMP

yes

Remote Controller

no

TEMP

Controller Remote

TEMP

Remote Controller

5feet (1.5meters)

no

no

Fig.1 Typical locations for remote controller

36 _ Ceiling Concealed Duct(High Static)


11. Accessories Standard Accessories Name

Drain hose

Clamp metal

Quantity

1 EA

1 EA

Washer for hanging backet 8 EA

Clamp (Tie Wrap)

Insulation for fitting

4 EA

1 SET

(Other)

• Owner's manual • Installation manual Shape

for gas pipe

for liquid pipe

Indoor Units

CAUTION • Use only those accessories (Standard or optional) which have designated specifications.

Ceiling Concealed Duct(High Static) _ 37


Indoor unit Ceiling Concealed Duct(Low Static) 1. List of functions 2. Specifications 3. Dimensions & Gravity point 4. Piping Diagrams 5. Wiring Diagrams 6. Capacity Tables 7. External Static Pressure (E.S.P) & Air Flow 8. Electric Characteristics 9. Sound Levels 10. Installation 11. Accessories


1. List of functions Category

Air flow

Air purifying

Installation

Convenience

Individual control

Special function kit

Air supply outlet Airflow direction control(left & right) Airflow direction control(up & down) Auto swing(left & right) Auto swing(up & down) Airflow steps(fan/cool/heat) Chaos swing Chaos wind(auto wind) Jet cool(Power wind) Swirl wind Deodorizing filter Plasma air purifier Prefilter(washable / anti-fungus) Drain pump E.S.P. control Electric heater(operation) High ceiling operation Hot start Self diagnosis Soft dry operation Auto changeover Auto cleaning Auto operation(artificial intelligence) Auto restart operation Child lock Forced operation Group control Sleep mode Timer(on/off) Timer(weekly) Two thermistor control Wide wired remote controller Deluxe wired remote controller Simple wired remote controller Wired remote controller(for hotel use) Wireless remote controller(simple) Wireless LCD remote control Zone control CTIE Electro thermostat

ARNU07GB1G2, ARNU09GB1G2, ARNU12GB1G2, ARNU15GB1G2, ARNU18GB2G2, ARNU24GB2G2 1 3/3/3 X X O O O X O O O O(Heat recovery) X O(Heat pump or Cooling only) O O O O O O O Accessory Accessory Accessory Accessory X Accessory Accessory -

O : Applied X : Not applied – : No relation Option : Model name & price are different according to options, and assembled in factory with main unit. Accessory : Installed at field, ordered and purchased separately by the corresponding model name, supplied with separate package.

Ceiling Concealed Duct(Low Static) _ 1

Indoor Units

Reliability

Function


2. Specifications Type Model Cooling Capacity

Heating Capacity

Unit kW kcal/h Btu/h kW kcal/h Btu/h

Casing Dimensions(WxDxH) Body

mm inch

Rows x Columns x FPI Face Area m3 Type Motor Output x Number W Running Current A Air Flow Rate(H / M / L) CMM (High Mode-factory set) cfm Fan External Static Pressure mmAq(Pa) Air Flow Rate(H / M / L) CMM (Standard Mode) cfm External Static Pressure mmAq(Pa) Drive Motor type Temperature Control Sound Absorbing Thermal Insulation Material Air Filter Safety Device Liquid Side mm(inch) Pipe Connections Gas Side mm(inch) Drain Pipe(Internal Dia.) mm(inch) Net Weight kg(lbs) Noise Level(Sound Press, 1.5m, H / M / L) dB(A)

Indoor Units

Coil

Power Supply Refrigerant Control Power cable Transmission cable

Ø, V, Hz mm2 mm2

Ceiling Concealed Duct (Low Static) ARNU07GB1G2 ARNU09GB1G2 ARNU12GB1G2 2.2 2.8 3.6 1,900 2,400 3,100 7,500 9,600 12,300 2.5 3.2 4.0 2,200 2,800 3,400 8,500 10,900 13,600 Galvanized Steel Plate Galvanized Steel Plate Galvanized Steel Plate 820 x 575 x 190 820 x 575 x 190 820 x 575 x 190 32.3 x 21.7 x 7.5 32.3 x 21.7 x 7.5 32.3 x 21.7 x 7.5 2 x 11 x 21 2 x 11 x 21 2 x 11 x 21 0.16 0.16 0.16 Sirocco Fan Sirocco Fan Sirocco Fan 28 28 28 0.15 0.15 0.15 8.5 / 7.5 / 6.5 9.5 / 8.5 / 7.5 10.5 / 9.5 / 8.5 300 / 265 / 229 335 / 300 / 265 371 / 335 / 300 2(20) 2(20) 2(20) 8.5 / 7.5 / 6.5 9.5 / 8.5 / 7.5 10.5 / 9.5 / 8.5 300 / 265 / 229 335 / 300 / 265 371 / 335 / 300 0(0) 0(0) 0(0) Direct Direct Direct BLDC BLDC BLDC Microprocessor, Thermostat for cooling and heating Microprocessor, Thermostat for cooling and heating Microprocessor, Thermostat for cooling and heating Foamed polystrene Foamed polystrene Foamed polystrene Fuse Fuse Fuser �Ø6.35(1/4) Ø6.35(1/4) Ø6.35(1/4) Ø12.7(1/2) Ø12.7(1/2) Ø12.7(1/2) 25.4(1) 25.4(1) 25.4(1) 21(46.3) 21(46.3) 21(46.3) 33 / 32 / 29 34 / 33 / 32 35 / 34 / 33 1, 220-240, 50 1, 220-240, 50 1, 220-240, 50 1, 220, 60 1, 220, 60 1, 220, 60 EEV EEV EEV CV1.5 x 3C CV1.5 x 3C CV1.5 x 3C CVV-SB 1.0~1.5 x 2C CVV-SB 1.0~1.5 x 2C CVV-SB 1.0~1.5 x 2C

Notes:1. Capacities are based on the following conditions: Cooling • Indoor temp. 27°C[80.6°F]DB/ 19°C[66.2°F]WB • Outdoor temp. 35°C[95°F]DB/ 24°C[75.2°F]WB • Interconnecting Piping Length 7.5m • Level Difference of Zero Heating • Indoor temp. 20°C[68°F]DB/ 15°C[59°F]WB • Outdoor temp. 7°C[44.6°F]DB/ 6°C[42.8°F]WB • Interconnecting Piping Length 7.5m • Level Difference of Zero 2. Capacities are net capacities 3. Due to our policy of innovation some specifications may be changed without prior notification 4. To be added for more available Models 5. EEV : Electronic Expansion Valve 6. Noise Level is Standard Mode (for actual High Mode(factory set) condition, Noise Level may exceed the standard level by 1.5dB(A)) 7. Anechoic chamber conversion value is measured at 1.5 m downward from unit centre. The values depends on the ambient conditions and values are normally higher in actual operation.

2 _ Ceiling Concealed Duct(Low Static)

Conversion Formula kcal/h= kW x 860 Btu/h = kW x 3412 cfm = m3/min x 35.3 l/s = CMM x 1000/60


2. Specifications Type Model

Ceiling Concealed Duct (Low Static) ARNU15GB1G2 ARNU18GB2G2 ARNU24GB2G2 4.5 5.6 7.1 Cooling Capacity 3,900 4,800 6,100 15,400 19,100 24,200 5.0 6.3 8.0 Heating Capacity 4,300 5,400 6,900 17,100 21,500 27,300 Casing Galvanized Steel Plate Galvanized Steel Plate Galvanized Steel Plate mm 820 x 575 x 190 1,100 x 575 x 190 1,100 x 575 x 190 Dimensions(WxDxH) Body inch 32.3 x 21.7 x 7.5 43.3 x 21.7 x 7.5 43.3 x 21.7 x 7.5 Rows x Columns x FPI 2 x 11 x 21 3 x 10 x 18 3 x 10 x 18 Coil Face Area m3 0.16 0.23 0.23 Type Sirocco Fan Sirocco Fan Sirocco Fan Motor Output x Number W 28 76 76 Running Current A 0.15 0.38 0.38 Air Flow Rate(H / M / L) CMM 11.5 / 10.5 / 9.5 16.0 / 14.0 / 12.0 19.0 / 17.0 / 15.0 (High Mode-factory set) cfm 406 / 371 / 335 565 / 494 / 424 671 / 600 / 530 Fan External Static Pressure mmAq(Pa) 2(20) 2(20) 2(20) Air Flow Rate(H / M / L) CMM 11.5 / 10.5 / 9.5 16.0 / 14.0 / 12.0 19.0 / 17.0 / 15.0 (Standard Mode) cfm 406 / 371 / 335 565 / 494 / 424 671 / 600 / 530 External Static Pressure mmAq(Pa) 0(0) 0(0) 0(0) Drive Direct Direct Direct Motor type BLDC BLDC BLDC Temperature Control Microprocessor, Thermostat for cooling and heating Microprocessor, Thermostat for cooling and heating Microprocessor, Thermostat for cooling and heating Sound Absorbing Thermal Insulation Material Foamed polystrene Foamed polystrene Foamed polystrene Air Filter Safety Device Fuse Fuse Fuse Liquid Side mm(inch) Ø6.35(1/4) Ø6.35(1/4) Ø9.52(3/8) Pipe Connections Gas Side mm(inch) Ø12.7(1/2) Ø12.7(1/2) Ø15.88(5/8) Drain Pipe(Internal Dia.) mm(inch) 25.4(1) 25.4(1) 25.4(1) Net Weight kg(lbs) 21(46.3) 26(57.3) 26(57.3) Noise Level(Sound Press, 1.5m, H / M / L) dB(A) 38 / 37 / 36 40 / 37 / 34 43 / 40 / 37 1, 220-240, 50 1, 220-240, 50 1, 220-240, 50 Power Supply Ø, V, Hz 1, 220, 60 1, 220, 60 1, 220, 60 Refrigerant Control EEV EEV EEV Power cable mm2 CV1.5 x 3C CV1.5 x 3C CV1.5 x 3C Transmission cable mm2 CVV-SB 1.0~1.5 x 2C CVV-SB 1.0~1.5 x 2C CVV-SB 1.0~1.5 x 2C Unit kW kcal/h Btu/h kW kcal/h Btu/h

Conversion Formula kcal/h= kW x 860 Btu/h = kW x 3412 cfm = m3/min x 35.3 l/s = CMM x 1000/60

Ceiling Concealed Duct(Low Static) _ 3

Indoor Units

Notes:1. Capacities are based on the following conditions: Cooling • Indoor temp. 27°C[80.6°F]DB/ 19°C[66.2°F]WB • Outdoor temp. 35°C[95°F]DB/ 24°C[75.2°F]WB • Interconnecting Piping Length 7.5m • Level Difference of Zero Heating • Indoor temp. 20°C[68°F]DB/ 15°C[59°F]WB • Outdoor temp. 7°C[44.6°F]DB/ 6°C[42.8°F]WB • Interconnecting Piping Length 7.5m • Level Difference of Zero 2. Capacities are net capacities 3. Due to our policy of innovation some specifications may be changed without prior notification 4. To be added for more available Models 5. EEV : Electronic Expansion Valve 6. Noise Level is Standard Mode (for actual High Mode(factory set) condition, Noise Level may exceed the standard level by 1.5dB(A)) 7. Anechoic chamber conversion value is measured at 1.5 m downward from unit centre. The values depends on the ambient conditions and values are normally higher in actual operation.


