BROAD Central Air Conditioning Terminals Design & Model Selection Manual (2)
Ceiling air handler Air flow: 3,000 – 12,000 m3/h Cooling capacity: 18 – 90kW(5~26Rt)
Combined air handler Air flow:10,000 – 100,000m3/h Cooling capacity: 48 – 830kW(14~236Rt)
2010.03 English
1 Ceiling air handler
Product view
Nomenclature
Framing
EMD 10000 - 4 - R
Framing is of aluminium alloy material: wallboard is CFC-free polyurethane foaming or hi-density polyethylene board or glasswood wallboard. Electrostatic Cleaner The tungsten filament releases hi-volt static electricity at the air inlet so that all particles are positively charged. When the air passes through the negatively charged plates, all tinier particles and bacteria are adsorbed onto the plates. Bacteria, viruses and pollens are killed immediately. Active carbon Can trap all kinds of toxic gases like formaldehyde, benzene. Fan Centrifugal fan with variable speed drive is used. High efficiency, low noise, smooth operation & drastic electricity saving. Coils Designed per ARI standard. Coils are of seamless quality copper tubes and hi-purity aluminium foil. High coil efficiency, low air/water resistance Dry Condensate Pan Insulation materials of condensate pan ensure no condensate drops even under a rigid working condition. Condensate tube drainage is 5 times than that under a normal operation. Condensate drainage minimizes the time of water on the condensate pan, which lessens pan corrosion and eliminates bacteria multiplying.
tube connection, R means right, L left coil row rated air flow m3/h Ceiling air handler
2
Rated Parameters Model
Rated Min Air Air Flow Noise m3/h Level dB(A) EMD3000 3000 34 EMD4000 4000
36
Max Air Power TP Fan 4 rows 6 rows Dimensions Noise Demand W.T W.T LxWxH Level kW Pa PC kg kg mm dB(A) 65 1.8 260 1 160 180 1742x1546x600 65 2.0 300 1 195 220 1936x1626x900
EMD5000 5000
36
65
2.2
EMD6000 6000
36
68
2.8
EMD7000 7000
36
69
3.0
EMD8000 8000
38
70
3.4
EMD10000 10000
38
70
3.8
EMD12000 12000
40
75
4.2
A/C water tube mm DN40
Condensate Tube mm Φ25
DN40 Φ25
460 1 480 2
220
235
2090x1726x920
DN40 Φ25
260
285
2240x1746x920
DN40 Φ25
500 2 560 2
280
310
2350x1846x1020 DN50 Φ25
360
345
2540x1846x1020 DN50 Φ25
580 2 600 2
335
370
2810x1946x1220 DN50 Φ25
438
475
3020x1946x1220 DN50 Φ25
Cooling/Heating capacity Model
EMD3000 EMD4000 EMD5000 EMD6000 EMD7000 EMD8000 EMD10000 EMD12000
Coils A/C Operation (rows) Cooling Heating Water Water
Fresh Air Operation
kW
kW
4
18
27
Back Cooling Heating Water Flow Resistance Pressure kW kW Flow t/h kPa Pa t/h 3.0 70 200 38 48 6.4
Water Resistance kPa 49
Back Pressure Pa 230
6
25
33
4.2
86
160
49
56
8.4
49
170
4
24
36
4.2
75
220
50
63
8.6
49
240
6
31
42
5.4
90
190
62
75
11.3
49
180
4
30
49
5.2
80
380
60
92
6.4
49
310
6
42
60
7.1
92
300
82
108
14.2
45
260
4
32
52
5.6
85
400
76
95
13.2
31
290
6
48
64
8.3
98
320
96
112
13.8
49
260
4
38
56
6.5
90
420
90
112
15.4
20
320
6
56
75
9.6
106
300
116
132
20.1
46
250
4
44
70
7.6
95
440
103
128
17.8
29
350
6
65
86
11.2
110
310
131
150
19.5
49
300
4
54
86
9.4
100
420
128
159
22.1
34
370
6
80
107
13.9
114
330
161
186
21.6
49
320
4
58
97
10.0
105
