Lg ceiling cassette(50hz,r22) thai lan

Page 1

Ceiling Cassette (50Hz/R22) TH5CST2-04A ( Replace : TH5CST2-03C)


General Description Thank you very much for your special patronage of LG air conditioners. LG’s "Ceiling Cassette" is a indoor unit which is installed for the significant purpose. The ceiling cassette is used for the commercial purposes. It can be installed in various places such as restaurants, hotels, offices and meeting rooms. This unit has nice outlook and is equipped with many special features. It has four louver for the air circulation in all directions which in turn can maintain even and wide cooling. In other side it has facility for high elevation piping (30m), built in drain pump (drain throw 70cm),high ceiling operation,others for facilitating its working. Noise level of the unit is very low. In installation field unit is installed in fall ceiling. It has wide capacity range from 18 to 48 kBtu/h. A lot of information regarding the design & installation of this system is provided in this publication. This new products series contains data on the same pattern. Please utilize all the information for conducting your business efficiently. Make sure the specification, dimension or others technical data are same as provided in enginering data book before you start the project. We look forward to your continuing support.

LG Electronics lnc. Air Conditioning Division

2

Ceiling Cassette(50Hz, R22)


LG Airconditioners Product Data

Table of contents Table of contents

Page

1. Models List ......................................................................................................................4 2. Model Number Nomenclature..........................................................................................5 3. Feature & Benefits ...........................................................................................................6 4. List of Functions..............................................................................................................11 5. Specifications.................................................................................................................12 6. Dimensional Drawings ...................................................................................................18 7. Wiring Diagrams .............................................................................................................21 8. Refrigerant Cycle Diagrams......................................................................................... 25 9. Selection Procedure ..................................................................................................... 26 10. Perfor mance Data......................................................................................................... 27 11. The Coefficient of Capacity Change ...........................................................................33 12. Operation range.............................................................................................................. 34 13. Air Velocity and Temperature Distributions(Reference Data)................................................. 35 14. Sound Levels ................................................................................................................37 15. Installation .....................................................................................................................38 16. Function of Remote Control.........................................................................................50

2008 Product Data

3


1. Models List

1.1 Cooling Only Nominal Capacity Model Name

kW

kBtu/h

5.3

18

HT-C186HLA0 HT-C186HLA1

7.0

24

HT-C246HLA0 HT-C246HLA1

8.8

30

HT-C306HLA0

10.6

36

HT-C368DLA0 HT-C368DLA1

14.1

48

Power Supply

Model Refrigerant

Ø,V,Hz

1Ø, 220-240V, 50Hz

R22

3Ø, 380-415V, 50Hz

HT-C488DLA0 HT-C488DLA1

Publication history Pub. No.

TH5CST2-04A

Frequency Category

50Hz

CAC

4 Ceiling Cassette(50Hz,R22)

Type Product name

Single Ceiling Cassette

Refrigerant

R22

Model

HT-C368DLA1 HT-C488DLA1

Notes

Addition of new models

Published in

Oct.2008


2. Model Number Nomenclature 2.1 Model Number Nomenclature H T

C 1 8 6 H L A 0 Development Sequence Function A : Basic E : Elevation Grille

C : Plasma Air Purifying F : Elevation Grille + Plasma Air Purifying

Decoration Panel Information L : Basic Panel

Chassis Type H : TH Chassis

D : TD1 Chassis

Electric Standard (Volts / Freq. / Phase) 6 : 220-240V, 50Hz, 1Ă˜

8 : 380-415V, 50Hz, 3Ă˜

Nominal Cooling Capacity Ex) 18-> 18,000 Btu/h

24-> 24,000 Btu/h

Model Type

C : Cooling Only N : Indoor Type , U : Outdoor Type T : Cassette Type H : Development in Thailand

2008 Product Data

5


3. Features & Benefits 840mm

Compact Design and Easy Installation (For TH Chassis)

840mm

Only about 225mm height in the ceiling is sufficient for installation space. 225mm

Low noise with 3-dimensional turbo fan The most advanced low-noise design.The adoption of turbo-fan and round type give the most quiet operation.

Noise output measured in anechoic test room

Hygienic and Easy-to-Clean Filter Washable and anti bacteria filter is adopted. It is easy to open grille and replace clean filter.

Anti Corrosion Gold Fin™ (Option) LG ’s Outdoor Heat Exchanger is coated with a golden anticorrosive epoxy treatment on the aluminum coil to minimized corrosion. This maintains heat transfer properties of the coil for an extended time where as non-Gold Fin coils progressively lose efficiency due to surface corrosion. Standard on every LG air conditioner, this assists in areas suffering from pollution or near the ocean where the unit

Salt Spray Test for 15 Days

After 15 Days

LG Gold Fin™ Anti Corrosion

Gold Coated Aluminum

After 15 Days

Uncoated Aluminum

• Gold Fin is long lasting, durable and makes the Outdoor Unit look prestigious.

6 Ceiling Cassette(50Hz,R22)

Conventional Starting to corrode


3. Features & Benefits Central Control (Optional)

It enables to control 16 x 8 = 128 units with the help of 8 controllers. All units can be put on and off from one central room. For setting the temperature, fan speed and other sub functions, access the sespecture LCD wired remote controller of each unit.

Main PCB

M 1

M 2

M 16

M 17

M 18

M 128

Sub 1

Sub 2

Sub 16

Sub 17

Sub 18

Sub 128

Controller #1

Controller #2

Controller #8

Cooling & Fan Operation(for cooling only) LG Ceiling Cassette air conditioner provides cooling & fan operation. In the cooling mode, it cools the air with an operation range of 18~30°C. In the fan operation mode, only indoor fan at the selected speed will run, outdoor fan and compressor will be off.

AUTO SWING

OPERATION

SET TEMP Room Temp

Wired Remote Control It can control all the functions of the unit. You can check/set temperature, change operation mode, set timer & also diagnose the error of the unit. It also has the option of weekly program.

2ndF Timer

FAN SPEED

SUB FUNCTION

AUTO Heater Preheat JET Defrost Humidify SLo Filter Out door ZONE 1 2 3 4

HI MED LO

Time

Operation unit No Func Program set

On Off Set no. Time 01

03

05

07

Timer

Cancel

2ndF

Program

Week

Holiday

09

11

13

15

17

19

21

23

PLASMA

Set/Clr Hour

Min

RESET

Auto Restart Operation When there is electricity failure the unit shuts off and after resumption of the power, unit will start in the same mode as prior to the power failure. Memorized condition are on / off condition, operating mode (cooling/heating), set temperature and fan speed.The unit will memorize the above conditions and start with same memorized condition.

Two Thermistor Control There may be a significant difference between the temperature taken at the installed product and indoor temperature. Two thermistor control provides option to control temperature by referring any of the two temperatures. With the help of the slide switch at the back of the LCD wired remote controller, selection of the desired thermistor for controlling the unit can be done. One thermistor is in the Indoor unit & the other one is in the LCD wired remote.

2008 Product Data

7


3. Features & Benefits Plasma Air Purifying System (Optional) The PLASMA Air Purifying Function not only removes microscopic contaminants and dust, b ut also removes house mites, pollen, and pet fur helps to prevent allergic diseases like asthma. Dust particles

Dust electrode discharge

Ionizer

Photo-Catalyst Coated Mesh

+4.8KV discharge

+

Polluted Air

+ +

Purified fresh Air

+

Generating plasma

Odour Odour molecule

High Head Drain Pump(700mm) Built-in Drain Pump drains out water automatically. A standard drain-head height of up to 700 mm is possible, creating the ideal solution for perfect water drainage. Pipe fixture

Slope 1/50~1/100

Maximum 700mm Flexible drain hose

Hard Tube(ex.PVC) Drain Pump

Drain Pan

Ceiling Board

High Ceiling Operation According to the height of the installation, it provides variability of indoor fan motor speed. If the height of installation is low then you can adjust low rpm of indoor fan motor. On the other hand if the height of the installation is high you can adjust high speed of indoor fan motor. Selection of speed can be done by slide switch at the back of the LCD wired remote controller. ex: If ceiling height of 2.7-3m(taken as standard for the product) is exceeded, then the slide switch is iperated in the high mode discharging air at a high volume rate and when below 2.7m, the switch is adjusted to discharge at a lower volume rate.

8 Ceiling Cassette(50Hz,R22)

Air velocity distribution


3. Features & Benefits Child Lock Function It prevents the children or others from tampering with the control buttons. Unit can be controlled by the wireless remote controller. This can be easily set by pressing timer key & Min key simultaneously. After child lock is set, pressing any key will display CL on the LCD for 3 seconds and all the keys will be ineffective.

AUTO SWING

OPERATION

SET TEMP Room Temp

Operation unit No Func Program set

On Off Set no. Time 01

Jet Cool

SUB FUNCTION

AUTO Heater Preheat JET Defrost Humidify SLo Filter Out door ZONE 1 2 3 4

HI MED LO

Time

2ndF Timer

FAN SPEED

03

05

07

09

11

13

15

17

19

21

23

Cancel Timer CHILD LOC2ndF K Display

In this mode quick and fast cooling is done. Cold

Program

and high velocity air is supplied to the room till the

Week

Holiday PLASMA

Set/Clr

indoor temperature reaches 18°C.

Hour

RESET

Min

4- Open(Conventional)

Comparison of Floor o Temp. Distri b ution( 20 C)

Swirl Swing

2.4%

Sw irl Sw ing(Ne w )

100% Improved

4.8%

It is the function for comfort cooling/heating operation. The diagonal two louvers are opened the more larger than the other louvers. After one minute, it is opposite.

Comparison of Air Flo w Types 4- Open(Conventional)

Sw irl Sw ing(Ne w )

Vane 1 Open

Vane 1 Close

Vane 2 Open

Vane 2 Open

Vane 3 Open

Vane 3 Close

Vane 4 Open

Vane 4 Open

Close

Time

Group Control

Open

Vane 2 Close

Open

Close

Close

Open

Close

Open

Open

Close

Open

Close

Open 71

Close

Open

Vane 3

Vane 1

Time Vane 4

1

2

16

1) Operation summary - Where several products are linked, one specific control device can control a specific number of products. 2) Specific operation

Remote Controller

- Connecting line is linked to each of the indoor equipments for communication. A specific control device is connected to each of them and this control device can control the same function. - Group control function is enabled by cutting an optional jump wire in the wired remote controller. At this time, the main system will not respond in order to prevent data collision. - While executing group control command, use the random data(0-3minutes) in the main body of indoor equipment for limiting starting current. - Control device can control up to 16 indoor equipments. 2008 Product Data

9


3. Features & Benefits Space Control (Accessory) • Space control Vanes angle can be controlled by pair, considering its installation environment. - For example direct drafts can be annoying, leading to discomfort and reduced productivity, vane control helps to eliminate this problem. - Easily controlled by wired remote control. - Air flow can be controlled easily regarding any space environment.

20°~70°

Time Delay Safety Function It delays restarting of the compressor by three minutes thereby preventing damage to the compressor.

Long Refrigerant Piping It provides flexibility of installation and keep the building in a good outlook.

Model HT-C186HLA0 HT-C186HLA1 HT-C246HLA0 HT-C246HLA1 HT-C306HLA0 HT-C368DLA0 HT-C368DLA1 HT-C488DLA0 HT-C488DLA1

B

Max. Piping length m. (A) Max. Elevation m. (B) 30 30 30 30 30 30 50 30 50

10 Ceiling Cassette(50Hz,R22)

10 10 10 10 10 15 15 15 15

A


4. List of Functions Indoor Unit C a tegory

F unc tion

Air supply outlet Airflow direction control(left & right) Airflow direction control(up & down Auto swing(left & right) Auto swing(up & down) Air flow Airflow steps(fan/cool) (wired remote) Chaos wind (auto wind) Vane Control Jet cool(Power wind) Swirl wind Deodorizing filter Air purifying Plasma air purifier Prefilter(washable / anti-fungus) Drain pump E.S.P. control Installation Electric heater(operation) High Ceiling Operation Hot start Reliability Self diagnosis Soft dry operation Auto changeover Auto cleaning Auto operation(artificial intelligence)

Auto restart operation Child lock Convenience Forced operation Group control Sleep mode Timer(on/off) Timer(weekly) Two thermistor control Standard wired remote controller Deluxe wired remote controller Individual Simple wired remote controller control Wired remote controller(for hotel use) Wireless remote controller(simple) Wireless LCD remote control General central controller (Non LGAP)

CAC network function

Dry contact Simple central control (LGAP) PDI(power distribution indicator) PI485 Zone control Special CTIE function kit Electro thermostat

Ceiling Cassette Type ( wired remote) 4

Ceiling Cassette Type ( wireless remote)

X

X

Auto

Auto

X

X

O

O

4/5

3/4

X

X

O O O

O O O

× Option

× Option

O O

O O

-

O ×

O O

× ×

O O O O O O O O O O

× × × × Accessory × Option

O

× Accessory × × ×

Remark

4

function for HT-C***HLC*

Accessory × Accessory

O

× ×

O O

Accessory

O Accessory

O O

Accessory Accessory Accessory × × × ×

O

× Option

O × Accessory × × ×

Outdoor Unit Defrost/Deicing High pressure switch Low pressure switch Phase protection Reliability Restart delay(3-minutes) Self diagnosis Soft start Test function Auto operation(Artificial intelligence) Convenience Auto restart operation CAC network Network soluation(LGAP) function PDI(Power Distribution Indicator) PI485 Special Low ambient operation function kit Others Thermistor

-

-

× × ×

× × ×

O O × × -

O Accessory × × -

O

O

× × ×

× × ×

×

×

-

-

Note: O : Applied, X : Not applied, - : No relation * Option : Model name & price are different according to options, and assembled in factory with main unit * Accessory : Installed at field, ordered and purchased separately by the corresponding model name, supplied separate package.

