Rain Water Harvesting

Page 1

Uniclass JR12/JS10 L731/L71121/L2123 CI/SfB (52.5) September 2004

AquaCell速 & Garastor速 Stormwater Management Systems

(90.51) WM417

Product and Installation Guide

FOR RESIDENTIAL, COMMERCIAL AND INDUSTRIAL APPLICATIONS

Intelligent Solutions for

Below Ground Projects

EPIC J3413 X721


STORMWATER MANAGEMENT SYSTEMS Introduction to OSMA - from Wavin

OSMA

From Wavin

OSMA, from Wavin Plastics Limited, is

Wavin is a leading European manufacturer

the leading name in plastic systems for

of industrial plastic products, and one of

building, construction and utilities. The

the largest producers of plastic pipe and

OSMA product range is unrivalled in

fittings in the world.

scope and quality, covering:

Wavin is credited with inventing and pioneering the use of plastic pipe

Above Ground systems Plumbing and Heating systems

for water distribution in the mid 1950s. Constant research and development has

Below Ground Drainage systems Water Management systems Ducting systems

enabled Wavin to maintain its position at the forefront of plastics technology.

Environmental responsibility

Water and Gas Distribution systems

Quality assured products

Wavin Plastics Limited has BS EN ISO 9001: 2000 BSI status and was the first plastic pipe manufacturer to be

OSMA systems are the benchmark for excellence and product innovation:

accredited to BS EN ISO 14001 Environmental Management Systems.

precision-manufactured in the UK using the most advanced injection moulding

Wavin Plastics Limited is committed to

and extrusion machines. All products

environmental responsibility, and is a

comply with or exceed relevant British

leading pioneer of systems to conserve

and European standards to ensure

and control water. In production,

reliability and long-lasting service.

the Company recycles the majority of waste materials, and sets annual

Intelligent connections OSMA systems offer integrated solutions. This enables specifiers and installers to assemble complete drainage, plumbing

targets for energy efficiency audited by the certifying body.

Passion and resourcefulness

and heating, and pressure pipe systems from a single source, with complete

All Wavin personnel are committed to

confidence in compatibility and

providing a comprehensive, responsive

performance.

service – and are passionate about delivering total Customer satisfaction.

All systems are backed by comprehensive technical support and a nationwide

Wavin Plastics Limited maintains an

distribution network to ensure availability

industry-wide dialogue and rigorous

when and where required.

assessment of all procedures to ensure that Wavin product development and product support accurately addresses the needs of all Customers – today and into the future.

2

CUSTOMER SERVICES 01249 766611

TECHNICAL ENQUIRIES 01249 766655

TECHNICAL FAX 01249 766653

EMAIL info@wavin.co.uk


STORMWATER MANAGEMENT SYSTEMS Contents

Contents

General Introduction Introduction to AquaCell

4

Introduction to Garastor 20

Further information

5

Garastor System Overview

21

The following related publications are

Garastor Principal Components

22

available for OSMA Stormwater

Typical Garastor Installation Methods

23

Management systems:

Case Studies

24

Design and Installation Manual

Notes

25

Trade Price List

Technical Advice and Assistance

27

AquaCell System Overview How it Works Key Benefits

6 6 6

AquaCell Principal Components

7

Typical Soakaway Installation Method

8

Typical Storage Tank Installation Method

9

Literature requests Tel: 01249 766333

Typical Silt Trap Installation Method & Air Vent Design

To obtain copies, please contact:

10

Fax: 01249 766332

Typical Connections to AquaCell

11

literature@wavin.co.uk

Typical Air Vent Connections

12

Typical Manifold Configuration

13

Typical Soakaway Detail: Non-Traffic Loading

14

Typical Soakaway Detail: Highway

15

Typical On-Line Water Storage Detail

16

Typical Off-Line Storage Detail

17

Hydraulically Designed On-Line Water Storage System Installed Off-Line

18

Typical Soakaway Detail with Silt Trap 19

STORMWATER MANAGEMENT SYSTEMS Product & Installation Guide 2004

www.wavin.co.uk

STORMWATER MANAGEMENT SYSTEMS Introduction to OSMA from Wavin Contents â–

3


STORMWATER MANAGEMENT SYSTEMS General introduction

General Introduction Development of sites results in a large

Wavin Stormwater Management Systems

Management Systems means that they

proportion of area being covered by

have been developed to provide a method

can be tailored to suit the specific

impermeable surfaces such as roofs, car

of source control in two ways:

requirements of each site. They can be

parks and roads. Surface water run-off therefore increases up to 80%. Regulators (Environment Agency, Scottish Environment Protection Agency and local authorities) are promoting the use of Sustainable Drainage Systems (SuDS) that control run-off to that

By providing temporary storage for excess flows and limiting outflow to streams and rivers. By providing soakaways to infiltrate stormwater back into the ground. The modular nature of Wavin Stormwater

of a greenfield site (around 20%).

used to provide temporary storage, attenuation and infiltration capacity for runoff for all sizes and types of site: from individual houses up to the largest commercial developments. The systems comprise:

AquaCell速 Storage/Infiltration System Individual polypropylene modules assembled together to form an underground structure, used for stormwater storage or as a soakaway.

