Page 1

Instruction for use

Fire-Door Control Panel BAZ 04-N Installation Safety system to protect human life and material assets! Monthly function check by qualified personnel! Annual maintenance by a specialist company authorized by the manufacturer! The green control diode on control panel must permanently lighten; otherwise see "Fault finding".

Locking devices potential free alarm contact 230V mains power supply

C

S US HL OL SC NTR DAD B DA CO E AN R OM BR DOO ON T E AU R I F LE A TR EN

99.823.23

1.1/06/07

control contact from fire-detection control panel

push-button control

fire detector en ss lie llen chckste

r ser rü TüMeld

D+H Mechatronic AG Georg-Sasse-Str. 28-32 D-22949 Ammersbek Tel. +4940-60565219 Fax +4940-60565264


Description Fire-door control panel BAZ 04-N controls the locking devices of fire-doors and gates. In neutral position, the electric locking device keeps the door open and facilitates unhindered movement of individuals and goods. In case of release by automatic fire detectors or pushbutton controls, the devices will be switched idle and the doors will be closed via sequence controllers by others. This prevents spreading of fire to other parts of a building. The BAZ 04-N is supplied with a power failure bridge which will facilitate power supply of connected locking devices for a period of up to 4 hours (depending on the number of connected appliances) in case of failure of the mains supply.

Installation Instructions

Guarantee

230V power supply: - Supply a separate, nondisconnectible electrical circuit - Label the fuses

You will get 2 years guarantee for all D+H products from date of verified handing over of the system up to maximal 3 years after date of delivery, when mounting and starting has been carried out by a D+H authorized distributor.

Regulations: Comply with VDE 0804 for telecommunication systems, the guidelines for locking systems issued by the Institute of Structural Engineering, the regulations of the local fire brigade, and the EVU for mains supply.

D+H guarantee is expired, with connection of D+H components with external systems or with mixing of D+H products with parts of other manufacturers.

Technical Data Rated power Power consumption Locking devices und Alarmgeber

: 230 V AC / 50 Hz Âą10 % : 15V A

Alarm contact

: Floating double-throw contact with neutral position max. 230 V / 3 A

Housing Protective system Housing dimensions WxHxD

: PC, RAL 7035 (light grey) : IP 52

2/8

BAZ 04-N Inst. Rev.:1.1

: 24 V DC / max. 0,4 A

: 172 x 151 x 95 mm


Mains Failure Bridge Accumulator type max. size W x H x D

: :

12V/ 1,2Ah (corresponds to D+H type 1) 97 x 53 x 43mm Netzüberbrückungszeit

Mains supply bridge time

5 4,5 4 3,5

t/h 3 2,5 2 1,5 1 0,5 0 50

100

150

200

I/mA

250

300

350

400

Mounting Notes Fire-door control panel - Mount the control panel, allowing for adequate ventilation (10 cm clearance between upper and lower housing surface to ceilings or shelves, etc.) - The indicator diodes on control panel must be clearly visible. Fire doors - Fire doors should not be drilled. Push-button controls - Mount adjacent to fire door where they are clearly visible and easily accessible. - Make sure the push buttons are not concealed by a locked fire door. Test phase during mounting - The facility can be tested as well without connected power supply (230VAC) for short-time test purposes, if the terminal pins Start on the central pcb will be shortly bridged. - After completion of the test phase, the accumulator must be disconnected for a short time to avoid total discharge of the accumulator.

1 2 3 4 5 6

1 2 3 4 5 6

BAZ 04-N Out: 24V/max. 0,4A

Battery: 12V/1,2Ah

rt

ta S BAZ 04-N Inst. Rev.:1.1

3/8


Acceptance Test

Maintenance

After the locking system has been installed completely in place, it must be subjected to an acceptance test to ensure that it has been installed in accordance with the relevant regulations and that it is in perfect working order. The user must arrange for such acceptance test.

Annual testing by the system manufacturer or specialist company authorized by the system manufacturer. Renew test label on control panel. Keep a test log book (D+H Ord.-No.: 99.823.15)

The acceptance test may only be conducted either by specialist personnel employed by the manufacturer of the locking devices, and authorized by same, or specialist personnel from an appropriately nominated testing authority. The result of a successful acceptance test shall be put down in an operational book (D+H Ord.-No.: 99.823.15). In addition, the operating company must permanently attach the plate, delivered by the manufacturer, to the wall adjacent to the fire-door. A takeover certificate of a successful acceptance test will be issued to the operating company, who shall ensure that it is kept in a safe place.

Locking system: Check triggering of locking system by activating both the fire detector alarm and push-button control. The fire door must close perfectly. Fire detectors: In case of visible severe dirt accumulation or false alarms, send device in for maintenance and use exchange detector. Check each detector individually with a D+H smoke detector testing device. Doors and locking devices: Clean and regrease all moving parts. Check smooth running during opening action and firm hold in final position. After being interrupted during closing, the door must automatically resume its closing action from any open position.