575

18

154

383

18

B1 : 448 B2 : 573

D

B A

C

6

5 13

161 14 B1 : 186 B2 : 175 B1 : 73 B2 : 81

4 _ Ceiling Concealed Duct(Low Static) 4

3

216 24

65 60

190

Gas pipe connection Drain pipe connection Power supply connection Air discharge Air suction

2 3 4 5 6

1072

794

D

Descripition

(unit : mm)

1131

856

C

Unit size(7k,9k,12k,18k):ø6.35 Unit size(24k):ø9.52 Unit size(7k,9k,12k,18k):ø12.7 Unit size(24k):ø15.88

1008

728

B

(unit: mm)

Gravity point

CHASSIS CODE: B1/B2

2. Unit shall be grounded in accordance with the local regulations or applicable national codes.

1. Unit should be installed in compliance with the installation manual in the product box.

Note

Liquid pipe connection

Name

1100

820

1

Number

ARNU18GB2G2 ARNU24GB2G2

76, Seongsan-dong, Changwon City, Gyeongnam, 641-713, Korea

2

1

A

ARNU07GB1G2 ARNU09GB1G2 ARNU12GB1G2 ARNU15GB1G2 ARNU18GB2G2 ARNU24GB2G2

Ceiling Concealed Duct (Low Static)

ARNU07GB1G2 ARNU09GB1G2 ARNU12GB1G2 ARNU15GB1G2

Indoor Units

3. Dimensions & Gravity point

277

190


4. Piping Diagrams

Heat Exchanger

EEV Filter

Th3

:Cooling :Heating

Th2 Sirocco Fan

Th1

Filter

lndoor unit

[Unit: mm(inch)]

MODEL

GAS

LIQUID

ARNU07GB1G2

Ø12.7(1/2)

Ø6.35(1/4)

ARNU09GB1G2

Ø12.7(1/2)

Ø6.35(1/4)

ARNU12GB1G2

Ø12.7(1/2)

Ø6.35(1/4)

ARNU15GB1G2

Ø12.7(1/2)

Ø6.35(1/4)

ARNU18GB2G2

Ø12.7(1/2)

Ø6.35(1/4)

ARNU24GB2G2

Ø15.88(5/8)

Ø9.52(3/8)

LOC.

Description

Th1

Room thermistor

Th2

Pipe in thermistor

Th3

Pipe out thermistor

Ceiling Concealed Duct(Low Static) _ 5

Indoor Units

Refrigerant pipe connection port diameter


5. Wiring Diagrams

Indoor Units

B1/B2 Chassis

CONNECTOR NUMBER CN-MOTOR1 CN-MOTOR2 CN-PIPE/OUT CN-PIPE/IN CN-ROOM CN-REMO CN-FLOAT CN-EEV CN-D/PUMP CN-OPTION CN-COM CN-D/PUMP CN-POWER CN-ZONE CN-DISPLAY CN-CC

SPEC. Fan motor output Fan motor output Discharge pipe sensor Suction pipe sensor Room sensor Remote controller Float switch input EEV output Drain pump output Option PWB. Communication Drain pump output AC power supply Zone Controller RF Remote controller Dry contact

DESCRIPTION Motor output of BLDC Motor output of BLDC Pipe out thermistor Pipe in thermistor Room thermistor Remote control line Float switch sensing EEV control output AC output for drain pump Communication between main and option Communication between indoor and outdoor AC output for drain pump AC power line input for indoor controller Zone control line RF remote control line Dry contact line

Dip Switch Setting SW3 GROUP

Off Master

On Slave

SW4

DRY CONTACT

Variable

Auto

SW5

EXTRA 1

Off

On

Remarks Group Control setting using Wired Remote Controller Old Dry Contact Mode Setting 1. Variable : Auto/Manual Mode can be chosen by Wide wired remote controller or Wireless remote controller (When shipped from Factory → Manual Mode) 2. Auto : For Dry Contact, it is always Auto mode. 1. Duct model -. OFF : Default(not operate continuosly ) -. ON : Fan operate continuosly 2. Cassette Model : No Function 3. Ceiling Suspended Model -. OFF : Ceiling(default) -. ON : Floor

CAUTION For Multi V Model, Dip Switch 1,2,6,7,8 must be set OFF That dip switch is used for the other model.

6 _ Ceiling Concealed Duct(Low Static)


6. Capacity Tables 6.1 Cooling Capacity

Capacity Index

2.2

3.6

10 12 14 16 18 20 21 23 25 27 29 31 33 35 37 39 10 12 14 16 18 20 21 23 25 27 29 31 33 35 37 39 10 12 14 16 18 20 21 23 25 27 29 31 33 35 37 39

Notes: TC: Total Capacity(kW)

20 14 TC SHC kW kW

23 16 TC SHC kW kW

Indoor air temp. (DB/WB, °C) 26 27 28 18 19 20 TC SHC TC SHC TC SHC kW kW kW kW kW kW

1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4

1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9

2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4

1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2

1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4

1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6

2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6

1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6

2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.2 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 2.9 2.9 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.7 3.7

1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.6 1.6 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.0 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.6 2.6

30 22 TC SHC kW kW 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.5 2.5 2.5 2.4 2.4 2.3 2.3 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.3 3.2 3.2 3.1 3.1 3.0 3.0 2.9 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.2 4.1 4.1 4.0 4.0 3.9 3.8 3.7

1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.6 1.6 1.6 1.6 1.5 1.5 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.1 2.1 2.1 2.0 2.0 1.9 1.9 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.7 2.7 2.6 2.6 2.6 2.5 2.5

32 24 TC SHC kW kW 2.9 2.9 2.8 2.8 2.7 2.7 2.7 2.6 2.6 2.6 2.5 2.5 2.5 2.4 2.4 2.3 3.7 3.6 3.6 3.5 3.5 3.4 3.4 3.4 3.3 3.3 3.2 3.2 3.1 3.1 3.0 3.0 4.7 4.7 4.6 4.6 4.5 4.4 4.4 4.3 4.3 4.2 4.2 4.1 4.0 4.0 3.9 3.8

1.7 1.7 1.7 1.6 1.6 1.6 1.6 1.6 1.5 1.5 1.5 1.5 1.5 1.4 1.4 1.4 2.2 2.1 2.1 2.1 2.1 2.0 2.0 2.0 2.0 1.9 1.9 1.9 1.9 1.8 1.8 1.8 2.8 2.8 2.7 2.7 2.7 2.6 2.6 2.6 2.5 2.5 2.5 2.4 2.4 2.3 2.3 2.3

SHC: Sensible Heat Capacity(kW)

Ceiling Concealed Duct(Low Static) _ 7

Indoor Units

2.8

Outdoor air temp. (DB, °C)

Cooling capacity


6. Capacity Tables Cooling capacity

Capacity Index

Indoor Units

4.5

5.6

7.1

Outdoor air temp. (DB, °C) 10 12 14 16 18 20 21 23 25 27 29 31 33 35 37 39 10 12 14 16 18 20 21 23 25 27 29 31 33 35 37 39 10 12 14 16 18 20 21 23 25 27 29 31 33 35 37 39

Notes: TC: Total Capacity(kW)

20 14 TC SHC kW kW

23 16 TC SHC kW kW

Indoor air temp. (DB/WB, °C) 26 27 28 18 19 20 TC SHC TC SHC TC SHC kW kW kW kW kW kW

3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8

3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7

4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6

2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1

3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6

3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0

4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1

3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0

SHC: Sensible Heat Capacity(kW)

8 _ Ceiling Concealed Duct(Low Static)

4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 5.8 5.7 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.4 7.2

3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.0 3.9 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.1 5.0

30 22 TC SHC kW kW 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 6.7 6.7 6.7 6.7 6.7 6.7 6.7 6.7 6.6 6.4 6.4 6.3 6.2 6.0 5.9 5.8 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.4 8.2 8.1 8.0 7.8 7.7 7.5 7.4

3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.2 4.1 4.1 4.0 3.9 3.9 3.8 3.7 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.2 5.2 5.1 5.0 4.9 4.8 4.7

32 24 TC SHC kW kW 5.9 5.8 5.8 5.7 5.6 5.5 5.5 5.4 5.3 5.3 5.2 5.1 5.0 5.0 4.9 4.8 7.4 7.3 7.2 7.1 7.0 6.9 6.8 6.7 6.6 6.6 6.5 6.4 6.3 6.2 6.1 6.0 9.3 9.2 9.1 9.0 8.8 8.7 8.7 8.5 8.4 8.3 8.2 8.1 7.9 7.8 7.7 7.6

3.5 3.5 3.4 3.4 3.3 3.3 3.3 3.2 3.2 3.1 3.1 3.0 3.0 2.9 2.9 2.8 4.2 4.2 4.1 4.1 4.0 4.0 3.9 3.9 3.8 3.8 3.7 3.7 3.6 3.5 3.5 3.4 5.4 5.3 5.2 5.2 5.1 5.0 5.0 4.9 4.8 4.8 4.7 4.6 4.6 4.5 4.4 4.4


6. Capacity Tables 6.2 Heating Capacity Outdoor air temp. Capacity Index DB(°C) WB(°C)

Heating capacity Indoor air temp. (DB, °C)