Small housing soakaway

Large scale storage tank

Highway drainage soakaway

Garastor 速 System* A polypropylene flow control chamber connected to a water storage reservoir EITHER made up of AquaCell units or located in a void beneath the garage of individual houses.

*Note: Garastor can be used as a flow control device for any AquaCell storage system, no greater than one unit deep with a discharge of up to 1.4 l/s via the 30mm release flow orifice.

Garastor domestic storage using garage void

Garastor domestic storage using AquaCell tank*

*Garastor is manufactured under licence (Patent Number GB2357093)

4

CUSTOMER SERVICES 01249 766611

TECHNICAL ENQUIRIES 01249 766655

TECHNICAL FAX 01249 766653

EMAIL info@wavin.co.uk


STORMWATER MANAGEMENT SYSTEMS Introduction to AquaCell

Introduction to AquaCell

OSMA AquaCell Stormwater Management System

System is fully BBA (British Board of

water courses. When the capacities of

Agrément) approved, Certificate No.

these systems are exceeded the

Comprises individual infiltration modules

03/4018, and can meet with the Technical

consequences can be dramatic and

assembled together to form an

Requirements of NHBC.

damaging.

underground structure which can either be

Heavy storms and major cloudbursts are

Stormwater must be controlled; either by

used for stormwater storage or as an

becoming more frequent, resulting in ever

limiting the outflow and providing

alternative to domestic soakaways.

increasing volumes of stormwater flowing

temporary storage or where the ground

The AquaCell Stormwater Management

into conventional drainage systems and

conditions are suitable, providing soakaways for the stormwater to infiltrate back into the surrounding ground. This has the added benefit of recharging the local groundwater. Both options can be achieved using the OSMA AquaCell Stormwater Management System.

Large scale AquaCell storage tank

Domestic AquaCell soakaway

STORMWATER MANAGEMENT SYSTEMS Product & Installation Guide 2004

www.wavin.co.uk

STORMWATER MANAGEMENT SYSTEMS General Introduction Introduction to AquaCell® ■

5


STORMWATER MANAGEMENT SYSTEMS AquaCell System Overview

â–

How it works

â–

Key benefits

AquaCell System Overview

AquaCell System The OSMA AquaCell unit is modular in

Geomembrane/Geotextile Wrap

shape (1.0m x 0.5m x 0.4m), has a

An impermeable geomembrane wrap is

capacity of 190 litres and weighs 9Kg. It is

required for storage solutions and a

95% void and has a surface area that is

permeable geotextile wrap is required for

43% perforated. Conical columns within

soakaway solutions.

the unit ensure high strength and rigidity. The AquaCell units are clipped together in

Manifold Configuration

single layers and pegged together in

A junctioned pipework assembly

multiple layers. Conventional pipework is

providing a controlled multiple feed of

connected to the units by means of a

stormwater into the AquaCell Units.

number of adaptors.

The configuration is tailored to suit the capacity required upon entry

Control Manhole

into the AquaCell Unit assembly

This manhole is designed to limit the

and upon discharging to the

downstream discharge using an outflow

control manhole.

control and if necessary redirect the excess stormwater via an overflow control into the AquaCell units.

How it works Stormwater exceeding the capacity of the

unit is designed to bring surging water

outflow control. However if the wrap is

conventional drainage system is

under control and hold it in temporary

permeable, the temporarily stored water

attenuated by the control manhole and

storage. If the wrap that envelopes the unit

may be released into the surrounding

channelled into the AquaCell unit

assembly is impermeable the water will

ground; soil conditions permitting. By

assembly. The internal structure of each

remain in the unit assembly until such a

controlling the stormwater at source and

time as it can flow back into the control

recharging the local groundwater it not

chamber and discharge through the

only eases the pressure on conventional drainage systems but benefits the local environment as well.

Key benefits Significantly reduced risk of flooding and its consequences. Controlled and reduced volume discharge into existing main sewer systems and water courses. Aerobic purification stimulated within the system improves water quality. Sustainable, cost effective management of the water environment. Recharging the local groundwater.

