PRODUCT SELECTION LOCATOR SECTION

SPECIFICATION

1

300V Instrumentation Cables

1000

2

600V Instrumentation Cables

2000

3

600V Flexible Control and Power Cables

3000

4

600V Multi Conductor Control and Power Cables

4000

5

600V Industrial Power Cables

5000

6

2.4kV — 35kV Industrial Medium-Voltage Cables

6000

7

600V — 35kV Industrial Armored Cables

7000

8

600V — 28kV TECK90 Armored Control and Power Cables 8000

Technical Information

A–F

Phone: 888-593-3355 www.generalcable.com


Table of Contents Date of Issue 01/09

Section 1

300V Instrumentation Cables

SPECIFICATION NO.

1050

CHTC

1100

CHTC®

1150

CVTC®

1200

CVTC®

1250

PVIC®

1300

PVIC®

1350

PVIC®

®

Section 2

PRODUCT DESCRIPTION

REVISION DATE

XLPE/HYP, Instrumentation, Shielded 300V, UL Type PLTC, Overall Shielded Pairs/Triads XLPE/HYP, Instrumentation, Shielded 300V, UL Type PLTC, Individual and Overall Shielded Pairs XLPE/PVC, Instrumentation, Shielded 300V, UL Type PLTC, Overall Shielded Pairs/Triads XLPE/PVC, Instrumentation, Shielded 300V, UL Type PLTC, Individual and Overall Shielded Pairs PVC/PVC, Instrumentation, Shielded 300V, UL Type PLTC/ITC, Overall Shielded Pairs/Triads PVC/PVC, Instrumentation, Shielded 300V, UL Type PLTC/ITC, Individual and Overall Shielded Pairs

Jan. 2009

PVC/PVC, Instrumentation, Shielded 300V, UL Type PLTC/ITC, Individual and Overall Shielded Triads

Jan. 2008

Jan. 2009 Jan. 2008 Jan. 2008 Jan. 2008 Jan. 2009

600V Instrumentation Cables

SPECIFICATION NO.

PRODUCT DESCRIPTION

2050†

CHTC

2100†

FREP®

2150†

FREP®

2200

FREP®

2250

Arctic-Flex®

2300

Arctic-Flex®

2350

CVTC®

2400

CVTC®

2450†

VNTC®

2500†

VNTC®

2600†

GenFree™

2625†

GenFree™

2650

GenFree™

XLPE/HYP, Instrumentation, Shielded 600V, UL Type TC, Individual and Overall Shielded Pairs/Triads FR-EPR/CPE, Instrumentation, Shielded 600V, UL Type TC, Overall Shielded Pairs/Triads FR-EPR/CPE, Instrumentation, Shielded 600V, UL Type TC, Individual and Overall Shielded Pairs FR-EPR/CPE, Instrumentation, Shielded 600V, UL Type TC, Individual and Overall Shielded Triads XLPE/ARCTIC-PVC, Instrumentation, Shielded 600V, UL Type TC, CSA Type CIC, Overall Shielded Pairs/Triads XLPE/ARCTIC-PVC, Instrumentation, Shielded 600V, UL Type TC, CSA Type CIC, Individual and Overall Shielded Pairs XLPE/PVC, Instrumentation, Shielded 600V, UL Type TC, Overall Shielded Pairs/Triads XLPE/PVC, Instrumentation, Shielded 600V, UL Type TC, Individual and Overall Shielded Pairs PVC/Nylon/PVC, Instrumentation, Shielded 600V, UL Type TC, Overall Shielded Pairs/Triads PVC/Nylon/PVC, Instrumentation, Shielded 600V, UL Type TC, Individual and Overall Shielded Pairs XLPO/LSZH, Instrumentation, Shielded 600V, UL Type TC-LS, Overall Shielded Pairs/Triads XLPO/LSZH, Instrumentation, Shielded 600V, UL Type TC-LS, Individual and Overall Shielded Pairs XLPO/LSZH, Instrumentation, Shielded 600V, UL Type TC-LS, Individual and Overall Shielded Triads

®

REVISION DATE

Jan. 2009 Jan. 2008 Jan. 2008 Jan. 2008 Jan. 2008 Jan. 2008 Jan. 2008 Jan. 2008 Jan. 2008 Jan. 2008 Feb. 2008 Feb. 2008 Feb. 2008

†Indicates these products are stocked by General Cable. Phone: 888-593-3355 www.generalcable.com


Table of Contents Date of Issue 01/09

Section 3

600V Flexible Control and Power Cables

SPECIFICATION NO.

PRODUCT DESCRIPTION

3050

Super Flexing

3100

PNH®

3150

NVN®

3200

PNP

3250

MTW

3300

Festoon

Section 4

XLPE/NYLON/HYP, Thermoset Super Flexing Control 600V, UL Type TC/CSA CIC PVC/NYLON/HYP, Thermoset Continuous Flexing Control 600V, UL Type TC/CSA AWM PVC/NYLON/NEOPRENE, Thermoset Flexible Control 600V, UL Type TC PVC/NYLON/NITRILE/PVC, Thermoset Continuous Flexing Control 600V, UL Type TC/CSA AWM PVC/NYLON/PVC, Thermoplastic Flexible Control 600V, UL Type MTW/CSA AWM PVC/PVC, Thermoplastic Extreme Flexing Festoon Control and Power 600V, UL/CSA Type Festoon

REVISION DATE

Jan. 2008 Jan. 2008 Jan. 2008 Jan. 2008 Jan. 2008 Jan. 2008

600V Multi Conductor Control and Power Cables

SPECIFICATION NO.

PRODUCT DESCRIPTION

4050†

CHTC

4075†

CHTC®

4100†

CHTC®

4150

EHTC®

4200

EHTC®

4250

EHTC®

4300†

FREP®

4310†

FREP®

4325†

FREP®

4350†

FREP®

4400

Arctic-Flex®

4450

Arctic-Flex®

4500†

CVTC®

4550†

CVTC®

XLPE/HYP, Control, Unshielded 600V, UL Type TC—E-2 Color Code XLPE/HYP, Control, Unshielded 600V, UL Type TC—E-1 Color Code XLPE/HYP, Low-Voltage Power, Unshielded 600V, UL Type TC-ER—Method 4 Color Code FR-EPR/HYP, Control, Unshielded 600V, UL Type TC (18 AWG/16 AWG)—E-2 Color Code FR-EPR/HYP, Control, Unshielded 600V, UL Type TC (14 AWG—10 AWG)—E-2 Color Code FR-EPR/HYP, Low-Voltage Power, Unshielded 600V, UL Type TC-ER—Method 4 Color Code FR-EPR/CPE, Control, Unshielded 600V, UL Type TC-ER—E-2 Color Code FR-EPR/CPE, Control, Unshielded 600V, UL Type TC-ER—E-1 Color Code FR-EPR/CPE, Control, Shielded 600V, UL Type TC-ER, Overall Shielded—E-2 Color Code FR-EPR/CPE, Low-Voltage Power, Unshielded 600V, UL Type TC-ER—Method 4 Color Code XLPE/ARCTIC-PVC, Control, Unshielded 600V, UL Type TC-ER, CSA Type RW90 XLPE, CSA TYPE TC XLPE/ARCTIC-PVC, Low-Voltage Power, Unshielded 600V, UL Type TC-ER, CSA Type RW90 XLPE, CSA TYPE TC XLPE/PVC, Control, Unshielded 600V, UL Type TC-ER—E-2 Color Code XLPE/PVC, Low-Voltage Power, Unshielded 600V, UL Type TC-ER—Method 4 Color Code

®

REVISION DATE

Jan. 2009 Jan. 2009 Jan. 2009 Jan. 2008 Jan. 2008 Jan. 2009 Jan. 2008 Jan. 2008 Jan. 2008 Jan. 2009 Jan. 2008 Jan. 2009 Jan. 2008 Jan. 2009

†Indicates these products are stocked by General Cable. Phone: 888-593-3355 www.generalcable.com


Table of Contents Date of Issue 01/09

Section 4

(cont’d.)

SPECIFICATION NO.

PRODUCT DESCRIPTION

4575

CVTC VFD

4580

CVTC® VFD

4600†

VNTC®

4650†

VNTC®

4700†

VNTC®

4750†

VNTC®

4800

20/10

4850

20/10

4900†

GenFree™

4925

GenFree™

4950†

GenFree™

®

Section 5

5100 5150 5200† 5250† 5300† 5350† 5400†

XLPE/PVC, Low-Voltage Power, Shielded 2000V, UL Type TC-ER—Method 4 Color Code XLPE/PVC, Low-Voltage Power, Copper Tape Shielded 2000V, UL Type TC-ER—Method 4 Color Code PVC/NYLON/PVC, Control, Unshielded 600V, UL Type TC-ER (18 AWG/16 AWG)—E-2 Color Code PVC/NYLON/PVC, Control, Unshielded 600V, UL Type TC-ER (14 AWG—10 AWG)—E-2 Color Code PVC/NYLON/PVC, Control, Shielded 600V, UL Type TC-ER, Overall Shielded—E-2 Color Code PVC/NYLON/PVC, Low-Voltage Power, Unshielded 600V, UL Type TC-ER—Method 4 Color Code PE/PVC/PVC, Control, Unshielded 600V (18 AWG/16 AWG)—E-1 Color Code PE/PVC/PVC, Control, Unshielded 600V (14 AWG—10 AWG)—E-1 Color Code XLPO/LSZH, Control 600V, UL Type TC-LS-ER—E-2 Color Code XLPO/LSZH, Control, Shielded 600V, UL Type TC-LS-ER, Overall Shielded—E-2 Color Code XLPO/LSZH, Low-Voltage Power, Unshielded 600V, UL Type TC-LS—Method 4 Color Code

REVISION DATE

Jan. 2009 Jan. 2009 Jan. 2008 Jan. 2008 Jan. 2008 Jan. 2009 Jan. 2008 Jan. 2008 Feb. 2008 Feb. 2008 Feb. 2008

600V Industrial Power Cables

SPECIFICATION NO.

5050†

600V Multi Conductor Control and Power Cables

PRODUCT DESCRIPTION

DuraSheath

EPR/HYP, Low-Voltage Power, Unshielded 600V, UL Type RHH/RHW-2/USE-2 LS Unicon® FREP® FR-EPR, Low-Voltage Power, Unshielded 600V, UL Type RHH/RHW-2/USE-2 XHHW-2 VW-1 XLPE, Control and Low-Voltage Power, Unshielded 600V, UL Type SIS/XHHW-2, VW-1 Rated XHHW-2 XLPE, Low-Voltage Power, Unshielded 600V, UL Type XHHW-2, c(UL) RW-90 ® Unicon XLPE XLPE, Low-Voltage Power, Unshielded 600V, UL Type RHH/RHW-2/USE-2 Super Vu-Tron® EPR/CPE, Diesel Locomotive Cable 2000V, Type DLO, 600V, UL Type RHH/RHW, 1000V, CSA Type R90 ™ GenFree LSZH XLPO, Low-Smoke, Zero-Halogen (LSZH), Low-Voltage Power, Unshielded 600V, Type RHH/RHW-LS/USE, CSA AWM I A/B, Class B ™ GenFree LSZH XLPO, Low-Smoke, Zero-Halogen (LSZH), Low-Voltage Power, Unshielded 600V, Type RHH/RHW-LS/USE, CSA AWM I A/B, Class I ®

REVISION DATE

Jan. 2008 Jan. 2008 Jan. 2008 Jan. 2008 Jan. 2009 Oct. 2008 Aug. 2008 Aug. 2008

†Indicates these products are stocked by General Cable.

Phone: 888-593-3355 www.generalcable.com


Table of Contents Date of Issue 01/09

Section 5

(cont’d.)

600V Industrial Power Cables

SPECIFICATION NO.

PRODUCT DESCRIPTION

5500†

RW90

5550†

RW90

5600†

RWU90

5650†

RWU90

5700†

RHH/RHW-2

XLPE, Building Wire 600V, CSA Type RW90 (-40˚C), Single Conductor, Copper XLPE, Building Wire 600V, CSA Type RW90 (-40˚C), Single Conductor, Aluminum XLPE, Building Wire 1000V, CSA Type RWU90 (-40˚C), Single Conductor, Copper XLPE, Building Wire 1000V, CSA Type RWU90 (-40˚C), Single Conductor, Aluminum XLPE, Low-Voltage Power, Unshielded 2000V, UL Type RHH/RHW-2, Single Conductor, Aluminum

Section 6

Jan. 2009 Jan. 2009 Jan. 2009 Jan. 2009 Oct. 2008

2.4kV – 35kV Industrial Medium-Voltage Cables

SPECIFICATION NO.

6050†

REVISION DATE

PRODUCT DESCRIPTION

DuraSheath

EPR/HYP, Medium-Voltage Power, Non-Shielded 2400V, UL Type MV-90 6100† UniShield® EPR/Copper Wire Shield/CPE, Medium-Voltage Power, Shielded 5kV and 8kV, UL Type MV-105, 133% / 100% Ins. Levels, 115 Mils 6150† Uniblend® EPR/Copper Tape Shield/PVC, Medium-Voltage Power, Shielded 5kV and 8kV, UL Type MV-105, 133% / 100% Ins. Levels, 115 Mils 6175 Uniblend® EPR/Copper Tape Shield/CPE, Medium-Voltage Power, Shielded 5kV and 8kV, UL Type MV-105, 133% / 100% Ins. Levels, 115 Mils ™ 6180 GenFree EPR/Copper Tape Shield/LSZH, Medium-Voltage Power, Shielded Uniblend® 5kV and 8kV, UL Type MV-105, 133% / 100% Ins. Levels, 115 Mils 6200 Copper Wire Shield TRXLPE/Copper Wire Shield/PVC, Medium-Voltage Power 5kV, UL Type MV-105, 100% Ins. Level, 90 Mils ® † 6250 Uniblend EPR/Copper Tape Shield with Overall PVC Jacket Medium-Voltage Power, Shielded, 5kV and 8kV, UL Type MV-105 133% / 100% Ins. Levels, 115 Mils, Three Conductor 6275 Uniblend® EPR/Copper Tape Shield with Overall CPE Jacket Medium-Voltage Power, Shielded, 5kV and 8kV, UL Type MV-105 133% / 100% Ins. Levels, 115 Mils, Three Conductor ™ 6280 GenFree EPR/Copper Tape Shield with Overall LSZH Jacket Uniblend® Medium-Voltage Power, Shielded, 5kV and 8kV, UL Type MV-105 133% / 100% Ins. Levels, 115 Mils, Three Conductor ® † 6300 UniShield EPR/Copper Wire Shield/CPE, Medium-Voltage Power, Shielded 15kV, UL Type MV-105, 133% Ins. Level, 220 Mils 6350† Uniblend® EPR/Copper Tape Shield/PVC, Medium-Voltage Power, Shielded 15kV, UL Type MV-105, 133% Ins. Level, 220 Mils 6375 Uniblend® EPR/Copper Tape Shield/CPE, Medium-Voltage Power, Shielded 15kV, UL Type MV-105, 133% Ins. Level, 220 Mils ™ 6380 GenFree EPR/Copper Tape Shield/LSZH, Medium-Voltage Power, Shielded Uniblend® 15kV, UL Type MV-105, 133% Ins. Level, 220 Mils 6400 Copper Wire Shield TRXLPE/Copper Wire Shield/PVC, Medium-Voltage Power 15kV, UL Type MV-105, 133% Ins. Level, 220 Mils ®

REVISION DATE

Jan. 2008 Jan. 2009 Jan. 2009 Jan. 2009 Jan. 2009 Jan. 2008 Jan. 2009

Jan. 2009

May 2008

Jan. 2009 Jan. 2009 Jan. 2009 Jan. 2009 Jan. 2008

†Indicates these products are stocked by General Cable.

Phone: 888-593-3355 www.generalcable.com


Table of Contents Date of Issue 01/09

Section 6

(cont’d.) 2.4kV

SPECIFICATION NO.

PRODUCT DESCRIPTION

6450†

Uniblend

6475

Uniblend®

®

6480 GenFree™ Uniblend® 6500 UniShield® 6550†

– 35kV Industrial Medium-Voltage Cables

Uniblend®

EPR/Copper Tape Shield with Overall PVC Jacket Medium-Voltage Power, Shielded, 15kV, UL Type MV-105 133% Ins. Level, 220 Mils, Three Conductor EPR/Copper Tape Shield with Overall CPE Jacket Medium-Voltage Power, Shielded, 15kV, UL Type MV-105 133% Ins. Level, 220 Mils, Three Conductor EPR/Copper Tape Shield with Overall LSZH Jacket Medium-Voltage Power, Shielded, 15kV, UL Type MV-105 133% Ins. Level, 220 Mils, Three Conductor EPR/Copper Wire Shield/CPE, Medium-Voltage Power, Shielded 25kV and 35kV, UL Type MV-105, 133% / 100% Ins. Levels, 345 Mils EPR/Copper Tape Shield/PVC, Medium-Voltage Power, Shielded 25kV and 35kV, UL Type MV-105, 133% / 100% Ins. Levels, 345 Mils

6575 Uniblend® 6580 GenFree™ Uniblend® 6600 Uniblend®

EPR/Copper Tape Shield/CPE, Medium-Voltage Power, Shielded 25kV and 35kV, UL Type MV-105, 133% / 100% Ins. Levels, 345 Mils EPR/Copper Tape Shield/LSZH, Medium-Voltage Power, Shielded 25kV and 35kV, UL Type MV-105, 133% / 100% Ins. Levels, 345 Mils EPR/Copper Tape Shield with Overall PVC Jacket Medium-Voltage Power, Shielded, 25kV and 35kV, UL Type MV-105 133% / 100% Ins. Levels, 345 Mils, Three Conductor

Section 7

600V – 35kV Industrial Armored Cables

SPECIFICATION NO.

PRODUCT DESCRIPTION

7050† 7100† 7150† 7160† 7200† 7250† 7300† 7310† 7350 7400

REVISION DATE

Jan. 2008

Jan. 2009

May 2008

Jan. 2009 Jan. 2009 Jan. 2009 Jan. 2009 Jan. 2008

REVISION DATE

Duralox®

XLPE/AIA/PVC, Control, Armored Jan. 2009 600V, UL Type MC, Multi Conductor Duralox® XLPE/AIA/PVC, Power, Armored Jan. 2008 600V, UL Type MC, Three and Four Conductor (8 AWG—4/0 AWG) Duralox® XLPE/AIA/PVC, Power, Armored Jan. 2008 600V, UL Type MC, Three and Four Conductor (250 kcmil—1000 kcmil) Duralox® XLPE/AIA/PVC, Power, Armored, with Enhanced Ground Wires (50%) Jan. 2008 600V, UL Type MC, Three Conductor (1/0 AWG—1000 kcmil) Duralox® EPR/AIA/PVC, Power, Non-Shielded, Armored Jan. 2008 2400V, UL Type MV-90 or MC, Three Conductor Duralox® Uniblend® EPR/AIA/PVC, Power, Shielded, Armored Jan. 2008 5kV/8kV, UL Type MV-105 or MC, 133% / 100% Ins. Levels, 115 Mils, Three Conductor Duralox® Uniblend® EPR/AIA/PVC, Power, Shielded, Armored Jan. 2008 15kV, UL Type MV-105 or MC, 133% Ins. Level, 220 Mils, Three Conductor Duralox® Uniblend® EPR/AIA/PVC, Power, Shielded, Armored, with Enhanced Ground Wires (50%) Jan. 2008 15kV, UL Type MV-105 or MC, 133% Ins. Level, 220 Mils, Three Conductor Duralox® Uniblend® EPR/AIA/PVC, Power, Shielded, Armored Jan. 2008 25kV, UL Type MV-105 or MC, 100% Ins. Level, 260 Mils, Three Conductor Duralox® Uniblend® EPR/AIA/PVC, Power, Shielded, Armored Jan. 2008 35kV, UL Type MV-105 or MC, 100% Ins. Level, 345 Mils, Three Conductor

†Indicates these products are stocked by General Cable.

Phone: 888-593-3355 www.generalcable.com


Table of Contents Date of Issue 01/09

Section 8

600V – 28kV TECK90 Armored Control and Power Cables

SPECIFICATION NO.

PRODUCT DESCRIPTION

8025†

TECK90

8050†

TECK90

8075†

TECK90

8100

TECK90

8125

TECK90

8150†

TECK90

XLPE/PVC/AIA/PVC, Control, Armored 600V, CSA TECK90, Multi Conductor, 14 AWG XLPE/PVC/AIA/PVC, Control, Armored 600V, CSA TECK90, Multi Conductor, 12 AWG XLPE/PVC/AIA/PVC, Control, Armored 600V, CSA TECK90, Multi Conductor, 10 AWG XLPE/PVC/AIA/PVC, Power, Armored 1000V, CSA TECK90, Single Conductor XLPE/PVC/AIA/PVC, Control and Power, Armored 1000V, CSA TECK90, Two Conductor XLPE/PVC/AIA/PVC, Control and Power, Armored 1000V, CSA TECK90, Three Conductor

8175†

TECK90

XLPE/PVC/AIA/PVC, Control and Power, Armored 1000V, CSA TECK90, Four Conductor 8200 TECK90 XLPE/PVC/AIA/PVC, Power/Control Composite 600V, CSA TECK90, Three Power and Three 14 AWG Control Conductors 8225 TECK90 XLPE/PVC/AIA/PVC, Power, Unshielded, Armored 5kV, CSA TECK90, Single Conductor 8250† TECK90 XLPE/PVC/AIA/PVC, Power, Unshielded, Armored 5kV, CSA TECK90, Three Conductor 8275 HVTECK TRXLPE/Wire Shield/PVC/AIA/PVC, Power, Shielded, Armored 5kV, CSA HVTECK, 100% / 133% Ins. Levels, 90 Mils, Single Conductor 8300 HVTECK TRXLPE/Wire Shield/PVC/AIA/PVC, Power, Shielded, Armored 5kV, CSA HVTECK, 133% Ins. Level, 115 Mils, Single Conductor 8325 HVTECK TRXLPE/Tape Shield/PVC/AIA/PVC, Power, Shielded, Armored 5kV, CSA HVTECK, 100% / 133% Ins. Levels, 90 Mils, Three Conductor 8350 HVTECK TRXLPE/Tape Shield/PVC/AIA/PVC, Power, Shielded, Armored 5kV, CSA HVTECK, 133% Ins. Level, 115 Mils, Three Conductor 8375 HVTECK TRXLPE/Wire Shield/PVC/AIA/PVC, Power, Shielded, Armored 15kV, CSA HVTECK, 100% Ins. Level, 175 Mils, Single Conductor 8400 HVTECK TRXLPE/Wire Shield/PVC/AIA/PVC, Power, Shielded, Armored 15kV, CSA HVTECK, 133% Ins. Level, 220 Mils, Single Conductor 8425 HVTECK TRXLPE/Tape Shield/PVC/AIA/PVC, Power, Shielded, Armored 15kV, CSA HVTECK, 100% Ins. Level, 175 Mils, Three Conductor 8450† HVTECK TRXLPE/Tape Shield/PVC/AIA/PVC, Power, Shielded, Armored 15kV, CSA HVTECK, 133% Ins. Level, 220 Mils, Three Conductor 8475 HVTECK TRXLPE/Tape Shield/PVC/AIA/PVC, Power, Shielded, Armored 25kV, CSA HVTECK, 100% Ins. Level, 260 Mils, Three Conductor 8500 HVTECK TRXLPE/Tape Shield/PVC/AIA/PVC, Power, Shielded, Armored 25kV, CSA HVTECK, 133% Ins. Level, 320 Mils, Three Conductor 8525 HVTECK TRXLPE/Tape Shield/PVC/AIA/PVC, Power, Shielded, Armored 28kV, CSA HVTECK, 133% Ins. Level, 345 Mils, Three Conductor 8550 VERTITECK® TECK90 XLPE/PVC/GSIA/PVC, Power, Unshielded, Armored 1kV, CSA TECK90, Three Conductor

REVISION DATE

Jan. 2009 Jan. 2009 Jan. 2009 Jan. 2008 Jan. 2008 Jan. 2008 Jan. 2008 Jan. 2008 Jan. 2009 Jan. 2009 Jan. 2009 Jan. 2008 Jan. 2009 Jan. 2008 Jan. 2008 Jan. 2008 Jan. 2008 Jan. 2008 Jan. 2008 Jan. 2008 Jan. 2008 Jan. 2008

†Indicates these products are stocked by General Cable.

Phone: 888-593-3355 www.generalcable.com


Table of Contents Date of Issue 01/09

Section 8

(cont’d.)

SPECIFICATION NO.

600V – 28kV TECK90 Armored Control and Power Cables PRODUCT DESCRIPTION

8575 VERTITECK TECK90 XLPE/PVC/GSIA/PVC, Power, Unshielded, Armored 5kV, CSA TECK90, 90 Mils, Three Conductor 8625 VERTITECK® HVTECK TRXLPE/Tape Shield/PVC/GSIA/PVC, Power, Shielded, Armored 15kV, CSA HVTECK, 100% Ins. Level, 175 Mils, Three Conductor † 8700 ACWU XLPE/AIA/PVC, Control, Armored 600V, CSA ACWU90 (-40˚C), Single Conductor † 8750 ACWU XLPE/AIA/PVC, Control, Armored 600V, CSA ACWU90 (-40˚C), Three Conductor † 8775 ACWU XLPE/AIA/PVC, Control, Armored 600V, CSA ACWU90 (-40˚C), Four Conductor ®

REVISION DATE

Jan. 2008 Jan. 2008 Jan. 2008 Jan. 2009 Jan. 2009

†Indicates these products are stocked by General Cable.

Phone: 888-593-3355 www.generalcable.com


Table of Contents Date of Issue 01/09

Section A

General Technical Information

SPECIFICATION NO.

DESCRIPTION

A005

REVISION DATE

Glossary

Jan. 2008

A025

Reference Standards

Jan. 2008

A050

Checklist for Specifications

Jan. 2008

A075

NEC and CSA Designations

Jan. 2008

A100

Common Color Sequence

Jan. 2008

A150

Metric Conversion Factors

Jan. 2008

A200

Reel Capacity Chart

Jan. 2008

Section B

Conductor Data

SPECIFICATION NO.

DESCRIPTION

B005

REVISION DATE

Conductor Reference

Jan. 2008

B025

Class B Conductors for General Wiring

Jan. 2008

B030

Class C Conductors for General Wiring

Jan. 2008

B035

Class H Conductors for General Wiring

Jan. 2008

B040

Class I Conductors for General Wiring

Jan. 2008

B045

Class K Conductors for General Wiring

Jan. 2008

Section C

Material Properties

SPECIFICATION NO.

DESCRIPTION

C005

C010

Section D SPECIFICATION NO.

D005

REVISION DATE

Thermoplastic Jacket and Insulation Material Properties

Jan. 2008

Thermoset Jacket and Insulation Material Properties

Jan. 2008

Handling and Storage Recommendations DESCRIPTION

REVISION DATE

Recommended Reel Handling Practices

Jan. 2008

D025

Recommended Cable Handling Practices

Jan. 2009

D050

Recommended Cable Storage Practices

Jan. 2008

Phone: 888-593-3355 www.generalcable.com


Table of Contents Date of Issue 01/09

Section E

Cable Installation Guidelines

SPECIFICATION NO.

DESCRIPTION

E005

REVISION DATE

Pre-Installation Instructions

Jan. 2008

E025

Installation — Overview and Checklist

Jan. 2008

E050

Installation — Feed-In Setups

Jan. 2008

E075

Installation — Conductor Maximum Pulling Tensions

Jan. 2008

E100

Installation — Training and Bending Limitations

Jan. 2008

E125

Installation — Maximum Sidewall Pressure

Jan. 2009

Section F SPECIFICATION NO.

F005 F025

Cable Testing DESCRIPTION

REVISION DATE

DC “HI-POT” Pre-Test Guidelines for MV Cables

Jan. 2008

DC “HI-POT” Testing Guidelines for MV Cables

Jan. 2008

F075

Field Electrical “HI-POT” Testing Guidelines

Jan. 2008

F100

Emergency Overload Current Guidelines

Jan. 2008

F125

Short Circuit Current Calculation Overview

Jan. 2008

F150

Short Circuit Current for Copper Shields

Jan. 2008

Phone: 888-593-3355 www.generalcable.com


Building Bridges in the Sky Directing Traffic without Gridlock Making Contact with the World General Cable is a leader in the development, design, manufacture, marketing and distribution of copper, aluminum and fiber optic wire and cable for the energy, industrial, specialty and communications markets. Our products inspire progress worldwide… customers use our value-added products to create global infrastructure that improves the standard of living for people everywhere. Each day we’re building business momentum — developing ideas into

General Cable is influencing the world…with more than two-thirds of our sales generated outside North America and more than 14,000 associates in 46 manufacturing facilities throughout 23 countries. As the fifth largest wire and cable manufacturer, we are the One Company that is connecting the world.

Energy Cables Our cables carry energy across the world — through the air, underground and under the sea. Increasing demand for energy is accelerating investment in exploration, extraction, power generation, transmission and distribution — whether based on coal, natural gas, oil, nuclear, wind or water.

Industrial & Specialty Cables We have the competitive product mix and global reach to support the production of oil, gas and petrochemical; construction of new factories and maintenance of existing industrial facilities; factory automation; and special applications such as military, nuclear, marine, mining, transit and automotive.

Communications Cables Our cables keep information flowing — facilitating a non-stop stream of words and images around the world. We meet the high-speed

products, expanding geographic access and

bandwidth needs of global communications networks from fiber optic submarine communications cables, copper and fiber aerial and underground cables, to copper and fiber optic enterprise cables and system solutions.

furthering our investment in highly capable

World Headquarters

associates, Lean manufacturing, material

General Cable 4 Tesseneer Drive, Highland Heights, KY 41076-9753 U.S.A.

innovative solutions and industry-leading

science and technology resources.


Industrial Cables

Date of Issue 01/09 Section 1

300V Instrumentation Cables SPECIFICATION NO.

PRODUCT DESCRIPTION

REVISION DATE

1050

CHTC

XLPE/HYP, Instrumentation, Shielded 300V, UL Type PLTC, Overall Shielded Pairs/Triads

Jan. 2009

1100

CHTC®

XLPE/HYP, Instrumentation, Shielded 300V, UL Type PLTC, Individual and Overall Shielded Pairs

Jan. 2009

1150

CVTC®

XLPE/PVC, Instrumentation, Shielded 300V, UL Type PLTC, Overall Shielded Pairs/Triads

Jan. 2008

1200

CVTC®

XLPE/PVC, Instrumentation, Shielded 300V, UL Type PLTC, Individual and Overall Shielded Pairs

Jan. 2008

1250

PVIC®

PVC/PVC, Instrumentation, Shielded 300V, UL Type PLTC/ITC, Overall Shielded Pairs/Triads

Jan. 2008

1300

PVIC®

PVC/PVC, Instrumentation, Shielded 300V, UL Type PLTC/ITC, Individual and Overall Shielded Pairs

Jan. 2009

1350

PVIC®

PVC/PVC, Instrumentation, Shielded 300V, UL Type PLTC/ITC, Individual and Overall Shielded Triads

Jan. 2008

®

Phone: 888-593-3355 www.generalcable.com


SPEC 1050

January, 2009

CHTC

®

XLPE/HYP, Instrumentation, Shielded 300V, UL Type PLTC, Overall Shielded Pairs/Triads Product Construction Conductor:

• 20 AWG thru 16 AWG tinned, annealed copper per ASTM B33 • Class B stranding per ASTM B8

Insulation:

CATALOG NUMBER

COPPER MINIMUM AVG. MINIMUM AVG. WEIGHT NET WEIGHT INSULATION JACKET NOMINAL NO. OF COND. THICKNESS CABLE O.D. LBS/ PAIRS/ SIZE COND. THICKNESS LBS/ TRIADS (AWG) STRAND INCHES mm INCHES mm INCHES mm 1000FT kg/km 1000FT kg/km

OVERALL SHIELDED PAIRS/TRIADS 20 AWG CONDUCTORS 337770* 337780* 337790* 309660* 309670* 309680* 337800* 337810* 309690* 311640* 309700*

1 1 TRI 2 4 8 12 16 20 24 36 50

20 20 20 20 20 20 20 20 20 20 20

7/.0121 7/.0121 7/.0121 7/.0121 7/.0121 7/.0121 7/.0121 7/.0121 7/.0121 7/.0121 7/.0121

0.012 0.012 0.012 0.012 0.012 0.012 0.012 0.012 0.012 0.012 0.012

0.30 0.30 0.30 0.30 0.30 0.30 0.30 0.30 0.30 0.30 0.30

0.035 0.035 0.040 0.040 0.050 0.050 0.060 0.060 0.060 0.070 0.070

0.89 0.89 1.02 1.02 1.27 1.27 1.52 1.52 1.52 1.78 1.78

0.230 0.240 0.320 0.370 0.500 0.575 0.665 0.740 0.795 1.005 1.175

5.84 6.10 8.13 9.40 12.70 14.61 16.89 18.80 20.19 25.53 29.85

1 1 TRI 2 4 8 12 16 20 24 36 50

18 18 18 18 18 18 18 18 18 18 18

7/.0152 7/.0152 7/.0152 7/.0152 7/.0152 7/.0152 7/.0152 7/.0152 7/.0152 7/.0152 7/.0152

0.015 0.015 0.015 0.015 0.015 0.015 0.015 0.015 0.015 0.015 0.015

0.38 0.38 0.38 0.38 0.38 0.38 0.38 0.38 0.38 0.38 0.38

0.035 0.035 0.040 0.050 0.050 0.060 0.060 0.060 0.070 0.070 0.070

0.89 0.89 1.02 1.27 1.27 1.52 1.52 1.52 1.78 1.78 1.78

0.245 0.255 0.350 0.425 0.545 0.640 0.730 0.810 0.895 1.095 1.255

6.22 6.48 8.89 10.80 13.84 16.26 18.54 20.57 22.73 27.81 31.88

9 13 17 31 60 89 118 148 177 264 365

14 19 25 47 90 133 176 220 263 392 544

27 33 48 73 138 186 248 300 350 525 697

40 49 71 109 205 277 369 446 521 781 1037

1 1 TRI 2 4 8 12 16 20 24 36 50

16 16 16 16 16 16 16 16 16 16 16

7/.0192 7/.0192 7/.0192 7/.0192 7/.0192 7/.0192 7/.0192 7/.0192 7/.0192 7/.0192 7/.0192

0.015 0.015 0.015 0.015 0.015 0.015 0.015 0.015 0.015 0.015 0.015

0.38 0.38 0.38 0.38 0.38 0.38 0.38 0.38 0.38 0.38 0.38

0.035 0.035 0.050 0.050 0.060 0.060 0.060 0.060 0.070 0.070 0.080

0.89 0.89 1.27 1.27 1.52 1.52 1.52 1.52 1.78 1.78 2.03

0.270 0.285 0.430 0.490 0.650 0.755 0.845 0.900 1.020 1.225 1.415

6.86 7.24 10.92 12.45 16.51 19.18 21.46 22.86 25.91 31.12 35.94

Overall shielded pairs/triads • Overall shield is Flexfoil® aluminum/polyester in contact with stranded tinned copper drain wire • Low-lead Hypalon® Chlorosulfonated Polyethylene (CSPE)/Elastomer blend

Print:

• General Cable® (WC) CHTC XX/PS/TS XXAWG CU/XLP/HYP SHIELDED (UL) Type PLTC 90˚C SUN RES OIL RES I & II plus day/month/year OF MFG sequential footage mark

Options:

• Bare copper conductor • Class C stranding • Individual and overall shielded pairs/triads • Thermoplastic Low-Smoke, Zero-Halogen (LSZH) jacket • In accordance with UL subject 2250 as Instrumentation Tray Cable (ITC) • Other constructions available upon request

Applications: 13 18 23 44 86 127 169 210 252 377 523

19 26 34 65 127 189 251 313 375 561 778

32 40 58 99 173 245 318 392 450 672 904

48 60 86 147 257 365 473 583 670 1000 1345

18 27 36 69 135 202 268 335 401 601 834

28 41 61 40 54 80 53 85 126 102 135 201 201 246 366 300 346 515 399 444 661 498 552 821 597 655 975 894 649 966 1241 1308 1947

OVERALL SHIELDED PAIRS/TRIADS 16 AWG CONDUCTORS 309520* 337930* 337940* 337950* 337960* 337970* 337980* 337990* 338000* 338010* 338020*

Shield:

Jacket:

OVERALL SHIELDED PAIRS/TRIADS 18 AWG CONDUCTORS 337820* 337830* 337840* 337850* 337860* 337870* 337880* 337890* 337900* 337910* 337920*

• Flame-retardant Cross-Linked Polyethylene (XLPE) • Color-coded: per ICEA Method 1; Pairs - black and white. Triads - black, white and red. One conductor in each pair or triad is printed alphanumerically for easy identification

Dimensions and weights are nominal; subject to industry tolerances. *Non-stock item, minimum runs apply. Please consult Customer Service for price and delivery.

• Typical applications include audio, intercom, control, energy management and alarm circuits • In free air or raceways in accordance with NEC • Permitted for use in Class I Division 2 industrial hazardous locations per NEC • In ducts, cable trays or conduit • In accordance with UL subject 13 as PowerLimited Circuit Cable • In class 3 circuits in accordance with NEC

Features:

• Rated at 90˚C • Ripcord applied to all cables with jacket thickness of 60 mils or less • Oil-resistant jacket • Sunlight- and weather-resistant • Excellent electrical, thermal and physical properties • Excellent moisture resistance • Excellent flame resistance • “Heavy duty” rating per ICEA standards • Excellent low temperature cold bend characteristics • Meets cold bend test at -35˚C

Compliances:

Industry Compliances: • UL 13 Type PLTC • UL 1581 Flame Tests Compliances: • UL 1581 VW-1 • IEEE 383 • IEEE 1202 • CSA FT-4 Other Compliances: • EPA 40 CFR, Part 261 for leachable lead content per TCLP • OSHA acceptable

Packaging:

• Material cut to length and shipped on non-returnable wood reels

Phone: 888-593-3355 www.generalcable.com


SPEC 1100

January, 2009

CHTC

®

XLPE/HYP, Instrumentation, Shielded 300V, UL Type PLTC, Individual and Overall Shielded Pairs Product Construction Conductor:

• 20 AWG thru 16 AWG tinned, annealed copper per ASTM B33 • Class B stranding per ASTM B8

Insulation:

CATALOG NUMBER

COPPER MINIMUM AVG. MINIMUM AVG. WEIGHT NET WEIGHT INSULATION JACKET NOMINAL COND. THICKNESS CABLE O.D. LBS/ NO. OF SIZE COND. THICKNESS LBS/ PAIRS (AWG) STRAND INCHES mm INCHES mm INCHES mm 1000FT kg/km 1000FT kg/km

INDIVIDUAL AND OVERALL SHIELDED PAIRS 20 AWG CONDUCTORS 338030* 309540* 309550* 309560* 338040* 338050* 309570* 309580* 338060*

2 4 8 12 16 20 24 36 50

20 20 20 20 20 20 20 20 20

7/.0121 7/.0121 7/.0121 7/.0121 7/.0121 7/.0121 7/.0121 7/.0121 7/.0121

0.012 0.012 0.012 0.012 0.012 0.012 0.012 0.012 0.012

0.30 0.30 0.30 0.30 0.30 0.30 0.30 0.30 0.30

0.040 0.050 0.050 0.060 0.060 0.060 0.070 0.070 0.070

1.02 1.27 1.27 1.52 1.52 1.52 1.78 1.78 1.78

0.340 0.415 0.525 0.645 0.715 0.785 0.875 1.045 1.215

8.64 10.54 13.34 16.38 18.16 19.94 22.23 26.54 30.86

21 40 78 117 155 193 231 346 479

31 60 116 147 231 287 344 515 713

54 93 157 233 294 357 422 620 828

80 138 234 347 438 531 628 923 1232

41 79 155 231 307 378 459 687 952

76 113 113 168 203 302 300 446 383 570 483 719 571 850 816 1214 1119 1665

INDIVIDUAL AND OVERALL SHIELDED PAIRS 18 AWG CONDUCTORS 338070* 338080* 338090* 338100* 338110* 338120* 338130* 338140* 338150*

2 4 8 12 16 20 24 36 50

18 18 18 18 18 18 18 18 18

7/.0152 7/.0152 7/.0152 7/.0152 7/.0152 7/.0152 7/.0152 7/.0152 7/.0152

0.015 0.015 0.015 0.015 0.015 0.015 0.015 0.015 0.015

0.38 0.38 0.38 0.38 0.38 0.38 0.38 0.38 0.38

0.050 0.050 0.060 0.060 0.060 0.070 0.070 0.070 0.080

1.27 1.27 1.52 1.52 1.52 1.78 1.758 1.78 2.03

0.415 0.475 0.605 0.750 0.830 0.945 1.045 1.225 1.450

10.54 12.07 15.37 19.05 21.08 24.00 26.54 31.12 36.83

28 53 104 155 206 254 308 461 640

INDIVIDUAL AND OVERALL SHIELDED PAIRS 16 AWG CONDUCTORS 338160* 338170* 338180* 338190* 338200* 338210* 338220* 338230* 338240*

2 4 8 12 16 20 24 36 50

16 16 16 16 16 16 16 16 16

7/.0192 7/.0192 7/.0192 7/.0192 7/.0192 7/.0192 7/.0192 7/.0192 7/.0192

0.015 0.015 0.015 0.015 0.015 0.015 0.015 0.015 0.015

0.38 0.38 0.38 0.38 0.38 0.38 0.38 0.38 0.38

0.050 0.050 0.060 0.060 0.070 0.070 0.070 0.080 0.080

1.27 1.27 1.52 1.52 1.78 1.78 1.78 2.03 2.03

0.440 0.545 0.965 0.885 0.980 1.080 1.235 1.405 1.640

11.18 13.84 24.51 22.48 24.89 27.43 31.37 35.69 41.66

40 78 153 229 304 380 455 662 945

Dimensions and weights are nominal; subject to industry tolerances. *Non-stock item, minimum runs apply. Please consult Customer Service for price and delivery.

60 92 137 116 163 243 228 287 427 341 437 650 453 553 823 566 680 1012 677 800 1191 985 1108 1649 1408 1523 2267

• Flame-retardant Cross-Linked Polyethylene (XLPE) • Color-coded: per ICEA Method 1; Pairs - black and white. One conductor in each pair is printed alpha-numerically for easy identification

Shield:

Individual and overall shielded pairs • Individual pairs are 100% shielded with Flexfoil® aluminum/polyester in contact with stranded tinned copper drain wire • Overall shield is Flexfoil® aluminum/polyester in contact with stranded tinned copper drain wire

Jacket:

• Low-lead Hypalon® Chlorosulfonated Polyethylene (CSPE)/Elastomer blend

Print:

• General Cable® (WC) CHTC XX/SPS XX AWG CU/XLP/HYP SHIELDED (UL) Type PLTC 90˚C SUN RES OIL RES I & II day/MONTH/YEAR OF MFG sequential footage mark

Options:

• Bare copper conductor • Class C stranding • Overall shielded pairs • Thermoplastic Low-Smoke, Zero-Halogen (LSZH) jacket • In accordance with UL subject 2250 as Instrumentation Tray Cable (ITC) • Other constructions available upon request

Applications:

• Typical applications include audio, intercom, control, energy management and alarm circuits • In free air or raceways in accordance with NEC • Permitted for use in Class I Division 2 industrial hazardous locations per NEC • In ducts, cable trays or conduit • In accordance with UL subject 13 as PowerLimited Circuit Cable • In class 3 circuits in accordance with NEC

Features:

• Rated at 90˚C • Ripcord applied to all cables with jacket thickness of 60 mils or less • Oil-resistant jacket • Sunlight- and weather-resistant • Excellent electrical, thermal and physical properties • Excellent moisture resistance • Excellent flame resistance • “Heavy duty” rating per ICEA standards • Excellent low temperature cold bend characteristics • Meets cold bend test at -35˚C

Compliances:

Industry Compliances: • UL 13 Type PLTC • UL 1581 Flame Tests Compliances: • UL 1581 VW-1 • IEEE 383 • IEEE 1202 • CSA FT-4 Other Compliances: • EPA 40 CFR, Part 261 for leachable lead content per TCLP • OSHA acceptable

Packaging:

• Material cut to length and shipped on non-returnable wood reels

Phone: 888-593-3355 www.generalcable.com


SPEC 1150

January, 2008

CVTC

®

XLPE/PVC, Instrumentation, Shielded 300V, UL Type PLTC, Overall Shielded Pairs/Triads Product Construction Conductor:

• 18 AWG and 16 AWG bare, annealed copper per ASTM B3 • Class B stranding per ASTM B8

Insulation:

CATALOG NUMBER

COPPER MINIMUM AVG. MINIMUM AVG. WEIGHT NET WEIGHT INSULATION JACKET NOMINAL NO. OF COND. THICKNESS CABLE O.D. LBS/ PAIRS/ SIZE COND. THICKNESS LBS/ TRIADS (AWG) STRAND INCHES mm INCHES mm INCHES mm 1000FT kg/km 1000FT kg/km

OVERALL SHIELDED PAIRS/TRIADS 18 AWG CONDUCTORS 366140* 342930* 342940* 342950* 342960* 342970* 342980* 342990* 343000* 343010* 343020*

1 1 TRI 2 4 8 12 16 20 24 36 50

18 18 18 18 18 18 18 18 18 18 18

7/.0152 7/.0152 7/.0152 7/.0152 7/.0152 7/.0152 7/.0152 7/.0152 7/.0152 7/.0152 7/.0152

0.015 0.015 0.015 0.015 0.015 0.015 0.015 0.015 0.015 0.015 0.015

0.38 0.38 0.38 0.38 0.38 0.38 0.38 0.38 0.38 0.38 0.38

0.035 0.040 0.040 0.050 0.050 0.060 0.060 0.060 0.060 0.070 0.070

0.89 1.02 1.02 1.27 1.27 1.52 1.52 1.52 1.52 1.78 1.78

0.235 0.250 0.365 0.440 0.550 0.675 0.750 0.785 0.905 1.080 1.245

5.97 6.35 9.27 11.18 13.97 17.15 19.05 19.94 22.99 27.43 31.62

1 1 TRI 2 4 8 12 16 20 24 36 50

16 16 16 16 16 16 16 16 16 16 16

7/.0192 7/.0192 7/.0192 7/.0192 7/.0192 7/.0192 7/.0192 7/.0192 7/.0192 7/.0192 7/.0192

0.015 0.015 0.015 0.015 0.015 0.015 0.015 0.015 0.015 0.015 0.015

0.38 0.38 0.38 0.38 0.38 0.38 0.38 0.38 0.38 0.38 0.38

0.035 0.040 0.050 0.050 0.060 0.060 0.060 0.070 0.070 0.070 0.080

0.89 1.02 1.27 1.27 1.52 1.52 1.52 1.78 1.78 1.78 2.03

0.262 0.280 0.430 0.490 0.650 0.755 0.845 0.880 1.020 1.220 1.405

6.65 7.11 10.92 12.45 16.51 19.18 21.46 22.35 25.91 30.99 35.69

Shield:

Overall shielded pairs/triads • Overall shield is Flexfoil® aluminum/polyester in contact with stranded tinned copper drain wire

Jacket: 13 18 25 46 87 129 171 211 253 377 524

19 27 37 68 129 192 254 314 377 561 780

32 40 56 98 175 250 317 392 476 681 913

48 60 83 146 260 372 472 583 708 1013 1359

19 27 37 71 135 203 270 334 400 599 831

28 42 63 40 53 79 55 81 121 106 131 195 201 254 378 302 350 521 402 451 671 497 545 811 595 657 978 891 965 1423 1237 1322 1967

OVERALL SHIELDED PAIRS/TRIADS 16 AWG CONDUCTORS 366150* 343030* 343040* 343050* 343060* 343070* 343080* 343090* 343100* 343110* 343120*

• Flame-retardant Cross-Linked Polyethylene (XLPE) • Color-coded: per ICEA Method 1; pairs - black and white. Triads - black, white and red. One conductor in each pair or triad is printed alphanumerically for easy identification

• Flame-retardant and sunlight-resistant Polyvinyl Chloride (PVC)

Print:

• General Cable® (WC) CVTC XX/PS/TS XXAWG FR-XLP/PVC SHIELDED (UL) Type PLTC 90˚C SUN RES plus day/MONTH/YEAR OF MFG sequential footage mark

Options:

• Tinned copper conductor • Class C stranding • Individual and overall shielded pairs/triads • Ethylene Propylene Rubber (EPR) insulation • In accordance with UL subject 2250 as Instrumentation Tray Cable (ITC) • Other constructions available upon request

Applications:

Dimensions and weights are nominal; subject to industry tolerances. *Non-stock item, minimum runs apply. Please consult Customer Service for price and delivery.

• In free air and raceways in accordance with NEC • Typical applications include audio, intercom, control, energy management and alarm circuits • In ducts, cable trays or conduit • In accordance with UL Subject 13 as PowerLimited Circuit Cable • In Class 3 circuits in accordance with NEC • Permitted for use in Class I Division 2 industrial hazardous locations per NEC

Features:

• Rated at 90˚C • Ripcord applied to all cables with jacket thickness of 60 mils or less • Abrasion- and chemical-resistant • Excellent electrical properties • Sunlight- and weather-resistant • Meets cold bend test at -25˚C

Compliances:

Industry Compliances: • UL 13 Type PLTC • UL 1581 Flame Tests Compliances: • UL 1581 VW-1 • IEEE 383 Other Compliances: • EPA 40 CFR, Part 261 for leachable lead content per TCLP • OSHA acceptable

Packaging:

• Material cut to length and shipped on non-returnable wood reels

Phone: 888-593-3355 www.generalcable.com


SPEC 1200

January, 2008

CVTC

®

XLPE/PVC, Instrumentation, Shielded 300V, UL Type PLTC, Individual and Overall Shielded Pairs Product Construction Conductor:

• 18 AWG and 16 AWG bare, annealed copper per ASTM B3 • Class B stranding per ASTM B8

Insulation:

CATALOG NUMBER

COPPER MINIMUM AVG. MINIMUM AVG. WEIGHT NET WEIGHT INSULATION JACKET NOMINAL COND. THICKNESS CABLE O.D. LBS/ NO. OF SIZE COND. THICKNESS LBS/ PAIRS (AWG) STRAND INCHES mm INCHES mm INCHES mm 1000FT kg/km 1000FT kg/km

INDIVIDUAL AND OVERALL SHIELDED PAIRS 18 AWG CONDUCTORS 343140* 343150* 343160* 343170* 343180* 343190* 343200* 343210* 343220*

2 4 8 12 16 20 24 36 50

18 18 18 18 18 18 18 18 18

7/.0152 7/.0152 7/.0152 7/.0152 7/.0152 7/.0152 7/.0152 7/.0152 7/.0152

0.015 0.015 0.015 0.015 0.015 0.015 0.015 0.015 0.015

0.38 0.38 0.38 0.38 0.38 0.38 0.38 0.38 0.38

0.050 0.050 0.050 0.060 0.060 0.070 0.070 0.070 0.080

1.27 1.27 1.27 1.52 1.52 1.78 1.78 1.78 2.03

0.410 0.475 0.605 0.750 0.830 0.955 1.030 1.210 1.425

10.41 12.07 15.37 19.05 21.08 24.26 26.16 30.73 36.20

30 55 105 156 207 252 302 452 637

45 82 156 232 308 375 449 673 948

73 109 117 174 215 320 308 458 392 583 494 735 583 868 830 1235 1145 1704

INDIVIDUAL AND OVERALL SHIELDED PAIRS 16 AWG CONDUCTORS 343240* 343250* 343260* 343270* 343280* 343290* 343300* 343310* 343320*

2 4 8 12 16 20 24 36 50

16 16 16 16 16 16 16 16 16

7/.0192 7/.0192 7/.0192 7/.0192 7/.0192 7/.0192 7/.0192 7/.0192 7/.0192

0.015 0.015 0.015 0.015 0.015 0.015 0.015 0.015 0.015

0.38 0.38 0.38 0.38 0.38 0.38 0.38 0.38 0.38

0.050 0.050 0.060 0.060 0.070 0.070 0.070 0.080 0.080

1.27 1.27 1.52 1.52 1.78 1.78 1.78 2.03 2.03

0.455 0.530 0.710 0.855 0.955 1.055 1.160 1.380 1.580

11.56 13.46 18.03 21.72 24.26 26.80 29.46 35.05 40.13

42 80 155 230 306 375 456 674 945

Dimensions and weights are nominal; subject to industry tolerances. *Non-stock item, minimum runs apply. Please consult Customer Service for price and delivery.

63 96 143 119 160 238 231 293 436 342 425 632 455 563 838 558 664 988 679 780 1161 1003 1137 1692 1406 1518 2259

• Flame-retardant Cross-Linked Polyethylene (XLPE) • Color-coded: per ICEA Method 1; pairs - black and white. One conductor in each pair is printed alpha-numerically for easy identification

Shield:

Individual and overall shielded pairs • Individual pairs are 100% shielded with Flexfoil® aluminum/polyester in contact with stranded tinned copper drain wire • Overall shield is Flexfoil® aluminum/polyester in contact with stranded tinned copper drain wire

Jacket:

• Flame-retardant and sunlight-resistant Polyvinyl Chloride (PVC)

Print:

• General Cable® (WC) CVTC XX/SPS XXAWG FR-XLP/PVC SHIELDED (UL) Type PLTC 90˚C SUN RES plus day/MONTH/YEAR OF MFG sequential footage mark

Options:

• Tinned copper conductor • Class C stranding • Overall shielded pairs • Ethylene Propylene Rubber (EPR) insulation • In accordance with UL subject 2250 as Instrumentation Tray Cable (ITC) • Other constructions available upon request

Applications:

• In free air and raceways in accordance with NEC • Typical applications include audio, intercom, control, energy management and alarm circuits • In ducts, cable trays or conduit • In accordance with UL Subject 13 as PowerLimited Circuit Cable • In Class 3 circuits in accordance with NEC • Permitted for use in Class I Division 2 industrial hazardous locations per NEC

Features:

• Rated at 90˚C • Ripcord applied to all cables with jacket thickness of 60 mils or less • Abrasion- and chemical-resistant • Excellent electrical properties • Sunlight- and weather-resistant • Meets cold bend test at -25˚C

Compliances:

Industry Compliances: • UL 13 Type PLTC • UL 1581 Flame Tests Compliances: • UL 1581 VW-1 • IEEE 383 Other Compliances: • EPA 40 CFR, Part 261 for leachable lead content per TCLP • OSHA acceptable

Packaging:

• Material cut to length and shipped on non-returnable wood reels

Phone: 888-593-3355 www.generalcable.com


SPEC 1250

January, 2008

PVIC

®

PVC/PVC, Instrumentation, Shielded 300V, UL Type PLTC/ITC, Overall Shielded Pairs/Triads Product Construction Conductor:

• 20 AWG thru 16 AWG bare, annealed copper per ASTM B3 • Class B stranding per ASTM B8

Insulation:

CATALOG NUMBER

COPPER MINIMUM AVG. MINIMUM AVG. WEIGHT NET WEIGHT INSULATION JACKET NOMINAL NO. OF COND. THICKNESS CABLE O.D. LBS/ PAIRS/ SIZE COND. THICKNESS LBS/ TRIADS (AWG) STRAND INCHES mm INCHES mm INCHES mm 1000FT kg/km 1000FT kg/km

OVERALL SHIELDED PAIRS/TRIADS 20 AWG CONDUCTORS 325900* 325910* 325920* 325940* 339620* 348090* 334630* 348100* 759610* 339650* 339660*

1 1 TRI 2 4 8 12 16 20 24 36 50

20 20 20 20 20 20 20 20 20 20 20

7/.0121 7/.0121 7/.0121 7/.0121 7/.0121 7/.0121 7/.0121 7/.0121 7/.0121 7/.0121 7/.0121

0.012 0.012 0.012 0.012 0.012 0.012 0.012 0.012 0.012 0.012 0.012

0.30 0.30 0.30 0.30 0.30 0.30 0.30 0.30 0.30 0.30 0.30

0.040 0.040 0.040 0.042 0.050 0.050 0.050 0.060 0.060 0.060 0.070

1.02 1.02 1.02 1.07 1.27 1.27 1.27 1.52 1.52 1.52 1.78

0.220 0.241 0.255 0.321 0.475 0.545 0.605 0.650 0.740 0.850 0.970

5.59 6.12 6.48 8.15 12.07 13.84 15.37 16.51 18.80 21.59 24.64

1 1 TRI 2 4 8 12 16 20 24 36 50

18 18 18 18 18 18 18 18 18 18 18

7/.0152 7/.0152 7/.0152 7/.0152 7/.0152 7/.0152 7/.0152 7/.0152 7/.0152 7/.0152 7/.0152

0.015 0.015 0.015 0.015 0.015 0.015 0.015 0.015 0.015 0.015 0.015

0.38 0.38 0.38 0.38 0.38 0.38 0.38 0.38 0.38 0.38 0.38

0.040 0.040 0.042 0.042 0.060 0.060 0.060 0.060 0.070 0.070 0.070

1.02 1.02 1.07 1.07 1.52 1.52 1.52 1.52 1.78 1.78 1.78

0.240 0.264 0.325 0.357 0.646 0.670 0.750 0.780 0.915 1.030 1.180

6.10 6.71 8.26 9.07 16.41 17.02 19.05 19.81 23.24 26.16 29.97

13 18 25 45 80 124 159 201 228 354 491

28 34 41 65 104 195 248 309 376 530 713

42 51 60 97 154 290 369 460 559 789 1061

12 18 25 46 87 129 171 211 253 453 524

18 27 37 68 129 192 254 314 377 674 780

35 52 44 66 55 82 90 133 192 285 293 436 374 556 449 668 564 839 787 1171 1059 1576

18 27 37 71 135 203 270 334 400 599 831

27 45 67 40 58 86 55 74 109 106 132 197 201 259 385 302 408 607 402 526 783 497 655 975 595 803 1195 891 1122 1670 1237 1544 2298

OVERALL SHIELDED PAIRS/TRIADS 16 AWG CONDUCTORS 325770* 325780* 325790* 325810* 339700* 298830* 760530* 339710* 339720* 339730* 339740*

1 1 TRI 2 4 8 12 16 20 24 36 50

16 16 16 16 16 16 16 16 16 16 16

7/.0192 7/.0192 7/.0192 7/.0192 7/.0192 7/.0192 7/.0192 7/.0192 7/.0192 7/.0192 7/.0192

0.015 0.015 0.015 0.015 0.015 0.015 0.015 0.015 0.015 0.015 0.015

0.38 0.38 0.38 0.38 0.38 0.38 0.38 0.38 0.38 0.38 0.38

0.040 0.042 0.042 0.053 0.060 0.060 0.070 0.070 0.070 0.070 0.080

1.02 1.07 1.07 1.35 1.52 1.52 1.78 1.78 1.78 1.78 2.03

0.273 0.297 0.344 0.481 0.726 0.755 0.845 0.905 1.030 1.165 1.355

6.93 7.54 8.74 12.22 18.44 19.18 21.46 22.99 26.16 29.59 34.42

Shield:

Overall shielded pairs/triads • Overall shield is Flexfoil® aluminum/polyester in contact with stranded tinned copper drain wire

Jacket: 9 12 17 30 54 83 107 135 153 238 330

OVERALL SHIELDED PAIRS/TRIADS 18 AWG CONDUCTORS 325830* 325840* 325850* 325880* 348020* 348030* 348040* 339670* 339680* 791720* 339690*

• Polyvinyl Chloride (PVC) • Color-coded: per ICEA Method 1; Pairs - black and white. Triads - black, white and red. One conductor in each pair or triad is printed alphanumerically for easy identification

• Sunlight-resistant Polyvinyl Chloride (PVC)

Print:

• General Cable® (WC) PVIC® XX/PS/TS XXAWG PVC/PVC SHIELDED (UL) Type PLTC or ITC 105˚C SUN RES MONTH/YEAR OF MFG sequential footage mark

Options:

• Tinned copper conductor • Class C stranding • Other constructions available upon request

Applications:

• In free air and raceways in accordance with NEC • Typical applications include audio, intercom, control, energy management and alarm circuits • In ducts, cable trays or conduit • In accordance with UL Subject 13 as PowerLimited Circuit Cable • In Class 3 circuits in accordance with NEC Article 725 • In accordance with UL subject 2250 as Instrumentation Tray Cable (ITC) • Permitted for use in Class I Division 2 industrial hazardous locations per NEC Article 501-4(b) for UL Type PLTC/ITC cables • Per NEC Article 727 for Type PLTC/ITC

Features:

• Rated at 105˚C • Good electrical properties • Oil- and sunlight-resistant • Flame-retardant • Good mechanical properties • Meets cold bend test at -25˚C

Compliances:

Industry Compliances: • UL Type PLTC/ITC Flame Tests Compliances: • IEEE 383 (70,000 BTU/hr) • UL Subject 13 (70,000 BTU/hr) for PLTC • UL Subject 2250 (70,000 BTU/hr) for ITC Other Compliances: • Meets EPA 40 CFR, Part 261 for leachable lead content per TCLP method • OSHA acceptable

Packaging:

• Material cut to length and shipped on non-returnable wood reels

Dimensions and weights are nominal; subject to industry tolerances. *Non-stock item, minimum runs apply. Please consult Customer Service for price and delivery.

Phone: 888-593-3355 www.generalcable.com


SPEC 1300

January, 2009

PVIC

®

PVC/PVC, Instrumentation, Shielded 300V, UL Type PLTC/ITC, Individual and Overall Shielded Pairs Product Construction Conductor:

• 20 AWG thru 16 AWG bare, annealed copper per ASTM B3 • Class B stranding per ASTM B8

Insulation:

CATALOG NUMBER

COPPER MINIMUM AVG. MINIMUM AVG. WEIGHT NET WEIGHT INSULATION JACKET NOMINAL COND. THICKNESS CABLE O.D. LBS/ NO. OF SIZE COND. THICKNESS LBS/ PAIRS (AWG) STRAND INCHES mm INCHES mm INCHES mm 1000FT kg/km 1000FT kg/km

INDIVIDUAL AND OVERALL SHIELDED PAIRS 20 AWG CONDUCTORS 325930* 325950* 339750* 339760* 348110* 339770* 339780* 348120* 341790*

2 4 8 12 16 20 24 36 50

20 20 20 20 20 20 20 20 20

7/.0121 7/.0121 7/.0121 7/.0121 7/.0121 7/.0121 7/.0121 7/.0121 7/.0121

0.012 0.012 0.012 0.012 0.012 0.012 0.012 0.012 0.012

0.30 0.30 0.30 0.30 0.30 0.30 0.30 0.30 0.30

0.040 0.042 0.050 0.060 0.060 0.060 0.060 0.070 0.070

1.02 1.07 1.27 1.52 1.52 1.52 1.52 1.78 1.78

0.316 0.325 0.426 0.640 0.705 0.780 0.845 1.015 1.190

8.03 8.26 10.82 16.26 17.91 19.81 21.46 25.78 30.23

22 39 71 83 165 175 209 324 433

33 58 106 124 246 260 311 482 644

46 76 148 223 280 339 397 586 786

69 113 220 332 417 504 591 872 1170

45 82 156 232 308 375 449 673 935

61 91 100 149 212 316 315 469 401 597 505 752 596 887 846 1259 1165 1734

INDIVIDUAL AND OVERALL SHIELDED PAIRS 18 AWG CONDUCTORS 325860* 325890* 348060* 348070* 760420* 339800* 339810* 339820* 339830*

2 4 8 12 16 20 24 36 50

18 18 18 18 18 18 18 18 18

7/.0152 7/.0152 7/.0152 7/.0152 7/.0152 7/.0152 7/.0152 7/.0152 7/.0152

0.015 0.015 0.015 0.015 0.015 0.015 0.015 0.015 0.015

0.38 0.38 0.38 0.38 0.38 0.38 0.38 0.38 0.38

0.042 0.042 0.060 0.060 0.060 0.070 0.070 0.070 0.080

1.07 1.07 1.52 1.52 1.52 1.78 1.78 1.78 2.03

0.380 0.410 0.485 0.760 0.845 0.955 1.040 1.215 1.450

9.65 10.41 12.32 19.30 21.46 24.26 26.42 30.86 36.83

30 55 105 156 207 252 302 452 628

2 4 8 12 16 20 24 36 50

16 16 16 16 16 16 16 16 16

7/.0192 7/.0192 7/.0192 7/.0192 7/.0192 7/.0192 7/.0192 7/.0192 7/.0192

0.015 0.015 0.015 0.015 0.015 0.015 0.015 0.015 0.015

0.38 0.38 0.38 0.38 0.38 0.38 0.38 0.38 0.38

0.042 0.053 0.060 0.060 0.070 0.070 0.070 0.080 0.090

1.07 1.35 1.52 1.52 1.78 1.78 1.78 2.03 2.29

0.346 0.506 0.665 0.855 0.970 1.080 1.165 1.390 1.655

8.79 12.85 16.89 21.72 24.64 27.43 29.59 35.31 42.04

42 80 155 230 306 375 456 674 935

Dimensions and weights are nominal; subject to industry tolerances. *Non-stock item, minimum runs apply. Please consult Customer Service for price and delivery.

Shield:

Individual and overall shielded pairs • Individual pairs are 100% shielded with Flexfoil® aluminum/polyester in contact with stranded tinned copper drain wire • Overall shield is Flexfoil® aluminum/polyester in contact with stranded tinned copper drain wire

Jacket:

• Sunlight-resistant Polyvinyl Chloride (PVC)

Print:

• General Cable® (WC) PVIC XX/SPS XXAWG PVC/PVC SHIELDED (UL) Type PLTC or ITC 105˚C SUN RES MONTH/YEAR OF MFG sequential footage mark

Options:

• Tinned copper conductor • Class C stranding • Other constructions available upon request

Applications:

INDIVIDUAL AND OVERALL SHIELDED PAIRS 16 AWG CONDUCTORS 325800* 325820* 298880* 298890* 759770* 339840* 759780* 339850* 339860*

• Polyvinyl Chloride (PVC) • Color-coded: per ICEA Method 1; Pairs - black and white. One conductor in each pair is printed alpha-numerically for easy identification

63 80 119 119 151 225 231 288 429 342 435 647 455 575 856 558 705 1049 679 828 1232 1003 1215 1808 1391 1670 2485

• In free air and raceways in accordance with NEC • Typical applications include audio, intercom, control, energy management and alarm circuits • In ducts, cable trays or conduit • In accordance with UL Subject 13 as PowerLimited Circuit Cable • In Class 3 circuits in accordance with NEC Article 725 • In accordance with UL subject 2250 as Instrumentation Tray Cable (ITC) • Permitted for use in Class I Division 2 industrial hazardous locations per NEC Article 501-4(b) for UL Type PLTC/ITC cables • Per NEC Article 727 for Type PLTC/ITC

Features:

• Rated at 105˚C • Good electrical properties • Oil- and sunlight-resistant • Flame-retardant • Good mechanical properties • Meets cold bend test at -25˚C

Compliances:

Industry Compliances: • UL Type PLTC/ITC Flame Tests Compliances: • IEEE 383 (70,000 BTU/hr) • UL Subject 13 (70,000 BTU/hr) for PLTC • UL Subject 2250 (70,000 BTU/hr) for ITC Other Compliances: • Meets EPA 40 CFR, Part 261 for leachable lead content per TCLP method • OSHA acceptable

Packaging:

• Material cut to length and shipped on non-returnable wood reels

Phone: 888-593-3355 www.generalcable.com


SPEC 1350

January, 2008

PVIC

®

PVC/PVC, Instrumentation, Shielded 300V, UL Type PLTC/ITC, Individual and Overall Shielded Triads Product Construction Conductor:

• 20 AWG thru 16 AWG bare, annealed copper per ASTM B3 • Class B stranding per ASTM B8

Insulation:

CATALOG NUMBER

COPPER MINIMUM AVG. MINIMUM AVG. WEIGHT NET WEIGHT INSULATION JACKET NOMINAL COND. THICKNESS CABLE O.D. LBS/ NO. OF SIZE COND. THICKNESS LBS/ TRIADS (AWG) STRAND INCHES mm INCHES mm INCHES mm 1000FT kg/km 1000FT kg/km

INDIVIDUAL AND OVERALL SHIELDED TRIADS 20 AWG CONDUCTORS 339870* 339880* 339890* 339900* 339910* 339920* 339930* 339940*

2 TRI 4 TRI 8 TRI 12 TRI 16 TRI 20 TRI 24 TRI 36 TRI

20 20 20 20 20 20 20 20

7/.0121 7/.0121 7/.0121 7/.0121 7/.0121 7/.0121 7/.0121 7/.0121

0.012 0.012 0.012 0.012 0.012 0.012 0.012 0.012

0.30 0.30 0.30 0.30 0.30 0.30 0.30 0.30

0.040 0.040 0.050 0.060 0.060 0.060 0.070 0.070

1.07 1.07 1.27 1.52 1.52 1.52 1.78 1.78

0.340 0.365 0.566 0.705 0.780 0.860 0.955 1.115

8.64 9.27 14.38 17.91 19.81 21.84 24.26 28.32

26 48 97 145 192 240 288 431

39 71 144 216 286 357 429 641

59 97 187 287 365 440 541 767

88 144 279 427 543 655 805 1141

57 109 219 320 426 531 637 954

77 115 143 213 275 409 412 613 550 819 668 994 785 1168 1151 1713

INDIVIDUAL AND OVERALL SHIELDED TRIADS 18 AWG CONDUCTORS 325870* 339960* 348010* 760300* 339980* 339990* 340000* 340010*

2 TRI 4 TRI 8 TRI 12 TRI 16 TRI 20 TRI 24 TRI 36 TRI

18 18 18 18 18 18 18 18

7/.0152 7/.0152 7/.0152 7/.0152 7/.0152 7/.0152 7/.0152 7/.0152

0.015 0.015 0.015 0.015 0.015 0.015 0.015 0.015

0.38 0.38 0.38 0.38 0.38 0.38 0.38 0.38

0.040 0.050 0.060 0.060 0.070 0.070 0.070 0.080

1.07 1.27 1.52 1.52 1.78 1.78 1.78 2.03

0.321 0.444 0.691 0.840 0.960 1.060 1.145 1.365

8.15 11.28 17.55 21.34 24.38 26.92 29.08 34.67

38 73 147 215 286 357 428 641

INDIVIDUAL AND OVERALL SHIELDED TRIADS 16 AWG CONDUCTORS 340020* 340030* 340040* 340050* 340060* 340070* 340080* 340090*

2 TRI 4 TRI 8 TRI 12 TRI 16 TRI 20 TRI 24 TRI 36 TRI

16 16 16 16 16 16 16 16

7/.0192 7/.0192 7/.0192 7/.0192 7/.0192 7/.0192 7/.0192 7/.0192

0.015 0.015 0.015 0.015 0.015 0.015 0.015 0.015

0.38 0.38 0.38 0.38 0.38 0.38 0.38 0.38

0.040 0.050 0.060 0.070 0.070 0.070 0.080 0.080

1.07 1.27 1.52 1.78 1.78 1.78 2.03 2.03

0.367 0.502 0.786 0.970 1.075 1.195 1.310 1.540

9.32 12.75 19.96 24.64 27.31 30.35 33.27 40.39

54 108 218 325 433 541 649 972

Dimensions and weights are nominal; subject to industry tolerances. *Non-stock item, minimum runs apply. Please consult Customer Service for price and delivery.

