Daikin Ductless R-32 Reference Guide

Page 1

2026 R-32: Single Zone, One to One - Heat Pumps (4-Wire) **Reference sheet only, not intended to replace engineering manuals, installation instructions or data sheets**

ENTRA™ SERIES

R-32 WALL MOUNT- HEAT PUMP Wireless Remote Included (p/n 2531835)

2/24/2026

*Must be registered within 60 days of install **5 years for commercial installations See Daikin 4-Wire, Single Head Unit Notes (Below)

Max System Charge DOES NOT exceed M1 (No A2L Mitigation Required)

***Cooling Operational Range 50⁰ - 114⁰ DB

Heating Operational Range 5⁰ - 65⁰ WB

R-32 Models: Replaced the R-410A, RXB_BXVJU w/ FTXB_BXVJU (R-32 Units ARE NOT cross compatible with R-410A Units) BTUH

Heat Pump

Wall Mounted

SEER2 EER2 HSPF2 COP

Line Set

9,000 12,000 18,000 24,000

RXC09AXVJU RXC12AXVJU RXC18AXVJU RXC24AXVJU

FTXC09AXVJU FTXC12AXVJU FTXC18AXVJU FTXC24AXVJU

18.00 11.00 18.00 8.50 18.00 10.50 18.00 10.50

1/4" x 3/8" 1/4" x 3/8" 1/4" x 1/2" 1/4" x 5/8"

Optional Wired Controls: Optional Wi-Fi Controls: Indoor Unit (H"xW"xD"): Outdoor Unit (H"xW"xD"):

9.00 9.00 9.00 9.00

3.60 3.30 3.30 3.40

Max Length MOCP (Total/Vertical) 66' / 33' 66' / 33' 99' / 33' 99' / 33'

15 15 20 20

NEEP (AHRI#)

M1 Cooling (AHRI 95⁰ F)

Cooling (Min/Max)

M1 Heating (AHRI 47⁰ F)

Heating (Min/Max)

M1 Heating (AHRI 17⁰ F)

213895727 213895723 213895724 213895725

9,000 12,000 18,100 22,400

4,400/10,200 4,400/13,300 6,900/20,000 6,900/24,200

9,400 11,300 18,000 23,000

4,400/13,000 4,400/16,400 5,800/22,500 5,800/27,300

5,600 7,100 11,000 12,500

M1 Heat/COP (5⁰ F DB/WB) 4,600 / 2.20 5,500 / 2.32 8,900 / 2.10 10,500 / 1.90

DTST-CWBSA-NI-B Daikin One+ / DTST-TOU-A Daikin One Touch (all DTST-C/T must order the DAPT-ONE-VMS Translation Adaptor) / DTST-LTE-LA-A Daikin One Lite (includes Translation Adapter) BRC51D61 Wired Controller (w/ req'd 32Ft. Connector cable)- See Application Chart for Compatibility AZAI6WSCDKB DKN Residential Cloud WiFi (S21) Low Ambient Operation: ***None- Unit will not operate in cooling below 50⁰ F AZAI6WSPDKC DKN Plus Interface (S21)- See Application Chart for Compatibility Wind Baffle: KPW937F4 (09 & 12) / KPW063B4E (18 & 24) 11-1/3 × 30-5/16 × 9-11/16 (09 & 12), 11-11/16 × 39-9/16 × 11-1/3 (18 & 24) Drain Pan Heater: KEH067A41E (09 & 12) / KEH063A4EA (18 & 24) 10 ft. min. length, additional charge required over 33 feet @ 0.18 oz/ft. 21-11/16 × 26-1/2 × 11-3/16 (09 & 12), 27-13/32 × 36-5/8 × 13-13/16 (18 & 24) Line Sets:

OTERRA™ SERIES

*Must be registered within 60 days of install **5 years for commercial installations See Daikin 4-Wire, Single Head Unit Notes (Below)

R-32 WALL MOUNT- HEAT PUMP (115V-1PH) Wireless Remote Included (p/n 2561958) Max System Charge DOES NOT exceed M1 (No A2L Mitigation Required) ***Cooling Operational Range 50⁰ - 115⁰ DB (09/12)

Heating Operational Range 5⁰ - 75⁰ DB

New 115V-1Ph , R-32 Models (R-32 Units ARE NOT cross compatible with R-410A Units) BTUH

