Smithsonian NMAAHC Programming Study Vol. 5

Page 1

CRITICALDIMENSIONS

SUBMITTED

OuterHall,VisitorAmenities, Yes Shaping 0 Fixed Yes
Glasswall/viewontoMall TBD Accessible
NumberofOccupants 350 OFEOSpaceDimensions NA VisualPrivacy(full,partial,open) Full/Partial RoomName Auditorium/Theater ZoneRoomID A3.1 UnitPublicNon-CollectionSpace NetSquareFeet(NSF) 6,000 FloorLevel SUSTAINABILITYFEATURES TechnicalComment: PublicAddress
DATA/TELECOMMUNICATIONS Adjacencies
FunctionalDescription
Formusic,limiteddance,performance,film,lectures/discussionpanelpriority
Yes Multi SpecialEquipment/Artifact AcousticVibrationSensitivity Sensitivity Plant/CleanSteam 0 ProcessFiltration(Pre/Final/Other) Water 45%RH 0 30/65 ±2ºF HumidityHumidityDeviation(+/-) No 8Positive±15%RH min. 15CFM/person AirPressure(+/-) Change/HR Yes NCRegurlarlyOccupiedSpace 0 RoomHeight High ACOUSTICS
Separation/STC STC58-60 Equipment OperableOutsideAirWindows 0 MoveableRoomLength,Width,Shape FINISHES Temperature 76ºFSummer,71ºFWinter doorsSoundvestibulesorappropriatesoundrated 0 Yes TemperatureDeviations(+/-) TBD Walls tosensativespaceandshouldbelocatedawayfromnoisy,highintensityspaces.Theroomshouldbeoptimizedforspeechincluidng bestaidtheprojectionofvoicefromthepossiblestagelocationsintotheaudienceareas.Variableaccousticsshouldbeprovidedmusicalrecitalspace,dramatheatre,auditoriumandcinema.
Accessibilityoptimizeforallnecessaryfunctions.
vs.Private SpecialExhaust Rating
Accoustical CRITERIA
HVAC No 0 No Yes No Yes No Voice/Data An association of Davis Brody Bond and The Freelon Group Architects Lord Cultural Resources and Amaze Design
FURNITURE/EQUIPMENT
Allowavolume/seatofaround100-175cubicfeetandensurereverberation
Requirement:
Optimizedforaspeechandareverbationtime,thiswillmostlikelyentailabsorptivefinsihesonthewallsandceiling Accoustical Sloped/Terraced Ceiling
underPlumbing,recommendstagelightingunderElectricalLighting.Pleaserefertostructuralnarrativeformoreinformationonstructural
Smithsonian Institution National Museum of African American History and Culture VOLUME V Room Data Sheets
BY: FREELON BOND January 30, 2009

Pre-design Document:

Smithsonian Institution

National Museum of African American History and Culture

VOLUME I

A Preamble

B Introduction and Executive Summary

C Pre-design and Programming

VOLUME II

A Visitation Estimate

B Audience Research

C Public Engagement

D Collections Storage Plan

E General Museum Requirements

F Exhibition Master Plan

VOLUME III

A Existing Site Conditions

B Geotechnical Analysis

C Vehicular and Pedestrian Traffic

D Site Analysis

VOLUME IV

A Facility Program

B Engineering Systems

C Sustainable Design

D Accessibility

E Security

F Cost Estimates

VOLUME V

A Room Data Sheets

VOLUME VI

A Appendix

V Contents A Room Data Sheets

01 Introduction

02 Room Data Sheets

Volume
A Room Data Sheets
Smithsonian Institution National Museum of African American History and Culture 8

Each space identified in the Space List (Volume IV, A, 02) has a corresponding Room Data Sheet located in Volume V. The Room Data Sheets provide additional detailed information about each programmed space in the museum. This additional data starts with the Zone Designation and Zone I.D. at the top of the page, along with the organizational unit and room name. Additional information lists the assignable square footage, general location in the building, adjacencies, and technical data including sustainability features, acoustical properties, and details regarding engineering system requirements.

While every space in the Space List has a corresponding Room Data Sheet, there is some information on each sheet that remains blank because 1), the information is not currently available, and/or 2), the information is irrelevant to the space.

There are a number of spaces in the Program List for which there are no assigned users at this time. In such cases, the information found on the room data sheet has been filled in based on SI or industry standards and best practices as determined by the Consulting Team.

9 Room Data Sheets | FREELON BOND 01
Introduction
Smithsonian Institution National Museum of African American History and Culture 10

Room Data Sheets

The Room Data Sheets are included on the following pages.

11 Room Data Sheets | FREELON BOND
02

with ADA/ABAAG (2004) citations is required for accessibility. SI also requires compliance with SI Accessibility Guidelines and the IBC. Comparisons should be made and the more stringent requirement followed for design purposes. See Accessibility Narrative for additional information.

CRITICAL DIMENSIONS

Smithsonian Institution National Museum of African American History and Culture 12 Infrastructure Only 0 Other Amenities Deionized Water Vacuum 0 Speakers 0 FIRE ALARM Smoke Detection 0 Wet Sprinkler Special Waste Dry Sprinkler Pre-Action Sprinkler 0 FIRE PROTECTION 0 Considerations for Water 0 0 Floor Drains Floor Sink Grey/Blackwater Piping 0 0 0 0 Protected Hot/Cold 0 0 Recycled Water Supply (treated) 0 0 Public Address Audio Compressed Air Audio Visual Requirements 0 Hot/Cold Water Task Light No No 0 Plant/Clean Steam 0 Acoustic Sensitivity 0 Vibration Sensitivity Special Equipment/Artifact Sensitivity PLUMBING Target Illuminance (IES 9th Edition) Daylight Sensor 5-10 FC Exhibit Light No Power Density (AHSRAE 2004) Exempt Temperature Deviations (+/-) 0 No Process Water UPS Switched Receptacles Dimming No Humidity 0 0 Other Humidity Deviation (+/-) 0 0 0 Outside Air Single/Multi-Level Switching 0 Emergency/Standby Power 0 0 Multi Occupancy Sensor Special Exhaust Sub-metering & Feedback Displays Filtration (Pre/Final/Other) Voice/Data DATA/TELECOMMUNICATIONS 0 0 SECURITY 0 0 Floor Loading/Point Loads DAYLIGHTING 0 0 Shading Considerations Top/Side Lighting 0 0 STRUCTURAL 0 0 Refer to information indicated in Volume IV, Section E Open 0 Technical Comment: Exterior Landmarks Assignable Square Feet (ASF) OFEO Space Dimensions 0 Organizational Unit Other Interior Glazing 0 0 0 No Weather Resistent Ceiling CRITICAL FINISHES 0 0 0 ELECTRICAL ARCHITECTURAL This room data sheet
not comprehensive
nature.
features may not have been available and was intentionally left blank. Zone Room ID O Room Name 0 Functional Description 0 Outdoor Areas NA Number of Occupants NA Visual Privacy (full, partial, open) Zone Designation Zone O Room Height 0 LEED NC Regurlarly Occupied Space 0 Base ACOUSTICS Equipment Hardware/STC Rating 0 NRC 0 0 0 Plug Loads Air Change/ HR Walls HVAC ENGINEERING CRITERIA Temperature Lighting 0 0 110v, 20a, 1ph 0 0 Power 0 0 Pressure (+/-) 0 Floor Operable Windows Separation/STC FURNITURE/EQUIPMENT Moveable 0 Fixed RT60 & Shaping 0 NA
Plaza SUSTAINABILITY FEATURES Adjacencies Accessibility
Floor Level 0 Room Length, Width, Shape Open
is
in
Information regarding specific room
Compliance
Requirement:
vs. Private

with ADA/ABAAG (2004) citations is required for accessibility. SI also requires compliance with SI Accessibility Guidelines and the IBC. Comparisons should be made and the more stringent requirement followed for design purposes. See Accessibility Narrative for additional information.

CRITICAL DIMENSIONS

13 Room Data Sheets | FREELON BOND Infrastructure Only 0 Other Amenities Deionized Water Vacuum 0 Speakers 0 FIRE ALARM Smoke Detection 0 Wet Sprinkler Special Waste Dry Sprinkler Pre-Action Sprinkler 0 FIRE PROTECTION 0 Considerations for Water 0 0 Floor Drains Floor Sink Grey/Blackwater Piping 0 0 0 0 Protected Hot/Cold 0 0 Recycled Water Supply (treated) 0 0 Public Address Audio Compressed Air Audio Visual Requirements Yes Hot/Cold Water Task Light No No 0 Plant/Clean Steam 0 Acoustic Sensitivity 0 Vibration Sensitivity Special Equipment/Artifact Sensitivity PLUMBING Target Illuminance (IES 9th Edition) Daylight Sensor 5 FC Exhibit Light No Power Density (AHSRAE 2004) 0.2 W/ft² Temperature Deviations (+/-) 0 No Process Water UPS Switched Receptacles Dimming No Humidity 0 0 Other Humidity Deviation (+/-) 0 0 0 Outside Air Single/Multi-Level Switching 0 Emergency/Standby Power 0 0 Multi Occupancy Sensor Special Exhaust Sub-metering & Feedback Displays Filtration (Pre/Final/Other) Voice/Data DATA/TELECOMMUNICATIONS 0 0 SECURITY 0 0 Floor Loading/Point Loads DAYLIGHTING 0 0 Shading Considerations Top/Side Lighting 0 0 STRUCTURAL 0 0 Refer to information indicated in Volume IV, Section E Partial 0 Technical Comment: Park/Garden Assignable Square Feet (ASF) OFEO Space Dimensions 0 Organizational Unit Other Interior Glazing 0 0 No No Weather Resistent FootpathsCeiling CRITICAL FINISHES 0 0 0 ELECTRICAL ARCHITECTURAL This room data sheet
not comprehensive
nature. Information regarding specific room features may not have been available and was intentionally left blank. Zone Room ID O Room Name 0 Functional Description 0 Outdoor Areas TBD Number of Occupants TBD Visual Privacy (full, partial, open) Zone Designation Zone O Room Height 0 LEED NC Regurlarly Occupied Space 0 Base ACOUSTICS Equipment Hardware/STC Rating 0 NRC 0 0 0 Plug Loads Air Change/ HR Walls HVAC ENGINEERING CRITERIA Temperature Lighting 0 0 110v, 20a, 1ph Yes 0 Power 0 0 Pressure (+/-) 0 Floor Operable Windows Separation/STC FURNITURE/EQUIPMENT Moveable Yes Fixed RT60 & Shaping 0 TBD
TBD
is
in
Compliance
Requirement: Floor Level 0 Room Length,
Open
SUSTAINABILITY FEATURES Adjacencies Accessibility
Width, Shape
vs. Private

This room data sheet is not comprehensive in nature. Information regarding specific room features may not have been available and was intentionally left

SUSTAINABILITY FEATURES Adjacencies

with ADA/ABAAG (2004) citations is required for accessibility. SI also requires compliance with SI Accessibility Guidelines and the IBC. Comparisons should be made and the more stringent requirement followed for design purposes. See Accessibility Narrative for additional information.

off, Car/Handicap Parking/Threshold Experience/Vestibule

Please refer to structural narrative for more information on structural requirements.

CRITICAL DIMENSIONS

Smithsonian Institution National Museum of African American History and Culture 14 Infrastructure Only 0 Other Amenities Deionized Water Vacuum 0 Speakers 0 FIRE ALARM Smoke Detection 0 Wet Sprinkler Special Waste Dry Sprinkler Pre-Action Sprinkler 0 FIRE PROTECTION 0 Considerations for Water 0 0 Floor Drains Floor Sink Grey/Blackwater Piping 0 0 0 0 Protected Hot/Cold 0 0 Recycled Water Supply (treated) 0 0 Public Address Audio Compressed Air Audio Visual Requirements Yes Hot/Cold Water Task Light No No 0 Plant/Clean Steam 0 Acoustic Sensitivity 0 Vibration Sensitivity Special Equipment/Artifact Sensitivity PLUMBING Target Illuminance (IES 9th Edition) Daylight Sensor 5 FC Exhibit Light No Power Density (AHSRAE 2004) 0.2 W/ft² Temperature Deviations (+/-) 0 No Process Water UPS Switched Receptacles Dimming No Humidity 0 0 Other Humidity Deviation (+/-) 0 0 0 Outside Air Single/Multi-Level Switching 0 Emergency/Standby Power 0 0 Multi Occupancy Sensor Special Exhaust Sub-metering & Feedback Displays Filtration (Pre/Final/Other) Voice/Data DATA/TELECOMMUNICATIONS Audio playback system. Connection to Interior 0 SECURITY 0 7.5 kPa/26.7 kN Floor Loading/Point Loads DAYLIGHTING 0 0 Shading Considerations Top/Side Lighting 0 0 STRUCTURAL 0Refer to information indicated in Volume IV, Section E Open 0 Technical Comment: Plaza Assignable Square Feet (ASF) OFEO Space Dimensions 0 Organizational Unit Other Interior Glazing 0 0 None None Vehicle Loads/Weather ResistantCeiling CRITICAL FINISHES 0 0
ELECTRICAL ARCHITECTURAL
blank. Zone Room ID O Room Name 0 Functional Description 0 Outdoor Areas TBD Number of Occupants Large Groups Visual Privacy (full, partial, open) Zone Designation Zone O Room Height 0 LEED NC Regurlarly Occupied Space 0 Base ACOUSTICS Equipment Hardware/STC Rating 0 NRC 0 0 0 Plug Loads Air Change/ HR Walls HVAC ENGINEERING CRITERIA Temperature Lighting 0 0 110v, 20a, 1ph Yes 0 Power 0 0 Pressure (+/-) 0 Floor Operable Windows Separation/STC FURNITURE/EQUIPMENT Moveable 0 Fixed RT60 & Shaping 0 TBD Compliance
Drop
Accessibility Requirement: Floor Level 0 Room Length, Width, Shape Open
vs. Private

Compliance with ADA/ABAAG (2004) citations is required for accessibility. SI also requires compliance with SI Accessibility Guidelines and the IBC. Comparisons should be made and the more stringent requirement followed for design purposes. See Accessibility Narrative for additional information.

CRITICAL DIMENSIONS

15 Room Data Sheets | FREELON BOND Infrastructure Only 0 Other Amenities Deionized Water Vacuum 0 Speakers 0 FIRE ALARM Smoke Detection 0 Wet Sprinkler Special Waste Dry Sprinkler Pre-Action Sprinkler 0 FIRE PROTECTION 0 Considerations for Water 0 0 Floor Drains Floor Sink Grey/Blackwater Piping 0 0 0 0 Protected Hot/Cold 0 0 Recycled Water Supply (treated) 0 0 Public Address Audio Compressed Air Audio Visual Requirements 0 Hot/Cold Water Task Light No No 0 Plant/Clean Steam 0 Acoustic Sensitivity 0 Vibration Sensitivity Special Equipment/Artifact Sensitivity PLUMBING Target Illuminance (IES 9th Edition) Daylight Sensor 1 FC Exhibit Light No Power Density (AHSRAE 2004) .15 W/ft² Temperature Deviations (+/-) 0 No Process Water UPS Switched Receptacles Dimming No Humidity 0Other Humidity Deviation (+/-) 0 0 0 Outside Air Single/Multi-Level Switching 0 Emergency/Standby Power 0 0 Single Occupancy Sensor Special Exhaust Sub-metering & Feedback Displays Filtration (Pre/Final/Other) Voice/Data DATA/TELECOMMUNICATIONS Yes 0 SECURITY 0 0 Floor Loading/Point Loads DAYLIGHTING 0 0 Shading Considerations Top/Side Lighting 0 0 STRUCTURAL 0 0 Refer to information indicated in Volume IV, Section E Open 0 Technical Comment: Parking Assignable Square Feet (ASF) OFEO Space Dimensions 0 Organizational Unit Other Interior Glazing 0 0 0 0 Vehicle Loads/Weather ResistentCeiling CRITICAL FINISHES 0 0 0 ELECTRICAL ARCHITECTURAL This room data sheet
not comprehensive in nature. Information regarding specific room features may not have been available and was intentionally left blank. Zone Room ID O Room Name 0 Functional Description VIP, Bus Drop Off, No Underground, Minimal Parking Outdoor Areas NA Number of Occupants NA Visual Privacy (full, partial, open) Zone Designation Zone O Room Height 0 LEED NC Regurlarly Occupied Space 0 Base ACOUSTICS Equipment Hardware/STC Rating 0 NRC0 0 Plug Loads Air Change/ HR Walls HVAC ENGINEERING CRITERIA Temperature Lighting 0 0 110v, 20a, 1ph 0 0 Power 0 0 Pressure (+/-) 0 Floor Operable Windows Separation/STC FURNITURE/EQUIPMENT Moveable 0 Fixed RT60 & Shaping 0 TBD
is
TBD
Requirement: Floor Level 0 Room Length,
Open
SUSTAINABILITY FEATURES Adjacencies Accessibility
Width, Shape
vs. Private

Compliance with ADA/ABAAG (2004) citations is required for accessibility. SI also requires compliance with SI Accessibility Guidelines and the IBC. Comparisons should be made and the more stringent requirement followed for design purposes. See Accessibility Narrative for additional information.

CRITICAL DIMENSIONS

Smithsonian Institution National Museum of African American History and Culture 16 Infrastructure Only 0 Other Amenities Deionized Water Vacuum 0 Speakers 0 FIRE ALARM Smoke Detection 0 Wet Sprinkler Special Waste Dry Sprinkler Pre-Action Sprinkler 0 FIRE PROTECTION 0 Considerations for Water 0 0 Floor Drains Floor Sink Grey/Blackwater Piping 0 0 0 0 Protected Hot/Cold 0 0 Recycled Water Supply (treated) 0 0 Public Address Audio Compressed Air Audio Visual Requirements 0 Hot/Cold Water Task Light No No 0 Plant/Clean Steam 0 Acoustic Sensitivity 0 Vibration Sensitivity Special Equipment/Artifact Sensitivity PLUMBING Target Illuminance (IES 9th Edition) Daylight Sensor 5 FC Exhibit Light No Power Density (AHSRAE 2004) 30 W/if door width Temperature Deviations (+/-) 0 No Process Water UPS Switched Receptacles Dimming No Humidity 0 0 Other Humidity Deviation (+/-) 0 0 0 Outside Air Single/Multi-Level Switching 0 Emergency/Standby Power 0 0 Single Occupancy Sensor Special Exhaust Sub-metering & Feedback Displays Filtration (Pre/Final/Other) Voice/Data DATA/TELECOMMUNICATIONS 0 0 SECURITY 0 0 Floor Loading/Point Loads DAYLIGHTING 0 0 Shading Considerations Top/Side Lighting 0 0 STRUCTURAL 0 0 Refer to information indicated in Volume IV, Section E Open 0 Technical Comment: Pedestrian Access, Handicap Parking, Drop Off Assignable Square Feet (ASF) OFEO Space Dimensions 0 Organizational Unit Other Interior Glazing 0 0 No No Vehicle Loads/Weather ResistentCeiling CRITICAL FINISHES 0 0 0 ELECTRICAL ARCHITECTURAL This room data sheet
not comprehensive
nature. Information regarding specific room features may not have been available and was intentionally left blank. Zone Room ID O Room Name 0 Functional Description Space for Pedestrian Queuing Outdoor Areas NA Number of Occupants NA Visual Privacy (full, partial, open) Zone Designation Zone O Room Height 0 LEED NC Regurlarly Occupied Space 0 Base ACOUSTICS Equipment Hardware/STC Rating 0 NRC 0 0 0 Plug Loads Air Change/ HR Walls HVAC ENGINEERING CRITERIA Temperature Lighting 0 0 110v, 20a, 1ph 0 0 Power 0 0 Pressure (+/-) 0 Floor Operable Windows Separation/STC FURNITURE/EQUIPMENT Moveable No Fixed RT60 & Shaping 0 TBD
TBD
Adjacencies
Requirement: Floor Level 0 Room Length,
Open vs. Private
is
in
SUSTAINABILITY FEATURES
Accessibility
Width, Shape

SUSTAINABILITY FEATURES Adjacencies

vs. Private

Compliance with ADA/ABAAG (2004) citations is required for accessibility. SI also requires compliance with SI Accessibility Guidelines and the IBC. Comparisons should be made and the more stringent requirement followed for design purposes. See Accessibility Narrative for additional information. Plaza/Threshold Experience

CRITICAL DIMENSIONS

17 Room Data Sheets | FREELON BOND Infrastructure Only 0 Other Amenities Deionized Water Vacuum 0 Speakers 0 FIRE ALARM Smoke Detection 0 Wet Sprinkler Special Waste Dry Sprinkler Pre-Action Sprinkler 0 FIRE PROTECTION 0 Considerations for Water 0 0 Floor Drains Floor Sink Grey/Blackwater Piping 0 0 0 0 Protected Hot/Cold 0 0 Recycled Water Supply (treated) 0 0 Public Address Audio Compressed Air Audio Visual Requirements 0 Hot/Cold Water Task Light No No 0 Plant/Clean Steam 0 Acoustic Sensitivity 0 Vibration Sensitivity Special Equipment/Artifact Sensitivity PLUMBING Target Illuminance (IES 9th Edition) Daylight Sensor 5 FC Exhibit Light No Power Density (AHSRAE 2004) 30 W/if door width Temperature Deviations (+/-) 0 No Process Water UPS Switched Receptacles Dimming No Humidity 0 0 Other Humidity Deviation (+/-) 0 0 0 Outside Air Single/Multi-Level Switching 0 Emergency/Standby Power 0 0 Single Occupancy Sensor Special Exhaust Sub-metering & Feedback Displays Filtration (Pre/Final/Other) Voice/Data DATA/TELECOMMUNICATIONS 0 0 SECURITY 0 0 Floor Loading/Point Loads DAYLIGHTING 0 0 Shading Considerations Top/Side Lighting 0 0 STRUCTURAL 0 0 Refer to information indicated in Volume IV, Section E Open 0 Technical Comment: Pedestrian Drop-off, Car Assignable Square Feet (ASF) OFEO Space Dimensions 0 Organizational Unit Other Interior Glazing 0 0 No No Vehicle Loads/Weather ResistentCeiling CRITICAL FINISHES 0 0 0 ELECTRICAL ARCHITECTURAL This room data sheet is not comprehensive in nature. Information regarding specific room features may not have been available and was intentionally left blank. Zone Room ID O Room Name 0 Functional Description 0 Outdoor Areas NA Number of Occupants NA Visual Privacy (full, partial, open) Zone Designation Zone O Room Height 0 LEED NC Regurlarly Occupied Space 0 Base ACOUSTICS Equipment Hardware/STC Rating 0 NRC 0 0 0 Plug Loads Air Change/ HR Walls HVAC ENGINEERING CRITERIA Temperature Lighting 0 0 110v, 20a, 1ph 0 0 Power 0 0 Pressure (+/-) 0 Floor Operable Windows Separation/STC FURNITURE/EQUIPMENT Moveable No Fixed RT60 & Shaping 0 Street
Requirement: Floor Level 0 Room Length,
Open
Accessibility
Width, Shape

Experience SUSTAINABILITY FEATURES Adjacencies Accessibility Requirement:

vs. Private

Compliance with ADA/ABAAG (2004) citations is required for accessibility. SI also requires compliance with SI Accessibility Guidelines and the IBC. Comparisons should be made and the more stringent requirement followed for design purposes. See 2004 ADAAG Chapter 6 Plumbing Elements and Facilities.See Accessibility Narrative for additional information.

CRITICAL DIMENSIONS

Width, Shape

Smithsonian Institution National Museum of African American History and Culture 18 Infrastructure Only 0 Other Amenities Deionized Water Vacuum 0 Speakers 0 FIRE ALARM Smoke Detection 0 Wet Sprinkler Special Waste Dry Sprinkler Pre-Action Sprinkler 0 FIRE PROTECTION 0 Considerations for Water 0 0 Floor Drains Floor Sink Grey/Blackwater Piping 0 0 0 0 Protected Hot/Cold 0 0 Recycled Water Supply (treated) 0 0 Public Address Audio Compressed Air Audio Visual Requirements 0 Hot/Cold Water Task Light No No 0 Plant/Clean Steam 0 Acoustic Sensitivity 0 Vibration Sensitivity Special Equipment/Artifact Sensitivity PLUMBING Target Illuminance (IES 9th Edition) Daylight Sensor 5 FC Exhibit Light No Power Density (AHSRAE 2004) 30 W/if door width Temperature Deviations (+/-) 0 No Process Water UPS Switched Receptacles Dimming No Humidity 0 0 Other Humidity Deviation (+/-) 0 0 0 Outside Air Single/Multi-Level Switching 0 Emergency/Standby Power 0 0 Single Occupancy Sensor Special Exhaust Sub-metering & Feedback Displays Filtration (Pre/Final/Other) Voice/Data DATA/TELECOMMUNICATIONS 0 0 SECURITY 0 0 Floor Loading/Point Loads DAYLIGHTING 0 0 Shading Considerations Top/Side Lighting Possible voice - audio amplification 0 STRUCTURAL 0 0 Refer to information indicated in Volume IV, Section E Open 0 Technical Comment: Pedestrian Drop-off, Coach Assignable Square Feet (ASF) OFEO Space Dimensions 0 Organizational Unit Other Interior Glazing 0 0 No No Vehicle Loads/Weather ResistentCeiling CRITICAL FINISHES 0 0 0 ELECTRICAL ARCHITECTURAL This
sheet
available
left blank. Zone Room ID O Room Name 0 Functional Description 0 Outdoor Areas NA Number of Occupants NA Visual Privacy (full, partial, open) Zone Designation Zone O Room Height 0 LEED NC Regurlarly Occupied Space 0 Base ACOUSTICS Equipment Hardware/STC Rating 0 NRC 0 0 0 Plug Loads Air Change/ HR Walls HVAC ENGINEERING CRITERIA Temperature Lighting 0 0 110v, 20a, 1ph 0 0 Power 0 0 Pressure (+/-) 0 Floor Operable Windows Separation/STC FURNITURE/EQUIPMENT Moveable No Fixed RT60 & Shaping 0 Street
room data
is not comprehensive in nature. Information regarding specific room features may not have been
and was intentionally
Floor Level 0 Room
Open
Plaza/Threshold
Length,

Compliance with ADA/ABAAG (2004) citations is required for accessibility. SI also requires compliance with SI Accessibility Guidelines and the IBC. Comparisons should be made and the more stringent requirement followed for design purposes. See Accessibility Narrative for additional information.

CRITICAL DIMENSIONS

19 Room Data Sheets | FREELON BOND Infrastructure Only 0 Other Amenities Deionized Water Vacuum 0 Speakers 0 FIRE ALARM Smoke Detection 0 Wet Sprinkler Special Waste Dry Sprinkler Pre-Action Sprinkler 0 FIRE PROTECTION 0 Considerations for Water 0 0 Floor Drains Floor Sink Grey/Blackwater Piping 0 0 0 0 Protected Hot/Cold 0 0 Recycled Water Supply (treated) 0 0 Public Address Audio Compressed Air Audio Visual Requirements 0 Hot/Cold Water Task Light 0 0 0 Plant/Clean Steam 0 Acoustic Sensitivity 0 Vibration Sensitivity Special Equipment/Artifact Sensitivity PLUMBING Target Illuminance (IES 9th Edition) Daylight Sensor 0 Exhibit Light 0 Power Density (AHSRAE 2004) 0 Temperature Deviations (+/-) 0 0 Process Water UPS Switched Receptacles Dimming 0 Humidity 0 0 Other Humidity Deviation (+/-) 0 0 0 Outside Air Single/Multi-Level Switching 0 Emergency/Standby Power 0 0 0 Occupancy Sensor Special Exhaust Sub-metering & Feedback Displays Filtration (Pre/Final/Other) Voice/Data DATA/TELECOMMUNICATIONS Voice 0 SECURITY 0 0 Floor Loading/Point Loads DAYLIGHTING 0 0 Shading Considerations Top/Side Lighting Possible voice - audio amplification 0 STRUCTURAL 0 0 Refer to information indicated in Volume IV, Section E 0 0 Technical Comment: VIP Drop Off Assignable Square Feet (ASF) OFEO Space Dimensions 0 Organizational Unit Other Interior Glazing 0 0 0 0 0 Ceiling CRITICAL FINISHES 0 0 0 ELECTRICAL ARCHITECTURAL
room data sheet
not comprehensive
nature.
may not have been available and was intentionally left blank. Zone Room ID O Room Name 0 Functional Description 0 Outdoor Areas NA Number of Occupants NA Visual Privacy (full, partial, open) Zone Designation Zone O Room Height 0 LEED NC Regurlarly Occupied Space 0 Base ACOUSTICS Equipment Hardware/STC Rating 0 NRC 0 0 0 Plug Loads Air Change/ HR Walls HVAC ENGINEERING CRITERIA Temperature Lighting 0 0 110v, 20a, 1ph 0 0 Power 0 0 Pressure (+/-) 0 Floor Operable Windows Separation/STC FURNITURE/EQUIPMENT Moveable 0 Fixed RT60 & Shaping 0 Street
0 SUSTAINABILITY
Requirement: Floor Level 0 Room Length, Width, Shape Open
This
is
in
Information regarding specific room features
FEATURES Adjacencies Accessibility
vs. Private

SUSTAINABILITY FEATURES

vs. Private

Compliance with ADA/ABAAG (2004) citations is required for accessibility. SI also requires compliance with SI Accessibility Guidelines and the IBC. Comparisons should be made and the more stringent requirement followed for design purposes. See Accessibility Narrative for additional information. Do Not Face White House, VIP/Donor Lounge/Special Events/Café

CRITICAL DIMENSIONS

Width, Shape

Smithsonian Institution National Museum of African American History and Culture 20 Infrastructure Only 0 Other Amenities Deionized Water Vacuum 0 Speakers 0 FIRE ALARM Smoke Detection 0 Wet Sprinkler Special Waste Dry Sprinkler Pre-Action Sprinkler 0 FIRE PROTECTION 0 Considerations for Water 0 0 Floor Drains Floor Sink Grey/Blackwater Piping 0 0 0 0 Protected Hot/Cold 0 0 Recycled Water Supply (treated) 0 0 Public Address Audio Compressed Air Audio Visual Requirements 0 Hot/Cold Water Task Light 0 0 0 Plant/Clean Steam 0 Acoustic Sensitivity 0 Vibration Sensitivity Special Equipment/Artifact Sensitivity PLUMBING Target Illuminance (IES 9th Edition) Daylight Sensor 0 Exhibit Light 0 Power Density (AHSRAE 2004) 0 Temperature Deviations (+/-) 0 0 Process Water UPS Switched Receptacles Dimming 0 Humidity 0 0 Other Humidity Deviation (+/-) 0 0 0 Outside Air Single/Multi-Level Switching 0 Emergency/Standby Power 0 0 0 Occupancy Sensor Special Exhaust Sub-metering & Feedback Displays Filtration (Pre/Final/Other) Voice/Data DATA/TELECOMMUNICATIONS 0 0 SECURITY 0 0 Floor Loading/Point Loads DAYLIGHTING 0 0 Shading Considerations Top/Side Lighting 0 0 STRUCTURAL 0 0 Refer to information indicated in Volume IV, Section E 0 0 Technical Comment: Terraces - Levels Assignable Square Feet (ASF) OFEO Space Dimensions 0 Organizational Unit Other Interior Glazing 0 0 0 0 0 Ceiling CRITICAL FINISHES 0 0 0 ELECTRICAL ARCHITECTURAL This room data sheet is not comprehensive in nature. Information regarding specific room features may not have been available and was intentionally left blank. Zone Room ID O Room Name 0 Functional Description Not @ Ground Level Outdoor Areas TBD Number of Occupants TBD Visual Privacy (full, partial, open) Zone Designation Zone O Room Height 0 LEED NC Regurlarly Occupied Space 0 Base ACOUSTICS Equipment Hardware/STC Rating 0 NRC 0 0 0 Plug Loads Air Change/ HR Walls HVAC ENGINEERING CRITERIA Temperature Lighting 0 0 110v, 20a, 1ph 0 0 Power 0 0 Pressure (+/-) 0 Floor Operable Windows Separation/STC FURNITURE/EQUIPMENT Moveable 0 Fixed RT60 & Shaping 0 Roof
Requirement: Floor Level 0 Room Length,
Open
Adjacencies Accessibility

Accessibility Requirement:

Adjacencies

SUSTAINABILITY FEATURES

vs. Private

Compliance with ADA/ABAAG (2004) citations is required for accessibility. SI also requires compliance with SI Accessibility Guidelines and the IBC. Comparisons should be made and the more stringent requirement followed for design purposes. See Accessibility Narrative for additional information.

Pump/Riser Room

CRITICAL DIMENSIONS

21 Room Data Sheets | FREELON BOND Infrastructure Only 0 Other Amenities Deionized Water Vacuum 0 Speakers 0 FIRE ALARM Smoke Detection 0 Wet Sprinkler Special Waste Dry Sprinkler Pre-Action Sprinkler 0 FIRE PROTECTION 0 Considerations for Water 0 0 Floor Drains Floor Sink Grey/Blackwater Piping 0 0 0 0 Protected Hot/Cold 0 0 Recycled Water Supply (treated) 0 0 Public Address Audio Compressed Air Audio Visual Requirements 0 Hot/Cold Water Task Light No No 0 Plant/Clean Steam 0 Acoustic Sensitivity 0 Vibration Sensitivity Special Equipment/Artifact Sensitivity PLUMBING Target Illuminance (IES 9th Edition) Daylight Sensor 5 FC Exhibit Light No Power Density (AHSRAE 2004) 30 W/If of door width Temperature Deviations (+/-) 0 No Process Water UPS Switched Receptacles Dimming No Humidity 0 0 Other Humidity Deviation (+/-) 0 0 0 Outside Air Single/Multi-Level Switching 0 Emergency/Standby Power 0 0 Single Occupancy Sensor Special Exhaust Sub-metering & Feedback Displays Filtration (Pre/Final/Other) Voice/Data DATA/TELECOMMUNICATIONS Yes 0 SECURITY 0 0 Floor Loading/Point Loads DAYLIGHTING 0 0 Shading Considerations Top/Side Lighting 0 0 STRUCTURAL 0 0 Refer to information indicated in Volume IV, Section E Open 0 Technical Comment: Emergency Response Entrance/Access Assignable Square Feet (ASF) OFEO Space Dimensions 0 Organizational Unit Other Interior Glazing 0 0 No Key Box Vehicle Loads/Weather ResistentCeiling CRITICAL FINISHES 0 0 0 ELECTRICAL ARCHITECTURAL This room data sheet is not comprehensive in nature. Information regarding specific room features may not have been available and was intentionally left blank. Zone Room ID O Room Name 0 Functional Description 0 Outdoor Areas TBD Number of Occupants NA Visual Privacy (full, partial, open) Zone Designation Zone O Room Height 0 LEED NC Regurlarly Occupied Space 0 Base ACOUSTICS Equipment Hardware/STC Rating 0 NRC 0 0 0 Plug Loads Air Change/ HR Walls HVAC ENGINEERING CRITERIA Temperature Lighting 0 0 110v, 20a, 1ph 0 0 Power 0 0 Pressure (+/-) 0 Floor Operable Windows Separation/STC FURNITURE/EQUIPMENT Moveable No Fixed RT60 & Shaping 0 Ground
Fire
Floor Level 20ft. Width for Emergency Vehicles Room Length,
Open
Width, Shape

Adjacencies

SUSTAINABILITY FEATURES

Compliance with ADA/ABAAG (2004) citations is required for accessibility. SI also requires compliance with SI Accessibility Guidelines and the IBC. Comparisons should be made and the more stringent requirement followed for design purposes. See Accessibility Narrative for additional information.

Plaza/Vestibule/Threshold Experience/Interior Courtyard

CRITICAL DIMENSIONS

Smithsonian Institution National Museum of African American History and Culture 22 Infrastructure Only 0 Other Amenities Deionized Water Vacuum 0 Speakers 0 FIRE ALARM Smoke Detection 0 Wet Sprinkler Special Waste Dry Sprinkler Pre-Action Sprinkler 0 FIRE PROTECTION 0 Considerations for Water 0 0 Floor Drains Floor Sink Grey/Blackwater Piping 0 0 0 0 Protected Hot/Cold 0 0 Recycled Water Supply (treated) 0 0 Public Address Audio Compressed Air Audio Visual Requirements 0 Hot/Cold Water Task Light No No 0 Plant/Clean Steam 0 Acoustic Sensitivity 0 Vibration Sensitivity Special Equipment/Artifact Sensitivity PLUMBING Target Illuminance (IES 9th Edition) Daylight Sensor 5 FC Exhibit Light No Power Density (AHSRAE 2004) 1.25 W/ft² Temperature Deviations (+/-) 0 No Process Water UPS Switched Receptacles Dimming No Humidity 0 0 Other Humidity Deviation (+/-) 0 0 0 Outside Air Single/Multi-Level Switching 0 Emergency/Standby Power 0 0 Single Occupancy Sensor Special Exhaust Sub-metering & Feedback Displays Filtration (Pre/Final/Other) Voice/Data DATA/TELECOMMUNICATIONS 0 0 SECURITY 0 0 Floor Loading/Point Loads DAYLIGHTING 0 0 Shading Considerations Top/Side Lighting Audio Playback System 0 STRUCTURAL 0 0 Refer to information indicated in Volume IV, Section E Open Inside/outside space Technical Comment: Threshold Experience Assignable Square Feet (ASF) OFEO Space Dimensions 0 Organizational Unit Other Interior Glazing Partial Weather Cover 0 No No Weather Resistent Ceiling CRITICAL FINISHES 0 0 0 ELECTRICAL ARCHITECTURAL This room data sheet is not comprehensive in nature. Information regarding specific room features may not have been available and was intentionally left blank. Zone Room ID O Room Name 0 Functional Description 0 Outdoor Areas TBD Number of Occupants Large Groups Visual Privacy (full, partial, open) Zone Designation Zone O Room Height 0 LEED NC Regurlarly Occupied Space 0 Base ACOUSTICS Equipment Hardware/STC Rating 0 NRC 0 0 0 Plug Loads Air Change/ HR Walls HVAC ENGINEERING CRITERIA Temperature Lighting 0 0 110v, 20a, 1ph 0 0 Power 0 0 Pressure (+/-) 0 Floor Operable Windows Separation/STC FURNITURE/EQUIPMENT Moveable Yes Fixed RT60 & Shaping 0 Main
Accessibility Requirement: Floor Level 0 Room Length, Width, Shape Open
vs. Private

This room data sheet is not comprehensive in nature. Information regarding specific room features may not have been available and was intentionally left blank.

SUSTAINABILITY FEATURES Adjacencies Accessibility Requirement:

Compliance with ADA/ABAAG (2004) citations is required for accessibility. SI also requires compliance with SI Accessibility Guidelines and the IBC. Comparisons should be made and the more stringent requirement followed for design purposes. See Accessibility Narrative for additional information.

Threshold Experience, Group Entry Entrance Lobby, Security Check Area

Functional Description Serves as transition space from

CRITICAL DIMENSIONS

Width, Shape

CRITERIA

Recommended space be heated under Fire Protection. Please refer to structural narrative for more information on structural requirements.

23 Room Data Sheets | FREELON BOND Infrastructure Only 0 Other Amenities Deionized Water Vacuum Yes Speakers OH Gr. 2, 130 SF/HD FIRE ALARM Smoke Detection Yes Wet Sprinkler Special Waste Dry Sprinkler Pre-Action Sprinkler No FIRE PROTECTION No Considerations for Water 0 No Floor Drains Floor Sink Grey/Blackwater Piping 0 No No No Protected Hot/Cold No No Recycled Water Supply (treated) 0 No Public Address Audio Compressed Air Audio Visual Requirements No Hot/Cold Water Task Light No To Be Considered 0 Plant/Clean Steam 0 Acoustic Sensitivity 0 Vibration Sensitivity Special Equipment/Artifact Sensitivity PLUMBING Target Illuminance (IES 9th Edition) Daylight Sensor 10 FC Exhibit Light To Be Considered Power Density (AHSRAE 2004) 0.5 W/ft² Temperature Deviations (+/-) 0 No Process Water UPS Switched Receptacles Dimming No Humidity 0 Yes Other Humidity Deviation (+/-) 6 min. 0 No Outside Air Single/Multi-Level Switching 0 Emergency/Standby Power 0.10 CMF/SF 30/65 Single Occupancy Sensor Special Exhaust Sub-metering & Feedback Displays Filtration (Pre/Final/Other) Voice/Data DATA/TELECOMMUNICATIONS 0 0 SECURITY 0 5.0 kPa/8.9 kN Floor Loading/Point Loads DAYLIGHTING 0 0 Shading Considerations Top/Side Lighting 0 0 STRUCTURAL 0 0 Refer to information
IV,
E Open Sets of doors should be spaced enough apart so that outside set can close before the inside set. Technical
Vestibules Assignable Square Feet (ASF) OFEO Space Dimensions 0 Organizational Unit Other Interior Glazing 0 0 No 0 0 Ceiling CRITICAL FINISHES 0 Positive
indicated in Volume
Section
Comment:
ELECTRICAL ARCHITECTURAL
Zone Room ID A1.1 Room Name 0
to interior. Public Non-Collection Space 700 Number of Occupants Varies Visual Privacy (full, partial, open) Zone Designation Zone A Room Height 0 LEED NC Regurlarly Occupied Space 0 Base ACOUSTICS Equipment Hardware/STC Rating NA NRC 0 0 0 Plug Loads Air Change/ HR Walls HVAC ENGINEERING
Temperature Lighting 45% RH ±2ºF 110v, 20a, 1ph Yes ±15% RH Power No 0 Pressure (+/-) 76ºF Summer, 71ºF Winter Floor Operable Windows
FURNITURE/EQUIPMENT Moveable No Fixed RT60 & Shaping 0 Ground
exterior
Separation/STC
Floor Level 0 Room
Open
Length,
vs. Private

This room data sheet is not comprehensive in nature. Information regarding specific room features may not have been available and was intentionally left blank.

with ADA/ABAAG (2004) citations is required for

SI also requires compliance with SI Accessibility Guidelines and the IBC. Comparisons should be made and the more stringent requirement followed for design purposes. See Accessibility Narrative for additional information. Outer Hall, Central Hall

Description Landscaped area with

Smithsonian Institution National Museum of African American History and Culture 24 Infrastructure Only Infrastructure for portable AV and IT requirements Other Amenities Deionized Water Vacuum 0 Speakers 0 FIRE ALARM Smoke Detection 0 Wet Sprinkler Special Waste Dry Sprinkler Pre-Action Sprinkler 0 FIRE PROTECTION 0 Considerations for Water 0 0 Floor Drains Floor Sink Grey/Blackwater Piping 0 0 0 0 Protected Hot/Cold 0 0 Recycled Water Supply (treated) 0 0 Public Address Audio Compressed Air Audio Visual Requirements 0 Hot/Cold Water Task Light 0 0 0 Plant/Clean Steam 0 Acoustic Sensitivity 0 Vibration Sensitivity Special Equipment/Artifact Sensitivity PLUMBING Target Illuminance (IES 9th Edition) Daylight Sensor 0 Exhibit Light 0 Power Density (AHSRAE 2004) 0 Temperature Deviations (+/-) 0 0 Process Water UPS Switched Receptacles Dimming 0 Humidity 0 0 Other Humidity Deviation (+/-) 0 0 0 Outside Air Single/Multi-Level Switching 0 Emergency/Standby Power 0 0 0 Occupancy Sensor Special Exhaust Sub-metering & Feedback Displays Filtration (Pre/Final/Other) Voice/Data DATA/TELECOMMUNICATIONS 0 0 SECURITY 0 7.5 kPa/26.7kN Floor Loading/Point Loads DAYLIGHTING 0 0 Shading Considerations Top/Side Lighting 0 Yes STRUCTURAL 0 0 Refer to information indicated in Volume IV, Section E Partial 0 Technical Comment: Interior Courtyard Assignable Square Feet (ASF) OFEO Space Dimensions 0 Organizational Unit Other Interior Glazing Daylighting 0 Yes No 0 Ceiling CRITICAL FINISHES 0 0 0 ELECTRICAL ARCHITECTURAL
Zone Room ID A1.2 Room Name 0
water feature and seating spaces. Consolidated with the Memorial space. Public Non-Collection Space 0 Number of Occupants TBD Visual Privacy (full, partial, open) Zone Designation Zone A Room Height 0 LEED NC Regurlarly Occupied Space 0 Base ACOUSTICS Equipment Hardware/STC Rating 0 NRC 0 0 0 Plug Loads Air Change/ HR Walls HVAC ENGINEERING CRITERIA Temperature Lighting 0 0 110v, 20a, 1ph 0 0 Power 0 0 Pressure (+/-) 0 Floor Operable Windows Separation/STC FURNITURE/EQUIPMENT Moveable Yes Fixed RT60 & Shaping 0 TBD Compliance
SUSTAINABILITY
Adjacencies Accessibility Requirement: Floor Level 0 Room Length, Width, Shape Open vs. Private
Functional
accessibility.
FEATURES
CRITICAL DIMENSIONS

This room data sheet is not comprehensive in nature. Information regarding specific room features may not have been available and was intentionally left blank.

Accessibility Requirement:

Compliance with ADA/ABAAG (2004) citations is required for accessibility. SI also requires compliance with SI Accessibility Guidelines and the IBC. Comparisons should be made and the more stringent requirement followed for design purposes. See Accessibility Narrative for additional information.

SUSTAINABILITY FEATURES Adjacencies

Vestibules, Group Entry Entrance Lobby, Threshold Experience, Check Rooms

Functional Description Security screening with magnetometers or similar electronic screening and bag check for all visitors, prior to main entrance, with separate bag drop off and pick up lines. Should be planned as an isolated area separated from the main entry vesitbule leading to the central hall.

CRITICAL DIMENSIONS

vs. Private

Length, Width, Shape

Recommend space is heated under Fire Protection. Please refer to structural narrative for more information on structural requirements.

25 Room Data Sheets | FREELON BOND Infrastructure Only 0 Other Amenities Deionized Water Vacuum Yes Speakers OH Gr. 2, 130 SF/HD FIRE ALARM Smoke Detection Yes Wet Sprinkler Special Waste Dry Sprinkler Pre-Action Sprinkler No FIRE PROTECTION No Considerations for Water 0 No Floor Drains Floor Sink Grey/Blackwater Piping 0 No No No Protected Hot/Cold No No Recycled Water Supply (treated) 0 No Public Address Audio Compressed Air Audio Visual Requirements No Hot/Cold Water Task Light To Be Considered No 0 Plant/Clean Steam 0 Acoustic Sensitivity NC 40 Vibration Sensitivity Special Equipment/Artifact Sensitivity PLUMBING Target Illuminance (IES 9th Edition) Daylight Sensor 10 FC Exhibit Light To Be Considered Power Density (AHSRAE 2004) 1.1 W/ft² Temperature Deviations (+/-) 0 No Process Water UPS Switched Receptacles Dimming No Humidity 0 Yes Other Humidity Deviation (+/-) 6 min. 0 No Outside Air Single/Multi-Level Switching 0 Emergency/Standby Power 15 CFM/person 30/65 Single Occupancy Sensor Special Exhaust Sub-metering & Feedback Displays Filtration (Pre/Final/Other) Voice/Data DATA/TELECOMMUNICATIONS Yes 0 SECURITY 0 5.0 kPa/8.9 kN Floor Loading/Point Loads DAYLIGHTING 0 0 Shading Considerations Top/Side Lighting 0 0 STRUCTURAL 0 0 Refer to information indicated in Volume IV, Section E 0 0 Technical Comment: Security Check Areas Assignable Square Feet (ASF) OFEO Space Dimensions 0 Organizational Unit Other Interior Glazing 0 0 Yes Yes 0 Ceiling CRITICAL FINISHES 0 Positive
ELECTRICAL ARCHITECTURAL
Zone Room ID A1.3 Room Name 0
Public Non-Collection Space 500 Number of Occupants Varies Visual Privacy (full, partial, open) Zone Designation Zone A Room Height 0 LEED
0 Base ACOUSTICS Equipment Hardware/STC Rating NA NRC 0 0 0 Plug Loads Air Change/ HR Walls HVAC ENGINEERING
Temperature Lighting 45% RH ±2ºF 110v, 20a, 1ph Yes ±15% RH Power 0 0 Pressure (+/-) 76ºF Summer, 71ºF Winter Floor Operable Windows Separation/STC FURNITURE/EQUIPMENT Moveable Yes Fixed RT60 & Shaping 0 Ground
NC Regurlarly Occupied Space
CRITERIA
Floor Level 0 Room
Open

room data

Accessibility Requirement:

Adjacencies

SUSTAINABILITY FEATURES

Compliance with ADA/ABAAG (2004) citations is required for accessibility. SI also requires compliance with SI Accessibility Guidelines and the IBC. Comparisons should be made and the more stringent requirement followed for design purposes. See Accessibility Narrative for additional information.

Vestibules, Group Entry Entrance Lobby, Security Check Area, Reception Podium/Desk/Information

CRITICAL DIMENSIONS

Length, Width, Shape Open vs. Private

Recommended space be heated under Fire Protection. Please refer to structural narrative for more information on structural requirements.

Smithsonian Institution National Museum of African American History and Culture 26 Infrastructure Only 0 Other Amenities Deionized Water Vacuum Yes Speakers OH Gr. 2, 130 SF/HD FIRE ALARM Smoke Detection Yes Wet Sprinkler Special Waste Dry Sprinkler Pre-Action Sprinkler No FIRE PROTECTION No Considerations for Water 0 No Floor Drains Floor Sink Grey/Blackwater Piping 0 No No No Protected Hot/Cold No No Recycled Water Supply (treated) 0 No Public Address Audio Compressed Air Audio Visual Requirements No Hot/Cold Water Task Light No To Be Considered 0 Plant/Clean Steam 0 Acoustic Sensitivity NC 40 Vibration Sensitivity Special Equipment/Artifact Sensitivity PLUMBING Target Illuminance (IES 9th Edition) Daylight Sensor 10 FC Exhibit Light To Be Considered Power Density (AHSRAE 2004) 0.5 W/ft² Temperature Deviations (+/-) 0 No Process Water UPS Switched Receptacles Dimming No Humidity 0 Yes Other Humidity Deviation (+/-) 0 0 Yes Outside Air Single/Multi-Level Switching 0 Emergency/Standby Power 15 CFM/person 30/65 Single Occupancy Sensor Special Exhaust Sub-metering & Feedback Displays Filtration (Pre/Final/Other) Voice/Data DATA/TELECOMMUNICATIONS 0 0 SECURITY 0 7.5 kPa/26.7 kN Floor Loading/Point Loads DAYLIGHTING 0 0 Shading Considerations Top/Side Lighting 0 0 STRUCTURAL 0 0 Refer to information indicated in Volume IV, Section E 0 0 Technical Comment: Threshold Experience Assignable Square Feet (ASF) OFEO Space Dimensions 0 Organizational Unit Other Interior Glazing 0 0 0 0 0 Ceiling CRITICAL FINISHES 0 Positive
ELECTRICAL ARCHITECTURAL
Zone Room ID A1.4 Room Name 0 Functional Description An outdoor/indoor transition space. It will
first experience
visitor
NMAAHC
outdoor space
exterior with the interior. Public Non-Collection Space 2,000 Number of Occupants NA Visual Privacy (full, partial, open) Zone Designation Zone A Room Height 0 LEED
Space 0 Base ACOUSTICS Equipment Hardware/STC Rating NA NRC 0 0 0 Plug Loads Air Change/ HR Walls HVAC ENGINEERING
Temperature Lighting 45% RH ±2ºF 110v, 20a, 1ph Yes ±15% RH Power No 0 Pressure (+/-) 76ºF Summer, 71ºF Winter Floor Operable Windows Separation/STC FURNITURE/EQUIPMENT Moveable 0 Fixed RT60 & Shaping 0 NA
This
sheet is not comprehensive in nature. Information regarding specific room features may not have been available and was intentionally left blank.
be the
the
to the
will have, this
seeks to merge the
NC Regurlarly Occupied
CRITERIA
Floor Level 0 Room

ARCHITECTURAL

This room data sheet is not comprehensive in nature. Information regarding specific room features may not have been available and was intentionally left blank.

Adjacencies Accessibility Requirement:

Compliance with ADA/ABAAG (2004) citations is required for accessibility. SI also requires compliance with SI Accessibility Guidelines and the IBC. Comparisons should be made and the more stringent requirement followed for design purposes. See Accessibility Narrative for additional information.

All Galleries, Resource Center, Theater/Auditorium, Food Services, Visitor Amenities, Orientation Theater

Functional Description Like a circulation space it leads to many of the visitor amenity functions (see adjacencies) but is more room-like and may contain artifacts to move visitors deeper into the museum.

SUSTAINABILITY FEATURES

vs. Private

CRITICAL DIMENSIONS

Width, Shape

NRC As needed to achieve desired RT absorptive finishes will most likely be necessary on the ceiling and walls

Recommend space is heated under Fire Protection. Please refer to structural narrative for more information on structural requirements.

ELECTRICAL

to information indicated in Volume IV, Section

27 Room Data Sheets | FREELON BOND Infrastructure Only 0 Other Amenities Deionized Water Vacuum Yes Speakers OH Gr. 2, 130 SF/HD FIRE ALARM Smoke Detection Yes Wet Sprinkler Special Waste Dry Sprinkler Pre-Action Sprinkler No FIRE PROTECTION No Considerations for Water 0 No Floor Drains Floor Sink Grey/Blackwater Piping 0 No No No Protected Hot/Cold No No Recycled Water Supply (treated) 0 No Public Address Audio Compressed Air Audio Visual Requirements No Hot/Cold Water Task Light No To Be Considered 0 Plant/Clean Steam 0 Acoustic Sensitivity NC 40 Vibration Sensitivity Special Equipment/Artifact Sensitivity PLUMBING Target Illuminance (IES 9th Edition) Daylight Sensor 10 FC Exhibit Light To Be Considered Power Density (AHSRAE 2004) 3.3 W/ft² Temperature Deviations (+/-) 0 To Be Considered Process Water UPS Switched Receptacles Dimming No Humidity 0 Yes Other Humidity Deviation (+/-) 6 min. 0 Yes Outside Air Single/Multi-Level Switching 0 Emergency/Standby Power 15 CFM/person 30/65 Multi Occupancy Sensor Special Exhaust Sub-metering & Feedback Displays Filtration (Pre/Final/Other) Voice/Data DATA/TELECOMMUNICATIONS 0 0 SECURITY 0 7.5 kPa/26.7 kN Floor Loading/Point Loads DAYLIGHTING 0 0 Shading Considerations Top/Side Lighting Audio system with local control Yes-Separate Zone STRUCTURAL 0 Connection for special events
0 0 Technical Comment: Outer Hall Assignable Square Feet (ASF) OFEO Space Dimensions 0 Organizational Unit Other Interior Glazing 0 0 Yes 0 0 Ceiling CRITICAL FINISHES 0 Positive
Refer
E
Zone Room ID A1.5 Room Name 0
Public Non-Collection Space 4,000 Number of Occupants TBD Visual Privacy (full, partial, open) Zone Designation Zone A Room Height 0 LEED
0 Base ACOUSTICS Equipment Hardware/STC Rating NA
NC Regurlarly Occupied Space
0 0 Plug Loads Air Change/ HR Walls HVAC ENGINEERING
Temperature Lighting 45% RH ±2ºF 110v,
1ph Yes ±15% RH Power No 0 Pressure (+/-) 76ºF Summer, 71ºF Winter Floor Operable
CRITERIA
20a,
Windows
Moveable No Fixed RT60 & Shaping 1.0-1.2 s Lower
Separation/STC FURNITURE/EQUIPMENT
Floor Level 0 Room
Length,
Open

ARCHITECTURAL

This room data sheet is not comprehensive in nature. Information regarding specific room features may not have been available and was intentionally left blank. Due to the round nature of the space, and the likelihood that the majoirty of the walls will be video screens or hard surfaces, acoustically absorptive surfaces will likely be required on all other areas. The Loudspeaker and Audio system will generate high sound levels and combined with visitor activity sound, this will require control with room surfaces.

Accessibility Requirement:

Adjacencies

Compliance with ADA/ABAAG (2004) citations is required for accessibility. SI also requires compliance with SI Accessibility Guidelines and the IBC. Comparisons should be made and the more stringent requirement followed for design purposes. See Accessibility Narrative for additional information.

Outer Hall, Threshold Experience, Reception Podium/Desk/Information, (Memorial?), Meeting Event Areas

Functional Description Will be the main welcoming space for visitors and introduce them to the history and main themes of the museum.

SUSTAINABILITY FEATURES

CRITICAL DIMENSIONS

Length, Width, Shape Open vs. Private

Occupied Space

Separation/STC

NRC As needed to achieve desired RT absorptive finishes will most likely be necessary on the ceiling and walls.

Please refer to structural narrative for more information on structural requirements.

ELECTRICAL

to information indicated in Volume IV, Section

Smithsonian Institution National Museum of African American History and Culture 28 Infrastructure Only 0 Other Amenities Deionized Water Vacuum Yes Speakers OH Gr. 2, 130 SF/HD FIRE ALARM Smoke Detection Yes Wet Sprinkler Special Waste Dry Sprinkler Pre-Action Sprinkler No FIRE PROTECTION No Considerations for Water 0 No Floor Drains Floor Sink Grey/Blackwater Piping 0 No No No Protected Hot/Cold No No Recycled Water Supply (treated) 0 No Public Address Audio Compressed Air Audio Visual Requirements No Hot/Cold Water Task Light No To Be Considered 0 Plant/Clean Steam 0 Acoustic Sensitivity NC 40 Vibration Sensitivity Special Equipment/Artifact Sensitivity PLUMBING Target Illuminance (IES 9th Edition) Daylight Sensor 10 FC Exhibit Light To Be Considered Power Density (AHSRAE 2004) 3.3 W/ft² Temperature Deviations (+/-) 0 To Be Considered Process Water UPS Switched Receptacles Dimming No Humidity 0 Yes Other Humidity Deviation (+/-) 6 min. 0 Yes Outside Air Single/Multi-Level Switching 0 Emergency/Standby Power 15 CFM/person 30/65 Multi Occupancy Sensor Special Exhaust Sub-metering & Feedback Displays Filtration (Pre/Final/Other) Voice/Data DATA/TELECOMMUNICATIONS 0 0 SECURITY 0 7.5 kPa/26.7 kN Floor Loading/Point Loads DAYLIGHTING 0 0 Shading Considerations Top/Side Lighting Visual displays
yes-separate zone STRUCTURAL 0 Connections for special events Refer
E 0 0 Technical Comment: Central Hall Assignable Square Feet (ASF) OFEO Space Dimensions 0 Organizational Unit Other Interior Glazing 0 0 0 0 0 Ceiling CRITICAL FINISHES 0 Positive
throughout the space, projected images, flat panel displays or alternate display technology such as LED.
Zone Room ID A1.6 Room Name 0
Public Non-Collection Space 6,000 Number of Occupants TBD Visual Privacy (full, partial, open) Zone Designation Zone A Room Height Level LEED
0 Base ACOUSTICS Equipment Hardware/STC Rating NA
NC Regurlarly
0 0 Plug Loads Air Change/ HR Walls HVAC ENGINEERING
Temperature Lighting 45% RH ±2ºF 110v,
1ph Yes ±15% RH Power No 0 Pressure (+/-) 76ºF Summer, 71ºF Winter Floor
CRITERIA
20a,
Operable Windows
FURNITURE/EQUIPMENT Moveable 0 Fixed RT60 & Shaping 1.0-1.2 s Lower
Floor Level 0 Room

This room data sheet is not comprehensive in nature. Information regarding specific room features may not have been available and was intentionally left blank.

Accessibility Requirement:

Adjacencies

Compliance with ADA/ABAAG (2004)citations is required for accessibility. SI also requires compliance with SI Accessibility Guidelines and the IBC. Comparisons should be made and the more stringent requirement followed for design purposes. See Accessibility Narrative for additional information.

Youth Gallery, Central Hall, Education Assembly, Education Program Spaces, Education Public Storage

Description Assembly and orientation for school groups or special groups with greeting podium, overhead video monitors; requires adjacent student coat room (lunch/backpack storage), washrooms, and access to classrooms. Need to consider security screening for this entrance.

SUSTAINABILITY FEATURES

CRITICAL DIMENSIONS

Length, Width, Shape Open vs. Private

NRC As needed to achieve desired RT absorptive finishes will most likely be necessary on the ceiling and walls

Recommend space is heated under Fire Protection. Recommend space has a drinking fountain under Plumbing.Please refer to structural narrative for more information on structural requirements.

29 Room Data Sheets | FREELON BOND Infrastructure Only 0 Other Amenities Deionized Water Vacuum Yes Speakers OH Gr. 2, 130 SF/HD FIRE ALARM Smoke Detection Yes Wet Sprinkler Special Waste Dry Sprinkler Pre-Action Sprinkler No FIRE PROTECTION No Considerations for Water 0 No Floor Drains Floor Sink Grey/Blackwater Piping 0 No No No Protected Hot/Cold No No Recycled Water Supply (treated) 0 No Public Address Audio Compressed Air Audio Visual Requirements Yes Hot/Cold Water Task Light no To Be Considered 0 Plant/Clean Steam 0 Acoustic Sensitivity NC 40 Vibration Sensitivity Special Equipment/Artifact Sensitivity PLUMBING Target Illuminance (IES 9th Edition) Daylight Sensor 10 FC Exhibit Light Yes Power Density (AHSRAE 2004) 1.3 W/ft² Temperature Deviations (+/-) 0 No Process Water UPS Switched Receptacles Dimming No Humidity 0 Yes Other Humidity Deviation (+/-) 6 min. 0 Yes Outside Air Single/Multi-Level Switching 0 Emergency/Standby Power 20 CFM/person 30/65 Multi Occupancy Sensor Special Exhaust Sub-metering & Feedback Displays Filtration (Pre/Final/Other) Voice/Data DATA/TELECOMMUNICATIONS Yes 0 SECURITY 0 7.5 kPa/26.7 kN Floor Loading/Point Loads DAYLIGHTING 0 0 Shading Considerations Top/Side Lighting Audio system with local control Yes- separate zone STRUCTURAL 0 0 Refer
IV,
0 Like American Indian Museum/Separate Group Entrance Technical Comment: Group Entrance Lobby Assignable Square Feet (ASF) OFEO Space Dimensions 0 Organizational Unit Other Interior Glazing 0 0 Yes 0 0 Ceiling CRITICAL FINISHES 0 Positive
to information indicated in Volume
Section E
ELECTRICAL ARCHITECTURAL
Zone Room ID A1.7 Room Name 0
Public Non-Collection Space 800 Number of Occupants 75 Visual Privacy (full, partial, open) Zone Designation Zone A Room Height 0 LEED NC Regurlarly
Space 0 Base ACOUSTICS Equipment Hardware/STC Rating NA
Functional
Occupied
0 0 Plug Loads Air Change/ HR Walls HVAC ENGINEERING
Temperature Lighting 45% RH ±2ºF 110v, 20a, 1ph Yes ±15% RH Power No 0 Pressure (+/-) 76ºF Summer, 71ºF Winter Floor Operable Windows
CRITERIA
Moveable 0 Fixed RT60 & Shaping 1.0-1.2 s Ground
Separation/STC FURNITURE/EQUIPMENT
Floor Level 0 Room

(2004)citations is

Located within Central Hall

Smithsonian Institution National Museum of African American History and Culture 30 Infrastructure Only 0 Other Amenities Deionized Water Vacuum Yes Speakers OH Gr. 2, 130 SF/HD FIRE ALARM Smoke Detection Yes Wet Sprinkler Special Waste Dry Sprinkler Pre-Action Sprinkler 0 FIRE PROTECTION 0 Considerations for Water 0 0 Floor Drains Floor Sink Grey/Blackwater Piping 0 0 0 0 Protected Hot/Cold 0 0 Recycled Water Supply (treated) 0 0 Public Address Audio Compressed Air Audio Visual Requirements 0 Hot/Cold Water Task Light 0 0 0 Plant/Clean Steam 0 Acoustic Sensitivity 0 Vibration Sensitivity Special Equipment/Artifact Sensitivity PLUMBING Target Illuminance (IES 9th Edition) Daylight Sensor 0 Exhibit Light 0 Power Density (AHSRAE 2004) 0 Temperature Deviations (+/-) 0 0 Process Water UPS Switched Receptacles Dimming 0 Humidity 0 0 Other Humidity Deviation (+/-) 0 0 0 Outside Air Single/Multi-Level Switching 0 Emergency/Standby Power 0 0 0 Occupancy Sensor Special Exhaust Sub-metering & Feedback Displays Filtration (Pre/Final/Other) Voice/Data DATA/TELECOMMUNICATIONS Yes 0 SECURITY 0 0 Floor Loading/Point Loads DAYLIGHTING 0 0 Shading Considerations Top/Side Lighting Permanent audio system for local speech amplification and program playback. Infrastructure for visual displays. 0 STRUCTURAL 0 0 Refer to information indicated in Volume IV, Section E 0 0 Technical Comment: Special Event Room Assignable Square Feet (ASF) OFEO Space Dimensions 0 Organizational Unit Other Interior Glazing 0 0 0 0 0 Ceiling CRITICAL FINISHES 0 0 0 ELECTRICAL ARCHITECTURAL
left blank. Zone Room ID A1.8 Room Name 0 Functional Description Flexible sapce within the Central Hall for temporary assembly purposes and special events. Public Non-Collection Space 0 Number of OccupantsVisual Privacy (full, partial, open) Zone Designation Zone A Room Height 0 LEED NC Regurlarly Occupied Space 0 Base ACOUSTICS Equipment Hardware/STC Rating 0 NRC 0 0 0 Plug Loads Air Change/ HR Walls HVAC ENGINEERING CRITERIA Temperature Lighting 0 0 110v, 20a, 1ph 0 0 Power 0 0 Pressure (+/-) 0 Floor Operable Windows Separation/STC FURNITURE/EQUIPMENT Moveable 0 Fixed RT60 & Shaping 0 0 Compliance with ADA/ABAAG
required
accessibility.
Within Central
SUSTAINABILITY
Adjacencies Accessibility Requirement: Floor Level 0 Room Length, Width, Shape Open vs. Private
This room data sheet is not comprehensive in nature. Information regarding specific room features may not have been available and was intentionally
for
SI also requires compliance with SI Accessibility Guidelines and the IBC. Comparisons should be made and the more stringent requirement followed for design purposes. See Accessibility Narrative for additional information.
Hall
FEATURES
CRITICAL DIMENSIONS NOTE: Space

This room data sheet is not comprehensive in nature. Information regarding specific room features may not have been available and was intentionally left

Accessibility Requirement:

Compliance with ADA/ABAAG (2004) citations is required for accessibility. SI also requires compliance with SI Accessibility Guidelines and the IBC. Comparisons should be made and the more stringent requirement followed for design purposes. See Accessibility Narrative for additional information.

with seating areas, possibly landscaped with plants.

CRITICAL DIMENSIONS

Recommend space have water feature under Plumbing. Recommend space is heated under Fire Protection. Please refer to structural narrative for more

requirements.

31 Room Data Sheets | FREELON BOND Infrastructure Only 0 Other Amenities Deionized Water Vacuum Yes Speakers OH Gr. 2, 130 SF/HD FIRE ALARM Smoke Detection Yes Wet Sprinkler Special Waste Dry Sprinkler Pre-Action Sprinkler No FIRE PROTECTION No Considerations for Water 0 No Floor Drains Floor Sink Grey/Blackwater Piping 0 No No No Protected Hot/Cold No No Recycled Water Supply (treated) 0 Yes Public Address Audio Compressed Air Audio Visual Requirements Yes Hot/Cold Water Task Light No To Be Considered 0 Plant/Clean Steam 0 Acoustic Sensitivity NC 30 Vibration Sensitivity Special Equipment/Artifact Sensitivity PLUMBING Target Illuminance (IES 9th Edition) Daylight Sensor 10 FC Exhibit Light Yes Power Density (AHSRAE 2004) 3.3 W/ft² Temperature Deviations (+/-) 0 Yes Process Water UPS Switched Receptacles Dimming No Humidity 0 No Other Humidity Deviation (+/-) 8 min. 0 No Outside Air Single/Multi-Level Switching 0 Emergency/Standby Power 20 CFM/person 30/65 Multi Occupancy Sensor Special Exhaust Sub-metering & Feedback Displays Filtration (Pre/Final/Other) Voice/Data DATA/TELECOMMUNICATIONS Yes 0 SECURITY 0 7.5 kPa/26.7 kN Floor Loading/Point Loads DAYLIGHTING 0 0 Shading Considerations Top/Side Lighting Audio system with local control 0 STRUCTURAL 0 0 Refer to information indicated in Volume IV, Section E Partial/Full Natural UGBT/WRBR Technical Comment: Memorial Assignable Square Feet (ASF) OFEO Space Dimensions 0 Organizational Unit Other Interior Glazing 0 0 0 0 0 Ceiling CRITICAL FINISHES 0 Positive
information on structural
ELECTRICAL ARCHITECTURAL
Zone Room ID A1.9 Room Name 0 Functional Description Consolidated with Interior Courtyard.
space
Public Non-Collection Space 4,000 Number of Occupants 80 Visual Privacy (full, partial, open) Zone Designation Zone A Room Height 0 LEED NC
0 Base ACOUSTICS Equipment Hardware/STC Rating NA NRC 0 STC 55 0 Plug Loads Air Change/ HR Walls HVAC ENGINEERING CRITERIA Temperature Lighting 45% RH ±2ºF 110v, 20a, 1ph Yes ±15% RH Power No 0 Pressure (+/-) 76ºF Summer, 71ºF Winter Floor Operable Windows Separation/STC FURNITURE/EQUIPMENT Moveable 0 Fixed RT60 & Shaping 1.0 s TBD
blank.
Reflective
Regurlarly Occupied Space
Outer Hall
SUSTAINABILITY FEATURES Adjacencies
Floor Level 0 Room
Open
Length, Width, Shape
vs. Private

This room data sheet is not comprehensive in nature. Information regarding specific room features may not have been available and was intentionally left blank.

vs. Private

Separation/STC

FEATURES

Compliance with ADA/ABAAG (2004) citations is required for accessibility. SI also requires compliance with SI Accessibility Guidelines and the IBC. Comparisons should be made and the more stringent requirement followed for design purposes. See Accessibility Narrative for additional information.

Patron Lounge Servery

CRITICAL DIMENSIONS

Recommend kitchen equipment and sinks under Plumbing. Please refer to structural narrative for more information on structural requirements.

Smithsonian Institution National Museum of African American History and Culture 32 Infrastructure Only 0 Other Amenities Deionized Water Vacuum Yes Speakers OH Gr. 2, 130 SF/HD FIRE ALARM Smoke Detection Yes Wet Sprinkler Special Waste Dry Sprinkler Pre-Action Sprinkler No FIRE PROTECTION No Considerations for Water 0 No Floor Drains Floor Sink Grey/Blackwater Piping 0 No No No Protected Hot/Cold No No Recycled Water Supply (treated) 0 Yes Public Address Audio Compressed Air Audio Visual Requirements Yes Hot/Cold Water Task Light No Yes 0 Plant/Clean Steam 0 Acoustic Sensitivity NC 35 Vibration Sensitivity Special Equipment/Artifact Sensitivity PLUMBING Target Illuminance (IES 9th Edition) Daylight Sensor 30 FC Exhibit Light Yes Power Density (AHSRAE 2004) 2.1 W/ft² Temperature Deviations (+/-) 0 Yes Process Water UPS Switched Receptacles Dimming No Humidity 0 Yes Other Humidity Deviation (+/-) 8 min. 0 No Outside Air Single/Multi-Level Switching 0 Emergency/Standby Power 20 CFM/person 30/65 Multi Occupancy Sensor Special Exhaust Sub-metering & Feedback Displays Filtration (Pre/Final/Other) Voice/Data DATA/TELECOMMUNICATIONS Yes 0 SECURITY 0 5.0 kPa/8.9 kN Floor Loading/Point Loads DAYLIGHTING 0 0 Shading Considerations Top/Side Lighting Audio system with local control No STRUCTURAL 0 0 Refer
0 NMAI Model Technical Comment: Patron Lounge Assignable Square Feet (ASF) OFEO Space Dimensions 0 Organizational Unit Other Interior Glazing 0 Solid core wood or insulated metal with neoprane strip seals max 1/4" undercut 0 0 0 Ceiling CRITICAL FINISHES 0 Positive
to information indicated in Volume IV, Section E
ARCHITECTURAL
Zone Room ID A1.10 Room Name 0 Functional Description Great vistas, possibly on top floor. Nicely furnished. Public Non-Collection Space 1,200 Number of Occupants 80-100 Standing Visual Privacy (full, partial, open) Zone Designation Zone A Room Height 0 LEED NC Regurlarly
Space 0 Base ACOUSTICS Equipment Hardware/STC Rating NA NRC Absorptive ceiling finish with an NRC 0.80 or higher, absorptive wall finish along one wall from 3'-7' aff with an NRC 0.70 or higher STC 55 0 Plug Loads Air Change/ HR Walls HVAC ENGINEERING CRITERIA Temperature Lighting 45% RH ±2ºF 110v, 20a, 1ph Yes ±15% RH Power No 0 Pressure (+/-) 76ºF Summer, 71ºF Winter Floor Operable
ELECTRICAL
Occupied
Windows
Fixed RT60 & Shaping 1.0 S Upper
FURNITURE/EQUIPMENT Moveable
Floor Level 0 Room
Open
SUSTAINABILITY
Adjacencies Accessibility Requirement:
Length, Width, Shape

This room data sheet is not comprehensive in nature. Information regarding specific room features may not have been available and was intentionally left blank.

SUSTAINABILITY FEATURES

Compliance with ADA/ABAAG (2004) citations is required for accessibility. SI also requires compliance with SI Accessibility Guidelines and the IBC. Comparisons should be made and the more stringent requirement followed for design purposes. See Accessibility Narrative for additional information.

CRITICAL DIMENSIONS

Width, Shape

Recommend kitchen equipment and sinks under Plumbing. Please refer to structural narrative for more information on structural requirements.

33 Room Data Sheets | FREELON BOND Infrastructure Only 0 Other Amenities Deionized Water Vacuum Yes Speakers OH Gr. 2, 130 SF/HD FIRE ALARM Smoke Detection Yes Wet Sprinkler Special Waste Dry Sprinkler Pre-Action Sprinkler No FIRE PROTECTION No Considerations for Water 0 No Floor Drains Floor Sink Grey/Blackwater Piping 0 No No No Protected Hot/Cold No No Recycled Water Supply (treated) 0 Yes Public Address Audio Compressed Air Audio Visual Requirements Yes Hot/Cold Water Task Light No Yes 0 Plant/Clean Steam 0 Acoustic Sensitivity NC 35 Vibration Sensitivity Special Equipment/Artifact Sensitivity PLUMBING Target Illuminance (IES 9th Edition) Daylight Sensor 30 FC Exhibit Light Yes Power Density (AHSRAE 2004) 2.1 W/ft² Temperature Deviations (+/-) 0 Yes Process Water UPS Switched Receptacles Dimming No Humidity 0 Yes Other Humidity Deviation (+/-) 8 min. 0 No Outside Air Single/Multi-Level Switching 0 Emergency/Standby Power 20 CFM/person 30/65 Multi Occupancy Sensor Special Exhaust Sub-metering & Feedback Displays Filtration (Pre/Final/Other) Voice/Data DATA/TELECOMMUNICATIONS Yes 0 SECURITY 0 5.0 kPa/8.9 kN Floor Loading/Point Loads DAYLIGHTING 0 0 Shading Considerations Top/Side Lighting Audio system with local control No STRUCTURAL 0 0 Refer to information indicated
Volume IV, Section E 0 0 Technical Comment: VIP Lounge Assignable Square Feet (ASF) OFEO Space Dimensions 0 Organizational Unit Other Interior Glazing 0 Solid core wood or insulated metal with neoprane strip seals max 1/4" undercut 0 0 0 Ceiling CRITICAL FINISHES 0 Positive
in
ELECTRICAL ARCHITECTURAL
Zone Room ID A1.11 Room Name 0 Functional
Small
Public Non-Collection Space 300 Number of Occupants NA Visual Privacy (full, partial, open) Zone Designation Zone A Room Height 0 LEED NC Regurlarly Occupied Space 0 Base ACOUSTICS Equipment Hardware/STC Rating NA NRC
0.80
3'-7'
with an NRC 0.70
higher STC 55 0 Plug Loads Air Change/ HR Walls HVAC ENGINEERING
Temperature Lighting 45% RH ±2ºF 110v, 20a, 1ph Yes ±15% RH Power No 0 Pressure (+/-) 76ºF Summer, 71ºF Winter Floor Operable Windows Separation/STC FURNITURE/EQUIPMENT Moveable Fixed RT60 & Shaping 1.0 S Lower
Description
intimate space used for VIP reception at entry sequence.
Absorptive ceiling finish with an NRC
or higher, absorptive wall finish along one wall from
aff
or
CRITERIA
Cafeteria, VIP
Entrance
Adjacencies
Floor Level 0 Room Length,
Open vs.
Accessibility Requirement:
Private

This room data sheet is not comprehensive in nature. Information regarding specific room features may not have been available and was intentionally left blank.

Accessibility Requirement:

Adjacencies

SUSTAINABILITY FEATURES

vs. Private

Compliance with ADA/ABAAG (2004) citations is required for accessibility. SI also requires compliance with SI Accessibility Guidelines and the IBC. Comparisons should be made and the more stringent requirement followed for design purposes. See Accessibility Narrative for additional information.

Threshold Experience, Central Hall, Public Washrooms, Wheelchair Storage

CRITICAL DIMENSIONS

Length, Width, Shape

NRC Include as many absorptive finishes within the design of the desk. Use of an overhead ceiling cloud with NRC 0.80 or higher

Please refer to structural narrative for more information on structural requirements.

Smithsonian Institution National Museum of African American History and Culture 34 Infrastructure Only 0 Other Amenities Deionized Water Vacuum Yes Speakers OH Gr. 2, 130 SF/HD FIRE ALARM Smoke Detection Yes Wet Sprinkler Special Waste Dry Sprinkler Pre-Action Sprinkler No FIRE PROTECTION No Considerations for Water 0 No Floor Drains Floor Sink Grey/Blackwater Piping 0 No No No Protected Hot/Cold No No Recycled Water Supply (treated) 0 No Public Address Audio Compressed Air Audio Visual Requirements No Hot/Cold Water Task Light Yes To Be Considered 0 Plant/Clean Steam 0 Acoustic Sensitivity NC 40 Vibration Sensitivity Special Equipment/Artifact Sensitivity PLUMBING Target Illuminance (IES 9th Edition) Daylight Sensor 10 FC Exhibit Light Yes Power Density (AHSRAE 2004) 3.3 W/ft² Temperature Deviations (+/-) 0 No Process Water UPS Switched Receptacles Dimming No Humidity 0 Yes Other Humidity Deviation (+/-) 6 min. 0 No Outside Air Single/Multi-Level Switching 0 Emergency/Standby Power 15 CFM/person 30/65 Multi Occupancy Sensor Special Exhaust Sub-metering & Feedback Displays Filtration (Pre/Final/Other) Voice/Data DATA/TELECOMMUNICATIONS Yes 0 SECURITY 0 5.0 kPa/8.9 kN Floor Loading/Point Loads DAYLIGHTING 0 0 Shading Considerations Top/Side Lighting 0 Yes STRUCTURAL 0 0 Refer to information indicated in Volume IV, Section E 0 Includes visitor tracking,
wall mounted charging
for audioguides
Reception Podium/Desk/Information Desk Assignable Square Feet (ASF) OFEO Space Dimensions 0 Organizational Unit Other Interior Glazing 0 0 Yes Yes 0 Ceiling CRITICAL FINISHES 0 Positive
and
stand
Technical Comment:
ELECTRICAL
ARCHITECTURAL
Zone Room ID A2.1 Room Name 0
Public Non-Collection Space 500 Number of Occupants 6 Visual Privacy (full, partial, open) Zone Designation Zone A Room Height 0 LEED NC Regurlarly Occupied Space 0 Base ACOUSTICS Equipment Hardware/STC Rating Yes
0 0 Plug Loads Air Change/ HR Walls HVAC ENGINEERING
Temperature Lighting 45% RH ±2ºF 110v, 20a, 1ph Yes ±15% RH Power Yes 0 Pressure (+/-) 76ºF Summer, 71ºF Winter Floor Operable Windows Separation/STC FURNITURE/EQUIPMENT Moveable Yes Fixed RT60 & Shaping 0 Lower
Functional Description Combined information and reception areas. To serve as ticketing desk if required
CRITERIA
Floor Level 0 Room
Open

This room data sheet is not comprehensive in nature. Information regarding specific room features may not have been available and was intentionally left blank.

Accessibility Requirement:

Adjacencies

Compliance with ADA/ABAAG (2004) citations is required for accessibility. SI also requires compliance with SI Accessibility Guidelines and the IBC. Comparisons should be made and the more stringent requirement followed for design purposes. See Accessibility Narrative for additional information.

Retail Storage/Wrapping, Outer Hall, Cafeteria, Café, Visitor Amenities, Orientation Theater

Functional Description Museum shop will support the Museum Mission and enhance the visitor experience.

SUSTAINABILITY FEATURES

CRITICAL DIMENSIONS

Length, Width, Shape Open vs. Private

FURNITURE/EQUIPMENT

Separation/STC

Please refer to structural narrative for more information on structural requirements.

35 Room Data Sheets | FREELON BOND Infrastructure Only 0 Other Amenities Deionized Water Vacuum Yes Speakers OH Gr. 2, 130 SF/HD FIRE ALARM Smoke Detection Yes Wet Sprinkler Special Waste Dry Sprinkler Pre-Action Sprinkler No FIRE PROTECTION No Considerations for Water 0 No Floor Drains Floor Sink Grey/Blackwater Piping 0 No No No Protected Hot/Cold No No Recycled Water Supply (treated) 0 No Public Address Audio Compressed Air Audio Visual Requirements No Hot/Cold Water Task Light Yes No 0 Plant/Clean Steam 0 Acoustic Sensitivity NC 40 Vibration Sensitivity Special Equipment/Artifact Sensitivity PLUMBING Target Illuminance (IES 9th Edition) Daylight Sensor 30-50 FC Exhibit Light To Be Considered Power Density (AHSRAE 2004) Exempt Temperature Deviations (+/-) 0 Yes Process Water UPS Switched Receptacles Dimming No Humidity 0 Yes Other Humidity Deviation (+/-) 6 min. 0 No Outside Air Single/Multi-Level Switching 0 Emergency/Standby Power 0.2 CFM/SF 30/65 Single Occupancy Sensor Special Exhaust Sub-metering & Feedback Displays Filtration (Pre/Final/Other) Voice/Data DATA/TELECOMMUNICATIONS Yes 0 SECURITY 0 5.0 kPa/8.9 kN Floor Loading/Point Loads DAYLIGHTING 0 0 Shading Considerations Top/Side Lighting SBV Standard Audio System-local 0 STRUCTURAL 0 0 Refer to information
IV,
E Open Operated by Smithsonian Enterprises Technical Comment: Shop, Main Museum Assignable Square Feet (ASF) OFEO Space Dimensions 0 Organizational Unit Other Interior Glazing 0 0 Yes Yes 0 Ceiling CRITICAL FINISHES 0 Positive
indicated in Volume
Section
ELECTRICAL ARCHITECTURAL
Zone Room ID A2.2 Room Name 0
Public Non-Collection Space 2,500 Number of Occupants TBD Visual Privacy (full, partial, open) Zone Designation Zone A Room Height 0 LEED NC Regurlarly Occupied Space 0 Base ACOUSTICS Equipment Hardware/STC Rating 0 NRCSTC 45 0 Plug Loads Air Change/ HR Walls HVAC ENGINEERING CRITERIA Temperature Lighting 45% RH ±2ºF 110v, 20a, 1ph Yes ±15% RH Power 0 0 Pressure (+/-) 76ºF Summer, 71ºF Winter Floor Operable Windows
Moveable Yes Fixed RT60 & Shaping 0 Lower
Floor Level 0 Room

This room data sheet is not

Accessibility Requirement:

Compliance with ADA/ABAAG (2004) citations is required for accessibility. SI also requires compliance with SI Accessibility Guidelines and the IBC. Comparisons should be made and the more stringent requirement followed for design purposes. See Accessibility Narrative for additional information.

Located within Gallery

NOTE: Space

Please refer to structural narrative for more information on structural requirements.

Smithsonian Institution National Museum of African American History and Culture 36 Infrastructure Only 0 Other Amenities Deionized Water Vacuum Yes Speakers OH Gr. 2, 130 SF/HD FIRE ALARM Smoke Detection Yes Wet Sprinkler Special Waste Dry Sprinkler Pre-Action Sprinkler No FIRE PROTECTION No Considerations for Water 0 No Floor Drains Floor Sink Grey/Blackwater Piping 0 No No No Protected Hot/Cold No No Recycled Water Supply (treated) 0 No Public Address Audio Compressed Air Audio Visual Requirements No Hot/Cold Water Task Light Yes No 0 Plant/Clean Steam 0 Acoustic Sensitivity NC 40 Vibration Sensitivity Special Equipment/Artifact Sensitivity PLUMBING Target Illuminance (IES 9th Edition) Daylight Sensor 30-50 FC Exhibit Light To Be Considered Power Density (AHSRAE 2004) Exempt Temperature Deviations (+/-) 0 Yes Process Water UPS Switched Receptacles Dimming No Humidity 0 No Other Humidity Deviation (+/-) 6 min. 0 Yes Outside Air Single/Multi-Level Switching 0 Emergency/Standby Power 0.2 CFM/SF 30/65 Single Occupancy Sensor Special Exhaust Sub-metering & Feedback Displays Filtration (Pre/Final/Other) Voice/Data DATA/TELECOMMUNICATIONS Yes 0 SECURITY 0 5.0 kPa/8.9 kN Floor Loading/Point Loads DAYLIGHTING 0 0 Shading Considerations Top/Side Lighting SBV Standard Audio System-local 0 STRUCTURAL 0 0 Refer to information indicated in Volume IV, Section E 0 0 Technical Comment: Shop, Special Exhibition Assignable Square Feet (ASF) OFEO Space Dimensions 0 Organizational Unit Other Interior Glazing 0 0 0 0 0 Ceiling CRITICAL FINISHES 0 Positive
ELECTRICAL ARCHITECTURAL
comprehensive
nature. Information regarding specific room features may not have been available and was intentionally left blank. Zone Room ID A2.3 Room Name 0 Functional Description The Special Exhibition shop will be integrated into the exhibit space as a separate shop/kiosk/carts as required. Public Non-Collection Space 0 Number of Occupants TBD Visual Privacy (full, partial, open) Zone Designation Zone A Room Height 0 LEED NC Regurlarly Occupied Space 0 Base ACOUSTICS Equipment Hardware/STC Rating 0 NRCSTC 45 0 Plug Loads Air Change/ HR Walls HVAC ENGINEERING CRITERIA Temperature Lighting 45% RH ±2ºF 110v, 20a, 1ph Yes ±15% RH Power No 0 Pressure (+/-) 76ºF Summer, 71ºF Winter Floor Operable Windows Separation/STC FURNITURE/EQUIPMENT Moveable 0 Fixed RT60 & Shaping 0 TBD
in
In
Special Exhibition area SUSTAINABILITY FEATURES Adjacencies
Floor Level 0 Room
Open
Length, Width, Shape
vs. Private CRITICAL DIMENSIONS

This room data sheet is not comprehensive in nature. Information regarding specific room features may not have been available and was intentionally left blank.

Accessibility Requirement:

Adjacencies

Compliance with ADA/ABAAG (2004) citations is required for accessibility. SI also requires compliance with SI Accessibility Guidelines and the IBC. Comparisons should be made and the more stringent requirement followed for design purposes. See Accessibility Narrative for additional information.

Outer Hall, Museum Shop, Café, Visitor Amenities, Orientation Theater

Functional Description Food from various regions of the country will be featured, healthy eating options will also be served. Includes seating and serving areas, will follow NMAI model of dual purpose use. Possible use as multi-purpose for after hours special events.

SUSTAINABILITY FEATURES

Please refer to structural narrative for more information on structural requirements.

CRITICAL DIMENSIONS

37 Room Data Sheets | FREELON BOND Infrastructure Only 0 Other Amenities Deionized Water Vacuum Yes Speakers OH Gr. 2, 130 SF/HD FIRE ALARM Smoke Detection Yes Wet Sprinkler Special Waste Dry Sprinkler Pre-Action Sprinkler No FIRE PROTECTION Grease Interceptor Considerations for Water 0 No Floor Drains Floor Sink Grey/Blackwater Piping 0 Yes No Yes Protected Hot/Cold No No Recycled Water Supply (treated) 0 Yes Public Address Audio Compressed Air Audio Visual Requirements Yes Hot/Cold Water Task Light Yes To Be Considered 0 Plant/Clean Steam 0 Acoustic Sensitivity NC 40 Vibration Sensitivity Special Equipment/Artifact Sensitivity PLUMBING Target Illuminance (IES 9th Edition) Daylight Sensor 30 FC Exhibit Light To Be Considered Power Density (AHSRAE 2004) 2.1 W/ft² Temperature Deviations (+/-) 0 Yes Process Water UPS Switched Receptacles Dimming No Humidity 0 No Other Humidity Deviation (+/-) 8 min. 0 No Outside Air Single/Multi-Level Switching 0 Emergency/Standby Power 20 CFM/person 30/65 Single Occupancy Sensor Special Exhaust Sub-metering & Feedback Displays Filtration (Pre/Final/Other) Voice/Data DATA/TELECOMMUNICATIONS Yes 0 SECURITY 0 5.0 kPa/8.9 kN Floor Loading/Point Loads DAYLIGHTING 0 0 Shading Considerations Top/Side Lighting Verify Yes- separate zone STRUCTURAL 0 0 Refer to information indicated in Volume IV, Section E Open dual purpose NMAI Model Technical Comment: Themed Public Cafeteria Assignable Square Feet (ASF) OFEO Space Dimensions 0 Organizational Unit Other Interior Glazing 0 0 Yes Yes Cleanable Ceiling CRITICAL FINISHES 0 Negative
ELECTRICAL ARCHITECTURAL
Zone Room ID A2.4 Room Name 0
Public Non-Collection Space 8,000 Number of Occupants 325 Visual Privacy (full, partial, open) Zone Designation Zone A Room Height 0 LEED
Regurlarly
Space 0 Base ACOUSTICS Equipment Hardware/STC Rating Yes NRC Absorptive ceiling finish with an NRC 0.80 or higher STC 55 0 Plug Loads Air Change/ HR Walls HVAC ENGINEERING
Temperature Lighting 45% RH ±2ºF 110v, 20a, 1ph Yes ±15% RH Power No Cleanable Pressure (+/-) 76ºF Summer, 71ºF Winter Floor Operable Windows
FURNITURE/EQUIPMENT Moveable Yes Fixed RT60 & Shaping 1.0 s Lower
NC
Occupied
CRITERIA
Separation/STC
Floor Level 0 Room
Open
Length, Width, Shape
vs. Private

This room data sheet is not comprehensive in nature. Information regarding specific room features may not have been available and was intentionally left blank.

Accessibility Requirement:

Adjacencies

SUSTAINABILITY FEATURES

Compliance with ADA/ABAAG (2004) citations is required for accessibility. SI also requires compliance with SI Accessibility Guidelines and the IBC. Comparisons should be made and the more stringent requirement followed for design purposes. See Accessibility Narrative for additional information.

Café Warming Kitchen, Outer Hall, Cafeteria, Museum Shop, Visitor Amenities, Patrons Lounge

at

up into the Patron's Lounge for extra

and/or multi-purpose for after hours special events. Vistas over the Mall but no views to the White House (as per Security restrictions).

CRITICAL DIMENSIONS

Separation/STC

ceiling finish with an NRC 0.80 or higher. Room has analog connectivity to alarm.

Please refer to structural narrative for more information on structural requirements.

Smithsonian Institution National Museum of African American History and Culture 38 Infrastructure Only 0 Other Amenities Deionized Water Vacuum Yes Speakers OH Gr. 2, 130 SF/HD FIRE ALARM Smoke Detection Yes Wet Sprinkler Special Waste Dry Sprinkler Pre-Action Sprinkler No FIRE PROTECTION Grease Interceptor Considerations for Water 0 No Floor Drains Floor Sink Grey/Blackwater Piping 0 Yes No Yes Protected Hot/Cold No No Recycled Water Supply (treated) 0 Yes Public Address Audio Compressed Air Audio Visual Requirements Yes Hot/Cold Water Task Light Yes To Be Considered 0 Plant/Clean Steam 0 Acoustic Sensitivity NC 35 Vibration Sensitivity Special Equipment/Artifact Sensitivity PLUMBING Target Illuminance (IES 9th Edition) Daylight Sensor 30 FC Exhibit Light To Be Considered Power Density (AHSRAE 2004) 2.1 W/ft² Temperature Deviations (+/-) 0 Yes Process Water UPS Switched Receptacles Dimming No Humidity 0 Yes Other Humidity Deviation (+/-) 8 min. 0 No Outside Air Single/Multi-Level Switching 0 Emergency/Standby Power 20 CFM/person 30/65 Single Occupancy Sensor Special Exhaust Sub-metering & Feedback Displays Filtration (Pre/Final/Other) Voice/Data DATA/TELECOMMUNICATIONS Yes 0 SECURITY 0 5.0 kPa/8.9 kN Floor Loading/Point Loads DAYLIGHTING 0 0 Shading Considerations Top/Side Lighting 0 Yes- separate zone STRUCTURAL 0 0 Refer to information indicated in Volume IV, Section E 0 dual purpose Technical Comment: Café Assignable Square Feet (ASF) OFEO Space Dimensions 0 Organizational Unit Other Interior Glazing 0 0 0 0 0 Ceiling CRITICAL FINISHES 0 Negative
ELECTRICAL ARCHITECTURAL
Zone Room ID A2.5 Room Name 0
fare
day,
Public Non-Collection Space 1,500 Number of Occupants 40 Seated Visual Privacy (full, partial, open) Zone Designation Zone A Room Height 0 LEED NC Regurlarly
Space 0 Base ACOUSTICS Equipment Hardware/STC Rating Yes
STC 55 0 Plug Loads Air Change/ HR Walls HVAC ENGINEERING
Temperature Lighting 45% RH ±2ºF 110v, 20a, 1ph Yes ±15% RH Power No 0 Pressure (+/-) 76ºF Summer, 71ºF Winter Floor Operable Windows
Functional Description This space will serve beverages and light
to visitors throughout the
night could possibly open
seating
Occupied
NRC Absorptive
CRITERIA
FURNITURE/EQUIPMENT Moveable 0 Fixed RT60 & Shaping 1.0 s TBD
Floor Level 0 Room
Length, Width, Shape Open vs. Private

This room data sheet is not comprehensive in nature. Information regarding specific room features may not have been available and was intentionally left

vs. Private

Compliance with ADA/ABAAG (2004) citations is required for accessibility. SI also requires compliance with SI Accessibility Guidelines and the IBC. Comparisons should be made and the more stringent requirement followed for design purposes. See Accessibility Narrative for additional information.

in life/rescue equipment (gurneys, etc.).

