Instruction Manual
DVC6200f Digital Valve Controller November 2011
D103412X012
Figure 2‐5. FIELDVUE DVC6205f Base Unit Mounting SPACER 1‐INCH 1/4‐20 HEX HEAD SCREW
MOUNTING BRACKET W8473
WALL MOUNTING
STANDOFF 4‐INCH 1/4‐20 HEX HEAD SCREW MOUNTING BRACKET W8474 / IL
PIPESTAND MOUNTING
DVC6215 Feedback Unit If ordered as part of a control valve assembly, the factory mounts the feedback unit on the actuator, makes pneumatic connections to the actuator, sets up, and calibrates the instrument. If you purchased the feedback unit separately, you will need a mounting kit to mount the feedback unit on the actuator. See the instructions that come with the mounting kit for detailed information on mounting the feedback unit to a specific actuator model. The DVC6215 housing is available in two different configurations, depending on the actuator mounting method. Figure 2‐6 shows the available configurations. The feedback system for the DVC6215 feedback unit utilizes a magnetic assembly for true linkage‐less, non‐contacting position measurement. In order to prevent inadvertent stem movement while the instrument is in operation, magnetic tools (such as a magnetic‐tipped screwdriver) should not be used. Figure 2‐6. Feedback Unit Housing Configurations HOUSING FOR LINEAR AND ROTARY ACTUATORS INTEGRAL OUTPUT PRESSURE PORT
X0124
LINEAR, M8
ROTARY NAMUR, M6 X0125
20
HOUSING FOR FISHER GX ACTUATORS
HOLES FOR MOUNTING BOLT