Industrial Catalog

Page 89

SPEC 6200

January, 2008

Copper Wire Shield

TRXLPE/Copper Wire Shield/PVC, Medium-Voltage Power 5kV, UL Type MV-105, 100% Ins. Level, 90 Mils Features:

Product Construction Conductor:

Print:

• 6 AWG thru 1000 kcmil annealed bare copper Class B compressed strand in accordance with ASTM B3 and B8

Extruded Strand Shield (ESS):

• Extruded thermoset semi-conducting stress control layer over conductor

Options:

Insulation:

• Tree Retardant Cross-Linked Polyethylene (TRXLPE)

Extruded Insulation Shield (EIS):

• Thermoset semi-conducting polymeric layer free stripping from insulation

Metallic Shield:

• A concentric serve of 24 AWG annealed solid bare copper wires over which shall be applied a lapped non-metallic tape

Jacket:

• Flame-retardant, moisture- and sunlight-resistant Polyvinyl Chloride (PVC)

CATALOG NUMBER

NOMINAL COND. CONDUCTOR SIZE DIAMETER (AWG/ kcmil) inCHES

• GENERAL CABLE® (DI) (MO/YR OF MANUFACTURE) LIGHTNING BOLT SYMBOL 1/C SIZE (AWG OR KCMIL) CU (INSULATION THICKNESS) TRXLPE TYPE MV-105 (VOLTAGE) KV% INSULATION LEVEL SUN RES (UL) SEQUENTIAL FOOTAGE MARK • Sizes 1/0 AWG and larger are listed and marked “Sunlight-Resistant FOR CT USE” in accordance with NEC and in accordance with UL 1685 (70,000 BTU/hr) • STRANDFILL® – blocked conductor. Tested in accordance with ICEA T-31-610

Applications:

• For use in wet or dry locations when installed in accordance with NEC • For use in aerial, conduit, open tray and underground duct installations where cost effectiveness is a factor • For use in direct burial if installed in a system with a ground conductor that is in close proximity, and conforms with NEC 250.4 (A) (5)

INSULATION NOMINAL DIAMETER JACKET INCHES THICKNESS Min. MAX. inCHES mm

• Rated at 105˚C • Triple tandem extrusion of the strand shield, insulation and insulation shield provides a virtually perfect cable core • Excellent resistance to electro-chemical treeing, heat, moisture and a wide variety of industrial chemicals • PVC jacket provides mechanical protection of the shielding system during installation, as well as protection from many industrial chemicals • Sunlight-resistant • Meets cold bend test at -35˚C

Compliances:

• National Electrical Code (NEC) • ICEA S-93-639/NEMA WC74 • ICEA S-97-682 • AEIC CS8 • UL 1072 • UL listed as Type MV-105 for use in accordance with NEC • Meets EPA 40 CFR, Part 261 for leachable lead content per TCLP method • OSHA acceptable

Packaging:

• Material cut to length and shipped on non-returnable wood reels. Lengths in excess of 10,000 lbs. are provided on returnable steel reels that require a deposit • Extra charges apply for cuts less than 1000 ft., lagging, pulling eyes, paralleling and plexing

NOMINAL CABLE COPPER WEIGHT DIAMETER WEIGHT inCHES mm LBS/1000 FT kg/km LBS/1000 FT kg/km

AMPACITY CONDUIT CONDUIT UNDERGROUND SIZING (3) IN AIR (1) DUCT (2) (INCHES)

5kV, UL TYPE MV-105, 100% INS. LEVELS, 90 MILS 17241.010600* 17241.010400* 17241.010200* 17241.015100* 17241.015200* 17241.015400* 17241.016000* 17241.016200* 17241.016500* 17241.017000* 17241.017500*

6 4 2 1/0 2/0 4/0 250 350 500 750 1000

0.18 0.23 0.29 0.37 0.41 0.52 0.56 0.67 0.80 0.97 1.12

0.370 0.420 0.475 0.555 0.600 0.705 0.760 0.865 0.990 1.180 1.325

0.445 0.495 0.555 0.630 0.675 0.780 0.835 0.940 1.070 1.255 1.405

0.060 0.060 0.060 0.060 0.060 0.080 0.080 0.080 0.080 0.080 0.080

1.52 1.52 1.52 1.52 1.52 2.03 2.03 2.03 2.03 2.03 2.03

0.67 0.72 0.77 0.85 0.89 1.04 1.10 1.20 1.36 1.53 1.66

17.02 18.29 19.55 21.59 22.61 26.42 28.19 30.48 34.54 38.86 42.16

250 317 420 580 670 1000 1155 1505 2060 2868 3684

372 472 625 863 997 1488 1719 2240 3066 4268 5482

93 141 217 338 427 669 788 1097 1563 2340 3113

138 210 323 503 635 996 1173 1632 2325 3482 4632

84 110 145 200 225 305 355 430 530 665 770

92 120 155 210 235 310 345 415 505 630 720

2.5 2.5 2.5 3 3 3.5 3.5 4 5 5 6

*Non-stock item, minimum runs apply. Please consult Customer Service for price and delivery. (1) Ampacities are in accordance with Table 310-73 of the NEC for triplexed or three single conductor copper cable in isolated conduit in air, based on a conductor temperature of 105˚C (221˚F) and an ambient air temperature of 40˚C (104˚F). (2) Ampacities are in accordance with Table 310-77 of the NEC for triplexed or three single conductor copper cable in underground ducts (three conductors per duct), based on a conductor temperature of 105˚C (221˚F) and an ambient earth temperature of 20˚C (68˚F), electrical duct arrangement per Figure 310.60 Detail 1, 100% load factor, and earth thermal resistance (rho) of 90. (3) Based on nominal cable diameters, three single cables in the duct (PVC Schedule 40) with no ground wire and a maximum of 40% fill. Jam ratio has been considered, but it should be checked for individual installations. Dimensions and weights are nominal; subject to industry tolerances. Note: The NESC Lighting bolt symbol is on all Uniblend constructions. ®