5.3

Field Settings

SA Indoor Unit

5.3.1 How to Change the Field Settings Outline

If optional accessories are mounted on the indoor unit, the indoor unit setting may have to be changed. Refer to the instruction manual for each optional accessory.

Wired remote controller

BRC1D528

Unit No.

Mode No.

Second code No.

Field setting mode

First code No. (4) (3)

(1) (7)

(6)

(5)

(2)

(R14595)

To set the field settings, you have to change: Mode No. First code No. Second code No. Step 1 2 3

4 5 6 7

Trial Operation and Field Settings

Action Press the [INSPECTION/TEST OPERATION] button for 4 seconds during normal mode to enter the field setting mode. Press the [TEMPERATURE ADJUST] button to select the desired mode No. If the indoor unit is under group control, all settings for all the indoor units are set at the same time. Use the codes 10 to 15 to apply this group control and proceed to the next step. If you want to set the indoor units of one group individually or if you want to read out the last settings, use the codes 20 to 25 which are displayed in brackets. Press the [PROGRAMMING] button to select the indoor unit No. for which you want to adjust the field settings. Press the upper part of the [TIME ADJUST] button to select the first code No. Press the lower part of the [TIME ADJUST] button to select the second code No. Press the [SCHEDULE TIMER] button to confirm the setting. Press the [INSPECTION/TEST OPERATION] button to return to normal mode.

258


Turn static files into dynamic content formats.

Create a flipbook
Issuu converts static files into: digital portfolios, online yearbooks, online catalogs, digital photo albums and more. Sign up and create your flipbook.