80 104 154 161 195 290 324 375 558 484 597 888 644 765 1138 805 933 1388 966 1125 1674 1447 1620 2411

• Polyvinyl Chloride (PVC) • Color-coded: per ICEA Method 1; Triads - black, white and red. One conductor in each triad is printed alpha-numerically for easy identification

Shield:

Individual and overall shielded triads • Individual triads are 100% shielded with Flexfoil® aluminum/polyester in contact with stranded tinned copper drain wire • Overall shield is Flexfoil® aluminum/polyester in contact with stranded tinned copper drain wire

Jacket:

• Sunlight-resistant Polyvinyl Chloride (PVC)

Print:

• General Cable® (WC) PVIC XX/STS XXAWG PVC/PVC SHIELDED (UL) Type PLTC or ITC 105˚C SUN RES MONTH/YEAR OF MFG sequential footage mark

Options:

• Tinned copper conductor • Class C stranding • Other constructions available upon request

Applications:

• In free air and raceways in accordance with NEC • Typical applications include audio, intercom, control, energy management and alarm circuits • In ducts, cable trays or conduit • In accordance with UL Subject 13 as PowerLimited Circuit Cable • In Class 3 circuits in accordance with NEC Article 725 • In accordance with UL subject 2250 as Instrumentation Tray Cable (ITC) • Permitted for use in Class I Division 2 industrial hazardous locations per NEC Article 501-4(b) for UL Type PLTC/ITC cables • Per NEC Article 727 for Type PLTC/ITC

Features:

• Rated at 105˚C • Good electrical properties • Oil and sunlight resistance • Flame-retardant • Good mechanical properties • Meets cold bend test at -25˚C

Compliances:

Industry Compliances: • UL Type PLTC/ITC Flame Tests Compliances: • IEEE 383 (70,000 BTU/hr) • UL Subject 13 (70,000 BTU/hr) for PLTC • UL Subject 2250 (70,000 BTU/hr) for ITC Other Compliances: • Meets EPA 40 CFR, Part 261 for leachable lead content per TCLP method • OSHA acceptable

Packaging:

• Material cut to length and shipped on non-returnable wood reels

Phone: 888-593-3355 www.generalcable.com


Industrial Cables

Date of Issue 01/09 Section 2

600V Instrumentation Cables 2050†

CHTC®

XLPE/HYP, Instrumentation, Shielded 600V, UL Type TC, Individual and Overall Shielded Pairs/Triads

Jan. 2009

2100†

FREP®

FR-EPR/CPE, Instrumentation, Shielded 600V, UL Type TC, Overall Shielded Pairs/Triads

Jan. 2008

2150†

FREP®

FR-EPR/CPE, Instrumentation, Shielded 600V, UL Type TC, Individual and Overall Shielded Pairs

Jan. 2008

2200

FREP®

FR-EPR/CPE, Instrumentation, Shielded 600V, UL Type TC, Individual and Overall Shielded Triads

Jan. 2008

2250

Arctic-Flex®

XLPE/ARCTIC-PVC, Instrumentation, Shielded 600V, UL Type TC, CSA Type CIC, Overall Shielded Pairs/Triads

Jan. 2008

2300

Arctic-Flex®

XLPE/ARCTIC-PVC, Instrumentation, Shielded 600V, UL Type TC, CSA Type CIC, Individual and Overall Shielded Pairs

Jan. 2008

2350

CVTC®

XLPE/PVC, Instrumentation, Shielded 600V, UL Type TC, Overall Shielded Pairs/Triads

Jan. 2008

2400

CVTC®

XLPE/PVC, Instrumentation, Shielded 600V, UL Type TC, Individual and Overall Shielded Pairs

Jan. 2008

2450†

VNTC®

PVC/Nylon/PVC, Instrumentation, Shielded 600V, UL Type TC, Overall Shielded Pairs/Triads

Jan. 2008

2500†

VNTC®

PVC/Nylon/PVC, Instrumentation, Shielded 600V, UL Type TC, Individual and Overall Shielded Pairs

Jan. 2008

2600†

GenFree™

XLPO/LSZH, Instrumentation, Shielded 600V, UL Type TC-LS, Overall Shielded Pairs/Triads

Feb. 2008

2625†

GenFree™

XLPO/LSZH, Instrumentation, Shielded 600V, UL Type TC-LS, Individual and Overall Shielded Pairs

Feb. 2008

2650

GenFree™

XLPO/LSZH, Instrumentation, Shielded 600V, UL Type TC-LS, Individual and Overall Shielded Triads

Feb. 2008

†Indicates

these products are stocked by General Cable

Phone: 888-593-3355 www.generalcable.com


SPEC 2050

January, 2009

CHTC

®

XLPE/HYP, Instrumentation, Shielded 600V, UL Type TC, Individual and Overall Shielded Pairs/Triads Product Construction Conductor:

• 18 AWG and 16 AWG tinned, annealed copper per ASTM B33 • Class B stranding per ASTM B8

Insulation:

CATALOG NUMBER

COPPER MINIMUM AVG. MINIMUM AVG. WEIGHT NET WEIGHT INSULATION JACKET NOMINAL NO. OF COND. THICKNESS CABLE O.D. LBS/ PAIRS/ SIZE COND. THICKNESS LBS/ TRIADS (AWG) STRAND inCHES mm INCHES mm INCHES mm 1000 FT kg/km 1000 FT kg/km

OVERALL SHIELDED PAIRS/TRIADS 18 AWG CONDUCTORS 285150 337620* 337630* 337640* 337650* 337660* 337670* 337680* 337690* 337700* 337710*

1 1 TRI 2 4 8 12 16 20 24 36 50

18 18 18 18 18 18 18 18 18 18 18

7/.0152 7/.0152 7/.0152 7/.0152 7/.0152 7/.0152 7/.0152 7/.0152 7/.0152 7/.0152 7/.0152

0.030 0.030 0.030 0.030 0.030 0.030 0.030 0.030 0.030 0.030 0.030

0.76 0.76 0.76 0.76 0.76 0.76 0.76 0.76 0.76 0.76 0.76

0.045 0.045 0.045 0.060 0.080 0.080 0.080 0.080 0.080 0.110 0.110

1.52 1.14 1.14 1.52 2.03 2.03 2.03 2.03 2.03 2.79 2.79

0.315 0.335 0.510 0.630 0.855 1.030 1.140 1.265 1.450 1.650 2.085

8.15 13 8.51 18 12.95 28 16.00 53 21.72 104 26.16 155 28.96 206 32.13 256 36.83 308 41.91 461 52.96 637

19 26 42 79 155 231 307 381 459 687 948

49 64 92 167 326 441 554 676 795 1118 1616

73 95 137 249 485 656 824 1006 1183 1664 2405

61 85 130 204 394 548 713 850 1001 1548 2020

91 127 193 304 586 816 1061 1265 1490 2304 3006

INDIVIDUAL AND OVERALL SHIELDED PAIRS/TRIADS 16 AWG CONDUCTORS 240990 241510 241010 232560 241000* 252370 337720* 337730* 337740* 337750* 337760*

1 1 TRI 2 4 8 12 16 20 24 36 50

16 16 16 16 16 16 16 16 16 16 16

7/.0192 7/.0192 7/.0192 7/.0192 7/.0192 7/.0192 7/.0192 7/.0192 7/.0192 7/.0192 7/.0192

0.030 0.030 0.030 0.030 0.030 0.030 0.030 0.030 0.030 0.030 0.030

0.76 0.76 0.76 0.76 0.76 0.76 0.76 0.76 0.76 0.76 0.76

0.045 0.045 0.060 0.060 0.080 0.080 0.080 0.080 0.080 0.110 0.110

1.52 1.52 1.52 1.52 2.03 2.03 2.03 2.03 2.03 2.79 2.79

0.345 0.360 0.585 0.675 0.915 1.110 1.350 1.365 1.570 1.980 2.165

8.76 9.10 14.86 17.15 23.24 28.19 34.29 34.67 39.88 50.29 54.99

19 28 28 42 40 60 78 116 153 228 229 341 304 453 380 566 455 677 682 1014 946 1408

Dimensions and weights are nominal; subject to industry tolerances. *Non-stock item, minimum runs apply. Please consult Customer Service for price and delivery.

• Flame-retardant Cross-Linked Polyethylene (XLPE) • Color-coded: per ICEA Method 1; Pairs - black and white. Triads - black, white and red. One conductor in each pair or triad is printed alpha-numerically for easy identification

Shield:

Individual and overall shielded pairs/triads • Individual pairs/triads are 100% shielded with Flexfoil® aluminum/polyester in contact with stranded tinned copper drain wire • Overall shield is Flexfoil® aluminum/polyester in contact with stranded tinned copper drain wire

Jacket:

• Low-Lead Hypalon® Chlorosulfonated Polyethylene (CSPE)/Elastomer blend

Print:

• GENERAL CABLE® (WC) CHTC® XX/SPS/STS XXAWG SHIELDED CU/XLP/HYP SHIELDED (UL) TYPE TC 600V 90˚C WET OR DRY SUN RES OIL RES I & II DAY/MONTH/YEAR OF MFG sequential footage mark

Options:

• 300V Type PLTC • Bare copper conductor • Class C stranding • Overall shielded pairs/triads • EHTC®—Ethylene Propylene Rubber (EPR) insulation • Thermoplastic Low-Smoke, Zero-Halogen (LSZH) jacket • Other constructions available upon request

Applications:

• In free air, raceways or direct burial • In wet or dry locations • Permitted for use in Class I Division 2 industrial hazardous locations per NEC

Features:

• Rated at 90˚C wet or dry • Ripcord applied to all cables with jacket thickness of 60 mils or less • Oil-resistant jacket • Sunlight- and weather-resistant • Excellent electrical, thermal and physical properties • Excellent moisture resistance • Excellent flame resistance • “Heavy duty” rating per ICEA standards • Excellent low temperature cold bend characteristics • Meets cold bend test at -35˚C

Compliances:

Industry Compliances: • UL Type RFH-2, FFH-2 conductors • UL 1277 Type TC • UL 1581 • ICEA S-82-552 • ICEA S-73-532 Flame Tests Compliances: • UL 1581 VW-1 • UL 1277 • IEEE 383 • IEEE 1202 • CSA FT-4 • ICEA T-29-520 Other Compliances: • EPA 40 CFR, Part 261 for leachable lead content per TCLP • OSHA acceptable

Packaging:

• Material cut to length and shipped on non-returnable wood reels

Phone: 888-593-3355 www.generalcable.com


SPEC 2100

January, 2008

FREP

®

FR-EPR/CPE, Instrumentation, Shielded 600V, UL Type TC, Overall Shielded Pairs/Triads Product Construction Conductor:

• 18 AWG and 16 AWG tinned, annealed copper per ASTM B33 • Class B stranding per ASTM B8

Insulation:

CATALOG NUMBER

COPPER MINIMUM AVG. MINIMUM AVG. WEIGHT NET WEIGHT INSULATION JACKET NOMINAL NO. OF COND. THICKNESS CABLE O.D. LBS/ PAIRS/ SIZE COND. THICKNESS LBS/ TRIADS (AWG) STRAND inCHES mm INCHES mm INCHES mm 1000 FT kg/km 1000 FT kg/km

OVERALL SHIELDED PAIRS/TRIADS 18 AWG CONDUCTORS 287650* 325250* 337010* 337020* 337030* 337040* 294580* 337050* 337060* 337070* 337080*

1 1 TRI 2 4 8 12 16 20 24 36 50

18 18 18 18 18 18 18 18 18 18 18

7/.0152 7/.0152 7/.0152 7/.0152 7/.0152 7/.0152 7/.0152 7/.0152 7/.0152 7/.0152 7/.0152

0.025 0.025 0.025 0.025 0.025 0.025 0.025 0.025 0.025 0.025 0.025

0.64 0.64 0.64 0.64 0.64 0.64 0.64 0.64 0.64 0.64 0.64

0.045 0.045 0.045 0.045 0.060 0.060 0.080 0.080 0.080 0.080 0.080

1.14 1.14 1.14 1.14 1.52 1.52 2.03 2.03 2.03 2.03 2.03

0.300 0.315 0.420 0.490 0.675 0.775 0.925 1.025 1.105 1.360 1.555

7.62 8.00 10.67 12.45 17.15 19.69 23.50 26.04 28.07 34.54 39.50

1 1 TRI 2 4 8 12 16 20 24 36 50

16 16 16 16 16 16 16 16 16 16 16

7/.0192 7/.0192 7/.0192 7/.0192 7/.0192 7/.0192 7/.0192 7/.0192 7/.0192 7/.0192 7/.0192

0.025 0.025 0.025 0.025 0.025 0.025 0.025 0.025 0.025 0.025 0.025

0.64 0.64 0.64 0.64 0.64 0.64 0.64 0.64 0.64 0.64 0.64

0.045 0.045 0.045 0.060 0.060 0.080 0.080 0.080 0.080 0.080 0.080

1.14 1.14 1.14 1.52 1.52 2.03 2.03 2.03 2.03 2.03 2.03

0.320 0.335 0.460 0.560 0.740 0.900 1.015 1.130 1.215 1.505 2.095

8.13 8.51 11.68 14.22 18.80 22.86 25.78 28.70 30.86 38.23 53.21

Shield:

Overall shielded pairs/triads • Overall shield is Flexfoil® aluminum/polyester in contact with stranded tinned copper drain wire

Jacket: 13 18 23 44 86 127 169 210 252 377 523

19 26 34 65 127 189 251 313 375 561 778

42 63 53 79 75 112 117 174 224 333 305 454 425 632 510 759 604 899 865 1287 1144 1703

OVERALL SHIELDED PAIRS/TRIADS 16 AWG CONDUCTORS 314960 279690 283170* 283180* 337090* 283190* 337100* 337110* 337120* 337130* 337140*

• Flame-retardant Ethylene Propylene Rubber (FR-EPR) Type II • Color-coded: per ICEA Method 1; Pairs - black and white. Triads - black, white and red. One conductor in each pair or triad is printed alpha-numerically for easy identification

18 28 52 77 26 39 66 98 36 54 95 141 69 103 171 254 135 201 294 438 202 300 438 652 268 399 560 833 335 498 680 1012 401 597 807 1201 601 894 1160 1726 834 1241 1702 2533

Dimensions and weights are nominal; subject to industry tolerances. *Non-stock item, minimum runs apply. Please consult Customer Service for price and delivery.

• Flame-retardant thermoplastic Chlorinated Polyethylene (CPE)

Print:

• GENERAL CABLE® (WC) FREP® XX/PS/TS XXAWG EPR/CPE SHIELDED UL TYPE TC 90˚C WET OR DRY 600V DIR BUR SUN RES DAY/MONTH/YEAR OF MFG SEQUENTIAL FOOTAGE MARK

Options:

• Bare copper conductor • Class C stranding • Individual and overall shielded pairs/triads • CCTC—Cross-Linked Polyethylene (XLPE) insulation • FREP® XL-flame-retardant, thermoset Chlorinated Polyethylene (XL-CPE) jacket • FREP® II-flame-retardant, thermoplastic Low-Smoke, Zero-Halogen (LSZH) Polyolefin jacket • FREP® 300V-UL Type PLTC • Other constructions available upon request

Applications:

• In free air, raceways or direct burial • In wet or dry locations • Permitted for use in Class I Division 2 industrial hazardous locations per NEC

Features:

• Rated at 90˚C wet or dry • Ripcord applied to all cables with jacket thickness of 60 mils or less • Excellent physical, thermal and electrical properties • Excellent moisture resistance • Excellent resistance to compression cuts and heat deformation • Excellent flame resistance—burns to an ash; does not exhibit thermoplastic drip • Low coefficient of friction for easy pulling • Sunlight- and weather-resistant • Excellent low temperature cold bend characteristics • Meets cold bend test at -40˚C

Compliances:

Industry Compliances: • UL 1277 Type TC • UL 1581 • ICEA S-82-552 Flame Tests Compliances: • UL 1581 VW-1 • UL 1277 • IEEE 383 • IEEE 1202 • CSA FT-4 • ICEA T-29-520 Other Compliances: • EPA 40 CFR, Part 261 for leachable lead content per TCLP • OSHA acceptable

Packaging:

• Material cut to length and shipped on non-returnable wood reels

Phone: 888-593-3355 www.generalcable.com


SPEC 2150

January, 2008

FREP

®

FR-EPR/CPE, Instrumentation, Shielded 600V, UL Type TC, Individual and Overall Shielded Pairs Product Construction Conductor:

• 18 AWG and 16 AWG tinned, annealed copper per ASTM B33 • Class B stranding per ASTM B8

Insulation:

CATALOG NUMBER

COPPER MINIMUM AVG. MINIMUM AVG. WEIGHT NET WEIGHT INSULATION JACKET NOMINAL COND. THICKNESS CABLE O.D. LBS/ NO. OF SIZE COND. THICKNESS LBS/ PAIRS (AWG) STRAND inCHES mm INCHES mm INCHES mm 1000 FT kg/km 1000 FT kg/km

INDIVIDUAL AND OVERALL SHIELDED PAIRS 18 AWG CONDUCTORS 279700 279710 279720* 279730* 279740* 319270* 279750* 337240* 337250*

2 4 8 12 16 20 24 36 50

18 18 18 18 18 18 18 18 18

7/.0152 7/.0152 7/.0152 7/.0152 7/.0152 7/.0152 7/.0152 7/.0152 7/.0152

0.025 0.025 0.025 0.025 0.025 0.025 0.025 0.025 0.025

0.64 0.64 0.64 0.64 0.64 0.64 0.64 0.64 0.64

0.045 0.060 0.060 0.080 0.080 0.080 0.080 0.080 0.110

1.14 1.52 1.52 2.03 2.03 2.03 2.03 2.03 2.79

0.473 0.586 0.751 0.948 1.050 1.185 1.220 1.474 1.780

12.01 14.88 19.08 24.08 26.67 30.10 30.99 37.44 45.21

27 53 103 153 206 254 311 461 640

41 83 124 78 152 226 153 259 385 228 398 592 307 502 747 378 623 927 463 709 1055 687 1008 1500 952 1454 2164

INDIVIDUAL AND OVERALL SHIELDED PAIRS 16 AWG CONDUCTORS 280500 280520 280530 280540 279760 280990* 337260* 279770* 288260* 288250*

2 4 6 8 12 16 20 24 36 50

16 16 16 16 16 16 16 16 16 16

7/.0192 7/.0192 7/.0192 7/.0192 7/.0192 7/.0192 7/.0192 7/.0192 7/.0192 7/.0192

0.025 0.025 0.025 0.025 0.025 0.025 0.025 0.025 0.025 0.025

0.64 0.64 0.64 0.64 0.64 0.64 0.64 0.64 0.64 0.64

0.045 0.060 0.060 0.060 0.080 0.080 0.080 0.080 0.080 0.110

1.14 1.52 1.52 1.52 2.03 2.03 2.03 2.03 2.03 2.79

0.500 0.650 0.755 0.840 1.065 1.185 1.320 1.485 1.760 2.035

12.70 16.51 19.18 21.34 27.05 30.10 33.53 37.72 44.70 51.69

40 59 103 77 114 189 115 171 268 151 225 330 226 337 506 305 453 643 380 566 777 455 677 932 683 1016 1410 946 1408 1883

Dimensions and weights are nominal; subject to industry tolerances. *Non-stock item, minimum runs apply. Please consult Customer Service for price and delivery.

153 281 399 491 753 957 1156 1387 2098 2802

• Flame-retardant Ethylene Propylene Rubber (FR-EPR) Type II • Color-coded: per ICEA Method 1; Pairs - black and white. One conductor in each pair is printed alphanumerically for easy identification

Shield:

Individual and overall shielded pairs • Individual pairs are 100% individually shielded with Flexfoil® aluminum/polyester in contact with stranded tinned copper drain wire • Overall shield is Flexfoil® aluminum/polyester in contact with stranded tinned copper drain wire

Jacket:

• Flame-retardant thermoplastic Chlorinated Polyethylene (CPE)

Print:

• GENERAL CABLE® (WC) FREP® XX/SPS XXAWG EPR/CPE SHIELDED UL TYPE TC 90˚C wet or dry 600V DIR BUR SUN RES DAY/MONTH/YEAR OF MFG SEQUENTIAL FOOTAGE MARK

Options:

• Bare copper conductor • Class C stranding • Overall shielded pairs • CCTC—Cross-Linked Polyethylene (XLPE) insulation • FREP® XL-flame-retardant, thermoset Chlorinated Polyethylene (XL-CPE) jacket • FREP® II-flame-retardant, thermoplastic Low-Smoke, Zero-Halogen (LSZH) Polyolefin jacket • FREP® 300V-UL Type PLTC • Other constructions available upon request

Applications:

• In free air, raceways or direct burial • In wet or dry locations • Permitted for use in Class I Division 2 industrial hazardous locations per NEC

Features:

• Rated at 90˚C wet or dry • Ripcord applied to all cables with jacket thickness of 60 mils or less • Excellent physical, thermal and electrical properties • Excellent moisture resistance • Excellent resistance to compression cuts and heat deformation • Excellent flame resistance—burns to an ash; does not exhibit thermoplastic drip • Low coefficient of friction for easy pulling • Sunlight- and weather-resistant • Excellent low temperature cold bend characteristics • Meets cold bend test at -40˚C

Compliances:

Industry Compliances: • UL 1277 Type TC • UL 1581 • ICEA S-82-552 Flame Tests Compliances: • UL 1581 VW-1 • UL 1277 • IEEE 383 • IEEE 1202 • CSA FT-4 • ICEA T-29-520 Other Compliances: • EPA 40 CFR, Part 261 for leachable lead content per TCLP • OSHA acceptable

Packaging:

• Material cut to length and shipped on non-returnable wood reels

Phone: 888-593-3355 www.generalcable.com


SPEC 2200

January, 2008

FREP

®

FR-EPR/CPE, Instrumentation, Shielded 600V, UL Type TC, Individual and Overall Shielded Triads Product Construction Conductor:

• 18 AWG and 16 AWG tinned, annealed copper per ASTM B33 • Class B stranding per ASTM B8

Insulation:

CATALOG NUMBER

COPPER MINIMUM AVG. MINIMUM AVG. WEIGHT NET WEIGHT INSULATION JACKET NOMINAL COND. THICKNESS CABLE O.D. LBS/ NO. OF SIZE COND. THICKNESS LBS/ TRIADS (AWG) STRAND inCHES mm INCHES mm INCHES mm 1000 FT kg/km 1000 FT kg/km

INDIVIDUAL AND OVERALL SHIELDED TRIADS 18 AWG CONDUCTORS 337150* 319250* 319260* 337160* 294540* 337170* 337180* 337190*

2 TRI 4 TRI 8 TRI 12 TRI 16 TRI 20 TRI 24 TRI 36 TRI

18 18 18 18 18 18 18 18

7/.0152 7/.0152 7/.0152 7/.0152 7/.0152 7/.0152 7/.0152 7/.0152

0.025 0.025 0.025 0.025 0.025 0.025 0.025 0.025

0.64 0.64 0.64 0.64 0.64 0.64 0.64 0.64

0.060 0.060 0.080 0.080 0.080 0.080 0.080 0.080

1.52 1.52 2.03 2.03 2.03 2.03 2.03 2.03

0.560 0.640 0.825 1.065 1.180 1.310 1.500 1.740

14.22 16.26 20.96 27.05 29.97 33.27 38.10 44.20

38 73 144 218 290 361 433 649

57 127 109 201 214 343 324 528 431 675 538 825 645 972 965 1470

189 299 510 786 1005 1228 1447 2188

INDIVIDUAL AND OVERALL SHIELDED TRIADS 16 AWG CONDUCTORS 280950* 280960* 280970* 287410* 337200* 337210* 337220* 337230*

2 TRI 4 TRI 8 TRI 12 TRI 16 TRI 20 TRI 24 TRI 36 TRI

16 16 16 16 16 16 16 16

7/.0192 7/.0192 7/.0192 7/.0192 7/.0192 7/.0192 7/.0192 7/.0192

0.025 0.025 0.025 0.025 0.025 0.025 0.025 0.025

0.64 0.64 0.64 0.64 0.64 0.64 0.64 0.64

0.060 0.060 0.080 0.080 0.080 0.080 0.080 0.110

1.52 1.52 2.03 2.03 2.03 2.03 2.03 2.79

0.615 0.705 0.850 1.160 1.290 1.380 1.615 1.920

15.62 17.91 21.59 29.46 32.77 35.05 41.02 48.77

57 84 159 237 108 160 249 371 217 323 472 702 328 487 683 1016 436 649 879 1308 545 811 1058 1575 653 972 1266 1884 979 1457 1918 2854

Dimensions and weights are nominal; subject to industry tolerances. *Non-stock item, minimum runs apply. Please consult Customer Service for price and delivery.

• Flame-retardant Ethylene Propylene Rubber (FR-EPR) Type II • Color-coded: per ICEA Method 1; Triads - black, white and red. One conductor in each triad is printed alpha-numerically for easy identification

Shield:

Individual and overall shielded triads • Individual triads are 100% shielded with Flexfoil® aluminum/polyester in contact with stranded tinned copper drain wire • Overall shield is Flexfoil® aluminum/polyester in contact with stranded tinned copper drain wire

Jacket:

• Flame-retardant thermoplastic Chlorinated Polyethylene (CPE)

Print:

• General Cable® (WC) FREP® XX/STS XXAWG EPR/CPE SHIELDED UL TYPE TC 90˚C WET OR DRY 600V DIR BUR SUN RES DAY/MONTH/YEAR OF MFG SEQUENTIAL FOOTAGE MARK

Options:

• Bare copper conductor • Class C stranding • Overall shielded pairs/triads • CCTC—Cross-Linked Polyethylene (XLPE) insulation • FREP® XL-flame-retardant, thermoset Chlorinated Polyethylene (XL-CPE) jacket • FREP® II-flame-retardant, thermoplastic Low-Smoke, Zero-Halogen (LSZH) polyolefin jacket • FREP® 300V-UL Type PLTC • Other constructions available upon request

Applications:

• In free air, raceways or direct burial • In wet or dry locations • Permitted for use in Class I Division 2 industrial hazardous locations per NEC

Features:

• Rated at 90˚C wet or dry • Ripcord applied to all cables with jacket thickness of 60 mils or less • Excellent physical, thermal and electrical properties • Excellent moisture resistance • Excellent resistance to compression cuts and heat deformation • Excellent flame resistance—burns to an ash; does not exhibit thermoplastic drip • Low coefficient of friction for easy pulling • Sunlight- and weather-resistant • Excellent low temperature cold bend characteristics • Meets cold bend test at -40˚C

Compliances:

Industry Compliances: • UL 1277 Type TC • UL 1581 • ICEA S-82-552 Flame Tests Compliances: • UL 1581 VW-1 • UL 1277 • IEEE 383 • IEEE 1202 • CSA FT-4 • ICEA T-29-520 Other Compliances: • EPA 40 CFR, Part 261 for leachable lead content per TCLP • OSHA acceptable

Packaging:

• Material cut to length and shipped on non-returnable wood reels

Phone: 888-593-3355 www.generalcable.com


SPEC 2250

January, 2008

Arctic-Flex

®

XLPE/ARCTIC-PVC, Instrumentation, Shielded 600V, UL Type TC, CSA Type CIC, Overall Shielded Pairs/Triads Product Construction Conductor:

• 18 AWG and 16 AWG tinned, annealed copper per ASTM B3 • Class B stranding per ASTM B8

Insulation:

CATALOG NUMBER

COPPER MINIMUM AVG. MINIMUM AVG. WEIGHT NET WEIGHT INSULATION JACKET NOMINAL NO. OF COND. THICKNESS CABLE O.D. LBS/ PAIRS/ SIZE COND. THICKNESS LBS/ TRIADS (AWG) STRAND inCHES mm INCHES mm INCHES mm 1000 FT kg/km 1000 FT kg/km

OVERALL SHIELDED PAIRS/TRIADS 18 AWG CONDUCTORS 366170* 347630* 347640* 347650* 347660* 347670* 347680* 347690* 347700* 347710* 347720*

1 1 TRI 2 4 8 12 16 20 24 36 50

18 18 18 18 18 18 18 18 18 18 18

7/.0152 7/.0152 7/.0152 7/.0152 7/.0152 7/.0152 7/.0152 7/.0152 7/.0152 7/.0152 7/.0152

0.030 0.030 0.030 0.030 0.030 0.030 0.030 0.030 0.030 0.030 0.030

0.76 0.76 0.76 0.76 0.76 0.76 0.76 0.76 0.76 0.76 0.76

0.045 0.045 0.045 0.045 0.060 0.080 0.080 0.080 0.080 0.080 0.080

1.14 1.14 1.14 1.14 1.52 2.03 2.03 2.03 2.03 2.03 2.03

0.315 0.340 0.450 0.560 0.750 0.850 1.010 1.085 1.210 1.500 2.570

1 1 TRI 2 4 8 12 16 20 24 36 50

16 16 16 16 16 16 16 16 16 16 16

7/.0192 7/.0192 7/.0192 7/.0192 7/.0192 7/.0192 7/.0192 7/.0192 7/.0192 7/.0192 7/.0192

0.030 0.030 0.030 0.030 0.030 0.030 0.030 0.030 0.030 0.030 0.030

0.76 0.76 0.76 0.76 0.76 0.76 0.76 0.76 0.76 0.76 0.76

0.045 0.045 0.045 0.060 0.060 0.080 0.080 0.080 0.080 0.080 0.110

1.14 1.14 1.14 1.52 1.52 2.03 2.03 2.03 2.03 2.03 2.79

0.345 0.360 0.560 0.650 0.810 1.000 1.120 1.170 1.440 1.650 2.020

8.00 12 8.64 18 11.43 23 14.22 44 19.05 94 21.59 141 25.65 187 27.56 233 30.73 279 38.10 418 65.28 580

8.76 9.14 14.22 16.51 20.57 25.40 28.45 29.72 36.58 41.91 51.31

Shield:

Overall shielded pairs/triads • Overall Shield is Flexfoil® aluminum/polyester in contact with stranded tinned copper drain wire

Jacket: 18 26 34 65 140 210 278 347 415 622 863

46 68 57 85 88 131 144 214 263 391 358 533 461 686 600 893 761 1043 1005 1496 1603 2386

OVERALL SHIELDED PAIRS/TRIADS 16 AWG CONDUCTORS 366180* 347730* 347740* 347750* 347760* 347770* 347780* 347790* 347800* 347810* 347820*

• Flame-retardant Cross-Linked Polyethylene (XLPE) • Color-coded: per ICEA Method 1; pairs - black and white. Triads - black, white, and red. One conductor in each pair or triad is printed alphanumerically for easy identification

• Flame-retardant and sunlight-resistant Arcticgrade Polyvinyl Chloride (PVC)

Print:

• GENERAL CABLE® (WC) (UL) TYPE TC ARCTIC-FLEX® FR-XLP/PVC XX PS/TS XX AWG SHIELDED 90C WET OR DRY SUN RES DIR BUR 600V - CSA TYPE CIC SHIELDED INSTRUMENTATION CABLE XLPE 90C WET OR DRY -40 FT-4 PLUS DAY/MONTH/YEAR OF MFG SEQUENTIAL FOOTAGE MARK

Options:

• Bare copper • Class C stranding • E-2 Color Code • CSA Rated TC for 14 AWG and larger • Other constructions available upon request

Applications: 19 28 27 40 36 53 69 102 135 201 202 300 268 399 335 498 401 597 601 894 834 1241

Dimensions and weights are nominal; subject to industry tolerances. *Non-stock item, minimum runs apply. Please consult Customer Service for price and delivery.

32 71 121 186 324 486 616 734 894 1254 1800

48 106 181 277 482 723 917 1092 1330 1866 2679

• Industrial lighting, control and signaling circuits • Primary installations in cable trays, raceways or outdoor applications where supported by a messenger wire • In wet or dry locations

Features:

• Rated 90˚C wet or dry • Ripcord applied to all cables with jacket thickness of 60 mils or less • Sunlight- and weather-resistant • Meets CSA cold impact test at -40˚C • Meets ICEA and CSA cold bend test at -65˚C

Compliances:

Industry Compliances: • UL 1277 Type TC • UL 1581 • CSA C22.2 No. 239 Type CIC Flame Tests Compliances: • UL 1581 VW-1 • UL 1277 • CSA FT-4 • IEEE 383 Other Compliances: • EPA 40 CFR, Part 261 for leachable lead content per TCLP • OSHA acceptable

Packaging:

• Material cut to lengths and shipped on non-returnable wood reels

Phone: 888-593-3355 www.generalcable.com


SPEC 2300

January, 2008

Arctic-Flex

®

XLPE/ARCTIC-PVC, Instrumentation, Shielded 600V, UL Type TC, CSA Type CIC, Individual and Overall Shielded Pairs Product Construction Conductor:

• 18 AWG and 16 AWG tinned, annealed copper per ASTM B3 • Class B stranding per ASTM B8

Insulation:

CATALOG NUMBER

COPPER MINIMUM AVG. MINIMUM AVG. WEIGHT NET WEIGHT INSULATION JACKET NOMINAL COND. THICKNESS CABLE O.D. LBS/ NO. OF SIZE COND. THICKNESS LBS/ PAIRS (AWG) STRAND inCHES mm INCHES mm INCHES mm 1000 FT kg/km 1000 FT kg/km

INDIVIDUAL AND OVERALL SHIELDED PAIRS 18 AWG CONDUCTORS 347830* 347840* 347850* 347860* 347870* 347880* 347890* 347900* 347910*

2 4 8 12 16 20 24 36 50

18 18 18 18 18 18 18 18 18

7/.0152 7/.0152 7/.0152 7/.0152 7/.0152 7/.0152 7/.0152 7/.0152 7/.0152

0.030 0.030 0.030 0.030 0.030 0.030 0.030 0.030 0.030

0.76 0.76 0.76 0.76 0.76 0.76 0.76 0.76 0.76

0.045 0.060 0.060 0.080 0.080 0.080 0.080 0.080 0.110

1.14 1.52 1.52 2.03 2.03 2.03 2.03 2.03 2.79

0.515 0.625 0.805 1.020 1.130 1.235 1.465 1.630 1.975

13.08 15.88 20.45 25.91 28.70 31.37 37.21 41.40 50.17

30 55 105 156 207 252 308 461 640

45 93 138 82 167 248 156 304 460 232 449 668 308 554 824 375 666 991 458 794 1182 686 1122 1670 952 1598 2378

INDIVIDUAL AND OVERALL SHIELDED PAIRS 16 AWG CONDUCTORS 347920* 347930* 347940* 347950* 347960* 347970* 347980* 347990* 348000*

2 4 8 12 16 20 24 36 50

16 16 16 16 16 16 16 16 16

7/.0192 7/.0192 7/.0192 7/.0192 7/.0192 7/.0192 7/.0192 7/.0192 7/.0192

0.030 0.030 0.030 0.030 0.030 0.030 0.030 0.030 0.030

0.76 0.76 0.76 0.76 0.76 0.76 0.76 0.76 0.76

0.060 0.060 0.060 0.080 0.080 0.080 0.080 0.110 0.110

1.52 1.52 1.52 2.03 2.03 2.03 2.03 2.79 2.79

0.595 0.695 0.900 1.110 1.260 1.315 1.510 1.820 2.095

15.11 17.65 22.86 28.19 32.00 33.40 38.35 46.23 53.21

42 63 132 80 119 212 155 231 395 230 342 578 306 455 733 375 558 845 456 679 1009 674 1003 1259 946 1408 2032

Dimensions and weights are nominal; subject to industry tolerances. *Non-stock item, minimum runs apply. Please consult Customer Service for price and delivery.

196 315 588 860 1091 1258 1502 1874 3024

• Flame-retardant Cross-Linked Polyethylene (XLPE) • Color-coded: per ICEA Method 1; pairs - black and white. One conductor in each pair is printed alpha-numerically for easy identification

Shield:

Individual and overall shielded pairs • Individual pairs are 100% shielded with Flexfoil® aluminum/polyester in contact with stranded tinned copper drain wire • Overall shield is Flexfoil® aluminum/polyester in contact with stranded tinned copper drain wire

Jacket:

• Flame-retardant and sunlight-resistant Arcticgrade Polyvinyl Chloride (PVC)

Print:

• GENERAL CABLE® (WC) (UL) TYPE TC ARCTIC-FLEX® FR-XLP/PVC XX SPS/STS XX AWG SHIELDED 90C WET OR DRY SUN RES DIR BUR 600V - CSA TYPE CIC SHIELDED INSTRUMENTATION CABLE XLPE 90C WET OR DRY -40 FT-4 PLUS DAY/MONTH/YEAR OF MFG SEQUENTIAL FOOTAGE MARK

Options:

• Bare copper • Class C stranding • E-2 Color Code • CSA Rated TC for 14 AWG and larger • Other constructions available upon request

Applications:

• Industrial lighting, control and signaling circuits • Primary installations in cable trays, raceways or outdoor applications where supported by a messenger wire • In wet or dry locations

Features:

• Rated 90˚C wet or dry • Ripcord applied to all cables with jacket thickness of 60 mils or less • Sunlight- and weather-resistant • Meets CSA cold impact test at -40˚C • Meets ICEA and CSA cold bend test at -65˚C

Compliances:

Industry Compliances: • UL 1277 Type TC • UL 1581 • CSA C22.2 No. 239 Type CIC Flame Tests Compliances: • UL 1581 VW-1 • UL 1277 • CSA FT-4 • IEEE 383 Other Compliances: • EPA 40 CFR, Part 261 for leachable lead content per TCLP • OSHA acceptable

Packaging:

• Material cut to lengths and shipped on non-returnable wood reels

Phone: 888-593-3355 www.generalcable.com


SPEC 2350

January, 2008

CVTC

®

XLPE/PVC, Instrumentation, Shielded 600V, UL Type TC, Overall Shielded Pairs/Triads Product Construction Conductor:

• 18 AWG and 16 AWG bare, annealed copper per ASTM B3 • Class B stranding per ASTM B8

Insulation:

CATALOG NUMBER

COPPER MINIMUM AVG. MINIMUM AVG. WEIGHT NET WEIGHT INSULATION JACKET NOMINAL NO. OF COND. THICKNESS CABLE O.D. LBS/ PAIRS/ SIZE COND. THICKNESS LBS/ TRIADS (AWG) STRAND inCHES mm INCHES mm INCHES mm 1000 FT kg/km 1000 FT kg/km

OVERALL SHIELDED PAIRS/TRIADS 18 AWG CONDUCTORS 366160* 337270* 337360* 337280* 337290* 337300* 337310* 337320* 337330* 337340* 337350*

1 1 TRI 2 4 8 12 16 20 24 36 50

18 18 18 18 18 18 18 18 18 18 18

7/.0152 7/.0152 7/.0152 7/.0152 7/.0152 7/.0152 7/.0152 7/.0152 7/.0152 7/.0152 7/.0152

0.030 0.030 0.030 0.030 0.030 0.030 0.030 0.030 0.030 0.030 0.030

0.76 0.76 0.76 0.76 0.76 0.76 0.76 0.76 0.76 0.76 0.76

0.045 0.045 0.045 0.045 0.060 0.080 0.080 0.080 0.080 0.080 0.080

1.14 1.14 1.14 1.14 1.52 2.03 2.03 2.03 2.03 2.03 2.03

0.315 0.340 0.450 0.560 0.750 0.850 1.010 1.085 1.210 1.500 2. 570

1 1 TRI 2 4 8 12 16 20 24 36 50

16 16 16 16 16 16 16 16 16 16 16

7/.0192 7/.0192 7/.0192 7/.0192 7/.0192 7/.0192 7/.0192 7/.0192 7/.0192 7/.0192 7/.0192

0.030 0.030 0.030 0.030 0.030 0.030 0.030 0.030 0.030 0.030 0.030

0.76 0.76 0.76 0.76 0.76 0.76 0.76 0.76 0.76 0.76 0.76

0.045 0.045 0.045 0.060 0.060 0.080 0.080 0.080 0.080 0.080 0.110

1.14 1.14 1.14 1.52 1.52 2.03 2.03 2.03 2.03 2.03 2.79

0.345 0.360 0.560 0.650 0.810 1.000 1.120 1.170 1.440 1.650 2.020

8.00 12 8.64 18 11.43 23 14.22 44 19.05 94 21.59 141 25.65 187 27.56 233 30.73 279 38.10 418 65.28 580

8.76 9.14 14.22 16.51 20.57 25.40 28.45 29.72 36.58 41.91 51.31

Shield:

Overall shielded pairs/triads • Overall shield is Flexfoil® aluminum/polyester in contact with stranded tinned copper drain wire

Jacket: 18 26 34 65 140 210 278 347 415 622 863

46 68 58 86 88 131 144 214 263 391 358 533 461 686 600 893 701 1043 1005 1496 1603 2386

OVERALL SHIELDED PAIRS/TRIADS 16 AWG CONDUCTORS 319810* 319870* 337370* 382260* 337390* 337400* 337410* 337420* 337430* 337440* 337450*

• Flame-retardant Cross-Linked Polyethylene (XLPE) • Color-coded: per ICEA Method 1; Pairs - black and white. Triads - black, white and red. One conductor in each pair or triad is printed alphanumerically for easy identification

• Flame-retardant and sunlight-resistant Polyvinyl Chloride (PVC)

Print:

• General Cable® (WC) CVTC® XX/PS/TS XXAWG FR-XLP/PVC SHIELDED (UL)Type TC 90˚C wet or dry DIR BUR SUN RES 600V MONTH/YEAR OF MFG sequential footage mark

Options:

• 300V Type PLTC • Tinned copper conductor • Class C stranding • Individual and overall shielded pairs/triads • EVTC—Ethylene Propylene Rubber (EPR) insulation • Other constructions available upon request

Applications: 19 27 36 69 135 202 268 335 401 601 834

Dimensions and weights are nominal; subject to industry tolerances. *Non-stock item, minimum runs apply. Please consult Customer Service for price and delivery.

28 32 48 40 72 107 53 121 180 102 186 277 201 324 482 300 486 723 399 616 917 498 734 1092 597 894 1330 894 1254 1866 1241 1800 2679

• In free air, raceways or direct burial • In wet or dry locations • Permitted for use in Class I Division 2 industrial hazardous locations per NEC

Features:

• Rated at 90˚C wet or dry • Ripcord applied to all cables with jacket thickness of 60 mils or less • Abrasion- and chemical-resistant • Excellent electrical properties • Sunlight- and weather-resistant • Meets cold bend test at -25˚C

Compliances:

Industry Compliances: • UL 1277 Type TC • UL 1581 • ICEA S-82-552 • ICEA S-73-532 Flame Tests Compliances: • UL 1581 VW-1 • UL 1277 • IEEE 383 • IEEE 1202 • CSA FT-4 Other Compliances: • EPA 40 CFR, Part 261 for leachable lead content per TCLP • OSHA acceptable

Packaging:

• Material cut to length and shipped on non-returnable wood reels

Phone: 888-593-3355 www.generalcable.com


SPEC 2400

January, 2008

CVTC

®

XLPE/PVC, Instrumentation, Shielded 600V, UL Type TC, Individual and Overall Shielded Pairs Product Construction Conductor:

• 18 AWG and 16 AWG bare, annealed copper per ASTM B3 • Class B stranding per ASTM B8

Insulation:

CATALOG NUMBER

COPPER MINIMUM AVG. MINIMUM AVG. WEIGHT NET WEIGHT INSULATION JACKET NOMINAL COND. THICKNESS CABLE O.D. LBS/ NO. OF SIZE COND. THICKNESS LBS/ PAIRS (AWG) STRAND inCHES mm INCHES mm INCHES mm 1000 FT kg/km 1000 FT kg/km

INDIVIDUAL AND OVERALL SHIELDED PAIRS 18 AWG CONDUCTORS 319820* 319840* 319850* 337460* 337470* 337480* 337490* 337500* 337510*

2 4 8 12 16 20 24 36 50

18 18 18 18 18 18 18 18 18

7/.0152 7/.0152 7/.0152 7/.0152 7/.0152 7/.0152 7/.0152 7/.0152 7/.0152

0.030 0.030 0.030 0.030 0.030 0.030 0.030 0.030 0.030

0.76 0.76 0.76 0.76 0.76 0.76 0.76 0.76 0.76

0.045 0.060 0.060 0.080 0.080 0.080 0.080 0.080 0.110

1.14 1.52 1.52 2.03 2.03 2.03 2.03 2.03 2.79

0.515 0.625 0.805 1.020 1.130 1.235 1.465 1.630 1.975

13.08 15.88 20.45 25.91 28.70 31.37 37.21 41.40 50.17

28 53 104 155 206 254 308 461 640

41 95 141 53 170 253 155 292 435 231 442 658 307 554 824 378 666 991 459 802 1194 687 1116 1661 952 1598 2378

INDIVIDUAL AND OVERALL SHIELDED PAIRS 16 AWG CONDUCTORS 337520* 337530* 337540* 337550* 337560* 337570* 337580* 337590* 337600*

2 4 8 12 16 20 24 36 50

16 16 16 16 16 16 16 16 16

7/.0192 7/.0192 7/.0192 7/.0192 7/.0192 7/.0192 7/.0192 7/.0192 7/.0192

0.030 0.030 0.030 0.030 0.030 0.030 0.030 0.030 0.030

0.76 0.76 0.76 0.76 0.76 0.76 0.76 0.76 0.76

0.060 0.060 0.060 0.080 0.080 0.080 0.080 0.110 0.110

1.52 1.52 1.52 2.03 2.03 2.03 2.03 2.79 2.79

0.595 0.695 0.900 1.110 1.260 1.315 1.510 1.820 2.095

15.11 17.65 22.86 28.19 32.00 33.40 38.35 46.23 53.21

40 78 153 229 304 380 455 682 946

Dimensions and weights are nominal; subject to industry tolerances. *Non-stock item, minimum runs apply. Please consult Customer Service for price and delivery.

60 135 201 116 214 318 228 399 594 341 584 869 453 712 1060 566 845 1258 677 1009 1502 1014 1259 1874 1408 2032 3024

• Flame-retardant Cross-Linked Polyethylene (XLPE) • Color-coded: per ICEA Method 1; Pairs - black and white. One conductor in each pair is printed alpha-numerically for easy identification

Shield:

Individual and overall shielded pairs • Individual pairs are 100% shielded with Flexfoil® aluminum/polyester in contact with stranded tinned copper drain wire • Overall shield is Flexfoil® aluminum/polyester in contact with stranded tinned copper drain wire

Jacket:

• Flame-retardant and sunlight-resistant Polyvinyl Chloride (PVC)

Print:

• General Cable® (WC) CVTC® XX/SPS XXAWG FR-XLP/PVC SHIELDED (UL)Type TC 90˚C wet or dry DIR BUR SUN RES 600V plus MONTH/YEAR OF MFG sequential footage mark

Options:

• 300V Type PLTC • Tinned copper conductor • Class C stranding • Overall shielded pairs/triads • EVTC—Ethylene Propylene Rubber (EPR) insulation • Other constructions available upon request

Applications:

• In free air, raceways or direct burial • In wet or dry locations • Permitted for use in Class I Division 2 industrial hazardous locations per NEC

Features:

• Rated at 90˚C wet or dry • Ripcord applied to all cables with jacket thickness of 60 mils or less • Abrasion- and chemical-resistant • Excellent electrical properties • Sunlight- and weather-resistant • Meets cold bend test at -25˚C

Compliances:

Industry Compliances: • UL 1277 Type TC • UL 1581 • ICEA S-82-552 • ICEA S-73-532 Flame Tests Compliances: • UL 1581 VW-1 • UL 1277 • IEEE 383 • IEEE 1202 • CSA FT-4 Other Compliances: • EPA 40 CFR, Part 261 for leachable lead content per TCLP • OSHA acceptable

Packaging:

• Material cut to length and shipped on non-returnable wood reels

Phone: 888-593-3355 www.generalcable.com


SPEC 2450

January, 2008

VNTC

®

PVC/Nylon/PVC, Instrumentation, Shielded 600V, UL Type TC, Overall Shielded Pairs/Triads Product Construction Conductor:

• 18 AWG thru 14 AWG bare, annealed copper per ASTM B3 • Class B stranding per ASTM B8

Insulation:

CATALOG NUMBER

COPPER MINIMUM AVG. MINIMUM AVG. WEIGHT NET WEIGHT INSULATION JACKET NOMINAL NO. OF COND. THICKNESS CABLE O.D. LBS/ PAIRS/ SIZE COND. THICKNESS LBS/ TRIADS (AWG) STRAND inCHES mm INCHES mm INCHES mm 1000 FT kg/km 1000 FT kg/km

OVERALL SHIELDED PAIRS/TRIADS 18 AWG CONDUCTORS 235020 239210 235910 319740* 235980 336830* 336840* 230760* 270970* 336850* 230750* 230800* 336860*

1 1 TRI 2 3 4 5 7 12 16 20 24 36 50

18 18 18 18 18 18 18 18 18 18 18 18 18

7/.0152 7/.0152 7/.0152 7/.0152 7/.0152 7/.0152 7/.0152 7/.0152 7/.0152 7/.0152 7/.0152 7/.0152 7/.0152

0.020 0.020 0.020 0.020 0.020 0.020 0.020 0.020 0.020 0.020 0.020 0.020 0.020

0.51 0.51 0.51 0.51 0.51 0.51 0.51 0.51 0.51 0.51 0.51 0.51 0.51

0.045 0.045 0.045 0.045 0.045 0.060 0.060 0.060 0.080 0.080 0.080 0.080 0.080

1.14 1.14 1.14 1.14 1.14 1.52 1.52 1.52 2.03 2.03 2.03 2.03 2.03

0.280 0.300 0.440 0.465 0.505 0.570 0.585 0.770 0.825 0.905 1.020 1.150 1.405

7.11 7.62 11.18 11.81 12.83 14.48 14.86 19.56 20.96 22.99 25.91 29.21 35.69

12 18 23 33 44 55 75 127 168 210 252 378 525

19 41 61 27 49 73 34 72 107 50 90 134 65 110 164 82 144 214 112 177 263 189 277 412 250 355 528 313 455 677 375 544 810 562 763 1135 781 1036 1542

OVERALL SHIELDED PAIRS/TRIADS 16 AWG CONDUCTORS 230830 230840 238410* 239200* 230790* 336870* 336880* 244590* 244610* 336890* 230780* 230820* 230810*

1 1 TRI 2 3 4 5 7 12 16 20 24 36 50

16 16 16 16 16 16 16 16 16 16 16 16 16

7/.0192 7/.0192 7/.0192 7/.0192 7/.0192 7/.0192 7/.0192 7/.0192 7/.0192 7/.0192 7/.0192 7/.0192 7/.0192

0.020 0.020 0.020 0.020 0.020 0.020 0.020 0.020 0.020 0.020 0.020 0.020 0.020

0.51 0.51 0.51 0.51 0.51 0.51 0.51 0.51 0.51 0.51 0.51 0.51 0.51

0.045 0.045 0.045 0.045 0.060 0.060 0.060 0.060 0.080 0.080 0.080 0.080 0.080

1.14 1.14 1.14 1.14 1.52 1.52 1.52 1.52 2.03 2.03 2.03 2.03 2.03

0.300 0.315 0.470 0.505 0.575 0.610 0.630 0.825 0.970 1.010 1.135 1.375 1.570

7.62 8.00 11.94 12.83 14.61 15.49 16.00 20.96 24.64 25.65 28.83 34.93 39.88

1

14

Shield:

Overall shielded pairs/triads • Overall shield is Flexfoil® aluminum/polyester in contact with stranded tinned copper drain wire

Jacket:

• Flame-retardant, moisture- and sunlightresistant Polyvinyl Chloride (PVC)

Print:

• General Cable® (WC) VNTC® XX/PS/TS XXAWG shielded (UL) Type TC 600V TFN SUN RES DIR BUR DAY/MONTH/YEAR OF MFG sequential footage mark

Options:

• Tinned copper conductor • Class C stranding • Individual and overall shielded pairs/triads • Other constructions available upon request

Applications:

• In free air, raceways or direct burial • In wet or dry locations • Permitted for use in Class I Division 2 industrial hazardous locations per NEC

Features: 20 29 52 77 27 40 61 91 37 54 93 138 53 79 117 174 69 103 160 238 87 129 190 283 117 174 239 356 201 299 370 551 267 397 513 763 337 502 628 935 398 592 740 1101 595 886 1063 1582 833 1240 1435 2136

OVERALL SHIELDED PAIRS/TRIADS 14 AWG CONDUCTORS 237490

• Flame-retardant Polyvinyl Chloride (PVC) with clear Polyamide (nylon) • Color-coded: per ICEA Method 1; Pairs - black and white. Triads - black, white and red. One conductor in each pair or triad is printed alphanumerically for easy identification

7/.0242 0.015 0.38 0.045 1.14 0.325 8.26

Dimensions and weights are nominal; subject to industry tolerances. *Non-stock item, minimum runs apply. Please consult Customer Service for price and delivery.

28

42

62

92

• Rated at 90˚C dry, 75˚C wet • Ripcord applied to all cables with jacket thickness of 60 mils or less • Provides sunlight, cold bend and cold impact resistance • Offer the smallest cable O.D. available for suitable applications • Provides excellent oil and chemical resistance • Provides a long service life • Meets cold bend test at -25˚C

Compliances:

Industry Compliances: • UL 1277 Type TC • UL 1581 • NEC Type TFN conductors Flame Tests Compliances: • UL 1277 • IEEE 383 • IEEE 1202 • CSA FT-4 Other Compliances: • EPA 40 CFR, Part 261 for leachable lead content per TCLP • OSHA acceptable

Packaging:

• Material cut to length and shipped on non-returnable wood reels

Phone: 888-593-3355 www.generalcable.com


SPEC 2500

January, 2008

VNTC

®

PVC/Nylon/PVC, Instrumentation, Shielded 600V, UL Type TC, Individual and Overall Shielded Pairs Product Construction Conductor:

• 18 AWG and 16 AWG bare, annealed copper per ASTM B3 • Class B stranding per ASTM B8

Insulation:

CATALOG NUMBER

COPPER MINIMUM AVG. MINIMUM AVG. WEIGHT NET WEIGHT INSULATION JACKET NOMINAL COND. THICKNESS CABLE O.D. LBS/ NO. OF SIZE COND. THICKNESS LBS/ PAIRS (AWG) STRAND inCHES mm INCHES mm INCHES mm 1000 FT kg/km 1000 FT kg/km

INDIVIDUAL AND OVERALL SHIELDED PAIRS 18 AWG CONDUCTORS 235970* 336900* 235900* 336910* 336920* 241020* 336930* 336940* 241030* 243880* 256300*

2 3 4 5 7 12 16 20 24 36 50

18 18 18 18 18 18 18 18 18 18 18

7/.0152 7/.0152 7/.0152 7/.0152 7/.0152 7/.0152 7/.0152 7/.0152 7/.0152 7/.0152 7/.0152

0.020 0.020 0.020 0.020 0.020 0.020 0.020 0.020 0.020 0.020 0.020

0.51 0.51 0.51 0.51 0.51 0.51 0.51 0.51 0.51 0.51 0.51

0.045 0.045 0.045 0.060 0.060 0.060 0.080 0.080 0.080 0.080 0.080

1.14 1.14 1.14 1.52 1.52 1.52 2.03 2.03 2.03 2.03 2.03

0.445 0.480 0.555 0.580 0.650 0.845 0.960 1.050 1.175 1.380 1.615

11.30 12.19 14.10 14.73 16.51 21.46 24.38 26.67 29.85 35.05 41.02

28 41 84 125 46 68 106 158 53 79 145 216 74 110 169 252 102 152 219 326 193 287 390 506 229 341 473 704 283 421 594 884 340 506 689 1025 508 756 979 1457 705 1049 1371 1960

2 3 4 5 7 8 12 16 20 24 36 50

16 16 16 16 16 16 16 16 16 16 16 16

7/.0192 7/.0192 7/.0192 7/.0192 7/.0192 7/.0192 7/.0192 7/.0192 7/.0192 7/.0192 7/.0192 7/.0192

0.020 0.020 0.020 0.020 0.020 0.020 0.020 0.020 0.020 0.020 0.020 0.020

0.51 0.51 0.51 0.51 0.51 0.51 0.51 0.51 0.51 0.51 0.51 0.51

0.045 0.045 0.045 0.060 0.060 0.060 0.060 0.080 0.080 0.080 0.080 0.080

1.14 1.14 1.14 1.52 1.52 1.52 1.52 2.03 2.03 2.03 2.03 2.03

0.495 0.520 0.600 0.655 0.710 0.760 0.940 1.055 1.175 1.350 1.480 1.810

12.57 44 65 105 13.21 64 95 137 15.24 84 125 188 16.64 105 157 224 18.03 145 216 290 19.30 155 224 307 23.88 244 363 498 26.80 324 482 635 29.85 407 605 768 34.29 486 724 903 37.59 732 1089 1290 45.97 1011 1504 1809

Dimensions and weights are nominal; subject to industry tolerances. *Non-stock item, minimum runs apply. Please consult Customer Service for price and delivery.

Shield:

Individual and overall shielded pairs • Individual pairs are 100% shielded with Flexfoil® aluminum/polyester in contact with stranded tinned copper drain wire • Overall shield is Flexfoil® aluminum/polyester in contact with stranded tinned copper drain wire

Jacket:

• Flame-retardant and sunlight-resistant Polyvinyl Chloride (PVC)

Print:

• General Cable® (WC) VNTC® XX/SPS XXAWG shielded (UL) Type TC 600V TFN SUN RES DIR BUR Plus DAY/MONTH/YEAR OF MFG sequential footage mark

Options:

• Tinned copper conductor • Class C stranding • Overall shielded pairs/triads • Other constructions available upon request

Applications:

INDIVIDUAL AND OVERALL SHIELDED PAIRS 16 AWG CONDUCTORS 237180 235990* 237160 336950* 336960* 235750 242870 237130* 277820* 242860* 243890* 244600*

• Flame-retardant Polyvinyl Chloride (PVC) with clear Polyamide (nylon) • Color-coded: per ICEA Method 1; Pairs - black and white. One conductor in each pair is printed alpha-numerically for easy identification

156 204 280 333 432 457 741 945 1143 1344 1920 2692

• In free air, raceways or direct burial • In wet or dry locations • Permitted for use in Class I Division 2 industrial hazardous locations per NEC

Features:

• Rated at 90˚C dry, 75˚C wet • Ripcord applied to all cables with jacket thickness of 60 mils or less • Provides sunlight, cold bend and cold impact resistance • Offer the smallest cable O.D. available for suitable applications • Provides excellent oil and chemical resistance • Provides a long service life • Meets cold bend test at -25˚C

Compliances:

Industry Compliances: • UL 1277 Type TC • UL 1581 • NEC Type TFN conductors Flame Tests Compliances: • UL 1277 • IEEE 383 • IEEE 1202 • CSA FT-4 Other Compliances: • EPA 40 CFR, Part 261 for leachable lead content per TCLP • OSHA acceptable

Packaging:

• Material cut to length and shipped on non-returnable wood reels

Phone: 888-593-3355 www.generalcable.com


SPEC 2600

February, 2008

GenFree

XLPO/LSZH, Instrumentation, Shielded 600V, UL Type TC-LS, Overall Shielded Pairs/Triads Product Construction Conductor:

• 18 AWG and 16 AWG tinned, annealed copper per ASTM B33 • Class B stranding per ASTM B8

Insulation:

CATALOG NUMBER

COPPER MINIMUM AVG. MINIMUM AVG. WEIGHT NET WEIGHT INSULATION JACKET NOMINAL NO. OF COND. THICKNESS CABLE O.D. LBS/ PAIRS/ SIZE COND. THICKNESS LBS/ TRIADS (AWG) STRAND inCHES mm INCHES mm INCHES mm 1000 FT kg/km 1000 FT kg/km

OVERALL SHIELDED PAIRS/TRIADS 18 AWG CONDUCTORS 393710* 393720* 393730* 393740* 393750* 393760* 393770* 393780* 393790* 393800* 393810*

1 1 TRI 2 4 8 12 16 20 24 36 50

18 18 18 18 18 18 18 18 18 18 18

7/.0152 7/.0152 7/.0152 7/.0152 7/.0152 7/.0152 7/.0152 7/.0152 7/.0152 7/.0152 7/.0152

0.030 0.030 0.030 0.030 0.030 0.030 0.030 0.030 0.030 0.030 0.030

0.76 0.76 0.76 0.76 0.76 0.76 0.76 0.76 0.76 0.76 0.76

0.045 0.045 0.045 0.045 0.060 0.080 0.080 0.080 0.080 0.080 0.080

1.14 1.14 1.14 1.14 1.52 2.03 2.03 2.03 2.03 2.03 2.03

0.315 0.340 0.450 0.560 0.750 0.850 1.010 1.085 1.210 1.500 2.570

8.00 8.64 11.43 14.22 19.05 21.59 25.65 27.56 30.73 38.10 65.28

1 1 TRI 2 4 8 12 16 20 24 36 50

16 16 16 16 16 16 16 16 16 16 16

7/.0192 7/.0192 7/.0192 7/.0192 7/.0192 7/.0192 7/.0192 7/.0192 7/.0192 7/.0192 7/.0192

0.030 0.030 0.030 0.030 0.030 0.030 0.030 0.030 0.030 0.030 0.030

0.76 0.76 0.76 0.76 0.76 0.76 0.76 0.76 0.76 0.76 0.76

0.045 0.045 0.045 0.060 0.060 0.080 0.080 0.080 0.080 0.080 0.110

1.14 1.14 1.14 1.52 1.52 2.03 2.03 2.03 2.03 2.03 2.79

0.345 0.360 0.560 0.650 0.810 1.000 1.120 1.170 1.440 1.650 2.020

8.76 9.14 14.22 16.51 20.57 25.40 28.45 29.72 36.58 41.91 51.31

Shield:

Overall shielded pairs/triads • Overall shield is Flexfoil® aluminum/polyester in contact with stranded tinned copper drain wire

Jacket: 13 18 23 44 86 127 169 210 252 377 523

19 26 34 65 127 189 251 313 375 561 778

46 58 88 144 263 358 461 600 701 1005 1603

68 86 131 214 391 533 686 893 1043 1496 2386

18 28 26 39 36 54 69 103 135 201 202 300 268 399 335 498 401 597 601 894 834 1241

32 72 121 186 324 486 616 734 894 1254 1800

48 107 180 277 482 723 917 1092 1330 1866 2679

OVERALL SHIELDED PAIRS/TRIADS 16 AWG CONDUCTORS 393820 393830 393840* 393850* 393860* 393870* 393880* 393890* 393900* 393910* 393920*

• Flame-retardant, Low-Smoke, Cross-Linked Polyolefin (XLPO) • Color-coded: per ICEA Method 1; Pairs - black and white. Triads - black, white and red. One conductor in each pair or triad is printed alphanumerically for easy identification

Dimensions and weights are nominal; subject to industry tolerances. *Non-stock item, minimum runs apply. Please consult Customer Service for price and delivery.

• Flame-retardant, Sunlight-resistant, Low-Smoke, Zero-Halogen Polyolefin (LSZH)

Print:

• GENERAL CABLE® (WC) GENFREE™ XX/PS/ TS XXAWG XLPO/LSZH SHIELDED UL TYPE TC-LS 90˚C WET OR DRY 600V DIR BUR SUN RES ROHS DAY/MONTH/YEAR OF MFG SEQUENTIAL FOOTAGE MARK

Options:

• Class C stranding • Individual and overall shielded pairs/triads • Other constructions available upon request

Applications:

• In free air, raceways, aerial or direct burial • In wet or dry locations • Permitted for use in Class I Division 2 industrial hazardous locations per NEC

Features:

• Rated at 90˚C wet or dry • Ripcord applied to all cables with jacket thickness of 60 mils or less • Excellent physical and electrical properties • Excellent moisture resistance • Excellent resistance to compression and impact • Chemical-resistant • Low coefficient of friction for easy pulling • Sunlight- and weather-resistant • Meets cold bend test at -30˚C • Low-Smoke, Zero-Halogen jacket is environmentally safe • Low-Smoke, Zero-Halogen jacket reduces the amount of toxic and corrosive gases emitted during combustion, providing a safer environment for personnel and equipment during the hazards of fire

Compliances:

Industry Compliances: • UL 1277 Type TC-LS • UL 1581 • ROHS Compliant Flame Tests Compliances: • UL 1581 • UL 1277 • UL 1685 • IEEE 1202 Other Compliances: • EPA 40 CFR, Part 261 for leachable lead content per TCLP • OSHA acceptable

Packaging:

• Material cut to length and shipped on non-returnable wood reels

Phone: 888-593-3355 www.generalcable.com


SPEC 2625

February, 2008

GenFree

XLPO/LSZH, Instrumentation, Shielded 600V, UL Type TC-LS, Individual and Overall Shielded Pairs Product Construction Conductor:

• 18 AWG and 16 AWG tinned, annealed copper per ASTM B33 • Class B stranding per ASTM B8

Insulation:

CATALOG NUMBER

COPPER MINIMUM AVG. MINIMUM AVG. WEIGHT NET WEIGHT INSULATION JACKET NOMINAL COND. THICKNESS CABLE O.D. LBS/ NO. OF SIZE COND. THICKNESS LBS/ PAIRS (AWG) STRAND inCHES mm INCHES mm INCHES mm 1000 FT kg/km 1000 FT kg/km

INDIVIDUAL AND OVERALL SHIELDED PAIRS 18 AWG CONDUCTORS 393930 393940 393950* 393960* 393970* 393980* 393990* 394000* 394010*

2 4 8 12 16 20 24 36 50

18 18 18 18 18 18 18 18 18

7/.0152 7/.0152 7/.0152 7/.0152 7/.0152 7/.0152 7/.0152 7/.0152 7/.0152

0.030 0.030 0.030 0.030 0.030 0.030 0.030 0.030 0.030

0.76 0.76 0.76 0.76 0.76 0.76 0.76 0.76 0.76

0.045 0.060 0.080 0.080 0.080 0.080 0.080 0.010 0.010

1.14 1.52 2.03 2.03 2.03 2.03 2.03 2.79 2.79

0.510 0.630 0.855 1.030 1.140 1.265 1.450 1.650 2.085

12.95 16.00 21.72 26.16 28.96 32.13 36.83 41.91 52.96

27 53 103 153 206 254 311 461 640

41 92 137 78 167 249 153 326 485 228 441 656 307 554 824 378 676 1006 463 795 1183 687 1118 1664 952 1616 2405

INDIVIDUAL AND OVERALL SHIELDED PAIRS 16 AWG CONDUCTORS 394020 394030 394040 394050 394060 394070* 394080* 394090* 394100* 394110*

2 4 6 8 12 16 20 24 36 50

16 16 16 16 16 16 16 16 16 16

7/.0192 7/.0192 7/.0192 7/.0192 7/.0192 7/.0192 7/.0192 7/.0192 7/.0192 7/.0192

0.030 0.030 0.030 0.030 0.030 0.030 0.030 0.030 0.030 0.030

0.76 0.76 0.76 0.76 0.76 0.76 0.76 0.76 0.76 0.76

0.060 0.060 0.060 0.080 0.080 0.080 0.080 0.080 0.110 0.110

1.52 1.52 1.52 2.03 2.03 2.03 2.03 2.03 2.79 2.79

0.585 0.675 0.800 0.915 1.110 1.350 1.365 1.570 1.980 2.165

14.86 17.15 20.32 23.24 28.19 34.29 34.67 39.88 50.29 54.99

40 59 130 77 114 204 115 171 301 151 225 394 226 337 548 305 453 713 380 566 850 455 677 1001 683 1016 1548 946 1408 2020

Dimensions and weights are nominal; subject to industry tolerances. *Non-stock item, minimum runs apply. Please consult Customer Service for price and delivery.

• Flame-retardant, Low-Smoke, Cross-Linked Polyolefin (XLPO) • Color-coded: per ICEA Method 1; Pairs - black and white. One conductor in each pair is printed alpha-numerically for easy identification

Shield:

Individual and overall shielded pairs • Individual pairs are 100% individually shielded with Flexfoil® aluminum/polyester in contact with stranded tinned copper drain wire • Overall shield is Flexfoil® aluminum/polyester in contact with stranded tinned copper drain wire

Jacket:

• Flame-retardant, Sunlight-resistant, Low-Smoke, Zero-Halogen Polyolefin (LSZH)

Print:

• GENERAL CABLE® (WC) GENFREE™ XX/SPS XXAWG XLPO/LSZH SHIELDED UL TYPE TC-LS 90˚C WET OR DRY 600V DIR BUR SUN RES ROHS DAY/MONTH/YEAR OF MFG SEQUENTIAL FOOTAGE MARK

Options:

• Class C stranding • Overall shielded pairs • Other constructions available upon request

Applications: 193 304 447 586 816 1061 1265 1490 2304 3006

• In free air, raceways, aerial or direct burial • In wet or dry locations • Permitted for use in Class I Division 2 industrial hazardous locations per NEC

Features:

• Rated at 90˚C wet or dry • Ripcord applied to all cables with jacket thickness of 60 mils or less • Excellent physical and electrical properties • Excellent moisture resistance • Excellent resistance to compression and impact • Chemical-resistant • Low coefficient of friction for easy pulling • Sunlight- and weather-resistant • Meets cold bend test at -30˚C • Low-Smoke, Zero-Halogen jacket is environmentally safe • Low-Smoke, Zero-Halogen jacket reduces the amount of toxic and corrosive gases emitted during combustion, providing a safer environment for personnel and equipment during the hazards of fire

Compliances:

Industry Compliances: • UL 1277 Type TC-LS • UL 1581 • ROHS Compliant Flame Tests Compliances: • UL 1581 • UL 1277 • UL 1685 • IEEE 1202 Other Compliances: • EPA 40 CFR, Part 261 for leachable lead content per TCLP • OSHA acceptable

Packaging:

• Material cut to length and shipped on non-returnable wood reels

Phone: 888-593-3355 www.generalcable.com


SPEC 2650

February, 2008

GenFree

XLPO/LSZH, Instrumentation, Shielded 600V, UL Type TC-LS, Individual and Overall Shielded Triads Product Construction Conductor:

• 18 AWG and 16 AWG tinned, annealed copper per ASTM B33 • Class B stranding per ASTM B8

Insulation:

CATALOG NUMBER

COPPER MINIMUM AVG. MINIMUM AVG. WEIGHT NET WEIGHT INSULATION JACKET NOMINAL COND. THICKNESS CABLE O.D. LBS/ NO. OF SIZE COND. THICKNESS LBS/ TRIADS (AWG) STRAND inCHES mm INCHES mm INCHES mm 1000 FT kg/km 1000 FT kg/km

INDIVIDUAL AND OVERALL SHIELDED TRIADS 18 AWG CONDUCTORS 394120* 394130* 394140* 394150* 394160* 394170* 394180* 394190*

2 TRI 4 TRI 8 TRI 12 TRI 16 TRI 20 TRI 24 TRI 36 TRI

18 18 18 18 18 18 18 18

7/.0152 7/.0152 7/.0152 7/.0152 7/.0152 7/.0152 7/.0152 7/.0152

0.030 0.030 0.030 0.030 0.030 0.030 0.030 0.030

0.76 0.76 0.76 0.76 0.76 0.76 0.76 0.76

0.060 0.060 0.080 0.080 0.080 0.080 0.080 0.110

1.52 1.52 2.03 2.03 2.03 2.03 2.03 2.79

0.595 0.690 0.940 1.135 1.265 1.405 1.565 1.860

15.11 17.53 23.88 28.83 32.13 35.69 39.75 47.24

38 74 145 217 289 361 432 647

57 150 223 110 231 344 216 435 647 323 612 911 430 773 1150 537 935 1391 643 1097 1633 963 1662 2473

INDIVIDUAL AND OVERALL SHIELDED TRIADS 16 AWG CONDUCTORS 394200* 394210* 394220* 394230* 394240* 394250* 394260* 394270*

2 TRI 4 TRI 8 TRI 12 TRI 16 TRI 20 TRI 24 TRI 36 TRI

16 16 16 16 16 16 16 16

7/.0192 7/.0192 7/.0192 7/.0192 7/.0192 7/.0192 7/.0192 7/.0192

0.030 0.030 0.030 0.030 0.030 0.030 0.030 0.030

0.76 0.76 0.76 0.76 0.76 0.76 0.76 0.76

0.060 0.060 0.080 0.080 0.080 0.080 0.110 0.110

1.52 1.52 2.03 2.03 2.03 2.03 2.79 2.79

0.640 0.745 1.015 1.230 1.370 1.525 1.760 2.015

16.26 18.92 25.78 31.24 34.80 38.74 44.70 51.18

57 84 183 272 111 165 494 735 219 326 549 817 328 487 777 1156 437 650 988 1470 545 811 1120 1667 654 973 1530 2277 979 1457 2142 3188

Dimensions and weights are nominal; subject to industry tolerances. *Non-stock item, minimum runs apply. Please consult Customer Service for price and delivery.

• Flame-retardant, Low-Smoke, Cross-Linked Polyolefin (XLPO) • Color-coded: per ICEA Method 1; Triads - black, white and red. One conductor in each triad is printed alpha-numerically for easy identification

Shield:

Individual and overall shielded triads • Individual triads are 100% shielded with Flexfoil® aluminum/polyester in contact with stranded tinned copper drain wire • Overall shield is Flexfoil® aluminum/polyester in contact with stranded tinned copper drain wire

Jacket:

• Flame-retardant, Sunlight-resistant, Low-Smoke, Zero-Halogen Polyolefin (LSZH)

Print:

• GENERAL CABLE® (WC) GENFREE™ XX/STS XXAWG XLPO/LSZH SHIELDED UL TYPE TC-LS 90˚C WET OR DRY 600V DIR BUR SUN RES ROHS DAY/MONTH/YEAR OF MFG SEQUENTIAL FOOTAGE MARK

Options:

• Class C stranding • Overall shielded pairs/triads • Other constructions available upon request

Applications:

• In free air, raceways, aerial or direct burial • In wet or dry locations • Permitted for use in Class I Division 2 industrial hazardous locations per NEC

Features:

• Rated at 90˚C wet or dry • Ripcord applied to all cables with jacket thickness of 60 mils or less • Excellent physical and electrical properties • Excellent moisture resistance • Excellent resistance to compression and impact • Chemical-resistant • Low coefficient of friction for easy pulling • Sunlight- and weather-resistant • Meets cold bend test at -30˚C • Low-Smoke, Zero-Halogen jacket is environmentally safe • Low-Smoke, Zero-Halogen jacket reduces the amount of toxic and corrosive gases emitted during combustion, providing a safer environment for personnel and equipment during the hazards of fire

Compliances:

Industry Compliances: • UL 1277 Type TC-LS • UL 1581 • ROHS Compliant Flame Tests Compliances: • UL 1581 • UL 1277 • UL 1685 • IEEE 1202 Other Compliances: • EPA 40 CFR, Part 261 for leachable lead content per TCLP • OSHA acceptable

Packaging:

• Material cut to length and shipped on non-returnable wood reels

Phone: 888-593-3355 www.generalcable.com


Industrial Cables

Date of Issue 01/08 Section 3

600V Flexible Control and Power Cables SPECIFICATION NO.

