Information and accessory card 2185

Page 1

,

INFORMATION AND ACCESSORY CARD

KAIR ECoCounter 2185 EC AIR HANDLING UNIT

with a counter-flow heat exchanger and air flow range of 150 - 570 l/s Extract air

Outdoor air

Supply air

Exhaust air

Ø 315

Ø 315

Ø 315

Ø 315 Outdoor air

Ø 315

Ø 315

Extract air

Exhaust air

Ø 315

Supply air Power supply fans and automation

1,900 Re-heating water connection 2 x 1” external thread.

Ø 315

Cooling coil 2 x 1” external thread accessory.

Condensate connection Ø 32

Power supply for electric heater (pre or re) and cooling compressors. For duct outputs one duct connection can be selected freely. For example, supply air connection either on the side or on the top.

100 + adjustable leg 35 - 100 780

2,040

Outdoor air Exhaust air

Maintenance space 750 x 2,040

Extract air Ø 315

Supply air

Ø 315

Ø 315

Ø 315 Extract air

Ø 315

Ø 315 Outdoor air

Arrangement R (arrangement L as a mirror image)

Supply air

Exhaust air

Dimensions and structure

Ø 315

Ø 315

• W x D x H: 2,040 x 780 x 1,900 mm • Opening size required for the machine: 800 x 1,910 mm • Condensate connection: 2 x Ø 32 • Weight: 367 kg, with standard fittings • Galvanised steel sheeting exterior, with 50 mm sound and thermal insulation and galvanised steel sheeting, powder-coated front and sides, grey RAL 7040 EF, stainless steel bottom

Power supply fans and automation

Re-heating water connection

1900

Cooling coil

Condensate connection Ø 32

100 + adjustable leg 35 - 100 780

2,040 Maintenance space 750 x 2,040

Arrangement L

Technical data EC fans Supply and extract systems: 0.75 kW, max. 1.35 A / 400 V, 50 Hz Re-heating Liquid-circulation system (VP): water 50/30°C and 60/40°C Liquid-circulation system (VPM): water temperature can be selected, for example 35/25 °C, 50/30 °C Electric heater: 7.2 kW or 14.4 kW

Power supply Liquid-circulation system: 1.8 kW, 3x10 A, 400 V, 50 Hz Liquid-circulation system with compressor cooling 7.5 kW, 2.5 kW, 3 x 16 A, 400 V, 50 Hz. Own supply Electric heater: 7.2 kW, input power 7.2 kW, 3 x 16 A. Own supply Electric heater: 4.4 kW, input power 14.4 kW, 3 x 25 A. Own supply Heat recovery Counter-flow heat exchanger, with a thermal efficiency of heat recovery of 89 – 94 %, depending on air flow (air flow of 1/1)


Turn static files into dynamic content formats.

Create a flipbook
Issuu converts static files into: digital portfolios, online yearbooks, online catalogs, digital photo albums and more. Sign up and create your flipbook.
Information and accessory card 2185 by Kair - Issuu