6

CUSTOMER SERVICES 01249 766611

TECHNICAL ENQUIRIES 01249 766655

TECHNICAL FAX 01249 766653

EMAIL info@wavin.co.uk


STORMWATER MANAGEMENT SYSTEMS AquaCell Principal Components

AquaCell Principal Components

1m

0.4m 6UR141 UltraRib S/S Adaptor (fits into pre-formed socket to connect to 150mm UltraRib)

AquaCell Unit 6LB100 0.5m 160mm diameter pre-formed socket

6TW141 TwinWall S/S Adaptor (fits into pre-formed socket to connect to 150mm TwinWall)

6LB102 Shear Connector (used to hold units together vertically)

4D916 160mm OsmaDrain P/E Adaptor (fits into pre-formed socket as an extension connection piece)

6LB105 Clip (used to hold units together horizontally)

6D099 160mm x 110mm OsmaDrain S/S Reducer (fits into pre-formed socket to connect to 110mm OsmaDrain)

6LB104 Flange Adaptor (Adaptor to be used at points other than pre-formed socket to connect to 150mm UltraRib)

Silt Trap 6LB600 (Extension Kit also available if required, see page 10 for details)

STORMWATER MANAGEMENT SYSTEMS Product & Installation Guide 2004

www.wavin.co.uk

STORMWATER MANAGEMENT SYSTEMS Overview How it works Key benefits Principal Components ■

7


STORMWATER MANAGEMENT SYSTEMS Typical Soakaway Installation Method

Typical Soakaway Installation Method

Permeable Geotextile*

OSMA AquaCell Units 100mm

Pre-formed Socket 100mm Coarse Sand or Non Angular Granular Material Base and Surround

100mm

1. Excavate the trench to the required

recommended that the Wavin Silt Trap

depth ensuring that the plan area is

(6LB600) is installed prior to the inlet

slightly greater than that of the

pipework - see page 10 for installation

AquaCell Units.

guidelines.

2. Lay 100mm bed of coarse sand or non angular granular material, level and compact.

7. Wrap and overlap the geotextile covering the entire AquaCell structure. 8. Lay 100mm of coarse sand or non

3. Lay the geotextile* over the base and up the sides of the trench.

angular granular material between the trench walls and the AquaCell structure

4. Lay the AquaCell Units parallel with each other. In multiple layer

and compact. 9. Lay 100mm of coarse sand or non

applications, wherever possible,

angular granular material over the

continuous vertical joints should be

geotextile and compact. Backfill with

avoided. AquaCell units can be laid in a

stone free as-dug material.

‘brick bonded’ formation (i.e. to overlap

10. Rainwater from roof areas may

the joints below). For single layer

discharge directly into the soakaway

applications use the Wavin Clips and

but rainwater fromcarparks must

for multi layers use the Wavin Clips and

discharge through a catchpit manhole

the Wavin Shear Connectors.

or a petrol interceptor.

5. Fix the Wavin Adaptors to the AquaCell * The geotextile should be selected according to specific site conditions, however, typically a 300g material will be suitable. Specialist advice should be sought if surrounding soil characteristics exhibit a high degree of fines/low infiltration capacity and/or there is a high risk of damage from ground contaminants.

Units as required and connect pipework. 6. In order to prevent silt from entering the tank, clogging inlet pipework and reducing storage capacity, it is

8

CUSTOMER SERVICES 01249 766611

TECHNICAL ENQUIRIES 01249 766655

TECHNICAL FAX 01249 766653

EMAIL info@wavin.co.uk


STORMWATER MANAGEMENT SYSTEMS Typical Storage Tank Installation Method

Typical Storage Tank Installation Method

Suitable Protective Geotextile Layer

OSMA AquaCell Units 100mm

Pre-formed Socket

100mm 100mm

Coarse Sand or Non Angular Granular Material Base

Suitable Impermeable Geomembrane*

1. Excavate the trench to the required

8. In order to prevent silt from entering

depth ensuring that the plan area is

the tank, clogging inlet pipework and

slightly greater than that of the

reducing storage capacity, it is

AquaCell units.

recommended that the Wavin Silt

2. Lay 100mm bed of coarse sand, level and compact. 3. Lay the geotextile over the base and up the sides of the trench. 4. Lay the geomembrane on top of the

Trap (6LB600) is installed prior to the inlet pipework – see page 10 for installation guidelines. 9. Wrap and overlap the geotextile covering the entire AquaCell

geotextile over the base and up the

structure, to protect the

sides of the trench.

geomembrane.

5. Lay the AquaCell units parallel with

10. Lay 100mm of coarse sand between

each other. In multiple layer

the trench walls and the Wavin

applications, wherever possible,

AquaCell units and compact.

continuous vertical joints should be

11. Lay 100mm bed of coarse sand over

avoided. AquaCell units can be laid in a

the geotextile and compact. Backfill

‘brick bonded’ formation (i.e. to overlap

with stone free as-dug material.

the joints below). For single layer applications use the Wavin Clips and

NB: A storage tank must be vented, and

for multi layers use the Wavin Clips and

it is recommended that one vent

the Wavin Shear Connectors (vertical

pipe, 110mm in diameter is provided

rods).

per 7,500 square metres of

6. Wrap the geomembrane around the AquaCell structure and seal to

impermeable catchment area on a site, see page 8 for design.

manufacturers recommendations.* * For large scale, deep installations a 1mm thick geomembrane is recommended and joints should be sealed using proprietary welding techniques. However, for shallow, domestic installations it may be suitable to use a geomembrane with taped joints. For further details contact Wavin Technical Services.