CRITICAL DIMENSIONS

Recommend sink under Plumbing. Please refer to structural narrative for more information on structural requirements.

39 Room Data Sheets | FREELON BOND Infrastructure Only 0 Other Amenities Deionized Water Vacuum Yes Speakers OH Gr. 2, 130 SF/HD FIRE ALARM Smoke Detection Yes Wet Sprinkler Special Waste Dry Sprinkler Pre-Action Sprinkler No FIRE PROTECTION No Considerations for Water 0 No Floor Drains Floor Sink Grey/Blackwater Piping 0 No No No Protected Hot/Cold No No Recycled Water Supply (treated) 0 No Public Address Audio Compressed Air Audio Visual Requirements Yes Hot/Cold Water Task Light Yes No 0 Plant/Clean Steam 0 Acoustic Sensitivity NC 35 Vibration Sensitivity Special Equipment/Artifact Sensitivity PLUMBING Target Illuminance (IES 9th Edition) Daylight Sensor 10 FC Exhibit Light To Be Considered Power Density (AHSRAE 2004) 0.6 W/ft² Temperature Deviations (+/-) 0 No Process Water UPS Switched Receptacles Dimming No Humidity 0 Yes Other Humidity Deviation (+/-) 6 min. 0 No Outside Air Single/Multi-Level Switching 0 Emergency/Standby Power 15 CFM/person 30/65 Single Occupancy Sensor Special Exhaust Sub-metering & Feedback Displays Filtration (Pre/Final/Other) Voice/Data DATA/TELECOMMUNICATIONS Yes 0 SECURITY 0 5.0 kPa/8.9 kN Floor Loading/Point Loads DAYLIGHTING 0 0 Shading Considerations Top/Side Lighting 0 0 STRUCTURAL 0 0 Refer to information indicated in Volume IV, Section E Full 0 Technical Comment: First Aid/Sickroom Assignable Square Feet (ASF) OFEO Space Dimensions 0 Organizational Unit Other Interior Glazing 0 0 0 0 Cleanable Ceiling CRITICAL FINISHES 0 Negative
ELECTRICAL ARCHITECTURAL
Zone Room ID A2.6 Room Name 0 Functional
First
Public Non-Collection Space 400 Number of Occupants TBD Visual Privacy (full, partial, open) Zone Designation Zone A Room Height 0 LEED
Space 0 Base ACOUSTICS Equipment Hardware/STC Rating Yes NRC
STC 55 0 Plug Loads Air Change/ HR Walls HVAC ENGINEERING
Temperature Lighting 45% RH ±2ºF 110v, 20a, 1ph Yes ±15% RH Power 0 Cleanable Pressure (+/-) 76ºF Summer, 71ºF Winter Floor Operable Windows Separation/STC FURNITURE/EQUIPMENT Moveable 0 Fixed RT60 & Shaping 0 Lower
blank.
Description
Aid area serving visitors and staff. Lie-down space and access for EMT required, large enough for emergency workers to bring
NC Regurlarly Occupied
Absorptive ceiling finish with an NRC 0.70 or higher
CRITERIA
Outer Hall
Floor Level 0 Room
Open
SUSTAINABILITY FEATURES Adjacencies Accessibility Requirement:
Length, Width, Shape

This room data sheet is not comprehensive in nature. Information regarding specific room features may not have been available and was intentionally left blank.

Accessibility Requirement:

Adjacencies

Compliance with ADA/ABAAG (2004) citations is required for accessibility. SI also requires compliance with SI Accessibility Guidelines and the IBC. Comparisons should be made and the more stringent requirement followed for design purposes. See Accessibility Narrative for additional information.

Threshold Experience, Central Hall, Reception Podium/Info Desk, Security Check Areas

Functional Description Staffed Checkroom, in non-ticketed area, with coat racks, separate drop-off and pickup lines. Up to 100 coin-operated backpack lockers may be incorporated into adjacent area, or replaced with bag check in security screening area. TBD per OPS.

SUSTAINABILITY FEATURES

vs. Private

Please refer to structural narrative for more information on structural requirements.

CRITICAL DIMENSIONS

Length, Width, Shape

Smithsonian Institution National Museum of African American History and Culture 40 Infrastructure Only 0 Other Amenities Deionized Water Vacuum Yes Speakers OH Gr. 2, 130 SF/HD FIRE ALARM Smoke Detection Yes Wet Sprinkler Special Waste Dry Sprinkler Pre-Action Sprinkler No FIRE PROTECTION No Considerations for Water 0 No Floor Drains Floor Sink Grey/Blackwater Piping 0 No No No Protected Hot/Cold No No Recycled Water Supply (treated) 0 No Public Address Audio Compressed Air Audio Visual Requirements No Hot/Cold Water Task Light Yes No 0 Plant/Clean Steam 0 Acoustic Sensitivity NC 40 Vibration Sensitivity Special Equipment/Artifact Sensitivity PLUMBING Target Illuminance (IES 9th Edition) Daylight Sensor 10 FC Exhibit Light To Be Considered Power Density (AHSRAE 2004) 1.1 W/ft² Temperature Deviations (+/-) 0 No Process Water UPS Switched Receptacles Dimming No Humidity 0 No Other Humidity Deviation (+/-) 6 min. 0 No Outside Air Single/Multi-Level Switching 0 Emergency/Standby Power 0.05 CFM/SF 30/65 Single Occupancy Sensor Special Exhaust Sub-metering & Feedback Displays Filtration (Pre/Final/Other) Voice/Data DATA/TELECOMMUNICATIONS Yes 0 SECURITY 0 5.0 kPa/8.9 kN Floor Loading/Point Loads DAYLIGHTING 0 0 Shading Considerations Top/Side Lighting 0 0 STRUCTURAL 0 0 Refer to information indicated
Volume IV,
E 0 Uncertain what SI's
will be Technical Comment: Checkrooms, Public Assignable Square Feet
OFEO Space Dimensions 0 Organizational Unit Other Interior Glazing 0 0 Yes Yes 0 Ceiling CRITICAL FINISHES 0 Positive
in
Section
process
(ASF)
ELECTRICAL ARCHITECTURAL
Zone Room ID A2.7 Room Name 0
Public Non-Collection Space 800 Number of Occupants NA Visual Privacy (full, partial, open) Zone Designation Zone A Room Height 0 LEED NC
Occupied Space 0 Base ACOUSTICS Equipment Hardware/STC Rating 0 NRCSTC 45 0 Plug Loads Air Change/ HR Walls HVAC ENGINEERING
Temperature Lighting 45% RH ±2ºF 110v, 20a, 1ph Yes ±15% RH Power No 0 Pressure (+/-) 76ºF Summer, 71ºF Winter Floor Operable Windows Separation/STC FURNITURE/EQUIPMENT Moveable Yes Fixed RT60 & Shaping 0 Lower
Regurlarly
CRITERIA
Floor Level 0 Room
Open

This room data sheet is not comprehensive in

Compliance with ADA/ABAAG (2004) citations is required for accessibility. SI also requires compliance with SI Accessibility Guidelines and the IBC. Comparisons should be made and the more stringent requirement followed for design purposes. See Accessibility Narrative for additional information.

CRITICAL DIMENSIONS

vs. Private

Please refer to structural narrative for more information on structural requirements.

41 Room Data Sheets | FREELON BOND Infrastructure Only 0 Other Amenities Deionized Water Vacuum Yes Speakers OH Gr. 2, 130 SF/HD FIRE ALARM Smoke Detection Yes Wet Sprinkler Special Waste Dry Sprinkler Pre-Action Sprinkler No FIRE PROTECTION No Considerations for Water 0 No Floor Drains Floor Sink Grey/Blackwater Piping 0 No No No Protected Hot/Cold No No Recycled Water Supply (treated) 0 No Public Address Audio Compressed Air Audio Visual Requirements No Hot/Cold Water Task Light No No 0 Plant/Clean Steam 0 Acoustic Sensitivity 0 Vibration Sensitivity Special Equipment/Artifact Sensitivity PLUMBING Target Illuminance (IES 9th Edition) Daylight Sensor 10 FC Exhibit Light No Power Density (AHSRAE 2004) 0.8 W/ft² Temperature Deviations (+/-) 0 No Process Water UPS Switched Receptacles Dimming To Be Considered Humidity 0 No Other Humidity Deviation (+/-) 6 min. 0 No Outside Air Single/Multi-Level Switching 0 Emergency/Standby Power 0.05 CFM/SF 30/65 Single Occupancy Sensor Special Exhaust Sub-metering & Feedback Displays Filtration (Pre/Final/Other) Voice/Data DATA/TELECOMMUNICATIONS 0 0 SECURITY 0 5.0 kPa/8.9 kN Floor Loading/Point Loads DAYLIGHTING 0 0 Shading Considerations Top/Side Lighting 0 0 STRUCTURAL 0 0 Refer to information indicated in Volume IV, Section E Full/Partial 0 Technical Comment: Wheelchair Storage Assignable Square Feet (ASF) OFEO Space Dimensions 0 Organizational Unit Other Interior Glazing 0 0 No No 0 Ceiling CRITICAL FINISHES 0 Positive
ELECTRICAL ARCHITECTURAL
nature.
available
left blank. Zone Room ID A2.8 Room Name 0 Functional Description These should be stored close to Reception/Information Desk area, so they can be brought
visitors in need. Public Non-Collection Space 100 Number of Occupants NA Visual Privacy (full, partial, open) Zone Designation Zone A Room Height 0 LEED NC Regurlarly Occupied Space 0 Base ACOUSTICS Equipment Hardware/STC Rating 0 NRC0 0 Plug Loads Air Change/ HR Walls HVAC ENGINEERING CRITERIA Temperature Lighting 45% RH ±2ºF 110v, 20a, 1ph Yes ±15% RH Power No 0 Pressure (+/-) 76ºF Summer, 71ºF Winter Floor Operable Windows
Information regarding specific room features may not have been
and was intentionally
out to
Moveable No Fixed RT60 & Shaping 0 Lower
Separation/STC FURNITURE/EQUIPMENT
Outer Hall
Adjacencies
Floor Level 0 Room
Open
SUSTAINABILITY FEATURES
Accessibility Requirement:
Length, Width, Shape

This room data sheet is not comprehensive in nature. Information regarding specific room features may not have been available and was intentionally left blank.

Accessibility Requirement:

SUSTAINABILITY FEATURES Adjacencies

Compliance with ADA/ABAAG (2004) citations is required for accessibility. SI also requires compliance with SI Accessibility Guidelines and the IBC. Comparisons should be made and the more stringent requirement followed for design purposes. See Accessibility Narrative for additional information.

Distributed, Visitor Amenities Area

CRITICAL DIMENSIONS

Width, Shape

Recommend sensor faucets under Plumbing. Please refer to structural narrative for more information on structural requirements.

Smithsonian Institution National Museum of African American History and Culture 42 Infrastructure Only 0 Other Amenities Deionized Water Vacuum Yes Speakers OH Gr. 2, 130 SF/HD FIRE ALARM Smoke Detection Yes Wet Sprinkler Special Waste Dry Sprinkler Pre-Action Sprinkler No FIRE PROTECTION No Considerations for Water 0 No Floor Drains Floor Sink Grey/Blackwater Piping 0 No No Reclaimed water for flushing Protected Hot/Cold No No Recycled Water Supply (treated) 0 Yes Public Address Audio Compressed Air Audio Visual Requirements Yes Hot/Cold Water Task Light No No 0 Plant/Clean Steam 0 Acoustic Sensitivity NC 40 Vibration Sensitivity Special Equipment/Artifact Sensitivity PLUMBING Target Illuminance (IES 9th Edition) Daylight Sensor 5 FC Exhibit Light No Power Density (AHSRAE 2004) 0.9 W/ft² Temperature Deviations (+/-) 0 No Process Water UPS Switched Receptacles Dimming To Be Considered Humidity 0 No Other Humidity Deviation (+/-) 8 min. 0 No Outside Air Single/Multi-Level Switching 0 Emergency/Standby Power 50 CFM/WC or Urinal 30/65 Single Occupancy Sensor Special Exhaust Sub-metering & Feedback Displays Filtration (Pre/Final/Other) Voice/Data DATA/TELECOMMUNICATIONS 0 0 SECURITY 0 5.0 kPa/8.9 kN Floor Loading/Point Loads DAYLIGHTING 0 0 Shading Considerations Top/Side Lighting 0 Yes STRUCTURAL 0 0 Refer to information indicated in Volume IV, Section E Full 0 Technical Comment: Public Washrooms, Men's Assignable Square Feet (ASF) OFEO Space Dimensions 0 Organizational Unit Other Interior Glazing 0 0 Yes Yes Cleanable Ceiling CRITICAL FINISHES 0 Negative
ELECTRICAL ARCHITECTURAL
Zone Room ID A2.9 Room Name 0 Functional Description 0 Public Non-Collection Space 0 Number of Occupants TBD Visual Privacy (full, partial, open) Zone Designation Zone A Room Height 0 LEED NC Regurlarly Occupied Space 0 Base ACOUSTICS Equipment Hardware/STC Rating Yes NRCSTC 55 0 Plug Loads Air Change/ HR Walls HVAC ENGINEERING CRITERIA Temperature Lighting 45% RH ±2ºF 110v, 20a, 1ph Yes ±15% RH Power No Cleanable Pressure (+/-) 76ºF Summer, 71ºF Winter Floor Operable Windows
Moveable Yes Fixed RT60 & Shaping 0 Lower/Upper
Separation/STC FURNITURE/EQUIPMENT
Floor Level 0 Room
Open
Length,
vs. Private

This room data sheet is not comprehensive in nature. Information regarding specific room features may not have been available and was intentionally left blank.

Accessibility Requirement:

SUSTAINABILITY FEATURES Adjacencies

Compliance with ADA/ABAAG (2004) citations is required for accessibility. SI also requires compliance with SI Accessibility Guidelines and the IBC. Comparisons should be made and the more stringent requirement followed for design purposes. See Accessibility Narrative for additional information.

Distributed, Visitor Amenities Area

CRITICAL DIMENSIONS

Width, Shape

Recommend sensor faucets under Plumbing. Please refer to structural narrative for more information on structural requirements.

43 Room Data Sheets | FREELON BOND Infrastructure Only 0 Other Amenities Deionized Water Vacuum Yes Speakers OH Gr. 2, 130 SF/HD FIRE ALARM Smoke Detection Yes Wet Sprinkler Special Waste Dry Sprinkler Pre-Action Sprinkler No FIRE PROTECTION No Considerations for Water 0 No Floor Drains Floor Sink Grey/Blackwater Piping 0 No No Reclaimed water for flushing Protected Hot/Cold No No Recycled Water Supply (treated) 0 Yes Public Address Audio Compressed Air Audio Visual Requirements Yes Hot/Cold Water Task Light No No 0 Plant/Clean Steam 0 Acoustic Sensitivity NC 40 Vibration Sensitivity Special Equipment/Artifact Sensitivity PLUMBING Target Illuminance (IES 9th Edition) Daylight Sensor 5 FC Exhibit Light No Power Density (AHSRAE 2004) 0.9 W/ft² Temperature Deviations (+/-) 0 No Process Water UPS Switched Receptacles Dimming To Be Considered Humidity 0 No Other Humidity Deviation (+/-) 8 min. 0 No Outside Air Single/Multi-Level Switching 0 Emergency/Standby Power 50 CFM/WC or Urinal 30/65 Single Occupancy Sensor Special Exhaust Sub-metering & Feedback Displays Filtration (Pre/Final/Other) Voice/Data DATA/TELECOMMUNICATIONS 0 0 SECURITY 0 5.0 kPa/8.9 kN Floor Loading/Point Loads DAYLIGHTING 0 0 Shading Considerations Top/Side Lighting 0 Yes STRUCTURAL 0 0 Refer to information indicated in Volume IV, Section E Full 0 Technical Comment: Public Washrooms, Women's Assignable Square Feet (ASF) OFEO Space Dimensions 0 Organizational Unit Other Interior Glazing 0 0 Yes Yes Cleanable Ceiling CRITICAL FINISHES 0 Negative
ELECTRICAL ARCHITECTURAL
Zone Room ID A2.10 Room Name 0 Functional Description 0 Public Non-Collection Space 0 Number of Occupants TBD Visual Privacy (full, partial, open) Zone Designation Zone A Room Height 0 LEED NC Regurlarly Occupied Space 0 Base ACOUSTICS Equipment Hardware/STC Rating Yes NRCSTC 55 0 Plug Loads Air Change/ HR Walls HVAC ENGINEERING CRITERIA Temperature Lighting 45% RH ±2ºF 110v, 20a, 1ph Yes ±15% RH Power No Cleanable Pressure (+/-) 76ºF Summer, 71ºF Winter Floor Operable Windows
Moveable Yes Fixed RT60 & Shaping 0 Lower/Upper
Separation/STC FURNITURE/EQUIPMENT
Floor Level 0 Room
Open
Length,
vs. Private

This room data sheet is not comprehensive in nature. Information regarding specific room features may not have been available and was intentionally left blank.

Accessibility Requirement:

Adjacencies

SUSTAINABILITY FEATURES

Compliance with ADA/ABAAG (2004) citations is required for accessibility. SI also requires compliance with SI Accessibility Guidelines and the IBC. Comparisons should be made and the more stringent requirement followed for design purposes. See Accessibility Narrative for additional information.

Distributed, Visitor Amenities Area

CRITICAL DIMENSIONS

Length, Width, Shape

FURNITURE/EQUIPMENT

Recommend sensor faucets under Plumbing. Please refer to structural narrative for more information on structural requirements.

Smithsonian Institution National Museum of African American History and Culture 44 Infrastructure Only 0 Other Amenities Deionized Water Vacuum Yes Speakers OH Gr. 2, 130 SF/HD FIRE ALARM Smoke Detection Yes Wet Sprinkler Special Waste Dry Sprinkler Pre-Action Sprinkler No FIRE PROTECTION No Considerations for Water 0 No Floor Drains Floor Sink Grey/Blackwater Piping 0 No No Reclaimed water for flushing Protected Hot/Cold No No Recycled Water Supply (treated) 0 Yes Public Address Audio Compressed Air Audio Visual Requirements Yes Hot/Cold Water Task Light No No 0 Plant/Clean Steam 0 Acoustic Sensitivity NC 40 Vibration Sensitivity Special Equipment/Artifact Sensitivity PLUMBING Target Illuminance (IES 9th Edition) Daylight Sensor 5 FC Exhibit Light No Power Density (AHSRAE 2004) 0.9 W/ft² Temperature Deviations (+/-) 0 No Process Water UPS Switched Receptacles Dimming To Be Considered Humidity 0 No Other Humidity Deviation (+/-) 8 min. 0 No Outside Air Single/Multi-Level Switching 0 Emergency/Standby Power 50 CFM/WC or Urinal 30/65 Single Occupancy Sensor Special Exhaust Sub-metering & Feedback Displays Filtration (Pre/Final/Other) Voice/Data DATA/TELECOMMUNICATIONS 0 0 SECURITY 0 5.0 kPa/8.9 kN Floor Loading/Point Loads DAYLIGHTING 0 0 Shading Considerations Top/Side Lighting 0 Yes STRUCTURAL 0 0 Refer to information indicated in Volume IV, Section E Full 0 Technical Comment: Family & H/C Washrooms Assignable Square Feet (ASF) OFEO Space Dimensions 0 Organizational Unit Other Interior Glazing 0 0 No Yes Cleanable Ceiling CRITICAL FINISHES 0 Negative
ELECTRICAL ARCHITECTURAL
Zone Room ID A2.11 Room Name 0 Functional Description 0 Public Non-Collection Space 0 Number of Occupants TBD Visual Privacy (full, partial, open) Zone Designation Zone A Room Height 0 LEED NC Regurlarly Occupied Space 0 Base ACOUSTICS Equipment Hardware/STC Rating Yes NRCSTC 55 0 Plug Loads Air Change/ HR Walls HVAC ENGINEERING CRITERIA Temperature Lighting 45% RH ±2ºF 110v, 20a, 1ph Yes ±15% RH Power No Cleanable Pressure (+/-) 76ºF Summer, 71ºF Winter Floor Operable Windows
Separation/STC
Moveable Yes Fixed RT60 & Shaping 0 Lower/Upper
Floor Level 0 Room
Open
vs. Private

A

ARCHITECTURAL

This room datasheet is not comprehensive in nature. Information regarding specific room features may not have been availabe and was intetionally left blank. The room should be optimized for speech incluidng overhead reflectors and interior finishes to best aid the projection of voice from the possible stage locations into the audience areas. Variable accoustics should be provided to allow for the space to be used as a musical recital space, drama theater, auditorium and cinema. Allow a volume/seat of around 100-175 cubic feet and ensure reverberation can be controlled to optimize for all necessary functions. Theaters have MGH net-to-gross ratios in the range of 1.6+.

Assignable Square Feet (ASF) OFEO Space Dimensions

Accessibility Requirement:

Adjacencies

(full,

Compliance with ADA/ABAAG (2004) citations is required for accessibility. SI also requires compliance with SI Accessibility Guidelines and the IBC. Comparisons should be made and the more stringent requirement followed for design purposes. Visual and sound displays must be accessible to people with sight and hearing impairments. See especially ADA/ABAAG (2004) 221.2.3 Lines of Sight and Dispersion for line of sight requirements. See Accessibility Narrative for additional information.

Outer Hall, Visitor Amenities,

Functional Description To be used primarily for

SUSTAINABILITY FEATURES

panels & film; limited music, dance, performance.

CRITICAL DIMENSIONS

Length, Width, Shape Open vs. Private

vestibules or appropriate sound

NRC Optimized for a speech and a reverbation time, this will most likely entail absorptive finsihes on the walls and ceiling

CRITICAL FINISHES

Recommend drinking fountain under Plumbing, recommend stage lighting under Electrical Lighting. Please refer to structural narrative for more information on structural requirements. ELECTRICAL

media box. Provisions for televised events. Refer to information indicated in Volume IV, Section E

45 Room Data Sheets | FREELON BOND Infrastructure OnlyOther Amenities Deionized Water Vacuum Yes Speakers OH Gr. 2, 130 SF/HD FIRE ALARM Smoke Detection Yes Wet Sprinkler Special Waste Dry Sprinkler Pre-Action Sprinkler No FIRE PROTECTION No Considerations for Water 0 No Floor Drains Floor Sink Grey/Blackwater Piping 0 No No No Protected Hot/Cold No No Recycled Water Supply (treated) 0 No Public Address Audio Compressed Air Audio Visual Requirements Yes Hot/Cold Water Task Light No Yes 0 Plant/Clean Steam 0 Acoustic Sensitivity NC 25-30 Vibration Sensitivity Special Equipment/Artifact Sensitivity PLUMBING Target Illuminance (IES 9th Edition) Daylight Sensor 10 FC Exhibit Light No Power Density (AHSRAE 2004) 0.7 W/ft² Temperature Deviations (+/-) 0 Yes Process Water UPS Switched Receptacles Dimming No Humidity 0 Yes Other Humidity Deviation (+/-) 8 min. 0 No Outside Air Single/Multi-Level Switching No Emergency/Standby Power 15 CFM/person 30/65 Multi Occupancy Sensor Special Exhaust Sub-metering & Feedback Displays Filtration (Pre/Final/Other) Voice/Data DATA/TELECOMMUNICATIONS Yes, State, Equipment and Operater Locations 0 SECURITY 0 5.0 kPa/8.9 kN Floor Loading/Point Loads DAYLIGHTING 0 0 Shading Considerations Top/Side Lighting Full presentation system-display, audio & control. Needs separate control rooms space. Yes STRUCTURAL 0 Connection to
door
Full/Partial 0 Technical Comment:
out
Auditorium/Theater
0
Other Interior
Accoustical Sound
doors Yes Yes Sloped/Stepped
Organizational Unit
Glazing
rated
Ceiling
Accoustical Positive
A3.1 Room Name 0
Zone Room ID
Public
5,500 Number
350
Room Height High LEED NC Regurlarly Occupied Space 0 Base ACOUSTICS Equipment Hardware/STC Rating 0
lectures/discussion
Non-Collection Space
of Occupants
Visual Privacy
partial, open) Zone Designation Zone
STC 58-60 0 Plug Loads Air Change/ HR Walls HVAC ENGINEERING
Temperature Lighting 45% RH ±2ºF 110v, 20a, 1ph Yes ±15% RH Power No 0 Pressure (+/-) 76ºF Summer, 71ºF Winter Floor Operable Windows
FURNITURE/EQUIPMENT Moveable Yes Fixed RT60 &
0 TBD
CRITERIA
Separation/STC
Shaping
Floor
0 Room
Level

The room data sheet is not comprehensive in nature. Information regarding specific room features may not have been availabe and was intentionally left blank. This is a sensative space and should be located awary from noisy, high intensity spaces. The room should be optimized for speech including overhead reflectors and interior finishes. Reverberation time 0.5-0.7 seconds.

Accessibility Requirement:

Adjacencies

SUSTAINABILITY FEATURES

vs. Private

Compliance withADA/ABAAG (2004) citations is required for accessibility. SI also requires compliance with SI Accessibility Guidelines and the IBC. Comparisons should be made and the more stringent requirement followed for design purposes. See Accessibility Narrative for additional information.

Outer Hall, Museum Shop, Café, Visitor Amenities, Orientation Theater

Functional Description The start times of these theaters will be staggered to provide a more even flow of people into the exhibition galleries.These 2 theaters capable of being merged into one larger theater for larger number of visitors/special presentations as required.

CRITICAL DIMENSIONS

Length, Width, Shape

Recommend stage lighting under Electrical Lighting. Please refer to structural narrative for more information on structural requirements. ELECTRICAL ARCHITECTURAL

NRC Optimized for a speech and audio systems presentation, this will most likely entail absorptive finishes on walls and ceiling

Refer to information indicated in Volume IV, Section

Smithsonian Institution National Museum of African American History and Culture 46 Infrastructure Only 0 Other Amenities Deionized Water Vacuum Yes Speakers OH Gr. 2, 130 SF/HD FIRE ALARM Smoke Detection Yes Wet Sprinkler Special Waste Dry Sprinkler Pre-Action Sprinkler No FIRE PROTECTION No Considerations for Water 0 No Floor Drains Floor Sink Grey/Blackwater Piping 0 No No No Protected Hot/Cold No No Recycled Water Supply (treated) 0 No Public Address Audio Compressed Air Audio Visual Requirements No Hot/Cold Water Task Light No To Be Considered 0 Plant/Clean Steam 0 Acoustic Sensitivity NC 25-30 Vibration Sensitivity Special Equipment/Artifact Sensitivity PLUMBING Target Illuminance (IES 9th Edition) Daylight Sensor 10 FC Exhibit Light No Power Density (AHSRAE 2004) 0.7 W/ft² Temperature Deviations (+/-) 0 Yes Process Water UPS Switched Receptacles Dimming No Humidity 0 Yes Other Humidity Deviation (+/-) 8 min. 0 No Outside Air Single/Multi-Level Switching 0 Emergency/Standby Power 15 CFM/person 30/65 Multi Occupancy Sensor Special Exhaust Sub-metering & Feedback Displays Filtration (Pre/Final/Other) Voice/Data DATA/TELECOMMUNICATIONS Yes, Equipment Locations 0 SECURITY 0 5.0 kPa/8.9 kN Floor Loading/Point Loads DAYLIGHTING 0 0 Shading Considerations Top/Side Lighting Experiental audiovisual solution developed in conjunction with orientation theatre. No STRUCTURAL 0 0
Full/Partial 0 Technical Comment: Orientation Theater 1 & 2 Assignable Square Feet (ASF) OFEO Space Dimensions 0 Organizational Unit Other Interior Glazing 0 Sound vestibules
appropriate sound rated door 0 Yes 0 Ceiling CRITICAL FINISHES 0 Positive
E
or
Zone Room ID A3.2 Room Name 0
Public Non-Collection Space 1,600 Number of Occupants 75
Visual Privacy
Zone
Zone A Room Height 0 LEED NC Regurlarly Occupied Space 0 Base ACOUSTICS Equipment Hardware/STC Rating 0
(100)
(full, partial, open)
Designation
STC 58-60 0 Plug Loads Air Change/ HR Walls HVAC ENGINEERING
Temperature Lighting 45% RH yr. md. ±2ºF 110v,
1ph Yes ±15% RH yr. md. Power No 0 Pressure (+/-) 76ºF Summer, 71ºF Winter Floor Operable Windows Separation/STC FURNITURE/EQUIPMENT Moveable 0 Fixed RT60 & Shaping 0 TBD
CRITERIA
20a,
Floor Level 0 Room
Open

Small Screening

This room datasheet is not comprehensive in nature. Information regardng specific room features may not have been available and was intentionally left blank. This is a sensitive space and should be located away from noisy, high intensity areas. All finishes should be soft to ensure a well controlled reverberation time, 0.4-0.6 seconds. All surfaces that could create reflections from sound systems should be absorptive.

Accessibility Requirement:

Adjacencies

Compliance withADA/ABAAG (2004) citations is required for accessibility. SI also requires compliance with SI Accessibility Guidelines and the IBC. Comparisons should be made and the more stringent requirement followed for design purposes. See Accessibility Narrative for additional information. CAAMA, Education Assembly

Functional Description Small stage with moveable seating to be aligned with Educational programs. This space is a more intimate room for screening CAAMA and other Educational material.

SUSTAINABILITY FEATURES

vs. Private

CRITICAL DIMENSIONS

Length, Width, Shape

This will most likely entail absorptive finishes on all the walls and ceiling

Please refer to structural narrative for more information on structural requirements.

to information indicated in Volume IV, Section E

47 Room Data Sheets | FREELON BOND Infrastructure Only 0 Other Amenities Deionized Water Vacuum Yes Speakers OH Gr. 2, 130 SF/HD FIRE ALARM Smoke Detection Yes Wet Sprinkler Special Waste Dry Sprinkler Pre-Action Sprinkler No FIRE PROTECTION No Considerations for Water 0 No Floor Drains Floor Sink Grey/Blackwater Piping 0 No No No Protected Hot/Cold No No Recycled Water Supply (treated) 0 No Public Address Audio Compressed Air Audio Visual Requirements No Hot/Cold Water Task Light No No 0 Plant/Clean Steam 0 Acoustic Sensitivity NC 25-30 Vibration Sensitivity Special Equipment/Artifact Sensitivity PLUMBING Target Illuminance (IES 9th Edition) Daylight Sensor 50-100 FC Exhibit Light No Power Density (AHSRAE 2004) Exempt Temperature Deviations (+/-) 0 Yes Process Water UPS Switched Receptacles Dimming No Humidity 0 No Other Humidity Deviation (+/-) 8 min. 0 No Outside Air Single/Multi-Level Switching 0 Emergency/Standby Power 15 CFM/person 30/65 Multi Occupancy Sensor Special Exhaust Sub-metering & Feedback Displays Filtration (Pre/Final/Other) Voice/Data DATA/TELECOMMUNICATIONS Yes 0 SECURITY 0 5.0 kPa/8.9 kN Floor Loading/Point Loads DAYLIGHTING 0 0 Shading Considerations Top/Side Lighting Full presentation system- display, audio & control. Needs separate control room space. No STRUCTURAL 0 0 Refer
0 0 Technical Comment:
Room Assignable
Feet
OFEO Space Dimensions 0 Organizational Unit Other Interior Glazing 0 Sound vestibules or appropriate sound rated doors Yes Yes 0 Ceiling CRITICAL FINISHES 0 Positive
Square
(ASF)
ELECTRICAL
ARCHITECTURAL
Zone Room ID A3.3 Room Name 0
Public Non-Collection Space 800 Number of Occupants 100(50) Visual Privacy (full, partial, open) Zone Designation Zone A Room Height 0 LEED
Regurlarly
0 Base ACOUSTICS Equipment Hardware/STC Rating 0
STC 58-60 0 Plug Loads Air Change/ HR Walls HVAC ENGINEERING
Temperature Lighting 45% RH ±2ºF 110v, 20a, 1ph Yes ±15% RH Power No 0 Pressure (+/-) 76ºF Summer, 71ºF Winter Floor Operable Windows Separation/STC FURNITURE/EQUIPMENT Moveable Yes Fixed RT60 & Shaping 0 TBD
NC
Occupied Space
NRC
CRITERIA
Floor Level 0 Room
Open

This room data sheet is not comprehensive in nature. Information regarding specific room features may not have been available and was intentionally left blank.

(ASF)

Technical Comment:

Compliance with ADA/ABAAG (2004)citations is required for accessibility. SI also requires compliance with SI Accessibility Guidelines and the IBC. Comparisons should be made and the more stringent requirement followed for design purposes. Any stage presentation areas must comply with ADA/ABAAG (2004) citations for access to those areas by a person in a wheelchair including backstage areas. See Accessibility Narrative for additional information.

Group Entry Entrance Lobby, Visitor Amenities, Resource Center, Education Program Spaces, Education Public Storage, Youth Gallery, Education Preparation Area, Education Technology Storage,

for group of 50. These spaces should also be able to be merged into a larger room.

Functional Description These spaces have dual purpose. They will serve as part of the Educational Center to orient and introduce school groups to the NMAAHC, as well as serve as the lunch areas for such groups.

CRITICAL DIMENSIONS

vs. Private

ceiling finish with

Recommend drinking fountain and vending under Plumbing. Please refer to structural narrative for more information on structural requirements.

Refer to information indicated in Volume IV, Section E

Smithsonian Institution National Museum of African American History and Culture 48 Infrastructure Only 0 Other Amenities Deionized Water Vacuum Yes Speakers OH Gr. 2, 130 SF/HD FIRE ALARM Smoke Detection Yes Wet Sprinkler Special Waste Dry Sprinkler Pre-Action Sprinkler No FIRE PROTECTION No Considerations for Water 0 No Floor Drains Floor Sink Grey/Blackwater Piping 0 No No Yes Protected Hot/Cold No No Recycled Water Supply (treated) 0 Yes Public Address Audio Compressed Air Audio Visual Requirements Yes Hot/Cold Water Task Light To Be Considered To Be Considered 0 Plant/Clean Steam 0 Acoustic Sensitivity NC 40 Vibration Sensitivity Special Equipment/Artifact Sensitivity PLUMBING Target Illuminance (IES 9th Edition) Daylight Sensor 30 FC Exhibit Light To Be Considered Power Density (AHSRAE 2004) 2.1 W/ft² Temperature Deviations (+/-) 0 Yes Process Water UPS Switched Receptacles Dimming Yes Humidity 0 No Other Humidity Deviation (+/-) 8 min. 0 No Outside Air Single/Multi-Level Switching 0 Emergency/Standby Power 15 CFM/person 30/65 Single Occupancy Sensor Special Exhaust Sub-metering & Feedback Displays Filtration (Pre/Final/Other) Voice/Data DATA/TELECOMMUNICATIONS Yes 0 SECURITY 0 5.0 kPa/8.9 kN Floor Loading/Point Loads DAYLIGHTING 0 0 Shading Considerations Top/Side Lighting Modest presentation system No STRUCTURAL 0 0
Open/Partial Space
Schools Orientation/Lunch Areas
0
Other Interior
0 Solid
undercut Yes Yes Cleanable Ceiling CRITICAL FINISHES 0 Positive
Assignable Square Feet
OFEO Space Dimensions
Organizational Unit
Glazing
core wood or insulated metal with neoprene strip seals 1/4"
ELECTRICAL
ARCHITECTURAL
Zone Room ID A4.1 Room Name 0
Public Non-Collection Space 1,000 Number of Occupants 50 Visual Privacy (full, partial, open) Zone Designation Zone A Room Height 0 LEED NC Regurlarly Occupied Space 0 Base ACOUSTICS Equipment Hardware/STC Rating 0 NRC Absorptive
an NRC 0.80 or higher STC 50 0 Plug Loads Air Change/ HR Walls HVAC ENGINEERING CRITERIA Temperature Lighting 45% RH ±2ºF 110v, 20a, 1ph Yes ±15% RH Power No Cleanable Pressure (+/-) 76ºF Summer, 71ºF Winter Floor Operable Windows Separation/STC FURNITURE/EQUIPMENT Moveable Yes Fixed RT60 & Shaping 1.0 s Lower
Floor Level 0 Room Length,
Open
SUSTAINABILITY FEATURES Adjacencies Accessibility Requirement:
Width, Shape

This room data sheet is not comprehensive in nature. Information regarding specific room features may not have been available and was intentionally left blank.

Group Entry Entrance Lobby, Visitor Amenities, Education Assembly, Education Public Storage SUSTAINABILITY FEATURES Adjacencies Accessibility Requirement:

Compliance with ADA/ABAAG (2004) citations is required for accessibility. SI also requires compliance with SI Accessibility Guidelines and the IBC. Comparisons should be made and the more stringent requirement followed for design purposes. Any stage presentation areas must comply with ADA/ABAAG (2004) citations for access to those areas by a person in a wheelchair including backstage areas. See Accessibility Narrative for additional information.

The space should be Subdividable into 2 units for smaller groups or different learning programs.

CRITICAL DIMENSIONS

Recommend hand sink under Plumbing. Please refer to structural narrative for more information on structural requirements.

Refer to information indicated in Volume IV, Section E

49 Room Data Sheets | FREELON BOND Infrastructure Only 0 Other Amenities Deionized Water Vacuum Yes Speakers OH Gr. 2, 130 SF/HD FIRE ALARM Smoke Detection Yes Wet Sprinkler Special Waste Dry Sprinkler Pre-Action Sprinkler No FIRE PROTECTION No Considerations for Water 0 No Floor Drains Floor Sink Grey/Blackwater Piping 0 No No No Protected Hot/Cold No No Recycled Water Supply (treated) 0 No Public Address Audio Compressed Air Audio Visual Requirements Yes Hot/Cold Water Task Light Yes To Be Considered 0 Plant/Clean Steam 0 Acoustic Sensitivity NC 40 Vibration Sensitivity Special Equipment/Artifact Sensitivity PLUMBING Target Illuminance (IES 9th Edition) Daylight Sensor 50 FC Exhibit Light To Be Considered Power Density (AHSRAE 2004) 1.4 W/ft² Temperature Deviations (+/-) 0 Yes Process Water UPS Switched Receptacles Dimming Yes Humidity 0 No Other Humidity Deviation (+/-) 8 min. 0 No Outside Air Single/Multi-Level Switching 0 Emergency/Standby Power 15 CFM/person 30/65 Multi Occupancy Sensor Special Exhaust Sub-metering & Feedback Displays Filtration (Pre/Final/Other) Voice/Data DATA/TELECOMMUNICATIONS Yes 0 SECURITY 0 5.0 kPa/8.9 kN Floor Loading/Point Loads DAYLIGHTING 0 0 Shading Considerations Top/Side Lighting 0 Yes STRUCTURAL 0 0
Full/Partial
Activity Room/Studio/Workshop Assignable Square Feet (ASF) OFEO Space Dimensions 0 Organizational Unit Other Interior Glazing 0 Solid core wood or insulated metal with neoprene strip seals 1/4" undercut Yes Yes Cleanable Ceiling CRITICAL FINISHES 0 Positive
Technical Comment:
ELECTRICAL
ARCHITECTURAL
Zone Room ID A4.2 Room Name 0 Functional Description This space is for studios and workshops is aligned with the Educational Programs Public Non-Collection Space 1,500 Number of Occupants TBD Visual Privacy (full, partial, open) Zone Designation Zone A Room Height 0 LEED NC Regurlarly Occupied Space 0 Base ACOUSTICS Equipment Hardware/STC Rating 0 NRC Absorptive
absorptive wall finish
higher STC 50 0 Plug Loads Air Change/ HR Walls HVAC ENGINEERING CRITERIA Temperature Lighting 45% RH ±2ºF 110v, 20a, 1ph Yes ±15% RH Power No Cleanable Pressure (+/-) 76ºF Summer, 71ºF Winter Floor Operable Windows Separation/STC FURNITURE/EQUIPMENT Moveable Yes Fixed RT60 & Shaping 0 TBD
ceiling finish with an NRC of 0.70 or higher,
on at least one wall from 3'-7' aff with an NRC of 0.7 or
Floor Level 0 Room Length,
Open
Width, Shape
vs. Private

This room data sheet is not comprehensive in nature. Information regarding specific room features may not have been available and was intentionally left blank.

Compliance with ADA/ABAAG (2004) citations is required for accessibility. SI also requires compliance with SI Accessibility Guidelines and the IBC. Comparisons should be made and the more stringent requirement followed for design purposes. Any stage presentation areas must comply with ADA/ABAAG (2004) citations for access to those areas by a person in a wheelchair including backstage areas. See Accessibility Narrative for additional information.

SUSTAINABILITY FEATURES Adjacencies

Group Entry Entrance Lobby, Visitor Amenities, Education Assembly, Education Public Storage

Description This space provides a flexible learning space or expansion for Studios and/or Workshops.

CRITICAL DIMENSIONS

and reverberation time

Please refer to structural narrative for more information on structural requirements.

Smithsonian Institution National Museum of African American History and Culture 50 Infrastructure Only 0 Other Amenities Deionized Water Vacuum Yes Speakers OH Gr. 2, 130 SF/HD FIRE ALARM Smoke Detection Yes Wet Sprinkler Special Waste Dry Sprinkler Pre-Action Sprinkler No FIRE PROTECTION No Considerations for Water 0 No Floor Drains Floor Sink Grey/Blackwater Piping 0 No No No Protected Hot/Cold No No Recycled Water Supply (treated) 0 No Public Address Audio Compressed Air Audio Visual Requirements No Hot/Cold Water Task Light Yes To Be Considered 0 Plant/Clean Steam 0 Acoustic Sensitivity NC 30 Vibration Sensitivity Special Equipment/Artifact Sensitivity PLUMBING Target Illuminance (IES 9th Edition) Daylight Sensor 30-50 FC Exhibit Light To Be Considered Power Density (AHSRAE 2004) 1.4 W/ft² Temperature Deviations (+/-) 0 Yes Process Water UPS Switched Receptacles Dimming Yes Humidity 0 No Other Humidity Deviation (+/-) 6 min. 0 No Outside Air Single/Multi-Level Switching 0 Emergency/Standby Power 15 CFM/person 30/65 Multi Occupancy Sensor Special Exhaust Sub-metering & Feedback Displays Filtration (Pre/Final/Other) Voice/Data DATA/TELECOMMUNICATIONS Yes 0 SECURITY 0 5.0 kPa/8.9 kN Floor Loading/Point Loads DAYLIGHTING 0 0 Shading Considerations Top/Side Lighting Modest presentation system No STRUCTURAL 0 0 Refer to information indicated in Volume IV, Section E Partial 0 Technical Comment: Multipurpose Room - Education Assignable Square Feet (ASF) OFEO Space Dimensions 0 Organizational Unit Other Interior Glazing 0 Solid core wood or insulated metal with neoprene strip seals max 1/4" undercut Yes 0 0 Ceiling CRITICAL FINISHES 0 Positive
ELECTRICAL ARCHITECTURAL
Zone Room ID A4.3 Room Name 0 Functional
Public Non-Collection Space 300 Number of Occupants TBD Visual Privacy (full, partial, open) Zone Designation Zone A Room Height 0 LEED NC Regurlarly Occupied Space 0 Base ACOUSTICS Equipment Hardware/STC Rating 0 NRC Optimized
STC 55 0 Plug Loads Air Change/ HR Walls HVAC ENGINEERING CRITERIA Temperature Lighting 45% RH ±2ºF 110v, 20a, 1ph Yes ±15% RH Power No 0 Pressure (+/-) 76ºF Summer, 71ºF Winter Floor Operable Windows Separation/STC FURNITURE/EQUIPMENT Moveable Yes Fixed RT60 & Shaping 0.6-0.8 s TBD
for speech
Floor Level 0 Room Length,
Open
Accessibility Requirement:
Width, Shape
vs. Private

This room data sheet is not comprehensive in nature. Information regarding specific room features may not have been

Accessibility Requirement:

SUSTAINABILITY FEATURES Adjacencies

Compliance with ADA/ABAAG (2004) citations is required for accessibility. SI also requires compliance with SI Accessibility Guidelines and the IBC. Comparisons should be made and the more stringent requirement followed for design purposes. See Accessibility Narrative for additional information.

Group Entry Entrance Lobby, Visitor Amenities, Program Spaces, Education Assembly

Please refer to structural narrative for more information on structural requirements.

CRITICAL DIMENSIONS

Length, Width, Shape

51 Room Data Sheets | FREELON BOND Infrastructure Only 0 Other Amenities Deionized Water Vacuum Yes Speakers OH Gr. 2, 130 SF/HD FIRE ALARM Smoke Detection Yes Wet Sprinkler Special Waste Dry Sprinkler Pre-Action Sprinkler No FIRE PROTECTION No Considerations for Water 0 No Floor Drains Floor Sink Grey/Blackwater Piping 0 No No No Protected Hot/Cold No No Recycled Water Supply (treated) 0 No Public Address Audio Compressed Air Audio Visual Requirements No Hot/Cold Water Task Light No No 0 Plant/Clean Steam 0 Acoustic Sensitivity 0 Vibration Sensitivity Special Equipment/Artifact Sensitivity PLUMBING Target Illuminance (IES 9th Edition) Daylight Sensor 10 FC Exhibit Light No Power Density (AHSRAE 2004) 0.8 W/ft² Temperature Deviations (+/-) 0 No Process Water UPS Switched Receptacles Dimming Yes Humidity 0 No Other Humidity Deviation (+/-) 6 min. 0 No Outside Air Single/Multi-Level Switching 0 Emergency/Standby Power 0.05 CFM/SF 30/65 Single Occupancy Sensor Special Exhaust Sub-metering & Feedback Displays Filtration (Pre/Final/Other) Voice/Data DATA/TELECOMMUNICATIONS 0 0 SECURITY 0 7.5 kPa/17.8 kN Floor Loading/Point Loads DAYLIGHTING 0 0 Shading Considerations Top/Side Lighting 0 Yes STRUCTURAL 0 0 Refer to information indicated in Volume IV, Section E Full 0 Technical Comment: Folding Stool Bins Storage Assignable Square Feet (ASF) OFEO Space Dimensions 0 Organizational Unit Other Interior Glazing 0 0 Yes No 0 Ceiling CRITICAL FINISHES 0 Negative
ELECTRICAL ARCHITECTURAL
blank. Zone Room ID A4.4 Room Name 0 Functional Description Storage for
folding stools
bins for
School Group Orientation
Public Non-Collection Space 50 Number of Occupants NA Visual Privacy (full, partial, open) Zone Designation Zone A Room Height 0 LEED NC Regurlarly Occupied Space 0 Base ACOUSTICS Equipment Hardware/STC Rating No NRC 0 0 0 Plug Loads Air Change/ HR Walls HVAC ENGINEERING CRITERIA Temperature Lighting 45% RH ±2ºF 110v, 20a, 1ph Yes ±15% RH Power No 0 Pressure (+/-) 76ºF Summer, 71ºF Winter Floor Operable Windows
FURNITURE/EQUIPMENT Moveable No Fixed RT60 & Shaping 0 TBD
available and was intentionally left
the
and
the
and Lunch Areas.
Separation/STC
Floor Level 0 Room
Open
vs. Private

This room data sheet is not comprehensive in nature. Information regarding specific room features may not have been available and was intentionally left blank.

Adjacencies Accessibility Requirement:

Compliance with ADA/ABAAG (2004) citations is required for accessibility. SI also requires compliance with SI Accessibility Guidelines and the IBC. Comparisons should be made and the more stringent requirement followed for design purposes. See Accessibility Narrative for additional information.

Group Entry Entrance Lobby, Visitor Amenities, Program Spaces, Education Assembly

Functional Description Students and groups can store their lunches and backpacks in bins or pull-out cabinets while they are in galleries and programs.

SUSTAINABILITY FEATURES

CRITICAL DIMENSIONS

Length, Width, Shape Open vs. Private

CRITERIA

Please refer to structural narrative for more information on structural requirements.

Smithsonian Institution National Museum of African American History and Culture 52 Infrastructure Only 0 Other Amenities Deionized Water Vacuum Yes Speakers OH Gr. 2, 130 SF/HD FIRE ALARM Smoke Detection Yes Wet Sprinkler Special Waste Dry Sprinkler Pre-Action Sprinkler No FIRE PROTECTION No Considerations for Water 0 No Floor Drains Floor Sink Grey/Blackwater Piping 0 No No No Protected Hot/Cold No No Recycled Water Supply (treated) 0 No Public Address Audio Compressed Air Audio Visual Requirements No Hot/Cold Water Task Light No No 0 Plant/Clean Steam 0 Acoustic Sensitivity 0 Vibration Sensitivity Special Equipment/Artifact Sensitivity PLUMBING Target Illuminance (IES 9th Edition) Daylight Sensor 30-50 FC Exhibit Light No Power Density (AHSRAE 2004) 0.8 W/ft² Temperature Deviations (+/-) 0 No Process Water UPS Switched Receptacles Dimming Yes Humidity 0 No Other Humidity Deviation (+/-) 6 min. 0 No Outside Air Single/Multi-Level Switching 0 Emergency/Standby Power 0.05 CFM/SF 30/65 Yes Occupancy Sensor Special Exhaust Sub-metering & Feedback Displays Filtration (Pre/Final/Other) Voice/Data DATA/TELECOMMUNICATIONS 0 0 SECURITY 0 5.0 kPa/8.9 kN Floor Loading/Point Loads DAYLIGHTING 0 0 Shading Considerations Top/Side Lighting 0 Yes STRUCTURAL 0 0 Refer to information indicated in Volume IV, Section E Full/Partial 0 Technical Comment: Backpack/Lunch Storage Assignable Square Feet (ASF) OFEO Space Dimensions 0 Organizational Unit Other Interior Glazing 0 0 Yes Yes Cleanable Ceiling CRITICAL FINISHES 0 Negative
ELECTRICAL ARCHITECTURAL
Zone Room ID A4.5 Room Name 0
Public Non-Collection Space 400 Number of Occupants NA Visual Privacy (full, partial, open) Zone Designation Zone A Room Height 0 LEED NC Regurlarly Occupied Space 0 Base ACOUSTICS Equipment Hardware/STC Rating No NRC 0 0 0 Plug Loads Air Change/ HR Walls HVAC ENGINEERING
Temperature Lighting 45% RH ±2ºF 110v, 20a, 1ph Yes ±15% RH Power No Cleanable Pressure (+/-) 76ºF Summer, 71ºF Winter Floor Operable Windows
FURNITURE/EQUIPMENT Moveable Yes Fixed RT60 & Shaping 0 Lower
Separation/STC
Floor Level 0 Room

This room data sheet is not comprehensive in nature. Information regarding specific room features may have not been available and was intentionally left blank. This room data sheet is not comprehensive in nature. Information regarding specific room features may not have been available and was intentionally left blank. Room should have the goal of controlling sound from audio systems and minimizing noise buildup due to crowd activity.

Compliance with ADA/ABAAG (2004) citations is required for accessibility. SI also requires compliance with SI Accessibility Guidelines and the IBC. Comparisons should be made and the more stringent requirement followed for design purposes. Ensure compliance with ADA/ABAAG (2004) 305 Reach Ranges; 305 Clear Floor or Ground Space & 309 Operable Parts. See Accessibility Narrative for additional information.

Outer Hall, Central Hall, Segregation, 1968 and Beyond

SUSTAINABILITY FEATURES

Please refer to structural narrative for more information on structural requirements.

CRITICAL DIMENSIONS

to information indicated in Volume IV, Section E. Dedicated

53 Room Data Sheets | FREELON BOND Infrastructure Only 0 Other Amenities Deionized Water Vacuum Yes Speakers OH Gr. 2, 130 SF/HD FIRE ALARM Smoke Detection Yes Wet Sprinkler Special Waste Dry Sprinkler Pre-Action Sprinkler No FIRE PROTECTION No Considerations for Water 0 No Floor Drains Floor Sink Grey/Blackwater Piping 0 No No No Protected Hot/Cold No No Recycled Water Supply (treated) 0 No Public Address Audio Compressed Air Audio Visual Requirements No Hot/Cold Water Task Light No Yes 0 Plant/Clean Steam Yes Acoustic Sensitivity NC 35-40 Vibration Sensitivity Special Equipment/Artifact Sensitivity PLUMBING Target Illuminance
Edition) Daylight Sensor 5-30 FC Exhibit Light To Be Considered Power Density
2004) Exempt Temperature Deviations (+/-) Yes To Be Considered Process Water UPS Switched Receptacles Dimming No Humidity 0 Yes Other Humidity Deviation (+/-) 10 min. 0 Yes Outside Air Single/Multi-Level Switching 0 Emergency/Standby Power 15 CFM/person 65/ Carbon/95 Multi Occupancy Sensor Special Exhaust Sub-metering & Feedback Displays Filtration (Pre/Final/Other) Voice/Data DATA/TELECOMMUNICATIONS Yes 0 SECURITY 0 7.5 kPa/26.7 kN Floor Loading/Point Loads DAYLIGHTING 0 0 Shading Considerations Top/Side Lighting AV for exhibits to be determined by exhibit design Yes STRUCTURAL 0 0
security closet. Open 0 Technical Comment: Slavery and Freedom Assignable Square Feet (ASF) OFEO Space Dimensions 0 Organizational Unit Other Interior Glazing 0 0 Yes Yes 0 Ceiling CRITICAL FINISHES 0 Positive
(IES 9th
(AHSRAE
Refer
ELECTRICAL
ARCHITECTURAL
Zone Room ID B1.1 Room Name 0 Functional Description General comment for the Permanent Exhibition Galleries: Please see Exhibition Master Plan for description of exhibitions. Area for each gallery is flexible within
overall allocation for the Permanent Collection Galleries. Public Collection Space 13,000 Number of Occupants +/- 320 Visual Privacy (full, partial, open) Zone Designation Zone B Room Height 0 LEED NC Regurlarly Occupied Space 0 Base ACOUSTICS Equipment Hardware/STC Rating 0 NRC
the ceiling with an NRC of 0.80 or higher 0 0 Plug Loads Air Change/ HR Walls HVAC ENGINEERING CRITERIA Temperature Lighting 45%RH yr. rd. ±2ºF 110v, 20a, 1ph Yes 8% RH yr. rd. Power No 0 Pressure (+/-) 70ºF Floor Operable Windows Separation/STC FURNITURE/EQUIPMENT Moveable Yes Fixed RT60 & Shaping 0.8-1.0 s Lower
the
Absorptive finish on
Floor Level 0 Room Length,
Open
Adjacencies Accessibility Requirement:
Width, Shape
vs. Private

This room data sheet is not comprehensive in nature. Information regarding specific room features may not have been available and was intentionally left

Adjacencies

SUSTAINABILITY FEATURES

Compliance with ADA/ABAAG (2004) citations is required for accessibility. SI also requires compliance with SI Accessibility Guidelines and the IBC. Comparisons should be made and the more stringent requirement followed for design purposes. Ensure compliance with ADA/ABAAG (2004) 305 Reach Ranges; 305 Clear Floor or Ground Space & 309 Operable Parts. See Accessibility Narrative for additional information.

Outer Hall, Central Hall, Slavery & Freedom, 1968 and Beyond

Please refer to structural narrative for more information on structural requirements.

CRITICAL DIMENSIONS

Smithsonian Institution National Museum of African American History and Culture 54 Infrastructure Only 0 Other Amenities Deionized Water Vacuum Yes Speakers OH Gr. 2, 130 SF/HD FIRE ALARM Smoke Detection Yes Wet Sprinkler Special Waste Dry Sprinkler Pre-Action Sprinkler No FIRE PROTECTION No Considerations for Water 0 No Floor Drains Floor Sink Grey/Blackwater Piping 0 No No No Protected Hot/Cold No No Recycled Water Supply (treated) 0 No Public Address Audio Compressed Air Audio Visual Requirements No Hot/Cold Water Task Light No Yes 0 Plant/Clean Steam Yes Acoustic Sensitivity NC 35-40 Vibration Sensitivity Special Equipment/Artifact Sensitivity PLUMBING Target Illuminance
9th Edition) Daylight Sensor 5-30 FC Exhibit Light To Be Considered Power Density (AHSRAE 2004) Exempt Temperature Deviations (+/-) Yes To Be Considered Process Water UPS Switched Receptacles Dimming No Humidity 0 Yes Other Humidity Deviation (+/-) 10 min. 0 Yes Outside Air Single/Multi-Level Switching 0 Emergency/Standby Power 15 CFM/person 65/ Carbon/95 Multi Occupancy Sensor Special Exhaust Sub-metering & Feedback Displays Filtration (Pre/Final/Other) Voice/Data DATA/TELECOMMUNICATIONS Yes 0 SECURITY 0 7.5 kPa/26.7 kN Floor Loading/Point Loads DAYLIGHTING 0 0 Shading Considerations Top/Side Lighting AV for exhibits to be determined by exhibit design Yes STRUCTURAL 0 0 Refer to information
Volume IV,
security closet. Open 0 Technical Comment: Segregation Assignable Square Feet (ASF) OFEO Space Dimensions 0 Organizational Unit Other Interior Glazing 0 0 Yes Yes 0 Ceiling CRITICAL FINISHES 0 Positive
(IES
indicated in
Section E. Dedicated
ELECTRICAL ARCHITECTURAL
blank.
Zone Room ID B1.2 Room Name 0 Functional Description 0 Public Collection Space 8,000 Number of Occupants +/- 190 Visual Privacy (full, partial, open) Zone Designation Zone B Room Height 1/3 Space Double Height LEED NC Regurlarly Occupied Space 0 Base ACOUSTICS Equipment Hardware/STC Rating 0 NRC
finish on the ceiling with an NRC of 0.80 or higher 0 0 Plug Loads Air Change/ HR Walls HVAC ENGINEERING CRITERIA Temperature Lighting 45%RH yr. rd. ±2ºF 110v, 20a, 1ph Yes 8% RH yr. rd. Power No 0 Pressure (+/-) 70ºF Floor Operable Windows Separation/STC FURNITURE/EQUIPMENT Moveable Yes Fixed RT60 & Shaping 1.0-1.4 s TBD
Room should have the goal of controlling sound from audio systems and minimizing noise buildup due to crowd activity.
Absorptive
Floor Level More
Room Length,
Accessibility Requirement:
Reflecting Space
Width, Shape Open vs. Private

This room data sheet is not comprehensive in nature. Information regarding specific room features may not have been available and was intentionally left

Room should have the goal of controlling sound from audio systems and minimizing noise buildup due to crowd activity.

Adjacencies Accessibility Requirement:

SUSTAINABILITY FEATURES

Compliance with ADA/ABAAG (2004) citations is required for accessibility. SI also requires compliance with SI Accessibility Guidelines and the IBC. Comparisons should be made and the more stringent requirement followed for design purposes. Ensure compliance with ADA/ABAAG (2004) 305 Reach Ranges; 305 Clear Floor or Ground Space & 309 Operable Parts. See Accessibility Narrative for additional information.

Outer Hall, Central Hall, History: Segregation, History: Slavery and Freedom

Absorptive finish on

Please refer to structural narrative for more information on structural requirements.

CRITICAL DIMENSIONS

55 Room Data Sheets | FREELON BOND Infrastructure Only 0 Other Amenities Deionized Water Vacuum Yes Speakers OH Gr. 2, 130 SF/HD FIRE ALARM Smoke Detection Yes Wet Sprinkler Special Waste Dry Sprinkler Pre-Action Sprinkler No FIRE PROTECTION No Considerations for Water 0 No Floor Drains Floor Sink Grey/Blackwater Piping 0 No No No Protected Hot/Cold No No Recycled Water Supply (treated) 0 No Public Address Audio Compressed Air Audio Visual Requirements No Hot/Cold Water Task Light No Yes 0 Plant/Clean Steam Yes Acoustic Sensitivity NC 35-40 Vibration Sensitivity Special Equipment/Artifact Sensitivity PLUMBING Target Illuminance (IES 9th Edition) Daylight Sensor 5-30 FC Exhibit Light To Be Considered Power Density (AHSRAE 2004) Exempt Temperature Deviations (+/-) Yes To Be Considered Process Water UPS Switched Receptacles Dimming No Humidity 0 Yes Other Humidity Deviation (+/-) 10 min. 0 Yes Outside Air Single/Multi-Level Switching 0 Emergency/Standby Power 15 CFM/person 65/ Carbon/95 Multi Occupancy Sensor Special Exhaust Sub-metering & Feedback Displays Filtration (Pre/Final/Other) Voice/Data DATA/TELECOMMUNICATIONS Yes 0 SECURITY 0 7.5 kPa/26.7 kN Floor Loading/Point Loads DAYLIGHTING 0 0 Shading Considerations Top/Side Lighting AV for exhibits to be determined by exhibit design Yes STRUCTURAL 0 0 Refer to information
Volume IV,
security closet. Open 0 Technical Comment: 1968 and Beyond Assignable Square Feet (ASF) OFEO Space Dimensions 0 Organizational Unit Other Interior Glazing 0 0 Yes Yes 0 Ceiling CRITICAL FINISHES 0 Positive
indicated in
Section E. Dedicated
ELECTRICAL ARCHITECTURAL
Zone Room ID B1.3 Room Name 0 Functional Description 0 Public Collection Space 4,000 Number of Occupants +/- 130 Visual Privacy (full, partial, open) Zone Designation Zone B Room Height 0 LEED NC Regurlarly Occupied Space 0 Base ACOUSTICS Equipment Hardware/STC Rating 0 NRC
the ceiling with an NRC of 0.80 or higher 0 0 Plug Loads Air Change/ HR Walls HVAC ENGINEERING CRITERIA Temperature Lighting 45%RH yr. rd. ±2ºF 110v, 20a, 1ph Yes 8% RH yr. rd. Power No 0 Pressure (+/-) 70ºF Floor Operable Windows Separation/STC FURNITURE/EQUIPMENT Moveable Yes Fixed RT60 & Shaping 0 TBD
blank.
Floor Level 0 Room Length,
Open
Width, Shape
vs. Private

This room data sheet is not comprehensive in nature. Information regarding specific room features may not have been available and was intentionally left

Accessibility Requirement:

Adjacencies

SUSTAINABILITY FEATURES

Compliance with ADA/ABAAG (2004) citations is required for accessibility. SI also requires compliance with SI Accessibility Guidelines and the IBC. Comparisons should be made and the more stringent requirement followed for design purposes. Ensure compliance with ADA/ABAAG (2004) 305 Reach Ranges; 305 Clear Floor or Ground Space & 309 Operable Parts. See Accessibility Narrative for additional information.

Outer Hall, Central Hall, Visual Arts, Cultural Traditions

CRITICAL DIMENSIONS

Length, Width, Shape Open vs. Private

Possible Rectagonal Space

Please refer to structural narrative for more information on structural requirements.

Smithsonian Institution National Museum of African American History and Culture 56 Infrastructure Only 0 Other Amenities Deionized Water Vacuum Yes Speakers OH Gr. 2, 130 SF/HD FIRE ALARM Smoke Detection Yes Wet Sprinkler Special Waste Dry Sprinkler Pre-Action Sprinkler No FIRE PROTECTION No Considerations for Water 0 No Floor Drains Floor Sink Grey/Blackwater Piping 0 No No No Protected Hot/Cold No No Recycled Water Supply (treated) 0 No Public Address Audio Compressed Air Audio Visual Requirements No Hot/Cold Water Task Light No Yes 0 Plant/Clean Steam Yes Acoustic Sensitivity NC 35-40 Vibration Sensitivity Special Equipment/Artifact Sensitivity PLUMBING Target Illuminance
Edition) Daylight Sensor 5-30 FC Exhibit Light To Be Considered Power Density
2004) Exempt Temperature Deviations (+/-) Yes To Be Considered Process Water UPS Switched Receptacles Dimming No Humidity 0 Yes Other Humidity Deviation (+/-) 10 min. 0 yes Outside Air Single/Multi-Level Switching 0 Emergency/Standby Power 15 CFM/person 65/ Carbon/95 Multi Occupancy Sensor Special Exhaust Sub-metering & Feedback Displays Filtration (Pre/Final/Other) Voice/Data DATA/TELECOMMUNICATIONS Yes 0 SECURITY 0 7.5 kPa/26.7 kN Floor Loading/Point Loads DAYLIGHTING 0 0 Shading Considerations Top/Side Lighting AV for exhibits to be determined by exhibit design Yes STRUCTURAL 0 0 Refer to information
security closet. Open 0 Technical Comment: Musical Crossroads Assignable Square Feet (ASF) OFEO Space Dimensions 0 Organizational Unit Other Interior Glazing 0 0 Yes Yes 0 Ceiling CRITICAL FINISHES 0 Positive
(IES 9th
(AHSRAE
indicated in Volume IV, Section E. Dedicated
ELECTRICAL ARCHITECTURAL
blank.
Zone Room ID B1.4 Room Name 0 Functional Description 0 Public Collection Space 13,000 Number of Occupants +/- 300 Visual Privacy (full, partial, open) Zone Designation Zone B Room Height 1/3 to 1/2 Space, 1.5 Stories LEED NC Regurlarly Occupied Space 0 Base ACOUSTICS Equipment Hardware/STC Rating 0 NRC Absorptive finish on the ceiling with an NRC of 0.80 or higher 0 0 Plug Loads Air Change/ HR Walls HVAC ENGINEERING CRITERIA Temperature Lighting 45%RH yr. rd. ±2ºF 110v, 20a, 1ph Yes 8% RH yr. rd. Power No 0 Pressure (+/-) 70ºF Floor Operable Windows Separation/STC FURNITURE/EQUIPMENT Moveable Yes Fixed RT60 & Shaping 1.0-1.4 s Lower
Room should have the goal of controlling sound from audio systems and minimizing noise buildup due to crowd activity.
Floor Level
Room

This room data sheet is not comprehensive in nature. Information regarding specific room features may not have been available and was intentionally left

SUSTAINABILITY

Compliance with ADA/ABAAG (2004) citations is required for accessibility. SI also requires compliance with SI Accessibility Guidelines and the IBC. Comparisons should be made and the more stringent requirement followed for design purposes. Ensure compliance with ADA/ABAAG (2004) 305 Reach Ranges; 305 Clear Floor or Ground Space & 309 Operable Parts. See Accessibility Narrative for additional information. Outer Hall, Central Hall, Musical Crossroads, Cultural Traditions, Visual Arts Gallery

CRITICAL DIMENSIONS

Please refer to structural narrative for more information on structural requirements.

57 Room Data Sheets | FREELON BOND Infrastructure Only 0 Other Amenities Deionized Water Vacuum Yes Speakers OH Gr. 2, 130 SF/HD FIRE ALARM Smoke Detection Yes Wet Sprinkler Special Waste Dry Sprinkler Pre-Action Sprinkler No FIRE PROTECTION No Considerations for Water 0 No Floor Drains Floor Sink Grey/Blackwater Piping 0 No No No Protected Hot/Cold No No Recycled Water Supply (treated) 0 No Public Address Audio Compressed Air Audio Visual Requirements No Hot/Cold Water Task Light No Yes 0 Plant/Clean Steam Yes Acoustic Sensitivity NC 35-40 Vibration Sensitivity Special Equipment/Artifact Sensitivity PLUMBING Target Illuminance (IES 9th Edition) Daylight Sensor 5-30 FC Exhibit Light To Be Considered Power Density (AHSRAE 2004) Exempt Temperature Deviations (+/-) Yes To Be Considered Process Water UPS Switched Receptacles Dimming No Humidity 0 Yes Other Humidity Deviation (+/-) 10 min. 0 yes Outside Air Single/Multi-Level Switching 0 Emergency/Standby Power 15 CFM/person 65/ Carbon/95 Multi Occupancy Sensor Special Exhaust Sub-metering & Feedback Displays Filtration (Pre/Final/Other) Voice/Data DATA/TELECOMMUNICATIONS Yes 0 SECURITY 0 7.5 kPa/26.7 kN Floor Loading/Point Loads DAYLIGHTING 0 0 Shading Considerations Top/Side Lighting AV for exhibits to be determined by exhibit design Yes STRUCTURAL 0 0 Refer to information indicated
Volume IV,
security closet. Open 0 Technical Comment: Visual Arts Assignable Square Feet (ASF) OFEO Space Dimensions 0 Organizational Unit Other Interior Glazing 0 0 Yes Yes 0 Ceiling CRITICAL FINISHES 0 Positive
in
Section E. Dedicated
ELECTRICAL ARCHITECTURAL
blank.
Zone Room ID B1.5 Room Name 0 Functional Description 0 Public Collection Space 4,000 Number of Occupants +/- 80 Visual Privacy (full, partial, open) Zone Designation Zone B Room Height 1/4 Space High Volumn Space LEED NC Regurlarly Occupied Space 0 Base ACOUSTICS Equipment Hardware/STC Rating 0 NRC Absorptive finish on the ceiling with an NRC of 0.70 or higher 0 0 Plug Loads Air Change/ HR Walls HVAC ENGINEERING CRITERIA Temperature Lighting 45%RH yr. rd. ±2ºF 110v, 20a, 1ph Yes 8% RH yr. rd. Power No 0 Pressure (+/-) 70ºF Floor Operable Windows Separation/STC FURNITURE/EQUIPMENT Moveable Yes Fixed RT60 & Shaping 0.8-1.0 s TBD
Room should have the goal of controlling sound from audio systems and minimizing noise buildup due to crowd activity.
Floor Level 0 Room Length,
Open
FEATURES Adjacencies Accessibility Requirement:
Width, Shape
vs. Private

This room data sheet is not comprehensive in nature. Information regarding specific room features may not have been available and was intentionally left

Room should have the goal of controlling sound from audio systems and minimizing noise buildup due to crowd activity.

Compliance with ADA/ABAAG (2004) citations is required for accessibility. SI also requires compliance with SI Accessibility Guidelines and the IBC. Comparisons should be made and the more stringent requirement followed for design purposes. Ensure compliance with ADA/ABAAG (2004) 305 Reach Ranges; 305 Clear Floor or Ground Space & 309 Operable Parts. See Accessibility Narrative for additional information.

SUSTAINABILITY FEATURES Adjacencies

vs. Private

Outer Hall, Central Hall, Musical Crossroads, Visual Arts

Absorptive finish on

Please refer to structural narrative for more information on structural requirements.

CRITICAL DIMENSIONS

Smithsonian Institution National Museum of African American History and Culture 58 Infrastructure Only 0 Other Amenities Deionized Water Vacuum Yes Speakers OH Gr. 2, 130 SF/HD FIRE ALARM Smoke Detection Yes Wet Sprinkler Special Waste Dry Sprinkler Pre-Action Sprinkler No FIRE PROTECTION No Considerations for Water 0 No Floor Drains Floor Sink Grey/Blackwater Piping 0 No No No Protected Hot/Cold No No Recycled Water Supply (treated) 0 No Public Address Audio Compressed Air Audio Visual Requirements No Hot/Cold Water Task Light No Yes 0 Plant/Clean Steam Yes Acoustic Sensitivity NC 35-40 Vibration Sensitivity Special Equipment/Artifact Sensitivity PLUMBING Target Illuminance
9th Edition) Daylight Sensor 5-30 FC Exhibit Light To Be Considered Power Density (AHSRAE 2004) Exempt Temperature Deviations (+/-) Yes To Be Considered Process Water UPS Switched Receptacles Dimming No Humidity 0 Yes Other Humidity Deviation (+/-) 10 min. 0 yes Outside Air Single/Multi-Level Switching 0 Emergency/Standby Power 15 CFM/person 65/ Carbon/95 Multi Occupancy Sensor Special Exhaust Sub-metering & Feedback Displays Filtration (Pre/Final/Other) Voice/Data DATA/TELECOMMUNICATIONS Yes 0 SECURITY 0 7.5 kPa/26.7 kN Floor Loading/Point Loads DAYLIGHTING 0 0 Shading Considerations Top/Side Lighting AV for exhibits to be determined by exhibit design Yes STRUCTURAL 0 0 Refer to information
security closet. Open 0 Technical Comment: Cultural Traditions Assignable Square Feet (ASF) OFEO Space Dimensions 0 Organizational Unit Other Interior Glazing 0 0 Yes Yes 0 Ceiling CRITICAL FINISHES 0 Positive
(IES
indicated in Volume IV, Section E. Dedicated
ELECTRICAL ARCHITECTURAL
Zone Room ID B1.6 Room Name 0 Functional Description 0 Public Collection Space 4,000 Number of Occupants +/- 130 Visual Privacy (full, partial, open) Zone Designation Zone B Room Height 0 LEED NC Regurlarly Occupied Space 0 Base ACOUSTICS Equipment Hardware/STC Rating 0 NRC
the ceiling with an NRC of 0.70 or higher 0 0 Plug Loads Air Change/ HR Walls HVAC ENGINEERING CRITERIA Temperature Lighting 45%RH yr. rd. ±2ºF 110v, 20a, 1ph Yes 8% RH yr. rd. Power No 0 Pressure (+/-) 70ºF Floor Operable Windows Separation/STC FURNITURE/EQUIPMENT Moveable Yes Fixed RT60 & Shaping 0.8-1.0 s TBD
blank.
Floor Level 0 Room Length,
Open
Accessibility Requirement:
Width, Shape

This room data sheet is not comprehensive in nature. Information regarding specific room features may not have been available and was intentionally left

Compliance with ADA/ABAAG (2004) citations is required for accessibility. SI also requires compliance with SI Accessibility Guidelines and the IBC. Comparisons should be made and the more stringent requirement followed for design purposes. Ensure compliance with ADA/ABAAG (2004) 305 Reach Ranges; 305 Clear Floor or Ground Space & 309 Operable Parts. See Accessibility Narrative for additional information.

SUSTAINABILITY FEATURES Adjacencies

Outer Hall, Central Hall, Cultural Traditions

Absorptive finish on the ceiling

Please refer to structural narrative for more information on structural requirements.

CRITICAL DIMENSIONS

59 Room Data Sheets | FREELON BOND Infrastructure Only 0 Other Amenities Deionized Water Vacuum Yes Speakers OH Gr. 2, 130 SF/HD FIRE ALARM Smoke Detection Yes Wet Sprinkler Special Waste Dry Sprinkler Pre-Action Sprinkler No FIRE PROTECTION No Considerations for Water 0 No Floor Drains Floor Sink Grey/Blackwater Piping 0 No No No Protected Hot/Cold No No Recycled Water Supply (treated) 0 No Public Address Audio Compressed Air Audio Visual Requirements No Hot/Cold Water Task Light No Yes 0 Plant/Clean Steam Yes Acoustic Sensitivity NC 35-40 Vibration Sensitivity Special Equipment/Artifact Sensitivity PLUMBING Target Illuminance (IES 9th Edition) Daylight Sensor 5-30 FC Exhibit Light To Be Considered Power Density (AHSRAE 2004) Exempt Temperature Deviations (+/-) Yes To Be Considered Process Water UPS Switched Receptacles Dimming No Humidity 0 Yes Other Humidity Deviation (+/-) 10 min. 0 yes Outside Air Single/Multi-Level Switching 0 Emergency/Standby Power 15 CFM/person 65/ Carbon/95 Multi Occupancy Sensor Special Exhaust Sub-metering & Feedback Displays Filtration (Pre/Final/Other) Voice/Data DATA/TELECOMMUNICATIONS Yes 0 SECURITY 0 7.5 kPa/26.7 kN Floor Loading/Point Loads DAYLIGHTING 0 0 Shading Considerations Top/Side Lighting AV for exhibits to be determined by exhibit design Yes STRUCTURAL 0 0 Refer to information
security closet. Open 0 Technical Comment: Sports Assignable Square Feet (ASF) OFEO Space Dimensions 0 Organizational Unit Other Interior Glazing 0 0 Yes Yes 0 Ceiling CRITICAL FINISHES 0 Positive
indicated in Volume IV, Section E. Dedicated
ELECTRICAL ARCHITECTURAL
blank.
Zone Room ID B1.7 Room Name 0 Functional Description 0 Public Collection Space 4,000 Number of Occupants +/- 130 Visual Privacy (full, partial, open) Zone Designation Zone B Room Height 0 LEED NC Regurlarly Occupied Space 0 Base ACOUSTICS Equipment Hardware/STC Rating 0 NRC
with an NRC of 0.70 or higher 0 0 Plug Loads Air Change/ HR Walls HVAC ENGINEERING CRITERIA Temperature Lighting 45%RH yr. rd. ±2ºF 110v, 20a, 1ph Yes 8% RH yr. rd. Power No 0 Pressure (+/-) 70ºF Floor Operable Windows Separation/STC FURNITURE/EQUIPMENT Moveable Yes Fixed RT60 & Shaping 0.8-1.0 s 0
Room should have the goal of controlling sound from audio systems and minimizing noise buildup due to crowd activity.
Accessibility
Floor Level 0 Room Length, Width, Shape Open
Requirement:
vs. Private

This room data sheet is not comprehensive in nature. Information regarding specific room features may not been available and was intentionally left

Room should have the goal of controlling sound from audio systems and minimizing noise buildup due to crowd activity.

Adjacencies Accessibility Requirement:

Compliance with ADA/ABAAG (2004) citations is required for accessibility. SI also requires compliance with SI Accessibility Guidelines and the IBC. Comparisons should be made and the more stringent requirement followed for design purposes. Ensure compliance with ADA/ABAAG (2004) 305 Reach Ranges; 305 Clear Floor or Ground Space & 309 Operable Parts. See Accessibility Narrative for additional information.

Outer Hall, Central Hall, Making a Way Somehow

SUSTAINABILITY FEATURES

vs. Private

Please refer to structural narrative for more information on structural requirements.

CRITICAL DIMENSIONS

Smithsonian Institution National Museum of African American History and Culture 60 Infrastructure Only 0 Other Amenities Deionized Water Vacuum Yes Speakers OH Gr. 2, 130 SF/HD FIRE ALARM Smoke Detection Yes Wet Sprinkler Special Waste Dry Sprinkler Pre-Action Sprinkler No FIRE PROTECTION No Considerations for Water 0 No Floor Drains Floor Sink Grey/Blackwater Piping 0 No No 0 Protected Hot/Cold No No Recycled Water Supply (treated) 0 No Public Address Audio Compressed Air Audio Visual Requirements 0 Hot/Cold Water Task Light No Yes 0 Plant/Clean Steam Yes Acoustic Sensitivity NC 35-40 Vibration Sensitivity Special Equipment/Artifact Sensitivity PLUMBING Target Illuminance (IES 9th Edition) Daylight Sensor 5-30 FC Exhibit Light To Be Considered Power Density (AHSRAE 2004) Exempt Temperature Deviations (+/-) Yes To Be Considered Process Water UPS Switched Receptacles Dimming No Humidity 0 Yes Other Humidity Deviation (+/-) 10 min. 0 Yes Outside Air Single/Multi-Level Switching 0 Emergency/Standby Power 15 CFM/person 65/ Carbon/95 Multi Occupancy Sensor Special Exhaust Sub-metering & Feedback Displays Filtration (Pre/Final/Other) Voice/Data DATA/TELECOMMUNICATIONS Yes 0 SECURITY 0 7.5 kPa/26.7 kN Floor Loading/Point Loads DAYLIGHTING 0 0 Shading Considerations Top/Side Lighting AV for exhibits to be determined by exhibit design Yes STRUCTURAL 0 0 Refer to information
security closet. Open 0 Technical Comment: Power of Place Assignable Square Feet (ASF) OFEO Space Dimensions 0 Organizational Unit Other Interior Glazing 0 0 Yes Yes 0 Ceiling CRITICAL FINISHES 0 Positive
indicated in Volume IV, Section E. Dedicated
ELECTRICAL ARCHITECTURAL
Zone Room ID B1.8 Room Name 0 Functional Description 0 Public Collection Space 11,000 Number of Occupants +/- 200 Visual Privacy (full, partial, open) Zone Designation Zone B Room Height 1.5 Stories LEED NC Regurlarly Occupied Space 0 Base ACOUSTICS Equipment Hardware/STC Rating 0 NRC
finish on the ceiling with an NRC of 0.80 or higher 0 0 Plug Loads Air Change/ HR Walls HVAC ENGINEERING CRITERIA Temperature Lighting 45%RH yr. rd. ±2ºF 110v, 20a, 1ph Yes 8% RH yr. rd. Power No 0 Pressure (+/-) 70ºF Floor Operable Windows Separation/STC FURNITURE/EQUIPMENT Moveable Yes Fixed RT60 & Shaping 0.8-1.0 s TBD
blank.
Absorptive
Floor Level No
Room
Open
Elongated Spaces
Length, Width, Shape

This room data sheet is not comprehensive in nature. Information regarding specific room features may not been available and was intentionally left blank. Room should have the goal of controlling sound from audio systems and minimizing noise buildup due to crowd activity.

Adjacencies Accessibility Requirement:

SUSTAINABILITY FEATURES

Compliance with ADA/ABAAG (2004) citations is required for accessibility. SI also requires compliance with SI Accessibility Guidelines and the IBC. Comparisons should be made and the more stringent requirement followed for design purposes. Ensure compliance with ADA/ABAAG (2004) 305 Reach Ranges; 305 Clear Floor or Ground Space & 309 Operable Parts. See Accessibility Narrative for additional information.

Outer Hall, Central Hall, Power of Place

Absorptive finish on

Please refer to structural narrative for more information on structural requirements.

CRITICAL DIMENSIONS

Elongated Spaces

61 Room Data Sheets | FREELON BOND Infrastructure Only 0 Other Amenities Deionized Water Vacuum Yes Speakers OH Gr. 2, 130 SF/HD FIRE ALARM Smoke Detection Yes Wet Sprinkler Special Waste Dry Sprinkler Pre-Action Sprinkler No FIRE PROTECTION No Considerations for Water 0 No Floor Drains Floor Sink Grey/Blackwater Piping 0 No No No Protected Hot/Cold No No Recycled Water Supply (treated) 0 No Public Address Audio Compressed Air Audio Visual Requirements No Hot/Cold Water Task Light no Yes 0 Plant/Clean Steam Yes Acoustic Sensitivity NC 35-40 Vibration Sensitivity Special Equipment/Artifact Sensitivity PLUMBING Target Illuminance (IES 9th Edition) Daylight Sensor 5-30 FC Exhibit Light To Be Considered Power Density (AHSRAE 2004) Exempt Temperature Deviations (+/-) Yes To Be Considered Process Water UPS Switched Receptacles Dimming No Humidity 0 Yes Other Humidity Deviation (+/-) 10 min. 0 Yes Outside Air Single/Multi-Level Switching 0 Emergency/Standby Power 15 CFM/person 65/ Carbon/95 Multi Occupancy Sensor Special Exhaust Sub-metering & Feedback Displays Filtration (Pre/Final/Other) Voice/Data DATA/TELECOMMUNICATIONS Yes 0 SECURITY 0 7.5 kPa/26.7 kN Floor Loading/Point Loads DAYLIGHTING 0 0 Shading Considerations Top/Side Lighting AV for exhibits to be determined by exhibit design Yes STRUCTURAL 0 0 Refer to information indicated in Volume IV,
security closet. Open 0 Technical Comment: Make a Way Somehow Assignable Square Feet (ASF) OFEO Space Dimensions 0 Organizational Unit Other Interior Glazing 0 0 Yes Yes 0 Ceiling CRITICAL FINISHES 0 Positive
Section E. Dedicated
ELECTRICAL ARCHITECTURAL
Zone Room ID B1.9 Room Name 0 Functional Description 0 Public Collection Space 6,000 Number of Occupants +/- 160 Visual Privacy (full, partial, open) Zone Designation Zone B Room Height 0 LEED NC Regurlarly Occupied Space 0 Base ACOUSTICS Equipment Hardware/STC Rating 0 NRC
the ceiling with an NRC of 0.70 or higher 0 0 Plug Loads Air Change/ HR Walls HVAC ENGINEERING CRITERIA Temperature Lighting 45%RH yr. rd. ±2ºF 110v, 20a, 1ph Yes 8% RH yr. rd. Power No 0 Pressure (+/-) 70ºF Floor Operable Windows Separation/STC FURNITURE/EQUIPMENT Moveable Yes Fixed RT60 & Shaping 1.0-1.4 s TBD
Floor Level No
Room
Length, Width, Shape Open vs. Private

This room data sheet is not comprehensive in nature. Information regarding specific room features may not have been available and was intentionally left blank. Room should have the goal of controlling sound from audio systems and minimizing noise buildup due to crowd activity.

Accessibility Requirement:

Adjacencies

SUSTAINABILITY FEATURES

Compliance with ADA/ABAAG (2004) citations is required for accessibility. SI also requires compliance with SI Accessibility Guidelines and the IBC. Comparisons should be made and the more stringent requirement followed for design purposes. Ensure compliance with ADA/ABAAG (2004) 305 Reach Ranges; 305 Clear Floor or Ground Space & 309 Operable Parts. See Accessibility Narrative for additional information.

Lobby/Assembly Area, Education Spaces, Library/Archives (Resource Center)

CRITICAL DIMENSIONS

Recommend hazard lighting under Electrical Lighting. Please refer to structural narrative for more information on structural requirements.

Smithsonian Institution National Museum of African American History and Culture 62 Infrastructure Only 0 Other Amenities Deionized Water Vacuum Yes Speakers OH Gr. 2, 130 SF/HD FIRE ALARM Smoke Detection Yes Wet Sprinkler Special Waste Dry Sprinkler Pre-Action Sprinkler No FIRE PROTECTION No Considerations for Water 0 No Floor Drains Floor Sink Grey/Blackwater Piping 0 No No No Protected Hot/Cold No No Recycled Water Supply (treated) 0 No Public Address Audio Compressed Air Audio Visual Requirements No Hot/Cold Water Task Light No Yes 0 Plant/Clean Steam Yes Acoustic Sensitivity NC 35-40 Vibration Sensitivity Special Equipment/Artifact Sensitivity PLUMBING Target Illuminance
Edition) Daylight Sensor 5-30 FC Exhibit Light To Be Considered Power Density
Exempt Temperature Deviations (+/-) Yes To Be Considered Process Water UPS Switched Receptacles Dimming No Humidity 0 Yes Other Humidity Deviation (+/-) 10 min. 0 Yes Outside Air Single/Multi-Level Switching 0 Emergency/Standby Power 15 CFM/person 65/ Carbon/95 Multi Occupancy Sensor Special Exhaust Sub-metering & Feedback Displays Filtration (Pre/Final/Other) Voice/Data DATA/TELECOMMUNICATIONS Yes 0 SECURITY 0 7.5 kPa/26.7 kN Floor Loading/Point Loads DAYLIGHTING 0 0 Shading Considerations Top/Side Lighting AV for exhibits to be determined by exhibit design Yes STRUCTURAL 0 0 Refer to information indicated
Volume IV,
Dedicated security closet. Open 0 Technical Comment: Youth Gallery Assignable Square Feet (ASF) OFEO Space Dimensions 0 Organizational Unit Other Interior Glazing 0 0 Yes Yes 0 Ceiling CRITICAL FINISHES 0 Positive
(IES 9th
(AHSRAE 2004)
in
Section E.
ELECTRICAL ARCHITECTURAL
Zone Room ID B1.10 Room Name 0 Functional Description 0 Public Collection Space 4,000 Number of Occupants +/-80 Visual Privacy (full, partial, open) Zone Designation Zone B Room Height 0 LEED NC Regurlarly Occupied Space 0 Base ACOUSTICS Equipment Hardware/STC Rating 0 NRC Absorptive finish on the ceiling with an NRC of 0.70 or higher 0 0 Plug Loads Air Change/ HR Walls HVAC ENGINEERING CRITERIA Temperature Lighting 45%RH yr. rd. ±2ºF 110v, 20a, 1ph Yes 8% RH yr. rd. Power No 0 Pressure (+/-) 70ºF Floor Operable Windows Separation/STC FURNITURE/EQUIPMENT Moveable Yes Fixed RT60 & Shaping 0.7-0.8 s Lower
Floor Level Open,
Room
Open
Flexible
Length, Width, Shape
vs. Private

This room data sheet is not comprehensive in nature. Information regarding specific room features may not been available and was intentionally left blank. Room should have the goal of controlling sound from audio systems and minimizing noise buildup due to crowd activity.

SUSTAINABILITY FEATURES Adjacencies Accessibility Requirement:

Compliance with ADA/ABAAG (2004) citations is required for accessibility. SI also requires compliance with SI Accessibility Guidelines and the IBC. Comparisons should be made and the more stringent requirement followed for design purposes. Ensure compliance with ADA/ABAAG (2004) 305 Reach Ranges; 305 Clear Floor or Ground Space & 309 Operable Parts. See Accessibility Narrative for additional information.

Outer Hall, Central Hall

Please refer to structural narrative for more information on structural requirements.

CRITICAL DIMENSIONS

to information indicated in Volume IV, Section E. Dedicated

63 Room Data Sheets | FREELON BOND Infrastructure Only 0 Other Amenities Deionized Water Vacuum Yes Speakers OH Gr. 2, 130 SF/HD FIRE ALARM Smoke Detection Yes Wet Sprinkler Special Waste Dry Sprinkler Pre-Action Sprinkler No FIRE PROTECTION No Considerations for Water 0 No Floor Drains Floor Sink Grey/Blackwater Piping 0 No No No Protected Hot/Cold No No Recycled Water Supply (treated) 0 No Public Address Audio Compressed Air Audio Visual Requirements No Hot/Cold Water Task Light No Yes 0 Plant/Clean Steam Yes Acoustic Sensitivity NC 35-40 Vibration Sensitivity Special Equipment/Artifact Sensitivity PLUMBING Target Illuminance (IES 9th Edition) Daylight Sensor 30-50 FC Exhibit Light To Be Considered Power Density (AHSRAE 2004) Exempt Temperature Deviations (+/-) Yes To Be Considered Process Water UPS Switched Receptacles Dimming No Humidity 0 Yes Other Humidity Deviation (+/-) 10 min. 0 Yes Outside Air Single/Multi-Level Switching 0 Emergency/Standby Power 15 CFM/person 65/ Carbon/95 Multi Occupancy Sensor Special Exhaust Sub-metering & Feedback Displays Filtration (Pre/Final/Other) Voice/Data DATA/TELECOMMUNICATIONS Yes 0 SECURITY 0 7.5 kPA/26.7kN Floor Loading/Point Loads DAYLIGHTING 0 0 Shading Considerations Top/Side Lighting AV for exhibits to be determined by exhibit design Yes STRUCTURAL 0 0
security closet. Open Content Driven 0 Technical Comment: Changing Gallery Assignable Square Feet
OFEO Space Dimensions 0 Organizational Unit Other Interior Glazing 0 0 Yes Yes 0 Ceiling CRITICAL FINISHES 0 Positive
Refer
(ASF)
ELECTRICAL ARCHITECTURAL
Zone Room ID B2.1 Room Name 0 Functional
Gallery space
changing
Public Collection Space 5,000 Number of Occupants +/- 100 Visual Privacy (full, partial, open) Zone Designation Zone B Room Height 25' Clear Height LEED NC Regurlarly Occupied Space 0 Base ACOUSTICS Equipment Hardware/STC Rating 0 NRC Absorptive finish on the ceiling with an NRC of 0.70 or higher 0 0 Plug Loads Air Change/ HR Walls HVAC ENGINEERING CRITERIA Temperature Lighting 45%RH yr. rd. ±2ºF 110v, 20a, 1ph Yes 8% RH yr. rd. Power No 0 Pressure (+/-) 70ºF Floor Operable Windows Separation/STC FURNITURE/EQUIPMENT Moveable Yes Fixed RT60 & Shaping 1.0 s TBD
Description
fit out to support
exhibitions.
Floor Level 0 Room
Length, Width, Shape Open vs. Private

Compliance with ADA/ABAAG (2004) citations is required for accessibility. SI also requires compliance with SI Accessibility Guidelines and the IBC. Comparisons should be made and the more stringent requirement followed for design purposes. Ensure compliance with ADA/ABAAG (2004) 305 Reach Ranges; 305 Clear Floor or Ground Space & 309 Operable Parts. See Accessibility Narrative for additional information.

