DVC6000 Series January 2001 Errata Sheet for FIELDVUER DVC6000 Series Digital Valve Controllers Quick-Start Guide Form 5654, November 2000

Make the following additions and corrections to the quick-start guide. 1. Add the following to the end of the Hazardous Area specification under Electrical Classification on page 5-1: Pollution Degree 2, Overvoltage Category III per ANSI/ISA-82.02.01-1999 (IEC 1010-1 Mod). 2. On page 5-2, in the Shaft Rotation specification heading, change DVC5020 to DVC6020 and DVC5030 to DVC6030. 3. On page 4-1, under the heading Stroking the Digital Valve Controller, change Main Menu to Setup & Diag. Change Stroke Output to Stroke Valve. 4. On page 4-1, in table 4-1, change Hex socket wrench to Hex key. 5. On page 2-3, under the Vent heading, add the following:

Venting First Production DVC6000 Series Digital Valve Controllers Certain applications require gas tight instruments. In these applications, the exhaust must be piped away to a safe location. First production DVC6000 Series digital valve controllers do not support gas tight applications. These units have a second vent to prevent cover flex (and potential breakage) at supply pressures over 100 psig with the relay fully exhausting. Because this second vent cannot be removed, the exhaust cannot be safely piped away. Therefore, these early units cannot be used for gas tight applications. We are in the process of implementing a change to the primary exhaust port in the housing to accomodate a greater exhaust flow. When this change is complete, the secondary vent in the module base will be eliminated and the gas may be safely piped away using the single primary vent.

See errata dated January 2001.

EFisher Controls International, Inc. 2001; All Rights Reserved FIELDVUE, Fisher and Fisher-Rosemount are marks owned by Fisher Controls International, Inc. or Fisher-Rosemount Systems, Inc.

The contents of this publication are presented for informational purposes only, and while every effort has been made to ensure their accuracy, they are not to be construed as warranties or guarantees, express or implied, regarding the products or services described herein or their use or applicability. We reserve the right to modify or improve the designs or specifications of such products at any time without notice.

For information, contact Fisher Controls: Marshalltown, Iowa 50158 USA Cernay 68700 France Sao Paulo 05424 Brazil Singapore 128461 Printed in U.S.A.