Testing According to regulations, the user is obliged to maintain locking systems constantly in working order and test them at least once a month to ensure perfect functioning. Keep a test log book (D+H Ord.-No.: 99.823.15) Testing: Check all devices and cable connections for visible signs of damage and dirt accumulation. The efficacy of fire detectors, push-button controls and fire doors must not be impeded by stored goods or structural modifications. Check triggering of locking system by using the push-button control. Fire door must close properly.

4/8

BAZ 04-N Inst. Rev.:1.1


Mounting fire detectors Fire detectors can be installed in following positions, according to the relevant regulations A)

Fire detector, flush with lintel beam and centre-mounted

Fire door, max. 300 cm wide

On a lateral surface of a lintel beam above the opening to be monitored, provided the fire detector fits flush with the underside of the lintel beam and the clear width of the door opening does not exceed 300cm.

Door width >300 cm: If necessary, several fire detectors on each side, as each fire detector has a max. lateral cover of 200 cm.

On a lateral surface of the lintel beam above the opening to be monitored and on the ceiling above the opening to be monitored, provided the ceiling is located more than 100 cm above the opening to be monitored.

> 100 cm

C)

On a lateral surface of the lintel beam above the opening to be monitored and on the ceiling above the opening to be monitored, provided the ceiling is located more than 100 cm above the opening to be monitored.

If the opening is wider, it may be necessary to install several fire detectors. The general rule is that one fire detector covers an area extending laterally up to 200 cm from an adjacent fire detector. The fire detector must cover the entire width of the opening. BAZ 04-N Inst. Rev.:1.1

5/8


Connection ire detectors Model** max. 14 off

Push-button Locking controls equipment UT4 total connected load 0,4A

-

+

10kW*

-

+

last or single

out in

-

+

-

+

out

***

in

YR 0,8

Main power supply 230V/ 15VA

+locking dev.

-

+locking dev.

-

+line

-

r

YR 0,8

button

u

< OR >

NYM-I 1,5

button a L

NYM-I 1,5

External signal max. 230V/ 6A

NYM-I 1,5

first or penultimate

1

2

3

4

5

6

1

2

3

4

5

6

N

Magnet

R

Detector

BAZ 04 (-N) * Terminal resistors for monitoring lines Connected to the terminals in the control panel when shipped. Disconnect and reconnect according to circuit diagramm. If the system is installed without fire detectors, the terminal resistors must remain connected to terminals R1 and R2. ** Fire detectors Only such fire detectors are permitted to use, which are listed on the table of page 7. Please consult the relevant catalogue of models or product information leaflet about the respective detector to determine the maximum permissible number of fire detectors. *** Cutout switch Cutout switch for closing of every door in a line or just a single door. Reset of an alarm is not possible with this switch. **** Jumper strip by others

6/8

BAZ 04-N Inst. Rev.:1.1


Fire detectors Model**

External control e.g. BMZ

max. 14 off. 10kW* out

in

in

1k

out

out in

10k

out

****

in

< OR > YR 0,8

YR 0,8

R

4

-

3

+line

2

-

-

1

+line

+line

YR 0,8

5

6

1

2

Detector

Type designation DO 1101 ORM 130 A(Y) 1420 O 1362 o.E. (FO 1362) SLK-E 1410 El 1000 I 1062 o.E. (Fl 1062) SIH-E DT 1101 WDM 215/A TD 1262 o.E. (FT 1262) DCC-1EL 1430 DT 1102

R

3

4

5

6

Detector

Manufacturer Maximum number Optical smoke detectors Cerberus AG Hekatron GmbH Apollo Caradon Esser Hochiki Ionization smoke detectors Apollo D+H Mechatronic AG Caradon Esser Hochiki Heat-sensitive detectors Cerberus AG Hekatron GmbH Caradon Esser Hochiki Apollo Cerberus AG

DIN EN 54

8 8 8 14 8

part 7 part 7 part 7 part 7 part 7

8 8 14 8

part 7 part 7 part 7 part 7

8 8 14 8 8 8

part 5, class 1 part 5, class 1 part 5, class 1 part 5, class 1 part 5, class 1 part 8 BAZ 04-N Inst. Rev.:1.1

7/8


Fault Finding Symptoms

Causes

Remedy

Fire doors close although no smoke is present and the push-button control has not been activated.

A number of causes could be responsible for the fault.

Check items 1 to 3 for diagnosis.

1. Red indicator diode "Alarm" on control panel is lit.

One of the wires of the fire detector lines or a wire from a cutout switch to terminal strip R is broken.

Check fire detector cables for short circuit and the 10kW terminal resistor in the last fire detector. For test purposes you can directly connect a 10K resistor to terminals R1 and R2.

2. The green indicator diode "Ready" on the control panel is not lit.

A wire in the magnet lines is broken.

Check cables and connections of locking device and of pushbutton control.

3. The green indicator diode "Ready" on the control panel is not lit.

8/8

BAZ 04-N Inst. Rev.:1.1

Check mains and mains fuse. If mains available, check fuse in control panel.

All sizes in millimetre • Rights to technical modifications reserved. • Reprinting and phototechnical reproduction also in extracts has to be expressively authorized by D+H Mechatronic AG.