CRITICAL DIMENSIONS

Smithsonian Institution National Museum of African American History and Culture 64 Infrastructure Only 0 Other Amenities Deionized Water Vacuum Yes Speakers OH Gr. 2, 130 SF/HD FIRE ALARM Smoke Detection Yes Wet Sprinkler Special Waste Dry Sprinkler Pre-Action Sprinkler No FIRE PROTECTION 0 Considerations for Water 0 0 Floor Drains Floor Sink Grey/Blackwater Piping 0 0 0 0 Protected Hot/Cold 0 0 Recycled Water Supply (treated) 0 0 Public Address Audio Compressed Air Audio Visual Requirements 0 Hot/Cold Water Task Light 0 0 0 Plant/Clean Steam 0 Acoustic Sensitivity 0 Vibration Sensitivity Special Equipment/Artifact Sensitivity PLUMBING Target Illuminance (IES 9th Edition) Daylight Sensor 0 Exhibit Light 0 Power Density (AHSRAE 2004) 0 Temperature Deviations (+/-) 0 0 Process Water UPS Switched Receptacles Dimming 0 Humidity 0 0 Other Humidity Deviation (+/-) 0 0 0 Outside Air Single/Multi-Level Switching 0 Emergency/Standby Power 0 0 0 Occupancy Sensor Special Exhaust Sub-metering & Feedback Displays Filtration (Pre/Final/Other) Voice/Data DATA/TELECOMMUNICATIONS Yes 0 SECURITY 0 0 Floor Loading/Point Loads DAYLIGHTING 0 0 Shading Considerations Top/Side Lighting AV for exhibits to be determined by exhibit design Yes STRUCTURAL 0 0 Refer to information indicated in Volume IV, Section E. Dedicated security closet. 0 0 Technical Comment: Changing Visual Arts Gallery Assignable Square Feet (ASF) OFEO Space Dimensions 0 Organizational Unit Other Interior Glazing 0 0 0 0 0 Ceiling CRITICAL FINISHES 0 0 0 ELECTRICAL ARCHITECTURAL This
left blank. Zone Room ID B2.2 Room Name 0 Functional Description 0 Public Collection Space 2,000 Number of Occupants +/- 40 Visual Privacy (full, partial, open) Zone Designation Zone B Room Height 0 LEED NC Regurlarly Occupied Space 0 Base ACOUSTICS Equipment Hardware/STC Rating 0 NRC 0 0 0 Plug Loads Air Change/ HR Walls HVAC ENGINEERING CRITERIA Temperature Lighting 0 0 110v, 20a, 1ph 0 0 Power 0 0 Pressure (+/-) 0 Floor Operable Windows Separation/STC FURNITURE/EQUIPMENT Moveable 0 Fixed RT60 & Shaping 0 TBD
room data sheet is not comprehensive in nature. Information regarding specific room features may not have been available and was intentionally
Visual
Requirement: Floor Level 0 Room Length, Width, Shape Open
Arts Permanent Gallery, Cultural Traditions SUSTAINABILITY FEATURES Adjacencies Accessibility
vs. Private

This room data sheet is not comprehensive in nature. Information regarding specific room features may not have been available and was intentionally left blank.

SUSTAINABILITY FEATURES Adjacencies Accessibility Requirement:

Compliance with ADA/ABAAG (2004) citations is required for accessibility. SI also requires compliance with SI Accessibility Guidelines and the IBC. Comparisons should be made and the more stringent requirement followed for design purposes. Ensure compliance with ADA/ABAAG (2004) 305 Reach Ranges; 305 Clear Floor or Ground Space & 309 Operable Parts. See Accessibility Narrative for additional information.

Resource Center, Small Screening Room

Functional Description Public exhibition component of the CAAMA program. See also additional space related to CAAMA in space list.

vs. Private

Absorptive finish on the

Please refer to structural narrative for more information on structural requirements.

CRITICAL DIMENSIONS

65 Room Data Sheets | FREELON BOND Infrastructure Only 0 Other Amenities Deionized Water Vacuum Yes Speakers OH Gr. 2, 130 SF/HD FIRE ALARM Smoke Detection Yes Wet Sprinkler Special Waste Dry Sprinkler Pre-Action Sprinkler No FIRE PROTECTION No Considerations for Water 0 No Floor Drains Floor Sink Grey/Blackwater Piping 0 No No No Protected Hot/Cold No No Recycled Water Supply (treated) 0 No Public Address Audio Compressed Air Audio Visual Requirements No Hot/Cold Water Task Light No Yes 0 Plant/Clean Steam Yes Acoustic Sensitivity NC 35-40 Vibration Sensitivity Special Equipment/Artifact Sensitivity PLUMBING Target Illuminance (IES 9th Edition) Daylight Sensor 5-30 FC Exhibit Light To Be Considered Power Density (AHSRAE 2004) Exempt Temperature Deviations (+/-) Yes To Be Considered Process Water UPS Switched Receptacles Dimming No Humidity 0 Yes Other Humidity Deviation (+/-) 10 min. 0 Yes Outside Air Single/Multi-Level Switching 0 Emergency/Standby Power 15 CFM/person 65/ Carbon/95 Multi Occupancy Sensor Special Exhaust Sub-metering & Feedback Displays Filtration (Pre/Final/Other) Voice/Data DATA/TELECOMMUNICATIONS Yes 0 SECURITY 0 7.5 kPa/26.7 kN Floor Loading/Point Loads DAYLIGHTING 0 0 Shading Considerations Top/Side Lighting AV for exhibits to be determined by exhibit design Yes STRUCTURAL 0 0 Refer to information
security closet. 0 Additional space in Program Technical Comment: CAAMA Assignable Square Feet (ASF) OFEO Space Dimensions 0 Organizational Unit Other Interior Glazing 0 0 0 0 0 Ceiling CRITICAL FINISHES 0 Positive
indicated in Volume IV, Section E. Dedicated
ELECTRICAL ARCHITECTURAL
Zone Room ID B2.3 Room Name 0
Public Collection Space 800 Number of Occupants NA Visual Privacy (full, partial, open) Zone Designation Zone B Room Height 0 LEED NC Regurlarly Occupied Space 0 Base ACOUSTICS Equipment Hardware/STC Rating 0
ceiling with an NRC of 0.80
higher 0 0 Plug Loads Air Change/ HR Walls HVAC ENGINEERING CRITERIA Temperature Lighting 45%RH yr. rd. ±2ºF 110v, 20a, 1ph Yes 8% RH yr. rd. Power No 0 Pressure (+/-) 70ºF Floor Operable Windows Separation/STC FURNITURE/EQUIPMENT Moveable 0 Fixed RT60 & Shaping 0.5-0.7 s TBD
NRC
or
Floor Level 0 Room
Open
Length, Width, Shape

This room data sheet is not comprehensive in nature. Information regarding specific room features may not have been available and was intentionally left blank.

Adjacencies Accessibility Requirement:

Compliance with ADA/ABAAG (2004) citations is required for accessibility. SI also requires compliance with SI Accessibility Guidelines and the IBC. Comparisons should be made and the more stringent requirement followed for design purposes. Ensure compliance with ADA/ABAAG (2004) 305 Reach Ranges; 305 Clear Floor or Ground Space & 309 Operable Parts. See Accessibility Narrative for additional information.

Lobby/Assembly, Youth Gallery, CAAMA

SUSTAINABILITY FEATURES

vs. Private

Please refer to structural narrative for more information on structural requirements.

CRITICAL DIMENSIONS

(IES 9th Edition)

Smithsonian Institution National Museum of African American History and Culture 66 Infrastructure Only 0 Other Amenities Deionized Water Vacuum Yes Speakers OH Gr. 2, 130 SF/HD FIRE ALARM Smoke Detection Yes Wet Sprinkler Special Waste Dry Sprinkler Pre-Action Sprinkler No FIRE PROTECTION No Considerations for Water 0 No Floor Drains Floor Sink Grey/Blackwater Piping 0 No No No Protected Hot/Cold No No Recycled Water Supply (treated) 0 No Public Address Audio Compressed Air Audio Visual Requirements No Hot/Cold Water Task Light To Be Considered Yes 0 Plant/Clean Steam Yes Acoustic Sensitivity NC 35-40 Vibration Sensitivity Special Equipment/Artifact Sensitivity PLUMBING Target
Daylight Sensor 5-30 FC
To Be Considered Power
Exempt Temperature Deviations (+/-) Yes To Be Considered Process Water UPS Switched Receptacles Dimming No Humidity 0 Yes Other Humidity Deviation (+/-) 10 min. 0 Yes Outside Air Single/Multi-Level Switching 0 Emergency/Standby Power 15 CFM/person 65/ Carbon/95 Multi Occupancy Sensor Special Exhaust Sub-metering & Feedback Displays Filtration (Pre/Final/Other) Voice/Data DATA/TELECOMMUNICATIONS Yes 0 SECURITY 0 7.5 kPa/26.7 kN Floor Loading/Point Loads DAYLIGHTING 0 0 Shading Considerations Top/Side Lighting AV for exhibits to be determined by exhibit design Yes STRUCTURAL 0 0 Refer to information
Dedicated security closet. 0 0 Technical Comment: Resource Gallery Assignable Square Feet (ASF) OFEO Space Dimensions 0 Organizational Unit Other Interior Glazing 0 0 0 0 0 Ceiling CRITICAL FINISHES 0 Positive
Illuminance
Exhibit Light
Density (AHSRAE 2004)
indicated in Volume IV, Section E.
ELECTRICAL ARCHITECTURAL
Zone Room ID B3.1 Room Name 0 Functional
use the facility.
study tables and
Public Collection Space 3,000 Number of Occupants TBD Visual Privacy (full, partial, open) Zone Designation Zone B Room Height 0 LEED NC Regurlarly Occupied Space 0 Base ACOUSTICS Equipment Hardware/STC Rating 0 NRC Absorptive finish on the ceiling with an NRC of 0.70 or higher 0 0 Plug Loads Air Change/ HR Walls HVAC ENGINEERING CRITERIA Temperature Lighting 45%RH yr. rd. ±2ºF 110v, 20a, 1ph Yes 8% RH yr. rd. Power No 0 Pressure (+/-) 70ºF Floor Operable Windows Separation/STC FURNITURE/EQUIPMENT Moveable 0 Fixed RT60 & Shaping 1.0 s TBD
Description The Resource Gallery will be fully accessible and have a resource person on hand to help visitors
Contains
media carrels.
Floor Level 0 Room Length,
Open
Width, Shape

This room data sheet is not comprehensive in nature. Information regarding specific room features may not have been available and was intentionally left blank.

Accessibility Requirement:

Adjacencies

Compliance with ADA/ABAAG (2004) citations is required for accessibility. SI also requires compliance with SI Accessibility Guidelines and the IBC. Comparisons should be made and the more stringent requirement followed for design purposes. Ensure compliance with ADA/ABAAG (2004) 305 Reach Ranges; 305 Clear Floor or Ground Space & 309 Operable Parts. See Accessibility Narrative for additional information.

Lobby/Assembly, Youth Gallery, Resource Gallery

SUSTAINABILITY FEATURES

vs. Private CRITICAL DIMENSIONS

Length, Width, Shape

finish on the ceiling with an NRC of 0.70 or higher

Please refer to structural narrative for more information on structural requirements.

67 Room Data Sheets | FREELON BOND Infrastructure Only 0 Other Amenities Deionized Water Vacuum Yes Speakers OH Gr. 2, 130 SF/HD FIRE ALARM Smoke Detection Yes Wet Sprinkler Special Waste Dry Sprinkler Pre-Action Sprinkler No FIRE PROTECTION No Considerations for Water 0 No Floor Drains Floor Sink Grey/Blackwater Piping 0 No No No Protected Hot/Cold No No Recycled Water Supply (treated) 0 No Public Address Audio Compressed Air Audio Visual Requirements No Hot/Cold Water Task Light Yes To Be Considered 0 Plant/Clean Steam Yes Acoustic Sensitivity NC 35-40 Vibration Sensitivity Special Equipment/Artifact Sensitivity PLUMBING Target Illuminance (IES 9th Edition) Daylight Sensor 5-30 FC Exhibit Light To Be Considered Power Density (AHSRAE 2004) 1.7 W/ft² Temperature Deviations (+/-) Yes No Process Water UPS Switched Receptacles Dimming To Be Considered Humidity 0 Yes Other Humidity Deviation (+/-) 10 min. 0 No Outside Air Single/Multi-Level Switching 0 Emergency/Standby Power 15 CFM/person 65/ Carbon/95 Single Occupancy Sensor Special Exhaust Sub-metering & Feedback Displays Filtration (Pre/Final/Other) Voice/Data DATA/TELECOMMUNICATIONS Yes 0 SECURITY 0 7.5 kPa/17.8 kN Floor Loading/Point Loads DAYLIGHTING 0 0 Shading Considerations Top/Side Lighting None Yes STRUCTURAL 0 0 Refer to information
0 0 Technical Comment: Library Assignable Square Feet (ASF) OFEO Space Dimensions 0 Organizational Unit Other Interior Glazing 0 0 0 0 0 Ceiling CRITICAL FINISHES 0 Positive
indicated in Volume IV, Section E
ELECTRICAL ARCHITECTURAL
Zone Room ID B3.2 Room Name 0
Public Collection Space 2,000 Number of Occupants TBD Visual Privacy (full, partial, open) Zone Designation Zone B Room Height 0 LEED NC Regurlarly Occupied Space 0 Base ACOUSTICS Equipment Hardware/STC Rating 0 NRC
0 0 Plug Loads Air Change/ HR Walls HVAC ENGINEERING
Temperature Lighting 45%RH yr. rd. ±2ºF 110v, 20a, 1ph Yes 8% RH yr. rd. Power No 0 Pressure (+/-) 70ºF Floor Operable Windows Separation/STC FURNITURE/EQUIPMENT Moveable 0 Fixed RT60 & Shaping 1.0 s TBD
Functional Description Library will open to the public during standard museum operating hours.
Absorptive
CRITERIA
Floor Level 0 Room
Open

This room data sheet is not comprehensive in nature. Information regarding specific room features may not have been available and was intentionally left blank.

Compliance with ADA/ABAAG (2004) citations is required for accessibility. SI also requires compliance with SI Accessibility Guidelines and the IBC. Comparisons should be made and the more stringent requirement followed for design purposes. Ensure compliance with ADA/ABAAG (2004) 305 Reach Ranges; 305 Clear Floor or Ground Space & 309 Operable Parts. See Accessibility Narrative for additional information.

Lobby/Assembly, Youth Gallery, Resource Gallery

SUSTAINABILITY FEATURES

vs. Private

Length, Width, Shape

Absorptive finish on the ceiling with an NRC of 0.70 or higher

Please refer to structural narrative for more information on structural requirements.

Smithsonian Institution National Museum of African American History and Culture 68 Infrastructure Only 0 Other Amenities Deionized Water Vacuum Yes Speakers OH Gr. 2, 130 SF/HD FIRE ALARM Smoke Detection Yes Wet Sprinkler Special Waste Dry Sprinkler Pre-Action Sprinkler No FIRE PROTECTION No Considerations for Water 0 No Floor Drains Floor Sink Grey/Blackwater Piping 0 No No No Protected Hot/Cold No No Recycled Water Supply (treated) 0 No Public Address Audio Compressed Air Audio Visual Requirements No Hot/Cold Water Task Light Yes To Be Considered 0 Plant/Clean Steam Yes Acoustic Sensitivity NC 35-40 Vibration Sensitivity Special Equipment/Artifact Sensitivity PLUMBING Target Illuminance (IES 9th Edition) Daylight Sensor 5-30 FC Exhibit Light To Be Considered Power Density (AHSRAE 2004) 1.7 W/ft² Temperature Deviations (+/-) Yes No Process Water UPS Switched Receptacles Dimming To Be Considered Humidity 0 No Other Humidity Deviation (+/-) 10 min. 0 No Outside Air Single/Multi-Level Switching 0 Emergency/Standby Power 15 CFM/person 65/ Carbon/95 Single Occupancy Sensor Special Exhaust Sub-metering & Feedback Displays Filtration (Pre/Final/Other) Voice/Data DATA/TELECOMMUNICATIONS Yes 0 SECURITY 0 5.0 kPa/8.9 kN Floor Loading/Point Loads DAYLIGHTING 0 0 Shading Considerations Top/Side Lighting None Yes STRUCTURAL 0 0 Refer to information
0 0 Technical Comment: Reading/Reference Room Assignable Square Feet (ASF) OFEO Space Dimensions 0 Organizational Unit Other Interior Glazing 0 0 0 0 0 Ceiling CRITICAL FINISHES 0 Positive
indicated in Volume IV, Section E
ELECTRICAL ARCHITECTURAL
Zone Room ID B3.3 Room Name 0 Functional
Reading
Public Collection Space 300 Number of Occupants TBD Visual Privacy (full, partial, open) Zone Designation Zone B Room Height 0 LEED NC Regurlarly Occupied Space 0 Base ACOUSTICS Equipment Hardware/STC Rating 0 NRC
0 0 Plug Loads Air Change/ HR Walls HVAC ENGINEERING
Temperature Lighting 45%RH yr. rd. ±2ºF 110v, 20a, 1ph Yes 8% RH yr. rd. Power No 0 Pressure (+/-) 70ºF Floor Operable Windows Separation/STC FURNITURE/EQUIPMENT Moveable 0 Fixed RT60 & Shaping 1.0 s TBD
Description
Room will open to the public during standard museum operating hours.
CRITERIA
Floor Level 0 Room
Open
Adjacencies Accessibility Requirement:
CRITICAL DIMENSIONS

This room data sheet is not comprehensive in nature.

Compliance with ADA/ABAAG (2004) citations is required for accessibility. SI also requires compliance with SI Accessibility Guidelines and the IBC. Comparisons should be made and the more stringent requirement followed for design purposes. Ensure compliance with ADA/ABAAG (2004) 305 Reach Ranges; 305 Clear Floor or Ground Space & 309 Operable Parts. See Accessibility Narrative for additional information. Lobby/Assembly, Youth Gallery, Resource Gallery

CRITICAL DIMENSIONS

finish on the ceiling with an NRC of

Please refer to structural narrative for more information on structural requirements.

69 Room Data Sheets | FREELON BOND Infrastructure Only 0 Other Amenities Deionized Water Vacuum Yes Speakers OH Gr. 2, 130 SF/HD FIRE ALARM Smoke Detection Yes Wet Sprinkler Special Waste Dry Sprinkler Pre-Action Sprinkler No FIRE PROTECTION No Considerations for Water 0 No Floor Drains Floor Sink Grey/Blackwater Piping 0 No No No Protected Hot/Cold No No Recycled Water Supply (treated) 0 No Public Address Audio Compressed Air Audio Visual Requirements No Hot/Cold Water Task Light Yes No 0 Plant/Clean Steam Yes Acoustic Sensitivity NC 35-40 Vibration Sensitivity Special Equipment/Artifact Sensitivity PLUMBING Target Illuminance (IES 9th Edition) Daylight Sensor 30 FC Exhibit Light No Power Density (AHSRAE 2004) 1.7 W/ft² Temperature Deviations (+/-) Yes No Process Water UPS Switched Receptacles Dimming To Be Considered Humidity 0 No Other Humidity Deviation (+/-) 10 min. 0 No Outside Air Single/Multi-Level Switching 0 Emergency/Standby Power 15 CFM/person 65/ Carbon/95 Single Occupancy Sensor Special Exhaust Sub-metering & Feedback Displays Filtration (Pre/Final/Other) Voice/Data DATA/TELECOMMUNICATIONS Yes 0 SECURITY 0 7.5 kPa/26.7 kN Floor Loading/Point Loads DAYLIGHTING 0 0 Shading Considerations Top/Side Lighting None Yes STRUCTURAL 0 0 Refer to information indicated in Volume IV, Section E 0 0 Technical Comment: Archives Assignable Square Feet (ASF) OFEO Space Dimensions 0 Organizational Unit Other Interior Glazing 0 0 0 0 0 Ceiling CRITICAL FINISHES 0 Positive
ELECTRICAL ARCHITECTURAL
regarding specific room features may
have
available and was intentionally left blank. Zone Room ID B3.4 Room Name 0 Functional Description Libray will open to the public during standard museum operating hours. The public may access
materials
assistance of resource
who will retrieve them from archive stacks. Public Collection Space 250 Number of Occupants TBD Visual Privacy (full, partial, open) Zone Designation Zone B Room Height 0 LEED NC Regurlarly Occupied Space 0 Base ACOUSTICS Equipment Hardware/STC Rating 0 NRC
0.70 or higher 0 0 Plug Loads Air Change/ HR Walls HVAC ENGINEERING CRITERIA Temperature Lighting 45%RH yr. rd. ±2ºF 110v, 20a, 1ph Yes 8% RH yr. rd. Power No 0 Pressure (+/-) 70ºF Floor Operable Windows Separation/STC FURNITURE/EQUIPMENT Moveable 0 Fixed RT60 & Shaping 1.0 s TBD
Information
not
been
these
with the
personnel
Absorptive
Floor Level 0 Room Length,
Open
SUSTAINABILITY FEATURES Adjacencies Accessibility Requirement:
Width, Shape
vs. Private

This room data sheet is not comprehensive in nature. Information regarding specific room features may not have been available and was intentionally left blank.

Accessibility Requirement: Floor

Adjacencies

Water Table

Compliance with ADA/ABAAG (2004) citations is required for accessibility. SI also requires compliance with SI Accessibility Guidelines and the IBC. Comparisons should be made and the more stringent requirement followed for design purposes. An accessible route including a minimum clear width of 36" (except at doors, whic must be at least 32" clear) is required. Refer to ADA/ABAAG (2004) for specifications regarding clear floor spaces at desks, files and equipment for individuals using wheelchairs. See Accessibility Narrative for additional information.

Collection Handling, Collection Prep and Installation, Curatorial and Collection Management, Conservation

Functional Description Since most of the NMAAHC Collection will be stored at an off-site location, this is a multipurpose collection storage space to support the exhibition program and is for the use of curators, researchers and other staff working with collection items on-site, to ensure the safety and security of the collection items.

SUSTAINABILITY FEATURES

Open vs. Private

Please refer to structural narrative for more information on structural requirements.

CRITICAL DIMENSIONS

Length, Width, Shape

Smithsonian Institution National Museum of African American History and Culture 70 Infrastructure Only 0 Other Amenities Deionized Water Vacuum Yes Speakers 0 FIRE ALARM Smoke Detection Yes Wet Sprinkler Special Waste Dry Sprinkler Pre-Action Sprinkler 0 FIRE PROTECTION No Considerations for Water 0 No Floor Drains Floor Sink Grey/Blackwater Piping 0 No No No Protected Hot/Cold No No Recycled Water Supply (treated) 0 No Public Address Audio Compressed Air Audio Visual Requirements No Hot/Cold Water Task Light Yes No 0 Plant/Clean Steam Yes Acoustic Sensitivity NC 40 Vibration Sensitivity Special Equipment/Artifact Sensitivity PLUMBING Target Illuminance (IES 9th Edition) Daylight Sensor 10 FC Exhibit Light No Power Density (AHSRAE 2004) 0.8 W/ft² Temperature Deviations (+/-) Yes No Process Water UPS Switched Receptacles Dimming To Be Considered Humidity 0 No Other Humidity Deviation (+/-) 10 min. 0 No Outside Air Single/Multi-Level Switching 0 Emergency/Standby Power 15 CFM/person 65/ Carbon/95 Single Occupancy Sensor Special Exhaust Sub-metering & Feedback Displays Filtration (Pre/Final/Other) Voice/Data DATA/TELECOMMUNICATIONS Yes 0 SECURITY 0 12.0 kPa/26.7 kN Floor Loading/Point Loads DAYLIGHTING 0 0 Shading Considerations Top/Side Lighting None No STRUCTURAL 0 0 Refer to information indicated in Volume IV, Section E Full 0 Technical Comment: Collection Storage Assignable Square Feet (ASF) OFEO Space Dimensions 0 Organizational Unit Other Interior Glazing 0 0 Yes Yes No Off GPSing/Organic/SealedCeiling CRITICAL FINISHES 0 Positive
ELECTRICAL ARCHITECTURAL
Zone Room ID C1.1 Room Name 0
Non Public Collection Space 1,500 Number of Occupants NA Visual Privacy (full, partial, open) Zone Designation Zone C Room Height 0 LEED NC Regurlarly
0 Base ACOUSTICS Equipment Hardware/STC Rating 0 NRCSTC 55 0 Plug Loads Air Change/ HR Walls HVAC ENGINEERING
Temperature Lighting 45%RH yr. rd. ±2ºF 110v, 20a, 1ph Yes 8% RH yr. rd. Power No No Off GPSing/Organic/Sealed Pressure (+/-) 70ºF Floor Operable Windows
FURNITURE/EQUIPMENT Moveable Yes Fixed RT60
0 Above
Occupied Space
CRITERIA
Separation/STC
& Shaping
0
Level
Room

Accessibility Requirement:

Adjacencies

SUSTAINABILITY FEATURES

Compliance with ADA/ABAAG (2004) citations is required for accessibility. SI also requires compliance with SI Accessibility Guidelines and the IBC. Comparisons should be made and the more stringent requirement followed for design purposes. An accessible route including a minimum clear width of 36" (except at doors, whic must be at least 32" clear) is required. Refer to ADA/ABAAG (2004) for specifications regarding clear floor spaces at desks, files and equipment for individuals using wheelchairs. See Accessibility Narrative for additional information.

Collections Shipping/Receiving, Loading Dock Security Booths and Washroom, Crating/Uncrating and Packing Studio, Receiving /Courier Office, Temporary Storage, Adjacent but separate to Loading Bay Non-Collections

CRITICAL DIMENSIONS

Length, Width, Shape Open vs. Private

Recommend hose bibb under Plumbing. If there is no roof or cover no additional Fire Protection needed. Please

requirements.

71 Room Data Sheets | FREELON BOND Infrastructure Only 0 Other Amenities Deionized Water Vacuum Yes Speakers No FIRE ALARM Smoke Detection 0 Wet Sprinkler Special Waste Dry Sprinkler Pre-Action Sprinkler No FIRE PROTECTION No Considerations for Water 0 OH 130 SF/HD Floor Drains Floor Sink Grey/Blackwater Piping 0 No No No Protected Hot/Cold No No Recycled Water Supply (treated) 0 Trench Drain Public Address Audio Compressed Air Audio Visual Requirements Yes Hot/Cold Water Task Light No No 0 Plant/Clean Steam Yes Acoustic Sensitivity 0 Vibration Sensitivity Special Equipment/Artifact Sensitivity PLUMBING Target Illuminance (IES 9th Edition) Daylight Sensor 10 FC Exhibit Light No Power Density (AHSRAE 2004) 1.1 W/ft² Temperature Deviations (+/-) Yes No Process Water UPS Switched Receptacles Dimming To Be Considered Humidity 0 No Other Humidity Deviation (+/-) 6 min. 0 No Outside Air Single/Multi-Level Switching 0 Emergency/Standby Power 15 CFM/person 30/65 Single Occupancy Sensor Special Exhaust Sub-metering & Feedback Displays Filtration (Pre/Final/Other) Voice/Data DATA/TELECOMMUNICATIONS Yes 0 SECURITY 0 12.0 kPa/26.7 kN Floor Loading/Point Loads DAYLIGHTING 0 0 Shading Considerations Top/Side Lighting None No STRUCTURAL 0 0 Refer to information indicated in Volume IV, Section E Full 0 Technical Comment: Enclosed Collections Loading Bay Assignable Square Feet (ASF) OFEO Space Dimensions 0 Organizational Unit Other Interior Glazing 0 0 Yes Yes No Off GPSing/Organic/SealedCeiling CRITICAL
Over Head Doors Positive
FINISHES
structural narrative for more information on structural
ELECTRICAL ARCHITECTURAL
blank. Zone Room ID C2.1 Room Name 0 Functional Description Fully enclosed truck bay, with exterior overhead door providing access to
Loading Dock and Shipping/Receiving
beyond;
meet
minimum requirement to handle one tractor-trailer loading
unloading, surveyed by CCTV cameras,
voice
visual
Loading Dock
Security Booth required. Non Public Collection Space 1,600 Number of Occupants NA Visual Privacy
partial,
Zone Designation Zone C Room Height Min 20' LEED NC Regurlarly Occupied Space 0 Base ACOUSTICS Equipment Hardware/STC Rating Yes NRCSTC 55 0 Plug Loads Air Change/ HR Walls HVAC
Temperature Lighting 45% RH yr. md. ±2ºF 110v,
Yes 15% RH yr. rd. Power No No Off GPSing/Organic/Sealed Pressure (+/-) 76ºF Summer, 71ºF Winter Floor Operable Windows Separation/STC FURNITURE/EQUIPMENT Moveable No Fixed RT60 & Shaping 0 Above
Table
refer to
This room data sheet is not comprehensive in nature. Information regarding specific room features may not have been available and was intentionally left
the
Area
must
the
or
with
and
communication between the
and the
(full,
open)
ENGINEERING CRITERIA
20a, 1ph
Water
0
Floor Level
Room

This room data sheet is not comprehensive in nature. Information regarding specific room features may not have been available and was intentionally left blank.

Above Water Table

Accessibility Requirement:

Adjacencies

SUSTAINABILITY FEATURES

Open vs. Private

Compliance with ADA/ABAAG (2004) citations is required for accessibility. SI also requires compliance with SI Accessibility Guidelines and the IBC. Comparisons should be made and the more stringent requirement followed for design purposes. An accessible route including a minimum clear width of 36" (except at doors, whic must be at least 32" clear) is required. Refer to ADA/ABAAG (2004) for specifications regarding clear floor spaces at desks, files and equipment for individuals using wheelchairs. See Accessibility Narrative for additional information.

Collections Shipping/Receiving, Loading Dock Security Booths and Washroom, Crating/Uncrating and Packing Studio, Receiving /Courier Office, Temporary Storage, Adjacent but separate to Loading Dock Non-Collections

different types of trucks.

CRITICAL DIMENSIONS

Length, Width, Shape

Smithsonian Institution National Museum of African American History and Culture 72 Infrastructure Only 0 Other Amenities Deionized Water Vacuum Yes Speakers No FIRE ALARM Smoke Detection 0 Wet Sprinkler Special Waste Dry Sprinkler Pre-Action Sprinkler No FIRE PROTECTION 0 Considerations for Water 0 OH Gr. 2, 130 SF/HD Floor Drains Floor Sink Grey/Blackwater Piping 0 0 0 0 Protected Hot/Cold 0 0 Recycled Water Supply (treated) 0 0 Public Address Audio Compressed Air Audio Visual Requirements 0 Hot/Cold Water Task Light 0 0 0 Plant/Clean Steam 0 Acoustic Sensitivity 0 Vibration Sensitivity Special Equipment/Artifact Sensitivity PLUMBING Target Illuminance (IES 9th Edition) Daylight Sensor 0 Exhibit Light 0 Power Density (AHSRAE 2004) 0 Temperature Deviations (+/-) 0 0 Process Water UPS Switched Receptacles Dimming 0 Humidity 0 0 Other Humidity Deviation (+/-) 0 0 0 Outside Air Single/Multi-Level Switching 0 Emergency/Standby Power 0 0 0 Occupancy Sensor Special Exhaust Sub-metering & Feedback Displays Filtration (Pre/Final/Other) Voice/Data DATA/TELECOMMUNICATIONS 0 0 SECURITY 0 0 Floor Loading/Point Loads DAYLIGHTING 0 0 Shading Considerations Top/Side Lighting 0 0 STRUCTURAL 0 0 Refer to information indicated in Volume IV, Section E 0 Dock levelers should be made of smooth steele, so as to prevent vibrations in the artefact cases as they are unloaded. Technical Comment: Enclosed Collections Loading Dock Assignable Square Feet (ASF) OFEO Space Dimensions 0 Organizational Unit Other Interior Glazing 0 0 0 0 0 Ceiling CRITICAL FINISHES 0 0 0 ELECTRICAL ARCHITECTURAL
Zone Room ID C2.2 Room Name 0 Functional Description Fully enclosed truck loading dock, with hydraulic lift, providing access to the Shipping/Receiving Area: This is the space that the collection will be unloaded from before entering the collection handling suite. The use of Dock Levelers is recommended to accommodate
Non Public Collection Space 650 Number of Occupants NA Visual Privacy (full, partial, open) Zone Designation Zone C Room Height 0 LEED NC Regurlarly Occupied Space 0 Base ACOUSTICS Equipment Hardware/STC Rating 0 NRC 0 0 0 Plug Loads Air Change/ HR Walls HVAC ENGINEERING CRITERIA Temperature Lighting 0 0 110v, 20a, 1ph 0 0 Power 0 0 Pressure (+/-) 0 Floor Operable Windows Separation/STC FURNITURE/EQUIPMENT Moveable 0 Fixed RT60 & Shaping 0
Floor Level 0
Room

This room data sheet is not comprehensive in nature. Information regarding specific room features may not have been available and was intentionally left

Water Table

Adjacencies

SUSTAINABILITY FEATURES

Accessibility Requirement: Floor Level 10' W x 12'H Door Opening Room Length, Width, Shape Open vs. Private

Compliance with ADA/ABAAG (2004) citations is required for accessibility. SI also requires compliance with SI Accessibility Guidelines and the IBC. Comparisons should be made and the more stringent requirement followed for design purposes. An accessible route including a minimum clear width of 36" (except at doors, whic must be at least 32" clear) is required. Refer to ADA/ABAAG (2004) for specifications regarding clear floor spaces at desks, files and equipment for individuals using wheelchairs. See Accessibility Narrative for additional information.

Enclosed Collections Loading Dock, Crating/Uncrating and Packing Studio, Receiving /Courier Office, Temporary Storage

Controls required: Overhead doors and personnel doors to both the Loading Dock and interior circulation space, acting as an environmental buffer zone designed to accommodate one tractor-trailer load of crates moving into the Crating/Uncrating Area. Inner doors to the building interior space should remain closed while exterior doors to the Loading Dock are open. This area may be used as an overnight acclimatization and holding area and therefore must be climate controlled.

CRITICAL DIMENSIONS

Please refer to structural narrative for more information on structural requirements.

73 Room Data Sheets | FREELON BOND Infrastructure Only 0 Other Amenities Deionized Water Vacuum Yes Speakers OH Gr. 2, 130 SF/HD FIRE ALARM Smoke Detection Yes Wet Sprinkler Special Waste Dry Sprinkler Pre-Action Sprinkler No FIRE PROTECTION No Considerations for Water 0 No Floor Drains Floor Sink Grey/Blackwater Piping 0 No No No Protected Hot/Cold No No Recycled Water Supply (treated) 0 No Public Address Audio Compressed Air Audio Visual Requirements No Hot/Cold Water Task Light Yes No 0 Plant/Clean Steam Yes Acoustic Sensitivity NC 40 Vibration Sensitivity Special Equipment/Artifact Sensitivity PLUMBING Target Illuminance (IES 9th Edition) Daylight Sensor 30 FC Exhibit Light No Power Density (AHSRAE 2004) 1.4 W/ft² Temperature Deviations (+/-) 0 No Process Water UPS Switched Receptacles Dimming To Be Considered Humidity 0 No Other Humidity Deviation (+/-) 10 min. 0 No Outside Air Single/Multi-Level Switching 0 Emergency/Standby Power 15 CFM/person 65/95 Single Occupancy Sensor Special Exhaust Sub-metering & Feedback Displays Filtration (Pre/Final/Other) Voice/Data DATA/TELECOMMUNICATIONS Yes 0 SECURITY 0 12.0 kPa/26.7 kN Floor Loading/Point Loads DAYLIGHTING 0 0 Shading Considerations Top/Side Lighting None No STRUCTURAL 0 0 Refer to information indicated in Volume IV, Section E Full 0 Technical Comment: Collections Shipping/Receiving Assignable Square Feet (ASF) OFEO Space Dimensions 0 Organizational Unit Other Interior Glazing 0 0 No No No Off GPSing/Organic/SealedCeiling CRITICAL FINISHES 0 Positive
ELECTRICAL ARCHITECTURAL
blank. Zone Room ID C2.3 Room Name 0 Functional Description Environmental
Non Public Collection Space 500 Number of Occupants NA Visual Privacy (full, partial, open) Zone Designation Zone C Room Height Min 12'-6" LEED NC Regurlarly Occupied Space 0 Base ACOUSTICS Equipment Hardware/STC Rating 0 NRC 0 STC 55 0 Plug Loads Air Change/ HR Walls HVAC ENGINEERING CRITERIA Temperature Lighting 45%RH yr. rd. ±2ºF 110v, 20a, 1ph Yes 8% RH yr. rd. Power No No Off GPSing/Organic/Sealed Pressure (+/-) 70ºF Floor Operable Windows Separation/STC
Moveable No Fixed RT60 & Shaping 0 Above
FURNITURE/EQUIPMENT
Smithsonian Institution National Museum of African American History and Culture 74 Infrastructure Only 0 Other Amenities Deionized Water Vacuum 0 Speakers 0 FIRE ALARM Smoke Detection 0 Wet Sprinkler Special Waste Dry Sprinkler Pre-Action Sprinkler 0 FIRE PROTECTION 0 Considerations for Water 0 0 Floor Drains Floor Sink Grey/Blackwater Piping 0 0 0 0 Protected Hot/Cold 0 0 Recycled Water Supply (treated) 0 0 Public Address Audio Compressed Air Audio Visual Requirements 0 Hot/Cold Water Task Light 0 0 0 Plant/Clean Steam 0 Acoustic Sensitivity 0 Vibration Sensitivity Special Equipment/Artifact Sensitivity PLUMBING Target Illuminance (IES 9th Edition) Daylight Sensor 0 Exhibit Light 0 Power Density (AHSRAE 2004) 0 Temperature Deviations (+/-) 0 0 Process Water UPS Switched Receptacles Dimming 0 Humidity 0 0 Other Humidity Deviation (+/-) 0 0 0 Outside Air Single/Multi-Level Switching 0 Emergency/Standby Power 0 0 0 Occupancy Sensor Special Exhaust Sub-metering & Feedback Displays Filtration (Pre/Final/Other) Voice/Data DATA/TELECOMMUNICATIONS 0 0 SECURITY 0 0 Floor Loading/Point Loads DAYLIGHTING 0 0 Shading Considerations Top/Side Lighting 0 0 STRUCTURAL 0 0 0 0 0 Technical Comment: Moving Equipment Storage Assignable Square Feet (ASF) OFEO Space Dimensions 0 Organizational Unit Other Interior Glazing 0 0 0 0 0 Ceiling CRITICAL FINISHES 0 0 0 ELECTRICAL ARCHITECTURAL 0 Zone Room ID C2.3A Room Name 0 Functional Description Designated area adjacent to Shipping/Receiving Area. This space stores the straps, padded mats, hand trucks, and small electric forklift to move larger artifacts (there should also be a charger located here for the forklift battery). Non Public Collection Space 125 Number of Occupants 0 Visual Privacy (full, partial, open) Zone Designation Zone C Room Height 0 LEED NC Regurlarly Occupied Space 0 Base ACOUSTICS Equipment Hardware/STC Rating 0 NRC 0 0 0 Plug Loads Air Change/ HR Walls HVAC ENGINEERING CRITERIA Temperature Lighting 0 0 110v, 20a, 1ph 0 0 Power 0 0 Pressure (+/-) 0 Floor Operable Windows Separation/STC FURNITURE/EQUIPMENT Moveable 0 Fixed RT60 & Shaping 0 Above Water Table 0 Enclosed Collections Loading Dock, Collections Shipping/Receiving, Crating/Uncrating Packing Studio, Loading Dock Security Booth and
Receiving Courier Office, Temporary Storage SUSTAINABILITY FEATURES Adjacencies Accessibility Requirement: Floor Level 0 Room Length, Width, Shape Open vs. Private
NOTE: Space
Shipping/Receiving
Washroom,
CRITICAL DIMENSIONS
Located within Collections

This room data sheet is not comprehensive in nature. Information regarding specific room features may not have been available and was intentionally left blank.

Accessibility Requirement:

Adjacencies

SUSTAINABILITY FEATURES

Compliance with ADA/ABAAG (2004) citations is required for accessibility. SI also requires compliance with SI Accessibility Guidelines and the IBC. Comparisons should be made and the more stringent requirement followed for design purposes. An accessible route including a minimum clear width of 36" (except at doors, whic must be at least 32" clear) is required. Refer to ADA/ABAAG (2004) for specifications regarding clear floor spaces at desks, files and equipment for individuals using wheelchairs. See Accessibility Narrative for additional information.

Enclosed Collections Loading Dock, Collections Shipping/Receiving, Loading Dock Security Booths and Washroom, Receiving /Courier Office, Temporary Storage

Controls required; This secure space provides an environmentally controlled area for unpacking and packing of artifact shipments. It is designed to accommodate one tractor-trailer load of crates. Could double as artifact processing and catalog space.

CRITICAL DIMENSIONS

Recommend hand sink under Plumbing. Please refer to structural narrative for more information on structural requirements.

75 Room Data Sheets | FREELON BOND Infrastructure Only 0 Other Amenities Deionized Water Vacuum Yes Speakers OH Gr. 2, 130 SF/HD FIRE ALARM Smoke Detection Yes Wet Sprinkler Special Waste Dry Sprinkler Pre-Action Sprinkler No FIRE PROTECTION No Considerations for Water 0 No Floor Drains Floor Sink Grey/Blackwater Piping 0 No No No Protected Hot/Cold No No Recycled Water Supply (treated) 0 No Public Address Audio Compressed Air Audio Visual Requirements Yes Hot/Cold Water Task Light Yes No 0 Plant/Clean Steam Yes Acoustic Sensitivity NC 40 Vibration Sensitivity Special Equipment/Artifact Sensitivity PLUMBING Target Illuminance (IES 9th Edition) Daylight Sensor 50 FC Exhibit Light No Power Density (AHSRAE 2004) 1.7 W/ft² Temperature Deviations (+/-) 0 No Process Water UPS Switched Receptacles Dimming To Be Considered Humidity 0 No Other Humidity Deviation (+/-) 10 min. 0 No Outside Air Single/Multi-Level Switching 0 Emergency/Standby Power 15 CFM/person 65/95 Single Occupancy Sensor Special Exhaust Sub-metering & Feedback Displays Filtration (Pre/Final/Other) Voice/Data DATA/TELECOMMUNICATIONS Yes 0 SECURITY 0 12.0 kPa/26.7 kN Floor Loading/Point Loads DAYLIGHTING 0 0 Shading Considerations Top/Side Lighting None No STRUCTURAL 0 0 Refer to information indicated in Volume IV, Section E Full 0 Technical Comment: Crating/Uncrating, Packing Studio
Square Feet
OFEO Space Dimensions 0 Organizational Unit Other Interior Glazing 0 0 Yes Yes No Off GPSing/Organic/SealedCeiling CRITICAL FINISHES 0 Positive
Assignable
(ASF)
ELECTRICAL ARCHITECTURAL
Zone Room ID C2.4 Room Name 0 Functional
Non Public Collection Space 800 Number of Occupants NA Visual Privacy (full, partial, open) Zone Designation Zone C Room Height Min 12'-6" LEED NC
Space 0 Base ACOUSTICS Equipment Hardware/STC Rating 0 NRC 0 STC 55 0 Plug Loads Air Change/ HR Walls HVAC ENGINEERING
Temperature Lighting 45%RH yr. rd. ±2ºF 110v, 20a, 1ph Yes 8% RH yr. rd. Power No No Off GPSing/Organic/Sealed Pressure (+/-) 70ºF Floor Operable Windows Separation/STC FURNITURE/EQUIPMENT Moveable Yes Fixed RT60
0 Above
Description Environmental
Regurlarly Occupied
CRITERIA
& Shaping
Water Table
Floor Level 10' W
12'H Door Opening Room
x
Length, Width, Shape Open vs. Private

This room data sheet is not comprehensive in nature. Information regarding specific room features may not have been available and was intentionally left blank.

Accessibility Requirement:

Adjacencies

Compliance with ADA/ABAAG (2004) citations is required for accessibility. SI also requires compliance with SI Accessibility Guidelines and the IBC. Comparisons should be made and the more stringent requirement followed for design purposes. An accessible route including a minimum clear width of 36" (except at doors, whic must be at least 32" clear) is required. Refer to ADA/ABAAG (2004) for specifications regarding clear floor spaces at desks, files and equipment for individuals using wheelchairs. See Accessibility Narrative for additional information.

Crating/Uncrating, Packing Studio

Description Environmental Controls required: Designed to accommodate up to one tractor-trailer load of crates.

SUSTAINABILITY FEATURES

vs. Private

CRITICAL DIMENSIONS

Length, Width, Shape

Recommend hand sink under Plumbing. Please refer to structural narrative for more information on structural requirements.

Smithsonian Institution National Museum of African American History and Culture 76 Infrastructure Only 0 Other Amenities Deionized Water Vacuum Yes Speakers OH Gr. 2, 130 SF/HD FIRE ALARM Smoke Detection Yes Wet Sprinkler Special Waste Dry Sprinkler Pre-Action Sprinkler No FIRE PROTECTION No Considerations for Water 0 No Floor Drains Floor Sink Grey/Blackwater Piping 0 No No No Protected Hot/Cold No No Recycled Water Supply (treated) 0 No Public Address Audio Compressed Air Audio Visual Requirements Yes Hot/Cold Water Task Light Yes No 0 Plant/Clean Steam Yes Acoustic Sensitivity NC 40 Vibration Sensitivity Special Equipment/Artifact Sensitivity PLUMBING Target Illuminance (IES 9th Edition) Daylight Sensor 50 FC Exhibit Light No Power Density (AHSRAE 2004) 1.7 W/ft² Temperature Deviations (+/-) 0 No Process Water UPS Switched Receptacles Dimming To Be Considered Humidity 0 No Other Humidity Deviation (+/-) 10 min. 0 No Outside Air Single/Multi-Level Switching 0 Emergency/Standby Power 15 CFM/person 65/95 Single Occupancy Sensor Special Exhaust Sub-metering & Feedback Displays Filtration (Pre/Final/Other) Voice/Data DATA/TELECOMMUNICATIONS Yes 0 SECURITY 0 12.0 kPa/26.7 kN Floor Loading/Point Loads DAYLIGHTING 0 0 Shading Considerations Top/Side Lighting None No STRUCTURAL 0 0 Refer to information indicated
Volume IV, Section E Full 0 Technical Comment: Crate Storage Assignable Square Feet (ASF) OFEO Space Dimensions 0 Organizational Unit Other Interior Glazing 0 0 Yes Yes No Off GPSing/Organic/SealedCeiling CRITICAL FINISHES 0 Positive
in
ELECTRICAL ARCHITECTURAL
Zone Room ID C2.5 Room Name 0 Functional
Non Public Collection Space 300 Number of Occupants NA Visual Privacy (full, partial, open) Zone Designation Zone C Room Height Min 12'-6" LEED NC Regurlarly Occupied Space 0 Base ACOUSTICS Equipment Hardware/STC Rating 0 NRC 0 STC 55 0 Plug Loads Air Change/ HR Walls HVAC ENGINEERING CRITERIA Temperature Lighting 45%RH yr. rd. ±2ºF 110v, 20a, 1ph Yes 8% RH yr. rd. Power No No Off GPSing/Organic/Sealed Pressure (+/-) 70ºF Floor Operable Windows Separation/STC FURNITURE/EQUIPMENT Moveable Yes Fixed RT60 & Shaping 0 0
Floor Level 10'
Room
W x 12'H Door Opening
Open

This room data sheet is not comprehensive in nature. Information regarding specific room features may not have been available and was intentionally left blank.

Water Table

Accessibility Requirement:

Adjacencies

Description Environmental Controls

SUSTAINABILITY FEATURES

Open vs. Private

Floor Level 10' W x 12'H Door Opening Room Length, Width, Shape

Compliance with ADA/ABAAG (2004) citations is required for accessibility. SI also requires compliance with SI Accessibility Guidelines and the IBC. Comparisons should be made and the more stringent requirement followed for design purposes. An accessible route including a minimum clear width of 36" (except at doors, whic must be at least 32" clear) is required. Refer to ADA/ABAAG (2004) for specifications regarding clear floor spaces at desks, files and equipment for individuals using wheelchairs. See Accessibility Narrative for additional information. Curatorial and Collection Spaces

This

is designed to be the secure storage area for packed artifacts in transit either entering or leaving, and waiting to be loaded onto trucks or enter the Collection space of the museum.

CRITICAL DIMENSIONS

Separation/STC FURNITURE/EQUIPMENT

Recommend hand sink under Plumbing. Please refer to structural narrative for more information on structural requirements.

77 Room Data Sheets | FREELON BOND Infrastructure Only 0 Other Amenities Deionized Water Vacuum Yes Speakers OH Gr. 2, 130 SF/HD FIRE ALARM Smoke Detection Yes Wet Sprinkler Special Waste Dry Sprinkler Pre-Action Sprinkler No FIRE PROTECTION No Considerations for Water 0 No Floor Drains Floor Sink Grey/Blackwater Piping 0 No No No Protected Hot/Cold No No Recycled Water Supply (treated) 0 No Public Address Audio Compressed Air Audio Visual Requirements Yes Hot/Cold Water Task Light Yes No 0 Plant/Clean Steam Yes Acoustic Sensitivity NC 40 Vibration Sensitivity Special Equipment/Artifact Sensitivity PLUMBING Target Illuminance (IES 9th Edition) Daylight Sensor 50 FC Exhibit Light No Power Density (AHSRAE 2004) 1.7 W/ft² Temperature Deviations (+/-) 0 No Process Water UPS Switched Receptacles Dimming To Be Considered Humidity 0 No Other Humidity Deviation (+/-) 10 min. 0 No Outside Air Single/Multi-Level Switching 0 Emergency/Standby Power 15 CFM/person 65/95 Single Occupancy Sensor Special Exhaust Sub-metering & Feedback Displays Filtration (Pre/Final/Other) Voice/Data DATA/TELECOMMUNICATIONS Yes 0 SECURITY 0 12.0 kPa/26.7 kN Floor Loading/Point Loads DAYLIGHTING 0 0 Shading Considerations Top/Side Lighting None No STRUCTURAL 0 0 Refer to information indicated in Volume IV, Section E Full 0 Technical Comment: Transit Storage Assignable Square Feet (ASF) OFEO Space Dimensions 0 Organizational Unit Other Interior Glazing 0 0 Yes Yes No Off GPSing/Organic/SealedCeiling CRITICAL FINISHES 0 Positive
ELECTRICAL ARCHITECTURAL
Zone Room ID C2.6 Room Name 0 Functional
Non Public Collection Space 800 Number of Occupants NA Visual Privacy (full, partial, open) Zone Designation Zone C Room Height Min 12'-6" LEED NC Regurlarly Occupied Space 0 Base ACOUSTICS Equipment Hardware/STC Rating 0 NRC 0 STC 55 0 Plug Loads Air Change/ HR Walls HVAC ENGINEERING CRITERIA Temperature Lighting 45%RH yr. rd. ±2ºF 110v, 20a, 1ph Yes 8% RH yr. rd. Power No No Off GPSing/Organic/Sealed Pressure (+/-) 70ºF Floor Operable Windows
required:
space
Moveable Yes Fixed RT60 &
0
Shaping
Above

This room data sheet is not comprehensive in nature. Information regarding specific room features may not have been available and was intentionally left blank.

Above Water Table

Accessibility Requirement:

Adjacencies

SUSTAINABILITY FEATURES

Compliance with ADA/ABAAG (2004) citations is required for accessibility. SI also requires compliance with SI Accessibility Guidelines and the IBC. Comparisons should be made and the more stringent requirement followed for design purposes. An accessible route including a minimum clear width of 36" (except at doors, whic must be at least 32" clear) is required. Refer to ADA/ABAAG (2004) for specifications regarding clear floor spaces at desks, files and equipment for individuals using wheelchairs. See Accessibility Narrative for additional information.

Preparator's Workshop, Curatorial and Collection Management

Floor Level 10' W x 12'H Door Opening Room Length, Width, Shape

Description Environmentally controlled area adjacent to Preparator's Workshop and Exhibit Staging for exhibit layout and staging with artifacts present. May be used for clean graphics prep.

CRITICAL DIMENSIONS

Open vs. Private

& Shaping

an

CRITERIA

Recommend hand sink under Plumbing. Please refer to structural narrative for more information on structural requirements. ELECTRICAL

Smithsonian Institution National Museum of African American History and Culture 78 Infrastructure Only 0 Other Amenities Deionized Water Vacuum Yes Speakers OH Gr. 2, 130 SF/HD FIRE ALARM Smoke Detection Yes Wet Sprinkler Special Waste Dry Sprinkler Pre-Action Sprinkler No FIRE PROTECTION No Considerations for Water 0 No Floor Drains Floor Sink Grey/Blackwater Piping 0 No No No Protected Hot/Cold No No Recycled Water Supply (treated) 0 No Public Address Audio Compressed Air Audio Visual Requirements Yes Hot/Cold Water Task Light Yes No 0 Plant/Clean Steam Yes Acoustic Sensitivity NC 40 Vibration Sensitivity Special Equipment/Artifact Sensitivity PLUMBING Target Illuminance (IES 9th Edition) Daylight Sensor 50 FC Exhibit Light No Power Density (AHSRAE 2004) 1.7 W/ft² Temperature Deviations (+/-) Yes No Process Water UPS Switched Receptacles Dimming No Humidity 0 No Other Humidity Deviation (+/-) 10 min. 0 No Outside Air Single/Multi-Level Switching 0 Emergency/Standby Power 15 CFM/person 65/ Carbon/95 Single Occupancy Sensor Special Exhaust Sub-metering & Feedback Displays Filtration (Pre/Final/Other) Voice/Data DATA/TELECOMMUNICATIONS Yes 0 SECURITY 0 7.5 kPa/17.8 kN Floor Loading/Point Loads DAYLIGHTING 0 0 Shading Considerations Top/Side Lighting None No STRUCTURAL 0 0 Refer to information
E Full 0 Technical Comment: Clean Installation Room (Includes Framing) Assignable
Feet (ASF) OFEO Space Dimensions 0 Organizational Unit Other Interior Glazing 0 0 Yes Yes No Off GPSing/Organic/SealedCeiling CRITICAL FINISHES 0 Positive
indicated in Volume IV, Section
Square
ARCHITECTURAL
Zone Room ID C2.7 Room Name 0
Non Public Collection Space 800 Number of Occupants TBD Visual Privacy (full, partial, open) Zone Designation Zone C Room Height Min 12'-6" LEED
0 Base ACOUSTICS Equipment Hardware/STC Rating 0 NRC Absorptive
higher STC 55 0 Plug Loads Air Change/ HR Walls HVAC ENGINEERING
Temperature Lighting 45%RH yr. rd. ±2ºF 110v,
Yes 8% RH yr. rd. Power No No Off GPSing/Organic/Sealed Pressure (+/-) 70ºF Floor Operable Windows
FURNITURE/EQUIPMENT Moveable Yes Fixed RT60
0
Functional
NC Regurlarly Occupied Space
finish on the ceiling with
NRC of 0.70 or
20a, 1ph
Separation/STC

SUSTAINABILITY FEATURES

Compliance with ADA/ABAAG (2004) citations is required for accessibility. SI also requires compliance with SI Accessibility Guidelines and the IBC. Comparisons should be made and the more stringent requirement followed for design purposes. An accessible route including a minimum clear width of 36" (except at doors, whic must be at least 32" clear) is required. Refer to ADA/ABAAG (2004) for specifications regarding clear floor spaces at desks, files and equipment for individuals using wheelchairs. See Accessibility Narrative for additional information.

CRITICAL DIMENSIONS

Please refer to structural narrative for more information on structural requirements.

79 Room Data Sheets | FREELON BOND Infrastructure Only 0 Other Amenities Deionized Water Vacuum Yes Speakers OH Gr. 2, 130 SF/HD FIRE ALARM Smoke Detection Yes Wet Sprinkler Special Waste Dry Sprinkler Pre-Action Sprinkler No FIRE PROTECTION No Considerations for Water 0 No Floor Drains Floor Sink Grey/Blackwater Piping 0 No No No Protected Hot/Cold No No Recycled Water Supply (treated) 0 No Public Address Audio Compressed Air Audio Visual Requirements No Hot/Cold Water Task Light Yes No 0 Plant/Clean Steam Yes Acoustic Sensitivity 0 Vibration Sensitivity Special Equipment/Artifact Sensitivity PLUMBING Target Illuminance (IES 9th Edition) Daylight Sensor 10 FC Exhibit Light No Power Density (AHSRAE 2004) 0.8 W/ft² Temperature Deviations (+/-) Yes No Process Water UPS Switched Receptacles Dimming To Be Considered Humidity 0 No Other Humidity Deviation (+/-) 10 min. 0 No Outside Air Single/Multi-Level Switching 0 Emergency/Standby Power 15 CFM/person 65/ Carbon/95 Single Occupancy Sensor Special Exhaust Sub-metering & Feedback Displays Filtration (Pre/Final/Other) Voice/Data DATA/TELECOMMUNICATIONS 0 0 SECURITY 0 12.0 kPa/26.7 kN Floor Loading/Point Loads DAYLIGHTING 0 0 Shading Considerations Top/Side Lighting None No STRUCTURAL 0 0 Refer to information indicated in Volume IV, Section E 0 0 Technical Comment: Temporary Storage for Pending Acquisition Assignable Square Feet (ASF) OFEO Space Dimensions 0 Organizational Unit Other Interior Glazing 0 0 0 0 No Off GPSing/Organic/SealedCeiling CRITICAL FINISHES 0 Positive
ELECTRICAL ARCHITECTURAL
room data sheet is not comprehensive in nature. Information regarding specific room features may not have been available and was intentionally left blank. Zone Room ID C2.8 Room Name 0 Functional Description Assumed to be provided at the off-site collections facility. Non Public Collection Space 0 Number of Occupants 0 Visual Privacy (full, partial, open) Zone Designation Zone C Room Height 0 LEED NC Regurlarly Occupied Space 0 Base ACOUSTICS Equipment Hardware/STC Rating 0 NRC0 0 Plug Loads Air Change/ HR Walls HVAC ENGINEERING
Temperature Lighting 45%RH yr. rd. ±2ºF 110v, 20a, 1ph Yes 8% RH yr. rd. Power No No Off GPSing/Organic/Sealed Pressure (+/-) 70ºF Floor Operable Windows Separation/STC FURNITURE/EQUIPMENT Moveable 0 Fixed RT60 & Shaping 0 Above Water Table
This
CRITERIA
0
Adjacencies
Floor Level 0 Room Length,
Shape Open
Accessibility Requirement:
Width,
vs. Private
NOTE: Space Located Offsite

This room data sheet is not comprehensive in nature. Information regarding specific room features may not have been available and was intentionally left blank.

Above Water Table

Accessibility Requirement:

Adjacencies

SUSTAINABILITY FEATURES

Floor Level 10' W x 12'H Door Opening Room Length, Width, Shape Open vs. Private

& Shaping

Compliance with ADA/ABAAG (2004) citations is required for accessibility. SI also requires compliance with SI Accessibility Guidelines and the IBC. Comparisons should be made and the more stringent requirement followed for design purposes. An accessible route including a minimum clear width of 36" (except at doors, whic must be at least 32" clear) is required. Refer to ADA/ABAAG (2004) for specifications regarding clear floor spaces at desks, files and equipment for individuals using wheelchairs. See Accessibility Narrative for additional information.

Clean Install Room, Curatorial and Collection Management

Controls

Space for touch up

exhibit case finishing, minor painting and repairs, with work counters and tables, storage for supplies and materials.

CRITICAL DIMENSIONS

Absorptive finish on the ceiling with an NRC of 0.70 or higher

ENGINEERING CRITERIA

Recommend hand sink under Plumbing. Please refer to structural narrative for more information on structural requirements.

to information indicated in Volume IV, Section E

Smithsonian Institution National Museum of African American History and Culture 80 Infrastructure Only 0 Other Amenities Deionized Water Vacuum Yes Speakers OH Gr. 2, 130 SF/HD FIRE ALARM Smoke Detection Yes Wet Sprinkler Special Waste Dry Sprinkler Pre-Action Sprinkler No FIRE PROTECTION No Considerations for Water 0 No Floor Drains Floor Sink Grey/Blackwater Piping 0 No No No Protected Hot/Cold No No Recycled Water Supply (treated) 0 No Public Address Audio Compressed Air Audio Visual Requirements Yes Hot/Cold Water Task Light Yes No 0 Plant/Clean Steam Yes Acoustic Sensitivity NC 35-40 Vibration Sensitivity Special Equipment/Artifact Sensitivity PLUMBING Target Illuminance (IES 9th Edition) Daylight Sensor 5-50 FC Exhibit Light To Be Considered Power Density (AHSRAE 2004) 1.9 W/ft² Temperature Deviations (+/-) Yes No Process Water UPS Switched Receptacles Dimming No Humidity 0 No Other Humidity Deviation (+/-) 10 min. 0 No Outside Air Single/Multi-Level Switching 0 Emergency/Standby Power 15 CFM/person 65/ Carbon/95 Multi Occupancy Sensor Special Exhaust Sub-metering & Feedback Displays Filtration (Pre/Final/Other) Voice/Data DATA/TELECOMMUNICATIONS Yes 0 SECURITY 0 7.5 kPa/26.7 kN Floor Loading/Point Loads DAYLIGHTING 0 0 Shading Considerations Top/Side Lighting None No STRUCTURAL 0 0 Refer
Full 0 Technical Comment: Preparator's Workshop
Square Feet
OFEO Space Dimensions 0 Organizational Unit Other Interior Glazing 0 Solid core wood or insulated metal with neoprene strip seals max 1/4" undercut Yes Yes No Off GPSing/Organic/SealedCeiling CRITICAL FINISHES 0 Positive
Assignable
(ASF)
ELECTRICAL
ARCHITECTURAL
Zone Room ID C2.9 Room Name 0
Environmental
Non Public Collection Space 400 Number of Occupants TBD Visual Privacy (full, partial, open) Zone Designation Zone C Room Height Min 12'-6"
Space 0 Base ACOUSTICS Equipment Hardware/STC Rating 0 NRC
STC 50 0 Plug Loads Air Change/ HR Walls HVAC
Functional Description
required:
work,
LEED NC Regurlarly Occupied
Temperature Lighting 45%RH yr. rd. ±2ºF 110v,
Yes 8% RH yr. rd. Power No No
Pressure (+/-) 70ºF Floor Operable
20a, 1ph
Off GPSing/Organic/Sealed
Windows
Moveable Yes Fixed RT60
0
Separation/STC FURNITURE/EQUIPMENT

Assignable Square Feet (ASF) OFEO Space

Accessibility Requirement:

Adjacencies

Technical Comment: Registration Workroom

This room data sheet is not comprehensive in nature. Information regarding specific room features may not have been available and was intentionally left blank.

SUSTAINABILITY FEATURES

Compliance with ADA/ABAAG (2004) citations is required for accessibility. SI also requires compliance with SI Accessibility Guidelines and the IBC. Comparisons should be made and the more stringent requirement followed for design purposes. An accessible route including a minimum clear width of 36" (except at doors, whic must be at least 32" clear) is required. Refer to ADA/ABAAG (2004) for specifications regarding clear floor spaces at desks, files and equipment for individuals using wheelchairs. See Accessibility Narrative for additional information.

Photography Conservation Lab

Functional Description This workroom will be large enough to do

CRITICAL DIMENSIONS

Length, Width, Shape Open vs. Private

& Shaping

ENGINEERING CRITERIA

Recommend hand sink under Plumbing. Please refer to structural narrative for more information on structural requirements. ELECTRICAL ARCHITECTURAL

Absorptive finish on the ceiling with an NRC of 0.70 or higher

81 Room Data Sheets | FREELON BOND Infrastructure Only 0 Other Amenities Deionized Water Vacuum Yes Speakers OH Gr. 2, 130 SF/HD FIRE ALARM Smoke Detection Yes Wet Sprinkler Special Waste Dry Sprinkler Pre-Action Sprinkler No FIRE PROTECTION No Considerations for Water 0 No Floor Drains Floor Sink Grey/Blackwater Piping 0 No No No Protected Hot/Cold No No Recycled Water Supply (treated) 0 No Public Address Audio Compressed Air Audio Visual Requirements Yes Hot/Cold Water Task Light Yes No 0 Plant/Clean Steam Yes Acoustic Sensitivity NC 35-40 Vibration Sensitivity Special Equipment/Artifact Sensitivity PLUMBING Target Illuminance (IES 9th Edition) Daylight Sensor 30-50 FC Exhibit Light To Be Considered Power Density (AHSRAE 2004) 1.1 W/ft² Temperature Deviations (+/-) Yes No Process Water UPS Switched
Dimming To Be Considered Humidity 0 No Other Humidity Deviation (+/-) 10 min. 0 No Outside Air Single/Multi-Level Switching 0 Emergency/Standby Power 15 CFM/person 65/ Carbon/95 Single Occupancy Sensor Special Exhaust Sub-metering
Filtration (Pre/Final/Other) Voice/Data DATA/TELECOMMUNICATIONS Yes 0 SECURITY 0 5.0 kPa/8.9 kN Floor Loading/Point Loads DAYLIGHTING 0 0 Shading Considerations Top/Side Lighting None No STRUCTURAL 0 0 Refer
information
Volume IV,
0 This
collection.
registrar
these
part
environmentally controlled area.
Receptacles
& Feedback Displays
to
indicated in
Section E
workroom will be large enough to do condition examination and registration of artifacts to be accessioned to the
It will have a landscape office from where the
will lead
activities. It is also
of the
Dimensions 0 Organizational Unit Other Interior Glazing 0 Solid core wood or insulated metal with neoprene seals max 1/4" undercut Yes Yes No Off GPSing/Organic/SealedCeiling CRITICAL
0 Positive
FINISHES
Zone Room ID C2.10 Room Name 0
examination
collection. It will
registrar will
these activities. It is also part of the environmentally controlled area. Non Public Collection Space 500 Number of Occupants TBD Visual Privacy (full, partial, open) Zone
Zone
Room Height 0 LEED NC Regurlarly Occupied Space 0 Base ACOUSTICS Equipment Hardware/STC Rating 0 NRC
STC 50 0 Plug Loads Air Change/ HR Walls HVAC
condition
and registration of artifacts to be accessioned to the
have a landscape office from where the
lead
Designation
C
Temperature Lighting 45%RH yr. rd. ±2ºF 110v,
Yes 8% RH yr. rd. Power No No
Pressure (+/-) 70ºF Floor Operable Windows
20a, 1ph
Off GPSing/Organic/Sealed
Moveable Yes Fixed RT60
0 TBD
Separation/STC FURNITURE/EQUIPMENT
Floor
0
Level
Room

This room data sheet is not comprehensive in nature. Information regarding specific room features may not have been available and was intentionally left blank.

Water Table

Accessibility Requirement:

Adjacencies

Compliance with ADA/ABAAG (2004) citations is required for accessibility. SI also requires compliance with SI Accessibility Guidelines and the IBC. Comparisons should be made and the more stringent requirement followed for design purposes. An accessible route including a minimum clear width of 36" (except at doors, whic must be at least 32" clear) is required. Refer to ADA/ABAAG (2004) for specifications regarding clear floor spaces at desks, files and equipment for individuals using wheelchairs. See Accessibility Narrative for additional information.

Photography Conservation Lab, Copy Area

Description This space is adjacent to the registration workroom because it contains all of the artifact records.

SUSTAINABILITY FEATURES

CRITICAL DIMENSIONS

Length, Width, Shape Open vs. Private

finish on the ceiling with an NRC of 0.70 or

Please refer to structural narrative for more information on structural requirements.

Smithsonian Institution National Museum of African American History and Culture 82 Infrastructure Only 0 Other Amenities Deionized Water Vacuum Yes Speakers 0 FIRE ALARM Smoke Detection Yes Wet Sprinkler Special Waste Dry Sprinkler Pre-Action Sprinkler 0 FIRE PROTECTION No Considerations for Water 0 No Floor Drains Floor Sink Grey/Blackwater Piping 0 No No No Protected Hot/Cold No No Recycled Water Supply (treated) 0 No Public Address Audio Compressed Air Audio Visual Requirements No Hot/Cold Water Task Light Yes No 0 Plant/Clean Steam Yes Acoustic Sensitivity NC 35-40 Vibration Sensitivity Special Equipment/Artifact Sensitivity PLUMBING Target Illuminance (IES 9th Edition) Daylight Sensor 30 FC Exhibit Light To Be Considered Power Density (AHSRAE 2004) 1.1 W/ft² Temperature Deviations (+/-) Yes No Process Water UPS Switched Receptacles Dimming To Be Considered Humidity 0 No Other Humidity Deviation (+/-) 10 min. 0 No Outside Air Single/Multi-Level Switching 0 Emergency/Standby Power 15 CFM/person 65/ Carbon/95 Single Occupancy Sensor Special Exhaust Sub-metering & Feedback Displays Filtration (Pre/Final/Other) Voice/Data DATA/TELECOMMUNICATIONS Yes 0 SECURITY 0 5.0 kPa/8.9 kN Floor Loading/Point Loads DAYLIGHTING 0 0 Shading Considerations Top/Side Lighting None No STRUCTURAL 0 0 Refer to information indicated in Volume IV, Section E Partial 0 Technical Comment: Documentation Center Assignable Square Feet (ASF) OFEO Space Dimensions 0 Organizational Unit Other Interior Glazing 0 Solid core wood or insulated metal with neoprane strip seals max 1/4" undercut 0 0 No Off GPSing/Organic/SealedCeiling CRITICAL FINISHES 0 Positive
ELECTRICAL ARCHITECTURAL
Zone Room ID C2.11 Room Name 0
Non Public Collection Space 300 Number of Occupants TBD Visual Privacy (full, partial, open) Zone Designation Zone C Room Height 0 LEED NC Regurlarly Occupied Space 0 Base ACOUSTICS Equipment Hardware/STC Rating 0 NRC
STC 45 0 Plug Loads Air Change/ HR Walls HVAC ENGINEERING
Temperature Lighting 45%RH yr. rd. ±2ºF 110v,
1ph Yes 8% RH yr. rd. Power No No Off GPSing/Organic/Sealed Pressure (+/-) 70ºF Floor Operable Windows
FURNITURE/EQUIPMENT Moveable - Fixed RT60 & Shaping 0
Functional
Absorptive
higher
CRITERIA
20a,
Separation/STC
Above
0 Room
Floor Level

Accessibility Requirement:

Adjacencies

SUSTAINABILITY FEATURES

Water Table

Compliance with ADA/ABAAG (2004) citations is required for accessibility. SI also requires compliance with SI Accessibility Guidelines and the IBC. Comparisons should be made and the more stringent requirement followed for design purposes. An accessible route including a minimum clear width of 36" (except at doors, whic must be at least 32" clear) is required. Refer to ADA/ABAAG (2004) for specifications regarding clear floor spaces at desks, files and equipment for individuals using wheelchairs. See Accessibility Narrative for additional information.

Enclosed Collections Loading Dock, Collections Shipping/Receiving, Loading Dock Security Booths and Washroom, Receiving /Courier Office, Temporary Storage, Crating/Uncrating and Packing Studio

CRITICAL DIMENSIONS

Length, Width, Shape Open vs. Private

or

83 Room Data Sheets | FREELON BOND Infrastructure Only 0 Other Amenities Deionized Water Vacuum Yes Speakers OH Gr. 2, 130 SF/HD FIRE ALARM Smoke Detection Yes Wet Sprinkler Special Waste Dry Sprinkler Pre-Action Sprinkler No FIRE PROTECTION No Considerations for Water 0 No Floor Drains Floor Sink Grey/Blackwater Piping 0 No No No Protected Hot/Cold No No Recycled Water Supply (treated) 0 No Public Address Audio Compressed Air Audio Visual Requirements No Hot/Cold Water Task Light No No 0 Plant/Clean Steam Yes Acoustic Sensitivity NC 35 Vibration Sensitivity Special Equipment/Artifact Sensitivity PLUMBING Target Illuminance (IES 9th Edition) Daylight Sensor 30 FC Exhibit Light No Power Density (AHSRAE 2004) 1.1 W/ft² Temperature Deviations (+/-) Yes No Process Water UPS Switched Receptacles Dimming To Be Considered Humidity 0 No Other Humidity Deviation (+/-) 10 min. 0 No Outside Air Single/Multi-Level Switching 0 Emergency/Standby Power 15 CFM/person 65/ Carbon/95 Single Occupancy Sensor Special Exhaust Sub-metering & Feedback Displays Filtration (Pre/Final/Other) Voice/Data DATA/TELECOMMUNICATIONS Yes 0 SECURITY 0 5.0 kPa/8.9 kN Floor Loading/Point Loads DAYLIGHTING 0 0 Shading Considerations Top/Side Lighting None No STRUCTURAL 0 0 Refer to information indicated in Volume IV, Section E Full 0 Technical Comment: Receiving/ Courier Office Assignable Square Feet (ASF) OFEO Space Dimensions 0 Organizational Unit Other Interior Glazing 0 Solid core wood or insulated metal with neoprene seals max 1/4" undercut Yes Yes No Off GPSing/Organic/SealedCeiling CRITICAL FINISHES 0 Positive
ELECTRICAL ARCHITECTURAL This
left blank. Zone Room ID C2.12 Room Name 0 Functional Description 0 Non Public Collection Space 80 Number of Occupants 1 Visual Privacy (full, partial, open) Zone Designation Zone C Room Height 0 LEED NC Regurlarly Occupied Space 0 Base ACOUSTICS Equipment Hardware/STC Rating 0 NRC Absorptive finish
ceiling
0.70
higher STC 45 0 Plug Loads Air Change/ HR Walls HVAC ENGINEERING CRITERIA Temperature Lighting 45%RH yr. rd. ±2ºF 110v, 20a, 1ph Yes 8% RH yr. rd. Power No No Off GPSing/Organic/Sealed Pressure (+/-) 70ºF Floor Operable Windows Separation/STC FURNITURE/EQUIPMENT Moveable Yes Fixed RT60 & Shaping 0 Above
Please refer to structural narrative for more information on structural requirements.
room data sheet is not comprehensive in nature. Information regarding specific room features may not have been available and was intentionally
on the
with an NRC of
Floor Level 0 Room

This room data sheet is not comprehensive in nature. Information regarding specific room features may not have been available and was intentionally left blank.

Accessibility Requirement:

Adjacencies

SUSTAINABILITY FEATURES

Above Water Table, Multiple Compliance with ADA/ABAAG (2004) citations is required for accessibility. SI also requires compliance with SI Accessibility Guidelines and the IBC. Comparisons should be made and the more stringent requirement followed for design purposes. An accessible route including a minimum clear width of 36" (except at doors, whic must be at least 32" clear) is required. Refer to ADA/ABAAG (2004) for specifications regarding clear floor spaces at desks, files and equipment for individuals using wheelchairs. See Accessibility Narrative for additional information.

Changing Exhibition, Exhibit Staging

CRITICAL DIMENSIONS

Recommend sump pump under Plumbing. Please refer to structural narrative for more information on structural requirements.

x

x

Smithsonian Institution National Museum of African American History and Culture 84 Infrastructure Only 0 Other Amenities Deionized Water Vacuum Yes Speakers Yes (in shaft) FIRE ALARM Smoke Detection Yes (in shaft) Wet Sprinkler Special Waste Dry Sprinkler Pre-Action Sprinkler No FIRE PROTECTION No Considerations for Water 0 No Floor Drains Floor Sink Grey/Blackwater Piping 0 No No No Protected Hot/Cold No No Recycled Water Supply (treated) 0 No Public Address Audio Compressed Air Audio Visual Requirements No Hot/Cold Water Task Light No No 0 Plant/Clean Steam 0 Acoustic Sensitivity 0 Vibration Sensitivity Special Equipment/Artifact Sensitivity PLUMBING Target Illuminance (IES 9th Edition) Daylight Sensor 5 FC Exhibit Light No Power Density (AHSRAE 2004) 0.5 W/ft² Temperature Deviations (+/-) 0 No Process Water UPS Switched Receptacles Dimming No Humidity 0 Yes Other Humidity Deviation (+/-) 0 0 No Outside Air Single/Multi-Level Switching 0 Emergency/Standby Power 0 0 Single Occupancy Sensor Special Exhaust Sub-metering & Feedback Displays Filtration (Pre/Final/Other) Voice/Data DATA/TELECOMMUNICATIONS Yes 0 SECURITY 0 12.0 kPa/26.7 kN Floor Loading/Point Loads DAYLIGHTING 0 0 Shading Considerations Top/Side Lighting 0 No STRUCTURAL 0 0 Refer to information indicated in Volume IV, Section E Full Included in Grossing Factor. Technical Comment: Collections Freight Elevator Assignable Square Feet (ASF) OFEO Space Dimensions 0 Organizational Unit Other Interior Glazing 0 0 No No No Off GPSing/Organic/SealedCeiling CRITICAL FINISHES 0 0
ELECTRICAL ARCHITECTURAL
Zone Room ID C2.13 Room Name 0 Functional
Non Public Collection Space 0 Number of Occupants NA Visual Privacy (full, partial, open) Zone Designation Zone C Room Height Min 12'-6" LEED NC Regurlarly Occupied Space 0 Base ACOUSTICS Equipment Hardware/STC Rating 0 NRC0 0 Plug Loads Air Change/ HR Walls HVAC ENGINEERING CRITERIA Temperature Lighting 0 0 110v, 20a, 1ph No 0 Power No No Off GPSing/Organic/Sealed Pressure (+/-) 0 Floor Operable Windows Separation/STC FURNITURE/EQUIPMENT Moveable No Fixed RT60 & Shaping 0
Description Dedicated Collections Freight Elevator in Grossing.
Floor Level
10' W
12'H Door Opening, 10
15 CAB Room Length, Width, Shape Open vs. Private

Accessibility Requirement:

Adjacencies

SUSTAINABILITY FEATURES

Open vs. Private

Floor Level 10' W x 12'H Door Opening Room Length, Width, Shape

Compliance with ADA/ABAAG (2004) citations is required for accessibility. SI also requires compliance with SI Accessibility Guidelines and the IBC. Comparisons should be made and the more stringent requirement followed for design purposes. See specifically ADA/ABAAG (2004) 407 Elevators. An accessible route including a minimum clear width of 36" (except through doors, which must be at least 32" clear) is required. Refer to ADA/ABAAG (2004) for specifications regarding clear floor spaces at desks, files and equipment for individuals using wheelchairs. See Accessibility Narrative for additional information. Changing Exhibition, Collections Freight Elevator

CRITICAL DIMENSIONS

85 Room Data Sheets | FREELON BOND Infrastructure Only 0 Other Amenities Deionized Water Vacuum Yes Speakers OH Gr. 2, 130 SF/HD FIRE ALARM Smoke Detection Yes Wet Sprinkler Special Waste Dry Sprinkler Pre-Action Sprinkler No FIRE PROTECTION No Considerations for Water 0 No Floor Drains Floor Sink Grey/Blackwater Piping 0 No No No Protected Hot/Cold No No Recycled Water Supply (treated) 0 No Public Address Audio Compressed Air Audio Visual Requirements No Hot/Cold Water Task Light To Be Considered No 0 Plant/Clean Steam Yes Acoustic Sensitivity NC 40 Vibration Sensitivity Special Equipment/Artifact Sensitivity PLUMBING Target Illuminance (IES 9th Edition) Daylight Sensor 10 FC Exhibit Light No Power Density (AHSRAE 2004) 1.7 W/ft² Temperature Deviations (+/-) Yes No Process Water UPS Switched Receptacles Dimming To Be Considered Humidity 0 Yes Other Humidity Deviation (+/-) 10 min. 0 No Outside Air Single/Multi-Level Switching 0 Emergency/Standby Power 15 CFM/person 65/ Carbon/95 Single Occupancy Sensor Special Exhaust Sub-metering & Feedback Displays Filtration (Pre/Final/Other) Voice/Data DATA/TELECOMMUNICATIONS Yes 0 SECURITY 0 12.0 kPa/26.7 kN Floor Loading/Point Loads DAYLIGHTING 0 0 Shading Considerations Top/Side Lighting 0 0 STRUCTURAL 0 0 Refer to information indicated in Volume IV, Section E Full 0 Technical Comment: Exhibit Staging Assignable Square Feet (ASF) OFEO Space Dimensions 0 Organizational Unit Other Interior Glazing 0 Solid core wood or insulated metal with neoprene strips max 1/4" undercut 0 0 No Off GPSing/Organic/SealedCeiling CRITICAL FINISHES 0 Positive
for
information on structural requirements. ELECTRICAL ARCHITECTURAL This room
nature. Information regarding specific room features may not have been available and was intentionally left blank. Zone Room ID C2.14 Room Name 0 Functional Description This area is used to layout and prepare the exhibit for installation in the galleries. This permits one exhibtion to be prepared for installation while another is being taken down and readied for transport. It permits the gallery to remain open while this prep work is going on. Non Public Collection Space 1,000 Number of Occupants NA Visual Privacy (full, partial, open) Zone
Zone C Room Height Min 12'-6" LEED NC Regurlarly Occupied Space 0 Base ACOUSTICS Equipment Hardware/STC Rating 0 NRC
STC 55 0 Plug Loads Air Change/ HR Walls HVAC ENGINEERING
Temperature Lighting 45%RH yr. rd. ±2ºF 110v, 20a, 1ph No 8% RH yr. rd. Power No No Off GPSing/Organic/Sealed Pressure (+/-) 70ºF Floor Operable Windows
FURNITURE/EQUIPMENT Moveable - Fixed RT60
0
Please refer to structural narrative
more
data sheet is not comprehensive in
Designation
Absorptive finish on the ceiling with an NRC of 0.70 or higher
CRITERIA
Separation/STC
& Shaping
Above Water Table

This room data sheet is not comprehensive in nature. Information regarding specific room features may not have been available and was intentionally left blank.

Accessibility Requirement:

Adjacencies

with ADA/ABAAG (2004) citations is required for accessibility. SI also requires compliance with SI Accessibility Guidelines and the IBC. Comparisons should be made and the more stringent requirement followed for design purposes. An accessible route including a minimum clear width of 36" (except through doors, which must be at least 32" clear) is required. Refer to ADA/ABAAG (2004) for specifications regarding clear floor spaces at desks, files and equipment for individuals using wheelchairs.See Accessibility Narrative for additional information.

SUSTAINABILITY FEATURES

vs. Private

finish on the

Please refer to structural narrative for more information on structural requirements.

CRITICAL DIMENSIONS

Length, Width, Shape

Smithsonian Institution National Museum of African American History and Culture 86 Infrastructure Only 0 Other Amenities Deionized Water Vacuum Yes Speakers OH Gr. 2, 130 SF/HD FIRE ALARM Smoke Detection Yes Wet Sprinkler Special Waste Dry Sprinkler Pre-Action Sprinkler No FIRE PROTECTION No Considerations for Water 0 No Floor Drains Floor Sink Grey/Blackwater Piping 0 No No No Protected Hot/Cold No No Recycled Water Supply (treated) 0 No Public Address Audio Compressed Air Audio Visual Requirements No Hot/Cold Water Task Light To Be Considered No 0 Plant/Clean Steam Yes Acoustic Sensitivity NC 35-40 Vibration Sensitivity Special Equipment/Artifact Sensitivity PLUMBING Target Illuminance (IES 9th Edition) Daylight Sensor 10 FC Exhibit Light To Be Considered Power Density (AHSRAE 2004) 1.1 W/ft² Temperature Deviations (+/-) Yes No Process Water UPS Switched Receptacles Dimming To Be Considered Humidity 0 Yes Other Humidity Deviation (+/-) 10 min. 0 No Outside Air Single/Multi-Level Switching 0 Emergency/Standby Power 15 CFM/person 65/ Carbon/95 Single Occupancy Sensor Special Exhaust Sub-metering & Feedback Displays Filtration (Pre/Final/Other) Voice/Data DATA/TELECOMMUNICATIONS Yes 0 SECURITY 0 7.5 kPa/17.8 kN Floor Loading/Point Loads DAYLIGHTING 0 0 Shading Considerations Top/Side Lighting None No STRUCTURAL 0 0 Refer to information indicated in Volume IV, Section E Partial 0 Technical Comment: Copy Area Assignable Square Feet (ASF) OFEO Space Dimensions 0 Organizational Unit Other Interior Glazing 0 Solid core wood or insulated metal with neoprene seals max 1/4" undercut 0 0 No Off GPSing/Organic/SealedCeiling CRITICAL FINISHES 0 Positive
ELECTRICAL ARCHITECTURAL
Zone Room ID C2.15 Room Name 0 Functional
Used for the copying and reproduction of photoraphs
the archive collection Non Public Collection Space 100 Number of Occupants TBD Visual Privacy (full, partial, open) Zone Designation Zone C Room Height 0 LEED NC Regurlarly Occupied Space 0 Base ACOUSTICS Equipment Hardware/STC Rating 0 NRC Absorptive
0.70
higher STC 50 0 Plug Loads Air Change/ HR Walls HVAC ENGINEERING
Temperature Lighting 45%RH yr. rd. ±2ºF 110v, 20a, 1ph No 8% RH yr. rd. Power No No Off GPSing/Organic/Sealed Pressure (+/-) 70ºF Floor Operable Windows
FURNITURE/EQUIPMENT Moveable - Fixed RT60 & Shaping 0 0 Compliance
Description
from
ceiling with an NRC of
or
CRITERIA
Separation/STC
Documentation Center
Floor Level 0 Room
Open

This room data sheet is not comprehensive in nature. Information regarding specific room features may not have been available and was intentionally left blank.

Water

Accessibility Requirement:

Adjacencies

Compliance with ADA/ABAAG (2004) citations is required for accessibility. SI also requires compliance with SI Accessibility Guidelines and the IBC. Comparisons should be made and the more stringent requirement followed for design purposes. An accessible route including a minimum clear width of 36" (except through doors, which must be at least 32" clear) is required. Refer to ADA/ABAAG (2004) for specifications regarding clear floor spaces at desks, files and equipment for individuals using wheelchairs.See Accessibility Narrative for additional information.

Description This

SUSTAINABILITY FEATURES

vs. Private CRITICAL DIMENSIONS

Length, Width, Shape

Separation/STC

finish on the

CRITERIA

Please refer to structural narrative for more information on structural requirements.

or

87 Room Data Sheets | FREELON BOND Infrastructure Only 0 Other Amenities Deionized Water Vacuum Yes Speakers OH Gr. 2, 130 SF/HD FIRE ALARM Smoke Detection Yes Wet Sprinkler Special Waste Dry Sprinkler Pre-Action Sprinkler No FIRE PROTECTION No Considerations for Water 0 No Floor Drains Floor Sink Grey/Blackwater Piping 0 No No No Protected Hot/Cold No No Recycled Water Supply (treated) 0 No Public Address Audio Compressed Air Audio Visual Requirements No Hot/Cold Water Task Light Yes No 0 Plant/Clean Steam Yes Acoustic Sensitivity NC 35-40 Vibration Sensitivity Special Equipment/Artifact Sensitivity PLUMBING Target Illuminance (IES 9th Edition) Daylight Sensor 30-50 FC Exhibit Light No Power Density (AHSRAE 2004) 1.7 W/ft² Temperature Deviations (+/-) Yes To Be Considered Process Water UPS Switched Receptacles Dimming No Humidity 0 Yes Other Humidity Deviation (+/-) 10 min. 0 No Outside Air Single/Multi-Level Switching 0 Emergency/Standby Power 15 CFM/person 65/ Carbon/95 Multi Occupancy Sensor Special Exhaust Sub-metering & Feedback Displays Filtration (Pre/Final/Other) Voice/Data DATA/TELECOMMUNICATIONS Yes 0 SECURITY 0 5.0 kPa/8.9 kN Floor Loading/Point Loads DAYLIGHTING 0 0 Shading Considerations Top/Side Lighting None No STRUCTURAL 0 0 Refer
Partial 0 Technical Comment: Digitization Lab Assignable Square Feet (ASF) OFEO Space Dimensions 0 Organizational Unit Other Interior Glazing 0 Solid core wood or insulated metal with neoprane strip seals max 1/4" undercut 0 0 No Off GPSing/Organic/SealedCeiling CRITICAL FINISHES 0 Positive
to information indicated in Volume IV, Section E
ELECTRICAL ARCHITECTURAL
Zone Room ID C2.16 Room Name 0 Functional
space
digitization
digital
work. Non Public Collection Space 200 Number of Occupants TBD Visual Privacy (full, partial, open) Zone Designation Zone C Room Height 0 LEED NC Regurlarly Occupied Space 0 Base ACOUSTICS Equipment Hardware/STC Rating 0 NRC Absorptive
ceiling
0.70
higher STC 50 0 Plug Loads Air Change/ HR Walls HVAC ENGINEERING
Temperature Lighting 45%RH yr. rd. ±2ºF 110v,
1ph No 8% RH yr. rd. Power No No Off GPSing/Organic/Sealed Pressure (+/-) 70ºF Floor Operable Windows
FURNITURE/EQUIPMENT Moveable - Fixed RT60
0 Above
is for the
of archived photos and all other
photography
with an NRC of
20a,
& Shaping
Table
Photo Studio
Floor Level 0 Room
Open

This room data sheet is not comprehensive in nature. Information regarding specific room features may not have been available and was intentionally left blank.

Accessibility Requirement:

Adjacencies

SUSTAINABILITY FEATURES

Compliance with ADA/ABAAG (2004) citations is required for accessibility. SI also requires compliance with SI Accessibility Guidelines and the IBC. Comparisons should be made and the more stringent requirement followed for design purposes. An accessible route including a minimum clear width of 36" (except through doors, which must be at least 32" clear) is required. Refer to ADA/ABAAG (2004) for specifications regarding clear floor spaces at desks, files and equipment for individuals using wheelchairs.See Accessibility Narrative for additional information.

Center, Curatorial and Collection Spaces

Please refer to structural narrative for more information on structural requirements.

CRITICAL DIMENSIONS

Smithsonian Institution National Museum of African American History and Culture 88 Infrastructure Only 0 Other Amenities Deionized Water Vacuum Yes Speakers OH Gr. 2, 130 SF/HD FIRE ALARM Smoke Detection Yes Wet Sprinkler Special Waste Dry Sprinkler Pre-Action Sprinkler No FIRE PROTECTION No Considerations for Water 0 No Floor Drains Floor Sink Grey/Blackwater Piping 0 No No No Protected Hot/Cold No No Recycled Water Supply (treated) 0 No Public Address Audio Compressed Air Audio Visual Requirements No Hot/Cold Water Task Light To Be Considered No 0 Plant/Clean Steam Yes Acoustic Sensitivity NC 40 Vibration Sensitivity Special Equipment/Artifact Sensitivity PLUMBING Target Illuminance (IES 9th Edition) Daylight Sensor 30 FC Exhibit Light No Power Density (AHSRAE 2004) 1.1 W/ft² Temperature Deviations (+/-) Yes No Process Water UPS Switched Receptacles Dimming To Be Considered Humidity 0 Yes Other Humidity Deviation (+/-) 10 min. 0 No Outside Air Single/Multi-Level Switching 0 Emergency/Standby Power 15 CFM/person 65/ Carbon/95 Single Occupancy Sensor Special Exhaust Sub-metering & Feedback Displays Filtration (Pre/Final/Other) Voice/Data DATA/TELECOMMUNICATIONS Yes 0 SECURITY 0 12.0 kPa/26.7 kN Floor Loading/Point Loads DAYLIGHTING 0 0 Shading Considerations Top/Side Lighting None No STRUCTURAL 0 0 Refer to information indicated in Volume IV, Section E Partial 0 Technical Comment: Photo Archives Assignable Square Feet (ASF) OFEO Space Dimensions 0 Organizational Unit Other Interior Glazing 0 0 0 0 No Off GPSing/Organic/SealedCeiling CRITICAL FINISHES 0 Positive
ELECTRICAL ARCHITECTURAL
Zone Room ID C2.17 Room Name 0
This
Non Public Collection Space 300 Number of Occupants TBD Visual Privacy (full, partial, open) Zone Designation Zone C Room Height 0 LEED NC Regurlarly Occupied Space 0 Base ACOUSTICS Equipment Hardware/STC Rating 0 NRCSTC 45 0 Plug Loads Air Change/ HR Walls HVAC ENGINEERING
Temperature Lighting 45%RH yr. rd. ±2ºF 110v, 20a, 1ph No 8% RH yr. rd. Power No No Off GPSing/Organic/Sealed Pressure (+/-) 70ºF Floor Operable Windows Separation/STC FURNITURE/EQUIPMENT Moveable 0 Fixed RT60
0 Above Water Table
Functional Description
room will hold the archives of photographs that the museum will begin to develop in conjunction with the Resource Center.
CRITERIA
& Shaping
Resource
Floor Level 0 Room Length,
Open
Width, Shape
vs. Private

This room data sheet is not comprehensive in nature. Information regarding specific room features may not have been available and was intentionally left blank.

Accessibility Requirement:

Adjacencies

Compliance with ADA/ABAAG (2004) citations is required for accessibility. SI also requires compliance with SI Accessibility Guidelines and the IBC. Comparisons should be made and the more stringent requirement followed for design purposes. An accessible route including a minimum clear width of 36" (except through doors, which must be at least 32" clear) is required. Refer to ADA/ABAAG (2004) for specifications regarding clear floor spaces at desks, files and equipment for individuals using wheelchairs.See Accessibility Narrative for additional information.

Digitization Lab

Description For publication quality

SUSTAINABILITY FEATURES

Open vs. Private

& Shaping

finish on the

Please refer to structural narrative for more information on structural requirements.

CRITICAL DIMENSIONS

Length, Width, Shape

89 Room Data Sheets | FREELON BOND Infrastructure Only 0 Other Amenities Deionized Water Vacuum Yes Speakers OH Gr. 2, 130 SF/HD FIRE ALARM Smoke Detection Yes Wet Sprinkler Special Waste Dry Sprinkler Pre-Action Sprinkler No FIRE PROTECTION No Considerations for Water 0 No Floor Drains Floor Sink Grey/Blackwater Piping 0 No No No Protected Hot/Cold No No Recycled Water Supply (treated) 0 No Public Address Audio Compressed Air Audio Visual Requirements No Hot/Cold Water Task Light Yes No 0 Plant/Clean Steam Yes Acoustic Sensitivity NC 35-40 Vibration Sensitivity Special Equipment/Artifact Sensitivity PLUMBING Target Illuminance (IES 9th Edition) Daylight Sensor 30-50 FC Exhibit Light No Power Density (AHSRAE 2004) 1.7 W/ft² Temperature Deviations (+/-) Yes To Be Considered Process Water UPS Switched Receptacles Dimming No Humidity 0 Yes Other Humidity Deviation (+/-) 10 min. 0 No Outside Air Single/Multi-Level Switching 0 Emergency/Standby Power 15 CFM/person 65/ Carbon/95 Multi Occupancy Sensor Special Exhaust Sub-metering & Feedback Displays Filtration (Pre/Final/Other) Voice/Data DATA/TELECOMMUNICATIONS Yes 0 SECURITY 0 5.0 kPa/8.9 kN Floor Loading/Point Loads DAYLIGHTING 0 0 Shading Considerations Top/Side Lighting None No STRUCTURAL 0 0 Refer to information
Volume IV, Section E Partial 0 Technical Comment: Photo Studio Assignable Square Feet (ASF) OFEO Space Dimensions 0 Organizational Unit Other Interior Glazing 0 Solid core wood or insulated metal with neoprane strip seals max 1/4" undercut 0 0 No Off GPSing/Organic/SealedCeiling CRITICAL FINISHES 0 Positive
indicated in
ELECTRICAL ARCHITECTURAL
Zone Room ID C2.18 Room Name 0 Functional
photo groupings of objects. Accommodate still photography or other objects, furniture, etc. Digitization for CAAMA activities. Non Public Collection Space 800 Number of Occupants TBD Visual Privacy (full, partial, open) Zone Designation Zone C Room Height 0 LEED NC Regurlarly Occupied Space 0 Base ACOUSTICS Equipment Hardware/STC Rating 0 NRC Absorptive
ceiling
higher STC 50 0 Plug Loads Air Change/ HR Walls HVAC ENGINEERING CRITERIA Temperature Lighting 45%RH yr. rd. ±2ºF 110v, 20a, 1ph No 8% RH yr. rd. Power No No Off GPSing/Organic/Sealed Pressure (+/-) 70ºF Floor Operable Windows
FURNITURE/EQUIPMENT Moveable - Fixed RT60
0 TBD
with an NRC of 0.70 or
Separation/STC
0
Floor Level
Room

This room data sheet is not comprehensive in nature. Information regarding specific room features may not have been available and was intentionally left blank.

