Free-standing gas fireplaces - Balanced flue system manual (GB)

Page 1

FREE-STANDING GAS FIREPLACES BALANCED FLUE PIPE MANUAL (GB) CARO GAS VIVA L GAS NEXO GAS Q-TEE 2 GAS Q-TEE 2 C GAS


1st edition 10.10.2023


BALANCED FLUE PIPE MANUAL

CONTENTS INTRODUCTION

FLUE REGULATIONS

Horizontal outlet Overhang requirements for parallel construction Distances from wall outlet Parallel building and distance requirements Vertical outlet

INSTALLATION

Introduction to flue pipe solutions Vertical terminal through the roof Vertical terminal along the outer wall Horizontal wall terminal Horizontal wall terminal with snorkel Horizontal snorkel wall terminal with back outlet Vertical terminal for existing chimney Exodraft Fan (optional)

SPARE PARTS LIST

Coloured design pipes – Ø100/150 US pipes – Ø100/150 Accessories – Ø100/150 Roof – Ø100/150 Renovation kits – Ø100/150

4 6

GB

Introduction to balanced flue pipe manual About balanced flue pipe systems

8 9 9 9 10

11 12 20 26 31 35 39 44

45 48 50 55 56

3


INTRODUCTION

GB

INTRODUCTION TO BALANCED FLUE PIPE MANUAL The manual provides a detailed description of how to connect a free-standing gas fireplace to a balanced flue pipe system. The balanced flue pipe manual covers all free-standing gas fireplaces from RAIS and Attika. It applies to the following models: • Caro Gas • Viva L Gas • Nexo Gas • Q-Tee 2 Gas • Q-Tee 2 C Gas A balanced flue pipe system consists of pipes with an outer and inner pipe. The outer pipe acts as an intake channel, bringing fresh air from outside for the combustion process, while the inner pipe efficiently removes the exhaust gases. A balanced flue pipe system contributes to a safer and more efficient operation of the gas fireplace and does not affect the house’s pressure or air quality. The chimney for a gas fireplace should be installed in accordance with this exhaust manual to ensure correct and safe operation. Follow all instructions carefully to achieve optimal performance and avoid any issues with the exhaust system. FIVE DIFFERENT FLUE PIPE SYSTEMS The manual is divided into six different exhaust systems. The installation solutions are: • Vertical terminal through a roof • Vertical terminal along an outer wall • Horizontal wall terminal • Horizontal wall terminal with snorkel • Horizontal snorkel wall terminal with back outlet • Vertical terminal for an existing chimney This manual describes the most common variations of these five solutions. It’s worth noting that there may be several different variants of each solution available. The manual provides examples of solutions for each of the five flue pipe systems. To achieve the best solution for your gas fireplace, it is recommended to carefully follow the instructions in the manual and consult with a professional technician for further guidance if necessary.

4

FIND PART NUMBERS FOR SPARE PARTS There is an overview of exhaust parts for gas fireplaces at the back of the flue pipe manual. The manual continuously references part numbers for examples of solutions for the four exhaust systems. Find spare parts with part numbers starting from page 45.


INTRODUCTION

INSTRUCTIONS FOR USING QR CODES Several places within the manual, you will find QR codes with links to video guides for different installations.

Please note that this manual is an essential part of the gas fireplace installation process. Ensure that you adhere to national or local regulations concerning exhaust systems before installation.

For using the QR codes, simply open the camera function on your phone and point it at the code. You will then get the option to open a link to the video guide.

If you have any doubts or questions about the guidance provided, do not hesitate to contact your RAIS/Attika dealer for further assistance.

This provides you with easy access to additional instructions and visual guidance during the installation process.

GB

HOW TO USE THIS MANUAL This manual provides you with step-by-step instructions and guidelines for the installation of a balanced flue pipe system.

WARNINGS Please note the symbols below that indicate potentially dangerous situations. SYMBOL

DESCRIPTION Visual sign illustrating an important notice or caution. Visual sign illustrating a potential hazard.

INFORMATION PLATE The balanced exhaust system comes with an accompanying information plate that includes a certificate number, indicating the product’s approval. Depending on the type of pipe, there are three different nameplates: US, USD, and XE/XD. These information plates are an important reference for verifying that the exhaust system is approved and meets the necessary standards and safety requirements.

5


INTRODUCTION

GB

ABOUT BALANCED FLUE PIPE SYSTEMS The balanced flue pipe system is crucial for the optimal function of the gas fireplace. Without proper flow in the flue pipe system, the fireplace will not operate efficiently. Ensure that you follow the instructions in the manual for safe operation and maximum performance. APPROVED FLUE PIPE SYSTEMS The following flue pipe systems are approved for RAIS and Attika gas fireplaces: MANUFACTURER

SYSTEM

ADAPTER

Schiedel

Metaloterm US system

No adapter

Schiedel

Metaloterm USD system

No adapter

Müllink & Grol

Multi-Vent system

Adapter needed

Poujoulat

DUOGAS system

Adapter needed

Jeremias

TWIN-GAS system

Adapter needed

Exodraft

RHGC

No adapter

RAIS and Attika recommend using the Metaloterm US and USD exhaust systems from the manufacturer SchiePART for the installation of gas fireplaces. The instructions in this manual are therefore based on the use of these pipes. They can be easily connected to the gas fireplace without the need for an adapter. THREE DIFFERENT PIPE TYPES The solutions are divided into the following three types: 1) US pipes 2) USD pipes 3) XE/XD flexible pipes US pipes are our “general” type of pipe, suitable for installations where chimneys are not visible. They are assembled with clamps and are available in black and stainless steel. ”USD pipes (also called design pipes) are typically used in solutions where chimneys are visible. The pipes are pushed together, creating almost invisible joints, and they can be secured with a smooth clamp band. USD pipes are available in all RAIS and Attika colors.” XE/XD flexible pipes are often used in conjunction with 6

US and/or USD pipes for installations where there is already an existing chimney. DIMENSIONS OF PIPES The three types of pipes are available in two dimensions: 1) Ø100/150 (with item numbers ending in 10) 2) Ø130/200 (with item numbers ending in 13) Free-standing gas fireplaces come with a coupling for Ø100/150 mm. To improve the draft in the chimney, it may be beneficial to expand the pipe dimension from Ø100/150 mm to Ø130/200 mm. This will help to optimize the efficiency and performance of the exhaust system, which is crucial for optimal operation of the gas fireplace. OBSERVE THE FOLLOWING REGULATIONS • Install the balanced flue pipe system in accordance with the manufacturer’s instructions and this manual. • Use the manufacturer’s prescribed wall brackets to secure the flue pipe system. • Avoid mixing different types of balanced flue pipe systems. • Ensure that the balanced pipes are fully assembled and pushed together as much as possible. • Install the system without tension and use the approved mounting brackets and clamps. • Ensure there is a slope of 3 degrees back towards the fireplace (approx. 5 mm per meter) to ensure proper drainage of condensation water. Only wall terminals should have a slope away from the fireplace. • Always maintain a distance of 50 mm from the chimney to combustible material. • Ensure that the balanced pipes do not come into contact with combustible material and are not placed in a closed environment with combustible material. • Refrain from starting exhaust systems with a measuring point, a bend, or an adjustable pipe.


INTRODUCTION

2. Install a square box made of non-combustible material with dimensions of 250 x 250 (Ø100/150) or 300 x 300 (Ø130/200) mm. On the inside and outside of the wall, use a set of center plates (item number USCP) or a large wall cover (item number USMPG) to center the terminal and cover the hole.

Connections in flue pipe systems must be tight and secured so that they cannot unintentionally be separated.

When the exhaust pipes need to be cut for adjustment, we do not recommend grinding the pipes afterward due to the risk of burning the stainless steel. Always remove burrs and sawdust after cutting. Only USPP and terminals can be cut.