7. Place the Wavin Flange Adaptor into position (at a point other than the preformed socket) and fix using self tapping screws. Drill a hole through the Flange Adaptor and connect pipework.

STORMWATER MANAGEMENT SYSTEMS Product & Installation Guide 2004

www.wavin.co.uk

STORMWATER MANAGEMENT SYSTEMS Soakaway Installation Storage Tank Installation ■

9


STORMWATER MANAGEMENT SYSTEMS Typical Silt Trap Installation Method

Typical Air Vent Design

Typical Silt Trap Installation Method COVER & FRAME – 1.2m deep use 6D.935. Greater than 1.2m deep use 6D.939 with reduced opening of 350mm

150mm side fill as dug material with no particle sizes larger than 40mm

SHAFT 500mm 1250mm

100mm bed as per pipe bedding specification

450mm

1. Place the Silt Trap (6LB600) on a

160mm OsmaDrain Inlet/Outlets or use the appropriate adaptor to connect to 110mm OsmaDrain, 150mm TwinWall or UltraRib

4. Fit relevant cover and frame according

minimum of 100mm bed as per pipe

to the depth of unit: Up to and

bedding specification. Ensure that the

including 1.2m deep = 6D935 Deeper

unit is as close to AquaCell tank as

than 1.2m = 6D939.

possible and in a suitable position to Notes:

allow pipework connection.

When surrounded by a concrete plinth (150mm x 150mm) the cover can be used in situations with a loading of up to 30Kn (3 tonnes) i.e domestic driveways.

2. Connect the relevant pipework in accordance with standard pipe installation guidelines.

The silt trap can be extended (if required) using the 500mm Extension Kit (see details on page 20) in conjunction with a 500mm shaft of TwinWall cut to suit.

3. Surround the sides of the Silt Trap with 150mm of ‘as dug’ material, with no particle sizes larger than 40mm.

Typical Air Vent Design

Balloon Grating 4S302

Ventilation Box (4D706)

110mm OsmaDrain Pipe

Flange Connector 6LB104

150mm x 110mm Reducer (6UR099) Geomembrane sealed to Flange

Note: It is recommended that one vent pipe, 110mm in diameter, is provided per 7,500 square meters of impermeable catchment area on a site. Please contact Wavin Technical Services for further details.

10

CUSTOMER SERVICES 01249 766611

TECHNICAL ENQUIRIES 01249 766655

TECHNICAL FAX 01249 766653

EMAIL info@wavin.co.uk


STORMWATER MANAGEMENT SYSTEMS Typical Connections to AquaCell

Typical Connections to AquaCell Note: It is recommended that all connections and air vent installations in storage applications (using geomembrane) are made using a Flange Adaptor. Adhesive or double sided tape should be used between the geomembrane and the flange plate to ensure a watertight seal.

Permeable Geotextile Wrap

Jubilee Clip

Connection for soakaway application using either the pre-formed socket (as shown below) or standard adaptors into pre-formed socket*

*Note: For pipework other than 160mm OsmaDrain, these adaptors can be used to connect to the following: 6TW141: TwinWall S/S Adaptor connects to 150mm TwinWall 6D099: 110mm OsmaDrain Adaptor connects to 110mm OsmaDrain 4D916: 160mm OsmaDrain PE Adaptor connects to 160mm OsmaDrain 6UR141: UltraRib S/S Adaptor connects to 150mm UltraRib

160mm OsmaDrain

Coarse Sand or Non Angular Granular Material Base and Surround

Geomembrane Wrap

Connection for storage application using flange adaptor at points other than preformed socket Installation Procedure:

Flange Adaptor (6LB104)

1. Fix Flange Adaptor to the AquaCell unit with self tapping screws 2. Drill through geomembrane and AquaCell unit with a long 150mm Crown Drill Bit Cutter 3. Insert pipework into Flange Adaptor

150mm Pipework to suit Coarse Sand or Non Angular Granular Material Base and Surround

STORMWATER MANAGEMENT SYSTEMS Product & Installation Guide 2004

www.wavin.co.uk

STORMWATER MANAGEMENT SYSTEMS Silt Trap Installation Air Vent Design Connections to AquaCell ■

11


STORMWATER MANAGEMENT SYSTEMS Typical Air Vent Connections

Typical Air Vent Connections Note:

Connect suitable pipework to form air vent Geomembrane Wrap Flange Adaptor (6LB104)

It is recommended that all connections and air vent installations in storage applications (using geomembrane) are made using a Flange Adaptor. Adhesive or double sided tape should be used between the geomembrane and the flange plate to ensure a watertight seal.