2008 Product Data

11


5. Specifications Model No : HTNC186HLA0, HTNC186HLA1, HTNC246HLA0 Indoor Unit Power Supply Cooling Capacity Heating Capacity Current

HTNC186HLA0

HTNC186HLA1

HTNC246HLA0

kW

1/220-240/50 5.3

1/220-240/50 5.3

1/220-240/50 7.0

Btu/h

18,000

18,000

24,000

kW

-

-

Btu/h

-

-

-

Ø / V / Hz

0.3

A

Nominal Running Current

Motor Type Fan Type

Turbo Fan 100x1

Motor Output(W) x No. of Unit Fan

Air Flow Rate (SH / H / M / L / SL) External Static Pressure Capacitor Drive

Coil Dimensions (W x H x D) Net Weight

Row × Column × FPI Body Decorative Panel

CMM

17/15/12/10/8 600/530/424/353/283

cfm mmAq

-

µF / Vac

220/450

Direct 2R x 9C x 18 mm(inch) 840x840x225(33.1x33.1x8.9) mm(inch) 950x950x30(37.4x37.4x1.2)

Body

kg (lbs)

Decorative Panel

kg (lbs)

26(57.3) 5(11) Long Life Filter

Air Filter Sound Level (SH / H / M / L / SL) Piping Connections

dB(A)+3

Liquid

mm (inch)

Gas

mm (inch)

Drain(OD/ID)

Dehumidification Rate

mm l/h

Safety Devices Temperature Sensor Referigerant Referigerant Control No.×mm

2

-

220/450 Direct 2R x 9C x 18 840x840x225(33.1x33.1x8.9) 950x950x30(37.4x37.4x1.2) 26(57.3) 5(11) Long Life Filter

35/31/27/24/20 6.35(1/4) 12.7(1/2) 32 / 25 1.2

35/31/27/24/20 6.35(1/4) 12.7(1/2) 32 / 25 1.15

Fuse, Thermal Protector Thermistor R22

Fuse, Thermal Protector Thermistor R22 Capillary HTUC186HLA1 4x0.75

Capillary

Connectable Outdoor Unit Power and Transmission Interunit Cable

0.3 BLDC Turbo fan 100x1 17/15/12/10/8 600/530/424/353/283

BLDC

HTUC186HLA0 4x0.75

Note : 1. Capacities are based on the following conditions: Cooling: - Indoor Temperature 27℃(80.6℉) DB/19℃(66.2℉) WB - Outdoor Temperature 35℃(95℉) DB/24℃(75.2℉) WB Heating: - Indoor Temperature 20℃(68℉) DB/15℃(59℉) WB - Outdoor Temperature 7℃(44.6℉) DB/6℃(42.8℉) WB Piping Length - Interconnecting Piping Length 7.5m - Level Difference of Zero 2. Wiring cable size must comply with the applicable local and national code. 3. The specification may be subject to change without prior notice for purpose of improvement.

12 Ceiling Cassette(50Hz,R22)

0.3 BLDC Turbo fan 100x1 22/17/15/13/12 776/600/530/459/424 -

220/450 Direct 2R x 9C x 18 840x840x225(33.1x33.1x8.9) 950x950x30(37.4x37.4x1.2) 33(72.7) 5(11) Long Life Filter 42/34/32/29/27 6.35(1/4) 15.88(5/8) 32 / 25 2.4 Fuse, Thermal Protector Thermistor R22 Capillary

HTUC246HLA0 4x0.75


Model No : HTNC246HLA,HTN306HLA0,HTNC368DLA0 Indoor Unit Power Supply Cooling Capacity Heating Capacity Current

HTNC246HLA1

HTNC306HLA0

1/220-240/50

kW

1/220-240/50 7.0

Btu/h

24,000

30,000

Ø / V / Hz

kW

-

-

Btu/h

-

-

0.3

A

Nominal Running Current

Motor Type Motor Output(W) x No. of Unit Fan

External Static Pressure Capacitor Drive Coil Dimensions (W x H x D) Net Weight

Row × Column × FPI Body Decorative Panel

CMM cfm mmAq

kg (lbs)

Decorative Panel

kg (lbs) dB(A)+3 mm (inch)

Gas

mm (inch)

Dehumidification Rate

mm l/h

42/34/32/29/27 6.35(1/4) 15.88(5/8) 32 / 25 2.4 Fuse, Thermal Protector Thermistor R22

Safety Devices Temperature Sensor Referigerant Referigerant Control

Capillary

Connectable Outdoor Unit Power and Transmission Interunit Cable

220/450

26(57.3) 5(11) Long Life Filter

Liquid Drain(OD/ID)

23/22/20/18/16 812/777/706/636/565

Direct 2R x 9C x 18 mm(inch) 840x840x225(33.1x33.1x8.9) mm(inch) 950x950x30(37.4x37.4x1.2)

Air Filter

Piping Connections

22/17/15/13/12 778/600/530/459/424 -

µF / Vac

Body

Sound Level (SH / H / M / L / SL)

Turbo Fan 100x1

0.3 BLDC Turbo fan 100x1

BLDC

Fan Type Air Flow Rate (SH / H / M / L / SL)

8.8

No.×mm

2

HTUC246HLA1 4x0.75

HTNC368DLA0

3/380-415/50 10.6 36, 000 -

0.4 BLDC Turbo fan 124x1 37/27/21/20/17 1,307/954/742/706/600

-

680 / 400 220/450 Direct Direct 2R x 12C x 19 2R x 9C x 18 840x840x225(33.1x33.1x8.9) 840x840x288(33.1x33.1x11.3) 950x950x30(37.4x37.4x1.2) 950x950x30(37.4x37.4x1.2) 33(72.7) 26(57.3) 5(11) 5(11) Long Life Filter Long Life Filter 51/44/39/38/35 44/42/40/37/35 6.35(1/4) 6.35(1/4) 15.88(5/8) 15.88(5/8) 32 / 25 32 / 25 3. 8 3.4 Fuse, Thermal Protector Fuse, Thermal Protector Thermistor Thermistor R22 R22 Capillary Capillary HTUC368DLA0 HTUC306HLA0 4x0.75 4x0.75

Note : 1. Capacities are based on the following conditions: Cooling: - Indoor Temperature 27℃(80.6℉) DB/19℃(66.2℉) WB - Outdoor Temperature 35℃(95℉) DB/24℃(75.2℉) WB Heating: - Indoor Temperature 20℃(68℉) DB/15℃(59℉) WB - Outdoor Temperature 7℃(44.6℉) DB/6℃(42.8℉) WB Piping Length - Interconnecting Piping Length 7.5m - Level Difference of Zero 2. Wiring cable size must comply with the applicable local and national code. 3. The specification may be subject to change without prior notice for purpose of improvement.

2008 Product Data

13


Model No : HTNC368DLA1,HTN488DLA0,HTNC488DLA1

Indoor Unit Power Supply Cooling Capacity

kW

Heating Capacity Current

HTNC368DLA1 Ø / V / Hz

Dimensions (W x H x D) Net Weight

Row × Column × FPI Body Decorative Panel Body Decorative Panel

Air Filter Sound Level (SH / H / M / L / SL) Piping Connections

Liquid Gas Drain(OD/ID)

Dehumidification Rate

-

-

-

-

-

A

0.4 BLDC Turbo fan

0.4 BLDC

0.4 BLDC Turbo fan

Turbo fan 124x1 43/36/31/27/23

124x1 43/36/31/27/23

1,519/1,271/1,095/954/812

1,519/1,271/1,095/954/812

124x1

CMM cfm

37/27/21/20/17 1,307/954/742/706/600

mmAq

-

µF / Vac

680 / 400 Direct 2R x 12C x 19

-

680 / 400 Direct

l/h

3. 8 Fuse, Thermal Protector Thermistor R22 Capillary

Temperature Sensor Referigerant Referigerant Control Connectable Outdoor Unit No.×mm

2

HTUC368DLA1 4x0.75

4.6 Fuse, Thermal Protector Thermistor R22 Capillary HTUC488DLA0 4x0.75

Note : 1. Capacities are based on the following conditions: Cooling: - Indoor Temperature 27℃(80.6℉) DB/19℃(66.2℉) WB - Outdoor Temperature 35℃(95℉) DB/24℃(75.2℉) WB Heating: - Indoor Temperature 20℃(68℉) DB/15℃(59℉) WB - Outdoor Temperature 7℃(44.6℉) DB/6℃(42.8℉) WB Piping Length - Interconnecting Piping Length 7.5m - Level Difference of Zero 2. Wiring cable size must comply with the applicable local and national code. 3. The specification may be subject to change without prior notice for purpose of improvement.

14 Ceiling cassette type (50Hz,R22)

-

680 / 400 Direct

2R x 12C x 19 2R x 12C x 19 mm(inch) 840x840x288(33.1x33.1x11.3) 840x840x288(33.1x33.1x11.3) 840x840x288(33.1x33.1x11.3) 950x950x30(37.4x37.4x1.2) mm(inch) 950x950x30(37.4x37.4x1.2) 950x950x30(37.4x37.4x1.2) 33(72.7) kg (lbs) 33(72.7) 33(72.7) 5(11) 5(11) kg (lbs) 5(11) Long Life Filter Long Life Filter Long Life Filter dB(A)+3 51/44/39/38/35 53/49/46/43/40 53/49/46/43/40 mm (inch) 6.35(1/4) 9.52(3/8) 9.52(3/8) mm (inch) 15.88(5/8) 19.05(3/4) 19.05(3/4) 32 / 25 mm 32 / 25 32 / 25

Safety Devices

Power and Transmission Interunit Cable

-

kW

Drive Coil

14.1 48,000

Btu/h

Motor Output(W) x No. of Unit

Capacitor

3/380-415/50

36, 000

Fan Type

External Static Pressure

HTNC488DLA1

3/380-415/50

Btu/h

Motor Type

Fan

HTNC488DLA0

14.1 48,000

Nominal Running Current

Air Flow Rate (SH / H / M / L / SL)

3/380-415/50 10.6

4.6 Fuse, Thermal Protector Thermistor R22 Capillary HTUC488DLA1 4x0.75


Model No : HTUC186HLA0,HTUC186HLA1,HTUC246HLA0 Outdoor unit Nominal Capacity (Min∼Rating∼Max) Nominal Input (Min∼Rating∼Max) Testing Combination Running Current(Rating) Starting Current Power Supply Power Supply Cable(Outdoor)

Cooling Heating Cooling Heating Cooling Heating Cooling/Heating

kW Btu/h kW Btu/h kW kW

Power and Transmission Cable(BD to Indoor) WxHxD

Net Weight Max. Number of Connectable Indoor Units Type Qty x Model Compressor (#1) Motor type Oil charge volume Oil Type Cycle A Charge (at 7.5m) Cycle B Charge (at 7.5m) Refrigerant Type Control Additional Refrigerant Charge (Rows x Column x FPI) × No. Heat Exchanger Defrosting Method Capacitor Drive Fan Discharge Direction(Side/Top) Air Flow Rate×No. of Fan Sound Level Sound Pressure Liquid(Cycle A) Gas(Cycle A) Piping Connections Liquid(Cycle B) Gas(Cycle B) High Pressure Gas Total Piping Max. Interunit Main Piping Piping Length Total Branch Piping Each Branch Piping Max. Elevation Outdoor Unit~Indoor Unit Difference Indoor Unit~Indoor Unit Cooling Operation Range (Outdoor) Heating

HTUC186HLA1

HTUC246HLA0

5.3

5.3

7.0

18,000

18,000 1.55

24,000 2.28 12.0 1/220~240/50

1.71

A A A Ø / V / Hz

7.75 1/220~240/50

7.75 1/220~240/50

2

3 × 1.5

2

4 × 0.75(Including Earth)

2

-

-

-

mm(inch)

870×655×320(34.2×25.8×12.6)

870×655×320(34.2×25.8×12.6)

870×655×320(34.2×25.8×12.6)

kg(lbs)

