Information and accessory card 6485

Page 1

INFORMATION AND ACCESSORY CARD

KAIR ECoCounter 6485 EC AIR HANDLING UNIT

with a counter-flow heat exchanger and air flow range of 500 - 2000 l/s Outdoor air

Extract air Supply air

Ø 630

Exhaust air

Ø 630

Ø 630

Ø 630 Outdoor air

Ø 630

Ø 630

Extract air

Exhaust air

Ø 630

Supply air

2,077 Re-heating water connection 2 x 1 ¼” external thread

Power supply fans and automation

Ø 630

Upper section 990 Lower section 990

Cooling coil 2 x 1 ¼” external thread accessory

Condensate connection Ø 32

Power supply for electric heater (pre or re) and cooling compressors For duct outputs one duct connection can be selected freely. For example, supply air connection either on the side or on the top.

100 +

adjustable leg 35 - 100

1,800 2,800 Maintenance space 1,000 x 2,800

990

Arrangement R (arrangement L as a mirror image)

Dimensions and structure • W x D x H: 2,800 x 1,800 x 1,990 mm • Opening size required for the machine: 1,000 x 1,830 mm (as components), 1,830 x 2,090 mm • Condensate connection: 2 x Ø 32 • Weight: 821 kg, with standard fittings • Galvanised steel sheeting exterior, with 50 mm sound and thermal insulation and galvanised steel sheeting, powder-coated front and sides, grey RAL 7040 EF, stainless steel bottom

990

1,800 2,800

Technical data EC fans Supply and extract systems: 3.0 kW, max. 4.6 A / 400 V, 50 Hz Re-heating Liquid-circulation system (VP): water 50/30°C and 60/40°C Liquid-circulation system (VPM): water temperature can be selected, for example 35/25°C, 50/30°C Electric heater: 21.6 kW, 36 kW, 50.4 kW

Power supply e.g. fans and automation, input power 6.7 kW, 3x16 A, 400 V, 50 Hz Liquid-circulation system: 21.5 kW, with compressor cooling 5.5 kW, 3 x 25 A, 400 V, 50 Hz. Own supply Electric heater: 21.6 kW, input power 21.6 kW, 3 x 40 A. Own supply Electric heater: 36 kW, input power 36 kW, 3 x 63 A. Own supply Electric heater: 50.4 kW, input power 50.4 kW, 3 x 80 A. Own supply Heat recovery Counter-flow heat exchanger, with a thermal efficiency of heat recovery of 90 – 95 %, depending on air flow (air flow of 1/1)