INFORMATION AND ACCESSORY CARD
KAIR ECoCounter 2185 EC AIR HANDLING UNIT
with a counter-flow heat exchanger and air flow range of 150 - 570 l/s Extract air
Outdoor air
Supply air
Exhaust air
Ø 315
Ø 315
Ø 315
Ø 315 Outdoor air
Ø 315
Ø 315
Extract air
Exhaust air
Ø 315
Supply air Power supply fans and automation
1,900 Re-heating water connection 2 x 1” external thread.
Ø 315
Cooling coil 2 x 1” external thread accessory.
Condensate connection Ø 32
Power supply for electric heater (pre or re) and cooling compressors. For duct outputs one duct connection can be selected freely. For example, supply air connection either on the side or on the top.
100 + adjustable leg 35 - 100 780
2,040
Outdoor air Exhaust air
Maintenance space 750 x 2,040
Extract air Ø 315
Supply air
Ø 315
Ø 315
Ø 315 Extract air
Ø 315
Ø 315 Outdoor air
Arrangement R (arrangement L as a mirror image)
Supply air
Exhaust air
Dimensions and structure
Ø 315
Ø 315
• W x D x H: 2,040 x 780 x 1,900 mm • Opening size required for the machine: 800 x 1,910 mm • Condensate connection: 2 x Ø 32 • Weight: 367 kg, with standard fittings • Galvanised steel sheeting exterior, with 50 mm sound and thermal insulation and galvanised steel sheeting, powder-coated front and sides, grey RAL 7040 EF, stainless steel bottom
Power supply fans and automation
Re-heating water connection
1900
Cooling coil
Condensate connection Ø 32
100 + adjustable leg 35 - 100 780
2,040 Maintenance space 750 x 2,040
Arrangement L
Technical data EC fans Supply and extract systems: 0.75 kW, max. 1.35 A / 400 V, 50 Hz Re-heating Liquid-circulation system (VP): water 50/30°C and 60/40°C Liquid-circulation system (VPM): water temperature can be selected, for example 35/25 °C, 50/30 °C Electric heater: 7.2 kW or 14.4 kW
Power supply Liquid-circulation system: 1.8 kW, 3x10 A, 400 V, 50 Hz Liquid-circulation system with compressor cooling 7.5 kW, 2.5 kW, 3 x 16 A, 400 V, 50 Hz. Own supply Electric heater: 7.2 kW, input power 7.2 kW, 3 x 16 A. Own supply Electric heater: 4.4 kW, input power 14.4 kW, 3 x 25 A. Own supply Heat recovery Counter-flow heat exchanger, with a thermal efficiency of heat recovery of 89 – 94 %, depending on air flow (air flow of 1/1)