57(125)

51(112)

1 Rotary

1 Rotary

62(136) 1 Rotary

1 × QP325PBA

1 x QJ292PBA Induction 450

No.×mm

Power and Transmission Cable(Outdoor to Indoor or Outdoor to BD)

Dimensions

HTUC186HLA0

No.×mm No.×mm

Induction

cc

700 SUNISO 4GSI

g(oz) g(oz)

g/m

1,360 (48) R22 Capillary 25 (2R × 30C × 21FPI) × 1

(2R × 30C × 21FPI) × 1

56

6.35(1/4) 12.7(1/2)

30

30

10

10

C( F)

21 ~ 43 (69.8 ~ 93.2)

21 ~ 43 (69.8 ~ 93.2)

C( F)

-

-

CMM(cfm) dB(A)+3 mm(inch) mm(inch) mm(inch) mm(inch) mm(inch) m m m m m m o

-R22 Capillary 25

6.35(1/4) 12.7(1/2)

Direct Side

o

SUNISO 4GSI 1,100 (39)

6/370 Direct Side 52(1,836) × 1 56

㎌/Vac

6/370

3 × 1.5 4 × 0.75(Including Earth)

o o

52(1,836) × 1

3 × 2.5 4 × 0.75(Including Earth)

1 x QP407PAB Induction 700 NM56 or SUNISO 4GSI 1,440 (51) R22 Capillary 30 (2R x 28C x 18FPI) x 1 6/370 Direct Side 52(1,836) × 1 56 6.35(1/4) 15.88(5/8) 30 10 21 ~ 43 (69.8 ~ 93.2) -

Note : 1. Capacities are based on the following conditions: Cooling: - Indoor Temperature 27℃(80.6℉) DB/19℃(66.2℉) WB - Outdoor Temperature 35℃(95℉) DB/24℃(75.2℉) WB Heating: - Indoor Temperature 20℃(68℉) DB/15℃(59℉) WB - Outdoor Temperature 7℃(44.6℉) DB/6℃(42.8℉) WB Piping Length - Interconnecting Piping Length 7.5m '- Level Difference of Zero 2. Wiring cable size must comply with the applicable local and national code.

3. The specification may be subject to change without prior notice for purpose of improvement.

2008 Product Data

15


Model No: HTUC246HLA1,HTUC3306HLA0,HTUC368DLA0 Outdoor unit Nominal Capacity (Min∼Rating∼Max) Nominal Input (Min∼Rating∼Max) Testing Combination Running Current(Rating) Starting Current Power Supply Power Supply Cable(Outdoor)

Cooling Heating Cooling Heating Cooling Heating Cooling/Heating

A A A Ø / V / Hz No.×mm

Power and Transmission Cable(Outdoor to Indoor or Outdoor to BD)

Power and Transmission Cable(BD to Indoor) Dimensions

kW Btu/h kW Btu/h kW kW

WxHxD

Net Weight Max. Number of Connectable Indoor Units Type Qty x Model Compressor (#1) Motor type Oil charge volume Oil Type Cycle A Charge (at 7.5m) Cycle B Charge (at 7.5m) Refrigerant Type Control Additional Refrigerant Charge (Rows x Column x FPI) × No. Heat Exchanger Defrosting Method Capacitor Drive Fan Discharge Direction(Side/Top) Air Flow Rate×No. of Fan Sound Level Sound Pressure Liquid(Cycle A) Gas(Cycle A) Piping Connections Liquid(Cycle B) Gas(Cycle B) High Pressure Gas Total Piping Max. Interunit Main Piping Piping Length Total Branch Piping Each Branch Piping Max. Elevation Outdoor Unit~Indoor Unit Difference Indoor Unit~Indoor Unit Cooling Operation Range (Outdoor) Heating

No.×mm

2 2 2

HTUC246HLA1

HTUC306HLA0

HTUC368DLA0

7.0

8.8 30,000

10.6 36,000 3.50

24,000 2.33 11.0 1/220~240/50 3 × 2.5 4 × 0.75(Including Earth)

15.0

6.0

1/220~240/50

3/380~415/50

3 × 2.5 4 × 0.75(Including Earth)

4 × 4.0 4 × 0.75(Including Earth)

-

-

-

mm(inch)

870×655×320(34.2×25.8×12.6)

870×800×320(34.2×31.4×12.6)

900×1,160×370(35.4×45.7×14.6)

kg(lbs)

62(136) 1 Rotary

73(160)

81(178) 1

1 x QP407PAB

1 x NHT52VBAT Induction 1,300

No.×mm

cc

Induction 700 NM56 or SUNISO 4GSI

g(oz) g(oz)

g/m

㎌/Vac

CMM(cfm) dB(A)+3 mm(inch) mm(inch) mm(inch) mm(inch) mm(inch) m m m m m m o o

1 Rotary

DIAMOND MS56

1,520 (53.6) R22 Capillary 30

2,000 (70.5)

(2R x 28C x 18FPI) x 1 6/370 Direct Side

(2R x 36C x 18FPI) x 1

52(1,836) × 1 53 6.35(1/4) 15.88(5/8) 30

-R22 Capillary 40 6/370 Direct Side 53(1,873.5) × 1 54 6.35(1/4) 15.88(5/8) 30

10

10

C( F)

21 ~ 43 (69.8 ~ 93.2)

21 ~ 43 (69.8 ~ 93.2)

C( F)

-

-

o o

Note : 1. Capacities are based on the following conditions: Cooling: - Indoor Temperature 27℃(80.6℉) DB/19℃(66.2℉) WB - Outdoor Temperature 35℃(95℉) DB/24℃(75.2℉) WB Heating: - Indoor Temperature 20℃(68℉) DB/15℃(59℉) WB - Outdoor Temperature 7℃(44.6℉) DB/6℃(42.8℉) WB Piping Length - Interconnecting Piping Length 7.5m '- Level Difference of Zero 2. Wiring cable size must comply with the applicable local and national code.

3. The specification may be subject to change without prior notice for purpose of improvement.

16 Ceiling Cassette Type (50Hz,R22)

3.05

Scroll 1 x SQ042YAA Induction 1,300 SUNISO 4GSI 2,000 (70.5) R22 Capillary 40 (1R x 22C x 17FPI) x 2 6/370 Direct Side 53(1,873.5) × 1 58 6.35(1/4) 15.88(5/8) 30 15 21 ~ 43 (69.8 ~ 93.2) -


Model No: HTUC368DLA1,HTUC488DLA0,HTUC488DLA1 Outdoor unit Nominal Capacity (Min∼Rating∼Max) Nominal Input (Min∼Rating∼Max) Testing Combination Running Current(Rating) Starting Current Power Supply Power Supply Cable(Outdoor)

Cooling Heating Cooling Heating Cooling Heating Cooling/Heating

A A A Ø / V / Hz No.×mm

Power and Transmission Cable(Outdoor to Indoor or Outdoor to BD)

Power and Transmission Cable(BD to Indoor) Dimensions

kW Btu/h kW Btu/h kW kW

WxHxD

Net Weight Max. Number of Connectable Indoor Units Type Qty x Model Compressor (#1) Motor type Oil charge volume Oil Type Cycle A Charge (at 7.5m) Cycle B Charge (at 7.5m) Refrigerant Type Control Additional Refrigerant Charge (Rows x Column x FPI) × No. Heat Exchanger Defrosting Method Capacitor Drive Fan Discharge Direction(Side/Top) Air Flow Rate×No. of Fan Sound Level Sound Pressure Liquid(Cycle A) Gas(Cycle A) Piping Connections Liquid(Cycle B) Gas(Cycle B) High Pressure Gas Total Piping Max. Interunit Main Piping Piping Length Total Branch Piping Each Branch Piping Max. Elevation Outdoor Unit~Indoor Unit Difference Indoor Unit~Indoor Unit Cooling Operation Range (Outdoor) Heating

No.×mm No.×mm

2 2 2

HTUC368DLA1

HTUC488DLA0

HTUC488DLA1

10.6 36,000

14.1 48,000

14.1 48,000

-

-

-

3.93

5.0

4.9

-

-

-

7.0

8.5

8.5

-

-

-

3 / 380 ~ 415 / 50 4 × 4.0 4 × 0.75(Including Earth)

-

mm(inch)

870×800×320(34.2×31.4×12.6)

kg(lbs)

79(173) 1

cc g(oz) g(oz)

g/m

CMM(cfm) dB(A)+3 mm(inch) mm(inch) mm(inch) mm(inch) mm(inch) m m m m m m o o

o

C( F) o

C( F)

4 × 4.0

4 × 0.75(Including Earth)

4 × 0.75(Including Earth)

-

-

900×1,160×370(35.4×45.7×14.6) 900×1,160×370(35.4×45.7×14.6)

87(192) 1

Scroll

Scroll 1 x SB061YAA Induction 1,650

SUNISO 4GSI

SUNISO 4GSI

2,100(74)

R22 Capillary 60 (2R x 30C x 17FPI) x 1

3 / 380 ~ 415 / 50

4 × 4.0

1 x SR049YAA Induction 1,800

-

㎌/Vac

3 / 380 ~ 415 / 50

2,600(92)

87(192) 1 Scroll 1 x SB061YAA Induction 1,650 SUNISO 4GSI 2,600(92)

--

R22 Capillary 60 (2R x 26C x 18FPI) x 2

R22 Capillary 50 (2R x 26C x 18FPI) x 2

-

-

6/370 Direct Side 53(1,873.5) × 1 54 6.35(1/4) 15.88(5/8)

6/370 Direct Side 53(1,873.5) × 2

6/370 Direct Side 53(1,873.5) × 2

59 9.52(3/8) 19.05(6/8)

59 9.52(3/8) 19.05(6/8)

-

-

-

50

30

50

15

15

-

-

-

21~ 43 (69.8~93.2)

-

-

-

21~ 43 (69.8~93.2)

15

-

21~ 43 (69.8~93.2)

-

-

Note : 1. Capacities are based on the following conditions: Cooling: - Indoor Temperature 27℃(80.6℉) DB/19℃(66.2℉) WB - Outdoor Temperature 35℃(95℉) DB/24℃(75.2℉) WB Heating: - Indoor Temperature 20℃(68℉) DB/15℃(59℉) WB - Outdoor Temperature 7℃(44.6℉) DB/6℃(42.8℉) WB Piping Length - Interconnecting Piping Length 7.5m '- Level Difference of Zero 2. Wiring cable size must comply with the applicable local and national code.

3. The specification may be subject to change without prior notice for purpose of improvement.

2008

17


6. Dimensional Drawings 6.1 Indoor Units Model No : HTNC186HLA0,HTNC186HLA1,HTNC246HLA0,HTNC246HLA1,HTNC306HLA0, HTNC368DLA0, HTNC368DLA1,HTNC488DLA0,HTNC488DLA1

875 (Ceiling opening) 785(Hanging bolt)

L1 950

840 Unit size 840 Unit size

950 950 5

875 (Ceiling opening)

45

101.5 672 (Hanging bolt) 101.5

45

Unit:mm

840

785

840

950

678

30

6

(unit : mm)

L1

L2

L3

L5

1

140

L4

288

47

90

HTNC368DLA0 HTNC368DLA1 HTNC488DLA0 HTNC488DLA1

84

90

70.4 139.8

3

210.5 152

52

: mm)

Descripition Number

Name

1 2

Liquid pipe connection Gas pipe connection

3 4

Drain pipe connection Power supply connection

5

Air discharge grille

6

Air suction grille

18 Ceiling Cassette (50Hz,R22)

HTNC186HLA0, HTNC246HLA0, HTNC368DLA0 HTNC306HLA0, HTNC186HLA1 HTNC246HLA1 HTNC368DLA1

ø 6.35 ø 12.70 -

ø 6.35 ø 15.88 -

ø 6.35 ø 15.88 -

ø 6.35 ø 15.88

2

110

L2 L5

225

L1

110

HTNC186HLA0 HTNC186HLA1 HTNC246HLA0 HTNC246HLA1 HTNC306HLA0

(unit

L4

30

Model

40

4

-

HTNC488DLA0 HTNC488DLA1

ø 9.52 ø 19.05

-

L3

Dimension


6. Dimensional Drawings 6.2 Outdoor Units Model No : HTUC186HLA0,HTUC186HLA1,HTUC246HLA0,HTUC246HLA1, HTU306HLA0,HTUC368DLA1 W

Air discharge grille

(18k,24k) (30k)

Model Dimensions W mm H mm D mm L1 mm L2 mm L3 mm L4 mm L5 mm L6 mm L7 mm L8 mm L9 mm L10 mm L11 mm 1 mm 2 mm