16

18

20

21

22

24

TC

TC

TC

TC

TC

TC

kW

kW

kW

kW

kW

2.2

-20.0 -19.0 -17.0 -15.0 -13.0 -11.0 -10.0 -9.1 -7.6 -5.6 -3.7 -0.7 2.2 4.1 6.0 7.9 9.8 11.8 13.7

1.7 1.7 1.8 1.9 2.0 2.1 2.2 2.2 2.3 2.4 2.5 2.6 2.8 2.8 2.9 2.9 2.9 2.9 2.9

1.7 1.7 1.8 1.9 2.0 2.1 2.2 2.2 2.3 2.4 2.5 2.6 2.7 2.7 2.7 2.7 2.7 2.7 2.7

1.7 1.7 1.8 1.7 1.8 1.9 1.9 2.0 2.0 2.1 2.2 2.3 2.4 2.5 2.5 2.5 2.5 2.5 2.5

1.7 1.7 1.8 1.9 2.0 2.1 2.2 2.2 2.2 2.3 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4

1.7 1.7 1.8 1.9 2.0 2.1 2.2 2.2 2.2 2.3 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4

1.7 1.7 1.8 1.9 2.0 2.1 2.1 2.1 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2

2.8

-19.8 -18.8 -16.7 -14.7 -12.6 -10.5 -9.5 -8.5 -7.0 -5.0 -3.0 0.0 3.0 5.0 7.0 9.0 11.0 13.0 15.0

-20.0 -19.0 -17.0 -15.0 -13.0 -11.0 -10.0 -9.1 -7.6 -5.6 -3.7 -0.7 2.2 4.1 6.0 7.9 9.8 11.8 13.7

2.1 2.2 2.3 2.5 2.6 2.7 2.8 2.8 2.9 3.0 3.2 3.4 3.6 3.6 3.7 3.7 3.7 3.7 3.7

2.1 2.2 2.3 2.4 2.6 2.7 2.8 2.8 2.9 3.0 3.2 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4

2.1 2.2 2.3 2.2 2.3 2.4 2.5 2.5 2.6 2.7 2.8 3.0 3.1 3.2 3.2 3.2 3.2 3.2 3.2

2.1 2.2 2.3 2.4 2.6 2.7 2.8 2.8 2.8 3.0 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1

2.1 2.2 2.3 2.4 2.6 2.7 2.8 2.8 2.8 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0

2.1 2.2 2.3 2.4 2.6 2.7 2.7 2.7 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8

3.6

-19.8 -18.8 -16.7 -14.7 -12.6 -10.5 -9.5 -8.5 -7.0 -5.0 -3.0 0.0 3.0 5.0 7.0 9.0 11.0 13.0 15.0

-20.0 -19.0 -17.0 -15.0 -13.0 -11.0 -10.0 -9.1 -7.6 -5.6 -3.7 -0.7 2.2 4.1 6.0 7.9 9.8 11.8 13.7

2.7 2.8 2.9 3.1 3.2 3.4 3.4 3.5 3.6 3.8 4.0 4.2 4.4 4.5 4.6 4.6 4.6 4.6 4.6

2.7 2.8 2.9 3.0 3.2 3.4 3.4 3.5 3.6 3.8 4.0 4.2 4.3 4.3 4.3 4.3 4.3 4.3 4.3

2.7 2.8 2.9 2.7 2.9 3.0 3.1 3.2 3.3 3.4 3.5 3.7 3.9 4.0 4.0 4.0 4.0 4.0 4.0

2.6 2.8 2.9 3.0 3.2 3.4 3.4 3.5 3.6 3.7 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9

2.6 2.7 2.9 3.0 3.2 3.4 3.4 3.5 3.6 3.7 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8

2.6 2.7 2.9 3.0 3.2 3.4 3.4 3.4 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5

Notes: TC: Total Capacity(kW)

Ceiling Concealed Duct(Low Static) _ 9

Indoor Units

kW -19.8 -18.8 -16.7 -14.7 -12.6 -10.5 -9.5 -8.5 -7.0 -5.0 -3.0 0.0 3.0 5.0 7.0 9.0 11.0 13.0 15.0


6. Capacity Tables Heating capacity Outdoor air temp. Capacity Index DB(°C) WB(°C)

Indoor Units

4.5

5.6

7.1

Indoor air temp. (DB, °C) 16

18

20

21

22

24

TC

TC

TC

TC

TC

TC

kW

kW

kW

kW

kW

kW

-19.8 -18.8 -16.7 -14.7 -12.6 -10.5 -9.5 -8.5 -7.0 -5.0 -3.0 0.0 3.0 5.0 7.0 9.0 11.0 13.0 15.0 -19.8 -18.8 -16.7 -14.7 -12.6 -10.5 -9.5 -8.5 -7.0 -5.0 -3.0 0.0 3.0 5.0 7.0 9.0 11.0 13.0 15.0

-20.0 -19.0 -17.0 -15.0 -13.0 -11.0 -10.0 -9.1 -7.6 -5.6 -3.7 -0.7 2.2 4.1 6.0 7.9 9.8 11.8 13.7 -20.0 -19.0 -17.0 -15.0 -13.0 -11.0 -10.0 -9.1 -7.6 -5.6 -3.7 -0.7 2.2 4.1 6.0 7.9 9.8 11.8 13.7

3.4 3.5 3.7 3.9 4.1 4.3 4.3 4.4 4.6 4.8 5.0 5.3 5.6 5.6 5.8 5.8 5.8 5.8 5.8 4.2 4.3 4.6 4.9 5.1 5.4 5.4 5.5 5.7 6.0 6.2 6.6 7.0 7.1 7.2 7.2 7.2 7.2 7.2

3.4 3.5 3.7 3.8 4.1 4.3 4.3 4.4 4.6 4.8 5.0 5.3 5.4 5.4 5.4 5.4 5.4 5.4 5.4 4.2 4.3 4.6 4.8 5.1 5.4 5.4 5.5 5.7 6.0 6.2 6.6 6.7 6.7 6.7 6.7 6.7 6.7 6.7

3.4 3.5 3.7 3.4 3.6 3.8 3.9 4.0 4.1 4.3 4.4 4.6 4.9 5.0 5.0 5.0 5.0 5.0 5.0 4.2 4.3 4.6 4.3 4.5 4.8 4.9 5.0 5.1 5.4 5.5 5.8 6.2 6.3 6.3 6.3 6.3 6.3 6.3

3.3 3.5 3.7 3.8 4.0 4.3 4.3 4.4 4.4 4.6 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.2 4.3 4.6 4.8 5.0 5.4 5.4 5.5 5.6 5.8 6.1 6.1 6.1 6.1 6.1 6.1 6.1 6.1 6.1

3.3 3.4 3.7 3.8 4.0 4.2 4.3 4.4 4.4 4.6 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.2 4.3 4.6 4.8 5.0 5.3 5.4 5.5 5.6 5.8 5.9 5.9 5.9 5.9 5.9 5.9 5.9 5.9 5.9

3.3 3.4 3.6 3.8 4.0 4.2 4.3 4.3 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.2 4.3 4.5 4.8 5.0 5.3 5.4 5.4 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5

-19.8 -18.8 -16.7 -14.7 -12.6 -10.5 -9.5 -8.5 -7.0 -5.0 -3.0 0.0 3.0 5.0 7.0 9.0 11.0 13.0 15.0

-20.0 -19.0 -17.0 -15.0 -13.0 -11.0 -10.0 -9.1 -7.6 -5.6 -3.7 -0.7 2.2 4.1 6.0 7.9 9.8 11.8 13.7

5.4 5.5 5.8 6.2 6.5 6.8 6.9 7.0 7.3 7.6 7.9 8.4 8.9 9.0 9.2 9.2 9.2 9.2 9.2

5.4 5.5 5.8 6.1 6.5 6.8 6.9 7.0 7.3 7.6 7.9 8.4 8.6 8.6 8.6 8.6 8.6 8.6 8.6

5.4 5.5 5.8 5.5 5.8 6.0 6.2 6.3 6.5 6.8 7.0 7.4 7.8 8.0 8.0 8.0 8.0 8.0 8.0

5.3 5.5 5.8 6.1 6.4 6.8 6.9 7.0 7.1 7.4 7.7 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8

5.3 5.4 5.8 6.1 6.4 6.7 6.9 7.0 7.1 7.4 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5

5.3 5.4 5.8 6.1 6.4 6.7 6.8 6.8 7.0 7.0 7.0 7.0 7.0 7.0 7.0 7.0 7.0 7.0 7.0

Notes: TC: Total Capacity(kW)

10 _ Ceiling Concealed Duct(Low Static)


7. External Static Pressure (E.S.P) & Air Flow ARNU07GB1G2, ARNU09GB1G2, ARNU12GB1G2, ARNU15GB1G2 Setting Value

Static Pressure(mmAq(Pa)) 0(0) 6.02 6.95 7.69 8.46 9.5 10.35 10.81 11.57 12.58 13.31 14.2 14.82

1(10) 2.25 3.32 5.16 6.93 7.37 8.72 9.66 10.31 11.22 12.27 13.24 13.92

2(20)

3(29)

4(39)

0.61 0.73 1.19 2.42 3.4 5.33 6.75 8.56 9.75 10.89 12.15 12.64

0.54 0.65 0.77 0.87 1.35 3.15 4.73 7.46 8.64 10.49 11.16

0.48 0.56 0.63 0.72 0.88 0.98 1.03 2.31 5.01 7.7 9.48

ARNU18GB2G2, ARNU24GB2G2 Setting Value 65 70 75 80 85 90 95 100 105 110 115 120 125 130

(Unit: CMM) Static Pressure(mmAq(Pa))

0(0)

1(10)

2(20)

3(29)

4(39)

10.07 11.39 12.01 13.21 14.24 15.04 16.02 17.11 17.99 19.04 19.77 20.94 21.97 22.83

6.9 8.49 9.79 11.03 12.36 13.34 14.63 15.56 16.53 17.71 18.62 19.92 20.56 21.98

0.82 2.2 4.2 5.92 9.41 10.8 12.5 13.66 15.17 16.22 17.1 18.56 19.25 20.75

0.92 2.1 5.29 7.59 11.53 12.35 14.23 15.23 16.98 17.68 19.32

1.01 1.34 5.35 7.67 10.45 13.25 14.66 16.06 17.73

Note : 1. The above table shows the correlation between the air rates and E.S.P.

