Length(ft) = [160,000 - 50,000pF] [50pF/ft] Length = 2200 ft. The HART communication cable length is limited by the cable characteristic capacitance. To increase cable length, select a wire with lower capacitance per foot. Contact your Emerson Process Management sales office for specific information relating to your control system.
Installation in Conjunction with a Rosemount 333 HART Tri‐Loop HART‐to‐Analog Signal Converter Use the DVC6200 digital valve controller in operation with a Rosemount 333 HART Tri‐Loop HART‐to‐Analog Signal Converter to acquire an independent 4‐20 mA analog output signal for the analog input, travel target, pressure, or travel. The HART Tri‐Loop accepts any three of these digital signals and converts them into three separate 4‐20 mA analog channels. Refer to figure 2‐29 for basic installation information. Refer to the 333 HART Tri‐Loop HART‐to‐Analog Signal Converter Product Manual for complete installation information. Figure 2‐29. HART Tri‐Loop Installation Flowchart START HERE
Unpack the HART Tri‐Loop
Install the HART Tri‐ Loop. See HART Tri‐ Loop product manual
Review the HART Tri‐Loop Product Manual
Digital valve controller Installed?
Yes
Mount the HART Tri‐Loop to the DIN rail.
No
Install the digital valve controller.
Wire the digital valve controller to the HART Tri‐Loop.
Set the digital valve controller Burst Option
Install Channel 1 wires from HART Tri‐Loop to the control room.
Set the digital valve controller Burst Mode
(Optional) Install Channel 2 and 3 wires from HART Tri‐Loop to the control room.
Configure the HART Tri‐Loop to receive digital valve controller burst commands
Pass system test?
Yes
No
Check troubleshooting procedures in HART Tri‐Loop product manual.
DONE
E0365 / IL
Commissioning the Digital Valve Controller for use with the HART Tri‐Loop Signal Converter To prepare the digital valve controller for use with a 333 HART Tri‐Loop, you must configure the digital valve controller to burst mode, and select Burst Command 3. In burst mode, the digital valve controller provides digital information to