Heat Pump

Wall Mounted

9,000 12,000

RXQ09ASBU9 RXQ12ASBU9

FTXQ09ASBU9 FTXQ12ASBU9

Optional S21 Adaptor: Optional Wired Controls: Optional Wi-Fi Controls: Indoor Unit (H"xW"xD"): Outdoor Unit (H"xW"xD"):

SEER2 EER2 HSPF2 COP 20.00 12.00 20.00 12.00

9.00 9.00

Line Set

3.51 1/4" x 3/8" 3.92 1/4" x 3/8"

Max Length MOCP (Total/Vertical) 115V 66' / 49' 66' / 49'

15 15

NEEP (AHRI#)

M1 Cooling (AHRI 95⁰ F)

Cooling (Min/Max)

M1 Heating (AHRI 47⁰ F)

Heating (Min/Max)

M1 Heating (AHRI 17⁰ F)

216504980 216504981

9,000 12,000

2,800/10,500 3,600/12,800

10,900 13,500

3,800/12,000 3,800/14,600

6,600 8,000

Condensate Lift Pumps: A2L / R-32 Systems Mitigation Requirements: Installation (Wiring): Installation (General):

(5⁰ F DB/WB) 7,600 / 1.90 9,300 / 2.10

KRP067A41E S21 Adaptor Kit (Must add S21 Adaptor Kit whenever utilizing Optional Wired / Wi-Fi Controls listed below). See Controls Application Chart for Compatibility . Daikin One +, Daikin One Touch and Daikin One Lite not compatible (awaiting certification). Consult w/Daikin Representative for any future applications. BRC073A6 Wired Controller (must include Connector Cable) / BRCW901A08 (26Ft.) or BRCW901A03 (10Ft.) Non-Plenum Rated / DACA-BRCW901A25 (26Ft.) or DACA-BRCW901A10 (10Ft.) Plenum Rated BRP084A61 Daikin One Home Wi-Fi Adaptor, AZAI6WSCDKB DKN Residential Cloud WiFi (S21) Low Ambient Operation: ***None- Unit will not operate in cooling below 50⁰ F AZAI6WSPDKC DKN Plus Interface (S21)- See Application Chart for Compatibility Wind Baffle: KPW937F4 (09 & 12) 11-1/4 × 30-5/16 × 8-3/4 (09 & 12) Drain Pan Heater: TBD (09 & 12) 10 ft. min. length, additional charge required over 50 feet @ 0.22 oz/ft. 21-15/16 × 26-9/16 × 11-3/16 (09 & 12) Line Sets:

Notes: All Daikin 4-Wire, Single Head Units: AHRI Certified Ratings: Cooling Min/Max Range: Heating Min/Max Range:

M1 Heat/COP

AHRI 210/240 - 2023 Using DOE 2023 M1 Test Procedures / 2024 UL-60335-2-40 Test Standards AHRI Certified Ratings w/ Indoor @ 80⁰F DB/67⁰F WB and Outdoor @ 95⁰F DB/75⁰F WB, 25 Ft. Pipe Length AHRI Certified Ratings w/ Indoor @ 70°F DB/60°F WB, Outdoor @ 47°F DB/43°F WB, 25 Ft. Pipe Length DACA-CP1-1 Aspen Mini Univolt Inline Pump / DACA-CP3-1 Sauermann Si30 Mini Inline Condensate Pump / DACA-CP4-1 Aspen Mini White (External) Univolt Pump Kit (or equal) ASHRAE 15.2 has established maximum design charge limits for A2L HVAC Systems. Any R-32 System with a full system refrigerant charge exceeding the M1 charge level of 4.050 lbs./1000 cu.ft., as specified by the safety standards, will require additional mitigation factors to be employed and/or room size restrictions. System charges not exceeding the M1 charge level will not require any room size restrictions or mitigation factors to be employed (see maximum charge - A2L limits tables this document) Use 4-Wire, 14AWG, Stranded, Non-Shielded Wire to Connect Outdoor to Indoor. Only Break L1 for proper condensate pump wiring (breaking L3 will result in a U4 Error Code). Mount outdoor units MINIMUM of 2" above anticipated snowfall. Always offer stand, disconnect, whip and pad. Wind Baffles recommended for all low temperature heating applications.

Typical Wiring (All 4 Wire Product):