Extraction must not be routed through common stairwells. Disconnected chimneys or ventilation ducts can be used as routing channels. Ensure that wall and roof penetrations are waterproof and properly secured. This will prevent water intrusion and ensure a reliable installation of the exhaust system. For wall terminals, always ensure that the air intake has a slight slope towards the outside to divert moisture. We recommend a slope of 2-3 degrees for optimal drainage. This will help maintain efficient and safe operation of the extraction system. When using an existing chimney, make sure the chimney is cleaned and sealed. To avoid fire hazards during installation, there should always be a 50 mm clearance around the exhaust system to flammable materials. This can be achieved in two ways:

The use of stainless steel systems in a closed room, where there may be a high concentration of steam and acid in the air (such as in swimming pools, laundries, etc.), can cause problems. This also applies to installations in the immediate vicinity of the sea and/or with a sea view. The terminal can reach temperatures of up to 200°C. Therefore, ensure that the placement of the terminal prevents direct contact between individuals and the terminal. Exhaust gases can reach temperatures of up to 400°C. Terminals placed under awnings or balconies can pose a danger due to the accumulation of hot gases and are therefore not allowed. If terminals are close to neighbouring buildings or ventilation openings, refer to national or local regulations.

1. Use an additional pipe made of non-combustible material with a diameter of 250 (Ø100/150) or 300 (Ø130/200) mm.

NOTE! Maximum length of pipes to external wall and roof: • The maximum permitted length without bends is 15 meters. • For Ø130/200, each bend counts as 0.5 meters. • For Ø100/150, each 30-45-degree bend counts as 0.5 meters, and each 90-degree bend counts as 1 meter. Minimum vertical starting height for exhaust pipes for the following free-standing gas models: Caro, Nexo, Viva L, Q-Tee 2 and Q-Tee 2 C is 0.5 meter.

WARNING! Secure the balanced exhaust system firmly to a noncombustible wall or ceiling using mounting brackets to prevent loosening and potential leaks of flue gas and/or combustion air, which can lead to dangerous situations. Recommendations: • Install a mounting bracket every 2 meters. • Always install a bracket after the first meter and the last meter. • Always install a bracket at every bend.

7

GB

BALANCES FLUE PIPE SYSTEM REGULATIONS Air supply and discharge from devices with a closed combustion chamber are safely directed into the openair environment without disturbing residents or the surrounding environment. Always ensure compliance with national requirements when determining the placement of terminals for exhaust and air intake. This will ensure that the installation meets the necessary safety standards and environmental guidelines.


FLUE REGULATIONS

GB

FLUE REGULATIONS Please note that the exhaust regulations on the following pages are in accordance with Danish national guidelines. It is important to always follow national regulations and requirements to ensure a correct and safe installation. HORIZONTAL OUTLET Please note that the horizontal exhaust pipe is not approved to terminate everywhere. There are several places where the exhaust opening must not be located, unless the gas supplier approves the location based on a comprehensive assessment. The flue outlet must not be placed: • In a carport • In a niche or base shaft • Under stairs • Under an extension or similar • Facing a walkway or public area For outlet in an external wall, the exhaust must be positioned so that, from the center of the exhaust opening, there is at least a 45° angle to any roof overhang, both for overhangs located above the exhaust and for overhangs on the flat angle perpendicular to the exhaust, if this is less than 1.5 m (see illustration 1).

Illustration 1

NOTE! Please note that the subsequent requirements for the exhaust are based on Danish regulations and can therefore only be used as guidance. You must always follow the national regulations when installing the balanced flue pipe system.

8


FLUE REGULATIONS

GB

OVERHANG REQUIREMENTS FOR PARALLEL CONSTRUCTION For horizontal distances greater than 0.5 meters to a parallel building, the requirement of 45° is no longer applicable (illustration 2).

Illustration 2

DISTANCE FROM WALL OUTLET On a surface around the outlet, with dimensions as shown below, the following must not be placed (illustration 3):

• Windows and doors that can be opened • Building corners and protruding elements • Openings for fresh air supply • Openings for the ventilation of combustion products

Illustration 3

PARALLEL BUILDING AND DISTANCE REQUIREMENTS For surfaces parallel to the exhaust, there must be at least 2.0 meters to:

• Windows and doors that can be opened • Openings for fresh air supply • Openings for the ventilation of combustion products Additionally, the following distance requirements from the chimney outlet must be met (illustration 4):

• Min. 0.2 m horizontally and 0.5 m vertically to the control cabinet.

• Min. 0.3 m above the ground. • Min. 1.0 m from the outlet to thatched or wood-cut

Illustration 4

roofs.

• Min. 2.0 m to the opposite building. • Min. 2.5 m to the neighbouring property line and common living and walking areas.

9


GB

FLUE REGULATIONS

VERTICAL OUTLET The chimney can be used as a fresh air duct under the following conditions:

• The chimney is assessed to be in reasonably good condition, and

• The cross-sectional area of the chimney minus the cross-sectional area of the appliance’s flue pipe is greater than or equal to the cross-sectional area of the appliance’s intake manifold.

• The system must be terminated at the outlet with

roof flashing and chimney covering in accordance with this manual.

The distance to the intake opening, measured perpendicular to the roof surface, should be at least 0.3 m. (see illustration 5). On a surface around the outlet, with dimensions as shown below in illustration 6, the following must not be placed: A: Windows and doors in living rooms that can be opened B: Building corners and protruding parts, including the chimney C: Openings for fresh air supply D: Openings for discharging combustion products

Illustration 5

Illustration 6 10


INSTALLATION

INTRODUCTION TO BALANCED FLUE PIPE SOLUTIONS The next pages cover the most fundamental exhaust installations and combinations.

On the following pages, each solution is described.

VERTICAL TERMINAL THROUGH THE ROOF

VERTICAL TERMINAL ALONG THE EXTERIOR WALL

HORIZONTAL WALL TERMINAL

HORIZONTAL WALL TERMINAL WITH SNORKEL

HORISONTAL SNORKEL WALL TERMINAL WITH BACK OUTLET

VERTICAL TERMINAL FOR EXISTING CHIMNEY

SIDE 12

SIDE 20

SIDE 28

SIDE 31

SIDE 35

SIDE 39

TABLE FOR MIN. AND MAX. PIPE LENGTH On the pages with the exhaust solutions, there’s an accompanying table with exhaust combinations. Each table explains the permitted vertical and horizontal lengths of the pipe to achieve the correct airflow.

RESTRICTORS During the installation of each gas fireplace, two different restrictors are included. These restrictors are used to achieve the correct airflow in the balanced exhaust system.

Table with exhaust combinations

To determine which restrictor to use, you can either observe the flames or use the pipe length diagrams (see A, B), which provide a good idea of the correct type of restrictor. At start-up, the flames should be blue-yellow, and after 20 minutes, they should have a clearer yellow colour. If the desired appearance of the flames and combustion is not achieved, another restrictor can be installed to adjust the airflow and achieve the desired result.

Restrictor A

Restrictor B

11

GB

In total, there are six exhaust solutions for our freestanding gas fireplaces, all of which are illustrated below. The green illustrations represent vertical solutions, the beige illustrations represent horizontal solutions, while the orange illustration shows a solution with an existing installation through the chimney.


INSTALLATION - VERTICAL TERMINAL THROUGH THE ROOF

GB

VERTICAL TERMINAL THROUGH THE ROOF Extraction solution 1: This section describes how to install the exhaust solution with a vertical terminal through a roof and which parts can be used. Follow the guide on the next pages.

VERTICAL TERMINAL THROUGH THE ROOF Page 13 - 19

12


INSTALLATION - VERTICAL TERMINAL THROUGH THE ROOF

FREE-STANDING GAS FIREPLACES – Ø100/150 AND Ø130/200 GB

Use the table below to determine the allowed vertical (and horizontal) lengths of the pipes.

Vertical

Vertical roof terminal (C31) – Ø100/150 and Ø130/200.

Restrictor For more information, see page 11

NOTE! The minimum vertical starting height for free-standing gas fireplaces is 0.5 meter.