3050

Super Flexing

3100

PRODUCT DESCRIPTION

REVISION DATE

XLPE/NYLON/HYP, Thermoset Super Flexing Control 600V, UL Type TC/CSA CIC

Jan. 2008

PNH速

PVC/NYLON/HYP, Thermoset Continuous Flexing Control 600V, UL Type TC/CSA AWM

Jan. 2008

3150

NVN速

PVC/NYLON/NEOPRENE, Thermoset Flexible Control 600V, UL Type TC

Jan. 2008

3200

PNP

PVC/NYLON/NITRILE/PVC, Thermoset Continuous Flexing Control 600V, UL Type TC/CSA AWM

Jan. 2008

3250

MTW

PVC/NYLON/PVC, Thermoplastic Flexible Control 600V, UL Type MTW/CSA AWM

Jan. 2008

3300

Festoon

PVC/PVC, Thermoplastic Extreme Flexing Festoon Control and Power 600V, UL/CSA Type Festoon

Jan. 2008

Phone: 888-593-3355 www.generalcable.com


SPEC 3050

January, 2008

Super Flexing

XLPE/NYLON/HYP, Thermoset Super Flexing Control 600V, UL Type TC/CSA CIC Product Construction Conductor:

• 18 AWG thru 10 AWG fully annealed stranded bare copper per ASTM B3 • Class M-18 AWG thru 16 AWG • Class K-14 AWG thru 10 AWG • Stranding per ASTM B8

Insulation: COPPER WEIGHT

MINIMUM AVG. MINIMUM AVG. MINIMUM NET WEIGHT INSULATION JACKET NOMINAL BEND COND. THICKNESS CABLE O.D. LBS/ RADIUS CATALOG NO. OF SIZE COND. THICKNESS LBS/ NUMBER COND. (AWG) STRAND INCHES mm INCHES mm INCHES mm 1000FT kg/km 1000FT kg/km INCHES mm

18 AWG CONDUCTORS 338950* 338960* 338970* 338980* 338990* 339000* 339010* 339020*

6 8 12 16 22 31 41 60

18 18 18 18 18 18 18 18

41/34 41/34 41/34 41/34 41/34 41/34 41/34 41/34

0.020 0.020 0.020 0.020 0.020 0.020 0.020 0.020

339030* 339040* 270230* 219390* 218990* 524310* 218970* 710580*

6 8 12 16 22 31 41 60

16 16 16 16 16 16 16 16

65/34 65/34 65/34 65/34 65/34 65/34 65/34 65/34

0.020 0.020 0.020 0.020 0.020 0.020 0.020 0.020

339050* 339060* 339070* 339080* 339090*

6 8 12 16 22

14 14 14 14 14

41/30 41/30 41/30 41/30 41/30

0.020 0.020 0.020 0.020 0.020

264980* 339100* 226130* 339110* 339120*

6 8 12 16 22

12 12 12 12 12

65/30 65/30 65/30 65/30 65/30

0.020 0.020 0.020 0.020 0.020

339130* 339140* 339150* 339160*

6 8 12 16

10 10 10 10

105/30 105/30 105/30 105/30

0.026 0.026 0.026 0.026

0.51 0.51 0.51 0.51 0.51 0.51 0.51 0.51

0.045 0.045 0.045 0.060 0.060 0.060 0.080 0.080

1.14 1.14 1.14 1.52 1.52 1.52 2.03 2.03

0.390 0.455 0.490 0.570 0.650 0.750 0.880 1.000

9.91 11.30 12.45 14.48 16.51 19.05 22.35 25.40

32 42 63 84 116 163 216 316

48 63 94 125 173 243 321 470

93 138 116 173 155 231 211 314 272 405 366 545 498 741 676 1006

3.0 3.5 4.0 4.5 5.0 6.0 7.0 8.0

76.2 88.9 101.6 114.3 127.0 152.4 177.8 203.2

50 66 99 132 182 256 339 496

74 98 147 196 271 381 504 738

122 182 3.5 152 226 4.0 216 321 4.5 277 412 5.0 368 548 5.5 491 731 6.5 683 1016 8.0 912 1357 9.0

88.9 101.6 114.3 127.0 139.7 165.1 203.2 228.6

80 107 160 213 293

119 159 238 317 737

159 219 295 375 495

237 326 439 558 737

3.5 4.5 5.0 5.5 6.0

88.9 114.3 127.0 139.7 152.4

129 172 258 344 473

192 256 384 512 704

238 300 433 535 789

354 446 644 796 1174

4.5 5.0 5.5 6.0 7.5

114.3 127.0 139.7 152.4 190.5

205 274 411 548

305 408 612 816

350 521 5.0 450 670 6.0 675 1005 7.0 905 1347 9.0

127.0 152.4 177.8 228.6

16 AWG CONDUCTORS 0.51 0.51 0.51 0.51 0.51 0.51 0.51 0.51

0.045 0.045 0.060 0.060 0.060 0.060 0.080 0.080

1.14 1.14 1.52 1.52 1.52 1.52 2.03 2.03

0.430 0.490 0.575 0.630 0.725 0.835 0.985 1.115

10.92 12.45 14.61 16.00 18.42 21.21 25.02 28.32

14 AWG CONDUCTORS 0.51 0.51 0.51 0.51 0.51

0.045 0.060 0.060 0.060 0.060

1.14 1.52 1.52 1.52 1.52

0.460 0.560 0.620 0.680 0.785

11.68 14.22 15.72 17.27 19.94

12 AWG CONDUCTORS 0.51 0.51 0.51 0.51 0.51

0.060 0.060 0.060 0.060 0.080

1.52 1.52 1.52 1.52 2.03

0.555 0.635 0.705 0.780 0.945

14.10 16.13 17.91 19.81 24.00

• Thermoset Cross-Linked Polyethylene (XLPE) with clear Polyamide (nylon) • Color-coded: all conductors red, except #2 is white and #3 is green, all with alpha-numeric designations

Jacket:

• Lead-Free Hypalon® Chlorosulfonated Polyethylene (CSPE)/Elastomer blend

Print:

• GENERAL CABLE® BRAND REX BRAND (WC) SUPER FLEXING (UL) Type TC 600V 90˚C DRY 75˚C WET XXAWG XX COND/CSA CIC 90˚C 600V XLPE -25˚C FT4

Applications:

• Any continuous flexing application requiring a small diameter flexible cable • Robots • Machine tools • Car body and vehicle assembly • Material handling equipment • Power tracks

Features:

• Rated at 90˚C, 75˚C wet • Extremely flexible with long flex life • Small diameter • Thermoset rubber insulation and jacket • Oil-resistant • Suitable for indoor and outdoor applications • Meets cold bend test at -30˚C • Meets cold impact test at -25˚C

Compliances:

Industry Compliances: • UL Type TC / CSA CIC Flame Tests Compliances: • IEEE 1202 (70,000 BTU/hr) CSA FT4 • IEEE 383 (70,000 BTU/hr) Other Compliances: • Meets EPA 40 CFR, part 261 for leachable lead content per TCLP method • OSHA acceptable

Packaging:

• Material cut to length and shipped on non-returnable wood reels

10 AWG CONDUCTORS 0.66 0.66 0.66 0.66

0.060 0.060 0.080 0.080

1.52 1.52 2.03 2.03

0.655 0.755 0.885 1.145

16.64 19.18 22.48 29.08

Dimensions and weights are nominal; subject to industry tolerances. *Non-stock item, minimum runs apply. Please consult Customer Service for price and delivery.

Phone: 888-593-3355 www.generalcable.com


SPEC 3100

January, 2008

PNH

®

PVC/NYLON/HYP, Thermoset Continuous Flexing Control 600V, UL Type TC/CSA AWM Product Construction Conductor:

• 18 AWG thru 12 AWG fully annealed stranded bare copper per ASTM B3 • Class M-18 AWG thru 16 AWG • Class K-14 AWG thru 12 AWG • Stranding per ASTM B8

Insulation: COPPER WEIGHT

MINIMUM AVG. MINIMUM AVG. MINIMUM NET WEIGHT INSULATION JACKET NOMINAL BEND COND. THICKNESS CABLE O.D. LBS/ RADIUS CATALOG NO. OF SIZE COND. THICKNESS LBS/ NUMBER COND. (AWG) STRAND INCHES mm INCHES mm INCHES mm 1000FT kg/km 1000FT kg/km INCHES mm

18 AWG CONDUCTORS 338470* 338480* 338490* 338500* 338510*

6 8 12 16 22

18 18 18 18 18

41/34 41/34 41/34 41/34 41/34

0.020 0.020 0.020 0.020 0.020

0.51 0.51 0.51 0.51 0.51

0.045 0.045 0.045 0.060 0.060

1.14 1.14 1.14 1.52 1.52

0.390 0.455 0.490 0.570 0.650

9.91 32 11.30 42 12.45 63 14.48 84 16.51 112

48 63 94 125 167

93 116 155 211 272

138 173 231 314 405

3.0 3.5 4.0 4.5 5.0

76.2 88.9 101.6 114.3 127.0

74 98 147 196 271

122 152 216 277 368

182 226 321 412 548

3.5 3.9 4.5 5.0 5.5

88.9 99.1 114.3 127.0 139.7

80 107 160 213 293

119 159 238 317 436

159 219 295 375 495

186 326 439 558 436

3.7 4.5 5.0 5.5 6.0

94.0 114.3 127.0 139.7 152.4

129 172 258 344 473

192 256 384 512 704

238 300 433 535 789

354 446 644 796 1174

4.5 5.0 5.5 6.0 7.5

114.3 127.0 139.7 152.4 190.5

16 AWG CONDUCTORS 338520* 338530* 338540* 338550* 338560*

6 8 12 16 22

16 16 16 16 16

65/34 65/34 65/34 65/34 65/34

0.020 0.020 0.020 0.020 0.020

0.51 0.51 0.51 0.51 0.51

0.045 0.045 0.060 0.060 0.060

1.14 1.14 1.52 1.52 1.52

0.430 0.490 0.575 0.630 0.725

10.92 50 12.45 66 14.61 99 16.00 132 18.42 182

14 AWG CONDUCTORS 338570* 338580* 338590* 338600* 338610*

6 8 12 16 22

14 14 14 14 14

41/30 41/30 41/30 41/30 41/30

0.020 0.020 0.020 0.020 0.020

0.51 0.51 0.51 0.51 0.51

0.045 0.060 0.060 0.060 0.060

1.14 1.52 1.52 1.52 1.52

0.460 0.560 0.670 0.680 0.785

11.68 14.22 17.02 17.27 19.94

12 AWG CONDUCTORS 338620* 338630* 338640* 338650* 338660*

6 8 12 16 22

12 12 12 12 12

65/30 65/30 65/30 65/30 65/30

0.020 0.020 0.020 0.020 0.020

0.51 0.51 0.51 0.51 0.51

0.060 0.060 0.060 0.060 0.080

1.52 1.52 1.52 1.52 2.03

0.555 0.635 0.705 0.780 0.945

14.10 16.13 17.91 19.81 24.00

Dimensions and weights are nominal; subject to industry tolerances. *Non-stock item, minimum runs apply. Please consult Customer Service for price and delivery.

• Flame-retardant Polyvinyl Chloride (PVC) with clear Polyamide (nylon) • Color-coded: all conductors are red, except #2 is white and #3 is green. All with alpha-numeric designations

Jacket:

• Lead-Free Hypalon® Chlorosulfonated Polyethylene (CSPE)/Elastomer blend

Print:

• GENERAL CABLE® BRAND REX BRAND (WC) PNH Flex 90˚C 600V Type TC XX/C XXAWG(TFFN) or (THHW/THWN) (UL)/CSA AWM IIA 90˚C 600V FT1

Applications:

• Any continuous flexing application requiring a small diameter flexible cable • Robots • Machine tools • Car body and vehicle assembly • Material handling equipment • Power tracks

Features:

• Rated at 90˚C • Extremely flexible with long flex life • Small diameter • Thermoset rubber jacket • Oil-resistant • Suitable for indoor or outdoor applications • Meets cold bend test at -40˚C

Compliances:

Industry Compliances: • UL Type TC / CSA AWM Flame Tests Compliances: • IEEE 1202 (70,000 BTU/hr) CSA FT4 • IEEE 383 (70,000 BTU/hr) Other Compliances: • Meets EPA 40 CFR, part 261 for leachable lead content per TCLP method • OSHA acceptable

Packaging:

• Material cut to length and shipped on non-returnable wood reels

Phone: 888-593-3355 www.generalcable.com


SPEC 3150

January, 2008

NVN

®

PVC/NYLON/NEOPRENE, Thermoset Flexible Control 600V, UL Type TC Product Construction Conductor:

• 18 AWG thru 12 AWG fully annealed stranded bare copper per ASTM B3 • Class C stranding per ASTM B8

Insulation:

COPPER MINIMUM AVG. MINIMUM AVG. MINIMUM WEIGHT NET WEIGHT INSULATION JACKET NOMINAL BEND COND. THICKNESS THICKNESS CABLE O.D. LBS/ RADIS CATALOG NO. OF SIZE COND. LBS/ NUMBER COND. (AWG) STRAND INCHES mm INCHES mm INCHES mm 1000FT kg/km 1000FT kg/km INCHES mm

18 AWG CONDUCTORS 554420* 624740* 624750* 624760* 624010* 624780* 624790* 686890*

4 8 10 12 16 19 24 30

18 18 18 18 18 18 18 18

19/.0092 19/.0092 19/.0092 19/.0092 19/.0092 19/.0092 19/.0092 19/.0092

0.020 0.020 0.020 0.020 0.020 0.020 0.020 0.020

0.51 0.51 0.51 0.51 0.51 0.51 0.51 0.51

0.045 0.045 0.045 0.045 0.045 0.060 0.060 0.060

1.14 1.14 1.14 1.14 1.14 1.52 1.52 1.52

0.310 0.420 0.450 0.465 0.515 0.570 0.660 0.695

7.87 21 10.67 42 11.43 53 11.81 63 13.08 85 14.48 100 16.76 127 17.65 158

31 63 79 94 126 149 189 235

65 116 135 137 175 192 297 345

97 173 201 204 260 286 442 513

2.5 3.3 3.6 3.7 4.1 4.6 5.3 5.6

63.5 83.8 91.5 94.0 104.1 116.8 134.6 142.2

33 66 83 100 133 158 199 249

49 98 124 149 198 235 296 371

85 153 179 186 257 320 403 476

126 228 266 277 382 476 600 708

2.8 3.7 4.0 4.2 4.8 5.1 5.9 6.2

71.1 94.0 101.6 106.7 121.9 129.5 149.9 157.5

53 105 132 158 210 250 316 394

79 156 196 235 313 372 470 586

117 174 181 269 270 402 278 414 353 525 449 668 565 841 727 1082

3.0 3.9 4.8 4.9 5.4 5.7 6.6 7.4

76.2 99.1 121.9 124.5 137.2 144.8 167.6 188.0

84 167 209 250 334 397 501 626

125 157 234 3.4 249 272 405 4.6 311 369 549 5.4 372 389 579 5.5 497 503 749 6.1 591 638 949 6.5 746 841 1252 7.8 932 1017 1513 8.3

86.4 116.9 137.2 139.7 155.0 165.1 198.1 210.8

16 AWG CONDUCTORS 625160* 625200* 625220* 625230* 625250* 625270* 625280* 625290*

4 8 10 12 16 19 24 30

16 16 16 16 16 16 16 16

19/.0117 19/.0117 19/.0117 19/.0117 19/.0117 19/.0117 19/.0117 19/.0117

0.020 0.020 0.020 0.020 0.020 0.020 0.020 0.020

624950* 624980* 624990* 625000* 625020* 625030* 625040* 625050*

4 8 10 12 16 19 24 30

14 14 14 14 14 14 14 14

19/.0147 19/.0147 19/.0147 19/.0147 19/.0147 19/.0147 19/.0147 19/.0147

0.020 0.020 0.020 0.020 0.020 0.020 0.020 0.020

324820* 624850* 624860* 624870* 624890* 624900* 624910* 624920*

4 8 10 12 16 19 24 30

12 12 12 12 12 12 12 12

19/.0185 19/.0185 19/.0185 19/.0185 19/.0185 19/.0185 19/.0185 19/.0185

0.020 0.020 0.020 0.020 0.020 0.020 0.020 0.020

0.51 0.51 0.51 0.51 0.51 0.51 0.51 0.51

0.045 0.045 0.045 0.045 0.045 0.060 0.060 0.060

1.14 1.14 1.14 1.14 1.14 1.52 1.52 1.52

0.345 0.465 0.500 0.520 0.605 0.635 0.735 0.775

8.76 11.81 12.70 13.21 15.37 16.13 18.67 19.69

14 AWG CONDUCTORS 0.51 0.51 0.51 0.51 0.51 0.51 0.51 0.51

0.045 0.045 0.060 0.060 0.060 0.060 0.060 0.080

1.14 1.14 1.52 1.52 1.52 1.52 1.52 2.03

0.375 0.485 0.595 0.615 0.675 0.710 0.825 0.920

9.53 12.32 15.11 15.62 17.15 18.03 20.96 23.37

• Flame-retardant Polyvinyl Chloride (PVC) with clear Polyamide (nylon) • Color-coded: per ICEA method 1: Table E-2 (Does not include white or green)

Jacket:

• Thermosetting Neoprene

Print:

• GENERAL CABLE® BRAND REX BRAND (WC) NVN 90˚C FLEXIBLE CONTROL CABLE 600V Type TC SUN RES XX/C XXAWG (TFFN) or (THHN/THWN) (UL)

Applications:

• Tight installations • Trays, conduits and raceways • Cranes and hoists • Pendant stations • Load lifts and platforms • Recommended for moderate flex applications

Features:

• Rated at 90˚C • Moderate flex cable • Small diameter • Thermosetting rubber jacket • Flame-retardant • Suitable for indoor and outdoor applications • Meets cold bend test at -40˚C

Compliances:

Industry Compliances: • UL Type TC - 600V Flame Tests Compliances: • IEEE 1202 (70,000 BTU/hr) • IEEE 383 (70,000 BTU/hr) Other Compliances: • Meets EPA 40 CFR, part 261 for leachable lead content per TCLP method • OSHA acceptable

Packaging:

• Material cut to length and shipped on non-returnable wood reels

12 AWG CONDUCTORS 0.51 0.51 0.51 0.51 0.51 0.51 0.51 0.51

0.045 0.060 0.060 0.060 0.060 0.060 0.080 0.080

1.14 1.52 1.52 1.52 1.52 1.52 2.03 2.03

0.420 0.575 0.670 0.690 0.765 0.805 0.980 1.040

10.67 14.61 17.02 17.53 19.43 20.45 24.89 26.42

Dimensions and weights are nominal; subject to industry tolerances. *Non-stock item, minimum runs apply. Please consult Customer Service for price and delivery.

Phone: 888-593-3355 www.generalcable.com


SPEC 3200

January, 2008

PNP

PVC/NYLON/NITRILE/PVC, Thermoset Continuous Flexing Control 600V, UL Type TC/CSA AWM Product Construction Conductor:

• 16 AWG fully annealed stranded bare copper per ASTM B3 • Class M stranding per ASTM B8

Insulation:

COPPER MINIMUM AVG. MINIMUM AVG. MINIMUM WEIGHT NET WEIGHT INSULATION JACKET NOMINAL BEND COND. THICKNESS THICKNESS CABLE O.D. LBS/ RADIUS CATALOG NO. OF SIZE COND. LBS/ NUMBER COND. (AWG) STRAND INCHES mm INCHES mm INCHES mm 1000FT kg/km 1000FT kg/km INCHES mm

16 AWG CONDUCTORS 338460* 293950* 338440* 307650* 293960* 311880* 306420* 288010* 338450* 293970* 288020* 307660* 292150* 307370* 293980* 292160*

11 12 16 17 19 21 22 25 31 33 41 42 47 49 60 65

16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16

65/34 65/34 65/34 65/34 65/34 65/34 65/34 65/34 65/34 65/34 65/34 65/34 65/34 65/34 65/34 65/34

0.020 0.020 0.020 0.020 0.020 0.020 0.020 0.020 0.020 0.020 0.020 0.020 0.020 0.020 0.020 0.020

0.51 0.51 0.51 0.51 0.51 0.51 0.51 0.51 0.51 0.51 0.51 0.51 0.51 0.51 0.51 0.51

0.060 0.060 0.060 0.060 0.060 0.060 0.060 0.060 0.080 0.080 0.080 0.080 0.080 0.080 0.080 0.080

1.52 1.52 1.52 1.52 1.52 1.52 1.52 1.52 2.03 2.03 2.03 2.03 2.03 2.03 2.03 2.03

0.580 0.580 0.635 0.670 0.705 0.770 0.770 0.815 0.890 0.890 0.975 0.975 1.025 1.055 1.125 1.180

14.73 14.73 16.13 17.02 17.91 19.56 19.56 22.70 22.61 22.61 24.77 24.77 26.04 26.80 28.58 29.97

91 99 132 140 157 174 182 207 256 273 339 347 388 405 496 537

135 147 196 208 233 258 270 308 380 406 504 516 577 602 738 799

Dimensions and weights are nominal; subject to industry tolerances. *Non-stock item, minimum runs apply. Please consult Customer Service for price and delivery.

190 195 251 275 304 339 346 401 483 506 622 629 684 724 851 927

283 290 374 409 452 504 515 597 719 753 922 932 1018 1077 1266 1380

4.50 4.50 5.00 5.25 5.50 6.00 6.00 6.50 7.00 7.00 7.75 7.75 8.25 8.50 9.00 9.50

114.3 114.3 127.0 133.4 139.7 152.4 152.4 165.1 177.8 177.8 196.8 196.8 209.6 215.9 228.6 241.3

• Flame-retardant Polyvinyl Chloride (PVC) with clear Polyamide (nylon) • Color-coded: all conductors red, except #2 is white, the last conductor in each construction is green/yellow. All with alpha-numeric designations

Jacket:

• Thermosetting Nitrile/Polyvinyl Chloride (PVC)

Print:

• GENERAL CABLE® BRAND REX BRAND (WC) T-15071 (XX/16) PNP 16 AWG XX COND (UL) Type TC 600V 90˚C (TFFN 16 AWG XX COND) CSA AWM IIA 90˚C 600V FT1

Applications:

• Any continuous flexing application requiring a small diameter flexible cable • Robots • Machine tools • Car body and vehicle assembly • Plant automation equipment • Flexible cable tracks

Features:

• Rated at 90˚C dry, 75˚C wet • Flame-retardant • Small diameter • Oil-resistant • Thermoset rubber jacket • Meets cold bend test at -25˚C

Compliances:

Industry Compliances: • UL Type TC/CSA AWM Flame Tests Compliances: • IEEE 1202 (70,000 BTU/hr) • IEEE 383 (70,000 BTU/hr) Other Compliances: • Meets EPA 40 CFR, part 261 for leachable lead content per TCLP method • OSHA acceptable

Packaging:

• Material cut to length and shipped on non-returnable wood reels

Phone: 888-593-3355 www.generalcable.com


SPEC 3250

January, 2008

MTW

PVC/NYLON/PVC, Thermoplastic Flexible Control 600V, UL Type MTW/CSA AWM Product Construction Conductor:

• 18 AWG thru 10 AWG fully annealed stranded bare copper per ASTM B3 • Class M-18 AWG thru 16 AWG • Class K-14 AWG thru 10 AWG • Stranding per ASTM B8

Insulation: COPPER WEIGHT

MINIMUM AVG. MINIMUM AVG. MINIMUM NET WEIGHT INSULATION JACKET NOMINAL BEND COND. THICKNESS CABLE O.D. LBS/ RADIUS CATALOG NO. OF SIZE COND. THICKNESS LBS/ NUMBER COND. (AWG) STRAND INCHES mm INCHES mm INCHES mm 1000FT kg/km 1000FT kg/km INCHES mm

18 AWG CONDUCTORS 339170* 339180* 339190* 339200* 339210* 339220* 339230* 339240*

6 8 12 16 22 31 41 60

18 18 18 18 18 18 18 18

41/34 41/34 41/34 41/34 41/34 41/34 41/34 41/34

0.020 0.020 0.020 0.020 0.020 0.020 0.020 0.020

339250* 339260* 339270* 339280* 339290* 339300* 339310* 339320*

6 8 12 16 22 31 41 60

16 16 16 16 16 16 16 16

65/34 65/34 65/34 65/34 65/34 65/34 65/34 65/34

0.020 0.020 0.020 0.020 0.020 0.020 0.020 0.020

339330* 339340* 339350* 339360* 339370*

6 8 12 16 22

14 14 14 14 14

41/30 41/30 41/30 41/30 41/30

0.020 0.020 0.020 0.020 0.020

339380* 339390* 339400* 339410* 339420*

6 8 12 16 22

12 12 12 12 12

65/30 65/30 65/30 65/30 65/30

0.020 0.020 0.020 0.020 0.020

339430* 339440* 339450* 339460*

6 8 12 16

10 10 10 10

105/30 105/30 105/30 105/30

0.026 0.026 0.026 0.026

0.51 0.51 0.51 0.51 0.51 0.51 0.51 0.51

0.045 0.045 0.045 0.060 0.060 0.060 0.080 0.080

1.14 1.14 1.14 1.52 1.52 1.52 2.03 2.03

0.400 0.455 0.500 0.580 0.660 0.760 0.890 1.010

10.16 11.56 12.70 14.73 16.76 19.30 22.61 25.65

32 42 63 84 116 163 216 316

48 63 94 125 173 243 321 470

88 108 144 196 252 325 460 617

131 161 214 292 375 484 685 918

3.0 3.5 4.0 4.5 5.0 6.0 7.0 8.0

76.2 88.9 101.6 114.3 127.0 152.4 177.8 203.2

50 66 99 132 182 256 339 496

74 98 147 196 271 381 504 738

113 168 141 210 214 318 263 391 377 561 518 771 652 970 909 1353

3.5 4.0 4.5 5.0 5.5 6.5 8.0 9.0

88.9 101.6 114.3 127.0 139.7 165.1 203.2 228.2

80 107 160 213 293

119 159 238 317 436

149 204 279 354 467

222 304 415 527 695

3.5 4.5 5.0 5.5 6.0

88.9 114.3 127.0 139.7 152.4

129 172 258 344 473

192 256 384 512 704

226 336 289 430 398 592 506 753 720 1072

4.5 5.0 5.5 6.0 7.5

114.3 127.0 139.7 152.4 190.0

205 274 411 548

305 408 612 816

329 490 5.0 127.0 424 631 6.0 152.4 604 899 7.0 177.8 852 1268 9.0 228.6

16 AWG CONDUCTORS 0.51 0.51 0.51 0.51 0.51 0.51 0.51 0.51

0.045 0.045 0.060 0.060 0.060 0.060 0.080 0.080

1.14 1.14 1.52 1.52 1.52 1.52 2.03 2.03

0.440 0.500 0.585 0.640 0.735 0.845 0.995 1.125

11.18 12.70 14.86 16.26 18.67 21.46 25.27 28.58

14 AWG CONDUCTORS 0.51 0.51 0.51 0.51 0.51

0.045 0.060 0.060 0.060 0.060

1.14 1.52 1.52 1.52 1.52

0.470 0.570 0.630 0.690 0.795

11.94 14.48 16.00 17.53 20.19

• Flame-retardant Polyvinyl Chloride (PVC) with clear Polyamide (nylon) • Color-coded: all conductors red, except #2 is white and #3 is green. All with alpha-numeric designations

Jacket:

• Heat-, moisture- and oil-resistant Polyvinyl Chloride (PVC)

Print:

• GENERAL CABLE® BRAND REX BRAND (WC) Type MTW FLEXING 600V (UL) NO OF COND/ AWG SIZE/CSA AWM IIA 90˚C 600V FT1

Applications:

• Pendant cable • Machine tool • Internal machine connections • Material handling equipment • Moderate flex

Features:

• Rated at 90˚C • Moisture- and oil-resistant • Heavy-duty PVC jacket • Meets cold bend test at -25˚C

Compliances:

Industry Compliances: • UL Type MTW/CSA AWM Other Compliances: • Meets EPA 40 CFR, part 261 for leachable lead content per TCLP method • OSHA acceptable • RoHS compliant

Packaging:

• Material cut to length and shipped on non-returnable wood reels

12 AWG CONDUCTORS 0.51 0.51 0.51 0.51 0.51

0.060 0.060 0.060 0.060 0.080

1.52 1.52 1.52 1.52 2.03

0.565 0.645 0.715 0.790 0.955

14.35 16.38 18.16 20.07 24.26

10 AWG CONDUCTORS 0.66 0.66 0.66 0.66

0.060 0.060 0.080 0.080

1.52 1.52 2.03 2.03

0.665 0.765 0.895 1.155

16.89 19.43 22.73 29.34

Dimensions and weights are nominal; subject to industry tolerances. *Non-stock item, minimum runs apply. Please consult Customer Service for price and delivery.

Phone: 888-593-3355 www.generalcable.com


SPEC 3300

January, 2008

Festoon

PVC/PVC, Thermoplastic Extreme Flexing Festoon Control and Power 600V, UL/CSA Type Festoon Product Construction Conductor:

• 16 AWG thru 2 AWG fully annealed stranded bare copper per ASTM B3 • Class M - 16 AWG • Class K - 14 AWG thru 2 AWG • Stranding per ASTM B8

Insulation: MINIMUM AVG. MINIMUM AVG. INSULATION JACKET COND. THICKNESS CATALOG NO. OF SIZE COND. THICKNESS NUMBER COND. (AWG) STRAND INCHES mm INCHES mm

NOMINAL CABLE O.D. INCHES mm

COPPER WEIGHT

NET WEIGHT

LBS/ LBS/ 1000FT kg/km 1000FT kg/km

Jacket:

5.1 x 14.73 5.1 x 14.73 5.1 x 28.20 5.1 x 28.20 5.1 x 40.77 5.1 x 40.77

31.92 31.92 63.84 63.84 95.76 95.76

47.05 47.05 95.00 95.00 142.50 142.50

91 91 173 173 253 253

135 135 257 257 377 377

Print:

5.33 x 18.54 5.33 x 18.54 5.33 x 29.85 5.33 x 29.85 5.33 x 43.18 5.33 x 43.18

51.52 51.52 103.04 103.04 154.56 154.56

76.67 76.67 153.33 153.33 230.00 230.00

116 116 224 224 330 330

173 173 333 333 491 491

5.84 x 18.54 5.84 x 18.54 5.84 x 21.97 5.84 x 21.97 5.84 x 34.04 5.84 x 34.04 5.84 x 41.91 5.84 x 41.91

83.04 83.04 103.80 103.80 145.32 145.32 166.08 166.08

123.57 123.57 154.47 154.47 216.25 216.25 247.14 247.14

160 160 195 195 271 271 307 307

238 238 290 290 403 403 457 457

0.270 x 0.880 6.86 x 22.35 132.32 196.91 241 0.270 x 0.880 6.86 x 22.35 132.32 196.91 241

359 359

16 AWG CONDUCTORS 245310* 4 419630* 4 ¥ 245320* 8 404010* 8 ¥ 245330* 12 404020* 12

16 16 16 16 16 16

65/34 65/34 65/34 65/34 65/34 65/34

0.030 0.030 0.030 0.030 0.030 0.030

245340* 4 404030* 4 ¥ 245350* 8 404090* 8 ¥ 245360* 12 403990* 12

14 14 14 14 14 14

41/30 41/30 41/30 41/30 41/30 41/30

0.030 0.030 0.030 0.030 0.030 0.030

245370* 404040* ¥ 245380* 238800* ¥ 365680* 404080* ¥ 245390* 404330*

4 4 5 5 7 7 8 8

12 12 12 12 12 12 12 12

65/30 65/30 65/30 65/30 65/30 65/30 65/30 65/30

0.030 0.030 0.030 0.030 0.030 0.030 0.030 0.030

245400* 404000*

4 4

10 10

105/30 0.030 105/30 0.030

¥

0.76 0.76 0.76 0.76 0.76 0.76

0.035 0.035 0.035 0.035 0.035 0.035

0.89 0.89 0.89 0.89 0.89 0.89

0.200 x 0.580 0.200 x 0.580 0.200 x 1.110 0.200 x 1.110 0.200 x 1.605 0.200 x 1.605

14 AWG CONDUCTORS ¥

0.76 0.76 0.76 0.76 0.76 0.76

0.035 0.035 0.035 0.035 0.035 0.035

0.89 0.89 0.89 0.89 0.89 0.89

0.210 x 0.710 0.210 x 0.710 0.210 x 1.175 0.210 x 1.175 0.210 x 1.700 0.210 x 1.700

12 AWG CONDUCTORS ¥

0.76 0.76 0.76 0.76 0.76 0.76 0.76 0.76

0.035 0.035 0.035 0.035 0.035 0.035 0.035 0.035

0.89 0.89 0.89 0.89 0.89 0.89 0.89 0.89

0.230 x 0.710 0.230 x 0.710 0.230 x 0.865 0.230 x 0.865 0.230 x 1.340 0.230 x 1.340 0.230 x 1.650 0.230 x 1.650

10 AWG CONDUCTORS ¥

0.76 0.76

0.045 0.045

1.14 1.14

8 AWG CONDUCTORS ¥

245410* 406320*

4 4

8 8

168/30 0.045 168/30 0.045

245420* 404050* ¥ 332010* 434680*

4 4 5 5

6 6 6 6

266/30 266/30 266/30 266/30

245440* 404060*

4 4

4 4

420/30 0.060 420/30 0.060

245450* 404070*

4 4

2 2

665/30 0.060 665/30 0.060

1.14 1.14

0.045 0.045

1.14 1.14

• Flame-retardant Polyvinyl Chloride (PVC) • Color-coded: per ICEA Method 1; Table E-2 (does not include white or green). All with alpha-numeric designations

0.365 x 1.190 9.27 x 30.23 212.40 316.07 405 0.365 x 1.190 9.27 x 30.23 212.40 316.07 405

• Flame-retardant Polyvinyl Chloride (PVC) yellow or black • E-24573 PVC T-XXXXX 105˚C 600V VW-1 (UL)FESTOON CABLE OUTDOOR XX/C XX/AWGCSA LL9755 105˚C 600V FT1

Applications:

• Cranes and hoists • Festooning systems • Track systems • Robots • Conveyors • Telescoping jetways

Features:

• Rated at 105˚C • Designed for continuous extreme flexing applications • Anti-coiling in festoon applications • Small bending radii • Flat construction allows for stacking • Oil- and chemical-resistant • Indoor or outdoor use • Meets cold bend test at -55˚C

Compliances:

Industry Compliances: • UL listed/CSA certified flat festoon cable Flame Tests Compliances: • UL VW-1/CSA FT1 Other Compliances: • Meets EPA 40 CFR, part 261 for leachable lead content per TCLP method • OSHA Acceptable

Packaging:

• Material cut to length and shipped on non-returnable wood reels

603 603

6 AWG CONDUCTORS ¥

0.060 0.060 0.060 0.060

1.52 1.52 1.52 1.52

0.045 0.045 0.045 0.045

1.14 1.14 1.14 1.14

0.430 x 1.450 0.430 x 1.450 0.430 x 1.735 0.430 x 1.735

10.92 x 36.83 10.92 x 36.83 10.92 x 44.07 10.92 x 44.07

332.88 332.88 416.10 416.10

495.36 495.36 619.20 619.20

612 612 747 747

911 911 1112 1112

0.490 x 1.690 12.45 x 42.93 560.00 833.34 750 0.490 x 1.690 12.45 x 42.93 560.00 833.34 750

1116 1116

4 AWG CONDUCTORS ¥

1.52 1.52

0.045 0.045

1.14 1.14

2 AWG CONDUCTORS ¥

1.52 1.52

0.045 0.045

1.14 1.14

0.560 x 1.955 14.23 x 49.66 852.00 1267.86 1273 1894 0.560 x 1.955 14.23 x 49.66 852.00 1267.86 1273 1894

Dimensions and weights are nominal; subject to industry tolerances. * Non-stock item, minimum runs apply. Please consult Customer Service for price and delivery. ¥ Indicates black jacketed cables.

Phone: 888-593-3355 www.generalcable.com


Industrial Cables

Date of Issue 01/09 Section 4

600V Multi Conductor Control and Power Cables SPECIFICATION NO.

PRODUCT DESCRIPTION

4050†

CHTC®

XLPE/HYP, Control, Unshielded 600V, UL Type TC—E-2 Color Code

Jan. 2009

4075†

CHTC®

XLPE/HYP, Control, Unshielded 600V, UL Type TC—E-1 Color Code

Jan. 2009

4100†

CHTC®

XLPE/HYP, Low-Voltage Power, Unshielded 600V, UL Type TC-ER—Method 4 Color Code

Jan. 2009

4150

EHTC®

FR-EPR/HYP, Control, Unshielded 600V, UL Type TC (18 AWG/16 AWG)—E-2 Color Code

Jan. 2008

4200

EHTC®

FR-EPR/HYP, Control, Unshielded 600V, UL Type TC (14 AWG—10 AWG)—E-2 Color Code

Jan. 2008

4250

EHTC®

FR-EPR/HYP, Low-Voltage Power, Unshielded 600V, UL Type TC-ER—Method 4 Color Code

Jan. 2009

4300†

FREP®

FR-EPR/CPE, Control, Unshielded 600V, UL Type TC-ER—E-2 Color Code

Jan. 2008

4310†

FREP®

FR-EPR/CPE, Control, Unshielded 600V, UL Type TC-ER—E-1 Color Code

Jan. 2008

4325†

FREP®

FR-EPR/CPE, Control, Shielded 600V, UL Type TC-ER, Overall Shielded—E-2 Color Code

Jan. 2008

4350†

FREP®

FR-EPR/CPE, Low-Voltage Power, Unshielded 600V, UL Type TC-ER—Method 4 Color Code

Jan. 2009

4400

Arctic-Flex®

XLPE/ARCTIC-PVC, Control, Unshielded 600V, UL Type TC-ER, CSA Type RW90 XLPE, CSA TYPE TC

Jan. 2008

4450

Arctic-Flex®

XLPE/ARCTIC-PVC, Low-Voltage Power, Unshielded 600V, UL Type TC-ER, CSA Type RW90 XLPE, CSA TYPE TC

Jan. 2009

4500†

CVTC®

XLPE/PVC, Control, Unshielded 600V, UL Type TC-ER—E-2 Color Code

Jan. 2008

4550†

CVTC®

XLPE/PVC, Low-Voltage Power, Unshielded 600V, UL Type TC-ER—Method 4 Color Code

Jan. 2009

4575

CVTC® VFD

XLPE/PVC, Low-Voltage Power, Shielded 2000V, UL Type TC-ER—Method 4 Color Code

Jan. 2009

4580

CVTC® VFD

XLPE/PVC, Low-Voltage Power, Copper Tape Shielded 2000V, UL Type TC-ER—Method 4 Color Code

Jan. 2009

4600†

VNTC®

PVC/NYLON/PVC, Control, Unshielded 600V, UL Type TC-ER (18 AWG/16 AWG)—E-2 Color Code

Jan. 2008

4650†

VNTC®

PVC/NYLON/PVC, Control, Unshielded 600V, UL Type TC-ER (14 AWG—10 AWG)—E-2 Color Code

Jan. 2008

†Indicates

REVISION DATE

these products are stocked by General Cable

Phone: 888-593-3355 www.generalcable.com


Industrial Cables

Date of Issue 01/09 Section 4

600V Multi Conductor Control and Power Cables SPECIFICATION NO.

PRODUCT DESCRIPTION

4700†

VNTC®

PVC/NYLON/PVC, Control, Shielded 600V, UL Type TC-ER, Overall Shielded—E-2 Color Code

REVISION DATE

Jan. 2008

4750†

VNTC®

PVC/NYLON/PVC, Low-Voltage Power, Unshielded 600V, UL Type TC-ER—Method 4 Color Code

Jan. 2009

4800

20/10

PE/PVC/PVC, Control, Unshielded 600V (18 AWG/16 AWG)—E-1 Color Code

Jan. 2008

4850

20/10

PE/PVC/PVC, Control, Unshielded 600V (14 AWG—10 AWG)—E-1 Color Code

Jan. 2008

4900†

GenFree™

XLPO/LSZH, Control 600V, UL Type TC-LS-ER—E-2 Color Code

Feb. 2008

4925

GenFree™

XLPO/LSZH, Control, Shielded 600V, UL Type TC-LS-ER, Overall Shielded—E-2 Color Code

Feb. 2008

4950†

GenFree™

XLPO/LSZH, Low-Voltage Power, Unshielded 600V, UL Type TC-LS—Method 4 Color Code

Feb. 2008

†Indicates

these products are stocked by General Cable

Phone: 888-593-3355 www.generalcable.com


SPEC 4050

January, 2009

CHTC

®

XLPE/HYP, Control, Unshielded 600V, UL Type TC—E-2 Color Code Product Construction Conductor:

• 16 AWG thru 10 AWG fully annealed stranded tinned copper per ASTM B33 • Class B stranding per ASTM B8

Insulation:

CATALOG NUMBER

COPPER MINIMUM AVG. MINIMUM AVG. WEIGHT NET WEIGHT INSULATION JACKET NOMINAL NO. COND. THICKNESS CABLE O.D. LBS/ OF SIZE COND. THICKNESS LBS/ COND. (AWG) STRAND inCHES mm INCHES mm INCHES mm 1000 FT kg/km 1000 FT kg/km

16 AWG MULTI CONDUCTORS 241420 312500 312510 312520 241430 241440

2 3 4 5 7 9

16 16 16 16 16 16

7/.0192 7/.0192 7/.0192 7/.0192 7/.0192 7/.0192

14 14 14 14 14 14 14 14 14 14

7/.0242 7/.0242 7/.0242 7/.0242 7/.0242 7/.0242 7/.0242 7/.0242 7/.0242 7/.0242

0.030 0.030 0.030 0.030 0.030 0.030

0.76 0.76 0.76 0.76 0.76 0.76

0.045 0.045 0.045 0.045 0.045 0.060

1.14 1.14 1.14 1.14 1.14 1.52

0.340 0.360 0.390 0.420 0.460 0.565

8.64 9.14 9.91 10.67 11.68 14.35

17 25 33 41 58 74

25 37 49 61 86 110

61 73 91 110 141 199

91 109 135 164 210 296

26 26 39 53 66 92 118 158 250 490

39 39 59 78 98 137 176 235 372 730

68 101 75 112 95 141 118 176 143 213 179 266 249 371 317 472 467 695 899 1338

50 74 51 76 64 95 85 126 106 158 168 251 191 285 255 380 403 600 741 1103

85 126 98 146 127 189 160 238 194 289 264 393 345 513 435 647 690 1027 1393 2073

14 AWG MULTI CONDUCTORS 223650* 2 Flat 2 272270 3 223790 4 223780 5 223770 7 223750 9 223760 12 223640 19 223670* 232850* 37

0.030 0.030 0.030 0.030 0.030 0.030 0.030 0.030 0.030 0.030

0.76 0.76 0.76 0.76 0.76 0.76 0.76 0.76 0.76 0.76

0.045 0.045 0.045 0.045 0.045 0.045 0.060 0.060 0.060 0.080

1.14 1.14 1.14 1.14 1.14 1.14 1.52 1.52 1.52 2.03

.230 x .365 5.84 x 9.27

0.370 0.390 0.425 0.465 0.505 0.620 0.700 0.815 1.130

9.40 9.91 10.80 11.81 12.83 15.75 17.78 20.70 28.70

12 AWG MULTI CONDUCTORS 260730* 2 Flat 2 272260 3 223910 4 223930 5 223920 7 224080 9 224070 12 224090 265940* 19 347050* 37

12 12 12 12 12 12 12 12 12 12

7/.0305 7/.0305 7/.0305 7/.0305 7/.0305 7/.0305 7/.0305 7/.0305 7/.0305 7/.0305

0.030 0.030 0.030 0.030 0.030 0.030 0.030 0.030 0.030 0.030

0.76 0.76 0.76 0.76 0.76 0.76 0.76 0.76 0.76 0.76

0.045 0.045 0.045 0.045 0.045 0.060 0.060 0.060 0.080 0.080

1.14 1.14 1.14 1.14 1.14 1.52 1.52 1.52 2.03 2.03

.250 x .400 6.35 x 10.16

0.410 0.435 0.475 0.520 0.595 0.695 0.780 0.955 1.265

10.41 11.05 12.07 13.21 15.11 17.65 19.81 24.26 32.13

10 AWG MULTI CONDUCTORS 361350* 2 Flat 2 355210 3 224100 4 224110 5 224120* 7 224130* 9 347060* 347070* 12

10 10 10 10 10 10 10 10

7/.0385 7/.0385 7/.0385 7/.0385 7/.0385 7/.0385 7/.0385 7/.0385

0.030 0.030 0.030 0.030 0.030 0.030 0.030 0.030

0.76 0.76 0.76 0.76 0.76 0.76 0.76 0.76

0.045 0.045 0.045 0.060 0.060 0.060 0.060 0.080

1.14 1.14 1.14 1.52 1.52 1.52 1.52 2.03

.270 x .445 6.86 x 11.30

0.455 0.485 0.560 0.615 0.670 0.765 0.905

5.26 12.32 14.22 15.62 17.02 19.43 22.99

66 67 100 134 167 234 302 404

Dimensions and weights are nominal; subject to industry tolerances. *Non-stock item, minimum runs apply. Please consult Customer Service for price and delivery.

98 100 150 199 249 349 449 601

117 126 176 240 291 376 456 636

174 188 262 357 433 560 679 946

• Flame-retardant Cross-Linked Polyethylene (XLPE) • Color-coded per ICEA Method 1; Table E-2 plus alpha-numeric printed numbers (Does not include white or green)

Jacket:

• Low-lead Hypalon® Chlorosulfonated Polyethylene (CSPE)/Elastomer blend

Print

• GENERAL CABLE® (WC) CHTC® XX/C XXAWG CU/XLP/HYP (UL) Type TC XHHW-2 CDRS DIR BUR SUN RES OIL RES I & II 600V DAY/MONTH/ YEAR OF MFG sequential footage mark

Options:

• 2kV version • Bare copper conductor • Class C stranding • E-1 Color Code—See Spec 4075 • Overall shielded multi conductor • Ethylene Propylene Rubber (EPR) insulation—See EHTC® Spec 4200 • Thermoplastic Low-Smoke, Zero-Halogen (LSZH) jacket • Flame-retardant, Polyvinyl Chloride (PVC) jacket—See CVTC® Spec 4500 • Other constructions available upon request

Applications:

• In free air, raceways or direct burial • In wet or dry locations • Permitted for use in Class I, Div. 2 industrial hazardous locations per NEC Article 501 and Class 1 circuits per NEC

Features:

• Rated at 90˚C wet or dry • Ripcord applied to all cables with jacket thickness of 60 mils or less • Excellent physical, thermal and electrical properties • Excellent moisture resistance • Excellent resistance to crush, compression cuts and heat deformation • Excellent flame resistance • Oil-resistant jacket • “Heavy Duty” rating per ICEA standards • Sunlight- and weather-resistant • Excellent low temperature cold bend characteristics • Meets cold bend test at -35˚C

Compliances:

Industry Compliances: • UL 44 Type XHHW-2 • UL 1277 Type TC • UL 1581 • ICEA S-73-532 • ICEA S-95-658/NEMA WC70 Flame Tests Compliances: • UL 1581 VW-1 • UL 1277 • IEEE 383 • IEEE 1202 • CSA FT-4 • ICEA T-29-520 Other Compliances: • EPA 40 CFR, Part 261 for leachable lead content per TCLP • OSHA acceptable

Packaging:

• Material cut to length and shipped on non-returnable wood reels

Phone: 888-593-3355 www.generalcable.com


SPEC 4075

January, 2009

CHTC

®

XLPE/HYP, Control, Unshielded 600V, UL Type TC—E-1 Color Code Product Construction Conductor:

• 14 AWG thru 10 AWG fully annealed stranded tinned copper per ASTM B33 • Class B stranding per ASTM B8

Insulation:

• Flame-retardant Cross-Linked Polyethylene (XLPE) • Color-coded per ICEA Method 1; Table E-1

CATALOG NUMBER

COPPER MINIMUM AVG. MINIMUM AVG. WEIGHT NET WEIGHT INSULATION JACKET NOMINAL NO. COND. THICKNESS CABLE O.D. LBS/ OF SIZE COND. THICKNESS LBS/ COND. (AWG) STRAND inCHES mm INCHES mm INCHES mm 1000 FT kg/km 1000 FT kg/km

14 AWG MULTI CONDUCTORS 256260* 2 Flat 2 330580 3 244160 4 239640 5 239700 7 237500 9 239660 12 252400 19 252410* 25 383980* 30 383990* 37 384000*

14 14 14 14 14 14 14 14 14 14 14 14

7/.0242 7/.0242 7/.0242 7/.0242 7/.0242 7/.0242 7/.0242 7/.0242 7/.0242 7/.0242 7/.0242 7/.0242

0.030 0.030 0.030 0.030 0.030 0.030 0.030 0.030 0.030 0.030 0.030 0.030

0.76 0.76 0.76 0.76 0.76 0.76 0.76 0.76 0.76 0.76 0.76 0.76

0.045 0.045 0.045 0.045 0.045 0.045 0.060 0.060 0.060 0.080 0.080 0.080

1.14 1.14 1.14 1.14 1.14 1.14 1.52 1.52 1.52 2.03 2.03 2.03

.230 x .365 5.84 x 9.27

0.370 0.390 0.425 0.465 0.505 0.620 0.700 0.815 1.000 1.050 1.130

9.40 9.91 10.80 11.81 12.83 15.75 17.78 20.70 25.40 26.67 28.70

26 26 39 53 66 92 118 158 250 330 398 490

39 39 59 78 98 137 176 235 372 491 592 730

68 75 95 118 143 179 249 317 467 632 731 899

101 112 141 176 213 266 371 472 695 941 1088 1338

50 51 64 85 106 168 191 255 403 515 618 741

74 85 76 98 95 127 126 160 158 194 251 264 285 345 380 435 600 690 767 858 920 997 1103 1393

126 146 189 238 289 393 513 647 1027 1277 1484 2073

66 67 100 134 167 234 302 404

98 100 150 199 249 349 449 601

174 188 262 357 433 560 679 946

12 AWG MULTI CONDUCTORS 233320* 239670 233330 239680 239650 243530 239620 252360 252230* 384010* 384020* 384030*

2 Flat 2 3 4 5 7 9 12 19 25 30 37

12 12 12 12 12 12 12 12 12 12 12 12

7/.0305 7/.0305 7/.0305 7/.0305 7/.0305 7/.0305 7/.0305 7/.0305 7/.0305 7/.0305 7/.0305 7/.0305

384040* 243540 239630 233310 262680* 375010* 235680* 375470*

2 Flat 2 3 4 5 7 9 12

10 10 10 10 10 10 10 10

7/.0385 7/.0385 7/.0385 7/.0385 7/.0385 7/.0385 7/.0385 7/.0385

0.030 0.030 0.030 0.030 0.030 0.030 0.030 0.030 0.030 0.030 0.030 0.030

0.76 0.76 0.76 0.76 0.76 0.76 0.76 0.76 0.76 0.76 0.76 0.76

0.045 0.045 0.045 0.045 0.045 0.060 0.060 0.060 0.080 0.080 0.080 0.080

1.14 1.14 1.14 1.14 1.14 1.52 1.52 1.52 2.03 2.03 2.03 2.03

.250 x .400 6.35 x 10.16

0.410 0.435 0.475 0.520 0.595 0.695 0.780 0.955 1.095 1.175 1.265

10.41 11.05 12.07 13.21 15.11 17.65 19.81 24.26 27.81 29.85 32.13

10 AWG MULTI CONDUCTORS 0.030 0.030 0.030 0.030 0.030 0.030 0.030 0.030

0.76 0.76 0.76 0.76 0.76 0.76 0.76 0.76

0.045 0.045 0.045 0.060 0.060 0.060 0.060 0.080

1.14 1.14 1.14 1.52 1.52 1.52 1.52 2.03

.270 x .445 6.86 x 11.30

0.455 0.485 0.560 0.615 0.670 0.765 0.905

5.26 12.32 14.22 15.62 17.02 19.43 22.99

Dimensions and weights are nominal; subject to industry tolerances. *Non-stock item, minimum runs apply. Please consult Customer Service for price and delivery.

117 126 176 240 291 376 456 636

Jacket:

• Low-lead Hypalon® Chlorosulfonated Polyethylene (CSPE)/Elastomer blend

Print

• GENERAL CABLE® (WC) CHTC® XX/C XXAWG CU/XLP/HYP (UL) Type TC XHHW-2 CDRS DIR BUR SUN RES OIL RES I & II 600V DAY/MONTH/ YEAR OF MFG sequential footage mark

Options:

• 2kV version • Bare copper conductor • Class C stranding • E-2 Color Code—See Spec 4050 • Overall shielded multi conductor • Ethylene Propylene Rubber (EPR) insulation—See EHTC Spec 4200 • Thermoplastic Low-Smoke, Zero-Halogen (LSZH) jacket • Flame-retardant, Polyvinyl Chloride (PVC) jacket—See CVTC® Spec 4500 • Other constructions available upon request

Applications:

• In free air, raceways or direct burial • In wet or dry locations • Permitted for use in Class I, Div. 2 industrial hazardous locations per NEC Article 501 and Class 1 circuits per NEC

Features:

• Rated at 90˚C wet or dry • Ripcord applied to all cables with jacket thickness of 60 mils or less • Excellent physical, thermal and electrical properties • Excellent moisture resistance • Excellent resistance to crush, compression cuts and heat deformation • Excellent flame resistance • Oil-resistant jacket • “Heavy Duty” rating per ICEA standards • Sunlight- and weather-resistant • Excellent low temperature cold bend characteristics • Meets cold bend test at -35˚C

Compliances:

Industry Compliances: • UL 44 Type XHHW-2 • UL 1277 Type TC • UL 1581 • ICEA S-73-532 • ICEA S-95-658/NEMA WC70 Flame Tests Compliances: • UL 1581 VW-1 • UL 1277 • IEEE 383 • IEEE 1202 • CSA FT-4 • ICEA T-29-520 Other Compliances: • EPA 40 CFR, Part 261 for leachable lead content per TCLP • OSHA acceptable

Packaging:

• Material cut to length and shipped on non-returnable wood reels

Phone: 888-593-3355 www.generalcable.com


SPEC 4100

January, 2009

CHTC

®

XLPE/HYP, Low-Voltage Power, Unshielded 600V, UL Type TC-ER1—Method 4 Color Code Features (cont’d.):

Product Construction Conductor:

• Excellent moisture resistance • Excellent resistance to crush, compression cuts and heat deformation • Excellent flame resistance • Excellent low temperature cold bend characteristics • “Heavy duty” rating per ICEA standards • Sunlight- and weather-resistant • Oil-resistant jacket • Meets cold bend test at -35˚C • Meets the crush and impact requirements of Type MC cable for 2 AWG and larger

Options:

• Bare copper conductor • Class C stranding • 2 kV version • E-1 or E-2 Color Code • Overall shielded multi conductor • Insulated ground conductor • Flame-retardant Ethylene Propylene Rubber (EPR) insulation—See EHTC® Spec 4250 • Thermoplastic Low-Smoke, Zero-Halogen (LSZH) jacket • Other constructions available upon request

• 14 AWG thru 500 kcmil tinned, annealed copper per ASTM B33 • Class B stranding per ASTM B8

Insulation:

• Flame-retardant Cross-Linked Polyethylene (XLPE) • Color-coded: per ICEA Method 4; Individual conductors colored black with conductor number surface printed in contrasting ink

Ground:

Compliances:

Industry Compliances: • UL 44 Type XHHW-2 • UL 1277 Type TC-ER for 2 AWG and larger • UL 1581 • ICEA S-95-658/NEMA WC70 Flame Tests Compliances: • UL 1581 VW-1 • UL 1277 • IEEE 383 • IEEE 1202 • CSA FT-4 • ICEA T-29-520 Other Compliances: • EPA 40 CFR, Part 261 for leachable lead content per TCLP • OSHA acceptable

Applications:

• Uninsulated tinned annealed copper per ASTM B3 • Class B stranding per ASTM B8

• In free air, raceways or direct burial • In wet or dry locations • Permitted for Exposed Run ‘ER’ use in accordance with NEC for 2 AWG and larger • Permitted for use in Class I Division 2 industrial hazardous locations per NEC

Jacket:

• Low-lead Hypalon® Chlorosulfonated Polyethylene (CSPE)/Elastomer blend

Features:

Print:

CATALOG NUMBER

NO. OF COND.

COND. SIZE (AWG/ kcmil)

Packaging:

• Rated at 90˚C wet or dry • Ripcord applied to all cables with jacket thickness of 60 mils or less • Excellent physical, thermal and electrical properties

• General Cable® (WC) CHTC® XX/C XXAWG WITH GRND CU/XLP/HYP (UL) TYPE TC-ER1 XHHW-2 CDRS DIR BUR SUN RES 600V MONTH/ YEAR OF MFG SEQUENTIAL FOOTAGE MARK

COND. STRAND

GROUND WIRE SIZE (AWG)

MINIMUM AVG. INSULATION THICKNESS INCHES

mm

• Material cut to length and shipped on non-returnable wood reels

MINIMUM AVG. JACKET THICKNESS NOMINAL CABLE O.D. INCHES

mm

INCHES

COPPER WEIGHT

mm

LBS/ 1000 FT

10.80 12.07 14.22 16.76 18.42 18.92 20.83 22.61 24.77 25.91 28.45 28.45 31.37 31.50 33.78 34.04 37.59 36.07 39.88 40.01 44.83 44.58 49.15 51.05 55.37 58.55 64.90

53 85 134 190 242 301 384 448 578 716 919 872 1136 1081 1413 1341 1760 1717 2245 2132 2796 2494 3282 3477 4577 4938 6509

NET WEIGHT

kg/km

LBS/ 1000 FT

kg/km

78 126 199 283 360 448 571 667 861 1066 1368 1298 1691 1609 2103 1996 2619 2555 3341 3173 4161 3712 4884 5174 6811 7349 9647

118 160 240 223 421 481 600 702 882 1024 1295 1199 1704 1505 1830 1810 2326 2437 3123 2725 3909 3605 4571 4423 6068 6097 7905

176 238 357 332 627 716 893 1045 1313 1524 1927 1784 2536 2240 2723 2694 3462 3627 4648 4055 5817 5365 6803 6582 9030 9074 11764

14 AWG - 500 kcmil MULTI CONDUCTORS 383790* 309340* 282570* 282580 282590* 282600 282610* 282620 282630* 282640 282650* 366070* 366080* 282660* 338860* 282670* 292410* 366090* 366100* 282680* 338880* 338890* 338900* 282690* 338910* 282710* 331150*

3 3 3 3 4 3 4 3 4 3 4 3 4 3 4 3 4 3 4 3 4 3 4 3 4 3 4

14 12 10 8 8 6 6 4 4 2 2 1 1 1/0 1/0 2/0 2/0 3/0 3/0 4/0 4/0 250 250 350 350 500 500

7/.0242 7/.0305 7/.0385 7/.0486 7/.0486 7/.0612 7/.0612 7/.0772 7/.0772 7/.0974 7/.0974 19/.0664 19/.0664 19/.0745 19/.0745 19/.0837 19/.0837 19/.0940 19/.0940 19/.1055 19/.1055 37/.0822 37/.0822 37/.0973 37/.0973 37/.1162 37/.1162

14 12 10 10 10 8 8 8 8 6 6 6 6 6 6 6 6 4 4 4 4 4 4 3 3 2 2

0.030 0.030 0.030 0.045 0.045 0.045 0.045 0.045 0.045 0.045 0.045 0.055 0.055 0.055 0.055 0.055 0.055 0.055 0.055 0.055 0.055 0.065 0.065 0.065 0.065 0.065 0.065

0.76 0.76 0.76 1.14 1.14 1.14 1.14 1.14 1.14 1.14 1.14 1.40 1.40 1.40 1.40 1.40 1.40 1.40 1.40 1.40 1.40 1.65 1.65 1.65 1.65 1.65 1.65

0.045 0.045 0.060 0.060 0.060 0.060 0.060 0.080 0.080 0.080 0.080 0.080 0.080 0.080 0.080 0.080 0.080 0.080 0.080 0.080 0.110 0.110 0.110 0.110 0.110 0.110 0.110

1.14 1.14 1.52 1.52 1.52 1.52 1.52 2.03 2.03 2.03 2.03 2.03 2.03 2.03 2.03 2.03 2.03 2.03 2.03 2.03 2.79 2.79 2.79 2.79 2.79 2.79 2.79

0.425 0.475 0.526 0.660 0.725 0.745 0.820 0.890 0.975 1.020 1.120 1.120 1.235 1.240 1.330 1.340 1.480 1.420 1.570 1.575 1.765 1.755 1.935 2.010 2.180 2.305 2.555

Dimensions and weights are nominal; subject to industry tolerances. *Non-stock item, minimum runs apply. Please consult Customer Service for price and delivery. 1Approved as TYPE TC-ER for Exposed Run applications of 2 AWG and larger defined by NEC.

Phone: 888-593-3355 www.generalcable.com


SPEC 4150

January, 2008

EHTC

®

FR-EPR/HYP, Control, Unshielded 600V, UL Type TC (18 AWG/16 AWG)—E-2 Color Code Product Construction Conductor:

• 18 AWG and 16 AWG tinned, annealed copper per ASTM B33 • Class B stranding per ASTM B8

Insulation:

CATALOG NUMBER

COPPER MINIMUM AVG. MINIMUM AVG. WEIGHT NET WEIGHT INSULATION JACKET NOMINAL NO. COND. THICKNESS CABLE O.D. LBS/ OF SIZE COND. THICKNESS LBS/ COND. (AWG) STRAND inCHES mm INCHES mm INCHES mm 1000 FT kg/km 1000 FT kg/km

18 AWG MULTI CONDUCTORS 366190* 343330* 343340* 343350* 343360* 343370* 343380* 343390* 343400* 343410* 343420* 343430* 343440* 343450*

2 Flat 2 3 4 5 7 9 10 12 15 19 25 30 37

18 18 18 18 18 18 18 18 18 18 18 18 18 18

7/.0152 7/.0152 7/.0152 7/.0152 7/.0152 7/.0152 7/.0152 7/.0152 7/.0152 7/.0152 7/.0152 7/.0152 7/.0152 7/.0152

366200* 343460* 343470* 343480* 343490* 343500* 343510* 343520* 343530* 343540* 343550* 343560* 343570* 343580*

2 Flat 2 3 4 5 7 9 10 12 15 19 25 30 37

16 16 16 16 16 16 16 16 16 16 16 16 16 16

7/.0192 7/.0192 7/.0192 7/.0192 7/.0192 7/.0192 7/.0192 7/.0192 7/.0192 7/.0192 7/.0192 7/.0192 7/.0192 7/.0192

0.025 0.025 0.025 0.025 0.025 0.025 0.025 0.025 0.025 0.025 0.025 0.025 0.025 0.025

0.64 0.64 0.64 0.64 0.64 0.64 0.64 0.64 0.64 0.64 0.64 0.64 0.64 0.64

0.045 0.045 0.045 0.045 0.045 0.045 0.045 0.045 0.045 0.060 0.060 0.060 0.060 0.060

1.14 1.14 1.14 1.14 1.14 1.14 1.14 1.14 1.14 1.52 1.52 1.52 1.52 1.52

.192 x .290 4.88 x 7.37

0.295 0.310 0.340 0.365 0.395 0.455 0.485 0.510 0.580 0.625 0.720 0.770 0.830

7.49 7.88 8.64 9.27 10.03 11.56 12.32 12.95 14.73 15.88 18.29 19.56 21.08

10 10 15 20 26 36 46 51 61 77 97 128 154 189

15 15 23 30 38 53 69 76 91 114 144 190 229 281

37 45 55 67 79 97 123 137 153 202 243 301 345 414

55 67 82 100 118 144 183 204 228 301 362 448 513 616

16 16 24 32 40 56 72 80 97 121 153 201 242 298

24 24 36 48 60 84 108 119 144 180 228 299 360 443

46 55 69 85 102 127 162 197 221 270 327 424 508 609

68 82 130 126 152 189 241 293 329 402 487 631 756 906

16 AWG MULTI CONDUCTORS 0.025 0.025 0.025 0.025 0.025 0.025 0.025 0.025 0.025 0.025 0.025 0.025 0.025 0.025

0.64 0.64 0.64 0.64 0.64 0.64 0.64 0.64 0.64 0.64 0.64 0.64 0.64 0.64

0.045 0.045 0.045 0.045 0.045 0.045 0.045 0.060 0.060 0.060 0.060 0.060 0.080 0.080

1.14 1.14 1.14 1.14 1.14 1.14 1.14 1.52 1.52 1.52 1.52 1.52 2.03 2.03

.204 x .314 5.18 x 7.98

0.320 0.340 0.365 0.400 0.430 0.500 0.565 0.590 0.640 0.690 0.795 0.890 0.955

8.13 8.67 9.27 10.20 10.90 12.70 14.40 14.97 16.26 17.53 20.19 22.61 24.26

Dimensions and weights are nominal; subject to industry tolerances. *Non-stock item, minimum runs apply. Please consult Customer Service for price and delivery.

• Flame-retardant Ethylene Propylene Rubber (FR-EPR) Type II • Color-coded per ICEA Method 1; Table E-2 (does not include white or green)

Jacket:

• Low-lead Hypalon Chlorosulfonated Polyethylene (CSPE)/Elastomer blend

Print

• GENERAL CABLE® (WC) EHTC® XX/C XXAWG EPR/HYP UL TYPE TC 90˚ WET OR DRY CDRS BUR SUN RES 600V, DAY/MONTH/YEAR OF MFG SEQUENTIAL FOOTAGE MARK

Options:

• 2kV version • Bare copper conductors • Class C stranding • Insulated or uninsulated ground conductors • Overall shielded multi conductors • Duralox® aluminum interlocked armor • E-1 Color Code • Flame-retardant Polyvinyl Chloride (PVC) jacket • Thermoplastic Low-Smoke, Zero-Halogen (LSZH) jacket • Flame-retardant Thermoplastic Chloronated Polyethylene (CPE)—See FREP® Spec 4300 • Other constructions available upon request

Applications:

• In free air, raceways or direct burial • In wet or dry locations • At temperature as low as -35˚C • In Class I Division 2 industrial hazardous locations per NEC

Features:

• Rated at 90˚C wet or dry • Ripcord applied to all cables with jacket thickness of 60 mils or less • Excellent physical, thermal and electrical properties • Excellent moisture resistance • Excellent resistance to crush, compression cuts and heat deformation • Excellent flame resistance • Excellent low temperature cold bend characteristics • Good abrasion resistance • Low moisture absorption characteristics • “Heavy duty” rated per ICEA standards • Meets cold bend test at -35˚C

Compliances:

Industry Compliances: • UL 1277 Type TC • UL 1581 • ICEA S-73-532 • ICEA S-95-658/NEMA WC70 Flame Tests Compliances: • UL 1581 VW-1 • UL 1277 • IEEE 383 • IEEE 1202 • CSA FT-4 • ICEA T-29-520 Other Compliances: • EPA 40 CFR, Part 261 for leachable lead content per TCLP • OSHA acceptable

Packaging:

• Material cut to length and shipped on non-returnable wood reels

Phone: 888-593-3355 www.generalcable.com


SPEC 4200

January, 2008

EHTC

®

FR-EPR/HYP, Control, Unshielded 600V, UL Type TC (14 AWG—10 AWG)—E-2 Color Code Product Construction Conductor:

• 14 AWG thru 10 AWG tinned, annealed copper per ASTM B33 • Class B stranding per ASTM B8

Insulation:

CATALOG NUMBER

COPPER MINIMUM AVG. MINIMUM AVG. WEIGHT NET WEIGHT INSULATION JACKET NOMINAL NO. COND. THICKNESS CABLE O.D. LBS/ OF SIZE COND. THICKNESS LBS/ COND. (AWG) STRAND inCHES mm INCHES mm INCHES mm 1000 FT kg/km 1000 FT kg/km

14 AWG MULTI CONDUCTORS 262130* 343590* 262140* 248240* 262150* 262160* 343600* 248290* 343630* 262190* 343640* 343650*

2 Flat 2 3 4 5 7 9 12 19 25 30 37

14 14 14 14 14 14 14 14 14 14 14 14

7/.0242 7/.0242 7/.0242 7/.0242 7/.0242 7/.0242 7/.0242 7/.0242 7/.0242 7/.0242 7/.0242 7/.0242

0.030 0.030 0.030 0.030 0.030 0.030 0.030 0.030 0.030 0.030 0.030 0.030

0.76 0.76 0.76 0.76 0.76 0.76 0.76 0.76 0.76 0.76 0.76 0.76

0.045 0.045 0.045 0.045 0.045 0.045 0.060 0.060 0.060 0.080 0.080 0.080

1.14 1.14 1.14 1.14 1.14 1.14 1.52 1.52 1.52 2.03 2.03 2.03

.230 x .365 5.84 x 9.27

0.370 0.390 0.425 0.465 0.505 0.620 0.700 0.815 1.000 1.050 1.130

9.40 9.91 10.80 11.81 12.83 15.75 17.78 20.71 25.40 26.70 28.71

26 26 39 53 66 92 118 158 250 330 398 490

38 39 59 78 98 137 176 235 372 491 592 729

68 76 97 120 145 183 254 323 477 645 746 919

101 113 144 179 216 272 378 481 710 960 1110 1368

343660* 343670* 343680* 343690* 262200* 343700* 343710* 343730* 343750* 343760* 343770* 343780*

2 Flat 2 3 4 5 7 9 12 19 25 30 37

12 12 12 12 12 12 12 12 12 12 12 12

7/.0305 7/.0305 7/.0305 7/.0305 7/.0305 7/.0305 7/.0305 7/.0305 7/.0305 7/.0305 7/.0305 7/.0305

343790* 343800* 343810* 264990* 343820* 343830* 343840* 343860*

2 Flat 2 3 4 5 7 9 12

10 10 10 10 10 10 10 10

7/.0385 7/.0385 7/.0385 7/.0385 7/.0385 7/.0385 7/.0385 7/.0385

0.030 0.030 0.030 0.030 0.030 0.030 0.030 0.030 0.030 0.030 0.030 0.030

0.76 0.76 0.76 0.76 0.76 0.76 0.76 0.76 0.76 0.76 0.76 0.76

0.045 0.045 0.045 0.045 0.045 0.060 0.060 0.060 0.080 0.080 0.080 0.080

1.14 1.14 1.14 1.14 1.14 1.52 1.52 1.52 2.03 2.03 2.03 2.03

0.410 0.435 0.475 0.520 0.595 0.695 0.780 0.955 1.115 1.150 1.240

10.41 11.05 12.07 13.21 15.11 17.65 19.81 24.26 28.32 29.21 31.50

50 51 64 85 106 168 191 255 403 515 618 741

76 88 76 99 95 129 127 163 158 198 250 269 285 351 380 443 600 703 767 875 920 1017 1103 1421

131 147 192 243 295 400 522 659 1046 1302 1513 2115

66 67 100 134 167 234 302 404

98 100 150 199 249 349 449 601

177 199 265 362 439 568 732 985

10 AWG MULTI CONDUCTORS 0.030 0.030 0.030 0.030 0.030 0.030 0.030 0.030

0.76 0.76 0.76 0.76 0.76 0.76 0.76 0.76

0.045 0.045 0.045 0.060 0.060 0.060 0.060 0.080

1.14 1.14 1.14 1.52 1.52 1.52 1.52 2.03

.270 x .445 6.86 x 11.30

0.455 0.485 0.560 0.615 0.670 0.765 0.905

11.6 12.3 14.2 15.6 17.0 19.4 23.0

Jacket:

• Low-lead Hypalon Chlorosulfonated Polyethylene (CSPE)/Elastomer blend

Print

• GENERAL CABLE® (WC) EHTC® XX/C XXAWG EPR/HYP UL TYPE TC XHHW-2 CDRS BUR SUN RES 600V, DAY/MONTH/ YEAR OF MFG SEQUENTIAL FOOTAGE MARK

Options:

• 2kV version • Bare copper conductors • Class C stranding • Insulated or uninsulated ground conductors • Overall shielded multi conductors • Duralox® aluminum interlocked armor • E-1 Color Code • Flame-retardant Polyvinyl Chloride (PVC) jacket • Thermoplastic Low-Smoke, Zero-Halogen (LSZH) jacket • Flame-retardant Thermoplastic Chloronated Polyethylene (CPE)—See FREP® Spec 4300 • Other constructions available upon request

Applications:

12 AWG MULTI CONDUCTORS .250 x .400 6.35 x 10.16

• Flame-retardant Ethylene Propylene Rubber (FREPR) Type II • Color-coded per ICEA Method 1; Table E-2 (does not include white or green)

Dimensions and weights are nominal; subject to industry tolerances. *Non-stock item, minimum runs apply. Please consult Customer Service for price and delivery.

119 134 178 243 295 382 492 662

• In free air, raceways or direct burial • In wet or dry locations • At temperature as low as -35˚C • In Class I Division 2 industrial hazardous locations per NEC

Features:

• Rated at 90˚C wet or dry • Ripcord applied to all cables with jacket thickness of 60 mils or less • Excellent physical, thermal and electrical properties • Excellent moisture resistance • Excellent resistance to crush, compression cuts and heat deformation • Excellent flame resistance • Excellent low temperature cold bend characteristics • Good abrasion resistance • Low moisture absorption characteristics • “Heavy duty” rated per ICEA standards • Meets cold bend test at -35˚C

Compliances:

Industry Compliances: • UL 44 Type XHHW-2 • UL 1277 Type TC • UL 1581 • ICEA S-73-532 • ICEA S-95-658/NEMA WC70 Flame Tests Compliances: • UL 1581 VW-1 • UL 1277 • IEEE 383 • IEEE 1202 • CSA FT-4 • ICEA T-29-520 Other Compliances: • EPA 40 CFR, Part 261 for leachable lead content per TCLP • OSHA acceptable

Packaging:

• Material cut to length and shipped on non-returnable wood reels

Phone: 888-593-3355 www.generalcable.com


SPEC 4250

January, 2009

EHTC

®

FR-EPR/HYP, Low-Voltage Power, Unshielded 600V, UL Type TC-ER1—Method 4 Color Code Features (cont’d.):

Options:

Product Construction Conductors:

• 2kV version • Bare copper conductors • Insulated ground conductor • Cross-Linked Polyethylene (XLPE) insulation • Flame-retardant Polyvinyl Chloride (PVC) jacket • Thermoplastic Low-Smoke, Zero-Halogen (LSZH) jacket • Flame-retardant Thermoplastic Chloronated Polyethylene (CPE)—See FREP® Spec 4350 • Class C stranding • E-1 or E-2 Color Code • Other constructions available upon request

• 14 AWG thru 500 kcmil tinned, annealed copper per ASTM B33 • Class B stranding per ASTM B8

Insulation:

• Flame-retardant Ethylene Propylene Rubber (FR-EPR) Type II • Color-coded per ICEA Method 4; Individual conductors colored black with conductor number surface printed in contrasting ink

Ground:

• Low-lead Hypalon Chlorosulfonated Polyethylene (CSPE)/Elastomer blend

Print:

Packaging:

Features:

• General Cable® (WC) EHTC® XX/C XXAWG WITH GRND EPR/HYP (UL)TYPE TC-ER1 XHHW-2 CDRS DIR BUR SUN RES 600V DAY/MONTH/ YEAR OF MFG SEQUENTIAL FOOTAGE MARK

NO. OF COND.