Ceiling Concealed Duct(Low Static) _ 11

Indoor Units

60 65 70 75 80 85 90 95 100 105 110 115

(Unit: CMM)


7. External Static Pressure (E.S.P) & Air Flow ARNU07GB1G2, ARNU09GB1G2, ARNU12GB1G2, ARNU15GB1G2 Capacity

7k

High (factory set) Standard

9k

High (factory set) Standard High (factory set)

12k

Indoor Units

Standard Set value ESP(mmAq(Pa))

Mode

Standard High (factory set) 15k Standard

HI Mid Low HI Mid Low HI Mid Low HI Mid Low HI Mid Low HI Mid Low HI Mid Low HI Mid Low

94 92 86 75 69 62 99 94 92 82 75 69 103 99 94 89 80 75 107 105 99 95 89 82

2(20) 0(0) 2(20) 0(0) 2(20) 0(0) 2(20) 0(0)

CMM 8.5 7.5 6.5 8.5 7.5 6.5 9.5 8.5 7.5 9.5 8.5 7.5 10.5 9.5 8.5 10.5 9.5 8.5 11.5 10.5 9.5 11.5 10.5 9.5

Lower Limit of External Static Pressure(mmAq(Pa))

Upper Limit of External Static Pressure(mmAq(Pa))

-

4(39)

-

4(39)

-

4(39)

-

4(39)

-

4(39)

-

4(39)

-

4(39)

-

4(39)

ARNU18GB2G2, ARNU24GB2G2 Capacity

18k

High (factory set) Standard

24k

Standard Set value ESP(mmAq(Pa))

Mode

High (factory set) Standard

HI Mid Low HI Mid Low HI Mid Low HI Mid Low

110 101 93 95 84 75 125 115 105 110 100 90

2(20) 0(0) 2(20) 0(0)

12 _ Ceiling Concealed Duct(Low Static)

CMM 16 14 12 16 14 12 19 17 15 19 17 15

Lower Limit of External Static Pressure(mmAq(Pa))

Upper Limit of External Static Pressure(mmAq(Pa))

-

4(39)

-

4(39)

-

4(39)

-

4(39)


8. Electric Characteristics Units Model

Type

Power Supply Hz

Volts

Voltage Range MCA

IFM

Input(W)

MFA

kW

FLA

Cooling Heating

B1

0.22

15

0.028

0.17

30

30

ARNU09GB1G2

B1

0.22

15

0.028

0.17

30

30

ARNU12GB1G2

B1

Max:264

0.22

15

0.028

0.17

30

30

ARNU15GB1G2

B1

Min:198

0.22

15

0.028

0.17

30

30

ARNU18GB2G2

B2

0.55

15

0.076

0.44

80

80

ARNU24GB2G2

B2

0.55

15

0.076

0.44

80

80

ARNU07GB1G2

B1

0.22

15

0.028

0.17

30

30

ARNU09GB1G2

B1

0.22

15

0.028

0.17

30

30

ARNU12GB1G2

B1

Max:242

0.22

15

0.028

0.17

30

30

ARNU15GB1G2

B1

Min:198

0.22

15

0.028

0.17

30

30

ARNU18GB2G2

B2

0.55

15

0.076

0.44

80

80

ARNU24GB2G2

B2

0.55

15

0.076

0.44

80

80

50

60

220-240

220

Symbols: MCA : Min, Circuit Amps(A) MFA : Max. Fuse Amps(see note 5) kW : Fan Motor Rated Output(kW) FLA : Full Load Amps(A) IFM : Indoor Fan Motor Note : 1. Voltage range Units are suitable for use on electrical systems where voltage supplied to unit terminals is not below or above the listed range limits, 2. Maximum allowable voltage unbalance between phases is 2% 3. MCA/MFA MCA=1.25 x FLA MFA≤ 4 x FLA (Next lower standard fuse rating. Min. 15A) 4. Select wire size based on the MCA 5. Instead of fuse, use Circuit Breaker.

Ceiling Concealed Duct(Low Static) _ 13

Indoor Units

ARNU07GB1G2


9. Sound Levels Overall Notes: - Sound measured at 1.5m away from the center of the unit. - Data is valid at free field condition - Data is valid at nominal operating condition - Reference accoustic pressure OdB = 20μPa - Sound level will vary depending on a range of factors such as the construction(acoustic absorption coefficient) of particular room in which the equipment is installed.

1.5m

Ceiling 2.0m Microphone

Sound Levels dB(A) H 33 34 35 38 40 43

ARNU07GB1G2 ARNU09GB1G2 ARNU12GB1G2 ARNU15GB1G2 ARNU18GB2G2 ARNU24GB2G2

M 32 33 34 37 37 40

L 29 32 33 36 34 37

Sound Pressure Level ARNU09GB1G2

ARNU12GB1G2

80

80

70

70

70

NC-65

60 NC-60 NC-55

50

NC-50 NC-45

40

NC-40 NC-35

30

NC-30

20

63

NC-55

50 NC-50 NC-45

40 NC-40

30

NC-30

NC-15

250

500

10

1000 2000 4000 8000

Octave Band Center Frequency (Hz)

ARNU15GB1G2

250

500

NC-55 NC-50 NC-45 NC-40 NC-35

30

NC-30

20

NC-25

Approximate Hearing Threshold 63

Octave Band Sound Pressure Level (dB re 20μPa )

NC-60

40

NC-15

250

500

1000 2000 4000 8000

Octave Band Center Frequency (Hz)

NC-40 NC-35

30

NC-30

NC-25 NC-20 NC-15

10 63

1000 2000 4000 8000

125

250

500

1000 2000 4000 8000

Octave Band Center Frequency (Hz)

ARNU24GB2G2 80

70

NC-65

60 NC-60 NC-55

50

NC-50 NC-45

40

NC-40 NC-35

30

NC-30

NC-25

20 Approximate Hearing Threshold

NC-20

125

NC-45

40

ARNU18GB2G2

NC-65

50

NC-50

Approximate Hearing Threshold

80

70

10

125

NC-55

50

Octave Band Center Frequency (Hz)

80

60

NC-60

NC-20 NC-15

63

NC-65

60

20

NC-25

Approximate Hearing Threshold

NC-20

125

NC-35

70

NC-65

60 NC-60

NC-15

125

250

500

1000 2000 4000 8000

Octave Band Center Frequency (Hz)

14 _ Ceiling Concealed Duct(Low Static)

NC-55

50

NC-50 NC-45

40

NC-40 NC-35

30

NC-30

NC-25

20 Approximate Hearing Threshold

NC-20

10 63

Octave Band Sound Pressure Level (dB re 20μPa )

10

NC-60

20

NC-25

Approximate Hearing Threshold

NC-65

60

Octave Band Sound Pressure Level (dB re 20μPa )

80

Octave Band Sound Pressure Level (dB re 20μPa )

Octave Band Sound Pressure Level (dB re 20μPa )

ARNU07GB1G2

Octave Band Sound Pressure Level (dB re 20μPa )

Indoor Units

Model Name

NC-20 NC-15

10 63

125

250

500

1000 2000 4000 8000

Octave Band Center Frequency (Hz)


10. Installation • Please read the instruction sheets completely before installing the product. • When the power cord is damaged, replacement work shall be performed by authorized personnel only. • Installation work must be performed in accordance with the national wiring standards by authorized personnel only.

Required Tools

• Connecting cable • Pipes: Gas side Liquid side • Hanging Bolt (W 3/8 or M10 length 650mm) • Insulated drain hose • Additional Drain hose

• Level • Screw driver • Electric drill • Hole core drill • Flaring Tool set • Torque Wrenches • Hexagonal Wrench • Gas-leak detector • Thermometer

Indoor Units

Required Parts

10.1 Selection of the best location Install the air conditioner in the location that satisfies the following conditions. • The place shall easily bear a load exceeding four times the indoor unitʼs weight. • The place shall be able to inspect the unit as given in the figure. • The place where the unit shall be leveled. • The place shall allow easy water drainage.(Suitable dimension “H” is necessary to get a slope to drain as figure.) • The place shall easily connect with the outdoor unit. • The place where the unit is not affected by an electrical noise. • The place where air circulation in the room will be good . • There should not be any heat source or steam near the unit. • The servicing inspection hole in the ceiling should be as large as the product. • The selection of the servicing hole should be approved by the customer.

[Inspection Hole Standard] Number of Inspection hole

Distance between False ceiling & Actual ceiling

1

More than 100cm

2

20cm to 100cm

Hole size should be more than the size of IDU.

Less than 20cm

Remarks Sufficient space in the ceiling for servicing. Insufficient space. Difficult for servicing Minimum height for motor replacement.

Inspection hole (600X600) Control box

Top view (unit: mm)

600

600

Front view

H

Ceiling Concealed Duct(Low Static) _ 15


10. Installation 10.2 Ceiling dimension and hanging bolt location ■ Installation of Unit Install the unit above the ceiling correctly.

CASE 1 M10 Nut

X4

M10 washer

X4

M10 washer

X4

M10 Nut

X8

POSITION OF SUSPENSION BOLT

Indoor Units

• Apply a joint-canvas between the unit and duct to absorb unnecessary vibration.

• Install the unit leaning to a drainage hole side as a figure for easy water drainage.

CASE 2 POSITION OF CONSOLE BOLT • A place where the unit will be leveled and that can support the weight of the unit. • A place where the unit can withstand its vibration. • A place where service can be easily performed.

NOTE: • Throughly study the following installation locations: 1. In such places as restaurants and kitchens, considerable amount of oil steam and flour adhere to the fan, the fin of the heat exchanger, resulting in heat exchange reduction, spraying, dispersing of water drops, etc. In these cases, take the following actions: • Make sure that the ventilation fan for smoke-collecting hood on a cooking table has sufficient capacity so that it draws oily steam which should not flow into the suction of the air conditioner. • Make enough distance from a cooking room to install the air conditioner in such a place where it may not suck in oil steam. 2. Avoid installing air conditioner in such circumstances where cutting oil mist or iron powder is in suspension in factories, etc. 3. Avoid places where inflammable gas is generated, flows in, is stored or vented. 4. Avoid places where sulfurous acid gas or corrosive gas is generated. 5. Avoid places near high frequency generators.

