A ronlowe

Page 1

Using Real Data to Guide Energy Efficiency at SickKids Hospital

Ron Lowe, Director of Facilities Operations Energy Matters Summit - May 28, 2012


History of Energy Savings – Atrium Site •  In 2005: •  11.7% savings; •  10,000 klbs steam

•  In 2006: •  44% savings; •  35,500 klbs steam

•  In 2010 vs 2006: •  10% savings; •  4,700 klbs steam


History of Energy Savings –Annex Site • In 2009; 2 million kWh annual electricity savings

• In 2009; 21,800 klbs steam savings (20.0%)


History of Energy Savings –McMaster Site •  In 2008: •  16.6% savings; •  3,100 klbs steam

•  In 2009: •  32.4% savings; •  6,100 klbs steam

•  In 2010: •  12.6% increase; •  1,500 klbs steam


2011 Hospital Benchmarking


Target Setting – Energy Cost Savings Potential (2011)

Electricity (ekWh/ft2) Hospitals

Base

Thermal (ekWh/ft2)

Cooling

Base

Heating

Total Energy (ekWh/ft2)

Actual Target Actual Target Actual Target Actual Target Actual SickKids Annex Site SickKids Atrium Site SickKids McMaster Site 4 5 6 7 8 9 10 11 12 13 14 15 16 17

18.9 33.1 35.4 25.6 29.1 16.1 29.7 28.4 17.3 21.0 23.7 26.1 13.7 15.0 23.5 24.7 14.9

18.9 20.2 25.2 20.2 13.8 13.8 20.2 20.2 13.8 20.2 20.2 20.2 13.7 13.8 19.5 20.2 14.9

1.9 4.0 7.0 3.9 1.2 1.1 3.0 3.8 2.0 4.3 3.8 3.0 1.6 1.9 3.7 4.0 0.2

1.9 2.8 2.8 2.8 1.2 1.1 2.8 2.8 1.6 2.8 2.8 2.8 1.6 1.6 2.2 2.8 0.2

> 25% savings potential

6.0 10.8 14.5 22.8 1.9 9.4 23.6 22.2 25.6 19.8 28.2 26.3 8.8 11.7 15.3 30.6 15.2

6.0 10.8 11.3 15.0 1.9 9.0 15.0 15.0 9.0 11.3 15.0 15.0 8.8 9.0 12.0 15.0 11.3

20.1 7.7 13.2 13.5 19.6 9.6 17.3 22.2 22.8 13.2 20.8 12.1 17.5 11.4 9.4 13.5 21.5

10.1 7.7 10.1 13.5 9.8 9.6 13.5 13.5 9.8 10.1 13.5 12.1 9.8 9.8 9.4 13.5 10.1

46.9 55.5 70.1 65.7 51.9 36.2 73.6 76.6 67.7 58.4 76.5 67.5 41.6 40.0 52.0 72.8 51.8

Target

Savings %

36.9 41.5 49.4 51.5 26.7 33.5 51.5 51.5 34.2 44.4 51.5 50.1 33.9 34.2 43.1 51.5 36.5

21.2% 25.3% 29.6% 21.7% 48.4% 7.3% 30.0% 32.8% 49.5% 24.0% 32.7% 25.8% 18.4% 14.6% 17.1% 29.2% 29.6%

Cost Savings ($) $626,271 $1,249,630 $366,734 $728,067 $659,797 $141,849 $898,813 $82,276 $76,923 $1,031,983 $458,685 $734,967 $182,002 $223,780 $855,484 $993,386 $220,166


Are we there yet?

Ø  Comprehensive energy audit - 2012 Ø  Expected savings: $1 - $2 Million per year Ø  Scope: Ø  Ventilation systems Ø  Steam system Ø  Heating & cooling systems Ø  Lighting systems Ø  Medical and office equipment Ø  Elevators Ø  Tenant energy use


Ventilation System Improvements


System Testing Identifies Inefficiencies

63,630 CFM; 100 HP

Test results highlight airflow and static pressure anomalies for correction by the project engineers


Targets Drive Continuous Improvement Guided by current best practice among Greening Health Care hospitals, SickKids is working towards energy targets below 40 ekWh/ sf for our two main sites, and below 50 ekWh/sf for McMaster


THANK-YOU!! For more information, contact: Ron Lowe Director, Facilities Operations ronald.lowe@sickkids.ca


Issuu converts static files into: digital portfolios, online yearbooks, online catalogs, digital photo albums and more. Sign up and create your flipbook.