Industry Compliances: • UL 44 Type XHHW-2 • UL 1277 Type TC-ER for 2 AWG & larger • UL 1581 • ICEA S-95-658/NEMA WC70 Flame Tests Compliances: • UL 1581 VW-1 • UL 1277 • IEEE 383 • IEEE 1202 • CSA FT-4 • ICEA T-29-520 Other Compliances: • EPA 40 CFR, Part 261 for leachable lead content per TCLP • OSHA acceptable

• In free air, raceways or direct burial • In wet or dry locations • Permitted for Exposed Run ‘ER’ use in accordance with NEC for 2 AWG and larger • In Class I Division 2 industrial hazardous locations per NEC

Jacket:

COND. SIZE (AWG/ kcmil)

Compliances:

Applications:

• Uninsulated tinned annealed copper per ASTM B3 • Class B stranding per ASTM B8.

CATALOG NUMBER

• UL 44 Type XHHW-2, VW-1, 600V • Excellent physical, thermal and electrical properties • Excellent resistance to moisture • Excellent resistance to crush, compression cuts and heat deformation • Excellent flame resistance • “Heavy Duty” rated per ICEA standards • Excellent low temperature cold bend characteristics • Meets cold bend test at -35˚C • Meets the crush and impact requirements of Type MC cable for 2 AWG and larger

• Material cut to length and shipped on non-returnable wood reels

• Rated at 90˚C wet or dry • Ripcord applied to all cables with jacket thickness of 60 mils or less

COND. STRAND

GROUND WIRE SIZE (AWG)

MINIMUM AVG. INSULATION THICKNESS INCHES

mm

MINIMUM AVG. JACKET THICKNESS NOMINAL CABLE O.D. INCHES

mm

INCHES

COPPER WEIGHT

mm

LBS/ 1000 FT

10.80 12.07 14.22 16.76 18.42 18.92 20.83 22.61 24.77 25.91 28.45 28.45 31.37 31.50 33.78 34.04 37.59 36.07 39.88 40.01 44.83 44.58 49.15 51.05 55.37 58.55 64.90

53 85 134 190 242 301 384 448 578 716 919 872 1136 1081 1413 1341 1760 1717 2245 2132 2796 2494 3282 3477 4577 4938 6509

NET WEIGHT

kg/km

LBS/ 1000 FT

kg/km

78 126 199 283 360 448 571 667 860 1066 1368 1298 1691 1609 2103 1996 2619 2555 3341 3173 4161 3712 4884 5174 6811 7349 9687

118 160 240 223 421 481 600 702 882 1024 1295 1199 1704 1505 1830 1810 2326 2437 3123 2725 3909 3605 4571 4423 6068 6097 7905

176 238 357 332 627 716 893 1045 1313 1524 1927 1784 2536 2240 2723 2694 3462 3627 4648 4055 5817 5365 6803 6582 9030 9074 11764

14 AWG - 500 kcmil MULTI CONDUCTORS 383800* 383810* 383820* 261000* 338670* 366210* 338680* 261010* 338690* 338700* 338710* 366220* 366230* 338720* 338730* 338740* 338750* 366240* 366250* 360990* 338770* 338780* 338790* 338800* 338310* 338820* 338830*

3 3 3 3 4 3 4 3 4 3 4 3 4 3 4 3 4 3 4 3 4 3 4 3 4 3 4

14 12 10 8 8 6 6 4 4 2 2 1 1 1/0 1/0 2/0 2/0 3/0 3/0 4/0 4/0 250 250 350 350 500 500

7/.0242 7/.0305 7/.0385 7/.0486 7/.0486 7/.0612 7/.0612 7/.0772 7/.0772 7/.0974 7/.0974 19/.0664 19/.0664 19/.0740 19/.0740 19/.0837 19/.0837 19/.0940 19/.0940 19/.1055 19/.1055 37/.0822 37/.0822 37/.0973 37/.0973 37/.1162 37/.1162

14 12 10 10 10 8 8 8 8 6 6 6 6 6 6 6 6 4 4 4 4 4 4 3 3 2 2

0.030 0.030 0.030 0.045 0.045 0.045 0.045 0.045 0.045 0.045 0.045 0.055 0.055 0.055 0.055 0.055 0.055 0.055 0.055 0.055 0.055 0.065 0.065 0.065 0.065 0.065 0.065

0.76 0.76 0.76 1.14 1.14 1.14 1.14 1.14 1.14 1.14 1.14 1.40 1.40 1.40 1.40 1.40 1.40 1.40 1.40 1.40 1.40 1.65 1.65 1.65 1.65 1.65 1.65

0.045 0.045 0.060 0.060 0.060 0.060 0.060 0.080 0.080 0.080 0.080 0.080 0.080 0.080 0.080 0.080 0.080 0.080 0.080 0.080 0.110 0.110 0.110 0.110 0.110 0.110 0.110

1.14 1.14 1.52 1.52 1.52 1.52 1.52 2.03 2.03 2.03 2.03 2.03 2.03 2.03 2.03 2.03 2.03 2.03 2.03 2.03 2.79 2.79 2.79 2.79 2.79 2.79 2.79

0.425 0.475 0.526 0.660 0.725 0.745 0.820 0.890 0.975 1.020 1.120 1.120 1.235 1.240 1.330 1.340 1.480 1.420 1.570 1.575 1.765 1.755 1.935 2.010 2.180 2.305 2.555

Dimensions and weights are nominal; subject to industry tolerances. *Non-stock item, minimum runs apply. Please consult Customer Service for price and delivery. 1Approved as TYPE TC-ER for Exposed Run applications of 2 AWG and larger defined by NEC.

Phone: 888-593-3355 www.generalcable.com


SPEC 4300

January, 2008

FREP

®

FR-EPR/CPE, Control, Unshielded 600V, UL Type TC-ER1—E-2 Color Code Product Construction Conductor:

• 14 AWG thru 10 AWG fully annealed stranded tinned copper per ASTM B33 • Class B stranding per ASTM B8

Insulation:

• Flame-retardant Ethylene Propylene Rubber (FR-EPR) Type II • Color-coded: per ICEA Method 1; Table E-2 (Does not include white or green)

CATALOG NUMBER

COPPER MINIMUM AVG. MINIMUM AVG. WEIGHT NET WEIGHT INSULATION JACKET NOMINAL NO. COND. THICKNESS CABLE O.D. LBS/ OF SIZE COND. THICKNESS LBS/ COND. (AWG) STRAND inCHES mm INCHES mm INCHES mm 1000 FT kg/km 1000 FT kg/km

14 AWG MULTI CONDUCTORS 279560 305320* 280180 280190 279870 280200 280210 279880 279580 279590 347080* 279600*

2 Flat 2 3 4 5 7 9 12 19 25 30 37

14 14 14 14 14 14 14 14 14 14 14 14

7/.0242 7/.0242 7/.0242 7/.0242 7/.0242 7/.0242 7/.0242 7/.0242 7/.0242 7/.0242 7/.0242 7/.0242

279840 2 Flat 2 307690* 280170 3+ Grnd 3 280300 4 280310 5 280320 7 279890 9 280330 12 280340 19 279610 25 295400* 30 347100* 37 301870

12 12 12 12 12 12 12 12 12 12 12 12 12

7/.0305 7/.0305 7/.0305 7/.0305 7/.0305 7/.0305 7/.0305 7/.0305 7/.0305 7/.0305 7/.0305 7/.0305 7/.0305

2 Flat 279570 2 305340* 279680 3+ Grnd 3 280410 4 279900 5 279620 7 279630 9 279640 12 279650

10 10 10 10 10 10 10 10 10

7/.0385 7/.0385 7/.0385 7/.0385 7/.0385 7/.0385 7/.0385 7/.0385 7/.0385

0.030 0.030 0.030 0.030 0.030 0.030 0.030 0.030 0.030 0.030 0.030 0.030

0.76 0.76 0.76 0.76 0.76 0.76 0.76 0.76 0.76 0.76 0.76 0.76

0.045 0.045 0.045 0.045 0.045 0.045 0.060 0.060 0.060 0.080 0.080 0.080

1.14 1.14 1.14 1.14 1.14 1.14 1.52 1.52 1.52 2.03 2.03 2.03

.365 x .230 9.30 x 5.80

0.370 0.390 0.425 0.465 0.505 0.620 0.700 0.815 0.935 1.030 1.110

9.40 9.91 10.80 11.81 12.83 15.75 17.78 20.70 23.75 26.16 28.19

26 26 39 53 66 92 118 158 250 323 387 466

38 39 59 78 98 137 176 235 372 481 576 694

61 71 92 115 139 173 240 301 468 624 747 875

91 106 137 171 207 257 357 448 696 929 1112 1302

40 41 85 64 85 106 149 191 247 391 515 618 762

60 82 61 94 127 148 95 124 127 157 158 191 221 268 285 337 368 428 582 688 767 854 920 1002 1134 1240

122 140 220 185 234 284 399 502 637 1024 1271 1491 1845

64 65 134 100 134 167 234 295 402

95 97 199 150 199 249 349 440 598

168 190 335 256 348 423 567 691 696

12 AWG MULTI CONDUCTORS 0.030 0.030 0.030 0.030 0.030 0.030 0.030 0.030 0.030 0.030 0.030 0.030 0.030

0.76 0.76 0.76 0.76 0.76 0.76 0.76 0.76 0.76 0.76 0.76 0.76 0.76

0.045 0.045 0.045 0.045 0.045 0.045 0.060 0.060 0.060 0.080 0.080 0.080 0.080

1.14 1.14 1.14 1.14 1.14 1.14 1.52 1.52 1.52 2.03 2.03 2.03 2.03

.400 x .245 10.20 x 6.20

0.410 0.410 0.435 0.475 0.520 0.595 0.695 0.765 0.940 1.095 1.150 1.240

10.41 10.41 11.05 12.07 13.21 15.11 17.65 19.43 23.88 27.81 29.21 31.50

10 AWG MULTI CONDUCTORS 0.030 0.030 0.030 0.030 0.030 0.030 0.030 0.030 0.030

0.76 0.76 0.76 0.76 0.76 0.76 0.76 0.76 0.76

0.045 0.045 0.045 0.045 0.060 0.060 0.060 0.060 0.080

1.14 1.14 1.14 1.14 1.52 1.52 1.52 1.52 2.03

.445 x .270 11.30 x 6.90

0.455 0.485 0.485 0.560 0.615 0.670 0.760 0.905

11.56 12.32 12.32 14.22 15.62 17.02 19.30 22.99

Dimensions and weights are nominal; subject to industry tolerances. *Non-stock item, minimum runs apply. Please consult Customer Service for price and delivery. 1Approved as TYPE TC-ER for Exposed Run applications of 3 or more conductors as defined by NEC.

113 128 225 172 234 284 381 464 651

Jacket:

• Flame-retardant thermoplastic Chlorinated Polyethylene (CPE)

Print

• GENERAL CABLE® (WC) FREP® XX/C XXAWG EPR/CPE (UL) Type TC-ER1 XHHW-2 CDRS 90°C WET or DRY 600V DIR BUR SUN RES DAY/ MONTH/YEAR OF MFG sequential footage mark

Options:

• 2kV version • Bare copper conductor • Class C stranding • E-1 Color Code—See Spec 4310 • Overall shielded multi conductor • Flame-retardant Cross-Linked Polyethene (FRXLPE) insulation • Thermoplastic Low-Smoke, Zero-Halogen (LSZH) jacket • Other constructions available upon request

Applications:

• In free air, raceways or direct burial • In wet or dry locations • Permitted for Exposed Run ‘ER’ use in accordance with NEC for 3 or more conductors • Approved for direct burial, Class I, Div. 2 industrial hazardous locations per NEC

Features:

• Rated at 90˚C wet or dry • Ripcord applied to all cables with jacket thickness of 60 mils or less • Excellent physical, thermal and electrical properties • Sunlight- and weather-resistant • Excellent moisture resistance • Excellent resistance to compression cuts and heat deformation • Low coefficient of friction for easy pulling • Excellent flame resistance—burns to ash; does not exhibit thermoplastic drip • Excellent low temperature cold bend characteristics • Meets cold bend test at -40˚C • Meets the crush and impact requirements of Type MC cable for 3 or more conductors

Compliances:

Industry Compliances: • UL 44 Type XHHW-2 • UL 1277 Type TC-ER for 3 or more conductors • UL 1581 • ICEA S-73-532 Flame Tests Compliances: • UL 1581 VW-1 • UL 1277 • IEEE 383 • IEEE 1202 • CSA FT-4 • ICEA T-29-520 Other Compliances: • EPA 40 CFR, Part 261 for leachable lead content per TCLP • OSHA acceptable

Packaging:

• Material cut to length and shipped on non-returnable wood reels

Phone: 888-593-3355 www.generalcable.com


SPEC 4310

January, 2008

FREP

®

FR-EPR/CPE, Control, Unshielded 600V, UL Type TC-ER1—E-1 Color Code Product Construction Conductor:

• 14 AWG thru 10 AWG fully annealed stranded tinned copper per ASTM B33 • Class B stranding per ASTM B8

Insulation:

• Flame-retardant Ethylene Propylene Rubber (FR-EPR) Type II • Color-coded per ICEA Method 1; Table E-1 (Includes white or green)

CATALOG NUMBER

COPPER MINIMUM AVG. MINIMUM AVG. WEIGHT NET WEIGHT INSULATION JACKET NOMINAL NO. COND. THICKNESS CABLE O.D. LBS/ OF SIZE COND. THICKNESS LBS/ COND. (AWG) STRAND inCHES mm INCHES mm INCHES mm 1000 FT kg/km 1000 FT kg/km

14 AWG MULTI CONDUCTORS 280590 280230 280240 280250 280260 280270 280280 280290* 385350* 385360* 385370*

2 Flat 3 4 5 7 9 12 19 25 30 37

14 14 14 14 14 14 14 14 14 14 14

7/.0242 7/.0242 7/.0242 7/.0242 7/.0242 7/.0242 7/.0242 7/.0242 7/.0242 7/.0242 7/.0242

0.030 0.030 0.030 0.030 0.030 0.030 0.030 0.030 0.030 0.030 0.030

0.76 0.76 0.76 0.76 0.76 0.76 0.76 0.76 0.76 0.76 0.76

0.045 0.045 0.045 0.045 0.045 0.060 0.060 0.060 0.080 0.080 0.080

1.14 1.14 1.14 1.14 1.14 1.52 1.52 1.52 2.03 2.03 2.03

.365 x .230 9.30 x 5.80

0.390 0.425 0.465 0.505 0.620 0.700 0.815 0.935 1.030 1.110

9.91 10.80 11.81 12.83 15.75 17.78 20.70 23.75 26.16 28.19

26 39 53 66 92 118 158 250 323 387 466

38 59 78 98 137 176 235 372 481 576 694

61 92 115 139 173 240 301 468 624 747 875

91 137 171 207 257 357 448 696 929 1112 1302

40 41 64 85 106 149 191 247 391 515 618 762

60 82 61 94 95 124 127 157 158 191 221 268 285 337 368 428 582 688 767 854 920 1002 1134 1240

122 140 185 234 284 399 502 637 1024 1271 1491 1845

64 65 100 134 167 234 295 402

95 97 150 199 249 349 440 598

168 190 256 348 423 567 691 969

12 AWG MULTI CONDUCTORS 279850 2 Flat 2 280350* 3 280360 4 279910 5 280370 7 280380 9 280390* 12 280400 19 383930* 25 383940* 30 383950* 37 330800*

12 12 12 12 12 12 12 12 12 12 12 12

7/.0305 7/.0305 7/.0305 7/.0305 7/.0305 7/.0305 7/.0305 7/.0305 7/.0305 7/.0305 7/.0305 7/.0305

280600* 280420* 279920 279930 330990* 280430* 382880* 383970*

10 10 10 10 10 10 10 10

7/.0385 7/.0385 7/.0385 7/.0385 7/.0385 7/.0385 7/.0385 7/.0385

0.030 0.030 0.030 0.030 0.030 0.030 0.030 0.030 0.030 0.030 0.030 0.030

0.76 0.76 0.76 0.76 0.76 0.76 0.76 0.76 0.76 0.76 0.76 0.76

0.045 0.045 0.045 0.045 0.045 0.060 0.060 0.060 0.080 0.080 0.080 0.080

1.14 1.14 1.14 1.14 1.14 1.52 1.52 1.52 2.03 2.03 2.03 2.03

.400 x .245 10.20 x 6.20

0.410 0.435 0.475 0.520 0.595 0.695 0.765 0.940 1.095 1.150 1.240

10.41 11.05 12.07 13.21 15.11 17.65 19.43 23.88 27.81 29.21 31.50

10 AWG MULTI CONDUCTORS 2 Flat 2 3 4 5 7 9 12

0.030 0.030 0.030 0.030 0.030 0.030 0.030 0.030

0.76 0.76 0.76 0.76 0.76 0.76 0.76 0.76

0.045 0.045 0.045 0.060 0.060 0.060 0.060 0.080

1.14 1.14 1.14 1.52 1.52 1.52 1.52 2.03

.445 x .270 11.30 x 6.90

0.455 0.485 0.560 0.615 0.670 0.760 0.950

11.56 12.32 14.22 15.62 17.02 19.30 22.99

Dimensions and weights are nominal; subject to industry tolerances. *Non-stock item, minimum runs apply. Please consult Customer Service for price and delivery. 1Approved as TYPE TC-ER for Exposed Run applications of 3 or more conductors as defined by NEC.

113 128 172 234 284 381 464 651

Jacket:

• Flame-retardant thermoplastic Chlorinated Polyethylene (CPE)

Print

• GENERAL CABLE® (WC) FREP® XX/C XXAWG EPR/CPE (UL) Type TC-ER1 XHHW-2 CDRS 90°C WET or DRY 600V DIR BUR SUN RES DAY/ MONTH/YEAR OF MFG sequential footage mark

Options:

• 2kV version • Bare copper conductor • Class C stranding • E-2 Color Code—See Spec 4300 • Overall shielded multi conductor • Flame-retardant Cross-Linked Polyethene (FR-XLPE) insulation • Thermoplastic Low-Smoke, Zero-Halogen (LSZH) jacket • Other constructions available upon request

Applications:

• In free air, raceways or direct burial • In wet or dry locations • Permitted for Exposed Run ‘ER’ use in accordance with NEC for 3 or more conductors • Approved for direct burial, Class I, Div. 2 industrial hazardous locations per NEC

Features:

• Rated at 90˚C wet or dry • Ripcord applied to all cables with jacket thickness of 60 mils or less • Excellent physical, thermal and electrical properties • Sunlight- and weather-resistant • Excellent moisture resistance • Excellent resistance to compression cuts and heat deformation • Low coefficient of fri ction for easy pulling • Excellent flame resistance—burns to ash; does not exhibit thermoplastic drip • Excellent low temperature cold bend characteristics • Meets cold bend test at -40˚C • Meets the crush and impact requirements of Type MC cable for 3 or more conductors

Compliances:

Industry Compliances: • UL 44 Type XHHW-2 • UL 1277 Type TC-ER for 3 or more conductors • UL 1581 • ICEA S-73-532 • ICEA S-95-658/NEMA WC70 Flame Tests Compliances: • UL 1581 VW-1 • UL 1277 • IEEE 383 • IEEE 1202 • CSA FT-4 • ICEA T-29-520 Other Compliances: • EPA 40 CFR, Part 261 for leachable lead content per TCLP • OSHA acceptable

Packaging:

• Material cut to length and shipped on non-returnable wood reels

Phone: 888-593-3355 www.generalcable.com


SPEC 4325

January, 2008

FREP

®

FR-EPR/CPE, Control, Shielded 600V, UL Type TC-ER1, Overall Shielded—E-2 Color Code Product Construction Conductor:

• 16 AWG thru 10 AWG fully annealed stranded tinned copper per ASTM B33 • Class B stranding per ASTM B8

Insulation:

• Flame-retardant Ethylene Propylene Rubber (FR-EPR) Type II • Color-coded per ICEA Method 1; Table E-2 (Does not include white or green)

CATALOG NUMBER

COPPER MINIMUM AVG. MINIMUM AVG. WEIGHT NET WEIGHT INSULATION JACKET NOMINAL NO. COND. THICKNESS CABLE O.D. LBS/ OF SIZE COND. THICKNESS LBS/ COND. (AWG) STRAND inCHES mm INCHES mm INCHES mm 1000 FT kg/km 1000 FT kg/km

2 3

16 16

7/.0192 0.025 0.64 0.045 1.14 0.320 8.13 7/.0192 0.025 0.64 0.045 1.14 0.335 8.51

19 27

28 40

52 66

77 98

43 63 82 101 140 180 238 375 484 579 696

74 95 118 142 176 243 304 471 627 750 878

110 141 176 211 262 362 452 701 933 1116 1307

OVERALL SHIELDED MULTI CONDUCTORS 14 AWG CONDUCTORS 280980* 354800* 305300* 354810* 354820* 367120* 354830* 305360* 367130* 367140* 367150*

2 3 4 5 7 9 12 19 25 30 37

14 14 14 14 14 14 14 14 14 14 14

7/.0242 7/.0242 7/.0242 7/.0242 7/.0242 7/.0242 7/.0242 7/.0242 7/.0242 7/.0242 7/.0242

0.030 0.030 0.030 0.030 0.030 0.030 0.030 0.030 0.030 0.030 0.030

0.76 0.76 0.76 0.76 0.76 0.76 0.76 0.76 0.76 0.76 0.76

0.045 0.045 0.045 0.045 0.045 0.060 0.060 0.060 0.080 0.080 0.080

1.14 1.14 1.14 1.14 1.14 1.52 1.52 1.52 2.03 2.03 2.03

0.375 0.395 0.430 0.470 0.510 0.625 0.705 0.820 0.940 1.035 1.115

9.53 10.03 10.92 11.94 12.95 15.88 17.91 20.83 25.53 26.29 28.32

29 42 55 68 94 121 160 252 325 389 468

OVERALL SHIELDED MULTI CONDUCTORS 12 AWG CONDUCTORS 367160* 367170* 326650* 367180* 326660* 367190* 326640* 326670* 367200* 367210* 367220*

2 3 4 5 7 9 12 19 25 30 37

12 12 12 12 12 12 12 12 12 12 12

7/.0305 7/.0305 7/.0305 7/.0305 7/.0305 7/.0305 7/.0305 7/.0305 7/.0305 7/.0305 7/.0305

0.030 0.030 0.030 0.030 0.030 0.030 0.030 0.030 0.030 0.030 0.030

0.76 0.76 0.76 0.76 0.76 0.76 0.76 0.76 0.76 0.76 0.76

0.045 0.045 0.045 0.045 0.060 0.060 0.060 0.080 0.080 0.080 0.080

1.14 1.14 1.14 1.14 1.52 1.52 1.52 2.03 2.03 2.03 2.03

0.415 0.440 0.480 0.525 0.600 0.700 0.770 0.945 1.100 1.155 1.245

10.45 11.18 12.19 13.34 15.24 17.78 19.56 24.00 27.94 29.80 31.62

43 66 87 108 151 193 249 393 517 620 764

2 3 4 5 7 9 12

10 10 10 10 10 10 10

7/.0385 7/.0385 7/.0385 7/.0385 7/.0385 7/.0385 7/.0385

0.030 0.030 0.030 0.030 0.030 0.030 0.030

0.76 0.76 0.76 0.76 0.76 0.76 0.76

0.045 0.045 0.060 0.060 0.060 0.060 0.080

1.14 1.14 1.52 1.52 1.52 1.52 2.03

0.460 0.490 0.565 0.620 0.675 0.765 0.910

11.68 12.45 14.35 15.75 17.15 19.43 23.11

68 103 136 170 237 298 404

Jacket: Print

• GENERAL CABLE® (WC) SHIELDED FREP® XX/C XXAWG EPR/CPE (UL) Type TC-ER1 XHHW-2 CDRS 90˚C WET or DRY 600V DIR BUR SUN RES DAY/MONTH/YEAR OF MFG sequential footage mark

Options:

• 2kV version • Bare copper conductor • Class C stranding • E-1 Color Code • Unshielded multi conductors • Flame-retardant Cross-Linked Polyethene (FR-XLPE) insulation • Thermoplastic Low-Smoke, Zero-Halogen (LSZH) jacket • Other constructions available upon request

Applications:

• In free air, raceway and direct burial • In wet or dry locations • Permitted for Exposed Run ‘ER’ use in accordance with NEC for 3 or more conductors • Approved for direct burial, Class I, Div. 2 industrial hazardous locations per NEC

Features: 64 97 144 98 127 189 129 160 238 162 194 289 225 271 403 287 340 506 371 431 641 585 691 1028 769 857 1275 923 1005 1496 1137 1243 1850

OVERALL SHIELDED MULTI CONDUCTORS 10 AWG CONDUCTORS 311900* 367230* 311910* 367240* 367250* 367260* 367270*

Overall shielded multi-conductor cable • Overall shield is Flexfoil® aluminum/polyester in contact with stranded tinned copper drain wire • Flame-retardant Thermoplastic Chlorinated Polyethylene (CPE)

OVERALL SHIELDED MULTI CONDUCTORS 16 AWG CONDUCTORS 280470 280490

Shield:

101 155 202 253 353 443 601

Dimensions and weights are nominal; subject to industry tolerances. *Non-stock item, minimum runs apply. Please consult Customer Service for price and delivery. 1Approved as TYPE TC-ER for Exposed Run applications of 3 or more conductors as defined by NEC.

131 175 237 287 384 467 654

195 260 353 427 571 695 973

• Rated at 90˚C wet or dry • Ripcord applied to all cables with jacket thickness of 60 mils or less • Excellent physical, thermal and electrical properties • Sunlight- and weather-resistant • Excellent moisture resistance • Excellent resistance to compression cuts and heat deformation • Low coefficient of friction for easy pulling • Excellent flame resistance—burns to ash; does not exhibit thermoplastic drip • Excellent low temperature cold bend characteristics • Meets cold bend test at -40˚C • Meets the crush and impact requirements of Type MC cable for 3 conductors or more

Compliances:

Industry Compliances: • UL 44 Type XHHW-2 • UL 1277 Type TC-ER for 3 or more conductors • UL 1581 • ICEA S-73-532 Flame Tests Compliances: • UL 1581 VW-1 • UL 1277 • IEEE 383 • IEEE 1202 • CSA FT-4 • ICEA T-29-520 Other Compliances: • EPA 40 CFR, Part 261 for leachable lead content per TCLP • OSHA acceptable

Packaging:

• Material cut to length and shipped on non-returnable wood reels

Phone: 888-593-3355 www.generalcable.com


SPEC 4350

January, 2009

FREP

®

FR-EPR/CPE, Low-Voltage Power, Unshielded 600V, UL Type TC-ER1—Method 4 Color Code Features (cont’d.):

Product Construction Conductor:

• Excellent moisture resistance • Excellent resistance to crush, compression cuts and heat deformation • Excellent low temperature cold bend characteristics • Excellent flame resistance—burns to ash; does not exhibit thermoplastic drip • Low coefficient of friction for easy pulling • Sunlight- and weather-resistant • Meets cold bend test at -40˚C • Meets the crush and impact requirements of Type MC cable for 2 AWG and larger

Options:

• 2kV version • Bare copper conductor • Class C stranding • E-1 or E-2 Color Code • Insulated ground conductors • Overall shielded multi conductors • Flame-retardant Cross-Linked Polyethylene (FR-XLPE) insulation • Flame-retardant, Thermoplastic Low-Smoke, Zero-Halogen (LSZH) jacket • Other constructions available upon request

• 14 AWG thru 750 kcmil tinned, annealed copper per ASTM B33 • Class B stranding per ASTM B8

Insulation:

• Flame-retardant Ethylene Propylene Rubber (FR-EPR) Type II • Color-coded per ICEA Method 4; Individual conductors colored black with conductor number surface printed in contrasting ink

• In free air, raceways or direct burial • In wet or dry locations • Permitted for Exposed Run ‘ER’ use in accordance with NEC for 3 or more conductors • Permitted for use in Class I Division 2 industrial hazardous locations per NEC

• Uninsulated tinned annealed copper per ASTM B3 • Class B stranding per ASTM B8

Jacket:

• Flame-retardant thermoplastic Chlorinated Polyethylene (CPE)

Features:

Print:

NO. OF COND.

383830* 383840* 383850* 279660 279670 283210 300380 283200 295390* 293600 295890* 297730* 356740* 283220 294530* 284560 295360* 325700* 365750* 325110 346980* 300780* 346990* 325120 347000* 298020 14407.546500* 14407.247000* 14407.547000*

3 3 3 3 4 3 4 3 4 3 4 3 4 3 4 3 4 3 4 3 4 3 4 3 4 3 4 3 4

14 12 10 8 8 6 6 4 4 2 2 1 1 1/0 1/0 2/0 2/0 3/0 3/0 4/0 4/0 250 250 350 350 500 500 750 750

Packaging:

• Rated at 90˚C wet or dry • Ripcord applied to all cables with jacket thickness of 60 mils or less • Excellent physical, thermal and electrical properties

• General Cable® (WC) OR (MI) FREP® XX/C XXAWG WITH GRND EPR/CPE (UL) TYPE TC-ER1 XHHW-2 CDRS 90˚C WET OR DRY 600V DIR BUR SUN RES DAY/MONTH/YEAR OF MFG SEQUENTIAL FOOTAGE MARK

CATALOG NUMBER

Industry Compliances: • UL 44 Type XHHW-2 • UL 1277 Type TC-ER • UL 1581 • ICEA S-95-658/NEMA WC70 Flame Tests Compliances: • UL 1581 VW-1 • UL 1277 • IEEE 383 • IEEE 1202 • CSA FT-4 • ICEA T-29-520 Other Compliances: • EPA 40 CFR, Part 261 for leachable lead content per TCLP • OSHA acceptable

Applications:

Ground:

COND. SIZE (AWG/ kcmil)

Compliances:

GROUND WIRE SIZE (AWG)

COND. STRAND 7/.0242 7/.0305 7/.0385 7/.0486 7/.0486 7/.0612 7/.0612 7/.0772 7/.0772 7/.0974 7/.0974 19/.0664 19/.0664 19/.0745 19/.0745 19/.0837 19/.0837 19/.0940 19/.0940 19/.1055 19/.1055 37/.0822 37/.0822 37/.0973 37/.0973 37/.1162 37/.1162 61/.1109 61/.1109

MINIMUM AVG. INSULATION THICKNESS INCHES

mm

• Material cut to length and shipped on non-returnable wood reels

MINIMUM AVG. JACKET THICKNESS NOMINAL CABLE O.D. INCHES

mm

INCHES

COPPER WEIGHT

mm

LBS/ 1000 FT

10.92 12.19 14.35 16.64 18.29 18.80 20.07 22.35 24.13 25.65 27.69 28.45 31.37 31.12 33.78 33.02 36.58 36.07 39.88 39.12 45.47 44.70 48.64 49.78 5499 57.02 62.87 71.37 79.12

55 87 136 190 242 297 384 442 578 703 919 872 1136 1069 1413 1340 1760 1717 2245 2130 2796 2494 3282 3474 4577 4934 6509 7278 9712

NET WEIGHT

kg/km

LBS/ 1000 FT

kg/km

82 129 202 283 360 442 571 658 861 1046 1368 1298 1691 1591 2103 1994 2619 2555 3341 3170 4161 3712 4884 5170 6811 7343 9687 10831 14453

118 160 237 314 393 456 561 642 822 979 1235 1021 1521 1439 1820 1720 2208 2176 2788 2614 3495 3184 4019 4187 5436 5847 7607 9145 11805

176 238 353 467 585 679 835 955 1223 1457 1838 1594 2264 2142 2709 2560 3286 3238 3405 3890 5201 4738 5981 6231 8090 8702 11321 13610 17569

14 AWG - 750 kcmil MULTI CONDUCTORS 14 12 10 10 10 8 8 8 8 6 6 6 6 6 6 6 6 4 4 4 4 4 4 3 3 2 2 1 1

0.030 0.030 0.030 0.045 0.045 0.045 0.045 0.045 0.045 0.045 0.045 0.055 0.055 0.055 0.055 0.055 0.055 0.055 0.055 0.055 0.055 0.065 0.065 0.065 0.065 0.065 0.065 0.080 0.080

0.76 0.76 0.76 1.14 1.14 1.14 1.14 1.14 1.14 1.14 1.14 1.40 1.40 1.40 1.40 1.40 1.40 1.40 1.40 1.40 1.40 1.65 1.65 1.65 1.65 1.65 1.65 2.03 2.03

0.045 0.045 0.060 0.060 0.060 0.060 0.060 0.080 0.080 0.080 0.080 0.080 0.080 0.080 0.080 0.080 0.080 0.080 0.080 0.080 0.110 0.110 0.110 0.110 0.110 0.110 0.110 0.140 0.140

1.14 1.14 1.52 1.52 1.52 1.52 1.52 2.03 2.03 2.03 2.03 2.03 2.03 2.03 2.03 2.03 2.03 2.03 2.03 2.03 2.79 2.79 2.79 2.79 2.79 2.79 2.79 3.56 3.56

0.430 0.480 0.565 0.655 0.720 0.740 0.790 0.880 0.950 1.010 1.090 1.120 1.235 1.225 1.330 1.300 1.440 1.420 1.570 1.540 1.790 1.760 1.915 1.960 2.165 2.245 2.475 2.810 3.115

Dimensions and weights are nominal; subject to industry tolerances. *Non-stock item, minimum runs apply. Please consult Customer Service for price and delivery. 1Approved as TYPE TC-ER for Exposed Run applications of 3 or more conductors as defined by NEC.

Phone: 888-593-3355 www.generalcable.com


SPEC 4400

January, 2008

Arctic-Flex

®

XLPE/ARCTIC-PVC, Control, Unshielded 600V, UL Type TC-ER1, CSA Type RW90 XLPE, CSA TYPE TC Product Construction Conductor:

• 14 AWG thru 10 AWG tinned, annealed copper per ASTM B3 • Class B stranding per ASTM B8

Insulation:

CATALOG NUMBER

COPPER MINIMUM AVG. MINIMUM AVG. WEIGHT NET WEIGHT INSULATION JACKET NOMINAL NO. COND. THICKNESS CABLE O.D. LBS/ OF SIZE COND. THICKNESS LBS/ COND. (AWG) STRAND inCHES mm INCHES mm INCHES mm 1000 FT kg/km 1000 FT kg/km

14 AWG MULTI CONDUCTORS 347340* 347350* 347360* 347370* 347380* 347390* 347400* 347410* 347420* 347430* 347440*

2 3 4 5 7 9 12 19 25 30 37

14 14 14 14 14 14 14 14 14 14 14

7/.0242 7/.0242 7/.0242 7/.0242 7/.0242 7/.0242 7/.0242 7/.0242 7/.0242 7/.0242 7/.0242

347450* 347460* 347470* 347480* 347490* 347500* 347510* 347520* 347530* 347540* 347550*

2 3 4 5 7 9 12 19 25 30 37

12 12 12 12 12 12 12 12 12 12 12

7/.0305 7/.0305 7/.0305 7/.0305 7/.0305 7/.0305 7/.0305 7/.0305 7/.0305 7/.0305 7/.0305

0.030 0.030 0.030 0.030 0.030 0.030 0.030 0.030 0.030 0.030 0.030

0.76 0.76 0.76 0.76 0.76 0.76 0.76 0.76 0.76 0.76 0.76

0.045 0.045 0.045 0.045 0.045 0.060 0.060 0.060 0.060 0.080 0.080

1.14 1.14 1.14 1.14 1.14 1.52 1.52 1.52 1.52 2.03 2.03

0.405 0.390 0.425 0.465 0.590 0.620 0.680 0.800 0.985 1.050 1.130

10.29 9.91 10.80 11.81 14.99 15.75 17.27 20.32 25.02 26.67 28.70

25 40 53 66 93 119 159 252 323 387 490

37 59 79 99 138 177 237 375 481 576 729

71 90 113 140 176 245 302 460 641 740 888

106 134 168 208 262 365 449 685 954 1101 1322

41 65 86 108 150 193 258 403 515 618 741

61 96 143 96 125 186 128 157 234 160 191 284 224 260 387 288 340 506 385 429 638 600 681 1013 767 885 1317 920 1005 1496 1103 1185 1764

67 101 135 167 234 295 402

100 150 200 249 349 440 598

12 AWG MULTI CONDUCTORS 0.030 0.030 0.030 0.030 0.030 0.030 0.030 0.030 0.030 0.030 0.030

0.76 0.76 0.76 0.76 0.76 0.76 0.76 0.76 0.76 0.76 0.76

0.045 0.045 0.045 0.045 0.060 0.060 0.060 0.080 0.080 0.080 0.080

1.14 1.14 1.14 1.14 1.52 1.52 1.52 2.03 2.03 2.03 2.03

0.410 0.435 0.475 0.520 0.595 0.695 0.780 0.930 1.095 1.150 1.240

10.41 11.05 12.07 13.21 15.11 17.65 19.81 23.62 27.81 29.21 31.50

10 AWG MULTI CONDUCTORS 347560* 347570* 347580* 347590* 347600* 347610* 347620*

2 3 4 5 7 9 12

10 10 10 10 10 10 10

7/.0385 7/.0385 7/.0385 7/.0385 7/.0385 7/.0385 7/.0385

0.030 0.030 0.030 0.030 0.030 0.030 0.030

0.76 0.76 0.76 0.76 0.76 0.76 0.76

0.045 0.045 0.060 0.060 0.060 0.060 0.080

1.14 1.14 1.52 1.52 1.52 1.52 2.03

0.455 0.485 0.515 0.615 0.670 0.785 0.895

11.56 12.32 13.08 15.62 17.02 19.94 22.73

Dimensions and weights are nominal; subject to industry tolerances. *Non-stock item, minimum runs apply. Please consult Customer Service for price and delivery. 1Approved as TYPE TC-ER for Exposed Run applications of 3 or more conductors as defined by NEC.

130 168 229 281 377 479 644

193 250 341 418 561 713 958

• Flame-retardant Cross-Linked Polyethylene (XLPE) Color-coded per CSA Standard C22.2 No. 38 as follows: Number of color coding of circuit conductors No. of Cond. Color Code 2 blk, wht 3 blk, red, blu 4 blk, red, blu, wht ≥5 all black All conductors for all constructions are alphanumeric printed

Jacket:

• Flame-retardant and sunlight-resistant Arcticgrade Polyvinyl Chloride (PVC)

Print:

• GENERAL CABLE® (WC) (UL) TYPE TC-ER1 ARCTIC-FLEX® XX/C XXAWG FR-XLP/PVC XHHW-2 CDRS 90C WET OR DRY SUN RES DIR BUR 600V - (CSA) TYPE RW90 XLPE -40C TC FT-4 600V PLUS DAY/MONTH/YEAR OF MFG SEQUENTIAL FOOTAGE MARK

Options:

• Bare copper, class C stranding • Uninsulated ground (bonding) conductor • Optional color code as specified per CSA standard C22.2 No. 38 for two to four conductor cable • Non-UL 1000 volt CSA Type RW90 XLPE, CSA Type TC • Other constructions available upon request

Applications:

• Industrial lighting, control and signaling circuits • Approved for direct burial, Class I, Div. 2 industrial hazardous locations per NEC for UL Type TC cables. In Canada, protection may be required by inspection authority per Canadian electrical code • Permitted for Exposed Run ‘ER’ use in accordance with NEC for 3 or more conductors • Approved for cable in tray, industrial hazardous locations, Class I, Zone 2, and Class II, Division 2 per CEC rules 18-156 and 18-252 when used with certified HL glands

Features:

• Rated 90˚C wet or dry • Ripcord applied to all cables with jacket thickness of 60 mils or less • Meets CSA cold impact test at -40˚C • Meets ICEA and CSA cold bend test at -65˚C • Meets the crush and impact requirements of Type MC cable

Compliances:

Industry Compliances: • ICEA S-73-532 • ICEA S-95-658/NEMA WC70 • UL 44 Type XHHW-2 • UL 1277 Type TC-ER for 3 or more conductors • UL 1581 • CSA C22.2 No. 38 XLPE RW90 • CSA C22.2 No. 230 Type TC Flame Tests Compliances: • UL 1581 VW-1 • UL 1277 • IEEE 383 • CSA FT-4 Other Compliances: • EPA 40 CFR, Part 261 for leachable lead content per TCLP • OSHA acceptable

Packaging:

• Material cut to lengths and shipped on nonreturnable wood reels

Phone: 888-593-3355 www.generalcable.com


SPEC 4450

January, 2009

Arctic-Flex

®

XLPE/ARCTIC-PVC, Low-Voltage Power, Unshielded 600V, UL Type TC-ER1, CSA Type RW90 XLPE, CSA TYPE TC Applications (cont’d.):

• Approved for cable in tray, industrial hazardous locations, Class I, Zone 2, and Class II, Division 2 per CEC rules 18-156 and 18-252 when used with certified HL cable glands

Features:

Product Construction Conductor:

Print:

• GENERAL CABLE® (WC) (UL) TYPE TC-ER1 ARCTIC-FLEX® XX/C XXAWG WITH GRND FR-XLP/PVC XHHW-2 CDRS 90C WET OR DRY SUN RES DIR BUR 600V (CSA) TYPE RW90 XLPE -40C TC FT-4 600V PLUS DAY/MONTH/YEAR OF MFG SEQUENTIAL FOOTAGE MARK

• 8 AWG thru 500 kcmil bare, annealed copper per ASTM B3 • Class B stranding per ASTM B8

Insulation:

Applications:

• Industrial power and control circuits • Permitted for Exposed Run ‘ER’ use in accordance with NEC for 3 or more conductors • Approved for direct burial, Class I, Div. 2 industrial hazardous locations per NEC for UL Type TC cables. In Canada protection may be required by inspection authority per Canadian electrical code

• Uninsulated bare annealed copper per ASTM B3 • Class B stranding per ASTM B8

Jacket:

• Flame-retardant and sunlight-resistant Arctic-grade Polyvinyl Chloride (PVC)

NO. OF COND.

Industry Compliances: • UL 44 Type XHHW-2 • UL 1277 Type TC-ER for 3 or more conductors • UL 1581 • ICEA S-95-658/NEMA WC70 • CSA C22.2 No. 38 RW90 XLPE • CSA C22.2 No. 230 Type TC Flame Tests Compliances: • UL 1581 VW-1 • UL 1277 • IEEE 383 • IEEE 1202 • CSA FT-4 Other Compliances: • EPA 40 CFR, Part 261 for leachable lead content per TCLP • OSHA acceptable

• Tinned copper • Class C stranding • Overall shielded multi conductors • Optional Color Code as specified per CSA standard C22.2 No. 38 for two to four conductor cable • Non-UL 1000 volt CSA Type RW90 XLPE, CSA Type TC • Other constructions are available upon request

Ground (Bonding) Conductor:

COND. SIZE (AWG/ kcmil)

Compliances:

Options:

• Flame-retardant Cross-Linked Polyethylene (XLPE) Color-coded per CSA Standard C22.2 No. 38 as follows: Number of color coding of circuit conductors No. of Cond. Color Code 2 blk, wht 3 blk, red, blu 4 blk, red, blu, wht ≥5 all black All conductors for all constructions are alphanumeric printed

CATALOG NUMBER

• Rated 90˚C wet or dry • Ripcord applied to all cables with jacket thickness of 60 mils or less • Meets CSA cold impact test at -40˚C • Meets ICEA and CSA cold bend test at -65˚C • Meets the crush and impact requirements of Type MC cable

GROUND WIRE SIZE (AWG)

COND. STRAND

MINIMUM AVG. INSULATION THICKNESS INCHES

mm

Packaging:

• Material cut to lengths and shipped on non-returnable wood reels

MINIMUM AVG. JACKET THICKNESS NOMINAL CABLE O.D. INCHES

mm

INCHES

mm

COPPER WEIGHT LBS/ 1000 FT kg/km

NET WEIGHT LBS/ 1000 FT kg/km

8 AWG - 500 kcmil MULTI CONDUCTORS 347150* 347160* 347170* 347180* 347190* 347200* 347210* 347220* 371280* 371290* 347230* 347240* 347250* 347260* 371300* 371310* 347270* 347280* 347290* 347300* 347310* 347320* 347330*

3 4 3 4 3 4 3 4 3 4 3 4 3 4 3 4 3 4 3 4 3 4 3

8 8 6 6 4 4 2 2 1 1 1/0 1/0 2/0 2/0 3/0 3/0 4/0 4/0 250 250 350 350 500

7/.0486 7/.0486 7/.0612 7/.0612 7/.0772 7/.0772 7/.0974 7/.0974 19/.0664 19/.0664 19/.0745 19/.0745 19/.0837 19/.0837 19/.0940 19/.0940 19/.1055 19/.1055 37/.0822 37/.0822 37/.0973 37/.0973 37/.1162

10 10 8 8 8 8 6 6 6 6 6 6 6 6 4 4 4 4 4 4 3 3 2

0.045 0.045 0.045 0.045 0.045 0.045 0.045 0.045 0.055 0.055 0.055 0.055 0.055 0.055 0.055 0.055 0.055 0.055 0.065 0.065 0.065 0.065 0.065

1.14 1.14 1.14 1.14 1.14 1.14 1.14 1.14 1.40 1.40 1.40 1.40 1.40 1.40 1.40 1.40 1.40 1.40 1.65 1.65 1.65 1.65 1.65

0.060 0.060 0.060 0.060 0.080 0.080 0.080 0.080 0.080 0.080 0.080 0.080 0.080 0.080 0.080 0.080 0.080 0.110 0.110 0.110 0.110 0.110 0.110

1.52 1.52 1.52 1.52 2.03 2.03 2.03 2.03 2.03 2.03 2.03 2.03 2.03 2.03 2.03 2.03 2.03 2.79 2.79 2.79 2.79 2.79 2.79

0.640 0.705 0.720 0.790 0.875 0.950 1.000 1.095 1.120 1.235 1.215 1.340 1.310 1.450 1.420 1.570 1.540 1.765 1.750 1.930 1.970 2.180 2.250

16.26 17.91 18.29 20.07 22.23 24.13 25.40 27.81 28.45 31.37 30.86 34.04 33.27 36.83 36.07 39.88 39.12 44.83 44.45 49.02 50.04 55.37 57.15

190 242 301 384 448 578 716 919 872 1136 1081 1413 1341 1760 1717 2245 2132 2796 2494 3282 3474 4577 4938

283 360 448 571 667 862 1066 1368 1298 1691 1609 2103 1996 2619 2555 3341 3173 4161 3712 4884 5170 6811 7349

314 385 445 558 653 820 964 1214 1199 1704 1414 1825 1706 2223 2437 3123 2600 3444 3142 4048 4230 5470 5829

467 573 662 830 972 1220 1435 1807 1784 2536 2104 2716 2539 3308 3627 4648 3869 5125 4676 6024 6295 8140 8675

Dimensions and weights are nominal; subject to industry tolerances. *Non-stock item, minimum runs apply. Please consult Customer Service for price and delivery. 1Approved as TYPE TC-ER for Exposed Run applications of 3 or more conductors as defined by NEC.

Phone: 888-593-3355 www.generalcable.com


SPEC 4500

January, 2008

CVTC

®

XLPE/PVC, Control, Unshielded 600V, UL Type TC-ER1—E-2 Color Code Product Construction Conductor:

• 14 AWG thru 10 AWG fully annealed stranded bare copper per ASTM B3 • Class B stranding per ASTM B8

Insulation:

• Flame-retardant Cross-Linked Polyethylene (XLPE) • Color-coded per ICEA Method 1; Table E-2 (Does not include white or green)

CATALOG NUMBER

COPPER MINIMUM AVG. MINIMUM AVG. WEIGHT NET WEIGHT INSULATION JACKET NOMINAL NO. COND. THICKNESS CABLE O.D. LBS/ OF SIZE COND. THICKNESS LBS/ COND. (AWG) STRAND inCHES mm INCHES mm INCHES mm 1000 FT kg/km 1000 FT kg/km

14 AWG MULTI CONDUCTORS 770460 771080* 770530 770610 770420 770560 770540 770470 770550 770450* 295320* 770430*

2 Flat 2 3 4 5 7 9 12 19 25 30 37

14 14 14 14 14 14 14 14 14 14 14 14

7/.0242 7/.0242 7/.0242 7/.0242 7/.0242 7/.0242 7/.0242 7/.0242 7/.0242 7/.0242 7/.0242 7/.0242

0.030 0.030 0.030 0.030 0.030 0.030 0.030 0.030 0.030 0.030 0.030 0.030

0.76 0.76 0.76 0.76 0.76 0.76 0.76 0.76 0.76 0.76 0.76 0.76

0.045 0.045 0.045 0.045 0.045 0.045 0.060 0.060 0.060 0.080 0.080 0.080

1.14 1.14 1.14 1.14 1.14 1.14 1.52 1.52 1.52 2.03 2.03 2.03

.235 x .370 5.97 x 9.40

0.365 0.390 0.425 0.465 0.590 0.620 0.680 0.800 0.985 1.050 1.130

9.27 9.91 10.80 11.81 14.99 15.75 17.27 20.32 25.02 26.67 28.70

25 25 40 53 66 93 119 159 252 323 387 490

37 37 59 79 99 138 177 237 375 481 571 729

62 73 93 116 140 176 245 302 460 641 740 888

92 109 138 173 208 262 365 449 685 954 1101 1322

40 41 86 65 86 108 150 193 258 403 515 618 741

60 86 61 96 128 143 96 125 128 157 160 191 224 260 288 340 385 429 600 681 767 885 920 1005 1103 1185

128 143 213 186 234 284 387 506 638 1013 1317 1496 1764

66 67 135 101 135 167 234 295 402

98 100 200 150 200 249 349 440 598

170 193 299 257 351 427 552 713 958

12 AWG MULTI CONDUCTORS 770480 2 Flat 2 346920* 365720 3+ Grnd 3 770570 4 770490 5 770410 7 770950 9 770580 12 770520 19 770700* 25 347110* 30 347120* 37 347130*

12 12 12 12 12 12 12 12 12 12 12 12 12

7/.0305 7/.0305 7/.0305 7/.0305 7/.0305 7/.0305 7/.0305 7/.0305 7/.0305 7/.0305 7/.0305 7/.0305 7/.0305

770590 2 Flat 2 346930* 770670 3+ Grnd 3 770600 4 770370 5 770380 7 770900 9 770390* 12 770400

10 10 10 10 10 10 10 10 10

7/.0385 7/.0385 7/.0385 7/.0385 7/.0385 7/.0385 7/.0385 7/.0385 7/.0385

0.030 0.030 0.030 0.030 0.030 0.030 0.030 0.030 0.030 0.030 0.030 0.030 0.030

0.76 0.76 0.76 0.76 0.76 0.76 0.76 0.76 0.76 0.76 0.76 0.76 0.76

0.045 0.045 0.045 0.045 0.045 0.045 0.060 0.060 0.060 0.080 0.080 0.080 0.080

1.14 1.14 1.14 1.14 1.14 1.14 1.52 1.52 1.52 2.03 2.03 2.03 2.03

.245 x .400 6.22 x 10.16

0.410 0.435 0.435 0.475 0.515 0.595 0.695 0.780 0.930 1.095 1.150 1.240

10.41 11.05 11.05 12.07 13.08 15.11 17.65 19.81 23.62 27.81 29.21 31.50

10 AWG MULTI CONDUCTORS 0.030 0.030 0.030 0.030 0.030 0.030 0.030 0.030 0.030

0.76 0.76 0.76 0.76 0.76 0.76 0.76 0.76 0.76

0.045 0.045 0.045 0.045 0.060 0.060 0.060 0.060 0.080

1.14 1.14 1.14 1.14 1.52 1.52 1.52 1.52 2.03

.290 x .480 7.37 x 12.19

0.455 0.485 0.485 0.515 0.615 0.670 0.785 0.895

11.56 12.32 12.32 13.08 15.62 17.02 19.94 22.73

Dimensions and weights are nominal; subject to industry tolerances. *Non-stock item, minimum runs apply. Please consult Customer Service for price and delivery. 1Approved as TYPE TC-ER for Exposed Run applications of 3 or more conductors as defined by NEC.

114 130 201 173 236 287 371 479 644

Jacket:

• Flame-retardant, moisture- and sunlight-resistant Polyvinyl Chloride (PVC)

Print

• GENERAL CABLE® (WC) CVTC® XX/C XXAWG FR-XLP/PVC (UL) Type TC-ER1 XHHW-2 CDRS DIR BUR SUN RES 90˚C WET or DRY 600V DAY/ MONTH/YEAR OF MFG sequential footage mark

Options:

• Tinned copper conductor • Class C stranding • E-1 Color Code • Overall shielded multi conductors • Ethylene Propylene Rubber (EPR) insulation • Low-lead Hypalon Chlorosulfonated Polyethylene (CSPE)/Elastomer blend—See CHTC® Spec 4050 • Insulated or uninsulated ground conductor • Other constructions available upon request

Applications:

• In free air, raceways and direct burial • In wet or dry locations • Approved for direct burial, Class I, Div. 2 industrial hazardous locations per NEC • Permitted for Exposed Run ‘ER’ use in accordance with NEC for 3 or more conductors

Features:

• Rated at 90˚C wet or dry • Ripcord applied to all cables with jacket thickness of 60 mils or less • Excellent electrical properties • Abrasion- and chemical-resistant • Sunlight- and weather-resistant • Meets cold bend test at -25˚C • Meets the crush and impact requirements of Type MC cable

Compliances:

Industry Compliances: • UL 44 Type XHHW-2 • UL 1277 Type TC-ER for 3 or more conductors • UL 1581 • ICEA S-73-532 • ICEA S-95-658/NEMA WC 70 Flame Tests Compliances: • UL 1581 VW-1 • UL 1277 • IEEE 383 • IEEE 1202 • CSA FT-4 Other Compliances: • EPA 40 CFR, Part 261 for leachable lead content per TCLP • OSHA acceptable

Packaging: • Material cut to length and shipped on non-returnable wood reels

Phone: 888-593-3355 www.generalcable.com


SPEC 4550

January, 2009

CVTC

®

XLPE/PVC, Low-Voltage Power, Unshielded 600V, UL Type TC-ER1—Method 4 Color Code Applications (cont’d.):

• Permitted for Exposed Run ‘ER’ use in accordance with NEC

Features:

Product Construction Conductor:

• Rated at 90˚C wet or dry • Ripcord applied to all cables with jacket thickness of 60 mils or less • Abrasion- and chemical-resistant • Excellent electrical properties • Sunlight- and weather-resistant • Meets cold bend test at -25˚C • Meets the crush and impact requirements of Type MC cable

Print (cont’d.):

TC-ER1 XHHW-2 CDRS 90˚C WET OR DRY 600V DAY/MONTH/YEAR SEQUENTIAL FOOTAGE MARK

• 14 AWG thru 750 kcmil bare, annealed copper per ASTM B3 • Class B stranding per ASTM B8 • Flame-retardant Cross-Linked Polyethylene (XLPE) • Color-coded per ICEA Method 4; Individual conductors colored black with conductor number surface printed in contrasting ink

Ground:

• Uninsulated bare annealed copper per ASTM B3 • Class B stranding per ASTM B8

Jacket:

Applications:

• Flame-retardant, moisture- and sunlight-resistant Polyvinyl Chloride (PVC)

• In free air, raceways or direct burial • In wet or dry locations • Permitted for use in Class I Division 2 industrial hazardous locations per NEC

Print:

• General Cable® (PLANT OF MFG) CVTC® XX/C XXAWG WITH GRND FR-XLP/PVC UL TYPE

CATALOG NUMBER

NO. OF COND.

383860* 383870* 383880* 783160 783190 339470 339480 783330 339500* 325610 329520* 352150* 371250* 339530 339540* 339550 339560* 371260* 371270* 783230 339570* 328540* 339590* 222570 339600* 222710 06790.086500* 06790.077000* 06790.047000*

3 3 3 3 4 3 4 3 4 3 4 3 4 3 4 3 4 3 4 3 4 3 4 3 4 3 4 3 4

14 12 10 8 8 6 6 4 4 2 2 1 1 1/0 1/0 2/0 2/0 3/0 3/0 4/0 4/0 250 250 350 350 500 500 750 750

Industry Compliances: • UL 44 Type XHHW-2 • UL 1277 Type TC-ER • UL 1581 • ICEA S-95-658/NEMA WC70 Flame Tests Compliances: • UL 1581 VW-1 • UL 1277 • IEEE 383 • IEEE 1202 • CSA FT-4 Other Compliances: • EPA 40 CFR, Part 261 for leachable lead content per TCLP • OSHA acceptable

• Tinned copper conductor • Class C stranding • E-1 or E-2 Color Code • Insulated ground conductors • Overall shielded multi conductors • Flame-retardant Ethylene Propylene Rubber (EPR) insulation • Low-lead Hypalon Chlorosulfonated Polyethylene (CSPE)/Elastomer blend—See CHTC® Spec 4100 • ICEA 1000V rated cable • Other constructions available upon request

Insulation:

COND. SIZE (AWG/ kcmil)

Compliances:

Options:

COND. STRAND 7/.0242 7/.0305 7/.0385 7/.0486 7/.0486 7/.0612 7/.0612 7/.0772 7/.0772 7/.0974 7/.0974 19/.0664 19/.0664 19/.0745 19/.0745 19/.0837 19/.0837 19/.0940 19/.0940 19/.1055 19/.1055 37/.0822 37/.0822 37/.0973 37/.0973 37/.1162 37/.1162 61/.1109 61/.1109

GROUND WIRE SIZE (AWG)

MINIMUM AVG. INSULATION THICKNESS INCHES

mm

Packaging:

• Material cut to length and shipped on non-returnable wood reels

MINIMUM AVG. JACKET THICKNESS NOMINAL CABLE O.D. INCHES

mm

INCHES

mm

COPPER WEIGHT LBS/ 1000 FT kg/km

NET WEIGHT LBS/ 1000 FT kg/km

14 AWG - 750 kcmil MULTI CONDUCTORS 14 12 10 10 10 8 8 8 8 6 6 6 6 6 6 6 6 4 4 4 4 4 4 3 3 2 2 1 1

0.030 0.030 0.030 0.045 0.045 0.045 0.045 0.045 0.045 0.045 0.045 0.055 0.055 0.055 0.055 0.055 0.055 0.055 0.055 0.055 0.055 0.065 0.065 0.065 0.065 0.065 0.065 0.080 0.080

0.76 0.76 0.76 1.14 1.14 1.14 1.14 1.14 1.14 1.14 1.14 1.40 1.40 1.40 1.40 1.40 1.40 1.40 1.40 1.40 1.40 1.65 1.65 1.65 1.65 1.65 1.65 2.03 2.03

0.045 0.045 0.060 0.060 0.060 0.060 0.060 0.080 0.080 0.080 0.080 0.080 0.080 0.080 0.080 0.080 0.080 0.080 0.080 0.080 0.110 0.110 0.110 0.110 0.110 0.110 0.110 0.140 0.140

1.14 1.14 1.52 1.52 1.52 1.52 1.52 2.03 2.03 2.03 2.03 2.03 2.03 2.03 2.03 2.03 2.03 2.03 2.03 2.03 2.79 2.79 2.79 2.79 2.79 2.79 2.79 3.56 3.56

0.425 0.475 0.515 0.640 0.705 0.720 0.790 0.875 0.950 1.000 1.095 1.120 1.235 1.215 1.340 1.310 1.450 1.420 1.570 1.540 1.765 1.750 1.930 1.970 2.180 2.250 2.475 2.810 3.115

10.80 12.07 13.08 16.26 17.91 18.29 20.07 22.23 24.13 25.40 27.81 28.45 31.37 30.86 34.04 33.27 36.83 36.07 39.88 39.12 44.83 44.45 49.02 50.04 55.37 57.15 62.87 71.37 79.12

53 86 135 190 242 301 384 448 578 716 919 872 1136 1081 1413 1341 1760 1717 2245 2132 2796 2494 3282 3474 4577 4938 6509 7278 9712

79 128 200 283 360 448 571 667 862 1066 1368 1298 1691 1609 2103 1996 2619 2555 3341 3173 4161 3712 4884 5170 6811 7349 9687 10831 14453

116 157 236 314 385 445 558 653 820 964 1214 1199 1704 1414 1825 1706 2223 2437 3123 2600 3444 3142 4048 4230 5470 5829 7579 9101 11746

173 234 351 467 573 662 830 972 1220 1435 1807 1784 2536 2104 2716 2539 3308 3627 4648 3869 5125 4676 6024 6295 8140 8675 11279 13544 17480

Dimensions and weights are nominal; subject to industry tolerances. *Non-stock item, minimum runs apply. Please consult Customer Service for price and delivery. 1Approved as TYPE TC-ER for Exposed Run applications of 3 or more conductors as defined by NEC.

Phone: 888-593-3355 www.generalcable.com


SPEC 4575

January, 2009

CVTC VFD ®

XLPE/PVC, Low-Voltage Power, Shielded 2000V, UL Type TC-ER1—Method 4 Color Code Features:

Product Construction Conductor:

Jacket:

• General Cable® (WC) CVTC® VFD XX/C XXAWG WITH GRND FR-XLP/PVC (UL) TYPE TC-ER RHH or RHW-2 CDRS 90˚C WET OR DRY 2000V DIR BUR SUN RES DAY/MONTH/YEAR SEQUENTIAL FOOTAGE MARK

• Flame-retardant Cross-Linked Polyethylene (XLPE)—90°C, VW-1 • Color-coded per ICEA Method 4; Individual conductors colored black with conductor number surface printed in contrasting ink

Applications:

• For use with AC motors controlled by Pulse Width Modulated Inverter in VFD applications rated up to 2000 volts. These motor drive systems require cables that are designed to prevent radio frequency interference (RFI) which can lead to malfunction • In raceways, cable trays or direct burial • In wet or dry locations • Permitted for use in Class 1, Division 2 industrial hazardous locations per NEC • Permitted for Exposed Run ‘ER’ use in accordance with NEC

Ground:

• 3 symmetrically placed annealed tinned copper conductors in direct contact with shield • Class B stranding per ASTM B8

Dual Shield:

• Overall tinned copper braided shield in conjunction with an aluminum/polymer tape shield

NO. OF COND.

Industry Compliances: • UL 1277 Type TC-ER • UL Type RHH or RHW-2 conductors per UL 44 Flame Test Compliances: • IEEE 383 • IEEE 1202 Other Compliances: • EPA 40 CFR, Part 261 for leachable lead content per TCLP • OSHA acceptable

Print:

Insulation:

COND. SIZE (AWG/ kcmil)

Compliances:

• Flame-retardant, moisture- and sunlight-resistant Polyvinyl Chloride (PVC)—Black

• 14 AWG thru 500 kcmil fully annealed tinned stranded copper • Class B stranding per ASTM B8

CATALOG NUMBER

• Rated at 90˚C wet or dry • Dual shield provides maximum shield coverage required for Variable Frequency Drive (VFD) applications • Meets crush and impact requirements to Type MC cable • Abrasion- and chemical-resistant • Excellent electrical properties • Sunlight- and weather-resistant

COND. STRAND

GROUND WIRE SIZE (AWG)

MINIMUM AVG. INSULATION THICKNESS INCHES

mm

Packaging:

• Material cut to length and shipped on non-returnable wood reels

MINIMUM AVG. JACKET THICKNESS NOMINAL CABLE O.D. INCHES

mm

INCHES

COPPER WEIGHT

mm

LBS/ 1000 FT

14.35 15.37 16.89 19.94 23.11 25.65 28.83 35.31 37.85 40.51 45.09 49.28 54.86 61.98

79 114 172 234 354 507 783 1251 1511 1897 2355 2719 3883 5507

NET WEIGHT

kg/km

LBS/ 1000 FT

kg/km

118 170 256 348 527 755 1165 1861 2248 2823 3504 4046 5778 8194

190 236 313 420 605 800 1126 1832 2134 2553 3254 3726 5040 6809

283 351 466 625 900 1191 1676 2726 3175 3799 4842 5544 7500 10132

14 AWG - 500 kcmil MULTI CONDUCTORS 384730* 384740* 384750* 384760* 384770* 384780* 384790* 384800* 384810* 384820* 384830* 384840* 384850* 384860*

3 3 3 3 3 3 3 3 3 3 3 3 3 3

14 12 10 8 6 4 2 1/0 2/0 3/0 4/0 250 350 500

7/.0242 7/.0305 7/.0385 7/.0486 7/.0612 7/.0772 7/.0974 19/.0745 19/.0837 19/.0940 19/.1055 37/.0822 37/.0973 37/.1162

3 x 18 3 x 16 3 x 14 3 x 14 3 x 12 3 x 12 3 x 10 3x6 3x6 3x5 3x4 3x4 3x2 3x1

0.060 0.060 0.060 0.070 0.070 0.070 0.070 0.090 0.090 0.090 0.090 0.105 0.105 0.105

1.52 1.52 1.52 1.78 1.78 1.78 1.78 2.29 2.29 2.29 2.29 2.67 2.67 2.67

0.060 0.060 0.060 0.060 0.080 0.080 0.080 0.080 0.080 0.080 0.110 0.110 0.110 0.110

1.52 1.52 1.52 1.52 2.03 2.03 2.03 2.03 2.03 2.03 2.79 2.79 2.79 2.79

0.565 0.605 0.665 0.785 0.910 1.010 1.315 1.390 1.490 1.595 1.775 1.940 2.160 2.440

Dimensions and weights are nominal; subject to industry tolerances. *Non-stock item, minimum runs apply. Please consult Customer Service for price and delivery. 1Approved as TYPE TC-ER for Exposed Run applications of 3 or more conductors as defined by NEC.

Phone: 888-593-3355 www.generalcable.com


SPEC 4580

January, 2009

CVTC VFD ®

XLPE/PVC, Low-Voltage Power, Copper Tape Shielded 2000V, UL Type TC-ER—Method 4 Color Code Features:

• Rated at 90˚C wet or dry • Overlapped bare copper tape shield provides necessary shield coverage required for Variable Frequency Drive (VFD) applications • Meets crush and impact requirements for Type MC cable • Abrasion- and chemical-resistant • Excellent electrical properties • Sunlight- and weather-resistant

Product Construction Conductor:

Jacket:

• 14 AWG thru 500 kcmil fully annealed bare stranded copper • Class B stranding per ASTM B8

• General Cable® (WC) CVTC® VFD XX/C XXAWG WITH GRNDS FR-XLP/PVC (UL) TYPE TC-ER RHH or RHW-2 CDRS 90˚C WET OR DRY 2000V DIR BUR SUN RES DAY/MONTH/YEAR SEQUENTIAL FOOTAGE MARK

• Flame-retardant Cross-Linked Polyethylene (XLPE)—90°C, VW-1 • Color-coded per ICEA Method 4; Individual conductors colored black with conductor number surface printed in contrasting ink

Applications:

• For use with AC motors controlled by Pulse Width Modulated Inverter in VFD applications rated up to 2000 volts. These motor drive systems require cables that are designed to prevent radio frequency interference (RFI) which can lead to malfunction • In raceways, cable trays or direct burial • In wet or dry locations • Permitted for use in Class 1, Division 2 industrial hazardous locations per NEC • Permitted for Exposed Run ‘ER’ use in accordance with NEC

Ground:

• 3 symmetrically placed annealed bare copper conductors in direct contact with shield • Class B stranding per ASTM B8

Metallic Shield:

• Overall 5 mil annealed bare copper tape shield with 50% overlap

CATALOG NUMBER

NO. OF COND.

395070 395080 395090 395100 395110 395120 395130 395140* 395150 395160* 395170 395180* 395190 395200

3 3 3 3 3 3 3 3 3 3 3 3 3 3

14 12 10 8 6 4 2 1/0 2/0 3/0 4/0 250 350 500

Industry Compliances: • UL 1277 Type TC-ER, 2000V • UL Type RHH or RHW-2 conductors per UL 44 Flame Test Compliances: • IEEE 383 • IEEE 1202 Other Compliances: • EPA 40 CFR, Part 261 for leachable lead content per TCLP • OSHA acceptable

Print:

Insulation:

COND. SIZE (AWG/ kcmil)

Compliances:

• Flame-retardant, moisture- and sunlight-resistant Polyvinyl Chloride (PVC)—Black

COND. STRAND 7/.0242 7/.0305 7/.0385 7/.0486 7/.0612 7/.0772 7/.0974 19/.0745 19/.0837 19/.0940 19/.1055 37/.0822 37/.0973 37/.1162

GROUND WIRE SIZE (AWG)

MINIMUM AVG. INSULATION THICKNESS INCHES

mm

Packaging:

• Material cut to length and shipped on non-returnable wood reels

MINIMUM AVG. JACKET THICKNESS NOMINAL CABLE O.D. INCHES

mm

INCHES

COPPER WEIGHT

mm

LBS/ 1000 FT

14.73 15.37 17.02 19.56 22.73 25.27 28.58 35.18 37.59 40.39 45.21 49.28 54.86 62.36

91 127 183 246 368 522 801 1348 1616 2010 2517 2895 4089 5693

NET WEIGHT

kg/km

LBS/ 1000 FT

kg/km

135 189 272 366 548 777 1192 2006 2405 2991 3745 4308 6084 8471

212 260 329 441 618 830 1152 1853 2169 2619 3241 3763 5109 6933

315 387 490 656 920 1235 1714 2757 3227 3897 4823 5599 7602 10316

14 AWG - 500 kcmil MULTI CONDUCTORS 3 x 18 3 x 16 3 x 14 3 x 14 3 x 12 3 x 12 3 x 10 3x6 3x6 3x5 3x4 3x4 3x2 3x1

0.060 0.060 0.060 0.070 0.070 0.070 0.070 0.090 0.090 0.090 0.090 0.105 0.105 0.105

1.52 1.52 1.52 1.78 1.78 1.78 1.78 2.29 2.29 2.29 2.29 2.67 2.67 2.67

0.060 0.060 0.060 0.060 0.080 0.080 0.080 0.080 0.080 0.080 0.110 0.110 0.110 0.110

1.52 1.52 1.52 1.52 2.03 2.03 2.03 2.03 2.03 2.03 2.79 2.79 2.79 2.79

0.580 0.615 0.670 0.770 0.895 0.995 1.125 1.385 1.480 1.590 1.780 1.940 2.160 2.455

Dimensions and weights are nominal; subject to industry tolerances. *Non-stock item, minimum runs apply. Please consult Customer Service for price and delivery.

Phone: 888-593-3355 www.generalcable.com


SPEC 4600

January, 2008

VNTC

®

PVC/NYLON/PVC, Control, Unshielded 600V, UL Type TC-ER1 (18 AWG/16 AWG)—E-2 Color Code Product Construction Conductor:

• 18 AWG and 16 AWG fully annealed stranded bare copper to ASTM B3 • Class B stranding per ASTM B8

Insulation:

CATALOG NUMBER

COPPER MINIMUM AVG. MINIMUM AVG. WEIGHT NET WEIGHT INSULATION JACKET NOMINAL NO. COND. THICKNESS CABLE O.D. LBS/ OF SIZE COND. THICKNESS LBS/ COND. (AWG) STRAND inCHES mm INCHES mm INCHES mm 1000 FT kg/km 1000 FT kg/km

236090 318050* 245920 236100 244680 244660 264570* 233270* 236120 244720* 236130 236140* 347140* 236150

2 Flat 2 3 4 5 7 9 10 12 15 19 25 30 37

18 AWG MULTI CONDUCTORS 18 18 18 18 18 18 18 18 18 18 18 18 18 18

7/.0152 7/.0152 7/.0152 7/.0152 7/.0152 7/.0152 7/.0152 7/.0152 7/.0152 7/.0152 7/.0152 7/.0152 7/.0152 7/.0152

0.020 0.020 0.020 0.020 0.020 0.020 0.020 0.020 0.020 0.020 0.020 0.020 0.020 0.020

0.51 0.51 0.51 0.51 0.51 0.51 0.51 0.51 0.51 0.51 0.51 0.51 0.51 0.51

0.045 0.045 0.045 0.045 0.045 0.045 0.045 0.045 0.045 0.045 0.060 0.060 0.060 0.060

1.14 1.14 1.14 1.14 1.14 1.14 1.14 1.14 1.14 1.14 1.52 1.52 1.52 1.52

.190 x .285 4.80 x 7.20

0.270 0.285 0.310 0.335 0.360 0.420 0.425 0.445 0.485 0.570 0.655 0.695 0.745

6.86 7.24 7.87 8.51 9.14 10.67 10.80 11.30 12.32 14.48 16.64 17.65 18.92

2 Flat 2 3 4 5 7 9 10 12 15 19 25 30 37

16 16 16 16 16 16 16 16 16 16 16 16 16 16

7/.0192 7/.0192 7/.0192 7/.0192 7/.0192 7/.0192 7/.0192 7/.0192 7/.0192 7/.0192 7/.0192 7/.0192 7/.0192 7/.0192

0.020 0.020 0.020 0.020 0.020 0.020 0.020 0.020 0.020 0.020 0.020 0.020 0.020 0.020

0.51 0.51 0.51 0.51 0.51 0.51 0.51 0.51 0.51 0.51 0.51 0.51 0.51 0.51

0.045 0.045 0.045 0.045 0.045 0.045 0.045 0.045 0.045 0.060 0.060 0.060 0.060 0.080

1.14 1.14 1.14 1.14 1.14 1.14 1.14 1.14 1.14 1.52 1.52 1.52 1.52 2.03

.200 x .310 5.08 x 7.87

0.300 0.315 0.340 0.370 0.400 0.460 0.495 0.505 0.605 0.635 0.705 0.760 0.880

7.62 8.00 8.64 9.40 10.16 11.68 12.57 12.83 15.37 16.13 17.91 19.30 22.35

Jacket:

• Flame-retardant, moisture- and sunlightresistant Polyvinyl Chloride (PVC)

Print 10 11 15 20 26 36 46 51 61 77 97 128 154 189

15 19 23 30 38 53 69 76 91 114 144 190 229 281

36 38 46 56 65 82 105 114 131 162 209 266 310 371

54 57 68 83 97 122 156 170 195 241 311 396 461 552

16 20 24 32 40 56 72 80 97 121 153 201 242 306

24 29 36 48 60 84 108 119 144 180 228 299 360 455

42 50 60 74 97 111 141 154 178 239 284 364 426 552

71 74 89 110 144 165 210 229 265 356 423 542 634 821

16 AWG MULTI CONDUCTORS 236160 245580 236170 236180 236190 236210 243640 236230* 236240 244650* 236260 236280 244670* 236290*

• Flame-retardant Polyvinyl Chloride (PVC) with clear Polyamide (nylon) • Color-coded per ICEA Method 1; Table E-2 plus alpha-numeric printed numbers (Does not include white or green)

Dimensions and weights are nominal; subject to industry tolerances. *Non-stock item, minimum runs apply. Please consult Customer Service for price and delivery. 1Approved as TYPE TC-ER for Exposed Run applications of 3 or more conductors as defined by NEC.