16 _ Ceiling Concealed Duct(Low Static)


10. Installation 10.3 Connecting Cables Connect the wires to the terminals on the control board individually according to the outdoor unit connection. • Ensure that the color of the wires of outdoor unit and the terminal No. are the same as those of indoor unit respectively [Multi V III Heat Pump Model]

Terminal Block Indoor 1(L)

2(N)

3

SODU B

SODU A

IDU B

IDU A

INT B

INT A

IDU

INTERNET DRY1 DRY2 GND 12V

4

INDOOR POWER INPUT

[Except Multi VIII Heat Pump Model]

Terminal Block Indoor 1(L)

2(N)

3

SODU

4

B

A

-

-

B

A

-

-

-

-

Outdoor Unit

Clamping of cables 1) Arrange 2 power cables on the control panel. 2) First, fasten the steel clamp with a screw to the inner boss of control panel. 3) For the cooling model, fix the other side of the clamp with a screw strongly. For the heat pump model, put the 0.75mm2 cable(thinner cable) on the clamp and tighten it with a plastic clamp to the other boss of the control panel.

10.4 Checking the Drainage • Spray one or two glasses of water on the evaporator. • Ensure that water flows drain hose of indoor unit without any leakage.

10.5 Indoor Unit Drain Piping • Drain piping must have down-slope (1/50 to 1/100): be sure not to pro- Pipe clamp vide up-and-down slope to prevent reversal flow. • During drain piping connection, be careful not to exert extra force on the Indoor unit drain port on the indoor unit. • The outside diameter of the drain connection on the indoor unit is 32mm. Piping material: Polyvinyl chloride pipe inner diometes Ø 25mm and pipe fittings

Upward routing not allowed

Maintenance drain port

• Be sure to install heat insulation on the drain piping. 1/50~1/100

Heat insulation material: Polyethylene foam with thickness more than 8 mm.

MAX 700mm

Ceiling Concealed Duct(Low Static) _ 17

Indoor Units

INDOOR POWER INPUT


10. Installation Drain test The air conditioner uses a drain pump to drain water. Use the following procedure to test the drain pump operation: Flexible drain hose (accessory) Main drain pipe

Drain Pump

Drain port

Glue the joint

Drain hose connection Use the clip (accessory)

• Connect the main drain pipe to the exterior and leave it provisionally until the test comes to an end. • Feed water to the flexible drain hose and check the piping for leakage. • Be sure to check the drain pump for normal operating and noise when electrical wiring is complete. • When the test is complete, connect the flexible drain hose to the drain port on the indoor unit.

Indoor Units

Drain pan Max 300mm

CAUTION

Hanger distance 1~15m

Hanger Bracket 1/50~1/100 slope

Metal clamp

The supplied flexible drain hose should not be strained. A strained hose may cause leakage of water.

Flexible drain hose

Max 700mm

Feed water

Insulation

10.6 Ground drain piping a) It is standard work practice to make connections to the main pipe from above. The pipe down from the combination should be as large as possible.

Flexible drain hose

Flexible drain hose

Face the vent pipe mouth downward to keep foreign matter from penetrating the system Face piping downward Vent pipe

b) The pipe work should be kept as short as possible and the number of indoor units per group kept to a minimum.

10.7 Use of an auxiliary drain hose(flexible) a) To connect drain pipe to the drain socket on the indoor unit, an auxiliary flexible drain hose should be used. auxiliary flexible drain hose allows that the drain pipe can be connected to the socket without breaking by excessive strain.

18 _ Ceiling Concealed Duct(Low Static)


10. Installation Auxiliary drain hose

Thermal insulation (drain pipe area)

Metal clamp

Metal clamp Thermal insulation(bend area) Drain pan

â?ˆ Important points

WIRED REMOTE CONTROLLER INSTALLATION • Since the room temperature sensor is in the remote controller, the remote controller box should be installed in a place away from direct sunlight, high humidity and direct supply of cold air to maintain proper space temperature. Install the remote controller about 5ft(1.5m) above the floor in an area with good air circulation at an average temperature.

Do not install the remote controller where it can be affected by: - Drafts, or dead spots behind doors and in corners. - Hot or cold air from ducts. - Radiant heat from sun or appliances. - Concealed pipes and chimneys. - Uncontrolled areas such as an outside wall behind the remote controller. - This remote controller is equipped with a seven segment LED. display. For proper display of the remote controller LED's, the remote controller should be installed properly as shown in Fig.1. (The standard height is 1.2~1.5 m from floor level.)

TEMP

yes

Remote Controller

no

TEMP

Controller Remote

TEMP

Remote Controller

5feet (1.5meters)

no

no

Fig.1 Typical locations for remote controller

Ceiling Concealed Duct(Low Static) _ 19

Indoor Units

- The drain pipe should be at least equal in size to that of the indoor unit. - The drain pipe is thermally insulated to prevent the formation of condensation inside the pipe. - The drain up mechanism should be fitted before the indoor unit is installed and when the electricity has been connected some water should be added to the drain pan and the drain pump to check and see if it is functioning correctly. - All connections should be secure. (Special care is needed with PVC pipe) - Insulate auxiliary drain hose with thermal insulation band.


11. Accessories Standard Accessories Name

Drain hose

Clamp metal

Quantity

1 EA

2 EA

Washer for hanging backet 8 EA

Clamp (Tie Wrap) 4 EA

Insulation for fitting

(Other)

1 SET

• Owner's manual • Installation manual Shape

for gas pipe

Indoor Units

for liquid pipe

CAUTION • Use only those accessories (Standard or optional) which have designated specifications.

20 _ Ceiling Concealed Duct(Low Static)


Indoor unit Ceiling Concealed Duct_Built in 1. List of functions 2. Specifications 3. Dimensions 4. Piping Diagrams 5. Wiring Diagrams 6. Capacity Tables 7. External Static Pressure (E.S.P) & Air Flow 8. Electric Characteristics 9. Sound Levels 10. Installation 11. Accessories


1. List of Functions Category

Air flow

Indoor Units

Air purifying

Installation

Reliability

Convenience

Individual control

Special function kit

Function

Air supply outlet Airflow direction control(left & right) Airflow direction control(up & down) Auto swing(left & right) Auto swing(up & down) Airflow steps(fan/cool/heat) Chaos swing Chaos wind(auto wind) Jet cool(Power wind) Swirl wind Deodorizing filter Plasma air purifier Prefilter(washable / anti-fungus) Drain pump E.S.P. control Electric heater(operation) High ceiling operation Hot start Self diagnosis Soft dry operation Auto changeover Auto cleaning Auto operation(artificial intelligence) Auto restart operation Child lock Forced operation Group control Sleep mode Timer(on/off) Timer(weekly) Two thermistor control Wide wired remote controller Deluxe wired remote controller Simple wired remote controller Wired remote controller(for hotel use) Wireless remote controller(simple) Wireless LCD remote control Zone control CTIE Electro thermostat

ARNU07GB3G2+PBSGB30(Acc'y), PBSC30(Acc'y) ARNU09GB3G2+PBSGB30(Acc'y), PBSC30(Acc'y) ARNU12GB3G2+PBSGB30(Acc'y), PBSC30(Acc'y) ARNU15GB3G2+PBSGB30(Acc'y), PBSC30(Acc'y) ARNU18GB4G2+PBSGB40(Acc'y), PBSC40(Acc'y) ARNU24GB4G2+PBSGB40(Acc'y), PBSC40(Acc'y) 1 3/3/3 X X O O O X O O O O(Heat recovery) X O(Heat pump or Cooling only) O O O O O O O Accessory Accessory Accessory Accessory X Accessory Accessory -

O : Applied X : Not applied – : No relation Option : Model name & price are different according to options, and assembled in factory with main unit. Accessory : Installed at field, ordered and purchased separately by the corresponding model name, supplied with separate package.

1 _ Ceiling Concealed Duct_Built in


2. Specification Ceiling Concealed Duct (Built-in) PBSGB30/PBSC30 PBSGB30/PBSC30 PBSGB30/PBSC30 Unit ARNU07GB3G2 ARNU09GB3G2 ARNU12GB3G2 kW 2.2 2.8 3.6 Cooling Capacity kcal/h 1,900 2,400 3,100 Btu/h 7,500 9,600 12,300 kW 2.5 3.2 4.0 Heating Capacity kcal/h 2,200 2,800 3,400 Btu/h 8,500 10,900 13,600 Casing Galvanized Steel Plate Galvanized Steel Plate Galvanized Steel Plate mm 820 x 575 x 190 820 x 575 x 190 820 x 575 x 190 Dimensions(WxDxH) Body inch 32.3 x 22.6 x 7.5 32.3 x 22.6 x 7.5 32.3 x 22.6 x 7.5 Rows x Columns x FPI 2 x 11 x 21 2 x 11 x 21 2 x 11 x 21 Coil Face Area m3 0.16 0.16 0.16 Type Sirocco Fan Sirocco Fan Sirocco Fan Motor Output x Number W 30 30 30 Running Current A 0.15 0.15 0.15 Air Flow Rate(H / M / L) CMM 8.0 / 6.5 / 5.5 9.0 / 7.0 / 6.0 10.0 / 8.0 / 6.5 (High Mode-factor set) cfm 283 / 229 / 194 318 / 247 / 212 353 / 283 / 229 Fan External Static Pressure mmAq(Pa) 2(20) 2(20) 2(20) Air Flow Rate(H / M / L) CMM 8.0 / 6.5 / 5.5 9.0 / 7.0 / 6.0 10.0 / 8.0 / 6.5 (Standard Mode) cfm 283 / 229 / 194 318 / 247 / 212 353 / 283 / 229 External Static Pressure mmAq(Pa) 0(0) 0(0) 0(0) Drive Direct Direct Direct Motor type BLDC BLDC BLDC Temperature Control Microprocessor, Thermostat for cooling and heating Microprocessor, Thermostat for cooling and heating Microprocessor, Thermostat for cooling and heating Sound Absorbing Thermal Insulation Material Foamed polystrene Foamed polystrene Foamed polystrene Air Filter Safety Device Fuse, Thermal Fuse for Fan Motor Fuse, Thermal Fuse for Fan Motor Fuse, Thermal Fuse for Fan Motor Liquid Side mm(inch) �Ø6.35(1/4) Ø6.35(1/4) Ø6.35(1/4) Pipe Connections Gas Side mm(inch) Ø12.7(1/2) Ø12.7(1/2) Ø12.7(1/2) Drain Pipe(Internal Dia.) mm(inch) 25.4(1) 25.4(1) 25.4(1) Net Weight kg(lbs) 21(46.3) 21(46.3) 21(46.3) Noise Level(Sound Press, 1m, H / M / L) dB(A) 33 / 32 / 29 34 / 33 / 32 35 / 34 / 33 1, 220-240, 50 1, 220-240, 50 1, 220-240, 50 Power Supply Ø, V, Hz 1, 220, 60 1, 220, 60 1, 220, 60 Refrigerant Control EEV EEV EEV Power cable mm2 CV1.5 x 3C CV1.5 x 3C CV1.5 x 3C Transmission cable mm2 CVV-SB 1.0~1.5 x 2C CVV-SB 1.0~1.5 x 2C CVV-SB 1.0~1.5 x 2C Type Accessory Model