Water Table

Accessibility Requirement:

Adjacencies

SUSTAINABILITY FEATURES

vs. Private

Compliance with ADA/ABAAG (2004) citations is required for accessibility. SI also requires compliance with SI Accessibility Guidelines and the IBC. Comparisons should be made and the more stringent requirement followed for design purposes. An accessible route including a minimum clear width of 36" (except through doors, which must be at least 32" clear) is required. Refer to ADA/ABAAG (2004) for specifications regarding clear floor spaces at desks, files and equipment for individuals using wheelchairs.See Accessibility Narrative for additional information. Resource Center, Curatorial and Collection Spaces

CRITICAL DIMENSIONS

Length, Width, Shape

finish on the ceiling with an NRC of 0.70 or higher

Please refer to structural narrative for more information on structural requirements.

Smithsonian Institution National Museum of African American History and Culture 90 Infrastructure Only 0 Other Amenities Deionized Water Vacuum Yes Speakers OH Gr. 2, 130 SF/HD FIRE ALARM Smoke Detection Yes Wet Sprinkler Special Waste Dry Sprinkler Pre-Action Sprinkler No FIRE PROTECTION No Considerations for Water 0 No Floor Drains Floor Sink Grey/Blackwater Piping 0 No No No Protected Hot/Cold No No Recycled Water Supply (treated) 0 No Public Address Audio Compressed Air Audio Visual Requirements No Hot/Cold Water Task Light To Be Considered No 0 Plant/Clean Steam Yes Acoustic Sensitivity NC 35 Vibration Sensitivity Special Equipment/Artifact Sensitivity PLUMBING Target Illuminance (IES 9th Edition) Daylight Sensor 30 FC Exhibit Light No Power Density (AHSRAE 2004) 1.7 W/ft² Temperature Deviations (+/-) Yes No Process Water UPS Switched Receptacles Dimming To Be Considered Humidity 0 Yes Other Humidity Deviation (+/-) 10 min. 0 No Outside Air Single/Multi-Level Switching 0 Emergency/Standby Power 15 CFM/person 65/ Carbon/95 Single Occupancy Sensor Special Exhaust Sub-metering & Feedback Displays Filtration (Pre/Final/Other) Voice/Data DATA/TELECOMMUNICATIONS Yes 0 SECURITY 0 7.5 kPa/17.8 kN Floor Loading/Point Loads DAYLIGHTING 0 0 Shading Considerations Top/Side Lighting None No STRUCTURAL 0 0 Refer to information indicated in Volume IV, Section E 0 0 Technical Comment: Library/Archive Processing Rooms Assignable Square Feet (ASF) OFEO Space Dimensions 0 Organizational Unit Other Interior Glazing 0 Solid core wood or insulated metal with neoprene seals max 1/4" undercut 0 0 No Off GPSing/Organic/SealedCeiling CRITICAL FINISHES 0 Positive
ELECTRICAL ARCHITECTURAL
Zone Room ID C3.1 Room Name 0
Non Public Collection Space 400 Number of Occupants TBD Visual Privacy (full, partial, open) Zone Designation Zone C Room Height 0 LEED NC Regurlarly Occupied Space 0 Base ACOUSTICS Equipment Hardware/STC Rating 0 NRC
STC 45 0 Plug Loads Air Change/ HR Walls HVAC ENGINEERING
Temperature Lighting 45%RH yr. rd. ±2ºF 110v, 20a, 1ph No 8% RH yr. rd. Power No No Off GPSing/Organic/Sealed Pressure (+/-) 70ºF Floor Operable Windows
FURNITURE/EQUIPMENT Moveable - Fixed RT60
0
Functional Description Processing rooms for books and reading materials.
Absorptive
CRITERIA
Separation/STC
& Shaping
Above
0 Room
Floor Level
Open

This room data sheet is not comprehensive in nature. Information regarding specific room features may not have been available and was intentionally left blank.

Water Table

Accessibility Requirement:

Adjacencies

Description

SUSTAINABILITY FEATURES

vs. Private

Separation/STC

Compliance with ADA/ABAAG (2004) citations is required for accessibility. SI also requires compliance with SI Accessibility Guidelines and the IBC. Comparisons should be made and the more stringent requirement followed for design purposes. An accessible route including a minimum clear width of 36" (except through doors, which must be at least 32" clear) is required. Refer to ADA/ABAAG (2004) for specifications regarding clear floor spaces at desks, files and equipment for individuals using wheelchairs.See Accessibility Narrative for additional information.

Resource Center, Curatorial and Collection Spaces

stacks of books and literary material available for research,

CRITICAL DIMENSIONS

Length, Width, Shape

finish on the ceiling with an NRC of 0.70 or higher

Please refer to structural narrative for more information on structural requirements.

91 Room Data Sheets | FREELON BOND Infrastructure Only 0 Other Amenities Deionized Water Vacuum Yes Speakers 0 FIRE ALARM Smoke Detection Yes Wet Sprinkler Special Waste Dry Sprinkler Pre-Action Sprinkler 0 FIRE PROTECTION No Considerations for Water 0 No Floor Drains Floor Sink Grey/Blackwater Piping 0 No No No Protected Hot/Cold No No Recycled Water Supply (treated) 0 No Public Address Audio Compressed Air Audio Visual Requirements No Hot/Cold Water Task Light Yes No 0 Plant/Clean Steam Yes Acoustic Sensitivity NC 35 Vibration Sensitivity Special Equipment/Artifact Sensitivity PLUMBING Target Illuminance (IES 9th Edition) Daylight Sensor 30 FC Exhibit Light No Power Density (AHSRAE 2004) 1.7 W/ft² Temperature Deviations (+/-) Yes No Process Water UPS Switched Receptacles Dimming To Be Considered Humidity 0 Yes Other Humidity Deviation (+/-) 10 min. 0 No Outside Air Single/Multi-Level Switching 0 Emergency/Standby Power 15 CFM/person 65/ Carbon/95 Single Occupancy Sensor Special Exhaust Sub-metering & Feedback Displays Filtration (Pre/Final/Other) Voice/Data DATA/TELECOMMUNICATIONS Yes 0 SECURITY 0 12.0 kPa/26.7 kN Floor Loading/Point Loads DAYLIGHTING 0 0 Shading Considerations Top/Side Lighting None No STRUCTURAL 0 0 Refer to information indicated in Volume IV, Section E 0 0 Technical Comment: Library/Archive Closed Stacks Assignable Square Feet (ASF) OFEO Space Dimensions 0 Organizational Unit Other Interior Glazing 0 Solid core wood or insulated metal with neoprene seals max 1/4" undercut 0 0 No Off GPSing/Organic/SealedCeiling CRITICAL FINISHES 0 Positive
ELECTRICAL ARCHITECTURAL
Zone Room ID C3.2 Room Name 0 Functional
public,
Non Public Collection Space 800 Number of Occupants TBD Visual Privacy (full, partial, open) Zone Designation Zone C Room Height 0 LEED NC Regurlarly
Space 0 Base ACOUSTICS Equipment Hardware/STC Rating 0 NRC Absorptive
STC 45 0 Plug Loads Air Change/ HR Walls HVAC
Temperature Lighting 45%RH yr. rd. ±2ºF 110v,
No 8% RH yr. rd. Power No No Off GPSing/Organic/Sealed Pressure (+/-) 70ºF Floor Operable Windows
Closed
closed to the
entance only granted to scholars.
Occupied
ENGINEERING CRITERIA
20a, 1ph
FURNITURE/EQUIPMENT Moveable - Fixed RT60 & Shaping 0 Above
Floor Level 0 Room
Open

This room data sheet is not comprehensive in nature. Information regarding specific room features may not have been available and was intentionally left blank.

Accessibility Requirement:

Adjacencies

Water Table Compliance with ADA/ABAAG (2004) citations is required for accessibility. SI also requires compliance with SI Accessibility Guidelines and the IBC. Comparisons should be made and the more stringent requirement followed for design purposes. An accessible route including a minimum clear width of 36" (except through doors, which must be at least 32" clear) is required. Refer to ADA/ABAAG (2004) for specifications regarding clear floor spaces at desks, files and equipment for individuals using wheelchairs.See Accessibility Narrative for additional information. Resource Center, Curatorial and Collection Spaces

Description Closed stacks of rare and

SUSTAINABILITY FEATURES

vs. Private

DIMENSIONS

Length, Width, Shape

Recommend alternative cleaning agents under Fire Protection. Please refer to structural narrative for more information on structural requirements.

Smithsonian Institution National Museum of African American History and Culture 92 Infrastructure Only 0 Other Amenities Deionized Water Vacuum Yes Speakers 0 FIRE ALARM Smoke Detection Yes Wet Sprinkler Special Waste Dry Sprinkler Pre-Action Sprinkler 0 FIRE PROTECTION No Considerations for Water 0 No Floor Drains Floor Sink Grey/Blackwater Piping 0 No No No Protected Hot/Cold No No Recycled Water Supply (treated) 0 No Public Address Audio Compressed Air Audio Visual Requirements No Hot/Cold Water Task Light Yes No 0 Plant/Clean Steam Yes Acoustic Sensitivity NC 35 Vibration Sensitivity Special Equipment/Artifact Sensitivity PLUMBING Target Illuminance (IES 9th Edition) Daylight Sensor 5-30 FC Exhibit Light No Power Density (AHSRAE 2004) 1.7 W/ft² Temperature Deviations (+/-) Yes To Be Considered Process Water UPS Switched Receptacles Dimming No Humidity 0 Yes Other Humidity Deviation (+/-) 10 min. 0 No Outside Air Single/Multi-Level Switching 0 Emergency/Standby Power 15 CFM/person 65/ Carbon/95 Multi Occupancy Sensor Special Exhaust Sub-metering & Feedback Displays Filtration (Pre/Final/Other) Voice/Data DATA/TELECOMMUNICATIONS Yes 0 SECURITY 0 7.5 kPa/17.8 kN Floor Loading/Point Loads DAYLIGHTING 0 0 Shading Considerations Top/Side Lighting None No STRUCTURAL 0 0 Refer to information indicated in Volume IV, Section E 0 0 Technical Comment: Rare Book Room Assignable Square Feet (ASF) OFEO Space Dimensions 0 Organizational Unit Other Interior Glazing 0 Solid core wood or insulated metal with neoprene seals max 1/4" undercut 0 0 No Off GPSing/Organic/SealedCeiling CRITICAL FINISHES 0 Positive
ARCHITECTURAL
ELECTRICAL
Zone Room ID C3.3 Room Name 0
out of print books and literary material available for research, closed to the public. Staff access only. Non Public Collection Space 800 Number of Occupants TBD Visual Privacy (full, partial, open) Zone Designation Zone C Room Height 0 LEED NC Regurlarly Occupied Space 0 Base ACOUSTICS Equipment Hardware/STC Rating 0 NRC Absorptive finish on the ceiling with
NRC of 0.70 or higher STC 45 0 Plug Loads Air Change/ HR Walls HVAC ENGINEERING
Temperature Lighting 45%RH yr. rd. ±2ºF 110v,
No 8% RH yr. rd. Power No No Off GPSing/Organic/Sealed Pressure (+/-) 70ºF Floor Operable Windows
Moveable - Fixed RT60 & Shaping 0 Above
Functional
an
CRITERIA
20a, 1ph
Separation/STC FURNITURE/EQUIPMENT
Floor Level 0 Room
Open
CRITICAL

Accessibility Requirement:

Adjacencies

SUSTAINABILITY FEATURES

Open vs. Private

Compliance with ADA/ABAAG (2004) citations is required for accessibility. SI also requires compliance with SI Accessibility Guidelines and the IBC. Comparisons should be made and the more stringent requirement followed for design purposes. An accessible route including a minimum clear width of 36" (except through doors, which must be at least 32" clear) is required. Refer to ADA/ABAAG (2004) for specifications regarding clear floor spaces at desks, files and equipment for individuals using wheelchairs.See Accessibility Narrative for additional information.

CRITICAL DIMENSIONS

Room Length, Width, Shape

93 Room Data Sheets | FREELON BOND Infrastructure Only 0 Other Amenities Deionized Water Vacuum Yes Speakers 0 FIRE ALARM Smoke Detection Yes Wet Sprinkler Special Waste Dry Sprinkler Pre-Action Sprinkler 0 FIRE PROTECTION 0 Considerations for Water 0 No Floor Drains Floor Sink Grey/Blackwater Piping 0 0 0 0 Protected Hot/Cold 0 0 Recycled Water Supply (treated) 0 0 Public Address Audio Compressed Air Audio Visual Requirements 0 Hot/Cold Water Task Light 0 0 0 Plant/Clean Steam 0 Acoustic Sensitivity 0 Vibration Sensitivity Special Equipment/Artifact Sensitivity PLUMBING Target Illuminance (IES 9th Edition) Daylight Sensor 0 Exhibit Light 0 Power Density (AHSRAE 2004) 0 Temperature Deviations (+/-) 0 0 Process Water UPS Switched Receptacles Dimming 0 Humidity 0 0 Other Humidity Deviation (+/-) 0 0 0 Outside Air Single/Multi-Level Switching 0 Emergency/Standby Power 0 0 0 Occupancy Sensor Special Exhaust Sub-metering & Feedback Displays Filtration (Pre/Final/Other) Voice/Data DATA/TELECOMMUNICATIONS 0 0 SECURITY 0 0 Floor Loading/Point Loads DAYLIGHTING 0 0 Shading Considerations Top/Side Lighting 0 0 STRUCTURAL 0 0 Refer to information indicated in Volume IV, Section E 0 0 Technical Comment: Archival Cold Storage Assignable Square Feet (ASF) OFEO Space Dimensions 0 Organizational Unit Other Interior Glazing 0 0 0 0 0 Ceiling CRITICAL FINISHES 0 0 0 ELECTRICAL ARCHITECTURAL
room data sheet
not comprehensive in nature.
regarding
room
may not have been available and was intentionally left blank. Zone Room ID C3.4 Room Name 0 Functional Description Assumed to be provided at the off-site collections facility. Non Public Collection Space 0 Number of Occupants 0 Visual Privacy (full, partial, open) Zone Designation Zone C Room Height 0 LEED NC Regurlarly Occupied Space 0 Base ACOUSTICS Equipment Hardware/STC Rating 0 NRC 0 0 0 Plug Loads Air Change/ HR Walls HVAC ENGINEERING CRITERIA Temperature Lighting 0 0 110v, 20a, 1ph 0 0 Power 0 0 Pressure (+/-) 0 Floor Operable Windows Separation/STC FURNITURE/EQUIPMENT Moveable 0 Fixed RT60 & Shaping 0 0
This
is
Information
specific
features
0
Floor Level 0
NOTE: Space Located Offsite

This room data sheet is not comprehensive in nature. Information regarding specific room features may not have been available and was intentionally left blank.

Accessibility Requirement: Floor Level

Adjacencies

SUSTAINABILITY FEATURES

Open vs. Private

Compliance with ADA/ABAAG (2004) citations is required for accessibility. SI also requires compliance with SI Accessibility Guidelines and the IBC. Comparisons should be made and the more stringent requirement followed for design purposes. An accessible route including a minimum clear width of 36" (except through doors, which must be at least 32" clear) is required. Refer to ADA/ABAAG (2004) for specifications regarding clear floor spaces at desks, files and equipment for individuals using wheelchairs.See Accessibility Narrative for additional information. Resource Center, Curatorial and Collection Spaces

a kind items, rare

CRITICAL DIMENSIONS

Length, Width, Shape

Recommend alternative clean agent under Fire Protection. Please refer to structural narrative for more information on structural requirements.

W x 12'H Door Opening

Smithsonian Institution National Museum of African American History and Culture 94 Infrastructure Only 0 Other Amenities Deionized Water Vacuum Yes Speakers OH Gr. 2, 130 SF/HD FIRE ALARM Smoke Detection Yes Wet Sprinkler Special Waste Dry Sprinkler Pre-Action Sprinkler No FIRE PROTECTION No Considerations for Water 0 No Floor Drains Floor Sink Grey/Blackwater Piping 0 No No No Protected Hot/Cold No No Recycled Water Supply (treated) 0 No Public Address Audio Compressed Air Audio Visual Requirements No Hot/Cold Water Task Light No No 0 Plant/Clean Steam Yes Acoustic Sensitivity 0 Vibration Sensitivity Special Equipment/Artifact Sensitivity PLUMBING Target Illuminance (IES 9th Edition) Daylight Sensor 30 FC Exhibit Light No Power Density (AHSRAE 2004) 1.7 W/ft² Temperature Deviations (+/-) Yes No Process Water UPS Switched Receptacles Dimming To Be Considered Humidity 0 Yes Other Humidity Deviation (+/-) 10 min. 0 No Outside Air Single/Multi-Level Switching 0 Emergency/Standby Power 15 CFM/person 65/ Carbon/95 Single Occupancy Sensor Special Exhaust Sub-metering & Feedback Displays Filtration (Pre/Final/Other) Voice/Data DATA/TELECOMMUNICATIONS 0 0 SECURITY 0 7.5 kPa/26.7 kN Floor Loading/Point Loads DAYLIGHTING 0 0 Shading Considerations Top/Side Lighting None No STRUCTURAL 0 0 Refer to information indicated
Volume IV, Section E Full 0 Technical Comment: Vault Assignable Square Feet (ASF) OFEO Space Dimensions 0 Organizational Unit Other Interior Glazing 0 0 Yes Yes No Off GPSing/Organic/SealedCeiling CRITICAL FINISHES 0 Positive
in
ELECTRICAL ARCHITECTURAL
Zone Room ID C3.5 Room Name 0
other
Non Public Collection Space 300 Number of Occupants NA Visual Privacy (full, partial, open) Zone Designation Zone C Room Height Min 12'-6" LEED NC Regurlarly Occupied Space 0 Base ACOUSTICS Equipment Hardware/STC Rating 0 NRC0 0 Plug Loads Air Change/ HR Walls HVAC ENGINEERING CRITERIA Temperature Lighting 45%RH yr. rd. ±2ºF 110v, 20a, 1ph No 8% RH yr. rd. Power No No Off GPSing/Organic/Sealed Pressure (+/-) 70ºF Floor Operable Windows Separation/STC FURNITURE/EQUIPMENT Moveable Yes Fixed RT60
0 Above
Table
Functional Description This room is an ultra-secure space for valuable, one of
books, and
reading materials.
& Shaping
Water
10'
Room

ARCHITECTURAL

This room data sheet is not comprehensive in nature. Information regarding specific room features may not have been available and was intentionally left blank.

Floor Level

Accessibility Requirement:

Adjacencies

Water Table

Compliance with ADA/ABAAG (2004) citations is required for accessibility. SI also requires compliance with SI Accessibility Guidelines and the IBC. Comparisons should be made and the more stringent requirement followed for design purposes. An accessible route including a minimum clear width of 36" (except through doors, which must be at least 32" clear) is required. Refer to ADA/ABAAG (2004) for specifications regarding clear floor spaces at desks, files and equipment for individuals using wheelchairs.See Accessibility Narrative for additional information.

Collection Preparation Area

Functional Description This room is used to isolate possibly contaminated artifacts from entering the rest of the collection and termination of contamination. Isolation room may be a nitrogen-fed system that lowers the temperature of the artifact to terminate contamination. Contamination includes bugs, mold, and bacteria.

SUSTAINABILITY FEATURES

Open vs. Private

Separation/STC

CRITICAL DIMENSIONS

Length, Width, Shape

finish on the ceiling with an NRC of 0.70 or

Please refer to structural narrative for more information on structural requirements. ELECTRICAL

20a, 1ph

to information indicated in Volume IV, Section E

W x 12'H Door Opening

95 Room Data Sheets | FREELON BOND Infrastructure Only 0 Other Amenities Deionized Water Vacuum Yes Speakers OH Gr. 2, 130 SF/HD FIRE ALARM Smoke Detection Yes Wet Sprinkler Special Waste Dry Sprinkler Pre-Action Sprinkler No FIRE PROTECTION No Considerations for Water 0 No Floor Drains Floor Sink Grey/Blackwater Piping 0 No No No Protected Hot/Cold No No Recycled Water Supply (treated) 0 No Public Address Audio Compressed Air Audio Visual Requirements No Hot/Cold Water Task Light To Be Considered No 0 Plant/Clean Steam Yes Acoustic Sensitivity NC 30-35 Vibration Sensitivity Special Equipment/Artifact Sensitivity PLUMBING Target Illuminance (IES 9th Edition) Daylight Sensor 50 FC Exhibit Light No Power Density (AHSRAE 2004) 0.8 W/ft² Temperature Deviations (+/-) Yes No Process Water UPS Switched
Dimming To Be Considered Humidity 0 Yes Other Humidity Deviation (+/-) 10 min. 0 No Outside Air Single/Multi-Level Switching 0 Emergency/Standby Power 15 CFM/person 65/ Carbon/95 Single Occupancy Sensor Special Exhaust Sub-metering
Filtration
Voice/Data DATA/TELECOMMUNICATIONS Yes 0 SECURITY 0 12.0 kPa/26.7 kN Floor Loading/Point Loads DAYLIGHTING 0 0 Shading Considerations Top/Side Lighting None No STRUCTURAL 0 0 Refer
0 Isolation
Isolation Room
OFEO Space Dimensions 0 Organizational Unit Other Interior Glazing 0 Solid core wood
insulated metal
undercut Yes Yes No Off GPSing/Organic/SealedCeiling CRITICAL FINISHES 0 Positive
Receptacles
& Feedback Displays
(Pre/Final/Other)
room may be a nitrogen fed system that lowers the temperature of the artifact to terminate contamination. Technical Comment:
Assignable Square Feet (ASF)
or
with neoprene seals max 1/4"
Zone
C4.1 Room Name 0
Room ID
Non Public Collection Space 400 Number of Occupants NA Visual Privacy (full, partial, open) Zone Designation Zone C Room Height Min 12'-6"
0 Base ACOUSTICS Equipment Hardware/STC Rating 0 NRC Absorptive
STC 55 0 Plug Loads Air Change/ HR Walls HVAC
Temperature Lighting 45%RH yr. rd. ±2ºF 110v,
No 8% RH yr. rd. Power No No Off GPSing/Organic/Sealed Pressure (+/-) 70ºF Floor Operable
LEED NC Regurlarly Occupied Space
higher
ENGINEERING CRITERIA
Windows
FURNITURE/EQUIPMENT Moveable Yes Fixed RT60 &
0
Shaping
Above
10'
Room

This room data sheet is not comprehensive in nature. Information regarding specific room features may not have been available and was intentionally left blank.

Accessibility Requirement:

Adjacencies

SUSTAINABILITY FEATURES

Compliance with ADA/ABAAG (2004) citations is required for accessibility. SI also requires compliance with SI Accessibility Guidelines and the IBC. Comparisons should be made and the more stringent requirement followed for design purposes. An accessible route including a minimum clear width of 36" (except through doors, which must be at least 32" clear) is required. Refer to ADA/ABAAG (2004) for specifications regarding clear floor spaces at desks, files and equipment for individuals using wheelchairs.See Accessibility Narrative for additional information.

CRITICAL DIMENSIONS

finish on the ceiling with an NRC of 0.70 or higher

Please refer to structural narrative for more information on structural requirements.

Smithsonian Institution National Museum of African American History and Culture 96 Infrastructure Only 0 Other Amenities Deionized Water Vacuum Yes Speakers OH Gr. 2, 130 SF/HD FIRE ALARM Smoke Detection Yes Wet Sprinkler Special Waste Dry Sprinkler Pre-Action Sprinkler No FIRE PROTECTION Review acid waste Considerations for Water 0 No Floor Drains Floor Sink Grey/Blackwater Piping 0 Yes Yes Yes Protected Hot/Cold Yes Yes Recycled Water Supply (treated) 0 Yes Public Address Audio Compressed Air Audio Visual Requirements Yes Hot/Cold Water Task Light To Be Considered To Be Considered 0 Plant/Clean Steam Yes Acoustic Sensitivity NC 35-40 Vibration Sensitivity Special Equipment/Artifact Sensitivity PLUMBING Target Illuminance (IES 9th Edition) Daylight Sensor 30-50 FC Exhibit Light To Be Considered Power Density (AHSRAE 2004) 1.7 W/ft² Temperature Deviations (+/-) Yes No Process Water UPS Switched Receptacles Dimming No Humidity 0 Yes Other Humidity Deviation (+/-) 10 min. 0 No Outside Air Single/Multi-Level Switching 0 Emergency/Standby Power 15 CFM/person 65/ Carbon/95 Multi Occupancy Sensor Special Exhaust Sub-metering & Feedback Displays Filtration (Pre/Final/Other) Voice/Data DATA/TELECOMMUNICATIONS Yes 0 SECURITY 0 7.5 kPa/26.7 kN Floor Loading/Point Loads DAYLIGHTING 0 0 Shading Considerations Top/Side Lighting None No STRUCTURAL 0 0 Refer
Full 0 Technical Comment: Multipurpose Conservation Lab Assignable Square Feet (ASF) OFEO Space Dimensions 0 Organizational Unit Other Interior Glazing 0 Solid core wood or insulated metal with neoprene seals max 1/4" undercut Yes Yes No Off GPSing/Organic/SealedCeiling CRITICAL FINISHES 0 Positive
to information indicated in Volume IV, Section E
ELECTRICAL ARCHITECTURAL
Zone Room ID C4.2 Room Name 0 Functional Description This lab will be used for all minor conservation work to be done on-site (larger efforts to be conducted at off-site facility), and be media nonspecific. Non Public Collection Space 1,000 Number of Occupants TBD Visual Privacy (full, partial, open) Zone
Room Height Min 12'-6" LEED NC Regurlarly Occupied Space 0 Base ACOUSTICS Equipment Hardware/STC Rating 0 NRC
STC 50 0 Plug Loads Air Change/ HR Walls HVAC
Temperature Lighting 45%RH yr. rd. ±2ºF 110v, 20a, 1ph No 8% RH yr. rd. Power No No Off GPSing/Organic/Sealed Pressure (+/-) 70ºF Floor Operable Windows Separation/STC FURNITURE/EQUIPMENT Moveable Yes Fixed RT60 & Shaping 0 Above
Table
Resource Center
Designation Zone C
Absorptive
ENGINEERING CRITERIA
Water
Floor Level 10'
Opening Room
Open
W x 12'H Door
Length, Width, Shape
vs. Private

This room data sheet is not comprehensive in nature. Information regarding specific room features may not have been available and was intentionally left blank.

Accessibility Requirement:

Adjacencies

SUSTAINABILITY FEATURES

Compliance with ADA/ABAAG (2004) citations is required for accessibility. SI also requires compliance with SI Accessibility Guidelines and the IBC. Comparisons should be made and the more stringent requirement followed for design purposes. An accessible route including a minimum clear width of 36" (except through doors, which must be at least 32" clear) is required. Refer to ADA/ABAAG (2004) for specifications regarding clear floor spaces at desks, files and equipment for individuals using wheelchairs.See Accessibility Narrative for additional information.

CRITICAL DIMENSIONS

finish on the ceiling with an NRC of 0.70 or higher

Please refer to structural narrative for more information on structural requirements.

97 Room Data Sheets | FREELON BOND Infrastructure Only 0 Other Amenities Deionized Water Vacuum Yes Speakers OH Gr. 2, 130 SF/HD FIRE ALARM Smoke Detection Yes Wet Sprinkler Special Waste Dry Sprinkler Pre-Action Sprinkler No FIRE PROTECTION No Considerations for Water 0 No Floor Drains Floor Sink Grey/Blackwater Piping 0 No No No Protected Hot/Cold No No Recycled Water Supply (treated) 0 No Public Address Audio Compressed Air Audio Visual Requirements No Hot/Cold Water Task Light To Be Considered No 0 Plant/Clean Steam Yes Acoustic Sensitivity NC 35-40 Vibration Sensitivity Special Equipment/Artifact Sensitivity PLUMBING Target Illuminance (IES 9th Edition) Daylight Sensor 30 FC Exhibit Light No Power Density (AHSRAE 2004) 1.1 W/ft² Temperature Deviations (+/-) Yes No Process Water UPS Switched Receptacles Dimming No Humidity 0 Yes Other Humidity Deviation (+/-) 10 min. 0 No Outside Air Single/Multi-Level Switching 0 Emergency/Standby Power 15 CFM/person 65/ Carbon/95 Single Occupancy Sensor Special Exhaust Sub-metering & Feedback Displays Filtration (Pre/Final/Other) Voice/Data DATA/TELECOMMUNICATIONS Yes 0 SECURITY 0 7.5 kPa/17.8 kN Floor Loading/Point Loads DAYLIGHTING 0 0 Shading Considerations Top/Side Lighting None No STRUCTURAL 0 0 Refer
Full Glass wall
Photography Conservation Lab Assignable Square Feet (ASF) OFEO Space Dimensions 0 Organizational Unit Other Interior Glazing 0 Solid core wood or insulated metal with neoprene strip seals max 1/4" undercut Yes Yes No Off GPSing/Organic/SealedCeiling CRITICAL FINISHES 0 Positive
to information indicated in Volume IV, Section E
or viewing area into the Conservation Space. Technical Comment:
ELECTRICAL ARCHITECTURAL
Zone Room ID C4.3 Room Name 0 Functional Description This lab will be used for all photo conservation work to be done. It will offer it's conservation services other SI institutions. Non Public Collection Space 875 Number of Occupants TBD Visual Privacy (full, partial, open) Zone Designation Zone C Room Height Min 12'-6" LEED NC Regurlarly
Space 0 Base ACOUSTICS Equipment Hardware/STC Rating 0 NRC Absorptive
STC 50 0 Plug Loads Air Change/ HR Walls HVAC ENGINEERING
Temperature Lighting 45%RH yr. rd. ±2ºF 110v, 20a, 1ph No 8% RH yr. rd. Power No No Off GPSing/Organic/Sealed Pressure (+/-) 70ºF Floor Operable Windows Separation/STC FURNITURE/EQUIPMENT Moveable Yes Fixed RT60
0 Above Water Table
Resource Center
Occupied
CRITERIA
& Shaping
Floor Level 10' W x 12'H Door Opening Room Length, Width, Shape Open vs. Private

This room data sheet is not comprehensive in nature. Information regarding specific room features may not have been available and was intentionally left blank.

Accessibility Requirement:

Adjacencies

SUSTAINABILITY FEATURES

Compliance with ADA/ABAAG (2004) citations is required for accessibility. SI also requires compliance with SI Accessibility Guidelines and the IBC. Comparisons should be made and the more stringent requirement followed for design purposes. An accessible route including a minimum clear width of 36" (except through doors, which must be at least 32" clear) is required. Refer to ADA/ABAAG (2004) for specifications regarding clear floor spaces at desks, files and equipment for individuals using wheelchairs.See Accessibility Narrative for additional information.

Board Room, Reception/Waiting Area, Director's Office Suite Offices, Project Management Offices, Staff Amenities, Meeting Rooms. Additional adjacency information is unavailable at this time pending finalization of organization chart by NMAAHC

CRITICAL DIMENSIONS

Please refer to structural narrative for more information on structural requirements.

Smithsonian Institution National Museum of African American History and Culture 98 Infrastructure Only 0 Other Amenities Deionized Water Vacuum Yes Speakers OH Gr. 2, 130 SF/HD FIRE ALARM Smoke Detection Yes Wet Sprinkler Special Waste Dry Sprinkler Pre-Action Sprinkler No FIRE PROTECTION No Considerations for Water 0 No Floor Drains Floor Sink Grey/Blackwater Piping 0 No No No Protected Hot/Cold No No Recycled Water Supply (treated) 0 No Public Address Audio Compressed Air Audio Visual Requirements No Hot/Cold Water Task Light Yes No 0 Plant/Clean Steam No Acoustic Sensitivity 0 Vibration Sensitivity Special Equipment/Artifact Sensitivity PLUMBING Target Illuminance (IES 9th Edition) Daylight Sensor 0 Exhibit Light Yes Power Density (AHSRAE 2004) 0 Temperature Deviations (+/-) No No Process Water UPS Switched Receptacles Dimming Yes Humidity 0 No Other Humidity Deviation (+/-) As required by load No No Outside Air Single/Multi-Level Switching 0 Emergency/Standby Power As required by code 30/85 Yes Occupancy Sensor Special Exhaust Sub-metering & Feedback Displays Filtration (Pre/Final/Other) Voice/Data DATA/TELECOMMUNICATIONS Yes 0 SECURITY 0 0 Floor Loading/Point Loads DAYLIGHTING 0 0 Shading Considerations Top/Side Lighting Yes 0 STRUCTURAL 0 0 Refer to information indicated in Volume IV, Section E 0 0 Technical Comment: Director's Office Assignable Square Feet (ASF) OFEO Space Dimensions 0 Organizational Unit Other Interior Glazing 0 0 0 0 0 Ceiling CRITICAL FINISHES 0 0
ELECTRICAL ARCHITECTURAL
Zone Room ID D1.1 Room Name 0 Functional Description Enclosed private office with office furnishings including worksurface, file storage and additional seating area for reception of VIP guests. Non Public-Non Collection Space 480 Number of Occupants 1 Visual Privacy (full, partial, open) Zone Designation Zone D Room Height 0 LEED NC
Space 0 Base ACOUSTICS Equipment Hardware/STC Rating None NRC 0 0 0 Plug Loads Air Change/ HR Walls HVAC ENGINEERING CRITERIA Temperature Lighting No Control ±2ºF 110v, 20a, 1ph Yes 0 Power No 0 Pressure (+/-) 78ºF Summer, 71ºF Winter Floor Operable Windows Separation/STC FURNITURE/EQUIPMENT Moveable 0 Fixed RT60 & Shaping 0 Upper
Regurlarly Occupied
Floor Level 0 Room
Length, Width, Shape Open vs. Private

This room data sheet is not comprehensive in nature. Information regarding specific room features may not have been available and was intentionally left blank.

Accessibility Requirement:

Adjacencies

SUSTAINABILITY FEATURES

Compliance with ADA/ABAAG (2004) citations is required for accessibility. SI also requires compliance with SI Accessibility Guidelines and the IBC. Comparisons should be made and the more stringent requirement followed for design purposes. An accessible route including a minimum clear width of 36" (except through doors, which must be at least 32" clear) is required. Refer to ADA/ABAAG (2004) for specifications regarding clear floor spaces at desks, files and equipment for individuals using wheelchairs.See Accessibility Narrative for additional information.

Director's Office, Director's Office Suite Offices, Project Management Offices, Staff Amenities, Meeting Rooms. Additional adjacency information is unavailable at this time pending finalization of organization chart by NMAAHC.

CRITICAL DIMENSIONS

Length, Width, Shape Open vs. Private

Please refer to structural narrative for more information on structural requirements.

99 Room Data Sheets | FREELON BOND Infrastructure Only 0 Other Amenities Deionized Water Vacuum Yes Speakers OH Gr. 2, 130 SF/HD FIRE ALARM Smoke Detection Yes Wet Sprinkler Special Waste Dry Sprinkler Pre-Action Sprinkler No FIRE PROTECTION No Considerations for Water 0 No Floor Drains Floor Sink Grey/Blackwater Piping 0 No No No Protected Hot/Cold No No Recycled Water Supply (treated) 0 No Public Address Audio Compressed Air Audio Visual Requirements No Hot/Cold Water Task Light Yes No 0 Plant/Clean Steam No Acoustic Sensitivity 0 Vibration Sensitivity Special Equipment/Artifact Sensitivity PLUMBING Target Illuminance (IES 9th Edition) Daylight Sensor 0 Exhibit Light Yes Power Density (AHSRAE 2004) 0 Temperature Deviations (+/-) No No Process Water UPS Switched Receptacles Dimming Yes Humidity 0 No Other Humidity Deviation (+/-) As required by load No No Outside Air Single/Multi-Level Switching 0 Emergency/Standby Power As required by code 30/85 Yes Occupancy Sensor Special Exhaust Sub-metering & Feedback Displays Filtration (Pre/Final/Other) Voice/Data DATA/TELECOMMUNICATIONS Yes 0 SECURITY 0 0 Floor Loading/Point Loads DAYLIGHTING 0 0 Shading Considerations Top/Side Lighting 0 0 STRUCTURAL 0 0 Refer to information indicated in Volume IV, Section E 0 0 Technical Comment: Reception/Waiting Area Assignable Square Feet (ASF) OFEO Space Dimensions 0 Organizational Unit Other Interior Glazing 0 0 0 0 0 Ceiling CRITICAL FINISHES 0 0
ELECTRICAL ARCHITECTURAL
Zone Room ID D1.2 Room Name 0 Functional Description Open area with loose seating for reception of guests. Non Public-Non Collection Space 200 Number of Occupants 1 Visual Privacy (full, partial, open) Zone Designation Zone D Room Height 0 LEED NC Regurlarly Occupied Space 0 Base ACOUSTICS Equipment Hardware/STC Rating None NRC 0 0 0 Plug Loads Air Change/ HR Walls HVAC ENGINEERING CRITERIA Temperature Lighting No Control ±2ºF 110v, 20a, 1ph Yes 0 Power No 0 Pressure (+/-) 78ºF Summer, 71ºF Winter Floor Operable Windows Separation/STC FURNITURE/EQUIPMENT Moveable 0 Fixed RT60 &
0 Upper
Shaping
Floor Level 0 Room

This room data sheet is not comprehensive in nature. Information regarding specific room features may not have been available and was intentionally left blank.

Adjacencies Accessibility Requirement:

SUSTAINABILITY FEATURES

Compliance with ADA/ABAAG (2004) citations is required for accessibility. SI also requires compliance with SI Accessibility Guidelines and the IBC. Comparisons should be made and the more stringent requirement followed for design purposes. An accessible route including a minimum clear width of 36" (except through doors, which must be at least 32" clear) is required. Refer to ADA/ABAAG (2004) for specifications regarding clear floor spaces at desks, files and equipment for individuals using wheelchairs.See Accessibility Narrative for additional information.

Director's Office, Reception/Waiting Area, Project Management Offices, Director's Office Suite Work Stations, Staff Amenities, Meeting Rooms. Additional adjacency information is unavailable at this time pending finalization of organization chart by NMAAHC.

CRITICAL DIMENSIONS

Length, Width, Shape Open vs. Private

Please refer to structural narrative for more information on structural requirements.

Smithsonian Institution National Museum of African American History and Culture 100 Infrastructure Only 0 Other Amenities Deionized Water Vacuum Yes Speakers OH Gr. 2, 130 SF/HD FIRE ALARM Smoke Detection Yes Wet Sprinkler Special Waste Dry Sprinkler Pre-Action Sprinkler No FIRE PROTECTION No Considerations for Water 0 No Floor Drains Floor Sink Grey/Blackwater Piping 0 No No No Protected Hot/Cold No No Recycled Water Supply (treated) 0 No Public Address Audio Compressed Air Audio Visual Requirements No Hot/Cold Water Task Light Yes No 0 Plant/Clean Steam No Acoustic Sensitivity 0 Vibration Sensitivity Special Equipment/Artifact Sensitivity PLUMBING Target Illuminance (IES 9th Edition) Daylight Sensor 0 Exhibit Light Yes Power Density (AHSRAE 2004) 0 Temperature Deviations (+/-) No No Process Water UPS Switched Receptacles Dimming Yes Humidity 0 No Other Humidity Deviation (+/-) As required by load No No Outside Air Single/Multi-Level Switching 0 Emergency/Standby Power As required by code 30/85 Yes Occupancy Sensor Special Exhaust Sub-metering & Feedback Displays Filtration (Pre/Final/Other) Voice/Data DATA/TELECOMMUNICATIONS Yes 0 SECURITY 0 0 Floor Loading/Point Loads DAYLIGHTING 0 0 Shading Considerations Top/Side Lighting 0 0 STRUCTURAL 0 0 Refer to information indicated in Volume IV, Section E 0 0 Technical Comment: Director's Office Suite Offices Assignable Square Feet (ASF) OFEO Space Dimensions 0 Organizational Unit Other Interior Glazing 0 0 0 0 0 Ceiling CRITICAL FINISHES 0 0
ELECTRICAL ARCHITECTURAL
Zone Room ID D1.3 Room Name 0 Functional
Enclosed private office with office furnishings including worksurface
file storage. Non Public-Non Collection Space 480 Number of Occupants 1 Visual Privacy (full, partial, open) Zone Designation Zone D Room Height 0 LEED NC Regurlarly Occupied
0 Base ACOUSTICS Equipment Hardware/STC Rating None NRC 0 0 0 Plug Loads Air Change/ HR Walls HVAC ENGINEERING CRITERIA Temperature Lighting No Control ±2ºF 110v, 20a, 1ph Yes 0 Power No 0 Pressure (+/-) 78ºF Summer, 71ºF Winter Floor Operable Windows Separation/STC FURNITURE/EQUIPMENT Moveable 0 Fixed RT60 & Shaping 0 Upper
Description
and
Space
Floor Level 0 Room

This room data sheet is not comprehensive in nature. Information regarding specific room features may not have been available and was intentionally left blank.

Accessibility Requirement:

Adjacencies

Compliance with ADA/ABAAG (2004) citations is required for accessibility. SI also requires compliance with SI Accessibility Guidelines and the IBC. Comparisons should be made and the more stringent requirement followed for design purposes. An accessible route including a minimum clear width of 36" (except through doors, which must be at least 32" clear) is required. Refer to ADA/ABAAG (2004) for specifications regarding clear floor spaces at desks, files and equipment for individuals using wheelchairs.See Accessibility Narrative for additional information.

Director's Office, Reception/Waiting Area, Director's Office Suite Offices, Project Management Work Stations, Staff Amenities, Meeting Rooms. Additional adjacency information is unavailable at this time pending finalization of organization chart by NMAAHC.

SUSTAINABILITY FEATURES

vs. Private

Please refer to structural narrative for more information on structural requirements.

CRITICAL DIMENSIONS

Length, Width, Shape

101 Room Data Sheets | FREELON BOND Infrastructure Only 0 Other Amenities Deionized Water Vacuum Yes Speakers OH Gr. 2, 130 SF/HD FIRE ALARM Smoke Detection Yes Wet Sprinkler Special Waste Dry Sprinkler Pre-Action Sprinkler No FIRE PROTECTION No Considerations for Water 0 No Floor Drains Floor Sink Grey/Blackwater Piping 0 No No No Protected Hot/Cold No No Recycled Water Supply (treated) 0 No Public Address Audio Compressed Air Audio Visual Requirements No Hot/Cold Water Task Light Yes No 0 Plant/Clean Steam No Acoustic Sensitivity 0 Vibration Sensitivity Special Equipment/Artifact Sensitivity PLUMBING Target Illuminance (IES 9th Edition) Daylight Sensor 0 Exhibit Light Yes Power Density (AHSRAE 2004) 0 Temperature Deviations (+/-) No No Process Water UPS Switched Receptacles Dimming Yes Humidity 0 No Other Humidity Deviation (+/-) As required by load No No Outside Air Single/Multi-Level Switching 0 Emergency/Standby Power As required by code 30/85 Yes Occupancy Sensor Special Exhaust Sub-metering & Feedback Displays Filtration (Pre/Final/Other) Voice/Data DATA/TELECOMMUNICATIONS Yes 0 SECURITY 0 0 Floor Loading/Point Loads DAYLIGHTING 0 0 Shading Considerations Top/Side Lighting 0 0 STRUCTURAL 0 0 Refer to information indicated in Volume IV, Section E 0 0 Technical Comment: Project Management Offices Assignable Square Feet (ASF) OFEO Space Dimensions 0 Organizational Unit Other Interior Glazing 0 0 0 0 0 Ceiling CRITICAL FINISHES 0 0
ELECTRICAL ARCHITECTURAL
Zone Room ID D1.4 Room Name 0 Functional
Enclosed
office with office furnishings
worksurface
Non Public-Non Collection Space 360 Number of Occupants 1 Visual Privacy (full, partial, open) Zone Designation Zone D Room Height 0 LEED NC Regurlarly Occupied Space 0 Base ACOUSTICS Equipment Hardware/STC Rating None NRC 0 0 0 Plug Loads Air Change/ HR Walls HVAC ENGINEERING CRITERIA Temperature Lighting No Control ±2ºF 110v, 20a, 1ph Yes 0 Power No 0 Pressure (+/-) 78ºF Summer, 71ºF Winter Floor Operable Windows Separation/STC FURNITURE/EQUIPMENT Moveable 0 Fixed RT60 & Shaping 0 Upper
Description
private
including
and file storage.
Floor Level 0 Room
Open

This room data sheet is not comprehensive in nature. Information regarding specific room features may not have been available and was intentionally left blank.

Accessibility Requirement:

Adjacencies

Compliance with ADA/ABAAG (2004) citations is required for accessibility. SI also requires compliance with SI Accessibility Guidelines and the IBC. Comparisons should be made and the more stringent requirement followed for design purposes. An accessible route including a minimum clear width of 36" (except through doors, which must be at least 32" clear) is required. Refer to ADA/ABAAG (2004) for specifications regarding clear floor spaces at desks, files and equipment for individuals using wheelchairs.See Accessibility Narrative for additional information.

Located in Resource Center. Additional adjacency information is unavailable at this time pending finalization of organization chart by NMAAHC.

SUSTAINABILITY FEATURES

vs. Private

Please refer to structural narrative for more information on structural requirements.

CRITICAL DIMENSIONS

Length, Width, Shape

Smithsonian Institution National Museum of African American History and Culture 102 Infrastructure Only 0 Other Amenities Deionized Water Vacuum Yes Speakers OH Gr. 2, 130 SF/HD FIRE ALARM Smoke Detection Yes Wet Sprinkler Special Waste Dry Sprinkler Pre-Action Sprinkler No FIRE PROTECTION No Considerations for Water 0 No Floor Drains Floor Sink Grey/Blackwater Piping 0 No No No Protected Hot/Cold No No Recycled Water Supply (treated) 0 No Public Address Audio Compressed Air Audio Visual Requirements No Hot/Cold Water Task Light Yes No 0 Plant/Clean Steam No Acoustic Sensitivity 0 Vibration Sensitivity Special Equipment/Artifact Sensitivity PLUMBING Target Illuminance (IES 9th Edition) Daylight Sensor 0 Exhibit Light Yes Power Density (AHSRAE 2004) 0 Temperature Deviations (+/-) No No Process Water UPS Switched Receptacles Dimming Yes Humidity 0 No Other Humidity Deviation (+/-) As required by load No No Outside Air Single/Multi-Level Switching 0 Emergency/Standby Power As required by code 30/85 Yes Occupancy Sensor Special Exhaust Sub-metering & Feedback Displays Filtration (Pre/Final/Other) Voice/Data DATA/TELECOMMUNICATIONS Yes 0 SECURITY 0 0 Floor Loading/Point Loads DAYLIGHTING 0 0 Shading Considerations Top/Side Lighting 0 0 STRUCTURAL 0 0 Refer to information indicated in Volume IV, Section E 0 0 Technical Comment: Associate Director CA Assignable Square Feet (ASF) OFEO Space Dimensions 0 Organizational Unit Other Interior Glazing 0 0 0 0 0 Ceiling CRITICAL FINISHES 0 0
ELECTRICAL ARCHITECTURAL
Zone Room ID D1.5 Room Name 0 Functional Description Enclosed private office with office furnishings including worksurface, file storage and additional seating area for reception of VIP guests. Non Public-Non Collection Space 280 Number of Occupants 1 Visual Privacy (full, partial, open) Zone Designation Zone D Room Height 0 LEED NC
0 Base ACOUSTICS Equipment Hardware/STC Rating None NRC 0 0 0 Plug Loads Air Change/ HR Walls HVAC ENGINEERING CRITERIA Temperature Lighting No Control ±2ºF 110v, 20a, 1ph Yes 0 Power No 0 Pressure (+/-) 78ºF Summer, 71ºF Winter Floor Operable Windows Separation/STC FURNITURE/EQUIPMENT Moveable 0 Fixed RT60 &
0 Upper
Regurlarly Occupied Space
Shaping
Floor Level 0 Room
Open

This room data sheet is not comprehensive in nature. Information regarding specific room features may not have been available and was intentionally left blank.

Accessibility Requirement:

Adjacencies

Compliance with ADA/ABAAG (2004) citations is required for accessibility. SI also requires compliance with SI Accessibility Guidelines and the IBC. Comparisons should be made and the more stringent requirement followed for design purposes. An accessible route including a minimum clear width of 36" (except through doors, which must be at least 32" clear) is required. Refer to ADA/ABAAG (2004) for specifications regarding clear floor spaces at desks, files and equipment for individuals using wheelchairs.See Accessibility Narrative for additional information.

Curatorial Affairs Work Stations, Staff Amenities and Meeting Rooms. Additional adjacency information is unavailable at this time pending finalization of organization chart by NMAAHC.

SUSTAINABILITY FEATURES

vs. Private

Please refer to structural narrative for more information on structural requirements.

CRITICAL DIMENSIONS

Length, Width, Shape

103 Room Data Sheets | FREELON BOND Infrastructure Only 0 Other Amenities Deionized Water Vacuum Yes Speakers OH Gr. 2, 130 SF/HD FIRE ALARM Smoke Detection Yes Wet Sprinkler Special Waste Dry Sprinkler Pre-Action Sprinkler No FIRE PROTECTION No Considerations for Water 0 No Floor Drains Floor Sink Grey/Blackwater Piping 0 No No No Protected Hot/Cold No No Recycled Water Supply (treated) 0 No Public Address Audio Compressed Air Audio Visual Requirements No Hot/Cold Water Task Light Yes No 0 Plant/Clean Steam No Acoustic Sensitivity 0 Vibration Sensitivity Special Equipment/Artifact Sensitivity PLUMBING Target Illuminance (IES 9th Edition) Daylight Sensor 0 Exhibit Light Yes Power Density (AHSRAE 2004) 0 Temperature Deviations (+/-) No No Process Water UPS Switched Receptacles Dimming Yes Humidity 0 No Other Humidity Deviation (+/-) As required by load No No Outside Air Single/Multi-Level Switching 0 Emergency/Standby Power As required by code 30/85 Yes Occupancy Sensor Special Exhaust Sub-metering & Feedback Displays Filtration (Pre/Final/Other) Voice/Data DATA/TELECOMMUNICATIONS Yes 0 SECURITY 0 0 Floor Loading/Point Loads DAYLIGHTING 0 0 Shading Considerations Top/Side Lighting 0 0 STRUCTURAL 0 0 Refer to information indicated in Volume IV, Section E 0 0 Technical Comment: Curators Assignable Square Feet (ASF) OFEO Space Dimensions 0 Organizational Unit Other Interior Glazing 0 0 0 0 0 Ceiling CRITICAL FINISHES 0 0
ELECTRICAL ARCHITECTURAL
Zone Room ID D1.6 Room Name 0 Functional Description Enclosed private office
office
Non Public-Non Collection Space 1,440 Number of Occupants 1 Visual Privacy (full, partial, open) Zone Designation Zone D Room Height 0 LEED NC Regurlarly Occupied Space 0 Base ACOUSTICS Equipment Hardware/STC Rating None NRC 0 0 0 Plug Loads Air Change/ HR Walls HVAC ENGINEERING CRITERIA Temperature Lighting No Control ±2ºF 110v, 20a, 1ph Yes 0 Power No 0 Pressure (+/-) 78ºF Summer, 71ºF Winter Floor Operable Windows Separation/STC FURNITURE/EQUIPMENT Moveable 0 Fixed RT60 &
0 Upper
with
furnishings including worksurface and file storage.
Shaping
Floor Level 0 Room
Open

This room data sheet is not comprehensive in nature. Information regarding specific room features may not have been

Curatorial Affairs Work Stations, Staff Amenities and Meeting Rooms. Additional adjacency information is unavailable at this time pending finalization of organization chart by NMAAHC. SUSTAINABILITY FEATURES Adjacencies Accessibility

vs. Private

Compliance with ADA/ABAAG (2004) citations is required for accessibility. SI also requires compliance with SI Accessibility Guidelines and the IBC. Comparisons should be made and the more stringent requirement followed for design purposes. See Accessibility Narrative for additional information.

CRITICAL DIMENSIONS

Smithsonian Institution National Museum of African American History and Culture 104 Infrastructure Only 0 Other Amenities Deionized Water Vacuum Yes Speakers OH Gr. 2, 130 SF/HD FIRE ALARM Smoke Detection Yes Wet Sprinkler Special Waste Dry Sprinkler Pre-Action Sprinkler No FIRE PROTECTION 0 Considerations for Water 0 No Floor Drains Floor Sink Grey/Blackwater Piping 0 0 0 0 Protected Hot/Cold 0 0 Recycled Water Supply (treated) 0 0 Public Address Audio Compressed Air Audio Visual Requirements 0 Hot/Cold Water Task Light 0 0 0 Plant/Clean Steam 0 Acoustic Sensitivity 0 Vibration Sensitivity Special Equipment/Artifact Sensitivity PLUMBING Target Illuminance (IES 9th Edition) Daylight Sensor 0 Exhibit Light 0 Power Density (AHSRAE 2004) 0 Temperature Deviations (+/-) 0 0 Process Water UPS Switched Receptacles Dimming 0 Humidity 0 0 Other Humidity Deviation (+/-) 0 0 0 Outside Air Single/Multi-Level Switching 0 Emergency/Standby Power 0 0 0 Occupancy Sensor Special Exhaust Sub-metering & Feedback Displays Filtration (Pre/Final/Other) Voice/Data DATA/TELECOMMUNICATIONS Yes 0 SECURITY 0 0 Floor Loading/Point Loads DAYLIGHTING 0 0 Shading Considerations Top/Side Lighting 0 0 STRUCTURAL 0 0 Refer to information indicated in Volume IV, Section E 0 0 Technical Comment: Assistant Curators o Assignable Square Feet (ASF) OFEO Space Dimensions 0 Organizational Unit Other Interior Glazing 0 0 0 0 0 Ceiling CRITICAL FINISHES 0 0 0 ELECTRICAL ARCHITECTURAL
left blank. Zone Room ID D1.7 Room Name 0 Functional
file storage. Non Public-Non Collection Space 360 Number of Occupants 1 Visual Privacy (full, partial, open) Zone Designation Zone D Room Height 0 LEED NC Regurlarly Occupied Space 0 Base ACOUSTICS Equipment Hardware/STC Rating 0 NRC 0 0 0 Plug Loads Air Change/ HR Walls HVAC ENGINEERING CRITERIA Temperature Lighting 0 0 110v, 20a, 1ph 0 0 Power 0 0 Pressure (+/-) 0 Floor Operable Windows
FURNITURE/EQUIPMENT Moveable 0 Fixed RT60 & Shaping 0 Upper
available and was intentionally
Description Enclosed private office with office furnishings including worksurface and
Separation/STC
Floor Level 0 Room Length,
Open
Requirement:
Width, Shape

This room data sheet is not comprehensive in nature. Information regarding specific room features may not have been available and was intentionally left

Accessibility Requirement:

Compliance withADA/ABAAG (2004) citations is required for accessibility. SI also requires compliance with SI Accessibility Guidelines and the IBC. Comparisons should be made and the more stringent requirement followed for design purposes. See Accessibility Narrative for additional information.

Curatorial Affairs Work Stations, Staff Amenities and Meeting Rooms. Additional adjacency information is unavailable at this time pending finalization of organization chart by NMAAHC. SUSTAINABILITY FEATURES Adjacencies

Description Enclosed private office with office furnishings including

CRITICAL DIMENSIONS

vs. Private

105 Room Data Sheets | FREELON BOND Infrastructure Only 0 Other Amenities Deionized Water Vacuum Yes Speakers OH Gr. 2, 130 SF/HD FIRE ALARM Smoke Detection Yes Wet Sprinkler Special Waste Dry Sprinkler Pre-Action Sprinkler No FIRE PROTECTION 0 Considerations for Water 0 No Floor Drains Floor Sink Grey/Blackwater Piping 0 0 0 0 Protected Hot/Cold 0 0 Recycled Water Supply (treated) 0 0 Public Address Audio Compressed Air Audio Visual Requirements 0 Hot/Cold Water Task Light 0 0 0 Plant/Clean Steam 0 Acoustic Sensitivity 0 Vibration Sensitivity Special Equipment/Artifact Sensitivity PLUMBING Target Illuminance (IES 9th Edition) Daylight Sensor 0 Exhibit Light 0 Power Density (AHSRAE 2004) 0 Temperature Deviations (+/-) 0 0 Process Water UPS Switched Receptacles Dimming 0 Humidity 0 0 Other Humidity Deviation (+/-) 0 0 0 Outside Air Single/Multi-Level Switching 0 Emergency/Standby Power 0 0 0 Occupancy Sensor Special Exhaust Sub-metering & Feedback Displays Filtration (Pre/Final/Other) Voice/Data DATA/TELECOMMUNICATIONS Yes 0 SECURITY 0 0 Floor Loading/Point Loads DAYLIGHTING 0 0 Shading Considerations Top/Side Lighting 0 0 STRUCTURAL 0 0 Refer to information indicated in Volume IV, Section E 0 0 Technical Comment: Curatorial Assistant/Collections Management O Assignable Square Feet (ASF) OFEO Space Dimensions 0 Organizational Unit Other Interior Glazing 0 0 0 0 0 Ceiling CRITICAL FINISHES 0 0 0 ELECTRICAL ARCHITECTURAL
blank. Zone Room ID D1.8 Room Name 0 Functional
worksurface and file storage. Non Public-Non Collection Space 240 Number of Occupants 1 Visual Privacy (full, partial, open) Zone Designation Zone D Room Height 0 LEED NC Regurlarly Occupied Space 0 Base ACOUSTICS Equipment Hardware/STC Rating 0 NRC 0 0 0 Plug Loads Air Change/ HR Walls HVAC ENGINEERING CRITERIA Temperature Lighting 0 0 110v, 20a, 1ph 0 0 Power 0 0 Pressure (+/-) 0 Floor Operable Windows
FURNITURE/EQUIPMENT Moveable 0 Fixed RT60 & Shaping 0 Upper
Separation/STC
Floor Level 0 Room Length,
Open
Width, Shape

This room data sheet is not comprehensive in nature. Information regarding specific room features may not have been available and was intentionally left

Compliance with ADA/ABAAG (2004)citations is required for accessibility. SI also requires compliance with SI Accessibility Guidelines and the IBC. Comparisons should be made and the more stringent requirement followed for design purposes. See Accessibility Narrative for additional information.

Curatorial Affairs Work Stations, Staff Amenities and Meeting Rooms. Additional adjacency information is unavailable at this time pending finalization of organization chart by NMAAHC. SUSTAINABILITY FEATURES Adjacencies

Description Enclosed private office with office furnishings including worksurface

CRITICAL DIMENSIONS

vs. Private

Smithsonian Institution National Museum of African American History and Culture 106 Infrastructure Only 0 Other Amenities Deionized Water Vacuum Yes Speakers OH Gr. 2, 130 SF/HD FIRE ALARM Smoke Detection Yes Wet Sprinkler Special Waste Dry Sprinkler Pre-Action Sprinkler No FIRE PROTECTION 0 Considerations for Water 0 No Floor Drains Floor Sink Grey/Blackwater Piping 0 0 0 0 Protected Hot/Cold 0 0 Recycled Water Supply (treated) 0 0 Public Address Audio Compressed Air Audio Visual Requirements 0 Hot/Cold Water Task Light 0 0 0 Plant/Clean Steam 0 Acoustic Sensitivity 0 Vibration Sensitivity Special Equipment/Artifact Sensitivity PLUMBING Target Illuminance (IES 9th Edition) Daylight Sensor 0 Exhibit Light 0 Power Density (AHSRAE 2004) 0 Temperature Deviations (+/-) 0 0 Process Water UPS Switched Receptacles Dimming 0 Humidity 0 0 Other Humidity Deviation (+/-) 0 0 0 Outside Air Single/Multi-Level Switching 0 Emergency/Standby Power 0 0 0 Occupancy Sensor Special Exhaust Sub-metering & Feedback Displays Filtration (Pre/Final/Other) Voice/Data DATA/TELECOMMUNICATIONS Yes 0 SECURITY 0 0 Floor Loading/Point Loads DAYLIGHTING 0 0 Shading Considerations Top/Side Lighting 0 0 STRUCTURAL 0 0 Refer to information indicated in Volume IV, Section E 0 0 Technical Comment: Publications/Editor/Writer O Assignable Square Feet (ASF) OFEO Space Dimensions 0 Organizational Unit Other Interior Glazing 0 0 0 0 0 Ceiling CRITICAL FINISHES 0 0 0 ELECTRICAL ARCHITECTURAL
blank. Zone Room ID D1.9 Room Name 0 Functional
and file storage. Non Public-Non Collection Space 120 Number of Occupants 1 Visual Privacy (full, partial, open) Zone Designation Zone D Room Height 0 LEED NC Regurlarly Occupied Space 0 Base ACOUSTICS Equipment Hardware/STC Rating 0 NRC 0 0 0 Plug Loads Air Change/ HR Walls HVAC ENGINEERING CRITERIA Temperature Lighting 0 0 110v, 20a, 1ph 0 0 Power 0 0 Pressure (+/-) 0 Floor Operable Windows Separation/STC FURNITURE/EQUIPMENT Moveable 0 Fixed RT60 & Shaping 0 Upper
Floor Level 0 Room Length,
Open
Accessibility Requirement:
Width, Shape

This room data sheet is not comprehensive in nature. Information regarding specific room features may not have been available and was intentionally left blank.

Accessibility Requirement:

Adjacencies

Compliance with ADA/ABAAG (2004) citations is required for accessibility. SI also requires compliance with SI Accessibility Guidelines and the IBC. Comparisons should be made and the more stringent requirement followed for design purposes. An accessible route including a minimum clear width of 36" (except through doors, which must be at least 32" clear) is required. Refer to ADA/ABAAG (2004) for specifications regarding clear floor spaces at desks, files and equipment for individuals using wheelchairs.See Accessibility Narrative for additional information.

Curatorial Affairs Work Stations, Staff Amenities and Meeting Rooms. Additional adjacency information is unavailable at this time pending finalization of organization chart by NMAAHC.

SUSTAINABILITY FEATURES

vs. Private

Please refer to structural narrative for more information on structural requirements.

CRITICAL DIMENSIONS

Length, Width, Shape

107 Room Data Sheets | FREELON BOND Infrastructure Only 0 Other Amenities Deionized Water Vacuum Yes Speakers OH Gr. 2, 130 SF/HD FIRE ALARM Smoke Detection Yes Wet Sprinkler Special Waste Dry Sprinkler Pre-Action Sprinkler No FIRE PROTECTION No Considerations for Water 0 No Floor Drains Floor Sink Grey/Blackwater Piping 0 No No No Protected Hot/Cold No No Recycled Water Supply (treated) 0 No Public Address Audio Compressed Air Audio Visual Requirements No Hot/Cold Water Task Light Yes No 0 Plant/Clean Steam No Acoustic Sensitivity 0 Vibration Sensitivity Special Equipment/Artifact Sensitivity PLUMBING Target Illuminance (IES 9th Edition) Daylight Sensor 0 Exhibit Light Yes Power Density (AHSRAE 2004) 0 Temperature Deviations (+/-) No No Process Water UPS Switched Receptacles Dimming Yes Humidity 0 No Other Humidity Deviation (+/-) As required by load No No Outside Air Single/Multi-Level Switching 0 Emergency/Standby Power As required by code 30/85 Yes Occupancy Sensor Special Exhaust Sub-metering & Feedback Displays Filtration (Pre/Final/Other) Voice/Data DATA/TELECOMMUNICATIONS Yes 0 SECURITY 0 0 Floor Loading/Point Loads DAYLIGHTING 0 0 Shading Considerations Top/Side Lighting 0 0 STRUCTURAL 0 0 Refer to information indicated in Volume IV, Section E 0 0 Technical Comment: CAAMA Office Assignable Square Feet (ASF) OFEO Space Dimensions 0 Organizational Unit Other Interior Glazing 0 0 0 0 0 Ceiling CRITICAL FINISHES 0 0
ELECTRICAL ARCHITECTURAL
Zone Room ID D1.10 Room Name 0 Functional Description Enclosed private office with office furnishings including worksurface
file storage. Non Public-Non Collection Space 240 Number of Occupants 1 Visual Privacy (full, partial, open) Zone Designation Zone D Room Height 0 LEED NC Regurlarly Occupied Space 0 Base ACOUSTICS Equipment Hardware/STC Rating None NRC 0 0 0 Plug Loads Air Change/ HR Walls HVAC ENGINEERING CRITERIA Temperature Lighting No Control ±2ºF 110v, 20a, 1ph Yes 0 Power No 0 Pressure (+/-) 78ºF Summer, 71ºF Winter Floor Operable Windows Separation/STC FURNITURE/EQUIPMENT Moveable 0 Fixed RT60
0 Upper
and
& Shaping
Floor Level 0 Room
Open

This room data sheet is not comprehensive in nature. Information regarding specific room features may not have been available and was intentionally left blank.

Accessibility Requirement:

SUSTAINABILITY FEATURES Adjacencies

Compliance with ADA/ABAAG (2004) citations is required for accessibility. SI also requires compliance with SI Accessibility Guidelines and the IBC. Comparisons should be made and the more stringent requirement followed for design purposes. See Accessibility Narrative for additional information.

Curatorial Affairs Work Stations, Staff Amenities and Meeting Rooms. Additional adjacency information is unavailable at this time pending finalization of organization chart by NMAAHC.

vs. Private CRITICAL DIMENSIONS

Width, Shape

Please refer to structural narrative for more information on structural requirements.

Smithsonian Institution National Museum of African American History and Culture 108 Infrastructure Only 0 Other Amenities Deionized Water Vacuum Yes Speakers OH Gr. 2, 130 SF/HD FIRE ALARM Smoke Detection Yes Wet Sprinkler Special Waste Dry Sprinkler Pre-Action Sprinkler No FIRE PROTECTION No Considerations for Water 0 No Floor Drains Floor Sink Grey/Blackwater Piping 0 No No No Protected Hot/Cold No No Recycled Water Supply (treated) 0 No Public Address Audio Compressed Air Audio Visual Requirements No Hot/Cold Water Task Light Yes No 0 Plant/Clean Steam No Acoustic Sensitivity 0 Vibration Sensitivity Special Equipment/Artifact Sensitivity PLUMBING Target Illuminance (IES 9th Edition) Daylight Sensor 0 Exhibit Light Yes Power Density (AHSRAE 2004) 0 Temperature Deviations (+/-) No No Process Water UPS Switched Receptacles Dimming Yes Humidity 0 No Other Humidity Deviation (+/-) As required by load No No Outside Air Single/Multi-Level Switching 0 Emergency/Standby Power As required by code 30/85 Yes Occupancy Sensor Special Exhaust Sub-metering & Feedback Displays Filtration (Pre/Final/Other) Voice/Data DATA/TELECOMMUNICATIONS Yes 0 SECURITY 0 0 Floor Loading/Point Loads DAYLIGHTING 0 0 Shading Considerations Top/Side Lighting 0 0 STRUCTURAL 0 0 Refer to information indicated in Volume IV, Section E 0 0 Technical Comment: Archives Assignable Square Feet (ASF) OFEO Space Dimensions 0 Organizational Unit Other Interior Glazing 0 0 0 0 0 Ceiling CRITICAL FINISHES 0 0
ELECTRICAL ARCHITECTURAL
Zone Room ID D1.11 Room Name 0 Functional Description Enclosed private office with office furnishings including worksurface
file storage. Non Public-Non Collection Space 240 Number of Occupants 1 Visual Privacy (full, partial, open) Zone Designation Zone D Room Height 0 LEED NC Regurlarly Occupied Space 0 Base ACOUSTICS Equipment Hardware/STC Rating None NRC 0 0 0 Plug Loads Air Change/ HR Walls HVAC ENGINEERING
Temperature Lighting No Control ±2ºF 110v, 20a, 1ph Yes 0 Power No 0 Pressure (+/-) 78ºF Summer, 71ºF Winter Floor Operable Windows Separation/STC FURNITURE/EQUIPMENT Moveable 0 Fixed RT60 & Shaping 0 Upper
and
CRITERIA
Floor Level 0 Room
Open
Length,

This room data sheet is not comprehensive in nature. Information regarding specific room features may not have been available and was intentionally left blank.

Accessibility Requirement:

Adjacencies

SUSTAINABILITY FEATURES

Compliance with ADA/ABAAG (2004) citations is required for accessibility. SI also requires compliance with SI Accessibility Guidelines and the IBC. Comparisons should be made and the more stringent requirement followed for design purposes. An accessible route including a minimum clear width of 36" (except through doors, which must be at least 32" clear) is required. Refer to ADA/ABAAG (2004) for specifications regarding clear floor spaces at desks, files and equipment for individuals using wheelchairs.See Accessibility Narrative for additional information.

Curatorial Affairs Work Stations, Staff Amenities and Meeting Rooms. Additional adjacency information is unavailable at this time pending finalization of organization chart by NMAAHC.

CRITICAL

DIMENSIONS

Length, Width, Shape Open vs. Private

Please refer to structural narrative for more information on structural requirements.

109 Room Data Sheets | FREELON BOND Infrastructure Only 0 Other Amenities Deionized Water Vacuum Yes Speakers OH Gr. 2, 130 SF/HD FIRE ALARM Smoke Detection Yes Wet Sprinkler Special Waste Dry Sprinkler Pre-Action Sprinkler No FIRE PROTECTION No Considerations for Water 0 No Floor Drains Floor Sink Grey/Blackwater Piping 0 No No No Protected Hot/Cold No No Recycled Water Supply (treated) 0 No Public Address Audio Compressed Air Audio Visual Requirements No Hot/Cold Water Task Light Yes No 0 Plant/Clean Steam No Acoustic Sensitivity 0 Vibration Sensitivity Special Equipment/Artifact Sensitivity PLUMBING Target Illuminance (IES 9th Edition) Daylight Sensor 0 Exhibit Light Yes Power Density (AHSRAE 2004) 0 Temperature Deviations (+/-) No No Process Water UPS Switched Receptacles Dimming Yes Humidity 0 No Other Humidity Deviation (+/-) As required by load No No Outside Air Single/Multi-Level Switching 0 Emergency/Standby Power As required by code 30/85 Yes Occupancy Sensor Special Exhaust Sub-metering & Feedback Displays Filtration (Pre/Final/Other) Voice/Data DATA/TELECOMMUNICATIONS Yes 0 SECURITY 0 0 Floor Loading/Point Loads DAYLIGHTING 0 0 Shading Considerations Top/Side Lighting 0 0 STRUCTURAL 0 0 Refer to information indicated in Volume IV, Section E 0 0 Technical Comment: Registration Assignable Square Feet (ASF) OFEO Space Dimensions 0 Organizational Unit Other Interior Glazing 0 0 0 0 0 Ceiling CRITICAL FINISHES 0 0
ELECTRICAL ARCHITECTURAL
Zone Room ID D1.12 Room Name 0 Functional Description Enclosed private office with office furnishings including worksurface
file storage. Non Public-Non Collection Space 240 Number of Occupants 1 Visual Privacy (full, partial, open) Zone Designation Zone D Room Height 0 LEED NC Regurlarly Occupied Space 0 Base ACOUSTICS Equipment Hardware/STC Rating None NRC 0 0 0 Plug Loads Air Change/ HR Walls HVAC ENGINEERING CRITERIA Temperature Lighting No Control ±2ºF 110v, 20a, 1ph Yes 0 Power No 0 Pressure (+/-) 78ºF Summer, 71ºF Winter Floor Operable Windows Separation/STC FURNITURE/EQUIPMENT Moveable 0 Fixed RT60
0 Upper
and
& Shaping
Floor Level 0 Room

This room data sheet is not comprehensive in nature. Information regarding specific room features may not have been available and was intentionally left blank.

Accessibility Requirement:

Adjacencies

SUSTAINABILITY FEATURES

Compliance with ADA/ABAAG (2004) citations is required for accessibility. SI also requires compliance with SI Accessibility Guidelines and the IBC. Comparisons should be made and the more stringent requirement followed for design purposes. An accessible route including a minimum clear width of 36" (except through doors, which must be at least 32" clear) is required. Refer to ADA/ABAAG (2004) for specifications regarding clear floor spaces at desks, files and equipment for individuals using wheelchairs.See Accessibility Narrative for additional information.

Curatorial Affairs Work Stations, Staff Amenities and Meeting Rooms. Additional adjacency information is unavailable at this time pending finalization of organization chart by NMAAHC.

CRITICAL

DIMENSIONS

Length, Width, Shape Open vs. Private

Please refer to structural narrative for more information on structural requirements.

Smithsonian Institution National Museum of African American History and Culture 110 Infrastructure Only 0 Other Amenities Deionized Water Vacuum Yes Speakers OH Gr. 2, 130 SF/HD FIRE ALARM Smoke Detection Yes Wet Sprinkler Special Waste Dry Sprinkler Pre-Action Sprinkler No FIRE PROTECTION No Considerations for Water 0 No Floor Drains Floor Sink Grey/Blackwater Piping 0 No No No Protected Hot/Cold No No Recycled Water Supply (treated) 0 No Public Address Audio Compressed Air Audio Visual Requirements No Hot/Cold Water Task Light Yes No 0 Plant/Clean Steam No Acoustic Sensitivity 0 Vibration Sensitivity Special Equipment/Artifact Sensitivity PLUMBING Target Illuminance (IES 9th Edition) Daylight Sensor 0 Exhibit Light Yes Power Density (AHSRAE 2004) 0 Temperature Deviations (+/-) No No Process Water UPS Switched Receptacles Dimming Yes Humidity 0 No Other Humidity Deviation (+/-) As required by load No No Outside Air Single/Multi-Level Switching 0 Emergency/Standby Power As required by code 30/85 Yes Occupancy Sensor Special Exhaust Sub-metering & Feedback Displays Filtration (Pre/Final/Other) Voice/Data DATA/TELECOMMUNICATIONS Yes 0 SECURITY 0 0 Floor Loading/Point Loads DAYLIGHTING 0 0 Shading Considerations Top/Side Lighting 0 0 STRUCTURAL 0 0 Refer to information indicated in Volume IV, Section E 0 0 Technical Comment: Conservation Assignable Square Feet (ASF) OFEO Space Dimensions 0 Organizational Unit Other Interior Glazing 0 0 0 0 0 Ceiling CRITICAL FINISHES 0 0
ELECTRICAL ARCHITECTURAL
Zone Room ID D1.13 Room Name 0 Functional Description Enclosed private office with office furnishings including worksurface
file storage. Non Public-Non Collection Space 120 Number of Occupants 1 Visual Privacy (full, partial, open) Zone Designation Zone D Room Height 0 LEED NC Regurlarly Occupied Space 0 Base ACOUSTICS Equipment Hardware/STC Rating None NRC 0 0 0 Plug Loads Air Change/ HR Walls HVAC ENGINEERING CRITERIA Temperature Lighting No Control ±2ºF 110v, 20a, 1ph Yes 0 Power No 0 Pressure (+/-) 78ºF Summer, 71ºF Winter Floor Operable Windows Separation/STC FURNITURE/EQUIPMENT Moveable 0 Fixed RT60
0 Upper
and
& Shaping
Floor Level 0 Room

This room data sheet is not comprehensive in nature. Information regarding specific room features may not have been available and was intentionally left blank.

Accessibility Requirement:

Adjacencies

Compliance with ADA/ABAAG (2004) citations is required for accessibility. SI also requires compliance with SI Accessibility Guidelines and the IBC. Comparisons should be made and the more stringent requirement followed for design purposes. An accessible route including a minimum clear width of 36" (except through doors, which must be at least 32" clear) is required. Refer to ADA/ABAAG (2004) for specifications regarding clear floor spaces at desks, files and equipment for individuals using wheelchairs.See Accessibility Narrative for additional information.

Curatorial Affairs Work Stations, Staff Amenities and Meeting Rooms. Additional adjacency information is unavailable at this time pending finalization of organization chart by NMAAHC.

SUSTAINABILITY FEATURES

vs. Private

Please refer to structural narrative for more information on structural requirements.

CRITICAL DIMENSIONS

Length, Width, Shape

111 Room Data Sheets | FREELON BOND Infrastructure Only 0 Other Amenities Deionized Water Vacuum Yes Speakers OH Gr. 2, 130 SF/HD FIRE ALARM Smoke Detection Yes Wet Sprinkler Special Waste Dry Sprinkler Pre-Action Sprinkler No FIRE PROTECTION No Considerations for Water 0 No Floor Drains Floor Sink Grey/Blackwater Piping 0 No No No Protected Hot/Cold No No Recycled Water Supply (treated) 0 No Public Address Audio Compressed Air Audio Visual Requirements No Hot/Cold Water Task Light Yes No 0 Plant/Clean Steam No Acoustic Sensitivity 0 Vibration Sensitivity Special Equipment/Artifact Sensitivity PLUMBING Target Illuminance (IES 9th Edition) Daylight Sensor 0 Exhibit Light Yes Power Density (AHSRAE 2004) 0 Temperature Deviations (+/-) No No Process Water UPS Switched Receptacles Dimming Yes Humidity 0 No Other Humidity Deviation (+/-) As required by load No No Outside Air Single/Multi-Level Switching 0 Emergency/Standby Power As required by code 30/85 Yes Occupancy Sensor Special Exhaust Sub-metering & Feedback Displays Filtration (Pre/Final/Other) Voice/Data DATA/TELECOMMUNICATIONS Yes 0 SECURITY 0 0 Floor Loading/Point Loads DAYLIGHTING 0 0 Shading Considerations Top/Side Lighting 0 0 STRUCTURAL 0 0 Refer to information indicated in Volume IV, Section E 0 0 Technical Comment: Education and Public Programs Assignable Square Feet (ASF) OFEO Space Dimensions 0 Organizational Unit Other Interior Glazing 0 0 0 0 0 Ceiling CRITICAL FINISHES 0 0
ELECTRICAL ARCHITECTURAL
Zone Room ID D1.14 Room Name 0 Functional
Enclosed
office with office furnishings
worksurface
Non Public-Non Collection Space 960 Number of Occupants 1 Visual Privacy (full, partial, open) Zone Designation Zone D Room Height 0 LEED NC Regurlarly Occupied Space 0 Base ACOUSTICS Equipment Hardware/STC Rating None NRC 0 0 0 Plug Loads Air Change/ HR Walls HVAC ENGINEERING CRITERIA Temperature Lighting No Control ±2ºF 110v, 20a, 1ph Yes 0 Power No 0 Pressure (+/-) 78ºF Summer, 71ºF Winter Floor Operable Windows Separation/STC FURNITURE/EQUIPMENT Moveable 0 Fixed RT60
0 Upper
Description
private
including
and file storage.
& Shaping
Floor Level 0 Room
Open

This room data sheet is not comprehensive in nature. Information regarding specific room features may not have been available and was intentionally left blank.

Accessibility Requirement:

Adjacencies

Compliance with ADA/ABAAG (2004) citations is required for accessibility. SI also requires compliance with SI Accessibility Guidelines and the IBC. Comparisons should be made and the more stringent requirement followed for design purposes. An accessible route including a minimum clear width of 36" (except through doors, which must be at least 32" clear) is required. Refer to ADA/ABAAG (2004) for specifications regarding clear floor spaces at desks, files and equipment for individuals using wheelchairs.See Accessibility Narrative for additional information.

Curatorial Affairs Work Stations, Staff Amenities and Meeting Rooms. Additional adjacency information is unavailable at this time pending finalization of organization chart by NMAAHC.

SUSTAINABILITY FEATURES

vs. Private

Please refer to structural narrative for more information on structural requirements.

CRITICAL DIMENSIONS

Length, Width, Shape

Smithsonian Institution National Museum of African American History and Culture 112 Infrastructure Only 0 Other Amenities Deionized Water Vacuum Yes Speakers OH Gr. 2, 130 SF/HD FIRE ALARM Smoke Detection Yes Wet Sprinkler Special Waste Dry Sprinkler Pre-Action Sprinkler No FIRE PROTECTION No Considerations for Water 0 No Floor Drains Floor Sink Grey/Blackwater Piping 0 No No No Protected Hot/Cold No No Recycled Water Supply (treated) 0 No Public Address Audio Compressed Air Audio Visual Requirements No Hot/Cold Water Task Light Yes No 0 Plant/Clean Steam No Acoustic Sensitivity 0 Vibration Sensitivity Special Equipment/Artifact Sensitivity PLUMBING Target Illuminance (IES 9th Edition) Daylight Sensor 0 Exhibit Light Yes Power Density (AHSRAE 2004) 0 Temperature Deviations (+/-) No No Process Water UPS Switched Receptacles Dimming Yes Humidity 0 No Other Humidity Deviation (+/-) As required by load No No Outside Air Single/Multi-Level Switching 0 Emergency/Standby Power As required by code 30/85 Yes Occupancy Sensor Special Exhaust Sub-metering & Feedback Displays Filtration (Pre/Final/Other) Voice/Data DATA/TELECOMMUNICATIONS Yes 0 SECURITY 0 0 Floor Loading/Point Loads DAYLIGHTING 0 0 Shading Considerations Top/Side Lighting 0 0 STRUCTURAL 0 0 Refer to information indicated in Volume IV, Section E 0 0 Technical Comment: Resource Center Assignable Square Feet (ASF) OFEO Space Dimensions 0 Organizational Unit Other Interior Glazing 0 0 0 0 0 Ceiling CRITICAL FINISHES 0 0
ELECTRICAL ARCHITECTURAL
Zone Room ID D1.15 Room Name 0 Functional Description Enclosed private office with office
worksurface
file storage. Non Public-Non Collection Space 120 Number of Occupants 1 Visual Privacy (full, partial, open) Zone Designation Zone D Room Height 0 LEED NC Regurlarly Occupied Space 0 Base ACOUSTICS Equipment Hardware/STC Rating None NRC 0 0 0 Plug Loads Air Change/ HR Walls HVAC ENGINEERING CRITERIA Temperature Lighting No Control ±2ºF 110v, 20a, 1ph Yes 0 Power No 0 Pressure (+/-) 78ºF Summer, 71ºF Winter Floor Operable Windows Separation/STC FURNITURE/EQUIPMENT Moveable 0 Fixed RT60
0 Upper
furnishings including
and
& Shaping
Floor Level 0 Room
Open

This room data sheet is not comprehensive in nature. Information regarding specific room features may not have been available and was intentionally left blank.

Accessibility Requirement:

Adjacencies

Compliance with ADA/ABAAG (2004) citations is required for accessibility. SI also requires compliance with SI Accessibility Guidelines and the IBC. Comparisons should be made and the more stringent requirement followed for design purposes. An accessible route including a minimum clear width of 36" (except through doors, which must be at least 32" clear) is required. Refer to ADA/ABAAG (2004) for specifications regarding clear floor spaces at desks, files and equipment for individuals using wheelchairs.See Accessibility Narrative for additional information.

Curatorial Affairs Work Stations, Staff Amenities and Meeting Rooms. Additional adjacency information is unavailable at this time pending finalization of organization chart by NMAAHC.

SUSTAINABILITY FEATURES

vs. Private

Please refer to structural narrative for more information on structural requirements.

CRITICAL DIMENSIONS

Length, Width, Shape

113 Room Data Sheets | FREELON BOND Infrastructure Only 0 Other Amenities Deionized Water Vacuum Yes Speakers OH Gr. 2, 130 SF/HD FIRE ALARM Smoke Detection Yes Wet Sprinkler Special Waste Dry Sprinkler Pre-Action Sprinkler No FIRE PROTECTION No Considerations for Water 0 No Floor Drains Floor Sink Grey/Blackwater Piping 0 No No No Protected Hot/Cold No No Recycled Water Supply (treated) 0 No Public Address Audio Compressed Air Audio Visual Requirements No Hot/Cold Water Task Light Yes No 0 Plant/Clean Steam No Acoustic Sensitivity 0 Vibration Sensitivity Special Equipment/Artifact Sensitivity PLUMBING Target Illuminance (IES 9th Edition) Daylight Sensor 0 Exhibit Light Yes Power Density (AHSRAE 2004) 0 Temperature Deviations (+/-) No No Process Water UPS Switched Receptacles Dimming Yes Humidity 0 No Other Humidity Deviation (+/-) As required by load No No Outside Air Single/Multi-Level Switching 0 Emergency/Standby Power As required by code 30/85 Yes Occupancy Sensor Special Exhaust Sub-metering & Feedback Displays Filtration (Pre/Final/Other) Voice/Data DATA/TELECOMMUNICATIONS Yes 0 SECURITY 0 0 Floor Loading/Point Loads DAYLIGHTING 0 0 Shading Considerations Top/Side Lighting 0 0 STRUCTURAL 0 0 Refer to information indicated in Volume IV, Section E 0 0 Technical Comment: Web and New Media Assignable Square Feet (ASF) OFEO Space Dimensions 0 Organizational Unit Other Interior Glazing 0 0 0 0 0 Ceiling CRITICAL FINISHES 0 0
ELECTRICAL ARCHITECTURAL
Zone Room ID D1.16 Room Name 0 Functional Description Enclosed
office with office furnishings including worksurface
file
Non Public-Non Collection Space 360 Number of Occupants 1 Visual Privacy (full, partial, open) Zone Designation Zone D Room Height 0 LEED NC Regurlarly Occupied Space 0 Base ACOUSTICS Equipment Hardware/STC Rating None NRC 0 0 0 Plug Loads Air Change/ HR Walls HVAC ENGINEERING CRITERIA Temperature Lighting No Control ±2ºF 110v, 20a, 1ph Yes 0 Power No 0 Pressure (+/-) 78ºF Summer, 71ºF Winter Floor Operable Windows Separation/STC FURNITURE/EQUIPMENT Moveable 0 Fixed RT60
0 Upper
private
and
storage.
& Shaping
Floor Level 0 Room
Open

This room data sheet is not comprehensive in nature. Information regarding specific room features may not have been available and was intentionally left blank.

Accessibility Requirement:

Adjacencies

SUSTAINABILITY FEATURES

Compliance with ADA/ABAAG (2004) citations is required for accessibility. SI also requires compliance with SI Accessibility Guidelines and the IBC. Comparisons should be made and the more stringent requirement followed for design purposes. An accessible route including a minimum clear width of 36" (except through doors, which must be at least 32" clear) is required. Refer to ADA/ABAAG (2004) for specifications regarding clear floor spaces at desks, files and equipment for individuals using wheelchairs.See Accessibility Narrative for additional information.

Curatorial Affairs Work Stations, Staff Amenities and Meeting Rooms. Additional adjacency information is unavailable at this time pending finalization of organization chart by NMAAHC.

CRITICAL

DIMENSIONS

Length, Width, Shape Open vs. Private

Please refer to structural narrative for more information on structural requirements.

Smithsonian Institution National Museum of African American History and Culture 114 Infrastructure Only 0 Other Amenities Deionized Water Vacuum Yes Speakers OH Gr. 2, 130 SF/HD FIRE ALARM Smoke Detection Yes Wet Sprinkler Special Waste Dry Sprinkler Pre-Action Sprinkler No FIRE PROTECTION No Considerations for Water 0 No Floor Drains Floor Sink Grey/Blackwater Piping 0 No No No Protected Hot/Cold No No Recycled Water Supply (treated) 0 No Public Address Audio Compressed Air Audio Visual Requirements No Hot/Cold Water Task Light Yes No 0 Plant/Clean Steam No Acoustic Sensitivity 0 Vibration Sensitivity Special Equipment/Artifact Sensitivity PLUMBING Target Illuminance (IES 9th Edition) Daylight Sensor 0 Exhibit Light Yes Power Density (AHSRAE 2004) 0 Temperature Deviations (+/-) No No Process Water UPS Switched Receptacles Dimming Yes Humidity 0 No Other Humidity Deviation (+/-) As required by load No No Outside Air Single/Multi-Level Switching 0 Emergency/Standby Power As required by code 30/85 Yes Occupancy Sensor Special Exhaust Sub-metering & Feedback Displays Filtration (Pre/Final/Other) Voice/Data DATA/TELECOMMUNICATIONS Yes 0 SECURITY 0 0 Floor Loading/Point Loads DAYLIGHTING 0 0 Shading Considerations Top/Side Lighting 0 0 STRUCTURAL 0 0 Refer to information indicated in Volume IV, Section E 0 0 Technical Comment: Interns/Fellows Coordinator Assignable Square Feet (ASF) OFEO Space Dimensions 0 Organizational Unit Other Interior Glazing 0 0 0 0 0 Ceiling CRITICAL FINISHES 0 0
ELECTRICAL ARCHITECTURAL
Zone Room ID D1.17 Room Name 0 Functional Description Enclosed private office with office furnishings including worksurface and file storage. Non Public-Non Collection Space 120 Number of Occupants 1 Visual Privacy (full, partial, open) Zone Designation Zone D Room Height 0 LEED NC Regurlarly Occupied
0 Base ACOUSTICS Equipment Hardware/STC Rating None NRC 0 0 0 Plug Loads Air Change/ HR Walls HVAC ENGINEERING
Temperature Lighting No Control ±2ºF 110v, 20a, 1ph Yes 0 Power No 0 Pressure (+/-) 78ºF Summer, 71ºF Winter Floor Operable Windows Separation/STC FURNITURE/EQUIPMENT Moveable 0 Fixed RT60 &
0 Upper
Space
CRITERIA
Shaping
Floor Level 0 Room

This room data sheet is not comprehensive in nature. Information regarding specific room features may not have been available and was intentionally left blank.

Accessibility Requirement:

Adjacencies

Compliance with ADA/ABAAG (2004) citations is required for accessibility. SI also requires compliance with SI Accessibility Guidelines and the IBC. Comparisons should be made and the more stringent requirement followed for design purposes. An accessible route including a minimum clear width of 36" (except through doors, which must be at least 32" clear) is required. Refer to ADA/ABAAG (2004) for specifications regarding clear floor spaces at desks, files and equipment for individuals using wheelchairs.See Accessibility Narrative for additional information.

Curatorial Affairs Work Stations, Staff Amenities and Meeting Rooms. Additional adjacency information is unavailable at this time pending finalization of organization chart by NMAAHC.

SUSTAINABILITY FEATURES

vs. Private

Please refer to structural narrative for more information on structural requirements.

CRITICAL DIMENSIONS

Length, Width, Shape

115 Room Data Sheets | FREELON BOND Infrastructure Only 0 Other Amenities Deionized Water Vacuum Yes Speakers OH Gr. 2, 130 SF/HD FIRE ALARM Smoke Detection Yes Wet Sprinkler Special Waste Dry Sprinkler Pre-Action Sprinkler No FIRE PROTECTION No Considerations for Water 0 No Floor Drains Floor Sink Grey/Blackwater Piping 0 No No No Protected Hot/Cold No No Recycled Water Supply (treated) 0 No Public Address Audio Compressed Air Audio Visual Requirements No Hot/Cold Water Task Light Yes No 0 Plant/Clean Steam No Acoustic Sensitivity 0 Vibration Sensitivity Special Equipment/Artifact Sensitivity PLUMBING Target Illuminance (IES 9th Edition) Daylight Sensor 0 Exhibit Light Yes Power Density (AHSRAE 2004) 0 Temperature Deviations (+/-) No No Process Water UPS Switched Receptacles Dimming Yes Humidity 0 No Other Humidity Deviation (+/-) As required by load No No Outside Air Single/Multi-Level Switching 0 Emergency/Standby Power As required by code 30/85 Yes Occupancy Sensor Special Exhaust Sub-metering & Feedback Displays Filtration (Pre/Final/Other) Voice/Data DATA/TELECOMMUNICATIONS Yes 0 SECURITY 0 0 Floor Loading/Point Loads DAYLIGHTING 0 0 Shading Considerations Top/Side Lighting 0 0 STRUCTURAL 0 0 Refer to information indicated in Volume IV, Section E 0 0 Technical Comment: Docent Coordinator Assignable Square Feet (ASF) OFEO Space Dimensions 0 Organizational Unit Other Interior Glazing 0 0 0 0 0 Ceiling CRITICAL FINISHES 0 0
ELECTRICAL ARCHITECTURAL
Zone Room ID D1.18 Room Name 0 Functional Description Enclosed private office with office furnishings including worksurface
file storage. Non Public-Non Collection Space 120 Number of Occupants 1 Visual Privacy (full, partial, open) Zone Designation Zone D Room Height 0 LEED NC Regurlarly Occupied Space 0 Base ACOUSTICS Equipment Hardware/STC Rating None NRC 0 0 0 Plug Loads Air Change/ HR Walls HVAC ENGINEERING CRITERIA Temperature Lighting No Control ±2ºF 110v, 20a, 1ph Yes 0 Power No 0 Pressure (+/-) 78ºF Summer, 71ºF Winter Floor Operable Windows Separation/STC FURNITURE/EQUIPMENT Moveable 0 Fixed RT60
0 Upper
and
& Shaping
Floor Level 0 Room
Open

This room data sheet is not comprehensive in nature. Information regarding specific room features may not have been available and was intentionally left blank.

