A1 A2 Quick Guide

Page 1

UPS A1 & A2 Quick Guide User’s Manual


A1 & A2 QUICK GUIDE

1. Table 1 Safety Symbols and Means Safety

Symbols

Means Secure alarm Risk of electric shock

2. Table 2 UPS Main Performance Index

Characteristic

Input

Index

Model

A2

Rating voltage (V)

In range 160~290V full load

Rating frequency (Hz)

50±5%

Input mode

Single-phase three-line

Battery voltage (V) Capacity

(VA/W)

Voltage Output Characteristic

A1

36

72

1000/700

2000/1400

(V)

Frequency

230±2%

(Hz)

50±0.2% (Battery mode)

Waveform

Sine wave

Voltage

distortion

THD < 3% (Linear load)

factor Power factor

0.7 (Lag)

Switching time (ms) Overload capacity

0 105%~130% Load, lasting 60 seconds. 135%~150% Load, lasting 30 seconds.≥150% lasting 300 milliseconds

Output mode

Sockets 5 minutes

Spare time

(PC LOAD)

Charge recovery time

Other Characteristics

Communication interface

5 minutes (PC LOAD) <12 hours (Standard time delay model) A1 & A2: RS232 & USB interface

RS232 interface supports UPS power management software UPSilon 2000 and SNMP adapter

Panel display Warning function Protection function

LED displays operation status of UPS Battery low voltage, abnormal power supply, UPS malfunction Battery low voltage protection, overload protection, short-circuit protection and excess temperature protection

Frequency noise (dB)

< 45

Working temperature

0 ~ 40℃

Relative humidity

0 ~ 95%, No condensation

Size (mm)(H × W × D) Weight

(kg)

88×440×500 14

◆ Specifications are subject to change without prior notice.

Copyright AST 2010

15] www.ast-global.com

11


A1 & A2 QUICK GUIDE

3. Rear Panel

BREAKER

RS232 PORT FUSE

RS232

USB PORT

FAN

USB

AC INPUT

AC OUTPUT

直流输入/DC INPUT

AC INPUT、DC INPUT TERMINAL

(REAR PANEL)

AC OUTPUT SOCKET

A1 Rear Panel

BREAKER

RS232 PORT RS232

FUSE

USB PORTFAN

FAN

AC OUTPUT SOCKET

USB

AC INPUT

AC OUTPUT

(+) BATTERY (-) DC INPUT

AC INPUT、DC INPUT TERMINAL

REAR PANEL

A2 Rear Panel

Copyright AST 2010

15] www.ast-global.com


A1 & A2 QUICK GUIDE

(REAR PANEL)

AC OUTPUT

AC OUTPUT SOCKET

FAN

(+) BATTERY (-) DC INPUT

USB

AC INPUT

AC INPUT SOCKET

RS232

RS232 PORT BREAKER

AC INPUT、 DC INPUT TERMINAL

FUSE

直流输入/DC INPUT

USB

AC INPUT

BREAKER

USB PORT

DC INPUT LINE BAR

RS232

RS232 PORT

FAN

FUSE

USB PORT

AC OUTPUT

AC OUTPUT SOCKET

(REAR PANEL)

Horizontal A1

Horizontal A2

4. Preparations before First Start-up To ensure normal operation of UPS, please confirm the following before use: A. Correct installation of input and output. B. If supply terminals connect to the rated power. . C. Confirm that UPS output does not short circuit, and the load capacity does not exceed UPS capacity. D. Confirm if computer or other instrument is turned off. E. Confirm if battery voltage is normal. F. It is not recommended to connect reactive load to the UPS output. Loads are normally powered by electric network directly.

5.

UPS Start-up Sequence

After confirming all the above, please start the machine by following means:

A. Press the "POWER" button on the UPS panel to start UPS, the "INV" indicator light will light up. After retardation time, the "BYP." light goes out and the UPS is changed inversion power supply. By this time, the start-up is completed and the equipment starts operation. Wait for about 20 seconds after normal no-load operation to turn on the computer or other instrument. Start the load in the sequence of high-power to low power, first start the high-power equipment then in turns start equipment with lower power. B. Start computer or other equipment.

Copyright AST 2010

15] www.ast-global.com


A1 & A2 QUICK GUIDE

6.

Daily Start-up and Shutdown

During daily operation, operate as per the following for start-up or shut down: A.

Press the "ON" button on the UPS panel to start UPS, after 20 seconds, turn on the computer or other

instrument. B.

Normally, only when the UPS has been started and is working stably, can the loading equipment

power switch be turned on. First turn on high-power equipment, then the equipment with lower power. Some equipment has large start current (such as monitors of some brands). When starting such equipment, overload protection (such as bypass operation) may occur. In this case, it's recommended to start this type of equipment before other equipment. C. Before shutdown, turn off the computer and other instrument first. Then press the "OFF" button on the panel for seconds.

7.

Maintenance Guide

The correct maintenance, including the preventative maintenance and remedial maintenance, is the key to the best operation and longer usage life of the UPS. The preventive maintenance includes some regular programs to avoid the faults of the power system and reach maximum efficiency. The remedial maintenance includes the probing of the power system fault for the effective maintenance.

8.

Safety Precaution

For safe and smooth maintenance on the power system, you must follow the related safety precautions, prepare the necessary gears and testing equipments and operate under the eligible maintainer’s control. Pay attention to the following safety operation regulations: A. Do remember there always exits hazardous voltage inside UPS even when UPS do not run. B. Make sure persons manipulating or maintaining UPS are familiar with the manual and instrument. C. When UPS operation, no golden or sliver accouterments like ring, watch wore. D. Do assume the safe operation procedure as a matter of course. If any doubt, consult with persons being familiar with the instrument. E. Keep eye on the hazardous voltage inside the UPS every moment. Using voltmeter to check if the input power is completely cutoff and in safe status before maintenance and adjustability. Please comply with the manual to use UPS. When UPS faults, please cut off the connection between battery cabinet and UPS immediately then deliver it to professional maintainer or station. Self-deal is prohibited.

Copyright AST 2010

15] www.ast-global.com


Issuu converts static files into: digital portfolios, online yearbooks, online catalogs, digital photo albums and more. Sign up and create your flipbook.