Conversion Formula kcal/h= kW x 860 Btu/h = kW x 3412 cfm = m3/min x 35.3 l/s = CMM x 1000/60

Ceiling Concealed Duct_Built in _ 2

Indoor Units

Notes:1. Capacities are based on the following conditions: Cooling • Indoor temp. 27°C[80.6°F]DB/ 19°C[66.2°F]WB • Outdoor temp. 35°C[95°F]DB/ 24°C[75.2°F]WB • Interconnecting Piping Length 7.5m • Level Difference of Zero Heating • Indoor temp. 20°C[68°F]DB/ 15°C[59°F]WB • Outdoor temp. 7°C[44.6°F]DB/ 6°C[42.8°F]WB • Interconnecting Piping Length 7.5m • Level Difference of Zero 2. Capacities are net capacities 3. Due to our policy of innovation some specifications may be changed without notification 4. EEV: Electronic Expansion Valve 5. To be added for more available Models 6. Anechoic chamber conversion value is measured at 1.5 m downward from unit centre. The values depends on the ambient conditions and values are normally higher in actual operation.


2. Specification Ceiling Concealed Duct (Built-in) PBSGB30/PBSC30 PBSGB40/PBSC40 PBSGB40/PBSC40 Unit ARNU15GB3G2 ARNU18GB4G2 ARNU24GB4G2 kW 4.5 5.6 7.1 Cooling Capacity kcal/h 3,900 4,800 6,100 Btu/h 15,400 19,100 24,200 kW 5.0 6.3 8.0 Heating Capacity kcal/h 4,300 5,400 6,900 Btu/h 17,100 21,500 27,300 Casing Galvanized Steel Plate Galvanized Steel Plate Galvanized Steel Plate mm 820 x 575 x 190 1,100 x 575 x 190 1,100 x 575 x 190 Dimensions(WxDxH) Body inch 32.3 x 22.6 x 7.5 32.3 x 22.6 x 7.5 32.3 x 22.6 x 7.5 Rows x Columns x FPI 2 x 11 x 21 3 x 10 x 18 3 x 10 x 18 Coil Face Area m3 0.16 0.23 0.23 Type Sirocco Fan Sirocco Fan Sirocco Fan Motor Output x Number W 30 80 80 Running Current A 0.15 0.38 0.38 Air Flow Rate(H / M / L) CMM 11.0 / 10.0 / 8.0 14.0 / 12.0 / 10.0 17.0 / 15.0 / 10.0 (High Mode-factor set) cfm 388 / 353 / 283 494 / 424 / 353 600 / 530 / 353 Fan External Static Pressure mmAq(Pa) 2(20) 2(20) 2(20) Air Flow Rate(H / M / L) CMM 11.0 / 10.0 / 8.0 14.0 / 12.0 / 10.0 17.0 / 15.0 / 10.0 (Standard Mode) cfm 388 / 353 / 283 494 / 424 / 353 600 / 530 / 353 External Static Pressure mmAq(Pa) 0(0) 0(0) 0(0) Drive Direct Direct Direct Motor type BLDC BLDC BLDC Temperature Control Microprocessor, Thermostat for cooling and heating Microprocessor, Thermostat for cooling and heating Microprocessor, Thermostat for cooling and heating Sound Absorbing Thermal Insulation Material Foamed polystrene Foamed polystrene Foamed polystrene Air Filter Safety Device Fuse, Thermal Fuse for Fan Motor Fuse, Thermal Fuse for Fan Motor Fuse, Thermal Fuse for Fan Motor Liquid Side mm(inch) Ø6.35(1/4) Ø6.35(1/4) Ø9.52(3/8) Pipe Connections Gas Side mm(inch) Ø12.7(1/2) Ø12.7(1/2) Ø15.88(5/8) Drain Pipe(Internal Dia.) mm(inch) 25.4(1) 25.4(1) 25.4(1) Net Weight kg(lbs) 21(46.3) 26(57.3) 26(57.3) Noise Level(Sound Press, 1m, H / M / L) dB(A) 41 / 40 / 37 43 / 40 / 37 46 / 43 / 37 1, 220-240, 50 1, 220-240, 50 1, 220-240, 50 Power Supply Ø, V, Hz 1, 220, 60 1, 220, 60 1, 220, 60 Refrigerant Control EEV EEV EEV Power cable mm2 CV1.5 x 3C CV1.5 x 3C CV1.5 x 3C Transmission cable mm2 CVV-SB 1.0~1.5 x 2C CVV-SB 1.0~1.5 x 2C CVV-SB 1.0~1.5 x 2C

Indoor Units

Type Accessory Model

Notes:1. Capacities are based on the following conditions: Cooling • Indoor temp. 27°C[80.6°F]DB/ 19°C[66.2°F]WB • Outdoor temp. 35°C[95°F]DB/ 24°C[75.2°F]WB • Interconnecting Piping Length 7.5m • Level Difference of Zero Heating • Indoor temp. 20°C[68°F]DB/ 15°C[59°F]WB • Outdoor temp. 7°C[44.6°F]DB/ 6°C[42.8°F]WB • Interconnecting Piping Length 7.5m • Level Difference of Zero 2. Capacities are net capacities 3. Due to our policy of innovation some specifications may be changed without notification 4. EEV: Electronic Expansion Valve 5. To be added for more available Models 6. Anechoic chamber conversion value is measured at 1.5 m downward from unit centre. The values depends on the ambient conditions and values are normally higher in actual operation.

3 _ Ceiling Concealed Duct_Built in

Conversion Formula kcal/h= kW x 860 Btu/h = kW x 3412 cfm = m3/min x 35.3 l/s = CMM x 1000/60


Ceiling Concealed Duct_Built in _ 4

E

B

F

575

A

With Suction Grille & Suction Canvas

250

388

PBSC30 PBSC40

PBSGB30 PBSGB40

E 821 1100

B 910 1188

Btu/h A 7,9,12,15k 820 18,24k 1100 D 56 56 F G 274 42~250 274 42~250

C 359 359

With Suction Grille

G

C

6

1

4

5

Drain pipe connection Power supply connection Air suction Air discharge

3 4 5 6

(unit : mm) Unit size(7k,9k,12k,15k,18k):ø6.35 Unit size(24k):ø9.52 Unit size(7k,9k,12k,15k,18k):ø12.7 Unit size(24k):ø15.88

Descripition

CHASSIS CODE: B3/B4

Gas pipe connection

2

Name

2

Liquid pipe connection

60

190

1

Number

3

65

ARNU07GB3G2+PBSGB30(Acc'y), PBSC30(Acc'y) ARNU09GB3G2+PBSGB30(Acc'y), PBSC30(Acc'y) ARNU12GB3G2+PBSGB30(Acc'y), PBSC30(Acc'y) ARNU15GB3G2+PBSGB30(Acc'y), PBSC30(Acc'y) ARNU18GB4G2+PBSGB40(Acc'y), PBSC40(Acc'y) ARNU24GB4G2+PBSGB40(Acc'y), PBSC40(Acc'y)

277

76, Seongsan-dong, Changwon City, Gyeongnam, 641-713, Korea

2. Unit shall be grounded in accordance with the local regulations or applicable national codes.

1. Unit should be installed in compliance with the installation manual in the product box.

Note

500(Max)

D

190

216 24

With Suction Grille & Suction Canvas

Indoor Units

With Suction Grille

388 190

B3/B4

618

Ceiling Concealed Duct (Built in)

3. Dimensions


4. Piping Diagrams

Heat Exchanger

EEV Filter

Th2

Th3 Sirocco Fan

Th1

Indoor Units

:Cooling :Heating

Filter

lndoor unit

Refrigerant pipe connection port diameter [Unit: mm(inch)]

MODEL

GAS

LIQUID

ARNU07GB3G2+PBSGB30(Acc'y), PBSC30(Acc'y)

Ø12.7(1/2)

Ø6.35(1/4)

ARNU09GB3G2+PBSGB30(Acc'y), PBSC30(Acc'y)

Ø12.7(1/2)

Ø6.35(1/4)

ARNU12GB3G2+PBSGB30(Acc'y), PBSC30(Acc'y)

Ø12.7(1/2)

Ø6.35(1/4)

ARNU15GB3G2+PBSGB30(Acc'y), PBSC30(Acc'y)

Ø12.7(1/2)

Ø6.35(1/4)

ARNU18GB4G2+PBSGB40(Acc'y), PBSC40(Acc'y)

Ø12.7(1/2)

Ø6.35(1/4)

ARNU24GB4G2+PBSGB40(Acc'y), PBSC40(Acc'y)

Ø15.88(5/8)

Ø9.52(3/8)

LOC.

Description

Th1

Room thermistor

Th2

Pipe in thermistor

Th3

Pipe out thermistor

5 _ Ceiling Concealed Duct_Built in


5. Wiring Diagrams B3/B4 Chassis

CN-MOTOR1 CN-MOTOR2 CN-PIPE/OUT CN-PIPE/IN CN-ROOM CN-REMO CN-FLOAT CN-EEV CN-D/PUMP CN-OPTION CN-COM CN-D/PUMP CN-POWER CN-ZONE CN-DISPLAY CN-CC

SPEC.