HTUC186HLA0 HTUC246HLA0 HTUC186HLA1 HTUC246HLA1 870 655 320 370 25 340 775 25 546 162 162 54 74.5 79 Ø6.35 Ø12.70

870 655 320 370 25 340 775 25 546 162 162 54 74.5 79 Ø6.35 Ø15.88

HTUC306HLA0 HTUC368DLA1 870 800 320 370 25 340 775 25 546 162 162 54 74. 5 79 Ø6.35 Ø15.88

2008 Product Data

19


6. Dimensional Drawings Model : HTUC368DLA0, HTUC488DLA0,HTUC488DLA1 4-hole for anchor bolts

L1

L2

D

L3

W

L4

H

Control cover

Liquid side 3-way valve

L5

L10 L11

Gas side 3-way valve

L7

L6

Mdel Dimensions W mm H mm D mm L1 mm L2 mm L3 mm L4 mm L5 mm L6 mm L7 mm L8 mm L9 mm L10 mm L11 mm mm 1 2 mm

20 Ceiling Cassette(50Hz,R22)

L8

L9

HTUC368DLA0

900 1,160 370 460 45 410 1,135 30 550 175 175 112 120 83 Ø6.35 Ø15.88

HTUC488DLA0 HTUC488DLA1

900 1,160 370 460 45 410 1,135 30 550 175 175 112 120 83 Ø9.52 Ø19.05


7. Wiring Diagrams 7.1 Indoor Wiring Diagrams Model No : HTNC186HLA0, HTNC186HLA1, HTNC246HLA0, HTNC246HLA1, HTNC306HLA0

Option

CONNECTOR NUMBER

LOCATION

CN-POWER

AC POWER SUPPLY

CN-MOTOR

BLDC FAN MOTOR OUTPUT

CN-D/PUMP

DRAIN PUMP OUTPUT

CN-DISP

DISPLAY

CN-FLOAT

FLOAT SWITCH INPUT

CN-REMO

REMOTE CONTROL

CN-GRILLE

ELEVATION TWILLE

CN-CC

CENTRAL CONTROL

CN-PIPE1

DISCHARGE PIPE SENSOR

CN-ROOM

ROOM SENSOR

CN-HVB

AIR CLEANER

CN-VANE1

STEP MOTOR

CN-VANE2

STEP MOTOR

2008 Product Data

21


7. Wiring Diagrams Model No : HTNC368DLA0,HTNC368DLA1,HTNC488DLA0,HTNC488DLA1

Option

CONNECTOR NUMBER

LOCATION

CN-POWER

AC POWER SUPPLY

CN-MOTOR

BLDC FAN MOTOR OUTPUT

CN-D/PUMP

DRAIN PUMP OUTPUT

CN-DISP

DISPLAY

CN-FLOAT

FLOAT SWITCH INPUT

CN-REMO

REMOTE CONTROL

CN-GRILLE

ELEVATION TWILLE

CN-CC

CENTRAL CONTROL

CN-PIPE1

DISCHARGE PIPE SENSOR

CN-ROOM

ROOM SENSOR

CN-HVB

AIR CLEANER

CN-VANE1

STEP MOTOR

CN-VANE2

STEP MOTOR

22 Ceiling Cassette(50Hz,R22)


7. Wiring Diagrams 7.2 Outdoor Wiring Diagrams Model No : HTUC186HLA0, HTUC186HLA1, HTUC246HLA0, HTUC246HLA1

Model No : HTUC368DLA1

Model No : HTUC306HLA0

OUTDOOR WIRING DIAGRAM

Notes: CM BR WH

COMPRESSOR BROWN WHITE

BL OR YL

BLUE ORANGE YELLOW

BK RD GN/YL

BLACK RED GREEN/YELLOW

2008 Product Data

23


7. Wiring Diagrams Model No : HTUC368DLA0, HTUC488DLA0

(U)

(V)

Model No : HTUC488DLA1

(W)

3854A20072Z

Notes: CM BR WH

COMPRESSOR BROWN WHITE

24 Ceiling Cassette(50Hz,R22)

BL OR YL

BLUE ORANGE YELLOW

BK RD GN/YL

BLACK RED GREEN/YELLOW


8. Refrigerant Cycle Diagrams Model No: HT-C186HLA0 , HT-C186HLA1, HT-C246HLA0 ,HT-C246HLA1, HT-C306HLA0 , HT-C368DLA0, HT-C368DLA1, HT-C488DLA0, HT-C488DLA1 INDOOR UNIT

OUTDOOR UNIT

CAPILLARY TUBE

INDOOR COIL

LIQUID SIDE CAPILLARY TUBE

OUTDOOR COIL

Th1

Th2

COMPRESSOR

GAS SIDE

COOLING

Th1 : Temp. thermistor Th2 : Pipe in thermistor

Refrigerant pipe connection part diameter

Model

Field Piping

Gas(mm)

Liquid(mm)

HT-C186HLA0,HT-C186HLA1

Ø12.70

Ø6.35

HT-C246HLA0,HT-C246HLA1

Ø15.88

Ø6.35

HT-C306HLA0

Ø15.88

Ø6.35

HT-C368DLA0,HT-C368DLA1

Ø15.88

Ø6.35

HT-C488DLA0,HT-C488DLA1

Ø19.05

Ø9.52

2008 Product Data

25


9. Selection Procedure Step 1. Determine cooling load requirements at design conditions. Required load conditions: Required cooling capacity (TC) .............................. 24,000 Btu/h Sensible capacity (SHC) ........................................ 20,200 Btu/h Temperature air entering Outdoor Unit ................. 95°F Temperature air entering Indoor Unit ..................... 80.6 °F DB/66.2°FWB DB — dry bulb temperature WB — wet bulb temperature Step 2. Select unit based on required cooling capacity. Based on Total Cooling Capacity, choose suitable model from the specification table. The model with net cooling capacity of 24,000 Btu/h is selected. The system is HT-C246HLA0. Verify the unit performance at the given conditions in accordance with step 3. Step 3. Determine if system selected satisfies cooling requirements. Enter cooling capacities table on page 30 at high speed and 95°F outdoor entering air temperature with 80.6°FDB/66.2°FWB indoor entering air temperature. Total cooling capacity = 24,000 Btu/h, Sensible capacity=20,200 Btu/h To find capacity at intermediate conditions not in the table ; Interpolation should be used when design conditions are between two numbers that are in the capacity table. Extra-polation is not recommended. If the interconnecting piping length is more than 7.5 m ; Find the capacity(%) at that particular interconnecting piping length from the coefficient of capacity change graph, on page 33. . Multiply coefficient factor with Total Cooling Capacity & Sensible Capacity. Ex: At 30m interconnecting piping length, from coefficient of capacity change graph, coeffienct factor is 0.915.

Total Cooling Capacity =

Capacity (%) x Total Cooling Capacity 91.5x24,000 = = 21,960 Btu/h 100 100

91.5x19,300 Sensible Capacity = Capacity (%) x Sensible Capacity = = 18,483 Btu/h 100 100

26 Ceiling Cassette(50Hz,R22)


10. Performance Data Cooling Capacity(SI Unit) Model No : HT-C186HLA0 Indoor Air Temperature °CWB °CDB 14 20 16 22 18 25 19 27 22 30 24 32

TC 4.3 5.0 5.6 5.8 6.4 6.6

20 SHC 3.5 4.0 4.4 4.5 4.8 4.9

PI 1.12 1.14 1.16 1.17 1.2 1.2

TC 4.2 4.9 5.5 5.7 6.3 6.5

25 SHC 3.5 4.0 4.3 4.5 4.7 4.8

PI 1.3 1.3 1.4 1.4 1.4 1.4

Outdoor Air Temperature (°CDB) 32 35 TC SHC PI TC SHC PI 4.0 3.4 1.5 3.9 3.3 1.6 4.7 3.9 1.6 4.5 3.8 1.7 5.2 4.2 1.6 5.0 4.1 1.7 5.4 4.3 1.6 5.3 4.2 1.7 6.0 4.6 1.6 5.8 4.5 1.7 6.2 4.6 1.7 6.0 4.5 1.8

TC 3.7 4.3 4.9 5.1 5.6 5.8

40 SHC 3.3 3.7 4.0 4.1 4.3 4.4

PI 1.7 1.8 1.8 1.8 1.8 1.9

TC 3.6 4.2 4.7 5.0 5.4 5.7

43 SHC 3.2 3.6 3.9 4.0 4.3 4.3

PI 1.8 1.8 1.8 1.9 1.9 1.9

PI 1.2 1.2 1.2 1.3 1.3 1.3

Outdoor Air Temperature (°CDB) 32 35 TC SHC PI TC SHC PI 4.0 3.6 1.4 3.9 3.5 1.5 4.7 4.0 1.4 4.5 4.0 1.5 5.2 4.4 1.4 5.0 4.3 1.5 5.4 4.5 1.5 5.3 4.4 1.6 6.0 4.8 1.5 5.8 4.7 1.6 6.2 4.9 1.5 6.0 4.7 1.6

TC 3.7 4.3 4.9 5.1 5.6 5.8

40 SHC 3.4 3.9 4.2 4.3 4.6 4.6

PI 1.6 1.6 1.6 1.6 1.7 1.7

TC 3.6 4.2 4.7 5.0 5.4 5.7

43 SHC 3.4 3.8 4.1 4.2 4.5 4.5

PI 1.6 1.6 1.7 1.7 1.7 1.8

PI 1.8 1.8 1.8 1.9 1.9 1.9

Outdoor Air Temperature (°CDB) 32 35 TC SHC PI TC SHC PI 5.3 4.8 2.1 5.2 4.7 2.2 6.2 5.4 2.1 6.0 5.3 2.2 6.9 5.9 2.1 6.7 5.7 2.2 7.3 6.0 2.2 7.0 5.9 2.3 8.0 6.4 2.2 7.7 6.2 2.3 8.3 6.5 2.2 8.0 6.3 2.3

Model No : HT-C186HLA1 Indoor Air Temperature °CWB °CDB 14 20 16 22 18 25 19 27 22 30 24 32

TC 4.3 5.0 5.6 5.8 6.4 6.6

20 SHC 3.7 4.2 4.6 4.7 5.0 5.1

PI 1.02 1.03 1.05 1.06 1.1 1.1

TC 4.2 4.9 5.5 5.7 6.3 6.5

25 SHC 3.7 4.2 4.5 4.7 5.0 5.0

Model No : HT-C246HLA0 Indoor Air Temperature °CWB °CDB 14 20 16 22 18 25 19 27 22 30 24 32

TC 5.7 6.7 7.4 7.8 8.5 8.9

20 SHC 4.9 5.6 6.1 6.3 6.7 6.8

PI 1.49 1.52 1.54 1.57 1.6 1.6

TC 5.6 6.5 7.3 7.6 8.3 8.7

25 SHC 4.9 5.6 6.0 6.2 6.6 6.7

TC 5.0 5.8 6.5 6.8 7.4 7.7

40 SHC 4.6 5.2 5.6 5.8 6.1 6.1

PI 2.3 2.3 2.4 2.4 2.5 2.5

TC 4.9 5.7 6.3 6.6 7.3 7.5

43 SHC 4.5 5.1 5.5 5.7 6.0 6.0

PI 2.4 2.4 2.5 2.5 2.5 2.6

43 SHC 4.2 4.8 5.2 5.3 5.6 5.7

PI 2.44 2.48 2.52 2.56 2.59 2.63

Model No : HT-C246HLA1 Indoor Air Temperature °CWB °CDB 14 20 16 22 18 25 19 27 22 30 24 32

TC 5.7 6.7 7.4 7.8 8.5 8.9

20 SHC 4.7 5.3 5.7 5.9 6.3 6.4

PI 1.53 1.55 1.57 1.60 1.62 1.64

TC 5.6 6.5 7.3 7.6 8.3 8.7

25 SHC 4.6 5.2 5.7 5.9 6.2 6.3

PI 1.81 1.84 1.87 1.90 1.92 1.95

◆Symbol AFR : Air Flow Rate [CMM] DB : Dry Bulb Temperature [°C] WB : Wet Bulb Temperature [°C] TC : Total Capacity [kW] SHC : Sensible Heating Capacity [kW] PI : Power Input [kW] (compressor + indoor fan motor + outdoor fan motor)

Outdoor Air Temperature (°CDB) 32 35 TC SHC PI TC SHC PI 5.3 4.5 2.11 5.2 4.4 2.22 6.2 5.1 2.14 6.0 5.0 2.26 6.9 5.5 2.17 6.7 5.4 2.29 7.3 5.7 2.21 7.0 5.6 2.33 8.0 6.0 2.24 7.7 5.9 2.36 8.3 6.1 2.27 8.0 5.9 2.39

TC 5.0 5.8 6.5 6.8 7.4 7.7

40 SHC 4.3 4.9 5.2 5.4 5.7 5.8

PI 2.36 2.40 2.44 2.48 2.51 2.55

TC 4.9 5.7 6.3 6.6 7.3 7.5

◆Notes 1. All capacites are net, evaporator fan motor heat is deducted. 2. Indicates rated capacity. 3. Direct interpolation is permissible. Do not extrapolate. 4. Capacities are based on the following conditions: - Interconnecting Piping Length 7.5m - Level Difference of Zero.