Accessibility Requirement:

Adjacencies

Compliance with ADA/ABAAG (2004) citations is required for accessibility. SI also requires compliance with SI Accessibility Guidelines and the IBC. Comparisons should be made and the more stringent requirement followed for design purposes. An accessible route including a minimum clear width of 36" (except through doors, which must be at least 32" clear) is required. Refer to ADA/ABAAG (2004) for specifications regarding clear floor spaces at desks, files and equipment for individuals using wheelchairs.See Accessibility Narrative for additional information.

Curatorial Affairs Work Stations, Staff Amenities and Meeting Rooms. Additional adjacency information is unavailable at this time pending finalization of organization chart by NMAAHC.

SUSTAINABILITY FEATURES

vs. Private

Please refer to structural narrative for more information on structural requirements.

CRITICAL DIMENSIONS

Length, Width, Shape

Smithsonian Institution National Museum of African American History and Culture 116 Infrastructure Only 0 Other Amenities Deionized Water Vacuum Yes Speakers OH Gr. 2, 130 SF/HD FIRE ALARM Smoke Detection Yes Wet Sprinkler Special Waste Dry Sprinkler Pre-Action Sprinkler No FIRE PROTECTION No Considerations for Water 0 No Floor Drains Floor Sink Grey/Blackwater Piping 0 No No No Protected Hot/Cold No No Recycled Water Supply (treated) 0 No Public Address Audio Compressed Air Audio Visual Requirements No Hot/Cold Water Task Light Yes No 0 Plant/Clean Steam No Acoustic Sensitivity 0 Vibration Sensitivity Special Equipment/Artifact Sensitivity PLUMBING Target Illuminance (IES 9th Edition) Daylight Sensor 0 Exhibit Light Yes Power Density (AHSRAE 2004) 0 Temperature Deviations (+/-) No No Process Water UPS Switched Receptacles Dimming Yes Humidity 0 No Other Humidity Deviation (+/-) As required by load No No Outside Air Single/Multi-Level Switching 0 Emergency/Standby Power As required by code 30/85 Yes Occupancy Sensor Special Exhaust Sub-metering & Feedback Displays Filtration (Pre/Final/Other) Voice/Data DATA/TELECOMMUNICATIONS Yes 0 SECURITY 0 0 Floor Loading/Point Loads DAYLIGHTING 0 0 Shading Considerations Top/Side Lighting 0 0 STRUCTURAL 0 0 Refer to information indicated in Volume IV, Section E 0 0 Technical Comment: Visitor Services Assignable Square Feet (ASF) OFEO Space Dimensions 0 Organizational Unit Other Interior Glazing 0 0 0 0 0 Ceiling CRITICAL FINISHES 0 0
ELECTRICAL ARCHITECTURAL
Zone Room ID D1.19 Room Name 0 Functional Description Enclosed private office with office furnishings including worksurface
file storage. Non Public-Non Collection Space 120 Number of Occupants 1 Visual Privacy (full, partial, open) Zone Designation Zone D Room Height 0 LEED NC Regurlarly Occupied Space 0 Base ACOUSTICS Equipment Hardware/STC Rating None NRC 0 0 0 Plug Loads Air Change/ HR Walls HVAC ENGINEERING CRITERIA Temperature Lighting No Control ±2ºF 110v, 20a, 1ph Yes 0 Power No 0 Pressure (+/-) 78ºF Summer, 71ºF Winter Floor Operable Windows Separation/STC FURNITURE/EQUIPMENT Moveable 0 Fixed RT60
0 Upper
and
& Shaping
Floor Level 0 Room
Open

This room data sheet is not comprehensive in nature. Information regarding specific room features may not have been available and was intentionally left blank.

Accessibility Requirement:

Adjacencies

Compliance with ADA/ABAAG (2004) citations is required for accessibility. SI also requires compliance with SI Accessibility Guidelines and the IBC. Comparisons should be made and the more stringent requirement followed for design purposes. An accessible route including a minimum clear width of 36" (except through doors, which must be at least 32" clear) is required. Refer to ADA/ABAAG (2004) for specifications regarding clear floor spaces at desks, files and equipment for individuals using wheelchairs.See Accessibility Narrative for additional information.

Curatorial Affairs Work Stations, Staff Amenities and Meeting Rooms. Additional adjacency information is unavailable at this time pending finalization of organization chart by NMAAHC.

SUSTAINABILITY FEATURES

vs. Private

Please refer to structural narrative for more information on structural requirements.

CRITICAL

DIMENSIONS

Length, Width, Shape

117 Room Data Sheets | FREELON BOND Infrastructure Only 0 Other Amenities Deionized Water Vacuum Yes Speakers OH Gr. 2, 130 SF/HD FIRE ALARM Smoke Detection Yes Wet Sprinkler Special Waste Dry Sprinkler Pre-Action Sprinkler No FIRE PROTECTION No Considerations for Water 0 No Floor Drains Floor Sink Grey/Blackwater Piping 0 No No No Protected Hot/Cold No No Recycled Water Supply (treated) 0 No Public Address Audio Compressed Air Audio Visual Requirements No Hot/Cold Water Task Light Yes No 0 Plant/Clean Steam No Acoustic Sensitivity 0 Vibration Sensitivity Special Equipment/Artifact Sensitivity PLUMBING Target Illuminance (IES 9th Edition) Daylight Sensor 0 Exhibit Light Yes Power Density (AHSRAE 2004) 0 Temperature Deviations (+/-) No No Process Water UPS Switched Receptacles Dimming Yes Humidity 0 No Other Humidity Deviation (+/-) As required by load No No Outside Air Single/Multi-Level Switching 0 Emergency/Standby Power As required by code 30/85 Yes Occupancy Sensor Special Exhaust Sub-metering & Feedback Displays Filtration (Pre/Final/Other) Voice/Data DATA/TELECOMMUNICATIONS Yes 0 SECURITY 0 0 Floor Loading/Point Loads DAYLIGHTING 0 0 Shading Considerations Top/Side Lighting 0 0 STRUCTURAL 0 0 Refer to information indicated in Volume IV, Section E 0 0 Technical Comment: Partnerships/Scholarly Programs Assignable Square Feet (ASF) OFEO Space Dimensions 0 Organizational Unit Other Interior Glazing 0 0 0 0 0 Ceiling CRITICAL FINISHES 0 0
ELECTRICAL ARCHITECTURAL
Zone Room ID D1.20 Room Name 0 Functional Description Enclosed private office with office furnishings including worksurface and file storage. Non Public-Non Collection Space 240 Number of Occupants 1 Visual Privacy (full, partial, open) Zone Designation Zone D Room Height 0 LEED NC Regurlarly Occupied
0 Base ACOUSTICS Equipment Hardware/STC Rating None NRC 0 0 0 Plug Loads Air Change/ HR Walls HVAC ENGINEERING CRITERIA Temperature Lighting No Control ±2ºF 110v, 20a, 1ph Yes 0 Power No 0 Pressure (+/-) 78ºF Summer, 71ºF Winter Floor Operable Windows Separation/STC FURNITURE/EQUIPMENT Moveable 0 Fixed RT60 &
0 Upper
Space
Shaping
Floor Level 0 Room
Open

This room data sheet is not comprehensive in nature. Information regarding specific room features may not have been available and was intentionally left blank.

Accessibility Requirement:

Adjacencies

Compliance with ADA/ABAAG (2004) citations is required for accessibility. SI also requires compliance with SI Accessibility Guidelines and the IBC. Comparisons should be made and the more stringent requirement followed for design purposes. An accessible route including a minimum clear width of 36" (except through doors, which must be at least 32" clear) is required. Refer to ADA/ABAAG (2004) for specifications regarding clear floor spaces at desks, files and equipment for individuals using wheelchairs.See Accessibility Narrative for additional information.

Curatorial Affairs Work Stations, Staff Amenities and Meeting Rooms. Additional adjacency information is unavailable at this time pending finalization of organization chart by NMAAHC.

SUSTAINABILITY FEATURES

vs. Private

Please refer to structural narrative for more information on structural requirements.

CRITICAL DIMENSIONS

Length, Width, Shape

Smithsonian Institution National Museum of African American History and Culture 118 Infrastructure Only 0 Other Amenities Deionized Water Vacuum Yes Speakers OH Gr. 2, 130 SF/HD FIRE ALARM Smoke Detection Yes Wet Sprinkler Special Waste Dry Sprinkler Pre-Action Sprinkler No FIRE PROTECTION No Considerations for Water 0 No Floor Drains Floor Sink Grey/Blackwater Piping 0 No No No Protected Hot/Cold No No Recycled Water Supply (treated) 0 No Public Address Audio Compressed Air Audio Visual Requirements No Hot/Cold Water Task Light Yes No 0 Plant/Clean Steam No Acoustic Sensitivity 0 Vibration Sensitivity Special Equipment/Artifact Sensitivity PLUMBING Target Illuminance (IES 9th Edition) Daylight Sensor 0 Exhibit Light Yes Power Density (AHSRAE 2004) 0 Temperature Deviations (+/-) No No Process Water UPS Switched Receptacles Dimming Yes Humidity 0 No Other Humidity Deviation (+/-) As required by load No No Outside Air Single/Multi-Level Switching 0 Emergency/Standby Power As required by code 30/85 Yes Occupancy Sensor Special Exhaust Sub-metering & Feedback Displays Filtration (Pre/Final/Other) Voice/Data DATA/TELECOMMUNICATIONS Yes 0 SECURITY 0 0 Floor Loading/Point Loads DAYLIGHTING 0 0 Shading Considerations Top/Side Lighting 0 0 STRUCTURAL 0 0 Refer to information indicated in Volume IV, Section E 0 0 Technical Comment: Local Programs Assignable Square Feet (ASF) OFEO Space Dimensions 0 Organizational Unit Other Interior Glazing 0 0 0 0 0 Ceiling CRITICAL FINISHES 0 0
ELECTRICAL ARCHITECTURAL
Zone Room ID D1.21 Room Name 0 Functional Description Enclosed private office with office furnishings
worksurface
file storage. Non Public-Non Collection Space 120 Number of Occupants 1 Visual Privacy (full, partial, open) Zone Designation Zone D Room Height 0 LEED NC Regurlarly Occupied Space 0 Base ACOUSTICS Equipment Hardware/STC Rating None NRC 0 0 0 Plug Loads Air Change/ HR Walls HVAC ENGINEERING CRITERIA Temperature Lighting No Control ±2ºF 110v, 20a, 1ph Yes 0 Power No 0 Pressure (+/-) 78ºF Summer, 71ºF Winter Floor Operable Windows Separation/STC FURNITURE/EQUIPMENT Moveable 0 Fixed RT60
0 Upper
including
and
& Shaping
Floor Level 0 Room
Open

This room data sheet is not comprehensive in nature. Information regarding specific room features may not have been available and was intentionally left blank.

Adjacencies

Compliance with ADA/ABAAG (2004) citations is required for accessibility. SI also requires compliance with SI Accessibility Guidelines and the IBC. Comparisons should be made and the more stringent requirement followed for design purposes. An accessible route including a minimum clear width of 36" (except through doors, which must be at least 32" clear) is required. Refer to ADA/ABAAG (2004) for specifications regarding clear floor spaces at desks, files and equipment for individuals using wheelchairs.See Accessibility Narrative for additional information.

Development & Public Affairs Work Stations, Staff Amenities, and Meeting Rooms. Additional adjacency information is unavailable at this time pending finalization of organization chart by NMAAHC. SUSTAINABILITY FEATURES

CRITICAL DIMENSIONS

Please refer to structural narrative for more information on structural requirements.

119 Room Data Sheets | FREELON BOND Infrastructure Only 0 Other Amenities Deionized Water Vacuum Yes Speakers OH Gr. 2, 130 SF/HD FIRE ALARM Smoke Detection Yes Wet Sprinkler Special Waste Dry Sprinkler Pre-Action Sprinkler No FIRE PROTECTION No Considerations for Water 0 No Floor Drains Floor Sink Grey/Blackwater Piping 0 No No No Protected Hot/Cold No No Recycled Water Supply (treated) 0 No Public Address Audio Compressed Air Audio Visual Requirements No Hot/Cold Water Task Light Yes No 0 Plant/Clean Steam No Acoustic Sensitivity 0 Vibration Sensitivity Special Equipment/Artifact Sensitivity PLUMBING Target Illuminance (IES 9th Edition) Daylight Sensor 0 Exhibit Light Yes Power Density (AHSRAE 2004) 0 Temperature Deviations (+/-) No No Process Water UPS Switched Receptacles Dimming Yes Humidity 0 No Other Humidity Deviation (+/-) As required by load No No Outside Air Single/Multi-Level Switching 0 Emergency/Standby Power As required by code 30/85 Yes Occupancy Sensor Special Exhaust Sub-metering & Feedback Displays Filtration (Pre/Final/Other) Voice/Data DATA/TELECOMMUNICATIONS Yes 0 SECURITY 0 0 Floor Loading/Point Loads DAYLIGHTING 0 0 Shading Considerations Top/Side Lighting 0 0 STRUCTURAL 0 0 Refer to information indicated in Volume IV, Section E 0 0 Technical Comment: Associate Director 2 Assignable Square Feet (ASF) OFEO Space Dimensions 0 Organizational Unit Other Interior Glazing 0 0 0 0 0 Ceiling CRITICAL FINISHES 0 0
ELECTRICAL ARCHITECTURAL
Zone Room ID D1.22 Room Name 0 Functional Description Enclosed private office with office furnishings including worksurface, file storage and additional seating area for reception of VIP guests. Non Public-Non Collection Space 280 Number of Occupants 1 Visual Privacy (full, partial, open) Zone Designation Zone D Room Height 0 LEED NC
0 Base ACOUSTICS Equipment Hardware/STC Rating None NRC 0 0 0 Plug Loads Air Change/ HR Walls HVAC ENGINEERING CRITERIA Temperature Lighting No Control ±2ºF 110v, 20a, 1ph Yes 0 Power No 0 Pressure (+/-) 78ºF Summer, 71ºF Winter Floor Operable Windows Separation/STC FURNITURE/EQUIPMENT Moveable 0 Fixed RT60 & Shaping 0 Upper
Regurlarly Occupied Space
Floor Level 0 Room
Accessibility Requirement:
Length, Width, Shape Open vs. Private

This room data sheet is not comprehensive in nature. Information regarding specific room features may not have been available and was intentionally left blank.

Accessibility Requirement:

Adjacencies

Compliance with ADA/ABAAG (2004) citations is required for accessibility. SI also requires compliance with SI Accessibility Guidelines and the IBC. Comparisons should be made and the more stringent requirement followed for design purposes. An accessible route including a minimum clear width of 36" (except through doors, which must be at least 32" clear) is required. Refer to ADA/ABAAG (2004) for specifications regarding clear floor spaces at desks, files and equipment for individuals using wheelchairs.See Accessibility Narrative for additional information.

Development & Public Affairs Work Stations, Staff Amenities, and Meeting Rooms. Additional adjacency information is unavailable at this time pending finalization of organization chart by NMAAHC.

SUSTAINABILITY FEATURES

vs. Private

Please refer to structural narrative for more information on structural requirements.

CRITICAL DIMENSIONS

Length, Width, Shape

Smithsonian Institution National Museum of African American History and Culture 120 Infrastructure Only 0 Other Amenities Deionized Water Vacuum Yes Speakers OH Gr. 2, 130 SF/HD FIRE ALARM Smoke Detection Yes Wet Sprinkler Special Waste Dry Sprinkler Pre-Action Sprinkler No FIRE PROTECTION No Considerations for Water 0 No Floor Drains Floor Sink Grey/Blackwater Piping 0 No No No Protected Hot/Cold No No Recycled Water Supply (treated) 0 No Public Address Audio Compressed Air Audio Visual Requirements No Hot/Cold Water Task Light Yes No 0 Plant/Clean Steam No Acoustic Sensitivity 0 Vibration Sensitivity Special Equipment/Artifact Sensitivity PLUMBING Target Illuminance (IES 9th Edition) Daylight Sensor 0 Exhibit Light Yes Power Density (AHSRAE 2004) 0 Temperature Deviations (+/-) No No Process Water UPS Switched Receptacles Dimming Yes Humidity 0 No Other Humidity Deviation (+/-) As required by load No No Outside Air Single/Multi-Level Switching 0 Emergency/Standby Power As required by code 30/85 Yes Occupancy Sensor Special Exhaust Sub-metering & Feedback Displays Filtration (Pre/Final/Other) Voice/Data DATA/TELECOMMUNICATIONS Yes 0 SECURITY 0 0 Floor Loading/Point Loads DAYLIGHTING 0 0 Shading Considerations Top/Side Lighting 0 0 STRUCTURAL 0 0 Refer to information indicated in Volume IV, Section E 0 0 Technical Comment: Development Assignable Square Feet (ASF) OFEO Space Dimensions 0 Organizational Unit Other Interior Glazing 0 0 0 0 0 Ceiling CRITICAL FINISHES 0 0
ELECTRICAL ARCHITECTURAL
Zone Room ID D1.23 Room Name 0 Functional Description Enclosed private office with office furnishings
worksurface
file storage. Non Public-Non Collection Space 960 Number of Occupants 1 Visual Privacy (full, partial, open) Zone Designation Zone D Room Height 0 LEED NC Regurlarly Occupied Space 0 Base ACOUSTICS Equipment Hardware/STC Rating None NRC 0 0 0 Plug Loads Air Change/ HR Walls HVAC ENGINEERING CRITERIA Temperature Lighting No Control ±2ºF 110v, 20a, 1ph Yes 0 Power No 0 Pressure (+/-) 78ºF Summer, 71ºF Winter Floor Operable Windows Separation/STC FURNITURE/EQUIPMENT Moveable 0 Fixed RT60
0 Upper
including
and
& Shaping
Floor Level 0 Room
Open

This room data sheet is not comprehensive in nature. Information regarding specific room features may not have been available and was intentionally left blank.

Accessibility Requirement:

Adjacencies

Compliance with ADA/ABAAG (2004) citations is required for accessibility. SI also requires compliance with SI Accessibility Guidelines and the IBC. Comparisons should be made and the more stringent requirement followed for design purposes. An accessible route including a minimum clear width of 36" (except through doors, which must be at least 32" clear) is required. Refer to ADA/ABAAG (2004) for specifications regarding clear floor spaces at desks, files and equipment for individuals using wheelchairs.See Accessibility Narrative for additional information.

Development & Public Affairs Work Stations, Staff Amenities, and Meeting Rooms. Additional adjacency information is unavailable at this time pending finalization of organization chart by NMAAHC.

SUSTAINABILITY FEATURES

vs. Private

Please refer to structural narrative for more information on structural requirements.

CRITICAL DIMENSIONS

Length, Width, Shape

121 Room Data Sheets | FREELON BOND Infrastructure Only 0 Other Amenities Deionized Water Vacuum Yes Speakers OH Gr. 2, 130 SF/HD FIRE ALARM Smoke Detection Yes Wet Sprinkler Special Waste Dry Sprinkler Pre-Action Sprinkler No FIRE PROTECTION No Considerations for Water 0 No Floor Drains Floor Sink Grey/Blackwater Piping 0 No No No Protected Hot/Cold No No Recycled Water Supply (treated) 0 No Public Address Audio Compressed Air Audio Visual Requirements No Hot/Cold Water Task Light Yes No 0 Plant/Clean Steam No Acoustic Sensitivity 0 Vibration Sensitivity Special Equipment/Artifact Sensitivity PLUMBING Target Illuminance (IES 9th Edition) Daylight Sensor 0 Exhibit Light Yes Power Density (AHSRAE 2004) 0 Temperature Deviations (+/-) No No Process Water UPS Switched Receptacles Dimming Yes Humidity 0 No Other Humidity Deviation (+/-) As required by load No No Outside Air Single/Multi-Level Switching 0 Emergency/Standby Power As required by code 30/85 Yes Occupancy Sensor Special Exhaust Sub-metering & Feedback Displays Filtration (Pre/Final/Other) Voice/Data DATA/TELECOMMUNICATIONS Yes 0 SECURITY 0 0 Floor Loading/Point Loads DAYLIGHTING 0 0 Shading Considerations Top/Side Lighting 0 0 STRUCTURAL 0 0 Refer to information indicated in Volume IV, Section E 0 0 Technical Comment: Special Events Assignable Square Feet (ASF) OFEO Space Dimensions 0 Organizational Unit Other Interior Glazing 0 0 0 0 0 Ceiling CRITICAL FINISHES 0 0
ELECTRICAL ARCHITECTURAL
Zone Room ID D1.24 Room Name 0 Functional Description Enclosed private office with office furnishings
worksurface
file storage. Non Public-Non Collection Space 120 Number of Occupants 1 Visual Privacy (full, partial, open) Zone Designation Zone D Room Height 0 LEED NC Regurlarly Occupied Space 0 Base ACOUSTICS Equipment Hardware/STC Rating None NRC 0 0 0 Plug Loads Air Change/ HR Walls HVAC ENGINEERING CRITERIA Temperature Lighting No Control ±2ºF 110v, 20a, 1ph Yes 0 Power No 0 Pressure (+/-) 78ºF Summer, 71ºF Winter Floor Operable Windows Separation/STC FURNITURE/EQUIPMENT Moveable 0 Fixed RT60
0 Upper
including
and
& Shaping
Floor Level 0 Room
Open

This room data sheet is not comprehensive in nature. Information regarding specific room features may not have been available and was intentionally left blank.

Accessibility Requirement:

Adjacencies

Compliance with ADA/ABAAG (2004) citations is required for accessibility. SI also requires compliance with SI Accessibility Guidelines and the IBC. Comparisons should be made and the more stringent requirement followed for design purposes. An accessible route including a minimum clear width of 36" (except through doors, which must be at least 32" clear) is required. Refer to ADA/ABAAG (2004) for specifications regarding clear floor spaces at desks, files and equipment for individuals using wheelchairs.See Accessibility Narrative for additional information.

Development & Public Affairs Work Stations, Staff Amenities, and Meeting Rooms. Additional adjacency information is unavailable at this time pending finalization of organization chart by NMAAHC.

SUSTAINABILITY FEATURES

vs. Private

Please refer to structural narrative for more information on structural requirements.

CRITICAL DIMENSIONS

Length, Width, Shape

Smithsonian Institution National Museum of African American History and Culture 122 Infrastructure Only 0 Other Amenities Deionized Water Vacuum Yes Speakers OH Gr. 2, 130 SF/HD FIRE ALARM Smoke Detection Yes Wet Sprinkler Special Waste Dry Sprinkler Pre-Action Sprinkler No FIRE PROTECTION No Considerations for Water 0 No Floor Drains Floor Sink Grey/Blackwater Piping 0 No No No Protected Hot/Cold No No Recycled Water Supply (treated) 0 No Public Address Audio Compressed Air Audio Visual Requirements No Hot/Cold Water Task Light Yes No 0 Plant/Clean Steam No Acoustic Sensitivity 0 Vibration Sensitivity Special Equipment/Artifact Sensitivity PLUMBING Target Illuminance (IES 9th Edition) Daylight Sensor 0 Exhibit Light Yes Power Density (AHSRAE 2004) 0 Temperature Deviations (+/-) No No Process Water UPS Switched Receptacles Dimming Yes Humidity 0 No Other Humidity Deviation (+/-) As required by load No No Outside Air Single/Multi-Level Switching 0 Emergency/Standby Power As required by code 30/85 Yes Occupancy Sensor Special Exhaust Sub-metering & Feedback Displays Filtration (Pre/Final/Other) Voice/Data DATA/TELECOMMUNICATIONS Yes 0 SECURITY 0 0 Floor Loading/Point Loads DAYLIGHTING 0 0 Shading Considerations Top/Side Lighting 0 0 STRUCTURAL 0 0 Refer to information indicated in Volume IV, Section E 0 0 Technical Comment: Public Affairs Assignable Square Feet (ASF) OFEO Space Dimensions 0 Organizational Unit Other Interior Glazing 0 0 0 0 0 Ceiling CRITICAL FINISHES 0 0
ELECTRICAL ARCHITECTURAL
Zone Room ID D1.25 Room Name 0 Functional Description Enclosed private office with office furnishings
worksurface
file
Non Public-Non Collection Space 240 Number of Occupants 1 Visual Privacy (full, partial, open) Zone Designation Zone D Room Height 0 LEED NC Regurlarly Occupied Space 0 Base ACOUSTICS Equipment Hardware/STC Rating None NRC 0 0 0 Plug Loads Air Change/ HR Walls HVAC ENGINEERING CRITERIA Temperature Lighting No Control ±2ºF 110v, 20a, 1ph Yes 0 Power No 0 Pressure (+/-) 78ºF Summer, 71ºF Winter Floor Operable Windows Separation/STC FURNITURE/EQUIPMENT Moveable 0 Fixed RT60
0 Upper
including
and
storage.
& Shaping
Floor Level 0 Room
Open

This room data sheet is not comprehensive in nature. Information regarding specific room features may not have been available and was intentionally left blank.

Accessibility Requirement:

Adjacencies

Compliance with ADA/ABAAG (2004) citations is required for accessibility. SI also requires compliance with SI Accessibility Guidelines and the IBC. Comparisons should be made and the more stringent requirement followed for design purposes. An accessible route including a minimum clear width of 36" (except through doors, which must be at least 32" clear) is required. Refer to ADA/ABAAG (2004) for specifications regarding clear floor spaces at desks, files and equipment for individuals using wheelchairs.See Accessibility Narrative for additional information.

Development & Public Affairs Work Stations, Staff Amenities, and Meeting Rooms. Additional adjacency information is unavailable at this time pending finalization of organization chart by NMAAHC.

SUSTAINABILITY FEATURES

vs. Private

Please refer to structural narrative for more information on structural requirements.

CRITICAL DIMENSIONS

Length, Width, Shape

123 Room Data Sheets | FREELON BOND Infrastructure Only 0 Other Amenities Deionized Water Vacuum Yes Speakers OH Gr. 2, 130 SF/HD FIRE ALARM Smoke Detection Yes Wet Sprinkler Special Waste Dry Sprinkler Pre-Action Sprinkler No FIRE PROTECTION No Considerations for Water 0 No Floor Drains Floor Sink Grey/Blackwater Piping 0 No No No Protected Hot/Cold No No Recycled Water Supply (treated) 0 No Public Address Audio Compressed Air Audio Visual Requirements No Hot/Cold Water Task Light Yes No 0 Plant/Clean Steam No Acoustic Sensitivity 0 Vibration Sensitivity Special Equipment/Artifact Sensitivity PLUMBING Target Illuminance (IES 9th Edition) Daylight Sensor 0 Exhibit Light Yes Power Density (AHSRAE 2004) 0 Temperature Deviations (+/-) No No Process Water UPS Switched Receptacles Dimming Yes Humidity 0 No Other Humidity Deviation (+/-) As required by load No No Outside Air Single/Multi-Level Switching 0 Emergency/Standby Power As required by code 30/85 Yes Occupancy Sensor Special Exhaust Sub-metering & Feedback Displays Filtration (Pre/Final/Other) Voice/Data DATA/TELECOMMUNICATIONS Yes 0 SECURITY 0 0 Floor Loading/Point Loads DAYLIGHTING 0 0 Shading Considerations Top/Side Lighting 0 0 STRUCTURAL 0 0 Refer to information indicated in Volume IV, Section E 0 0 Technical Comment: Editor Assignable Square Feet (ASF) OFEO Space Dimensions 0 Organizational Unit Other Interior Glazing 0 0 0 0 0 Ceiling CRITICAL FINISHES 0 0
ELECTRICAL ARCHITECTURAL
Zone Room ID D1.26 Room Name 0 Functional Description Enclosed private office with office furnishings including worksurface and file storage. Non Public-Non Collection Space 120 Number of Occupants 1 Visual Privacy (full, partial, open) Zone Designation Zone D Room Height 0 LEED NC Regurlarly Occupied Space 0 Base ACOUSTICS Equipment Hardware/STC Rating None NRC 0 0 0 Plug Loads Air Change/ HR Walls HVAC ENGINEERING CRITERIA Temperature Lighting No Control ±2ºF 110v, 20a, 1ph Yes 0 Power No 0 Pressure (+/-) 78ºF Summer, 71ºF Winter Floor Operable Windows Separation/STC FURNITURE/EQUIPMENT Moveable 0 Fixed RT60
0 Upper
& Shaping
Floor Level 0 Room
Open

This room data sheet is not comprehensive in nature. Information regarding specific room features may not have been available and was intentionally left blank.

Accessibility Requirement:

Adjacencies

SUSTAINABILITY FEATURES

Compliance with ADA/ABAAG (2004) citations is required for accessibility. SI also requires compliance with SI Accessibility Guidelines and the IBC. Comparisons should be made and the more stringent requirement followed for design purposes. An accessible route including a minimum clear width of 36" (except through doors, which must be at least 32" clear) is required. Refer to ADA/ABAAG (2004) for specifications regarding clear floor spaces at desks, files and equipment for individuals using wheelchairs.See Accessibility Narrative for additional information.

Administration Work Stations, Staff Amenities, and Meeting Rooms. Additional adjacency information is unavailable at this time pending finalization of organization chart by NMAAHC.

CRITICAL DIMENSIONS

Length, Width, Shape Open vs. Private

Please refer to structural narrative for more information on structural requirements.

Smithsonian Institution National Museum of African American History and Culture 124 Infrastructure Only 0 Other Amenities Deionized Water Vacuum Yes Speakers OH Gr. 2, 130 SF/HD FIRE ALARM Smoke Detection Yes Wet Sprinkler Special Waste Dry Sprinkler Pre-Action Sprinkler No FIRE PROTECTION No Considerations for Water 0 No Floor Drains Floor Sink Grey/Blackwater Piping 0 No No No Protected Hot/Cold No No Recycled Water Supply (treated) 0 No Public Address Audio Compressed Air Audio Visual Requirements No Hot/Cold Water Task Light Yes No 0 Plant/Clean Steam No Acoustic Sensitivity 0 Vibration Sensitivity Special Equipment/Artifact Sensitivity PLUMBING Target Illuminance (IES 9th Edition) Daylight Sensor 0 Exhibit Light Yes Power Density (AHSRAE 2004) 0 Temperature Deviations (+/-) No No Process Water UPS Switched Receptacles Dimming Yes Humidity 0 No Other Humidity Deviation (+/-) As required by load No No Outside Air Single/Multi-Level Switching 0 Emergency/Standby Power As required by code 30/85 Yes Occupancy Sensor Special Exhaust Sub-metering & Feedback Displays Filtration (Pre/Final/Other) Voice/Data DATA/TELECOMMUNICATIONS Yes 0 SECURITY 0 0 Floor Loading/Point Loads DAYLIGHTING 0 0 Shading Considerations Top/Side Lighting 0 0 STRUCTURAL 0 0 Refer to information indicated in Volume IV, Section E 0 0 Technical Comment: Associate Director Assignable Square Feet (ASF) OFEO Space Dimensions 0 Organizational Unit Other Interior Glazing 0 0 0 0 0 Ceiling CRITICAL FINISHES 0 0
ELECTRICAL ARCHITECTURAL
Zone Room ID D1.27 Room Name 0 Functional Description Enclosed private office with office furnishings including worksurface, file storage and additional seating area for reception of VIP guests. Non Public-Non Collection Space 280 Number of Occupants 1 Visual Privacy (full, partial, open) Zone Designation Zone D Room Height 0 LEED NC Regurlarly
Space 0 Base ACOUSTICS Equipment Hardware/STC Rating None NRC 0 0 0 Plug Loads Air Change/ HR Walls HVAC ENGINEERING CRITERIA Temperature Lighting No Control ±2ºF 110v, 20a, 1ph Yes 0 Power No 0 Pressure (+/-) 78ºF Summer, 71ºF Winter Floor Operable Windows Separation/STC FURNITURE/EQUIPMENT Moveable 0 Fixed RT60 &
0 Upper
Occupied
Shaping
Floor Level 0 Room

This room data sheet is not comprehensive in nature. Information regarding specific room features may not have been available and was intentionally left blank.

Accessibility Requirement:

Adjacencies

SUSTAINABILITY FEATURES

Compliance with ADA/ABAAG (2004) citations is required for accessibility. SI also requires compliance with SI Accessibility Guidelines and the IBC. Comparisons should be made and the more stringent requirement followed for design purposes. An accessible route including a minimum clear width of 36" (except through doors, which must be at least 32" clear) is required. Refer to ADA/ABAAG (2004) for specifications regarding clear floor spaces at desks, files and equipment for individuals using wheelchairs.See Accessibility Narrative for additional information.

Administration Work Stations, Staff Amenities, and Meeting Rooms. Additional adjacency information is unavailable at this time pending finalization of organization chart by NMAAHC.

CRITICAL

DIMENSIONS

Length, Width, Shape Open vs. Private

Please refer to structural narrative for more information on structural requirements.

125 Room Data Sheets | FREELON BOND Infrastructure Only 0 Other Amenities Deionized Water Vacuum Yes Speakers OH Gr. 2, 130 SF/HD FIRE ALARM Smoke Detection Yes Wet Sprinkler Special Waste Dry Sprinkler Pre-Action Sprinkler No FIRE PROTECTION No Considerations for Water 0 No Floor Drains Floor Sink Grey/Blackwater Piping 0 No No No Protected Hot/Cold No No Recycled Water Supply (treated) 0 No Public Address Audio Compressed Air Audio Visual Requirements No Hot/Cold Water Task Light Yes No 0 Plant/Clean Steam No Acoustic Sensitivity 0 Vibration Sensitivity Special Equipment/Artifact Sensitivity PLUMBING Target Illuminance (IES 9th Edition) Daylight Sensor 0 Exhibit Light Yes Power Density (AHSRAE 2004) 0 Temperature Deviations (+/-) No No Process Water UPS Switched Receptacles Dimming Yes Humidity 0 No Other Humidity Deviation (+/-) As required by load No No Outside Air Single/Multi-Level Switching 0 Emergency/Standby Power As required by code 30/85 Yes Occupancy Sensor Special Exhaust Sub-metering & Feedback Displays Filtration (Pre/Final/Other) Voice/Data DATA/TELECOMMUNICATIONS Yes 0 SECURITY 0 0 Floor Loading/Point Loads DAYLIGHTING 0 0 Shading Considerations Top/Side Lighting 0 0 STRUCTURAL 0 0 Refer to information indicated in Volume IV, Section E 0 0 Technical Comment: Finance Assignable Square Feet (ASF) OFEO Space Dimensions 0 Organizational Unit Other Interior Glazing 0 0 0 0 0 Ceiling CRITICAL FINISHES 0 0
ELECTRICAL ARCHITECTURAL
Zone Room ID D1.28 Room Name 0 Functional Description Enclosed private office with office furnishings
worksurface
file storage. Non Public-Non Collection Space 480 Number of Occupants 1 Visual Privacy (full, partial, open) Zone Designation Zone D Room Height 0 LEED NC Regurlarly Occupied Space 0 Base ACOUSTICS Equipment Hardware/STC Rating None NRC 0 0 0 Plug Loads Air Change/ HR Walls HVAC ENGINEERING CRITERIA Temperature Lighting No Control ±2ºF 110v, 20a, 1ph Yes 0 Power No 0 Pressure (+/-) 78ºF Summer, 71ºF Winter Floor Operable Windows Separation/STC FURNITURE/EQUIPMENT Moveable 0 Fixed RT60
0 Upper
including
and
& Shaping
Floor Level 0 Room

This room data sheet is not comprehensive in nature. Information regarding specific room features may not have been available and was intentionally left blank.

Accessibility Requirement:

Adjacencies

SUSTAINABILITY FEATURES

Compliance with ADA/ABAAG (2004) citations is required for accessibility. SI also requires compliance with SI Accessibility Guidelines and the IBC. Comparisons should be made and the more stringent requirement followed for design purposes. An accessible route including a minimum clear width of 36" (except through doors, which must be at least 32" clear) is required. Refer to ADA/ABAAG (2004) for specifications regarding clear floor spaces at desks, files and equipment for individuals using wheelchairs.See Accessibility Narrative for additional information.

Administration Work Stations, Staff Amenities, and Meeting Rooms. Additional adjacency information is unavailable at this time pending finalization of organization chart by NMAAHC.

CRITICAL

DIMENSIONS

Length, Width, Shape Open vs. Private

Please refer to structural narrative for more information on structural requirements.

Smithsonian Institution National Museum of African American History and Culture 126 Infrastructure Only 0 Other Amenities Deionized Water Vacuum Yes Speakers OH Gr. 2, 130 SF/HD FIRE ALARM Smoke Detection Yes Wet Sprinkler Special Waste Dry Sprinkler Pre-Action Sprinkler No FIRE PROTECTION No Considerations for Water 0 No Floor Drains Floor Sink Grey/Blackwater Piping 0 No No No Protected Hot/Cold No No Recycled Water Supply (treated) 0 No Public Address Audio Compressed Air Audio Visual Requirements No Hot/Cold Water Task Light Yes No 0 Plant/Clean Steam No Acoustic Sensitivity 0 Vibration Sensitivity Special Equipment/Artifact Sensitivity PLUMBING Target Illuminance (IES 9th Edition) Daylight Sensor 0 Exhibit Light Yes Power Density (AHSRAE 2004) 0 Temperature Deviations (+/-) No No Process Water UPS Switched Receptacles Dimming Yes Humidity 0 No Other Humidity Deviation (+/-) As required by load No No Outside Air Single/Multi-Level Switching 0 Emergency/Standby Power As required by code 30/85 Yes Occupancy Sensor Special Exhaust Sub-metering & Feedback Displays Filtration (Pre/Final/Other) Voice/Data DATA/TELECOMMUNICATIONS Yes 0 SECURITY 0 0 Floor Loading/Point Loads DAYLIGHTING 0 0 Shading Considerations Top/Side Lighting 0 0 STRUCTURAL 0 0 Refer to information indicated in Volume IV, Section E 0 0 Technical Comment: Business Development Assignable Square Feet (ASF) OFEO Space Dimensions 0 Organizational Unit Other Interior Glazing 0 0 0 0 0 Ceiling CRITICAL FINISHES 0 0
ELECTRICAL ARCHITECTURAL
Zone Room ID D1.29 Room Name 0 Functional Description Enclosed private office with office furnishings including worksurface
file storage. Non Public-Non Collection Space 120 Number of Occupants 1 Visual Privacy (full, partial, open) Zone Designation Zone D Room Height 0 LEED NC Regurlarly Occupied Space 0 Base ACOUSTICS Equipment Hardware/STC Rating None NRC 0 0 0 Plug Loads Air Change/ HR Walls HVAC ENGINEERING CRITERIA Temperature Lighting No Control ±2ºF 110v, 20a, 1ph Yes 0 Power No 0 Pressure (+/-) 78ºF Summer, 71ºF Winter Floor Operable Windows Separation/STC FURNITURE/EQUIPMENT Moveable 0 Fixed RT60
0 Upper
and
& Shaping
Floor Level 0 Room

This room data sheet is not comprehensive in nature. Information regarding specific room features may not have been available and was intentionally left blank.

Accessibility Requirement:

Adjacencies

SUSTAINABILITY FEATURES

Compliance with ADA/ABAAG (2004) citations is required for accessibility. SI also requires compliance with SI Accessibility Guidelines and the IBC. Comparisons should be made and the more stringent requirement followed for design purposes. An accessible route including a minimum clear width of 36" (except through doors, which must be at least 32" clear) is required. Refer to ADA/ABAAG (2004) for specifications regarding clear floor spaces at desks, files and equipment for individuals using wheelchairs.See Accessibility Narrative for additional information.

Administration Work Stations, Staff Amenities, and Meeting Rooms. Additional adjacency information is unavailable at this time pending finalization of organization chart by NMAAHC.

CRITICAL

DIMENSIONS

Length, Width, Shape Open vs. Private

Please refer to structural narrative for more information on structural requirements.

127 Room Data Sheets | FREELON BOND Infrastructure Only 0 Other Amenities Deionized Water Vacuum Yes Speakers OH Gr. 2, 130 SF/HD FIRE ALARM Smoke Detection Yes Wet Sprinkler Special Waste Dry Sprinkler Pre-Action Sprinkler No FIRE PROTECTION No Considerations for Water 0 No Floor Drains Floor Sink Grey/Blackwater Piping 0 No No No Protected Hot/Cold No No Recycled Water Supply (treated) 0 No Public Address Audio Compressed Air Audio Visual Requirements No Hot/Cold Water Task Light Yes No 0 Plant/Clean Steam No Acoustic Sensitivity 0 Vibration Sensitivity Special Equipment/Artifact Sensitivity PLUMBING Target Illuminance (IES 9th Edition) Daylight Sensor 0 Exhibit Light Yes Power Density (AHSRAE 2004) 0 Temperature Deviations (+/-) No No Process Water UPS Switched Receptacles Dimming Yes Humidity 0 No Other Humidity Deviation (+/-) As required by load No No Outside Air Single/Multi-Level Switching 0 Emergency/Standby Power As required by code 30/85 Yes Occupancy Sensor Special Exhaust Sub-metering & Feedback Displays Filtration (Pre/Final/Other) Voice/Data DATA/TELECOMMUNICATIONS Yes 0 SECURITY 0 0 Floor Loading/Point Loads DAYLIGHTING 0 0 Shading Considerations Top/Side Lighting 0 0 STRUCTURAL 0 0 Refer to information indicated in Volume IV, Section E 0 0 Technical Comment: Personnel Assignable Square Feet (ASF) OFEO Space Dimensions 0 Organizational Unit Other Interior Glazing 0 0 0 0 0 Ceiling CRITICAL FINISHES 0 0
ELECTRICAL ARCHITECTURAL
Zone Room ID D1.30 Room Name 0 Functional Description Enclosed private office with office furnishings including worksurface
file storage. Non Public-Non Collection Space 120 Number of Occupants 1 Visual Privacy (full, partial, open) Zone Designation Zone D Room Height 0 LEED NC Regurlarly Occupied Space 0 Base ACOUSTICS Equipment Hardware/STC Rating None NRC 0 0 0 Plug Loads Air Change/ HR Walls HVAC ENGINEERING CRITERIA Temperature Lighting No Control ±2ºF 110v, 20a, 1ph Yes 0 Power No 0 Pressure (+/-) 78ºF Summer, 71ºF Winter Floor Operable Windows Separation/STC FURNITURE/EQUIPMENT Moveable 0 Fixed RT60
0 Upper
and
& Shaping
Floor Level 0 Room

This room data sheet is not comprehensive in nature. Information regarding specific room features may not have been available and was intentionally left blank.

Accessibility Requirement:

Adjacencies

SUSTAINABILITY FEATURES

Compliance with ADA/ABAAG (2004) citations is required for accessibility. SI also requires compliance with SI Accessibility Guidelines and the IBC. Comparisons should be made and the more stringent requirement followed for design purposes. An accessible route including a minimum clear width of 36" (except through doors, which must be at least 32" clear) is required. Refer to ADA/ABAAG (2004) for specifications regarding clear floor spaces at desks, files and equipment for individuals using wheelchairs.See Accessibility Narrative for additional information.

Administration Work Stations, Staff Amenities, and Meeting Rooms. Additional adjacency information is unavailable at this time pending finalization of organization chart by NMAAHC.

CRITICAL

DIMENSIONS

Length, Width, Shape Open vs. Private

Please refer to structural narrative for more information on structural requirements.

Smithsonian Institution National Museum of African American History and Culture 128 Infrastructure Only 0 Other Amenities Deionized Water Vacuum Yes Speakers OH Gr. 2, 130 SF/HD FIRE ALARM Smoke Detection Yes Wet Sprinkler Special Waste Dry Sprinkler Pre-Action Sprinkler No FIRE PROTECTION No Considerations for Water 0 No Floor Drains Floor Sink Grey/Blackwater Piping 0 No No No Protected Hot/Cold No No Recycled Water Supply (treated) 0 No Public Address Audio Compressed Air Audio Visual Requirements No Hot/Cold Water Task Light Yes No 0 Plant/Clean Steam No Acoustic Sensitivity 0 Vibration Sensitivity Special Equipment/Artifact Sensitivity PLUMBING Target Illuminance (IES 9th Edition) Daylight Sensor 0 Exhibit Light Yes Power Density (AHSRAE 2004) 0 Temperature Deviations (+/-) No No Process Water UPS Switched Receptacles Dimming Yes Humidity 0 No Other Humidity Deviation (+/-) As required by load No No Outside Air Single/Multi-Level Switching 0 Emergency/Standby Power As required by code 30/85 Yes Occupancy Sensor Special Exhaust Sub-metering & Feedback Displays Filtration (Pre/Final/Other) Voice/Data DATA/TELECOMMUNICATIONS Yes 0 SECURITY 0 0 Floor Loading/Point Loads DAYLIGHTING 0 0 Shading Considerations Top/Side Lighting 0 0 STRUCTURAL 0 0 Refer to information indicated in Volume IV, Section E 0 0 Technical Comment: IT Assignable Square Feet (ASF) OFEO Space Dimensions 0 Organizational Unit Other Interior Glazing 0 0 0 0 0 Ceiling CRITICAL FINISHES 0 0
ELECTRICAL ARCHITECTURAL
Zone Room ID D1.31 Room Name 0 Functional Description Enclosed private office with office furnishings including worksurface
file storage. Non Public-Non Collection Space 120 Number of Occupants 1 Visual Privacy (full, partial, open) Zone Designation Zone D Room Height 0 LEED NC Regurlarly Occupied Space 0 Base ACOUSTICS Equipment Hardware/STC Rating None NRC 0 0 0 Plug Loads Air Change/ HR Walls HVAC ENGINEERING CRITERIA Temperature Lighting No Control ±2ºF 110v, 20a, 1ph Yes 0 Power No 0 Pressure (+/-) 78ºF Summer, 71ºF Winter Floor Operable Windows Separation/STC FURNITURE/EQUIPMENT Moveable 0 Fixed RT60
0 Upper
and
& Shaping
Floor
0 Room
Level

This room data sheet is not comprehensive in nature. Information regarding specific room features may not have been available and was intentionally left blank.

Accessibility Requirement:

Adjacencies

SUSTAINABILITY FEATURES

Compliance withADA/ABAAG (2004) citations is required for accessibility. SI also requires compliance with SI Accessibility Guidelines and the IBC. Comparisons should be made and the more stringent requirement followed for design purposes. An accessible route including a minimum clear width of 36" (except through doors, which must be at least 32" clear) is required. Refer to ADA/ABAAG (2004) for specifications regarding clear floor spaces at desks, files and equipment for individuals using wheelchairs.See Accessibility Narrative for additional information.

Administration Work Stations, Staff Amenities, and Meeting Rooms. Additional adjacency information is unavailable at this time pending finalization of organization chart by NMAAHC.

CRITICAL DIMENSIONS

Length, Width, Shape Open vs. Private

Please refer to structural narrative for more information on structural requirements.

129 Room Data Sheets | FREELON BOND Infrastructure Only 0 Other Amenities Deionized Water Vacuum Yes Speakers OH Gr. 2, 130 SF/HD FIRE ALARM Smoke Detection Yes Wet Sprinkler Special Waste Dry Sprinkler Pre-Action Sprinkler No FIRE PROTECTION No Considerations for Water 0 No Floor Drains Floor Sink Grey/Blackwater Piping 0 No No No Protected Hot/Cold No No Recycled Water Supply (treated) 0 No Public Address Audio Compressed Air Audio Visual Requirements No Hot/Cold Water Task Light Yes No 0 Plant/Clean Steam No Acoustic Sensitivity 0 Vibration Sensitivity Special Equipment/Artifact Sensitivity PLUMBING Target Illuminance (IES 9th Edition) Daylight Sensor 0 Exhibit Light Yes Power Density (AHSRAE 2004) 0 Temperature Deviations (+/-) No No Process Water UPS Switched Receptacles Dimming Yes Humidity 0 No Other Humidity Deviation (+/-) As required by load No No Outside Air Single/Multi-Level Switching 0 Emergency/Standby Power As required by code 30/85 Yes Occupancy Sensor Special Exhaust Sub-metering & Feedback Displays Filtration (Pre/Final/Other) Voice/Data DATA/TELECOMMUNICATIONS Yes 0 SECURITY 0 0 Floor Loading/Point Loads DAYLIGHTING 0 0 Shading Considerations Top/Side Lighting 0 0 STRUCTURAL 0 0 Refer to information indicated in Volume IV, Section E 0 0 Technical Comment: Exhibitions Design Assignable Square Feet (ASF) OFEO Space Dimensions 0 Organizational Unit Other Interior Glazing 0 0 0 0 0 Ceiling CRITICAL FINISHES 0 0
ELECTRICAL ARCHITECTURAL
Zone Room ID D1.32 Room Name 0
Description Enclosed
office with office furnishings including worksurface
file storage. Non Public-Non Collection Space 120 Number of Occupants 1 Visual Privacy (full, partial, open) Zone Designation Zone D Room Height 0 LEED NC Regurlarly Occupied Space 0 Base ACOUSTICS Equipment Hardware/STC Rating None NRC 0 0 0 Plug Loads Air Change/ HR Walls HVAC ENGINEERING CRITERIA Temperature Lighting No Control ±2ºF 110v, 20a, 1ph Yes 0 Power No 0 Pressure (+/-) 78ºF Summer, 71ºF Winter Floor Operable Windows Separation/STC FURNITURE/EQUIPMENT Moveable 0 Fixed RT60
0 Upper
Functional
private
and
& Shaping
Floor Level 0 Room

This room data sheet is not comprehensive in nature. Information regarding specific room features may not have been available and was intentionally left blank.

Accessibility Requirement:

Adjacencies

Compliance with ADA/ABAAG (2004) citations is required for accessibility. SI also requires compliance with SI Accessibility Guidelines and the IBC. Comparisons should be made and the more stringent requirement followed for design purposes. An accessible route including a minimum clear width of 36" (except through doors, which must be at least 32" clear) is required. Refer to ADA/ABAAG (2004) for specifications regarding clear floor spaces at desks, files and equipment for individuals using wheelchairs.See Accessibility Narrative for additional information.

Administration Work Stations, Staff Amenities, and Meeting Rooms. Additional adjacency information is unavailable at this time pending finalization of organization chart by NMAAHC.

SUSTAINABILITY FEATURES

vs. Private

Please refer to structural narrative for more information on structural requirements.

CRITICAL

DIMENSIONS

Length, Width, Shape

Smithsonian Institution National Museum of African American History and Culture 130 Infrastructure Only 0 Other Amenities Deionized Water Vacuum Yes Speakers OH Gr. 2, 130 SF/HD FIRE ALARM Smoke Detection Yes Wet Sprinkler Special Waste Dry Sprinkler Pre-Action Sprinkler No FIRE PROTECTION No Considerations for Water 0 No Floor Drains Floor Sink Grey/Blackwater Piping 0 No No No Protected Hot/Cold No No Recycled Water Supply (treated) 0 No Public Address Audio Compressed Air Audio Visual Requirements No Hot/Cold Water Task Light Yes No 0 Plant/Clean Steam No Acoustic Sensitivity 0 Vibration Sensitivity Special Equipment/Artifact Sensitivity PLUMBING Target Illuminance (IES 9th Edition) Daylight Sensor 0 Exhibit Light Yes Power Density (AHSRAE 2004) 0 Temperature Deviations (+/-) No No Process Water UPS Switched Receptacles Dimming Yes Humidity 0 No Other Humidity Deviation (+/-) As required by load No No Outside Air Single/Multi-Level Switching 0 Emergency/Standby Power As required by code 30/85 Yes Occupancy Sensor Special Exhaust Sub-metering & Feedback Displays Filtration (Pre/Final/Other) Voice/Data DATA/TELECOMMUNICATIONS Yes 0 SECURITY 0 0 Floor Loading/Point Loads DAYLIGHTING 0 0 Shading Considerations Top/Side Lighting 0 0 STRUCTURAL 0 0 Refer to information indicated in Volume IV, Section E 0 0 Technical Comment: Exhibitions Productions/Maintenance Assignable Square Feet (ASF) OFEO Space Dimensions 0 Organizational Unit Other Interior Glazing 0 0 0 0 0 Ceiling CRITICAL FINISHES 0 0
ELECTRICAL ARCHITECTURAL
Zone Room ID D1.33 Room Name 0 Functional Description Enclosed private office with office furnishings including worksurface and file storage. Non Public-Non Collection Space 120 Number of Occupants 1 Visual Privacy (full, partial, open) Zone Designation Zone D Room Height 0 LEED NC Regurlarly Occupied
0 Base ACOUSTICS Equipment Hardware/STC Rating None NRC 0 0 0 Plug Loads Air Change/ HR Walls HVAC ENGINEERING CRITERIA Temperature Lighting No Control ±2ºF 110v, 20a, 1ph Yes 0 Power No 0 Pressure (+/-) 78ºF Summer, 71ºF Winter Floor Operable Windows Separation/STC FURNITURE/EQUIPMENT Moveable 0 Fixed RT60 &
0 Upper
Space
Shaping
Floor Level 0 Room
Open

This room data sheet is not comprehensive in nature. Information regarding specific room features may not have been available and was intentionally left blank.

Compliance with ADA/ABAAG (2004) citations is required for accessibility. SI also requires compliance with SI Accessibility Guidelines and the IBC. Comparisons should be made and the more stringent requirement followed for design purposes. An accessible route including a minimum clear width of 36" (except through doors, which must be at least 32" clear) is required. Refer to ADA/ABAAG (2004) for specifications regarding clear floor spaces at desks, files and equipment for individuals using wheelchairs.See Accessibility Narrative for additional information.

Director's Office Suite Offices, Staff Amenities, and Meeting Rooms. Additional adjacency information is unavailable at this time pending finalization of organization chart by NMAAHC. SUSTAINABILITY FEATURES

CRITICAL DIMENSIONS

Width, Shape

Please refer to structural narrative for more information on structural requirements.

131 Room Data Sheets | FREELON BOND Infrastructure Only 0 Other Amenities Deionized Water Vacuum Yes Speakers OH Gr. 2, 130 SF/HD FIRE ALARM Smoke Detection Yes Wet Sprinkler Special Waste Dry Sprinkler Pre-Action Sprinkler No FIRE PROTECTION No Considerations for Water 0 No Floor Drains Floor Sink Grey/Blackwater Piping 0 No No No Protected Hot/Cold No No Recycled Water Supply (treated) 0 No Public Address Audio Compressed Air Audio Visual Requirements No Hot/Cold Water Task Light Yes No 0 Plant/Clean Steam No Acoustic Sensitivity 0 Vibration Sensitivity Special Equipment/Artifact Sensitivity PLUMBING Target Illuminance (IES 9th Edition) Daylight Sensor 0 Exhibit Light Yes Power Density (AHSRAE 2004) 0 Temperature Deviations (+/-) No No Process Water UPS Switched Receptacles Dimming Yes Humidity 0 No Other Humidity Deviation (+/-) As required by load No No Outside Air Single/Multi-Level Switching 0 Emergency/Standby Power As required by code 30/85 Yes Occupancy Sensor Special Exhaust Sub-metering & Feedback Displays Filtration (Pre/Final/Other) Voice/Data DATA/TELECOMMUNICATIONS Yes 0 SECURITY 0 5.0 kPa/8.9 kN Floor Loading/Point Loads DAYLIGHTING 0 0 Shading Considerations Top/Side Lighting None No STRUCTURAL 0 0 Refer to information indicated in Volume IV, Section E 0 0 Technical Comment: Director's Office Suite Work Stations Assignable Square Feet (ASF) OFEO Space Dimensions 0 Organizational Unit Other Interior Glazing 0 0 0 0 0 Ceiling CRITICAL FINISHES 0 0
ELECTRICAL ARCHITECTURAL
Zone Room ID D1.34 Room Name 0 Functional Description Open office workspace with office furnishings including worksurface and file storage. Non Public-Non Collection Space 160 Number of Occupants 1 Visual Privacy (full, partial, open) Zone Designation Zone D Room Height 0 LEED NC
0 Base ACOUSTICS Equipment Hardware/STC Rating None NRC0 0 Plug Loads Air Change/ HR Walls HVAC ENGINEERING CRITERIA Temperature Lighting No Control ±2ºF 110v, 20a, 1ph Yes 0 Power No 0 Pressure (+/-) 78ºF Summer, 71ºF Winter Floor Operable Windows Separation/STC FURNITURE/EQUIPMENT Moveable 0 Fixed RT60 & Shaping 0 Upper
Regurlarly Occupied Space
Floor Level 0 Room
Open
Adjacencies Accessibility Requirement:
Length,
vs. Private

This room data sheet is not comprehensive in nature. Information regarding specific room features may not have been available and was intentionally left blank.

Compliance with ADA/ABAAG (2004) citations is required for accessibility. SI also requires compliance with SI Accessibility Guidelines and the IBC. Comparisons should be made and the more stringent requirement followed for design purposes. An accessible route including a minimum clear width of 36" (except through doors, which must be at least 32" clear) is required. Refer to ADA/ABAAG (2004) for specifications regarding clear floor spaces at desks, files and equipment for individuals using wheelchairs.See Accessibility Narrative for additional information.

Project Management Offices, Staff Amenities, and Meeting Rooms. Additional adjacency information is unavailable at this time pending finalization of organization chart by NMAAHC. SUSTAINABILITY FEATURES

CRITICAL DIMENSIONS

Please refer to structural narrative for more information on structural requirements.

Smithsonian Institution National Museum of African American History and Culture 132 Infrastructure Only 0 Other Amenities Deionized Water Vacuum Yes Speakers OH Gr. 2, 130 SF/HD FIRE ALARM Smoke Detection Yes Wet Sprinkler Special Waste Dry Sprinkler Pre-Action Sprinkler No FIRE PROTECTION No Considerations for Water 0 No Floor Drains Floor Sink Grey/Blackwater Piping 0 No No No Protected Hot/Cold No No Recycled Water Supply (treated) 0 No Public Address Audio Compressed Air Audio Visual Requirements No Hot/Cold Water Task Light Yes No 0 Plant/Clean Steam No Acoustic Sensitivity 0 Vibration Sensitivity Special Equipment/Artifact Sensitivity PLUMBING Target Illuminance (IES 9th Edition) Daylight Sensor 0 Exhibit Light Yes Power Density (AHSRAE 2004) 0 Temperature Deviations (+/-) No No Process Water UPS Switched Receptacles Dimming Yes Humidity 0 No Other Humidity Deviation (+/-) As required by load No No Outside Air Single/Multi-Level Switching 0 Emergency/Standby Power As required by code 30/85 Yes Occupancy Sensor Special Exhaust Sub-metering & Feedback Displays Filtration (Pre/Final/Other) Voice/Data DATA/TELECOMMUNICATIONS Yes 0 SECURITY 0 5.0 kPa/8.9 kN Floor Loading/Point Loads DAYLIGHTING 0 0 Shading Considerations Top/Side Lighting None No STRUCTURAL 0 0 Refer to information indicated in Volume IV, Section E Full 0 Technical Comment: Project Management Suite Work Stations Assignable Square Feet (ASF) OFEO Space Dimensions 0 Organizational Unit Other Interior Glazing 0 0 Yes Yes 0 Ceiling CRITICAL FINISHES 0 0
ELECTRICAL ARCHITECTURAL
Zone Room ID D1.35 Room Name 0 Functional Description Open office workspace with office furnishings including worksurface and file storage. Non Public-Non Collection Space 160 Number of Occupants 1 Visual Privacy (full, partial, open) Zone Designation Zone D Room Height 0 LEED NC
Space 0 Base ACOUSTICS Equipment Hardware/STC Rating None NRC0 0 Plug Loads Air Change/ HR Walls HVAC ENGINEERING CRITERIA Temperature Lighting No Control ±2ºF 110v, 20a, 1ph Yes 0 Power No 0 Pressure (+/-) 78ºF Summer, 71ºF Winter Floor Operable Windows Separation/STC FURNITURE/EQUIPMENT Moveable Yes Fixed RT60 & Shaping 0 Upper
Regurlarly Occupied
Floor Level 0 Room
Open
Adjacencies Accessibility Requirement:
Length, Width, Shape
vs. Private

This room data sheet is not comprehensive in nature. Information regarding specific room features may not have been available and was intentionally left

Accessibility Requirement:

Adjacencies

Compliance with ADA/ABAAG (2004) citations is required for accessibility. SI also requires compliance with SI Accessibility Guidelines and the IBC. Comparisons should be made and the more stringent requirement followed for design purposes. An accessible route including a minimum clear width of 36" (except through doors, which must be at least 32" clear) is required. Refer to ADA/ABAAG (2004) for specifications regarding clear floor spaces at desks, files and equipment for individuals using wheelchairs.See Accessibility Narrative for additional information.

Curatorial Affairs Offices, Staff Amenities and Meeting Rooms. Additional adjacency information is unavailable at this time pending finalization of organization chart by NMAAHC.

SUSTAINABILITY FEATURES

vs. Private

Please refer to structural narrative for more information on structural requirements.

CRITICAL DIMENSIONS

Length, Width, Shape

133 Room Data Sheets | FREELON BOND Infrastructure Only 0 Other Amenities Deionized Water Vacuum Yes Speakers OH Gr. 2, 130 SF/HD FIRE ALARM Smoke Detection Yes Wet Sprinkler Special Waste Dry Sprinkler Pre-Action Sprinkler No FIRE PROTECTION No Considerations for Water 0 No Floor Drains Floor Sink Grey/Blackwater Piping 0 No No No Protected Hot/Cold No No Recycled Water Supply (treated) 0 No Public Address Audio Compressed Air Audio Visual Requirements No Hot/Cold Water Task Light Yes No 0 Plant/Clean Steam No Acoustic Sensitivity 0 Vibration Sensitivity Special Equipment/Artifact Sensitivity PLUMBING Target Illuminance (IES 9th Edition) Daylight Sensor 0 Exhibit Light Yes Power Density (AHSRAE 2004) 0 Temperature Deviations (+/-) No No Process Water UPS Switched Receptacles Dimming Yes Humidity 0 No Other Humidity Deviation (+/-) As required by load No No Outside Air Single/Multi-Level Switching 0 Emergency/Standby Power As required by code 30/85 Yes Occupancy Sensor Special Exhaust Sub-metering & Feedback Displays Filtration (Pre/Final/Other) Voice/Data DATA/TELECOMMUNICATIONS Yes 0 SECURITY 0 5.0 kPa/8.9 kN Floor Loading/Point Loads DAYLIGHTING 0 0 Shading Considerations Top/Side Lighting None No STRUCTURAL 0 0 Refer to information indicated in Volume IV, Section E 0 0 Technical Comment: Assistant Curators Assignable Square Feet (ASF) OFEO Space Dimensions 0 Organizational Unit Other Interior Glazing 0 0 0 0 0 Ceiling CRITICAL FINISHES 0 0
ELECTRICAL ARCHITECTURAL
Zone Room ID D1.36 Room Name 0 Functional Description Open office workspace with office furnishings including worksurface and file storage. Non Public-Non Collection Space 240 Number of Occupants 1 Visual Privacy (full, partial, open) Zone Designation Zone D Room Height 0 LEED NC
0 Base ACOUSTICS Equipment Hardware/STC Rating None NRC0 0 Plug Loads Air Change/ HR Walls HVAC ENGINEERING CRITERIA Temperature Lighting No Control ±2ºF 110v, 20a, 1ph Yes 0 Power No 0 Pressure (+/-) 78ºF Summer, 71ºF Winter Floor Operable Windows Separation/STC FURNITURE/EQUIPMENT Moveable 0 Fixed RT60 & Shaping 0 TBD
blank.
Regurlarly Occupied Space
Floor Level 0 Room
Open

This room data sheet is not comprehensive in nature. Information regarding specific room features may not have been available and was intentionally left blank.

Accessibility Requirement:

Adjacencies

Compliance withADA/ABAAG (2004) citations is required for accessibility. SI also requires compliance with SI Accessibility Guidelines and the IBC. Comparisons should be made and the more stringent requirement followed for design purposes. An accessible route including a minimum clear width of 36" (except through doors, which must be at least 32" clear) is required. Refer to ADA/ABAAG (2004) for specifications regarding clear floor spaces at desks, files and equipment for individuals using wheelchairs.See Accessibility Narrative for additional information.

Curatorial Affairs Offices, Staff Amenities and Meeting Rooms. Additional adjacency information is unavailable at this time pending finalization of organization chart by NMAAHC.

SUSTAINABILITY FEATURES

vs. Private

Please refer to structural narrative for more information on structural requirements.

CRITICAL DIMENSIONS

Length, Width, Shape

Smithsonian Institution National Museum of African American History and Culture 134 Infrastructure Only 0 Other Amenities Deionized Water Vacuum Yes Speakers OH Gr. 2, 130 SF/HD FIRE ALARM Smoke Detection Yes Wet Sprinkler Special Waste Dry Sprinkler Pre-Action Sprinkler No FIRE PROTECTION No Considerations for Water 0 No Floor Drains Floor Sink Grey/Blackwater Piping 0 No No No Protected Hot/Cold No No Recycled Water Supply (treated) 0 No Public Address Audio Compressed Air Audio Visual Requirements No Hot/Cold Water Task Light Yes No 0 Plant/Clean Steam No Acoustic Sensitivity 0 Vibration Sensitivity Special Equipment/Artifact Sensitivity PLUMBING Target Illuminance (IES 9th Edition) Daylight Sensor 0 Exhibit Light Yes Power Density (AHSRAE 2004) 0 Temperature Deviations (+/-) No No Process Water UPS Switched Receptacles Dimming Yes Humidity 0 No Other Humidity Deviation (+/-) As required by load No No Outside Air Single/Multi-Level Switching 0 Emergency/Standby Power As required by code 30/85 Yes Occupancy Sensor Special Exhaust Sub-metering & Feedback Displays Filtration (Pre/Final/Other) Voice/Data DATA/TELECOMMUNICATIONS Yes 0 SECURITY 0 5.0 kPa/8.9 kN Floor Loading/Point Loads DAYLIGHTING 0 0 Shading Considerations Top/Side Lighting None No STRUCTURAL 0 0 Refer to information indicated in Volume IV, Section E 0 0 Technical Comment: Curatorial Assistant/Collections Management Assignable Square Feet (ASF) OFEO Space Dimensions 0 Organizational Unit Other Interior Glazing 0 0 0 0 0 Ceiling CRITICAL FINISHES 0 0
ELECTRICAL ARCHITECTURAL
Zone Room ID D1.37 Room Name 0 Functional Description Open office workspace with office furnishings including worksurface and file storage. Non Public-Non Collection Space 640 Number of Occupants 1 Visual Privacy (full, partial, open) Zone Designation Zone D Room Height 0 LEED
0 Base ACOUSTICS Equipment Hardware/STC Rating None NRC0 0 Plug Loads Air Change/ HR Walls HVAC ENGINEERING CRITERIA Temperature Lighting No Control ±2ºF 110v, 20a, 1ph Yes 0 Power No 0 Pressure (+/-) 78ºF Summer, 71ºF Winter Floor Operable Windows Separation/STC FURNITURE/EQUIPMENT Moveable 0 Fixed RT60 & Shaping 0 TBD
NC Regurlarly Occupied Space
Floor Level 0 Room
Open

This room data sheet is not comprehensive in nature. Information regarding specific room features may not have been available and was intentionally left blank.

Accessibility Requirement:

Adjacencies

Compliance with ADA/ABAAG (2004) citations is required for accessibility. SI also requires compliance with SI Accessibility Guidelines and the IBC. Comparisons should be made and the more stringent requirement followed for design purposes. An accessible route including a minimum clear width of 36" (except through doors, which must be at least 32" clear) is required. Refer to ADA/ABAAG (2004) for specifications regarding clear floor spaces at desks, files and equipment for individuals using wheelchairs.See Accessibility Narrative for additional information.

Curatorial Affairs Offices, Staff Amenities and Meeting Rooms. Additional adjacency information is unavailable at this time pending finalization of organization chart by NMAAHC.

SUSTAINABILITY FEATURES

vs. Private

Please refer to structural narrative for more information on structural requirements.

CRITICAL DIMENSIONS

Length, Width, Shape

135 Room Data Sheets | FREELON BOND Infrastructure Only 0 Other Amenities Deionized Water Vacuum Yes Speakers OH Gr. 2, 130 SF/HD FIRE ALARM Smoke Detection Yes Wet Sprinkler Special Waste Dry Sprinkler Pre-Action Sprinkler No FIRE PROTECTION No Considerations for Water 0 No Floor Drains Floor Sink Grey/Blackwater Piping 0 No No No Protected Hot/Cold No No Recycled Water Supply (treated) 0 No Public Address Audio Compressed Air Audio Visual Requirements No Hot/Cold Water Task Light Yes No 0 Plant/Clean Steam No Acoustic Sensitivity 0 Vibration Sensitivity Special Equipment/Artifact Sensitivity PLUMBING Target Illuminance (IES 9th Edition) Daylight Sensor 0 Exhibit Light Yes Power Density (AHSRAE 2004) 0 Temperature Deviations (+/-) No No Process Water UPS Switched Receptacles Dimming Yes Humidity 0 No Other Humidity Deviation (+/-) As required by load No No Outside Air Single/Multi-Level Switching 0 Emergency/Standby Power As required by code 30/85 Yes Occupancy Sensor Special Exhaust Sub-metering & Feedback Displays Filtration (Pre/Final/Other) Voice/Data DATA/TELECOMMUNICATIONS Yes 0 SECURITY 0 7.5 kPA/26.7kN Floor Loading/Point Loads DAYLIGHTING 0 0 Shading Considerations Top/Side Lighting None No STRUCTURAL 0 0 Refer to information indicated in Volume IV, Section E 0 0 Technical Comment: Publications/Editor/Writer Assignable Square Feet (ASF) OFEO Space Dimensions 0 Organizational Unit Other Interior Glazing 0 0 0 0 0 Ceiling CRITICAL FINISHES 0 0
ELECTRICAL ARCHITECTURAL
Zone Room ID D1.38 Room Name 0 Functional Description Open office workspace with office furnishings including worksurface and file storage. Non Public-Non Collection Space 80 Number of Occupants 1 Visual Privacy (full, partial, open) Zone Designation Zone D Room Height 0 LEED
0 Base ACOUSTICS Equipment Hardware/STC Rating None NRC0 0 Plug Loads Air Change/ HR Walls HVAC ENGINEERING CRITERIA Temperature Lighting No Control ±2ºF 110v, 20a, 1ph Yes 0 Power No 0 Pressure (+/-) 78ºF Summer, 71ºF Winter Floor Operable Windows Separation/STC FURNITURE/EQUIPMENT Moveable 0 Fixed RT60 & Shaping 0 TBD
NC Regurlarly Occupied Space
Floor Level 0 Room
Open

This room data sheet is not comprehensive in nature. Information regarding specific room features may not have been available and was intentionally left

Accessibility Requirement:

Adjacencies

Compliance with ADA/ABAAG (2004) citations is required for accessibility. SI also requires compliance with SI Accessibility Guidelines and the IBC. Comparisons should be made and the more stringent requirement followed for design purposes. An accessible route including a minimum clear width of 36" (except through doors, which must be at least 32" clear) is required. Refer to ADA/ABAAG (2004) for specifications regarding clear floor spaces at desks, files and equipment for individuals using wheelchairs.See Accessibility Narrative for additional information.

Curatorial Affairs Offices, Staff Amenities and Meeting Rooms. Additional adjacency information is unavailable at this time pending finalization of organization chart by NMAAHC.

SUSTAINABILITY FEATURES

vs. Private

Please refer to structural narrative for more information on structural requirements.

CRITICAL DIMENSIONS

Length, Width, Shape

Smithsonian Institution National Museum of African American History and Culture 136 Infrastructure Only 0 Other Amenities Deionized Water Vacuum Yes Speakers OH Gr. 2, 130 SF/HD FIRE ALARM Smoke Detection Yes Wet Sprinkler Special Waste Dry Sprinkler Pre-Action Sprinkler No FIRE PROTECTION No Considerations for Water 0 No Floor Drains Floor Sink Grey/Blackwater Piping 0 No No No Protected Hot/Cold No No Recycled Water Supply (treated) 0 No Public Address Audio Compressed Air Audio Visual Requirements No Hot/Cold Water Task Light Yes No 0 Plant/Clean Steam No Acoustic Sensitivity 0 Vibration Sensitivity Special Equipment/Artifact Sensitivity PLUMBING Target Illuminance (IES 9th Edition) Daylight Sensor 0 Exhibit Light Yes Power Density (AHSRAE 2004) 0 Temperature Deviations (+/-) No No Process Water UPS Switched Receptacles Dimming Yes Humidity 0 No Other Humidity Deviation (+/-) As required by load No No Outside Air Single/Multi-Level Switching 0 Emergency/Standby Power As required by code 30/85 Yes Occupancy Sensor Special Exhaust Sub-metering & Feedback Displays Filtration (Pre/Final/Other) Voice/Data DATA/TELECOMMUNICATIONS Yes 0 SECURITY 0 5.0 kPa/8.9 kN Floor Loading/Point Loads DAYLIGHTING 0 0 Shading Considerations Top/Side Lighting None No STRUCTURAL 0 0 Refer to information indicated in Volume IV, Section E 0 0 Technical Comment: CAAMA Work Assignable Square Feet (ASF) OFEO Space Dimensions 0 Organizational Unit Other Interior Glazing 0 0 0 0 0 Ceiling CRITICAL FINISHES 0 0
ELECTRICAL ARCHITECTURAL
Zone Room ID D1.39 Room Name 0 Functional Description Open office workspace with office furnishings including worksurface and file storage. Non Public-Non Collection Space 320 Number of Occupants 1 Visual Privacy (full, partial, open) Zone Designation Zone D Room Height 0 LEED NC
0 Base ACOUSTICS Equipment Hardware/STC Rating None NRC0 0 Plug Loads Air Change/ HR Walls HVAC ENGINEERING CRITERIA Temperature Lighting No Control ±2ºF 110v, 20a, 1ph Yes 0 Power No 0 Pressure (+/-) 78ºF Summer, 71ºF Winter Floor Operable Windows Separation/STC FURNITURE/EQUIPMENT Moveable 0 Fixed RT60 & Shaping 0 TBD
blank.
Regurlarly Occupied Space
Floor Level 0 Room
Open

This room data sheet is not comprehensive in nature. Information regarding specific room features may not have been available and was intentionally left blank.

Accessibility Requirement:

Adjacencies

Compliance with ADA/ABAAG (2004) citations is required for accessibility. SI also requires compliance with SI Accessibility Guidelines and the IBC. Comparisons should be made and the more stringent requirement followed for design purposes. An accessible route including a minimum clear width of 36" (except through doors, which must be at least 32" clear) is required. Refer to ADA/ABAAG (2004) for specifications regarding clear floor spaces at desks, files and equipment for individuals using wheelchairs.See Accessibility Narrative for additional information.

Curatorial Affairs Offices, Staff Amenities and Meeting Rooms. Additional adjacency information is unavailable at this time pending finalization of organization chart by NMAAHC.

SUSTAINABILITY FEATURES

vs. Private

Please refer to structural narrative for more information on structural requirements.

CRITICAL DIMENSIONS

Length, Width, Shape

137 Room Data Sheets | FREELON BOND Infrastructure Only 0 Other Amenities Deionized Water Vacuum Yes Speakers OH Gr. 2, 130 SF/HD FIRE ALARM Smoke Detection Yes Wet Sprinkler Special Waste Dry Sprinkler Pre-Action Sprinkler No FIRE PROTECTION No Considerations for Water 0 No Floor Drains Floor Sink Grey/Blackwater Piping 0 No No No Protected Hot/Cold No No Recycled Water Supply (treated) 0 No Public Address Audio Compressed Air Audio Visual Requirements No Hot/Cold Water Task Light Yes No 0 Plant/Clean Steam No Acoustic Sensitivity 0 Vibration Sensitivity Special Equipment/Artifact Sensitivity PLUMBING Target Illuminance (IES 9th Edition) Daylight Sensor 0 Exhibit Light Yes Power Density (AHSRAE 2004) 0 Temperature Deviations (+/-) No No Process Water UPS Switched Receptacles Dimming Yes Humidity 0 No Other Humidity Deviation (+/-) As required by load No No Outside Air Single/Multi-Level Switching 0 Emergency/Standby Power As required by code 30/85 Yes Occupancy Sensor Special Exhaust Sub-metering & Feedback Displays Filtration (Pre/Final/Other) Voice/Data DATA/TELECOMMUNICATIONS Yes 0 SECURITY 0 5.0 kPa/8.9 kN Floor Loading/Point Loads DAYLIGHTING 0 0 Shading Considerations Top/Side Lighting None No STRUCTURAL 0 0 Refer to information indicated in Volume IV, Section E 0 0 Technical Comment: Archives (ws) Assignable Square Feet (ASF) OFEO Space Dimensions 0 Organizational Unit Other Interior Glazing 0 0 0 0 0 Ceiling CRITICAL FINISHES 0 0
ELECTRICAL ARCHITECTURAL
Zone Room ID D1.40 Room Name 0 Functional Description Open office workspace with office furnishings including worksurface and file storage. Non Public-Non Collection Space 160 Number of Occupants 1 Visual Privacy (full, partial, open) Zone Designation Zone D Room Height 0 LEED
0 Base ACOUSTICS Equipment Hardware/STC Rating None NRC0 0 Plug Loads Air Change/ HR Walls HVAC ENGINEERING CRITERIA Temperature Lighting No Control ±2ºF 110v, 20a, 1ph Yes 0 Power No 0 Pressure (+/-) 78ºF Summer, 71ºF Winter Floor Operable Windows Separation/STC FURNITURE/EQUIPMENT Moveable 0 Fixed RT60 & Shaping 0 TBD
NC Regurlarly Occupied Space
Floor Level 0 Room
Open

This room data sheet is not comprehensive in nature. Information regarding specific room features may not have been available and was intentionally left blank.

Accessibility Requirement:

Adjacencies

Compliance with ADA/ABAAG (2004) citations is required for accessibility. SI also requires compliance with SI Accessibility Guidelines and the IBC. Comparisons should be made and the more stringent requirement followed for design purposes. An accessible route including a minimum clear width of 36" (except through doors, which must be at least 32" clear) is required. Refer to ADA/ABAAG (2004) for specifications regarding clear floor spaces at desks, files and equipment for individuals using wheelchairs.See Accessibility Narrative for additional information.

Curatorial Affairs Offices, Staff Amenities and Meeting Rooms. Additional adjacency information is unavailable at this time pending finalization of organization chart by NMAAHC.

SUSTAINABILITY FEATURES

vs. Private

Please refer to structural narrative for more information on structural requirements.

CRITICAL DIMENSIONS

Length, Width, Shape

Smithsonian Institution National Museum of African American History and Culture 138 Infrastructure Only 0 Other Amenities Deionized Water Vacuum Yes Speakers OH Gr. 2, 130 SF/HD FIRE ALARM Smoke Detection Yes Wet Sprinkler Special Waste Dry Sprinkler Pre-Action Sprinkler No FIRE PROTECTION No Considerations for Water 0 No Floor Drains Floor Sink Grey/Blackwater Piping 0 No No No Protected Hot/Cold No No Recycled Water Supply (treated) 0 No Public Address Audio Compressed Air Audio Visual Requirements No Hot/Cold Water Task Light Yes No 0 Plant/Clean Steam No Acoustic Sensitivity 0 Vibration Sensitivity Special Equipment/Artifact Sensitivity PLUMBING Target Illuminance (IES 9th Edition) Daylight Sensor 0 Exhibit Light Yes Power Density (AHSRAE 2004) 0 Temperature Deviations (+/-) No No Process Water UPS Switched Receptacles Dimming Yes Humidity 0 No Other Humidity Deviation (+/-) As required by load No No Outside Air Single/Multi-Level Switching 0 Emergency/Standby Power As required by code 30/85 Yes Occupancy Sensor Special Exhaust Sub-metering & Feedback Displays Filtration (Pre/Final/Other) Voice/Data DATA/TELECOMMUNICATIONS Yes 0 SECURITY 0 5.0 kPa/8.9 kN Floor Loading/Point Loads DAYLIGHTING 0 0 Shading Considerations Top/Side Lighting None No STRUCTURAL 0 0 Refer to information indicated in Volume IV, Section E 0 0 Technical Comment: Registration (ws) Assignable Square Feet (ASF) OFEO Space Dimensions 0 Organizational Unit Other Interior Glazing 0 0 0 0 0 Ceiling CRITICAL FINISHES 0 0
ELECTRICAL ARCHITECTURAL
Zone Room ID D1.41 Room Name 0 Functional Description Open office workspace with office furnishings including worksurface and file storage. Non Public-Non Collection Space 560 Number of Occupants 1 Visual Privacy (full, partial, open) Zone Designation Zone D Room Height 0 LEED
0 Base ACOUSTICS Equipment Hardware/STC Rating None NRC0 0 Plug Loads Air Change/ HR Walls HVAC ENGINEERING CRITERIA Temperature Lighting No Control ±2ºF 110v, 20a, 1ph Yes 0 Power No 0 Pressure (+/-) 78ºF Summer, 71ºF Winter Floor Operable Windows Separation/STC FURNITURE/EQUIPMENT Moveable 0 Fixed RT60 & Shaping 0 TBD
NC Regurlarly Occupied Space
Floor Level 0 Room
Open

This room data sheet is not comprehensive in nature. Information regarding specific room features may not have been available and was intentionally left blank.

Accessibility Requirement:

Adjacencies

Compliance with ADA/ABAAG (2004) citations is required for accessibility. SI also requires compliance with SI Accessibility Guidelines and the IBC. Comparisons should be made and the more stringent requirement followed for design purposes. An accessible route including a minimum clear width of 36" (except through doors, which must be at least 32" clear) is required. Refer to ADA/ABAAG (2004) for specifications regarding clear floor spaces at desks, files and equipment for individuals using wheelchairs.See Accessibility Narrative for additional information.

Curatorial Affairs Offices, Staff Amenities and Meeting Rooms. Additional adjacency information is unavailable at this time pending finalization of organization chart by NMAAHC.

SUSTAINABILITY FEATURES

vs. Private

Please refer to structural narrative for more information on structural requirements.

CRITICAL DIMENSIONS

Length, Width, Shape

139 Room Data Sheets | FREELON BOND Infrastructure Only 0 Other Amenities Deionized Water Vacuum Yes Speakers OH Gr. 2, 130 SF/HD FIRE ALARM Smoke Detection Yes Wet Sprinkler Special Waste Dry Sprinkler Pre-Action Sprinkler No FIRE PROTECTION No Considerations for Water 0 No Floor Drains Floor Sink Grey/Blackwater Piping 0 No No No Protected Hot/Cold No No Recycled Water Supply (treated) 0 No Public Address Audio Compressed Air Audio Visual Requirements No Hot/Cold Water Task Light Yes No 0 Plant/Clean Steam No Acoustic Sensitivity 0 Vibration Sensitivity Special Equipment/Artifact Sensitivity PLUMBING Target Illuminance (IES 9th Edition) Daylight Sensor 0 Exhibit Light Yes Power Density (AHSRAE 2004) 0 Temperature Deviations (+/-) No No Process Water UPS Switched Receptacles Dimming Yes Humidity 0 No Other Humidity Deviation (+/-) As required by load No No Outside Air Single/Multi-Level Switching 0 Emergency/Standby Power As required by code 30/85 Yes Occupancy Sensor Special Exhaust Sub-metering & Feedback Displays Filtration (Pre/Final/Other) Voice/Data DATA/TELECOMMUNICATIONS Yes 0 SECURITY 0 5.0 kPa/8.9 kN Floor Loading/Point Loads DAYLIGHTING 0 0 Shading Considerations Top/Side Lighting None No STRUCTURAL 0 0 Refer to information indicated in Volume IV, Section E 0 0 Technical Comment: Conservation (ws) Assignable Square Feet (ASF) OFEO Space Dimensions 0 Organizational Unit Other Interior Glazing 0 0 0 0 0 Ceiling CRITICAL FINISHES 0 0
ELECTRICAL ARCHITECTURAL
Zone Room ID D1.42 Room Name 0 Functional Description Open office workspace with office furnishings including worksurface and file storage. Non Public-Non Collection Space 240 Number of Occupants 1 Visual Privacy (full, partial, open) Zone Designation Zone D Room Height 0 LEED
0 Base ACOUSTICS Equipment Hardware/STC Rating None NRC0 0 Plug Loads Air Change/ HR Walls HVAC ENGINEERING CRITERIA Temperature Lighting No Control ±2ºF 110v, 20a, 1ph Yes 0 Power No 0 Pressure (+/-) 78ºF Summer, 71ºF Winter Floor Operable Windows Separation/STC FURNITURE/EQUIPMENT Moveable 0 Fixed RT60 & Shaping 0 TBD
NC Regurlarly Occupied Space
Floor Level 0 Room
Open

This room data sheet is not comprehensive in nature. Information regarding specific room features may not have been available and was intentionally left blank.

Accessibility Requirement:

Adjacencies

Compliance with ADA/ABAAG (2004) citations is required for accessibility. SI also requires compliance with SI Accessibility Guidelines and the IBC. Comparisons should be made and the more stringent requirement followed for design purposes. An accessible route including a minimum clear width of 36" (except through doors, which must be at least 32" clear) is required. Refer to ADA/ABAAG (2004) for specifications regarding clear floor spaces at desks, files and equipment for individuals using wheelchairs.See Accessibility Narrative for additional information.

Curatorial Affairs Offices, Staff Amenities and Meeting Rooms. Additional adjacency information is unavailable at this time pending finalization of organization chart by NMAAHC.

SUSTAINABILITY FEATURES

vs. Private

Please refer to structural narrative for more information on structural requirements.

CRITICAL DIMENSIONS

Length, Width, Shape

Smithsonian Institution National Museum of African American History and Culture 140 Infrastructure Only 0 Other Amenities Deionized Water Vacuum Yes Speakers OH Gr. 2, 130 SF/HD FIRE ALARM Smoke Detection Yes Wet Sprinkler Special Waste Dry Sprinkler Pre-Action Sprinkler No FIRE PROTECTION No Considerations for Water 0 No Floor Drains Floor Sink Grey/Blackwater Piping 0 No No No Protected Hot/Cold No No Recycled Water Supply (treated) 0 No Public Address Audio Compressed Air Audio Visual Requirements No Hot/Cold Water Task Light Yes No 0 Plant/Clean Steam No Acoustic Sensitivity 0 Vibration Sensitivity Special Equipment/Artifact Sensitivity PLUMBING Target Illuminance (IES 9th Edition) Daylight Sensor 0 Exhibit Light Yes Power Density (AHSRAE 2004) 0 Temperature Deviations (+/-) No No Process Water UPS Switched Receptacles Dimming Yes Humidity 0 No Other Humidity Deviation (+/-) As required by load No No Outside Air Single/Multi-Level Switching 0 Emergency/Standby Power As required by code 30/85 Yes Occupancy Sensor Special Exhaust Sub-metering & Feedback Displays Filtration (Pre/Final/Other) Voice/Data DATA/TELECOMMUNICATIONS Yes 0 SECURITY 0 5.0 kPa/8.9 kN Floor Loading/Point Loads DAYLIGHTING 0 0 Shading Considerations Top/Side Lighting None No STRUCTURAL 0 0 Refer to information indicated in Volume IV, Section E 0 0 Technical Comment: Affiliations Assignable Square Feet (ASF) OFEO Space Dimensions 0 Organizational Unit Other Interior Glazing 0 0 0 0 0 Ceiling CRITICAL FINISHES 0 0
ELECTRICAL ARCHITECTURAL
Zone Room ID D1.43 Room Name 0 Functional Description Open office workspace with office furnishings including worksurface and file storage. Non Public-Non Collection Space 80 Number of Occupants 1 Visual Privacy (full, partial, open) Zone Designation Zone D Room Height 0 LEED NC
0 Base ACOUSTICS Equipment Hardware/STC Rating None NRC0 0 Plug Loads Air Change/ HR Walls HVAC ENGINEERING CRITERIA Temperature Lighting No Control ±2ºF 110v, 20a, 1ph Yes 0 Power No 0 Pressure (+/-) 78ºF Summer, 71ºF Winter Floor Operable Windows Separation/STC FURNITURE/EQUIPMENT Moveable 0 Fixed RT60 & Shaping 0 TBD
Regurlarly Occupied Space
Floor Level 0 Room
Open

This room data sheet is not comprehensive in nature. Information regarding specific room features may not have been available and was intentionally left blank.

SUSTAINABILITY FEATURES Adjacencies Accessibility Requirement:

Compliance with ADA/ABAAG (2004) citations is required for accessibility. SI also requires compliance with SI Accessibility Guidelines and the IBC. Comparisons should be made and the more stringent requirement followed for design purposes. An accessible route including a minimum clear width of 36" (except through doors, which must be at least 32" clear) is required. Refer to ADA/ABAAG (2004) for specifications regarding clear floor spaces at desks, files and equipment for individuals using wheelchairs.See Accessibility Narrative for additional information.

Curatorial Affairs Offices, Staff Amenities and Meeting Rooms. Additional adjacency information is unavailable at this time pending finalization of organization chart by NMAAHC.

CRITICAL DIMENSIONS

Please refer to structural narrative for more information on structural requirements.

141 Room Data Sheets | FREELON BOND Infrastructure Only 0 Other Amenities Deionized Water Vacuum Yes Speakers OH Gr. 2, 130 SF/HD FIRE ALARM Smoke Detection Yes Wet Sprinkler Special Waste Dry Sprinkler Pre-Action Sprinkler No FIRE PROTECTION No Considerations for Water 0 No Floor Drains Floor Sink Grey/Blackwater Piping 0 No No No Protected Hot/Cold No No Recycled Water Supply (treated) 0 No Public Address Audio Compressed Air Audio Visual Requirements No Hot/Cold Water Task Light Yes No 0 Plant/Clean Steam No Acoustic Sensitivity 0 Vibration Sensitivity Special Equipment/Artifact Sensitivity PLUMBING Target Illuminance (IES 9th Edition) Daylight Sensor 0 Exhibit Light Yes Power Density (AHSRAE 2004) 0 Temperature Deviations (+/-) No No Process Water UPS Switched Receptacles Dimming Yes Humidity 0 No Other Humidity Deviation (+/-) As required by load No No Outside Air Single/Multi-Level Switching 0 Emergency/Standby Power As required by code 30/85 Yes Occupancy Sensor Special Exhaust Sub-metering & Feedback Displays Filtration (Pre/Final/Other) Voice/Data DATA/TELECOMMUNICATIONS Yes 0 SECURITY 0 5.0 kPa/8.9 kN Floor Loading/Point Loads DAYLIGHTING 0 0 Shading Considerations Top/Side Lighting None No STRUCTURAL 0 0 Refer to information indicated in Volume IV, Section E 0 0 Technical Comment: Education & Public Programs (WS) Assignable Square Feet (ASF) OFEO Space Dimensions 0 Organizational Unit Other Interior Glazing 0 0 0 0 0 Ceiling CRITICAL FINISHES 0 0
ELECTRICAL ARCHITECTURAL
Zone Room ID D1.44 Room Name 0 Functional Description Open office workspace with office furnishings including worksurface and file storage. Non Public-Non Collection Space 320 Number of Occupants 1 Visual Privacy (full, partial, open) Zone Designation Zone D Room Height 0 LEED
0 Base ACOUSTICS Equipment Hardware/STC Rating None NRC0 0 Plug Loads Air Change/ HR Walls HVAC ENGINEERING CRITERIA Temperature Lighting No Control ±2ºF 110v, 20a, 1ph Yes 0 Power No 0 Pressure (+/-) 78ºF Summer, 71ºF Winter Floor Operable Windows Separation/STC FURNITURE/EQUIPMENT Moveable 0 Fixed RT60 & Shaping 0 TBD
NC Regurlarly Occupied Space
Floor Level 0 Room
Length, Width, Shape Open vs. Private

This room data sheet is not comprehensive in nature. Information regarding specific room features may not have been available and was intentionally left

Accessibility Requirement:

Adjacencies

Compliance with ADA/ABAAG (2004) citations is required for accessibility. SI also requires compliance with SI Accessibility Guidelines and the IBC. Comparisons should be made and the more stringent requirement followed for design purposes. An accessible route including a minimum clear width of 36" (except through doors, which must be at least 32" clear) is required. Refer to ADA/ABAAG (2004) for specifications regarding clear floor spaces at desks, files and equipment for individuals using wheelchairs.See Accessibility Narrative for additional information.

Located in Resource Center. Additional adjacency information is unavailable at this time pending finalization of organization chart by NMAAHC.

SUSTAINABILITY FEATURES

vs. Private

Please refer to structural narrative for more information on structural requirements.

CRITICAL DIMENSIONS

Length, Width, Shape

Smithsonian Institution National Museum of African American History and Culture 142 Infrastructure Only 0 Other Amenities Deionized Water Vacuum Yes Speakers OH Gr. 2, 130 SF/HD FIRE ALARM Smoke Detection Yes Wet Sprinkler Special Waste Dry Sprinkler Pre-Action Sprinkler No FIRE PROTECTION No Considerations for Water 0 No Floor Drains Floor Sink Grey/Blackwater Piping 0 No No No Protected Hot/Cold No No Recycled Water Supply (treated) 0 No Public Address Audio Compressed Air Audio Visual Requirements No Hot/Cold Water Task Light Yes No 0 Plant/Clean Steam No Acoustic Sensitivity 0 Vibration Sensitivity Special Equipment/Artifact Sensitivity PLUMBING Target Illuminance (IES 9th Edition) Daylight Sensor 0 Exhibit Light Yes Power Density (AHSRAE 2004) 0 Temperature Deviations (+/-) No No Process Water UPS Switched Receptacles Dimming Yes Humidity 0 No Other Humidity Deviation (+/-) As required by load No No Outside Air Single/Multi-Level Switching 0 Emergency/Standby Power As required by code 30/85 Yes Occupancy Sensor Special Exhaust Sub-metering & Feedback Displays Filtration (Pre/Final/Other) Voice/Data DATA/TELECOMMUNICATIONS Yes 0 SECURITY 0 5.0 kPa/8.9 kN Floor Loading/Point Loads DAYLIGHTING 0 0 Shading Considerations Top/Side Lighting None No STRUCTURAL 0 0 Refer to information indicated in Volume IV, Section E 0 0 Technical Comment: Resource Center WS Assignable Square Feet (ASF) OFEO Space Dimensions 0 Organizational Unit Other Interior Glazing 0 0 0 0 0 Ceiling CRITICAL FINISHES 0 0
ELECTRICAL ARCHITECTURAL
Zone Room ID D1.45 Room Name 0 Functional Description Open office workspace with office furnishings including worksurface and file storage. Non Public-Non Collection Space 80 Number of Occupants 1 Visual Privacy (full, partial, open) Zone Designation Zone D Room Height 0 LEED NC
0 Base ACOUSTICS Equipment Hardware/STC Rating None NRC0 0 Plug Loads Air Change/ HR Walls HVAC ENGINEERING CRITERIA Temperature Lighting No Control ±2ºF 110v, 20a, 1ph Yes 0 Power No 0 Pressure (+/-) 78ºF Summer, 71ºF Winter Floor Operable Windows Separation/STC FURNITURE/EQUIPMENT Moveable 0 Fixed RT60 &
0 TBD
blank.
Regurlarly Occupied Space
Shaping
Floor Level 0 Room
Open

This room data sheet is not comprehensive in nature. Information regarding specific room features may not have been available and was intentionally left blank.