DESCRIPTION

Fan motor output Fan motor output Discharge pipe sensor Suction pipe sensor Room sensor Remote controller Float switch input EEV output Drain pump output Option PWB. Communication Drain pump output AC power supply Zone Controller RF Remote controller Dry contact

Motor output of BLDC Motor output of BLDC Pipe out thermistor Pipe in thermistor Room thermistor Remote control line Float switch sensing EEV control output AC output for drain pump Communication between main and option Communication between indoor and outdoor AC output for drain pump AC power line input for indoor controller Zone control line RF remote control line Dry contact line

Dip Switch Setting SW3 GROUP

Off Master

On Slave

SW4

DRY CONTACT

Variable

Auto

SW5

EXTRA 1

Off

On

Remarks Group Control setting using Wired Remote Controller Old Dry Contact Mode Setting 1. Variable : Auto/Manual Mode can be chosen by Wide wired remote controller or Wireless remote controller (When shipped from Factory → Manual Mode) 2. Auto : For Dry Contact, it is always Auto mode. 1. Duct model -. OFF : Default(not operate continuosly ) -. ON : Fan operate continuosly 2. Cassette Model : No Function 3. Ceiling Suspended Model -. OFF : Ceiling(default) -. ON : Floor

CAUTION For Multi V Model, Dip Switch 1,2,6,7,8 must be set OFF That dip switch is used for the other model.

Ceiling Concealed Duct_Built in _ 6

Indoor Units

CONNECTOR NUMBER


6. Capacity Tables 6.1 Cooling Capacity

20 14 TC SHC kW kW

23 16 TC SHC kW kW

Indoor air temp. (DB/WB, °C) 26 27 28 18 19 20 TC SHC TC SHC TC SHC kW kW kW kW kW kW

10 12 14 16 18 20 21 23 25 27 29 31 33 35 37 39

1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5

1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3

1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8

1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5

2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1

1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6

2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2

1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6

2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.2

1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.6 1.6

2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.5 2.5 2.5 2.4 2.4 2.3 2.3

1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.6 1.6 1.6 1.6 1.5 1.5

2.9 2.9 2.8 2.8 2.7 2.7 2.7 2.6 2.6 2.6 2.5 2.5 2.5 2.4 2.4 2.3

1.7 1.7 1.7 1.6 1.6 1.6 1.6 1.6 1.5 1.5 1.5 1.5 1.5 1.4 1.4 1.4

10 12 14 16 18 20 21 23 25 27 29 31 33 35 37 39 10 12 14 16 18 20 21 23 25 27 29 31 33 35 37 39

1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4

1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2

2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9

1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4

2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4

2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6

2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6

2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6

3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 2.9 2.9 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.7 3.7

2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.0 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.6 2.6

3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.3 3.2 3.2 3.1 3.1 3.0 3.0 2.9 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.2 4.1 4.1 4.0 4.0 3.9 3.8 3.7

2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.1 2.1 2.1 2.0 2.0 1.9 1.9 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.7 2.7 2.6 2.6 2.6 2.5 2.5

3.7 3.6 3.6 3.5 3.5 3.4 3.4 3.4 3.3 3.3 3.2 3.2 3.1 3.1 3.0 3.0 4.7 4.7 4.6 4.6 4.5 4.4 4.4 4.3 4.3 4.2 4.2 4.1 4.0 4.0 3.9 3.8

2.2 2.1 2.1 2.1 2.1 2.0 2.0 2.0 2.0 1.9 1.9 1.9 1.9 1.8 1.8 1.8 2.8 2.8 2.7 2.7 2.7 2.6 2.6 2.6 2.5 2.5 2.5 2.4 2.4 2.3 2.3 2.3

Outdoor air temp. (DB, °C)

2.2 Indoor Units

Capacity Index

2.8

3.6

Cooling capacity

Notes: TC: Total Capacity(kW)

7 _ Ceiling Concealed Duct_Built in

SHC: Sensible Heat Capacity(kW)

30 22 TC SHC kW kW

32 24 TC SHC kW kW


6. Capacity Tables Cooling capacity

20 14 TC SHC kW kW

23 16 TC SHC kW kW

Indoor air temp. (DB/WB, °C) 26 27 28 18 19 20 TC SHC TC SHC TC SHC kW kW kW kW kW kW

30 22 TC SHC kW kW

Capacity Index

Outdoor air temp. (DB, °C)

4.5

10 12 14 16 18 20 21 23 25 27 29 31 33 35 37 39

3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0

2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7

3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6

3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0

4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2

3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2

4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5

3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3

4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8

3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4

5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4

3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5

5.9 5.8 5.8 5.7 5.6 5.5 5.5 5.4 5.3 5.3 5.2 5.1 5.0 5.0 4.9 4.8

3.5 3.5 3.4 3.4 3.3 3.3 3.3 3.2 3.2 3.1 3.1 3.0 3.0 2.9 2.9 2.8

10 12 14 16 18 20 21 23 25 27 29 31 33 35 37 39 10 12 14 16 18 20 21 23 25 27 29 31 33 35 37 39

3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8

3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1

4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7

3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6 4.6

5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6

3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0

5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1 7.1

4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0

6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 5.8 5.7 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.4 7.2

4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.0 3.9 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.1 5.0

6.7 6.7 6.7 6.7 6.7 6.7 6.7 6.7 6.6 6.4 6.4 6.3 6.2 6.0 5.9 5.8 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.4 8.2 8.1 8.0 7.8 7.7 7.5 7.4

4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.2 4.1 4.1 4.0 3.9 3.9 3.8 3.7 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.4 5.2 5.2 5.1 5.0 4.9 4.8 4.7

7.4 7.3 7.2 7.1 7.0 6.9 6.8 6.7 6.6 6.6 6.5 6.4 6.3 6.2 6.1 6.0 9.3 9.2 9.1 9.0 8.8 8.7 8.7 8.5 8.4 8.3 8.2 8.1 7.9 7.8 7.7 7.6

4.2 4.2 4.1 4.1 4.0 4.0 3.9 3.9 3.8 3.8 3.7 3.7 3.6 3.5 3.5 3.4 5.4 5.3 5.2 5.2 5.1 5.0 5.0 4.9 4.8 4.8 4.7 4.6 4.6 4.5 4.4 4.4

7.1

Notes: TC: Total Capacity(kW)

SHC: Sensible Heat Capacity(kW)

Ceiling Concealed Duct_Built in _ 8

Indoor Units

5.6

32 24 TC SHC kW kW


6. Capacity Tables 6.2 Heating Capacity Outdoor air temp. Capacity Index DB(°C) WB(°C)

Heating capacity Indoor air temp. (DB, °C)

16

18

20

21

22

24

TC

TC

TC

TC

TC

TC

kW

kW

kW

kW

kW

2.2

-20.0 -19.0 -17.0 -15.0 -13.0 -11.0 -10.0 -9.1 -7.6 -5.6 -3.7 -0.7 2.2 4.1 6.0 7.9 9.8 11.8 13.7

1.7 1.7 1.8 1.9 2.0 2.1 2.2 2.2 2.3 2.4 2.5 2.6 2.8 2.8 2.9 2.9 2.9 2.9 2.9

1.7 1.7 1.8 1.9 2.0 2.1 2.2 2.2 2.3 2.4 2.5 2.6 2.7 2.7 2.7 2.7 2.7 2.7 2.7

1.7 1.7 1.8 1.7 1.8 1.9 1.9 2.0 2.0 2.1 2.2 2.3 2.4 2.5 2.5 2.5 2.5 2.5 2.5

1.7 1.7 1.8 1.9 2.0 2.1 2.2 2.2 2.2 2.3 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4

1.7 1.7 1.8 1.9 2.0 2.1 2.2 2.2 2.2 2.3 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4

1.7 1.7 1.8 1.9 2.0 2.1 2.1 2.1 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2

2.8

-19.8 -18.8 -16.7 -14.7 -12.6 -10.5 -9.5 -8.5 -7.0 -5.0 -3.0 0.0 3.0 5.0 7.0 9.0 11.0 13.0 15.0

-20.0 -19.0 -17.0 -15.0 -13.0 -11.0 -10.0 -9.1 -7.6 -5.6 -3.7 -0.7 2.2 4.1 6.0 7.9 9.8 11.8 13.7

2.1 2.2 2.3 2.5 2.6 2.7 2.8 2.8 2.9 3.0 3.2 3.4 3.6 3.6 3.7 3.7 3.7 3.7 3.7

2.1 2.2 2.3 2.4 2.6 2.7 2.8 2.8 2.9 3.0 3.2 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4

2.1 2.2 2.3 2.2 2.3 2.4 2.5 2.5 2.6 2.7 2.8 3.0 3.1 3.2 3.2 3.2 3.2 3.2 3.2

2.1 2.2 2.3 2.4 2.6 2.7 2.8 2.8 2.8 3.0 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1

2.1 2.2 2.3 2.4 2.6 2.7 2.8 2.8 2.8 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0

2.1 2.2 2.3 2.4 2.6 2.7 2.7 2.7 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8

3.6

-19.8 -18.8 -16.7 -14.7 -12.6 -10.5 -9.5 -8.5 -7.0 -5.0 -3.0 0.0 3.0 5.0 7.0 9.0 11.0 13.0 15.0

-20.0 -19.0 -17.0 -15.0 -13.0 -11.0 -10.0 -9.1 -7.6 -5.6 -3.7 -0.7 2.2 4.1 6.0 7.9 9.8 11.8 13.7

2.7 2.8 2.9 3.1 3.2 3.4 3.4 3.5 3.6 3.8 4.0 4.2 4.4 4.5 4.6 4.6 4.6 4.6 4.6

2.7 2.8 2.9 3.0 3.2 3.4 3.4 3.5 3.6 3.8 4.0 4.2 4.3 4.3 4.3 4.3 4.3 4.3 4.3

2.7 2.8 2.9 2.7 2.9 3.0 3.1 3.2 3.3 3.4 3.5 3.7 3.9 4.0 4.0 4.0 4.0 4.0 4.0

2.6 2.8 2.9 3.0 3.2 3.4 3.4 3.5 3.6 3.7 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9

2.6 2.7 2.9 3.0 3.2 3.4 3.4 3.5 3.6 3.7 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8

2.6 2.7 2.9 3.0 3.2 3.4 3.4 3.4 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5

Indoor Units

kW -19.8 -18.8 -16.7 -14.7 -12.6 -10.5 -9.5 -8.5 -7.0 -5.0 -3.0 0.0 3.0 5.0 7.0 9.0 11.0 13.0 15.0

Notes: TC: Total Capacity(kW)