13


Vertical

FREE-STANDING GAS FIREPLACES – Ø100/150 Vertical roof outlet with a bend (C31) – Ø100/150

Horizontal

Restrictor For more information, see page 11

FREE-STANDING GAS FIREPLACES – Ø130/200 Vertical roof outlet with a bend (C31) – Ø130/200

Vertical

GB

INSTALLATION - VERTICAL TERMINAL THROUGH THE ROOF

Horizontal

NOTE! The minimum vertical starting height for free-standing gas fireplaces is 0.5 meter.

14

Restrictor For more information, see page 11


INSTALLATION - VERTICAL TERMINAL THROUGH THE ROOF

GB

EXAMPLE OF INSTALLATION SOLUTION WITH VERTICAL THROUGH THE ROOF There are several potential installation solutions with a vertical terminal through a roof. The demonstrated solution serves as an example of how a vertical roof outlet can be installed. Next to each arrow on the drawing is a reference to the part used for the installation solution. For each reference (on the following pages), there is a mounting guide. The part number is indicated in parentheses. All item numbers are collected in an overview at the back of the manual. Please note that the parts used refer to an item number in stainless steel. Several of the parts are available in multiple colours. It is possible to get our Ø100/150 exhaust in design pipes. This means exhausts that do not require a clamp band. Contact your local RAIS or Attika dealer to learn more about our design pipes. In some countries, it is a requirement to install a measuring port. Therefore, follow national regulations. The measuring port is used, among other things, to measure the CO level. Vertical roof vent (99-USDVC210) See part 6 Rosette (more variants) (99-USDR10) See part 7 Flexible roof flashing for corrugated roof (three variants) (99-150M) See part 5A Vapor barrier/membrane (99-UDS150) See part 4 Roof guide (99-USDQ10) See part 3

Flashing for a flat roof (three variants) (99-150G) See part 5B

Clamp (99-USKB10) See part 2

US pipe (three lengths) (99-US) See part 1

NOTE! The solution examples are shown with the pipe dimension Ø100/150. The pipes are also available in the dimension Ø130/200 (these item numbers end in 13).

NOTE! When transitioning from USD pipes, an adapter is needed (99-USDO10/99-USDO2510).

15


GB

INSTALLATION - VERTICAL TERMINAL THROUGH THE ROOF

PART 1: US pipe The US pipe is installed with the end that has one groove facing down towards the gas fireplace (see circle). Item no. 99-US2510 99-US5010 99-US10010 (NOTE! Available in three lengths)

PART 2: Clamp The pipes are mounted and locked with a clamp. Item no. 99-USKB10 (NOTE! Available in seven colours)

PART 3: Roof guide Use a roof guide to protect the pipe against wind and weather. It is mounted around the pipe and secured to the rafters.

Mounted around the pipe

Item no. 99-USDQ10 Secure to the rafters

PART 4: Vapor barrier/membrane The vapor barrier is pulled down over the pipe, and the ends are distributed by connecting it with the existing vapor barrier using approved vapor barrier tape. Item no. 99-UDS150

16


INSTALLATION - VERTICAL TERMINAL THROUGH THE ROOF

The collar is secured with the screws by crosstightening them. Finally, the joints are sealed with a weather-resistant silicone.

GB

PART 5A: Flexible roof flashing The screws are removed (illustration 8). Afterwards, the collar is gently bent around the roof surface and the pipe (illustration 9). Illustration 8

Item no. 99-150M (NOTE! Available in three slopes) See the mounting instructions below. NOTE! To achieve the minimum height for the terminal, an adjustment pipe can be used.

Illustration 9

Installation of flex flashing for corrugated roof

Place the roof flashing over the pipe and the hole, ensuring that the cone is supported. The sides should end with a downward wave.

Remove the back foil.

Lift the froof flashing and heat the roof with a gas burner to max. 60°C.

Install the roof flashing on the roof.

Shape the flex with your fingers to fit the roof profile. Shape only along the edge without the use of tools. Avoid water accumulation.

After the collar is mounted, put the roof plate and roof tiles back in place.

7

Seal the top of the collar with a weather-resistant silicone.

17


GB

INSTALLATION - VERTICAL TERMINAL THROUGH THE ROOF

PART 5B: Flashings for a flat roof The screws are removed (illustration 10). Afterwards, the collar is gently bent around the roof surface and the pipe (illustration 11). The collar is secured with the screws by crosstightening them. Finally, the joints are sealed with a weather-resistant silicone.

Illustration 10

Item no. 99-150G (NOTE! Available in three slopes) Se vejledning for montering herunder. NOTE! To achieve the minimum height for the terminal, an adjustment pipe can be used.

Illustration 11

Installation of hot-dip galvanized flashing for flat roof The plate is secured in a zigzag pattern to the base with roofing nails (however, not if there is insulation in between, then it is glued with silicone adhesive). It is important that there is a solid substrate under the entire flashing plate (see illustration 12). Top paper is welded on with a factor 50/50. Stop at min. 15 mm from the penetration.

Illustration 12

The 15 mm until the pipe/cone is sealed with a weather-resistant silicone (see illustration 13).

Illustration 13

18


INSTALLATION - VERTICAL TERMINAL THROUGH THE ROOF

GB

PART 6: Vertical roof vent The vertical roof cap is mounted with a clamp. Item no. 99-USDVC210 (NOTE! Available in black and stainless steel) The clamp has the following item no.: 99-USKB10.

Vertical roof vent

Spændebånd

PART 7: Rosette The rosette is mounted between the pipe and the ceiling. Item no. 99-USDR10 (smooth rosette without screw holes) 99-USR10 (smooth rosette with screw holes) DIV1000RAIS (rosette with custom-made incline)

19


INSTALLATION - VERTICAL TERMINAL ALONG THE EXTERIOR

GB

VERTICAL TERMINAL ALONG THE EXTERIOR WALL Extraction solution 2: This section describes how to install the exhaust solution with a vertical terminal along an exterior wall, and which parts can be used. Follow the guide on the next pages.

VERTICAL TERMINAL ALONG THE EXTERIOR WALL Page 21 - 25

20


INSTALLATION - VERTICAL TERMINAL ALONG THE EXTERIOR

FREE-STANDING GAS FIREPLACES – Ø100/150 GB

Use the tables below to determine the allowed vertical and horizontal lengths of the pipes.

Vertical

Vertical roof outlet with bend (C31) – Ø100/150.

Horizontal

Restrictor For more information, see page 11

Vertical

FREE-STANDING GAS FIREPLACES – Ø130/200 Vertical roof outlet with bend (C31) – Ø130/200

Horizontal

Restrictor For more information, see page 11

NOTE! The minimum vertical starting height 0,5 meter.

21


GB

INSTALLATION - VERTICAL TERMINAL ALONG THE EXTERIOR

EXAMPLE OF INSTALLATION SOLUTION WITH VERTICAL TERMINAL ALONG EXTERIOR WALL There are several potential installation solutions with a vertical terminal along an exterior wall exist. The solution illustrates how a vertical installation along an exterior wall can be implemented. Next to each arrow on the drawing is a reference to the part used for the installation solution. For each reference (on the following pages), there is a mounting guide. The part number is indicated in parentheses. All item numbers are collected in an overview at the back of the manual. Please note that the parts used refer to an item number in stainless steel. Several of the parts are available in multiple colours. It is possible to get our Ø100/150 exhaust in design pipes. This means exhausts that do not require a clamp band. Contact your local RAIS or Attika dealer to learn more about our design pipes. In some countries, it is a requirement to install a measuring port. Therefore, follow national regulations. The measuring port is used, among other things, to measure the CO level.