Connection onto top of AquaCell unit using Flange Adaptor Installation Procedure: 1. Fix Flange Adaptor to the AquaCell Unit with self tapping screws 2. Drill through geomembrane and AquaCell unit with a long 150mm Crown Drill Bit Cutter 3. Insert pipework into Flange Adaptor to form air vent

Coarse Sand or Non Angular Granular Material Base and Surround

Permeable Geotextile Wrap Jubilee Clip

Suitable bend and pipework to form air vent

OsmaDrain S/S Reducer (6D099)

Connection into side of AquaCell unit using standard adaptors Coarse Sand or Non Angular Granular Material Base and Surround

12

CUSTOMER SERVICES 01249 766611

TECHNICAL ENQUIRIES 01249 766655

TECHNICAL FAX 01249 766653

EMAIL info@wavin.co.uk


STORMWATER MANAGEMENT SYSTEMS Typical Manifold Configuration

Typical Manifold Configuration

AQUACELL UNITS

150mm ULTRARIB

300mm ULTRARIB

Note: Pipe configuration is dependent on maximum flow. Alternative pipe systems such as Wavin TwinWall and OsmaDrain can be used. Please contact Wavin Technical Services for further details.

STORMWATER MANAGEMENT SYSTEMS Product & Installation Guide 2004

www.wavin.co.uk

STORMWATER MANAGEMENT SYSTEMS Typical Air Vent Connections Typical Manifold Configuration â–

13


STORMWATER MANAGEMENT SYSTEMS Typical Soakaway Detail: Non-Traffic Loading

Typical Soakaway Detail: Non-Traffic Loading

ROOF AREA = 98m2

S

KEY:

S

= AquaCell Soakaway (see note 2)

S

DEEP SOAKAWAY NON-TRAFFIC LOADING AREA

Notes:

Min Depth 0.5m

1. Soakaways should be sited at least 5m away from the building. (Ref BS8301) 2. The exact size and shape of the soakaways are to be determined once all the necessary calculations have been produced.

TRENCH SOAKAWAY NON-TRAFFIC LOADING AREA

14

CUSTOMER SERVICES 01249 766611

TECHNICAL ENQUIRIES 01249 766655

TECHNICAL FAX 01249 766653

EMAIL info@wavin.co.uk


STORMWATER MANAGEMENT SYSTEMS Typical Soakaway Detail - Highway

TO SOAKAWAY

150mm ULTRARIB

FOR MINIMUM DEPTH OF COVER CONTACT WAVIN

FOOTPATH

225mm ULTRARIB

SILT TRAP

150mm ULTRARIB

TO ROAD GULLY

150mm CONCRETE SURROUND

FINISHED ROAD LEVEL

Typical Soakaway Detail - Highway

STORMWATER MANAGEMENT SYSTEMS Product & Installation Guide 2004

www.wavin.co.uk

STORMWATER MANAGEMENT SYSTEMS Soakaway Details: Non-Traffic Loading Highway ■

15


STORMWATER MANAGEMENT SYSTEMS Typical On-Line Water Storage Detail

SUMP

REVERSE BACKDROP OVERFLOW

16

CUSTOMER SERVICES 01249 766611

TECHNICAL ENQUIRIES 01249 766655

SUMP

MESH LEAFGUARD

PRIVATE CATCHPIT

AIR VENT

DIRECTION OF FLOW

GROUND LEVEL

PRIVATE CATCHPIT WITH FLOW CONTROL DEVICE

110mm OSMADRAIN

Typical On-Line Water Storage Detail

TECHNICAL FAX 01249 766653

EMAIL info@wavin.co.uk


STORMWATER MANAGEMENT SYSTEMS Typical Off-Line Water Storage Detail

NON-RETURN FLAP VALVE

SUMP

WEIR WALL

AIR VENT

GROUND LEVEL

CONTROL CHAMBER WITH FLOW CONTROL DEVICE

INCOMING PIPE

Typical Off-Line Water Storage Detail

STORMWATER MANAGEMENT SYSTEMS Product & Installation Guide 2004

www.wavin.co.uk

STORMWATER MANAGEMENT SYSTEMS On-Line Water Storage Detail Off-Line Water Storage Detail ■

17


STORMWATER MANAGEMENT SYSTEMS Hydraulically Designed On-Line Water Storage System Installed Off-Line

SUMP

OUTFLOW CONTROL DEVICE

REVERSE BACKDROP OVERFLOW PIPE

AIR VENT

CONTROL CHAMBER

INCOMING 150mm ULTRARIB

Hydraulically Designed On-Line Water Storage System Installed Off-Line

18

CUSTOMER SERVICES 01249 766611

TECHNICAL ENQUIRIES 01249 766655

TECHNICAL FAX 01249 766653

EMAIL info@wavin.co.uk


STORMWATER MANAGEMENT SYSTEMS Typical Soakaway Detail with Silt Trap

Typical Soakaway Detail with Silt Trap

For bedding specification information refer to page 10.

