ED45_939.book Page 98 Wednesday, March 18, 2009 2:48 PM
Indoor unit
ED45-939
ACCESSORIES
Check if the following are included with your unit.
Insulation Clamp Switch box Switch box Name Installation for fitting <FD05-10> <FD13-20> manual Quantity
1 each
1 pc 1
2 pcs
1 pc
1 pc
3
For gas pipe
Shape 2
For liquid pipe
OPTIONS The following optional remote controller is available for this indoor unit. Remote controller
BRC1NU64
NOTE) A commercially available remote controller can be used if its specifications are compatible with those shown in the wiring diagram and technical materials. TAKE SPECIAL CARE DURING INSTALLATION AND CHECK THE FOLLOWING ITEMS AFTER INSTALLATION IS FINISHED. Items to be checked Is the indoor unit securely installed? Has the gas leak test been performed? Is the unit properly insulated? Is the drain flow smooth?
Result of improper installation The unit may drop, vibrate or make noise. Insufficient cooling may result. Condensate may drip. Condensate may drip.
Does the power supply voltage correspond to that shown on the name plate? Is the wiring and piping correct?
The unit may malfunction or components may burn out.
Is the unit safely grounded? Are the wire sizes according to specifications?
Dangerous electric leakage may result. The unit may malfunction or components may burn out.
Are the air outlets and inlets of the indoor and outdoor units free of blockage?
Insufficient cooling may result.
Checked
The unit may malfunction or components may burn out.
Are refrigerant piping lengths and additional The systemâ&#x20AC;&#x2122;s refrigerant charge is not known. refrigerant charges written down?
1
BEFORE INSTALLATION
<Do not throw away any of the parts or contents packaged with this unit until installation is completed.> Plan a convenient path for transporting the unit prior to unpacking or installing it. Unpack the unit at the site of installation. In the event that the unit is unpacked away from the installation site,use a wrap sheet or some other device when lifting or transporting it to avoid scratches or other damage.
3
3PN10228-1A
98
Installation of indoor / outdoor unit