• GENERAL CABLE® (WC) VNTC® XX/C XXAWG (UL) Type TC-ER1 TFN SUN RES DIR BUR 600V DAY/MONTH/YEAR OF MFG sequential footage mark

Options:

• Tinned copper conductor • Class C stranding • E-1 Color Code • Overall shielded multi conductors • Other constructions available upon request

Applications:

• In free air, raceways or direct burial • In wet or dry locations • Approved for direct burial, Class I, Div. 2 industrial hazardous locations per NEC • Permitted for Exposed Run ‘ER’ use in accordance with NEC for 3 or more conductors

Features:

• Rated at 90˚C dry, 75˚C wet • Ripcord applied to all cables with jacket thickness of 60 mils or less • Provides outstanding sunlight, cold bend and cold impact resistance • Offers the smallest cable O.D. available for suitable applications • Provides long service life • Provides good oil and chemical resistance • Meets cold bend test at -25˚C • Meets the crush and impact requirements of Type MC cable

Compliances:

Industry Compliances: • UL 66 NEC Type TFN conductors • UL 1277 Type TC-ER for 3 or more conductors • UL 1581 • ICEA S-95-658 Flame Tests Compliances: • UL 1277 • IEEE 383 • IEEE 1202 • CSA FT-4 Other Compliances: • EPA 40 CFR, Part 261 for leachable lead content per TCLP • OSHA acceptable

Packaging:

• Material cut to length and shipped on non-returnable wood reels

Phone: 888-593-3355 www.generalcable.com


SPEC 4650

January, 2008

VNTC

®

PVC/NYLON/PVC, Control, Unshielded 600V, UL Type TC-ER1 (14 AWG—10 AWG)—E-2 Color Code Product Construction Conductor:

• 14 AWG thru 10 AWG fully annealed stranded bare copper per ASTM B3 • Class B stranding per ASTM B8

Insulation:

CATALOG NUMBER

COPPER MINIMUM AVG. MINIMUM AVG. WEIGHT NET WEIGHT INSULATION JACKET NOMINAL NO. COND. THICKNESS CABLE O.D. LBS/ OF SIZE COND. THICKNESS LBS/ COND. (AWG) STRAND inCHES mm INCHES mm INCHES mm 1000 FT kg/km 1000 FT kg/km

235040 245590* 235050 235060 235070 235080 235090 235110 235130 235150 235160* 235170

2 Flat 2 3 4 5 7 9 12 19 25 30 37

14 14 14 14 14 14 14 14 14 14 14 14

7/.0242 7/.0242 7/.0242 7/.0242 7/.0242 7/.0242 7/.0242 7/.0242 7/.0242 7/.0242 7/.0242 7/.0242

234580 2 Flat 2 260150* 3 234590 255090 3+Grnd 4 234600 5 226420 7 234620 9 226500 12 234640 19 243600 25 243610* 30 321720* 37 234680*

12 12 12 12 12 12 12 12 12 12 12 12 12

7/.0305 7/.0305 7/.0305 7/.0305 7/.0305 7/.0305 7/.0305 7/.0305 7/.0305 7/.0305 7/.0305 7/.0305 7/.0035

236300 2 Flat 2 243630* 3 236310 255080* 3+Grnd 4 236320 5 236330 7 236340 9 243620* 12 236350

10 10 10 10 10 10 10 10 10

7/.0385 7/.0385 7/.0385 7/.0385 7/.0385 7/.0385 7/.0385 7/.0385 7/.0385

14 AWG MULTI CONDUCTORS 0.020 0.020 0.020 0.020 0.020 0.020 0.020 0.020 0.020 0.020 0.020 0.020

0.51 0.51 0.51 0.51 0.51 0.51 0.51 0.51 0.51 0.51 0.51 0.51

0.045 0.045 0.045 0.045 0.045 0.045 0.060 0.060 0.060 0.060 0.080 0.080

1.14 1.14 1.14 1.14 1.14 1.14 1.52 1.52 1.52 1.52 2.03 2.03

.210 x .320 5.33 x 8.13

0.320 0.345 0.365 0.410 0.445 0.505 0.595 0.695 0.785 0.895 0.970

8.13 8.76 9.27 10.41 11.30 12.83 15.11 17.65 19.94 22.73 24.64

25 26 39 52 65 90 116 155 245 323 387 478

37 39 58 77 97 134 173 231 365 481 576 711

54 64 80 100 118 153 213 267 396 507 637 766

80 95 119 149 176 228 317 397 589 755 948 1140

40 41 86 86 86 108 144 185 247 391 515 618 762

60 74 110 61 85 127 128 131 195 128 131 195 128 138 205 160 165 246 214 217 323 275 297 442 368 377 561 582 568 845 767 775 1153 920 919 1368 1134 1100 1637

64 65 131 131 135 169 236 295 404

95 97 195 195 200 252 351 440 602

12 AWG MULTI CONDUCTORS 0.020 0.020 0.020 0.020 0.020 0.020 0.020 0.020 0.020 0.020 0.020 0.020 0.020

0.51 0.51 0.51 0.51 0.51 0.51 0.51 0.51 0.51 0.51 0.51 0.51 0.51

0.045 0.045 0.045 0.045 0.045 0.045 0.045 0.060 0.060 0.060 0.080 0.080 0.080

1.14 1.14 1.14 1.14 1.14 1.14 1.14 1.52 1.52 1.52 2.03 2.03 2.03

.225 x .360 5.72 x 9.14

0.355 0.385 0.385 0.420 0.445 0.490 0.605 0.675 0.785 0.940 1.030 1.105

9.02 9.78 9.78 10.67 11.30 12.45 15.37 17.15 19.94 23.88 26.16 28.07

10 AWG MULTI CONDUCTORS 0.026 0.026 0.026 0.026 0.026 0.026 0.026 0.026 0.026

0.66 0.66 0.66 0.66 0.66 0.66 0.66 0.66 0.66

0.045 0.045 0.045 0.045 0.045 0.060 0.060 0.060 0.060

1.14 1.14 1.14 1.14 1.14 1.52 1.52 1.52 1.52

.260 x .425 6.60 x 10.80

0.420 0.450 0.450 0.505 0.570 0.620 0.725 0.815

10.67 11.43 11.43 12.83 14.48 15.75 18.42 20.70

Dimensions and weights are nominal; subject to industry tolerances. *Non-stock item, minimum runs apply. Please consult Customer Service for price and delivery. 1Approved as TYPE TC-ER for Exposed Run applications of 3 or more conductors as defined by NEC.

108 115 191 191 209 268 350 440 584

161 171 284 284 311 399 521 655 869

• Flame-retardant Polyvinyl Chloride (PVC) with clear Polyamide (nylon) • Color-coded per ICEA Method 1; Table E-2 plus alpha-numeric printed numbers (Does not include white or green)

Jacket:

• Flame-retardant, moisture and sunlightresistant Polyvinyl Chloride (PVC)

Print

• GENERAL CABLE® (WC) VNTC® XX/C XXAWG (UL) Type TC-ER1 THHN/THWN SUN RES DIR BUR 600V DAY/MONTH/ YEAR OF MFG sequential footage mark

Options:

• Tinned copper conductor • Class C stranding • E-1 Color Code • Overall shielded multi conductors • Other constructions available upon request

Applications:

• In free air, raceways and direct burial • In wet or dry locations • Approved for direct burial, Class I, Div. 2 industrial hazardous locations per NEC • Permitted for Exposed Run ‘ER’ use in accordance with NEC for 3 or more conductors

Features:

• Rated at 90˚C dry, 75˚C wet • Ripcord applied to all cables with jacket thickness of 60 mils or less • Provides outstanding sunlight, cold bend and cold impact resistance • Offers the smallest cable O.D. available for suitable applications • Provides long service life • Provides good oil and chemical resistance • Meets cold bend test at -25˚C • Meets the crush and impact requirements of Type MC cable

Compliances:

Industry Compliances: • UL 83 NEC Type THHN/THWN conductors • UL 1277 Type TC-ER for 3 or more conductors • UL 1581 • ICEA S-95-658 Flame Tests Compliances: • UL 1277 • IEEE 383 • IEEE 1202 • CSA FT-4 Other Compliances: • EPA 40 CFR, Part 261 for leachable lead content per TCLP • OSHA acceptable

Packaging:

• Material cut to length and shipped on non-returnable wood reels

Phone: 888-593-3355 www.generalcable.com


SPEC 4700

January, 2008

VNTC

®

PVC/NYLON/PVC, Control, Shielded 600V, UL Type TC-ER1, Overall Shielded—E-2 Color Code Product Construction Conductor:

• 18 AWG thru 10 AWG fully annealed stranded bare copper per ASTM B3 • Class B stranding per ASTM B8

Insulation:

CATALOG NUMBER

COPPER MINIMUM AVG. MINIMUM AVG. WEIGHT NET WEIGHT INSULATION JACKET NOMINAL NO. COND. THICKNESS CABLE O.D. LBS/ OF SIZE COND. THICKNESS LBS/ COND. (AWG) STRAND inCHES mm INCHES mm INCHES mm 1000 FT kg/km 1000 FT kg/km

OVERALL SHIELDED MULTI CONDUCTORS 18 AWG CONDUCTORS 261130 261140 261150 260000* 259980*

2 3 4 5 7

18 18 18 18 18

7/.0152 7/.0152 7/.0152 7/.0152 7/.0152

0.020 0.020 0.020 0.020 0.020

0.51 0.51 0.51 0.51 0.51

0.045 0.045 0.045 0.045 0.045

1.14 1.14 1.14 1.14 1.14

0.280 7.11 0.290 7.37 0.310 7.87 0.340 8.64 0.370 9.40

12 18 23 28 39

2 3 4 5 7 9 12

16 16 16 16 16 16 16

7/.0192 7/.0192 7/.0192 7/.0192 7/.0192 7/.0192 7/.0192

0.020 0.020 0.020 0.020 0.020 0.020 0.020

0.51 0.51 0.51 0.51 0.51 0.51 0.51

0.045 0.045 0.045 0.045 0.045 0.045 0.045

1.14 1.14 1.14 1.14 1.14 1.14 1.14

0.300 0.320 0.350 0.370 0.410 0.470 0.510

7.62 8.13 8.89 9.40 10.41 11.97 12.95

20 28 36 44 60 76 100

19 26 34 41 58

40 49 58 70 89

60 73 86 104 132

2 3 4 5 7

14 14 14 14 14

7/.0242 7/.0242 7/.0242 7/.0242 7/.0242

0.020 0.020 0.020 0.020 0.020

0.51 0.51 0.51 0.51 0.51

0.045 0.045 0.045 0.045 0.045

1.14 1.14 1.14 1.14 1.14

0.330 0.350 0.380 0.400 0.440

8.38 8.89 9.65 10.16 11.18

31 44 57 70 96

29 41 53 65 89 113 149

52 63 77 91 119 150 185

77 94 115 135 177 223 275

2 3 4

12 12 12

7/.0305 0.020 0.51 0.045 1.14 0.370 9.40 7/.0305 0.020 0.51 0.045 1.14 0.390 9.91 7/.0305 0.020 0.51 0.045 1.14 0.420 10.67

43 64 85

46 65 85 104 142

67 84 104 123 161

100 125 155 183 240

64 95 126

83 111 139

124 165 207

101 150 198

119 162 205

177 241 305

OVERALL SHIELDED MULTI CONDUCTORS 10 AWG CONDUCTORS 243770* 243820* 243690*

2 3 4

10 10 10

7/.0385 0.026 0.66 0.045 1.14 0.430 10.92 7/.0385 0.026 0.66 0.045 1.14 0.460 11.68 7/.0385 0.026 0.66 0.045 1.14 0.500 12.70

68 101 133

• Flame-retardant, moisture- and sunlight-resistant Polyvinyl Chloride (PVC)

Print

• GENERAL CABLE® (WC) Shielded VNTC® XX/C XX AWG (UL) Type TC-ER1 TFN or THHN/THWN SUN RES DIR BUR 600V DAY/MONTH/YEAR OF MFG sequential footage mark • Tinned copper conductor • Class C stranding • E-1 Color Code • Unshielded multi conductors • Other constructions available upon request

Applications:

• In free air, raceways and direct burial • In wet or dry locations • Approved for direct burial, Class I, Div. 2 industrial hazardous locations per NEC • Permitted for Exposed Run ‘ER’ use in accordance with NEC for 3 or more conductors

Features:

OVERALL SHIELDED MULTI CONDUCTORS 12 AWG CONDUCTORS 243670 243810* 243840

Overall shielded multi conductor • Overall shield is Flexfoil® aluminum/polyester, in contact with stranded tinned copper drain wire

Options:

OVERALL SHIELDED MULTI CONDUCTORS 14 AWG CONDUCTORS 243660 243720 243650 243570* 243580

Shield:

Jacket:

OVERALL SHIELDED MULTI CONDUCTORS 16 AWG CONDUCTORS 247620 261160 243710 266580* 243740* 243560* 229600*

• Flame-retardant Polyvinyl Chloride (PVC) with clear Polyamide (nylon) • Color-coded per ICEA Method 1; Table E-2 plus alpha-numeric printed numbers (Does not include white or green)

Dimensions and weights are nominal; subject to industry tolerances. *Non-stock item, minimum runs apply. Please consult Customer Service for price and delivery. 1Approved as TYPE TC-ER for Exposed Run applications of 3 or more conductors as defined by NEC.

• Rated at 90˚C dry, 75˚C wet • Ripcord applied to all cables with jacket thickness of 60 mils or less • Provides outstanding sunlight, cold bend and cold impact resistance • Offers the smallest cable O.D. available for suitable applications • Provides long service life • Provides good oil and chemical resistance • Meets cold bend test at -25˚C • Meets the crush and impact requirements of Type MC cable

Compliances:

Industry Compliances: • UL 1277 Type TC-ER for 3 or more conductors • UL 1581 • UL 66 NEC Type TFN conductors (16 & 18 AWG) • UL 83 NEC Type THHN/THWN conductors (14 through 10 AWG) • ICEA S-95-658 Flame Tests Compliances: • UL 1277 • IEEE 383 • IEEE 1202 • CSA FT-4 Other Compliances: • EPA 40 CFR, Part 261 for leachable lead content per TCLP • OSHA acceptable

Packaging:

• Material cut to length and shipped on non-returnable wood reels

Phone: 888-593-3355 www.generalcable.com


SPEC 4750

January, 2009

VNTC

®

PVC/NYLON/PVC, Low-Voltage Power, Unshielded 600V, UL Type TC-ER1 —Method 4 Color Code Features:

Product Construction Conductor:

Print:

• General Cable® (WC) VNTC® XX/C XXAWG WITH GRND (UL) TYPE TC-ER1 THHN/THWN CDRS DIR BUR SUN RES 600V DAY/MONTH/ YEAR OF MFG SEQUENTIAL FOOTAGE MARK

• 14 AWG thru 500 kcmil bare, annealed copper per ASTM B3 • Class B stranding per ASTM B8

Applications:

Ground:

• In free air, raceways or direct burial • In wet or dry locations • Permitted for use in Class I Division 2 industrial hazardous locations per NEC • Permitted for Exposed Run ‘ER’ use in accordance with NEC

• Uninsulated bare annealed copper per ASTM B3 • Class B stranding per ASTM B8

Jacket:

• Flame-retardant, moisture- and sunlight-resistant Polyvinyl Chloride (PVC)

NO. OF COND.

Industry Compliances: • NEC Type THHN/THWN conductors • UL 1277 Type TC-ER • UL 1581 Flame Tests Compliances: • UL 1277 • IEEE 383 • IEEE 1202 • CSA FT-4 Other Compliances: • EPA 40 CFR, Part 261 for leachable lead content per TCLP • OSHA acceptable

• Tinned copper conductor • Class C stranding • Insulated ground conductors • 5 mil bare copper tape shield with 25% overlap • Other constructions available upon request

• Flame-retardant Polyvinyl Chloride (PVC) with clear Polymide (nylon) • Color-coded per ICEA Method 4; Individual conductors colored black with conductor number surface printed in contrasting ink

COND. SIZE (AWG/ kcmil)

Compliances:

Options:

Insulation:

CATALOG NUMBER

• Rated at 90˚C dry, 75˚C wet • Ripcord applied to all cables with jacket thickness of 60 mils or less • Provide outstanding sunlight, cold bend and cold impact resistance • Offer the smallest cable O.D. available for suitable applications • Provide good oil and chemical resistance • Provides a long service life • Meets cold bend test at -25˚C • Meets the crush and impact requirements of Type MC cable

COND. STRAND

GROUND WIRE SIZE (AWG)

MINIMUM AVG. INSULATION THICKNESS INCHES

mm

Packaging:

• Material cut to length and shipped on non-returnable wood reels

MINIMUM AVG. JACKET THICKNESS NOMINAL CABLE O.D. INCHES

mm

INCHES

mm

COPPER WEIGHT LBS/ 1000 FT kg/km

NET WEIGHT LBS/ 1000 FT kg/km

14 AWG - 500 kcmil MULTI CONDUCTORS 383890* 234250 234260 386700** 236370 236380 226410 231980 236400 236410* 236420 236430* 236440 219580* 243760 219610* 221560 329240* 222490 297050* 226430 297060* 219630 222510*

3 3 3 3 3 4 3 4 3 4 3 4 3 4 3 4 3 4 3 4 3 4 3 4

14 12 10 10 8 8 6 6 4 4 2 2 1/0 1/0 2/0 2/0 4/0 4/0 250 250 350 350 500 500

7/.0242 7/.0305 7/.0385 7/.0385 7/.0486 7/.0486 7/.0612 7/.0612 7/.0772 7/.0772 7/.0974 7/.0974 19/.0745 19/.0745 19/.0837 19/.0837 19/.1055 19/.1055 37/.0822 37/.0822 37/.0973 37/.0973 37/.1162 37/.1162

14 12 10 10 10 10 8 8 8 8 6 6 6 6 6 6 4 4 4 4 3 3 2 2

0.020 0.020 0.020 0.020 0.036 0.036 0.036 0.036 0.048 0.048 0.048 0.048 0.059 0.059 0.059 0.059 0.059 0.059 0.070 0.070 0.070 0.070 0.070 0.070

0.51 0.51 0.51 0.51 0.91 0.91 0.91 0.91 1.22 1.22 1.22 1.22 1.50 1.50 1.50 1.50 1.50 1.50 1.78 1.78 1.78 1.78 1.78 1.78

0.045 0.045 0.045 0.045 0.060 0.060 0.060 0.060 0.080 0.080 0.080 0.080 0.080 0.080 0.080 0.080 0.080 0.110 0.110 0.110 0.110 0.110 0.110 0.110

1.14 1.14 1.14 1.14 1.52 1.52 1.52 1.52 2.03 2.03 2.03 2.03 2.03 2.03 2.03 2.03 2.03 2.79 2.79 2.79 2.79 2.79 2.79 2.79

0.365 0.420 0.505 0.505 0.600 0.655 0.690 0.760 0.875 0.970 1.000 1.100 1.225 1.360 1.320 1.455 1.545 1.770 1.740 1.945 1.990 2.190 2.270 2.505

9.27 10.67 12.83 12.83 15.24 16.64 17.53 19.30 22.28 24.64 25.40 27.94 31.12 34.54 33.53 36.96 39.24 44.96 44.20 49.40 50.55 55.63 57.66 63.63

52 86 135 135 189 241 300 383 446 578 710 919 1080 1413 1340 1760 2130 2796 2494 3281 3474 4586 4934 6509

77 128 200 200 281 359 446 570 664 860 1057 1368 1607 2103 1994 2619 3170 4161 3696 4883 5170 6825 7343 9687

100 138 209 209 308 373 434 533 650 824 964 1227 1447 1830 1754 2252 2630 3502 3177 4107 4263 5585 5890 7694

149 205 311 311 458 555 646 793 967 1226 1435 1826 2153 2723 2610 3351 3914 5212 4728 6112 6344 8312 8765 11450

Dimensions and weights are nominal; subject to industry tolerances. *Non-stock item, minimum runs apply. Please consult Customer Service for price and delivery. **E-2 Color Code. 1Approved as TYPE TC-ER for Exposed Run applications as defined by NEC.

Phone: 888-593-3355 www.generalcable.com


SPEC 4800

January, 2008

20/10

PE/PVC/PVC, Control, Unshielded 600V (18 AWG/16 AWG)—E-1 Color Code Product Construction Conductor:

• 18 AWG and 16 AWG • Bare, annealed copper per ASTM B3 • Class B stranding per ASTM B8

Insulation:

• Clear Polyethylene (PE)

Conductor Jacket:

CATALOG NUMBER

AVG. COND. MINIMUM INSULATION NO. SIZE THICKNESS OF (AWG/ COND. kcmil) inCHES mm

MINIMUM AVG. JACKET THICKNESS INCHES mm

NOMINAL CABLE O.D. INCHES mm

COPPER WEIGHT

NET WEIGHT

LBS/ LBS/ 1000 FT kg/km 1000 FT kg/km

18 AWG MULTI CONDUCTORS 365290* 2 Flat 2 365300* 3 363310* 4 543640* 5 365320* 7 365330* 9 365340* 547230* 12 365350* 19

18 18 18 18 18 18 18 18 18

0.025 0.025 0.025 0.025 0.025 0.025 0.025 0.025 0.025

283530* 365360* 365370* 647530* 283540* 365380* 365390* 647550* 365400*

16 16 16 16 16 16 16 16 16

0.025 0.025 0.025 0.025 0.025 0.025 0.025 0.025 0.025

0.64 0.64 0.64 0.64 0.64 0.64 0.64 0.64 0.64

0.045 0.045 0.045 0.045 0.045 0.045 0.045 0.045 0.060

1.14 1.14 1.14 1.14 1.14 1.14 1.14 1.14 1.52

.200 x .300

5.10 x 7.50

0.30 0.31 0.34 0.37 0.40 0.46 0.51 0.63

7.6 7.9 8.6 9.4 10.2 11.7 13.0 16.0

10 10 15 20 25 36 46 61 96

15 15 23 30 38 53 68 91 143

39 41 49 60 71 90 113 145 229

58 61 73 89 106 134 168 216 341

16 16 24 32 40 56 73 97 153

24 24 36 48 60 84 108 144 228

43 49 62 77 92 118 148 209 304

84 73 92 115 137 176 220 311 452

16 AWG MULTI CONDUCTORS 2 Flat 2 3 4 5 7 9 12 19

0.64 0.64 0.64 0.64 0.64 0.64 0.64 0.64 0.64

0.045 0.045 0.045 0.045 0.045 0.045 0.045 0.060 0.060

1.14 1.14 1.14 1.14 1.14 1.14 1.14 1.52 1.52

.210 x .320

5.30 x 8.10

0.32 0.34 0.37 0.40 0.43 0.50 0.59 0.69

8.1 8.6 9.4 10.2 10.9 12.7 15.0 17.5

Dimensions and weights are nominal; subject to industry tolerances. *Non-stock item, minimum runs apply. Please consult Customer Service for price and delivery.

• Color-coded Polyvinyl Chloride (PVC) • Color-coded per ICEA Method 1; Table E-1 (includes white and green)

Cable Core:

• Conductors are cabled with non-hygroscopic fillers as necessary, and an overall binder tape

Overall Jacket:

• Flame-retardant and sunlight-resistant Polyvinyl Chloride (PVC)

Print:

• General Cable® SUBSTATION CONTROL CABLE X/C XXAWG CU/PE/PVC 75˚C 600V YEAR OF MFG SEQUENTIAL FOOTAGE MARK

Options:

• Tinned copper conductors • Class C stranding per ASTM B8 • Insulated or uninsulated ground conductors • Copper tape shield or aluminum/polymer tape shield with tinned copper drain wire over cable core • Bare or tinned copper braided basket weave shield • Duralox® aluminum or galvanized steel interlocked armor • Intergrabon® Moisture Barrier system • Corrugated copper tape shield longitudinally applied

Applications:

• For applications where environmental factors require cable characteristics including flameretardance, resistance to chemicals, abrasion and resistance to the harmful effects of sunlight and weather • May be installed in ducts, cable trays, conduit, Class I Division 2 industrial hazardous locations or continuous rigid cable supports

Features:

• Rated at 75˚C • Thermoplastic PE insulation provides chemical resistance and excellent electrical properties • Flame-retardant PVC conductor jacket is colorcoded for easy circuit identification • Flame-retardant PVC overall jacket provides abrasion, chemical, sunlight and weathering resistance

Compliances:

Industry Compliances: • ICEA S-73-532 Other Compliances: • Meets EPA 10 CFR, Part 261 for leachable lead content per TCLP method

Phone: 888-593-3355 www.generalcable.com


SPEC 4850

January, 2008

20/10

PE/PVC/PVC, Control, Unshielded 600V (14 AWG—10 AWG)—E-1 Color Code Product Construction Conductor:

• 14 AWG thru 10 AWG • Bare, annealed copper per ASTM B3 • Class B stranding per ASTM B8

Insulation:

• Clear Polyethylene (PE)

Conductor Jacket:

CATALOG NUMBER

AVG. COND. MINIMUM INSULATION NO. SIZE THICKNESS OF (AWG/ COND. kcmil) inCHES mm

MINIMUM AVG. JACKET THICKNESS INCHES mm

NOMINAL CABLE O.D. INCHES mm

COPPER WEIGHT

NET WEIGHT

LBS/ LBS/ 1000 FT kg/km 1000 FT kg/km

14 AWG MULTI CONDUCTORS 269080* 2 Flat 2 647560* 3 365410* 4 267950* 5 286130* 7 365240* 9 365430* 647590* 12 647600* 19

14 14 14 14 14 14 14 14 14

0.030 0.030 0.030 0.030 0.030 0.030 0.030 0.030 0.030

257750* 257770* 267830* 257730* 270720* 256750* 270730* 267860* 647650*

2 Flat 2 3 4 5 7 9 12 19

12 12 12 12 12 12 12 12 12

0.030 0.030 0.030 0.030 0.030 0.030 0.030 0.030 0.030

257760* 2 Flat 2 257780* 3 267840* 4 257740* 5 257790* 7 257800* 9 261690* 257810* 12 271740* 19

10 10 10 10 10 10 10 10 10

0.030 0.030 0.030 0.030 0.030 0.030 0.030 0.030 0.030

0.76 0.76 0.76 0.76 0.76 0.76 0.76 0.76 0.76

0.045 0.045 0.045 0.045 0.045 0.045 0.060 0.060 0.060

1.14 1.14 1.14 1.14 1.14 1.14 1.52 1.52 1.52

.230 x .370

5.30 x 9.30

0.37 0.39 0.42 0.46 0.50 0.62 0.69 0.80

9.4 9.9 10.7 11.7 12.7 15.8 17.5 20.3

25 26 38 51 64 90 116 154 244

38 38 57 76 95 133 172 229 363

57 66 87 108 130 173 236 300 443

85 98 130 161 194 258 351 447 659

40 41 61 81 102 143 184 245 388

60 61 91 121 152 212 273 364 577

82 87 116 147 180 255 321 412 654

122 130 173 219 268 380 478 613 973

64 65 97 129 162 227 292 389 616

96 96 96 144 192 241 337 434 579

110 130 170 235 286 365 466 626 930

164 194 253 350 426 543 694 932 1384

12 AWG MULTI CONDUCTORS 0.76 0.76 0.76 0.76 0.76 0.76 0.76 0.76 0.76

0.045 0.045 0.045 0.045 0.045 0.060 0.060 0.060 0.080

1.14 1.14 1.14 1.14 1.14 1.52 1.52 1.52 2.03

.250 x .400

6.40 x 10.30

0.40 0.43 0.47 0.52 0.59 0.68 0.77 0.94

10.2 10.9 11.9 13.2 15.0 17.3 19.6 23.9

10 AWG MULTI CONDUCTORS 0.76 0.76 0.76 0.76 0.76 0.76 0.76 0.76 0.76

0.045 0.045 0.045 0.060 0.060 0.060 0.060 0.080 0.080

1.14 1.14 1.14 1.52 1.52 1.52 1.52 2.03 2.03

.270 x .450

6.90 x 11.40

0.45 0.48 0.52 0.60 0.66 0.76 0.90 1.05

11.4 12.2 13.2 15.2 16.8 19.3 22.9 26.7

Dimensions and weights are nominal; subject to industry tolerances. *Non-stock item, minimum runs apply. Please consult Customer Service for price and delivery.

• Color-coded Polyvinyl Chloride (PVC) • Color-coded per ICEA Method 1; Table E-1 (includes white and green)

Cable Core:

• Conductors are cabled with non-hygroscopic fillers as necessary, and an overall binder tape

Overall Jacket:

• Flame-retardant and sunlight-resistant Polyvinyl Chloride (PVC)

Print:

• General Cable® SUBSTATION CONTROL CABLE X/C XXAWG CU/PE/PVC 75˚C 600V YEAR OF MFG SEQUENTIAL FOOTAGE MARK

Options:

• Tinned copper conductors • Class C stranding per ASTM B8 • Insulated or uninsulated ground conductors • Copper tape shield or aluminum/polymer tape shield with tinned copper drain wire over cable core • Bare or tinned copper braided basket weave shield • Duralox® aluminum or galvanized steel interlocked armor • Intergrabon® Moisture Barrier system • Corrugated copper tape shield longitudinally applied

Applications:

• For applications where environmental factors require cable characteristics including flameretardance, resistance to chemicals, abrasion and resistance to the harmful effects of sunlight and weather • May be installed in ducts, cable trays, conduit, Class I Division 2 industrial hazardous locations or continuous rigid cable supports

Features:

• Rated at 75˚C • Thermoplastic PE insulation provides chemical resistance and excellent electrical properties • Flame-retardant PVC conductor jacket is colorcoded for easy circuit identification • Flame-retardant PVC overall jacket provides abrasion, chemical, sunlight and weathering resistance

Compliances:

Industry Compliances: • ICEA S-73-532 Other Compliances: • Meets EPA 10 CFR, Part 261 for leachable lead content per TCLP method

Phone: 888-593-3355 www.generalcable.com


SPEC 4900

February, 2008

GenFree

XLPO/LSZH, Control 600V, UL Type TC-LS-ER1—E-2 Color Code Product Construction Conductor:

• 14 AWG thru 10 AWG fully annealed stranded tinned copper per ASTM B33 • Class B stranding per ASTM B8

Insulation:

CATALOG NUMBER

COPPER MINIMUM AVG. MINIMUM AVG. WEIGHT NET WEIGHT INSULATION JACKET NOMINAL NO. COND. THICKNESS CABLE O.D. LBS/ OF SIZE COND. THICKNESS LBS/ COND. (AWG) STRAND inCHES mm INCHES mm INCHES mm 1000 FT kg/km 1000 FT kg/km

14 AWG MULTI CONDUCTORS 394280 394290* 394300 394310 394320 394330 394340 394350 394360 394370* 394380* 394390*

2 Flat 2 3 4 5 7 9 12 19 25 30 37

14 14 14 14 14 14 14 14 14 14 14 14

7/.0242 7/.0242 7/.0242 7/.0242 7/.0242 7/.0242 7/.0242 7/.0242 7/.0242 7/.0242 7/.0242 7/.0242

0.030 0.030 0.030 0.030 0.030 0.030 0.030 0.030 0.030 0.030 0.030 0.030

0.76 0.76 0.76 0.76 0.76 0.76 0.76 0.76 0.76 0.76 0.76 0.76

0.045 0.045 0.045 0.045 0.045 0.045 0.060 0.060 0.060 0.080 0.080 0.080

1.14 1.14 1.14 1.14 1.14 1.14 1.52 1.52 1.52 2.03 2.03 2.03

.365 x .230 9.30 x 5.80

0.370 0.390 0.425 0.465 0.505 0.620 0.700 0.815 0.935 1.030 1.110

9.40 9.91 10.80 11.81 12.83 15.75 17.78 20.70 23.75 26.16 28.19

26 26 39 53 66 92 118 158 250 323 387 466

38 39 59 78 98 137 176 235 372 481 576 694

61 71 92 115 139 173 240 301 468 624 747 875

91 106 137 171 207 257 357 448 696 929 1112 1302

40 41 85 64 85 106 149 191 247 391 515 618 762

60 82 61 94 127 148 95 124 127 157 158 191 221 268 285 337 368 428 582 688 767 854 920 1002 1134 1240

122 140 220 185 234 284 399 502 637 1024 1271 1491 1845

64 65 134 100 134 167 234 295 402

95 97 199 150 199 249 349 440 598

168 190 335 256 348 423 567 691 696

12 AWG MULTI CONDUCTORS 394400 2 Flat 2 394410* 3944202 3+ Grnd 3 394430 4 394440 5 394450 7 394460 9 394470 12 394480 19 394490 25 394500* 30 394510* 37 394520*

12 12 12 12 12 12 12 12 12 12 12 12 12

7/.0305 7/.0305 7/.0305 7/.0305 7/.0305 7/.0305 7/.0305 7/.0305 7/.0305 7/.0305 7/.0305 7/.0305 7/.0305

0.030 0.030 0.030 0.030 0.030 0.030 0.030 0.030 0.030 0.030 0.030 0.030 0.030

0.76 0.76 0.76 0.76 0.76 0.76 0.76 0.76 0.76 0.76 0.76 0.76 0.76

0.045 0.045 0.045 0.045 0.045 0.045 0.060 0.060 0.060 0.080 0.080 0.080 0.080

1.14 1.14 1.14 1.14 1.14 1.14 1.52 1.52 1.52 2.03 2.03 2.03 2.03

.400 x .245 10.20 x 6.20

0.410 0.410 0.435 0.475 0.520 0.595 0.695 0.765 0.940 1.095 1.150 1.240

10.41 10.41 11.05 12.07 13.21 15.11 17.65 19.43 23.88 27.81 29.21 31.50

10 AWG MULTI CONDUCTORS 394530 2 Flat 2 394540* 3945502 3+ Grnd 3 394560 4 394570 5 394580 7 394590 9 394600 12 394610

10 10 10 10 10 10 10 10 10

7/.0385 7/.0385 7/.0385 7/.0385 7/.0385 7/.0385 7/.0385 7/.0385 7/.0385

0.030 0.030 0.030 0.030 0.030 0.030 0.030 0.030 0.030

0.76 0.76 0.76 0.76 0.76 0.76 0.76 0.76 0.76

0.045 0.045 0.045 0.045 0.060 0.060 0.060 0.060 0.080

1.14 1.14 1.14 1.14 1.52 1.52 1.52 1.52 2.03

.445 x .270 11.30 x 6.90

0.455 0.485 0.485 0.560 0.615 0.670 0.760 0.905

11.56 12.32 12.32 14.22 15.62 17.02 19.30 22.99

Dimensions and weights are nominal; subject to industry tolerances. *Non-stock item, minimum runs apply. Please consult Customer Service for price and delivery. 1 Approved as -ER for Exposed Run applications of 3 or more conductors as defined by the NEC. 2 This construction does not require an -ER mark.

113 128 225 172 234 284 381 464 651

• Flame-retardant, Low-Smoke, Cross-Linked Polyolefin (XLPO) • Color-coded: per ICEA Method 1; Table E-2 (Does not include white or green)

Jacket:

• Flame-retardant, Sunlight-resistant, Low-Smoke, Zero-Halogen Polyolefin (LSZH)

Print

• GENERAL CABLE® (WC) GENFREE™ XX/C XXAWG xlpo/lszh (UL) Type TC-LS-ER1 XHHW-2 CDRS 90°C WET or DRY 600V DIR BUR SUN RES ROHS DAY/MONTH/YEAR OF MFG sequential footage mark

Options:

• Class C stranding • E-1 Color Code • Overall shielded multi conductor • Other constructions available upon request

Applications:

• In free air, raceways, aerial or direct burial • In wet or dry locations • Permitted for use in Class I Division 2 industrial hazardous locations per NEC • Permitted for Exposed Run (ER) use in accordance with the NEC for 3 or more conductors

Features:

• Rated at 90˚C wet or dry • Ripcord applied to all cables with jacket thickness of 60 mils or less • Excellent physical and electrical properties • Excellent moisture resistance • Excellent resistance to compression and impact • Chemical-resistant • Low coefficient of friction for easy pulling • Sunlight- and weather-resistant • Meets cold bend test at -30˚C • Low-Smoke, Zero-Halogen jacket is environmentally safe • Low-Smoke, Zero-Halogen jacket reduces the amount of toxic and corrosive gases emitted during combustion, providing a safer environment for personnel and equipment during the hazards of fire • Meets the crush and impact requirements of Type MC cable for 3 or more conductors

Compliances:

Industry Compliances: • UL 44 Type XHHW-2 • UL 1277 Type TC-LS-ER • UL 1581 • ROHS Compliant Flame Tests Compliances: • UL 1581 • UL 1277 • UL 1685 • IEEE 1202 Other Compliances: • EPA 40 CFR, Part 261 for leachable lead content per TCLP • OSHA acceptable

Packaging:

• Material cut to length and shipped on non-returnable wood reels

Phone: 888-593-3355 www.generalcable.com


SPEC 4925

February, 2008

GenFree

XLPO/LSZH, Control, Shielded 600V, UL Type TC-LS-ER1, Overall Shielded—E-2 Color Code Product Construction Conductor:

• 16 AWG thru 10 AWG fully annealed stranded tinned copper per ASTM B33 • Class B stranding per ASTM B8

Insulation:

• Flame-retardant, Low-Smoke, Cross-Linked Polyolefin (XLPO) • Color-coded per ICEA Method 1; Table E-2 (Does not include white or green)

CATALOG NUMBER

COPPER MINIMUM AVG. MINIMUM AVG. WEIGHT NET WEIGHT INSULATION JACKET NOMINAL NO. COND. THICKNESS CABLE O.D. LBS/ OF SIZE COND. THICKNESS LBS/ COND. (AWG) STRAND inCHES mm INCHES mm INCHES mm 1000 FT kg/km 1000 FT kg/km

2 3

16 16

7/.0192 0.025 0.64 0.045 1.14 0.320 8.13 7/.0192 0.025 0.64 0.045 1.14 0.335 8.51

19 27

28 40

52 66

77 98

43 63 82 101 140 180 238 375 484 579 696

74 95 118 142 176 243 304 471 627 750 878

110 141 176 211 262 362 452 701 933 1116 1307

OVERALL SHIELDED MULTI CONDUCTORS 14 AWG CONDUCTORS 394640* 394650* 394660* 394670* 394680* 394690* 394700* 394710* 394720* 394730* 394740*

2 3 4 5 7 9 12 19 25 30 37

14 14 14 14 14 14 14 14 14 14 14

7/.0242 7/.0242 7/.0242 7/.0242 7/.0242 7/.0242 7/.0242 7/.0242 7/.0242 7/.0242 7/.0242

0.030 0.030 0.030 0.030 0.030 0.030 0.030 0.030 0.030 0.030 0.030

0.76 0.76 0.76 0.76 0.76 0.76 0.76 0.76 0.76 0.76 0.76

0.045 0.045 0.045 0.045 0.045 0.060 0.060 0.060 0.080 0.080 0.080

1.14 1.14 1.14 1.14 1.14 1.52 1.52 1.52 2.03 2.03 2.03

0.375 0.395 0.430 0.470 0.510 0.625 0.705 0.820 0.940 1.035 1.115

9.53 10.03 10.92 11.94 12.95 15.88 17.91 20.83 25.53 26.29 28.32

29 42 55 68 94 121 160 252 325 389 468

OVERALL SHIELDED MULTI CONDUCTORS 12 AWG CONDUCTORS 394750* 394760* 394770* 394780* 394790* 394800* 394810* 394820* 394830* 394840* 394850*

2 3 4 5 7 9 12 19 25 30 37

12 12 12 12 12 12 12 12 12 12 12

7/.0305 7/.0305 7/.0305 7/.0305 7/.0305 7/.0305 7/.0305 7/.0305 7/.0305 7/.0305 7/.0305

0.030 0.030 0.030 0.030 0.030 0.030 0.030 0.030 0.030 0.030 0.030

0.76 0.76 0.76 0.76 0.76 0.76 0.76 0.76 0.76 0.76 0.76

0.045 0.045 0.045 0.045 0.060 0.060 0.060 0.080 0.080 0.080 0.080

1.14 1.14 1.14 1.14 1.52 1.52 1.52 2.03 2.03 2.03 2.03

0.415 0.440 0.480 0.525 0.600 0.700 0.770 0.945 1.100 1.155 1.245

10.45 11.18 12.19 13.34 15.24 17.78 19.56 24.00 27.94 29.80 31.62

43 66 87 108 151 193 249 393 517 620 764

64 98 129 162 225 287 371 585 769 923 1137

97 144 127 189 160 238 194 289 271 403 340 506 431 641 691 1028 857 1275 1005 1496 1243 1850

OVERALL SHIELDED MULTI CONDUCTORS 10 AWG CONDUCTORS 394860* 394870* 394880* 394890* 394900* 394910* 394920*

2 3 4 5 7 9 12

10 10 10 10 10 10 10

7/.0385 7/.0385 7/.0385 7/.0385 7/.0385 7/.0385 7/.0385

0.030 0.030 0.030 0.030 0.030 0.030 0.030

0.76 0.76 0.76 0.76 0.76 0.76 0.76

0.045 0.045 0.060 0.060 0.060 0.060 0.080

1.14 1.14 1.52 1.52 1.52 1.52 2.03

0.460 0.490 0.565 0.620 0.675 0.765 0.910

11.68 12.45 14.35 15.75 17.15 19.43 23.11

68 103 136 170 237 298 404

Dimensions and weights are nominal; subject to industry tolerances. *Non-stock item, minimum runs apply. Please consult Customer Service for price and delivery. 1 Approved as -ER for Exposed Run applications of 3 or more conductors as defined by the NEC.

Overall shielded multi-conductor cable • Overall shield is Flexfoil® aluminum/polyester in contact with stranded tinned copper drain wire

Jacket:

• Flame-retardant, Sunlight-resistant, Low-Smoke, Zero-Halogen Polyolefin (LSZH)

OVERALL SHIELDED MULTI CONDUCTORS 16 AWG CONDUCTORS 394960* 394630*

Shield:

101 155 202 253 353 443 601

131 175 237 287 384 467 654

195 260 353 427 571 695 973

Print

• GENERAL CABLE® (WC) SHIELDED GENFREE™ XX/C XXAWG XLPO/LSZH (UL) TYPE TC-LS-ER1 XHHW-2 CDRS 90˚C WET OR DRY 600V DIR BUR SUN RES ROHS DAY/MONTH/YEAR OF MFG SEQUENTIAL FOOTAGE MARK

Options:

• Class C stranding • E-1 Color Code • Unshielded multi conductors • Other constructions available upon request

Applications:

• In free air, raceway, aerial and direct burial • In wet or dry locations • Permitted for use in Class I Division 2 industrial hazardous locations per NEC • Permitted for Exposed Run (ER) use in accordance with the NEC for 3 or more conductors

Features:

• Rated at 90˚C wet or dry • Ripcord applied to all cables with jacket thickness of 60 mils or less • Excellent physical and electrical properties • Excellent moisture resistance • Excellent resistance to compression and impact • Chemical-resistant • Low coefficient of friction for easy pulling • Sunlight- and weather-resistant • Meets cold bend test at -30˚C • Low-Smoke, Zero-Halogen jacket is environmentally safe • Low-Smoke, Zero-Halogen jacket reduces the amount of toxic and corrosive gases emitted during combustion, providing a safer environment for personnel and equipment during the hazards of fire • Meets the crush and impact requirements of Type MC cable for 3 or more conductors

Compliances:

Industry Compliances: • UL 44 Type XHHW-2 • UL 1277 Type TC-LS-ER • UL 1581 • ROHS Compliant Flame Tests Compliances: • UL 1581 • UL 1277 • UL 1685 • IEEE 1202 Other Compliances: • EPA 40 CFR, Part 261 for leachable lead content per TCLP • OSHA acceptable

Packaging:

• Material cut to length and shipped on non-returnable wood reels

Phone: 888-593-3355 www.generalcable.com


SPEC 4950

February, 2008

GenFree

XLPO/LSZH, Low-Voltage Power, Unshielded 600V, UL Type TC-LS—Method 4 Color Code Features (cont’d.):

Product Construction Conductor:

• Meets cold bend test at -30˚C • Low-Smoke, Zero-Halogen jacket is environmentally safe • Low-Smoke, Zero-Halogen jacket reduces the amount of toxic and corrosive gases emitted during combustion, providing a safer environment for personnel and equipment during the hazards of fire

Options:

• 14 AWG thru 750 kcmil tinned, annealed copper per ASTM B33 • Class B stranding per ASTM B8

Insulation:

• In free air, raceways, aerial or direct burial • In wet or dry locations • Permitted for use in Class I Division 2 industrial hazardous locations per NEC

Features:

Ground:

• Rated at 90˚C wet or dry • Ripcord applied to all cables with jacket thickness of 60 mils or less • Excellent physical, thermal and electrical properties • Excellent moisture resistance • Excellent resistance to crush, compression and impact • Chemical-resistant • Low coefficient of friction for easy pulling • Sunlight- and weather-resistant

• Uninsulated tinned annealed copper per ASTM B3 • Class B stranding per ASTM B8

Jacket:

• Flame-retardant, Sunlight-resistant, Low-Smoke, Zero-Halogen Polyolefin (LSZH)

Print:

• GENERAL CABLE® (WC) OR (MI) GENFREE™ XX/C XXAWG XLPO/LSZH (UL) TYPE TC-LS XHHW-2 CDRS 90˚C WET OR DRY 600V DIR BUR SUN RES ROHS DAY/MONTH/YEAR OF MFG SEQUENTIAL FOOTAGE MARK

CATALOG NUMBER

NO. OF COND.

394930* 394940* 394950* 14428.030800 14428.040800* 14428.030600 14428.040600* 14428.030400 14428.040400* 14428.030200 14428.040200* 14428.030100* 14428.040100* 14428.035100 14428.045100* 14428.035200 14428.045200* 14428.035300* 14428.045300* 14428.035400 14428.045400* 14428.036000* 14428.046000* 14428.036200 14428.046200* 14428.036500 14428.046500* 14428.037000* 14428.047000*

3 3 3 3 4 3 4 3 4 3 4 3 4 3 4 3 4 3 4 3 4 3 4 3 4 3 4 3 4

14 12 10 8 8 6 6 4 4 2 2 1 1 1/0 1/0 2/0 2/0 3/0 3/0 4/0 4/0 250 250 350 350 500 500 750 750

Industry Compliances: • UL 44 Type XHHW-2 • UL 1277 Type TC-LS • UL 1581 • ROHS Compliant Flame Tests Compliances: • UL 1581 • UL 1277 • UL 1685 • IEEE 1202 Other Compliances: • EPA 40 CFR, Part 261 for leachable lead content per TCLP • OSHA acceptable

Applications:

• Flame-retardant, Low-Smoke, Cross-Linked Polyolefin (XLPO) • Color-coded per ICEA Method 4; Individual conductors colored black with conductor number surface printed in contrasting ink

COND. SIZE (AWG/ kcmil)

Compliances:

• Class C stranding • E-1 or E-2 Color Code • Insulated ground conductors • Overall shielded multi conductors • Other constructions available upon request

GROUND WIRE SIZE (AWG)

COND. STRAND 7/.0242 7/.0305 7/.0385 7/.0486 7/.0486 7/.0612 7/.0612 7/.0772 7/.0772 7/.0974 7/.0974 19/.0664 19/.0664 19/.0745 19/.0745 19/.0837 19/.0837 19/.0940 19/.0940 19/.1055 19/.1055 37/.0822 37/.0822 37/.0973 37/.0973 37/.1162 37/.1162 61/.1109 61/.1109

MINIMUM AVG. INSULATION THICKNESS INCHES

mm

Packaging:

• Material cut to length and shipped on non-returnable wood reels

MINIMUM AVG. JACKET THICKNESS NOMINAL CABLE O.D. INCHES

mm

INCHES

COPPER WEIGHT

mm

LBS/ 1000 FT

10.92 12.19 14.35 16.64 18.29 18.80 20.07 22.35 24.13 25.65 27.69 28.45 31.37 31.12 33.78 33.02 36.58 36.07 39.88 39.12 45.47 44.70 48.64 49.78 54.99 57.02 62.87 71.37 79.12

55 87 136 190 242 297 384 442 578 703 919 872 1136 1069 1413 1340 1760 1717 2245 2130 2796 2494 3282 3474 4577 4934 6509 7278 9712

NET WEIGHT

kg/km

LBS/ 1000 FT

kg/km

82 129 202 283 360 442 571 658 861 1046 1368 1298 1691 1591 2103 1994 2619 2555 3341 3170 4161 3712 4884 5170 6811 7343 9687 10831 14453

118 160 237 314 393 456 561 642 822 979 1235 1021 1521 1439 1820 1720 2208 2176 2788 2614 3495 3184 4019 4187 5436 5847 7607 9145 11805

176 238 353 467 585 679 835 955 1223 1457 1838 1594 2264 2142 2709 2560 3286 3238 3405 3890 5201 4738 5981 6231 8090 8702 11321 13610 17569

14 AWG - 750 kcmil MULTI CONDUCTORS 14 12 10 10 10 8 8 8 8 6 6 6 6 6 6 6 6 4 4 4 4 4 4 3 3 2 2 1 1

0.030 0.030 0.030 0.045 0.045 0.045 0.045 0.045 0.045 0.045 0.045 0.055 0.055 0.055 0.055 0.055 0.055 0.055 0.055 0.055 0.055 0.065 0.065 0.065 0.065 0.065 0.065 0.080 0.080

0.76 0.76 0.76 1.14 1.14 1.14 1.14 1.14 1.14 1.14 1.14 1.40 1.40 1.40 1.40 1.40 1.40 1.40 1.40 1.40 1.40 1.65 1.65 1.65 1.65 1.65 1.65 2.03 2.03

0.045 0.045 0.060 0.060 0.060 0.060 0.060 0.080 0.080 0.080 0.080 0.080 0.080 0.080 0.080 0.080 0.080 0.080 0.080 0.080 0.110 0.110 0.110 0.110 0.110 0.110 0.110 0.140 0.140

1.14 1.14 1.52 1.52 1.52 1.52 1.52 2.03 2.03 2.03 2.03 2.03 2.03 2.03 2.03 2.03 2.03 2.03 2.03 2.03 2.79 2.79 2.79 2.79 2.79 2.79 2.79 3.56 3.56

0.430 0.480 0.565 0.655 0.720 0.740 0.790 0.880 0.950 1.010 1.090 1.120 1.235 1.225 1.330 1.300 1.440 1.420 1.570 1.540 1.790 1.760 1.915 1.960 2.165 2.245 2.475 2.810 3.115

Dimensions and weights are nominal; subject to industry tolerances. *Non-stock item, minimum runs apply. Please consult Customer Service for price and delivery.

Phone: 888-593-3355 www.generalcable.com


Industrial Cables

Date of Issue 01/09 Section 5

600V Industrial Power Cables SPECIFICATION NO.

PRODUCT DESCRIPTION

5050†

DuraSheath®

EPR/HYP, Low-Voltage Power, Unshielded 600V, UL Type RHH/RHW-2/USE-2 LS

REVISION DATE

Jan. 2008

5100

Unicon® FREP®

FR-EPR, Low-Voltage Power, Unshielded 600V, UL Type RHH/RHW-2/USE-2

Jan. 2008

5150

XHHW-2 VW-1

XLPE, Control and Low-Voltage Power, Unshielded 600V, UL Type SIS/XHHW-2, VW-1 Rated

Jan. 2008

5200†

XHHW-2

XLPE, Low-Voltage Power, Unshielded 600V, UL Type XHHW-2, c(UL) RW-90

Jan. 2008

5250†

Unicon® XLPE

XLPE, Low-Voltage Power, Unshielded 600V, UL Type RHH/RHW-2/USE-2

Jan. 2009

5300† Super Vu-Tron® EPR/CPE, Diesel Locomotive Cable 2000V, Type DLO, 600V, UL Type RHH/RHW, 1000V, CSA Type R90

Oct. 2008

5350† GenFree™ LSZH XLPO, Low-Smoke, Zero-Halogen (LSZH), Low-Voltage Power, Unshielded 600V, Type RHH/RHW-LS/USE, CSA AWM I A/B, Class B

Aug. 2008

5400† GenFree™ LSZH XLPO, Low-Smoke, Zero-Halogen (LSZH), Low-Voltage Power, Unshielded 600V, Type RHH/RHW-LS/USE, CSA AWM I A/B, Class I

Aug. 2008

5500†

RW90

XLPE, Building Wire 600V, CSA Type RW90 (-40˚C), Single Conductor, Copper

Jan. 2009

5550†

RW90

XLPE, Building Wire 600V, CSA Type RW90 (-40˚C), Single Conductor, Aluminum

Jan. 2009

5600†

RWU90

XLPE, Building Wire 1000V, CSA Type RWU90 (-40˚C), Single Conductor, Copper

Jan. 2009

5650†

RWU90

XLPE, Building Wire 1000V, CSA Type RWU90 (-40˚C), Single Conductor, Aluminum

Jan. 2009

5700†

RHH/RHW-2

XLPE, Low-Voltage Power, Unshielded 2000V, UL Type RHH/RHW-2, Single Conductor, Aluminum

Oct. 2008

†Indicates

these products are stocked by General Cable

Phone: 888-593-3355 www.generalcable.com


SPEC 5050

January, 2008

DuraSheath

®

EPR/HYP, Low-Voltage Power, Unshielded 600V, UL Type RHH/RHW-2/USE-2 LS

Product Construction Conductor:

Features:

• Rated at 90˚C wet or dry • Deformation-resistant at high temperatures • Excellent moisture resistance, exceeds UL 44 • Stable electrical properties over a broad temperature range • Excellent flexibility at low temperatures; suitable for installation in sub-zero conditions • Extra-tough, mechanically rugged composite insulation and jacket construction • Resistant to most oils and chemicals • UV/sunlight-resistant • Meets UL-44 cold bend test at -40˚C • Colors available upon request

• 14 AWG thru 1000 kcmil tin-coated copper compressed Class B stranding per ASTM B33 and B8

Insulation:

• Flame-retardant Ethylene Propylene Rubber (EPR) colored for contrast with black lowlead Hypalon® Chlorosulfonated Polyethylene (CSPE)/Elastomer blend

Print:

• GENERAL CABLE® (MI) DURASHEATH LL TYPE USE-2 OR RHH OR RHW-2 LS VW-1 (SIZE) EP 600 VOLTS SUN RES FOR CT USE (UL) DAY/MONTH/YEAR OF MFG SEQUENTIAL FOOTAGE MARK

Compliances:

* Sizes smaller than 1/0 AWG do not include “FOR CT USE”

• Ideally suited for use in a broad range of commercial, industrial and utility applications where reliability is a major concern and where maximum performance will be demanded • In free air, raceways or direct burial • For use in aerial, conduit, open tray and underground duct/installations

CATALOG NUMBER

COND. STRAND

14511.411400 14511.411200 14511.411000 14511.410800 14511.410600 14511.410400 14511.710200 14511.715100 14511.715200 14511.715400 14511.716000 14511.716200 14511.716500 14511.717000 14511.717500

14 12 10 8 6 4 2 1/0 2/0 4/0 250 350 500 750 1000

7/.0242 7/.0305 7/.0385 7/.0486 7/.0612 7/.0772 7/.0974 19/.0740 19/.0837 19/.1055 37/.0822 37/.0973 37/.1162 61/.1109 61/.1280

Flame Tests Compliances: • UL 1581 VW-1 • For 1/0 AWG and larger: IEEE 383, IEEE 1202/CSA FT-4 Optional Flame Tests: (See General Cable Sales Representative) Other Compliances: • EPA 40 CFR, Part 261 for leachable lead content per TCLP • OSHA acceptable

Packaging:

• Material cut to length and shipped on non-returnable wood reels

Industry Compliances: • National Electric Code (NEC) • ICEA S-95-658 / NEMA WC70 • “FOR CT USE” on 1/0 AWG and larger in accordance with the NEC • UL 44 Type RHH/RHW-2 • UL 854 Type USE-2 • Low-smoke rating per UL

Applications:

COND. SIZE (AWG/ kcmil)

Compliances (cont’d.):

NOMINAL COND. DIAMETER INCHES mm

MINIMUM AVG. INSULATION THICKNESS DIAMETER INCHES mm INCHES mm

MINIMUM AVG. JACKET THICKNESS DIAMETER INCHES mm INCHES mm

COPPER WEIGHT

NET WEIGHT

LBS/ 1000 FT

kg/ km

LBS/ 1000 FT

kg/ km

13 20 32 50 81 129 205 326 411 653 772 1081 1542 2316 3806

19 30 48 75 121 192 305 485 612 972 1149 1609 2295 3447 5664

24 33 48 77 122 178 265 422 518 785 960 1299 1803 2664 3989

36 49 71 115 182 265 394 628 771 1168 1429 1933 2683 3965 5936

14 AWG - 1000 kcmil CONDUCTORS 0.07 0.09 0.12 0.15 0.18 0.23 0.29 0.37 0.41 0.52 0.56 0.67 0.80 0.98 1.13

1.78 2.29 3.05 3.81 4.57 5.84 7.37 9.40 10.41 13.21 14.22 17.02 20.32 24.89 28.70

0.030 0.030 0.030 0.045 0.045 0.045 0.045 0.055 0.055 0.055 0.065 0.065 0.065 0.080 0.080

0.76 0.76 0.76 1.14 1.14 1.14 1.14 1.40 1.40 1.40 1.65 1.65 1.65 2.03 2.03

0.14 0.16 0.18 0.24 0.28 0.33 0.39 0.48 0.53 0.64 0.70 0.81 0.94 1.15 1.31

3.56 4.06 4.57 6.10 7.11 8.38 9.91 12.19 13.46 16.26 17.78 20.57 23.88 29.21 33.27

0.015 0.015 0.015 0.015 0.030 0.030 0.030 0.045 0.045 0.045 0.065 0.065 0.065 0.065 0.065

0.38 0.38 0.38 0.38 0.76 0.76 0.76 1.14 1.14 1.14 1.65 1.65 1.65 1.65 1.65

0.17 0.19 0.21 0.28 0.35 0.39 0.46 0.58 0.63 0.74 0.85 0.96 1.09 1.31 1.46

4.32 4.83 5.33 7.11 8.89 9.91 11.68 14.73 16.00 18.80 21.59 24.38 27.69 33.27 37.08

Dimensions and weights are nominal; subject to industry tolerances.

Phone: 888-593-3355 www.generalcable.com


SPEC 5100

January, 2008

Unicon FREP ®

®

FR-EPR, Low-Voltage Power, Unshielded 600V, UL Type RHH/RHW-2/USE-2

Product Construction Conductor:

Applications:

• 14 AWG thru 1000 kcmil stranded annealed bare copper compressed Class B stranding per ASTM B8

Insulation:

• Flame-retardant Ethylene Propylene Rubber (EPR) • GENERAL CABLE® (MI) UNICON® FREP® TYPE USE-2 OR RHH OR RHW-2 VW-1 SIZE (AWG OR KCMIL) 600 VOLTS SUN RES FOR CT USE (UL) DAY/MONTH/YEAR OF MFG SEQUENTIAL FOOTAGE MARK * Sizes smaller than 1/0 AWG do not include “FOR CT USE”

Options:

• 2kV version • Tinned copper conductor • Class C stranding • Unicon® XLPE-Flame-retardant Cross-Linked Polyethylene (XLPE) insulation • Other constructions available upon request

CATALOG NUMBER

COND. STRAND

Compliances:

Industry Compliances: • National Electrical Code (NEC) • UL 44 Type RHH/RHW-2 • UL 854 Type USE-2 • ICEA S-95-658/NEMA WC70) • “FOR CT USE” on 1/0 AWG and larger in accordance with NEC • UL Listed VW-1 Flame Tests Compliances: • UL 1581 VW-1 • For 1/0 AWG and larger: IEEE 383, IEEE 1202/ CSA FT4, ICEA T-29-520 Other Compliances: • EPA 40 CFR, Part 261 for leachable lead content per TCLP • OSHA acceptable

Features:

Print:

COND. SIZE (AWG/ kcmil)

• Ideally suited for use in broad range of commercial, industrial and utility applications where reliability is the major concern, where maximum performance will be demanded and where space is limited • In free air, raceways or direct burial in accordance with NEC • Rated at 90˚C wet or dry • Smaller cable diameter • Excellent electrical, thermal and physical properties • Excellent resistance to moisture • Excellent resistance to crush, compression cuts and heat deformation • Excellent flame-resistance • Excellent low temperature cold bend characteristics • Meets cold bend test at -25˚C

NOMINAL COND. DIAMETER inches mm

MINIMUM AVG. INSULATION THICKNESS INches mm

Packaging:

• Material cut to length and shipped on nonreturnable wood reels

NOMINAL CABLE O.D. INCHES mm

COPPER WEIGHT

NET WEIGHT

LBS/ 1000 FT

kg/km

LBS/ 1000 FT

kg/km

13 20 32 50 81 129 205 326 411 653 772 1081 1542 2316 3086

19 30 48 75 121 192 305 485 612 972 1149 1609 2295 3447 4593

24 33 48 78 114 169 254 402 500 759 905 1235 1728 2573 3402

36 49 71 116 170 252 378 598 744 1130 1347 1838 2572 3829 5063

14 AWG - 1000 kcmil CONDUCTORS 14101.211400* 14101.211200* 14101.211000* 14101.210800* 14101.210600* 14101.210400* 14101.210200* 14101.215100* 14101.215200* 14101.215400* 14101.216000* 14101.216200* 14101.216500* 14101.217000* 14101.217500*

14 12 10 8 6 4 2 1/0 2/0 4/0 250 350 500 750 1000

7/.0242 7/.0305 7/.0385 7/.0486 7/.0612 7/.0772 7/.0974 19/.0740 19/.0837 19/.1055 37/.0822 37/.0973 37/.1162 61/.1109 61/.1280

0.07 0.09 0.12 0.15 0.18 0.23 0.29 0.37 0.41 0.52 0.56 0.67 0.80 0.98 1.13

1.78 2.29 3.05 3.81 4.57 5.84 7.37 9.40 10.41 13.21 14.22 17.02 20.32 24.89 28.70

0.045 0.045 0.045 0.060 0.060 0.060 0.060 0.080 0.080 0.080 0.095 0.095 0.095 0.110 0.110

1.14 1.14 1.14 1.52 1.52 1.52 1.52 2.03 2.03 2.03 2.41 2.41 2.41 2.79 2.79

0.17 0.19 0.21 0.27 0.31 0.36 0.42 0.53 0.58 0.69 0.77 0.87 1.00 1.22 1.37

4.32 4.83 5.33 6.86 7.87 9.14 10.67 13.46 14.73 17.53 19.56 22.10 25.40 30.99 34.80

Dimensions and weights are nominal; subject to industry tolerances. *Non-stock item, minimum runs apply. Please consult Customer Service for price and delivery.

Phone: 888-593-3355 www.generalcable.com


SPEC 5150

January, 2008

XHHW-2 VW-1

XLPE, Control and Low-Voltage Power, Unshielded 600V, UL Type SIS1/XHHW-2, VW-1 Rated

Product Construction Conductor:

Applications:

• For use in power and control circuits in switchboards, control panels and raceways in applications not exceeding 600 volts • Acceptable for use in OSHA regulated installations

• 18 AWG thru 500 kcmil tinned, annealed copper per ASTM B33 • Class B stranding per ASTM B8

Compliances:

Industry Compliances: • UL Type SIS/XHHW-2¥—600V • UL type XHHW-2¥¥—600V • ICEA S-95-658/NEMA WC70 • 1/0 and larger are listed “Sun Res FOR CT USE” in accordance with NEC Flame Tests Compliances: • UL 44 VW-1 Other Compliances: • Meets EPA 40 CFR, Part 261 for leachable lead content per TCLP method • OSHA acceptable

Features:

Insulation:

• Flame-retardant Cross-Linked Polyethylene (XLPE) • Color code: Gray

Print:

For 18 AWG and 16 AWG: • General Cable® (WC) 1C XXAWG COPPER XLPE SIS TYPE 600V 90C YEAR OF MFG For 14 AWG thru 4 AWG: • General Cable® (WC) 1C XXAWG COPPER XLPE TYPE SIS/XHHW-2 VW-1 (UL) 600V 90C YEAR OF MFG For 2 AWG and larger: • General Cable® (WC) 1C XXAWG COPPER XLPE TYPE XHHW-2 VW-1 SUN RES FOR CT USE (UL) YEAR OF MFG SEQUENTIAL FOOTAGE MARK

• Rated at 90˚C wet or dry • UL Listed as SIS/XHHW-2¥ and XHHW-2¥¥ for general power or control wiring in accordance with the National Electrical Code • Sizes 1/0 and larger for CT USE • Excellent flame resistance • Sunlight-resistant • Excellent physical, thermal and electrical properties

Packaging:

• Material to be shipped on spools or nonreturnable wood reels ¥ UL Type

SIS/XHHW-2 for sizes 14 AWG thru 4/0 AWG

¥¥ UL Type

XHHW-2 for sizes 250 kcmil thru 500 kcmil

* Sizes smaller than 1/0 AWG do not include “FOR CT USE”

CATALOG NUMBER

COND. SIZE (AWG/ kcmil)

COND. STRAND

NOMINAL COND. DIAMETER inCHES mm

MINIMUM AVG. INSULATION THICKNESS INCHES mm

NOMINAL CABLE O.D. INCHES mm

COPPER WEIGHT

NET WEIGHT

LBS/ 1000 FT

kg/km

LBS/ 1000 FT

kg/km

5 8 13 20 32 51 81 129 205 326 411 518 653 772 1081 1544

8 12 19 30 48 76 121 192 305 485 612 771 972 1149 1609 2298

9 13 19 27 41 69 103 156 239 373 464 579 722 860 1185 1669

14 20 28 41 61 102 153 232 355 556 691 862 1075 1280 1764 2484

18 AWG - 500 kcmil CONDUCTORS 381500* 381510* 381520* 381530* 381540* 381550* 381560* 381570* 06591.210200* 06591.215100* 06591.215200* 06591.215300* 06591.215400* 06591.216000* 06591.216200* 06591.216500*

18 16 14 12 10 8 6 4 2 1/0 2/0 3/0 4/0 250 350 500

7/.0152 7/.0192 7/.0242 7/.0305 7/.0385 7/.0486 7/.0612 7/.0772 7/.0974 19/.0745 19/.0837 19/.0940 19/.1055 37/.0822 37/.0973 37/.1162

0.05 0.06 0.07 0.09 0.11 0.14 0.18 0.23 0.29 0.36 0.41 0.46 0.51 0.56 0.66 0.79

1.27 1.47 1.80 2.29 2.87 3.56 4.57 5.84 7.37 9.14 10.41 11.68 12.95 14.22 16.76 20.07

0.030 0.030 0.030 0.030 0.030 0.045 0.045 0.045 0.045 0.055 0.055 0.055 0.055 0.065 0.065 0.065

0.76 0.76 0.76 0.76 0.76 1.14 1.14 1.14 1.14 1.40 1.40 1.40 1.40 1.65 1.65 1.65

0.11 0.12 0.13 0.15 0.18 0.24 0.28 0.32 0.38 0.48 0.52 0.57 0.63 0.70 0.80 0.93

2.74 3.05 3.38 3.86 4.45 6.05 6.99 8.18 9.68 12.14 13.28 14.55 15.98 17.75 20.37 23.65

Dimensions and weights are nominal; subject to industry tolerances. *Non-stock item, minimum runs apply. Please consult Customer Service for price and delivery. 1SIS on sizes 4 AWG and smaller

Phone: 888-593-3355 www.generalcable.com


SPEC 5200

January, 2008

XHHW-2

XLPE, Low-Voltage Power, Unshielded 600V, UL Type XHHW-2, c(UL) RW-90

Product Construction Conductor:

Applications:

• 8 AWG thru 750 kcmil annealed bare copper per ASTM B3 • Class B stranding per ASTM B8

Insulation:

• Flame-retardant Cross-Linked Polyethylene (XLPE) – Black

• General purpose building wire for use in air, cable tray or approved raceways • Industrial environments where superior insulation toughness and chemical resistance is required • Maximum operating temperature not to exceed 90˚C in dry or wet locations

Features:

• Rated at 90˚C wet or dry • Smaller cable O.D. • Excellent electrical, thermal and physical properties • Excellent resistance to moisture • Excellent resistance to crush, compression cuts and heat deformation

Print:

• GENERAL CABLE® (MI) AWG/KCMIL TYPE XHHW-2 (UL) TYPE RW90 C(UL) 600V MONTH/YEAR OF MFG SEQUENTIAL FOOTAGE MARK

Options:

Compliances:

• National Electric Code (NEC) • UL 44 Stranded for rubber-insulated wires and cables and UL 854 • ICEA S-95-658/NEMA WC70 • UL listed as Type XHHW-2 • c(UL) Type RW-90 • OSHA acceptable

Packaging:

• Material cut to length and shipped on non-returnable wood reels

• Tinned copper conductor • Full colored insulation

CATALOG NUMBER

COND. SIZE (AWG/ kcmil)

COND. STRAND

798751 496517 358172 760698 288411 629439 321736 309824 935802 840671* 592915 369093 878916

8 6 4 2 1/0 2/0 4/0 250 350 400 500 600 750

7/.0486 7/.0612 7/.0772 7/.0974 19/.0740 19/.0837 19/.1055 37/.0822 37/.0973 37/.1040 37/.1162 61/.1109 61/.1280

NOMINAL COND. DIAMETER inCHES mm

MINIMUM AVG. INSULATION THICKNESS INCHES mm

NOMINAL CABLE O.D. INCHES mm

COPPER WEIGHT LBS/ 1000 FT 51 81 129 205 326 411 653 722 1081 1235 1544 1853 2316

NET WEIGHT

kg/km

LBS/ 1000 FT

kg/km

76 121 192 305 485 612 972 1074 1609 1838 2298 2758 3447

65 99 152 233 364 453 706 837 1157 1322 1634 1972 2448

97 147 226 347 572 674 1051 1246 1722 1967 2432 2935 3643

8 AWG - 750 kcmil CONDUCTORS 0.14 0.18 0.23 0.29 0.36 0.41 0.51 0.56 0.66 0.73 0.79 0.87 0.98

3.56 4.57 5.84 7.37 9.14 10.41 12.95 14.22 16.76 18.54 20.07 22.10 24.89

0.045 0.045 0.045 0.045 0.055 0.055 0.055 0.065 0.065 0.065 0.065 0.080 0.080

1.14 1.14 1.14 1.14 1.40 1.40 1.40 1.65 1.65 1.65 1.65 2.03 2.03

0.24 0.28 0.33 0.39 0.48 0.53 0.63 0.70 0.80 0.87 0.93 1.04 1.15

6.10 7.11 8.38 9.91 12.19 13.46 16.00 17.78 20.32 22.10 23.62 26.42 29.21

Dimensions and weights are nominal; subject to industry tolerances. *Non-stock item, minimum runs apply. Please consult Customer Service for price and delivery.