2008 Product Data

27


10. Performance Data Model No : HT-C306HLA0 Indoor Air Temperature °CWB °CDB 14 20 16 22 18 25 19 27 22 30 24 32

20 TC SHC 7.1 5.4 8.3 6.2 9.3 6.7 9.7 7.0 10.7 7.4 11.1 7.5

PI 2.00 2.03 2.06 2.10 2.1 2.2

25 TC SHC 7.0 5.4 8.1 6.1 9.1 6.7 9.5 6.9 10.4 7.3 10.8 7.4

PI 2.4 2.4 2.4 2.5 2.5 2.6

Outdoor Air Temperature 32 TC SHC PI TC 6.7 5.3 2.8 6.5 7.8 5.9 2.8 7.5 8.7 6.4 2.8 8.4 9.1 6.7 2.9 8.8 9.9 7.0 2.9 9.6 10.3 7.1 3.0 10.0

(°CDB) 35 SHC PI 5.1 2.9 5.8 3.0 6.3 3.0 6.5 3.1 6.9 3.1 7.0 3.1

40 43 TC SHC PI TC SHC 6.2 5.0 3.1 6.1 5.0 7.2 5.7 3.1 7.1 5.6 8.1 6.1 3.2 7.9 6.0 8.5 6.3 3.2 8.3 6.2 9.3 6.7 3.3 9.1 6.6 9.6 6.8 3.3 9.4 6.6

PI 3.2 3.2 3.3 3.4 3.4 3.4

Model No : HT-C368DLA0 Indoor Air Temperature °CWB °CDB 14 20 16 22 18 25 19 27 22 30 24 32

TC 8.6 10.0 11.1 11.7 12.8 13.3

20 SHC 7.2 8.2 8.9 9.3 9.8 10.0

PI 2.29 2.33 2.36 2.40 2.4 2.5

TC 8.4 9.8 10.9 11.4 12.5 13.0

25 SHC 7.2 8.1 8.8 9.1 9.7 9.8

PI 2.7 2.8 2.8 2.8 2.9 2.9

Outdoor Air Temperature (°CDB) 32 35 TC SHC PI TC SHC PI 8.0 7.0 3.2 7.7 6.8 3.3 9.3 7.9 3.2 9.0 7.7 3.4 10.4 8.6 3.3 10.1 8.4 3.4 10.9 8.9 3.3 10.6 8.7 3.5 11.9 9.4 3.4 11.6 9.1 3.5 12.4 9.5 3.4 12.0 9.3 3.6

TC 7.5 8.7 9.7 10.2 11.1 11.6

40 SHC 6.7 7.6 8.2 8.4 8.9 9.0

PI 3.6 3.6 3.7 3.7 3.8 3.8

TC 7.3 8.5 9.5 9.9 10.9 11.3

43 SHC 6.6 7.4 8.0 8.3 8.7 8.8

PI 3.7 3.7 3.8 3.8 3.9 4.0

Model No : HT-C368DLA1 Indoor Air Temperature °CWB °CDB 14 20 16 22 18 25 19 27 22 30 24 32

TC 8.6 10.0 11.1 11.7 12.8 13.3

20 SHC 7.5 8.5 9.3 9.6 10.2 10.3

PI 2.57 2.61 2.65 2.70 2.7 2.8

TC 8.4 9.8 10.9 11.4 12.5 13.0

25 SHC 7.4 8.4 9.2 9.5 10.0 10.2

PI 3.0 3.1 3.1 3.2 3.2 3.3

◆Symbol AFR : Air Flow Rate [CMM] DB : Dry Bulb Temperature [°C] WB : Wet Bulb Temperature [°C] TC : Total Capacity [kW] SHC : Sensible Heating Capacity [kW] PI : Power Input [kW] (compressor + indoor fan motor + outdoor fan motor)

28 Ceiling Cassette(50Hz, R22)

Outdoor Air Temperature (°CDB) 32 35 TC SHC PI TC SHC 8.0 7.2 3.6 7.7 7.1 9.3 8.2 3.6 9.0 8.0 10.4 8.9 3.7 10.1 8.7 10.9 9.2 3.7 10.6 9.0 11.9 9.7 3.8 11.6 9.5 12.4 9.8 3.8 12.0 9.6

PI TC 3.74 7.5 3.80 8.7 3.86 9.7 3.93 10.2 3.98 11.1 4.03 11.6

40 SHC 6.9 7.8 8.5 8.7 9.2 9.3

PI 4.0 4.0 4.1 4.2 4.2 4.3

43 TC SHC PI 7.3 6.8 4.1 8.5 7.7 4.2 9.5 8.3 4.2 9.9 8.6 4.3 10.9 9.0 4.4 11.3 9.2 4.4

◆Notes 1. All capacites are net, evaporator fan motor heat is deducted. 2. Indicates rated capacity. 3. Direct interpolation is permissible. Do not extrapolate. 4. Capacities are based on the following conditions: - Interconnecting Piping Length 7.5m - Level Difference of Zero.


10. Performance Data Cooling Capacity(SI Unit) Model No : HT-C488DLA0 Indoor Air Temperature °CWB °CDB 14 20 16 22 18 25 19 27 22 30 24 32

TC 11.4 13.3 14.9 15.5 17.1 17.7

20 SHC 9.1 10.3 11.2 11.6 12.3 12.5

PI 3.28 3.33 3.38 3.43 3.5 3.5

TC 11.2 13.0 14.5 15.2 16.7 17.3

25 SHC 9.0 10.2 11.1 11.4 12.1 12.3

PI 3.9 3.9 4.0 4.1 4.1 4.2

Outdoor Air Temperature (°CDB) 32 35 TC SHC PI TC SHC PI 10.6 8.7 4.5 10.3 8.6 4.8 12.4 9.9 4.6 12.0 9.7 4.8 13.9 10.7 4.7 13.4 10.5 4.9 14.5 11.1 4.7 14.1 10.8 5.0 15.9 11.7 4.8 15.4 11.4 5.1 16.5 11.9 4.9 16.0 11.6 5.1

TC 9.9 11.6 12.9 13.5 14.9 15.4

40 SHC 8.4 9.5 10.2 10.6 11.1 11.3

PI 5.1 5.2 5.2 5.3 5.4 5.5

TC 9.7 11.3 12.6 13.2 14.5 15.1

43 SHC 8.3 9.3 10.1 10.4 10.9 11.1

PI 5.2 5.3 5.4 5.5 5.6 5.6

Model No : HT-C488DLA1 Indoor Air Temperature °CWB °CDB 14 20 16 22 18 25 19 27 22 30 24 32

TC 11.4 13.3 14.9 15.5 17.1 17.7

20 SHC 9.2 10.4 11.3 11.7 12.4 12.6

PI 3.21 3.26 3.31 3.37 3.4 3.5

TC 11.2 13.0 14.5 15.2 16.7 17.3

25 SHC 9.1 10.3 11.2 11.6 12.3 12.5

PI 3.8 3.9 3.9 4.0 4.0 4.1

Outdoor Air Temperature (°CDB) 32 35 TC SHC PI TC SHC 10.6 8.9 4.4 10.3 8.7 12.4 10.0 4.5 12.0 9.8 13.9 10.9 4.6 13.4 10.6 14.5 11.2 4.7 14.1 11.0 15.9 11.9 4.7 15.4 11.6 16.5 12.0 4.8 16.0 11.7

◆Symbol AFR : Air Flow Rate [CMM] DB : Dry Bulb Temperature [°C] WB : Wet Bulb Temperature [°C] TC : Total Capacity [kW] SHC : Sensible Heating Capacity [kW] PI : Power Input [kW] (compressor + indoor fan motor + outdoor fan motor)

PI 4.7 4.7 4.8 4.9 5.0 5.0

TC 9.9 11.6 12.9 13.5 14.9 15.4

40 SHC 8.5 9.6 10.4 10.7 11.3 11.4

PI 5.0 5.0 5.1 5.2 5.3 5.4

TC 9.7 11.3 12.6 13.2 14.5 15.1

43 SHC 8.4 9.4 10.2 10.5 11.1 11.2

PI 5.1 5.2 5.3 5.4 5.5 5.5

◆Notes 1. All capacites are net, evaporator fan motor heat is deducted. 2. Indicates rated capacity. 3. Direct interpolation is permissible. Do not extrapolate. 4. Capacities are based on the following conditions: - Interconnecting Piping Length 7.5m - Level Difference of Zero.

2008 Product Data

29


10. Performance Data Cooling Capacity(English Units) Model No : HT-C186HLA0 Indoor Air Temperature °FWB °FDB 57.2 68.0 60.8 71.6 64.4 77.0 66.2 80.6 71.6 86.0 75.2 89.6

TC 14.6 17.0 19.0 19.9 21.8 22.7

68.0 SHC 12.1 13.7 14.9 15.4 16.3 16.6

PI 1.12 1.14 1.16 1.17 1.2 1.2

TC 14.3 16.7 18.6 19.5 21.4 22.2

77.0 SHC 12.0 13.6 14.7 15.2 16.1 16.4

PI 1.3 1.3 1.4 1.4 1.4 1.4

Outdoor Air Temperature (°FDB) 89.6 95.0 TC SHC PI TC SHC PI 13.6 11.6 1.5 13.2 11.4 1.6 15.9 13.2 1.6 15.4 12.9 1.7 17.7 14.3 1.6 17.2 14.0 1.7 18.6 14.7 1.6 18.0 14.4 1.7 20.4 15.6 1.6 19.8 15.2 1.7 21.1 15.8 1.7 20.5 15.4 1.8

TC 12.7 14.8 16.6 17.3 19.0 19.7

104.0 SHC 11.1 12.6 13.6 14.0 14.8 15.0

PI 1.7 1.8 1.8 1.8 1.8 1.9

TC 12.4 14.5 16.2 16.9 18.6 19.3

109.4 SHC 11.0 12.4 13.4 13.8 14.5 14.7

PI 1.8 1.8 1.8 1.9 1.9 1.9

PI 1.2 1.2 1.2 1.3 1.3 1.3

Outdoor Air Temperature (°FDB) 89.6 95.0 TC SHC PI TC SHC PI 13.6 12.2 1.4 13.2 12.0 1.5 15.9 13.8 1.4 15.4 13.5 1.5 17.7 15.0 1.4 17.2 14.7 1.5 18.6 15.5 1.5 18.0 15.1 1.6 20.4 16.4 1.5 19.8 16.0 1.6 21.1 16.6 1.5 20.5 16.2 1.6

TC 12.7 14.8 16.6 17.3 19.0 19.7

104.0 SHC 11.7 13.2 14.3 14.7 15.5 15.7

PI 1.6 1.6 1.6 1.6 1.7 1.7

TC 12.4 14.5 16.2 16.9 18.6 19.3

109.4 SHC 11.5 13.0 14.1 14.5 15.3 15.4

PI 1.6 1.6 1.7 1.7 1.7 1.8

PI 1.8 1.8 1.8 1.9 1.9 1.9

Outdoor Air Temperature (°FDB) 89.6 95.0 TC SHC PI TC SHC PI 18.2 16.3 2.1 17.6 15.9 2.2 21.2 18.4 2.1 20.6 18.0 2.2 23.6 20.0 2.1 22.9 19.5 2.2 24.7 20.6 2.2 24.0 20.2 2.3 27.1 21.8 2.2 26.3 21.3 2.3 28.2 22.1 2.2 27.3 21.6 2.3

TC 17.0 19.8 22.1 23.1 25.4 26.3

104.0 SHC 15.6 17.6 19.0 19.6 20.7 21.0

PI 2.3 2.3 2.4 2.4 2.5 2.5

TC 16.6 19.3 21.6 22.6 24.8 25.7

109.4 SHC 15.4 17.3 18.7 19.3 20.3 20.6

PI 2.4 2.4 2.5 2.5 2.5 2.6

109.4 SHC 14.5 16.3 17.6 18.2 19.1 19.4

PI 2.44 2.48 2.52 2.56 2.59 2.63

Model No : HT-C186HLA1 Indoor Air Temperature °FWB °FDB 57.2 68.0 60.8 71.6 64.4 77.0 66.2 80.6 71.6 86.0 75.2 89.6

TC 14.6 17.0 19.0 19.9 21.8 22.7

68.0 SHC 12.7 14.4 15.6 16.2 17.1 17.4

PI 1.02 1.03 1.05 1.06 1.1 1.1

TC 14.3 16.7 18.6 19.5 21.4 22.2

77.0 SHC 12.5 14.2 15.5 16.0 16.9 17.2

Model No : HT-C246HLA0 Indoor Air Temperature °FWB °FDB 57.2 68.0 60.8 71.6 64.4 77.0 66.2 80.6 71.6 86.0 75.2 89.6

