DLC3000 Quick Start~Errata~Instruction Manual

Page 144

DVC5000 Series SAFETY GROUND

LOOP–

WARNING

LOOP+

2

TALK+ TALK–

SAFETY GROUND

Personal injury or property damage can result from the discharge of static electricity. Connect a 14 AWG (2.08 mm2) ground strap between the digital valve controller and earth ground when flammable or hazardous gases are present. Refer to national and local codes and standards for grounding requirements. To avoid static discharge from the plastic cover, do not rub or clean the cover with solvents. Clean with a mild detergent and water only. 4. Connect the safety ground and the earth ground as shown in figure 2-20. Replace and hand tighten the cover on the terminal box. When the loop is ready for startup, apply power to the control system output card.

A6193-1/IL

Figure 2-20. Type DVC5000 Series Digital Valve Controller Terminal Box

Test Connections WARNING

CAUTION Do not connect the digital valve controller directly to a voltage source when implementing the point-to-point wiring mode, or damage to the pwb assembly submodule may result. In point-to-point wiring mode, the digital valve controller may only be connected to a 4–20 mA current source.

Wire the digital valve controller as follows: (refer to figures 10-1 through 10-4 for identification of parts). 1. Remove the terminal box cap (key 4) from the terminal box (key 3). 2. Bring the field wiring into the terminal box. When applicable, install conduit using local and national electrical codes which apply to the application. 3. Connect the positive wire from the control system output card ‘‘current output’’ to the LOOP + screw terminal on the pwb/terminal strip assembly in the terminal box. Connect the negative (or return) wire from the control system output card to the LOOP – screw terminal in the terminal box as shown in figure 2-20.

2-24

Personal injury or property damage caused by fire or explosion may occur if the following procedure is attempted in an area which contains a potentially explosive atmosphere or has been classified as hazardous. Confirm that area classification and atmosphere conditions permit the safe removal of the terminal box cap before proceeding. Test connections inside the terminal box can be used to measure loop current across a 1 ohm resistor. 1. Remove the terminal box cap. 2. Adjust the test meter to measure a range of 0.001 to 0.1 volts. 3. Connect the positive lead of the test meter to the TEST + connection and the negative lead to the TEST – connection inside the terminal box. 4. Measure Loop current as: Voltage (on test meter) 1000 = milliamps example: Test meter Voltage X 1000 = Loop Milliamps 0.004 X1000 = 4.0 milliamperes 0.020 X 1000 = 20.0 milliamperes May 1998


Turn static files into dynamic content formats.

Create a flipbook
Issuu converts static files into: digital portfolios, online yearbooks, online catalogs, digital photo albums and more. Sign up and create your flipbook.
DLC3000 Quick Start~Errata~Instruction Manual by RMC Process Controls & Filtration, LLC. - Issuu