Phone: 888-593-3355 www.generalcable.com


SPEC 5250

January, 2009

Unicon XLPE ®

XLPE, Low-Voltage Power, Unshielded 600V, UL Type RHH/RHW-2/USE-2 Features (cont’d.):

• Excellent resistance to moisture • Excellent resistance to crush, compression cuts and heat deformation • Excellent flame resistance • Excellent low temperture cold bend characteristics • Meets cold bend test at -25˚C

Compliances: Product Construction Conductor:

Industry Compliances: • National Electrical Code (NEC) • ICEA S-95-658 / NEMA WC70 • “FOR CT USE” on 1/0 AWG and larger in accordance with NEC • UL 44 Type RHH/RHW-2 • UL 854 Type USE-2 Flame Tests Compliances: • UL 1581 VW-1 • For 1/0 AWG and larger: IEEE 383, IEEE 1202/CSA FT-4, ICEA T-29-520 Optional Flame Tests: (See General Cable Sales Representative) Other Compliances: • EPA 40 CFR, Part 261 for leachable lead content per TCLP • OSHA acceptable

Options:

• 14 AWG thru 1000 kcmil stranded annealed bare copper compressed class B stranding per ASTM B8

Insulation:

• Flame-retardant Cross-Linked Polyethylene (XLPE) – Black

• 2 kV version • Tinned copper conductor • Class C stranding • Various colors available • Unicon® FREP®—Flame-retardant Ethylene Propylene Rubber (EPR) insulation • Other constructions available upon request

Applications:

Print:

For 14 AWG – 4 AWG: • GENERAL CABLE® (PLANT OF MFG) UNICON®-XLP TYPE USE-2 OR RHH OR RHW-2 VW-1 SIZE (AWG OR KCMIL) 600 VOLTS SUN RES (UL) DAY/MONTH/YEAR OF MFG SEQUENTIAL FOOTAGE MARK For 2 AWG and larger: • GENERAL CABLE® (PLANT OF MFG) UNICON®-XLP TYPE USE-2 OR RHH OR RHW-2 VW-1 (SIZE) 600 VOLTS SUN RES FOR CT USE (UL) DAY/MONTH/YEAR OF MFG SEQUENTIAL FOOTAGE MARK

• Ideally suited for use in a broad range of commercial, industrial and utility applications where reliability is a major concern, where maximum performance will be demanded and where space is limited • In free air, raceways or direct burial in accordance with NEC

Features:

Packaging:

• Material cut to length and shipped on non-returnable wood reels

• Rated at 90˚C wet or dry • Smaller cable O.D. • Excellent electrical, thermal and physical properties

* Sizes smaller than 1/0 AWG do not include “FOR CT USE”

CATALOG NUMBER

COND. SIZE (AWG/ kcmil)

COND. STRAND

NOMINAL COND. DIAMETER inCHES mm

MINIMUM AVG. INSULATION THICKNESS INCHES mm

NOMINAL CABLE O.D. INCHES mm

COPPER WEIGHT

NET WEIGHT

LBS/ 1000 FT

kg/km

LBS/ 1000 FT

kg/km

13 20 32 50 81 129 205 326 411 653 772 1081 1542 2316 3086

19 30 48 75 121 192 305 485 612 972 1149 1609 2295 3447 4593

24 33 48 78 114 169 254 403 501 760 906 1237 1730 2576 3405

36 49 71 116 170 252 378 600 746 1131 1349 1841 2575 3834 5068

14 AWG - 1000 kcmil CONDUCTORS 364830* 364840* 364850* 16602.210800* 16602.210600* 16602.210400* 16602.210200 16602.215100 16602.215200 16602.215400 16602.216000 16602.216200 16602.216500 16602.217000 16602.217500*

14 12 10 8 6 4 2 1/0 2/0 4/0 250 350 500 750 1000

7/.0242 7/.0305 7/.0385 7/.0486 7/.0612 7/.0772 7/.0974 19/.0740 19/.0837 19/.1055 37/.0822 37/.0973 37/.1162 61/.1109 61/.1280

0.07 0.09 0.12 0.15 0.18 0.23 0.29 0.37 0.41 0.52 0.56 0.67 0.80 0.98 1.13

1.78 2.29 3.05 3.81 4.57 5.84 7.37 9.40 10.41 13.21 14.22 17.02 20.32 24.89 28.70

0.045 0.045 0.045 0.060 0.060 0.060 0.060 0.080 0.080 0.080 0.095 0.095 0.095 0.110 0.110

1.14 1.14 1.14 1.52 1.52 1.52 1.52 2.03 2.03 2.03 2.41 2.41 2.41 2.79 2.79

0.17 0.19 0.21 0.27 0.31 0.36 0.42 0.53 0.58 0.69 0.77 0.87 1.00 1.22 1.37

4.32 4.83 5.33 6.86 7.87 9.14 10.67 13.46 14.73 17.53 19.56 22.10 25.40 30.99 34.80

Dimensions and weights are nominal; subject to industry tolerances. *Non-stock item, minimum runs apply. Please consult Customer Service for price and delivery.

Phone: 888-593-3355 www.generalcable.com


SPEC 5300

October, 2008

Super Vu-Tron

®

EPR/CPE, Diesel Locomotive Cable 2000V, Type DLO; 600V, UL Type RHH/RHW; 1000V, CSA Type R90 Applications:

• Diesel electric locomotives • Telecom power supply • Oil and gas drilling rigs • Mining and earth-moving equipment • Shipyards • Motor leads • Where flexible power leads must be installed in conduit or raceways

Product Construction: Conductor:

Features:

Jacket Marking:

• 10 AWG through 777.7 kcmil stranded tinned annealed copper per AAR 589

Insulation:

• Premium-grade 90˚C EP

Jacket:

• Chlorinated Polyethylene (CPE), Black

CATALOG NUMBER

AWG OR MCM

COND. STRAND

81910 81908 81906 81904 81902 81901 81911 81920 81930 81940 81926 81931 81937 81944 81953 81964 81977

10 8 6 4 2 1 1/0 2/0 3/0 4/0 262.6 313.3 373.7 444.4 535.3 646.4 777.7

27/24 37/24 61/24 105/24 154/24 224/24 280/24 329/24 456/24 551/24 650/24 777/24 925/24 1110/24 1332/24 1609/24 1924/24

• SIZES 10 THROUGH 1 AWG - CAROL SUPER VU-TRON® (SIZE) (STRANDING) 90C DLO 2000 VOLTS P-7K-123040 MSHA CSA R90 1000V (UL) RHH or RHW 600 VOLTS • SIZES 1/0 THROUGH 646.4 - CAROL SUPER VU-TRON® (SIZE) 90C DLO 2000 VOLTS P7K-123040 MSHA CSA R90 1000V (-40C) FT-1 – (UL) RHH or RHW 600 VOLTS SUNLIGHT RESISTANT FOR CT USE NOTE: (535.3 AND 646.4 MCM printed (UL) RHH OR RHW 2000 VOLTS) • SIZE 777.7 MCM ONLY - CAROL SUPER VU-TRON® C(UL) TYPE RHW-2 2KV VW-1 FOR CT USE TYPE DLO 2000V 90C P-102 MSHA

NOMINAL INSULATION THICKNESS INCHES mm

NOMINAL O.D. INCHES mm

• 90˚C temperature rating • Excellent impact and abrasion resistance • Resists oils, acids, alkalies, heat, flame • Flexible tinned copper stranding • FT4 upon request

Industry Approvals:

• UL Listed • Accepted for listing as flame-resistant by MSHA • CSA R90 • RoHS Compliant

Packaging:

• Lengths cut to order

CURRENT AMPS (1) (2)

APPROX. NET WEIGHT LBS/MFT(S)

10 AWG - 777.7 kcmil DLO - 2000 VOLTS 0.045 0.060 0.060 0.060 0.060 0.080 0.080 0.080 0.080 0.080 0.095 0.095 0.095 0.095 0.120 0.120 0.120

1.14 1.52 1.52 1.52 1.52 2.03 2.03 2.03 2.03 2.03 2.41 2.41 2.41 2.41 3.05 3.05 3.05

0.26 0.34 0.40 0.46 0.52 0.65 0.69 0.73 0.81 0.87 1.00 1.06 1.10 1.23 1.34 1.45 1.50

6.60 8.64 10.16 11.68 13.21 16.51 17.53 18.54 20.57 22.10 25.40 26.92 27.94 31.24 34.04 36.83 38.10

40 55 75 95 130 150 170 195 225 260 296 326 362 400 445 493 546

55 80 105 140 190 220 260 300 350 405 467 522 591 652 728 815 904

60 95 145 205 295 440 515 580 770 930 1130 1295 1545 1820 2195 2560 3050

Dimensions and weights are nominal; subject to industry tolerances. *Non-stock item, minimum runs apply. Please consult Customer Service for price and delivery. (1) Ampacities based on 90°C Conductor and 30°C Ambient temperature based on the National Electrical Code for not more than three current-carrying conductors inches raceway, cable or earth. (2) Ampacities based on single-conductor inches free air. 90°C conductor temperature and an ambient air temperature of 30°C inches accordance with National Electrical Code ® (NEC). (S) Actual shipping weight may vary. ®

Phone: 888-593-3355 www.generalcable.com


SPEC 5350

August, 2008

GenFree™ LSZH

XLPO, Low-Smoke, Zero-Halogen (LSZH), Low-Voltage Power, Unshielded 600V, Type RHH/RHW-LS/USE, CSA AWM I A/B, Class B

Product Construction Conductor:

Applications (cont’d.):

• USE rating for Direct Burial Applications • CT-rated for installation in Cable Tray – 1/0 AWG and larger • For use in all closed environments or populated spaces such as auditoriums, arenas and health facilities where more stringent specifications for smoke and toxicity emission levels are desired • Ideally suited for use in a broad range of commercial and Industrial applications where reliability is the major concern, where maximum performance is demanded and where space is limited

• 14 AWG thru 750 kcmil tinned coated compressed copper per ASTM B3 and B33. Class B stranding per ASTM B8.

Composite Insulation/Jacket:

• Flame-retardant, oil-resistant, limited smoke, Cross-Linked Polyolefin (XLPO), Black

Print:

• General Cable® (PLANT OF MFG) (UL) Type USE or RHH or RHW-LS VW-1 (Size) 600V Oil Res. I Sun Res. FOR CT USE*/CSA AWM I A/B 105˚C 600V FT4 month/year of MFG Sequential Footage Mark

• UL Type RHH/RHW/USE Rated at 90˚C dry, 75˚C wet • CSA AWM I A/B Rated at 105˚C • UL AWM styles 3237 and 3578 • Smooth surface for reduced coefficient of friction for ease of installation • Excellent moisture resistance • Excellent resistance to salt water • Available in colors for ease of phase identification • Minimum acid gas emissions under combustion • Meets cold bend test at -40˚C • Meets UL Oil Res. I and II

Options:

• Available in Blue, Green, Red and Gray

Applications:

• General purpose 600V Power Cable Applications • For use in conduit, open tray, underground duct and aerial installations when properly supported and installed • RHH/RHW ratings for installation in conduit or raceway

CATALOG NUMBER

COND. STRAND (CLASS B)

• UL 44 Standard for Rubber Insulated Wire • UL 758 Standard for Appliance Wiring Material • UL 854 Standard for Service Entrance Cable • UL 1685 Standard for Vertical Tray Fire Propagation and Smoke Release Test for Electrical and Optical Fiber Cables • Telcordia GR347 Core • UL Listed VW-1 • ICEA S-95-658/NEMA WC 70 • IEEE 1202 (70,000 BTU/hr) • IEEE 383 (70,000 BTU/hr) • Sizes 1/0 AWG and larger are listed “FOR CT USE” • CSA FT4 • CSA Standard C22.2 No. 0.3 • CSA Standard C22.2 No. 210.2 • Meets EPA 40 CFR, Part 261 for leachable lead content per TCLP method • OSHA acceptable

Features:

* Sizes smaller than 1/0 AWG do not include “FOR CT USE”

COND. SIZE (AWG/ kcmil)

Compliances:

NOMINAL COND. DIAMETER inCHES mm

MINIMUM AVG. INSULATION THICKNESS INCHES mm

Packaging:

• Material cut to length and shipped on nonreturnable wood reels

NOMINAL CABLE O.D. INCHES mm

COPPER WEIGHT LBS/ 1000 FT

NET WEIGHT

kg/km

LBS/ 1000 FT

kg/km

14 AWG - 750 kcmil CONDUCTORS, CLASS B 14311.011400 14311.011200 14311.011000 14311.010800 14311.010600 14311.010400 14311.010200 14311.010100 14311.015100 14311.015200 14311.015300 14311.015400 14311.016000 14311.016200 14311.016500 14311.017000

14 12 10 8

7/.0242 7/.0305 7/.0385 7/.0486

0.07 0.09 0.12 0.15

1.78 2.29 3.05 3.81

0.045 0.045 0.045 0.060

1.14 1.14 1.14 1.52

0.17 0.19 0.22 0.28

4.32 4.83 5.59 7.11

13 20 32 50

19 30 48 75

18 25 38 58

27 37 57 86

6 4 2 1 1/0 2/0 3/0 4/0 250 350 500 750

7/.0612 7/.0772 7/.0974 19/.0644 19/.0745 19/.0837 19/.0940 19/.1055 37/.0822 37/.0973 37/.1162 61/.1109

0.18 0.23 0.28 0.32 0.36 0.41 0.46 0.51 0.56 0.66 0.79 0.97

4.57 5.84 7.11 8.13 9.14 10.41 11.68 12.95 14.22 16.76 20.07 24.64

0.060 0.060 0.060 0.080 0.080 0.080 0.080 0.080 0.095 0.095 0.095 0.110

1.52 1.52 1.52 2.03 2.03 2.03 2.03 2.03 2.41 2.41 2.41 2.79

0.31 0.36 0.42 0.49 0.53 0.58 0.63 0.68 0.76 0.87 1.00 1.21

7.87 9.14 10.67 12.45 13.46 14.73 16.00 17.27 19.30 22.10 25.40 30.73

81 129 205 258 326 411 518 653 772 1081 1544 2316

121 192 305 385 485 612 771 972 1149 1609 2298 3447

116 171 257 331 406 495 612 757 905 1237 1728 2572

173 254 382 493 604 737 911 1126 1347 1841 2571 3827

Dimensions and weights are nominal; subject to industry tolerances.

Phone: 888-593-3355 www.generalcable.com


SPEC 5400

August, 2008

GenFree™ LSZH

XLPO, Low-Smoke, Zero-Halogen (LSZH), Low-Voltage Power, Unshielded 600V, Type RHH/RHW-LS/USE, CSA AWM I A/B, Class I* Features (cont’d.):

• Available in colors for ease of phase identification • Minimum acid gas emissions under combustion • Meets cold bend test at -40˚C • Meets UL Oil Res. I and II

Compliances: Product Construction Conductor:

Applications (cont’d.):

• RHH/RHW ratings for installation in conduit or raceway • USE rating for Direct Burial Applications • CT rated for installation in Cable Tray – 1/0 AWG and larger • For use in all closed environments or populated spaces such as auditoriums, arenas and health facilities where more stringent specifications for smoke and toxicity emission levels are desired • Ideally suited for use in a broad range of commercial and Industrial applications where reliability is the major concern, where maximum performance is demanded and where space is limited

• 14 AWG thru 750 kcmil tinned coated copper per ASTM B3 and B33. Class I stranding per ASTM B8

Composite Insulation/Jacket:

• Flame-retardant, oil-resistant, limited smoke, Cross-Linked Polyolefin (XLPO), Black

Print:

• General Cable® (PLANT OF MFG) (UL) Type USE or RHH or RHW-LS VW-1 (Size) 600V Oil Res. I Sun Res. FOR CT USE*/CSA AWM I A/B 105˚C 600V FT4 month/year of MFG Sequential Footage Mark * Sizes smaller than 1/0 AWG do not include “FOR CT USE”

Features:

• UL Type RHH/RHW/USE Rated at 90˚C dry, 75˚C wet • CSA AWM I A/B Rated at 105˚C • UL AWM styles 3237 and 3578 • Smooth surface for reduced coefficient of friction for ease of installation • Excellent moisture resistance • Excellent resistance to salt water

Options:

• Available in Blue, Green, Red and Gray

Applications:

• General purpose 600V Power Cable Applications • For use in conduit, open tray, underground duct and aerial installations when properly supported and installed

CATALOG NUMBER

• UL 44 Standard for Rubber Insulated Wire • UL 758 Standard for Appliance Wiring Material • UL 854 Standard for Service Entrance Cable • UL 1685 Standard for Vertical Tray Fire Propagation and Smoke Release Test for Electrical and Optical Fiber Cables • Telcordia GR347 Core • UL Listed VW-1 • ICEA S-95-658/NEMA WC 70 • IEEE 1202 (70,000 BTU/hr) • IEEE 383 (70,000 BTU/hr) • Sizes 1/0 AWG and larger are listed “FOR CT USE” • CSA FT4 • CSA Standard C22.2 No. 0.3 • CSA Standard C22.2 No. 210.2 • Meets EPA 40 CFR, Part 261 for leachable lead content per TCLP method • OSHA acceptable

Packaging:

• Material cut to length and shipped on nonreturnable wood reels

COND. SIZE (AWG/ kcmil)

COND. STRAND (CLASS I)*

14 12 10 8 6

41 65 65 41 63/24

0.07 0.09 0.12 0.16 0.21

1.88 2.39 3.15 4.06 5.33

0.045 0.045 0.045 0.060 0.060

1.14 1.14 1.14 1.52 1.52

0.18 0.20 0.23 0.29 0.34

4.57 5.08 5.84 7.37 8.64

4 2 1 1/0 2/0 3/0 4/0 250 350 500 750

105/24 161/24 210/24 259/24 329/24 413/24 532/24 608/24 851/24 1221/24 1850/24

0.26 0.32 0.38 0.42 0.47 0.53 0.61 0.65 0.78 0.95 1.11

6.60 8.13 9.65 10.67 11.94 13.46 15.49 16.51 19.81 24.13 28.19

0.060 0.060 0.080 0.080 0.080 0.080 0.080 0.095 0.095 0.095 0.110

1.52 1.52 2.03 2.03 2.03 2.03 2.03 2.41 2.41 2.41 2.79

0.38 0.45 0.55 0.59 0.64 0.71 0.78 0.85 1.00 1.16 1.36

9.65 11.43 13.97 14.99 16.26 18.03 19.81 21.59 25.40 29.46 34.54

NOMINAL COND. DIAMETER inCHES mm

MINIMUM AVG. INSULATION THICKNESS INCHES mm

NOMINAL CABLE O.D. INCHES mm

COPPER WEIGHT LBS/ 1000 FT

NET WEIGHT

kg/km

LBS/ 1000 FT

kg/km

14 21 33 51 80

20 31 48 76 119

20 27 39 59 120

29 40 58 87 179

134 205 261 329 417 524 682 779 1095 1517 2408

199 305 389 489 621 780 1014 1159 1630 2258 3584

184 266 356 433 529 654 831 946 1301 1821 2723

274 396 530 644 787 973 1237 1408 1936 2710 4052

14 AWG - 750 kcmil CONDUCTORS, CLASS I 14315.011400 14315.011200 14315.011000 14315.010800 14315.010600 14315.010400 14315.010200 14315.010100 14315.015100 14315.015200 14315.015300 14315.015400 14315.016000 14315.016200 14315.016500 14315.017000

Dimensions and weights are nominal; subject to industry tolerances. *Class I: sizes 8 AWG and larger.

Phone: 888-593-3355 www.generalcable.com


SPEC 5500

January, 2009

RW90

XLPE, Building Wire 600V, CSA Type RW90 (-40°C), Single Conductor, Copper

Product Construction: Conductor:

Option:

• 14 AWG thru 1000 kcmil compressed stranded plain copper

Insulation:

• Heat- and moisture-resistant, low-temperature Cross-Linked Polyethylene (XLPE), Type RW90, -40°C • Color code: 8 AWG thru 2 AWG – black, white, red, blue, green; 1 AWG and larger– black (other colors available subject to minimum order quantity)

Print:

• GENERAL CABLE BICC® BRAND SQ-CSA RW90 XLPE SIZE (AWG OR KCMIL) CU 600V (-40°C) YEAR OF MFG SEQUENTIAL METER MARKING NOTE: For black insulation, add ­– SUN RES

COND. SIZE (AWG/ kcmil)

COND. STRAND

Compliances:

• For 1000 volt applications, use RWU90

NOMINAL COND. O.D.** inCHES

mm

• CSA standard C 22.2 No. 38 • CSA Approval number: LL7319C

Applications:

Packaging:

• In accordance with Canadian Electrical Code (CEC), Part 1 – 19th Edition • For wiring exposed to the weather (black color only) • For use in raceways (except cable trays) in dry, damp or wet locations in accordance with Canadian Electrical Code (CEC) • Refer to CEC, Table 19 for conditions of use

• 8 AWG thru 350 kcmil: 300m or 1500m reels • 500 kcmil: 300m or 1200m reels • 600 kcmil and 750m kcmil: 600m reels Note: Not for sale in the U.S.

Features:

• Rated at 90°C wet or dry • Meets cold bend and cold impact tests at -40°C

MIN. AVG. INS. THICKNESS inCHES

mm

NOMINAL DIAMETER (OVER) INSULATION INCHES

mm

COPPER WEIGHT LBS/1000 FT

NET WEIGHT kg/km

LBS/1000 FT

kg/km

AMPACITY** 30˚C AMBIENT

19 19 30 30 48 48 76 121 192 242 305 385 485 611 771 972 1149 1378 1609 1838 2297 2802 3446 4595

18 18 26 26 39 39 62 94 146 180 225 283 353 441 552 690 822 981 1144 1235 1602 1943 2406 3201

27 27 39 39 58 58 92 140 217 268 335 421 526 656 821 1027 1224 1460 1702 1838 2384 2892 3580 4763

15 15 20 20 30 30 45 65 85 105 120 140 155 185**** 210 235 265 295 325 345 395 455 500 585

14 AWG - 1000 kcmil CONDUCTORS 14 14 12 12 10 10 8 6 4 3 2 1 1/0 2/0 3/0 4/0 250 300 350 400* 500 600 750 1000*

1 7/.0242 1 7/.0305 1 7/.0385 7/.0486 7/.0612 7/.0772 7/.0867 7/.0974 19/.0664 19/.0745 19/.0837 19/.0940 19/.1055 37.0822 37.0900 37/.0973 37/.1040 37/.1162 61/.0992 61/.1109 61/.1280

0.07 0.07 0.08 0.09 0.10 0.12 0.14 0.18 0.23 0.25 0.28 0.32 0.36 0.41 0.46 0.51 0.56 0.61 0.66 0.71 0.79 0.87 0.97 1.12

1.78 1.78 2.03 2.29 2.54 3.05 3.56 4.57 5.84 6.35 7.11 8.13 9.14 10.41 11.68 12.95 14.22 15.49 16.76 18.03 20.06 22.10 24.64 28.45

0.030 0.030 0.030 0.030 0.030 0.030 0.045 0.045 0.045 0.045 0.045 0.055 0.055 0.055 0.055 0.055 0.065 0.065 0.065 0.065 0.065 0.080 0.080 0.080

0.76 0.76 0.76 0.76 0.76 0.76 1.14 1.14 1.14 1.14 1.14 1.40 1.40 1.40 1.40 1.40 1.65 1.65 1.65 1.65 1.65 2.03 2.03 2.03

0.13 0.13 0.14 0.15 0.16 0.17 0.24 0.27 0.32 0.34 0.38 0.43 0.47 0.51 0.56 0.62 0.69 0.75 0.80 0.84 0.93 1.03 1.14 1.29

3.20 3.37 3.63 3.86 4.16 4.32 5.60 6.90 8.10 8.70 9.60 10.90 11.80 13.00 14.20 15.60 17.60 18.90 20.20 21.40 23.50 26.20 28.80 32.60

12 13 20 20 31 32 51 81 129 163 205 258 326 411 518 653 772 926 1081 1235 1544 1883 2316 3088

Dimensions and weights are nominal; subject to industry tolerances. *Non-stock item, minimum runs apply. Please consult Customer Service for price and delivery. **For compact-stranded constructions, the number of wires may be reduced as follows: 19-Wire Constructions - 18 Wires Minimum 37-Wire Constructions - 35 Wires Minimum 61-Wire Constructions - 58 Wires Minimum ***Based on CEC Part 1-19th Edition, Table 2 for three conductors in raceway (conduit). For underground installations, refer to CEC, Rule 4-004 for ampacity rating. ****For 3 wires, 120/240V and 120/208V residential services or subservices, the allowable ampacity for 2/0 AWG shall be 200A. In this case, the 5% adjustment of Rule 8-106(1) cannot be applied.

Phone: 800-561-0649 www.generalcable.com


SPEC 5550

January, 2009

RW90

XLPE, Building Wire 600V, CSA Type RW90 (-40°C), Single Conductor, Aluminum

Product Construction: Conductor:

• 8 AWG thru 1000 kcmil compact stranded Aluminum ACM (8000 Series)

Option:

Compliances:

Applications:

Packaging:

• For 1000 Volt applications, use RWU90 XLPE Aluminum ACM

• In accordance with Canadian Electrical Code (CEC), Part 1 – 19th Edition • For wiring exposed to the weather (black color only) • For use in raceways (except cable trays) in dry, damp or wet locations in accordance with Canadian Electrical Code (CEC) • Refer to CEC, Table 19 for conditions of use • For Termination and Splicing of Aluminum Conductors, refer to CEC Rule 12-118

Insulation:

• Heat- and moisture-resistant, low-temperature Cross-Linked Polyethylene (XLPE) — Type RW90, -40°C • Color code: 8 AWG thru 2 AWG – black, white, red, blue, green; 1 AWG and larger– black (other colors available subject to minimum order quantity)

Print:

• GENERAL CABLE BICC® BRAND SQ-CSA RW90 XLPE SIZE (AWG OR KCMIL) AL ACM — 600V (-40°C) YEAR OF MFG SEQUENTIAL METER MARKING NOTE: For black insulation, add ­– SUN RES

COND. SIZE (AWG/ kcmil)

COND. STRAND

NOMINAL COND. O.D.** inCHES

mm

• CSA standard C 22.2 No. 38 • CSA Approval File Number LL7319C • 8 AWG thru 400 kcmil: 300m or 1500m reels • 500 kcmil: 300m or 1200m reels • 600 kcmil and 750m kcmil: 600m reels Note: Not for sale in the U.S.

Features:

• Rated at 90°C wet or dry • Meets cold bend and cold impact tests at -40°C

MIN. AVG. INS. THICKNESS inCHES

mm

NOMINAL DIAMETER (OVER) INSULATION INCHES

mm

ALUMINUM WEIGHT LBS/1000 FT

NET WEIGHT

kg/km

LBS/1000 FT

kg/km

23 37 59 74 93 117 148 186 235 296 350 420 490 559 701 841 1050 1400

27 38 56 68 83 107 131 161 198 245 292 345 397 449 551 670 824 1078

40 57 84 101 123 160 195 239 295 364 435 513 590 667 820 998 1226 1604

AMPACITY*** 30˚C AMBIENT

8 AWG - 1000 kcmil CONDUCTORS 8 6 4 3 2 1 1/0 2/0 3/0 4/0 250 300 350 400* 500 600 750 1000*

7/.0486 7/.0612 7/.0772 7/.0867 7/.0974 19/.0664 19/.0745 19/.0837 19/.0940 19/.1055 37/.0822 37/.0900 37/.0973 37/.1040 37/.1162 61/.0992 61/.1109 61/.1280

0.13 0.17 0.21 0.24 0.27 0.30 0.34 0.38 0.42 0.48 0.52 0.57 0.62 0.66 0.74 0.81 0.91 1.06

3.30 4.32 5.33 6.10 6.86 7.62 8.64 9.65 10.67 12.19 13.21 14.48 15.75 16.76 18.80 20.57 23.11 26.92

.045 .045 .045 .045 .045 .055 .055 .055 .055 .055 .065 .065 .065 .065 .065 .080 .080 .080

1.14 1.14 1.14 1.14 1.14 1.40 1.40 1.40 1.40 1.40 1.65 1.65 1.65 1.65 1.65 2.03 2.03 2.03

0.24 0.27 0.32 0.35 0.38 0.44 0.48 0.52 0.57 0.63 0.69 0.75 0.80 0.84 0.93 1.03 1.14 1.29

6.0 6.9 8.1 8.8 9.6 11.0 12.1 13.2 14.5 16.0 17.6 18.9 20.2 21.4 23.5 26.2 23.8 32.6

16 25 39 50 63 79 99 125 158 199 235 282 329 376 471 565 706 941

30 55**** 65 75 95**** 105 120 145 165 185**** 215 240 260 290 330 370 405 480

Dimensions and weights are nominal; subject to industry tolerances. *Non-stock item, minimum runs apply. Please consult Customer Service for price and delivery. **For compact-stranded constructions, the number of wires may be reduced as follows: 19-Wire Constructions - 18 Wires Minimum 37-Wire Constructions - 35 Wires Minimum 61-Wire Constructions - 58 Wires Minimum ***Based on CEC Part 1-19th Edition, Table 2 for three conductors in raceway (conduit). For underground installations, refer to CEC, Rule 4-004 for ampacity rating. ****For 3 wires, 120/240V and 120/208V residential services or subservices, the allowable ampacity for 2/0 AWG shall be 200A. In this case, the 5% adjustment of Rule 8-106(1) cannot be applied.

Phone: 800-561-0649 www.generalcable.com


SPEC 5600

January, 2009

RWU90

XLPE, Building Wire 1000V, CSA Type RWU90 (-40°C), Single Conductor, Copper

Product Construction: Conductor:

Applications:

• 8 AWG thru 1000 kcmil compressed stranded plain copper

Insulation:

• Heat- and moisture-resistant, low-temperature Cross-Linked Polyethylene (XLPE), Type RWU90, -40°C • Color code: 8 AWG thru 2 AWG – black, white, red, blue, green; 1 AWG and larger– black (other colors available subject to minimum order quantity)

Features:

• In accordance with Canadian Electrical Code (CEC), Part 1 – 19th Edition • For wiring exposed to the weather (black color only) • For use in raceways (except cable trays) in dry, damp or wet locations in accordance with Canadian Electrical Code (CEC) • Approved for direct burial per CEC Rule 12-012 • For service entrance below ground • Refer to CEC, Table 19 for conditions of use

• Rated at 90°C wet or dry • Meets cold bend and cold impact tests at -40°C

Compliances:

• CSA standard C 22.2 No. 38 • CSA certification (file) number: LL7319C

Packaging:

• 8 AWG thru 350 kcmil: 300m or 1500m reels • 500 kcmil: 300m or 1200m reels Note: Not for sale in the U.S.

Print:

• GENERAL CABLE BICC® BRAND SQ-CSA RWU90 XLPE SIZE (AWG OR KCMIL) CU 1000V (-40°C) YEAR OF MFG SEQUENTIAL METER MARKING NOTE: For black insulation, add ­– SUN RES

COND. SIZE (AWG/ kcmil)

COND. STRAND

NOMINAL COND. O.D.** inCHES

mm

MIN. AVG. INS. THICKNESS inCHES

mm

NOMINAL DIAMETER (OVER) INSULATION INCHES

mm

COPPER WEIGHT LBS/1000 FT

NET WEIGHT kg/km

LBS/1000 FT

kg/km

AMPACITY*** 30˚C AMBIENT

76 121 192 242 305 485 611 771 972 1149 1378 1609 2297 2802 3446 4595

73 108 161 197 242 379 469 583 724 866 926 1189 1667 2027 2505 3323

109 160 239 293 361 565 698 867 1077 1289 1547 1769 2481 3016 3728 4945

45 65 85 105 120 155 185**** 210 210 235 265 325 395 455 500 585

8 AWG - 1000 kcmil CONDUCTORS 8 6 4 3 2 1/0 2/0 3/0 4/0 250 300 350 500 600 750 1000*

7/.0486 7/.0612 7/.0772 7/.0867 7/.0974 19/.0745 19/.0837 19/.0940 19/.1055 37/.0822 37/.0900 37/.0973 37/.1162 61/.0992 61/.1109 61/.1280

0.14 0.18 0.23 0.25 0.28 0.36 0.41 0.46 0.51 0.56 0.61 0.66 0.79 0.87 0.97 1.12

3.56 4.57 5.84 6.35 7.11 9.14 10.41 11.68 12.95 14.22 15.49 16.76 20.06 22.10 24.64 28.45

0.080 0.080 0.080 0.080 0.080 0.095 0.095 0.095 0.095 0.110 0.110 0.110 0.110 0.110 0.125 0.125

2.03 2.03 2.03 2.03 2.03 2.41 2.41 2.41 2.41 2.79 2.79 2.79 2.79 2.79 3.18 3.18

0.31 0.34 0.40 0.42 0.45 0.55 0.60 0.64 0.70 0.78 0.84 0.90 1.02 1.12 1.23 1.38

7.80 8.70 9.90 10.60 11.40 13.90 15.00 16.20 17.70 19.90 21.20 22.50 25.80 28.50 31.24 35.05

51 81 129 163 205 326 411 518 653 772 926 1081 1544 1883 2316 3088

Dimensions and weights are nominal; subject to industry tolerances. *Non-stock item, minimum runs apply. Please consult Customer Service for price and delivery. **For compact-stranded constructions, the number of wires may be reduced as follows: 19-Wire Constructions - 18 Wires Minimum 37-Wire Constructions - 35 Wires Minimum 61-Wire Constructions - 58 Wires Minimum ***Based on CEC Part 1-19th Edition, Table 2 for three conductors in raceway (conduit). For underground installations, refer to CEC, Rule 4-004 for ampacity rating. ****For 3 wires, 120/240V and 120/208V residential services or subservices, the allowable ampacity for 2/0 AWG shall be 200A. In this case, the 5% adjustment of Rule 8-106(1) cannot be applied.

Phone: 800-561-0649 www.generalcable.com


SPEC 5650

January, 2009

RWU90

XLPE, Building Wire 1000V, CSA Type RWU90 (-40°C), Single Conductor, Aluminum

Product Construction: Conductor:

Applications:

• 8 AWG thru 1000 kcmil compact stranded Aluminum ACM (8000 Series)

Insulation:

• Heat- and moisture-resistant, low-temperature Cross-Linked Polyethylene (XLPE), Type RWU90, -40°C • Color code: 8 AWG thru 2 AWG – black, white, red, blue, green; 1 AWG and larger– black (other colors available subject to minimum order quantity)

Print:

Features:

• In accordance with Canadian Electrical Code (CEC), Part 1 – 19th Edition • For wiring exposed to the weather (black color only) • For use in raceways (except cable trays) in dry, damp or wet locations in accordance with Canadian Electrical Code (CEC) • Approved for direct burial per CEC rule 12-012 • For sercie entrance below ground • Refer to CEC, Table 19 for conditions of use • For Termination and Splicing of Aluminum Conductors, refer to CEC Rule 12-118

• Rated at 90°C wet or dry • Meets cold bend and cold impact tests at -40°C

Industry Compliances:

• CSA standard C 22.2 No. 38 • CSA Approval File Number LL7319C

Packaging:

• 8 AWG thru 400 kcmil: 300m or 1500m reels • 500 kcmil: 300m or 1200m reels • 600 kcmil and 750m kcmil: 600m reels Note: Not for sale in the U.S.

• GENERAL CABLE BICC® BRAND SQ-CSA RWU90 XLPE SIZE (AWG OR KCMIL) AL ACM 1000V (-40°C) YEAR OF MFG SEQUENTIAL METER MARKING NOTE: For black insulation, add ­– SUN RES

COND. SIZE (AWG/ kcmil)

COND. STRAND

NOMINAL COND. O.D.** inCHES

mm

MIN. AVG. INS. THICKNESS inCHES

mm

NOMINAL DIAMETER (OVER) INSULATION INCHES

mm

ALUMINUM WEIGHT LBS/1000 FT

NET WEIGHT

kg/km

LBS/1000 FT

kg/km

AMPACITY*** 30˚C AMBIENT

23 37 59 74 93 117 148 186 235 296 350 420 490 559 701 841 1050 1400

39 52 72 85 102 132 158 190 229 279 335 391 446 500 608 733 893 1155

58 78 107 127 151 197 235 283 341 415 498 581 663 743 905 1091 1329 1718

30 50**** 65 75 95**** 105 120 145 165 185**** 215 240 260 290 330 370 405 480

8 AWG - 1000 kcmil CONDUCTORS 8 6 4 3 2 1 1/0 2/0 3/0 4/0 250 300 350 400* 500 600 750 1000*

7/.0486 7/.0612 7/.0772 7/.0867 7/.0974 19/.0664 19/.0745 19/.0837 19/.0940 19/.1055 37.0822 37.0900 37/.0973 37/.1040 37/.1162 61/.0992 61/.1109 61/.1280

0.13 0.17 0.21 0.24 0.27 0.30 0.34 0.38 0.42 0.48 0.52 0.57 0.62 0.66 0.74 0.81 0.91 1.06

3.30 4.32 5.33 6.10 6.86 7.62 8.64 9.65 10.67 12.19 13.21 14.48 15.75 16.76 18.80 20.57 23.11 26.92

0.080 0.080 0.080 0.080 0.080 0.095 0.095 0.095 0.095 0.095 0.110 0.110 0.110 0.110 0.110 0.125 0.125 0.125

2.03 2.03 2.03 2.03 2.03 2.41 2.41 2.41 2.41 2.41 2.79 2.79 2.79 2.79 2.79 3.17 3.17 3.17

0.31 0.34 0.39 0.42 0.45 0.52 0.56 0.60 0.65 0.78 0.84 0.89 0.89 0.93 1.02 1.12 1.23 1.38

7.70 8.70 9.90 10.60 11.40 13.10 14.10 15.30 16.50 18.00 19.90 21.20 22.60 23.70 25.80 28.50 31.10 34.90

16 25 39 50 63 79 99 125 158 199 235 282 329 376 471 565 706 941

Dimensions and weights are nominal; subject to industry tolerances. *Non-stock item, minimum runs apply. Please consult Customer Service for price and delivery. **For compact-stranded constructions, the number of wires may be reduced as follows: 19-Wire Constructions - 18 Wires Minimum 37-Wire Constructions - 35 Wires Minimum 61-Wire Constructions - 58 Wires Minimum ***Based on CEC Part 1-19th Edition, Table 2 for three conductors in raceway (conduit). For underground installations, refer to CEC, Rule 4-004 for ampacity rating. ****For 3 wires, 120/240V and 120/208V residential services or subservices, the allowable ampacity for 2/0 AWG shall be 200A. In this case, the 5% adjustment of Rule 8-106(1) cannot be applied.

Phone: 800-561-0649 www.generalcable.com


SPEC 5700

October, 2008

RHH/RHW-2

XLPE, Low-Voltage Power, Unshielded 2000V, UL Type RHH/RHW-2, Single Conductor, Aluminum Features:

• Rated at 90°C wet or dry • UV resistant - black is marked SR • Smaller cable O.D. • Excellent electrical, thermal and physical properties • Excellent resistance to moisture • Excellent reisistance to crush, compression cuts and heat deformation

Product Construction: Conductor:

• 8 AWG thru 1000 kcmil compacted aluminum ACM (AA-8000 Series)

Insulation:

• Flame-retardant Cross-Linked Polyethylene (XLPE) - Black

Print:

• GENERAL CABLE (SQ) AWG/KCMIL TYPE RHH/RHW-2 (UL) 2000V YEAR OF MFG SEQUENTIAL FOOTAGE MARK

CATALOG NUMBER

CONDUCTOR SIZE (AWG/kcmil)

COND. STRAND

Compliances:

Applications:

NOMINIAL CONDUCTOR MINIMAL AVERAGE DIAMETER INSULATION THICKNESS inCHES

• National Electric Code (NEC) • UL 44 Stranded for rubber-insulated wires and cables • ICEA S-95-685/NEMA WC70 • UL listed as Type RHH/RHW-2 • OSHA acceptable

• For use from the lower control box at the base of the wind power tower and out to the step-up transformer through conduit • General purpose building wire for use in air and approved raceways • Industrial environments where superior insulation toughness and chemical resistance is required • Maximum operating temperature not to exceed 90°C in wet or dry locations

mm

INCHES

mm

Packaging:

• Material cut to length and shipped on non-returnable wood reels

NOMINAL CABLE O.D. INCHES

NOMINAL ALUMINUM WEIGHT

mm

LBS/1000 FT

kg/km

NET WEIGHT LBS/1000 FT

kg/km

8 AWG - 1000 kcmil CONDUCTORS 522582M* 650981M* 589692M* 313406M* 149512M* 827197M* 977766M* 861898M* 763699M* 607078M* 506887M* 292686M* 526839M 883753M* 614607M

8

7/W

0.134

3.4

0.070

1.78

0.285

7.20

6

7/W

4

7/W

0.169

4.1

0.070

0.213

5.4

0.070

2

2/W

0.268

6.8

0.070

1.78

1

18/W

0.301

7.6

0.090

2.29

15.49

23.05

38.15

56.78

1.78

0.320

8.10

24.60

36.61

51.08

76.01

1.78

0.360

9.10

40.20

59.82

71.50

106.40

0.420

10.70

62.40

92.86

100.10

148.96

0.495

12.60

77.81

115.79

133.76

199.05 239.32

1/0

18/W

0.339

8.6

0.090

2.29

0.530

13.50

100.12

148.99

160.82

2/0

18/W

0.379

9.6

0.090

2.29

0.580

14.70

123.90

184.38

191.50

284.97

3/0

18/W

0.426

10.8

0.090

2.29

0.615

15.60

156.22

232.47

228.68

340.30

4/0

18/W

0.476

12.1

0.090

2.29

0.665

16.90

201.40

299.70

281.10

418.31

250

35/W

0.524

13.3

0.105

2.70

0.745

18.90

233.50

347.47

336.15

500.23

350

35/W

0.619

15.7

0.105

2.70

0.840

21.30

330.90

492.41

448.90

668.00

500

35/W

0.740

18.8

0.105

2.70

0.960

24.40

467.10

695.09

604.77

899.96

600

58/W

0.820

20.8

0.105

2.70

1.040

26.40

559.50

832.59

710.14

1056.76

750

58/W

0.910

23.1

0.120

3.05

1.175

29.90

700.50

1042.41

901.20

1341.08

1000

58/W

1.060

26.9

0.120

3.05

1.325

33.70

939.00

1397.33

1168.00

1738.10

Dimensions and weights are nominal; subject to industry tolerances.

Phone: 888-593-3355 www.generalcable.com


Industrial Cables

Date of Issue 01/09 Section 6

2.4kV — 35kV Industrial Medium-Voltage Cables SPECIFICATION NO.

PRODUCT DESCRIPTION

6050†

DuraSheath®

EPR/HYP, Medium-Voltage Power, Non-Shielded 2400V, UL Type MV-90

REVISION DATE

Jan. 2008

6100†

UniShield®

EPR/Copper Wire Shield/CPE, Medium-Voltage Power, Shielded 5kV and 8kV, UL Type MV-105, 133% / 100% Ins. Levels, 115 Mils

Jan. 2009

6150† Uniblend®

EPR/Copper Tape Shield/PVC, Medium-Voltage Power, Shielded 5kV and 8kV, UL Type MV-105, 133% / 100% Ins. Levels, 115 Mils

Jan. 2009

6175

Uniblend®

EPR/Copper Tape Shield/CPE, Medium-Voltage Power, Shielded 5kV and 8kV, UL Type MV-105, 133% / 100% Ins. Levels, 115 Mils

Jan. 2009

6180

GenFree™ Uniblend®

EPR/Copper Tape Shield/LSZH, Medium-Voltage Power, Shielded 5kV and 8kV, UL Type MV-105, 133% / 100% Ins. Levels, 115 Mils

Jan. 2009

6200 Copper Wire Shield TRXLPE/Copper Wire Shield/PVC, Medium-Voltage Power 5kV, UL Type MV-105, 100% Ins. Level, 90 Mils

Jan. 2008

6250†

Uniblend®

EPR/Copper Tape Shield with Overall PVC Jacket Medium-Voltage Power, Shielded, 5kV and 8kV, UL Type MV-105 133% / 100% Ins. Levels, 115 Mils, Three Conductor

Jan. 2009

6275

Uniblend®

EPR/Copper Tape Shield with Overall CPE Jacket Medium-Voltage Power, Shielded, 5kV and 8kV, UL Type MV-105 133% / 100% Ins. Levels, 115 Mils, Three Conductor

Jan. 2009

6280 GenFree™ Uniblend®

EPR/Copper Tape Shield with Overall LSZH Jacket Medium-Voltage Power, Shielded, 5kV and 8kV, UL Type MV-105 133% / 100% Ins. Levels, 115 Mils, Three Conductor

May 2008

6300†

UniShield®

EPR/Copper Wire Shield/CPE, Medium-Voltage Power, Shielded 15kV, UL Type MV-105, 133% Ins. Level, 220 Mils

Jan. 2009

6350†

Uniblend®

EPR/Copper Tape Shield/PVC, Medium-Voltage Power, Shielded 15kV, UL Type MV-105, 133% Ins. Level, 220 Mils

Jan. 2009

6375

Uniblend®

EPR/Copper Tape Shield/CPE, Medium-Voltage Power, Shielded 15kV, UL Type MV-105, 133% Ins. Level, 220 Mils

Jan. 2009

6380

GenFree™ Uniblend®

EPR/Copper Tape Shield/LSZH, Medium-Voltage Power, Shielded 15kV, UL Type MV-105, 133% Ins. Level, 220 Mils

Jan. 2009

6400 Copper Wire Shield TRXLPE/Copper Wire Shield/PVC, Medium-Voltage Power 15kV, UL Type MV-105, 133% Ins. Level, 220 Mils

Jan. 2008

6450†

Uniblend®

Jan. 2008

†Indicates

these products are stocked by General Cable

EPR/Copper Tape Shield with Overall PVC Jacket Medium-Voltage Power, Shielded, 15kV, UL Type MV-105 133% Ins. Level, 220 Mils, Three Conductor

Phone: 888-593-3355 www.generalcable.com


Industrial Cables

Date of Issue 01/09 Section 6

2.4kV — 35kV Industrial Medium-Voltage Cables SPECIFICATION NO.

PRODUCT DESCRIPTION

REVISION DATE

Uniblend®

EPR/Copper Tape Shield with Overall CPE Jacket Medium-Voltage Power, Shielded, 15kV, UL Type MV-105 133% Ins. Level, 220 Mils, Three Conductor

Jan. 2009

6480 GenFree™ Uniblend®

EPR/Copper Tape Shield with Overall LSZH Jacket Medium-Voltage Power, Shielded, 15kV, UL Type MV-105 133% Ins. Level, 220 Mils, Three Conductor

May 2008

6475

6500

UniShield®

EPR/Copper Wire Shield/CPE, Medium-Voltage Power, Shielded 25kV and 35kV, UL Type MV-105, 133% / 100% Ins. Levels, 345 Mils

Jan. 2009

6550†

Uniblend®

EPR/Copper Tape Shield/PVC, Medium-Voltage Power, Shielded 25kV and 35kV, UL Type MV-105, 133% / 100% Ins. Levels, 345 Mils

Jan. 2009

6575 Uniblend®

EPR/Copper Tape Shield/CPE, Medium-Voltage Power, Shielded 25kV and 35kV, UL Type MV-105, 133% / 100% Ins. Levels, 345 Mils

Jan. 2009

6580

GenFree™ Uniblend®

EPR/Copper Tape Shield/LSZH, Medium-Voltage Power, Shielded 25kV and 35kV, UL Type MV-105, 133% / 100% Ins. Levels, 345 Mils

Jan. 2009

6600

Uniblend®

EPR/Copper Tape Shield with Overall PVC Jacket Medium-Voltage Power, Shielded, 25kV and 35kV, UL Type MV-105 133% / 100% Ins. Levels, 345 Mils, Three Conductor

Jan. 2008

†Indicates

these products are stocked by General Cable

Phone: 888-593-3355 www.generalcable.com


SPEC 6050

January, 2008

DuraSheath

®

EPR/HYP, Medium-Voltage Power, Non-Shielded 2400V, UL Type MV-90

Product Construction Conductor:

Applications:

• 8 AWG thru 1000 kcmil annealed bare copper compact Class B strand

Extruded Strand Shield (ESS):

• Extruded thermoset semi-conducting stresscontrol layer over conductor

Insulation:

• Ethylene Propylene Rubber (EPR) insulation, colored to contrast with the black jacket material

Jacket:

• Low-Lead Chlorosulfonated Polyethylene (CSPE)/ Elastomer blend

Print:

Features:

• GENERAL CABLE® (MI) SIZE (AWG or KCMIL) COMPACT CU DURASHEATH® LL 2400V NONSHIELDED EP TYPE MV-90 WET OR DRY SUN RES FOR CT USE OIL RES II (UL) MONTH/ YEAR OF MFG SEQUENTIAL FOOTAGE MARK

Options:

• Multi conductor constructions • Other constructions available upon request

CATALOG NUMBER

14901.410800* 14901.410600 14901.410400 14901.410200 14901.410100* 14901.415100 14901.415200 14901.415300* 14901.415400 14901.416000 14901.416200 14901.416500 14901.417000 14901.417500*

8 6 4 2 1 1/0 2/0 3/0 4/0 250 350 500 750 1000

NOMINAL CONDUCTOR DIAMETER inCHES mm

Compliances:

• National Electric Code (NEC) • ICEA S-96-659/NEMA WC71 • UL 1072 • FAA L824 specification for cable for Underground Airport Lighting Circuits • UL listed as Type MV-90 for use in accordance with NEC • Sizes 1/0 AWG and larger are listed and marked “Sunlight-Resistant FOR CT USE” in accordance with NEC and also meet IEEE 383 (70,000 BTU/hr) • Listed “oil-resistant II” • Meets EPA 40 CFR, Part 261 for leachable lead content per TCLP method • OSHA acceptable

Packaging:

• Material cut to length and shipped on non-returnable wood reels

• Rated at 90˚C • Excellent heat and moisture resistance • Flexibility for easy handling • High dielectric strength • Low moisture absorption • Electrical stability under stress • Low dielectric loss • Chemical- and sunlight-resistant • Simplification of splicing and terminating by elimination of need to handle cable shield • Extra-tough, mechanically rugged composite insulation and jacket construction • Meets cold bend test at -35˚C

* Sizes smaller than 1/0 AWG do not include “FOR CT USE”

COND. SIZE (AWG/ kcmil)

• Proven record of reliable performance through extensive use in these applications: pulp and paper mills, petrochemical plants, sewage treatment facilities, water treatment plants, steel mills, textile mills, utility power generating stations, scrubbers and other environmental protections systems, railroad and mining facilities • For use in industrial and utility applications, where ease of installation is a major concern because of limited space and exposure to personnel is minimal • For use in wet or dry locations when installed in accordance with NEC • For use in aerial, conduit, open tray and underground duct installations

NOMINAL EXTRUDED STRAND SHIELD DIAMETER inCHES mm

NOMINAL INSULATION THICKNESS inCHES mm

NOMINAL INSULATION DIAMETER inCHES mm

NOMINAL CABLE O.D inCHES mm

COPPER WEIGHT

NET WEIGHT

LBS/ 1000 FT

kg/ km

LBS/ 1000 FT

kg/ km

51 81 129 205 259 326 411 518 653 772 1080 1544 2316 3086

76 121 192 305 385 485 612 771 972 1149 1607 2298 3447 4593

196 241 308 408 476 562 666 823 983 1183 1545 2077 3040 3913

292 359 458 607 708 836 991 1225 1463 1761 2299 3091 4524 5823

2400V, UL TYPE MV-90 0.14 0.17 0.22 0.27 0.31 0.34 0.38 0.43 0.48 0.53 0.62 0.74 0.91 1.06

3.56 4.32 5.59 6.86 7.87 8.64 9.65 10.92 12.19 13.46 15.75 18.80 23.11 26.92

0.15 0.19 0.23 0.29 0.33 0.36 0.41 0.45 0.50 0.55 0.64 0.77 0.94 1.09

3.81 4.83 5.84 7.37 8.38 9.14 10.41 11.43 12.70 13.97 16.26 19.56 23.88 27.69

0.125 0.125 0.125 0.125 0.125 0.125 0.125 0.125 0.125 0.140 0.140 0.140 0.155 0.155

3.18 3.18 3.18 3.18 3.18 3.18 3.18 3.18 3.18 3.56 3.56 3.56 3.94 3.94

0.41 0.44 0.49 0.55 0.58 0.62 0.66 0.71 0.76 0.84 0.93 1.06 1.26 1.42

10.41 11.18 12.45 13.97 14.73 15.75 16.76 18.03 19.30 21.34 23.62 26.92 32.00 36.07

0.58 0.62 0.66 0.72 0.76 0.79 0.84 0.92 0.97 1.08 1.17 1.30 1.54 1.70

14.73 15.75 16.76 18.29 19.30 20.07 21.34 23.37 24.64 27.43 29.72 33.02 39.12 43.18

Dimensions and weights are nominal; subject to industry tolerances. *Non-stock item, minimum runs apply. Please consult Customer Service for price and delivery.

Phone: 888-593-3355 www.generalcable.com


SPEC 6100

January, 2009

UniShield

®

EPR/Copper Wire Shield/CPE, Medium-Voltage Power, Shielded 5kV and 8kV, UL Type MV-105, 133% / 100% Ins. Levels, 115 Mils

Product Construction

Applications:

• Installed in a broad range of commercial, industrial and utility projects such as pulp and paper mills, petrochemical plants, steel mills, textile mills, water and sewage treatment facilities, environmental protection systems, railroads, mines and fossil fuel utility generating stations • Suitable for use in wet or dry locations when installed in accordance with NEC • For use in aerial, conduit, open tray and underground duct installations • For use in direct burial if installed in a system with a ground conductor that is in close proximity, and conforms with NEC 250.4 (A) (5)

Conductor: • 2 AWG thru 1000 kcmil annealed bare copper compact Class B strand

Extruded Strand Shield (ESS):

• Extruded thermoset semi-conducting stresscontrol layer over conductor

Insulation:

• Ethylene Propylene Rubber (EPR) insulation colored to contrast with black conducting shield layers

Composite Insulation Shield and Jacket:

• Six corrugated copper drain wires embedded in composite layers of semi-conducting thermoset copolymer and semi-conducting black flameretardant Chlorinated Polyethylene (CPE)

• Rated at 105˚C • Reduced conductor size and shield system provides the smallest premium medium-voltage shielded power cable with full insulation • Smaller outside dimensions reduce the size of duct needed or increase the ampacity per duct • All features contribute to faster and easier installation • Superior cold bend and cold impact performance • Stable and constant shield short circuit performance • Excellent heat and moisture resistance • Outstanding corona resistance • Flexibility for easy handling • High dielectric strength • Low dielectric loss

• GENERAL CABLE® (DI) (MO/YR OF MANUFACTURE) LIGHTNING BOLT SYMBOL 1/C SIZE (AWG OR KCMIL) COMPACT CU UNISHIELD® (INSULATION THICKNESS) EPR DRTP SEMI-CON CPE JKT TYPE MV105 (VOLTAGE) KV% INSULATION LEVEL SUN RES FOR CT USE (UL) Sequential Footage Mark * Sizes smaller than 1/0 AWG do not include “FOR CT USE”

CATALOG NUMBER

• Low moisture absorption • Electrical stability under stress • Chemical-resistant • Sunlight-resistant • Meets cold bend test at -55˚C

Compliances:

• National Electrical Code (NEC) • UL 1072 • ICEA S-93-639/NEMA WC74 • ICEA S-97-682 • AEIC CS8 • UL listed as Type MV-105 for use in accordance with NEC • UL 1685 (Sizes 1/0 AWG and larger) UL Flame Exposure Test • Sizes 1/0 AWG and larger are listed and marked “Sunlight-Resistant FOR CT USE” in accordance with NEC • IEEE 1202 (70,000 BTU/hr)/CSA FT4 • Meets EPA 40 CFR, Part 2671 for leachable lead content per TCLP method • OSHA acceptable Optional Flame Tests: • ICEA T-29-520 (210,000 BTU/hr)

Features:

Print:

NOMINAL COND. CONDUCTOR SIZE DIAMETER (AWG/ kcmil) inCHES

Features (cont’d.):

INSULATION DRAIN NOMINAL CABLE DIAMETER WIRE INCHES DIAMETER WEIGHT SIZE Min. MAX. (AWG) inCHES mm LBS/1000 FT kg/km

Packaging:

• Material cut to length and shipped on nonreturnable wood reels. Lengths in excess of 10,000 lbs. are provided on returnable steel reels that require a deposit • Extra charges apply for cuts less than 1000 ft., lagging, pulling eyes, paralleling and triplexing

AMPACITY

COPPER WEIGHT LBS/1000 FT kg/km

CONDUIT CONDUIT UNDERGROUND SIZING (3) IN AIR (1) DUCT (2) (INCHES)

5kV AND 8kV, UL TYPE MV-105, 133% / 100% INS. LEVELS, 115 MILS 19101.650200 19101.655100 19101.665200 19101.665300* 19101.665400 19101.676000 19101.676200 19101.686500 19101.687000 19101.667500*

2 1/0 2/0 3/0 4/0 250 350 500 750 1000

0.27 0.34 0.38 0.43 0.48 0.53 0.62 0.74 0.91 1.06

0.510 0.580 0.620 0.665 0.720 0.770 0.870 0.990 1.170 1.320

0.590 0.655 0.695 0.745 0.795 0.850 0.945 1.065 1.250 1.400

20 20 19 19 19 18 18 17 17 16

0.71 0.78 0.83 0.88 0.93 1.01 1.11 1.24 1.44 1.61

18.03 19.81 21.08 22.35 23.62 25.65 28.19 31.50 36.57 40.89

404 555 666 791 951 1112 1463 2003 2875 3746

601 825 990 1177 1415 1655 2176 2980 4278 5574

225 346 436 562 678 804 1113 1585 2357 3138

335 515 649 808 1010 1196 1656 2358 3507 4669

165 215 255 290 330 365 440 535 655 755

165 215 245 275 315 345 415 500 610 690

2.5 2.5 3 3 3 3.5 3.5 4 5 5

*Non-stock item, minimum runs apply. Please consult Customer Service for price and delivery. (1) Ampacities are in accordance with Table 310-73 of the NEC for triplexed or three single conductor copper cable in isolated conduit in air, based on a conductor temperature of 105˚C (221˚F) and an ambient air temperature of 40˚C (104˚F). (2) Ampacities are in accordance with Table 310-77 of the NEC for triplexed or three single conductor copper cable in underground ducts (three conductors per duct), based on a conductor temperature of 105˚C (221˚F) and an ambient earth temperature of 20˚C (68˚F), electrical duct arrangement per Figure 310.60 Detail 1, 100% load factor, and earth thermal resistance (rho) of 90. (3) Based on nominal cable diameters, three single cables in the duct (PVC Schedule 40) with no ground wire and a maximum of 40% fill. Jam ratio has been considered, but it should be checked for individual installations. Dimensions and weights are nominal; subject to industry tolerances. Note: a) Sizes smaller than 1/0 AWG do not include “FOR CT USE” b) The NESC Lightning bolt symbol is on all UniShield® constructions

Phone: 888-593-3355 www.generalcable.com


SPEC 6150

January, 2009

Uniblend

®

EPR/Copper Tape Shield/PVC, Medium-Voltage Power, Shielded 5kV and 8kV, UL Type MV-105, 133% / 100% Ins. Levels, 115 Mils Features:

Product Construction Conductor:

Print (cont’d.):

TYPE MV-105 (VOLTAGE) KV% INSULATION LEVEL SUN RES FOR CT USE (UL) Sequential Footage Mark

• 6 AWG thru 1000 kcmil annealed bare copper compact Class B strand

* Sizes smaller than 1/0 AWG do not include “FOR CT USE”

Extruded Strand Shield (ESS):

• Extruded thermoset semi-conducting stresscontrol layer over conductor

Options:

• PVC jacket colors other than black • Flame-retardant, Chlorinated Polyethylene (CPE) jacket • Low-Smoke, Zero-Halogen (LSZH) jacket • STRANDFILL® – blocked conductor. Tested in accordance with ICEA T-31-610

Insulation:

• Ethylene Propylene Rubber (EPR) insulation, colored to contrast with the black conducting shield layers

Extruded Insulation Shield (EIS):

• Thermoset semi-conducting polymeric layer free stripping from insulation

Metallic Shield:

• 5 mil annealed copper tape with an overlap of 25%

Jacket:

• Flame-retardant, moisture- and sunlight-resistant Polyvinyl Chloride (PVC)

Print:

• GENERAL CABLE® (DI) (MO/YR OF MANUFACTURE) LIGHTNING BOLT SYMBOL 1/C SIZE (AWG OR KCMIL) COMPACT CU UNIBLEND® (INSULATION THICKNESS) EPR

CATALOG NUMBER

NOMINAL COND. CONDUCTOR SIZE DIAMETER (AWG/ kcmil) inCHES

Applications:

• Superior performance in petrochemical plants, pulp and paper mills, sewage and water treatment plants, environmental protection systems, railroads, mines, utility power generating stations, steel mills, textile plants and other industrial threephase applications • For use in wet or dry locations when installed in accordance with NEC • For use in aerial, conduit, open tray and underground duct installations • For use in direct burial if installed in a system with a ground conductor that is in close proximity, and conforms with NEC 250.4 (A) (5)

INSULATION NOMINAL DIAMETER JACKET INCHES THICKNESS Min. MAX. inCHES mm

• Rated at 105˚C • Excellent heat and moisture resistance • Excellent flame resistance • Outstanding corona resistance • Flexibility for easy handling • High dielectric strength • Low moisture absorption • Electrical stability under stress • Low dielectric loss • Chemical-resistant • Meets cold bend test at -35˚C

Compliances:

• National Electrical Code (NEC) • UL 1072 • ICEA S-93-639/NEMA WC74 • ICEA S-97-682 • AEIC CS8 • UL listed as Type MV-105 for use in accordance with NEC • UL 1685 (Sizes 1/0 AWG and larger) UL Flame Exposure Test • Sizes 1/0 AWG and larger are listed and marked “Sunlight-Resistant FOR CT USE” in accordance with NEC • IEEE 1202 (70,000 BTU/hr)/CSA FT4 • Meets EPA 40 CFR, Part 2671 for leachable lead content per TCLP method • OSHA acceptable Optional Flame Tests: • ICEA T-29-520 (210,000 BTU/hr)

Packaging:

• Material cut to length and shipped on non-returnable wood reels. Lengths in excess of 10,000 lbs. are provided on returnable steel reels that require a deposit • Extra charges apply for cuts less than 1000 ft., lagging, pulling eyes, paralleling and triplexing

NOMINAL CABLE AMPACITY CONDUIT COPPER WEIGHT DIAMETER WEIGHT CONDUIT UNDERGROUND SIZING (3) inCHES mm LBS/1000 FT kg/km LBS/1000 FT kg/km IN AIR (1) DUCT (2) (INCHES)

5kV AND 8kV, UL TYPE MV-105, 133% / 100% INS. LEVELS, 115 MILS 17001.120600* 17001.120400* 17001.120200 17001.120100* 17001.125100 17001.125200 17001.125300* 17001.135400 17001.136000 17001.136200 17001.136500 17001.137000 17001.637500

6 4 2 1 1/0 2/0 3/0 4/0 250 350 500 750 1000

0.17 0.22 0.27 0.31 0.34 0.38 0.43 0.48 0.53 0.62 0.74 0.91 1.06

0.415 0.455 0.510 0.545 0.580 0.620 0.665 0.720 0.770 0.870 0.990 1.170 1.330

0.490 0.535 0.590 0.620 0.655 0.695 0.745 0.795 0.850 0.945 1.065 1.250 1.400

0.060 0.060 0.060 0.060 0.060 0.060 0.080 0.080 0.080 0.080 0.080 0.080 0.080

1.52 1.52 1.52 1.52 1.52 1.52 2.03 2.03 2.03 2.03 2.03 2.03 2.03

0.65 0.70 0.76 0.79 0.82 0.86 0.94 1.00 1.05 1.14 1.27 1.45 1.60

16.51 17.15 19.05 20.07 21.08 22.10 24.38 25.65 27.18 29.72 33.53 38.35 42.42

295 365 471 539 623 728 886 1053 1199 1559 2088 2962 3815

439 543 701 802 927 1083 1318 1567 1784 2320 3107 4407 5677

126 178 259 315 386 474 585 725 849 1165 1639 2427 3210

188 265 385 468 575 706 871 1080 1263 1735 2439 3611 4777

93 120 165 190 215 255 290 330 365 440 535 655 755

97 125 165 185 215 245 275 315 345 415 500 610 690

2 2.5 2.5 2.5 3 3 3 3 3.5 3.5 4 5 5

*Non-stock item, minimum runs apply. Please consult Customer Service for price and delivery. (1) Ampacities are in accordance with Table 310-73 of the NEC for triplexed or three single conductor copper cable in isolated conduit in air, based on a conductor temperature of 105˚C (221˚F) and an ambient air temperature of 40˚C (104˚F). (2) Ampacities are in accordance with Table 310-77 of the NEC for triplexed or three single conductor copper cable in underground ducts (three conductors per duct), based on a conductor temperature of 105˚C (221˚F) and an ambient earth temperature of 20˚C (68˚F), electrical duct arrangement per Figure 310.60 Detail 1, 100% load factor, and earth thermal resistance (rho) of 90. (3) Based on nominal cable diameters, three single cables in the duct (PVC Schedule 40) with no ground wire and a maximum of 40% fill. Jam ratio has been considered, but it should be checked for individual installations. Dimensions and weights are nominal; subject to industry tolerances. Note: a) Sizes smaller than 1/0 AWG do not include “FOR CT USE” b) The NESC Lightning bolt symbol is on all Uniblend® constructions

Phone: 888-593-3355 www.generalcable.com


SPEC 6175

January, 2009

Uniblend

®

EPR/Copper Tape Shield/CPE, Medium-Voltage Power, Shielded 5kV and 8kV, UL Type MV-105, 133% / 100% Ins. Levels, 115 Mils Features:

Product Construction Conductor:

Print (cont’d.):

UNIBLEND® CPE JKT (INSULATION THICKNESS) EPR TYPE MV-105 (VOLTAGE) KV% INSULATION LEVEL SUN RES FOR CT USE (UL) Sequential Footage Mark

• 6 AWG thru 1000 kcmil annealed bare copper compact Class B strand

Extruded Strand Shield (ESS):

* Sizes smaller than 1/0 AWG do not include “FOR CT USE”

• Extruded thermoset semi-conducting stresscontrol layer over conductor

Options:

Insulation:

• PVC jacket • Low-Smoke, Zero-Halogen (LSZH) jacket • STRANDFILL® – blocked conductor. Tested in accordance with ICEA T-31-610

• Ethylene Propylene Rubber (EPR) insulation, colored to contrast with the black conducting shield layers

Applications:

Extruded Insulation Shield (EIS):

• Thermoset semi-conducting polymeric layer free stripping from insulation

Metallic Shield:

• 5 mil annealed copper tape with an overlap of 25%

Jacket:

• Flame-retardant, moisture- and sunlight-resistant Chlorinated Polyethylene (CPE)

Print:

• GENERAL CABLE® (DI) (MO/YR OF MANUFACTURE) LIGHTNING BOLT SYMBOL 1/C SIZE (AWG OR KCMIL) COMPACT CU

CATALOG NUMBER

NOMINAL COND. CONDUCTOR SIZE DIAMETER (AWG/ kcmil) inCHES

• Superior performance in petrochemical plants, pulp and paper mills, sewage and water treatment plants, environmental protection systems, railroads, mines, utility power generating stations, steel mills, textile plants and other industrial threephase applications • For use in wet or dry locations when installed in accordance with NEC • For use in aerial, conduit, open tray and underground duct installations • For use in direct burial if installed in a system with a ground conductor that is in close proximity, and conforms with NEC 250.4 (A) (5)

INSULATION NOMINAL DIAMETER JACKET INCHES THICKNESS Min. MAX. inCHES mm

• Rated at 105˚C • Excellent heat and moisture resistance • Excellent flame resistance • Outstanding corona resistance • Flexibility for easy handling • High dielectric strength • Low moisture absorption • Electrical stability under stress • Low dielectric loss • Chemical-resistant • Meets cold bend test at -35˚C

Compliances:

• National Electrical Code (NEC) • UL 1072 • ICEA S-93-639/NEMA WC74 • ICEA S-97-682 • AEIC CS8 • UL listed as Type MV-105 for use in accordance with NEC • UL 1685 (Sizes 1/0 AWG and larger) UL Flame Exposure Test • Sizes 1/0 AWG and larger are listed and marked “Sunlight-Resistant FOR CT USE” in accordance with NEC • IEEE 1202 (70,000 BTU/hr)/CSA FT4 • Meets EPA 40 CFR, Part 2671 for leachable lead content per TCLP method • OSHA acceptable Optional Flame Tests: • ICEA T-29-520 (210,000 BTU/hr)

Packaging:

• Material cut to length and shipped on non-returnable wood reels. Lengths in excess of 10,000 lbs. are provided on returnable steel reels that require a deposit • Extra charges apply for cuts less than 1000 ft., lagging, pulling eyes, paralleling and triplexing

NOMINAL CABLE AMPACITY CONDUIT COPPER WEIGHT DIAMETER WEIGHT CONDUIT UNDERGROUND SIZING (3) IN mm LBS/1000 FT kg/km LBS/1000 FT kg/km IN AIR (1) DUCT (2) (INCHES)

5kV AND 8kV, UL TYPE MV-105, 133% / 100% INS. LEVELS, 115 MILS 17101.120600* 17101.120400* 17101.120200* 17101.120100* 17101.125100* 17101.125200* 17101.125300* 17101.135400* 17101.136000* 17101.136200* 17101.136500* 17101.137000* 17101.137500*

6 4 2 1 1/0 2/0 3/0 4/0 250 350 500 750 1000

0.17 0.22 0.27 0.31 0.34 0.38 0.43 0.48 0.53 0.62 0.74 0.91 1.06

0.415 0.455 0.510 0.545 0.580 0.620 0.665 0.720 0.770 0.870 0.990 1.170 1.330

0.490 0.535 0.590 0.620 0.655 0.695 0.745 0.795 0.850 0.945 1.065 1.250 1.400

0.060 0.060 0.060 0.060 0.060 0.060 0.080 0.080 0.080 0.080 0.080 0.080 0.080

1.52 1.52 1.52 1.52 1.52 1.52 2.03 2.03 2.03 2.03 2.03 2.03 2.03

0.65 0.70 0.76 0.79 0.82 0.86 0.94 1.00 1.05 1.14 1.27 1.45 1.60

16.51 17.15 19.05 20.07 21.08 22.10 24.38 25.65 27.18 29.72 33.53 38.35 42.42

293 363 469 537 621 726 883 1049 1195 1555 2083 2981 3808

436 540 698 799 924 1080 1314 1561 1778 2314 3100 4436 5666

126 178 259 315 386 474 585 725 849 1165 1639 2427 3210

188 265 385 468 575 706 871 1080 1263 1735 2439 3611 4777

93 120 165 190 215 255 290 330 365 440 535 655 755

97 125 165 185 215 245 275 315 345 415 500 610 690

2 2.5 2.5 2.5 3 3 3 3 3.5 3.5 4 5 5

*Non-stock item, minimum runs apply. Please consult Customer Service for price and delivery. (1) Ampacities are in accordance with Table 310-73 of the NEC for triplexed or three single conductor copper cable in isolated conduit in air, based on a conductor temperature of 105˚C (221˚F) and an ambient air temperature of 40˚C (104˚F). (2) Ampacities are in accordance with Table 310-77 of the NEC for triplexed or three single conductor copper cable in underground ducts (three conductors per duct), based on a conductor temperature of 105˚C (221˚F) and an ambient earth temperature of 20˚C (68˚F), electrical duct arrangement per Figure 310.60 Detail 1, 100% load factor, and earth thermal resistance (rho) of 90. (3) Based on nominal cable diameters, three single cables in the duct (PVC Schedule 40) with no ground wire and a maximum of 40% fill. Jam ratio has been considered, but it should be checked for individual installations. Dimensions and weights are nominal: subject to industry tolerances. Note: a) Sizes smaller than 1/0 AWG do not include “FOR CT USE” b) The NESC Lightning bolt symbol is on all Uniblend® constructions

Phone: 888-593-3355 www.generalcable.com


SPEC 6180

January, 2009

GenFree Uniblend ™

®

EPR/Copper Tape Shield/LSZH, Medium-Voltage Power, Shielded 5kV and 8kV, UL Type MV-105, 133% / 100% Ins. Levels, 115 Mils Features:

Product Construction Conductor:

Print:

• GENERAL CABLE® (DI) (MO/YR OF MANUFACTURE) LIGHTNING BOLT SYMBOL 1/C SIZE (AWG OR KCMIL) COMPACT CU GENFREE™ UNIBLEND® LSZH JKT (INSULATION THICKNESS) EPR TYPE MV-105 (VOLTAGE) KV% INSULATION LEVEL SUN RES FOR CT USE (UL) Sequential Footage Mark

• 6 AWG thru 1000 kcmil annealed bare copper compact Class B strand

Extruded Strand Shield (ESS):

• Extruded thermoset semi-conducting stresscontrol layer over conductor

* Sizes smaller than 1/0 AWG do not include “FOR CT USE”

Insulation:

• Ethylene Propylene Rubber (EPR) insulation, colored to contrast with the black conducting shield layers

Options:

• STRANDFILL® – blocked conductor. Tested in accordance with ICEA T-31-610

Extruded Insulation Shield (EIS):

• Thermoset semi-conducting polymeric layer free stripping from insulation

Metallic Shield:

• 5 mil annealed copper tape with an overlap of 25%

Jacket:

• Flame-retardant, moisture- and sunlight-resistant, Low-Smoke, Zero-Halogen Polyolefin (LSZH)

CATALOG NUMBER

NOMINAL COND. CONDUCTOR SIZE DIAMETER (AWG/ kcmil) inCHES

Applications:

• Superior performance in petrochemical plants, pulp and paper mills, sewage and water treatment plants, environmental protection systems, railroads, mines, utility power generating stations, steel mills, textile plants and other industrial threephase applications • For use in wet or dry locations when installed in accordance with NEC • For use in aerial, conduit, open tray and underground duct installations • For use in direct burial if installed in a system with a ground conductor that is in close proximity, and conforms with NEC 250.4 (A) (5)

INSULATION NOMINAL DIAMETER JACKET INCHES THICKNESS Min. MAX. inCHES mm

• Rated at 105˚C ��� Excellent heat and moisture resistance • Excellent flame resistance • Outstanding corona resistance • Flexibility for easy handling • High dielectric strength • Low moisture absorption • Electrical stability under stress • Low dielectric loss • Chemical-resistant • Meets cold bend test at -35˚C

Compliances:

• National Electrical Code (NEC) • UL 1072 • ICEA S-93-639/NEMA WC74 • ICEA S-97-682 • AEIC CS8 • UL listed as Type MV-105 for use in accordance with NEC • UL 1685 (Sizes 1/0 AWG and larger) UL Flame Exposure Test • Sizes 1/0 AWG and larger are listed and marked “Sunlight-Resistant FOR CT USE” in accordance with NEC • IEEE 1202 (70,000 BTU/hr)/CSA FT4 • Meets EPA 40 CFR, Part 2671 for leachable lead content per TCLP method • OSHA acceptable Optional Flame Tests: • ICEA T-29-520 (210,000 BTU/hr)

Packaging:

• Material cut to length and shipped on non-returnable wood reels. Lengths in excess of 10,000 lbs. are provided on returnable steel reels that require a deposit • Extra charges apply for cuts less than 1000 ft., lagging, pulling eyes, paralleling and triplexing

NOMINAL CABLE AMPACITY CONDUIT COPPER WEIGHT DIAMETER WEIGHT CONDUIT UNDERGROUND SIZING (3) inCHES mm LBS/1000 FT kg/km LBS/1000 FT kg/km IN AIR (1) DUCT (2) (INCHES)

5kV AND 8kV, UL TYPE MV-105, 133% / 100% INS. LEVELS, 115 MILS 17201.120600* 17201.120400* 17201.120200* 17201.120100* 17201.125100* 17201.125200* 17201.125300* 17201.135400* 17201.136000* 17201.136200* 17201.136500* 17201.137000* 17201.637500*

