Skip to main content

Evidence Based Healthcare Design - Environment of Care - Handrails

Page 1

Handrails

When handrails are terminated or interrupted, consider a tactile signal (a notch cut into the rail) 4 in (100 mm) from the end point or have the rail curve and connect back to the wall.

Install handrails 3 ft (850 mm) from the ground. Handrails should be between 1.6 in (40 mm) and 1.8 in (45 mm) in diameter with a non-slip texture.

Install handrails on both sides of stairways and hallways and on at least one side of ramps.

On ramps and stairways, extend handrails 12 in (300 mm) beyond the end of the ramp and consider installing a safety rail along with the handrail at 8 in (200 mm) above ground, a curb at the same height.

Curve the end of handrails down to 27 in (680 mm) for easier detection by visually impaired older adults using cane technique.

In stairways, continue handrails through and around landings, especially in long stairways.

In elevators, provide handrails on both sides of the cabin at a height between 32 in to 40 in (800 mm to 1000 mm).

Handrails should be in a color that contrasts with the floor and the wall to help older adults with visual impairments to locate the handrails; consider Braille on end of handrail.

Consider handrails in outpatient clinics where patients undergo medical diagnostic testing.

(Note: All handrails must be able to withstand a force of 2 kN pressure. As part of the International System of Measurement, a kN (or kilonewton) is an unit of force equal to 1000 newtons, with one newton representing the amount of force required to accelerate a one kilogram mass at a rate of one meter per second squared.)

Handrails - Environment of Care

JPT Architects, P.C.


Turn static files into dynamic content formats.

Create a flipbook
Evidence Based Healthcare Design - Environment of Care - Handrails by JPT Architects - Issuu