Vertical roof vent (99-USDVC210) See part 10 Vapor barrier/membrane (99-USD150) See part 3

US pipe (three lengths) (99-US) See part 9

Rosette (more varants) (99-UDS150) See part 2

Wall bracket US (USMB10) See part 8

US pipe (three lengths) (99-US) See part 1

Clamp (99-USKB10) PART 7 90° pipe with a tee fitting (99-UST9010) PART 6 Condensate collector (99-USRBK10) PART 5 Condensate drain cap (99-USE0304) PART 5 Adjustable pipe (99-USPP10) PART 4

NOTE! The solution examples are shown with the pipe dimension Ø100/150. The pipes are also available in the dimension Ø130/200 (these item numbers end in 13). It is not possible to start with a measuring point; a minimum of a 250 mm straight pipe must be used first.

NOTE! When transitioning from USD pipes, an adapter is needed (99-USDO10/99-USDO2510). 22


INSTALLATION - VERTICAL TERMINAL ALONG THE EXTERIOR

GB

PART 1: US pipe The US pipe is installed with the end that has one groove facing down towards the gas fireplace (see circle). Item no. 99-US2510 99-US5010 99-US10010 (NOTE! Available in three lengths)

PART 2: Rosette The rosette is mounted between the pipe and the ceiling. Item no. 99-USDR10 (smooth rosette without screw holes) 99-USR10 (smooth rosette with screw holes) DIV1000RAIS (rosette with custom-made incline)

PART 3: Vapor barrier/membrane The vapor barrier/membrane is pulled down over the pipe, and the ends are sealed to the existing vapor barrier with approved vapor barrier tape. Item no. 99-UDS150

PART 4: Adjustable pipe Adjustable pipe 330-500 mm. Pull the sliding pipe out to the desired length and lock it using the included clamp. Item no. 99-USPP10 (NOTE! Available in seven lenghts)

23


GB

INSTALLATION - VERTICAL TERMINAL ALONG THE EXTERIOR

PART 5: Condensate collector and condensate drain cap The condensate collector is mounted with a clamp. The condensate drain cap is mounted in extension of the condensate collector. Item no. 99-USRBK10 99-USE0304

PART 6: 90° pipe with a tee fitting The pipes are mounted and locked with a clamp. Item no. 99-UST9010

PART 7: Clamp The pipes are mounted and locked with a clamp. Item no. 99-USKB10

PART 8: Wall bracket Use brackets to secure the pipe to the wall. The bracket is mounted using raw plugs and two screws. Item no. 99-USMB10

24

Condensate collector

Condensate drain cap

Connection through wall


INSTALLATION - VERTICAL TERMINAL ALONG THE EXTERIOR

GB

PART 9: US pipe The US pipe is installed with the end that has one groove facing down towards the gas fireplace (see circle). Item no. 99-US2510 99-US5010 99-US10010 (NOTE! Available in three lengths)

PART 10: Vertical roof vent The vertical roof vent is mounted with a clamp. Item no. USDVC210 (NOTE! Available in black and stainless steel) The clamp has the following item no.: 99-USKB10. Vertical roof vent

Clamp

25


INSTALLATION - HORIZONTAL WALL TERMINAL

GB

HORIZONTAL WALL TERMINAL Extraction solution 3: This section describes how to install the exhaust solution with a horizontal wall terminal and which parts can be used. Follow the guide on the next pages.

HORIZONTAL WALL TERMINAL Page 27 - 30

26


INSTALLATION - HORIZONTAL WALL TERMINAL

FREE-STANDING GAS FIREPLACES – Ø100/150 GB

Use the tables below to determine the allowed vertical and horizontal lengths of the pipes.

Vertical

Horizontal wall terminal with bend (C31) – Ø100/150.

Horizontal

Restrictor For more information, see page 11

Vertical

FREE-STANDING GAS FIREPLACES – Ø130/200 Horizontal wall terminal through the wall (C31) – Ø130/200.

Horizontal

Restrictor For more information, see page 11

NOTE! The minimum vertical starting height 0,5 meter.

27


GB

INSTALLATION - HORIZONTAL WALL TERMINAL

EXAMPLE OF INSTALLATION SOLUTION WITH HORIZONTAL TERMINAL THROUGH WALL There are different variants of installation solutions with a horizontal terminal through a wall, and the shown solution is just an example of how such a horizontal installation can be performed. Next to each arrow on the drawing is a reference to the part used for the installation solution. For each reference (on the following pages) there is a guide to assembly. The item number of the part is stated in the parenthesis. All item numbers are compiled in an overview at the back of the manual. Please note that the used parts refer to an item number in stainless steel. It is possible to get our Ø100/150 exhaust in design pipes. This means exhausts that do not require a clamp band. Contact your local RAIS or Attika dealer to learn more about our design pipes. In some countries, it is a requirement to install a measuring port. Therefore, follow national regulations. The measuring port is used, among other things, to measure the CO level. Vapor barrier/membrane (99-UDS150) See part 6 Horizontal wall outlet (99-USDHC210) See part 7

Rosette (99-USR10) See part 5 90° pipe bend US (99-USB9010) See part 4 Adjustable pipe (99-USPP10) See part 3 Clamp (99-USKB10) See part 2 US pipe (three lengths) (99-US) See part 1

NOTE! The solution examples are shown with the pipe dimension Ø100/150. The pipes are also available in the dimension Ø130/200 (these item numbers end in 13).

28


INSTALLATION - HORIZONTAL WALL TERMINAL

GB

PART 1: US pipe The US pipe is installed with the end that has one groove facing down towards the gas fireplace (see circle). Item no.99-US2510 99-US5010 99-US10010 (NOTE! Available in three lengths)

PART 2: Clamp The pipes are mounted and locked with a clamp. Item no. 99-USKB10 (NOTE! Available in seven colours)

PART 4: Adjustable pipe Adjustable pipe 330-500 mm. Pull the sliding pipe out to the desired length and lock it using the included clamp. Item no. 99-USPP10 (NOTE! Available in more colours)

PART 4: 90° US bend The clamp is mounted with a clamp. Item no. 99-USB9010

29


GB

INSTALLATION - HORIZONTAL WALL TERMINAL

PART 5: Rosette The rosette is mounted between the pipe and the ceiling. Item no. 99-USDR10 (glat rosette uden skruehuller) 99-USR10 (smooth rosette with screw holes) DIV1000RAIS (rosette with custom-made incline)

PART 6: Vapor barrier/membrane The vapor barrier/membrane is pulled down over the pipe, and the ends are sealed to the existing vapor barrier with approved vapor barrier tape. Item no. 99-UDS150

PART 7: Horizontal wall outlet The horizontal wall outlet is mounted externally and secured to the wall with the included screws. Ensure that the air intake is at a slight angle so that moisture can drain out. The recommended angle is 1.3 degrees or a slope of 2-5%. Item no. 99-USDHC210 (NOTE! Available in black and stainless steel)

30


INSTALLATION - HORIZONTAL WALL TERMINAL WITH SNORKEL

HORIZONTAL WALL TERMINAL WITH SNORKEL

GB

Extraction solution 4: This section describes how to install the exhaust solution with a horizontal wall terminal with a snorkel, and which parts can be used. Follow the guide on the next pages.

