10. Performance Data Cooling Capacity(SI Unit) Model No : HT-C488DLA0 Indoor Air Temperature °CWB °CDB 14 20 16 22 18 25 19 27 22 30 24 32
TC 11.4 13.3 14.9 15.5 17.1 17.7
20 SHC 9.1 10.3 11.2 11.6 12.3 12.5
PI 3.28 3.33 3.38 3.43 3.5 3.5
TC 11.2 13.0 14.5 15.2 16.7 17.3
25 SHC 9.0 10.2 11.1 11.4 12.1 12.3
PI 3.9 3.9 4.0 4.1 4.1 4.2
Outdoor Air Temperature (°CDB) 32 35 TC SHC PI TC SHC PI 10.6 8.7 4.5 10.3 8.6 4.8 12.4 9.9 4.6 12.0 9.7 4.8 13.9 10.7 4.7 13.4 10.5 4.9 14.5 11.1 4.7 14.1 10.8 5.0 15.9 11.7 4.8 15.4 11.4 5.1 16.5 11.9 4.9 16.0 11.6 5.1
TC 9.9 11.6 12.9 13.5 14.9 15.4
40 SHC 8.4 9.5 10.2 10.6 11.1 11.3
PI 5.1 5.2 5.2 5.3 5.4 5.5
TC 9.7 11.3 12.6 13.2 14.5 15.1
43 SHC 8.3 9.3 10.1 10.4 10.9 11.1
PI 5.2 5.3 5.4 5.5 5.6 5.6
Model No : HT-C488DLA1 Indoor Air Temperature °CWB °CDB 14 20 16 22 18 25 19 27 22 30 24 32
TC 11.4 13.3 14.9 15.5 17.1 17.7
20 SHC 9.2 10.4 11.3 11.7 12.4 12.6
PI 3.21 3.26 3.31 3.37 3.4 3.5
TC 11.2 13.0 14.5 15.2 16.7 17.3
25 SHC 9.1 10.3 11.2 11.6 12.3 12.5
PI 3.8 3.9 3.9 4.0 4.0 4.1
Outdoor Air Temperature (°CDB) 32 35 TC SHC PI TC SHC 10.6 8.9 4.4 10.3 8.7 12.4 10.0 4.5 12.0 9.8 13.9 10.9 4.6 13.4 10.6 14.5 11.2 4.7 14.1 11.0 15.9 11.9 4.7 15.4 11.6 16.5 12.0 4.8 16.0 11.7
◆Symbol AFR : Air Flow Rate [CMM] DB : Dry Bulb Temperature [°C] WB : Wet Bulb Temperature [°C] TC : Total Capacity [kW] SHC : Sensible Heating Capacity [kW] PI : Power Input [kW] (compressor + indoor fan motor + outdoor fan motor)
PI 4.7 4.7 4.8 4.9 5.0 5.0
TC 9.9 11.6 12.9 13.5 14.9 15.4
40 SHC 8.5 9.6 10.4 10.7 11.3 11.4
PI 5.0 5.0 5.1 5.2 5.3 5.4
TC 9.7 11.3 12.6 13.2 14.5 15.1
43 SHC 8.4 9.4 10.2 10.5 11.1 11.2
PI 5.1 5.2 5.3 5.4 5.5 5.5
◆Notes 1. All capacites are net, evaporator fan motor heat is deducted. 2. Indicates rated capacity. 3. Direct interpolation is permissible. Do not extrapolate. 4. Capacities are based on the following conditions: - Interconnecting Piping Length 7.5m - Level Difference of Zero.
2008 Product Data
29