Outdoor cables

FiberConnect® Universal cable with functional integrity 90 min

Fiber optic cables (SM / MM)

rodent protected , with central multi-fiber loose tube (2500 N)

Outer jacket Loose tube, gel-filled Rip cord inner fire protection tape Strain relief elements and rodent protection/outer fire protection tape

Functional integrity in the event of fire

U-D(ZN)BH n…FS Order no.

84 040 Q Q Q Q

Standardisation

IEC 60794-2

for at least 90 minutes

Description

Mechanical properties

Non-metallic, light and flexible cable with increased tensile

Min. bending radius static dynamic

strength that can be used both inside and outside buildings. Installation in cable ducts, on cable trays or in cable conduits.

15 × outer diameter 20 × outer diameter

Max. pull force on jacket

2500 N

Max. crush resistance

3000 N/dm

Composition Cable core

Loose tube, gel-filled

Fire performance

inner fire protection tape

Flame retardancy

IEC 60332-1-2 and IEC 60332-3-22 Cat. A

Multifunctional reinforced glass rovings,

Smoke density

IEC 61034

moisture blocking, as non-metallic strain

Absence of halogen IEC 60754-1

relief elements and rodent protection

Acidity of combus-

Cable jacket

Halogen-free, flame-retardant material

tion gases

Colour of jacket

O blue

Armour

IEC 60754-2

Functional integrity test Acc. to IEC 60 331-11, IEC 60 331-25 and EN 50200

Thermal properties

09

Transport/storage

– 25 °C to + 70 °C

Installation

– 5 °C to + 50 °C

Operating tempe-

– 20 °C to + 60 °C

90 min (VDE test report).

rature

Max. number of fibers

12 24

Outer Ø

Weight

Fire load

mm

kg/km

MJ/m

10.3 10.8

115 125

1.03 1.28