9 _ Ceiling Concealed Duct_Built in


6. Capacity Tables Heating capacity Outdoor air temp. Capacity Index DB(°C) WB(°C)

4.5

7.1

16

18

20

21

22

24

TC

TC

TC

TC

TC

TC

kW

kW

kW

kW

kW

kW

-19.8 -18.8 -16.7 -14.7 -12.6 -10.5 -9.5 -8.5 -7.0 -5.0 -3.0 0.0 3.0 5.0 7.0 9.0 11.0 13.0 15.0 -19.8 -18.8 -16.7 -14.7 -12.6 -10.5 -9.5 -8.5 -7.0 -5.0 -3.0 0.0 3.0 5.0 7.0 9.0 11.0 13.0 15.0

-20.0 -19.0 -17.0 -15.0 -13.0 -11.0 -10.0 -9.1 -7.6 -5.6 -3.7 -0.7 2.2 4.1 6.0 7.9 9.8 11.8 13.7 -20.0 -19.0 -17.0 -15.0 -13.0 -11.0 -10.0 -9.1 -7.6 -5.6 -3.7 -0.7 2.2 4.1 6.0 7.9 9.8 11.8 13.7

3.4 3.5 3.7 3.9 4.1 4.3 4.3 4.4 4.6 4.8 5.0 5.3 5.6 5.6 5.8 5.8 5.8 5.8 5.8 4.2 4.3 4.6 4.9 5.1 5.4 5.4 5.5 5.7 6.0 6.2 6.6 7.0 7.1 7.2 7.2 7.2 7.2 7.2

3.4 3.5 3.7 3.8 4.1 4.3 4.3 4.4 4.6 4.8 5.0 5.3 5.4 5.4 5.4 5.4 5.4 5.4 5.4 4.2 4.3 4.6 4.8 5.1 5.4 5.4 5.5 5.7 6.0 6.2 6.6 6.7 6.7 6.7 6.7 6.7 6.7 6.7

3.4 3.5 3.7 3.4 3.6 3.8 3.9 4.0 4.1 4.3 4.4 4.6 4.9 5.0 5.0 5.0 5.0 5.0 5.0 4.2 4.3 4.6 4.3 4.5 4.8 4.9 5.0 5.1 5.4 5.5 5.8 6.2 6.3 6.3 6.3 6.3 6.3 6.3

3.3 3.5 3.7 3.8 4.0 4.3 4.3 4.4 4.4 4.6 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.2 4.3 4.6 4.8 5.0 5.4 5.4 5.5 5.6 5.8 6.1 6.1 6.1 6.1 6.1 6.1 6.1 6.1 6.1

3.3 3.4 3.7 3.8 4.0 4.2 4.3 4.4 4.4 4.6 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.2 4.3 4.6 4.8 5.0 5.3 5.4 5.5 5.6 5.8 5.9 5.9 5.9 5.9 5.9 5.9 5.9 5.9 5.9

3.3 3.4 3.6 3.8 4.0 4.2 4.3 4.3 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.2 4.3 4.5 4.8 5.0 5.3 5.4 5.4 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5

-19.8 -18.8 -16.7 -14.7 -12.6 -10.5 -9.5 -8.5 -7.0 -5.0 -3.0 0.0 3.0 5.0 7.0 9.0 11.0 13.0 15.0

-20.0 -19.0 -17.0 -15.0 -13.0 -11.0 -10.0 -9.1 -7.6 -5.6 -3.7 -0.7 2.2 4.1 6.0 7.9 9.8 11.8 13.7

5.4 5.5 5.8 6.2 6.5 6.8 6.9 7.0 7.3 7.6 7.9 8.4 8.9 9.0 9.2 9.2 9.2 9.2 9.2

5.4 5.5 5.8 6.1 6.5 6.8 6.9 7.0 7.3 7.6 7.9 8.4 8.6 8.6 8.6 8.6 8.6 8.6 8.6

5.4 5.5 5.8 5.5 5.8 6.0 6.2 6.3 6.5 6.8 7.0 7.4 7.8 8.0 8.0 8.0 8.0 8.0 8.0

5.3 5.5 5.8 6.1 6.4 6.8 6.9 7.0 7.1 7.4 7.7 7.8 7.8 7.8 7.8 7.8 7.8 7.8 7.8

5.3 5.4 5.8 6.1 6.4 6.7 6.9 7.0 7.1 7.4 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5

5.3 5.4 5.8 6.1 6.4 6.7 6.8 6.8 7.0 7.0 7.0 7.0 7.0 7.0 7.0 7.0 7.0 7.0 7.0

Notes: TC: Total Capacity(kW)

Ceiling Concealed Duct_Built in _ 10

Indoor Units

5.6

Indoor air temp. (DB, °C)


7. External Static Pressure (E.S.P) & Air Flow ARNU07GB3G2+PBSGB30(Acc'y), PBSC30(Acc'y) ARNU09GB3G2+PBSGB30(Acc'y), PBSC30(Acc'y) ARNU12GB3G2+PBSGB30(Acc'y), PBSC30(Acc'y) ARNU15GB3G2+PBSGB30(Acc'y), PBSC30(Acc'y)

Indoor Units

Setting Value

(Unit: CMM)

Static Pressure(mmAq(Pa)) 0(0)

1(10)

2(20)

3(29)

4(39)

60

6.29

3.03

0.93

-

-

65

6.61

4.84

1.52

-

-

70

7.69

5.64

2.18

0.79

-

75

8.19

6.28

2.81

0.85

-

80

8.91

7.43

4.96

1.58

-

85

9.51

8.14

5.91

2.75

0.95

90

10.21

8.76

6.79

3.41

1.36

95

10.83

9.62

8.11

5.48

2.61

100

11.31

10.55

9.02

6.12

3.31

105

11.84

11.19

9.99

8.28

5.32

110

12.68

11.88

10.38

9.16

6.92

115

13.19

12.22

11.55

10.21

8.23

ARNU18GB4G2+PBSGB40(Acc'y), PBSC40(Acc'y) ARNU24GB4G2+PBSGB40(Acc'y), PBSC40(Acc'y) Setting Value

(Unit: CMM)

Static Pressure(mmAq(Pa)) 0(0)

1(10)

2(20)

3(29)

4(39)

75

10.32

7.68

3.55

-

-

80

11.06

8.77

4.71

1.38

-

85

11.84

10.02

6.95

2.16

-

90

12.73

10.74

8.26

4.73

1.25

95

13.47

12.13

9.93

6.74

2.73

100

14.16

13.25

10.51

8.41

3.65

105

15.29

14.11

12.31

9.83

6.21

110

16.09

14.77

13.49

10.39

8.32

115

16.91

15.88

14.48

12.77

9.92

120

17.81

16.88

15.15

13.98

10.85

125

18.55

17.84

16.12

15.13

12.97

130

19.01

18.55

17.33

16.28

14.59

Note : 1. The above table shows the correlation between the air rates and E.S.P. 2. E.S.P. is given after subtracting coil losses motor step factory installed 3. E.S.P. can be higher than the maximum given in the table, but the unit faces the problem of freezing the coil.

11 _ Ceiling Concealed Duct_Built in


7. External Static Pressure (E.S.P) & Air Flow ARNU07GB3G2+PBSGB30(Acc'y), PBSC30(Acc'y) ARNU09GB3G2+PBSGB30(Acc'y), PBSC30(Acc'y) ARNU12GB3G2+PBSGB30(Acc'y), PBSC30(Acc'y) ARNU15GB3G2+PBSGB30(Acc'y), PBSC30(Acc'y) Capacity

7k

High (factory set) Standard

9k

Standard Set value ESP(mmAq(Pa))

Mode

High (factory set)

High (factory set) 12k Standard High (factory set) 15k Standard

94 88 83 74 62 56 99 89 85 82 66 58 105 94 88 90 74 62 110 105 94 96 90 74

2(20) 0(0) 2(20) 0(0) 2(20) 0(0) 2(20) 0(0)

8 6.5 5.5 8 6.5 5.5 9 7 6 9 7 6 10 8 6.5 10 8 6.5 11 10 8 11 10 8

Lower Limit of External Static Pressure(mmAq(Pa))

Upper Limit of External Static Pressure(mmAq(Pa))

-

4(39)

-

4(39)

-

4(39)

-

4(39)

-

4(39)

-

4(39)

-

4(39)

-

4(39))

ARNU18GB4G2+PBSGB40(Acc'y), PBSC40(Acc'y) ARNU24GB4G2+PBSGB40(Acc'y), PBSC40(Acc'y) Capacity

18k

High (factory set) Standard

24k

Standard Set value ESP(mmAq(Pa))

Mode

High (factory set) Standard

HI Mid Low HI Mid Low HI Mid Low HI Mid Low

115 103 93 100 86 74 128 118 93 116 104 74

2(20) 0(0) 2(20) 0(0)

CMM 14 12 10 14 12 10 17 15 10 17 15 10

Lower Limit of External Static Pressure(mmAq(Pa))

Upper Limit of External Static Pressure(mmAq(Pa))

-

4(39)

-

4(39)

-

4(39)

-

4(39)

Ceiling Concealed Duct_Built in _ 12

Indoor Units

Standard

HI Mid Low HI Mid Low HI Mid Low HI Mid Low HI Mid Low HI Mid Low HI Mid Low HI Mid Low

CMM


8. Electric Characteristics

Indoor Units

Units

Power Supply

Input(W)

MFA

kW

FLA

0.22

15

0.028

0.17

30

30

0.22

15

0.028

0.17

30

30

Max:264

0.22

15

0.028

0.17

30

30

Min:198

0.22

15

0.028

0.17

30

30

B4

0.55

15

0.076

0.44

80

80

ARNU24GB4G2+PBSGB40(Acc'y), PBSC40(Acc'y)

B4

0.55

15

0.076

0.44

80

80

ARNU07GB3G2+PBSGB30(Acc'y), PBSC30(Acc'y)

B3

0.22

15

0.028

0.17

30

30

ARNU09GB3G2+PBSGB30(Acc'y), PBSC30(Acc'y)

B3

0.22

15

0.028

0.17

30

30

ARNU12GB3G2+PBSGB30(Acc'y), PBSC30(Acc'y)

B3

Max:242

0.22

15

0.028

0.17

30

30

ARNU15GB3G2+PBSGB30(Acc'y), PBSC30(Acc'y)

B3

Min:198

0.22

15

0.028

0.17