Compliance with ADA/ABAAG (2004) citations is required for accessibility. SI also requires compliance with SI Accessibility Guidelines and the IBC. Comparisons should be made and the more stringent requirement followed for design purposes. An accessible route including a minimum clear width of 36" (except through doors, which must be at least 32" clear) is required. Refer to ADA/ABAAG (2004) for specifications regarding clear floor spaces at desks, files and equipment for individuals using wheelchairs.See Accessibility Narrative for additional information.

Curatorial Affairs Offices, Staff Amenities and Meeting Rooms. Additional adjacency information is unavailable at this time pending finalization of organization chart by NMAAHC.

CRITICAL DIMENSIONS

vs. Private

Please refer to structural narrative for more information on structural requirements.

143 Room Data Sheets | FREELON BOND Infrastructure Only 0 Other Amenities Deionized Water Vacuum Yes Speakers OH Gr. 2, 130 SF/HD FIRE ALARM Smoke Detection Yes Wet Sprinkler Special Waste Dry Sprinkler Pre-Action Sprinkler No FIRE PROTECTION No Considerations for Water 0 No Floor Drains Floor Sink Grey/Blackwater Piping 0 No No No Protected Hot/Cold No No Recycled Water Supply (treated) 0 No Public Address Audio Compressed Air Audio Visual Requirements No Hot/Cold Water Task Light Yes No 0 Plant/Clean Steam No Acoustic Sensitivity 0 Vibration Sensitivity Special Equipment/Artifact Sensitivity PLUMBING Target Illuminance (IES 9th Edition) Daylight Sensor 0 Exhibit Light Yes Power Density (AHSRAE 2004) 0 Temperature Deviations (+/-) No No Process Water UPS Switched Receptacles Dimming Yes Humidity 0 No Other Humidity Deviation (+/-) As required by load No No Outside Air Single/Multi-Level Switching 0 Emergency/Standby Power As required by code 30/85 Yes Occupancy Sensor Special Exhaust Sub-metering & Feedback Displays Filtration (Pre/Final/Other) Voice/Data DATA/TELECOMMUNICATIONS Yes 0 SECURITY 0 5.0 kPa/8.9 kN Floor Loading/Point Loads DAYLIGHTING 0 0 Shading Considerations Top/Side Lighting None No STRUCTURAL 0 0 Refer to information indicated in Volume IV, Section E 0 0 Technical Comment: Web & New Media WS Assignable Square Feet (ASF) OFEO Space Dimensions 0 Organizational Unit Other Interior Glazing 0 0 0 0 0 Ceiling CRITICAL FINISHES 0 0
ELECTRICAL ARCHITECTURAL
Zone Room ID D1.46 Room Name 0 Functional Description Open office workspace with office furnishings including worksurface and file storage. Non Public-Non Collection Space 400 Number of Occupants 1 Visual Privacy (full, partial, open) Zone Designation Zone D Room Height 0 LEED
0 Base ACOUSTICS Equipment Hardware/STC Rating None NRC0 0 Plug Loads Air Change/ HR Walls HVAC ENGINEERING CRITERIA Temperature Lighting No Control ±2ºF 110v, 20a, 1ph Yes 0 Power No 0 Pressure (+/-) 78ºF Summer, 71ºF Winter Floor Operable Windows Separation/STC FURNITURE/EQUIPMENT Moveable 0 Fixed RT60 & Shaping 0 TBD
NC Regurlarly Occupied Space
Floor Level 0 Room
Open
SUSTAINABILITY FEATURES Adjacencies Accessibility Requirement:
Length, Width, Shape

This room data sheet is not comprehensive in nature. Information regarding specific room features may not have been available and was intentionally left blank.

SUSTAINABILITY FEATURES Adjacencies Accessibility Requirement:

Compliance with ADA/ABAAG (2004) citations is required for accessibility. SI also requires compliance with SI Accessibility Guidelines and the IBC. Comparisons should be made and the more stringent requirement followed for design purposes. An accessible route including a minimum clear width of 36" (except through doors, which must be at least 32" clear) is required. Refer to ADA/ABAAG (2004) for specifications regarding clear floor spaces at desks, files and equipment for individuals using wheelchairs.See Accessibility Narrative for additional information.

Curatorial Affairs Offices, Staff Amenities and Meeting Rooms. Additional adjacency information is unavailable at this time pending finalization of organization chart by NMAAHC.

CRITICAL DIMENSIONS

Length, Width, Shape

Please refer to structural narrative for more information on structural requirements.

Smithsonian Institution National Museum of African American History and Culture 144 Infrastructure Only 0 Other Amenities Deionized Water Vacuum Yes Speakers OH Gr. 2, 130 SF/HD FIRE ALARM Smoke Detection Yes Wet Sprinkler Special Waste Dry Sprinkler Pre-Action Sprinkler No FIRE PROTECTION No Considerations for Water 0 No Floor Drains Floor Sink Grey/Blackwater Piping 0 No No No Protected Hot/Cold No No Recycled Water Supply (treated) 0 No Public Address Audio Compressed Air Audio Visual Requirements No Hot/Cold Water Task Light Yes No 0 Plant/Clean Steam No Acoustic Sensitivity 0 Vibration Sensitivity Special Equipment/Artifact Sensitivity PLUMBING Target Illuminance (IES 9th Edition) Daylight Sensor 0 Exhibit Light Yes Power Density (AHSRAE 2004) 0 Temperature Deviations (+/-) No No Process Water UPS Switched Receptacles Dimming Yes Humidity 0 No Other Humidity Deviation (+/-) As required by load No No Outside Air Single/Multi-Level Switching 0 Emergency/Standby Power As required by code 30/85 Yes Occupancy Sensor Special Exhaust Sub-metering & Feedback Displays Filtration (Pre/Final/Other) Voice/Data DATA/TELECOMMUNICATIONS Yes 0 SECURITY 0 5.0 kPa/8.9 kN Floor Loading/Point Loads DAYLIGHTING 0 0 Shading Considerations Top/Side Lighting None No STRUCTURAL 0 0 Refer to information indicated in Volume IV, Section E 0 0 Technical Comment: Visitor Services WS Assignable Square Feet (ASF) OFEO Space Dimensions 0 Organizational Unit Other Interior Glazing 0 0 0 0 0 Ceiling CRITICAL FINISHES 0 0
ELECTRICAL ARCHITECTURAL
Zone Room ID D1.47 Room Name 0 Functional Description Open office workspace with office furnishings including worksurface and file storage. Non Public-Non Collection Space 720 Number of Occupants 1 Visual Privacy (full, partial, open) Zone Designation Zone D Room Height 0 LEED
0 Base ACOUSTICS Equipment Hardware/STC Rating None NRC0 0 Plug Loads Air Change/ HR Walls HVAC ENGINEERING CRITERIA Temperature Lighting No Control ±2ºF 110v, 20a, 1ph Yes 0 Power No 0 Pressure (+/-) 78ºF Summer, 71ºF Winter Floor Operable Windows Separation/STC FURNITURE/EQUIPMENT Moveable 0 Fixed RT60 & Shaping 0 TBD
NC Regurlarly Occupied Space
Floor Level 0 Room
Open vs. Private

This room data sheet is not comprehensive in nature. Information regarding specific room features may not have been available and was intentionally left blank.

SUSTAINABILITY FEATURES Adjacencies Accessibility Requirement:

with ADA/ABAAG (2004)G citations is required for accessibility. SI also requires compliance with SI Accessibility Guidelines and the IBC. Comparisons should be made and the more stringent requirement followed for design purposes. An accessible route including a minimum clear width of 36" (except through doors, which must be at least 32" clear) is required. Refer to ADA/ABAAG (2004) for specifications regarding clear floor spaces at desks, files and equipment for individuals using wheelchairs.See Accessibility Narrative for additional information. Curatorial Affairs Offices, Staff Amenities and Meeting Rooms. Additional adjacency information is unavailable at this time pending finalization of organization chart by NMAAHC.

CRITICAL DIMENSIONS

Please refer to structural narrative for more information on structural requirements.

145 Room Data Sheets | FREELON BOND Infrastructure Only 0 Other Amenities Deionized Water Vacuum Yes Speakers OH Gr. 2, 130 SF/HD FIRE ALARM Smoke Detection Yes Wet Sprinkler Special Waste Dry Sprinkler Pre-Action Sprinkler No FIRE PROTECTION No Considerations for Water 0 No Floor Drains Floor Sink Grey/Blackwater Piping 0 No No No Protected Hot/Cold No No Recycled Water Supply (treated) 0 No Public Address Audio Compressed Air Audio Visual Requirements No Hot/Cold Water Task Light Yes No 0 Plant/Clean Steam No Acoustic Sensitivity 0 Vibration Sensitivity Special Equipment/Artifact Sensitivity PLUMBING Target Illuminance (IES 9th Edition) Daylight Sensor 0 Exhibit Light Yes Power Density (AHSRAE 2004) 0 Temperature Deviations (+/-) No No Process Water UPS Switched Receptacles Dimming Yes Humidity 0 No Other Humidity Deviation (+/-) As required by load No No Outside Air Single/Multi-Level Switching 0 Emergency/Standby Power As required by code 30/85 Yes Occupancy Sensor Special Exhaust Sub-metering & Feedback Displays Filtration (Pre/Final/Other) Voice/Data DATA/TELECOMMUNICATIONS Yes 0 SECURITY 0 5.0 kPa/8.9 kN Floor Loading/Point Loads DAYLIGHTING 0 0 Shading Considerations Top/Side Lighting None No STRUCTURAL 0 0 Refer to information indicated in Volume IV, Section E 0 0 Technical Comment: Partnerships/Scholarly Programs WS Assignable Square Feet (ASF) OFEO Space Dimensions 0 Organizational Unit Other Interior Glazing 0 0 0 0 0 Ceiling CRITICAL FINISHES 0 0
ELECTRICAL ARCHITECTURAL
Zone Room ID D1.48 Room Name 0 Functional Description Open office workspace with office furnishings including worksurface and file storage. Non Public-Non Collection Space 80 Number of Occupants 1 Visual Privacy (full, partial, open) Zone Designation Zone D Room Height 0 LEED NC
0 Base ACOUSTICS Equipment Hardware/STC Rating None NRC0 0 Plug Loads Air Change/ HR Walls HVAC ENGINEERING CRITERIA Temperature Lighting No Control ±2ºF 110v, 20a, 1ph Yes 0 Power No 0 Pressure (+/-) 78ºF Summer, 71ºF Winter Floor Operable Windows Separation/STC FURNITURE/EQUIPMENT Moveable 0 Fixed RT60 & Shaping 0 TBD
Regurlarly Occupied Space
Compliance
Floor Level 0 Room
Length, Width, Shape Open vs. Private

This room data sheet is not comprehensive in nature. Information regarding specific room features may not have been available and was intentionally left

Accessibility Requirement:

Adjacencies

SUSTAINABILITY FEATURES

Compliance with ADA/ABAAG (2004) citations is required for accessibility. SI also requires compliance with SI Accessibility Guidelines and the IBC. Comparisons should be made and the more stringent requirement followed for design purposes. An accessible route including a minimum clear width of 36" (except through doors, which must be at least 32" clear) is required. Refer to ADA/ABAAG (2004) for specifications regarding clear floor spaces at desks, files and equipment for individuals using wheelchairs.See Accessibility Narrative for additional information.

Curatorial Affairs Offices, Staff Amenities and Meeting Rooms. Additional adjacency information is unavailable at this time pending finalization of organization chart by NMAAHC.

CRITICAL DIMENSIONS

Length, Width, Shape

Please refer to structural narrative for more information on structural requirements.

Smithsonian Institution National Museum of African American History and Culture 146 Infrastructure Only 0 Other Amenities Deionized Water Vacuum Yes Speakers OH Gr. 2, 130 SF/HD FIRE ALARM Smoke Detection Yes Wet Sprinkler Special Waste Dry Sprinkler Pre-Action Sprinkler No FIRE PROTECTION No Considerations for Water 0 No Floor Drains Floor Sink Grey/Blackwater Piping 0 No No No Protected Hot/Cold No No Recycled Water Supply (treated) 0 No Public Address Audio Compressed Air Audio Visual Requirements No Hot/Cold Water Task Light Yes No 0 Plant/Clean Steam No Acoustic Sensitivity 0 Vibration Sensitivity Special Equipment/Artifact Sensitivity PLUMBING Target Illuminance (IES 9th Edition) Daylight Sensor 0 Exhibit Light Yes Power Density (AHSRAE 2004) 0 Temperature Deviations (+/-) No No Process Water UPS Switched Receptacles Dimming Yes Humidity 0 No Other Humidity Deviation (+/-) As required by load No No Outside Air Single/Multi-Level Switching 0 Emergency/Standby Power As required by code 30/85 Yes Occupancy Sensor Special Exhaust Sub-metering & Feedback Displays Filtration (Pre/Final/Other) Voice/Data DATA/TELECOMMUNICATIONS Yes 0 SECURITY 0 5.0 kPa/8.9 kN Floor Loading/Point Loads DAYLIGHTING 0 0 Shading Considerations Top/Side Lighting None No STRUCTURAL 0 0 Refer to information indicated in Volume IV, Section E 0 0 Technical Comment: Local Programs WS Assignable Square Feet (ASF) OFEO Space Dimensions 0 Organizational Unit Other Interior Glazing 0 0 0 0 0 Ceiling CRITICAL FINISHES 0 0
ELECTRICAL ARCHITECTURAL
Zone Room ID D1.49 Room Name 0 Functional Description Open office workspace with office furnishings including worksurface and file storage. Non Public-Non Collection Space 80 Number of Occupants 1 Visual Privacy (full, partial, open) Zone Designation Zone D Room Height 0 LEED NC
0 Base ACOUSTICS Equipment Hardware/STC Rating None NRC0 0 Plug Loads Air Change/ HR Walls HVAC ENGINEERING CRITERIA Temperature Lighting No Control ±2ºF 110v, 20a, 1ph Yes 0 Power No 0 Pressure (+/-) 78ºF Summer, 71ºF Winter Floor Operable Windows Separation/STC FURNITURE/EQUIPMENT Moveable 0 Fixed RT60 & Shaping 0 TBD
blank.
Regurlarly Occupied Space
Floor Level 0 Room
Open vs. Private

This room data sheet is not comprehensive in nature. Information regarding specific room features may not have been available and was intentionally left

Accessibility Requirement:

Adjacencies

SUSTAINABILITY FEATURES

Compliance with ADA/ABAAG (2004) citations is required for accessibility. SI also requires compliance with SI Accessibility Guidelines and the IBC. Comparisons should be made and the more stringent requirement followed for design purposes. An accessible route including a minimum clear width of 36" (except through doors, which must be at least 32" clear) is required. Refer to ADA/ABAAG (2004) for specifications regarding clear floor spaces at desks, files and equipment for individuals using wheelchairs.See Accessibility Narrative for additional information.

Curatorial Affairs Offices, Staff Amenities and Meeting Rooms. Additional adjacency information is unavailable at this time pending finalization of organization chart by NMAAHC.

CRITICAL DIMENSIONS

Length, Width, Shape Open vs. Private

Please refer to structural narrative for more information on structural requirements.

147 Room Data Sheets | FREELON BOND Infrastructure Only 0 Other Amenities Deionized Water Vacuum Yes Speakers OH Gr. 2, 130 SF/HD FIRE ALARM Smoke Detection Yes Wet Sprinkler Special Waste Dry Sprinkler Pre-Action Sprinkler No FIRE PROTECTION No Considerations for Water 0 No Floor Drains Floor Sink Grey/Blackwater Piping 0 No No No Protected Hot/Cold No No Recycled Water Supply (treated) 0 No Public Address Audio Compressed Air Audio Visual Requirements No Hot/Cold Water Task Light Yes No 0 Plant/Clean Steam No Acoustic Sensitivity 0 Vibration Sensitivity Special Equipment/Artifact Sensitivity PLUMBING Target Illuminance (IES 9th Edition) Daylight Sensor 0 Exhibit Light Yes Power Density (AHSRAE 2004) 0 Temperature Deviations (+/-) No No Process Water UPS Switched Receptacles Dimming Yes Humidity 0 No Other Humidity Deviation (+/-) As required by load No No Outside Air Single/Multi-Level Switching 0 Emergency/Standby Power As required by code 30/85 Yes Occupancy Sensor Special Exhaust Sub-metering & Feedback Displays Filtration (Pre/Final/Other) Voice/Data DATA/TELECOMMUNICATIONS Yes 0 SECURITY 0 5.0 kPa/8.9 kN Floor Loading/Point Loads DAYLIGHTING 0 0 Shading Considerations Top/Side Lighting None No STRUCTURAL 0 0 Refer to information indicated in Volume IV, Section E 0 0 Technical Comment: Management Support Assignable Square Feet (ASF) OFEO Space Dimensions 0 Organizational Unit Other Interior Glazing 0 0 0 0 0 Ceiling CRITICAL FINISHES 0 0
ELECTRICAL ARCHITECTURAL
blank. Zone Room ID D1.50 Room Name 0 Functional Description Open office workspace with office furnishings including worksurface and file storage. Non Public-Non Collection Space 400 Number of Occupants 1 Visual Privacy (full, partial, open) Zone Designation Zone D Room Height 0 LEED NC Regurlarly
0 Base ACOUSTICS Equipment Hardware/STC Rating None NRC0 0 Plug Loads Air Change/ HR Walls HVAC ENGINEERING CRITERIA Temperature Lighting No Control ±2ºF 110v, 20a, 1ph Yes 0 Power No 0 Pressure (+/-) 78ºF Summer, 71ºF Winter Floor Operable Windows Separation/STC FURNITURE/EQUIPMENT Moveable 0 Fixed RT60 &
0 TBD
Occupied Space
Shaping
Floor Level 0 Room

This room data sheet is not comprehensive in nature. Information regarding specific room features may not have been available and was intentionally left

Accessibility Requirement:

Adjacencies

Compliance with ADA/ABAAG (2004) citations is required for accessibility. SI also requires compliance with SI Accessibility Guidelines and the IBC. Comparisons should be made and the more stringent requirement followed for design purposes. An accessible route including a minimum clear width of 36" (except through doors, which must be at least 32" clear) is required. Refer to ADA/ABAAG (2004) for specifications regarding clear floor spaces at desks, files and equipment for individuals using wheelchairs.See Accessibility Narrative for additional information.

Development & Public Affairs Offices, Staff Amenities, and Meeting Rooms. Additional adjacency information is unavailable at this time pending finalization of organization chart by NMAAHC.

SUSTAINABILITY FEATURES

vs. Private

Please refer to structural narrative for more information on structural requirements.

CRITICAL DIMENSIONS

Length, Width, Shape

Smithsonian Institution National Museum of African American History and Culture 148 Infrastructure Only 0 Other Amenities Deionized Water Vacuum Yes Speakers OH Gr. 2, 130 SF/HD FIRE ALARM Smoke Detection Yes Wet Sprinkler Special Waste Dry Sprinkler Pre-Action Sprinkler No FIRE PROTECTION No Considerations for Water 0 No Floor Drains Floor Sink Grey/Blackwater Piping 0 No No No Protected Hot/Cold No No Recycled Water Supply (treated) 0 No Public Address Audio Compressed Air Audio Visual Requirements No Hot/Cold Water Task Light Yes No 0 Plant/Clean Steam No Acoustic Sensitivity 0 Vibration Sensitivity Special Equipment/Artifact Sensitivity PLUMBING Target Illuminance (IES 9th Edition) Daylight Sensor 0 Exhibit Light Yes Power Density (AHSRAE 2004) 0 Temperature Deviations (+/-) No No Process Water UPS Switched Receptacles Dimming Yes Humidity 0 No Other Humidity Deviation (+/-) As required by load No No Outside Air Single/Multi-Level Switching 0 Emergency/Standby Power As required by code 30/85 Yes Occupancy Sensor Special Exhaust Sub-metering & Feedback Displays Filtration (Pre/Final/Other) Voice/Data DATA/TELECOMMUNICATIONS Yes 0 SECURITY 0 5.0 kPa/8.9 kN Floor Loading/Point Loads DAYLIGHTING 0 0 Shading Considerations Top/Side Lighting None No STRUCTURAL 0 0 Refer to information indicated in Volume IV, Section E 0 0 Technical Comment: Development WS Assignable Square Feet (ASF) OFEO Space Dimensions 0 Organizational Unit Other Interior Glazing 0 0 0 0 0 Ceiling CRITICAL FINISHES 0 0
ELECTRICAL
ARCHITECTURAL
Zone Room ID D1.51 Room Name 0 Functional Description Open office workspace with office furnishings including worksurface and file storage. Non Public-Non Collection Space 640 Number of Occupants 1 Visual Privacy (full, partial, open) Zone Designation Zone D Room Height 0 LEED NC Regurlarly
0 Base ACOUSTICS Equipment Hardware/STC Rating None NRC0 0 Plug Loads Air Change/ HR Walls HVAC ENGINEERING CRITERIA Temperature Lighting No Control ±2ºF 110v, 20a, 1ph Yes 0 Power No 0 Pressure (+/-) 78ºF Summer, 71ºF Winter Floor Operable Windows Separation/STC FURNITURE/EQUIPMENT Moveable 0 Fixed RT60 & Shaping 0 TBD
blank.
Occupied Space
Floor Level 0 Room
Open

This room data sheet is not comprehensive in nature. Information regarding specific room features may not have been available and was intentionally left

Accessibility Requirement:

Adjacencies

Compliance with ADA/ABAAG (2004) citations is required for accessibility. SI also requires compliance with SI Accessibility Guidelines and the IBC. Comparisons should be made and the more stringent requirement followed for design purposes. An accessible route including a minimum clear width of 36" (except through doors, which must be at least 32" clear) is required. Refer to ADA/ABAAG (2004) for specifications regarding clear floor spaces at desks, files and equipment for individuals using wheelchairs.See Accessibility Narrative for additional information.

Development & Public Affairs Offices, Staff Amenities, and Meeting Rooms. Additional adjacency information is unavailable at this time pending finalization of organization chart by NMAAHC.

SUSTAINABILITY FEATURES

vs. Private

Please refer to structural narrative for more information on structural requirements.

CRITICAL DIMENSIONS

Length, Width, Shape

149 Room Data Sheets | FREELON BOND Infrastructure Only 0 Other Amenities Deionized Water Vacuum Yes Speakers OH Gr. 2, 130 SF/HD FIRE ALARM Smoke Detection Yes Wet Sprinkler Special Waste Dry Sprinkler Pre-Action Sprinkler No FIRE PROTECTION No Considerations for Water 0 No Floor Drains Floor Sink Grey/Blackwater Piping 0 No No No Protected Hot/Cold No No Recycled Water Supply (treated) 0 No Public Address Audio Compressed Air Audio Visual Requirements No Hot/Cold Water Task Light Yes No 0 Plant/Clean Steam No Acoustic Sensitivity 0 Vibration Sensitivity Special Equipment/Artifact Sensitivity PLUMBING Target Illuminance (IES 9th Edition) Daylight Sensor 0 Exhibit Light Yes Power Density (AHSRAE 2004) 0 Temperature Deviations (+/-) No No Process Water UPS Switched Receptacles Dimming Yes Humidity 0 No Other Humidity Deviation (+/-) As required by load No No Outside Air Single/Multi-Level Switching 0 Emergency/Standby Power As required by code 30/85 Yes Occupancy Sensor Special Exhaust Sub-metering & Feedback Displays Filtration (Pre/Final/Other) Voice/Data DATA/TELECOMMUNICATIONS Yes 0 SECURITY 0 5.0 kPa/8.9 kN Floor Loading/Point Loads DAYLIGHTING 0 0 Shading Considerations Top/Side Lighting None No STRUCTURAL 0 0 Refer to information indicated in Volume IV, Section E 0 0 Technical Comment: Special Events WS Assignable Square Feet (ASF) OFEO Space Dimensions 0 Organizational Unit Other Interior Glazing 0 0 0 0 0 Ceiling CRITICAL FINISHES 0 0
ELECTRICAL ARCHITECTURAL
Zone Room ID D1.52 Room Name 0 Functional Description Open office workspace with office furnishings including worksurface and file storage. Non Public-Non Collection Space 80 Number of Occupants 1 Visual Privacy (full, partial, open) Zone Designation Zone D Room Height 0 LEED NC
0 Base ACOUSTICS Equipment Hardware/STC Rating None NRC0 0 Plug Loads Air Change/ HR Walls HVAC ENGINEERING CRITERIA Temperature Lighting No Control ±2ºF 110v, 20a, 1ph Yes 0 Power No 0 Pressure (+/-) 78ºF Summer, 71ºF Winter Floor Operable Windows Separation/STC FURNITURE/EQUIPMENT Moveable 0 Fixed RT60 & Shaping 0 TBD
blank.
Regurlarly Occupied Space
Floor Level 0 Room
Open

This room data sheet is not comprehensive in nature. Information regarding specific room features may not have been available and was intentionally left

Accessibility Requirement:

Adjacencies

Compliance with ADA/ABAAG (2004) citations is required for accessibility. SI also requires compliance with SI Accessibility Guidelines and the IBC. Comparisons should be made and the more stringent requirement followed for design purposes. An accessible route including a minimum clear width of 36" (except through doors, which must be at least 32" clear) is required. Refer to ADA/ABAAG (2004) for specifications regarding clear floor spaces at desks, files and equipment for individuals using wheelchairs.See Accessibility Narrative for additional information.

Development & Public Affairs Offices, Staff Amenities, and Meeting Rooms. Additional adjacency information is unavailable at this time pending finalization of organization chart by NMAAHC.

SUSTAINABILITY FEATURES

vs. Private

Please refer to structural narrative for more information on structural requirements.

CRITICAL DIMENSIONS

Length, Width, Shape

Smithsonian Institution National Museum of African American History and Culture 150 Infrastructure Only 0 Other Amenities Deionized Water Vacuum Yes Speakers OH Gr. 2, 130 SF/HD FIRE ALARM Smoke Detection Yes Wet Sprinkler Special Waste Dry Sprinkler Pre-Action Sprinkler No FIRE PROTECTION No Considerations for Water 0 No Floor Drains Floor Sink Grey/Blackwater Piping 0 No No No Protected Hot/Cold No No Recycled Water Supply (treated) 0 No Public Address Audio Compressed Air Audio Visual Requirements No Hot/Cold Water Task Light Yes No 0 Plant/Clean Steam No Acoustic Sensitivity 0 Vibration Sensitivity Special Equipment/Artifact Sensitivity PLUMBING Target Illuminance (IES 9th Edition) Daylight Sensor 0 Exhibit Light Yes Power Density (AHSRAE 2004) 0 Temperature Deviations (+/-) No No Process Water UPS Switched Receptacles Dimming Yes Humidity 0 No Other Humidity Deviation (+/-) As required by load No No Outside Air Single/Multi-Level Switching 0 Emergency/Standby Power As required by code 30/85 Yes Occupancy Sensor Special Exhaust Sub-metering & Feedback Displays Filtration (Pre/Final/Other) Voice/Data DATA/TELECOMMUNICATIONS Yes 0 SECURITY 0 5.0 kPa/8.9 kN Floor Loading/Point Loads DAYLIGHTING 0 0 Shading Considerations Top/Side Lighting None No STRUCTURAL 0 0 Refer to information indicated in Volume IV, Section E 0 0 Technical Comment: Public Affairs WS Assignable Square Feet (ASF) OFEO Space Dimensions 0 Organizational Unit Other Interior Glazing 0 0 0 0 0 Ceiling CRITICAL FINISHES 0 0
ELECTRICAL ARCHITECTURAL
Zone Room ID D1.53 Room Name 0 Functional Description Open office workspace with office furnishings including worksurface and file storage. Non Public-Non Collection Space 160 Number of Occupants 1 Visual Privacy (full, partial, open) Zone Designation Zone D Room Height 0 LEED NC
0 Base ACOUSTICS Equipment Hardware/STC Rating None NRC0 0 Plug Loads Air Change/ HR Walls HVAC ENGINEERING CRITERIA Temperature Lighting No Control ±2ºF 110v, 20a, 1ph Yes 0 Power No 0 Pressure (+/-) 78ºF Summer, 71ºF Winter Floor Operable Windows Separation/STC FURNITURE/EQUIPMENT Moveable 0 Fixed RT60 & Shaping 0 TBD
blank.
Regurlarly Occupied Space
Floor Level 0 Room
Open

This room data sheet is not comprehensive in nature. Information regarding specific room features may not have been available and was intentionally left blank.

Accessibility Requirement:

Adjacencies

SUSTAINABILITY FEATURES

Compliance with ADA/ABAAG (2004) citations is required for accessibility. SI also requires compliance with SI Accessibility Guidelines and the IBC. Comparisons should be made and the more stringent requirement followed for design purposes. An accessible route including a minimum clear width of 36" (except through doors, which must be at least 32" clear) is required. Refer to ADA/ABAAG (2004) for specifications regarding clear floor spaces at desks, files and equipment for individuals using wheelchairs.See Accessibility Narrative for additional information.

Development & Public Affairs Offices, Staff Amenities, and Meeting Rooms. Additional adjacency information is unavailable at this time pending finalization of organization chart by NMAAHC.

CRITICAL DIMENSIONS

Length, Width, Shape Open vs. Private

Please refer to structural narrative for more information on structural requirements.

151 Room Data Sheets | FREELON BOND Infrastructure Only 0 Other Amenities Deionized Water Vacuum Yes Speakers OH Gr. 2, 130 SF/HD FIRE ALARM Smoke Detection Yes Wet Sprinkler Special Waste Dry Sprinkler Pre-Action Sprinkler No FIRE PROTECTION No Considerations for Water 0 No Floor Drains Floor Sink Grey/Blackwater Piping 0 No No No Protected Hot/Cold No No Recycled Water Supply (treated) 0 No Public Address Audio Compressed Air Audio Visual Requirements No Hot/Cold Water Task Light Yes No 0 Plant/Clean Steam No Acoustic Sensitivity 0 Vibration Sensitivity Special Equipment/Artifact Sensitivity PLUMBING Target Illuminance (IES 9th Edition) Daylight Sensor 0 Exhibit Light Yes Power Density (AHSRAE 2004) 0 Temperature Deviations (+/-) No No Process Water UPS Switched Receptacles Dimming Yes Humidity 0 No Other Humidity Deviation (+/-) As required by load No No Outside Air Single/Multi-Level Switching 0 Emergency/Standby Power As required by code 30/85 Yes Occupancy Sensor Special Exhaust Sub-metering & Feedback Displays Filtration (Pre/Final/Other) Voice/Data DATA/TELECOMMUNICATIONS Yes 0 SECURITY 0 5.0 kPa/8.9 kN Floor Loading/Point Loads DAYLIGHTING 0 0 Shading Considerations Top/Side Lighting None No STRUCTURAL 0 0 Refer to information indicated in Volume IV, Section E 0 0 Technical Comment: Photography Assignable Square Feet (ASF) OFEO Space Dimensions 0 Organizational Unit Other Interior Glazing 0 0 0 0 0 Ceiling CRITICAL FINISHES 0 0
ELECTRICAL
ARCHITECTURAL
Zone Room ID D1.54 Room Name 0 Functional Description Open office workspace with office furnishings including worksurface and file storage. Non Public-Non Collection Space 160 Number of Occupants 1 Visual Privacy (full, partial, open) Zone Designation Zone D Room Height 0 LEED NC Regurlarly
0 Base ACOUSTICS Equipment Hardware/STC Rating None NRC0 0 Plug Loads Air Change/ HR Walls HVAC ENGINEERING CRITERIA Temperature Lighting No Control ±2ºF 110v, 20a, 1ph Yes 0 Power No 0 Pressure (+/-) 78ºF Summer, 71ºF Winter Floor Operable Windows Separation/STC FURNITURE/EQUIPMENT Moveable 0 Fixed RT60 & Shaping 0 TBD
Occupied Space
Floor Level 0 Room

This room data sheet is not comprehensive in nature. Information regarding specific room features may not have been available and was intentionally left

Accessibility Requirement:

Adjacencies

SUSTAINABILITY FEATURES

Compliance with ADA/ABAAG (2004) citations is required for accessibility. SI also requires compliance with SI Accessibility Guidelines and the IBC. Comparisons should be made and the more stringent requirement followed for design purposes. An accessible route including a minimum clear width of 36" (except through doors, which must be at least 32" clear) is required. Refer to ADA/ABAAG (2004) for specifications regarding clear floor spaces at desks, files and equipment for individuals using wheelchairs.See Accessibility Narrative for additional information.

Development & Public Affairs Offices, Staff Amenities, and Meeting Rooms. Additional adjacency information is unavailable at this time pending finalization of organization chart by NMAAHC.

CRITICAL DIMENSIONS

Please refer to structural narrative for more information on structural requirements.

Smithsonian Institution National Museum of African American History and Culture 152 Infrastructure Only 0 Other Amenities Deionized Water Vacuum Yes Speakers OH Gr. 2, 130 SF/HD FIRE ALARM Smoke Detection Yes Wet Sprinkler Special Waste Dry Sprinkler Pre-Action Sprinkler No FIRE PROTECTION No Considerations for Water 0 No Floor Drains Floor Sink Grey/Blackwater Piping 0 No No No Protected Hot/Cold No No Recycled Water Supply (treated) 0 No Public Address Audio Compressed Air Audio Visual Requirements No Hot/Cold Water Task Light Yes No 0 Plant/Clean Steam No Acoustic Sensitivity 0 Vibration Sensitivity Special Equipment/Artifact Sensitivity PLUMBING Target Illuminance (IES 9th Edition) Daylight Sensor 0 Exhibit Light Yes Power Density (AHSRAE 2004) 0 Temperature Deviations (+/-) No No Process Water UPS Switched Receptacles Dimming Yes Humidity 0 No Other Humidity Deviation (+/-) As required by load No No Outside Air Single/Multi-Level Switching 0 Emergency/Standby Power As required by code 30/85 Yes Occupancy Sensor Special Exhaust Sub-metering & Feedback Displays Filtration (Pre/Final/Other) Voice/Data DATA/TELECOMMUNICATIONS Yes 0 SECURITY 0 5.0 kPa/8.9 kN Floor Loading/Point Loads DAYLIGHTING 0 0 Shading Considerations Top/Side Lighting None No STRUCTURAL 0 0 Refer to information indicated in Volume IV, Section E 0 0 Technical Comment: Management Support ws Assignable Square Feet (ASF) OFEO Space Dimensions 0 Organizational Unit Other Interior Glazing 0 0 0 0 0 Ceiling CRITICAL FINISHES 0 0
ELECTRICAL ARCHITECTURAL
Zone Room ID D1.55 Room Name 0 Functional Description Open office workspace with office furnishings including worksurface and file storage. Non Public-Non Collection Space 160 Number of Occupants 1 Visual Privacy (full, partial, open) Zone Designation Zone D Room Height 0 LEED
0 Base ACOUSTICS Equipment Hardware/STC Rating None NRC0 0 Plug Loads Air Change/ HR Walls HVAC ENGINEERING CRITERIA Temperature Lighting No Control ±2ºF 110v, 20a, 1ph Yes 0 Power No 0 Pressure (+/-) 78ºF Summer, 71ºF Winter Floor Operable Windows Separation/STC FURNITURE/EQUIPMENT Moveable 0 Fixed RT60 & Shaping 0 TBD
blank.
NC Regurlarly Occupied Space
Floor Level 0 Room
Length, Width, Shape Open vs. Private

This room data sheet is not comprehensive in nature. Information regarding specific room features may not have been available and was intentionally left blank.

Accessibility Requirement:

Adjacencies

SUSTAINABILITY FEATURES

Compliance with ADA/ABAAG (2004) citations is required for accessibility. SI also requires compliance with SI Accessibility Guidelines and the IBC. Comparisons should be made and the more stringent requirement followed for design purposes. An accessible route including a minimum clear width of 36" (except through doors, which must be at least 32" clear) is required. Refer to ADA/ABAAG (2004) for specifications regarding clear floor spaces at desks, files and equipment for individuals using wheelchairs.See Accessibility Narrative for additional information.

Administration Work Offices, Staff Amenities, and Meeting Rooms. Additional adjacency information is unavailable at this time pending finalization of organization chart by NMAAHC.

CRITICAL

DIMENSIONS

Length, Width, Shape Open vs. Private

Please refer to structural narrative for more information on structural requirements.

153 Room Data Sheets | FREELON BOND Infrastructure Only 0 Other Amenities Deionized Water Vacuum Yes Speakers OH Gr. 2, 130 SF/HD FIRE ALARM Smoke Detection Yes Wet Sprinkler Special Waste Dry Sprinkler Pre-Action Sprinkler No FIRE PROTECTION No Considerations for Water 0 No Floor Drains Floor Sink Grey/Blackwater Piping 0 No No No Protected Hot/Cold No No Recycled Water Supply (treated) 0 No Public Address Audio Compressed Air Audio Visual Requirements No Hot/Cold Water Task Light Yes No 0 Plant/Clean Steam No Acoustic Sensitivity 0 Vibration Sensitivity Special Equipment/Artifact Sensitivity PLUMBING Target Illuminance (IES 9th Edition) Daylight Sensor 0 Exhibit Light Yes Power Density (AHSRAE 2004) 0 Temperature Deviations (+/-) No No Process Water UPS Switched Receptacles Dimming Yes Humidity 0 No Other Humidity Deviation (+/-) As required by load No No Outside Air Single/Multi-Level Switching 0 Emergency/Standby Power As required by code 30/85 Yes Occupancy Sensor Special Exhaust Sub-metering & Feedback Displays Filtration (Pre/Final/Other) Voice/Data DATA/TELECOMMUNICATIONS Yes 0 SECURITY 0 0 Floor Loading/Point Loads DAYLIGHTING 0 0 Shading Considerations Top/Side Lighting 0 0 STRUCTURAL 0 0 Refer to information indicated in Volume IV, Section E 0 0 Technical Comment: Finance WS Assignable Square Feet (ASF) OFEO Space Dimensions 0 Organizational Unit Other Interior Glazing 0 0 0 0 0 Ceiling CRITICAL FINISHES 0 0
ELECTRICAL ARCHITECTURAL
Zone Room ID D1.56 Room Name 0 Functional Description Open office workspace with office furnishings including worksurface
file storage. Non Public-Non Collection Space 240 Number of Occupants 1 Visual Privacy (full, partial, open) Zone Designation Zone D Room Height 0 LEED NC Regurlarly Occupied Space 0 Base ACOUSTICS Equipment Hardware/STC Rating None NRC 0 0 0 Plug Loads Air Change/ HR Walls HVAC ENGINEERING CRITERIA Temperature Lighting No Control ±2ºF 110v, 20a, 1ph Yes 0 Power No 0 Pressure (+/-) 78ºF Summer, 71ºF Winter Floor Operable Windows Separation/STC FURNITURE/EQUIPMENT Moveable 0 Fixed RT60
0 TBD
and
& Shaping
Floor Level 0 Room

This room data sheet is not comprehensive in nature. Information regarding specific room features may not have been available and was intentionally left blank.

Accessibility Requirement:

Adjacencies

SUSTAINABILITY FEATURES

Compliance with ADA/ABAAG (2004) citations is required for accessibility. SI also requires compliance with SI Accessibility Guidelines and the IBC. Comparisons should be made and the more stringent requirement followed for design purposes. An accessible route including a minimum clear width of 36" (except through doors, which must be at least 32" clear) is required. Refer to ADA/ABAAG (2004) for specifications regarding clear floor spaces at desks, files and equipment for individuals using wheelchairs.See Accessibility Narrative for additional information.

Administration Work Offices, Staff Amenities, and Meeting Rooms. Additional adjacency information is unavailable at this time pending finalization of organization chart by NMAAHC.

CRITICAL

DIMENSIONS

Length, Width, Shape Open vs. Private

Please refer to structural narrative for more information on structural requirements.

Smithsonian Institution National Museum of African American History and Culture 154 Infrastructure Only 0 Other Amenities Deionized Water Vacuum Yes Speakers OH Gr. 2, 130 SF/HD FIRE ALARM Smoke Detection Yes Wet Sprinkler Special Waste Dry Sprinkler Pre-Action Sprinkler No FIRE PROTECTION No Considerations for Water 0 No Floor Drains Floor Sink Grey/Blackwater Piping 0 No No No Protected Hot/Cold No No Recycled Water Supply (treated) 0 No Public Address Audio Compressed Air Audio Visual Requirements No Hot/Cold Water Task Light Yes No 0 Plant/Clean Steam No Acoustic Sensitivity 0 Vibration Sensitivity Special Equipment/Artifact Sensitivity PLUMBING Target Illuminance (IES 9th Edition) Daylight Sensor 0 Exhibit Light Yes Power Density (AHSRAE 2004) 0 Temperature Deviations (+/-) No No Process Water UPS Switched Receptacles Dimming Yes Humidity 0 No Other Humidity Deviation (+/-) As required by load No No Outside Air Single/Multi-Level Switching 0 Emergency/Standby Power As required by code 30/85 Yes Occupancy Sensor Special Exhaust Sub-metering & Feedback Displays Filtration (Pre/Final/Other) Voice/Data DATA/TELECOMMUNICATIONS Yes 0 SECURITY 0 0 Floor Loading/Point Loads DAYLIGHTING 0 0 Shading Considerations Top/Side Lighting 0 0 STRUCTURAL 0 0 Refer to information indicated in Volume IV, Section E 0 0 Technical Comment: Personnel WS Assignable Square Feet (ASF) OFEO Space Dimensions 0 Organizational Unit Other Interior Glazing 0 0 0 0 0 Ceiling CRITICAL FINISHES 0 0
ELECTRICAL ARCHITECTURAL
Zone Room ID D1.57 Room Name 0 Functional Description Open office workspace with office furnishings
worksurface
file storage. Non Public-Non Collection Space 80 Number of Occupants 1 Visual Privacy (full, partial, open) Zone Designation Zone D Room Height 0 LEED NC Regurlarly Occupied Space 0 Base ACOUSTICS Equipment Hardware/STC Rating None NRC 0 0 0 Plug Loads Air Change/ HR Walls HVAC ENGINEERING CRITERIA Temperature Lighting No Control ±2ºF 110v, 20a, 1ph Yes 0 Power No 0 Pressure (+/-) 78ºF Summer, 71ºF Winter Floor Operable Windows Separation/STC FURNITURE/EQUIPMENT Moveable 0 Fixed RT60
0 TBD
including
and
& Shaping
Floor Level 0 Room

This room data sheet is not comprehensive in nature. Information regarding specific room features may not have been available and was intentionally left blank.

Accessibility Requirement:

Adjacencies

SUSTAINABILITY FEATURES

Compliance with ADA/ABAAG (2004) citations is required for accessibility. SI also requires compliance with SI Accessibility Guidelines and the IBC. Comparisons should be made and the more stringent requirement followed for design purposes. An accessible route including a minimum clear width of 36" (except through doors, which must be at least 32" clear) is required. Refer to ADA/ABAAG (2004) for specifications regarding clear floor spaces at desks, files and equipment for individuals using wheelchairs.See Accessibility Narrative for additional information.

Administration Work Offices, Staff Amenities, and Meeting Rooms. Additional adjacency information is unavailable at this time pending finalization of organization chart by NMAAHC.

CRITICAL

DIMENSIONS

Length, Width, Shape Open vs. Private

Please refer to structural narrative for more information on structural requirements.

155 Room Data Sheets | FREELON BOND Infrastructure Only 0 Other Amenities Deionized Water Vacuum Yes Speakers OH Gr. 2, 130 SF/HD FIRE ALARM Smoke Detection Yes Wet Sprinkler Special Waste Dry Sprinkler Pre-Action Sprinkler No FIRE PROTECTION No Considerations for Water 0 No Floor Drains Floor Sink Grey/Blackwater Piping 0 No No No Protected Hot/Cold No No Recycled Water Supply (treated) 0 No Public Address Audio Compressed Air Audio Visual Requirements No Hot/Cold Water Task Light Yes No 0 Plant/Clean Steam No Acoustic Sensitivity 0 Vibration Sensitivity Special Equipment/Artifact Sensitivity PLUMBING Target Illuminance (IES 9th Edition) Daylight Sensor 0 Exhibit Light Yes Power Density (AHSRAE 2004) 0 Temperature Deviations (+/-) No No Process Water UPS Switched Receptacles Dimming Yes Humidity 0 No Other Humidity Deviation (+/-) As required by load No No Outside Air Single/Multi-Level Switching 0 Emergency/Standby Power As required by code 30/85 Yes Occupancy Sensor Special Exhaust Sub-metering & Feedback Displays Filtration (Pre/Final/Other) Voice/Data DATA/TELECOMMUNICATIONS Yes 0 SECURITY 0 0 Floor Loading/Point Loads DAYLIGHTING 0 0 Shading Considerations Top/Side Lighting 0 0 STRUCTURAL 0 0 Refer to information indicated in Volume IV, Section E 0 0 Technical Comment: IT WS Assignable Square Feet (ASF) OFEO Space Dimensions 0 Organizational Unit Other Interior Glazing 0 0 0 0 0 Ceiling CRITICAL FINISHES 0 0
ELECTRICAL ARCHITECTURAL
Zone Room ID D1.58 Room Name 0 Functional Description Open office workspace with office furnishings
worksurface
file storage. Non Public-Non Collection Space 80 Number of Occupants 1 Visual Privacy (full, partial, open) Zone Designation Zone D Room Height 0 LEED NC Regurlarly Occupied Space 0 Base ACOUSTICS Equipment Hardware/STC Rating None NRC 0 0 0 Plug Loads Air Change/ HR Walls HVAC ENGINEERING CRITERIA Temperature Lighting No Control ±2ºF 110v, 20a, 1ph Yes 0 Power No 0 Pressure (+/-) 78ºF Summer, 71ºF Winter Floor Operable Windows Separation/STC FURNITURE/EQUIPMENT Moveable 0 Fixed RT60
0 TBD
including
and
& Shaping
Floor
0 Room
Level

This room data sheet is not comprehensive in nature. Information regarding specific room features may not have been available and was intentionally left blank.

Accessibility Requirement: Floor Level

Adjacencies

Technical Comment:

Compliance with ADA/ABAAG (2004) citations is required for accessibility. SI also requires compliance with SI Accessibility Guidelines and the IBC. Comparisons should be made and the more stringent requirement followed for design purposes. An accessible route including a minimum clear width of 36" (except through doors, which must be at least 32" clear) is required. Refer to ADA/ABAAG (2004) for specifications regarding clear floor spaces at desks, files and equipment for individuals using wheelchairs.See Accessibility Narrative for additional information.

Exhibition Design Workstations located adjacent to Exhibition Design Office, to create an exhibit design studio. The Exhibit Design Studio may be located in the Administrative area or adjacent to the Design/Graphic Studio and Exhibition Workshops.

Desk/computer workstation, computer operator chair, in-desk file drawer, waste baskets, telephones, wall-mounted bookshelves, and optional printer.

Functional Description Workstations to support Exhibition Design and coordination activities.

SUSTAINABILITY FEATURES

Open vs. Private

CRITERIA

Please refer to structural narrative for more information on structural requirements.

CRITICAL DIMENSIONS

Room Length, Width, Shape

to information indicated in Volume IV, Section E

Smithsonian Institution National Museum of African American History and Culture 156 Infrastructure Only 0 Other Amenities Deionized Water Vacuum Yes Speakers OH Gr. 2, 130 SF/HD FIRE ALARM Smoke Detection Yes Wet Sprinkler Special Waste Dry Sprinkler Pre-Action Sprinkler No FIRE PROTECTION No Considerations for Water 0 No Floor Drains Floor Sink Grey/Blackwater Piping 0 No No No Protected Hot/Cold No No Recycled Water Supply (treated) 0 No Public Address Audio Compressed Air Audio Visual Requirements No Hot/Cold Water Task Light Yes No 0 Plant/Clean Steam No Acoustic Sensitivity 0 Vibration Sensitivity Special Equipment/Artifact Sensitivity PLUMBING Target Illuminance (IES 9th Edition) Daylight Sensor 0 Exhibit Light Yes Power Density (AHSRAE 2004) 0 Temperature Deviations (+/-) No No Process Water UPS Switched Receptacles Dimming Yes Humidity 0 No Other Humidity Deviation (+/-) As required by load No No Outside Air Single/Multi-Level Switching 0 Emergency/Standby Power As required by code 30/85 Yes Occupancy Sensor Special Exhaust Sub-metering & Feedback Displays Filtration (Pre/Final/Other) Voice/Data DATA/TELECOMMUNICATIONS Yes 0 SECURITY 0 5.0 kPa/8.9 kN Floor Loading/Point Loads DAYLIGHTING 0 0 Shading Considerations Top/Side Lighting None No STRUCTURAL 0 0
0
Refer
Exhibitions Design WS Assignable Square Feet (ASF) OFEO Space Dimensions 0 Organizational Unit Other Interior Glazing 0 0 0 0 0 Ceiling CRITICAL FINISHES 0 0
ELECTRICAL ARCHITECTURAL
Zone Room ID D1.59 Room Name 0
Non Public-Non Collection Space 160 Number of Occupants 1 Visual Privacy (full, partial, open) Zone Designation Zone D Room Height 0 LEED NC Regurlarly Occupied Space 0 Base ACOUSTICS Equipment Hardware/STC Rating None NRC0 0 Plug Loads Air Change/ HR Walls HVAC ENGINEERING
Temperature Lighting No Control ±2ºF 110v, 20a, 1ph Yes 0 Power No 0 Pressure (+/-) 78ºF Summer, 71ºF Winter Floor Operable Windows Separation/STC FURNITURE/EQUIPMENT Moveable 0 Fixed RT60
0 TBD
& Shaping
0

This room data sheet is not comprehensive in nature. Information regarding specific room features may not have been available and was intentionally left blank.

Accessibility Requirement:

Adjacencies

Technical Comment:

Compliance with ADA/ABAAG (2004) citations is required for accessibility. SI also requires compliance with SI Accessibility Guidelines and the IBC. Comparisons should be made and the more stringent requirement followed for design purposes. An accessible route including a minimum clear width of 36" (except through doors, which must be at least 32" clear) is required. Refer to ADA/ABAAG (2004) for specifications regarding clear floor spaces at desks, files and equipment for individuals using wheelchairs.See Accessibility Narrative for additional information.

Exhibition Production/Maintenance Workstations located adjacent to Exhibition Production Office and/or Exhibition Workshops.

bookshelves, and optional printer.

Functional Description Workstations to support Exhibition Production, Installation and

SUSTAINABILITY FEATURES

Please refer to structural narrative for more information on structural requirements.

CRITICAL DIMENSIONS

157 Room Data Sheets | FREELON BOND Infrastructure Only 0 Other Amenities Deionized Water Vacuum Yes Speakers OH Gr. 2, 130 SF/HD FIRE ALARM Smoke Detection Yes Wet Sprinkler Special Waste Dry Sprinkler Pre-Action Sprinkler No FIRE PROTECTION No Considerations for Water 0 No Floor Drains Floor Sink Grey/Blackwater Piping 0 No No No Protected Hot/Cold No No Recycled Water Supply (treated) 0 No Public Address Audio Compressed Air Audio Visual Requirements No Hot/Cold Water Task Light Yes No 0 Plant/Clean Steam No Acoustic Sensitivity 0 Vibration Sensitivity Special Equipment/Artifact Sensitivity PLUMBING Target Illuminance (IES 9th Edition) Daylight Sensor 0 Exhibit Light Yes Power Density (AHSRAE 2004) 0 Temperature Deviations (+/-) No No Process Water UPS Switched Receptacles Dimming Yes Humidity 0 No Other Humidity Deviation (+/-) As required by load No No Outside Air Single/Multi-Level Switching 0 Emergency/Standby Power As required by code 30/85 Yes Occupancy Sensor Special Exhaust Sub-metering & Feedback Displays Filtration (Pre/Final/Other) Voice/Data DATA/TELECOMMUNICATIONS Yes 0 SECURITY 0 5.0 kPa/8.9 kN Floor Loading/Point Loads DAYLIGHTING 0 0 Shading Considerations Top/Side Lighting None No STRUCTURAL 0 0 Refer to information indicated in Volume IV, Section E 0 Desk/computer
operator
in-desk file drawer, waste
wall-mounted
workstation, computer
chair,
baskets, telephones,
Exhibitions Productions/Maintenance WS Assignable Square Feet
OFEO Space Dimensions 0 Organizational Unit Other Interior Glazing 0 0 0 0 0 Ceiling CRITICAL FINISHES 0 0
(ASF)
ELECTRICAL ARCHITECTURAL
Zone Room ID D1.60 Room Name 0
Non Public-Non Collection Space 560 Number of Occupants 1 Visual Privacy (full, partial, open) Zone Designation Zone D Room Height 0 LEED NC Regurlarly Occupied Space 0 Base ACOUSTICS Equipment Hardware/STC Rating None NRC0 0 Plug Loads Air Change/ HR Walls HVAC ENGINEERING CRITERIA Temperature Lighting No Control ±2ºF 110v, 20a, 1ph Yes 0 Power No 0 Pressure (+/-) 78ºF Summer, 71ºF Winter Floor Operable Windows Separation/STC FURNITURE/EQUIPMENT Moveable 0 Fixed RT60 &
0 TBD
Maintenance Technicians
Shaping
Floor Level 0 Room Length,
Open
Width, Shape
vs. Private

This room data sheet is not comprehensive in nature. Information regarding specific room features may not have been available and was intentionally left blank.

Accessibility Requirement:

Adjacencies

Comment:

SUSTAINABILITY FEATURES

Open vs. Private

Compliance with ADA/ABAAG (2004) citations is required for accessibility. SI also requires compliance with SI Accessibility Guidelines and the IBC. Comparisons should be made and the more stringent requirement followed for design purposes. An accessible route including a minimum clear width of 36" (except through doors, which must be at least 32" clear) is required. Refer to ADA/ABAAG (2004) for specifications regarding clear floor spaces at desks, files and equipment for individuals using wheelchairs.See Accessibility Narrative for additional information.

Exhibition A/V Lighting Workstations are located adjacent to Exhibition Production Office and/or Exhibition Workshops.

CRITICAL DIMENSIONS

Length, Width, Shape

Please refer to structural narrative for more information on structural requirements.

Smithsonian Institution National Museum of African American History and Culture 158 Infrastructure Only 0 Other Amenities Deionized Water Vacuum Yes Speakers OH Gr. 2, 130 SF/HD FIRE ALARM Smoke Detection Yes Wet Sprinkler Special Waste Dry Sprinkler Pre-Action Sprinkler No FIRE PROTECTION No Considerations for Water 0 No Floor Drains Floor Sink Grey/Blackwater Piping 0 No No No Protected Hot/Cold No No Recycled Water Supply (treated) 0 No Public Address Audio Compressed Air Audio Visual Requirements No Hot/Cold Water Task Light Yes No 0 Plant/Clean Steam No Acoustic Sensitivity 0 Vibration Sensitivity Special Equipment/Artifact Sensitivity PLUMBING Target Illuminance (IES 9th Edition) Daylight Sensor 0 Exhibit Light Yes Power Density (AHSRAE 2004) 0 Temperature Deviations (+/-) No No Process Water UPS Switched Receptacles Dimming Yes Humidity 0 No Other Humidity Deviation (+/-) As required by load No No Outside Air Single/Multi-Level Switching 0 Emergency/Standby Power As required by code 30/85 Yes Occupancy Sensor Special Exhaust Sub-metering & Feedback Displays Filtration (Pre/Final/Other) Voice/Data DATA/TELECOMMUNICATIONS Yes 0 SECURITY 0 0 Floor Loading/Point Loads DAYLIGHTING 0 0 Shading Considerations Top/Side Lighting 0 0 STRUCTURAL 0 0 Refer to information indicated in Volume IV, Section E 0 Divisional Offices, including Executive/Director private office, smaller private offices and landscape workstations, with office partitioning, furnishings together, and connectivity TBD. Technical
Exhibitions AV/Lighting WS Assignable Square Feet
OFEO Space Dimensions 0 Organizational Unit Other Interior Glazing 0 0 0 0 0 Ceiling CRITICAL FINISHES 0 0
(ASF)
ELECTRICAL ARCHITECTURAL
Zone Room ID D1.61 Room Name 0 Functional
Workstations
A/V Lighting Technicians Non Public-Non Collection Space 160 Number of Occupants 1 Visual Privacy (full, partial, open) Zone Designation Zone D Room Height 0 LEED NC Regurlarly Occupied Space 0 Base ACOUSTICS Equipment Hardware/STC Rating None NRC 0 0 0 Plug Loads Air Change/ HR Walls HVAC ENGINEERING
Temperature Lighting No Control ±2ºF 110v, 20a, 1ph Yes 0 Power No 0 Pressure (+/-) 78ºF Summer, 71ºF Winter Floor Operable Windows Separation/STC FURNITURE/EQUIPMENT Moveable 0 Fixed RT60 & Shaping 0 TBD
Description
for Exhibitions
CRITERIA
Floor Level 0 Room

This room data sheet is not comprehensive in nature. Information regarding specific room features may not have been available and was intentionally left blank.

Compliance with ADA/ABAAG (2004) citations is required for

SI also requires compliance with SI

Guidelines and the IBC. Comparisons should be made and the more stringent requirement followed for design purposes. See Accessibility Narrative for additional information.

CRITICAL

Please refer to structural narrative for more information on structural requirements.

159 Room Data Sheets | FREELON BOND Infrastructure Only 0 Other Amenities Deionized Water Vacuum Yes Speakers OH Gr. 2, 130 SF/HD FIRE ALARM Smoke Detection Yes Wet Sprinkler Special Waste Dry Sprinkler Pre-Action Sprinkler No FIRE PROTECTION No Considerations for Water 0 No Floor Drains Floor Sink Grey/Blackwater Piping 0 No No No Protected Hot/Cold No No Recycled Water Supply (treated) 0 No Public Address Audio Compressed Air Audio Visual Requirements No Hot/Cold Water Task Light To Be Considered No 0 Plant/Clean Steam No Acoustic Sensitivity NC 35-40 Vibration Sensitivity Special Equipment/Artifact Sensitivity PLUMBING Target Illuminance (IES 9th Edition) Daylight Sensor 10 FC Exhibit Light To Be Considered Power Density (AHSRAE 2004) 1.1 W/ft² Temperature Deviations (+/-) No No Process Water UPS Switched Receptacles Dimming To Be Considered Humidity 0 No Other Humidity Deviation (+/-) As required by load No No Outside Air Single/Multi-Level Switching 0 Emergency/Standby Power As required by code 30/85 Single Occupancy Sensor Special Exhaust Sub-metering & Feedback Displays Filtration (Pre/Final/Other) Voice/Data DATA/TELECOMMUNICATIONS Yes 0 SECURITY 0 7.5 kPa/17.8 kN Floor Loading/Point Loads DAYLIGHTING 0 0 Shading Considerations Top/Side Lighting None No STRUCTURAL 0 0 Refer to information indicated in Volume IV, Section E 0
Comment: Photocopy/Mailroom - (Central) Assignable Square Feet (ASF) OFEO Space Dimensions 0 Organizational Unit Other Interior Glazing 0 Solid core wood or insulated metal with neoprene strip seals max 1/4" undercut 0 0 0 Ceiling CRITICAL FINISHES 0 0
Confirm SF supports 175 staff. Technical
ELECTRICAL ARCHITECTURAL
Zone Room ID D1.62 Room Name 0 Functional Description Area for processing mail and courier shipments in and out, with assembly counter, postage meter, sorting bins and carts, staff mailboxes TBD. Non Public-Non Collection Space 200 Number of Occupants TBD Visual Privacy (full, partial, open) Zone Designation Zone D Room Height 0 LEED NC Regurlarly Occupied Space 0 Base ACOUSTICS Equipment Hardware/STC Rating None NRC Absorptive finish on the ceiling with an NRC of 0.70 or higher STC 50 0 Plug Loads Air Change/ HR Walls HVAC ENGINEERING CRITERIA Temperature Lighting No Control ±2ºF 110v, 20a, 1ph Yes 0 Power No 0 Pressure (+/-) 78ºF Summer, 71ºF Winter Floor Operable Windows Separation/STC FURNITURE/EQUIPMENT Moveable - Fixed RT60 & Shaping 0 TBD
Central to Offices
FEATURES Adjacencies Accessibility Requirement: Floor Level 0 Room Length, Width, Shape Open vs. Private
accessibility.
Accessibility
SUSTAINABILITY
DIMENSIONS

room data sheet is

Compliance with ADA/ABAAG (2004) citations is required for accessibility. SI also requires compliance with SI Accessibility Guidelines and the IBC. Comparisons should be made and the more stringent requirement followed for design purposes. See Accessibility Narrative for additional information.

vs. Private CRITICAL DIMENSIONS

Length, Width, Shape

Separation/STC FURNITURE/EQUIPMENT

Please refer to structural narrative for more information on structural requirements.

Smithsonian Institution National Museum of African American History and Culture 160 Infrastructure Only 0 Other Amenities Deionized Water Vacuum Yes Speakers OH Gr. 2, 130 SF/HD FIRE ALARM Smoke Detection Yes Wet Sprinkler Special Waste Dry Sprinkler Pre-Action Sprinkler No FIRE PROTECTION No Considerations for Water 0 No Floor Drains Floor Sink Grey/Blackwater Piping 0 No No No Protected Hot/Cold No No Recycled Water Supply (treated) 0 No Public Address Audio Compressed Air Audio Visual Requirements No Hot/Cold Water Task Light No No 0 Plant/Clean Steam No Acoustic Sensitivity No Vibration Sensitivity Special Equipment/Artifact Sensitivity PLUMBING Target Illuminance (IES 9th Edition) Daylight Sensor 10 FC Exhibit Light No Power Density (AHSRAE 2004) 0.8 W/ft² Temperature Deviations (+/-) No No Process Water UPS Switched Receptacles Dimming To Be Considered Humidity 0 No Other Humidity Deviation (+/-) As required by load No No Outside Air Single/Multi-Level Switching 0 Emergency/Standby Power As required by code 30/85 Single Occupancy Sensor Special Exhaust Sub-metering & Feedback Displays Filtration (Pre/Final/Other) Voice/Data DATA/TELECOMMUNICATIONS Yes 0 SECURITY 0 12.0 kPa/26.7 kN Floor Loading/Point Loads DAYLIGHTING 0 0 Shading Considerations Top/Side Lighting None No STRUCTURAL 0 0 Refer to information indicated in Volume IV, Section E Full Confirm SF supports 175 staff. Technical Comment: Files Storage (Central)
Square Feet
OFEO Space Dimensions 0 Organizational Unit Other Interior Glazing 0 0 Yes Yes 0 Ceiling CRITICAL FINISHES 0 0
Assignable
(ASF)
ELECTRICAL ARCHITECTURAL
blank. Zone Room ID D1.63 Room Name 0
administrative files, in file cabinets. Centralized
offices.
may
archived
Non Public-Non Collection Space 400 Number of Occupants TBD Visual Privacy (full, partial, open) Zone Designation Zone D Room Height 0 LEED NC Regurlarly Occupied Space 0 Base ACOUSTICS Equipment Hardware/STC Rating None NRC0 0 Plug Loads Air Change/ HR Walls HVAC ENGINEERING
Temperature Lighting No Control ±2ºF 110v, 20a, 1ph Yes 0 Power No 0 Pressure (+/-) 78ºF Summer, 70ºF Winter Floor Operable Windows
This
not comprehensive in nature. Information regarding specific room features may not have been available and was intentionally left
Functional Description Storage areas for
with
Part
be
files in less accessible locations.
CRITERIA
Moveable Yes Fixed RT60 & Shaping 0 TBD
Central
Floor
0 Room
Open
to Offices SUSTAINABILITY FEATURES Adjacencies Accessibility Requirement:
Level

room

Compliance with ADA/ABAAG (2004) citations is required for accessibility. SI also requires compliance with SI Accessibility Guidelines and the IBC. Comparisons should be made and the more stringent requirement followed for design purposes. See Accessibility Narrative for additional information.

Please refer to structural narrative for more information on structural requirements.

161 Room Data Sheets | FREELON BOND Infrastructure Only 0 Other Amenities Deionized Water Vacuum Yes Speakers OH Gr. 2, 130 SF/HD FIRE ALARM Smoke Detection Yes Wet Sprinkler Special Waste Dry Sprinkler Pre-Action Sprinkler No FIRE PROTECTION No Considerations for Water 0 No Floor Drains Floor Sink Grey/Blackwater Piping 0 No No No Protected Hot/Cold No No Recycled Water Supply (treated) 0 No Public Address Audio Compressed Air Audio Visual Requirements No Hot/Cold Water Task Light No No 0 Plant/Clean Steam No Acoustic Sensitivity No Vibration Sensitivity Special Equipment/Artifact Sensitivity PLUMBING Target Illuminance (IES 9th Edition) Daylight Sensor 10 FC Exhibit Light No Power Density (AHSRAE 2004) 0.8 W/ft² Temperature Deviations (+/-) No No Process Water UPS Switched Receptacles Dimming To Be Considered Humidity 0 No Other Humidity Deviation (+/-) As required by load No No Outside Air Single/Multi-Level Switching 0 Emergency/Standby Power As required by code 30/85 Single Occupancy Sensor Special Exhaust Sub-metering & Feedback Displays Filtration (Pre/Final/Other) Voice/Data DATA/TELECOMMUNICATIONS 0 0 SECURITY 0 7.5 kPa/17.8 kN Floor Loading/Point Loads DAYLIGHTING 0 0 Shading Considerations Top/Side Lighting None No STRUCTURAL 0 0 Refer to information indicated in Volume IV, Section E Full Confirm SF supports 175 staff. Technical Comment: Office Supplies Stockroom (Central) Assignable Square Feet
OFEO Space Dimensions 0 Organizational Unit Other Interior Glazing 0 0 Yes Yes 0 Ceiling CRITICAL FINISHES 0 0
(ASF)
ELECTRICAL ARCHITECTURAL
blank. Zone Room ID D1.64 Room Name 0
Non Public-Non Collection Space 300 Number of Occupants TBD Visual Privacy (full, partial, open) Zone Designation Zone D Room Height 0 LEED NC Regurlarly Occupied Space 0 Base ACOUSTICS Equipment Hardware/STC Rating None NRC0 0 Plug Loads Air Change/ HR Walls HVAC ENGINEERING CRITERIA Temperature Lighting No Control ±2ºF 110v, 20a, 1ph Yes 0 Power No 0 Pressure (+/-) 78ºF Summer, 70ºF Winter Floor Operable Windows
This
data sheet is not comprehensive in nature. Information regarding specific room features may not have been available and was intentionally left
Functional Description Storage areas for all types of Office supplies, in Stationary Cabinets; Centralized with offices.
Moveable Yes Fixed RT60 & Shaping 0 TBD
Separation/STC FURNITURE/EQUIPMENT
Central to Offices SUSTAINABILITY
Adjacencies
Floor Level 0 Room
Open
FEATURES
Accessibility Requirement:
Length, Width, Shape
vs. Private CRITICAL DIMENSIONS

room data sheet is not comprehensive in nature. Information regarding specific room features

Compliance with ADA/ABAAG (2004) citations is required for accessibility. SI also requires compliance with SI Accessibility Guidelines and the IBC. Comparisons should be made and the more stringent requirement followed for design purposes. See Accessibility Narrative for additional information. Museum Shop, Cafeteria, Café SUSTAINABILITY FEATURES Adjacencies Accessibility

CRITICAL DIMENSIONS

Please refer to structural narrative for more information on structural requirements.

Smithsonian Institution National Museum of African American History and Culture 162 Infrastructure Only 0 Other Amenities Deionized Water Vacuum Yes Speakers OH Gr. 2, 130 SF/HD FIRE ALARM Smoke Detection Yes Wet Sprinkler Special Waste Dry Sprinkler Pre-Action Sprinkler No FIRE PROTECTION No Considerations for Water 0 No Floor Drains Floor Sink Grey/Blackwater Piping 0 No No No Protected Hot/Cold No No Recycled Water Supply (treated) 0 No Public Address Audio Compressed Air Audio Visual Requirements No Hot/Cold Water Task Light Yes No 0 Plant/Clean Steam 0 Acoustic Sensitivity NC 40 Vibration Sensitivity Special Equipment/Artifact Sensitivity PLUMBING Target Illuminance (IES 9th Edition) Daylight Sensor 30 FC Exhibit Light No Power Density (AHSRAE 2004) 0.8 W/ft² Temperature Deviations (+/-) 0 No Process Water UPS Switched Receptacles Dimming No Humidity 0 Yes Other Humidity Deviation (+/-) 6 min. 0 No Outside Air Single/Multi-Level Switching 0 Emergency/Standby Power 15 CFM/person 30/65 Single Occupancy Sensor Special Exhaust Sub-metering & Feedback Displays Filtration (Pre/Final/Other) Voice/Data DATA/TELECOMMUNICATIONS Yes 0 SECURITY 0 7.5 kPa/26.7 kN Floor Loading/Point Loads DAYLIGHTING 0 0 Shading Considerations Top/Side Lighting 0 No STRUCTURAL 0 0 Refer to information indicated in Volume IV, Section E Full Dual Purpose Technical Comment: Safe Room Assignable Square Feet (ASF) OFEO Space Dimensions 0 Organizational Unit Other Interior Glazing 0 0 Yes Yes 0 Ceiling CRITICAL FINISHES 0 Positive
ELECTRICAL ARCHITECTURAL
may not have been available and was intentionally left blank. Zone Room ID D1.65 Room Name 0 Functional Description Cash Drop built into wall for after-hour deposits, secure room with key or electronic lock mechanism on door. Adjacent door in the corridor has access to outside for security guards. TBD per Security
safe
counting table. Non Public-Non Collection Space 150 Number of Occupants TBD Visual Privacy (full, partial, open) Zone Designation Zone D Room Height 0 LEED NC Regurlarly Occupied Space 0 Base ACOUSTICS Equipment Hardware/STC Rating 0 NRC0 0 Plug Loads Air Change/ HR Walls HVAC ENGINEERING
Temperature Lighting 45% RH ±2ºF 110v, 20a, 1ph Yes ±15% RH Power 0 0 Pressure (+/-) 76ºF Summer, 71ºF Winter Floor Operable Windows Separation/STC FURNITURE/EQUIPMENT Moveable Yes Fixed RT60 & Shaping 0 TBD
This
Policy. Floor
and
CRITERIA
Floor Level 0 Room Length,
Open
Requirement:
Width, Shape
vs. Private

This room data sheet is not comprehensive in nature. Information regarding specific room features may not have been

SI also requires compliance with SI Accessibility Guidelines and the IBC. Comparisons should be made and the more stringent requirement followed for design purposes. See Accessibility Narrative for additional information. Distributed as required next to offices

163 Room Data Sheets | FREELON BOND Infrastructure Only 0 Other Amenities Deionized Water Vacuum Yes Speakers OH Gr. 2, 130 SF/HD FIRE ALARM Smoke Detection Yes Wet Sprinkler Special Waste Dry Sprinkler Pre-Action Sprinkler No FIRE PROTECTION 0 Considerations for Water 0 No Floor Drains Floor Sink Grey/Blackwater Piping 0 0 0 0 Protected Hot/Cold 0 0 Recycled Water Supply (treated) 0 0 Public Address Audio Compressed Air Audio Visual Requirements 0 Hot/Cold Water Task Light 0 0 0 Plant/Clean Steam 0 Acoustic Sensitivity 0 Vibration Sensitivity Special Equipment/Artifact Sensitivity PLUMBING Target Illuminance (IES 9th Edition) Daylight Sensor 0 Exhibit Light 0 Power Density (AHSRAE 2004) 0 Temperature Deviations (+/-) 0 0 Process Water UPS Switched Receptacles Dimming 0 Humidity 0 0 Other Humidity Deviation (+/-) 0 0 0 Outside Air Single/Multi-Level Switching 0 Emergency/Standby Power 0 0 0 Occupancy Sensor Special Exhaust Sub-metering & Feedback Displays Filtration (Pre/Final/Other) Voice/Data DATA/TELECOMMUNICATIONS Yes 0 SECURITY 0 7.5 kPA/17.8 kN Floor Loading/Point Loads DAYLIGHTING 0 0 Shading Considerations Top/Side Lighting 0 0 STRUCTURAL 0 0 Refer to information indicated in Volume IV, Section E 0 0 Technical Comment: Miscellaneous File Rooms Assignable Square Feet (ASF) OFEO Space Dimensions 0 Organizational Unit Other Interior Glazing 0 0 0 0 0 Ceiling CRITICAL FINISHES 0 0 0 ELECTRICAL ARCHITECTURAL
left blank. Zone Room ID D1.66 Room Name 0
building
necessary to accommodate offices. Non Public-Non Collection Space 720 Number of Occupants TBD Visual Privacy (full, partial, open) Zone Designation Zone D Room Height 0 LEED NC Regurlarly Occupied Space 0 Base ACOUSTICS Equipment Hardware/STC Rating 0 NRC0 0 Plug Loads Air Change/ HR Walls HVAC ENGINEERING CRITERIA Temperature Lighting 0 0 110v, 20a, 1ph 0 0 Power 0 0 Pressure (+/-) 0 Floor Operable Windows
FURNITURE/EQUIPMENT Moveable 0 Fixed RT60 & Shaping 0 TBD Compliance
accessibility.
SUSTAINABILITY
Accessibility
Floor Level 0 Room Length,
Open
available and was intentionally
Functional Description Distributed throughout, the
as
Separation/STC
with 2004 ADAAG citations is required for
FEATURES Adjacencies
Requirement:
Width, Shape
vs. Private CRITICAL DIMENSIONS

This room data sheet is not comprehensive in nature. Information regarding specific room features may not have been available and was intentionally left blank.

Accessibility Requirement:

Adjacencies

Compliance with ADA/ABAAG (2004) citations is required for accessibility. SI also requires compliance with SI Accessibility Guidelines and the IBC. Comparisons should be made and the more stringent requirement followed for design purposes. An accessible route including a minimum clear width of 36" (except through doors, which must be at least 32" clear) is required. Refer to ADA/ABAAG (2004) for specifications regarding clear floor spaces at desks, files and equipment for individuals using wheelchairs.See Accessibility Narrative for additional information.

Central Mail/Photocopy, Supplies and File Rooms, Offices, Staff Amenities

Functional Description Smart Board Room to support administrative, Board and VIP meeting needs. Network connections- AV and computer presentation capabilities. Formal Board Room setup - potentially with microphone and recording capabilities.

SUSTAINABILITY FEATURES

vs. Private

CRITICAL DIMENSIONS

Length, Width, Shape

finish on the ceiling with an NRC of 0.70 or

Please refer to structural narrative for more information on structural requirements.

Smithsonian Institution National Museum of African American History and Culture 164 Infrastructure Only 0 Other Amenities Deionized Water Vacuum Yes Speakers OH Gr. 2, 130 SF/HD FIRE ALARM Smoke Detection Yes Wet Sprinkler Special Waste Dry Sprinkler Pre-Action Sprinkler No FIRE PROTECTION 0 Considerations for Water 0 No Floor Drains Floor Sink Grey/Blackwater Piping 0 0 0 0 Protected Hot/Cold 0 0 Recycled Water Supply (treated) 0 0 Public Address Audio Compressed Air Audio Visual Requirements 0 Hot/Cold Water Task Light Yes No 0 Plant/Clean Steam No Acoustic Sensitivity NC 35-40 Vibration Sensitivity Special Equipment/Artifact Sensitivity PLUMBING Target Illuminance (IES 9th Edition) Daylight Sensor 10 FC Exhibit Light To Be Considered Power Density (AHSRAE 2004) 3.3 W/ft² Temperature Deviations (+/-) No No Process Water UPS Switched Receptacles Dimming No Humidity 0 No Other Humidity Deviation (+/-) As required by load No No Outside Air Single/Multi-Level Switching 0 Emergency/Standby Power As required by code 30/85 Multi Occupancy Sensor Special Exhaust Sub-metering & Feedback Displays Filtration (Pre/Final/Other) Voice/Data DATA/TELECOMMUNICATIONS Yes 0 SECURITY 0 5.0 kPa/8.9 kN Floor Loading/Point Loads DAYLIGHTING 0 0 Shading Considerations Top/Side Lighting 0 No STRUCTURAL 0 0 Refer to information
Open 0 Technical Comment: Meeting Reception/Waiting Assignable Square Feet (ASF) OFEO Space Dimensions 0 Organizational Unit Other Interior Glazing 0 Solid core wood or insulated metal with neoprene strip seals max 1/4" undercut Yes Yes 0 Ceiling CRITICAL FINISHES 0 0
indicated in Volume IV, Section E
ARCHITECTURAL
ELECTRICAL
Zone Room ID D1.67 Room Name 0
Non Public-Non Collection Space 400 Number of Occupants TBD Visual Privacy (full, partial, open) Zone Designation Zone D Room Height 0 LEED NC Regurlarly
Space 0 Base
Equipment Hardware/STC Rating None NRC Absorptive
STC 45 0 Plug Loads Air Change/ HR Walls HVAC ENGINEERING CRITERIA Temperature Lighting No Control ±2ºF 110v, 20a, 1ph Yes 0 Power No 0 Pressure (+/-) 78ºF Summer, 70ºF Winter Floor Operable Windows Separation/STC FURNITURE/EQUIPMENT Moveable 0 Fixed RT60
0 TBD
Occupied
ACOUSTICS
higher
& Shaping
Floor Level 0 Room
Open

This room data sheet is not comprehensive in nature. Information regarding specific room features may not have been available and was intentionally left blank.

Accessibility Requirement: Floor Level

Adjacencies

Compliance with ADA/ABAAG (2004) citations is required for accessibility. SI also requires compliance with SI Accessibility Guidelines and the IBC. Comparisons should be made and the more stringent requirement followed for design purposes. See Accessibility Narrative for additional information.

Directors Office, SUSTAINABILITY FEATURES

CRITICAL DIMENSIONS

No long rectangular spaces Room Length, Width, Shape Open vs. Private

Separation/STC

Sink recommended under Plumbing. Please refer to structural narrative for more information on structural requirements.

information indicated in Volume IV, Section

165 Room Data Sheets | FREELON BOND Infrastructure Only 0 Other Amenities Deionized Water Vacuum Yes Speakers OH Gr. 2, 130 SF/HD FIRE ALARM Smoke Detection Yes Wet Sprinkler Special Waste Dry Sprinkler Pre-Action Sprinkler No FIRE PROTECTION No Considerations for Water 0 No Floor Drains Floor Sink Grey/Blackwater Piping 0 No No No Protected Hot/Cold No No Recycled Water Supply (treated) 0 No Public Address Audio Compressed Air Audio Visual Requirements Yes Hot/Cold Water Task Light To Be Considered No 0 Plant/Clean Steam No Acoustic Sensitivity NC 30 Vibration Sensitivity Special Equipment/Artifact Sensitivity PLUMBING Target Illuminance (IES 9th Edition) Daylight Sensor 30-50 FC Exhibit Light To Be Considered Power Density (AHSRAE 2004) 1.3 W/ft² Temperature Deviations (+/-) No Yes Process Water UPS Switched Receptacles Dimming No Humidity 0 No Other Humidity Deviation (+/-) As required by load No No Outside Air Single/Multi-Level Switching 0 Emergency/Standby Power As required by code 30/85 Multi Occupancy Sensor Special Exhaust Sub-metering & Feedback Displays Filtration (Pre/Final/Other) Voice/Data DATA/TELECOMMUNICATIONS Yes 0 SECURITY 0 5.0 kPa/8.9 kN Floor Loading/Point Loads DAYLIGHTING 0 0 Shading Considerations Top/Side Lighting Full presentation system with video and audio conference capability. No STRUCTURAL 0 0 Refer
Partial/Open 0 Technical Comment: Board Room Assignable Square Feet (ASF) OFEO Space Dimensions 0 Organizational Unit Other Interior Glazing 0 Solid core wood or insulated metal with neoprene strips max 1/4" undercut Yes Yes 0 Ceiling CRITICAL FINISHES 0 0
to
E
ELECTRICAL ARCHITECTURAL
Zone Room ID D1.68 Room Name 0 Functional Description Coat racks and shelf for storage of staff's belongings. Non Public-Non Collection Space 1,500 Number of Occupants 35 Visual Privacy (full, partial, open) Zone Designation Zone D Room Height 0 LEED NC Regurlarly Occupied Space 0 Base ACOUSTICS Equipment Hardware/STC Rating None NRC Absorptive
ceiling
higher,
higher STC 55 0 Plug Loads Air Change/ HR Walls HVAC ENGINEERING CRITERIA Temperature Lighting No Control ±2ºF 110v, 20a, 1ph Yes 0 Power No 0 Pressure (+/-) 78ºF Summer, 70ºF Winter Floor
finish on the
with an NRC of 0.80 or
absorptive wall finish on two adjacent walls with an NRC 0.70 or
Operable Windows
FURNITURE/EQUIPMENT Moveable Yes Fixed RT60 & Shaping 0.7-0.9 s Upper

This room data sheet is not comprehensive in nature. Information regarding specific room features may not have been available and was intentionally left blank.

Assignable Square Feet (ASF) OFEO Space Dimensions

Accessibility Requirement:

Technical Comment:

SUSTAINABILITY FEATURES Adjacencies

vs. Private

Compliance with ADA/ABAAG (2004) citations is required for accessibility. SI also requires compliance with SI Accessibility Guidelines and the IBC. Comparisons should be made and the more stringent requirement followed for design purposes. See Accessibility Narrative for additional information.

Special communication requirement for the ECC will be developed and defined by SI-OPS.

and

whiteboard, AV equipment brought in as needed. Also designated as the Emergency Command

CRITICAL DIMENSIONS

Length, Width, Shape

Absorptive finish on the ceiling with an NRC of 0.80 or higher, absorptive wall finish on two adjacent walls with an NRC 0.70 or higher

Sink recommended under Plumbing. Please refer to structural narrative for more information on structural requirements.

Refer to information indicated in Volume IV, Section E

Smithsonian Institution National Museum of African American History and Culture 166 Infrastructure Only 0 Other Amenities Deionized Water Vacuum Yes Speakers OH Gr. 2, 130 SF/HD FIRE ALARM Smoke Detection Yes Wet Sprinkler Special Waste Dry Sprinkler Pre-Action Sprinkler No FIRE PROTECTION No Considerations for Water 0 No Floor Drains Floor Sink Grey/Blackwater Piping 0 No No No Protected Hot/Cold No No Recycled Water Supply
0 No Public Address Audio Compressed Air Audio Visual Requirements Yes Hot/Cold Water Task Light To Be Considered No 0 Plant/Clean Steam No Acoustic Sensitivity NC 30 Vibration Sensitivity Special Equipment/Artifact Sensitivity PLUMBING Target Illuminance
Daylight Sensor 30-50 FC Exhibit Light To Be Considered Power Density (AHSRAE 2004) 1.3 W/ft² Temperature Deviations (+/-) No Yes Process Water UPS
Dimming To Be Considered Humidity 0 No Other Humidity Deviation (+/-) As required by load No No Outside Air Single/Multi-Level Switching 0 Emergency/Standby Power As required by code 30/85 Multi Occupancy Sensor Special Exhaust Sub-metering
Filtration
Voice/Data DATA/TELECOMMUNICATIONS Yes 0 SECURITY 0 5.0 kPa/8.9 kN Floor Loading/Point Loads DAYLIGHTING 0 0 Shading Considerations Top/Side Lighting Full presentation system with video and audio conference capability. No STRUCTURAL 0 0
Partial/Open
(treated)
(IES 9th Edition)
Switched Receptacles
& Feedback Displays
(Pre/Final/Other)
Large Meeting Room
0
Other Interior
0 Solid core wood
metal
1/4" undercut Yes Yes 0 Ceiling CRITICAL FINISHES 0 0
Organizational Unit
Glazing
or insulated
with neoprene seals max
ELECTRICAL
ARCHITECTURAL
Zone Room ID D1.69 Room Name 0
meeting room,
standard meeting tables
Center
Non Public-Non Collection Space 1,200 Number of Occupants 20 Visual Privacy (full, partial, open) Zone Designation Zone D Room Height 0 LEED NC Regurlarly Occupied Space 0 Base ACOUSTICS Equipment Hardware/STC Rating None NRC
STC 55 0 Plug Loads Air Change/ HR Walls HVAC ENGINEERING
Temperature Lighting No Control ±2ºF 110v, 20a, 1ph Yes 0 Power No 0 Pressure (+/-) 78ºF Summer, 70ºF Winter Floor Operable Windows Separation/STC FURNITURE/EQUIPMENT Moveable Yes Fixed RT60 & Shaping 0.7-0.9 s TBD
Functional Description Staff
with
chairs,
(ECC)
CRITERIA
Central
to Offices
Floor Level 0 Room
Open

This room data sheet is not comprehensive in nature. Information regarding specific room features may not have been available and was intentionally left blank.

Compliance with ADA/ABAAG (2004) citations is required for accessibility. SI also requires compliance with SI Accessibility Guidelines and the IBC. Comparisons should be made and the more stringent requirement followed for design purposes. See Accessibility Narrative for additional information.

Description Staff meeting room, with standard meeting

vs. Private

Please refer to structural narrative for more information on structural requirements.

CRITICAL DIMENSIONS

167 Room Data Sheets | FREELON BOND Infrastructure Only 0 Other Amenities Deionized Water Vacuum Yes Speakers OH Gr. 2, 130 SF/HD FIRE ALARM Smoke Detection Yes Wet Sprinkler Special Waste Dry Sprinkler Pre-Action Sprinkler No FIRE PROTECTION No Considerations for Water 0 No Floor Drains Floor Sink Grey/Blackwater Piping 0 No No No Protected Hot/Cold No No Recycled Water Supply (treated) 0 No Public Address Audio Compressed Air Audio Visual Requirements No Hot/Cold Water Task Light To Be Considered No 0 Plant/Clean Steam No Acoustic Sensitivity NC 30 Vibration Sensitivity Special Equipment/Artifact Sensitivity PLUMBING Target Illuminance (IES 9th Edition) Daylight Sensor 30-50 FC Exhibit Light To Be Considered Power Density (AHSRAE 2004) 1.3 W/ft² Temperature Deviations (+/-) No Yes Process Water UPS Switched Receptacles Dimming To Be Considered Humidity 0 No Other Humidity Deviation (+/-) As required by load No No Outside Air Single/Multi-Level Switching 0 Emergency/Standby Power As required by code 30/85 Single Occupancy Sensor Special Exhaust Sub-metering & Feedback Displays Filtration (Pre/Final/Other) Voice/Data DATA/TELECOMMUNICATIONS Yes 0 SECURITY 0 5.0 kPa/8.9 kN Floor Loading/Point Loads DAYLIGHTING 0 0 Shading Considerations Top/Side Lighting Modest presentation system No STRUCTURAL 0 0 Refer to
Partial/Open 0 Technical Comment: Medium Meeting Room Assignable Square Feet (ASF) OFEO Space Dimensions 0 Organizational Unit Other Interior Glazing 0 Solid core wood or insulated metal with neoprene strip seals max 1/4" undercut Yes Yes 0 Ceiling CRITICAL FINISHES 0 0
information indicated in Volume IV, Section E
ELECTRICAL ARCHITECTURAL
Zone Room ID D1.70 Room Name 0
tables and chairs, whiteboard, AV equipment brought in as needed. Non Public-Non Collection Space 900 Number of Occupants 12 Visual Privacy (full, partial, open) Zone Designation Zone D Room Height 0 LEED NC Regurlarly Occupied Space 0 Base ACOUSTICS Equipment Hardware/STC Rating None NRC Absorptive
ceiling
of 0.80
higher,
0.70
higher STC 50 0 Plug Loads Air Change/ HR Walls HVAC ENGINEERING CRITERIA Temperature Lighting No Control ±2ºF 110v, 20a, 1ph Yes 0 Power No 0 Pressure (+/-) 78ºF Summer, 70ºF Winter Floor Operable Windows
FURNITURE/EQUIPMENT Moveable Yes Fixed RT60 & Shaping 0.7-0.9 s TBD
Functional
finish on the
with an NRC
or
absorptive wall finish on two adjacent walls with an NRC
or
Separation/STC
Central
Offices
Floor Level 0 Room
Open
to
SUSTAINABILITY FEATURES Adjacencies Accessibility Requirement:
Length, Width, Shape

This room data sheet is not comprehensive in nature. Information regarding specific room features may not have been available and was intentionally left blank.

Accessibility Requirement:

Compliance with ADA/ABAAG (2004) citations is required for accessibility. SI also requires compliance with SI Accessibility Guidelines and the IBC. Comparisons should be made and the more stringent requirement followed for design purposes. See Accessibility Narrative for additional information.

CRITICAL DIMENSIONS

vs. Private

Please refer to structural narrative for more information on structural requirements.

Smithsonian Institution National Museum of African American History and Culture 168 Infrastructure Only 0 Other Amenities Deionized Water Vacuum Yes Speakers OH Gr. 2, 130 SF/HD FIRE ALARM Smoke Detection Yes Wet Sprinkler Special Waste Dry Sprinkler Pre-Action Sprinkler No FIRE PROTECTION No Considerations for Water 0 No Floor Drains Floor Sink Grey/Blackwater Piping 0 No No No Protected Hot/Cold No No Recycled Water Supply (treated) 0 No Public Address Audio Compressed Air Audio Visual Requirements No Hot/Cold Water Task Light To Be Considered No 0 Plant/Clean Steam No Acoustic Sensitivity NC 30 Vibration Sensitivity Special Equipment/Artifact Sensitivity PLUMBING Target Illuminance (IES 9th Edition) Daylight Sensor 30-50 FC Exhibit Light To Be Considered Power Density (AHSRAE 2004) 1.3 W/ft² Temperature Deviations (+/-) No Yes Process Water UPS Switched Receptacles Dimming To Be Considered Humidity 0 No Other Humidity Deviation (+/-) As required by load No No Outside Air Single/Multi-Level Switching 0 Emergency/Standby Power As required by code 30/85 Multi Occupancy Sensor Special Exhaust Sub-metering & Feedback Displays Filtration (Pre/Final/Other) Voice/Data DATA/TELECOMMUNICATIONS Yes 0 SECURITY 0 5.0 kPa/8.9 kN Floor Loading/Point Loads DAYLIGHTING 0 0 Shading Considerations Top/Side Lighting None No STRUCTURAL 0 0 Refer to
Partial/Open 0 Technical Comment: Small Meeting Room Assignable Square Feet (ASF) OFEO Space Dimensions 0 Organizational Unit Other Interior Glazing 0 Solid core wood or insulated metal with neoprene strip seals 1/4" undercut Yes Yes 0 Ceiling CRITICAL FINISHES 0 0
information indicated in Volume IV, Section E
ELECTRICAL ARCHITECTURAL
Zone Room ID D1.71 Room Name 0 Functional
whiteboard, AV equipment brought
needed. Non Public-Non Collection Space 200 Number of Occupants 8 Visual Privacy (full, partial, open) Zone Designation Zone D Room Height 0 LEED NC Regurlarly Occupied Space 0 Base ACOUSTICS Equipment Hardware/STC Rating None NRC Absorptive
ceiling
0.80
higher,
higher STC 50 0 Plug Loads Air Change/ HR Walls HVAC ENGINEERING CRITERIA Temperature Lighting No Control ±2ºF 110v, 20a, 1ph Yes 0 Power No 0 Pressure (+/-) 78ºF Summer, 70ºF Winter Floor Operable Windows
FURNITURE/EQUIPMENT Moveable Yes Fixed RT60 & Shaping 0.6-0.7 s TBD
Description Staff meeting room, with standard meeting tables and chairs,
in as
finish on the
with an NRC of
or
absorptive wall finish on two adjacent walls with an NRC 0.70 or
Separation/STC
Central to Offices
Adjacencies
Floor Level 0 Room
Open
SUSTAINABILITY FEATURES
Length, Width, Shape

This room data sheet is not comprehensive in nature. Information regarding specific

with ADA/ABAAG (2004) citations is required for accessibility. SI also requires compliance with SI Accessibility Guidelines and the IBC. Comparisons should be made and the more stringent requirement followed for design purposes. See Accessibility Narrative for additional information.

CRITICAL DIMENSIONS

Please refer to structural narrative for more information on structural requirements.