TC 19.5 22.7 25.3 26.5 29.1 30.2

68.0 SHC 16.9 19.2 20.8 21.6 22.9 23.2

PI 1.49 1.52 1.54 1.57 1.6 1.6

TC 19.1 22.2 24.8 26.0 28.5 29.6

77.0 SHC 16.7 19.0 20.6 21.3 22.6 22.9

Model No : HT-C246HLA1 Indoor Air Temperature °FWB °FDB 57.2 68.0 60.8 71.6 64.4 77.0 66.2 80.6 71.6 86.0 75.2 89.6

TC 19.5 22.7 25.3 26.5 29.1 30.2

68.0 SHC 15.9 18.0 19.6 20.3 21.5 21.9

PI 1.53 1.55 1.57 1.60 1.62 1.64

TC 19.1 22.2 24.8 26.0 28.5 29.6

77.0 SHC 15.7 17.8 19.4 20.0 21.2 21.6

PI 1.81 1.84 1.87 1.90 1.92 1.95

Outdoor Air Temperature (°FDB) 89.6 95.0 TC SHC PI TC SHC PI 18.2 15.3 2.11 17.6 15.0 2.22 21.2 17.3 2.14 20.6 17.0 2.26 23.6 18.8 2.17 22.9 18.4 2.29 24.7 19.4 2.21 24.0 19.0 2.33 27.1 20.5 2.24 26.3 20.0 2.36 28.2 20.8 2.27 27.3 20.3 2.39

◆Symbol AFR : Air Flow Rate [CFM] DB : Dry Bulb Temperature [°F] WB : Wet Bulb Temperature [°F] TC : Total Capacity [kBtu/h] SHC : Sensible Heating Capacity [kBtu/h] PI : Power Input [kW] (compressor + indoor fan motor + outdoor fan motor)

30 Ceiling Cassette (50Hz,R22)

TC 17.0 19.8 22.1 23.1 25.4 26.3

104.0 SHC 14.7 16.6 17.9 18.5 19.5 19.7

PI 2.36 2.40 2.44 2.48 2.51 2.55

TC 16.6 19.3 21.6 22.6 24.8 25.7

◆Notes 1. All capacites are net, evaporator fan motor heat is deducted. 2. Indicates rated capacity. 3. Direct interpolation is permissible. Do not extrapolate. 4. Capacities are based on the following conditions: - Interconnecting Piping Length 24.6ft - Level Difference of Zero.


10. Performance Data Cooling Capacity(English Units)

Model No : HT -C306HLA0 Indoor Air Temperature °FWB °FDB 57.2 68.0 60.8 71.6 64.4 77.0 66.2 80.6 71.6 86.0 75.2 89.6

TC 24.3 28.4 31.7 33.2 36.4 37.8

68.0 SHC 18.6 21.1 23.0 23.7 25.2 25.6

PI 2.00 2.03 2.06 2.10 2.12 2.15

TC 23.8 27.8 31.0 32.5 35.6 37.0

77.0 SHC 18.4 20.9 22.7 23.5 24.9 25.2

PI 2.37 2.41 2.44 2.48 2.51 2.55

Outdoor Air 89.6 TC SHC 22.7 17.9 26.5 20.3 29.5 22.0 30.9 22.7 33.9 24.0 35.2 24.4

Temperature (°FDB) 95.0 PI TC SHC PI 2.76 22.0 17.5 2.91 2.80 25.7 19.9 2.95 2.85 28.7 21.5 3.00 2.90 30.0 22.2 3.05 2.93 32.9 23.4 3.09 2.98 34.2 23.8 3.13

TC 21.2 24.7 27.6 28.9 31.7 32.9

104.0 SHC 17.2 19.4 21.0 21.6 22.8 23.1

PI 3.09 3.14 3.19 3.24 3.29 3.33

TC 20.7 24.2 27.0 28.2 31.0 32.1

109.4 SHC 16.9 19.1 20.6 21.3 22.4 22.7

PI 3.20 3.25 3.30 3.35 3.39 3.44

Model No : HT -C368DLA0 Indoor Air Temperature °FWB °FDB 57.2 68.0 60.8 71.6 64.4 77.0 66.2 80.6 71.6 86.0 75.2 89.6

TC 29.2 34.1 38.0 39.8 43.7 45.3

68.0 SHC 24.7 28.1 30.5 31.6 33.5 34.0

PI 2.29 2.33 2.36 2.40 2.4 2.5

TC 28.6 33.3 37.2 38.9 42.7 44.4

77.0 SHC 24.5 27.8 30.2 31.2 33.0 33.6

PI 2.7 2.8 2.8 2.8 2.9 2.9

Outdoor Air Temperature (°FDB) 89.6 95.0 TC SHC PI TC SHC PI 27.2 23.8 3.2 26.4 23.3 3.3 31.8 27.0 3.2 30.8 26.4 3.4 35.5 29.3 3.3 34.4 28.6 3.4 37.1 30.2 3.3 36.0 29.5 3.5 40.7 31.9 3.4 39.5 31.2 3.5 42.3 32.4 3.4 41.0 31.6 3.6

TC 25.4 29.7 33.1 34.7 38.0 39.5

104.0 SHC 22.8 25.8 27.9 28.8 30.3 30.7

PI 3.6 3.6 3.7 3.7 3.8 3.8

TC 24.8 29.0 32.4 33.9 37.2 38.6

109.4 SHC 22.5 25.4 27.4 28.3 29.8 30.1

PI 3.7 3.7 3.8 3.8 3.9 4.0

PI 3.0 3.1 3.1 3.2 3.2 3.3

Outdoor Air Temperature (°FDB) 89.6 95.0 TC SHC PI TC SHC PI 27.2 24.7 3.6 26.4 24.2 3.7 31.8 28.0 3.6 30.8 27.4 3.8 35.5 30.3 3.7 34.4 29.7 3.9 37.1 31.3 3.7 36.0 30.6 3.9 40.7 33.1 3.8 39.5 32.3 4.0 42.3 33.6 3.8 41.0 32.8 4.0

TC 25.4 29.7 33.1 34.7 38.0 39.5

104.0 SHC 23.7 26.7 28.9 29.8 31.4 31.8

PI 4.0 4.0 4.1 4.2 4.2 4.3

TC 24.8 29.0 32.4 33.9 37.2 38.6

109.4 SHC 23.3 26.3 28.4 29.3 30.9 31.2

PI 4.1 4.2 4.2 4.3 4.4 4.4

Model No : HT -C368DLA1 Indoor Air Temperature °FWB °FDB 57.2 68.0 60.8 71.6 64.4 77.0 66.2 80.6 71.6 86.0 75.2 89.6

TC 29.2 34.1 38.0 39.8 43.7 45.3

68.0 SHC 25.6 29.1 31.6 32.7 34.7 35.3

PI 2.57 2.61 2.65 2.70 2.7 2.8

TC 28.6 33.3 37.2 38.9 42.7 44.4

77.0 SHC 25.4 28.8 31.3 32.3 34.3 34.8

◆Symbol AFR : Air Flow Rate [CFM] DB : Dry Bulb Temperature [°F] WB : Wet Bulb Temperature [°F] TC : Total Capacity [kBtu/h] SHC : Sensible Heating Capacity [kBtu/h] PI : Power Input [kW] (compressor + indoor fan motor + outdoor fan motor)

◆Notes 1. All capacites are net, evaporator fan motor heat is deducted. 2. Indicates rated capacity. 3. Direct interpolation is permissible. Do not extrapolate. 4. Capacities are based on the following conditions: - Interconnecting Piping Length 24.6ft - Level Difference of Zero.

2008 Product Data

31


10. Performance Data Cooling Capacity(English Units) Model No : HT-C488DLA0 Indoor Air Temperature °FWB °FDB 57.2 68.0 60.8 71.6 64.4 77.0 66.2 80.6 71.6 86.0 75.2 89.6

TC 38.9 45.4 50.7 53.0 58.2 60.4

68.0 SHC 31.0 35.1 38.2 39.5 41.9 42.6

PI 3.28 3.33 3.38 3.43 3.5 3.5

TC 38.1 44.5 49.6 51.9 57.0 59.1

77.0 SHC 30.7 34.8 37.8 39.1 41.4 42.0

PI 3.9 3.9 4.0 4.1 4.1 4.2

Outdoor Air Temperature (°FDB) 89.6 95.0 TC SHC PI TC SHC PI 36.3 29.8 4.5 35.2 29.2 4.8 42.4 33.8 4.6 41.1 33.0 4.8 47.3 36.6 4.7 45.9 35.8 4.9 49.5 37.8 4.7 48.0 37.0 5.0 54.3 40.0 4.8 52.7 39.0 5.1 56.4 40.6 4.9 54.7 39.6 5.1

PI 3.8 3.9 3.9 4.0 4.0 4.1

Outdoor Air Temperature (°FDB) 89.6 95.0 TC SHC PI TC SHC PI 36.3 30.2 4.4 35.2 29.6 4.7 42.4 34.2 4.5 41.1 33.5 4.7 47.3 37.1 4.6 45.9 36.3 4.8 49.5 38.3 4.7 48.0 37.4 4.9 54.3 40.5 4.7 52.7 39.5 5.0 56.4 41.1 4.8 54.7 40.1 5.0

TC 33.9 39.6 44.2 46.2 50.7 52.6

104.0 SHC 28.6 32.3 34.9 36.0 38.0 38.4

TC 33.9 39.6 44.2 46.2 50.7 52.6

104.0 SHC 28.9 32.7 35.4 36.5 38.4 38.9

PI 5.1 5.2 5.2 5.3 5.4 5.5

TC 33.1 38.7 43.1 45.1 49.5 51.4

109.4 SHC 28.2 31.8 34.4 35.4 37.3 37.7

PI 5.2 5.3 5.4 5.5 5.6 5.6

TC 33.1 38.7 43.1 45.1 49.5 51.4

109.4 SHC 28.5 32.2 34.8 35.9 37.8 38.2

PI 5.1 5.2 5.3 5.4 5.5 5.5

Model No : HT-C488DLA1 Indoor Air Temperature °FWB °FDB 57.2 68.0 60.8 71.6 64.4 77.0 66.2 80.6 71.6 86.0 75.2 89.6

TC 38.9 45.4 50.7 53.0 58.2 60.4

68.0 SHC 31.4 35.6 38.7 40.0 42.5 43.2

PI 3.21 3.26 3.31 3.37 3.4 3.5

TC 38.1 44.5 49.6 51.9 57.0 59.1

77.0 SHC 31.1 35.2 38.3 39.6 41.9 42.6

◆Symbol AFR : Air Flow Rate [CFM] DB : Dry Bulb Temperature [°F] WB : Wet Bulb Temperature [°F] TC : Total Capacity [kBtu/h] SHC : Sensible Heating Capacity [kBtu/h] PI : Power Input [kW] (compressor + indoor fan motor + outdoor fan motor)

32 Ceiling Cassette (50Hz,R22)

PI 5.0 5.0 5.1 5.2 5.3 5.4

◆Notes 1. All capacites are net, evaporator fan motor heat is deducted. 2. Indicates rated capacity. 3. Direct interpolation is permissible. Do not extrapolate. 4. Capacities are based on the following conditions: - Interconnecting Piping Length 24.6ft - Level Difference of Zero.


11. The Coefficient of Capacity Change Model No : HT-C186HLA0, HT-C186HLA1,HT-C246HLA0,HT-C246HLA1,HT-C306HLA0 HT-C368DLA0,HT-C368DLA1,HT-C488DLA0,HT-C488DLA1

Cooling Capacity 100

HT-C368DLA0 HT-C186HLA0(1) HT-C488DLA0 HT-C246HLA0(1)

95

Cap ac i ty (% )

90

+ HT-C306HLA0

85 80

HT-C488DLA1

75

HT-C368DLA1

70 7. 5

10

30

20

50

To t a l Pi p e Leng t h (m )

Models

HT-C186HLA0 HT-C246HLA0 HT-C186HLA1 HT-C246HLA1

HT-C306HLA0 HT-C368DLA0

HT-C488DLA0 HT-C368DLA1

HT-C488DLA1

Additional

Refrigerant

25

30

40

40

60

50

( g/m)

Notes: * Equivalent pipe length = Actual pipe length + number of bend x 0.3 * Refer to the specification for the maximum pipe length of each model.