440
142
181
24.5
41
400
6
90
124
15.5
118
350
179
213
21.6
49
320
Notes: A/C operation: in cooling, air inlet t(DB)=27℃, t (WB)=19.5℃, chilled water inlet tw=7℃,chilled water outlet tw2=12℃, in heating air inlet t(DB)=15℃, heating water inlet tw=60℃ fresh air operation:in cooling, air inlet t(DB)=34℃,t (WB)=28℃,chilled water inlet tw=7℃,chilled water outlet tw2=12℃;in heating air inlet t(DB)=7℃,heating water inlet tw= 60℃
3
Ceiling air handler EMD3000~5000 A/C water outlet
A/C water inlet
air inlet
condensate water outlet
Lugging Hole
Dimensions (mm) Model
A
B
C
D
E
F
H
I
EMD3000 1742
1546
600
1170
818
270.5
99
100
EMD4000 1936
1626
900
1250
1008
180.5
99
80
EMD5000 2090
1726
920
1350
1494
180.5
99
90
Model
K
M
O
P
Q
R
ÎŚ
EMD3000 770
175
1581
1500
1540
490
118
DN40
EMD4000 1137
31.5
1777
1660
1734
776
118
DN40
EMD5000 1187
31.5
1777
1848
2164
786
118
DN40
J
Note:Base height 100mm is not included in C
4
Ceiling air handler EMD6000~12000
A/C water outlet
A/C water inlet
air inlet
condensate water outlet
Lugging Hole
Dimensions (mm) Model
A
B
C
D
E
F
G
H
I
EMD6000
2240
1746
920
1350
1494
400
180.5
99
90
EMD7000
2350
1846
1020
1450
1494
500
190
120
140
EMD8000
2540
1846
1020
1450
1494
500
190
120
140
EMD10000 2810
1946
1220
1550
2379
600
200
120
240
EMD12000 3020
1946
1220
1550
2379
800
200
120
240
Model
J
K
M
O
P
Q
R
ÎŚ
EMD6000
1187
31.5
1777
2090
1992
786
118
DN40
EMD7000
1237
31.5
2465
2108
2182
880
118
DN50
EMD8000
1237
31.5
2465
2298
2372
880
118
DN50
EMD10000 1287
31.5
2661
2568
2642
1080
118
DN50
EMD12000 1287
31.5
2661
2778
2852
1080
118
DN50
Note:Base height 100mm is not included in C
5 combined Air Handler
Product View
Nomenclature
Framing Combined air handlers are equipped with temperature adjustment, humidifier, electrostatic cleaner, silencer, etc. It can be modularized and accommodated to various applications. It is suitable for shopping malls, hotels, office buildings, gyms, operating rooms at hospitals, phar maceutical/tobacco/food/precision instrument factories.
EM 10000 - 4 - R
Framing R e i n f o rc e d a l u m i n i u m f r a m i n g , h i n g e s & supporters in the middle with even force & no high pressure deformation. Casing panel is double-skin. The inner part is zinc-coating steel plate, the outer part is compound steel, the middle part is insulation materials of CFC-free polyurethane foaming with low heat transfer coefficient, low air leakage & high air tightness. Electrostatic Cleaner The tungsten filament releases hi-volt static electricity at the air inlet so that all particles are positively charged. When the air passes through the negatively charged plates, all tinier particles and bacteria are adsorbed onto the plates. Bacteria, viruses and pollens are killed immediately. It can be washed automatically. Coils Designed per ARI standard. High coil efficiency, low air/water resistance Humidifier High pressure atomizer, dry steam humidifier, membrane humidifier can be selected. High efficiency & low energy consumption. Fan Centrifugal fan with variable speed drive is used. High efficiency, low noise, smooth operation & drastic electricity saving.