169 Room Data Sheets | FREELON BOND Infrastructure Only 0 Other Amenities Deionized Water Vacuum Yes Speakers OH Gr. 2, 130 SF/HD FIRE ALARM Smoke Detection Yes Wet Sprinkler Special Waste Dry Sprinkler Pre-Action Sprinkler No FIRE PROTECTION No Considerations for Water 0 No Floor Drains Floor Sink Grey/Blackwater Piping 0 No No No Protected Hot/Cold No No Recycled Water Supply (treated) 0 No Public Address Audio Compressed Air Audio Visual Requirements No Hot/Cold Water Task Light No No 0 Plant/Clean Steam No Acoustic Sensitivity NC 40 Vibration Sensitivity Special Equipment/Artifact Sensitivity PLUMBING Target Illuminance (IES 9th Edition) Daylight Sensor 10 FC Exhibit Light No Power Density (AHSRAE 2004) 0.6 W/ft² Temperature Deviations (+/-) No No Process Water UPS Switched Receptacles Dimming To Be Considered Humidity 0 No Other Humidity Deviation (+/-) As required by load No No Outside Air Single/Multi-Level Switching 0 Emergency/Standby Power As required by code 30/85 Single Occupancy Sensor Special Exhaust Sub-metering & Feedback Displays Filtration (Pre/Final/Other) Voice/Data DATA/TELECOMMUNICATIONS 0 0 SECURITY 0 5.0 kPa/8.9 kN Floor Loading/Point Loads DAYLIGHTING 0 0 Shading Considerations Top/Side Lighting None No STRUCTURAL 0 0 Refer to information indicated in Volume IV, Section E Full 0 Technical Comment: Coatroom Assignable Square Feet (ASF) OFEO Space Dimensions 0 Organizational Unit Other Interior Glazing 0 0 Yes No 0 Ceiling CRITICAL FINISHES 0 0
ELECTRICAL ARCHITECTURAL
room features may not have been available and was intentionally left blank. Zone Room ID D1.72 Room Name 0 Functional Description Coat racks and shelf for storage of staff's belongings. Non Public-Non Collection Space 100 Number of Occupants NA Visual Privacy (full, partial, open) Zone Designation Zone D Room Height 0 LEED NC Regurlarly Occupied Space 0 Base ACOUSTICS Equipment Hardware/STC Rating None NRCSTC 45 0 Plug Loads Air Change/ HR Walls HVAC ENGINEERING CRITERIA Temperature Lighting No Control ±2ºF 110v, 20a, 1ph Yes 0 Power No 0 Pressure (+/-) 78ºF Summer, 70ºF Winter Floor Operable Windows Separation/STC FURNITURE/EQUIPMENT Moveable Yes Fixed RT60 & Shaping 0 TBD
Central to Offices
Compliance
Adjacencies Accessibility Requirement: Floor Level 0 Room Length, Width, Shape Open vs. Private
SUSTAINABILITY FEATURES

This room data sheet is not comprehensive in nature. Information regarding specific

SUSTAINABILITY FEATURES

(2004) citations is required for

SI also requires compliance with

Guidelines and the IBC. Comparisons should be made and the more stringent requirement followed for design purposes.

Please refer to structural narrative for more information on structural requirements.

CRITICAL DIMENSIONS

Smithsonian Institution National Museum of African American History and Culture 170 Infrastructure Only 0 Other Amenities Deionized Water Vacuum Yes Speakers OH Gr. 2, 130 SF/HD FIRE ALARM Smoke Detection Yes Wet Sprinkler Special Waste Dry Sprinkler Pre-Action Sprinkler No FIRE PROTECTION No Considerations for Water 0 No Floor Drains Floor Sink Grey/Blackwater Piping 0 No No No Protected Hot/Cold No No Recycled Water Supply (treated) 0 No Public Address Audio Compressed Air Audio Visual Requirements No Hot/Cold Water Task Light No No 0 Plant/Clean Steam No Acoustic Sensitivity No Vibration Sensitivity Special Equipment/Artifact Sensitivity PLUMBING Target Illuminance (IES 9th Edition) Daylight Sensor 10 FC Exhibit Light No Power Density (AHSRAE 2004) 0.8 W/ft² Temperature Deviations (+/-) No No Process Water UPS Switched Receptacles Dimming To Be Considered Humidity 0 No Other Humidity Deviation (+/-) As required by load No No Outside Air Single/Multi-Level Switching 0 Emergency/Standby Power As required by code 30/85 Single Occupancy Sensor Special Exhaust Sub-metering & Feedback Displays Filtration (Pre/Final/Other) Voice/Data DATA/TELECOMMUNICATIONS Yes 0 SECURITY 0 5.0 kPa/8.9 kN Floor Loading/Point Loads DAYLIGHTING 0 0 Shading Considerations Top/Side Lighting None No STRUCTURAL 0 0 Refer to information indicated in Volume IV, Section E Full 0 Technical Comment: Board Room Storage Assignable Square Feet (ASF) OFEO Space Dimensions 0 Organizational Unit Other Interior Glazing 0 0 Yes Yes 0 Ceiling CRITICAL FINISHES 0 0
ELECTRICAL ARCHITECTURAL
room features may not have been available and was intentionally left blank. Zone Room ID D1.73 Room Name 0 Functional Description Storage for supplies and equipment to support Boardroom activities. Non Public-Non Collection Space 100 Number of Occupants NA Visual Privacy (full, partial, open) Zone Designation Zone D Room Height 0 LEED NC Regurlarly Occupied Space 0 Base ACOUSTICS Equipment Hardware/STC Rating None NRC0 0 Plug Loads Air Change/ HR Walls HVAC ENGINEERING CRITERIA Temperature Lighting No Control ±2ºF 110v, 20a, 1ph Yes 0 Power No 0 Pressure (+/-) 78ºF Summer, 70ºF Winter Floor Operable Windows Separation/STC FURNITURE/EQUIPMENT Moveable No Fixed RT60 & Shaping 0 Same
accessibility.
Board Room
level as Board Room Compliance with ADA/ABAAG
SI Accessibility
See Accessibility Narrative for additional information.
Adjacencies Accessibility Requirement: Floor Level 0 Room Length, Width, Shape Open
vs. Private

This room data sheet is not comprehensive in nature. Information regarding specific room features may not have been available and was intentionally left blank.

Accessibility Requirement:

Adjacencies

SUSTAINABILITY FEATURES

Compliance with ADA/ABAAG (2004) citations is required for accessibility. SI also requires compliance with SI Accessibility Guidelines and the IBC. Comparisons should be made and the more stringent requirement followed for design purposes. See Accessibility Narrative for additional information.

Central Mail/Photocopy, Supplies and File Rooms, Meeting Rooms

Separation/STC

CRITICAL DIMENSIONS

Absorptive finish on the ceiling with an NRC of 0.70 or higher

Recommend Sink under Plumbing. Please refer to structural narrative for more information on structural requirements.

171 Room Data Sheets | FREELON BOND Infrastructure Only 0 Other Amenities Deionized Water Vacuum Yes Speakers OH Gr. 2, 130 SF/HD FIRE ALARM Smoke Detection Yes Wet Sprinkler Special Waste Dry Sprinkler Pre-Action Sprinkler No FIRE PROTECTION No Considerations for Water 0 No Floor Drains Floor Sink Grey/Blackwater Piping 0 No No No Protected Hot/Cold No No Recycled Water Supply (treated) 0 No Public Address Audio Compressed Air Audio Visual Requirements Yes Hot/Cold Water Task Light No No 0 Plant/Clean Steam No Acoustic Sensitivity NC 35-40 Vibration Sensitivity Special Equipment/Artifact Sensitivity PLUMBING Target Illuminance (IES 9th Edition) Daylight Sensor 30 FC Exhibit Light To Be Considered Power Density (AHSRAE 2004) 1.4 W/ft² Temperature Deviations (+/-) No No Process Water UPS Switched
Dimming To Be Considered Humidity 0 No Other Humidity Deviation (+/-) As required by load No No Outside Air Single/Multi-Level Switching 0 Emergency/Standby Power As required by code 30/85 Single Occupancy Sensor Special Exhaust Sub-metering & Feedback Displays Filtration (Pre/Final/Other) Voice/Data DATA/TELECOMMUNICATIONS Yes 0 SECURITY 0 5.0 kPa/8.9 kN Floor Loading/Point Loads DAYLIGHTING 0 0 Shading Considerations Top/Side Lighting None No STRUCTURAL 0 0 Refer to information
E Partial 0 Technical Comment: Staff Lounge/Break Room/Servery Assignable Square Feet
OFEO Space Dimensions 0 Organizational Unit Other Interior Glazing 0 Solid core wood or insulated metal with neoprane strip seals max 1/4" undercut Yes Yes Cleanable Ceiling CRITICAL FINISHES 0 0
Receptacles
indicated in Volume IV, Section
(ASF)
ELECTRICAL ARCHITECTURAL
Zone Room ID D2.1 Room Name 0 Functional Description Refreshment/prep facility for Staff including countertop for food preparation, microwave and coffee machine, sink and dish washer, refrigerator, and shelving for cutlery and dishes. Lunch tables and chairs. Non Public-Non Collection Space 600 Number of Occupants TBD Visual Privacy (full, partial, open) Zone Designation Zone D Room Height 0 LEED NC Regurlarly Occupied Space 0 Base ACOUSTICS Equipment Hardware/STC Rating None NRC
STC 50 0 Plug Loads Air Change/ HR Walls HVAC ENGINEERING
Temperature Lighting No Control ±2ºF 110v, 20a, 1ph Yes 0 Power No 0 Pressure (+/-) 78ºF Summer, 70ºF Winter Floor Operable Windows
CRITERIA
FURNITURE/EQUIPMENT Moveable Yes Fixed RT60 & Shaping 0 TBD
Floor Level 0 Room
Length, Width, Shape Open vs. Private

This room data sheet is not comprehensive in nature. Information regarding specific room features may not have been available and was intentionally left blank.

Technical Comment:

Compliance with ADA/ABAAG (2004) citations is required for accessibility. SI also requires compliance with SI Accessibility Guidelines and the IBC. Comparisons should be made and the more stringent requirement followed for design purposes. See Accessibility Narrative for additional information.

Volunteer/Teachers,

Incorporate Web Station, Day Lockers for Volunteer belongings.

CRITICAL DIMENSIONS

Absorptive finish on the ceiling with an NRC of 0.70 or higher

Please refer to structural narrative for more information on structural requirements.

to information indicated in Volume IV, Section E

Smithsonian Institution National Museum of African American History and Culture 172 Infrastructure Only 0 Other Amenities Deionized Water Vacuum Yes Speakers OH Gr. 2, 130 SF/HD FIRE ALARM Smoke Detection Yes Wet Sprinkler Special Waste Dry Sprinkler Pre-Action Sprinkler No FIRE PROTECTION No Considerations for Water 0 No Floor Drains Floor Sink Grey/Blackwater Piping 0 No No No Protected Hot/Cold No No Recycled Water Supply (treated) 0 No Public Address Audio Compressed Air Audio Visual Requirements Yes Hot/Cold Water Task Light No No 0 Plant/Clean Steam No Acoustic Sensitivity NC 35 Vibration Sensitivity Special Equipment/Artifact Sensitivity PLUMBING Target Illuminance (IES 9th Edition) Daylight Sensor 30-50 FC Exhibit Light To Be Considered Power Density (AHSRAE 2004) 1.3 W/ft² Temperature Deviations (+/-) No No Process Water UPS Switched
Dimming To Be Considered Humidity 0 No Other Humidity Deviation (+/-) As required by load No No Outside Air Single/Multi-Level Switching 0 Emergency/Standby Power As required by code 30/85 Single Occupancy Sensor Special Exhaust Sub-metering & Feedback Displays Filtration (Pre/Final/Other) Voice/Data DATA/TELECOMMUNICATIONS Yes 0 SECURITY 0 5.0 kPa/8.9 kN Floor Loading/Point Loads DAYLIGHTING 0 0 Shading Considerations Top/Side Lighting None No STRUCTURAL 0 0
Partial/Open
Receptacles
Refer
Training Room/Docent Lounge/Day
0
Other Interior Glazing 0 Solid core wood or insulated metal with
strip
max 1/4" undercut Yes Yes 0 Ceiling CRITICAL FINISHES 0 0
Volunteer
Lockers, Volunteer/Teachers Assignable Square Feet (ASF) OFEO Space Dimensions
Organizational Unit
neoprene
seals
ELECTRICAL ARCHITECTURAL
Zone Room ID D2.2 Room Name 0 Functional Description Flexible space usable for development projects such as telethons, package assembly, or as drop-in offices, etc.,
data
phone lines, folding tables, stacking chairs, blackboards/whiteboards. Non Public-Non Collection Space 800 Number of Occupants TBD Visual Privacy (full, partial, open) Zone Designation Zone D Room Height 0 LEED NC Regurlarly Occupied Space 0 Base ACOUSTICS Equipment Hardware/STC Rating None NRC
STC 50 0 Plug Loads Air Change/ HR Walls HVAC ENGINEERING CRITERIA Temperature Lighting No Control ±2ºF 110v, 20a, 1ph Yes 0 Power No 0 Pressure (+/-) 78ºF Summer, 70ºF Winter Floor Operable Windows Separation/STC FURNITURE/EQUIPMENT Moveable Yes Fixed RT60 & Shaping 0 TBD
with
and
Day
Floor Level 0 Room
Open
Lockers,
Public Space SUSTAINABILITY FEATURES Adjacencies Accessibility Requirement:
Length, Width, Shape
vs. Private

This

data sheet is not comprehensive in nature. Information regarding specific room features may not have been available and was intentionally left

Compliance with ADA/ABAAG (2004) citations is required for accessibility. SI also requires compliance with SI Accessibility Guidelines and the IBC. Comparisons should be made and the more stringent requirement followed for design purposes. See ADA/ABAAG (2004) Chapter 6 Plumbing Elements and Facilities. See Accessibility Narrative for additional information. Gym Facility, Staff Washrooms

CRITICAL DIMENSIONS

Separation/STC FURNITURE/EQUIPMENT

Please refer to structural narrative for more information on structural requirements.

173 Room Data Sheets | FREELON BOND Infrastructure Only 0 Other Amenities Deionized Water Vacuum Yes Speakers OH Gr. 2, 130 SF/HD FIRE ALARM Smoke Detection Yes Wet Sprinkler Special Waste Dry Sprinkler Pre-Action Sprinkler No FIRE PROTECTION No Considerations for Water 0 No Floor Drains Floor Sink Grey/Blackwater Piping 0 Yes No Rainwater Flush Protected Hot/Cold No No Recycled Water Supply (treated) 0 Yes Public Address Audio Compressed Air Audio Visual Requirements Yes Hot/Cold Water Task Light No No 0 Plant/Clean Steam No Acoustic Sensitivity NC 40 Vibration Sensitivity Special Equipment/Artifact Sensitivity PLUMBING Target Illuminance (IES 9th Edition) Daylight Sensor 5 FC Exhibit Light No Power Density (AHSRAE 2004) 0.9 W/ft² Temperature Deviations (+/-) No No Process Water UPS Switched Receptacles Dimming To Be Considered Humidity 0 No Other Humidity Deviation (+/-) As required by load No No Outside Air Single/Multi-Level Switching 0 Emergency/Standby Power As required by code 30/85 Single Occupancy Sensor Special Exhaust Sub-metering & Feedback Displays Filtration (Pre/Final/Other) Voice/Data DATA/TELECOMMUNICATIONS Yes 0 SECURITY 0 5.0 kPa/8.9 kN Floor Loading/Point Loads DAYLIGHTING 0 0 Shading Considerations Top/Side Lighting None No STRUCTURAL 0 0 Refer to information indicated
Volume IV, Section E Full 0 Technical Comment: Staff Changing Room, Male w/ Showers Assignable Square Feet (ASF) OFEO Space Dimensions 0 Organizational Unit Other Interior Glazing Cleanable 0 No Yes Cleanable Ceiling CRITICAL FINISHES Cleanable 0
in
ELECTRICAL ARCHITECTURAL
blank. Zone Room ID D2.3 Room Name 0
Male Staff changing
Non Public-Non Collection Space 300 Number of Occupants TBD Visual Privacy (full, partial, open) Zone Designation Zone D Room Height 0 LEED NC Regurlarly Occupied Space 0 Base ACOUSTICS Equipment Hardware/STC Rating None NRCSTC 55 0 Plug Loads Air Change/ HR Walls HVAC ENGINEERING CRITERIA Temperature Lighting No Control ±2ºF 110v, 20a, 1ph Yes 0 Power No Cleanable Pressure (+/-) 78ºF Summer, 70ºF Winter Floor Operable Windows
room
Functional Description
area with showers and lockers, adjacent to staff washroom facilities.
Moveable Yes Fixed RT60 & Shaping 0 TBD
Floor Level 0 Room Length,
Open
SUSTAINABILITY FEATURES Adjacencies Accessibility Requirement:
Width, Shape
vs. Private

This

Compliance with ADA/ABAAG (2004) citations is required for accessibility. SI also requires compliance with SI Accessibility Guidelines and the IBC. Comparisons should be made and the more stringent requirement followed for design purposes. See ADA/ABAAG (2004) Chapter 6 Plumbing Elements and Facilities. See Accessibility Narrative for additional information. Gym Facility, Staff Washrooms

CRITICAL DIMENSIONS

Separation/STC FURNITURE/EQUIPMENT

Please refer to structural narrative for more information on structural requirements.

Smithsonian Institution National Museum of African American History and Culture 174 Infrastructure Only 0 Other Amenities Deionized Water Vacuum Yes Speakers OH Gr. 2, 130 SF/HD FIRE ALARM Smoke Detection Yes Wet Sprinkler Special Waste Dry Sprinkler Pre-Action Sprinkler No FIRE PROTECTION No Considerations for Water 0 No Floor Drains Floor Sink Grey/Blackwater Piping 0 Yes No Rainwater Flush Protected Hot/Cold No No Recycled Water Supply (treated) 0 Yes Public Address Audio Compressed Air Audio Visual Requirements Yes Hot/Cold Water Task Light No No 0 Plant/Clean Steam No Acoustic Sensitivity NC 40 Vibration Sensitivity Special Equipment/Artifact Sensitivity PLUMBING Target Illuminance (IES 9th Edition) Daylight Sensor 5 FC Exhibit Light No Power Density (AHSRAE 2004) 0.9 W/ft² Temperature Deviations (+/-) No No Process Water UPS Switched Receptacles Dimming To Be Considered Humidity 0 No Other Humidity Deviation (+/-) As required by load No No Outside Air Single/Multi-Level Switching 0 Emergency/Standby Power As required by code 30/85 Single Occupancy Sensor Special Exhaust Sub-metering & Feedback Displays Filtration (Pre/Final/Other) Voice/Data DATA/TELECOMMUNICATIONS Yes 0 SECURITY 0 5.0 kPa/8.9 kN Floor Loading/Point Loads DAYLIGHTING 0 0 Shading Considerations Top/Side Lighting None No STRUCTURAL 0 0 Refer to information indicated
Volume IV,
E Full 0 Technical Comment: Staff Changing Room, Female w/ Showers Assignable Square Feet
OFEO Space Dimensions 0 Organizational Unit Other Interior Glazing Cleanable 0 No Yes Cleanable Ceiling CRITICAL FINISHES Cleanable 0
in
Section
(ASF)
ELECTRICAL ARCHITECTURAL
blank. Zone Room ID D2.4 Room Name 0
Female Staff changing area
Non Public-Non Collection Space 300 Number of Occupants TBD Visual Privacy (full, partial, open) Zone Designation Zone D Room Height 0 LEED NC Regurlarly Occupied Space 0 Base ACOUSTICS Equipment Hardware/STC Rating None NRCSTC 55 0 Plug Loads Air Change/ HR Walls HVAC ENGINEERING CRITERIA Temperature Lighting No Control ±2ºF 110v, 20a, 1ph Yes 0 Power No Cleanable Pressure (+/-) 78ºF Summer, 70ºF Winter Floor Operable Windows
room data sheet is not comprehensive in nature. Information regarding specific room features may not have been available and was intentionally left
Functional Description
with showers and lockers, adjacent to staff washrooms facilities.
Moveable Yes Fixed RT60 & Shaping 0 TBD
Floor Level 0 Room Length,
Open
SUSTAINABILITY FEATURES Adjacencies Accessibility Requirement:
Width, Shape
vs. Private

Adjacencies Accessibility Requirement:

Compliance with ADA/ABAAG (2004) citations is required for accessibility. SI also requires compliance with SI Accessibility Guidelines and the IBC. Comparisons should be made and the more stringent requirement followed for design purposes. See ADA/ABAAG (2004) Chapter 6 Plumbing Elements and Facilities. See Accessibility Narrative for additional information. Gym Facility, Staff Changing Rooms, Administration Area

SUSTAINABILITY FEATURES

Please refer to structural narrative for more information on structural requirements.

CRITICAL DIMENSIONS

175 Room Data Sheets | FREELON BOND Infrastructure Only 0 Other Amenities Deionized Water Vacuum Yes Speakers OH Gr. 2, 130 SF/HD FIRE ALARM Smoke Detection Yes Wet Sprinkler Special Waste Dry Sprinkler Pre-Action Sprinkler No FIRE PROTECTION No Considerations for Water 0 No Floor Drains Floor Sink Grey/Blackwater Piping 0 No No Rainwater Flush Protected Hot/Cold No No Recycled Water Supply (treated) 0 Yes Public Address Audio Compressed Air Audio Visual Requirements Yes Hot/Cold Water Task Light No No 0 Plant/Clean Steam No Acoustic Sensitivity NC 40 Vibration Sensitivity Special Equipment/Artifact Sensitivity PLUMBING Target Illuminance (IES 9th Edition) Daylight Sensor 5 FC Exhibit Light No Power Density (AHSRAE 2004) 0.9 W/ft² Temperature Deviations (+/-) No No Process Water UPS Switched Receptacles Dimming To Be Considered Humidity 0 No Other Humidity Deviation (+/-) As required by load No No Outside Air Single/Multi-Level Switching 0 Emergency/Standby Power As required by code 30/85 Single Occupancy Sensor Special Exhaust Sub-metering & Feedback Displays Filtration (Pre/Final/Other) Voice/Data DATA/TELECOMMUNICATIONS 0 0 SECURITY 0 5.0 kPa/8.9 kN Floor Loading/Point Loads DAYLIGHTING 0 0 Shading Considerations Top/Side Lighting None No STRUCTURAL 0 0 Refer to information indicated in Volume IV, Section E Full Included in Grossing Factor. Technical Comment: Staff Washrooms, Male Assignable Square Feet (ASF) OFEO Space Dimensions 0 Organizational Unit Other Interior Glazing Cleanable 0 No Yes Cleanable Ceiling CRITICAL FINISHES Cleanable 0
ELECTRICAL ARCHITECTURAL
room
nature.
available
left blank. Zone Room ID D2.5 Room Name 0 Functional Description 0 Non Public-Non Collection Space 0 Number of Occupants NA Visual Privacy (full, partial, open) Zone
Room Height 0 LEED NC Regurlarly Occupied Space 0 Base ACOUSTICS Equipment Hardware/STC Rating None NRCSTC 55 0 Plug Loads Air Change/ HR Walls HVAC ENGINEERING CRITERIA Temperature Lighting No Control ±2ºF 110v, 20a, 1ph Yes 0 Power No Cleanable Pressure (+/-) 78ºF Summer, 70ºF Winter Floor Operable Windows Separation/STC FURNITURE/EQUIPMENT Moveable Yes Fixed RT60 & Shaping 0 TBD
This
data sheet is not comprehensive in
Information regarding specific room features may not have been
and was intentionally
Designation Zone D
Floor Level 0 Room
Length, Width, Shape Open vs. Private

This room data sheet is not comprehensive in nature. Information regarding specific room features may not have been available and was intentionally left

Accessibility Requirement:

SUSTAINABILITY FEATURES Adjacencies

Compliance with ADA/ABAAG (2004) citations is required for accessibility. SI also requires compliance with SI Accessibility Guidelines and the IBC. Comparisons should be made and the more stringent requirement followed for design purposes. See ADA/ABAAG (2004) Chapter 6 Plumbing Elements and Facilities. See Accessibility Narrative for additional information. Gym Facility, Staff Changing Rooms, Administration Area

CRITICAL DIMENSIONS

Please refer to structural narrative for more information on structural requirements.

Smithsonian Institution National Museum of African American History and Culture 176 Infrastructure Only 0 Other Amenities Deionized Water Vacuum Yes Speakers OH Gr. 2, 130 SF/HD FIRE ALARM Smoke Detection Yes Wet Sprinkler Special Waste Dry Sprinkler Pre-Action Sprinkler No FIRE PROTECTION No Considerations for Water 0 No Floor Drains Floor Sink Grey/Blackwater Piping 0 No No Rainwater Flush Protected Hot/Cold No No Recycled Water Supply (treated) 0 Yes Public Address Audio Compressed Air Audio Visual Requirements Yes Hot/Cold Water Task Light No No 0 Plant/Clean Steam No Acoustic Sensitivity NC 40 Vibration Sensitivity Special Equipment/Artifact Sensitivity PLUMBING Target Illuminance (IES 9th Edition) Daylight Sensor 5 FC Exhibit Light No Power Density (AHSRAE 2004) 0.9 W/ft² Temperature Deviations (+/-) No No Process Water UPS Switched Receptacles Dimming To Be Considered Humidity 0 No Other Humidity Deviation (+/-) As required by load No No Outside Air Single/Multi-Level Switching 0 Emergency/Standby Power As required by code 30/85 Single Occupancy Sensor Special Exhaust Sub-metering & Feedback Displays Filtration (Pre/Final/Other) Voice/Data DATA/TELECOMMUNICATIONS 0 0 SECURITY 0 5.0 kPa/8.9 kN Floor Loading/Point Loads DAYLIGHTING 0 0 Shading Considerations Top/Side Lighting None No STRUCTURAL 0 0 Refer to information indicated in Volume IV,
E Full Included in
Technical
Staff Washrooms, Female Assignable Square Feet (ASF) OFEO Space Dimensions 0 Organizational Unit Other Interior Glazing Cleanable 0 No Yes Cleanable Ceiling CRITICAL FINISHES Cleanable 0
Section
Grossing Factor.
Comment:
ELECTRICAL ARCHITECTURAL
Zone Room ID D2.6 Room Name 0
Non Public-Non Collection Space 0 Number of Occupants NA Visual Privacy (full, partial, open) Zone Designation Zone
Room Height 0 LEED NC Regurlarly Occupied Space 0 Base ACOUSTICS Equipment Hardware/STC Rating None NRCSTC 55 0 Plug Loads Air Change/ HR Walls HVAC ENGINEERING CRITERIA Temperature Lighting No Control ±2ºF 110v, 20a, 1ph Yes 0 Power No Cleanable Pressure (+/-) 78ºF Summer, 70ºF Winter Floor Operable Windows
FURNITURE/EQUIPMENT Moveable Yes Fixed RT60 & Shaping 0 TBD
blank.
Functional Description Allow for more female than male.
D
Separation/STC
Floor Level 0 Room
Length, Width, Shape Open vs. Private

This room data sheet is not comprehensive in nature. Information regarding specific room features may not have been available and was intentionally left blank.

Accessibility Requirement:

Adjacencies

SUSTAINABILITY FEATURES

vs. Private

Separation/STC

Occupied Space

Compliance with ADA/ABAAG (2004) citations is required for accessibility. SI also requires compliance with SI Accessibility Guidelines and the IBC. Comparisons should be made and the more stringent requirement followed for design purposes. See Accessibility Narrative for additional information.

Staff Changing/Shower Rooms and Washrooms

CRITICAL DIMENSIONS

Length, Width, Shape

finish on the ceiling with an NRC of 0.70 or higher

Recommend Drinking Fountain under Plumbing. Please refer to structural narrative for more information on structural requirements.

to information indicated in Volume IV, Section E

177 Room Data Sheets | FREELON BOND Infrastructure Only 0 Other Amenities Deionized Water Vacuum Yes Speakers OH Gr. 2, 130 SF/HD FIRE ALARM Smoke Detection Yes Wet Sprinkler Special Waste Dry Sprinkler Pre-Action Sprinkler No FIRE PROTECTION No Considerations for Water 0 No Floor Drains Floor Sink Grey/Blackwater Piping 0 No No No Protected Hot/Cold No No Recycled Water Supply (treated) 0 No Public Address Audio Compressed Air Audio Visual Requirements Yes Hot/Cold Water Task Light No No 0 Plant/Clean Steam No Acoustic Sensitivity NC 35-40 Vibration Sensitivity Special Equipment/Artifact Sensitivity PLUMBING Target Illuminance (IES 9th Edition) Daylight Sensor 30 FC Exhibit Light To Be Considered Power Density (AHSRAE 2004) 0.9 W/ft² Temperature Deviations (+/-) No No Process Water UPS Switched Receptacles Dimming No Humidity 0 No Other Humidity Deviation (+/-) As required by load No No Outside Air Single/Multi-Level Switching 0 Emergency/Standby Power As required by code 30/85 Multi Occupancy Sensor Special Exhaust Sub-metering & Feedback Displays Filtration (Pre/Final/Other) Voice/Data DATA/TELECOMMUNICATIONS Yes 0 SECURITY 0 5.0 kPa/8.9 kN Floor Loading/Point Loads DAYLIGHTING 0 0 Shading Considerations Top/Side Lighting Television viewing provded with fitness center equipment No STRUCTURAL 0 0 Refer
Partial/Open 0 Technical Comment: Small Gym / Fitness Center Assignable Square Feet
OFEO Space Dimensions 0 Organizational Unit Other Interior Glazing 0 Solid core wood or insulated metal with neoprene strip seals 1/4" undercut Yes Yes Padded Ceiling CRITICAL FINISHES 0 0
(ASF)
ELECTRICAL ARCHITECTURAL
Zone Room ID D2.7 Room Name 0
racks,
floor
room
padded
absorb shock
dropped
Non Public-Non Collection Space 800 Number of Occupants TBD Visual Privacy (full, partial, open) Zone Designation Zone D Room Height 0 LEED
0 Base
Equipment Hardware/STC Rating None NRC Absorptive
STC 55 0 Plug Loads Air Change/ HR Walls HVAC ENGINEERING
Temperature Lighting No Control ±2ºF 110v, 20a, 1ph Yes 0 Power No 0 Pressure (+/-) 78ºF Summer, 70ºF Winter Floor Operable Windows
Functional Description Gym equipment, some freeweights on storage
towel hangers. The
of this
should be
to
of
weights.
NC Regurlarly
ACOUSTICS
CRITERIA
FURNITURE/EQUIPMENT Moveable Yes Fixed RT60
0 TBD
& Shaping
Floor Level 0 Room
Open

This room data sheet is not comprehensive in nature. Information regarding specific room features may not have been available and was intentionally left blank.

Accessibility Requirement:

Adjacencies

Comment:

Functional Description

SUSTAINABILITY FEATURES

vs. Private

Compliance with ADA/ABAAG (2004) citations is required for accessibility. SI also requires compliance with SI Accessibility Guidelines and the IBC. Comparisons should be made and the more stringent requirement followed for design purposes. See Accessibility Narrative for additional information.

Confirm SF supports 175 staff.

CRITICAL DIMENSIONS

Recommended Sink under Plumbing. Please refer to structural narrative for more information on structural requirements.

to information indicated in Volume IV, Section E

Smithsonian Institution National Museum of African American History and Culture 178 Infrastructure Only 0 Other Amenities Deionized Water Vacuum Yes Speakers OH Gr. 2, 130 SF/HD FIRE ALARM Smoke Detection Yes Wet Sprinkler Special Waste Dry Sprinkler Pre-Action Sprinkler No FIRE PROTECTION 0 Considerations for Water 0 No Floor Drains Floor Sink Grey/Blackwater Piping 0 0 0 0 Protected Hot/Cold 0 0 Recycled Water Supply (treated) 0 0 Public Address Audio Compressed Air Audio Visual Requirements Yes Hot/Cold Water Task Light Yes No 0 Plant/Clean Steam No Acoustic Sensitivity NC 30-40 Vibration Sensitivity Special Equipment/Artifact Sensitivity PLUMBING Target Illuminance (IES 9th Edition) Daylight Sensor 10 FC Exhibit Light To Be Considered Power Density (AHSRAE 2004) 0.6 W/ft² Temperature Deviations (+/-) No No Process Water UPS Switched Receptacles Dimming To Be Considered Humidity 0 No Other Humidity Deviation (+/-) As required by load No No Outside Air Single/Multi-Level Switching 0 Emergency/Standby Power As required by code 30/85 Single Occupancy Sensor Special Exhaust Sub-metering & Feedback Displays Filtration (Pre/Final/Other) Voice/Data DATA/TELECOMMUNICATIONS Yes 0 SECURITY 0 5.0 kPa/8.9 kN Floor Loading/Point Loads DAYLIGHTING 0 0 Shading Considerations Top/Side Lighting None No STRUCTURAL 0 0 Refer
Full
Technical
Staff First Aid Emergency
OFEO Space Dimensions 0 Organizational Unit Other Interior Glazing 0 Solid core wood or insulated metal with neoprane strip seals max 1/4" undercut Yes Yes 0 Ceiling CRITICAL FINISHES 0 0
Assignable Square Feet (ASF)
ELECTRICAL ARCHITECTURAL
Zone Room ID D2.8 Room Name 0
First Aid area serving staff. Lie-down space
access
Non Public-Non Collection Space 1,500 Number of Occupants TBD Visual Privacy (full, partial, open) Zone Designation Zone D Room Height Do we need to accommodate survey LEED
Space 0 Base ACOUSTICS Equipment Hardware/STC Rating None NRC
ceiling
higher STC 50 0 Plug Loads Air Change/ HR Walls HVAC ENGINEERING
Temperature Lighting No Control ±2ºF 110v, 20a, 1ph Yes 0 Power No 0 Pressure (+/-) 78ºF Summer, 70ºF Winter Floor Operable Windows Separation/STC FURNITURE/EQUIPMENT Moveable Yes Fixed RT60 & Shaping 0 TBD
and
for EMT required.
NC Regurlarly Occupied
Absorptive finish on the
with an NRC of 0.70 or
CRITERIA
Central to Staff Amenities
Floor Level Do we need to accommodate survey Room
Open
Length, Width, Shape

This room data sheet is not comprehensive in nature. Information regarding specific room features may not have been available and was intentionally left blank.

Compliance with ADA/ABAAG (2004) citations is required for accessibility. SI also requires compliance with SI Accessibility Guidelines and the IBC. Comparisons should be made and the more stringent requirement followed for design purposes. See Accessibility Narrative for additional information.

Functional Description Space where lighting fixtures are tested, repaired and fitted with filters if necessary.

CRITICAL DIMENSIONS

Absorptive finish on the ceiling with an NRC of 0.70 or higher

Please refer to structural narrative for more information on structural requirements.

179 Room Data Sheets | FREELON BOND Infrastructure Only 0 Other Amenities Deionized Water Vacuum Yes Speakers OH Gr. 2, 130 SF/HD FIRE ALARM Smoke Detection Yes Wet Sprinkler Special Waste Dry Sprinkler Pre-Action Sprinkler No FIRE PROTECTION No Considerations for Water 0 No Floor Drains Floor Sink Grey/Blackwater Piping 0 No No No Protected Hot/Cold No No Recycled Water Supply (treated) 0 No Public Address Audio Compressed Air Audio Visual Requirements No Hot/Cold Water Task Light Yes No 0 Plant/Clean Steam No Acoustic Sensitivity NC 40 Vibration Sensitivity Special Equipment/Artifact Sensitivity PLUMBING Target Illuminance (IES 9th Edition) Daylight Sensor 30-100 FC Exhibit Light To Be Considered Power Density (AHSRAE 2004) 1.9 W/ft² Temperature Deviations (+/-) No No Process Water UPS Switched Receptacles Dimming To Be Considered Humidity 0 No Other Humidity Deviation (+/-) As required by load No No Outside Air Single/Multi-Level Switching 0 Emergency/Standby Power As required by code 30/85 Single Occupancy Sensor Special Exhaust Sub-metering & Feedback Displays Filtration (Pre/Final/Other) Voice/Data DATA/TELECOMMUNICATIONS Yes 0 SECURITY 0 5.0 kPa/8.9 kN Floor Loading/Point Loads DAYLIGHTING 0 0 Shading Considerations Top/Side Lighting None No STRUCTURAL 0 0 Refer to information indicated
Volume IV, Section E Full 0 Technical Comment: Lighting Workroom Assignable Square Feet (ASF) OFEO Space Dimensions 0 Organizational Unit Other Interior Glazing 0 Solid core wood or insulated metal with neoprene seals max 1/4" undercut Yes Yes 0 Ceiling CRITICAL FINISHES 0 0
in
ELECTRICAL ARCHITECTURAL
Zone Room ID D3.1 Room Name 0
Non Public-Non Collection Space 250 Number of Occupants NA Visual Privacy (full, partial, open) Zone Designation Zone D Room Height 0 LEED NC Regurlarly Occupied Space 0 Base ACOUSTICS Equipment Hardware/STC Rating None NRC
STC 50 0 Plug Loads Air Change/ HR Walls HVAC ENGINEERING
Temperature Lighting No Control ±2ºF 110v, 20a, 1ph Yes 0 Power No 0 Pressure (+/-) 78ºF Summer, 70ºF Winter Floor Operable Windows Separation/STC FURNITURE/EQUIPMENT Moveable Yes Fixed RT60 & Shaping 0 TBD
CRITERIA
Lighting
Floor Level 0 Room Length,
Open
Electrical Storage, Workshops SUSTAINABILITY FEATURES Adjacencies Accessibility Requirement:
Width, Shape
vs. Private

This room data sheet is not comprehensive in nature. Information regarding specific room features may not have been available and was intentionally left blank.

Accessibility Requirement:

Adjacencies

SUSTAINABILITY FEATURES

vs. Private

Separation/STC

Compliance with ADA/ABAAG (2004) citations is required for accessibility. SI also requires compliance with SI Accessibility Guidelines and the IBC. Comparisons should be made and the more stringent requirement followed for design purposes. See Accessibility Narrative for additional information.

Curatorial and Collection Spaces

CRITICAL DIMENSIONS

Length, Width, Shape

Absorptive finish on the ceiling with an NRC of 0.70 or higher

CRITERIA

Recommend Sink under Plumbing. Please refer to structural narrative for more information on structural requirements.

Smithsonian Institution National Museum of African American History and Culture 180 Infrastructure Only 0 Other Amenities Deionized Water Vacuum Yes Speakers OH Gr. 2, 130 SF/HD FIRE ALARM Smoke Detection Yes Wet Sprinkler Special Waste Dry Sprinkler Pre-Action Sprinkler No FIRE PROTECTION No Considerations for Water 0 No Floor Drains Floor Sink Grey/Blackwater Piping 0 No No No Protected Hot/Cold No No Recycled Water Supply (treated) 0 No Public Address Audio Compressed Air Audio Visual Requirements Yes Hot/Cold Water Task Light Yes No 0 Plant/Clean Steam No Acoustic Sensitivity NC 40 Vibration Sensitivity Special Equipment/Artifact Sensitivity PLUMBING Target Illuminance
9th Edition) Daylight Sensor 50-100 FC Exhibit Light To Be Considered Power Density (AHSRAE 2004) 1.1 W/ft² Temperature Deviations (+/-) No To Be Considered Process Water UPS Switched Receptacles Dimming To Be Considered Humidity 0 No Other Humidity Deviation (+/-) As required by load No No Outside Air Single/Multi-Level Switching 0 Emergency/Standby Power As required by code 30/85 Multi Occupancy Sensor Special Exhaust Sub-metering & Feedback Displays Filtration (Pre/Final/Other) Voice/Data DATA/TELECOMMUNICATIONS Yes 0 SECURITY 0 5.0 kPa/8.9 kN Floor Loading/Point Loads DAYLIGHTING 0 0 Shading Considerations Top/Side Lighting None No STRUCTURAL 0 0 Refer
Partial/Open 0 Technical Comment: Design/Graphics Studio Assignable Square Feet
OFEO Space Dimensions 0 Organizational Unit Other Interior Glazing 0 Solid core wood or insulated metal with neoprane strip seals max 1/4" undercut Yes Yes 0 Ceiling CRITICAL FINISHES 0 0
(IES
to information indicated in Volume IV, Section E
(ASF)
ELECTRICAL ARCHITECTURAL
Zone Room ID D3.2 Room Name 0
production space for in-house design
promotions, publications, exhibits
exhibit graphics, etc. Drafting and light tables, computer drafting
capabilities, color booth, printers
scanners etc., TBD. Non Public-Non Collection Space 500 Number of Occupants TBD Visual Privacy (full, partial, open) Zone Designation Zone D Room Height 0 LEED NC Regurlarly
0 Base ACOUSTICS Equipment Hardware/STC Rating None NRC
STC 50 0 Plug Loads Air Change/ HR Walls HVAC ENGINEERING
Temperature Lighting No Control ±2ºF 110v, 20a, 1ph Yes 0 Power No 0 Pressure (+/-) 78ºF Summer, 70ºF Winter Floor Operable Windows
Functional Description Studio and
of
and
(CAD)
and
Occupied Space
FURNITURE/EQUIPMENT Moveable Yes Fixed RT60 & Shaping 0 TBD
Floor Level 0 Room
Open

This room data sheet is not comprehensive in nature. Information regarding specific room features may not have been available and was intentionally left blank.

extractor fans needed.

Hazard Lighting recommended under Lighting Other. Please refer to structural narrative for more information on structural requirements.

to information indicated in Volume IV, Section E

181 Room Data Sheets | FREELON BOND Infrastructure Only 0 Other Amenities Deionized Water Vacuum Yes Speakers OH Gr. 2, 130 SF/HD FIRE ALARM Smoke Detection Yes Wet Sprinkler Special Waste Dry Sprinkler Pre-Action Sprinkler No FIRE PROTECTION No Considerations for Water 0 No Floor Drains Floor Sink Grey/Blackwater Piping 0 No No No Protected Hot/Cold Yes Yes Recycled Water Supply (treated) 0 Yes Public Address Audio Compressed Air Audio Visual Requirements Yes Hot/Cold Water Task Light Yes No 0 Plant/Clean Steam No Acoustic Sensitivity NC 40 Vibration Sensitivity Special Equipment/Artifact Sensitivity PLUMBING Target Illuminance (IES 9th Edition) Daylight Sensor 30-100 FC Exhibit Light To Be Considered Power Density (AHSRAE 2004) 1.9 W/Ft² Temperature Deviations (+/-) No No Process Water UPS Switched
Dimming To Be Considered Humidity 0 No Other Humidity Deviation (+/-) As required by load No No Outside Air Single/Multi-Level Switching 0 Emergency/Standby Power As required by code 30/85 Single Occupancy Sensor Special Exhaust Sub-metering & Feedback Displays Filtration (Pre/Final/Other) Voice/Data DATA/TELECOMMUNICATIONS Yes 0 SECURITY 0 7.5 kPa/26.7 kN Floor Loading/Point Loads DAYLIGHTING 0 0 Shading Considerations Top/Side Lighting None No STRUCTURAL 0 0
Full/Partial Dust
Receptacles
Refer
Workshop, Carpenter, Metals, Mountmaking Assignable Square Feet
OFEO Space Dimensions 0 Organizational Unit Other Interior Glazing 0 Solid core wood or insulated metal with neoprene strip seals max 1/4" undercut Yes Yes 0 Ceiling CRITICAL FINISHES 0 0
Technical Comment:
(ASF)
ELECTRICAL ARCHITECTURAL
Zone Room ID D3.3 Room Name 0
Description Full carpentry/metal shop mountmaking is also built here. Non Public-Non Collection Space 800 Number of Occupants TBD Visual Privacy (full, partial, open) Zone Designation Zone D Room Height 0 LEED NC Regurlarly Occupied Space 0 Base ACOUSTICS Equipment Hardware/STC Rating None NRC
higher STC 50 0 Plug Loads Air Change/ HR Walls HVAC ENGINEERING CRITERIA Temperature Lighting No Control ±2ºF 110v, 20a, 1ph Yes 0 Power No 0 Pressure (+/-) 78ºF Summer, 70ºF Winter Floor Operable Windows Separation/STC FURNITURE/EQUIPMENT Moveable Yes Fixed RT60 & Shaping 0 TBD Compliance
ADA/ABAAG
All Workshops
Floor Level 0 Room Length, Width,
Open vs.
Functional
Absorptive finish on the ceiling with an NRC of 0.70 or
under
(2004) is not required . See Accessibility Narrative for additional information.
SUSTAINABILITY FEATURES Adjacencies Accessibility Requirement:
Shape
Private CRITICAL DIMENSIONS

This room data sheet is not comprehensive in nature. Information regarding specific room features may not have been available and was intentionally left blank.

Recommend Hazard under Lighting Other. Recommend Sink under Plumbing. Please refer to structural narrative for more information on structural requirements. ELECTRICAL ARCHITECTURAL

Compliance with ADA/ABAAG (2004) citations is required for accessibility. SI also requires compliance with SI Accessibility Guidelines and the IBC. Comparisons should be made and the more stringent requirement followed for design purposes. See Accessibility Narrative for additional information.

with

Absorptive finish on the

CRITICAL DIMENSIONS

to information indicated in Volume IV, Section E

Smithsonian Institution National Museum of African American History and Culture 182 Infrastructure Only 0 Other Amenities Deionized Water Vacuum Yes Speakers OH Gr. 2, 130 SF/HD FIRE ALARM Smoke Detection Yes Wet Sprinkler Special Waste Dry Sprinkler Pre-Action Sprinkler No FIRE PROTECTION No Considerations for Water 0 No Floor Drains Floor Sink Grey/Blackwater Piping 0 No No No
Hot/Cold No No Recycled
0 No Public Address Audio
Air Audio Visual Requirements Yes Hot/Cold Water Task Light Yes No Spray Booth Plant/Clean Steam No Acoustic
NC 40 Vibration
PLUMBING Target
Daylight Sensor 30-100 FC Exhibit Light To Be Considered Power Density (AHSRAE 2004) 1.9 W/Ft² Temperature Deviations (+/-) No No Process Water UPS
Dimming To Be Considered Humidity 0 No Other Humidity Deviation (+/-) As required by load No No Outside Air Single/Multi-Level Switching 0 Emergency/Standby Power As required by code 30/85 Single
Sensor Special Exhaust Sub-metering & Feedback Displays Filtration
Voice/Data DATA/TELECOMMUNICATIONS Yes 0 SECURITY 0 5.0 kPa/8.9 kN Floor Loading/Point Loads DAYLIGHTING 0 0 Shading Considerations Top/Side Lighting None No STRUCTURAL 0 0
Full Spray
Workshop, Paint Assignable Square Feet
OFEO Space Dimensions 0 Organizational Unit Other Interior Glazing 0 Solid core wood or insulated metal with neoprene strip seals max 1/4" undercut Yes Yes 0 Ceiling CRITICAL FINISHES 0 0
Protected
Water Supply (treated)
Compressed
Sensitivity
Sensitivity Special Equipment/Artifact Sensitivity
Illuminance (IES 9th Edition)
Switched Receptacles
Occupancy
(Pre/Final/Other)
Refer
Booth
fume hood extractor (vented to outside) Technical Comment:
(ASF)
Zone Room ID D3.4 Room Name 0 Functional Description All painting activities take place here. Non Public-Non Collection Space 300 Number of Occupants TBD Visual Privacy (full, partial, open) Zone Designation Zone D Room Height 0 LEED NC Regurlarly Occupied Space 0 Base ACOUSTICS Equipment Hardware/STC Rating None NRC
STC 50 0 Plug Loads Air Change/ HR Walls HVAC ENGINEERING CRITERIA Temperature Lighting No Control ±2ºF 110v, 20a, 1ph Yes 0 Power No 0 Pressure (+/-) 78ºF Summer, 70ºF Winter Floor Operable Windows Separation/STC FURNITURE/EQUIPMENT Moveable Yes Fixed RT60 & Shaping 0 TBD
ceiling with an NRC of 0.70 or higher
All Workshops
Floor Level 0 Room
Open
SUSTAINABILITY FEATURES Adjacencies Accessibility Requirement:
Length, Width, Shape
vs. Private

This room data sheet is not comprehensive in nature. Information regarding specific room features may not have been available and was intentionally left

Accessibility Requirement:

Adjacencies

Compliance with ADA/ABAAG (2004) citations is required for accessibility. SI also requires compliance with SI Accessibility Guidelines and the IBC. Comparisons should be made and the more stringent requirement followed for design purposes. An accessible route including a minimum clear width of 36" (except through doors, which must be at least 32" clear) is required. Refer to ADA/ABAAG (2004) for specifications regarding clear floor spaces at desks, files and equipment for individuals using wheelchairs.See Accessibility Narrative for additional information. Staging and Workshop Areas

SUSTAINABILITY FEATURES

vs. Private

Please refer to structural narrative for more information on structural requirements.

CRITICAL DIMENSIONS

Length, Width, Shape

183 Room Data Sheets | FREELON BOND Infrastructure Only 0 Other Amenities Deionized Water Vacuum Yes Speakers OH 130 SF/HD FIRE ALARM Smoke Detection Yes Wet Sprinkler Special Waste Dry Sprinkler Pre-Action Sprinkler No FIRE PROTECTION No Considerations for Water 0 No Floor Drains Floor Sink Grey/Blackwater Piping 0 No No No Protected Hot/Cold No No Recycled Water Supply (treated) 0 No Public Address Audio Compressed Air Audio Visual Requirements No Hot/Cold Water Task Light No No 0 Plant/Clean Steam No Acoustic Sensitivity 0 Vibration Sensitivity Special Equipment/Artifact Sensitivity PLUMBING Target Illuminance (IES 9th Edition) Daylight Sensor 10 FC Exhibit Light No Power Density (AHSRAE 2004) 0.8 W/ft² Temperature Deviations (+/-) No No Process Water UPS Switched Receptacles Dimming To Be Considered Humidity 0 No Other Humidity Deviation (+/-) As required by load No No Outside Air Single/Multi-Level Switching 0 Emergency/Standby Power As required by code 30/85 Single Occupancy Sensor Special Exhaust Sub-metering & Feedback Displays Filtration (Pre/Final/Other) Voice/Data DATA/TELECOMMUNICATIONS 0 0 SECURITY 0 7.5 kPa/26.7 kN Floor Loading/Point Loads DAYLIGHTING 0 0 Shading Considerations Top/Side Lighting None No STRUCTURAL 0 0 Refer to information indicated in Volume IV, Section E Full 0 Technical Comment: Exhibit Case/Prop Storage Assignable Square Feet (ASF) OFEO Space Dimensions 0 Organizational Unit Other Interior Glazing 0 0 Yes Yes 0 Ceiling CRITICAL FINISHES 0 0
ELECTRICAL ARCHITECTURAL
Zone Room ID D3.5 Room Name 0 Functional Description Storage room for reused mounts, cases, and props not currently in the exhibits. Non Public-Non Collection Space 400 Number of Occupants NA Visual Privacy (full, partial, open) Zone Designation Zone D Room Height Min 12'-6" LEED NC Regurlarly
Space 0 Base ACOUSTICS Equipment Hardware/STC Rating None NRC0 0 Plug Loads Air Change/ HR Walls HVAC ENGINEERING CRITERIA Temperature Lighting No Control ±2ºF 110v,
1ph Yes 0 Power No 0 Pressure (+/-) 78ºF Summer, 70ºF Winter Floor Operable Windows
FURNITURE/EQUIPMENT Moveable Yes Fixed RT60 & Shaping 0 TBD
blank.
Occupied
20a,
Separation/STC
Floor Level 0 Room
Open

This room data sheet is not comprehensive in nature. Information regarding specific room features may not have been available and was intentionally left

Accessibility Requirement:

Adjacencies

SUSTAINABILITY FEATURES

Compliance with ADA/ABAAG (2004) citations is required for accessibility. SI also requires compliance with SI Accessibility Guidelines and the IBC. Comparisons should be made and the more stringent requirement followed for design purposes. An accessible route including a minimum clear width of 36" (except through doors, which must be at least 32" clear) is required. Refer to ADA/ABAAG (2004) for specifications regarding clear floor spaces at desks, files and equipment for individuals using wheelchairs.See Accessibility Narrative for additional information.

CRITICAL DIMENSIONS

Length, Width, Shape Open vs. Private

Please refer to structural narrative for more information on structural requirements.

Smithsonian Institution National Museum of African American History and Culture 184 Infrastructure Only 0 Other Amenities Deionized Water Vacuum Yes Speakers OH Gr. 2, 130 SF/HD FIRE ALARM Smoke Detection Yes Wet Sprinkler Special Waste Dry Sprinkler Pre-Action Sprinkler No FIRE PROTECTION No Considerations for Water 0 No Floor Drains Floor Sink Grey/Blackwater Piping 0 No No No Protected Hot/Cold No No Recycled Water Supply (treated) 0 No Public Address Audio Compressed Air Audio Visual Requirements No Hot/Cold Water Task Light No No 0 Plant/Clean Steam No Acoustic Sensitivity No Vibration Sensitivity Special Equipment/Artifact Sensitivity PLUMBING Target Illuminance (IES 9th Edition) Daylight Sensor 10 FC Exhibit Light No Power Density (AHSRAE 2004) 0.8 W/ft² Temperature Deviations (+/-) No No Process Water UPS Switched Receptacles Dimming To Be Considered Humidity 0 No Other Humidity Deviation (+/-) As required by load No No Outside Air Single/Multi-Level Switching 0 Emergency/Standby Power As required by code 30/85 Single Occupancy Sensor Special Exhaust Sub-metering & Feedback Displays Filtration (Pre/Final/Other) Voice/Data DATA/TELECOMMUNICATIONS 0 0 SECURITY 0 7.5 kPa/17.8 kN Floor Loading/Point Loads DAYLIGHTING 0 0 Shading Considerations Top/Side Lighting None No STRUCTURAL 0 0 Refer to information indicated in Volume IV, Section E 0 0 Technical Comment: Chair and Table Storage Assignable Square Feet (ASF) OFEO Space Dimensions 0 Organizational Unit Other Interior Glazing 0 0 Yes No 0 Ceiling CRITICAL FINISHES 0 0
ELECTRICAL ARCHITECTURAL
Zone Room ID D3.6 Room Name 0 Functional Description Storage for tables and chairs to be used for special events, such as a banquet. Non Public-Non Collection Space 600 Number of Occupants NA Visual Privacy (full, partial, open) Zone Designation Zone D Room Height 0 LEED NC Regurlarly
Space 0 Base ACOUSTICS Equipment Hardware/STC Rating None NRC0 0 Plug Loads Air Change/ HR Walls HVAC ENGINEERING CRITERIA Temperature Lighting No Control ±2ºF 110v,
1ph Yes 0 Power No 0 Pressure (+/-) 78ºF Summer, 70ºF Winter Floor Operable Windows
FURNITURE/EQUIPMENT Moveable Yes Fixed RT60 & Shaping 0 TBD
blank.
Occupied
20a,
Separation/STC
Floor Level 0 Room

This room data sheet is not comprehensive in nature. Information regarding specific room features may not have been available and was intentionally left

Accessibility Requirement:

Adjacencies

SUSTAINABILITY FEATURES

vs. Private

Compliance with ADA/ABAAG (2004) citations is required for accessibility. SI also requires compliance with SI Accessibility Guidelines and the IBC. Comparisons should be made and the more stringent requirement followed for design purposes. An accessible route including a minimum clear width of 36" (except through doors, which must be at least 32" clear) is required. Refer to ADA/ABAAG (2004) for specifications regarding clear floor spaces at desks, files and equipment for individuals using wheelchairs.See Accessibility Narrative for additional information.

Workshop

Please refer to structural narrative for more information on structural requirements.

CRITICAL DIMENSIONS

Width, Shape

185 Room Data Sheets | FREELON BOND Infrastructure Only 0 Other Amenities Deionized Water Vacuum Yes Speakers OH Gr. 2, 130 SF/HD FIRE ALARM Smoke Detection Yes Wet Sprinkler Special Waste Dry Sprinkler Pre-Action Sprinkler No FIRE PROTECTION No Considerations for Water 0 No Floor Drains Floor Sink Grey/Blackwater Piping 0 No No No Protected Hot/Cold No No Recycled Water Supply (treated) 0 No Public Address Audio Compressed Air Audio Visual Requirements No Hot/Cold Water Task Light No No 0 Plant/Clean Steam No Acoustic Sensitivity No Vibration Sensitivity Special Equipment/Artifact Sensitivity PLUMBING Target Illuminance (IES 9th Edition) Daylight Sensor 10 FC Exhibit Light No Power Density (AHSRAE 2004) 0.8 W/ft² Temperature Deviations (+/-) No No Process Water UPS Switched Receptacles Dimming To Be Considered Humidity 0 No Other Humidity Deviation (+/-) As required by load No No Outside Air Single/Multi-Level Switching 0 Emergency/Standby Power As required by code 30/85 Single Occupancy Sensor Special Exhaust Sub-metering & Feedback Displays Filtration (Pre/Final/Other) Voice/Data DATA/TELECOMMUNICATIONS 0 0 SECURITY 0 7.5 kPa/17.8 kN Floor Loading/Point Loads DAYLIGHTING 0 0 Shading Considerations Top/Side Lighting None No STRUCTURAL 0 0 Refer to information indicated in Volume IV, Section E Full 0 Technical Comment: Lighting Storage Assignable Square Feet (ASF) OFEO Space Dimensions 0 Organizational Unit Other Interior Glazing 0 0 Yes Yes 0 Ceiling CRITICAL FINISHES 0 0
ELECTRICAL ARCHITECTURAL
Zone Room ID D3.7 Room Name 0 Functional Description Storage for different types of lighting fixtures and bulbs. Non Public-Non Collection Space 300 Number of Occupants NA Visual Privacy (full, partial, open) Zone Designation Zone D Room Height 0 LEED
0 Base ACOUSTICS Equipment Hardware/STC Rating None NRC0 0 Plug Loads Air Change/ HR Walls HVAC ENGINEERING CRITERIA Temperature Lighting No Control ±2ºF 110v, 20a, 1ph Yes 0 Power No 0 Pressure (+/-) 78ºF Summer, 70ºF Winter Floor Operable Windows Separation/STC FURNITURE/EQUIPMENT Moveable Yes Fixed RT60 & Shaping 0 TBD
blank.
NC Regurlarly Occupied Space
Lighting
Floor Level 0 Room
Length,
Open

This room data sheet is not comprehensive in nature. Information regarding specific room features may not have been available and was intentionally left blank.

Accessibility Requirement: Floor Level

Adjacencies

SUSTAINABILITY FEATURES

Open vs. Private

& Shaping

Compliance with ADA/ABAAG (2004) citations is required for accessibility. SI also requires compliance with SI Accessibility Guidelines and the IBC. Comparisons should be made and the more stringent requirement followed for design purposes. An accessible route including a minimum clear width of 36" (except through doors, which must be at least 32" clear) is required. Refer to ADA/ABAAG (2004) for specifications regarding clear floor spaces at desks, files and equipment for individuals using wheelchairs.See Accessibility Narrative for additional information.

Non-Collections Shipping and Receiving

CRITICAL DIMENSIONS

Length, Width, Shape

CRITERIA

Refer to NFPA 30 under Fire Protection. Recommend an Emergency Shower under Plumbing. Please refer to structural narrative for more information on structural requirements.

Smithsonian Institution National Museum of African American History and Culture 186 Infrastructure Only 0 Other Amenities Deionized Water Vacuum Yes Speakers EH 130 SF/H FIRE ALARM Smoke Detection Yes Wet Sprinkler Special Waste Dry Sprinkler Pre-Action Sprinkler No FIRE PROTECTION Yes Considerations for Water 0 No Floor Drains Floor Sink Grey/Blackwater Piping 0 No No No Protected Hot/Cold No No Recycled Water Supply (treated) 0 Yes Public Address Audio Compressed Air Audio Visual Requirements Yes Hot/Cold Water Task Light No No 0 Plant/Clean Steam No Acoustic Sensitivity No Vibration Sensitivity Special Equipment/Artifact Sensitivity PLUMBING Target Illuminance (IES 9th Edition) Daylight Sensor 10 FC Exhibit Light No Power Density (AHSRAE 2004) 0.8 W/ft² Temperature Deviations (+/-) No No Process Water UPS Switched Receptacles Dimming To Be Considered Humidity 0 No Other Humidity Deviation (+/-) As required by load No No Outside Air Single/Multi-Level Switching 0 Emergency/Standby Power As required by code 30/85 Single Occupancy Sensor Special Exhaust Sub-metering & Feedback Displays Filtration (Pre/Final/Other) Voice/Data DATA/TELECOMMUNICATIONS 0 0 SECURITY 0 7.5 kPa/17.8 kN Floor Loading/Point Loads DAYLIGHTING 0 0 Shading Considerations Top/Side Lighting None No STRUCTURAL 0 0 Refer to information indicated in Volume IV, Section E Full 0 Technical Comment: Flammables Storage Assignable Square Feet (ASF) OFEO Space Dimensions 0 Organizational Unit Other Interior Glazing 0 0 Yes No 0 Ceiling CRITICAL FINISHES 0 0
ELECTRICAL ARCHITECTURAL
Zone Room ID D3.8 Room Name 0
Non Public-Non Collection Space 100 Number of Occupants NA Visual Privacy (full, partial, open) Zone Designation Zone D Room Height 0 LEED NC Regurlarly
Space 0 Base ACOUSTICS Equipment Hardware/STC Rating None NRC0 0 Plug Loads Air Change/ HR Walls HVAC ENGINEERING
Temperature Lighting No Control ±2ºF 110v, 20a, 1ph No 0 Power No 0 Pressure (+/-) 78ºF Summer, 70ºF Winter Floor Operable Windows
FURNITURE/EQUIPMENT Moveable Yes Fixed RT60
0 TBD
Functional Description Storage for flammable chemicals, these should be stored in a metal, lockable cabinet.
Occupied
Separation/STC
0
Room

This room data sheet is not comprehensive in nature. Information regarding specific room features may not have been available and was intentionally left

Accessibility Requirement:

Adjacencies

Compliance with ADA/ABAAG (2004) citations is required for accessibility. SI also requires compliance with SI Accessibility Guidelines and the IBC. Comparisons should be made and the more stringent requirement followed for design purposes. An accessible route including a minimum clear width of 36" (except through doors, which must be at least 32" clear) is required. Refer to ADA/ABAAG (2004) for specifications regarding clear floor spaces at desks, files and equipment for individuals using wheelchairs.See Accessibility Narrative for additional information.

Non-Collections Shipping and Receiving, Workshops

SUSTAINABILITY FEATURES

vs. Private

Please refer to structural narrative for more information on structural requirements.

CRITICAL DIMENSIONS

Length, Width, Shape

187 Room Data Sheets | FREELON BOND Infrastructure Only 0 Other Amenities Deionized Water Vacuum Yes Speakers OH Gr. 2, 130 SF/HD FIRE ALARM Smoke Detection Yes Wet Sprinkler Special Waste Dry Sprinkler Pre-Action Sprinkler No FIRE PROTECTION No Considerations for Water 0 No Floor Drains Floor Sink Grey/Blackwater Piping 0 No No No Protected Hot/Cold No No Recycled Water Supply (treated) 0 No Public Address Audio Compressed Air Audio Visual Requirements No Hot/Cold Water Task Light No No 0 Plant/Clean Steam No Acoustic Sensitivity No Vibration Sensitivity Special Equipment/Artifact Sensitivity PLUMBING Target Illuminance (IES 9th Edition) Daylight Sensor 10 FC Exhibit Light No Power Density (AHSRAE 2004) 0.8 W/ft² Temperature Deviations (+/-) No No Process Water UPS Switched Receptacles Dimming To Be Considered Humidity 0 No Other Humidity Deviation (+/-) As required by load No No Outside Air Single/Multi-Level Switching 0 Emergency/Standby Power As required by code 30/85 Single Occupancy Sensor Special Exhaust Sub-metering & Feedback Displays Filtration (Pre/Final/Other) Voice/Data DATA/TELECOMMUNICATIONS 0 0 SECURITY 0 7.5 kPa/17.8 kN Floor Loading/Point Loads DAYLIGHTING 0 0 Shading Considerations Top/Side Lighting None No STRUCTURAL 0 0 Refer to information indicated in Volume IV, Section E Full 0 Technical Comment: Supplies, Bulk Shop Assignable Square Feet (ASF) OFEO Space Dimensions 0 Organizational Unit Other Interior Glazing 0 0 Yes Yes 0 Ceiling CRITICAL FINISHES 0 0
ELECTRICAL ARCHITECTURAL
Zone Room ID D3.9 Room Name 0 Functional Description Storage for bulk supplies used in the Workshops (wood and metals). Non Public-Non Collection Space 300 Number of Occupants NA Visual Privacy (full, partial, open) Zone Designation Zone D Room Height 0 LEED NC Regurlarly Occupied Space 0 Base ACOUSTICS Equipment Hardware/STC Rating None NRC0 0 Plug Loads Air Change/ HR Walls HVAC ENGINEERING CRITERIA Temperature Lighting No Control ±2ºF 110v, 20a, 1ph Yes 0 Power No 0 Pressure (+/-) 78ºF Summer, 70ºF Winter Floor Operable Windows
FURNITURE/EQUIPMENT Moveable Yes Fixed RT60 & Shaping 0 TBD
blank.
Separation/STC
Floor Level 0 Room
Open

This room data sheet is not comprehensive in nature. Information

SUSTAINABILITY FEATURES

Compliance with ADA/ABAAG (2004) citations is required for accessibility. SI also requires compliance with SI Accessibility Guidelines and the IBC. Comparisons should be made and the more stringent requirement followed for design purposes. See Accessibility Narrative for additional information. Non-Collections Shipping and Receiving, Workshops

Please refer to structural narrative for more information on structural requirements.

Smithsonian Institution National Museum of African American History and Culture 188 Infrastructure Only 0 Other Amenities Deionized Water Vacuum Yes Speakers OH Gr. 2, 130 SF/HD FIRE ALARM Smoke Detection Yes Wet Sprinkler Special Waste Dry Sprinkler Pre-Action Sprinkler No FIRE PROTECTION No Considerations for Water 0 No Floor Drains Floor Sink Grey/Blackwater Piping 0 No No No Protected Hot/Cold No No Recycled Water Supply (treated) 0 No Public Address Audio Compressed Air Audio Visual Requirements No Hot/Cold Water Task Light No No 0 Plant/Clean Steam No Acoustic Sensitivity No Vibration Sensitivity Special Equipment/Artifact Sensitivity PLUMBING Target Illuminance (IES 9th Edition) Daylight Sensor 10 FC Exhibit Light No Power Density (AHSRAE 2004) 0.8 W/ft² Temperature Deviations (+/-) No No Process Water UPS Switched Receptacles Dimming To Be Considered Humidity 0 No Other Humidity Deviation (+/-) As required by load No No Outside Air Single/Multi-Level Switching 0 Emergency/Standby Power As required by code 30/85 Single Occupancy Sensor Special Exhaust Sub-metering & Feedback Displays Filtration (Pre/Final/Other) Voice/Data DATA/TELECOMMUNICATIONS 0 0 SECURITY 0 7.5 kPa/17.8 kN Floor Loading/Point Loads DAYLIGHTING 0 0 Shading Considerations Top/Side Lighting None No STRUCTURAL 0 0 Refer to information indicated in Volume IV, Section E Full 0 Technical Comment: Supplies, Tool Room Assignable Square Feet (ASF) OFEO Space Dimensions 0 Organizational Unit Other Interior Glazing 0 0 Yes Yes 0 Ceiling CRITICAL FINISHES 0 0
ELECTRICAL ARCHITECTURAL
regarding specific room features may not have been available and was intentionally left blank. Zone Room ID D3.10 Room Name 0 Functional Description Storage room for tools used in the Workshops. Non Public-Non Collection Space 300 Number of Occupants NA Visual Privacy (full, partial, open) Zone Designation Zone D Room Height 0 LEED NC Regurlarly Occupied Space 0 Base ACOUSTICS Equipment Hardware/STC Rating None NRC0 0 Plug Loads Air Change/ HR Walls HVAC ENGINEERING CRITERIA Temperature Lighting No Control ±2ºF 110v, 20a, 1ph Yes 0 Power No 0 Pressure (+/-) 78ºF Summer, 70ºF Winter Floor Operable Windows Separation/STC FURNITURE/EQUIPMENT Moveable Yes Fixed RT60 & Shaping 0 TBD
Adjacencies Accessibility Requirement: Floor Level 0 Room Length,
Open
Width, Shape
vs. Private
CRITICAL DIMENSIONS

This room data sheet is not comprehensive in nature. Information regarding specific room features may not have been available and was intentionally left blank.

Accessibility Requirement:

Adjacencies

Compliance with ADA/ABAAG (2004) citations is required for accessibility. SI also requires compliance with SI Accessibility Guidelines and the IBC. Comparisons should be made and the more stringent requirement followed for design purposes. See Accessibility Narrative for additional information. Education Program Spaces

SUSTAINABILITY FEATURES

vs. Private

Please refer to structural narrative for more information on structural requirements.

CRITICAL DIMENSIONS

Width, Shape

189 Room Data Sheets | FREELON BOND Infrastructure Only 0 Other Amenities Deionized Water Vacuum Yes Speakers OH Gr. 2, 130 SF/HD FIRE ALARM Smoke Detection Yes Wet Sprinkler Special Waste Dry Sprinkler Pre-Action Sprinkler No FIRE PROTECTION No Considerations for Water 0 No Floor Drains Floor Sink Grey/Blackwater Piping 0 No No No Protected Hot/Cold No No Recycled Water Supply (treated) 0 No Public Address Audio Compressed Air Audio Visual Requirements No Hot/Cold Water Task Light To Be Considered No 0 Plant/Clean Steam No Acoustic Sensitivity NC 35-40 Vibration Sensitivity Special Equipment/Artifact Sensitivity PLUMBING Target Illuminance (IES 9th Edition) Daylight Sensor 30 FC Exhibit Light To Be Considered Power Density (AHSRAE 2004) 1.3 W/ft² Temperature Deviations (+/-) No No Process Water UPS Switched Receptacles Dimming To Be Considered Humidity 0 No Other Humidity Deviation (+/-) As required by load No No Outside Air Single/Multi-Level Switching 0 Emergency/Standby Power As required by code 30/85 Single Occupancy Sensor Special Exhaust Sub-metering & Feedback Displays Filtration (Pre/Final/Other) Voice/Data DATA/TELECOMMUNICATIONS Yes 0 SECURITY 0 5.0 kPa/8.9 kN Floor Loading/Point Loads DAYLIGHTING 0 0 Shading Considerations Top/Side Lighting None No STRUCTURAL 0 0 Refer to information indicated in Volume IV, Section E Partial 0 Technical Comment: Education Prep Area Assignable Square Feet (ASF) OFEO Space Dimensions 0 Organizational Unit Other Interior Glazing 0 0 Yes Yes 0 Ceiling CRITICAL FINISHES 0 0
ELECTRICAL ARCHITECTURAL
Zone Room ID D3.11 Room Name 0
Non Public-Non Collection Space 400 Number of Occupants TBD Visual Privacy (full, partial, open) Zone Designation Zone D Room Height 0 LEED NC Regurlarly Occupied Space 0 Base ACOUSTICS Equipment Hardware/STC Rating None NRCSTC 45 0 Plug Loads Air Change/ HR Walls HVAC ENGINEERING
Temperature Lighting No Control ±2ºF 110v, 20a, 1ph Yes 0 Power No 0 Pressure (+/-) 78ºF Summer, 70ºF Winter Floor Operable Windows Separation/STC FURNITURE/EQUIPMENT Moveable Yes Fixed RT60 & Shaping 0 0
Functional Description Preparation for larger programs.
CRITERIA
Floor Level 0 Room
Open
Length,

This room data sheet is not comprehensive in nature. Information regarding specific

with ADA/ABAAG (2004) citations is required for accessibility. SI also requires compliance with SI Accessibility Guidelines and the IBC. Comparisons should be made and the more stringent requirement followed for design purposes. See Accessibility Narrative for additional information.

CRITICAL DIMENSIONS

Please refer to structural narrative for more information on structural requirements.

Smithsonian Institution National Museum of African American History and Culture 190 Infrastructure Only 0 Other Amenities Deionized Water Vacuum Yes Speakers OH Gr. 2, 130 SF/HD FIRE ALARM Smoke Detection Yes Wet Sprinkler Special Waste Dry Sprinkler Pre-Action Sprinkler No FIRE PROTECTION No Considerations for Water 0 No Floor Drains Floor Sink Grey/Blackwater Piping 0 No No No Protected Hot/Cold No No Recycled Water Supply (treated) 0 No Public Address Audio Compressed Air Audio Visual Requirements No Hot/Cold Water Task Light No No 0 Plant/Clean Steam No Acoustic Sensitivity No Vibration Sensitivity Special Equipment/Artifact Sensitivity PLUMBING Target Illuminance (IES 9th Edition) Daylight Sensor 10 FC Exhibit Light No Power Density (AHSRAE 2004) 0.8 W/ft² Temperature Deviations (+/-) No No Process Water UPS Switched Receptacles Dimming To Be Considered Humidity 0 No Other Humidity Deviation (+/-) As required by load No No Outside Air Single/Multi-Level Switching 0 Emergency/Standby Power As required by code 30/85 Single Occupancy Sensor Special Exhaust Sub-metering & Feedback Displays Filtration (Pre/Final/Other) Voice/Data DATA/TELECOMMUNICATIONS 0 0 SECURITY 0 5.0 kPa/8.9 kN Floor Loading/Point Loads DAYLIGHTING 0 0 Shading Considerations Top/Side Lighting None No STRUCTURAL 0 0 Refer to information indicated in Volume IV, Section E Full 0 Technical Comment: Education Program Storage Assignable Square Feet (ASF) OFEO Space Dimensions 0 Organizational Unit Other Interior Glazing 0 0 Yes Yes 0 Ceiling CRITICAL FINISHES 0 0
ELECTRICAL ARCHITECTURAL
room features may not have been available and was intentionally left blank. Zone Room ID D3.12 Room Name 0 Functional Description Storage for bins, carts, etc. Non Public-Non Collection Space 200 Number of Occupants NA Visual Privacy (full, partial, open) Zone Designation Zone D Room Height 0 LEED NC Regurlarly Occupied Space 0 Base ACOUSTICS Equipment Hardware/STC Rating None NRC0 0 Plug Loads Air Change/ HR Walls HVAC ENGINEERING CRITERIA Temperature Lighting No Control ±2ºF 110v, 20a, 1ph Yes 0 Power No 0 Pressure (+/-) 78ºF Summer, 70ºF Winter Floor Operable Windows Separation/STC FURNITURE/EQUIPMENT Moveable Yes Fixed RT60 & Shaping 0 TBD
Education
Compliance
Program Spaces
Accessibility Requirement: Floor Level 0 Room Length,
Open
SUSTAINABILITY FEATURES Adjacencies
Width, Shape
vs. Private

This room data sheet is not comprehensive in nature. Information regarding specific

Compliance with ADA/ABAAG (2004) citations is required for accessibility. SI also requires compliance with SI Accessibility Guidelines and the IBC. Comparisons should be made and the more stringent requirement followed for design purposes. See Accessibility Narrative for additional information.

CRITICAL DIMENSIONS

Please refer to structural narrative for more information on structural requirements.

191 Room Data Sheets | FREELON BOND Infrastructure Only 0 Other Amenities Deionized Water Vacuum Yes Speakers OH Gr. 2, 130 SF/HD FIRE ALARM Smoke Detection Yes Wet Sprinkler Special Waste Dry Sprinkler Pre-Action Sprinkler No FIRE PROTECTION No Considerations for Water 0 No Floor Drains Floor Sink Grey/Blackwater Piping 0 No No No Protected Hot/Cold No No Recycled Water Supply (treated) 0 No Public Address Audio Compressed Air Audio Visual Requirements No Hot/Cold Water Task Light No No 0 Plant/Clean Steam No Acoustic Sensitivity No Vibration Sensitivity Special Equipment/Artifact Sensitivity PLUMBING Target Illuminance (IES 9th Edition) Daylight Sensor 10 FC Exhibit Light No Power Density (AHSRAE 2004) 0.8 W/ft² Temperature Deviations (+/-) No No Process Water UPS Switched Receptacles Dimming To Be Considered Humidity 0 No Other Humidity Deviation (+/-) As required by load No No Outside Air Single/Multi-Level Switching 0 Emergency/Standby Power As required by code 30/85 Single Occupancy Sensor Special Exhaust Sub-metering & Feedback Displays Filtration (Pre/Final/Other) Voice/Data DATA/TELECOMMUNICATIONS Yes 0 SECURITY 0 7.5 kPa/17.8 kN Floor Loading/Point Loads DAYLIGHTING 0 0 Shading Considerations Top/Side Lighting None No STRUCTURAL 0 0 Refer to information indicated in Volume IV, Section E Full 0 Technical Comment: Educational Technologies Storage Assignable Square Feet (ASF) OFEO Space Dimensions 0 Organizational Unit Other Interior Glazing 0 0 Yes Yes 0 Ceiling CRITICAL FINISHES 0 0
ELECTRICAL ARCHITECTURAL
room features may not have been available and was intentionally left blank. Zone Room ID D3.13 Room Name 0 Functional Description Storage for educational materials, computer carts, some AV equipment, etc. Non Public-Non Collection Space 300 Number of Occupants NA Visual Privacy (full, partial, open) Zone Designation Zone D Room Height 0 LEED NC Regurlarly Occupied Space 0 Base ACOUSTICS Equipment Hardware/STC Rating None NRC0 0 Plug Loads Air Change/ HR Walls HVAC ENGINEERING CRITERIA Temperature Lighting No Control ±2ºF 110v, 20a, 1ph Yes 0 Power No 0 Pressure (+/-) 78ºF Summer, 70ºF Winter Floor Operable Windows Separation/STC FURNITURE/EQUIPMENT Moveable Yes Fixed RT60 & Shaping 0 TBD
Education
Program Spaces
Requirement: Floor Level 0 Room Length, Width, Shape Open
SUSTAINABILITY FEATURES Adjacencies Accessibility
vs. Private

This room data sheet is not comprehensive in nature. Information regarding specific room features may not have been available and was intentionally left blank.

Compliance with ADA/ABAAG (2004) citations is required for accessibility. SI also requires compliance with SI Accessibility Guidelines and the IBC. Comparisons should be made and the more stringent requirement followed for design purposes. See Accessibility Narrative for additional information.

Adjacencies

Auditorium/Theater SUSTAINABILITY FEATURES

Functional Description Performance area and wings where performers, stage sets, and props are kept during performances.

vs. Private

CRITICAL DIMENSIONS

Width, Shape

Optimized for a speech

Recommend deluge at proscenium under Fire Protection. Please refer to structural narrative for more information on structural requirements.

Illuminance (IES 9th Edition)

Density (AHSRAE 2004)

to information indicated in Volume IV, Section E

Smithsonian Institution National Museum of African American History and Culture 192 Infrastructure Only 0 Other Amenities Deionized Water Vacuum Yes Speakers OH Gr. 2, 130 SF/HD FIRE ALARM Smoke Detection Yes Wet Sprinkler Special Waste Dry Sprinkler Pre-Action Sprinkler No FIRE PROTECTION No Considerations for Water 0 No Floor Drains Floor Sink Grey/Blackwater Piping 0 No No No Protected Hot/Cold No No Recycled Water Supply
0 No Public Address Audio Compressed Air Audio Visual Requirements No Hot/Cold Water Task Light No To Be Considered 0 Plant/Clean Steam No Acoustic Sensitivity NC 25-30 Vibration Sensitivity Special Equipment/Artifact Sensitivity PLUMBING Target
Daylight
50-100 FC
No
Exempt Temperature Deviations (+/-) No Yes Process Water UPS Switched Receptacles Dimming No Humidity 0 Yes Other Humidity Deviation (+/-) As required by load No No Outside Air Single/Multi-Level Switching 0 Emergency/Standby Power As required by code 30/85 Multi Occupancy Sensor Special Exhaust Sub-metering & Feedback Displays Filtration (Pre/Final/Other) Voice/Data DATA/TELECOMMUNICATIONS Yes 0 SECURITY 0 7.5 kPa/17.8 kN Floor Loading/Point Loads DAYLIGHTING 0 0 Shading Considerations Top/Side Lighting Audio from auditorium for monitoring. Auditorium intercom. No STRUCTURAL 0 0 Refer
Full 0 Technical Comment: Theater Stage and Wings Assignable Square Feet
OFEO Space Dimensions 0 Organizational Unit Other Interior Glazing 0 Sound vestibules or appropriate sound rated doors Yes Yes 0 Ceiling CRITICAL FINISHES 0 0
(treated)
Sensor
Exhibit Light
Power
(ASF)
ELECTRICAL ARCHITECTURAL
Zone Room ID D3.14 Room Name 0
Non Public-Non Collection Space 1,500 Number of Occupants NA Visual Privacy (full, partial, open) Zone Designation Zone D Room Height 0 LEED NC Regurlarly Occupied Space 0 Base ACOUSTICS Equipment Hardware/STC Rating None
STC 58-60 0 Plug Loads Air Change/ HR Walls HVAC ENGINEERING CRITERIA Temperature Lighting No Control ±2ºF 110v, 20a, 1ph Yes 0 Power No 0 Pressure (+/-) 78ºF Summer, 70ºF Winter Floor Operable Windows Separation/STC FURNITURE/EQUIPMENT Moveable Yes Fixed RT60 & Shaping 0 TBD
NRC
Floor Level 0 Room
Open
Accessibility Requirement:
Length,

This

data sheet is not comprehensive in nature. Information regarding specific room features may not have been available and was intentionally left

vs. Private

FEATURES

Compliance with ADA/ABAAG (2004) citations is required for accessibility. SI also requires compliance with SI Accessibility Guidelines and the IBC. Comparisons should be made and the more stringent requirement followed for design purposes. See Accessibility Narrative for additional information.

Auditorium/Theater

Optimized for a speech

Please refer to structural narrative for more information on structural requirements.

CRITICAL DIMENSIONS

193 Room Data Sheets | FREELON BOND Infrastructure Only 0 Other Amenities Deionized Water Vacuum Yes Speakers OH Gr. 2, 130 SF/HD FIRE ALARM Smoke Detection Yes Wet Sprinkler Special Waste Dry Sprinkler Pre-Action Sprinkler No FIRE PROTECTION No Considerations for Water 0 No Floor Drains Floor Sink Grey/Blackwater Piping 0 No No No Protected Hot/Cold No No Recycled Water Supply (treated) 0 No Public Address Audio Compressed Air Audio Visual Requirements No Hot/Cold Water Task Light No No 0 Plant/Clean Steam No Acoustic Sensitivity NC 25-30 Vibration Sensitivity Special Equipment/Artifact Sensitivity PLUMBING Target Illuminance (IES 9th Edition) Daylight Sensor 10 FC Exhibit Light No Power Density (AHSRAE 2004) 0.6 W/ft² Temperature Deviations (+/-) No Yes Process Water UPS Switched Receptacles Dimming No Humidity 0 No Other Humidity Deviation (+/-) As required by load No No Outside Air Single/Multi-Level Switching 0 Emergency/Standby Power As required by code 30/85 Multi Occupancy Sensor Special Exhaust Sub-metering & Feedback Displays Filtration (Pre/Final/Other) Voice/Data DATA/TELECOMMUNICATIONS Yes 0 SECURITY 0 7.5 kPa/17.8 kN Floor Loading/Point Loads DAYLIGHTING 0 0 Shading Considerations Top/Side Lighting Audio from auditorium for monitoring. Auditorium intercom. No STRUCTURAL 0 0 Refer to information indicated in Volume IV, Section E Full 0 Technical Comment: Theater Backstage Assignable Square Feet (ASF) OFEO Space Dimensions 0 Organizational Unit Other Interior Glazing 0 Sound vestibules or appropriate sound rated doors Yes Yes 0 Ceiling CRITICAL FINISHES 0 0
ELECTRICAL ARCHITECTURAL
Zone Room ID D3.15 Room Name 0 Functional
Area for theater equipment
scrims, sets, etc.). Non Public-Non Collection Space 600 Number of Occupants NA Visual Privacy (full, partial, open) Zone Designation Zone D Room Height 0 LEED NC Regurlarly Occupied Space 0 Base ACOUSTICS Equipment Hardware/STC Rating None NRC
STC 58-60 0 Plug Loads Air Change/ HR Walls HVAC ENGINEERING
Temperature Lighting No Control ±2ºF 110v, 20a, 1ph Yes 0 Power No 0 Pressure (+/-) 78ºF Summer, 70ºF Winter Floor Operable Windows Separation/STC FURNITURE/EQUIPMENT Moveable Yes Fixed RT60 & Shaping 0 TBD
room
blank.
Description
(lights
CRITERIA
SUSTAINABILITY
Floor Level 0 Room Length,
Open
Adjacencies Accessibility Requirement:
Width, Shape

This room data sheet is not comprehensive in nature. Information regarding specific room features may not have been available and was intentionally left blank.

Accessibility Requirement:

Adjacencies

Compliance with ADA/ABAAG (2004) citations is required for accessibility. SI also requires compliance with SI Accessibility Guidelines and the IBC. Comparisons should be made and the more stringent requirement followed for design purposes. See Accessibility Narrative for additional information.

Auditorium/Theater, Stage, Theater Washrooms/ Showers

Description Dressing rooms with separate

SUSTAINABILITY FEATURES

vs. Private

CRITICAL DIMENSIONS

Length, Width, Shape

Recommend drinking fountain under Plumbing. Please refer to structural narrative for more information on structural requirements.

Smithsonian Institution National Museum of African American History and Culture 194 Infrastructure Only 0 Other Amenities Deionized Water Vacuum Yes Speakers OH Gr. 2, 130 SF/HD FIRE ALARM Smoke Detection Yes Wet Sprinkler Special Waste Dry Sprinkler Pre-Action Sprinkler No FIRE PROTECTION No Considerations for Water 0 No Floor Drains Floor Sink Grey/Blackwater Piping 0 No No No Protected Hot/Cold No No Recycled Water Supply (treated) 0 No Public Address Audio Compressed Air Audio Visual Requirements Yes Hot/Cold Water Task Light To Be Considered No 0 Plant/Clean Steam No Acoustic Sensitivity NC 35-40 Vibration Sensitivity Special Equipment/Artifact Sensitivity PLUMBING Target Illuminance (IES 9th Edition) Daylight Sensor 30 FC Exhibit Light No Power Density (AHSRAE 2004) 0.8 W/ft² Temperature Deviations (+/-) No To Be Considered Process Water UPS Switched Receptacles Dimming To Be Considered Humidity 0 No Other Humidity Deviation (+/-) As required by load No No Outside Air Single/Multi-Level Switching 0 Emergency/Standby Power As required by code 30/85 Multi Occupancy Sensor Special Exhaust Sub-metering & Feedback Displays Filtration (Pre/Final/Other) Voice/Data DATA/TELECOMMUNICATIONS Yes 0 SECURITY 0 5.0 kPa/8.9 kN Floor Loading/Point Loads DAYLIGHTING 0 0 Shading Considerations Top/Side Lighting Audio monitoring of on-stage performance. Audio intercom with related production spaces. No STRUCTURAL 0 0 Refer to information indicated
Volume IV, Section E Full 0 Technical Comment: Theater Dressing Rooms Assignable Square Feet (ASF) OFEO Space Dimensions 0 Organizational Unit Other Interior Glazing 0 0 Yes Yes 0 Ceiling CRITICAL FINISHES 0 0
in
ARCHITECTURAL
ELECTRICAL
Zone Room ID D3.16 Room Name 0
dressing/makeup areas
toilets,
Non Public-Non Collection Space 800 Number of Occupants TBD Visual Privacy (full, partial, open) Zone Designation Zone D Room Height 0 LEED NC
Space 0 Base ACOUSTICS Equipment Hardware/STC Rating None NRCSTC 45 0 Plug Loads Air Change/ HR Walls HVAC ENGINEERING CRITERIA Temperature Lighting No Control ±2ºF 110v, 20a, 1ph Yes 0 Power No 0 Pressure (+/-) 78ºF Summer, 70ºF Winter Floor Operable Windows Separation/STC FURNITURE/EQUIPMENT Moveable Yes Fixed RT60 & Shaping 0 TBD
Functional
for two persons and two eight person rooms with access to
lavatories, showers
Regurlarly Occupied
Floor Level 0 Room
Open

This room data sheet is not comprehensive in nature. Information regarding specific room features may not have been available and was intentionally left

Accessibility Requirement:

Adjacencies

SUSTAINABILITY FEATURES

Compliance with ADA/ABAAG (2004) citations is required for accessibility. SI also requires compliance with SI Accessibility Guidelines and the IBC. Comparisons should be made and the more stringent requirement followed for design purposes. See ADA/ABAAG (2004) Chapter 6 Plumbing Elements and Facilities. See Accessibility Narrative for additional information.

Auditorium/Theater,Theater Dressing Rooms

CRITICAL DIMENSIONS

Width, Shape

FURNITURE/EQUIPMENT

Recommend W&V and hose bibs under Plumbing. Please refer to structural narrative for more information on structural requirements.

195 Room Data Sheets | FREELON BOND Infrastructure Only 0 Other Amenities Deionized Water Vacuum Yes Speakers OH Gr. 2, 130 SF/HD FIRE ALARM Smoke Detection Yes Wet Sprinkler Special Waste Dry Sprinkler Pre-Action Sprinkler No FIRE PROTECTION No Considerations for Water 0 No Floor Drains Floor Sink Grey/Blackwater Piping 0 No No Rainwater Flush Protected Hot/Cold No No Recycled Water Supply (treated) 0 Yes Public Address Audio Compressed Air Audio Visual Requirements Yes Hot/Cold Water Task Light No No 0 Plant/Clean Steam No Acoustic Sensitivity NC 40 Vibration Sensitivity Special Equipment/Artifact Sensitivity PLUMBING Target Illuminance (IES 9th Edition) Daylight Sensor 5 FC Exhibit Light No Power Density (AHSRAE 2004) 0.9 W/ft² Temperature Deviations (+/-) No No Process Water UPS Switched Receptacles Dimming To Be Considered Humidity 0 No Other Humidity Deviation (+/-) As required by load No No Outside Air Single/Multi-Level Switching 0 Emergency/Standby Power As required by code 30/85 Single Occupancy Sensor Special Exhaust Sub-metering & Feedback Displays Filtration (Pre/Final/Other) Voice/Data DATA/TELECOMMUNICATIONS 0 0 SECURITY 0 5.0 kPa/8.9 kN Floor Loading/Point Loads DAYLIGHTING 0 0 Shading Considerations Top/Side Lighting 0 No STRUCTURAL 0 0 Refer to information indicated in Volume IV, Section E Full In Grossing Factor. Technical Comment: Theater Washrooms/ Showers Assignable Square Feet (ASF) OFEO Space Dimensions 0 Organizational Unit Other Interior Glazing Cleanable 0 No Yes Cleanable Ceiling CRITICAL FINISHES Cleanable 0
ELECTRICAL ARCHITECTURAL
Zone Room ID D3.17 Room Name 0 Functional Description 0 Non Public-Non Collection Space 600 Number of Occupants TBD Visual Privacy (full, partial, open) Zone Designation Zone D Room Height 0 LEED NC Regurlarly Occupied Space 0 Base ACOUSTICS Equipment Hardware/STC Rating None NRCSTC 55 0 Plug Loads Air Change/ HR Walls HVAC ENGINEERING CRITERIA Temperature Lighting No Control ±2ºF 110v, 20a, 1ph Yes 0 Power No Cleanable Pressure (+/-) 78ºF Summer, 70ºF Winter Floor Operable Windows
blank.
Separation/STC
Moveable Yes Fixed RT60 & Shaping 0 TBD
Floor Level 0 Room Length,
Open
vs. Private

This room data sheet is not comprehensive in nature. Information regarding specific room features may not have been available and was intentionally left

Compliance with ADA/ABAAG (2004) citations is required for accessibility. SI also requires compliance with SI Accessibility Guidelines and the IBC. Comparisons should be made and the more stringent requirement followed for design purposes. See Accessibility Narrative for additional information.

Auditorium/Theater, Stage

Please refer to structural narrative for more information on structural requirements.

CRITICAL DIMENSIONS

Width, Shape

Smithsonian Institution National Museum of African American History and Culture 196 Infrastructure Only 0 Other Amenities Deionized Water Vacuum Yes Speakers OH Gr. 2, 130 SF/HD FIRE ALARM Smoke Detection Yes Wet Sprinkler Special Waste Dry Sprinkler Pre-Action Sprinkler No FIRE PROTECTION No Considerations for Water 0 No Floor Drains Floor Sink Grey/Blackwater Piping 0 No No No Protected Hot/Cold No No Recycled Water Supply (treated) 0 No Public Address Audio Compressed Air Audio Visual Requirements No Hot/Cold Water Task Light No No 0 Plant/Clean Steam No Acoustic Sensitivity 0 Vibration Sensitivity Special Equipment/Artifact Sensitivity PLUMBING Target Illuminance (IES 9th Edition) Daylight Sensor 10 FC Exhibit Light No Power Density (AHSRAE 2004) 0.8 W/ft² Temperature Deviations (+/-) No No Process Water UPS Switched Receptacles Dimming To Be Considered Humidity 0 No Other Humidity Deviation (+/-) As required by load No No Outside Air Single/Multi-Level Switching 0 Emergency/Standby Power As required by code 30/85 Single Occupancy Sensor Special Exhaust Sub-metering & Feedback Displays Filtration (Pre/Final/Other) Voice/Data DATA/TELECOMMUNICATIONS 0 0 SECURITY 0 7.5 kPa/17.8 kN Floor Loading/Point Loads DAYLIGHTING 0 0 Shading Considerations Top/Side Lighting Audio from auditorium for monitoring. Auditorium intercom. No STRUCTURAL 0 0 Refer to information indicated in Volume IV, Section E Full 0 Technical Comment: Theater Storage Assignable Square Feet (ASF) OFEO Space Dimensions 0 Organizational Unit Other Interior Glazing 0 0 No Yes 0 Ceiling CRITICAL FINISHES 0 0
ELECTRICAL ARCHITECTURAL
blank. Zone Room ID D3.18 Room Name 0 Functional Description Storage area for theater equipment. Non Public-Non Collection Space 500 Number of Occupants NA Visual Privacy (full, partial, open) Zone Designation Zone D Room Height 0 LEED NC Regurlarly Occupied Space 0 Base ACOUSTICS Equipment Hardware/STC Rating None NRC0 0 Plug Loads Air Change/ HR Walls HVAC ENGINEERING CRITERIA Temperature Lighting No Control ±2ºF 110v, 20a, 1ph Yes 0 Power No 0 Pressure (+/-) 78ºF Summer, 70ºF Winter Floor Operable Windows Separation/STC FURNITURE/EQUIPMENT Moveable No Fixed RT60 & Shaping 0 TBD
Floor Level 0 Room Length,
Open
SUSTAINABILITY FEATURES Adjacencies Accessibility Requirement:
vs. Private

This room data sheet is not comprehensive in nature. Information regarding specific room features may not have been available and was intentionally

Compliance with ADA/ABAAG (2004) citations is required for accessibility. SI also requires compliance with SI Accessibility Guidelines and the IBC. Comparisons should be made and the more stringent requirement followed for design purposes. See Accessibility Narrative for additional information.