450mm

The silt trap can be used in conjunction with a soakaway (as shown) or a storage tank.

FOR MINIMUM DEPTH OF COVER CONTACT WAVIN

160mm OSMADRAIN

GROUND LEVEL

160mm OSMADRAIN

SILT TRAP

160mm OSMADRAIN

1250mm

Notes:

STORMWATER MANAGEMENT SYSTEMS Product & Installation Guide 2004

www.wavin.co.uk

STORMWATER MANAGEMENT SYSTEMS Hydraulically Designed Soakaway Detail with Silt Trap ■

19


STORMWATER MANAGEMENT SYSTEMS Introduction to Garastor

Introduction to Garastor ÂŽ*

Development of sites results in a large proportion of area being covered by impermeable surfaces such as roofs, car parks and roads. Surface water run-off therefore increases up to 80%. Building Regulations and guidance now requires a sustainable approach to development, which minimises the effects of run-off to that of a greenfield site (20%). Developed in collaboration with Bryant Homes, Garastor (polypropylene control chamber) represents a house by house, rather than a development wide approach, to stormwater management. Garastor controls the flow of water at source by temporarily storing water under a soft landscaped area using the AquaCell system or in the void space under the

Garastor – polypropylene control chamber

floor slab of a residential garage. It eliminates the need for costly, spacehungry, on-site communal water-storage structures or ponds which enables better use of developable land. During high intensity rainfall, water from the roof or hardstanding areas is diverted via the Garastor control unit into the storage void. As the storm subsides the rainwater can be slowly released back into the main drainage system. Note: Garastor can be used as a flow control device for any AquaCell storage system, no greater than one unit deep with a discharge of up to 1.4 l/s via the 30mm release flow orifice.

Internal view of Garastor

*Garastor is manufactured under licence (Patent Number GB2357093)

20

CUSTOMER SERVICES 01249 766611

TECHNICAL ENQUIRIES 01249 766655

TECHNICAL FAX 01249 766653

EMAIL info@wavin.co.uk


STORMWATER MANAGEMENT SYSTEMS Garastor System Overview

Garastor ÂŽ System Overview

Garastor System The Garastor unit is a polypropylene chamber that connects to a water storage reservoir. There are two versions of the Garastor available both of which are 500mm in diameter, the 6SC500 version is 1m deep for garage installations (with a 300mm storage depth capacity) and the 6SC501 is 1.25m deep for use with AquaCell (with a 400mm storage depth capacity). When Garastor is used in conjunction with an AquaCell tank the configuration of units must be no deeper than 1 AquaCell unit. If site conditions are such that a deeper Garastor unit is required then the 500mm Extension Kit (6SC205 - consisting of a coupler and two ring seals) can be used in conjunction with a shaft of 500mm Twinwall cut to suit, to extend the Garastor unit.

HOW IT WORKS Storm or surace water flows through two 110mm diameter incoming pipes. If the flow is light to moderate, the water is simply stored in the chamber before being slowly released through a 30mm orifice. However, if the inflow is heavy, excess water in the chamber discharges through a 150mm diameter pipe into the water storage area (either the undercroft of a garage or an AquaCell tank). The water is temporarily stored until the water level inside the chamber has dropped sufficiently, and the water can flow out to

KEY BENEFITS

the drainage system via the 110mm

No use of valuable, developable land.

outflow pipe.

Safer than open/above ground storage structures.

Inside the Garastor chamber there are

Caters for 1 in 150 year storm.

specially designed weir walls that ensure

Spreads cost of water storage over the development period.

that the hydraulics of the unit work to the

Maintenance free, with no moving parts or filters.

optimum levels.

Run-off reverts to that of a greenfield site.

STORMWATER MANAGEMENT SYSTEMS Product & Installation Guide 2004

www.wavin.co.uk

STORMWATER MANAGEMENT SYSTEMS Introduction to Garastor Garastor System Overview â–

21


STORMWATER MANAGEMENT SYSTEMS Garastor Principal Components

Garastor ® Principal Components

500mm diameter

6TW142 TwinWall D/S Adaptor (150mm TwinWall socket x 160mm OsmaDrain socket for connection of 150mm TwinWall pipe to 160mm OsmaDrain pipe)

1m (6SC500) 1.25m (6SC501) 150mm TwinWall Socket (for connection to other pipe materials, a small section of 150mm TwinWall is required, alternatively use the 150mm Garastor Connection Kit (6SC200 – consisting of a short section of 150mm TwinWall pipe and two ring seals)

Garastor 6SC500 (for use with garage undercroft) 6SC501 (for use with AquaCell)