tube connection, R means right, L left coil row rated air flow m3/h Combined air handler
6
Combined Air Handler-rated performance data Model
rated air TP flow Pa m3/h
EM10000 10000
EM20000 20000
EM30000 30000
EM40000 40000
EM50000 50000
EM60000 60000
EM70000 70000
EM80000 80000
EM100000 100000
700 900 1300 700 900 1300 700 1000 1300 700 1000 1400 700 1100 1500 700 1100 1400 800 1100 1400 800 1100 1400 1000 1200 1500
fan power kW 4 5.5 7.5 7.5 11 11 11 15 18.5 15 18.5 30 18.5 30 37 22 30 37 30 37 45 30 45 55 45 55 75
rated cooling capacity kW rated heating capacity kW
Dimension mm
4rows
6rows
8rows
4rows
6rows
8rows
width
height
48
68
83
108
119
128
1650
1450
96
136
166
208
228
249
1890
1740
144
204
240
316
352
378
2250
2000
200
275
330
432
476
510
2600
2250
250
330
400
502
592
630
2650
2500
300
400
490
630
700
768
2900
2700
350
470
540
740
810
890
3100
2930
380
540
660
850
950
1020
3400
3130
500
680
800
998
1150
1260
3800
3500
Notes: 1.cooling operation air inlet t(DB)=27℃,t(WB)=19.5℃,chilled water inlet tW1=7℃,chilled water outlet tW2=12℃ 2. heating operation air inlet t(DB) =15℃,heating water inlet tW1=60℃
Coil performance data Model
cooling capacity kW water flow t/h
4rows EM10000 48 EM20000 96 EM30000 144 EM40000 200 EM50000 250 EM60000 300 EM70000 350 EM80000 380 EM100000 500
6rows 68 136 204 275 330 400 470 540 680
8rows 83 166 240 330 400 490 540 660 800
4rows 9.0 18.0 26.0 36.0 44.0 54.0 60.0 66.0 86.0
6rows 11.8 22.7 35.0 45.5 56.5 68.0 80.0 91.0 114.0
8rows 14.3 28.5 41.0 55.6 70.0 84.0 91.0 114.0 140.0
water resistance kPa
air resistance Pa
4rows 18 12 20 27 16 20 30 25 20
4rows 100 100 100 100 120 120 120 120 120
6rows 10 22 30 30 20 20 45 30 20
8rows 20 30 30 30 20 20 50 30 35
6rows 180 180 180 200 200 200 200 200 200
8rows 220 220 230 230 250 250 250 250 250
Notes: air inlet t(DB)=27℃,t(WB)=19.5℃,chilled water inlet tW1=7℃,chilled water outlet tW2=12℃
7
modules of mixed air, air inlet air inlet can be selected
front
rear rightv
Left
Notes:A*B is a standard air inlet.Air inlet can be added to the top per clients.
Dimensions (mm) Model
L
W
H
A
B
air resistance Pa
EM10000
700
1650
1450
600
800
20
EM20000
700
1890
1740
800
1200
20
EM30000
700
2250
2000
1000
1500
20
EM40000
700
2600
2250
1200
1600
20
EM50000
700
2650
2500
1500
1700
20
EM60000
800
2900
2700
1600
1700
20
EM70000
800
3100
2930
1600
2000
20
EM80000
800
3400
3130
1800
2000
20
EM100000 800
3800
3500
1800
2400
20
8
filter module Coarse filter G3 module
Medium efficiency filter F6
front
rear Left
right
Dimensions (mm) Model
L
W
H
air resistance Pa
EM10000
500
1650
1450
250
EM20000
500
1890
1740
250
EM30000
500
2250
2000
250
EM40000
500
2600
2250
250
EM50000
500
2650
2500
300
EM60000
500
2900
2700
300
EM70000
500
3100
2930
300
EM80000
500
3400
3130
300
EM100000
500
3800
3500
300
9
electrostatic cleaner
front
rear
drainage
Left
right
City water
Notes:tube connection can be left or right.The connection
illustration is right
Dimensions (mm) Model
L
W
H
Φa
Φb
air purification resistance efficiency Pa %
EM10000
700
1650
1450
DN25
DN15
50
≥50%
EM20000
750
1890
1740
DN25
DN15
50
≥50%
EM30000
750
2250
2000
DN25
DN15
50
≥50%
EM40000
800
2600
2250
DN32
DN20