2008 Product Data

33


12. Operation Range

Cooling 46

Operative Operative

43 Outdoor Unit [ ℃ DB]

Continuous operation

21

Operative -5 18 Indoor Unit [℃ DB]

34

Ceiling Cassette (50Hz,R22)

32


13. Air Velocity and temperature Distributions(Reference Data) Ceiling Cassette 4 -way TH chassis (18kBtu/h) Models Air velocity [m/s]

Discharge angle : 45°

2.7m 2.0

2.0 2m

1.5

1.5

1.0

1.0

0.5

4m

3m

1m

0.5

2m

1m

0m

1m

2m

3m

0m 4m

Ceiling Cassette 4 -way TD1 chassis (36kBtu/h) Models Air velocity [m/s]

Discharge angle : 40°

2.7m 2m 2.0

2.0

1.5 0.5

4m

3m

1.5

1.0

2m

1.0

1m

0m

1m

2m

1m 0.5

3m

0m 4m

2008 Product Data

35


13. Air Velocity and temperature Distribution Ceiling Cassette 4 -way TH chassis

(18kBtu/h) Models

Temperature [ C] Discharge angle:45

2.7m 18

18

20

2m

20

22

22 1m

24 4m

3m

2m

24 1m

0m

Ceiling Cassette 4 -way TD1 chassis

1m

2m

3m

0m 4m

(36kBtu/h) Models

Temperature [ C] Discharge angle:40 2.7m

20

2m

20

22 24 4m

3m

36 Ceiling Cassette (50Hz,R22)

1m

22 24

2m

1m

0m

1m

2m

3m

0m 4m


14. Sound Levels Notes: - Sound measured at 1.5m away from the center of the unit. - Data is valid at free field condition - Data is valid at nominal operation condition - Reference accoustic pressure OdB = 20 Pa - Sound level will vary depending on a range of factors such as the construction(acoustic absorption coefficient) of particular room in which the equipment is installed. - The operating conditions are assumed to be standard.

Overall Ceiling 1.5m

Sound Levels(dBA)

Model HT-C186HLA0(1) HT-C246HLA0(1) HT-C306HLA0 HT-C368DLA0(1) HT-C488DLA0(1)

SH 35 42 44 51 53

M 27 32 40 39 46

H 31 34 42 44 49

L

SL

24 29 37 38 43

20 27 35 35 40

Sound Pressure Level

90

90

90

80

80

80

NC-70 NC-65

60

NC-60 NC-55

50

NC-50 NC-45

40

NC-40 NC-35

30

70

70 NC-70 NC-65

60

NC-60 NC-55

50

NC-50 NC-45

40

NC-40 NC-35

30

NC-25

NC-25

20

NC-15 125

250

500

1000

2000

4000

Octave Band Center Frequency (Hz)

NC-60 NC-55

50

NC-50 NC-45

40

NC-40 NC-35

30

NC-30 NC-25

20

NC-20

NC-15

10 63

8000

125

250

500

1000

2000

4000

Octave Band Center Frequency (Hz)

NC-15

10 63

8000

HT-C368DLA0(1)

125

250

500

1000

2000

4000

Octave Band Center Frequency (Hz)

8000

HT-C488DLA0(1)

90

90

80

80

70

70 NC-70 NC-65

60

NC-60 NC-55

50

NC-50 NC-45

40

NC-40 NC-35

30

NC-30 NC-25

20

NC-70

Sound Pressure Level (dB re 20 Pa )

63

NC-65

NC-20

NC-20 10

NC-70 60

NC-30

NC-30 20

Sound Pressure Level (dB re 20 Pa )

Sound Pressure Level (dB re 20 Pa )

70

Sound Pressure Level (dB re 20 Pa )

Sound Pressure Level (dB re 20 Pa )

HT-C306HLA0

HT-C246HLA0(1)

HT-C186HLA0(1)

NC-65

60

NC-60 NC-55

50

NC-50 NC-45

40

NC-40 NC-35

30

NC-30 NC-2510

20

NC-2010

NC-20 NC-15

NC-15 63

125

250

500

1000

2000

4000

Octave Band Center Frequency (Hz)

8000

63

125

250

500

1000

2000

4000

8000

Octave Band Center Frequency (Hz)

2008 Product Data

37


15. Installation 15.1 Select the best location 15.1.1 Indoor Unit There should not be any heat source or steam near the unit. There should not be any obstacles to the air circulation. Taking into account the noise prevention criteria, spot the installation location. Keep proper distance of the unit from ceiling, fence, walls & other obstacles as shown figure. The indoor unit must have the maintenance space around.

20 or more

Ceiling

Ceiling Board

Ceiling Board

1500 or more

There should be easy provision of condensate drain.

1500 or more

In case of the multi flow type, use the high humidity kit. Otherwise the dew drops can be seen on the unit body.

1500 or more H Unit:mm Floor

Refrigerant piping: Increase the piping insulation thickness upto 20mm or more. Refrigerant piping

NOTE

Above figure means minimum value. Please keep these value at least. If H is 2700~3200mm: High ceiling operation control requied Others: Inside the ceiling near th air tight seal places (no escape of the humidity)

If H is ~2700: Normal operation

1500 or more 1500 or more

Grill for ventilation

Indoor unit

Indoor unit Ventilator Lighting

1500 or more

In case of multiple indoor cassette units (recommended)

1500 or more

Above 1500mm

Unit:mm

Above 2000mm Above 3000mm

38 Ceiling Cassette(50Hz, R22)


15. Installation 15.1.2 Outdoor Unit If a roof is built over the unit to prevent direct sunlight or rain exposure, make sure that heat radiation from the condenser is not restricted. Do not place animals and plants in the path of the warm air. Take the air conditioner weight into account and select a place where noise and vibration are minimum. Select a place so that the warm air and noise from the air conditioner do not disturb neighbors. Rooftop Installations : If the outdoor unit is installed on a roof structure, be sure to level the unit. Ensure the roof structure and anchoring method are adequate for the unit location. Consult local codes regarding rooftop mounting.

More than 30cm

Fe ob nce sta or cle s

Su

nro of

More than 30cm

M ore than than More 30cm 30cm

More than 60cm

Su

nro

Fe ob nce sta or cle s

More than 70cm

of Mo ore re tthan han 30cm 30cm

More than 50cm (Service space)

More than 60cm More than 70cm

15.2 Settlement of outdoor unit Anchor the outdoor unit with a bolt and nut(ø10mm) tightly and horizontally on a concrete or rigid mount.

Bolt

Tubing connection

When installing on the wall, roof or rooftop, anchor the mounting base securely with a nail or wire assuming the influence of wind and earthquake. In the case when the vibration of the unit is conveyed to the hose, secure the unit with an anti-vibration rubber.

2008 Product Data

39


15. Installation 15.3 Installation guide at the seaside CAUTION

1. Air conditioners should not be installed in areas where corrosive gases, such as acid or alkaline gas, are produced. 2. Do not install the product where it could be exposed to sea wind (salty wind) directly. It can result corrosion on the product. Corrosion, particularly on the condenser and evaporator fins, could cause product malfunction or inefficient performance. 3. If outdoor unit is installed close to the seaside, it should avoid direct exposure to the sea wind. Otherwise it needs additional anticorrosion treatment on the heat exchanger.

15.3.1 Selecting the location(Outdoor Unit) 1) If the outdoor unit is to be installed close to the seaside, direct exposure to the sea wind should be avoided. Install the outdoor unit on the opposite side of the sea wind direction.

Sea wind

Sea wind

2) In case, to install the outdoor unit on the seaside, set up a windbreak not to be exposed to the sea wind.

Windbreak

the sea wind from the sea. the outdoor unit.

Sea wind

between outdoor unit and the windbreak for easy air flow.

3) Select a well-drained place. 1. If you can’t meet above guide line in the seaside installation, please contact LG Electronics for the additional anticorrosion treatment. 2. Periodic ( more than once/year ) cleaning of the dust or salt particles stuck on the heat exchanger by using water.

40

Ceiling Cassette (50Hz, R22)


15. Installation 15.4 Ceiling Opening dimensions and hanging bolt location 870 (Ceiling opening) 785(Hanging bolt)

840 Unit size

840 Unit size

672 (Hanging bolt)

TH,TD1 Chassis

870 (Ceiling opening)

The dimensions of the paper model for installing are the same as those of the ceiling opening dimensions.

Unit:mm

Select and mark the position for fixing bolts and piping hole. Decide the position for fixing bolts slightly tilted to the drain direction after considering the direction of drain hose. Drill the hole for anchor bolt on the wall.

Ceiling board

CA U TI O N This air-conditioner uses a drain pump. Install the unit horizontally using a level gauge. During the installation, care should be taken not to damage electric wires.

Ceiling Level gauge

NOTE:

Avoid the following installation location. 1. Such places as restaurants and kitchen where considerable amount of oil steam and flour is generated. These may cause heat exchange efficiency reduction, or water drops, drain pump mal-function. In these cases, take the following actions; Make sure that ventilation fan is enough to cover all noxious gases from this place. Ensure enough distance from the cooking room to install the air conditioner in such a place where it may not suck oily steam. 2. Avoid installng air conditioner in such places where cooking oil or iron powder is generated. 3. Avoid places where inflammable gas is generated. 4. Avoid place where noxious gas is generated. 5. Avoid places near high frequency generators.

Air conditioner

Take enough distance

Cooking table

Use the ventilation fan for smoke-collecting hood with sufficient capacity.

2008 Product Data

41


15. Installation 15.5 The Indoor Unit Installation Ceiling

Nut (W3/8 or M10) Spring washer (M10)

Keep the length of the bolt from the bracket to 40mm Flat washer for M10 (accessory) Ceiling board

Flat washer for M10 (accessory) Nut (W3/8 or M10)

Air Conditioner body

Ceiling board

Paper model for installation Adjust the same height

The following parts are local purchasing. Hanging Bolt - W 3/8 or M10 Nut - W 3/8 or M10 Spring Washer - M10 Plate Washer - M10

150mm

Hanging bolt (W3/8 or M10)

Set screw of paper model (4 pieces) Open the ceiling board along the outer edge of the paper model

Drill the piping hole on the wall slightly tilted to the outdoor side using a Ă˜ 70 hole-core drill.

CA U TI O N

Wall Indoor

Outdoor

5~7mm

Tighten the nut and bolt to prevent unit from falling off.

42 Ceiling Cassette(50Hz, R22)


15. Installation 15.6 Wiring Connection 1. All wiring must comply with LOCAL REGULATIONS. 2. Select a power source that is capable of supplying the current as required by the air conditioner. 3. Feed the power source to the unit via a distribution switch board designed for this purpose. 4. The terminal screws inside the control box may be loose due to vibration during transport. Check the screws for loose connection. (Running the air conditioner with loose connection can overload and damage electrical components.) 5. Always ground the air conditioner with a grounding wire and connector to meet the LOCAL REGULATION.

Terminal Block in Indoor 1(L)

2(N)

3

Terminal Block in Indoor 4

1(L)

2(N)

3

Connected to indoor unit

1(L)

2(N)

3(L)

4(N)

5

6

7

Connected to indoor unit 1(R) 2(S)

8

3(T)

4(N )

6(L)

7(N)

8

9

outdoor unit

outdoor unit

Main

Main

3Ă˜,380V ,50HZ

1Ă˜ ,220V , 50Hz

The power cord connected to the outdoor unit should be complied with the following specifications (Rubber insulation, type H05RN-F approved by HAR or SAA). 18kBtu/h

1 Phase 3 Phase 1.5mm2

24k/30kBtu/h 2.5mm

2

GN

/YL

36k/48kBtu/h 20

CAUTION The connecting cable connected to the indoor and outdoor unit should be complied with the following specifications (Rubber insulation, type H05RN-F approved by HAR or SAA).

-

NORMAL CROSS-SECTIO NAL AREA 0.75mm2

4.0 mm 2

7.5mm

Capacity

8.5mm

4

GN /YL

mm

20 m

m

If the supply cord is damaged, it must be replaced by a special cord or assembly available from the manufacturer or its service agent.

WARNIN G Make sure that the screws of the terminal are free from looseness.

2008 Product Data

43


15. Installation 15.7 Piping Connection 1. Form the piping according to its routing. Avoid bending and bending back the same piping point more than three times. (This will result in hardening the pipe.) 2. After deforming the piping, align centers of the union fitting of the indoor unit and the piping, and tighten them firmly with wrenches. 3. Connect pipe to the service valve or ball valve which is located below the outdoor unit. 4. After completing the piping connection, be sure to check if there is gas leakage in indoor and outdoor connection.

15.8 Vacuum drying After completing the piping connection, execute vacuum drying for the connecting piping and the indoor unit. The vacuum drying must be carried out using the service ports of both the liquid and gas side valves.

44

Ceiling Cassette(50Hz,R22)

Liquid side Indoor unit Outdoor unit

Flare connection Gas side Flare connection

Model 18kBtu/h 24kBtu/h

Liquid side piping Gas side piping Ø 12.70mm Ø 6.35mm

30kBtu/h

Ø 6.35mm

Ø15.88mm

36kBtu/h 48kBtu/h

Ø 9.52mm

Ø19.05mm


15. Installation 15.9 Installation of Decoration Panel Before installing the decoration panel, always remove the paper template.

The decoration panel has its installation direction.

