3582~3582i~582i~3583 Instruction Manual Feb 2012

Page 33

Instruction Manual

3582, 582i, and 3583

D200138X012

February 2012

Figure 17. Schematic Illustration of Fisher 3582 Positioner OUTPUT TO ACTUATOR RELAY INSTRUMENT INPUT

BELLOWS SUPPLY

FEEDBACK AXIS PIVOT NOZZLE FLAPPER ASSEMBLY

ROTARY SHAFT ARM

DIRECT ACTING QUADRANT

TRAVEL PIN

INPUT AXIS CAM BEAM

22A7965‐A A2453‐2

REVERSE ACTING QUADRANT

3582i Valve Positioner As shown in figure 18, the 3582i electro‐pneumatic valve positioner has a 582i electro‐pneumatic converter attached to the valve positioner. The 582i contains an I/P module which provides a pneumatic output proportional to a DC current input signal. The DC current input operates coils in a force balanced beam system which in turn, control bleed air through an integral nozzle/flapper arrangement. The nozzle pressure provides the pneumatic input signal pressure used by the pneumatic valve positioner. Figure 18. Schematic Illustration of Fisher 3582i Positioner 4‐20 MILLIAMPERE— INPUT SIGNAL ) PNEUMATIC SIGNAL FROM CONVERTER 582i CONVERTER

BELLOWS FEEDBACK AXIS

SUPPLY

NOZZLE BEAM DIRECT ACTING QUADRANT

OUTPUT TO ACTUATOR RELAY ROTARY SHAFT ARM

INPUT AXIS CAM

PIVOT FLAPPER ASSEMBLY

REVERSE ACTING QUADRANT

A4818‐2