INFORMATION AND ACCESSORY CARD
KAIR ECoCounter 9585 EC AIR HANDLING UNIT
with a counter-flow heat exchanger and air flow range of 600 - 3150 l/s
Ø 800 Outdoor air
Extract air Supply air
Extract air
Ø 800
925
927
925
925
925
Outdoor air Exhaust air
927
Outdoor air
Ø 800 Ø 800
Ø 800
Ø 800
Ø 800
Extract air
Exhaust air
Ø 800
Supply air
1,853
2,005
Ø 800 Ø 800 150 1,850 5,580
Arrangement R (arrangement L as a mirror image)
Dimensions and structure • W x D x H: 5,580 x 1,850 x 2,005 mm • Opening size required for the machine: 940 x 1,870 mm (as components) • Condensate connection: 2 x Ø 32 • Weight: 2,082 kg, with standard fittings • Galvanised steel sheeting exterior, with 50 mm sound and thermal insulation and galvanised steel sheeting, powder-coated front and sides, grey RAL 7040 EF, stainless steel bottom
Technical data EC fans Supply and extract systems: 5.5 kW, max. 8.4 A / 400 V, 50 Hz Re-heating Liquid-circulation system (VP): water 60/40°C and 50/30°C Liquid-circulation system (VPM): water temperature can be selected, for example 35/25°C, 50/30°C Electric heater: 36 kW, 50.4 kW, 79.2 kW
Power supply Fans and automation, input power 11.6 kW, 3x25 A, 400 V, 50 Hz Compressor cooling 33 kW, 3 x 25 A, 400 V, 50 Hz. Own supply Electric heater: 36 kW, 3 x 63 A, 400 V, 50 Hz. Own supply Electric heater: 50.4 kW, 3 x 80 A, 400 V, 50 Hz. Own supply Electric heater: 79.2 kW, 3 x 120 A, 400 V, 50 Hz. Own supply Heat recovery Counter-flow heat exchanger, with a thermal efficiency of heat recovery of 89 – 96 %, depending on air flow (air flow of 1/1)