6 4 2 1 1/0 2/0 3/0 4/0 250 350 500 750 1000

0.17 0.22 0.27 0.31 0.34 0.38 0.43 0.48 0.53 0.62 0.74 0.91 1.06

0.415 0.455 0.510 0.545 0.580 0.620 0.665 0.720 0.770 0.870 0.990 1.170 1.330

0.490 0.535 0.590 0.620 0.655 0.695 0.745 0.795 0.850 0.945 1.065 1.250 1.400

0.060 0.060 0.060 0.060 0.060 0.060 0.080 0.080 0.080 0.080 0.080 0.080 0.080

1.52 1.52 1.52 1.52 1.52 1.52 2.03 2.03 2.03 2.03 2.03 2.03 2.03

0.65 0.70 0.76 0.79 0.82 0.86 0.94 1.00 1.05 1.14 1.27 1.45 1.60

16.51 17.15 19.05 20.07 21.08 22.10 24.38 25.65 27.18 29.72 33.53 38.35 42.42

295 365 471 539 623 728 886 1053 1199 1559 2088 2962 3815

439 543 701 802 927 1083 1318 1567 1784 2320 3107 4407 5677

126 178 259 315 386 474 585 725 849 1165 1639 2427 3210

188 265 385 468 575 706 871 1080 1263 1735 2439 3611 4777

93 120 165 190 215 255 290 330 365 440 535 655 755

97 125 165 185 215 245 275 315 345 415 500 610 690

2 2.5 2.5 2.5 3 3 3 3 3.5 3.5 4 5 5

*Non-stock item, minimum runs apply. Please consult Customer Service for price and delivery. (1) Ampacities are in accordance with Table 310-73 of the NEC for triplexed or three single conductor copper cable in isolated conduit in air, based on a conductor temperature of 105˚C (221˚F) and an ambient air temperature of 40˚C (104˚F). (2) Ampacities are in accordance with Table 310-77 of the NEC for triplexed or three single conductor copper cable in underground ducts (three conductors per duct), based on a conductor temperature of 105˚C (221˚F) and an ambient earth temperature of 20˚C (68˚F), electrical duct arrangement per Figure 310.60 Detail 1, 100% load factor, and earth thermal resistance (rho) of 90. (3) Based on nominal cable diameters, three single cables in the duct (PVC Schedule 40) with no ground wire and a maximum of 40% fill. Jam ratio has been considered, but it should be checked for individual installations. Dimensions and weights are nominal; subject to industry tolerances. Note: a) Sizes smaller than 1/0 AWG do not include “FOR CT USE” b) The NESC Lightning bolt symbol is on all Uniblend® constructions

Phone: 888-593-3355 www.generalcable.com


SPEC 6200

January, 2008

Copper Wire Shield

TRXLPE/Copper Wire Shield/PVC, Medium-Voltage Power 5kV, UL Type MV-105, 100% Ins. Level, 90 Mils Features:

Product Construction Conductor:

Print:

• 6 AWG thru 1000 kcmil annealed bare copper Class B compressed strand in accordance with ASTM B3 and B8

Extruded Strand Shield (ESS):

• Extruded thermoset semi-conducting stress control layer over conductor

Options:

Insulation:

• Tree Retardant Cross-Linked Polyethylene (TRXLPE)

Extruded Insulation Shield (EIS):

• Thermoset semi-conducting polymeric layer free stripping from insulation

Metallic Shield:

• A concentric serve of 24 AWG annealed solid bare copper wires over which shall be applied a lapped non-metallic tape

Jacket:

• Flame-retardant, moisture- and sunlight-resistant Polyvinyl Chloride (PVC)

CATALOG NUMBER

NOMINAL COND. CONDUCTOR SIZE DIAMETER (AWG/ kcmil) inCHES

• GENERAL CABLE® (DI) (MO/YR OF MANUFACTURE) LIGHTNING BOLT SYMBOL 1/C SIZE (AWG OR KCMIL) CU (INSULATION THICKNESS) TRXLPE TYPE MV-105 (VOLTAGE) KV% INSULATION LEVEL SUN RES (UL) SEQUENTIAL FOOTAGE MARK • Sizes 1/0 AWG and larger are listed and marked “Sunlight-Resistant FOR CT USE” in accordance with NEC and in accordance with UL 1685 (70,000 BTU/hr) • STRANDFILL® – blocked conductor. Tested in accordance with ICEA T-31-610

Applications:

• For use in wet or dry locations when installed in accordance with NEC • For use in aerial, conduit, open tray and underground duct installations where cost effectiveness is a factor • For use in direct burial if installed in a system with a ground conductor that is in close proximity, and conforms with NEC 250.4 (A) (5)

INSULATION NOMINAL DIAMETER JACKET INCHES THICKNESS Min. MAX. inCHES mm

• Rated at 105˚C • Triple tandem extrusion of the strand shield, insulation and insulation shield provides a virtually perfect cable core • Excellent resistance to electro-chemical treeing, heat, moisture and a wide variety of industrial chemicals • PVC jacket provides mechanical protection of the shielding system during installation, as well as protection from many industrial chemicals • Sunlight-resistant • Meets cold bend test at -35˚C

Compliances:

• National Electrical Code (NEC) • ICEA S-93-639/NEMA WC74 • ICEA S-97-682 • AEIC CS8 • UL 1072 • UL listed as Type MV-105 for use in accordance with NEC • Meets EPA 40 CFR, Part 261 for leachable lead content per TCLP method • OSHA acceptable

Packaging:

• Material cut to length and shipped on non-returnable wood reels. Lengths in excess of 10,000 lbs. are provided on returnable steel reels that require a deposit • Extra charges apply for cuts less than 1000 ft., lagging, pulling eyes, paralleling and plexing

NOMINAL CABLE COPPER WEIGHT DIAMETER WEIGHT inCHES mm LBS/1000 FT kg/km LBS/1000 FT kg/km

AMPACITY CONDUIT CONDUIT UNDERGROUND SIZING (3) IN AIR (1) DUCT (2) (INCHES)

5kV, UL TYPE MV-105, 100% INS. LEVELS, 90 MILS 17241.010600* 17241.010400* 17241.010200* 17241.015100* 17241.015200* 17241.015400* 17241.016000* 17241.016200* 17241.016500* 17241.017000* 17241.017500*

6 4 2 1/0 2/0 4/0 250 350 500 750 1000

0.18 0.23 0.29 0.37 0.41 0.52 0.56 0.67 0.80 0.97 1.12

0.370 0.420 0.475 0.555 0.600 0.705 0.760 0.865 0.990 1.180 1.325

0.445 0.495 0.555 0.630 0.675 0.780 0.835 0.940 1.070 1.255 1.405

0.060 0.060 0.060 0.060 0.060 0.080 0.080 0.080 0.080 0.080 0.080

1.52 1.52 1.52 1.52 1.52 2.03 2.03 2.03 2.03 2.03 2.03

0.67 0.72 0.77 0.85 0.89 1.04 1.10 1.20 1.36 1.53 1.66

17.02 18.29 19.55 21.59 22.61 26.42 28.19 30.48 34.54 38.86 42.16

250 317 420 580 670 1000 1155 1505 2060 2868 3684

372 472 625 863 997 1488 1719 2240 3066 4268 5482

93 141 217 338 427 669 788 1097 1563 2340 3113

138 210 323 503 635 996 1173 1632 2325 3482 4632

84 110 145 200 225 305 355 430 530 665 770

92 120 155 210 235 310 345 415 505 630 720

2.5 2.5 2.5 3 3 3.5 3.5 4 5 5 6

*Non-stock item, minimum runs apply. Please consult Customer Service for price and delivery. (1) Ampacities are in accordance with Table 310-73 of the NEC for triplexed or three single conductor copper cable in isolated conduit in air, based on a conductor temperature of 105˚C (221˚F) and an ambient air temperature of 40˚C (104˚F). (2) Ampacities are in accordance with Table 310-77 of the NEC for triplexed or three single conductor copper cable in underground ducts (three conductors per duct), based on a conductor temperature of 105˚C (221˚F) and an ambient earth temperature of 20˚C (68˚F), electrical duct arrangement per Figure 310.60 Detail 1, 100% load factor, and earth thermal resistance (rho) of 90. (3) Based on nominal cable diameters, three single cables in the duct (PVC Schedule 40) with no ground wire and a maximum of 40% fill. Jam ratio has been considered, but it should be checked for individual installations. Dimensions and weights are nominal; subject to industry tolerances. Note: The NESC Lighting bolt symbol is on all Uniblend constructions. ®

Phone: 888-593-3355 www.generalcable.com


SPEC 6250

January, 2009

Uniblend

®

EPR/Copper Tape Shield with Overall PVC Jacket, Medium-Voltage Power, Shielded 5kV and 8kV, UL Type MV-105, 133% / 100% Ins. Levels, 115 Mils, Three Conductor Features:

Product Construction Conductor:

Print:

• 6 AWG thru 1000 kcmil annealed bare copper compact Class B strand

Extruded Strand Shield (ESS):

• Extruded thermoset semi-conducting stresscontrol layer over conductor

Options:

Insulation:

• Ethylene Propylene Rubber (EPR) insulation, colored to contrast with the black conducting shield layers

Extruded Insulation Shield (EIS):

• Thermoset semi-conducting polymeric layer free stripping from insulation

Metallic Shield:

• 5mil annealed copper tape with an overlap of 25% • 1 bare grounding conductor may be in contact with metallic shielding tape

Overall Jacket:

• Flame-retardant, moisture- and sunlight-resistant Polyvinyl Chloride (PVC)

NOMINAL COND. CONDUCTOR SIZE DIAMETER (AWG/ kcmil) inCHES

• PVC jacket colors other than black • Flame-retardant, Chlorinated Polyethylene (CPE) jacket • Low-Smoke, Zero-Halogen (LSZH) jacket • Jacketed singles • UniShield® singles • STRANDFILL® – blocked conductor. Tested in accordance with ICEA T-31-610 • 3 bare copper ground wires • Covered ground wires

Applications:

Grounding Conductor:

CATALOG NUMBER

• GENERAL CABLE® (DI) (MO/YR OF MANUFACTURE) LIGHTNING BOLT SYMBOL 3/C SIZE (AWG OR KCMIL) COMPACT CU UNIBLEND® (INSULATION THICKNESS) EPR TYPE MV-105 (VOLTAGE) KV% INSULATION LEVEL SUN RES FOR CT USE (UL) SEQUENTIAL FOOTAGE MARK

• Suited for use in a broad range of commercial, industrial and utility applications, where reliability is the major concern, space is limited and ease of installation is critical • In wet or dry locations when installed in accordance with NEC • In aerial, direct burial, conduit, open tray and underground duct installations

INSULATION NOMINAL DIAMETER OVERALL JKT GROUND INCHES THICKNESS WIRE Min. MAX. (AWG) inCHES mm

• Rated at 105˚C • Excellent heat and moisture resistance • Outstanding corona resistance • Flexibility for easy handling • High dielectric strength • Low moisture absorption • Electrical stability under stress • Low dielectric loss • Chemical-resistant • Meets cold bend test at -35˚C

Compliances:

• National Electrical Code (NEC) • UL 1072 • ICEA S-93-639/NEMA WC74 • ICEA S-97-682 • AEIC CS8 • UL listed as Type MV-105 for use in accordance with NEC • UL 1685 (70,000 BTU/hr) • Meets EPA 40 CFR, Part 261 for leachable lead content per TCLP method • OSHA acceptable Optional Flame Tests: • IEEE 1202 (70,000 BTU/hr)/CSA FT4 • ICEA T-29-520 (210,000 BTU/hr)

Packaging:

• Material cut to length and shipped on non-returnable wood reels. Lengths in excess of 10,000 lbs. are provided on returnable steel reels that require a deposit • Extra charges apply for cuts less than 1000 ft., lagging, pulling eyes, paralleling and plexing

NOMINAL CABLE AMPACITY COPPER WEIGHT DIAMETER WEIGHT CONDUIT UNDERGROUND inCHES mm LBS/1000 FT kg/km LBS/1000 FT kg/km IN AIR (1) DUCT (2)

5kV AND 8kV, UL TYPE MV-105, 133% / 100% INS. LEVELS, 115 MILS, THREE CONDUCTOR 6 0.17 0.415 0.490 6 0.080 2.03 1.29 32.77 939 1397 460 685 92 15493.400600 4 0.22 0.455 0.535 6 0.080 2.03 1.39 35.31 1158 1723 616 917 120 15493.400400 2 0.27 0.510 0.590 6 0.080 2.03 1.51 38.35 1511 2249 860 1279 165 15493.400200 0.34 0.580 0.655 4 0.080 2.03 1.67 42.42 2030 3021 1290 1919 215 15493.405100 1/0 0.38 0.620 0.695 4 0.080 2.03 1.82 46.23 2449 3645 1556 2315 245 15493.405200 2/0 0.48 0.720 0.795 3 0.110 2.79 2.07 52.58 3438 5116 2344 3488 320 15493.405400 4/0 0.53 0.770 0.850 2 0.110 2.79 2.15 54.61 3968 5904 2759 4105 350 15493.406000* 250 0.62 0.870 0.945 2 0.110 2.79 2.36 59.94 5009 7454 3713 5525 430 15493.406200 350 0.74 0.990 1.065 1 0.110 2.79 2.64 67.06 6793 10065 5191 7724 525 15493.406500 500 0.91 1.170 1.250 1/0 0.140 3.56 3.14 79.76 9833 14633 7629 11352 635 15493.407000* 750 1.06 1.330 1.400 2/0 0.140 3.56 3.48 88.39 12601 18753 10070 14985 725 15493.407500* 1000

95 125 160 210 235 305 335 400 485 585 660

*Non-stock item, minimum runs apply. Please consult Customer Service for price and delivery. (1) Ampacities are in accordance with Table 310-75 of the NEC for three conductor copper cable in isolated conduit in air, based on a conductor temperature of 105˚C (221˚F) and an ambient air temperature of 40˚C (104˚F). (2) Ampacities are in accordance with Table 310-79 of the NEC for three conductor copper cable in underground ducts (three conductors per duct), based on a conductor temperature of 105˚C (221˚F) and an ambient earth temperature of 20˚C (68˚F), electrical duct arrangement per Figure 310.60 Detail 1, 100% load factor, and earth thermal resistance (rho) of 90. Dimensions and weights are nominal; subject to industry tolerances. Note: a) All sizes are “FOR CT USE” b) The NESC Lightning bolt symbol is on all Uniblend® constructions

Phone: 888-593-3355 www.generalcable.com


SPEC 6275

January, 2009

Uniblend

®

EPR/Copper Tape Shield with Overall CPE Jacket, Medium-Voltage Power, Shielded 5kV and 8kV, UL Type MV-105, 133% / 100% Ins. Levels, 115 Mils, Three Conductor Features:

Product Construction Conductor:

• 6 AWG thru 1000 kcmil annealed bare copper compact Class B strand

Extruded Strand Shield (ESS):

• Extruded thermoset semi-conducting stresscontrol layer over conductor

Print:

• GENERAL CABLE® (DI) (MO/YR OF MANUFACTURE) LIGHTNING BOLT SYMBOL 3/C SIZE (AWG OR KCMIL) COMPACT CU UNIBLEND® CPE JKT (INSULATION THICKNESS) EPR TYPE MV-105 (VOLTAGE) KV% INSULATION LEVEL SUN RES FOR CT USE (UL) Sequential Footage Mark

Compliances:

• National Electrical Code (NEC) • UL 1072 • ICEA S-93-639/NEMA WC74 • ICEA S-97-682 • AEIC CS8 • UL listed as Type MV-105 for use in accordance with NEC • UL 1685 (70,000 BTU/hr) • OSHA acceptable Optional Flame Tests: • IEEE 1202 (70,000 BTU/hr)/CSA FT4 • ICEA T-29-520 (210,000 BTU/hr)

Options:

Insulation:

• Ethylene Propylene Rubber (EPR) insulation, colored to contrast with the black conducting shield layers

Extruded Insulation Shield (EIS):

• Thermoset semi-conducting polymeric layer free stripping from insulation

Metallic Shield:

• 5mil annealed copper tape with an overlap of 25%

Grounding Conductor:

• 1 bare grounding conductor may be in contact with metallic shielding tape

Overall Jacket:

• Flame-retardant, moisture- and sunlight-resistant Chlorinated Polyethylene (CPE)

CATALOG NUMBER

• Rated at 105˚C • Excellent heat and moisture resistance • Outstanding corona resistance • Flexibility for easy handling • High dielectric strength • Low moisture absorption • Electrical stability under stress • Low dielectric loss • Chemical-resistant • Meets cold bend test at -35˚C

• PVC jacket • Low-Smoke, Zero-Halogen (LSZH) jacket • Jacketed singles • UniShield® singles • STRANDFILL® – blocked conductor. Tested in accordance with ICEA T-31-610 • 3 bare copper ground wires • Covered ground wires

Packaging:

Applications:

• Suited for use in a broad range of commercial, industrial and utility applications, where reliability is the major concern, space is limited and ease of installation is critical • In wet or dry locations when installed in accordance with NEC • In aerial, direct burial, conduit, open tray and underground duct installations

NOMINAL INSULATION NOMINAL COND. CONDUCTOR DIAMETER GROUND OVERALL JKT SIZE DIAMETER INCHES THICKNESS (AWG/ WIRE kcmil) inCHES Min. MAX. (AWG) inCHES mm

NOMINAL CABLE DIAMETER WEIGHT inCHES mm LBS/1000 FT kg/km

• Material cut to length and shipped on non-returnable wood reels. Lengths in excess of 10,000 lbs. are provided on returnable steel reels that require a deposit • Extra charges apply for cuts less than 1000 ft., lagging, pulling eyes, paralleling and plexing

AMPACITY COPPER WEIGHT LBS/1000 FT kg/km

CONDUIT UNDERGROUND IN AIR (1) DUCT (2)

5kV AND 8kV, UL TYPE MV-105, 133% / 100% INS. LEVELS, 115 MILS, THREE CONDUCTOR 0.17 0.415 0.490 6 0.080 2.03 1.29 32.77 939 1397 460 685 92 15593.400600* 6 0.22 0.455 0.535 6 0.080 2.03 1.39 35.31 1158 1723 616 917 120 15593.400400* 4 0.27 0.510 0.590 6 0.080 2.03 1.51 38.35 1511 2249 860 1279 165 15593.400200* 2 0.34 0.580 0.655 4 0.080 2.03 1.67 42.42 2030 3021 1290 1919 215 15593.405100* 1/0 0.38 0.620 0.695 4 0.080 2.03 1.82 46.23 2449 3645 1556 2315 245 15593.405200* 2/0 0.48 0.720 0.795 3 0.110 2.79 2.07 52.58 3438 5116 2344 3488 320 15593.405400* 4/0 0.53 0.770 0.850 2 0.110 2.79 2.15 54.61 3968 5904 2759 4105 350 15593.406000* 250 0.62 0.870 0.945 2 0.110 2.79 2.36 59.94 5009 7454 3713 5525 430 15593.406200* 350 0.74 0.990 1.065 1 0.110 2.79 2.64 67.06 6793 10065 5191 7724 525 15593.406500* 500 0.91 1.170 1.250 1/0 0.140 3.56 3.14 79.76 9833 14633 7629 11352 635 15593.407000* 750 1.06 1.330 1.400 2/0 0.140 3.56 3.48 88.39 12601 18753 10070 14985 725 15593.407500* 1000

95 125 160 210 235 305 335 400 485 585 660

*Non-stock item, minimum runs apply. Please consult Customer Service for price and delivery. (1) Ampacities are in accordance with Table 310-75 of the NEC for three conductor copper cable in isolated conduit in air, based on a conductor temperature of 105˚C (221˚F) and an ambient air temperature of 40˚C (104˚F). (2) Ampacities are in accordance with Table 310-79 of the NEC for three conductor copper cable in underground ducts (three conductors per duct), based on a conductor temperature of 105˚C (221˚F) and an ambient earth temperature of 20˚C (68˚F), electrical duct arrangement per Figure 310.60 Detail 1, 100% load factor, and earth thermal resistance (rho) of 90. Dimensions and weights are nominal; subject to industry tolerances. Note: a) Sizes smaller than 4/0 AWG do not include “FOR CT USE” b) The NESC Lightning bolt symbol is on all Uniblend® constructions

Phone: 888-593-3355 www.generalcable.com


SPEC 6280

May, 2008

GenFree Uniblend ™

®

EPR/Copper Tape Shield with Overall LSZH Jacket, Medium-Voltage Power, Shielded 5kV and 8kV, UL Type MV-105, 133% / 100% Ins. Levels, 115 Mils, Three Conductor Features:

Product Construction Conductor:

• 6 AWG thru 1000 kcmil annealed bare copper compact Class B strand

Extruded Strand Shield (ESS):

• Extruded thermoset semi-conducting stresscontrol layer over conductor

• Rated at 105˚C • Excellent heat and moisture resistance • Outstanding corona resistance • Flexibility for easy handling • High dielectric strength • Low moisture absorption • Electrical stability under stress • Low dielectric loss • Chemical-resistant • Meets cold bend test at -35˚C

Print:

• GENERAL CABLE® (DI) (MO/YR OF MANUFACTURE) LIGHTNING BOLT SYMBOL 3/C SIZE (AWG OR KCMIL) COMPACT CU GENFREE™ UNIBLEND® LSZH JKT (INSULATION THICKNESS) EPR TYPE MV-105 (VOLTAGE) KV% INSULATION LEVEL SUN RES FOR CT USE (UL) Sequential Footage Mark

Compliances:

• National Electrical Code (NEC) • UL 1072 • ICEA S-93-639/NEMA WC74 • ICEA S-97-682 • ICEA T-33-655 • AEIC CS8 • UL listed as Type MV-105 for use in accordance with NEC • UL 1685 (70,000 BTU/hr) • OSHA acceptable Optional Flame Tests: • IEEE 1202 (70,000 BTU/hr)/CSA FT4 • ICEA T-29-520 (210,000 BTU/hr)

Options:

Insulation:

• Ethylene Propylene Rubber (EPR) insulation, colored to contrast with the black conducting shield layers

Extruded Insulation Shield (EIS):

• Thermoset semi-conducting polymeric layer free stripping from insulation

Metallic Shield:

• 5 mil annealed copper tape with an overlap of 25%

Grounding Conductor:

• 1 bare grounding conductor may be in contact with metallic shielding tape

• STRANDFILL® – blocked conductor. Tested in accordance with ICEA T-31-610 • 3 bare copper ground wires • Covered ground wires

Applications:

• Suited for use in a broad range of commercial, industrial and utility applications, where reliability is the major concern, space is limited and ease of installation is critical • In wet or dry locations when installed in accordance with NEC • In aerial, direct burial, conduit, open tray and underground duct installations

Packaging:

Overall Jacket:

• Material cut to length and shipped on non-returnable wood reels. Lengths in excess of 10,000 lbs. are provided on returnable steel reels that require a deposit • Extra charges apply for cuts less than 1000 ft., lagging, pulling eyes, paralleling and plexing

• Flame-retardant, moisture- and sunlight-resistant, Low-Smoke, Zero-Halogen Polyolefin (LSZH)

CATALOG NUMBER

NOMINAL INSULATION NOMINAL COND. CONDUCTOR DIAMETER GROUND OVERALL JKT SIZE DIAMETER INCHES THICKNESS (AWG/ WIRE kcmil) inCHES Min. MAX. (AWG) inCHES mm

NOMINAL CABLE DIAMETER WEIGHT inCHES mm LBS/1000 FT kg/km

AMPACITY COPPER WEIGHT LBS/1000 FT kg/km

CONDUIT UNDERGROUND IN AIR (1) DUCT (2)

5kV AND 8kV, UL TYPE MV-105, 133% / 100% INS. LEVELS, 115 MILS, THREE CONDUCTOR 0.17 0.415 0.490 6 0.080 2.03 1.29 32.77 939 1397 460 685 92 15693.400600* 6 0.22 0.455 0.535 6 0.080 2.03 1.39 35.31 1158 1723 616 917 120 15693.400400* 4 0.27 0.510 0.590 6 0.080 2.03 1.51 38.35 1511 2249 860 1279 165 15693.400200* 2 0.34 0.580 0.655 4 0.080 2.03 1.67 42.42 2030 3021 1290 1919 215 15693.405100* 1/0 0.38 0.620 0.695 4 0.080 2.03 1.82 46.23 2449 3645 1556 2315 245 15693.405200* 2/0 0.48 0.720 0.795 3 0.110 2.79 2.07 52.58 3438 5116 2344 3488 320 15693.405400* 4/0 0.53 0.770 0.850 2 0.110 2.79 2.15 54.61 3968 5904 2759 4105 350 15693.406000* 250 0.62 0.870 0.945 2 0.110 2.79 2.36 59.94 5009 7454 3713 5525 430 15693.406200* 350 0.74 0.990 1.065 1 0.110 2.79 2.64 67.06 6793 10065 5191 7724 525 15693.406500* 500 0.91 1.170 1.250 1/0 0.140 3.56 3.14 79.76 9833 14633 7629 11352 635 15693.407000* 750 1.06 1.330 1.400 2/0 0.140 3.56 3.48 88.39 12601 18753 10070 14985 725 15693.407500* 1000

95 125 160 210 235 305 335 400 485 585 660

*Non-stock item, minimum runs apply. Please consult Customer Service for price and delivery. (1) Ampacities are in accordance with Table 310-75 of the NEC for three conductor copper cable in isolated conduit in air, based on a conductor temperature of 105˚C (221˚F) and an ambient air temperature of 40˚C (104˚F). (2) Ampacities are in accordance with Table 310-79 of the NEC for three conductor copper cable in underground ducts (three conductors per duct), based on a conductor temperature of 105˚C (221˚F) and an ambient earth temperature of 20˚C (68˚F), electrical duct arrangement per Figure 310.60 Detail 1, 100% load factor, and earth thermal resistance (rho) of 90. Dimensions and weights are nominal; subject to industry tolerances. Note: a) Sizes smaller than 1/0 AWG do not include “FOR CT USE” b) The NESC Lightning bolt symbol is on all Uniblend® constructions

Phone: 888-593-3355 www.generalcable.com


SPEC 6300

January, 2009

UniShield

®

EPR/Copper Wire Shield/CPE, Medium-Voltage Power, Shielded 15kV, UL Type MV-105, 133% Ins. Level, 220 Mils Features (cont’d.):

Product Construction Conductor:

Applications:

• Installed in a broad range of commercial, industrial and utility projects such as pulp and paper mills, petrochemical plants, steel mills, textile mills, water and sewage treatment facilities, environmental protection systems, railroads, mines and fossil fuel utility generating stations • Suitable for use in wet or dry locations when installed in accordance with NEC • For use in aerial, conduit, open tray and underground duct installations • For use in direct burial if installed in a system with a ground conductor that is in close proximity, and conforms with NEC 250.4 (A) (5)

• 2 AWG thru 1000 kcmil annealed bare copper compact Class B strand

Extruded Strand Shield (ESS):

• Extruded thermoset semi-conducting stresscontrol layer over conductor

Insulation:

• Ethylene Propylene Rubber (EPR) insulation colored to contrast with black conducting shield layers

Composite Insulation Shield and Jacket:

• Six corrugated copper drain wires embedded in composite layers of semi-conducting thermoset copolymer and semi-conducting black flameretardant Chlorinated Polyethylene (CPE)

Features:

• Rated at 105˚C • Reduced conductor size and shield system provides the smallest premium medium-voltage shielded power cable with full insulation • Smaller outside dimensions reduce the size of duct needed or increase the ampacity per duct • All features contribute to faster and easier installation • Superior cold bend and cold impact performance • Stable and constant shield short circuit performance

Print:

• GENERAL CABLE® (DI) (MO/YR OF MANUFACTURE) LIGHTNING BOLT SYMBOL 1/C SIZE (AWG OR KCMIL) COMPACT CU UNISHIELD® (INSULATION THICKNESS) EPR DRTP SEMI-CON CPE JKT TYPE MV-105 (VOLTAGE) KV% INSULATION LEVEL SUN RES FOR CT USE (UL) Sequential Footage Mark * Sizes smaller than 1/0 AWG do not include “FOR CT USE”

CATALOG NUMBER

NOMINAL COND. CONDUCTOR SIZE DIAMETER (AWG/ kcmil) INCHES

INSULATION DIAMETER INCHES Min. MAX.

• Excellent heat and moisture resistance • Outstanding corona resistance • Flexibility for easy handling • High dielectric strength • Low dielectric loss • Low moisture absorption • Electrical stability under stress • Chemical-resistant • Sunlight-resistant • Meets cold bend test at -55˚C

Compliances:

• National Electrical Code (NEC) • UL 1072 • ICEA S-93-639/NEMA WC74 • ICEA S-97-682 • AEIC CS8 • UL listed as Type MV-105 for use in accordance with NEC • UL 1685 (Sizes 1/0 AWG and larger) UL Flame Exposure Test • Sizes 1/0 AWG and larger are listed and marked “Sunlight-Resistant FOR CT USE” in accordance with NEC • IEEE 1202 (70,000 BTU/hr)/CSA FT4 • Meets EPA 40 CFR, Part 2671 for leachable lead content per TCLP method • OSHA acceptable Optional Flame Tests: • ICEA T-29-520 (210,000 BTU/hr)

Packaging:

• Material cut to length and shipped on nonreturnable wood reels. Lengths in excess of 10,000 lbs. are provided on returnable steel reels that require a deposit • Extra charges apply for cuts less than 1000 ft., lagging, pulling eyes, paralleling and triplexing

DRAIN NOMINAL CABLE WIRE COPPER WEIGHT DIAMETER WEIGHT SIZE (AWG) INCHES mm LBS/1000 FT kg/km LBS/1000 FT kg/km

AMPACITY CONDUIT CONDUIT UNDERGROUND TRAY SIZING (4) IN AIR (1) DUCT (2) (3) (INCHES)

15kV ¥ , UL TYPE MV-105, 133% INS. LEVEL, 220 MILS 2 19161.660200 19161.675100 1/0 19161.675200 2/0 19161.665300* 3/0 19161.675400 4/0 19161.686000 250 19161.686200 350 19161.686500 500 19161.697000 750 19161.307500* 1000

0.27 0.34 0.38 0.43 0.48 0.53 0.62 0.74 0.91 1.06

0.710 0.780 0.820 0.865 0.920 0.970 1.070 1.190 1.370 1.520

0.800 0.865 0.905 0.955 1.005 1.060 1.155 1.275 1.460 1.610

19 18 18 18 18 17 17 17 16 16

0.93 1.01 1.05 1.10 1.16 1.23 1.33 1.46 1.67 1.86

23.88 25.91 27.18 28.45 29.72 31.50 33.78 37.08 42.42 47.24

555 734 844 978 1151 1325 1691 2238 3174 4122

835 1102 1259 1458 1716 1984 2530 3344 4739 6133

230 358 443 550 685 813 1122 1585 2368 3138

342 533 659 818 1019 1210 1669 2358 3523 4669

165 215 255 290 330 365 440 535 655 755

165 215 245 275 315 345 415 500 610 690

220 250 290 335 370 460 575 745 890

3 3.5 3.5 3.5 4 4 5 5 6 6

*Non-stock item, minimum runs apply. Please consult Customer Service for price and delivery. (1) Ampacities are in accordance with Table 310-73 of the NEC for triplexed or three single conductor copper cable in isolated conduit in air, based on a conductor temperature of 105˚C (221˚F) and an ambient air temperature of 40˚C (104˚F). (2) Ampacities are in accordance with Table 310-77 of the NEC for triplexed or three single conductor copper cable in underground ducts (three conductors per duct), based on a conductor temperature of 105˚C (221˚F) and an ambient earth temperature of 20˚C (68˚F), electrical duct arrangement per Figure 310.60 Detail 1, 100% load factor, and earth thermal resistance (rho) of 90. (3) Ampacities are based on single conductor Type MV-105 sizes #1/0 AWG and larger in an uncovered tray in accordance with Section 392-13(B) of the NEC at an ambient air temperature of 40˚C (104˚F); the ampacities are based on 75% of the values per Table 310-69. For cable trays with unventilated covers for more than 6 feet, the ampacities shall not exceed 95% of the values shown above. (4) Based on nominal cable diameters, three single cables in the duct (PVC Schedule 40) with no ground wire and a maximum of 40% fill. Jam ratio has been considered, but it should be checked for individual installations. ¥100% insulation level is available upon request Dimensions and weights are nominal; subject to industry tolerances. Note: a) Sizes smaller than 1/0 AWG do not include “FOR CT USE” b) The NESC Lightning bolt symbol is on all UniShield® constructions

Phone: 888-593-3355 www.generalcable.com


SPEC 6350

January, 2009

Uniblend

®

EPR/Copper Tape Shield/PVC, Medium-Voltage Power, Shielded 15kV, UL Type MV-105, 133% Ins. Level, 220 Mils Features:

Product Construction Conductor:

Print (cont’d.):

TYPE MV-105 (VOLTAGE) KV% INSULATION LEVEL SUN RES FOR CT USE (UL) Sequential Footage Mark

• 2 AWG thru 1000 kcmil annealed bare copper compact Class B strand • Extruded thermoset semi-conducting stresscontrol layer over conductor

• National Electrical Code (NEC) • UL 1072 • ICEA S-93-639/NEMA WC74 • ICEA S-97-682 • AEIC CS8 • UL listed as Type MV-105 for use in accordance with NEC • UL 1685 (Sizes 1/0 AWG and larger) UL Flame Exposure Test • Sizes 1/0 AWG and larger are listed and marked “Sunlight-Resistant FOR CT USE” in accordance with NEC • IEEE 1202 (70,000 BTU/hr)/CSA FT4 • Meets EPA 40 CFR, Part 2671 for leachable lead content per TCLP method • OSHA acceptable Optional Flame Tests: • ICEA T-29-520 (210,000 BTU/hr)

Options:

• PVC jacket colors other than black • Flame-retardant, Chlorinated Polyethylene (CPE) jacket • Low-Smoke, Zero-Halogen (LSZH) jacket • STRANDFILL® – blocked conductor. Tested in accordance with ICEA T-31-610 • 100% insulation level

Insulation:

• Ethylene Propylene Rubber (EPR) insulation, colored to contrast with the black conducting shield layers

Extruded Insulation Shield (EIS):

• Thermoset semi-conducting polymeric layer free stripping from insulation

Applications:

• Superior performance in petrochemical plants, pulp and paper mills, sewage and water treatment plants, environmental protection systems, railroads, mines, utility power generating stations, steel mills, textile plants and other industrial threephase applications • For use in wet or dry locations when installed in accordance with NEC • For use in aerial, conduit, open tray and underground duct installations • For use in direct burial if installed in a system with a ground conductor that is in close proximity, and conforms with NEC 250.4 (A) (5)

Metallic Shield:

• 5 mil annealed copper tape with an overlap of 25%

Jacket:

• Flame-retardant, moisture- and sunlight-resistant Polyvinyl Chloride (PVC)

Print:

• GENERAL CABLE® (DI) (MO/YR OF MANUFACTURE) LIGHTNING BOLT SYMBOL 1/C SIZE (AWG OR KCMIL) COMPACT CU UNIBLEND® (INSULATION THICKNESS) EPR

NOMINAL COND. CONDUCTOR SIZE DIAMETER (AWG/ kcmil) inCHES

Compliances:

* Sizes smaller than 1/0 AWG do not include “FOR CT USE”

Extruded Strand Shield (ESS):

CATALOG NUMBER

• Rated at 105˚C • Excellent heat and moisture resistance • Excellent flame resistance • Outstanding corona resistance • Flexibility for easy handling • High dielectric strength • Low moisture absorption • Electrical stability under stress • Low dielectric loss • Chemical-resistant • Meets cold bend test at -35˚C

Packaging:

• Material cut to length and shipped on non-returnable wood reels. Lengths in excess of 10,000 lbs. are provided on returnable steel reels that require a deposit • Extra charges apply for cuts less than 1000 ft., lagging, pulling eyes, paralleling and triplexing

INSULATION NOMINAL NOMINAL CABLE AMPACITY DIAMETER JACKET CONDUIT INCHES THICKNESS COPPER WEIGHT CONDUIT UNDERGROUND TRAY SIZING DIAMETER WEIGHT (4) Min. MAX. inCHES mm inCHES mm LBS/1000 FT kg/km LBS/1000 FT kg/km IN AIR (1) DUCT (2) (3) (INCHES)

15kV ¥ , UL TYPE MV-105, 133% INS. LEVEL, 220 MILS 2 17031.130200 17031.130100* 1 17031.135100 1/0 17031.135200 2/0 17031.135300* 3/0 17031.135400 4/0 17031.136000 250 17031.136200 350 17031.136500 500 17031.137000 750 17031.137500 1000

0.27 0.31 0.34 0.38 0.43 0.48 0.53 0.62 0.74 0.91 1.06

0.710 0.745 0.780 0.820 0.865 0.920 0.970 1.070 1.190 1.370 1.520

0.800 0.830 0.865 0.905 0.955 1.005 1.060 1.155 1.275 1.460 1.610

0.080 0.080 0.080 0.080 0.080 0.080 0.080 0.080 0.080 0.080 0.110

2.03 2.03 2.03 2.03 2.03 2.03 2.03 2.03 2.03 2.03 2.79

0.99 1.02 1.06 1.10 1.14 1.21 1.25 1.35 1.47 1.65 1.86

25.14 25.91 26.92 27.94 28.95 30.73 31.75 34.29 37.34 41.91 47.24

658 733 825 938 1078 1261 1407 1783 2331 3234 4219

979 1090 1228 1396 1604 1876 2093 2653 3468 4812 6278

276 332 403 492 603 743 866 1184 1657 2445 3228

411 494 600 732 897 1105 1289 1761 2466 3638 4803

165 190 215 255 290 330 365 440 535 655 755

165 185 215 245 275 315 345 415 500 610 690

220 250 290 335 370 460 575 745 890

3 3.5 3.5 3.5 3.5 3.5 4 5 5 6 6

*Non-stock item, minimum runs apply. Please consult Customer Service for price and delivery. (1) Ampacities are in accordance with Table 310-73 of the NEC for triplexed or three single conductor copper cable in isolated conduit in air, based on a conductor temperature of 105˚C (221˚F) and an ambient air temperature of 40˚C (104˚F). (2) Ampacities are in accordance with Table 310-77 of the NEC for triplexed or three single conductor copper cable in underground ducts (three conductors per duct), based on a conductor temperature of 105˚C (221˚F) and an ambient earth temperature of 20˚C (68˚F), electrical duct arrangement per Figure 310.60 Detail 1, 100% load factor, and earth thermal resistance (rho) of 90. (3) Ampacities are based on single conductor Type MV-105 sizes #1/0 AWG and larger in an uncovered tray in accordance with Section 392-13(B) of the NEC at an ambient air temperature of 40˚C (104˚F); the ampacities are based on 75% of the values per Table 310-69. For cable trays with unventilated covers for more than 6 feet, the ampacities shall not exceed 95% of the values shown above. (4) Based on nominal cable diameters, three single cables in the duct (PVC Schedule 40) with no ground wire and a maximum of 40% fill. Jam ratio has been considered, but it should be checked for individual installations. ¥100% insulation level is available upon request Dimensions and weights are nominal; subject to industry tolerances. Note: a) Sizes smaller than 1/0 AWG do not include “FOR CT USE” b) The NESC Lightning bolt symbol is on all Uniblend® constructions

Phone: 888-593-3355 www.generalcable.com


SPEC 6375

January, 2009

Uniblend

®

EPR/Copper Tape Shield/CPE, Medium-Voltage Power, Shielded 15kV, UL Type MV-105, 133% Ins. Level, 220 Mils Features:

Product Construction Conductor:

Print (cont’d.):

UNIBLEND® CPE JKT (INSULATION THICKNESS) EPR TYPE MV-105 (VOLTAGE) KV% INSULATION LEVEL SUN RES FOR CT USE (UL) Sequential Footage Mark

• 2 AWG thru 1000 kcmil annealed bare copper compact Class B strand

Extruded Strand Shield (ESS):

* Sizes smaller than 1/0 AWG do not include “FOR CT USE”

• Extruded thermoset semi-conducting stresscontrol layer over conductor

Options:

Insulation:

• PVC jacket • Low-Smoke, Zero-Halogen (LSZH) jacket • STRANDFILL® – blocked conductor. Tested in accordance with ICEA T-31-610 • 100% insulation level

• Ethylene Propylene Rubber (EPR) insulation, colored to contrast with the black conducting shield layers

Extruded Insulation Shield (EIS):

• Thermoset semi-conducting polymeric layer free stripping from insulation

Applications:

• Superior performance in petrochemical plants, pulp and paper mills, sewage and water treatment plants, environmental protection systems, railroads, mines, utility power generating stations, steel mills, textile plants and other industrial threephase applications • For use in wet or dry locations when installed in accordance with NEC • For use in aerial, conduit, open tray and underground duct installations • For use in direct burial if installed in a system with a ground conductor that is in close proximity, and conforms with NEC 250.4 (A) (5)

Metallic Shield:

• 5 mil annealed copper tape with an overlap of 25%

Jacket:

• Flame-retardant, moisture- and sunlight-resistant Chlorinated Polyethylene (CPE)

Print:

• GENERAL CABLE® (DI) (MO/YR OF MANUFACTURE) LIGHTNING BOLT SYMBOL 1/C SIZE (AWG OR KCMIL) COMPACT CU

CATALOG NUMBER

• Rated at 105˚C • Excellent heat and moisture resistance • Excellent flame resistance • Outstanding corona resistance • Flexibility for easy handling • High dielectric strength • Low moisture absorption • Electrical stability under stress • Low dielectric loss • Chemical-resistant • Meets cold bend test at -35˚C

Compliances:

• National Electrical Code (NEC) • UL 1072 • ICEA S-93-639/NEMA WC74 • ICEA S-97-682 • AEIC CS8 • UL listed as Type MV-105 for use in accordance with NEC • UL 1685 (Sizes 1/0 AWG and larger) UL Flame Exposure Test • Sizes 1/0 AWG and larger are listed and marked “Sunlight-Resistant FOR CT USE” in accordance with NEC • IEEE 1202 (70,000 BTU/hr)/CSA FT4 • Meets EPA 40 CFR, Part 2671 for leachable lead content per TCLP method • OSHA acceptable Optional Flame Tests: • ICEA T-29-520 (210,000 BTU/hr)

Packaging:

• Material cut to length and shipped on non-returnable wood reels. Lengths in excess of 10,000 lbs. are provided on returnable steel reels that require a deposit • Extra charges apply for cuts less than 1000 ft., lagging, pulling eyes, paralleling and triplexing

NOMINAL INSULATION NOMINAL COND. CONDUCTOR NOMINAL CABLE AMPACITY DIAMETER JACKET SIZE DIAMETER CONDUIT INCHES THICKNESS COPPER WEIGHT DIAMETER WEIGHT (AWG/ CONDUIT UNDERGROUND TRAY SIZING (4) kcmil) INCHES Min. MAX. INCHES mm INCHES mm LBS/1000 FT kg/km LBS/1000 FT kg/km IN AIR (1) DUCT (2) (3) (INCHES)

15kV ¥ , UL TYPE MV-105, 133% INS. LEVEL, 220 MILS 17131.130200* 17131.130100* 17131.135100* 17131.135200* 17131.135300* 17131.135400* 17131.136000* 17131.136200* 17131.136500* 17131.137000* 17131.637500*

2 1 1/0 2/0 3/0 4/0 250 350 500 750 1000

0.27 0.31 0.34 0.38 0.43 0.48 0.53 0.62 0.74 0.91 1.06

0.710 0.745 0.780 0.820 0.865 0.920 0.970 1.070 1.190 1.370 1.520

0.800 0.830 0.865 0.905 0.955 1.005 1.060 1.155 1.275 1.460 1.610

0.080 0.080 0.080 0.080 0.080 0.080 0.080 0.080 0.080 0.080 0.110

2.03 2.03 2.03 2.03 2.03 2.03 2.03 2.03 2.03 2.03 2.79

0.99 1.02 1.06 1.10 1.14 1.21 1.25 1.35 1.47 1.65 1.86

25.14 25.91 26.92 27.94 28.95 30.73 31.75 34.29 37.34 41.91 47.24

655 730 820 933 1072 1248 1402 1778 2325 3250 4209

975 1086 1220 1388 1595 1857 2086 2646 3460 4836 6263

276 332 403 492 603 743 866 1184 1657 2445 3228

411 494 600 732 897 1105 1289 1761 2466 3638 4803

165 190 215 255 290 330 365 440 535 655 755

165 185 215 245 275 315 345 415 500 610 690

220 250 290 335 370 460 575 745 890

3 3.5 3.5 3.5 3.5 3.5 4 5 5 6 6

*Non-stock item, minimum runs apply. Please consult Customer Service for price and delivery. (1) Ampacities are in accordance with Table 310-73 of the NEC for triplexed or three single conductor copper cable in isolated conduit in air, based on a conductor temperature of 105˚C (221˚F) and an ambient air temperature of 40˚C (104˚F). (2) Ampacities are in accordance with Table 310-77 of the NEC for triplexed or three single conductor copper cable in underground ducts (three conductors per duct), based on a conductor temperature of 105˚C (221˚F) and an ambient earth temperature of 20˚C (68˚F), electrical duct arrangement per Figure 310.60 Detail 1, 100% load factor, and earth thermal resistance (rho) of 90. (3) Ampacities are based on single conductor Type MV-105 sizes #1/0 AWG and larger in an uncovered tray in accordance with Section 392-13(B) of the NEC at an ambient air temperature of 40˚C (104˚F; the ampacities are based on 75% of the values per Table 310-69. For cable trays with unventilated covers for more than 6 feet, the ampacities shall not exceed 95% of the values shown above. (4) Based on nominal cable diameters, three single cables in the duct (PVC Schedule 40) with no ground wire and a maximum of 40% fill. Jam ratio has been considered, but it should be checked for individual installations. ¥100% insulation level is available upon request Dimensions and weights are nominal: subject to industry tolerances. Note: a) Sizes smaller than 1/0 AWG do not include “FOR CT USE” b) The NESC Lightning bolt symbol is on all Uniblend® constructions

Phone: 888-593-3355 www.generalcable.com


SPEC 6380

January, 2009

GenFree Uniblend ™

®

EPR/Copper Tape Shield/LSZH, Medium-Voltage Power, Shielded 15kV, UL Type MV-105, 133% Ins. Level, 220 Mils Features:

Product Construction Conductor:

Print:

• GENERAL CABLE® (DI) (MO/YR OF MANUFACTURE) LIGHTNING BOLT SYMBOL 1/C SIZE (AWG OR KCMIL) COMPACT CU GENFREE™ UNIBLEND® LSZH JKT (INSULATION THICKNESS) EPR TYPE MV-105 (VOLTAGE) KV% INSULATION LEVEL SUN RES FOR CT USE (UL) Sequential Footage Mark

• 2 AWG thru 1000 kcmil annealed bare copper compact Class B strand

Extruded Strand Shield (ESS):

• Extruded thermoset semi-conducting stresscontrol layer over conductor • Ethylene Propylene Rubber (EPR) insulation, colored to contrast with the black conducting shield layers

• National Electrical Code (NEC) • UL 1072 • ICEA S-93-639/NEMA WC74 • ICEA S-97-682 • AEIC CS8 • UL listed as Type MV-105 for use in accordance with NEC • UL 1685 (Sizes 1/0 AWG and larger) UL Flame Exposure Test • Sizes 1/0 AWG and larger are listed and marked “Sunlight-Resistant FOR CT USE” in accordance with NEC • IEEE 1202 (70,000 BTU/hr)/CSA FT4 • Meets EPA 40 CFR, Part 2671 for leachable lead content per TCLP method • OSHA acceptable Optional Flame Tests: • ICEA T-29-520 (210,000 BTU/hr)

Options:

Extruded Insulation Shield (EIS):

• Thermoset semi-conducting polymeric layer free stripping from insulation

Metallic Shield:

• 5 mil annealed copper tape with an overlap of 25%

Jacket:

• Flame-retardant, moisture- and sunlight-resistant, Low-Smoke, Zero-Halogen Polyolefin (LSZH)

NOMINAL COND. CONDUCTOR SIZE DIAMETER (AWG/ kcmil) inCHES

Compliances:

* Sizes smaller than 1/0 AWG do not include “FOR CT USE”

Insulation:

CATALOG NUMBER

• Rated at 105˚C • Excellent heat and moisture resistance • Excellent flame resistance • Outstanding corona resistance • Flexibility for easy handling • High dielectric strength • Low moisture absorption • Electrical stability under stress • Low dielectric loss • Chemical-resistant • Meets cold bend test at -35˚C

• STRANDFILL® – blocked conductor. Tested in accordance with ICEA T-31-610 • 100% insulation level

Applications:

• Superior performance in petrochemical plants, pulp and paper mills, sewage and water treatment plants, environmental protection systems, railroads, mines, utility power generating stations, steel mills, textile plants and other industrial threephase applications • For use in wet or dry locations when installed in accordance with NEC • For use in aerial, conduit, open tray and underground duct installations • For use in direct burial if installed in a system with a ground conductor that is in close proximity, and conforms with NEC 250.4 (A) (5)

Packaging:

• Material cut to length and shipped on non-returnable wood reels. Lengths in excess of 10,000 lbs. are provided on returnable steel reels that require a deposit • Extra charges apply for cuts less than 1000 ft., lagging, pulling eyes, paralleling and triplexing

INSULATION NOMINAL NOMINAL CABLE AMPACITY DIAMETER JACKET CONDUIT INCHES THICKNESS COPPER WEIGHT CONDUIT UNDERGROUND TRAY SIZING DIAMETER WEIGHT (4) Min. MAX. inCHES mm inCHES mm LBS/1000 FT kg/km LBS/1000 FT kg/km IN AIR (1) DUCT (2) (3) (INCHES)

15kV ¥ , UL TYPE MV-105, 133% INS. LEVEL, 220 MILS 17231.130200* 17231.130100* 17231.135100* 17231.135200* 17231.135300* 17231.135400* 17231.136000* 17231.136200* 17231.136500* 17231.137000* 17231.137500*

2 1 1/0 2/0 3/0 4/0 250 350 500 750 1000

0.27 0.31 0.34 0.38 0.43 0.48 0.53 0.62 0.74 0.91 1.06

0.710 0.745 0.780 0.820 0.865 0.920 0.970 1.070 1.190 1.370 1.520

0.800 0.830 0.865 0.905 0.955 1.005 1.060 1.155 1.275 1.460 1.610

0.080 0.080 0.080 0.080 0.080 0.080 0.080 0.080 0.080 0.080 0.110

2.03 2.03 2.03 2.03 2.03 2.03 2.03 2.03 2.03 2.03 2.79

0.99 1.02 1.06 1.10 1.14 1.21 1.25 1.35 1.47 1.65 1.86

25.14 25.91 26.92 27.94 28.95 30.73 31.75 34.29 37.34 41.91 47.24

658 733 825 938 1078 1261 1407 1783 2331 3234 4219

979 1090 1228 1396 1604 1876 2093 2653 3468 4812 6278

276 332 403 492 603 743 866 1184 1657 2445 3228

411 494 600 732 897 1105 1289 1761 2466 3638 4803

165 190 215 255 290 330 365 440 535 655 755

165 185 215 245 275 315 345 415 500 610 690

220 250 290 335 370 460 575 745 890

3 3.5 3.5 3.5 3.5 3.5 4 5 5 6 6

*Non-stock item, minimum runs apply. Please consult Customer Service for price and delivery. (1) Ampacities are in accordance with Table 310-73 of the NEC for triplexed or three single conductor copper cable in isolated conduit in air, based on a conductor temperature of 105˚C (221˚F) and an ambient air temperature of 40˚C (104˚F). (2) Ampacities are in accordance with Table 310-77 of the NEC for triplexed or three single conductor copper cable in underground ducts (three conductors per duct), based on a conductor temperature of 105˚C (221˚F) and an ambient earth temperature of 20˚C (68˚F), electrical duct arrangement per Figure 310.60 Detail 1, 100% load factor, and earth thermal resistance (rho) of 90. (3) Ampacities are based on single conductor Type MV-105 sizes #1/0 AWG and larger in an uncovered tray in accordance with Section 392-13(B) of the NEC at an ambient air temperature of 40˚C (104˚F); the ampacities are based on 75% of the values per Table 310-69. For cable trays with unventilated covers for more than 6 feet, the ampacities shall not exceed 95% of the values shown above. (4) Based on nominal cable diameters, three single cables in the duct (PVC Schedule 40) with no ground wire and a maximum of 40% fill. Jam ratio has been considered, but it should be checked for individual installations. ¥100% insulation level is available upon request Dimensions and weights are nominal; subject to industry tolerances. Note: a) Sizes smaller than 1/0 AWG do not include “FOR CT USE” b) The NESC Lightning bolt symbol is on all Uniblend® constructions

Phone: 888-593-3355 www.generalcable.com


SPEC 6400

January, 2008

Copper Wire Shield

TRXLPE/Copper Wire Shield/PVC, Medium-Voltage Power 15kV, UL Type MV-105, 133% Ins. Level, 220 Mils Features:

Product Construction Conductor:

Print:

• GENERAL CABLE® (DI) (MO/YR OF MANUFACTURE) LIGHTNING BOLT SYMBOL 1/C SIZE (AWG OR KCMIL) CU (INSULATION THICKNESS) TRXLPE TYPE MV-105 (VOLTAGE) KV% INSULATION LEVEL SUN RES (UL) SEQUENTIAL FOOTAGE MARK

• 2 AWG thru 1000 kcmil annealed bare copper, Class B compressed strand in accordance with ASTM B3 and B8

Extruded Strand Shield (ESS):

• Extruded thermoset semi-conducting stresscontrol layer over conductor

Options:

• Sizes 1/0 AWG and larger are listed and marked “Sunlight-Resistant FOR CT USE” in accordance with NEC and in accordance with UL 1685 (70,000 BTU/hr) • STRANDFILL® – blocked conductor. Tested in accordance with ICEA T-31-610

Insulation:

• Tree Retardant Cross-Linked Polyethylene (TRXLPE)

Extruded Insulation Shield (EIS):

• Thermoset semi-conducting polymeric layer free stripping from insulation

Applications:

• For use in wet or dry locations when installed in accordance with NEC • For use in aerial, conduit, open tray and underground duct installations where cost effectiveness is a factor • For use in direct burial if installed in a system with a ground conductor that is in close proximity, and conforms with NEC 250.4 (A) (5)

Metallic Shield:

• A concentric serve of 24 AWG annealed solid bare copper wires over which shall be applied a lapped non-metallic tape

Jacket:

• Flame-retardant, moisture- and sunlight-resistant Polyvinyl Chloride (PVC)

CATALOG NUMBER

• Rated at 105˚C • Triple tandem extrusion of the strand shield, insulation and insulation shield provides a virtually perfect cable core • Excellent resistance to electro-chemical treeing, heat, moisture and a wide variety of industrial chemicals • PVC jacket provides mechanical protection of the shielding system during installation as well as protection from many industrial chemicals • Sunlight-resistant • Meets cold bend test at -35˚C

Compliances:

• National Electrical Code (NEC) • ICEA S-93-639/NEMA WC74 • ICEA S-97-682 • AEIC CS8 • UL 1072 • UL listed as Type MV-105 for use in accordance with NEC • Meets EPA 40 CFR, Part 261 for leachable lead content per TCLP method • OSHA acceptable

Packaging:

• Material cut to length and shipped on nonreturnable wood reels. Lengths in excess of 10,000 lbs. are provided on returnable steel reels that require a deposit • Extra charges apply for cuts less than 1000 ft., lagging, pulling eyes, paralleling and triplexing

NOMINAL INSULATION NOMINAL COND. CONDUCTOR NOMINAL CABLE AMPACITY JACKET SIZE DIAMETER DIAMETER CONDUIT INCHES THICKNESS COPPER WEIGHT CONDUIT IN UNDERGROUND TRAY SIZING DIAMETER WEIGHT (AWG/ (4) kcmil) INCHES Min. MAX. INCHES mm INCHES mm LBS/1000 FT kg/km LBS/1000 FT kg/km AIR (1) DUCT (2) (3) (INCHES)

15kV ¥ , UL TYPE MV-105, 133% INS. LEVEL, 220 MILS 17245.010200* 17245.010100* 17245.015100* 17245.015200* 17245.015400* 17245.016000* 17245.016200* 17245.016500* 17245.017000* 17245.017500*

2 1 1/0 2/0 4/0 250 350 500 750 1000

0.29 0.33 0.37 0.41 0.52 0.56 0.67 0.80 0.97 1.12

0.725 0.765 0.805 0.850 0.955 1.010 1.115 1.240 1.430 1.575

0.815 0.855 0.895 0.935 1.045 1.100 1.200 1.330 1.520 1.670

0.080 0.080 0.080 0.080 0.080 0.080 0.080 0.080 0.110 0.110

2.03 2.03 2.03 2.03 2.03 2.03 2.03 2.03 2.79 2.79

1.05 1.09 1.13 1.18 1.29 1.34 1.45 1.57 1.82 1.97

26.67 27.68 28.27 29.97 32.76 34.03 36.83 39.87 46.23 50.04

600 671 761 871 1179 1327 1700 2236 3225 4090

893 998 1132 1296 1754 1974 2529 3327 4798 6086

221 274 342 427 672 791 1105 1568 2344 3114

329 408 509 635 1000 1177 1644 2333 3488 4634

165 190 215 255 330 365 440 535 655 755

165 185 215 245 315 345 415 500 610 690

220 250 335 370 460 575 745 890

3.5 3.5 3.5 4 4 5 5 5 6 6

*Non-stock item, minimum runs apply. Please consult Customer Service for price and delivery. (1) Ampacities are in accordance with Table 310-73 of the NEC for triplexed or three single conductor copper cable in isolated conduit in air, based on a conductor temperature of 105˚C (221˚F) and an ambient air temperature of 40˚C (104˚F). (2) Ampacities are in accordance with Table 310-77 of the NEC for triplexed or three single conductor copper cable in underground ducts (three conductors per duct), based on a conductor temperature of 105˚C (221˚F) and an ambient earth temperature of 20˚C (68˚F), electrical duct arrangement per Figure 310.60 Detail 1, 100% load factor, and earth thermal resistance (rho) of 90. (3) Ampacities are based on single conductor Type MV-105 sizes #1/0 AWG and larger in an uncovered tray in accordance with Section 392-13(B) of the NEC at an ambient air temperature of 40˚C (104˚F); the ampacities are based on 75% of the values per Table 310-69. For cable trays with unventilated covers for more than 6 feet, the ampacities shall not exceed 95% of the values shown above. (4) Based on nominal cable diameters, three single cables in the duct (PVC Schedule 40) with no ground wire and a maximum of 40% fill. Jam ratio has been considered, but it should be checked for individual installations. ¥100% insulation level is available upon request Dimensions and weights are nominal; subject to industry tolerances. Note: The NESC Lightning bolt symbol is on all Uniblend® constructions.

Phone: 888-593-3355 www.generalcable.com


SPEC 6450

January, 2008

Uniblend

®

EPR/Copper Tape Shield with Overall PVC Jacket, Medium-Voltage Power, Shielded 15kV, UL Type MV-105, 133% Ins. Level, 220 Mils, Three Conductor Applications (cont’d.):

• For use in direct burial if installed in a system with a ground conductor that is in close proximity, and conforms with NEC 250.4 (A) (5)

Features:

Product Construction Conductor:

Print:

• GENERAL CABLE® (DI) (MO/YR OF MANUFACTURE) LIGHTNING BOLT SYMBOL 3/C SIZE (AWG OR KCMIL) COMPACT CU UNIBLEND® (INSULATION THICKNESS) EPR TYPE MV-105 (VOLTAGE) KV% INSULATION LEVEL SUN RES FOR CT USE (UL) SEQUENTIAL FOOTAGE MARK

• 2 AWG thru 1000 kcmil annealed bare copper compact Class B strand

Extruded Strand Shield (ESS):

• Extruded thermoset semi-conducting stresscontrol layer over conductor

Options:

Insulation:

• PVC jacket colors other than black • Flame-retardant, Chlorinated Polyethylene (CPE) jacket • Low-Smoke, Zero-Halogen (LSZH) jacket • Jacketed singles • UniShield® singles • STRANDFILL® – blocked conductor. Tested in accordance with ICEA T-31-610 • 3 bare copper ground wires • Covered ground wires

• Ethylene Propylene Rubber (EPR) insulation, colored to contrast with the black conducting shield layers

Extruded Insulation Shield (EIS):

• Thermoset semi-conducting polymeric layer free stripping from insulation

Metallic Shield:

• 5 mil annealed copper tape with an overlap of 25%

Applications:

Grounding Conductor:

• Suited for use in a broad range of commercial, industrial and utility applications, where reliability is the major concern, space is limited and ease of installation is critical • In wet or dry locations when installed in accordance with NEC • In aerial, direct burial, conduit, open tray and underground duct installations

• 1 bare grounding conductor may be in contact with metallic shielding tape

Overall Jacket:

• Flame-retardant, moisture- and sunlight-resistant Polyvinyl Chloride (PVC)

CATALOG NUMBER

NOMINAL COND. CONDUCTOR SIZE DIAMETER (AWG/ kcmil) inCHES

• Rated at 105˚C • Excellent heat and moisture resistance • Outstanding corona resistance • Flexibility for easy handling • High dielectric strength • Low moisture absorption • Electrical stability under stress • Low dielectric loss • Chemical-resistant • Meets cold bend test at -35˚C

Compliances:

• National Electrical Code (NEC) • UL 1072 • ICEA S-93-639/NEMA WC74 • ICEA S-97-682 • AEIC CS8 • UL listed as Type MV-105 for use in accordance with NEC • UL 1685 (70,000 BTU/hr) • Meets EPA 40 CFR, Part 261 for leachable lead content per TCLP method • OSHA acceptable Optional Flame Tests: • IEEE 1202 (70,000 BTU/hr)/CSA FT4 • ICEA T-29-520 (210,000 BTU/hr)

Packaging:

• Material cut to length and shipped on non-returnable wood reels. Lengths in excess of 10,000 lbs. are provided on returnable steel reels that require a deposit • Extra charges apply for cuts less than 1000 ft., lagging, pulling eyes, paralleling and plexing

INSULATION NOMINAL NOMINAL CABLE AMPACITY DIAMETER GROUND OVERALL JKT INCHES THICKNESS COPPER WEIGHT CONDUIT UNDERGROUND DIRECT DIAMETER WEIGHT WIRE Min. MAX. (AWG) inCHES mm inCHES mm LBS/1000 FT kg/km LBS/1000 FT kg/km IN AIR (1) DUCT (2) BURIAL (3)

15kV ¥ , UL TYPE MV-105, 133% INS. LEVEL, 220 MILS, THREE CONDUCTOR 15493.440200 15493.445100* 15493.445200 15493.445400 15493.446000* 15493.446200 15493.446500 15493.447000* 15493.447500*

2 1/0 2/0 4/0 250 350 500 750 1000

0.27 0.34 0.38 0.48 0.53 0.62 0.74 0.91 1.06

0.710 0.780 0.820 0.920 0.970 1.070 1.190 1.370 1.520

0.800 0.865 0.905 1.005 1.060 1.155 1.275 1.460 1.610

6 4 4 3 2 2 1 1/0 2/0

0.110 0.110 0.110 0.110 0.110 0.110 0.140 0.140 0.140

2.79 2.79 2.79 2.79 2.79 2.79 3.56 3.56 3.56

2.04 2.20 2.30 2.52 2.66 2.94 3.21 3.61 3.99

51.82 55.88 58.42 64.01 67.56 74.68 81.53 91.69 101.35

2226 2811 3163 4203 4775 6182 7686 10978 13983

3313 4183 4707 6255 7106 9200 11438 16337 20810

913 1343 1609 2398 2812 3766 5244 7682 10124

1358 1998 2394 3567 4184 5604 7803 11431 15064

165 215 245 320 350 430 525 635 725

160 210 235 305 335 400 485 585 660

185 240 275 360 400 490 600 745 860

*Non-stock item, minimum runs apply. Please consult Customer Service for price and delivery. (1) Ampacities are in accordance with Table 310-75 of the NEC for three conductor copper cable in isolated conduit in air, based on a conductor temperature of 105˚C (221˚F) and an ambient air temperature of 40˚C (104˚F). (2) Ampacities are in accordance with Table 310-79 of the NEC for three conductor copper cable in underground ducts (three conductors per duct), based on a conductor temperature of 105˚C (221˚F) and an ambient earth temperature of 20˚C (68˚F), electrical duct arrangement per Figure 310.60 Detail 1, 100% load factor, and earth thermal resistance (rho) of 90. (3) Ampacities are based on single conductor Type MV-105 sizes #1/0 AWG and larger in an uncovered tray in accordance with Section 392-13(B) of the NEC at an ambient air temperature of 40˚C (104˚F); the ampacities are based on 75% of the values per Table 310-71. For cable trays with unventilated covers for more than 6 feet, the ampacities shall not exceed the values in NEC Table 310-75. ¥100% insulation level is available upon request Dimensions and weights are nominal; subject to industry tolerances. Note: a) All sizes are “FOR CT USE” b) The NESC Lightning bolt symbol is on all Uniblend® constructions

Phone: 888-593-3355 www.generalcable.com


SPEC 6475

January, 2009

Uniblend

®

EPR/Copper Tape Shield with Overall CPE Jacket, Medium-Voltage Power, Shielded 15kV, UL Type MV-105, 133% Ins. Level, 220 Mils, Three Conductor Features:

Product Construction Conductor:

Print:

• GENERAL CABLE® (DI) (MO/YR OF MANUFACTURE) LIGHTNING BOLT SYMBOL 3/C SIZE (AWG OR KCMIL) COMPACT CU UNIBLEND® CPE JKT (INSULATION THICKNESS) EPR TYPE MV-105 (VOLTAGE) KV% INSULATION LEVEL SUN RES FOR CT USE (UL) Sequential Footage Mark

• 2 AWG thru 1000 kcmil annealed bare copper compact Class B strand

Extruded Strand Shield (ESS):

• Extruded thermoset semi-conducting stresscontrol layer over conductor

Options:

Insulation:

• PVC jacket • Low-Smoke, Zero-Halogen (LSZH) jacket • Jacketed singles • UniShield® singles • STRANDFILL® – blocked conductor. Tested in accordance with ICEA T-31-610 • 3 bare copper ground wires • Covered ground wires

• Ethylene Propylene Rubber (EPR) insulation, colored to contrast with the black conducting shield layers

Extruded Insulation Shield (EIS):

• Thermoset semi-conducting polymeric layer free stripping from insulation

Metallic Shield:

Applications:

• 5 mil annealed copper tape with an overlap of 25%

• Suited for use in a broad range of commercial, industrial and utility applications, where reliability is the major concern, space is limited and ease of installation is critical • In wet or dry locations when installed in accordance with NEC • In aerial, direct burial, conduit, open tray and underground duct installations • For use in direct burial if installed in a system with a ground conductor that is in close proximity, and conforms with NEC 250.4 (A) (5)

Grounding Conductor:

• 1 bare grounding conductor may be in contact with metallic shielding tape

Overall Jacket:

• Flame-retardant, moisture- and sunlight-resistant Chlorinated Polyethylene (CPE)

CATALOG NUMBER

• Rated at 105˚C • Excellent heat and moisture resistance • Outstanding corona resistance • Flexibility for easy handling • High dielectric strength • Low moisture absorption • Electrical stability under stress • Low dielectric loss • Chemical-resistant • Meets cold bend test at -35˚C

Compliances:

• National Electrical Code (NEC) • UL 1072 • ICEA S-93-639/NEMA WC74 • ICEA S-97-682 • AEIC CS8 • UL listed as Type MV-105 for use in accordance with NEC • UL 1685 (70,000 BTU/hr) • OSHA acceptable Optional Flame Tests: • IEEE 1202 (70,000 BTU/hr)/CSA FT4 • ICEA T-29-520 (210,000 BTU/hr)

Packaging:

• Material cut to length and shipped on non-returnable wood reels. Lengths in excess of 10,000 lbs. are provided on returnable steel reels that require a deposit • Extra charges apply for cuts less than 1000 ft., lagging, pulling eyes, paralleling and plexing

NOMINAL INSULATION NOMINAL COND. CONDUCTOR NOMINAL CABLE AMPACITY DIAMETER GROUND OVERALL JKT SIZE DIAMETER INCHES COPPER WEIGHT CONDUIT UNDERGROUND DIRECT DIAMETER WEIGHT (AWG/ WIRE THICKNESS kcmil) inCHES Min. MAX. (AWG) inCHES mm inCHES mm LBS/1000 FT kg/km LBS/1000 FT kg/km IN AIR (1) DUCT (2) BURIAL (3)

15kV ¥ , UL TYPE MV-105, 133% INS. LEVEL, 220 MILS, THREE CONDUCTOR 15593.440200* 15593.445100* 15593.445200* 15593.445400* 15593.446000* 15593.446200* 15593.446500* 15593.447000* 15593.447500*

2 1/0 2/0 4/0 250 350 500 750 1000

0.27 0.34 0.38 0.48 0.53 0.62 0.74 0.91 1.06

0.710 0.780 0.820 0.920 0.970 1.070 1.190 1.370 1.520

0.800 0.865 0.905 1.005 1.060 1.155 1.275 1.460 1.610

6 4 4 3 2 2 1 1/0 2/0

0.110 0.110 0.110 0.110 0.110 0.110 0.140 0.140 0.140

2.79 2.79 2.79 2.79 2.79 2.79 3.56 3.56 3.56

2.04 51.82 2.20 55.88 2.30 58.42 2.52 64.01 2.66 67.56 2.94 74.68 3.21 81.53 3.61 91.69 3.99 101.35

2226 2811 3163 4203 4775 6182 7686 10978 13938

3313 4183 4707 6255 7106 9200 11438 16337 20810

913 1343 1609 2398 2812 3766 5244 7682 10124

1358 1998 2394 3567 4184 5604 7803 11431 15064

165 215 245 320 350 430 525 635 725

160 210 235 305 335 400 485 585 660

185 240 275 360 400 490 600 745 860

*Non-stock item, minimum runs apply. Please consult Customer Service for price and delivery. (1) Ampacities are in accordance with Table 310-75 of the NEC for three conductor copper cable in isolated conduit in air, based on a conductor temperature of 105˚C (221˚F) and an ambient air temperature of 40˚C (104˚F). (2) Ampacities are in accordance with Table 310-79 of the NEC for three conductor copper cable in underground ducts (three conductors per duct), based on a conductor temperature of 105˚C (221˚F) and an ambient earth temperature of 20˚C (68˚F), electrical duct arrangement per Figure 310.60 Detail 1, 100% load factor, and earth thermal resistance (rho) of 90. (3) Ampacities are based on single conductor Type MV-105 sizes #1/0 AWG and larger in an uncovered tray in accordance with Section 392-13 (B) of the NEC at an ambient air temperature of 40˚C (104˚F); the ampacities are based on 75% of the values per Table 310-71. For cable trays with unventilated covers for more than 6 feet, the ampacities shall not exceed the values in NEC Table 310-75. ¥100% insulation level is available upon request Dimensions and weights are nominal; subject to industry tolerances. Note: a) Sizes smaller than 4/0 AWG do not include “FOR CT USE” b) The NESC Lightning bolt symbol is on all Uniblend® constructions

Phone: 888-593-3355 www.generalcable.com


SPEC 6480

May, 2008

GenFree Uniblend ™

®

EPR/Copper Tape Shield with Overall LSZH Jacket, Medium-Voltage Power, Shielded 15kV, UL Type MV-105, 133% Ins. Level, 220 Mils, Three Conductor Features:

Product Construction Conductor:

Print:

• GENERAL CABLE® (DI) (MO/YR OF MANUFACTURE) LIGHTNING BOLT SYMBOL 3/C SIZE (AWG OR KCMIL) COMPACT CU GENFREE™ UNIBLEND® LSZH JKT (INSULATION THICKNESS) EPR TYPE MV-105 (VOLTAGE) KV% INSULATION LEVEL SUN RES FOR CT USE (UL) SEQUENTIAL FOOTAGE MARK

• 2 AWG thru 1000 kcmil annealed bare copper compact Class B strand

Extruded Strand Shield (ESS):

• Extruded thermoset semi-conducting stresscontrol layer over conductor

Options:

Insulation:

• STRANDFILL® – blocked conductor. Tested in accordance with ICEA T-31-610 • 3 bare copper ground wires • Covered ground wires

• Ethylene Propylene Rubber (EPR) insulation, colored to contrast with the black conducting shield layers

Extruded Insulation Shield (EIS):

• Thermoset semi-conducting polymeric layer free stripping from insulation

Applications:

• Suited for use in a broad range of commercial, industrial and utility applications, where reliability is the major concern, space is limited and ease of installation is critical • In wet or dry locations when installed in accordance with NEC • In aerial, direct burial, conduit, open tray and underground duct installations • For use in direct burial if installed in a system with a ground conductor that is in close proximity, and conforms with NEC 250.4 (A) (5)

Metallic Shield:

• 5 mil annealed copper tape with an overlap of 25%

Grounding Conductor:

• 1 bare grounding conductor may be in contact with metallic shielding tape

Overall Jacket:

• Flame-retardant, moisture- and sunlight-resistant, Low-Smoke, Zero-Halogen Polyolefin (LSZH)

CATALOG NUMBER

• Rated at 105˚C • Excellent heat and moisture resistance • Outstanding corona resistance • Flexibility for easy handling • High dielectric strength • Low moisture absorption • Electrical stability under stress • Low dielectric loss • Chemical-resistant • Meets cold bend test at -35˚C

Compliances:

• National Electrical Code (NEC) • UL 1072 • ICEA S-93-639/NEMA WC74 • ICEA S-97-682 • ICEA T-33-655 • AEIC CS8 • UL listed as Type MV-105 for use in accordance with NEC • UL 1685 (70,000 BTU/hr) • OSHA acceptable Optional Flame Tests: • IEEE 1202 (70,000 BTU/hr)/CSA FT4 • ICEA T-29-520 (210,000 BTU/hr)

Packaging:

• Material cut to length and shipped on non-returnable wood reels. Lengths in excess of 10,000 lbs. are provided on returnable steel reels that require a deposit • Extra charges apply for cuts less than 1000 ft., lagging, pulling eyes, paralleling and plexing

NOMINAL INSULATION NOMINAL COND. CONDUCTOR NOMINAL CABLE AMPACITY DIAMETER GROUND OVERALL JKT SIZE DIAMETER INCHES COPPER WEIGHT CONDUIT UNDERGROUND DIRECT DIAMETER WEIGHT (AWG/ WIRE THICKNESS kcmil) inCHES Min. MAX. (AWG) inCHES mm inCHES mm LBS/1000 FT kg/km LBS/1000 FT kg/km IN AIR (1) DUCT (2) BURIAL (3)

15kV ¥ , UL TYPE MV-105, 133% INS. LEVEL, 220 MILS, THREE CONDUCTOR 15793.440200* 15793.445100* 15793.445200* 15793.445400* 15793.446000* 15793.446200* 15793.446500* 15793.447000* 15793.447500*

2 1/0 2/0 4/0 250 350 500 750 1000

0.27 0.34 0.38 0.48 0.53 0.62 0.74 0.91 1.06

0.710 0.780 0.820 0.920 0.970 1.070 1.190 1.370 1.520

0.800 0.865 0.905 1.005 1.060 1.155 1.275 1.460 1.610

6 4 4 3 2 2 1 1/0 2/0

0.110 0.110 0.110 0.110 0.110 0.110 0.140 0.140 0.140

2.79 2.79 2.79 2.79 2.79 2.79 3.56 3.56 3.56

2.04 51.82 2.20 55.88 2.30 58.42 2.52 64.01 2.66 67.56 2.94 74.68 3.21 81.53 3.61 91.69 3.99 101.35

2226 2811 3163 4203 4775 6182 7686 10978 13938

3313 4183 4707 6255 7106 9200 11438 16337 20810

913 1343 1609 2398 2812 3766 5244 7682 10124

1358 1998 2394 3567 4184 5604 7803 11431 15064

165 215 245 320 350 430 525 635 725

160 210 235 305 335 400 485 585 660

185 240 275 360 400 490 600 745 860

*Non-stock item, minimum runs apply. Please consult Customer Service for price and delivery. (1) Ampacities are in accordance with Table 310-75 of the NEC for three conductor copper cable in isolated conduit in air, based on a conductor temperature of 105˚C (221˚F) and an ambient air temperature of 40˚C (104˚F). (2) Ampacities are in accordance with Table 310-79 of the NEC for three conductor copper cable in underground ducts (three conductors per duct), based on a conductor temperature of 105˚C (221˚F) and an ambient earth temperature of 20˚C (68˚F), electrical duct arrangement per Figure 310.60 Detail 1, 100% load factor, and earth thermal resistance (rho) of 90. (3) Ampacities are based on single conductor Type MV-105 sizes #1/0 AWG and larger in an uncovered tray in accordance with Section 392-13 (B) of the NEC at an ambient air temperature of 40˚C (104˚F); the ampacities are based on 75% of the values per Table 310-71. For cable trays with unventilated covers for more than 6 feet, the ampacities shall not exceed the values in NEC Table 310-75. ¥100% insulation level is available upon request Dimensions and weights are nominal; subject to industry tolerances. Note: a) Sizes smaller than 1/0 AWG do not include “FOR CT USE” b) The NESC Lightning bolt symbol is on all Uniblend® constructions

Phone: 888-593-3355 www.generalcable.com


SPEC 6500

January, 2009

UniShield

®

EPR/Copper Wire Shield/CPE, Medium-Voltage Power, Shielded 25kV and 35kV, UL Type MV-105, 133% / 100% Ins. Levels, 345 Mils Features (cont’d.):

Product Construction Conductor:

Options:

• 1/0 AWG thru 1000 kcmil annealed bare copper compact Class B strand

• 25kV 100% Insulation Level • 35kV 133% Insulation Level

Applications:

• Installed in a broad range of commercial, industrial and utility projects such as pulp and paper mills, petrochemical plants, steel mills, textile mills, water and sewage treatment facilities, environmental protection systems, railroads, mines and fossil fuel utility generating stations • Suitable for use in wet or dry locations when installed in accordance with NEC • For use in aerial, conduit, open tray and underground duct installations • For use in direct burial if installed in a system with a ground conductor that is in close proximity, and conforms with NEC 250.4 (A) (5)

Extruded Strand Shield (ESS):

• Extruded thermoset semi-conducting stresscontrol layer over conductor

Insulation:

• Ethylene Propylene Rubber (EPR) insulation colored to contrast with black conducting shield layers

Composite Insulation Shield and Jacket:

• Six corrugated copper drain wires embedded in composite layers of semi-conducting thermoset copolymer and semi-conducting black flameretardant Chlorinated Polyethylene (CPE)

Print:

Features:

• Rated at 105˚C • Reduced conductor size and shield system provide the smallest premium medium-voltage shielded power cable with full insulation • Smaller outside dimensions reduce the size of duct needed or increase the ampacity per duct • All features contribute to faster and easier installation • Superior cold bend and cold impact performance

• GENERAL (DI) (MO/YR OF MANUFACTURE) LIGHTNING BOLT SYMBOL 1/C SIZE (AWG OR KCMIL) COMPACT CU UNISHIELD® (INSULATION THICKNESS) EPR DRTP SEMI-CON CPE JKT TYPE MV-105 (VOLTAGE) KV% INSULATION LEVEL SUN RES FOR CT USE (UL) Sequential Footage Mark

CABLE®

* Sizes smaller than 1/0 AWG do not include “FOR CT USE”

CATALOG NUMBER

• Stable and constant shield short circuit performance • Excellent heat and moisture resistance • Outstanding corona resistance • Flexibility for easy handling • High dielectric strength • Low dielectric loss • Low moisture absorption • Electrical stability under stress • Chemical-resistant • Sunlight-resistant • Meets cold bend test at -55˚C

NOMINAL COND. CONDUCTOR SIZE DIAMETER (AWG/ kcmil) inCHES

INSULATION DIAMETER INCHES Min. MAX.