HORIZONTAL WALL TERMINAL WITH SNORKEL Page 32 - 34

31


GB

INSTALLATION - HORIZONTAL WALL TERMINAL WITH SNORKEL

EXAMPLE OF INSTALLATION SOLUTION WITH HORIZONTAL WALL TERMINAL WITH SNORKEL There are different variants of installation solutions with a horizontal wall terminal with a snorkel. The shown solution is an example of how to install a horizontal solution with a snorkel. It is also possible to mount the snorkel on our freestanding gas fireplaces with a direct rear exit from the fireplace. Next to each arrow on the drawing is a reference to the part used for the installation solution. For each reference (on the following pages), there is a mounting guide. The item number of the part is shown in the parentheses. All item numbers are compiled in an overview at the back of the manual. Please note that the used parts refer to an item number in stainless steel. Several of the parts are available in multiple colors. It is possible to get our Ø100/150 exhaust in design pipes. This means exhausts that do not require a clamp band. Contact your local RAIS or Attika dealer to learn more about our design pipes. In some countries, it is a requirement to install a measuring port. Therefore, follow national regulations. The measuring port is used, among other things, to measure the CO level. Wall penetration for snorkel 600 mm (USWT6010) See part 5 Vapor barrier/membrane (99-UDS200) See part 4 Rosette (more variants) (99-USR10) See part 3

90° US bend (99-USB9013) See part 2

US pipes (three lengths) (99-US) See part 1

NOTE! The maximum horizontal length for a snorkel installation is 1500 mm. 32

Snorkel terminal (USDSC10 or USDSC110) See part 6


INSTALLATION - HORIZONTAL WALL TERMINAL WITH SNORKEL

GB

PART 1: US pipe The US pipe is installed with the end that has one groove facing down towards the gas fireplace (see circle). Item no. 99-US2510 99-US5010 99-US10010 (NOTE! Available in three lengths)

PART 2: 90° US bend The clamp is mounted with a clamp. Item no. 99-USB9010

PART 3: Rosette The rosette is mounted between the pipe and the ceiling. Item no. 99-USDR10 (glat rosette uden skruehuller) 99-USR10 (smooth rosette with screw holes) DIV1000RAIS (rosette with custom-made incline)

PART 4: Vapor barrier/membrane The vapor barrier is pulled down over the pipe, and the ends are connected to the existing vapor barrier using approved vapor barrier tape. Item no. 99-UDS150

PART 5: Wall penetration for snorkel (600 mm) The wall penetration is mounted outside with four screws (see arrow). Any excess length can – if necessary – be cut off (see circle). Item no. USWT6010 (NOTE! Available in more colours) 33


GB

INSTALLATION - HORIZONTAL WALL TERMINAL WITH SNORKEL

PART 6: Snorkel terminal The snorkel terminal is available in two heights: 865 mm (99-USDSC10) and 1300 mm (99-US10U0036). Installation 1. Mark the center of the pipe dimensions on the wall and make a 160 mm hole through the wall using a core drill, a hammer and chisel, or other appropriate methods. 2. Align the fireplace with the hole. 3. Determine the necessary horizontal length of the pipe. The wall entry pipe can be both shortened and extended by mounting an additional length. If an additional length is used, the joint must be secured with a stainless screw or rivet. 4. Install the wall entry pipe on the wall and connect it to the fireplace’s outlet. Secure the wall plate with 4 mounting screws. Ensure that the air intake is on a slight slope so that moisture can drain outwards. The recommended angle is 1-3 degrees or a 2-5% slope. 5. Dismantle the snorkel by unscrewing the 4 screws. 6. Adjust the snorkel’s backplate with the wall entry pipe. Place the backplate completely flat against the wall and check that it is vertical. Screw the backplate in place using the four mounting points. Use the spacers to protect the back wall. 7. Finally, mount the snorkel body on the backplate. First, position the top of the snorkel body in place, and then place the exhaust hose in the wall plate pipe. The body should fit flat on the backplate. Secure the snorkel body to the backplate using the 4 mounting bolts.

Always remember to maintain a safety distance of 50 mm from the pipe to flammable material.

Spacers for the protection of external walls.

34


INSTALLATION - HORIZONTAL SNORKEL WALL TERMINAL WITH BACK OUTLET

HORIZONTAL SNORKEL WALL TERMINAL WITH BACK OUTLET

GB

Extraction solution 5: This section describes how to install the exhaust solution with a vertical snorkel wall terminal with a direct back outlet, and which parts can be used. Follow the guide on the next pages.

HORIZONTAL SNORKEL WALL TERMINAL WITH BACK OUTLET Page 36 - 38

35


GB

INSTALLATION - HORIZONTAL SNORKEL WALL TERMINAL WITH BACK OUTLET

EXAMPLE OF INSTALLATION SOLUTION WITH VERTICAL SNORKEL WALL TERMINAL WITH BACK OUTLET There can be several variants of an installation solution with a vertical snorkel wall terminal with a rear exit. The solution shown is an example of how to install a vertical snorkel solution with a rear exit. Next to each arrow on the drawing is a reference to the part used for the installation solution. For each reference (on the following pages), there is an assembly guide. The part number is indicated in parentheses. All part numbers are listed in an overview at the end of the manual. Please note that the parts used refer to a stainless steel part number. Several of the parts are available in different colors. It is possible to obtain our Ø100/150 ventilation in design pipes. This means ventilation that does not require a clamp. Contact your local RAIS dealer for more information on our design pipes. In some countries, it is a requirement to install a measurement piece. Therefore, follow national regulations. The measurement piece is used, among other things, to measure CO levels. For direct rear exit with a measurement piece, our Viva L and Caro models require a starting piece of 250 mm. WALL PENETRATION FOR SNORKEL 600 MM (USWT6010) See part 4 Vapor barrier/membrane (99-UDS200) See part 3 Rosette (more variants) (99-USR10) See part 2

US PIPES (THREE LENGTHS) (99-US) See part 1

NB! The maximum horizontal length for a snorkel installation is 1500 mm.

36

Snorkel terminal (USDSC10 or USDSC110) See part 5


INSTALLATION - HORIZONTAL SNORKEL WALL TERMINAL WITH BACK OUTLET

GB

PART 1: US pipes The US pipe is installed with the end that has one groove facing down towards the gas fireplace (see circle). Item no. 99-US2510 99-US5010 99-US10010 (NOTE! Available in three lengths)

PART 2: Rosette The rosette is mounted between the pipe and the ceiling. Item no. 99-USDR10 (glat rosette uden skruehuller) 99-USR10 (smooth rosette with screw holes) DIV1000RAIS (rosette with custom-made incline)

PART 3: Vapor barrier/membrane The vapor barrier is pulled down over the pipe, and the ends are connected to the existing vapor barrier using approved vapor barrier tape. Item no. 99-UDS150

PART 4: WALL PENETRATION FOR SNORKEL (600 mm) The wall penetration is mounted outside with four screws (see arrow). Any excess length can – if necessary – be cut off (see circle). Item no. USWT6010 (NOTE! Available in more colours)

37


GB

INSTALLATION - HORIZONTAL SNORKEL WALL TERMINAL WITH BACK OUTLET

PART 5: Snorkel terminal The snorkel terminal is available in two heights: 865 mm (99-USDSC10) and 1300 mm (99-US10U0036). Montering 1. Mark the center of the pipe dimensions on the wall and make a 160 mm hole through the wall using a core drill, a hammer and chisel, or other appropriate methods. 2. Align the fireplace with the hole. 3. Determine the necessary horizontal length of the pipe. The wall entry pipe can be both shortened and extended by mounting an additional length. If an additional length is used, the joint must be secured with a stainless screw or rivet. 4. Install the wall entry pipe on the wall and connect it to the fireplace’s outlet. Secure the wall plate with 4 mounting screws. Ensure that the air intake is on a slight slope so that moisture can drain outwards. The recommended angle is 1-3 degrees or a 2-5% slope. 5. Dismantle the snorkel by unscrewing the 4 screws. 6. Adjust the snorkel’s backplate with the wall entry pipe. Place the backplate completely flat against the wall and check that it is vertical. Screw the backplate in place using the four mounting points. Use the spacers to protect the back wall. 7. Finally, mount the snorkel body on the backplate. First, position the top of the snorkel body in place, and then place the exhaust hose in the wall plate pipe. The body should fit flat on the backplate. Secure the snorkel body to the backplate using the 4 mounting bolts.

Always remember to maintain a safety distance of 50 mm from the pipe to flammable material.

Spacers for the protection of external walls.

38


INSTALLATION - VERTICAL TERMINAL FOR EXISTING CHIMNEY

VERTICAL TERMINAL FOR EXISTING CHIMNEY

GB

Extraction solution 6: This section describes how to install the exhaust solution with a vertical terminal through an existing chimney and which parts can be used. Follow the guide on the next pages.

