DVC6200f Instruction Manual Nov 2011

Page 22

Instruction Manual

DVC6200f Digital Valve Controller November 2011

D103412X012

Figure 2‐5. FIELDVUE DVC6205f Base Unit Mounting SPACER 1‐INCH 1/4‐20 HEX HEAD SCREW

MOUNTING BRACKET W8473

WALL MOUNTING

STANDOFF 4‐INCH 1/4‐20 HEX HEAD SCREW MOUNTING BRACKET W8474 / IL

PIPESTAND MOUNTING

DVC6215 Feedback Unit If ordered as part of a control valve assembly, the factory mounts the feedback unit on the actuator, makes pneumatic connections to the actuator, sets up, and calibrates the instrument. If you purchased the feedback unit separately, you will need a mounting kit to mount the feedback unit on the actuator. See the instructions that come with the mounting kit for detailed information on mounting the feedback unit to a specific actuator model. The DVC6215 housing is available in two different configurations, depending on the actuator mounting method. Figure 2‐6 shows the available configurations. The feedback system for the DVC6215 feedback unit utilizes a magnetic assembly for true linkage‐less, non‐contacting position measurement. In order to prevent inadvertent stem movement while the instrument is in operation, magnetic tools (such as a magnetic‐tipped screwdriver) should not be used. Figure 2‐6. Feedback Unit Housing Configurations HOUSING FOR LINEAR AND ROTARY ACTUATORS INTEGRAL OUTPUT PRESSURE PORT

X0124

LINEAR, M8

ROTARY NAMUR, M6 X0125

20

HOUSING FOR FISHER GX ACTUATORS

HOLES FOR MOUNTING BOLT


Turn static files into dynamic content formats.

Create a flipbook
Issuu converts static files into: digital portfolios, online yearbooks, online catalogs, digital photo albums and more. Sign up and create your flipbook.
DVC6200f Instruction Manual Nov 2011 by RMC Process Controls & Filtration, LLC. - Issuu