6TW148 TwinWall D/S Adaptor (150mm TwinWall socket x 150mm UltraRib socket for connection of 150mm TwinWall pipe to 150mm UltraRib pipe)

6D935 < 1.2m deep 6D939 > 1.2m deep Covers and Frames

+

6SC205 Extension Kit (a shaft of 500mm TwinWall pipe or an Inspection Chamber Shaft (6D938 - 3.0m length / 6D934 - 1.5m length) cut to suit will also be required)

22

CUSTOMER SERVICES 01249 766611

6TW145 TwinWall S/S Adaptor (150mm TwinWall socket x 150mm UltraRib spigot for connection of 150mm TwinWall pipe directly to 150mm UltraRib socket)

TECHNICAL ENQUIRIES 01249 766655

TECHNICAL FAX 01249 766653

6TW141 TwinWall S/S Adaptor (150mm TwinWall socket x 160mm OsmaDrain spigot for connection of 150mm TwinWall pipe directly into the AquaCell pre-formed socket)

EMAIL info@wavin.co.uk


STORMWATER MANAGEMENT SYSTEMS Typical Garastor Installation Methods

Typical Garastor ® Installation Methods

1. Place the Garastor Unit (6SC500 or

Garastor installation using garage void

6SC501) on a minimum of 100mm

Rainwater pipe (or air brick) for ventilation

“as-dug” or granular material. Ensure that the unit is as close to the garage undercroft or AquaCell structure as possible and in a suitable position to allow pipework connection. Note: It is important to ensure that the chamber is placed in a level position and that the invert of the 150mm pipe connection is level with the base of the concrete undercroft or the base of the AquaCell units.

Bitumastic paint applied to walls of void area and underside of the garage floor cover and frame Wall to retain storage area 150mm outflow pipework to undercroft/void

2. Connect pipework in accordance with standard pipe installation guidelines. 3. Surround the Garastor unit with 150mm of similar material to that used for the bedding.

1200g polythene damp proof membrane

Garastor (6SC500)

110mm outflow pipework to drainage system

110mm inflow pipework to chamber

75mm thickness of smooth finished 50mm concrete Stored water sand layer

Note: The depth of foundations for standard block and beam garage floors will need to be lowered by approx. 300mm to accommodate the storage capacity required.

4. Fit relevant cover and frame according to depth of unit: Up to and including1.2m deep 6D935 Deeper than 1.2m6D939

Garastor installation using AquaCell Note: When surounded by a concrete plinth (150mm x 150mm) the cover can be used in situations with a loading of upto 30Kn (3 tonnes) i.e. domestic driveways.

Cover and Frame

Suitable impermeable geomembrane AquaCell storage tank

5. Adequate ventilation must be provided: -

to the garage undercroft using either air bricks or rainwater downpipes connected directly into the storage area.

-

to the AquaCell structure using an air vent (NB. One air vent is required per 7,500 square metres of impermeable area to be drained).

Garastor (6SC501)

Notes: When using Garastor with the undercroft/void of a garage, it is the responsibility of the designer to ensure that the enhancement to the garage undercroft/void and drainage works comply with current prevailing Building Regulations.

Also to prevent softening of the soils below the foundations or loss of fines leading to settlement, the void beneath the garage should be lined as follows: Underneath the concrete base of the void area there should be a 1200g polythene damp proof membrane Bitumastic paint should be applied to the walls of the void area and to the underside of the reinforced garage floor beams.

STORMWATER MANAGEMENT SYSTEMS Product & Installation Guide 2004

www.wavin.co.uk

STORMWATER MANAGEMENT SYSTEMS Garastor Principal Components Garastor Installation Methods ■

23


STORMWATER MANAGEMENT SYSTEMS Case studies

Case studies

The sky’s the limit for Wavin Plastics

AquaCell passes toughest tests during worst storms for 50 years

Weathering the storm on Brownfield Land

THE CLIENT:

THE CLIENT:

THE CLIENT:

Birmingham Airport

Ilchester Cheese Company

Graham & Brown Wallcovering

THE PROBLEM:

THE PROBLEM:

THE PROBLEM:

To prevent flooding on a new long-stay

Controlling flooding/water on a regularly

How to manage/control storm or flood

car park covered with paving, and help

flooded area.

water on a low lying brownfield site,

the Airport to comply with its policy of

adjacent to a river with a history of THE SOLUTION:

flooding, and prevent the leaching of

In order to control stormwater at the

contaminants into the high water table

THE SOLUTION:

Ilchester site, a system which comprised

from the site which used to be a power

Over 7,000 AquaCell infiltration modules

of 1,352 AquaCell units was installed to

station.

were installed on the site providing a

limit the outflow and provide temporary

robust and long life infiltration base. A

storage.

sustainable development.

THE SOLUTION:

permeable geotextile was the only other

To collect stormwater from the

component required to complete the

THE QUOTE:

development in a trench surrounding the

installations.