VERTICAL TERMINAL FOR EXISTING CHIMNEY Page 40 - 43

39


INSTALLATION - VERTICAL TERMINAL FOR EXISTING CHIMNEY

Use the table below to determine the allowed vertical lengths of the pipes. Horizontal roof terminal through existing chimney (C91) – Ø100/150 and Ø130/200.

Vertical

GB

FREE-STANDING GAS FIREPLACES – Ø100/150 AND Ø130/200

Restrictor For more information, see page 11

40


INSTALLATION - VERTICAL TERMINAL FOR EXISTING CHIMNEY

GB

EXAMPLE OF INSTALLATION SOLUTION WITH VERTICAL TERMINAL FOR EXISTING CHIMNEY There are various types of installation solutions with a vertical terminal going through an existing chimney. The presented solution illustrates how a vertical installation with an already existing chimney can be performed. Next to each arrow on the drawing is a reference to the part used for the installation solution. For each reference (on the following pages), there is a mounting guide. The item number of the part is shown in the parentheses. All item numbers are compiled in an overview at the back of the manual. Please note that the used parts refer to an item number in stainless steel. Several of the parts are available in multiple colors. It is possible to get our Ø100/150 exhaust in design pipes. This means exhausts that do not require a clamp band. Contact your local RAIS or Attika dealer to learn more about our design pipes. In some countries, it is a requirement to install a measuring port. Therefore, follow national regulations. The measuring port is used, among other things, to measure the CO level. Vertical roof vent (99-USDVC10) See part 7 Renovation kit (top) (USSAN110) See part 6

Transition pipe from flex hose (top) (99-XEAC10 See part 5 Flex hose (99-XE1010P) See part 4 Transition pipe from flex hose (bottom) (99-XEA10) See part 3 Renovation kit (bund) (99-USSAN210) See part 2 US pipe (three lengths) (99-US) See part 1

NOTE! The solution examples are shown with the pipe dimension Ø100/150. The pipes are also available in the dimension Ø130/200 (these item numbers end in 13). 41


GB

INSTALLATION - VERTICAL TERMINAL FOR EXISTING CHIMNEY

PART 1: US pipe The US pipe is installed with the end that has one groove facing down towards the gas fireplace (see circle). Item no. 99-US2510 99-US5010 99-US10010 (NOTE! Available in three lengths)

PART 2: Renovation kit (bottom) The renovation kit can be mounted both horizontally and vertically. In a horizontal installation, a 90-degree elbow (MEB9013) should be used. Item no. 99-USSAN210

Horisontal Vertical

Bend inside chimney (MEB9013)

Plate for mounting on the wall. Seal it with sealant or a sealing ring.

PART 3: Transition pipe from flex hose (bottom)

Flex hose – 10 meter (XE1013P)

Item no. 99-XEA10 Transition pipe for flexible hose. Install the flexible hose on XE1013P.

Bend for attaching to flexible hose (MEB9013).

42


INSTALLATION - VERTICAL TERMINAL FOR EXISTING CHIMNEY

GB

PART 4: Flex hose The flexible hose is available in a box of 10 meters. The hose is cut to an appropriate length. Item no. 99-XE1010P

PART 5: Transition pipe from flex hose (top) Push the flex hose into the transition pipe and twist it to lock it securely. Item no. 99-XEAC10

PART 6: Renovation kit (top) Split transition from flex to balanced exhaust. The inner pipe is for exhaust gases, while the cavity around the pipe is for the supply of fresh air. Item no. 99-USSAN110

Transition to double pipe at the top of the chimney. Secure the plate to the chimney top and seal it with weather-resistant silicone.

Transition to flex hose

PART 7: Vertical roof vent The vertical roof cap is mounted with a clamp. Item no. 99-USDVC210 (NOTE! Available in black and stainless steel) The clamp has the following item no.: 99-USKB10.

43


EXODRAFT FAN

GB

EXODRAFT FAN (OPTIONAL) If the balanced flue system cannot be maintained within the maximum/permitted lengths, it may be a solution to install an Exodraft smoke extractor. GUIDE FOR EXODRAFT FAN Scan the QR code to view an installation guide.

44


SPARE PARTS

COLOURED DESIGN PIPES – Ø100/150 Assembled without clamp DESCRIPTION

99-USD10010 99-USD100B10 99-USD100W10 99-USD100P10 99-USD100SA10 99-USD100N10 99-USD100M10

Pipe Ø100/150 - 1000 mm - Stainless steel Pipe Ø100/150 - 1000 mm - Black Pipe Ø100/150 - 1000 mm - White   Pipe Ø100/150 - 1000 mm - Platinum   Pipe Ø100/150 - 1000 mm - Sand   Pipe Ø100/150 - 1000 mm - Nickel   Pipe Ø100/150 - 1000 mm - Mocha

99-USD5010 99-USD50B10 99-USD50W10 99-USD50P10 99-USD50SA10 99-USD50N10 99-USD50M10

Pipe Ø100/150 - 500 mm - Stainless steel   Pipe Ø100/150 - 500 mm - Black   Pipe Ø100/150 - 500 mm - White   Pipe Ø100/150 - 500 mm - Platinum Pipe Ø100/150 - 500 mm - Sand   Pipe Ø100/150 - 500 mm - Nickel   Pipe Ø100/150 - 500 mm - Mocha

99-USD2510 99-USD25B10 99-USD25W10 99-USD25P10 99-USD25SA10 99-USD25N10 99-USD25M10

Pipe Ø100/150 - 250 mm - Stainless steel Pipe Ø100/150 - 250 mm - Black Pipe Ø100/150 - 250 mm - White       Pipe Ø100/150 - 250 mm - Platinum       Pipe Ø100/150 - 250 mm - Sand Pipe Ø100/150 - 250 mm - Nickel   Pipe Ø100/150 - 250 mm - Mocha

99-USDPP10 99-USDPPB10 99-USDPPW10 99-USDPPP10 99-USDPPSA10 99-USDPPN10 99-USDPPM10

Adjustable pipe Ø100/150 fra 250-360 mm - Stainless steel

Pipe Ø100/150 - 1250 mm w. measuring - Stainless steel Pipe Ø100/150 - 1250 mm w. measuring - Black Pipe Ø100/150 - 1250 mm w. measuring - White   Pipe Ø100/150 - 1250 mm w. measuring - Platinum   Pipe Ø100/150 - 1250 mm w. measuring - Sand   Pipe Ø100/150 - 1250 mm w. measuring - Nickel   Pipe Ø100/150 - 1250 mm w. measuring - Mocha

Adjustable pipe Ø100/150 fra 250-360 mm - Black      Adjustable pipe Ø100/150 fra 250-360 mm - White       Adjustable pipe Ø100/150 fra 250-360 mm - Platinum     Adjustable pipe Ø100/150 fra 250-360 mm - Sand       Adjustable pipe Ø100/150 fra 250-360 mm - Nickel    Adjustable pipe Ø100/150 fra 250-360 mm - Mocha

45

COLOURED DESIGN PIPES – Ø100/150

99-USDS1210 99-USDS12B10 99-USDS12W10 99-USDS12P10 99-USDS12SA10 99-USDS12N10 99-USDS12M10

GB

ITEM NO.


