extend from the cylinder with increasing input signal, connect OUTPUT A to the upper actuator cylinder connection. Connect OUTPUT B to the lower cylinder connection. To have the actuator stem retract into the cylinder with increasing input signal, connect OUTPUT A to the lower actuator cylinder connection. Connect OUTPUT B to the upper cylinder connection.
Special Construction to Support Solenoid Valve Testing Note Solenoid valve testing is only available for instrument level ODV.
In single‐acting actuator applications with a solenoid valve installed, the DVC6200 can be configured to test the operation of the solenoid valve. This is accomplished by connecting the “unused” output port from the DVC6200 to the pneumatic line between the solenoid valve and the actuator, as shown in figure 2‐22. When single‐acting, direct relay C is installed, the “unused” output port is port B. When single‐acting, reverse relay B is used, the unused port is port A. Figure 2‐22. Pneumatic Hookup for Solenoid Testing (Instrument Level ODV only) 24/48 VDC 110/220 VAC, etc.
CONTROL SIGNAL (4‐20 mA, 0‐20 mA, 0‐24 VDC)
CONTROL LINE
Port A Port B
DVC6200 DIGITAL VALVE CONTROLLER WITH RELAY C
SUPPLY PRESSURE
MONITORING LINE
NOTES: 1/4‐18 NPT X 3/8 OD TUBING ELECTRICAL WIRING
SPRING RETURN ACTUATOR
Note This application is called “special application” in the Setup Wizard relay selection. This configuration is not possible with a double‐acting actuator or when using relay A in single‐acting mode.