“What we have seen at the Cheese

new factory filled with 2,000 Wavin

Company over the past fortnight is

AquaCell units clipped together,

THE QUOTE:

evidence of a highly successful system.

encapsulated in a robust fully welded

“Wavin’s solution to stormwater

The surrounding area is completely

hydrocarbon resistant geomembrane,

management combines practical and

waterlogged with the river only half a mile

which in turn was wrapped in a non-

operational benefits over the alternative

down the road. Our site is bone dry - any

woven needle-punched geotextile.

methods available to the developer. Its

risk of damaged land has been alleviated”.

system proved to be economically and

THE QUOTE:

functionally favourable whilst providing

“The 95% void capacity of Wavin’s system

storage of over 1,300 cubic metres of

was a key factor for us. The original

surface water run-off.”

proposal for the site was based on installing stone-filled trenches with a maximum void capacity of 30%.”

24

CUSTOMER SERVICES 01249 766611

TECHNICAL ENQUIRIES 01249 766655

TECHNICAL FAX 01249 766653

EMAIL info@wavin.co.uk


STORMWATER MANAGEMENT SYSTEMS Notes

STORMWATER MANAGEMENT SYSTEMS Product & Installation Guide 2004

www.wavin.co.uk

STORMWATER MANAGEMENT SYSTEMS Case studies Notes ■

25


STORMWATER MANAGEMENT SYSTEMS Notes

26

CUSTOMER SERVICES 01249 766611

TECHNICAL ENQUIRIES 01249 766655

TECHNICAL FAX 01249 766653

EMAIL info@wavin.co.uk


STORMWATER MANAGEMENT SYSTEMS Technical Assistance

n

Further Information

Technical Advice Contents and Assistance

Further Information

OSMA Stormwater Management systems

STORMWATER MANAGEMENT SYSTEMS

are backed by Wavin’s comprehensive

The following related publications are available for OSMA

technical advisory service. This is available

Stormwater Management systems:

to provide expert assistance at every stage

Design and Installation Manual

of a project, from planning and product selection to installation and maintenance. Services include:

Trade Price List

ASSOCIATED OSMA SYSTEMS OSMA systems are fully integrated to provide a total

Full technical literature, including:

solution for above and below ground drainage,

- System Product Guides

plumbing and heating. Contact Wavin Technical

- Design and Installation Guides

Design Department for further details regarding:

- Trade Price Lists Contact Wavin Technical Design Department for prompt assistance:

TECHNICAL DESIGN Tel: 01249 766655 Fax: 01249 766653 Email: technical.design@wavin.co.uk

OSMA Rainwater systems OSMA Soil & Waste systems OSMA Flexible Plumbing systems OSMA Underfloor Heating systems OSMA Below Ground Drainage systems OSMA Water Management systems OSMA Ducting systems OSMA Pressure Pipes for Water OSMA Pressure Pipes for Gas

WAVIN ONLINE The complete OSMA product catalogue, together with design and installation guidance, is also available online at: www.wavin.co.uk To request a copy of any item(s) of current

All literature can be downloaded via the searchable PDF library at

literature, please contact:

www.wavinpdfs.co.uk

LITERATURE REQUESTS Tel: 01249 766333 Fax: 01249 766332 Email: literature@wavin.co.uk

Wavin images can be downloaded at different resolutions from www.wavinimages.co.uk

STORMWATER MANAGEMENT SYSTEMS Product & Installation Guide 2004

www.wavin.co.uk

STORMWATER MANAGEMENT SYSTEMS Notes Technical Further Information n

n

27


AquaCell速 & Garastor速 Stormwater Management Systems

Product and Installation Guide

Meeting your needs OSMA Water Management systems, developed by Wavin Plastics Limited, form part of a comprehensive range of plastic systems to provide intelligent solutions for all building, construction and utilities projects. These include: Above Ground Projects OSMA Rainwater systems OSMA Soil & Waste systems Plumbing & Heating Projects OSMA Flexible Plumbing systems OSMA Underfloor Heating systems Below Ground Projects OSMA Below Ground Drainage systems OSMA Water Management systems OSMA Ducting systems Pressure Pipe Projects OSMA Pressure Pipes for Water OSMA Pressure Pipes for Gas

Wavin Plastics Limited Parsonage Way Chippenham Wiltshire SN15 5PN Tel: 01249 766600 Fax: 01249 443286 Email: info@wavin.co.uk

Wavin Plastics Limited operates a programme of continuous product development, and therefore reserves the right to modify or amend the specification of their products without notice. All information in this publication is given in good faith, and believed to be correct at the time of going to press. However, no responsibility can be accepted for any errors, omissions or incorrect assumptions. Users should satisfy themselves that products are suitable for the purpose and application intended.

www.wavin.co.uk

WM417

All OSMA systems are backed by full technical literature and project support. See inside back cover for details.

ISO 9001:2000