Compliances:

• National Electrical Code (NEC) • UL 1072 • ICEA S-93-639/NEMA WC74 • ICEA S-97-682 • AEIC CS8 • UL listed as Type MV-105 for use in accordance with NEC • UL 1685 (Sizes 1/0 AWG and larger) UL Flame Exposure Test • Sizes 1/0 AWG and larger are listed and marked “Sunlight-Resistant FOR CT USE” in accordance with NEC • IEEE 1202 (70,000 BTU/hr)/CSA FT4 • Meets EPA 40 CFR, Part 2671 for leachable lead content per TCLP method • OSHA acceptable Optional Flame Tests: • ICEA T-29-520 (210,000 BTU/hr)

Packaging:

• Material cut to length and shipped on nonreturnable wood reels. Lengths in excess of 10,000 lbs. are provided on returnable steel reels that require a deposit • Extra charges apply for cuts less than 1000 ft., lagging, pulling eyes, paralleling and triplexing

DRAIN NOMINAL CABLE AMPACITY WIRE COPPER WEIGHT CONDUIT IN UNDERGROUND DIRECT CONDUlT DIAMETER WEIGHT SIZE (AWG) inCHES mm LBS/1000 FT kg/km LBS/1000 FT kg/km AIR (1) DUCT (2) BURIAL (3) SIZING (4)

25kV ¥ & 35kV ¥¥ , UL TYPE MV-105, 133% / 100% INS. LEVEL, 345 MILS 19261.685100* 1/0 19261.685200* 2/0 19261.685300* 3/0 19261.685400* 4/0 19261.686000* 250 19261.686200* 350 19261.686500* 500 19261.687000* 750 19261.687500* 1000

0.34 0.38 0.43 0.48 0.53 0.62 0.74 0.91 1.06

1.020 1.060 1.105 1.160 1.210 1.310 1.430 1.610 1.760

1.120 1.160 1.205 1.260 1.315 1.410 1.530 1.710 1.865

17 17 17 17 16 16 16 16 16

1.29 1.36 1.41 1.43 1.51 1.60 1.74 1.95 2.11

32.77 34.54 35.81 36.32 38.35 40.64 44.20 49.78 53.59

1014 1163 1310 1442 1645 2024 2608 3596 4513

1509 1731 1949 2146 2448 3012 3881 5351 6715

367 452 559 694 824 1133 1596 2368 3138

546 672 832 1033 1226 1685 2374 3523 4669

215 255 290 330 365 440 535 655 755

215 245 275 315 345 415 500 610 690

295 335 380 435 475 575 700 865 1005

4 5 5 5 5 5 6 6 8

*Non-stock item, minimum runs apply. Please consult Customer Service for price and delivery. (1) Ampacities are in accordance with Table 310-73 of the NEC for triplexed or three single conductor copper cable in isolated conduit in air, based on a conductor temperature of 105˚C (221˚F) and an ambient air temperature of 40˚C (104˚F). (2) Ampacities are in accordance with Table 310-77 of the NEC for triplexed or three single conductor copper cable in underground ducts (three conductors per duct), based on a conductor temperature of 105˚C (221˚F) and an ambient earth temperature of 20˚C (68˚F), electrical duct arrangement per Figure 310.60 Detail 1, 100% load factor, and earth thermal resistance (rho) of 90. (3) Ampacities are in accordance with Table 310-81 of the NEC for single insulated copper conductors directly buried in earth, based on a conductor temperature of 105˚C (221˚F) and an ambient earth temperature of 20˚C (68˚F), arrangement per Figure 310.06 Detail 9, 100% load factor, and earth thermal resistance (rho) of 90. (4) Based on nominal cable diameters, three single cables in the duct (PVC Schedule 40) with no ground wire and a maximum of 40% fill. Jam ratio has been considered, but it should be checked for individual installations. ¥100% insulation level is available upon request ¥¥133% insulation level is available upon request Dimensions and weights are nominal; subject to industry tolerances. Note: a) Sizes smaller than 1/0 AWG do not include “FOR CT USE” b) The NESC Lightning bolt symbol is on all UniShield® constructions

Phone: 888-593-3355 www.generalcable.com


SPEC 6550

January, 2009

Uniblend

®

EPR/Copper Tape Shield/PVC, Medium-Voltage Power, Shielded 25kV and 35kV, UL Type MV-105, 133% / 100% Ins. Levels, 345 Mils Features:

Product Construction Conductor:

Print (cont’d.):

TYPE MV-105 (VOLTAGE) KV% INSULATION LEVEL SUN RES FOR CT USE (UL) Sequential Footage Mark

• 1/0 AWG thru 1000 kcmil annealed bare copper compact Class B strand

* Sizes smaller than 1/0 AWG do not include “FOR CT USE”

Extruded Strand Shield (ESS):

• Extruded thermoset semi-conducting stresscontrol layer over conductor

Options:

• PVC jacket colors other than black • Flame-retardant, Chlorinated Polyethylene (CPE) jacket • Low-Smoke, Zero-Halogen (LSZH) jacket • STRANDFILL® - blocked conductor. Tested in accordance with ICEA T-31-610 • 25kV 100% Insulation Level • 35kV 133% Insulation Level

Insulation:

• Ethylene Propylene Rubber (EPR) insulation, colored to contrast with the black conducting shield layers

Extruded Insulation Shield (EIS):

• Thermoset semi-conducting polymeric layer free stripping from insulation

Metallic Shield:

Applications:

• Superior performance in petrochemical plants, pulp and paper mills, sewage and water treatment plants, environmental protection systems, railroads, mines, utility power generating stations, steel mills, textile plants and other industrial threephase applications • For use in wet or dry locations when installed in accordance with NEC • For use in aerial, conduit, open tray and underground duct installations • For use in direct burial if installed in a system with a ground conductor that is in close proximity, and conforms with NEC 250.4 (A) (5)

• 5 mil annealed copper tape with an overlap of 25%

Jacket:

• Flame-retardant, moisture- and sunlight-resistant Polyvinyl Chloride (PVC)

Print:

• GENERAL CABLE® (DI) (MO/YR OF MANUFACTURE) LIGHTNING BOLT SYMBOL 1/C SIZE (AWG OR KCMIL) COMPACT CU UNIBLEND® (INSULATION THICKNESS) EPR

CATALOG NUMBER

• Rated at 105˚C • Excellent heat and moisture resistance • Excellent flame resistance • Outstanding corona resistance • Flexibility for easy handling • High dielectric strength • Low moisture absorption • Electrical stability under stress • Low dielectric loss • Chemical-resistant • Meets cold bend test at -35˚C

Compliances:

• National Electrical Code (NEC) • UL 1072 • ICEA S-93-639/NEMA WC74 • ICEA S-97-682 • AEIC CS8 • UL listed as Type MV-105 for use in accordance with NEC • UL 1685 (Sizes 1/0 AWG and larger) UL Flame Exposure Test • Sizes 1/0 AWG and larger are listed and marked “Sunlight-Resistant FOR CT USE” in accordance with NEC • IEEE 1202 (70,000 BTU/hr)/CSA FT4 • Meets EPA 40 CFR, Part 2671 for leachable lead content per TCLP method • OSHA acceptable Optional Flame Tests: • ICEA T-29-520 (210,000 BTU/hr)

Packaging:

• Material cut to length and shipped on non-returnable wood reels. Lengths in excess of 10,000 lbs. are provided on returnable steel reels that require a deposit • Extra charges apply for cuts less than 1000 ft., lagging, pulling eyes, paralleling and triplexing

NOMINAL INSULATION NOMINAL COND. CONDUCTOR NOMINAL CABLE AMPACITY JACKET SIZE DIAMETER DIAMETER INCHES THICKNESS COPPER WEIGHT CONDUIT UNDERGROUND DIRECT CONDUIT DIAMETER WEIGHT (AWG/ kcmil) INCHES Min. MAX. INCHES mm INCHES mm LBS/1000 FT kg/km LBS/1000 FT kg/km IN AIR (1) DUCT (2) BURIAL (3) SIZING (4)

25kV ¥ AND 35kV ¥¥ , UL TYPE MV-105, 133% / 100% INS. LEVELS, 345 MILS 17061.135100 17061.135200* 17061.135300* 17061.135400 17061.136000* 17061.136200 17061.136500 17061.137000* 17061.137500*

1/0 2/0 3/0 4/0 250 350 500 750 1000

0.34 0.38 0.43 0.48 0.53 0.62 0.74 0.91 1.06

1.020 1.060 1.105 1.160 1.210 1.310 1.430 1.610 1.760

1.115 1.160 1.205 1.260 1.315 1.410 1.530 1.710 1.865

0.080 0.080 0.080 0.080 0.080 0.080 0.080 0.110 0.110

2.03 2.03 2.03 2.03 2.03 2.03 2.03 2.79 2.79

1.31 1.35 1.40 1.45 1.51 1.60 1.78 1.96 2.10

33.27 34.29 35.56 36.83 38.35 40.64 45.21 49.78 53.59

1090 1211 1360 1547 1712 2108 2783 3733 4651

1622 1802 2024 2302 2547 3137 4141 5555 6921

425 514 625 765 888 1206 1679 2467 3250

633 765 930 1138 1322 1794 2498 3670 4836

215 255 290 330 365 440 535 655 755

215 245 275 315 345 415 500 610 690

295 335 380 435 475 575 700 865 1005

5 5 5 5 5 5 6 6 8

*Non-stock item, minimum runs apply. Please consult Customer Service for price and delivery. (1) Ampacities are in accordance with Table 310-73 of the NEC for triplexed or three single conductor copper cable in isolated conduit in air, based on a conductor temperature of 105˚C (221˚F) and an ambient air temperature of 40˚C (104˚F). (2) Ampacities are in accordance with Table 310-77 of the NEC for triplexed or three single conductor copper cable in underground ducts (three conductors per duct), based on a conductor temperature of 105˚C (221˚F) and an ambient earth temperature of 20˚C (68˚F), electrical duct arrangement per Figure 310.60 Detail 1, 100% load factor, and earth thermal resistance (rho) of 90. (3) Ampacities are in accordance with Table 310-81 of the NEC for single insulated copper conductors directly buried in earth, based on a conductor temperature of 105˚C (221˚F) and an ambient earth temperature of 20˚C (68˚F), arrangement per Figure 310.06 Detail 9, 100% load factor, and earth thermal resistance (rho) of 90. (4) Based on nominal cable diameters, three single cables in the duct (PVC Schedule 40) with no ground wire and a maximum of 40% fill. Jam ratio should be checked for individual installations. ¥100% insulation level is available upon request ¥¥133% insulation level is available upon request Dimensions and weights are nominal; subject to industry tolerances. Note: a) Sizes smaller than 1/0 AWG do not include “FOR CT USE” b) The NESC Lightning bolt symbol is on all Uniblend® constructions

Phone: 888-593-3355 www.generalcable.com


SPEC 6575

January, 2009

Uniblend

®

EPR/Copper Tape Shield/CPE, Medium-Voltage Power, Shielded 25kV and 35kV, UL Type MV-105, 133% / 100% Ins. Levels, 345 Mils Features:

Product Construction Conductor:

Print (cont’d.):

• 1/0 AWG thru 1000 kcmil annealed bare copper compact Class B strand

Extruded Strand Shield (ESS):

• Extruded thermoset semi-conducting stresscontrol layer over conductor

Insulation:

• Ethylene Propylene Rubber (EPR) insulation, colored to contrast with the black conducting shield layers

Extruded Insulation Shield (EIS):

• Thermoset semi-conducting polymeric layer free stripping from insulation

Metallic Shield:

• 5 mil annealed copper tape with an overlap of 25%

Jacket:

• Flame-retardant, moisture- and sunlight-resistant Chlorinated Polyethylene (CPE)

Print:

• GENERAL CABLE® (DI) (MO/YR OF MANUFACTURE) LIGHTNING BOLT SYMBOL 1/C SIZE (AWG OR KCMIL) COMPACT CU UNIBLEND® CPE JKT (INSULATION THICKNESS)

CATALOG NUMBER

NOMINAL INSULATION COND. CONDUCTOR SIZE DIAMETER DIAMETER INCHES (AWG/ kcmil) INCHES Min. MAX.

EPR TYPE MV-105 (VOLTAGE) KV% INSULATION LEVEL SUN RES FOR CT USE (UL) Sequential Footage Mark

* Sizes smaller than 1/0 AWG do not include “FOR CT USE”

Options:

• PVC jacket • Low-Smoke, Zero-Halogen (LSZH) jacket • STRANDFILL® - blocked conductor. Tested in accordance with ICEA T-31-610 • 25kV 100% Insulation Level • 35kV 133% Insulation Level

Applications:

• Superior performance in petrochemical plants, pulp and paper mills, sewage and water treatment plants, environmental protection systems, railroads, mines, utility power generating stations, steel mills, textile plants and other industrial threephase applications • For use in wet or dry locations when installed in accordance with NEC • For use in aerial, conduit, open tray and underground duct installations • For use in direct burial if installed in a system with a ground conductor that is in close proximity, and conforms with NEC 250.4 (A) (5)

• Rated at 105˚C • Excellent heat and moisture resistance • Excellent flame resistance • Outstanding corona resistance • Flexibility for easy handling • High dielectric strength • Low moisture absorption • Electrical stability under stress • Low dielectric loss • Chemical-resistant • Meets cold bend test at -35˚C

Compliances:

• National Electrical Code (NEC) • UL 1072 • ICEA S-93-639/NEMA WC74 • ICEA S-97-682 • AEIC CS8 • UL listed as Type MV-105 for use in accordance with NEC • UL 1685 (Sizes 1/0 AWG and larger) UL Flame Exposure Test • Sizes 1/0 AWG and larger are listed and marked “Sunlight-Resistant FOR CT USE” in accordance with NEC • IEEE 1202 (70,000 BTU/hr)/CSA FT4 • Meets EPA 40 CFR, Part 2671 for leachable lead content per TCLP method • OSHA acceptable Optional Flame Tests: • ICEA T-29-520 (210,000 BTU/hr)

Packaging:

• Material cut to length and shipped on non-returnable wood reels. Lengths in excess of 10,000 lbs. are provided on returnable steel reels that require a deposit • Extra charges apply for cuts less than 1000 ft., lagging, pulling eyes, paralleling and triplexing

NOMINAL NOMINAL CABLE AMPACITY JACKET CONDUIT THICKNESS COPPER WEIGHT CONDUIT UNDERGROUND DIRECT SIZING DIAMETER WEIGHT (4) INCHES INCHES mm LBS/1000 FT kg/km LBS/1000 FT kg/km IN AIR (1) DUCT (2) BURIAL (3) (INCHES)

25kV ¥ AND 35kV ¥¥ , UL TYPE MV-105, 133% / 100% INS. LEVELS, 345 MILS 17161.135100* 17161.135200* 17161.135300* 17161.135400* 17161.136000* 17161.136200* 17161.136500* 17161.137000* 17161.137500*

1/0 2/0 3/0 4/0 250 350 500 750 1000

0.340 0.380 0.430 0.480 0.530 0.630 0.740 0.910 1.060

1.020 1.060 1.105 1.160 1.210 1.310 1.430 1.610 1.760

1.120 1.160 1.205 1.260 1.315 1.410 1.530 1.710 1.865

0.080 0.080 0.080 0.080 0.080 0.080 0.080 0.110 0.110

1.31 1.35 1.40 1.45 1.51 1.60 1.78 1.96 2.10

33.27 34.29 35.56 36.83 38.35 40.64 45.21 49.78 53.59

1066 1187 1335 1516 1681 2075 2644 3687 4603

1586 1766 1986 2256 2501 3088 3934 5486 6849

425 514 625 765 888 1206 1679 2467 3250

633 765 930 1138 1322 1794 2498 3670 4836

215 255 290 330 365 440 535 655 755

215 245 275 315 345 415 500 610 690

295 335 380 435 475 575 700 865 1005

5 5 5 5 5 5 6 6 8

*Non-stock item, minimum runs apply. Please consult Customer Service for price and delivery. (1) Ampacities are in accordance with Table 310-73 of the NEC for triplexed or three single conductor copper cable in isolated conduit in air, based on a conductor temperature of 105˚C (221˚F) and an ambient air temperature of 40˚C (104˚F). (2) Ampacities are in accordance with Table 310-77 of the NEC for triplexed or three single conductor copper cable in underground ducts (three conductors per duct), based on a conductor temperature of 105˚C (221˚F) and an ambient earth temperature of 20˚C (68˚F), electrical duct arrangement per Figure 310.60 Detail 1, 100% load factor, and earth thermal resistance (rho) of 90. (3) Ampacities are in accordance with Table 310-81 of the NEC for single insulated copper conductors directly buried in earth, based on a conductor temperature of 105˚C (221˚F) and an ambient earth temperature of 20˚C (68˚F), arrangement per Figure 310.06 Detail 9, 100% load factor, and earth thermal resistance (rho) of 90. (4) Based on nominal cable diameters, three single cables in the duct with no ground wire and a maximum of 40% fill. Jam ratio should be checked for individual installations. ¥100% insulation level is available upon request ¥¥133% insulation level is available upon request Dimensions and weights are nominal; subject to industry tolerances. Note: a) Sizes smaller than 1/0 AWG do not include “FOR CT USE” b) The NESC Lightning bolt symbol is on all Uniblend® constructions

Phone: 888-593-3355 www.generalcable.com


SPEC 6580

January, 2009

GenFree Uniblend ™

®

EPR/Copper Tape Shield/LSZH, Medium-Voltage Power, Shielded 25kV and 35kV, UL Type MV-105, 133% / 100% Ins. Levels, 345 Mils Features:

Product Construction Conductor:

Print:

• GENERAL CABLE® (DI) (MO/YR OF MANUFACTURE) LIGHTNING BOLT SYMBOL 1/C SIZE (AWG OR KCMIL) COMPACT CU GENFREE™ UNIBLEND® LSZH JKT (INSULATION THICKNESS) EPR TYPE MV-105 (VOLTAGE) KV% INSULATION LEVEL SUN RES FOR CT USE (UL) Sequential Footage Mark

• 1/0 AWG thru 1000 kcmil annealed bare copper compact Class B strand

Extruded Strand Shield (ESS):

• Extruded thermoset semi-conducting stresscontrol layer over conductor

* Sizes smaller than 1/0 AWG do not include “FOR CT USE”

Insulation:

• Ethylene Propylene Rubber (EPR) insulation, colored to contrast with the black conducting shield layers

Options:

• STRANDFILL® - blocked conductor. Tested in accordance with ICEA T-31-610 • 25kV 100% Insulation Level • 35kV 133% Insulation Level

Extruded Insulation Shield (EIS):

• Thermoset semi-conducting polymeric layer free stripping from insulation

Metallic Shield:

Applications:

• Superior performance in petrochemical plants, pulp and paper mills, sewage and water treatment plants, environmental protection systems, railroads, mines, utility power generating stations, steel mills, textile plants and other industrial threephase applications • For use in wet or dry locations when installed in accordance with NEC • For use in aerial, conduit, open tray and underground duct installations • For use in direct burial if installed in a system with a ground conductor that is in close proximity, and conforms with NEC 250.4 (A) (5)

• 5 mil annealed copper tape with an overlap of 25%

Jacket:

• Flame-retardant, moisture- and sunlight-resistant, Low-Smoke, Zero-Halogen Polyolefin (LSZH)

CATALOG NUMBER

• Rated at 105˚C • Excellent heat and moisture resistance • Excellent flame resistance • Outstanding corona resistance • Flexibility for easy handling • High dielectric strength • Low moisture absorption • Electrical stability under stress • Low dielectric loss • Chemical-resistant • Meets cold bend test at -35˚C

Compliances:

• National Electrical Code (NEC) • UL 1072 • ICEA S-93-639/NEMA WC74 • ICEA S-97-682 • AEIC CS8 • UL listed as Type MV-105 for use in accordance with NEC • UL 1685 (Sizes 1/0 AWG and larger) UL Flame Exposure Test • Sizes 1/0 AWG and larger are listed and marked “Sunlight-Resistant FOR CT USE” in accordance with NEC • IEEE 1202 (70,000 BTU/hr)/CSA FT4 • Meets EPA 40 CFR, Part 2671 for leachable lead content per TCLP method • OSHA acceptable Optional Flame Tests: • ICEA T-29-520 (210,000 BTU/hr)

Packaging:

• Material cut to length and shipped on non-returnable wood reels. Lengths in excess of 10,000 lbs. are provided on returnable steel reels that require a deposit • Extra charges apply for cuts less than 1000 ft., lagging, pulling eyes, paralleling and triplexing

NOMINAL INSULATION NOMINAL COND. CONDUCTOR NOMINAL CABLE AMPACITY JACKET SIZE DIAMETER DIAMETER CONDUIT INCHES THICKNESS COPPER WEIGHT CONDUIT UNDERGROUND DIRECT SIZING DIAMETER WEIGHT (AWG/ (4) kcmil) INCHES Min. MAX. INCHES mm INCHES mm LBS/1000 FT kg/km LBS/1000 FT kg/km IN AIR (1) DUCT (2) BURIAL (3) (INCHES)

25kV ¥ AND 35kV ¥¥ , UL TYPE MV-105, 133% / 100% INS. LEVELS, 345 MILS 17261.135100* 17261.135200* 17261.135300* 17261.135400* 17261.136000* 17261.136200* 17261.136500* 17261.137000* 17261.137500*

1/0 2/0 3/0 4/0 250 350 500 750 1000

0.34 0.38 0.43 0.48 0.53 0.62 0.74 0.91 1.06

1.020 1.060 1.105 1.160 1.210 1.310 1.430 1.610 1.760

1.115 1.160 1.205 1.260 1.315 1.410 1.530 1.710 1.865

0.080 0.080 0.080 0.080 0.080 0.080 0.080 0.110 0.110

2.03 2.03 2.03 2.03 2.03 2.03 2.03 2.79 2.79

1.31 1.35 1.40 1.45 1.51 1.60 1.78 1.96 2.10

33.27 34.29 35.56 36.83 38.35 40.64 45.21 49.78 53.59

1090 1211 1360 1547 1712 2108 2783 3733 4651

1622 1802 2024 2302 2547 3137 4141 5555 6921

425 514 625 765 888 1206 1679 2467 3250

633 765 930 1138 1322 1794 2498 3670 4836

215 255 290 330 365 440 535 655 755

215 245 275 315 345 415 500 610 690

295 335 380 435 475 575 700 865 1005

5 5 5 5 5 5 6 6 8

*Non-stock item, minimum runs apply. Please consult Customer Service for price and delivery. (1) Ampacities are in accordance with Table 310-73 of the NEC for triplexed or three single conductor copper cable in isolated conduit in air, based on a conductor temperature of 105˚C (221˚F) and an ambient air temperature of 40˚C (104˚F). (2) Ampacities are in accordance with Table 310-77 of the NEC for triplexed or three single conductor copper cable in underground ducts (three conductors per duct), based on a conductor temperature of 105˚C (221˚F) and an ambient earth temperature of 20˚C (68˚F), electrical duct arrangement per Figure 310.60 Detail 1, 100% load factor, and earth thermal resistance (rho) of 90. (3) Ampacities are in accordance with Table 310-81 of the NEC for single insulated copper conductors directly buried in earth, based on a conductor temperature of 105˚C (221˚F) and an ambient earth temperature of 20˚C (68˚F), arrangement per Figure 310.06 Detail 9, 100% load factor, and earth thermal resistance (rho) of 90. (4) Based on nominal cable diameters, three single cables in the duct (PVC Schedule 40) with no ground wire and a maximum of 40% fill. Jam ratio should be checked for individual installations. ¥100% insulation level is available upon request ¥¥133% insulation level is available upon request Dimensions and weights are nominal; subject to industry tolerances. Note: a) Sizes smaller than 1/0 AWG do not include “FOR CT USE” b) The NESC Lightning bolt symbol is on all Uniblend® constructions

Phone: 888-593-3355 www.generalcable.com


SPEC 6600

January, 2008

Uniblend

®

EPR/Copper Tape Shield with Overall PVC Jacket, Medium-Voltage Power, Shielded 25kV and 35kV, UL Type MV-105, 133% / 100% Ins. Levels, 345 Mils, Three Conductor Features:

Product Construction Conductor:

• 1/0 AWG thru 750 kcmil annealed bare copper compact Class B strand

Extruded Strand Shield (ESS):

• Extruded thermoset semi-conducting stress control layer over conductor

• GENERAL CABLE® (DI) (MO/YR OF MANUFACTURE) LIGHTNING BOLT SYMBOL 3/C SIZE (AWG OR KCMIL) COMPACT CU UNIBLEND® (INSULATION THICKNESS) EPR TYPE MV-105 (VOLTAGE) KV% INSULATION LEVEL SUN RES FOR CT USE (UL) SEQUENTIAL FOOTAGE MARK

Options:

Insulation:

• Ethylene Propylene Rubber (EPR) insulation colored to contrast with black conducting shield layers

Extruded Insulation Shield (EIS):

• Thermoset semi-conducting polymeric layer free stripping from insulation

Metallic Shield:

• 5 mil annealed copper tape with an overlap of 25%

Grounding Conductor:

• 1 bare grounding conductor may be in contact with metallic shielding tape

Overall Jacket:

• Flame-retardant, moisture- and sunlight-resistant Polyvinyl Chloride (PVC)

CATALOG NUMBER

Print:

• PVC jacket colors other than black • Flame-retardant, Chlorinated Polyethylene (CPE) jacket • Low-Smoke, Zero-Halogen (LSZH) jacket • Jacketed singles • UniShield® singles • STRANDFILL® - blocked conductor. Tested in accordance with ICEA T-31-610 • 3 bare copper ground wires • Covered ground wires • 25kV 100% Insulation Level • 35kV 133% Insulation Level

Applications:

• Suited for use in a broad range of commercial, industrial and utility applications, where reliability is the major concern, space is limited and ease of installation is critical • Suitable for use in wet or dry locations when installed in accordance with NEC • In aerial, direct burial, conduit, open tray and underground duct installations

• Rated at 105˚C • Excellent heat and moisture resistance • Outstanding corona resistance • Flexibility for easy handling • High dielectric strength • Low moisture absorption • Electrical stability under stress • Low dielectric loss • Chemical-resistant • Meets cold bend test at -35˚C

Compliances:

• National Electrical Code (NEC) • UL 1072 • ICEA S-93-639/NEMA WC74 • ICEA S-97-682 • AEIC CS8 • UL listed as Type MV-105 for use in accordance with NEC • UL 1685 (70,000 BTU/hr) • Meets EPA 40 CFR, Part 2671 for leachable lead content per TCLP method • OSHA acceptable Optional Flame Tests: • IEEE 1202 (70,000 BTU/hr)/CSA FT4 • ICEA T-29-520 (210,000 BTU/hr)

Packaging:

• Material cut to length and shipped on nonreturnable wood reels. Lengths in excess of 10,000 lbs. are provided on returnable steel reels that require a deposit • Extra charges apply for cuts less than 1000 ft., lagging, pulling eyes, paralleling and triplexing

NOMINAL INSULATION NOMINAL COND. CONDUCTOR NOMINAL CABLE AMPACITY OVERALL JKT SIZE DIAMETER DIAMETER GROUND INCHES THICKNESS COPPER WEIGHT CONDUIT IN UNDERGROUND DIRECT DIAMETER WEIGHT (AWG/ WIRE kcmil) inCHES Min. MAX. (AWG) inCHES mm inCHES mm LBS/1000 FT kg/km LBS/1000 FT kg/km AIR (1) DUCT (2) BURIAL (3)

25kV ¥ AND 35kV ¥¥ , UL TYPE MV-105, 133% / 100% INS. LEVELS, 345 MILS, THREE CONDUCTOR 0.34 1.020 1.115 4 0.110 2.79 2.73 69.34 3672 5464 1410 2098 215 210 15493.485100* 1/0 0.38 1.060 1.160 4 0.110 2.79 2.81 71.37 4061 6042 1675 2492 245 235 15493.485200* 2/0 0.48 1.160 1.260 3 0.140 3.56 3.10 78.74 5313 7906 2465 3668 320 305 15493.485400* 4/0 0.53 1.210 1.315 2 0.140 3.56 3.21 81.53 6214 9246 2879 4284 350 335 15493.486000* 250 0.62 1.310 1.410 2 0.140 3.56 3.42 86.86 7138 10621 3834 5705 430 400 15493.486200* 350 0.74 1.430 1.530 1 0.140 3.56 3.68 93.47 9012 13410 5312 7904 525 485 15493.486500* 500 0.91 1.610 1.710 1/0 0.140 3.56 4.10 104.14 12030 17901 7750 11532 635 585 15493.487000* 750

255 290 375 410 495 590 720

*Non-stock item, minimum runs apply. Please consult Customer Service for price and delivery. (1) Ampacities are in accordance with Table 310-75 of the NEC for three conductor copper cable in isolated conduit in air, based on a conductor temperature of 105˚C (221˚F) and an ambient air temperature of 40˚C (104˚F). (2) Ampacities are in accordance with Table 310-79 of the NEC for three conductor copper cable in underground ducts (three conductors per duct), based on a conductor temperature of 105˚C (221˚F) and an ambient earth temperature of 20˚C (68˚F), electrical duct arrangement per Figure 310.60 Detail 1, 100% load factor, and earth thermal resistance (rho) of 90. (3) Ampacities are in accordance with Table 310-83 of the NEC for single insulated copper conductors directly buried in earth, based on a conductor temperature of 105˚C (221˚F) and an ambient earth temperature of 20˚C (68˚F), arrangement per Figure 310.60 Detail 5, 100% load factor, and earth thermal resistance (rho) of 90. ¥100% insulation level is available upon request ¥¥133% insulation level is available upon request Dimensions and weights are nominal; subject to industry tolerances. Note: a) All sizes are “FOR CT USE” b) The NESC Lightning bolt symbol is on all Uniblend® constructions

Phone: 888-593-3355 www.generalcable.com


Industrial Cables

Date of Issue 01/09 Section 7

600V – 35kV Industrial Armored Cables SPECIFICATION NO.

PRODUCT DESCRIPTION

REVISION DATE

7050†

Duralox

XLPE/AIA/PVC, Control, Armored 600V, UL Type MC, Multi Conductor

Jan. 2009

7100†

Duralox®

XLPE/AIA/PVC, Power, Armored 600V, UL Type MC, Three and Four Conductor (8 AWG—4/0 AWG)

Jan. 2008

7150†

Duralox®

XLPE/AIA/PVC, Power, Armored 600V, UL Type MC, Three and Four Conductor (250 kcmil—1000 kcmil)

Jan. 2008

7160†

Duralox®

XLPE/AIA/PVC, Power, Armored, with Enhanced Ground Wires (50%) 600V, UL Type MC, Three Conductor (1/0 AWG—1000 kcmil)

Jan. 2008

7200†

Duralox®

EPR/AIA/PVC, Power, Non-Shielded, Armored 2400V, UL Type MV-90 or MC, Three Conductor

Jan. 2008

®

Jan. 2008 7250† Duralox® Uniblend® EPR/AIA/PVC, Power, Shielded, Armored 5kV/8kV, UL Type MV-105 or MC, 133% / 100% Ins. Levels, 115 Mils, Three Conductor 7300† Duralox® Uniblend® EPR/AIA/PVC, Power, Shielded, Armored 15kV, UL Type MV-105 or MC, 133% Ins. Level, 220 Mils, Three Conductor

Jan. 2008

7310† Duralox® Uniblend® EPR/AIA/PVC, Power, Shielded, Armored, with Enhanced Ground Wires (50%) 15kV, UL Type MV-105 or MC, 133% Ins. Level, 220 Mils, Three Conductor

Jan. 2008

7350 Duralox® Uniblend® EPR/AIA/PVC, Power, Shielded, Armored 25kV, UL Type MV-105 or MC, 100% Ins. Level, 260 Mils, Three Conductor

Jan. 2008

7400 Duralox® Uniblend® EPR/AIA/PVC, Power, Shielded, Armored 35kV, UL Type MV-105 or MC, 100% Ins. Level, 345 Mils, Three Conductor

Jan. 2008

†Indicates

these products are stocked by General Cable

Phone: 888-593-3355 www.generalcable.com


SPEC 7050

January, 2009

Duralox

®

XLPE/AIA/PVC, Control, Armored 600V, UL Type MC, Multi Conductor Features:

Product Construction Conductor:

• Rated at 90˚C wet or dry • Sunlight-resistant • Provides excellent oil and chemical resistance • Excellent crush resistance • Provides a long service life • Flame-retardant and resistant to moisture • Cost-effective alternative to installations in conduit • Meets cold bend test at -25˚C

Print:

• General Cable® XX/C XX AWG (UL) TYPE MC XHHW-2 CDRS DIR BUR SUN RES FOR CT USE 600V MONTH-YEAR Sequential Footage Mark

• 14 AWG thru 10 AWG bare, compressed copper • Class B stranding per ASTM B3 and B8

Options:

Insulation:

• Flame-retardant Cross-Linked Polyethylene (XLPE) • Color-coded: per ICEA Method 1; Table E-2 (does not include white or green)

Ground:

• Annealed bare copper Class B stranding per ASTM B8

Armor:

• Tinned copper conductors • E-1 color code • Copper tape shield or aluminum/polymer tape shield with tinned copper drain wire over cable core • Inner jacket only, outer jacket only, or both • Galvanized Steel Interlocked Armor (GSIA) • Other constructions available upon request

Jacket:

• Flame-retardant, moisture- and sunlight-resistant Polyvinyl Chloride (PVC)—Black

MINIMUM COND. INSULATION THICKNESS SIZE (AWG) INCHES mm

CATALOG NUMBER

NO. OF COND.

346410* 346420 346430* 346440 346450 346460* 346470* 346480* 346490* 346500*

2 3 4 5 7 9 12 19 25 37

14 14 14 14 14 14 14 14 14 14

0.030 0.030 0.030 0.030 0.030 0.030 0.030 0.030 0.030 0.030

0.76 0.76 0.76 0.76 0.76 0.76 0.76 0.76 0.76 0.76

346510* 346520 346530 346540 346550 346560* 346570* 346580* 346590* 346600*

2 3 4 5 7 9 12 19 25 37

12 12 12 12 12 12 12 12 12 12

0.030 0.030 0.030 0.030 0.030 0.030 0.030 0.030 0.030 0.030

0.76 0.76 0.76 0.76 0.76 0.76 0.76 0.76 0.76 0.76

346610 346620

3 4

10 10

0.030 0.030

0.76 0.76

• In all raceways or direct burial • In wet or dry locations • Permitted for use in Class I Division 2, Class II Division 2, and Class III Division 1 and 2 per NEC Article 334

NOM. DIA. GRND. (OVER) WIRE ARMOR SIZE (AWG) INCHES mm

NOMINAL JACKET THICKNESS INCHES mm

• UL 1569 • UL 44 • ICEA S-95-658/NEMA WC 70 • UL Type MC- 600 volts • NEC Type XHHW-2 conductors • IEEE 383 (70,000 BTU/hr) • UL 1581 (70,000 BTU/hr) • IEEE 1202 (70,000 BTU/hr)/CSA FT4 • ICEA T-29-520 (210,000 BTU/hr) • Meets EPA 40 CFR part 261 for leachable lead content per TCLP method • OSHA acceptable

Packaging:

Applications:

• Aluminum Interlocked Armor (AIA)

Compliances:

• Material cut to length and shipped on non-returnable wood reels, while lengths in excess of 10,000 lbs. are provided on returnable steel reels that require a deposit. Extra charges apply for cuts less than 1000 ft., lagging, pulling eyes, paralleling and plexing

NOMINAL CABLE O.D. INCHES mm

COPPER NET WEIGHT WEIGHT LBS/1000FT kg/km LBS/1000FT kg/km

14 AWG - MULTI CONDUCTOR - 600V 14 14 14 14 14 14 14 14 14 14

0.49 0.52 0.55 0.59 0.64 0.72 0.80 0.99 1.07 1.19

12.5 13.2 14.0 15.0 16.3 18.3 20.3 25.2 27.2 30.3

0.050 0.050 0.050 0.050 0.050 0.050 0.050 0.050 0.050 0.050

1.27 1.27 1.27 1.27 1.27 1.27 1.27 1.27 1.27 1.27

0.60 0.63 0.66 0.69 0.74 0.83 0.90 1.02 1.17 1.29

15.3 16.0 16.8 17.6 18.8 21.1 22.9 25.9 29.7 32.8

39 52 65 79 104 130 168 259 337 492

58 78 97 118 155 193 250 385 502 732

175 183 233 246 297 379 460 621 776 1043

261 273 347 367 443 564 685 924 1155 1533

16.3 16.8 18.1 19.1 20.6 22.6 24.7 28.0 32.5 35.8

64 83 103 129 165 214 279 428 557 793

96 124 154 192 246 319 416 637 829 1180

218 227 272 336 380 479 596 830 1058 1403

324 338 405 500 566 713 887 1235 1575 2088

18.3 19.6

131 164

195 244

301 355

448 529

12 AWG - MULTI CONDUCTOR - 600V 12 12 12 12 12 12 12 12 12 12

0.53 0.56 0.60 0.64 0.70 0.78 0.86 0.99 1.18 1.31

13.5 14.3 15.3 16.3 17.8 19.8 21.9 25.2 30.0 33.3

0.050 0.050 0.050 0.050 0.050 0.050 0.050 0.050 0.050 0.050

1.27 1.27 1.27 1.27 1.27 1.27 1.27 1.27 1.27 1.27

0.64 0.66 0.71 0.75 0.81 0.89 0.97 1.10 1.28 1.41

10 AWG - MULTI CONDUCTOR - 600V 10 10

0.61 0.66

15.5 16.8

0.050 0.050

1.27 1.27

0.72 0.77

Dimensions and weights are nominal; subject to industry tolerances. *Non-stock item, minimum runs apply. Please consult Customer Service for price and delivery.

Phone: 888-593-3355 www.generalcable.com


SPEC 7100

January, 2008

Duralox

®

XLPE/AIA/PVC, Power, Armored 600V, UL Type MC, Three and Four Conductor (8 AWG - 4/0 AWG)

Product Construction Conductors:

Options:

• 8 AWG thru 4/0 AWG bare copper compressed • Class B stranding per ASTM B8

Insulation:

• Cross-Linked Polyethylene (XLPE) • Color-coded: per ICEA method 3; Table E-2

Ground:

• Annealed bare copper Class B stranding per ASTM B8

Armor:

• Aluminum Interlocked Armor (AIA) • Flame-retardant, moisture- and sunlight-resistant Polyvinyl Chloride (PVC)—Black

Print:

• General Cable® SIZE (AWG OR KCMIL) 3/C OR 4/C (AS APPLICABLE) TYPE XHHW-2 CDRS 1/C SIZE AWG GRD SUN RES FOR CT USE DIR BUR 600V (UL) MONTH/YEAR Sequential Footage Mark

CATALOG NUMBER

346630 346640* 11298.030600 11298.040600* 11298.030400 11298.040400* 11298.030200 11298.040200* 11298.030100* 11298.040100* 11298.035100 11298.045100* 11298.035200 11298.045200* 11298.035300* 11298.045300* 11298.035400 11298.045400*

3 4 3 4 3 4 3 4 3 4 3 4 3 4 3 4 3 4

Applications:

• Ideally suited for use in a broad range of commercial, industrial and utility applications, where maximum performance is demanded, ease of installation desired and fire resistance is critical • Permitted for use in Class I, Class II, Division 2, Class III Division 1 and 2 hazardous locations per the NEC • Installed in both exposed or concealed work, wet or dry locations, indoors or outdoors and cable trays

Features:

Jacket:

NO. OF COND.

Compliances:

• Other constructions available upon request

Packaging:

• Rated at 90˚C wet or dry • Provides excellent oil and chemical resistance • Excellent crush resistance • Provides a long service life • Cost-effective alternative to installations in conduit • Meets cold bend test at -25˚C

MINIMUM GRND. INSULATION COND. WIRE THICKNESS SIZE SIZE (AWG) (AWG) INCHES mm

NOM. DIA. (OVER) ARMOR INCHES mm

NOMINAL JACKET THICKNESS INCHES mm

• National Electric Code (NEC) • UL 1569 • UL 44 • ICEA S-95-658/NEMA WC 70 • UL Type MC- 600 volts • NEC Type XHHW-2 conductors • IEEE 383 (70,000 BTU/hr) • UL 1581 (70,000 BTU/hr) • IEEE 1202 (70,000 BTU/hr)/CSA FT4 • ICEA T-29-520 (210,000 BTU/hr) • Meets EPA 40 CFR part 261 for leachable lead content per TCLP method • OSHA acceptable • For U.S. customers, material cut to length and shipped on non-returnable wood reels, while lengths in excess of 10,000 lbs. are provided on returnable steel reels that require a deposit. Extra charges apply for cuts less than 1000 ft., lagging, pulling eyes, paralleling and plexing

NOMINAL CABLE O.D. INCHES mm

COPPER NET WEIGHT WEIGHT LBS/1000FT kg/km LBS/1000FT kg/km

8 AWG - 4/0 AWG - THREE AND FOUR CONDUCTOR - 600V 8 8 6 6 4 4 2 2 1 1 1/0 1/0 2/0 2/0 3/0 3/0 4/0 4/0

10 10 8 8 8 8 6 6 6 6 6 6 6 6 4 4 4 4

0.045 0.045 0.045 0.045 0.045 0.045 0.045 0.045 0.055 0.055 0.055 0.055 0.055 0.055 0.055 0.055 0.055 0.055

1.14 1.14 1.14 1.14 1.14 1.14 1.14 1.14 1.40 1.40 1.40 1.40 1.40 1.40 1.40 1.40 1.40 1.40

0.74 0.80 0.84 0.91 0.94 1.03 1.07 1.18 1.19 1.31 1.27 1.40 1.37 1.51 1.48 1.66 1.66 1.78

18.8 20.3 21.4 23.1 23.9 26.2 27.2 30.0 30.3 33.3 32.3 35.6 34.8 38.2 37.6 42.2 42.2 45.2

0.050 0.050 0.050 0.050 0.050 0.050 0.050 0.050 0.050 0.050 0.050 0.050 0.050 0.050 0.050 0.050 0.060 0.060

1.27 1.27 1.27 1.27 1.27 1.27 1.27 1.27 1.27 1.27 1.27 1.27 1.27 1.27 1.27 1.27 1.52 1.52

0.84 0.90 0.95 1.01 1.05 1.13 1.18 1.28 1.29 1.41 1.38 1.50 1.48 1.61 1.59 1.78 1.79 1.90

21.4 22.9 24.2 25.6 26.7 28.7 30.0 32.5 32.8 35.9 35.1 38.1 37.6 40.9 40.4 45.3 45.5 48.3

189 241 300 383 447 577 710 919 873 1136 1081 1512 1341 1760 1717 2245 2130 2796

281 359 446 570 665 859 1057 1368 1299 1691 1609 2250 1996 2619 2555 3341 3170 4161

420 507 567 670 757 912 1075 1295 1269 1596 1528 1913 1860 2345 2259 2878 2840 3586

625 755 844 997 1127 1357 1600 1927 1889 2375 2274 2847 2768 3490 3362 4283 4226 5336

Dimensions and weights are nominal; subject to industry tolerances. *Non-stock item, minimum runs apply. Please consult Customer Service for price and delivery.

Phone: 888-593-3355 www.generalcable.com


SPEC 7150

January, 2008

Duralox

®

XLPE/AIA/PVC, Power, Armored 600V, UL Type MC, Three and Four Conductor (250 kcmil - 1000 kcmil)

Product Construction Conductors:

Options:

Applications:

• 250 kcmil thru 1000 kcmil bare copper compressed • Class B stranding per ASTM B8

• Ideally suited for use in a broad range of commercial, industrial and utility applications, where maximum performance is demanded, ease of installation desired and fire resistance is critical • Permitted for use in Class I, Class II, Division 2, Class III Division 1 and 2 hazardous locations per the NEC • Installed in both exposed or concealed work, wet or dry locations, indoors or outdoors and cable trays

Insulation:

• Cross-Linked Polyethylene (XLPE) • Color-coded: Per ICEA method 3; Table E-2

Ground:

• Annealed bare copper Class B stranding per ASTM B8

Armor:

Features:

• Aluminum Interlocked Armor (AIA)

Jacket:

• Flame-retardant, moisture- and sunlight-resistant Polyvinyl Chloride (PVC)—Black

Print:

• General Cable® SIZE (AWG OR KCMIL) 3/C OR 4/C (AS APPLICABLE) TYPE XHHW-2 CDRS 1/C SIZE AWG GRD SUN RES FOR CT USE DIR BUR 600V (UL) MONTH/YEAR Sequential Footage Mark

CATALOG NUMBER

NO. OF COND.

11298.036000 11298.046000* 11298.036200 11298.046200* 11298.036500 11298.046500* 11298.037000* 11298.047000* 11298.037500* 11298.047500*

3 4 3 4 3 4 3 4 3 4

Compliances:

• Other constructions available upon request

Packaging:

• Rated at 90˚C wet or dry • Provides excellent oil and chemical resistance • Excellent crush resistance • Provides a long service life • Cost-effective alternative to installations in conduit • Meets cold bend test at -25˚C

MINIMUM GRND. INSULATION COND. WIRE THICKNESS SIZE SIZE (AWG) (AWG) INCHES mm

NOM. DIA. (OVER) ARMOR INCHES mm

NOMINAL JACKET THICKNESS INCHES mm

• National Electric Code (NEC) • UL 1569 • UL 44 • ICEA S-95-658/NEMA WC 70 • UL Type MC- 600 volts • NEC Type XHHW-2 conductors • IEEE 383 (70,000 BTU/hr) • UL 1581 (70,000 BTU/hr) • IEEE 1202 (70,000 BTU/hr)/CSA FT4 • ICEA T-29-520 (210,000 BTU/hr) • Meets EPA 40 CFR part 261 for leachable lead content per TCLP method • OSHA acceptable • For U.S. customers, material cut to length and shipped on non-returnable wood reels, while lengths in excess of 10,000 lbs. are provided on returnable steel reels that require a deposit. Extra charges apply for cuts less than 1000 ft., lagging, pulling eyes, paralleling and plexing

NOMINAL CABLE O.D. INCHES mm

COPPER NET WEIGHT WEIGHT LBS/1000FT kg/km LBS/1000FT kg/km

250 kcmil - 1000 kcmil - THREE AND FOUR CONDUCTOR - 600V 250 250 350 350 500 500 750 750 1000 1000

4 4 3 3 2 2 1 1 1/0 1/0

0.065 0.065 0.065 0.065 0.065 0.065 0.080 0.080 0.080 0.080

1.65 1.65 1.65 1.65 1.65 1.65 2.03 2.03 2.03 2.03

1.81 1.95 2.03 2.20 2.30 2.51 2.74 3.04 3.07 3.41

46.0 49.5 51.6 55.9 58.5 63.8 69.6 77.2 78.0 86.6

0.060 0.060 0.060 0.060 0.075 0.075 0.075 0.075 0.075 0.075

1.52 1.52 1.52 1.52 1.91 1.91 1.91 1.91 1.91 1.91

1.94 2.07 2.16 2.32 2.46 2.66 2.89 3.21 3.24 3.58

49.3 52.6 54.9 59.0 62.5 67.6 73.4 81.6 82.3 91.0

2495 3282 3474 4576 4934 6509 7351 9713 9783 12932

3713 4884 5170 6810 7343 9687 10940 14455 14559 19245

3295 4174 4400 5608 6126 7825 8806 11494 11476 14931

4903 6211 6548 8345 9116 11644 13104 17104 17077 22218

Dimensions and weights are nominal; subject to industry tolerances. *Non-stock item, minimum runs apply. Please consult Customer Service for price and delivery.

Phone: 888-593-3355 www.generalcable.com


SPEC 7160

January, 2008

Duralox

®

XLPE/AIA/PVC, Power, Armored, with Enhanced Ground Wires (50%) 600V, UL Type MC, Three Conductor (1/0 AWG—1000 kcmil)

Product Construction Conductors:

Options:

Applications:

• 1/0 AWG thru 1000 kcmil bare copper compressed • Class B stranding per ASTM B8

• Ideally suited for use in a broad range of commercial, industrial and utility applications, where maximum performance is demanded, ease of installation desired and fire resistance is critical • Permitted for use in Class I, Class II, Division 2, Class III Division 1 and 2 hazardous locations per the NEC • Installed in both exposed or concealed work, wet or dry locations, indoors or outdoors and cable trays

Insulation:

• Cross-Linked Polyethylene (XLPE) • Color-coded: Per ICEA method 3; Table E-2

Ground:

• Annealed bare copper Class B stranding per ASTM B8

Armor:

Features:

• Aluminum Interlocked Armor (AIA)

Jacket:

• Flame-retardant, moisture- and sunlight-resistant Polyvinyl Chloride (PVC)—Black

Print:

• General Cable® SIZE (AWG OR KCMIL) 3/C TYPE XHHW-2 CDRS 1/C SIZE AWG GRD SUN RES FOR CT USE DIR BUR 600V (UL) MONTH/ YEAR Sequential Footage Mark

CATALOG NUMBER

NO. OF COND.

11298.515100* 11298.515200* 11298.515300* 11298.515400* 11298.516000* 11298.516200* 11298.516500 11298.517000* 11298.517500*

3 3 3 3 3 3 3 3 3

Compliances:

• Other constructions available upon request

Packaging:

• Rated at 90˚C wet or dry • Provides excellent oil and chemical resistance • Excellent crush resistance • Provides a long service life • Cost-effective alternative to installations in conduit • Meets cold bend test at -25˚C

MINIMUM GRND. INSULATION COND. WIRE THICKNESS SIZE SIZE (AWG) (AWG) INCHES mm

NOM. DIA. (OVER) ARMOR INCHES mm

NOMINAL JACKET THICKNESS INCHES mm

• National Electric Code (NEC) • UL 1569 • UL 44 • ICEA S-95-658/NEMA WC 70 • UL Type MC- 600 volts • NEC Type XHHW-2 conductors • IEEE 383 (70,000 BTU/hr) • UL 1581 (70,000 BTU/hr) • IEEE 1202 (70,000 BTU/hr)/CSA FT4 • ICEA T-29-520 (210,000 BTU/hr) • Meets EPA 40 CFR part 261 for leachable lead content per TCLP method • OSHA acceptable • For U.S. customers, material cut to length and shipped on non-returnable wood reels, while lengths in excess of 10,000 lbs. are provided on returnable steel reels that require a deposit. Extra charges apply for cuts less than 1000 ft., lagging, pulling eyes, paralleling and plexing

NOMINAL CABLE O.D. INCHES mm

COPPER NET WEIGHT WEIGHT LBS/1000FT kg/km LBS/1000FT kg/km

1/0 AWG - 1000 kcmil - THREE CONDUCTOR - 600V 1/0 2/0 3/0 4/0 250 350 500 750 1000

3x6 3x6 3x5 3x4 3x4 3x2 3x1 3x2/0 3x3/0

0.055 0.055 0.055 0.055 0.065 0.065 0.065 0.080 0.080

1.40 1.40 1.40 1.40 1.65 1.65 1.65 2.03 2.03

1.27 1.37 1.48 1.66 1.81 2.03 2.30 2.74 3.07

32.3 34.8 37.6 42.2 46.0 51.6 58.5 69.6 78.0

0.050 0.050 0.050 0.060 0.060 0.060 0.075 0.075 0.075

1.27 1.27 1.27 1.52 1.52 1.52 1.91 1.91 1.91

1.38 1.48 1.59 1.79 1.94 2.16 2.46 2.89 3.24

35.1 37.6 40.4 45.5 49.3 54.9 62.5 73.4 82.3

1247 1507 1939 2395 2760 3944 5473 8022 10629

1858 2245 2889 3569 4112 5877 8155 11953 15837

1694 2026 2481 3105 3560 4870 6665 9477 12322

2524 3019 3697 4626 5304 7256 9931 14121 18360

Dimensions and weights are nominal; subject to industry tolerances. *Non-stock item, minimum runs apply. Please consult Customer Service for price and delivery.

Phone: 888-593-3355 www.generalcable.com


SPEC 7200

January, 2008

Duralox

®

EPR/AIA/PVC, Power, Non-Shielded, Armored 2400V, UL Type MV-90 or MC, Three Conductor Features:

Product Construction Conductors:

• Rated at 90˚C wet or dry • Excellent heat and moisture resistance • Outstanding corona resistance • Flexibility for easy handling • High dielectric strength • Low moisture absorption • Electrical stability under stress • Low dielectric loss • Chemical- and radiation-resistant • Excellent crush resistance • Flame or sunlight resistance • Cost-effective alternative to installations in conduit • Meets the cold bend test at -25˚C

Print:

• General Cable® SIZE (KCMIL OR AWG) COMPACT CU 3/C GENERAL CABLE 115 MILS EPR TYPE MV-90 OR MC 3/C SIZE AWG GRD SUN RES FO R CT USE DIR BUR 2400V NON-SHIELDED (UL) MONTH-YEAR LIGHTNING BOLT SYMBOL Sequential Footage Mark

• 6 AWG thru 1000 kcmil bare copper, compact Class B strand

Extruded Strand Shield (ESS):

• Extruded thermoset semi-conducting stress control layer over conductor

Compliances:

• National Electric Code (NEC) • ICEA S-96-659/NEMA WC-71 • UL Listed as Type MV or Type MC • UL 1072 • UL 1569 • IEEE 1202 (70,000 BTU/hr) • IEEE 383 (70,000 BTU/hr) • UL 1581 (70,000 BTU/hr) • ICEA T-29-520 (210,000 BTU/hr) • ICEA T-30-520 (70,000 BTU/hr) • Meets EPA 40 CFR part 261 for leachable lead content per TCLP method • OSHA acceptable

Options:

Insulation:

• Other constructions available upon request

• Ethylene Propylene Rubber (EPR) colored to contrast with black conducting shield layer

Applications:

Ground:

• Annealed bare copper Class B stranding per ASTM B8

Armor:

• Aluminum Interlocked Armor (AIA)

Jacket:

• Flame-retardant, moisture- and sunlight-resistant polyvinyl chloride (PVC)—Yellow

CATALOG NUMBER

NO. OF COND.

17471.580600 17471.580400 17471.580200 17471.585100* 17471.585200 17471.585400 17471.586000* 17471.586200 17471.586500 17471.587000* 17471.587500*

3 3 3 3 3 3 3 3 3 3 3

• Ideally suited for use in a broad range of commercial, industrial and utility applications where reliability is the major concern, maximum performance will be demanded, space is limited, ease of installation is critical and fire resistance is necessary • May be installed in wet or dry locations, indoors or outdoors and in exposed or concealed work • May be used in cable trays or on approved supports in protected areas • Permitted for use in Class I, Class II Division 2, Class III Divisions 1 and 2 hazardous locations per the NEC

MINIMUM GRND. COND. COND. WIRE INSULATION THICKNESS SIZE DIA. SIZE (AWG) INCHES (AWG) INCHES mm

NOM. DIA. (OVER) ARMOR INCHES mm

NOMINAL JACKET THICKNESS INCHES mm

Packaging:

• Material cut to length and shipped on non-returnable wood reels, while lengths in excess of 10,000 lbs. are provided on returnable steel reels that require a deposit. Extra charges apply for cuts less than 1000 ft., lagging, pulling eyes, paralleling and plexing

NOMINAL CABLE O.D. INCHES mm

COPPER NET WEIGHT WEIGHT LBS/1000FT kg/km LBS/1000FT kg/km

6 AWG - 1000 kcmil - THREE CONDUCTOR - 115 MILS INS. (2.92 mm) - 2400V 6 4 2 1/0 2/0 4/0 250 350 500 750 1000

0.17 0.21 0.27 0.34 0.38 0.48 0.52 0.62 0.74 0.91 1.07

6 6 6 4 4 3 3 2 1 1/0 1/0

0.115 0.115 0.115 0.115 0.115 0.115 0.115 0.115 0.115 0.115 0.115

2.92 2.92 2.92 2.92 2.92 2.92 2.92 2.92 2.92 2.92 2.92

1.16 1.26 1.37 1.61 1.71 1.92 2.00 2.21 2.46 2.83 3.16

29.4 31.9 34.8 41.0 43.3 48.7 50.7 56.0 62.6 72.0 80.3

0.050 0.050 0.050 0.060 0.060 0.060 0.060 0.060 0.075 0.075 0.085

1.27 1.27 1.27 1.52 1.52 1.52 1.52 1.52 1.91 1.91 2.16

1.27 1.37 1.48 1.74 1.84 2.05 2.13 2.34 2.63 3.00 3.35

32.2 34.7 37.6 44.3 46.6 52.0 54.1 59.3 66.7 76.1 85.0

327 473 703 1118 1376 2143 2503 3479 4933 7347 9680

487 704 1047 1665 2049 3191 3727 5180 7345 10940 14414

854 1056 1363 2003 2326 3256 3689 4825 6567 9320 12023

1272 1572 2030 2982 3463 4848 5493 7184 9778 13877 17902

Dimensions and weights are nominal; subject to industry tolerances. *Non-stock item, minimum runs apply. Please consult Customer Service for price and delivery.

Phone: 888-593-3355 www.generalcable.com


SPEC 7250

January, 2008

Duralox Uniblend ®

®

EPR/AIA/PVC, Power, Shielded, Armored 5kV/8kV, UL Type MV-105 or MC, 133% / 100% Ins. Levels, 115 Mils, Three Conductor Features:

Product Construction Conductors:

• 6 AWG thru 1000 kcmil bare, compact copper Class B strand

Extruded Strand Shield (ESS):

• Thermoset semi-conducting extruded stress control layer over conductor

Insulation:

• Ethylene Propylene Rubber (EPR) insulation, colored to contrast with black conducting layers

Extruded Insulation Shield (EIS):

• Thermoset semi-conducting polymeric layer free stripping from insulation

Shield:

• 5 mil annealed copper tape with a minimum 25% overlap

Ground:

• Annealed bare copper Class B stranding per ASTM B8

Armor:

• Aluminum Interlocked Armor (AIA)

CATALOG NUMBER

Jacket:

• Flame-retardant, moisture- and sunlight-resistant Polyvinyl Chloride (PVC)—Yellow

Print:

• General Cable® SIZE (KCMIL OR AWG) COMPACT CU 3/C (INS THICKNESS) MILS EPR TYPE MV-105 OR MC 3/C SIZE AWG GRD VOLTAGE kV% INS LEVEL SUN RES FOR CT USE DIR BUR (UL) LIGHTING BOLT SYMBOL MONTHYEAR Sequential Footage Mark

Options:

• Other constructions available upon request

Applications:

• Ideally suited for use in a broad range of commercial, industrial and utility applications where reliability is the major concern, maximum performance is demanded, space is limited, ease of installation is critical and fire resistance is necessary • Installed in wet or dry locations, indoors or outdoors, in exposed or concealed work • May be used in cable trays or on approved support in protected areas • Permitted for use in Class I, Class II Division 2, Class III Divisions 1 and 2 hazardous locations per the NEC

INSULATION DIAMETER NO. COND. COND. MIN. MAX. OF SIZE DIA. COND. (AWG) INCHES INCHES mm INCHES mm

• Rated at 105˚C wet or dry • Excellent heat and moisture resistance • Outstanding corona resistance • Flexibility for easy handling • High dielectric strength • Low moisture absorption • Electrical stability under stress • Low dielectric loss • Chemical- and radiation-resistant • Excellent crush resistance • Cost-effective alternative to installations in conduit • Meets cold bend test at -25˚C

Compliances:

• National Electric Code (NEC) • UL 1072 • ICEA S-93-639/NEMA WC-74 • AEIC CS8 • UL listed as Type MV-105 • IEEE 1202 (70,000 BTU/hr)/CSA FT4 • IEEE 383 (70,000 BTU/hr) • UL 1581 (70,000 BTU/hr) • ICEA T-29-520 (210,000 BTU/hr) • ICEA T-30-520 (70,000 BTU/hr) • Meets EPA 40 CFR part 261 for leachable lead content per TCLP method • OSHA acceptable

Packaging:

• Material cut to length and shipped on non-returnable wood reels, while lengths in excess of 10,000 lbs. are provided on returnable steel reels that require a deposit. Extra charges apply for cuts less than 1000 ft., lagging, pulling eyes, paralleling and plexing

DIA. NOMINAL NOMINAL GRND. NOM. (OVER) JACKET CABLE WIRE ARMOR THICKNESS O.D. SIZE (AWG) INCHES mm INCHES mm INCHES mm

COPPER WEIGHT LBS/ 1000FT

NET. WEIGHT W/AL ARMOR

kg/ km

LBS/ 1000FT

6 AWG - 1000 kcmil - THREE CONDUCTOR W/JACKET OVER ARMOR, 5kV 133% INS. LEVEL OR 8kV, 100% INS. LEVEL, 115 MILS INS. (2.92 mm) 3 6 0.17 0.42 10.5 0.49 12.5 6 1.33 33.8 0.050 1.27 1.44 36.6 462 688 1133 17473.530600* 3 4 0.21 0.46 11.6 0.54 13.7 6 1.43 36.2 0.050 1.27 1.54 39.1 619 922 1354 17473.530400* 3 2 0.27 0.51 13.0 0.59 14.9 6 1.64 41.6 0.060 1.52 1.77 44.9 864 1286 1819 17473.530200 3 1/0 0.34 0.58 14.7 0.66 16.7 4 1.79 45.3 0.060 1.52 1.92 48.6 1298 1933 2364 17473.535100* 3 2/0 0.38 0.62 15.7 0.70 17.7 4 1.87 47.5 0.060 1.52 2.00 50.8 1566 2332 2696 17473.535200 3 4/0 0.48 0.72 18.3 0.80 20.3 3 2.09 53.2 0.060 1.52 2.22 56.5 2360 3514 3687 17473.535400 3 250 0.52 0.77 19.6 0.85 21.5 3 2.21 56.0 0.060 1.52 2.34 59.3 2735 4072 4165 17473.536000* 3 350 0.62 0.87 22.1 0.95 24.1 2 2.41 61.3 0.075 1.91 2.57 65.4 3736 5563 5436 17473.536200 3 500 0.74 0.99 25.1 1.07 27.1 1 2.64 67.0 0.075 1.91 2.84 72.0 5222 7776 7170 17473.536500 3 750 0.91 1.17 29.7 1.25 31.8 1/0 3.06 77.8 0.085 2.16 3.25 82.4 7684 11441 10084 17473.537000* 3 1000 1.07 1.33 33.8 1.40 35.6 1/0 3.39 86.1 0.085 2.16 3.57 90.8 10057 14975 12793 17473.537500*

kg/ km

1687 2016 2708 3520 4014 5490 6202 8094 10676 15015 19049

Dimensions and weights are nominal; subject to industry tolerances. *Non-stock item, minimum runs apply. Please consult Customer Service for price and delivery.

Phone: 888-593-3355 www.generalcable.com


SPEC 7300

January, 2008

Duralox Uniblend ®

®

EPR/AIA/PVC, Power, Shielded, Armored 15kV, UL Type MV-105 or MC, 133% Ins. Level, 220 Mils, Three Conductor Features:

Product Construction Conductors:

Jacket:

• Flame-retardant, moisture- and sunlight-resistant Polyvinyl Chloride (PVC)—Red

• 2 AWG thru 1000 kcmil bare, compact copper Class B strand

Print:

• General Cable® SIZE (KCMIL OR AWG) COMPACT CU 3/C (INS THICKNESS) MILS EPR TYPE MV-105 OR MC 3/C SIZE AWG GRD VOLTAGE kV% INS LEVEL SUN RES FOR CT USE DIR BUR (UL) LIGHTING BOLT SYMBOL MONTHYEAR Sequential Footage Mark

Extruded Strand Shield (ESS):

• Thermoset semi-conducting extruded stress control layer over conductor

Insulation:

• Ethylene Propylene Rubber (EPR) insulation, colored to contrast with black conducting layers

Compliances:

• National Electric Code (NEC) • UL 1072 • ICEA S-93-639/NEMA WC-74 • AEIC CS8 • UL listed as Type MV-105 • IEEE 1202 (70,000 BTU/hr)/CSA FT4 • IEEE 383 (70,000 BTU/hr) • UL 1581 (70,000 BTU/hr) • ICEA T-29-520 (210,000 BTU/hr) • ICEA T-30-520 (70,000 BTU/hr) • Meets EPA 40 CFR part 261 for leachable lead content per TCLP method • OSHA acceptable

Options:

Extruded Insulation Shield (EIS):

• Other constructions available upon request

• Thermoset semi-conducting polymeric layer free stripping from insulation

Applications:

• Ideally suited for use in a broad range of commercial, industrial and utility applications where reliability is the major concern, maximum performance is demanded, space is limited, ease of installation is critical and fire resistance is necessary • Installed in wet or dry locations, indoors or outdoors, in exposed or concealed work • May be used in cable trays or on approved support in protected areas • Permitted for use in Class I, Class II Division 2, Class III Divisions 1 and 2 hazardous locations per the NEC

Shield:

• 5 mil annealed copper tape with a minimum 25% overlap

Ground:

• Annealed bare copper Class B stranding per ASTM B8

Armor:

• Aluminum Interlocked Armor (AIA)

CATALOG NUMBER

• Rated at 105˚C wet or dry • Excellent heat and moisture resistance • Outstanding corona resistance • Flexibility for easy handling • High dielectric strength • Low moisture absorption • Electrical stability under stress • Low dielectric loss • Chemical- and radiation-resistant • Excellent crush resistance • Cost-effective alternative to installations in conduit • Meets cold bend test at -25˚C

INSULATION DIAMETER COND. NO. SIZE COND. MIN. MAX. OF (AWG/) DIA. COND. kcmil INCHES INCHES mm INCHES mm

Packaging:

• Material cut to length and shipped on non-returnable wood reels, while lengths in excess of 10,000 lbs. are provided on returnable steel reels that require a deposit. Extra charges apply for cuts less than 1000 ft., lagging, pulling eyes, paralleling and plexing

DIA. NOMINAL NOMINAL GRND. NOM. (OVER) JACKET CABLE WIRE ARMOR THICKNESS O.D. SIZE (AWG) INCHES mm INCHES mm INCHES mm

COPPER WEIGHT LBS/ 1000FT

NET. WEIGHT W/AL ARMOR

kg/ km

LBS/ 1000FT

kg/ km

1368 2013 2412 3594 4153 5643 7856 11522 15055

2416 2997 3371 4502 5005 6252 8091 11086 13870

3597 4463 5019 6703 7452 9309 12047 16507 20652

2 AWG - 1000 kcmil - THREE CONDUCTOR W/JACKET OVER ARMOR, 15kV 133% INS. LEVEL, 220 MILS INS. (5.59 mm) 17476.530200 17476.535100* 17476.535200 17476.535400 17476.536000* 17476.536200 17476.536500 17476.537000* 17476.537500*

3 3 3 3 3 3 3 3 3

2 1/0 2/0 4/0 250 350 500 750 1000

0.27 0.34 0.38 0.48 0.53 0.62 0.74 0.91 1.06

0.71 0.78 0.82 0.92 0.97 1.07 1.19 1.37 1.52

18.0 19.8 20.8 23.4 24.6 27.2 30.2 34.8 38.6

0.80 0.87 0.91 1.01 1.06 1.16 1.28 1.46 1.61

20.3 22.0 24.3 25.6 26.9 29.4 32.4 37.1 40.9

6 4 4 3 3 2 1 1/0 1/0

2.08 2.22 2.31 2.53 2.65 2.85 3.11 3.50 3.83

52.8 56.5 58.7 64.3 67.2 72.4 79.0 89.0 97.3

0.060 0.060 0.060 0.075 0.075 0.075 0.085 0.085 0.085

1.52 1.52 1.52 1.91 1.91 1.91 2.16 2.16 2.16

2.21 2.35 2.44 2.70 2.81 3.01 3.30 3.69 4.01

56.1 919 59.8 1352 62.0 1620 68.5 2114 71.3 2789 76.6 3790 83.7 5276 93.6 7738 101.9 10111

Dimensions and weights are nominal;