SPARE PARTS

GB

99-USDEM10 99-USDEMB10 99-USDEMW10 99-USDEMP10 99-USDEMSA10 99-USDEMN10 99-USDEMM10

46

DESCRIPTION

Measuring part for design pipe - Stainless steel Measuring part for design pipe - Black Measuring part for design pipe - White Measuring part for design pipe - Platinum Measuring part for design pipe - Sand Measuring part for design pipe - Nickel Measuring part for design pipe - Mocha

99-USDB1510 99-USDB15B10 99-USDB15W10 99-USDB15P10 99-USDB15SA10 99-USDB15N10 99-USDB15M10

15° pipe bend Ø100/150 - Stainless steel 15° pipe bend Ø100/150 - Black 15° pipe bend Ø100/150 - White 15° pipe bend Ø100/150 - Platinum 15° pipe bend Ø100/150 - Sand 15° pipe bend Ø100/150 - Nickel 15° pipe bend Ø100/150 - Mocha

99-USDB3010 99-USDB30B10 99-USDB30W10 99-USDB30P10 99-USDB30SA10 99-USDB30N10 99-USDB30M10

30° pipe bend Ø100/150 - Stainless steel 30° pipe bend Ø100/150 - Black 30° pipe bend Ø100/150 - White 30° pipe bend Ø100/150 - Platinum 30° pipe bend Ø100/150 - Sand 30° pipe bend Ø100/150 - Nickel 30° pipe bend Ø100/150 - Mocha

99-USDB4510 99-USDB45B10 99-USDB45W10 99-USDB45P10 99-USDB45SA10 99-USDB45N10 99-USDB45M10

45° pipe bend Ø100/150 - Stainless steel 45° pipe bend Ø100/150 - Black 45° pipe bend Ø100/150 - White 45° pipe bend Ø100/150 - Platinum 45° pipe bend Ø100/150 - Sand 45° pipe bend Ø100/150 - Nickel 45° pipe bend Ø100/150 - Mocha

99-USDI4510 99-USDI45B10 99-USDI45W10 99-USDI45P10 99-USDI45SA10 99-USDI45N10 99-USDI45M10

45° pipe bend w. measuring - Stainless steel 45° pipe bend w. measuring - Black 45° pipe bend w. measuring - White 45° pipe bend w. measuring - Platinum 45° pipe bend w. measuring - Sand 45° pipe bend w. measuring - Nickel 45° pipe bend w. measuring - Mocha

COLOURED DESIGN PIPES – Ø100/150

ITEM NO.


SPARE PARTS

99-USDI90 10 99-USDI90B10 99-USDI90W10 99-USDI90P10 99-USDI90SA10 99-USDI90N10   99-USDI90M10

90° pipe bend Ø100/150 - Stainless steel 90° pipe bend Ø100/150 - Black 90° pipe bend Ø100/150 - White 90° pipe bend Ø100/150 - Platinum 90° pipe bend Ø100/150 - Sand 90° pipe bend Ø100/150 - Nickel 90° pipe bend Ø100/150 - Mocha

GB

99-USDB9010 99-USDB90B10 99-USDB90W10 99-USDB90P10 99-USDB90SA10 99-USDB90N10 99-USDB90M10

DESCRIPTION

90° pipe bend Ø100/150 w. measurement point - Stainless steel 90° pipe bend Ø100/150 w. measurement poin - Black 90° pipe bend Ø100/150 w. measurement poin - White 90° pipe bend Ø100/150 w. measurement point - Platinum 90° pipe bend Ø100/150 w. measurement poin - Sand 90° pipe bend Ø100/150 w. measurement poin - Nickel 90° pipe bend Ø100/150 w. measurement poin - Mocha

COLOURED DESIGN PIPES – Ø100/150

ITEM NO.

47


SPARE PARTS

US PIPES – Ø100/150 Assembled with clamp

ITEM NO.

DESCRIPTION

99-USPP10 99-USPPB10 99-USPPW10 99-USPPP10 99-USPPSA10 99-USPPN10 99-USPPM10

Adjustable pipe Ø100/150 fra 250 - 360 mm - Stainless steel      Adjustable pipe Ø100/150 fra 250 - 360 mm - Black      Adjustable pipe Ø100/150 fra 250 - 360 mm - White       Adjustable pipe Ø100/150 fra 250 - 360 mm - Platinum       Adjustable pipe Ø100/150 fra 250 - 360 mm - Sand       Adjustable pipe Ø100/150 fra 250 - 360 mm - Nickel      Adjustable pipe Ø100/150 fra 250 - 360 mm - Mocha

99-USEM10 99-USEMB 10 99-USEMW10 99-USEMP10 99-USEMSA10 99-USEMN10 99-USEMM10

Measuring part - Stainless steel Measuring part - Black Measuring part - White Measuring part - Platinum Measuring part - Sand Measuring part - Nickel Measuring part - Mocha

99-USB1510

15° pipe bend Ø100/150 - Stainless steel

99-USB3010

30° pipe bend Ø100/150 - Stainless steel

Pipe US Ø100/150 - 1000 mm - Stainless steel                   Pipe US Ø100/150 - 1000 mm - Black        Pipe US Ø100/150 - 500 mm - Stainless steel Pipe US Ø100/150 - 500 mm - Black Pipe US Ø100/150 - 250 mm - Stainless steel       Pipe US Ø100/150 - 250 mm - Black

US PIPES – Ø100/150

GB

99-US10010 99-US100B10 99-US5010 99-US50B10 99-US2510 99-US25B10

48


99-USB4510 99-USB45B10 99-USB45W10 99-USB45SA10 99-USB45P10 99-USB45N10 99-USB45M10

DESCRIPTION

45° pipe bend Ø100/150 - Stainless steel 45° pipe bend Ø100/150 - Black 45° pipe bend Ø100/150 - White 45° pipe bend Ø100/150 - Sand 45° pipe bend Ø100/150 - Platinum 45° pipe bend Ø100/150 - Nickel 45° pipe bend Ø100/150 - Mocha

99-USB9010 99-USB90B10 99-USB90W10 99-USB90SA10 99-USB90P10 99-USB90N10 99-USB90M10

90° pipe bend Ø100/150 - Stainless steel 90° pipe bend Ø100/150 - Black 90° pipe bend Ø100/150 - White 90° pipe bend Ø100/150 - Sand 90° pipe bend Ø100/150 - Platinum 90° pipe bend Ø100/150 - Nickel 90° pipe bend Ø100/150 - Mocha

99-USKB10 99-USKBB10 99-USKBW10 99-USKBSA10 99-USKBP10 99-USKBN10 99-USKBM10

Clamp Ø100/150 - Stainless steel Clamp Ø100/150 - Black Clamp Ø100/150 - White Clamp Ø100/150 - Sand Clamp Ø100/150 - Platinum Clamp Ø100/150 - Nickel Clamp Ø100/150 - Mocha

99-USKBS10 99-USKBSB10

Clamp with screw Ø100/150 mm - Stainless steel     Clamp with screw Ø100/150 mm - Black

99-USAB10 99-USABB10 99-USABW10 99-USABP10 99-USABS10 99-USABN10 99-USABM10

Covering clamp (glat) Ø100/150 mm - Stainless steel Covering clamp (glat) Ø100/150 - Black Covering clamp (glat) Ø100/150 - White Covering clamp (glat) Ø100/150 - Platinum Covering clamp (glat)t Ø100/150 - Sand Covering clamp (glat) Ø100/150 - Nickel Covering clamp (glat) Ø100/150 - Mocha

US PIPES – Ø100/150

ITEM NO.

