DVC6200 Instruction Manual June 2011

Page 27

Instruction Manual

DVC6200 Digital Valve Controller

D103409X012

June 2011

Quarter‐Turn Rotary Actuators The DVC6215 feedback unit can be mounted to any quarter‐turn rotary actuator, as well as those that comply with the NAMUR guidelines. A mounting bracket and associated hardware are required. Refer to figure 2‐17. 1. Isolate the control valve from the process line pressure and release pressure from both sides of the valve body. Shut off all pressure lines to the actuator, releasing all pressure from the actuator. Use lock‐out procedures to be sure that the above measures stay in effect while you work on the equipment. 2. Attach the magnet assembly to the actuator shaft. At mid‐travel, the flats on the magnet assembly must be parallel to the channel on the back of the DVC6215 housing, as shown in figure 2‐18. 3. Install the mounting bracket on the actuator. 4. Attach the feedback unit to the mounting bracket using the 4 mounting bolts, as shown in figure 2‐17. 5. Check for clearance between the magnet assembly and the DVC6215 feedback slot. 6. Install tubing between the actuator casing and the appropriate DVC6215 pneumatic output port. Figure 2‐17. Mounting on Quarter‐Turn Actuators

Figure 2‐18. Magnet Assembly Orientation on Quarter‐Turn Actuators ORIENTATION AT ONE TRAVEL EXTREME

ORIENTATION AT MID‐TRAVEL (FLATS PARALLEL TO DVC6215 CHANNEL)

M6 MOUNTING BOLTS (4) X0129

ORIENTATION AT THE OTHER TRAVEL EXTREME

27


Turn static files into dynamic content formats.

Create a flipbook
Issuu converts static files into: digital portfolios, online yearbooks, online catalogs, digital photo albums and more. Sign up and create your flipbook.
DVC6200 Instruction Manual June 2011 by RMC Process Controls & Filtration, LLC. - Issuu