50
≥50%
EM50000
800
2650
2500
DN32
DN20
50
≥50%
EM60000
850
2900
2700
DN32
DN20
50
≥50%
EM70000
900
3100
2930
DN32
DN25
50
≥50%
EM80000
950
3400
3130
DN32
DN25
50
≥50%
3800
3500
DN32
DN25
50
≥50%
EM100000 1000
10
module of coils
A/C water outlet
front
rear right
Left A/C water inlet condensate water outlet
Notes:tube connection can be left or right.The illustration is right connection
Dimensions (mm) Model
L
W
H
ÎŚa
air resistance Pa
4R
6R
8R
4R
6R
8R
EM10000
600 1650 1450
DN50
DN50
DN65
100
180
220
EM20000
600 1890 1740
DN65
DN80
DN80
100
180
220
EM30000
600 2250 2000
DN80
DN80
DN100
100
180
230
EM40000
600 2600 2250
DN80
DN100
DN100
100
200
230
EM50000
600 2650 2500
DN100
DN100
DN100
120
200
250
EM60000
700 2900 2700
DN80*2
DN80*2
DN100*2
120
200
250
EM70000
700 3100 2930
DN80*2
DN100*2 DN100*2
120
200
250
EM80000
700 3400 3130
DN80*2
DN100*2 DN100*2
120
200
250
DN100*2
DN100*2 DN100*2
120
200
250
EM100000 700 3800 3500
11
module of fan
right
Left front
rear
Note:If there is no other module after air supply,A*A is air outlet,which can be selected upward per clients.Air inlet/outlet can be selected.
Dimensions (mm) Model
L
W
H
A
air resistance Pa
EM10000
1400
1650
1450
510
60
EM20000
1600
1890
1740
810
60
EM30000
1750
2250
2000
810
60
EM40000
2050
2600
2250
1010
60
EM50000
2250
2650
2500
1130
60
EM60000
2250
2900
2700
1130
60
EM70000
2450
3100
2930
1270
60
EM80000
2550
3400
3130
1270
60
EM100000 2900
3800
3500
1430
60
12
air supply
rear
/front
air outlet can be selected Left
right
Notes:selective air outlet is a standard supply.Air outlet can be adjusted to the rear.
Dimensions (mm) Model
L
W
H
A
B
air resistance Pa
EM10000
700
1650
1450
500
800
20
EM20000
700
1890
1740
500
1200
20
EM30000
700
2250
2000
500
1600
20
EM40000
700
2600
2250
500
2000
20
EM50000
800
2650
2500
600
2000
20
EM60000
900
2900
2700
700
2200
20
EM70000
900
3100
2930
700
2400
20
EM80000
1000
3400
3130
800
2500
20
EM100000 1000
3800
3500
800
2600
20
13
function module illustrations Option One: modules of mixed air, electrostatic cleaner, coils, fan
Option Two: modules of mixed air, filter,electrostatic cleaner, coils, fan, even air distribution, silencer, air supply
Option Three: modules of mixed air, filter,electrostatic cleaner, coils, humidifier, fan, even air distribution, silencer, air supply
Installation tips 1.Air handlers must be located on the base plane which is of U-steel or concrete construction. 2.Air handlers must reserve service space at 0.8m all around. 3.There must be a ditch around the unit. A drainage is at the bottom of the ditch connecting to sewage system. 4.A valve must be installed at the water tube inlet/outlet externally to adjust the flow or water supply cutoff for service purpose. All tubes should be well insulated. 5.No excessive force for all water tube connectors during the unit locating and external tube connecting. 6.There must be a flexible conduit between air inlet/outlet and fan. The weight of water tubes & fans can not be borne by units. 7.unit power supply 3 ph, 380 V, 50 Hz/60Hz. First power on, then motor on, check the fan to see if it’s ok. If the fan is reversed, stop the unit, change the phase and power on