Letter # SMK-ELEC-111s Smoke barrier at RM 111s - Elect Dist. Construction Specialties, Inc. 6696 State Route 405, PO Box 380 Muncy, Pennsylvania (570) 546-5941 Fax: (570) 546-8022 www.c-sgroup.com
January 27, 2016 Spectrum Specialty Builders Attn: Dan Pridemore 3902 West Valley Hwy North, Suite 500 Auburn, WA 98001 Project: Lincoln Square II
Location: Bellevue, WA
C/S Project #156859 Re: Stainless steel foil cover smoke barrier
Mr. Pridemore, In reference to the above mentioned project it has come to our attention that the use of stainless steel foil has come into question for use as a smoke barrier. In the following Intertek test report, you find the stainless steel foil product has been tested per the UL 2079, Standards for Safety, Tests for Fire resistance of Building Joint Systems, 2015. The system was Air Leakage tested as per Section 21 of UL2079. As a result of the test, you will find the conclusion shows that the stainless steel foil system has exceeded (0.00 cfm/ft) the target pressure differential of 0.3�WC for both Ambient Temperature Test and an Elevated Temperature Test. If additional information is required, please feel free to contact us. Sincerely,
Justin Moon Product Development Specialist Expansion Joint Cover Systems P: 570-546-4602 E: jmoon@c-sgroup.com Encl Cc: file, Pam Weihermuller (C/S)