GB

SPARE PARTS

49


SPARE PARTS

50

ITEM NO. 99-USVG1013

DESCRIPTION Transition fitting US from Ø100/150 - Ø130/200

99-USVK1013

Transition fitting US from Ø130/200 - Ø100/150

99-USMB10

Wall bracket US Ø100/150 - Stainless steel

99-USMBV410

Adjustable wall bracket US 290-400 mm Ø100/150 mm - Stainless steel

99-USDQ10

Roof guide Ø150

99-USOH210

Wall bracket, heavy, (pair) 50-200 mm for USAPO/USAPU, Ø100/150 - Stainless steel

ACCESSORIES – Ø100/150

GB

TILBEHØR – Ø100/150


SPARE PARTS

DESCRIPTION Justerbart vægophæng NB! Husk supportbånd (99-USMO10)

99-USMO10

Support band (for 99-USOL110) Ø100/150 mm - Stainless steel

99-USOH410

Wall bracket, heavy, (pair) 200-400 mm for USAPO/USAPU, Ø100/150 - Stainless steel

99-USMPG10

Wall covering (large) Ø100 - Stainless steel

99-UDS150

Vapor barrier/membrane Ø150 mm

99-UST9010 99-UST90B10

90° pipe with a tee fitting - Stainless steel 90° pipe with a tee fitting - Black

ACCESSORIES – Ø100/150

GB

ITEM NO. 99-USOL110

51


SPARE PARTS

52

DESCRIPTION Rosette without screw holes (smooth) Ø155/300 mm - Stainless steel

Rosette without screw holes (Smooth) Ø155/300 mm - Black                             Rosette without screw holes (Smooth) Ø155/300 mm - White                                     Rosette without screw holes (Smooth) Ø155/300 mm - Platinum                                  Rosette without screw holes (Smooth) Ø155/300 mm - Sand                                       Rosette without screw holes (Smooth) Ø155/300 mm - Nickel                                   Rosette without screw holes (Smooth) Ø155/300 mm - Mocha Rosette without screw holes (Smooth) - Custom-made to order

99-USR10 99-USRB10 99-USRW10 99-USRP10 99-USRSA10 99-USRN10 99-USRM10 DIV1000RAIS

Rosette w. screw holes (smooth) Ø154/290 mm - Stainless steel                       Rosette w. screw holes (smooth) Ø154/290 mm - Black            Rosette w. screw holes (smooth) Ø154/290 mm - White Rosette w. screw holes (smooth) Ø154/290 mm - Platinum    Rosette w. screw holes (smooth) Ø154/290 mm - Sand    Rosette w. screw holes (smooth) Ø154/290 mm - Nickel    Rosette w. screw holes (smooth) Ø154/290 mm - Mocha Rosette w. screw holes (smooth) - Custom-made to order

99-USCPR10 99-USCPRB10 99-USCPRW10 99-USCPRP10 99-USCPRSA10 99-USCPRN10 99-USCPRM10

Two-part ceiling panel US Ø100/150 - Stainless steel Two-part ceiling panel US Ø100/150 - Black Two-part ceiling panel US Ø100/150 - White Two-part ceiling panel US Ø100/150 - Platinum Two-part ceiling panel US Ø100/150 - Sand Two-part ceiling panel US Ø100/150 - Nickel Two-part ceiling panel US Ø100/150 - Mocha

99-USDO10 99-USDOB10 99-USDOW10 99-USDOP10 99-USDOSA10 99-USDON10 99-USDOM10

Transition pipe from design pipe to US pipe 1000 mm - Stainless steel    Transition pipe from design pipe to US pipe 1000 mm - Black        Transition pipe from design pipe to US pipe 1000 mm - White        Transition pipe from design pipe to US pipe 1000 mm - Platinum                 Transition pipe from design pipe to US pipe 1000 mm - Sand         Transition pipe from design pipe to US pipe 1000 mm - Nickel              Transition pipe from design pipe to US pipe 1000 mm - Mocha

99-USDO2510 99-USDO25B10 99-USDO25W10 99-USDO25P10 99-USDO25SA10 99-USDO25N10 99-USDO25M10

Transition pipe from design pipe to US pipe 250 mm - Stainless steel     Transition pipe from design pipe to US pipe 250 mm - Black        Transition pipe from design pipe to US pipe 250 mm - White        Transition pipe from design pipe to US pipe 250 mm - Platinum                 Transition pipe from design pipe to US pipe 250 mm - Sand         Transition pipe from design pipe to US pipe 250 mm - Nickel              Transition pipe from design pipe to US pipe 250 mm - Mocha

ACCESSORIES – Ø100/150

GB

ITEM NO. 99-USDR10 99-USDRB10 99-USDRW10 99-USDRP10 99-USDRSA10 99-USDRN10 99-USDRM10 DIV1000RAIS


SPARE PARTS

ITEM NO.

DESCRIPTION

99-USE0304 99-USE0304B

Condensate drain cap - Stainless steel Condensate drain cap - Black

99-USWT6010 99-USWT60B10 99-USWT60W10 99-USWT60P10 99-USWT60SA10 99-USWT60N10 99-USWT60M10

Wall penetration for snorkel 600 mm - Stainless steel                    Wall penetration for snorkel 600 mm - Black Wall penetration for snorkel 600 mm - White Wall penetration for snorkel 600 mm - Platinum Wall penetration for snorkel 600 mm - Sand Wall penetration for snorkel 600 mm - Nickel Wall penetration for snorkel 600 mm - Mocha

99-US10U005500 99-US10U005590

Rosette, snorkel w. spacers - Stainless steel     Rosette, snorkel w. spacers - Black

Condensate collector - Stainless steel Condensate collector - Black

GB

99-USRBK10 99-USRBKB10

NOTE! Rosette with spacers must always be used outdoors together with a snorkel.

99-USDSC10 99-USDSCB10 99-USDSC110 99-USDSC1B10

Snorkel 865 x 290 x 250 mm passage - Stainless steel      Snorkel 865 x 290 x 250 mm passage - Black Snorkel 1300 x 290 x 250 mm passage - Stainless steel Snorkel 1300 x 290 x 250 mm passage - Black

53

ACCESSORIES – Ø100/150


SPARE PARTS

ITEM NO.

DESCRIPTION

99-USDHR110 99-USDHR1B10

Horizontal wall outlet 700 mm w. small cover plate - Stainless steel Horizontal wall outlet 700 mm w. small cover plate - Black

99-USDHC210 99-USDHC2B10

Horizontal wall outlet 475 mm w. small cover plate - Stainless steel Horizontal wall outlet 475 mm w. small cover plate - Black

99-USDHR210 99-USDHR2B10

Horizontal wall outlet 700 mm w. large cover plate - Stainless steel Horizontal wall outlet 700 mm w. large cover plate - Black

Vertical roof vent US Ø100/150 mm - Stainless steel Vertical roof vent US Ø100/150 mm - Black

ACCESSORIES – Ø100/150

GB

99-USDVC210 99-USDVC2B10

54


SPARE PARTS

FLASHINGS – Ø100/150 Assembled with clamp

ITEM NO.

DESCRIPTION

99-150G10-32

10-32° roof flashing for flat roof Ø150 - Black incl. storm collar

99-150G31-45

31-45° roof flashing for flat roof Ø150 - Black incl. storm collar

99-150M10-32

10-32° flexible roof flashing for corrugated roof Ø150 - Black incl. storm collar

99-150M31-45

31-45° flexible roof flashing for corrugated roof Ø150 - Black       incl. storm collar

99-150M46-65

46 - 65° flexible roof flashing for corrugated roof Ø150 - Black - incl. storm collar

0-9° roof flashing for flat roof Ø150 - Black incl. storm collar

GB

99-150G0-9

55

FLASHINGS – Ø130/200


SPARE PARTS

56

ITEM NO. 99-USSAN210 99-USSAN2B10 99-USSAN2W10 99-USSAN2P10 99-USSAN2SA10 99-USSAN2N10 99-USSAN2M10

DESCRIPTION Renovation kit (bottom) Ø100/150 - Stainless steel          Renovation kit (bottom) Ø100/150 - Black Renovation kit (bottom) Ø100/150 - White     Renovation kit (bottom) Ø100/150 - Platinum Renovation kit (bottom) Ø100/150 - Sand Renovation kit (bottom) Ø100/150 - Nickel     Renovation kit (bottom) Ø100/150 - Mocha

99-MEB9010

90° bend - Ø100/150 mm - Stainless steel

99-XEA10

Transition pipe from flex hose (bottom) Ø100 mm

99-XE1010P

Flex hose Ø100 mm - 10 meter

99-MEAH10

Guide for centrering flexible hose in chimney

RENOVATION KIT – Ø100/150

GB

RENOVATION KIT – Ø100/150


SPARE PARTS

99-XEAC10

Transition pipe from flex hose (top) Ø100 mm

99-USSAN110

Renovation kit (top) Ø100/150 mm - Stainless steel

99-USKB10

Clamp Ø100/150 - Stainless steel

RENOVATION KIT – Ø100/150

DESCRIPTION GB

ITEM NO.

57