1. Temporarily fix two decoration panel fixing screws (hexagon M5 screw) on the unit body. (Tighten by amount 10mm in length.) The fixing screws (hexagon M5 screw) are included the indoor unit box. 2. Remove the air inlet grille from the decoration panel. (Remove the hook for the air inlet grille cord.) 3. Hook the decoration panel key hole ( ) on the screws fixed in step above, and slide the panel so that the screws reach the key hole edge. 4. Retighten completely two temporarily fixed screws and other two screws. (Total 4 screws) 5. Connect the louver motor connector and display connector. 6. After tightening these screws, install the air inlet grille (including the air filter). Piping side

Air conditioner unit

Decoration panel fixing screws (hexagon M5 screws) Temporally fitting at 2 places (Tightening about 10mm)

Control box cover

Louver motor Inlet Grille

Decoration panel Display Key holes Lead wire for louver motor and display

Decoration panel fixing screws (Hexagon M5 screw)

Inlet Grille

CA U TI O N Install certainly the decoration Good example panel. Cool air leakage causes sweating. Water drops fall.

Bad example Air conditioner unit Ceiling board

Decoration panel Fit the insulator (this part) and be careful for cool air leakage

Air conditioner unit Air

Cool air leakage (no good) Ceiling board Decoration panel

2008 Product Data

45


15. Installation 15.11 Drain Pipe Work Drain pipe gradient and support 1) - The drain pipe must be fitted at a gradient of at least 1/100. - The drain pipe should be as short as possible and free from airlocks. Indoor unit Gradient of at least 1 / 100 (1cm/ 1m)

2) Suspension bolts should be used to support long stretches of drain pipe in order to ensure that a gradient of 1/100 is maintained.(PVC pipe should not be bent) Spacing of supports for horizontal piping Class

Nominal diameter

Spacing

Rigid PVC pipe

25~40mm

1.0m or less

3) The length of pipe laid horizontally should be kept a minimum. Drain piping must have down-slope (1/50 to 1/100): be sure not to provide up-and-down slope to prevent reversal flow. During drain piping connection, be careful not to exert extra force on the drain port on the indoor unit. The outside diameter of the drain connection on the indoor unit is 32mm. Piping material: Polyvinyl chloride pipe VP-25 and pipe fittings

Upward routing not allowed

Pipe clamp Indoor unit

Maintenance drain port

Be sure to install heat insulation on the drain piping.

1/50~1/100

Heat insulation material: Polyethylene foam with thickness more than 8 mm.

MAX 700mm

Drain test The air conditioner uses a drain pump to drain water. Use the following procedure to test the drain pump operation:

Feed water

Flexible drain hose (accessory) Main drain pipe

Drain Pump

Drain port

Glue the joint

Drain hose connection Use the clip (accessory)

Drain pan

46

Ceiling Cassette(50Hz, R22)

Connect the main drain pipe to the exterior and leave it provisionally until the test comes to an end. Feed water to the flexible drain hose and check the piping for leakage. Be sure to check the drain pump for normal operating and noise when electrical wiring is complete. When the test is complete, connect the flexib le drain hose to the drain port on the indoor unit.


15. Installation Grouped drain piping 1) It is standard work practice to make connections to the main pipe from above. The pipe coming down from the combination should be as large as possible.

Face piping downward

Face the vent pipe mouth downward to keep foreign matter from penetrating the system Vent pipe

2) The pipe work should be kept as short as possible and the number of indoor units per group kept to a minimum.

CAUTION The supplied flexible drain hose should not be curved, neither screwed. The curved or screwed hose may cause a leakage of water.

Flexiblle Flexi ed drain rain h hose ose

1/50~1/100 MAX 700mm

CAUTION After the confirmation of the above conditions, prepare the wiring as follows: 1) Never fail to have an individual po w er speciali zed for the air conditioner. As for the method of w iring , b e guided b y the circuit diagram pasted on the inside of control b o x cover. 2) Provide a circuit b reaker s w itch b et w een po w er source and the unit. 3) The scre w w hich fasten the w iring in the casing of electrical fittings are lia b le to come loose from vi b rations to w hich the unit is su bj ected during the course of transportation. Check them and make sure that they are all tightly fastened. (If they are loose , it could give rise to b urn -out of the w ires.) 4) Specification of po w er source 5) Confirm that electrical capacity is sufficient. 6) B e sure that the starting voltage is maintained at more than 90 percent of the rated voltage marked on the name plate. 7) Confirm that the ca b le thickness is as specified in the po w er sources specification. (Particularly note the relation b et w een ca b le length and thickness.) 8) Never fail to equip a leakage b reaker w here it is w et or moist. 9) The follo w ing trou b les w ould b e caused b y voltage drop -do w n. Vibration of a magnetic switch, damage on the contact point there of, fuse breaking, disturbance to the normal function of a overload protection device. Proper starting power is not given to the compressor.

2008 Product Data

47


15. Installation 15.12 Optional Operation (For wire remote) 1) Two Thermistor System (1) Open the rear cover of the wired remote-controller to set the mode. (2) Select one of three selectable modes as follows. Position 1: The room temperature is controlled by the thermistor of the main body. Position 2: The room themperature is controlled by the thermistor of the wired remote-controller, control the temperature according to the position of wired remote-controller. Position 3: The room temperature is controlled by lower temperature between the temperature of main body and of remote-controller sensor. (3) Move the slide switch to set position. Room Temp. sensor Slide switch for 2 Thermistor

TH

R14H OP3 SW TH

REMO MAIN 2TH

OP2

REMO MAIN 2TH R17H

R12H

CO1H

OP1 R19H R11H

OP5R16H

OP4 R15H

OP7 R18H OP6

STAND

LO

C070

Position 2 Position 1 Position 3

R13H

R03S

HI

R04S HIGH

R01S

R02S

SW

Slide switch for ceiling height

(4) Close the rear cover and check if it works normally.

CA U TI O N Select the position after counselling with a customer. In case of cooling mode, room temperature is controlled by the main body sensor. To control the room temperature by a wired remote controller, install controller(room temp. sensor) to sense the temperature more accurately. Maunfactured in the position 3.

48 Ceiling Cassette(50Hz,R22)


15. Installation 2) Adjusting air volume to the height of ceiling You can choose the RPM(or air volume) of indoor motor according to the height of ceiling to supply the comfortable atmosphere to consumers. Procedure 1. Choose the selectable position in the table after measuring the height of ceiling. Ceiling height more than 3.3m 2.7~3.3m less than 2.7m

Mode of slide switch High Ceiling Standard Low Ceiling

Change of air volume Increasing Decreasing

Remark Maunfactured in standard mode

2. In the case of changing the height as "high" or "low", open the rear cover of the wired remote-controller. Slide switch for 2 Thermistor

3. Move the slide switch to the set position.

R13H

TH

4. Close the rear cover and check if it works nomally.

Low ceiling Standard (Default) High Ceiling

STAND

Lo

OP2 R14H OP3 SW TH

REMO MAIN 2TH

Hi

R17H

R12H

CO1H

OP1 R19H R11H

OP5R16H

OP4 R15H

OP7 R18H OP6

LO

C070

STAND

R03S

HI

R04S HIGH

R01S

R02S

Slide switch for ceiling height

SW

3) Group Control(Optional Wiring) It operates maximum 16 Units by only one Wired Remote Controller, and each Unit starts sequentially to prevent overcurrent. Main PCB Wiring design Indoor Unit 1

Indoor Unit 2

Terminal(Local Supply) Block Connector

Terminal(Local Supply) Block Connector

RED(12V) YL(SIGNAL) BR(GND)

RED(12V) YL(SIGNAL) BR(GND)

Main PCB #1

YL(SIGNAL) BR(GND)

YL(SIGNAL) BR(GND)

Indoor Unit 16

Terminal(Local Supply) Block Connector

Main PCB #2

....

AUTO SWING

OPERATION

SET TEMP Room Temp

Operation unit 03

FAN SPEED HI MED LO

Time Timer

On Off Set no. Time 01

ZONE

....

YL(SIGNAL) BR(GND)

YL(SIGNAL) BR(GND)

Main PCB #16

Connecting Cable(Local Supply)

SUB FUNCTION

AUTO Heater Preheat JET Defrost Humidify Filter Out door 1 2 3 4

Program set 05

07

09

11

13

15

17

19

21

23

Wired Remote Controller

S/W GR

Single Group

Remote Controller PCB

Using the supplied Wired Remote Controller, wire them like above. Move S/W GR to "Group" position. Check the line color of the wire.

CA U TI O N Be careful not to exchange the color of wires. The maximum length of connecting wire should be below 200m(25â„Ś) on connecting each units. Use a wire more than 0.5mm2

2008 Product Data

49


16. Function of Remote Control 16.1 Wired LCD Remote Control Name and Function of Remote Control

.

AUTO SWING

OPERATION

SET TEMP Room Temp

1

2ndF Timer

FAN SPEED

Cooling Model

SUB FUNCTION

AUTO Heater Preheat JET Defrost Humidify SLo Filter Out door ZONE 1 2 3 4

HI MED LO

Time

Operation unit No Func Program set

On Off Set no. Time 01

03

05

07

09

11

13

15

17

19

21

23

5

14 2 3 4

6 7 Timer

Cancel

2ndF

Program

Week

Holiday

8 9 10 11 12 13

PLASMA

Set/Clr Hour

Min

RESET

1 Operation indication screen

9

2 Swirl button

10

Horizontal/Vertical air flow direction button

11

Room temperature/filtersign release button Used to check the room temperature and release the filter in Second Function Mode.

12

Plasma/Heater button

Displays the operation conditions.

Used to select swirl cool mode.

3 2ndF button 4 Timer set/cancel /Program/Week

Holiday/Hour/Min/SET/Clr/Ventilator

5

Set temperature button

Fan speed button Used to set the disired fan speed.

Used plasma and saved power in Second Function.

Used to set the temperature when required.

6 ON/OFF button

13

Reset Used to set the current time and clear the setting time.

Operation starts when this button is pressed and stops when the button is pressed again.

7

Fan operation Used to circulate room air without cooling or heating.

8

Operation mode selection button Used to select the operation mode.

50

Ceiling Cassette(50Hz,R22)

Time reset button

14

Operation lamp


16. Function of Remote Control 16.2.Wireless Remote Controller Name and Function of Remote Controller

.

This air-conditione r is equipped with wired remote controller basically . Bu t if you want to be availabl e with wireles s remote controller, you pay for it. 1.START/STOP BUTTON Operation starts when this button is pressed and stops when the button is pressed again. The controls will look like the following. 2. OPERATION MODE SELECTION BUTTON Used to select the operation mode. Controls 3. ROOM TEMPERATURE SETTING BUTTONS Used to select the room temperature. Signal transmitter 4. INDOOR FAN SPEED SELECTOR Used to select fan speed in four steps low, medium, high and CHAOS. 5. JET COOL Used to start or stop the speed cooling.(speed cooling operates super high fan speed in cooling mode.) 6. CHAOS SWING BUTTON Used to stop or start louver movement and set the desired up/down airflow direction. 7. ON/OFF TIMER BUTTONS 5 1 Used to set the time of starting and stopping 6 operation. 8. TIME SETTING BUTTONS 3 Used to adjust the time. 9. TIMER SET/CANCEL BUTTON 4 Used to set the timer when the desired time 10 2 is obtained and to cancel the Timer CANCEL operation. 9 7 SET ON OFF 10. SLEEP MODE AUTO BUTTON AUTO CLEAN 12 11 Used to set Sleep Mode Auto operation. 17 8 11. AIR CIRCULATION BUTTON Used to circulate the room air without 13 14 cooling or heating. 16 15 12. ROOM TEMPERATURE CHECKING BUTTON Used to check the room temperature. 13. NEO PLASMA(OPTIONAL) Used to start or stop the plasma-purification function. Flip-up door (opened) 14. HORIZONTAL AIRFLOW DIRECTION CONTROL BUTTON (OPTIONAL) Used to set the desired horizontal airflow direction. 15. RESET BUTTON Used prior to resetting time. 16. 2nd F Button Used prior to using modes printed in blue at the bottom of buttons.

CAUTION:of handling the Remote Controller

17. AUTO CLEAN (OPTIONAL) Used to set Auto Clean mode.

Aim at the signal receiver on the wired remote controller so as to operate. The remote control signal can be received at a distance of up to about 7m. Be sure that there are no obstructions between the remote controller and the signal receptor. Do not drop or throw the remote controller. Do not place the remote controller in a location exposed to direct sunlight, or near the heating unit, or any other heat source. Block a strong light over the signal receptor with a curtain or etc. so as to prevent the abnormal operation. (ex:electronic quick start, ELBA, inverter type fluorescent lamp)

2008 Product Data

51


P/No.:MFL32271301

Rayong Office:

October/2008

The air conditioners manufactured by LG have received ISO9001 certificate for quality assurance and ISO14001 certificate for environmental management system.


Issuu converts static files into: digital portfolios, online yearbooks, online catalogs, digital photo albums and more. Sign up and create your flipbook.