Information and accessory card 1085

Page 1

INFORMATION AND ACCESSORY CARD

KAIR ECoCounter 1085 EC AIR HANDLING UNIT

with a counter-flow heat exchanger and air flow range of 100 - 300 l/s Exhaust air

Supply air

Outdoor air Extract air

4 x Ø 315

Water connection 2 x Ø 22

1200

Condensate connection

2 x R 1/2” UK

126

760 1,350

Maintenance space 1,480 x 700

Supply air Water connection 2 x Ø 22

Exhaust air Outdoor air

Extract air 4 x Ø 315

Arrangement R (arrangement L as a mirror image) 1200

Dimensions and structure • W x D x H: 1,350 x 760 x 1,200 mm • Condensate connection: 2 x R 1/2” UK • Weight: 156 kg, with standard fittings • Powder-coated frame, grey, with 50 mm sound and thermal insulation and galvanised steel sheeting

126

Arrangement L

760 1,350

Technical data EC fans Supply and extract systems: 0.50 kW, 2.3 A / 230 V Re-heating Liquid-circulation system (VP) installed on the unit: water 60/40°C and 50/30°C Electric heater: 7.2 kW, 400 V, 50 Hz

Power supply Liquid-circulation system: 3 x 10 A, 230 V, 50 Hz Electric heater: 3 x 16 A, 400 V, 50 Hz Heat recovery Aluminium counter-flow heat exchanger, with a thermal efficiency of heat recovery of 91 – 95 %, depending on air flow