Auditorium/Theater, Stage

Please refer to structural narrative for more information on structural requirements.

CRITICAL DIMENSIONS

Width, Shape

197 Room Data Sheets | FREELON BOND Infrastructure Only 0 Other Amenities Deionized Water Vacuum Yes Speakers OH Gr. 2, 130 SF/HD FIRE ALARM Smoke Detection Yes Wet Sprinkler Special Waste Dry Sprinkler Pre-Action Sprinkler No FIRE PROTECTION No Considerations for Water 0 No Floor Drains Floor Sink Grey/Blackwater Piping 0 No No No Protected Hot/Cold No No Recycled Water Supply (treated) 0 No Public Address Audio Compressed Air Audio Visual Requirements No Hot/Cold Water Task Light No No 0 Plant/Clean Steam No Acoustic Sensitivity No Vibration Sensitivity Special Equipment/Artifact Sensitivity PLUMBING Target Illuminance (IES 9th Edition) Daylight Sensor 10 FC Exhibit Light No Power Density (AHSRAE 2004) 0.8 W/ft² Temperature Deviations (+/-) No No Process Water UPS Switched Receptacles Dimming To Be Considered Humidity 0 No Other Humidity Deviation (+/-) As required by load No No Outside Air Single/Multi-Level Switching 0 Emergency/Standby Power As required by code 30/85 Single Occupancy Sensor Special Exhaust Sub-metering & Feedback Displays Filtration (Pre/Final/Other) Voice/Data DATA/TELECOMMUNICATIONS 0 0 SECURITY 0 7.5 kPa/17.8 kN Floor Loading/Point Loads DAYLIGHTING 0 0 Shading Considerations Top/Side Lighting 0 No STRUCTURAL 0 0 Refer to information indicated in Volume IV, Section E Full 0 Technical Comment: Piano/Instrument Storage Assignable Square Feet (ASF) OFEO Space Dimensions 0 Organizational Unit Other Interior Glazing 0 0 No Yes 0 Ceiling CRITICAL FINISHES 0 0
ELECTRICAL ARCHITECTURAL
blank. Zone Room ID D3.19 Room Name 0 Functional Description Storage for instruments belonging to the museum, can double as performer's instrument storage. Non Public-Non Collection Space 300 Number of Occupants NA Visual Privacy (full, partial, open) Zone Designation Zone D Room Height 0 LEED NC Regurlarly Occupied Space 0 Base ACOUSTICS Equipment Hardware/STC Rating None NRC0 0 Plug Loads Air Change/ HR Walls HVAC ENGINEERING CRITERIA Temperature Lighting Yes ±2ºF 110v, 20a, 1ph Yes 0 Power No 0 Pressure (+/-) 78ºF Summer, 71ºF Winter Floor Operable Windows Separation/STC FURNITURE/EQUIPMENT Moveable No Fixed RT60 & Shaping 0 Lower
left
SUSTAINABILITY FEATURES Adjacencies
Floor Level 0 Room Length,
Open
Accessibility Requirement:
vs. Private

This room data sheet is not comprehensive in nature. Information regarding specific room features may not have been available and was intentionally left blank.

Adjacencies

SUSTAINABILITY FEATURES

Compliance with ADA/ABAAG (2004) citations is required for accessibility. SI also requires compliance with SI Accessibility Guidelines and the IBC. Comparisons should be made and the more stringent requirement followed for design purposes. See Accessibility Narrative for additional information.

Auditorium/Theater

Please refer to structural narrative for more information on structural requirements.

CRITICAL DIMENSIONS

Width, Shape

Smithsonian Institution National Museum of African American History and Culture 198 Infrastructure Only 0 Other Amenities Deionized Water Vacuum Yes Speakers OH Gr. 2, 130 SF/HD FIRE ALARM Smoke Detection Yes Wet Sprinkler Special Waste Dry Sprinkler Pre-Action Sprinkler No FIRE PROTECTION No Considerations for Water 0 No Floor Drains Floor Sink Grey/Blackwater Piping 0 No No No Protected Hot/Cold No No Recycled Water Supply (treated) 0 No Public Address Audio Compressed Air Audio Visual Requirements No Hot/Cold Water Task Light Yes No 0 Plant/Clean Steam No Acoustic Sensitivity NC 35-40 Vibration Sensitivity Special Equipment/Artifact Sensitivity PLUMBING Target Illuminance (IES 9th Edition) Daylight Sensor 30 FC Exhibit Light No Power Density (AHSRAE 2004) 1.5 W/ft² Temperature Deviations (+/-) No No Process Water UPS Switched Receptacles Dimming No Humidity 0 No Other Humidity Deviation (+/-) As required by load No No Outside Air Single/Multi-Level Switching Yes Emergency/Standby Power As required by code 30/85 Single Occupancy Sensor Special Exhaust Sub-metering & Feedback Displays Filtration (Pre/Final/Other) Voice/Data DATA/TELECOMMUNICATIONS Yes 0 SECURITY 0 5.0 kPa/8.9 kN Floor Loading/Point Loads DAYLIGHTING 0 0 Shading Considerations Top/Side Lighting Equipment space for auditorium AV system. Auditorium intercom. No STRUCTURAL 0 0 Refer
Partial Window into
Technical Booth, Theater Assignable Square Feet (ASF) OFEO Space Dimensions 0 Organizational Unit Other Interior Glazing 0 Sound vestibules or appropriate sound rated doors Yes Yes 0 Ceiling CRITICAL FINISHES 0 0
to information indicated in Volume IV, Section E
theater provided. Technical Comment:
ELECTRICAL ARCHITECTURAL
Zone Room ID D3.20 Room Name 0
Acoustically
packs and sound/light
multimedia equipment racks.
control, sound,
light
Non Public-Non Collection Space 400 Number of Occupants NA Visual Privacy (full, partial, open) Zone Designation Zone D Room Height 0 LEED NC Regurlarly Occupied Space 0 Base ACOUSTICS Equipment Hardware/STC Rating None NRC Absorptive
higher STC 50 0 Plug Loads Air Change/ HR Walls HVAC ENGINEERING CRITERIA Temperature Lighting No Control ±2ºF 110v, 20a, 1ph Yes 0 Power No 0 Pressure (+/-) 78ºF Summer, 70ºF Winter Floor Operable Windows Separation/STC FURNITURE/EQUIPMENT Moveable Yes Fixed RT60 & Shaping 0 TBD
Functional Description
isolated, ventilated space for dimmer
and
Show
and
boards TBD.
finish on the ceiling with an NRC of 0.80 or
Floor Level 0 Room Length,
Open
Accessibility Requirement:
vs. Private

This room data sheet is not comprehensive in nature. Information regarding specific room features may not have been available and was intentionally left blank.

SUSTAINABILITY FEATURES Adjacencies Accessibility Requirement:

Compliance with ADA/ABAAG (2004) citations is required for accessibility. SI also requires compliance with SI Accessibility Guidelines and the IBC. Comparisons should be made and the more stringent requirement followed for design purposes. See Accessibility Narrative for additional information.

Auditorium/Theater

Please refer to structural narrative for more information on structural requirements.

CRITICAL DIMENSIONS

Width, Shape

indicated

199 Room Data Sheets | FREELON BOND Infrastructure Only 0 Other Amenities Deionized Water Vacuum Yes Speakers OH Gr. 2, 130 SF/HD FIRE ALARM Smoke Detection Yes Wet Sprinkler Special Waste Dry Sprinkler Pre-Action Sprinkler No FIRE PROTECTION No Considerations for Water 0 No Floor Drains Floor Sink Grey/Blackwater Piping 0 No No No Protected Hot/Cold No No Recycled Water Supply (treated) 0 No Public Address Audio Compressed Air Audio Visual Requirements No Hot/Cold Water Task Light Yes No 0 Plant/Clean Steam No Acoustic Sensitivity NC 35-40 Vibration Sensitivity Special Equipment/Artifact Sensitivity PLUMBING Target Illuminance (IES 9th Edition) Daylight Sensor 30 FC Exhibit Light No Power Density (AHSRAE 2004) 1.2 W/ft² Temperature Deviations (+/-) No No Process Water UPS Switched Receptacles Dimming No Humidity 0 No Other Humidity Deviation (+/-) As required by load No No Outside Air Single/Multi-Level Switching 0 Emergency/Standby Power As required by code 30/85 Single Occupancy Sensor Special Exhaust Sub-metering & Feedback Displays Filtration (Pre/Final/Other) Voice/Data DATA/TELECOMMUNICATIONS Yes 0 SECURITY 0 5.0 kPa/8.9 kN Floor Loading/Point Loads DAYLIGHTING 0 0 Shading Considerations Top/Side Lighting Control space for auditorium AV system - can be opened to audience space for direct listening to auditorium audio system. No STRUCTURAL 0 0 Refer
Volume IV, Section E Partial Room located
projection
Technical Comment: Projection/Audio Booth, Auditorium Assignable Square Feet (ASF) OFEO Space Dimensions 0 Organizational Unit Other Interior Glazing 0 Sound vestibules or appropriate sound rated doors Yes Yes 0 Ceiling CRITICAL FINISHES 0 0
to information
in
as required for optimum
and followspot angle.
ELECTRICAL ARCHITECTURAL
Zone Room ID D3.21 Room Name 0 Functional Description Auditorium's Sound and Projection control room. Non Public-Non Collection Space 400 Number of Occupants TBD Visual Privacy (full, partial, open) Zone Designation Zone D Room Height 0 LEED NC Regurlarly Occupied Space 0 Base ACOUSTICS Equipment Hardware/STC Rating None NRC
ceiling
0.80
higher STC 50 0 Plug Loads Air Change/ HR Walls HVAC ENGINEERING CRITERIA Temperature Lighting No Control ±2ºF 110v, 20a, 1ph Yes 0 Power No 0 Pressure (+/-) 78ºF Summer, 71ºF Winter Floor Operable Windows Separation/STC FURNITURE/EQUIPMENT Moveable Yes Fixed RT60 & Shaping 0 TBD
Absorptive finish on the
with an NRC of
or
Floor Level 0 Room
Open
Length,
vs. Private

This room data sheet is not comprehensive in nature. Information regarding specific room features may not have been available and was intentionally left blank.

Accessibility Requirement:

Adjacencies

SUSTAINABILITY FEATURES

vs. Private

Compliance with ADA/ABAAG (2004) citations is required for accessibility. SI also requires compliance with SI Accessibility Guidelines and the IBC. Comparisons should be made and the more stringent requirement followed for design purposes. See Accessibility Narrative for additional information.

Auditorium/Theater, Stage, Theater Dressing Rooms

CRITICAL DIMENSIONS

Length, Width, Shape

Absorptive finish on the ceiling with an NRC of 0.80 or higher

Recommend drinking fountain under Plumbing. Please refer to structural narrative for more information on structural requirements.

Smithsonian Institution National Museum of African American History and Culture 200 Infrastructure Only 0 Other Amenities Deionized Water Vacuum Yes Speakers OH Gr. 2, 130 SF/HD FIRE ALARM Smoke Detection Yes Wet Sprinkler Special Waste Dry Sprinkler Pre-Action Sprinkler No FIRE PROTECTION No Considerations for Water 0 No Floor Drains Floor Sink Grey/Blackwater Piping 0 No No No Protected Hot/Cold No No Recycled Water Supply (treated) 0 No Public Address Audio Compressed Air Audio Visual Requirements Yes Hot/Cold Water Task Light No No 0 Plant/Clean Steam No Acoustic Sensitivity NC 30-35 Vibration Sensitivity Special Equipment/Artifact Sensitivity PLUMBING Target Illuminance (IES 9th Edition) Daylight Sensor 30 FC Exhibit Light No Power Density (AHSRAE 2004) 1.2 W/ft² Temperature Deviations (+/-) No No Process Water UPS Switched Receptacles Dimming To Be Considered Humidity 0 No Other Humidity Deviation (+/-) As required by load No No Outside Air Single/Multi-Level Switching 0 Emergency/Standby Power As required by code 30/85 Single Occupancy Sensor Special Exhaust Sub-metering & Feedback Displays Filtration (Pre/Final/Other) Voice/Data DATA/TELECOMMUNICATIONS Yes 0 SECURITY 0 7.5 kPa/26.7 kN Floor Loading/Point Loads DAYLIGHTING 0 0 Shading Considerations Top/Side Lighting Audio from auditorium for monitoring. Auditorium intercom. No STRUCTURAL 0 0 Refer to information
E Full 0 Technical Comment: Green Room Assignable Square Feet (ASF) OFEO Space Dimensions 0 Organizational Unit Other Interior Glazing 0 Sound vestibules or appropriate sound rate doors Yes Yes 0 Ceiling CRITICAL FINISHES 0 0
indicated in Volume IV, Section
ELECTRICAL ARCHITECTURAL
Zone Room ID D3.22 Room Name 0 Functional
Non Public-Non Collection Space 400 Number of Occupants TBD Visual Privacy (full, partial, open) Zone Designation Zone D Room Height 0 LEED NC Regurlarly Occupied Space 0 Base ACOUSTICS Equipment Hardware/STC Rating None NRC
STC 50 0 Plug Loads Air Change/ HR Walls HVAC ENGINEERING CRITERIA Temperature Lighting No Control ±2ºF 110v, 20a, 1ph Yes 0 Power No 0 Pressure (+/-) 78ºF Summer, 70ºF Winter Floor Operable Windows Separation/STC FURNITURE/EQUIPMENT Moveable Yes Fixed RT60 & Shaping 0 TBD
Description Secure large room that serves as a waiting space for performers.
Floor Level 0 Room
Open

This room data sheet is not comprehensive in nature. Information regarding specific room features may not have been available and was intentionally left blank.

Accessibility Requirement:

Adjacencies

Technical Comment:

Compliance with ADA/ABAAG (2004) citations is required for accessibility. SI also requires compliance with SI Accessibility Guidelines and the IBC. Comparisons should be made and the more stringent requirement followed for design purposes. See Accessibility Narrative for additional information.

Auditorium/Theater, Stage

Projectors, computer workstations, microphones, and sound mixing console.

SUSTAINABILITY FEATURES

vs. Private

Please refer to structural narrative for more information on structural requirements.

CRITICAL DIMENSIONS

Width, Shape

to information indicated in Volume IV, Section

201 Room Data Sheets | FREELON BOND Infrastructure Only 0 Other Amenities Deionized Water Vacuum Yes Speakers OH Gr. 2, 130 SF/HD FIRE ALARM Smoke Detection Yes Wet Sprinkler Special Waste Dry Sprinkler Pre-Action Sprinkler No FIRE PROTECTION No Considerations for Water 0 No Floor Drains Floor Sink Grey/Blackwater Piping 0 No No No Protected Hot/Cold No No Recycled Water Supply (treated) 0 No Public Address Audio Compressed Air Audio Visual Requirements No Hot/Cold Water Task Light To Be Considered No 0 Plant/Clean Steam No Acoustic Sensitivity NC 30-35 Vibration Sensitivity Special Equipment/Artifact Sensitivity PLUMBING Target Illuminance (IES 9th Edition) Daylight Sensor 30 FC Exhibit Light No Power Density (AHSRAE 2004) 1.5 W/ft² Temperature Deviations (+/-) No No Process Water UPS Switched
Dimming To Be Considered Humidity 0 No Other Humidity Deviation (+/-) As required by load No No Outside Air Single/Multi-Level Switching 0 Emergency/Standby Power As required by code 30/85 Single Occupancy Sensor Special Exhaust Sub-metering & Feedback Displays Filtration (Pre/Final/Other) Voice/Data DATA/TELECOMMUNICATIONS Yes 0 SECURITY 0 5.0 kPa/8.9 kN Floor Loading/Point Loads DAYLIGHTING 0 0 Shading Considerations Top/Side Lighting Audio from auditorium for monitoring. Auditorium intercom. No STRUCTURAL 0 0
E Full
Receptacles
Refer
AV Workroom/Studio
OFEO Space Dimensions 0
Unit Other Interior Glazing 0 Sound vestibules
appropriate sound rated doors Yes Yes 0 Ceiling CRITICAL FINISHES 0 0
Assignable Square Feet (ASF)
Organizational
or
ELECTRICAL ARCHITECTURAL
Zone Room ID D3.23 Room Name 0
Description Space
room
Non Public-Non Collection Space 300 Number of Occupants TBD Visual Privacy (full, partial, open) Zone Designation Zone D Room Height 0 LEED NC
Space 0 Base ACOUSTICS Equipment Hardware/STC Rating None NRCSTC 50 0 Plug Loads Air Change/ HR Walls HVAC ENGINEERING CRITERIA Temperature Lighting No Control ±2ºF 110v, 20a, 1ph Yes 0 Power No 0 Pressure (+/-) 78ºF Summer, 70ºF Winter Floor Operable Windows Separation/STC FURNITURE/EQUIPMENT Moveable Yes Fixed RT60 & Shaping 0 TBD
Functional
for the development of Audio Visual presentations,
should have a measure of soundproofing and have a voice recording space for voice-over recording.
Regurlarly Occupied
Floor Level 0 Room
Open
Length,

This room data sheet is not comprehensive in nature. Information regarding specific room

Compliance with ADA/ABAAG (2004) citations is required for accessibility. SI also requires compliance with SI Accessibility Guidelines and the IBC. Comparisons should be made and the more stringent requirement followed for design purposes. See Accessibility Narrative for additional information.

Auditorium/Theater

Please refer to structural narrative for more information on structural requirements.

CRITICAL DIMENSIONS

Smithsonian Institution National Museum of African American History and Culture 202 Infrastructure Only 0 Other Amenities Deionized Water Vacuum Yes Speakers OH Gr. 2, 130 SF/HD FIRE ALARM Smoke Detection Yes Wet Sprinkler Special Waste Dry Sprinkler Pre-Action Sprinkler No FIRE PROTECTION No Considerations for Water 0 No Floor Drains Floor Sink Grey/Blackwater Piping 0 No No No Protected Hot/Cold No No Recycled Water Supply (treated) 0 No Public Address Audio Compressed Air Audio Visual Requirements No Hot/Cold Water Task Light No No 0 Plant/Clean Steam No Acoustic Sensitivity No Vibration Sensitivity Special Equipment/Artifact Sensitivity PLUMBING Target Illuminance (IES 9th Edition) Daylight Sensor 10 FC Exhibit Light No Power Density (AHSRAE 2004) 0.8 W/ft² Temperature Deviations (+/-) No No Process Water UPS Switched Receptacles Dimming To Be Considered Humidity 0 No Other Humidity Deviation (+/-) As required by load No No Outside Air Single/Multi-Level Switching 0 Emergency/Standby Power As required by code 30/85 Single Occupancy Sensor Special Exhaust Sub-metering & Feedback Displays Filtration (Pre/Final/Other) Voice/Data DATA/TELECOMMUNICATIONS Yes 0 SECURITY 0 7.5 kPa/17.8 kN Floor Loading/Point Loads DAYLIGHTING 0 0 Shading Considerations Top/Side Lighting None No STRUCTURAL 0 0 Refer to information indicated in Volume IV, Section E Full 0 Technical Comment: AV Storage Assignable Square Feet (ASF) OFEO Space Dimensions 0 Organizational Unit Other Interior Glazing 0 0 Yes Yes 0 Ceiling CRITICAL FINISHES 0 0
ELECTRICAL ARCHITECTURAL
features may not have been available and was intentionally left blank. Zone Room ID D3.24 Room Name 0 Functional Description Storage of AV equipment on carts so they can be brought out to needed space. Non Public-Non Collection Space 300 Number of Occupants NA Visual Privacy (full, partial, open) Zone Designation Zone D Room Height 0 LEED NC Regurlarly Occupied Space 0 Base ACOUSTICS Equipment Hardware/STC Rating None NRC0 0 Plug Loads Air Change/ HR Walls HVAC ENGINEERING CRITERIA Temperature Lighting No Control ±2ºF 110v, 20a, 1ph Yes 0 Power No 0 Pressure (+/-) 78ºF Summer, 70ºF Winter Floor Operable Windows Separation/STC FURNITURE/EQUIPMENT Moveable Yes Fixed RT60 & Shaping 0 TBD
Accessibility Requirement: Floor Level 0 Room Length,
Open
SUSTAINABILITY FEATURES Adjacencies
Width, Shape
vs. Private

This room data sheet is not comprehensive in nature. Information regarding specific

SUSTAINABILITY FEATURES Adjacencies Accessibility Requirement:

Compliance with ADA/ABAAG (2004) citations is required for accessibility. SI also requires compliance with SI Accessibility Guidelines and the IBC. Comparisons should be made and the more stringent requirement followed for design purposes. See Accessibility Narrative for additional information.

Please refer to structural narrative for more information on structural requirements.

CRITICAL DIMENSIONS

203 Room Data Sheets | FREELON BOND Infrastructure Only 0 Other Amenities Deionized Water Vacuum Yes Speakers OH Gr. 2, 130 SF/HD FIRE ALARM Smoke Detection Yes Wet Sprinkler Special Waste Dry Sprinkler Pre-Action Sprinkler No FIRE PROTECTION No Considerations for Water 0 No Floor Drains Floor Sink Grey/Blackwater Piping 0 No No No Protected Hot/Cold No No Recycled Water Supply (treated) 0 No Public Address Audio Compressed Air Audio Visual Requirements No Hot/Cold Water Task Light No No 0 Plant/Clean Steam No Acoustic Sensitivity No Vibration Sensitivity Special Equipment/Artifact Sensitivity PLUMBING Target Illuminance (IES 9th Edition) Daylight Sensor 10 FC Exhibit Light No Power Density (AHSRAE 2004) 0.8 W/ft² Temperature Deviations (+/-) No No Process Water UPS Switched Receptacles Dimming To Be Considered Humidity 0 No Other Humidity Deviation (+/-) As required by load No No Outside Air Single/Multi-Level Switching 0 Emergency/Standby Power As required by code 30/85 Single Occupancy Sensor Special Exhaust Sub-metering & Feedback Displays Filtration (Pre/Final/Other) Voice/Data DATA/TELECOMMUNICATIONS 0 0 SECURITY 0 7.5 kPa/17.8 kN Floor Loading/Point Loads DAYLIGHTING 0 0 Shading Considerations Top/Side Lighting None No STRUCTURAL 0 0 Refer to information indicated in Volume IV, Section E Full 0 Technical Comment: Special Event Storage Assignable Square Feet (ASF) OFEO Space Dimensions 0 Organizational Unit Other Interior Glazing 0 0 Yes Yes 0 Ceiling CRITICAL FINISHES 0 0
ELECTRICAL ARCHITECTURAL
room features may not have been available and was intentionally left blank. Zone Room ID D3.25 Room Name 0 Functional Description Storage space for chairs, tables, podium, stanchions, etc., used in all event rooms. Accessible to Lobby, event space. Non Public-Non Collection Space 600 Number of Occupants NA Visual Privacy (full, partial, open) Zone Designation Zone D Room Height 0 LEED NC Regurlarly Occupied Space 0 Base ACOUSTICS Equipment Hardware/STC Rating None NRC0 0 Plug Loads Air Change/ HR Walls HVAC ENGINEERING CRITERIA Temperature Lighting No Control ±2ºF 110v, 20a, 1ph Yes 0 Power No 0 Pressure (+/-) 78ºF Summer, 70ºF Winter Floor Operable Windows Separation/STC FURNITURE/EQUIPMENT Moveable Yes Fixed RT60 & Shaping 0 TBD
Event
Special
Room
Floor Level 0 Room Length,
Open
Width, Shape
vs. Private

This room data sheet is not comprehensive in nature. Information regarding specific room features may not have been available and was

Smithsonian Institution National Museum of African American History and Culture 204 Infrastructure Only 0 Other Amenities Deionized Water Vacuum Yes Speakers OH Gr. 2, 130 SF/HD FIRE ALARM Smoke Detection Yes Wet Sprinkler Special Waste Dry Sprinkler Pre-Action Sprinkler No FIRE PROTECTION 0 Considerations for Water 0 No Floor Drains Floor Sink Grey/Blackwater Piping 0 0 0 0 Protected Hot/Cold 0 0 Recycled Water Supply (treated) 0 0 Public Address Audio Compressed Air Audio Visual Requirements 0 Hot/Cold Water Task Light 0 0 0 Plant/Clean Steam 0 Acoustic Sensitivity 0 Vibration Sensitivity Special Equipment/Artifact Sensitivity PLUMBING Target Illuminance (IES 9th Edition) Daylight Sensor 0 Exhibit Light 0 Power Density (AHSRAE 2004) 0 Temperature Deviations (+/-) 0 0 Process Water UPS Switched Receptacles Dimming 0 Humidity 0 0 Other Humidity Deviation (+/-) 0 0 0 Outside Air Single/Multi-Level Switching 0 Emergency/Standby Power 0 0 0 Occupancy Sensor Special Exhaust Sub-metering & Feedback Displays Filtration (Pre/Final/Other) Voice/Data DATA/TELECOMMUNICATIONS Yes 0 SECURITY 0 5.0 kPa/8.9 kN Floor Loading/Point Loads DAYLIGHTING 0 0 Shading Considerations Top/Side Lighting Simultaneous Interpretation equipment and video monitoring. 0 STRUCTURAL 0 0 Refer to information indicated in Volume IV, Section E 0 Headphones and microphone at workstation overlooking both spaces. Technical Comment: Interpreter Booth Assignable Square Feet (ASF) OFEO Space Dimensions 0 Organizational Unit Other Interior Glazing 0 0 0 0 0 Ceiling CRITICAL FINISHES 0 0 0 ELECTRICAL ARCHITECTURAL
intentionally left blank. Zone Room ID D3.26 Room Name 0 Functional Description Soundproof booth for simultaneous interpretation of non-English speaking performances occuring in Theater or Auditorium. Non Public-Non Collection Space 100 Number of Occupants TBD Visual Privacy (full, partial, open) Zone Designation Zone D Room Height 0 LEED NC Regurlarly Occupied Space 0 Base ACOUSTICS Equipment Hardware/STC Rating 0 NRC0 0 Plug Loads Air Change/ HR Walls HVAC ENGINEERING CRITERIA Temperature Lighting 0 0 110v, 20a, 1ph 0 0 Power 0 0 Pressure (+/-) 0 Floor Operable Windows Separation/STC FURNITURE/EQUIPMENT Moveable 0 Fixed RT60 & Shaping 0 TBD Compliance under ADA/ABAAG (2004) is not required . See Accessibility Narrative for additional information.
Adjacencies Accessibility Requirement: Floor Level 0 Room Length, Width, Shape Open vs. Private
Auditorium/Theater SUSTAINABILITY FEATURES
CRITICAL DIMENSIONS

CRITICAL DIMENSIONS

Recommend Clean Agent System under Fire Protection. Please refer to structural narrative for more information on structural requirements.

205 Room Data Sheets | FREELON BOND Infrastructure Only 0 Other Amenities Deionized Water Vacuum Yes Speakers OH Gr. 2, 130 SF/HD FIRE ALARM Smoke Detection Yes Wet Sprinkler Special Waste Dry Sprinkler Pre-Action Sprinkler No FIRE PROTECTION No Considerations for Water 0 No Floor Drains Floor Sink Grey/Blackwater Piping 0 No No No Protected Hot/Cold No No Recycled Water Supply (treated) 0 No Public Address Audio Compressed Air Audio Visual Requirements No Hot/Cold Water Task Light To Be Considered No 0 Plant/Clean Steam No Acoustic Sensitivity No Vibration Sensitivity Special Equipment/Artifact Sensitivity PLUMBING Target Illuminance (IES 9th Edition) Daylight Sensor 30 FC Exhibit Light No Power Density (AHSRAE 2004) 1.5 W/ft² Temperature Deviations (+/-) No No Process Water UPS Switched Receptacles Dimming To Be Considered Humidity 0 Yes Other Humidity Deviation (+/-) As required by load No No Outside Air Single/Multi-Level Switching 0 Emergency/Standby Power As required by code 30/85 Single Occupancy Sensor Special Exhaust Sub-metering & Feedback Displays Filtration (Pre/Final/Other) Voice/Data DATA/TELECOMMUNICATIONS Yes 0 SECURITY 0 5.0 kPa/8.9 kN Floor Loading/Point Loads DAYLIGHTING 0 0 Shading Considerations Top/Side Lighting None No STRUCTURAL 0 0 Refer to information indicated in Volume IV, Section E Full Included in Grossing Factor. Technical Comment: IS Server Rooms Assignable Square Feet (ASF) OFEO Space Dimensions 0 Organizational Unit Other Interior Glazing 0 0 Yes Yes 0 Ceiling CRITICAL FINISHES 0 0
ELECTRICAL ARCHITECTURAL This room data sheet
comprehensive
nature. Information regarding specific room features may not have been available and was intentionally left blank. Zone Room ID D3.27 Room Name 0 Functional Description Utility closet for specialty equipment and services Non Public-Non Collection Space 0 Number of Occupants NA Visual Privacy (full, partial, open) Zone Designation Zone D Room Height 0 LEED NC Regurlarly Occupied Space 0 Base ACOUSTICS Equipment Hardware/STC Rating None NRCSTC 55 0 Plug Loads Air Change/ HR Walls HVAC ENGINEERING CRITERIA Temperature Lighting No Control ±2ºF 110v, 20a, 1ph Yes 0 Power Yes 0 Pressure (+/-) 78ºF Summer, 70ºF Winter Floor Operable Windows Separation/STC FURNITURE/EQUIPMENT Moveable Yes Fixed RT60 & Shaping 0 TBD Compliance
ADA/ABAAG
is not required per the exception at 203.5 Machinery Spaces.
Accessibility
information. Distributed
Adjacencies Accessibility Requirement: Floor Level 0 Room Length, Width, Shape Open vs. Private
is not
in
under
(2004)
See
Narrative for additional
SUSTAINABILITY FEATURES

This room data sheet is not comprehensive in nature. Information regarding specific room features may not have been available and was intentionally left

Accessibility Requirement:

SUSTAINABILITY FEATURES Adjacencies

CRITICAL DIMENSIONS

Recommend Clean Agent System under Fire Protection. Please refer to structural narrative for more information on structural requirements.

Smithsonian Institution National Museum of African American History and Culture 206 Infrastructure Only 0 Other Amenities Deionized Water Vacuum Yes Speakers OH Gr. 2, 130 SF/HD FIRE ALARM Smoke Detection Yes Wet Sprinkler Special Waste Dry Sprinkler Pre-Action Sprinkler No FIRE PROTECTION No Considerations for Water 0 No Floor Drains Floor Sink Grey/Blackwater Piping 0 No No No Protected Hot/Cold No No Recycled Water Supply (treated) 0 No Public Address Audio Compressed Air Audio Visual Requirements No Hot/Cold Water Task Light To Be Considered No 0 Plant/Clean Steam No Acoustic Sensitivity No Vibration Sensitivity Special Equipment/Artifact Sensitivity PLUMBING Target Illuminance (IES 9th Edition) Daylight Sensor 50 FC Exhibit Light No Power Density (AHSRAE 2004) 1.5 W/ft² Temperature Deviations (+/-) Yes No Process Water UPS Switched Receptacles Dimming To Be Considered Humidity 208v, 30a Yes Other Humidity Deviation (+/-) As required by load No No Outside Air Single/Multi-Level Switching 0 Emergency/Standby Power As required by code 30/85 Single Occupancy Sensor Special Exhaust Sub-metering & Feedback Displays Filtration (Pre/Final/Other) Voice/Data DATA/TELECOMMUNICATIONS Yes 0 SECURITY 0 5.0 kPa/8.9 kN Floor Loading/Point Loads DAYLIGHTING 0 0 Shading Considerations Top/Side Lighting None No STRUCTURAL 0 0 Refer
Full Included
Technical
IS Telephone Server Rooms Assignable Square Feet
OFEO Space Dimensions 0 Organizational Unit Other Interior Glazing 0 0 Yes Yes 0 Ceiling CRITICAL FINISHES 0 Positive
to information indicated in Volume IV, Section E
in Grossing Factor.
Comment:
(ASF)
ELECTRICAL ARCHITECTURAL
Zone Room ID D3.28 Room Name 0 Functional
closet for specialty equipment and services Non Public-Non Collection Space 0 Number of Occupants NA Visual Privacy (full, partial, open) Zone Designation Zone D Room Height 0 LEED NC Regurlarly Occupied Space 0 Base ACOUSTICS Equipment Hardware/STC Rating None NRCSTC 55 0 Plug Loads Air Change/ HR Walls HVAC ENGINEERING
Temperature Lighting 45%RH yr. rd. ±2ºF 110v, 20a, 1ph Yes 8% RH yr. rd. Power Yes 0 Pressure (+/-) 78ºF Summer, 70ºF Winter Floor Operable Windows Separation/STC FURNITURE/EQUIPMENT Moveable Yes Fixed RT60 & Shaping 0 TBD
Distributed
blank.
Description Utility
CRITERIA
Compliance under ADA/ABAAG (2004) is not required per the exception at 203.5 Machinery Spaces. See Accessibility Narrative for additional information.
Floor Level 0 Room Length,
Open
Width, Shape
vs. Private

This room data sheet

Please refer to structural narrative for more information on structural requirements.

CRITICAL DIMENSIONS

207 Room Data Sheets | FREELON BOND Infrastructure Only 0 Other Amenities Deionized Water Vacuum Yes Speakers OH Gr. 2, 130 SF/HD FIRE ALARM Smoke Detection Yes Wet Sprinkler Special Waste Dry Sprinkler Pre-Action Sprinkler No FIRE PROTECTION No Considerations for Water 0 No Floor Drains Floor Sink Grey/Blackwater Piping 0 No No No Protected Hot/Cold No No Recycled Water Supply (treated) 0 No Public Address Audio Compressed Air Audio Visual Requirements No Hot/Cold Water Task Light To Be Considered No 0 Plant/Clean Steam No Acoustic Sensitivity No Vibration Sensitivity Special Equipment/Artifact Sensitivity PLUMBING Target Illuminance (IES 9th Edition) Daylight Sensor 50 FC Exhibit Light No Power Density (AHSRAE 2004) 1.5 W/ft² Temperature Deviations (+/-) No No Process Water UPS Switched Receptacles Dimming To Be Considered Humidity 208v, 30a No Other Humidity Deviation (+/-) As required by load No No Outside Air Single/Multi-Level Switching 0 Emergency/Standby Power As required by code 30/85 Single Occupancy Sensor Special Exhaust Sub-metering & Feedback Displays Filtration (Pre/Final/Other) Voice/Data DATA/TELECOMMUNICATIONS Yes 0 SECURITY 0 5.0 kPa/8.9 kN Floor Loading/Point Loads DAYLIGHTING 0 0 Shading Considerations Top/Side Lighting None No STRUCTURAL 0 0 Refer to information indicated in Volume IV, Section E Full 0 Technical Comment: IS Communications Closets Assignable Square Feet (ASF) OFEO Space Dimensions 0 Organizational Unit Other Interior Glazing 0 0 Yes Yes 0 Ceiling CRITICAL FINISHES 0 NA
ELECTRICAL ARCHITECTURAL
is not comprehensive in nature. Information regarding specific room features may not have been available and was intentionally left blank. Zone Room ID D3.29 Room Name 0 Functional Description Utility closet for specialty equipment and services Non Public-Non Collection Space 0 Number of Occupants NA Visual Privacy (full, partial, open) Zone Designation Zone D Room Height 0 LEED NC Regurlarly Occupied Space 0 Base ACOUSTICS Equipment Hardware/STC Rating None NRCSTC 55 0 Plug Loads Air Change/ HR Walls HVAC ENGINEERING CRITERIA Temperature Lighting 45% RH yr. rd ±2ºF 110v, 20a, 1ph Yes 8% RH yr. rd. Power 0 0 Pressure (+/-) 78ºF Summer, 70ºF Winter Floor Operable Windows Separation/STC FURNITURE/EQUIPMENT Moveable Yes Fixed RT60 & Shaping 0 TBD Compliance under ADA/ABAAG
is not required per the exception at 203.5 Machinery Spaces. See Accessibility Narrative for additional information. Distributed
Requirement: Floor Level 0 Room Length, Width, Shape Open vs. Private
(2004)
SUSTAINABILITY FEATURES Adjacencies Accessibility

This room data sheet is not comprehensive

SUSTAINABILITY FEATURES

Please refer to structural narrative for more information on structural requirements.

CRITICAL DIMENSIONS

Smithsonian Institution National Museum of African American History and Culture 208 Infrastructure Only 0 Other Amenities Deionized Water Vacuum Yes Speakers OH Gr. 2, 130 SF/HD FIRE ALARM Smoke Detection Yes Wet Sprinkler Special Waste Dry Sprinkler Pre-Action Sprinkler No FIRE PROTECTION No Considerations for Water 0 No Floor Drains Floor Sink Grey/Blackwater Piping 0 No No No Protected Hot/Cold No No Recycled Water Supply (treated) 0 No Public Address Audio Compressed Air Audio Visual Requirements No Hot/Cold Water Task Light Yes No 0 Plant/Clean Steam No Acoustic Sensitivity NC 35-40 Vibration Sensitivity Special Equipment/Artifact Sensitivity PLUMBING Target Illuminance (IES 9th Edition) Daylight Sensor 30-100 FC Exhibit Light To Be Considered Power Density (AHSRAE 2004) 1.9 W/ft² Temperature Deviations (+/-) No No Process Water UPS Switched Receptacles Dimming No Humidity 0 Yes Other Humidity Deviation (+/-) As required by load No No Outside Air Single/Multi-Level Switching 0 Emergency/Standby Power As required by code 30/85 Single Occupancy Sensor Special Exhaust Sub-metering & Feedback Displays Filtration (Pre/Final/Other) Voice/Data DATA/TELECOMMUNICATIONS Yes 0 SECURITY 0 5.0 kPa/8.9 kN Floor Loading/Point Loads DAYLIGHTING 0 0 Shading Considerations Top/Side Lighting None No STRUCTURAL 0 0 Refer to information indicated in Volume IV, Section E Full 0 Technical Comment: IS Tech Shop Facility Assignable Square Feet (ASF) OFEO Space Dimensions 0 Organizational Unit Other Interior Glazing 0 0 Yes Yes 0 Ceiling CRITICAL FINISHES 0 0
ELECTRICAL ARCHITECTURAL
in nature. Information regarding specific room features may not have been available and was intentionally left blank. Zone Room ID D3.30 Room Name 0 Functional Description Secure workshop for repair of info services equipment, with metal racking and floor space to store equipment and tool carts. Non Public-Non Collection Space 300 Number of Occupants NA Visual Privacy (full, partial, open) Zone Designation Zone D Room Height 0 LEED NC Regurlarly Occupied Space 0 Base ACOUSTICS Equipment Hardware/STC Rating None NRC Absorptive finish on the ceiling with an NRC of 0.70 or higher STC 50 0 Plug Loads Air Change/ HR Walls HVAC ENGINEERING CRITERIA Temperature Lighting No Control ±2ºF 110v, 20a, 1ph Yes 0 Power Yes 0 Pressure (+/-) 78ºF Summer, 70ºF Winter Floor Operable Windows Separation/STC FURNITURE/EQUIPMENT Moveable Yes Fixed RT60 & Shaping 0 TBD Compliance under ADA/ABAAG (2004) is not required per the exception at 203.5 Machinery Spaces. See Accessibility Narrative for additional information. Distributed
Adjacencies Accessibility Requirement: Floor Level 0 Room Length, Width, Shape Open vs. Private

room data sheet is not comprehensive in nature. Information regarding

CRITICAL DIMENSIONS

209 Room Data Sheets | FREELON BOND Infrastructure Only 0 Other Amenities Deionized Water Vacuum Yes Speakers OH Gr. 2, 130 SF/HD FIRE ALARM Smoke Detection Yes Wet Sprinkler Special Waste Dry Sprinkler Pre-Action Sprinkler No FIRE PROTECTION No Considerations for Water 0 No Floor Drains Floor Sink Grey/Blackwater Piping 0 No No No Protected Hot/Cold No No Recycled Water Supply (treated) 0 No Public Address Audio Compressed Air Audio Visual Requirements No Hot/Cold Water Task Light No No 0 Plant/Clean Steam No Acoustic Sensitivity No Vibration Sensitivity Special Equipment/Artifact Sensitivity PLUMBING Target Illuminance (IES 9th Edition) Daylight Sensor 10 FC Exhibit Light No Power Density (AHSRAE 2004) 0.8 W/ft² Temperature Deviations (+/-) No No Process Water UPS Switched Receptacles Dimming To Be Considered Humidity 0 Yes Other Humidity Deviation (+/-) As required by load No No Outside Air Single/Multi-Level Switching 0 Emergency/Standby Power As required by code 30/85 Single Occupancy Sensor Special Exhaust Sub-metering & Feedback Displays Filtration (Pre/Final/Other) Voice/Data DATA/TELECOMMUNICATIONS Yes 0 SECURITY 0 7.5 k/PA/17.8 kN Floor Loading/Point Loads DAYLIGHTING 0 0 Shading Considerations Top/Side Lighting None No STRUCTURAL 0 0 Refer to information indicated in Volume IV, Section E Full 0 Technical Comment: IS Equipment Storage Assignable Square Feet (ASF) OFEO Space Dimensions 0 Organizational Unit Other Interior Glazing 0 0 Yes Yes 0 Ceiling CRITICAL FINISHES 0 0 Please
structural
ELECTRICAL ARCHITECTURAL This
specific room features may not have been available and was intentionally left blank. Zone Room ID D3.31 Room Name 0 Functional Description Secure utility storage area for info services equipment, with metal racking and floor space to store equipment carts. Non Public-Non Collection Space 300 Number of Occupants NA Visual Privacy (full, partial, open) Zone Designation Zone D Room Height 0 LEED NC Regurlarly Occupied Space 0 Base ACOUSTICS Equipment Hardware/STC Rating None NRC 0 STC 55 0 Plug Loads Air Change/ HR Walls HVAC ENGINEERING CRITERIA Temperature Lighting No Control ±2ºF 110v, 20a, 1ph Yes 0 Power Yes 0 Pressure (+/-) 78ºF Summer, 70ºF Winter Floor Operable Windows Separation/STC FURNITURE/EQUIPMENT Moveable Yes Fixed RT60 & Shaping 0 TBD Compliance under ADAAG is not required per the exception at 203.5 Machinery Spaces. See Accessibility Narrative for additional information. Distributed SUSTAINABILITY FEATURES Adjacencies Accessibility Requirement: Floor Level 0 Room Length, Width, Shape Open vs. Private
refer to structural narrative for more information on
requirements.

CRITICAL DIMENSIONS

Smithsonian Institution National Museum of African American History and Culture 210 Infrastructure Only 0 Other Amenities Deionized Water Vacuum Yes Speakers OH Gr. 2, 130 SF/HD FIRE ALARM Smoke Detection Yes Wet Sprinkler Special Waste Dry Sprinkler Pre-Action Sprinkler No FIRE PROTECTION 0 Considerations for Water 0 No Floor Drains Floor Sink Grey/Blackwater Piping 0 0 0 0 Protected Hot/Cold 0 0 Recycled Water Supply (treated) 0 0 Public Address Audio Compressed Air Audio Visual Requirements 0 Hot/Cold Water Task Light 0 0 0 Plant/Clean Steam 0 Acoustic Sensitivity 0 Vibration Sensitivity Special Equipment/Artifact Sensitivity PLUMBING Target Illuminance (IES 9th Edition) Daylight Sensor 0 Exhibit Light 0 Power Density (AHSRAE 2004) 0 Temperature Deviations (+/-) 0 0 Process Water UPS Switched Receptacles Dimming 0 Humidity 0 0 Other Humidity Deviation (+/-) 0 0 0 Outside Air Single/Multi-Level Switching 0 Emergency/Standby Power 0 0 0 Occupancy Sensor Special Exhaust Sub-metering & Feedback Displays Filtration (Pre/Final/Other) Voice/Data DATA/TELECOMMUNICATIONS Yes 0 SECURITY 0 0 Floor Loading/Point Loads DAYLIGHTING 0 0 Shading Considerations Top/Side Lighting 0 0 STRUCTURAL 0 0 Refer to information indicated in Volume IV, Section E 0 Included in Grossing Factor. Technical Comment: AV Closet/Room Assignable Square Feet (ASF) OFEO Space Dimensions 0 Organizational Unit Other Interior Glazing 0 0 0 0 0 Ceiling CRITICAL FINISHES 0 0 0 ELECTRICAL ARCHITECTURAL This room data sheet is not comprehensive in nature. Information regarding specific room features may not have been available and was intentionally left blank. Zone Room ID D3.32 Room Name 0 Functional Description Utility closet for specialty equipment and services Non Public-Non Collection Space 0 Number of Occupants NA Visual Privacy (full, partial, open) Zone Designation Zone D Room Height 0 LEED NC Regurlarly Occupied Space 0 Base ACOUSTICS Equipment Hardware/STC Rating 0 NRC 0 0 0 Plug Loads Air Change/ HR Walls HVAC ENGINEERING CRITERIA Temperature Lighting 0 0 110v, 20a, 1ph 0 0 Power 0 0 Pressure (+/-) 0 Floor Operable Windows Separation/STC FURNITURE/EQUIPMENT Moveable 0 Fixed RT60 & Shaping 0 TBD Compliance under ADAAG is not required per the exception at 203.5 Machinery Spaces. See Accessibility Narrative for additional information. Distributed SUSTAINABILITY FEATURES Adjacencies Accessibility Requirement: Floor Level 0 Room Length, Width, Shape Open vs. Private

(2004) citations is

for

Guidelines and the IBC. Comparisons should be made and the more stringent requirement followed for design purposes. See Accessibility Narrative for additional information.

211 Room Data Sheets | FREELON BOND Infrastructure Only 0 Other Amenities Deionized Water Vacuum Yes Speakers OH Gr. 2, 130 SF/HD FIRE ALARM Smoke Detection Yes Wet Sprinkler Special Waste Dry Sprinkler Pre-Action Sprinkler No FIRE PROTECTION 0 Considerations for Water 0 No Floor Drains Floor Sink Grey/Blackwater Piping 0 0 0 0 Protected Hot/Cold 0 0 Recycled Water Supply (treated) 0 0 Public Address Audio Compressed Air Audio Visual Requirements 0 Hot/Cold Water Task Light 0 0 0 Plant/Clean Steam 0 Acoustic Sensitivity 0 Vibration Sensitivity Special Equipment/Artifact Sensitivity PLUMBING Target Illuminance (IES 9th Edition) Daylight Sensor 0 Exhibit Light 0 Power Density (AHSRAE 2004) 0 Temperature Deviations (+/-) 0 0 Process Water UPS Switched Receptacles Dimming 0 Humidity 0 0 Other Humidity Deviation (+/-) 0 0 0 Outside Air Single/Multi-Level Switching 0 Emergency/Standby Power 0 0 0 Occupancy Sensor Special Exhaust Sub-metering & Feedback Displays Filtration (Pre/Final/Other) Voice/Data DATA/TELECOMMUNICATIONS Yes 0 SECURITY 0 0 Floor Loading/Point Loads DAYLIGHTING 0 0 Shading Considerations Top/Side Lighting Location for head-end equipment for public address system. 0 STRUCTURAL 0 0 Refer to information indicated in Volume IV, Section E 0 Included in Grossing Factor. Technical Comment: Public Address System Room Assignable Square Feet (ASF) OFEO Space Dimensions 0 Organizational Unit Other Interior Glazing 0 0 0 0 0 Ceiling CRITICAL FINISHES 0 0 0 ELECTRICAL ARCHITECTURAL This
comprehensive
room
may
have been available
was intentionally left blank. Zone Room ID D3.33 Room Name 0 Functional Description Utility closet for specialty equipment and services Non Public-Non Collection Space 0 Number of Occupants NA Visual Privacy (full, partial, open) Zone Designation Zone D Room Height 0 LEED NC Regurlarly Occupied Space 0 Base ACOUSTICS Equipment Hardware/STC Rating 0 NRC 0 0 0 Plug Loads Air Change/ HR Walls HVAC ENGINEERING CRITERIA Temperature Lighting 0 0 110v, 20a, 1ph 0 0 Power 0 0 Pressure (+/-) 0 Floor Operable Windows Separation/STC FURNITURE/EQUIPMENT Moveable 0 Fixed RT60 & Shaping 0 TBD Compliance
required
accessibility.
Accessibility
Distributed SUSTAINABILITY
Adjacencies Accessibility Requirement: Floor Level 0 Room Length, Width, Shape Open
room data sheet is not
in nature. Information regarding specific
features
not
and
with ADA/ABAAG
SI also requires compliance with SI
FEATURES
vs. Private CRITICAL DIMENSIONS

This room data sheet is not comprehensive in nature. Information regarding specific room features may not have been available and was intentionally left blank.

Accessibility Requirement:

Adjacencies

SUSTAINABILITY FEATURES

vs. Private

Compliance with ADA/ABAAG (2004) citations is required for accessibility. SI also requires compliance with SI Accessibility Guidelines and the IBC. Comparisons should be made and the more stringent requirement followed for design purposes. An accessible route including a minimum clear width of 36" (except through doors, which must be at least 32" clear) is required. Refer to ADA/ABAAG (2004) for specifications regarding clear floor spaces at desks, files and equipment for individuals using wheelchairs.See Accessibility Narrative for additional information.

CRITICAL DIMENSIONS

Length, Width, Shape

Absorptive finish on the ceiling with an NRC of 0.70 or higher

Recommend W&V and gas under Plumbing. Please refer to structural narrative for more information on structural requirements.

Smithsonian Institution National Museum of African American History and Culture 212 Infrastructure Only 0 Other Amenities Deionized Water Vacuum Yes Speakers OH Gr. 2, 130 SF/HD FIRE ALARM Smoke Detection Yes Wet Sprinkler Special Waste Dry Sprinkler Pre-Action Sprinkler No FIRE PROTECTION Kitchen Waste Considerations for Water 0 No Floor Drains Floor Sink Grey/Blackwater Piping 0 Yes No Yes Protected Hot/Cold No No Recycled Water Supply (treated) 0 Yes Public Address Audio Compressed Air Audio Visual Requirements Yes Hot/Cold Water Task Light To Be Considered No 0 Plant/Clean Steam No Acoustic Sensitivity No Vibration Sensitivity Special Equipment/Artifact Sensitivity PLUMBING Target Illuminance (IES 9th Edition) Daylight Sensor 30 FC Exhibit Light To Be Considered Power Density (AHSRAE 2004) 1.2 W/ft² Temperature Deviations (+/-) No No Process Water UPS Switched Receptacles Dimming No Humidity 0 No Other Humidity Deviation (+/-) As required by load No No Outside Air Single/Multi-Level Switching 0 Emergency/Standby Power As required by code 30/85 Single Occupancy Sensor Special Exhaust Sub-metering & Feedback Displays Filtration (Pre/Final/Other) Voice/Data DATA/TELECOMMUNICATIONS 0 0 SECURITY 0 5.0 kPa/8.9 kN Floor Loading/Point Loads DAYLIGHTING 0 0 Shading Considerations Top/Side Lighting None No STRUCTURAL 0 0 Refer to information indicated in Volume IV, Section E 0 0 Technical Comment: Café Warming Kitchen Assignable Square Feet (ASF) OFEO Space Dimensions 0 Organizational Unit Other Interior Glazing 0 0 0 0 0 Ceiling CRITICAL FINISHES 0 0
ELECTRICAL ARCHITECTURAL
Zone Room ID D3.34 Room Name 0 Functional Description 0 Non Public-Non Collection Space 400 Number of Occupants TBD Visual Privacy (full, partial, open) Zone Designation Zone D Room Height 0 LEED NC Regurlarly Occupied Space 0 Base ACOUSTICS Equipment Hardware/STC Rating None NRC
0 0 Plug Loads Air Change/ HR Walls HVAC ENGINEERING
Temperature Lighting No Control ±2ºF 110v, 20a, 1ph Yes 0 Power No 0 Pressure (+/-) 78ºF Summer, 70ºF Winter Floor Operable Windows
CRITERIA
Moveable 0 Fixed RT60 & Shaping 0 TBD
Separation/STC FURNITURE/EQUIPMENT
Café
Floor Level 0 Room
Open

This room data sheet is not comprehensive in

Adjacencies

Compliance with ADA/ABAAG (2004) citations is required for accessibility. SI also requires compliance with SI Accessibility Guidelines and the IBC. Comparisons should be made and the more stringent requirement followed for design purposes. An accessible route including a minimum clear width of 36" (except through doors, which must be at least 32" clear) is required. Refer to ADA/ABAAG (2004) for specifications regarding clear floor spaces at desks, files and equipment for individuals using wheelchairs.See Accessibility Narrative for additional information. Food Services, link to Food Delivery area SUSTAINABILITY FEATURES

CRITICAL DIMENSIONS

Please refer to structural narrative for more information on structural requirements.

213 Room Data Sheets | FREELON BOND Infrastructure Only 0 Other Amenities Deionized Water Vacuum Yes Speakers OH Gr. 2, 130 SF/HD FIRE ALARM Smoke Detection Yes Wet Sprinkler Special Waste Dry Sprinkler Pre-Action Sprinkler No FIRE PROTECTION Kitchen Waste Considerations for Water 0 No Floor Drains Floor Sink Grey/Blackwater Piping 0 No No No Protected Hot/Cold No No Recycled Water Supply (treated) 0 Yes Public Address Audio Compressed Air Audio Visual Requirements No Hot/Cold Water Task Light No No 0 Plant/Clean Steam No Acoustic Sensitivity NC 40 Vibration Sensitivity Special Equipment/Artifact Sensitivity PLUMBING Target Illuminance (IES 9th Edition) Daylight Sensor 10 FC Exhibit Light No Power Density (AHSRAE 2004) 0.8 W/ft² Temperature Deviations (+/-) No No Process Water UPS Switched Receptacles Dimming To Be Considered Humidity 0 No Other Humidity Deviation (+/-) As required by load No No Outside Air Single/Multi-Level Switching 0 Emergency/Standby Power As required by code 30/85 Single Occupancy Sensor Special Exhaust Sub-metering & Feedback Displays Filtration (Pre/Final/Other) Voice/Data DATA/TELECOMMUNICATIONS 0 0 SECURITY 0 7.5 kPa/17.8 kN Floor Loading/Point Loads DAYLIGHTING 0 0 Shading Considerations Top/Side Lighting None No STRUCTURAL 0 0 Refer to information indicated in Volume IV, Section E Full 0 Technical Comment: Kitchen Food Storage Assignable Square Feet (ASF) OFEO Space Dimensions 0 Organizational Unit Other Interior Glazing Cleanable 0 Yes Yes Cleanable Ceiling CRITICAL FINISHES Cleanable 0
ELECTRICAL ARCHITECTURAL
nature. Information regarding specific room features may not have been available and was intentionally left blank. Zone Room ID D3.35 Room Name 0 Functional Description This is the central storage area for food, it is comprised of a walk-in fridge and freezer. It has access to other kitchens and Serveries via service
Non Public-Non Collection Space 500 Number of Occupants NA Visual Privacy (full, partial, open) Zone Designation Zone D Room Height 0 LEED NC Regurlarly Occupied Space 0 Base ACOUSTICS Equipment Hardware/STC Rating None NRCSTC 55 0 Plug Loads Air Change/ HR Walls HVAC ENGINEERING CRITERIA Temperature Lighting No Control ±2ºF 110v, 20a, 1ph Yes 0 Power No Cleanable Pressure (+/-) 78ºF Summer, 70ºF Winter Floor Operable Windows Separation/STC FURNITURE/EQUIPMENT Moveable Yes Fixed RT60 & Shaping 0 Lower
elevator.
Floor Level 0 Room Length, Width, Shape Open
Accessibility Requirement:
vs. Private

Compliance with ADA/ABAAG (2004) citations is required for accessibility. SI also requires compliance with SI Accessibility Guidelines and the IBC. Comparisons should be made and the more stringent requirement followed for design purposes. An accessible route including a minimum clear width of 36" (except through doors, which must be at least 32" clear) is required. Refer to ADA/ABAAG (2004) for specifications regarding clear floor spaces at desks, files and equipment for individuals using wheelchairs.See Accessibility Narrative for additional information. Food Services, link to Food Delivery area SUSTAINABILITY FEATURES

CRITICAL DIMENSIONS

Recommend W&V and gas under Plumbing. Please refer to structural narrative for more information on structural requirements.

Smithsonian Institution National Museum of African American History and Culture 214 Infrastructure Only 0 Other Amenities Deionized Water Vacuum Yes Speakers OH Gr. 2, 130 SF/HD FIRE ALARM Smoke Detection Yes Wet Sprinkler Special Waste Dry Sprinkler Pre-Action Sprinkler No FIRE PROTECTION Kitchen Waste Considerations for Water 0 No Floor Drains Floor Sink Grey/Blackwater Piping 0 Yes No Yes Protected Hot/Cold No No Recycled Water Supply (treated) 0 Yes Public Address Audio Compressed Air Audio Visual Requirements Yes Hot/Cold Water Task Light Yes No 0 Plant/Clean Steam No Acoustic Sensitivity NC 40 Vibration Sensitivity Special Equipment/Artifact Sensitivity PLUMBING Target Illuminance (IES 9th Edition) Daylight Sensor 30 FC Exhibit Light To Be Considered Power Density (AHSRAE 2004) 1.2 W/ft² Temperature Deviations (+/-) No Yes Process Water UPS Switched Receptacles Dimming No Humidity 0 Yes Other Humidity Deviation (+/-) As required by load No No Outside Air Single/Multi-Level Switching 0 Emergency/Standby Power As required by code 30/85 Single Occupancy Sensor Special Exhaust Sub-metering & Feedback Displays Filtration (Pre/Final/Other) Voice/Data DATA/TELECOMMUNICATIONS Yes 0 SECURITY 0 5.0 kPa/8.9 kN Floor Loading/Point Loads DAYLIGHTING 0 0 Shading Considerations Top/Side Lighting None No STRUCTURAL 0 0 Refer to information indicated in Volume IV, Section E Full 0 Technical Comment: Kitchen, Cafeteria Assignable Square Feet (ASF) OFEO Space Dimensions 0 Organizational Unit Other Interior Glazing Cleanable 0 Yes Yes Cleanable Ceiling CRITICAL FINISHES Cleanable 0
ELECTRICAL ARCHITECTURAL
blank. Zone Room ID D3.36 Room Name 0 Functional Description This kitchen serves the cafeteria by providing space to prepare and cook a range of foods, from light to full fare meals. Non Public-Non Collection Space 3,000 Number of Occupants TBD Visual Privacy (full, partial, open) Zone Designation Zone D Room Height 0 LEED NC Regurlarly Occupied Space 0 Base ACOUSTICS Equipment Hardware/STC Rating None NRC
finish on the ceiling with an NRC of 0.70 or higher STC 55 0 Plug Loads Air Change/ HR Walls HVAC ENGINEERING CRITERIA Temperature Lighting No Control ±2ºF 110v, 20a, 1ph Yes 0 Power No Cleanable Pressure (+/-) 78ºF Summer, 70ºF Winter Floor Operable Windows Separation/STC FURNITURE/EQUIPMENT Moveable Yes Fixed RT60 & Shaping 0 Lower
This room data sheet is not comprehensive in nature. Information regarding specific room features may not have been available and was intentionally left
Absorptive
Floor Level 0 Room Length, Width, Shape Open
Adjacencies Accessibility Requirement:
vs. Private

room

Accessibility Requirement:

Adjacencies

SUSTAINABILITY FEATURES

vs. Private

Compliance with ADA/ABAAG (2004) citations is required for accessibility. SI also requires compliance with SI Accessibility Guidelines and the IBC. Comparisons should be made and the more stringent requirement followed for design purposes. An accessible route including a minimum clear width of 36" (except through doors, which must be at least 32" clear) is required. Refer to ADA/ABAAG (2004) for specifications regarding clear floor spaces at desks, files and equipment for individuals using wheelchairs.See Accessibility Narrative for additional information. Food Services, link to Food Delivery area, Central Hall

CRITICAL DIMENSIONS

Length, Width, Shape

FURNITURE/EQUIPMENT

Recommend W&V under Plumbing. Please refer to structural narrative for more information on structural requirements.

215 Room Data Sheets | FREELON BOND Infrastructure Only 0 Other Amenities Deionized Water Vacuum Yes Speakers OH Gr. 2, 130 SF/HD FIRE ALARM Smoke Detection Yes Wet Sprinkler Special Waste Dry Sprinkler Pre-Action Sprinkler No FIRE PROTECTION Kitchen Waste Considerations for Water 0 No Floor Drains Floor Sink Grey/Blackwater Piping 0 0 No No Protected Hot/Cold No No Recycled Water Supply (treated) 0 Yes Public Address Audio Compressed Air Audio Visual Requirements Yes Hot/Cold Water Task Light No No 0 Plant/Clean Steam No Acoustic Sensitivity NC 40 Vibration Sensitivity Special Equipment/Artifact Sensitivity PLUMBING Target Illuminance (IES 9th Edition) Daylight Sensor 10 FC Exhibit Light No Power Density (AHSRAE 2004) 1.2 W/ft² Temperature Deviations (+/-) No No Process Water UPS Switched Receptacles Dimming No Humidity 0 No Other Humidity Deviation (+/-) As required by load No No Outside Air Single/Multi-Level Switching 0 Emergency/Standby Power As required by code 30/85 Single Occupancy Sensor Special Exhaust Sub-metering & Feedback Displays Filtration (Pre/Final/Other) Voice/Data DATA/TELECOMMUNICATIONS Yes 0 SECURITY 0 5.0 kPa/8.9 kN Floor Loading/Point Loads DAYLIGHTING 0 0 Shading Considerations Top/Side Lighting None No STRUCTURAL 0 0 Refer to information indicated in Volume IV, Section E Full 0 Technical Comment: Catering and Setup Area Assignable Square Feet (ASF) OFEO Space Dimensions 0 Organizational Unit Other Interior Glazing 0 0 Yes Yes Cleanable Ceiling CRITICAL FINISHES Cleanable 0
ELECTRICAL ARCHITECTURAL
nature.
available
left blank. Zone Room ID D3.37 Room Name 0 Functional Description This space provides the area for catering services to setup for banquets and large dinners to occur in the Central Hall. The food
Non Public-Non Collection Space 1,000 Number of Occupants TBD Visual Privacy (full, partial, open) Zone Designation Zone D Room Height 0 LEED NC Regurlarly Occupied Space 0 Base ACOUSTICS Equipment Hardware/STC Rating None NRC Absorptive finish on the ceiling with an NRC of 0.70 or higher STC 55 0 Plug Loads Air Change/ HR Walls HVAC ENGINEERING CRITERIA Temperature Lighting No Control ±2ºF 110v, 20a, 1ph Yes 0 Power No Cleanable Pressure (+/-) 78ºF Summer, 70ºF Winter Floor Operable Windows Separation/STC
This
data sheet is not comprehensive in
Information regarding specific room features may not have been
and was intentionally
from the Catering Warming Kitchen comes to this room to be assembled and brought out to banquet space.
Moveable Yes Fixed RT60 & Shaping 0 TBD
Floor Level 0 Room
Open

This room data sheet is not comprehensive in nature. Information regarding specific room features may not have been available and was intentionally left

Accessibility Requirement:

Adjacencies

SUSTAINABILITY FEATURES

Compliance with ADA/ABAAG (2004) citations is required for accessibility. SI also requires compliance with SI Accessibility Guidelines and the IBC. Comparisons should be made and the more stringent requirement followed for design purposes. An accessible route including a minimum clear width of 36" (except through doors, which must be at least 32" clear) is required. Refer to ADA/ABAAG (2004) for specifications regarding clear floor spaces at desks, files and equipment for individuals using wheelchairs.See Accessibility Narrative for additional information. Central Hall

CRITICAL DIMENSIONS

Length, Width, Shape Open vs. Private

Smithsonian Institution National Museum of African American History and Culture 216 Infrastructure Only 0 Other Amenities Deionized Water Vacuum Yes Speakers OH Gr. 2, 130 SF/HD FIRE ALARM Smoke Detection Yes Wet Sprinkler Special Waste Dry Sprinkler Pre-Action Sprinkler No FIRE PROTECTION 0 Considerations for Water 0 No Floor Drains Floor Sink Grey/Blackwater Piping 0 0 0 0 Protected Hot/Cold 0 0 Recycled Water Supply (treated) 0 0 Public Address Audio Compressed Air Audio Visual Requirements 0 Hot/Cold Water Task Light 0 0 0 Plant/Clean Steam 0 Acoustic Sensitivity 0 Vibration Sensitivity Special Equipment/Artifact Sensitivity PLUMBING Target Illuminance (IES 9th Edition) Daylight Sensor 0 Exhibit Light 0 Power Density (AHSRAE 2004) 0 Temperature Deviations (+/-) 0 0 Process Water UPS Switched Receptacles Dimming 0 Humidity 0 0 Other Humidity Deviation (+/-) 0 0 0 Outside Air Single/Multi-Level Switching 0 Emergency/Standby Power 0 0 0 Occupancy Sensor Special Exhaust Sub-metering & Feedback Displays Filtration (Pre/Final/Other) Voice/Data DATA/TELECOMMUNICATIONS 0 0 SECURITY 0 5.0 kPa/8.9 kN Floor Loading/Point Loads DAYLIGHTING 0 0 Shading Considerations Top/Side Lighting 0 0 STRUCTURAL 0 0 Refer to information indicated in Volume IV, Section E 0 0 Technical Comment: Catering Warming Kitchen Assignable Square Feet (ASF) OFEO Space Dimensions 0 Organizational Unit Other Interior Glazing 0 0 0 0 0 Ceiling CRITICAL FINISHES 0 0 0 ELECTRICAL ARCHITECTURAL
blank. Zone Room ID D3.38 Room Name 0 Functional
kitchen is where the catered food is kept warm or cooked before going out to the Set Up area to be plated. Non Public-Non Collection Space 500 Number of Occupants TBD Visual Privacy (full, partial, open) Zone Designation Zone D Room Height 0 LEED NC Regurlarly Occupied
0 Base ACOUSTICS Equipment Hardware/STC Rating 0 NRC0 0 Plug Loads Air Change/ HR Walls HVAC ENGINEERING CRITERIA Temperature Lighting 0 0 110v, 20a, 1ph 0 0 Power 0 0 Pressure (+/-) 0 Floor Operable Windows Separation/STC FURNITURE/EQUIPMENT Moveable 0 Fixed RT60 & Shaping 0 Lower
Description This
Space
Floor Level 0 Room

This room data sheet is not comprehensive in nature. Information regarding specific room features may not have been available and was intentionally left blank.

Accessibility Requirement: Floor Level

Adjacencies

SUSTAINABILITY FEATURES

Open vs. Private

NC Regurlarly Occupied Space

Compliance with ADA/ABAAG (2004) citations is required for accessibility. SI also requires compliance with SI Accessibility Guidelines and the IBC. Comparisons should be made and the more stringent requirement followed for design purposes. An accessible route including a minimum clear width of 36" (except through doors, which must be at least 32" clear) is required. Refer to ADA/ABAAG (2004) for specifications regarding clear floor spaces at desks, files and equipment for individuals using wheelchairs.See Accessibility Narrative for additional information. Food Services, link to Food Delivery area

CRITICAL DIMENSIONS

Room Length, Width, Shape

CRITERIA

Recommend Sink under Plumbing. Please refer to structural narrative for more information on structural requirements.

217 Room Data Sheets | FREELON BOND Infrastructure Only 0 Other Amenities Deionized Water Vacuum Yes Speakers OH Gr. 2, 130 SF/HD FIRE ALARM Smoke Detection Yes Wet Sprinkler Special Waste Dry Sprinkler Pre-Action Sprinkler No FIRE PROTECTION No Considerations for Water 0 No Floor Drains Floor Sink Grey/Blackwater Piping 0 No No No Protected Hot/Cold No No Recycled Water Supply (treated) 0 No Public Address Audio Compressed Air Audio Visual Requirements Yes Hot/Cold Water Task Light No No 0 Plant/Clean Steam No Acoustic Sensitivity No Vibration Sensitivity Special Equipment/Artifact Sensitivity PLUMBING Target Illuminance (IES 9th Edition) Daylight Sensor 0 Exhibit Light No Power Density (AHSRAE 2004) 0 Temperature Deviations (+/-) No No Process Water UPS Switched Receptacles Dimming Yes Humidity 0 No Other Humidity Deviation (+/-) As required by load No No Outside Air Single/Multi-Level Switching 0 Emergency/Standby Power As required by code 30/85 Yes Occupancy Sensor Special Exhaust Sub-metering & Feedback Displays Filtration (Pre/Final/Other) Voice/Data DATA/TELECOMMUNICATIONS 0 0 SECURITY 0 0 Floor Loading/Point Loads DAYLIGHTING 0 0 Shading Considerations Top/Side Lighting 0 0 STRUCTURAL 0 0 Refer to information indicated in Volume IV, Section E 0 0 Technical Comment: Pantry Assignable Square Feet (ASF) OFEO Space Dimensions 0 Organizational Unit Other Interior Glazing 0 0 0 0 0 Ceiling CRITICAL FINISHES 0 0
ELECTRICAL ARCHITECTURAL
Zone Room ID D3.39 Room Name 0 Functional Description This space is where dry goods are kept, it is a complement to the Food Storage area where cold food is kept. Non Public Non-Collection Space 100 Number of Occupants NA Visual Privacy (full, partial, open) Zone Designation Zone D Room Height 0
0 Base ACOUSTICS Equipment Hardware/STC Rating None NRC 0 0 0 Plug Loads Air Change/ HR Walls HVAC ENGINEERING
Temperature Lighting No Control ±2ºF 110v, 20a, 1ph Yes 0 Power No 0 Pressure (+/-) 78ºF Summer, 70ºF Winter Floor Operable Windows
FURNITURE/EQUIPMENT Moveable 0 Fixed RT60 & Shaping 0 0
LEED
Separation/STC
0

This room data sheet is not comprehensive in nature. Information regarding specific room features may not have been available and was intentionally left blank.

Accessibility Requirement:

SUSTAINABILITY FEATURES Adjacencies

Compliance with ADA/ABAAG (2004) citations is required for accessibility. SI also requires compliance with SI Accessibility Guidelines and the IBC. Comparisons should be made and the more stringent requirement followed for design purposes. An accessible route including a minimum clear width of 36" (except through doors, which must be at least 32" clear) is required. Refer to ADA/ABAAG (2004) for specifications regarding clear floor spaces at desks, files and equipment for individuals using wheelchairs.See Accessibility Narrative for additional information. Patron Lounge

Functional Description This Servery

CRITICAL DIMENSIONS

Length, Width, Shape Open vs. Private

Smithsonian Institution National Museum of African American History and Culture 218 Infrastructure Only 0 Other Amenities Deionized Water Vacuum Yes Speakers OH Gr. 2, 130 SF/HD FIRE ALARM Smoke Detection Yes Wet Sprinkler Special Waste Dry Sprinkler Pre-Action Sprinkler No FIRE PROTECTION 0 Considerations for Water 0 No Floor Drains Floor Sink Grey/Blackwater Piping 0 0 0 0 Protected Hot/Cold 0 0 Recycled Water Supply (treated) 0 0 Public Address Audio Compressed Air Audio Visual Requirements 0 Hot/Cold Water Task Light 0 0 0 Plant/Clean Steam 0 Acoustic Sensitivity 0 Vibration Sensitivity Special Equipment/Artifact Sensitivity PLUMBING Target Illuminance (IES 9th Edition) Daylight Sensor 0 Exhibit Light 0 Power Density (AHSRAE 2004) 0 Temperature Deviations (+/-) 0 0 Process Water UPS Switched Receptacles Dimming 0 Humidity 0 0 Other Humidity Deviation (+/-) 0 0 0 Outside Air Single/Multi-Level Switching 0 Emergency/Standby Power 0 0 0 Occupancy Sensor Special Exhaust Sub-metering & Feedback Displays Filtration (Pre/Final/Other) Voice/Data DATA/TELECOMMUNICATIONS 0 0 SECURITY 0 5.0 kPa/8.9 kN Floor Loading/Point Loads DAYLIGHTING 0 0 Shading Considerations Top/Side Lighting 0 0 STRUCTURAL 0 0 Refer to information indicated in Volume IV, Section E Partial 0 Technical Comment: Patron Lounge Servery Assignable Square Feet (ASF) OFEO Space Dimensions 0 Organizational Unit Other Interior Glazing 0 0 0 No 0 Ceiling CRITICAL FINISHES 0 0 0 ELECTRICAL ARCHITECTURAL
Zone Room ID D3.40 Room Name 0
serves the Patron Lounge, it provides light fare and beverages for patron events. Non Public-Non Collection Space 120 Number of Occupants TBD Visual Privacy (full, partial, open) Zone Designation Zone D Room Height 0 LEED NC Regurlarly Occupied Space 0 Base ACOUSTICS Equipment Hardware/STC Rating 0 NRC0 0 Plug Loads Air Change/ HR Walls HVAC ENGINEERING CRITERIA Temperature Lighting 0 0 110v, 20a, 1ph 0 0 Power 0 0 Pressure (+/-) 0 Floor Operable Windows Separation/STC FURNITURE/EQUIPMENT Moveable 0 Fixed RT60 & Shaping 0 Upper
0
Floor Level
Room

This room data sheet is not comprehensive in nature. Information regarding specific room features may not have been available and was intentionally left blank.

Accessibility Requirement: Floor Level

Adjacencies

Compliance with ADA/ABAAG (2004) citations is required for accessibility. SI also requires compliance with SI Accessibility Guidelines and the IBC. Comparisons should be made and the more stringent requirement followed for design purposes. An accessible route including a minimum clear width of 36" (except through doors, which must be at least 32" clear) is required. Refer to ADA/ABAAG (2004) for specifications regarding clear floor spaces at desks, files and equipment for individuals using wheelchairs.See Accessibility Narrative for additional information. Board Room

Functional Description This Servery

SUSTAINABILITY FEATURES

Open vs. Private

CRITICAL DIMENSIONS

Length, Width, Shape

219 Room Data Sheets | FREELON BOND Infrastructure Only 0 Other Amenities Deionized Water Vacuum Yes Speakers OH Gr. 2, 130 SF/HD FIRE ALARM Smoke Detection Yes Wet Sprinkler Special Waste Dry Sprinkler Pre-Action Sprinkler No FIRE PROTECTION 0 Considerations for Water 0 No Floor Drains Floor Sink Grey/Blackwater Piping 0 0 0 0 Protected Hot/Cold 0 0 Recycled Water Supply (treated) 0 0 Public Address Audio Compressed Air Audio Visual Requirements 0 Hot/Cold Water Task Light 0 0 0 Plant/Clean Steam 0 Acoustic Sensitivity 0 Vibration Sensitivity Special Equipment/Artifact Sensitivity PLUMBING Target Illuminance (IES 9th Edition) Daylight Sensor 0 Exhibit Light 0 Power Density (AHSRAE 2004) 0 Temperature Deviations (+/-) 0 0 Process Water UPS Switched Receptacles Dimming 0 Humidity 0 0 Other Humidity Deviation (+/-) 0 0 0 Outside Air Single/Multi-Level Switching 0 Emergency/Standby Power 0 0 0 Occupancy Sensor Special Exhaust Sub-metering & Feedback Displays Filtration (Pre/Final/Other) Voice/Data DATA/TELECOMMUNICATIONS 0 0 SECURITY 0 5.0 kPa/8.9 kN Floor Loading/Point Loads DAYLIGHTING 0 0 Shading Considerations Top/Side Lighting 0 0 STRUCTURAL 0 0 Refer to information indicated in Volume IV, Section E 0 0 Technical Comment: Board Room Servery Assignable Square Feet (ASF) OFEO Space Dimensions 0 Organizational Unit Other Interior Glazing 0 0 0 0 0 Ceiling CRITICAL FINISHES 0 0 0 ELECTRICAL ARCHITECTURAL
Zone Room ID D3.41 Room Name 0
light
Non Public-Non Collection Space 100 Number of Occupants TBD Visual Privacy (full, partial, open) Zone Designation Zone D Room Height 0 LEED NC Regurlarly Occupied Space 0 Base ACOUSTICS Equipment Hardware/STC Rating 0 NRC0 0 Plug Loads Air Change/ HR Walls HVAC ENGINEERING CRITERIA Temperature Lighting 0 0 110v, 20a, 1ph 0 0 Power 0 0 Pressure (+/-) 0 Floor Operable Windows Separation/STC FURNITURE/EQUIPMENT Moveable 0 Fixed RT60
0 Upper
serves the Boardroom, it provides
fare and beverages for boardroom meetings.
& Shaping
0
Room

This room data sheet is not comprehensive in nature. Information regarding specific room features may not have been available and was intentionally left

Accessibility Requirement:

Adjacencies

with ADA/ABAAG (2004) citations is required for accessibility. SI also requires compliance with SI Accessibility Guidelines and the IBC. Comparisons should be made and the more stringent requirement followed for design purposes. An accessible route including a minimum clear width of 36" (except through doors, which must be at least 32" clear) is required. Refer to ADA/ABAAG (2004) for specifications regarding clear floor spaces at desks, files and equipment for individuals using wheelchairs.See Accessibility Narrative for additional information.

Catering and Set-up Area

Functional Description Centralized Dish Washing Facility for the kitchens and serveries.

SUSTAINABILITY FEATURES

vs. Private

CRITICAL DIMENSIONS

Length, Width, Shape

Smithsonian Institution National Museum of African American History and Culture 220 Infrastructure Only 0 Other Amenities Deionized Water Vacuum Yes Speakers OH Gr. 2, 130 SF/HD FIRE ALARM Smoke Detection Yes Wet Sprinkler Special Waste Dry Sprinkler Pre-Action Sprinkler No FIRE PROTECTION 0 Considerations for Water 0 No Floor Drains Floor Sink Grey/Blackwater Piping 0 0 0 0 Protected Hot/Cold 0 0 Recycled Water Supply (treated) 0 0 Public Address Audio Compressed Air Audio Visual Requirements 0 Hot/Cold Water Task Light 0 0 0 Plant/Clean Steam 0 Acoustic Sensitivity 0 Vibration Sensitivity Special Equipment/Artifact Sensitivity PLUMBING Target Illuminance (IES 9th Edition) Daylight Sensor 0 Exhibit Light 0 Power Density (AHSRAE 2004) 0 Temperature Deviations (+/-) 0 0 Process Water UPS Switched Receptacles Dimming 0 Humidity 0 0 Other Humidity Deviation (+/-) 0 0 0 Outside Air Single/Multi-Level Switching 0 Emergency/Standby Power 0 0 0 Occupancy Sensor Special Exhaust Sub-metering & Feedback Displays Filtration (Pre/Final/Other) Voice/Data DATA/TELECOMMUNICATIONS 0 0 SECURITY 0 0 Floor Loading/Point Loads DAYLIGHTING 0 0 Shading Considerations Top/Side Lighting 0 0 STRUCTURAL 0 0 Refer to information indicated in Volume IV, Section E 0 0 Technical Comment: Dish Washing Assignable Square Feet (ASF) OFEO Space Dimensions 0 Organizational Unit Other Interior Glazing 0 0 0 0 0 Ceiling CRITICAL FINISHES 0 0 0 ELECTRICAL ARCHITECTURAL
Zone Room ID D3.42 Room Name 0
blank.
Non Public-Non Collection Space 1,200 Number of Occupants TBD Visual Privacy (full, partial, open) Zone Designation Zone D Room Height 0 LEED NC Regurlarly Occupied Space 0 Base ACOUSTICS Equipment Hardware/STC Rating 0 NRC 0 0 0 Plug Loads Air Change/ HR Walls HVAC ENGINEERING CRITERIA Temperature Lighting 0 0 110v, 20a, 1ph 0 0 Power 0 0 Pressure (+/-) 0 Floor Operable Windows
FURNITURE/EQUIPMENT Moveable 0 Fixed RT60 & Shaping 0 0
Separation/STC
Compliance
Floor Level 0 Room
Open

This room data sheet is not comprehensive in nature. Information regarding specific room features may not have been available and was intentionally left blank.

Accessibility Requirement:

Adjacencies

SUSTAINABILITY FEATURES

Compliance with ADA/ABAAG (2004) citations is required for accessibility. SI also requires compliance with SI Accessibility Guidelines and the IBC. Comparisons should be made and the more stringent requirement followed for design purposes. An accessible route including a minimum clear width of 36" (except through doors, which must be at least 32" clear) is required. Refer to ADA/ABAAG (2004) for specifications regarding clear floor spaces at desks, files and equipment for individuals using wheelchairs.See Accessibility Narrative for additional information.

CRITICAL DIMENSIONS

Length, Width, Shape Open vs. Private

CRITERIA

Please refer to structural narrative for more information on structural requirements.

221 Room Data Sheets | FREELON BOND Infrastructure Only 0 Other Amenities Deionized Water Vacuum Yes Speakers LH 225 SF/HD FIRE ALARM Smoke Detection Yes Wet Sprinkler Special Waste Dry Sprinkler Pre-Action Sprinkler No FIRE PROTECTION No Considerations for Water 0 No Floor Drains Floor Sink Grey/Blackwater Piping 0 No No No Protected Hot/Cold No No Recycled Water Supply (treated) 0 No Public Address Audio Compressed Air Audio Visual Requirements No Hot/Cold Water Task Light To Be Considered No 0 Plant/Clean Steam No Acoustic Sensitivity NC 30-35 Vibration Sensitivity Special Equipment/Artifact Sensitivity PLUMBING Target Illuminance (IES 9th Edition) Daylight Sensor 30-50 FC Exhibit Light To Be Considered Power Density (AHSRAE 2004) 1.3 W/ft² Temperature Deviations (+/-) No Yes Process Water UPS Switched Receptacles Dimming To Be Considered Humidity 0 No Other Humidity Deviation (+/-) As required by load No No Outside Air Single/Multi-Level Switching 0 Emergency/Standby Power As required by code 30/85 Single Occupancy Sensor Special Exhaust Sub-metering & Feedback Displays Filtration (Pre/Final/Other) Voice/Data DATA/TELECOMMUNICATIONS Yes 0 SECURITY 0 5.0 kPa/8.9 kN Floor Loading/Point Loads DAYLIGHTING 0 0 Shading Considerations Top/Side Lighting None No STRUCTURAL 0 0 Refer to information
E Partial 0 Technical Comment: Retail Dept Conference Assignable Square Feet (ASF) OFEO Space Dimensions 0 Organizational Unit Other Interior Glazing 0 Solid core wood or insulated metal with neoprene seals max 1/4" undercut Yes Yes 0 Ceiling CRITICAL FINISHES 0 0
indicated in Volume IV, Section
ELECTRICAL ARCHITECTURAL
Zone Room ID D3.43 Room Name 0 Functional
a small
by outside retailers and suppliers to demonstrate new products and point-
Non Public-Non Collection Space 120 Number of Occupants TBD Visual Privacy (full, partial, open) Zone Designation Zone D Room Height 0 LEED NC Regurlarly Occupied Space 0 Base ACOUSTICS Equipment Hardware/STC Rating None NRC Absorptive finish on the ceiling with an NRC of 0.80 or higher, absorptive finish on one wall from 3'-7' aff with an NRC 0.70 or higher STC 50 0 Plug Loads Air Change/ HR Walls HVAC ENGINEERING
Temperature Lighting No Control ±2ºF 110v, 20a, 1ph Yes 0 Power No 0 Pressure (+/-) 78ºF Summer, 70ºF Winter Floor Operable Windows Separation/STC FURNITURE/EQUIPMENT Moveable Yes Fixed RT60
1.0 s TBD
Description This is
conference room/office for the retail department, used
of-sale displays.
& Shaping
In
Retail Offices
Floor
0 Room
Level

This room data sheet is not comprehensive in nature. Information regarding specific room features may not have been available and was intentionally

Accessibility Requirement:

Adjacencies

SUSTAINABILITY FEATURES

Compliance with ADA/ABAAG (2004) citations is required for accessibility. SI also requires compliance with SI Accessibility Guidelines and the IBC. Comparisons should be made and the more stringent requirement followed for design purposes. An accessible route including a minimum clear width of 36" (except through doors, which must be at least 32" clear) is required. Refer to ADA/ABAAG (2004) for specifications regarding clear floor spaces at desks, files and equipment for individuals using wheelchairs.See Accessibility Narrative for additional information. In Retail Offices (confirm location adjacent to Retail Store)

CRITICAL DIMENSIONS

Length, Width, Shape Open vs. Private

Please refer to structural narrative for more information on structural requirements.

Smithsonian Institution National Museum of African American History and Culture 222 Infrastructure Only 0 Other Amenities Deionized Water Vacuum Yes Speakers OH 130 SF/HD FIRE ALARM Smoke Detection Yes Wet Sprinkler Special Waste Dry Sprinkler Pre-Action Sprinkler No FIRE PROTECTION No Considerations for Water 0 No Floor Drains Floor Sink Grey/Blackwater Piping 0 No No No Protected Hot/Cold No No Recycled Water Supply (treated) 0 No Public Address Audio Compressed Air Audio Visual Requirements No Hot/Cold Water Task Light No No 0 Plant/Clean Steam No Acoustic Sensitivity No Vibration Sensitivity Special Equipment/Artifact Sensitivity PLUMBING Target Illuminance (IES 9th Edition) Daylight Sensor 10 FC Exhibit Light No Power Density (AHSRAE 2004) 0.8 W/ft² Temperature Deviations (+/-) No No Process Water UPS Switched Receptacles Dimming To Be Considered Humidity 0 No Other Humidity Deviation (+/-) As required by load No No Outside Air Single/Multi-Level Switching 0 Emergency/Standby Power As required by code 30/85 Single Occupancy Sensor Special Exhaust Sub-metering & Feedback Displays Filtration (Pre/Final/Other) Voice/Data DATA/TELECOMMUNICATIONS 0 0 SECURITY 0 7.5 kPa/17.8 kN Floor Loading/Point Loads DAYLIGHTING 0 0 Shading Considerations Top/Side Lighting None No STRUCTURAL 0 0 Refer to information indicated in Volume IV, Section E Partial 0 Technical Comment: Retail Storage/Wrapping Assignable Square Feet (ASF) OFEO Space Dimensions 0 Organizational Unit Other Interior Glazing 0 0 Yes Yes 0 Ceiling CRITICAL FINISHES 0 0
ELECTRICAL ARCHITECTURAL
blank. Zone Room ID D3.44 Room Name 0 Functional Description This space is for retail and wrapping supplies storage. Non Public-Non Collection Space 200 Number of Occupants TBD Visual Privacy (full, partial, open) Zone Designation Zone D Room Height 0 LEED NC
Space 0 Base ACOUSTICS Equipment Hardware/STC Rating None NRC0 0 Plug Loads Air Change/ HR Walls HVAC ENGINEERING CRITERIA Temperature Lighting No Control ±2ºF 110v, 20a, 1ph Yes 0 Power No 0 Pressure (+/-) 78ºF Summer, 70ºF Winter Floor Operable Windows Separation/STC FURNITURE/EQUIPMENT Moveable Yes Fixed RT60 & Shaping 0 TBD
left
Regurlarly Occupied
Floor Level 0 Room

This

Accessibility Requirement:

Adjacencies

SUSTAINABILITY FEATURES

Compliance with ADA/ABAAG (2004) citations is required for accessibility. SI also requires compliance with SI Accessibility Guidelines and the IBC. Comparisons should be made and the more stringent requirement followed for design purposes. An accessible route including a minimum clear width of 36" (except through doors, which must be at least 32" clear) is required. Refer to ADA/ABAAG (2004) for specifications regarding clear floor spaces at desks, files and equipment for individuals using wheelchairs.See Accessibility Narrative for additional information.

Security, Employee/Visitor/ Package Entrance/ Control Room, Loading Dock, Non-Collections

both

and noncollections) there is an included washroom facility in the booth so the guard position can always supervise the docks.

CRITICAL DIMENSIONS

Length, Width, Shape Open vs. Private

Recommend W&V and drinking fountain under Plumbing. Please refer to structural narrative for more information on structural requirements.

223 Room Data Sheets | FREELON BOND Infrastructure Only 0 Other Amenities Deionized Water Vacuum Yes Speakers LH 225 SF/HD FIRE ALARM Smoke Detection Yes Wet Sprinkler Special Waste Dry Sprinkler Pre-Action Sprinkler No FIRE PROTECTION No Considerations for Water 0 No Floor Drains Floor Sink Grey/Blackwater Piping 0 No No Yes Protected Hot/Cold No No Recycled Water Supply (treated) 0 Yes Public Address Audio Compressed Air Audio Visual Requirements Yes Hot/Cold Water Task Light To Be Considered No 0 Plant/Clean Steam No Acoustic Sensitivity NC 40 Vibration Sensitivity Special Equipment/Artifact Sensitivity PLUMBING Target Illuminance (IES 9th Edition) Daylight Sensor 5 FC Exhibit Light No Power Density (AHSRAE 2004) 0.9 W/ft² Temperature Deviations (+/-) No No Process Water UPS Switched Receptacles Dimming To Be Considered Humidity 0 No Other Humidity Deviation (+/-) As required by load No No Outside Air Single/Multi-Level Switching 0 Emergency/Standby Power As required by code 30/85 Single Occupancy Sensor Special Exhaust Sub-metering & Feedback Displays Filtration (Pre/Final/Other) Voice/Data DATA/TELECOMMUNICATIONS Yes 0 SECURITY 0 5.0 kPa/8.9 kN Floor Loading/Point Loads DAYLIGHTING 0 0 Shading Considerations Top/Side Lighting None No STRUCTURAL 0 0 Refer to information indicated in Volume IV, Section E Full 0 Technical Comment: Loading Dock Security Booth Assignable Square Feet (ASF) OFEO Space Dimensions 0 Organizational Unit Other Interior Glazing 0 0 Yes Yes 0 Ceiling CRITICAL FINISHES 0 0
ELECTRICAL ARCHITECTURAL
blank. Zone Room ID D3.45 Room Name 0 Functional Description This is
Security booth that
located
Deliveries area.
position oversees
Non Public-Non Collection Space 200 Number of Occupants NA Visual Privacy (full, partial, open) Zone Designation Zone D Room Height 0 LEED NC Regurlarly
0 Base ACOUSTICS Equipment Hardware/STC Rating None NRCSTC 55 0 Plug Loads Air Change/ HR Walls HVAC ENGINEERING CRITERIA Temperature Lighting No Control ±2ºF 110v, 20a, 1ph Yes 0 Power No 0 Pressure (+/-) 78ºF Summer, 70ºF Winter Floor Operable Windows Separation/STC FURNITURE/EQUIPMENT Moveable Yes Fixed RT60
0 Lower
room data sheet is not comprehensive in nature. Information regarding specific room features may not have been available and was intentionally left
the
is
in the
The
security for
sets of docks (collections
Occupied Space
& Shaping
Floor Level 0 Room

This room data sheet is not comprehensive in nature.

Compliance withADA/ABAAG (2004) citations is required for accessibility. SI also requires compliance with SI Accessibility Guidelines and the IBC. Comparisons should be made and the more stringent requirement followed for design purposes. An accessible route including a minimum clear width of 36" (except through doors, which must be at least 32" clear) is required. Refer to ADA/ABAAG (2004) for specifications regarding clear floor spaces at desks, files and equipment for individuals using wheelchairs.See Accessibility Narrative for additional information.

and exits of staff and visitors.

CRITICAL DIMENSIONS

Please refer to structural narrative for more information on structural requirements.

Smithsonian Institution National Museum of African American History and Culture 224 Infrastructure Only 0 Other Amenities Deionized Water Vacuum Yes Speakers LH 225 SF/HD FIRE ALARM Smoke Detection Yes Wet Sprinkler Special Waste Dry Sprinkler Pre-Action Sprinkler No FIRE PROTECTION No Considerations for Water 0 No Floor Drains Floor Sink Grey/Blackwater Piping 0 No No No Protected Hot/Cold No No Recycled Water Supply (treated) 0 No Public Address Audio Compressed Air Audio Visual Requirements No Hot/Cold Water Task Light To Be Considered No 0 Plant/Clean Steam No Acoustic Sensitivity NC 40 Vibration Sensitivity Special Equipment/Artifact Sensitivity PLUMBING Target Illuminance (IES 9th Edition) Daylight Sensor 10 FC Exhibit Light No Power Density (AHSRAE 2004) 1.1 W/ft² Temperature Deviations (+/-) No No Process Water UPS Switched Receptacles Dimming To Be Considered Humidity 0 No Other Humidity Deviation (+/-) As required by load No No Outside Air Single/Multi-Level Switching 0 Emergency/Standby Power As required by code 30/85 Single Occupancy Sensor Special Exhaust Sub-metering & Feedback Displays Filtration (Pre/Final/Other) Voice/Data DATA/TELECOMMUNICATIONS Yes 0 SECURITY 0 5.0 kPa/8.9 kN Floor Loading/Point Loads DAYLIGHTING 0 0 Shading Considerations Top/Side Lighting None No STRUCTURAL 0 0 Refer to information indicated in Volume IV, Section E Full 0 Technical Comment: Mail Room (Screening Function) Assignable Square Feet (ASF) OFEO Space Dimensions 0 Organizational Unit Other Interior Glazing 0 0 Yes Yes 0 Ceiling CRITICAL FINISHES 0 0
ELECTRICAL ARCHITECTURAL
Information regarding specific room features may not have been available and was intentionally left blank. Zone Room ID D3.46 Room Name 0 Functional Description This control room is a smaller security check point at the staff and package delivery entrance. It provides control over smaller deliveries (such as Fed-Ex) and the entrances
Non Public-Non Collection Space 100 Number of Occupants TBD Visual Privacy (full, partial, open) Zone Designation Zone D Room Height 0 LEED NC Regurlarly Occupied Space 0 Base ACOUSTICS Equipment Hardware/STC Rating None NRCSTC 45 0 Plug Loads Air Change/ HR Walls HVAC ENGINEERING CRITERIA Temperature Lighting No Control ±2ºF 110v, 20a, 1ph Yes 0 Power No 0 Pressure (+/-) 78ºF Summer, 70ºF Winter Floor Operable Windows Separation/STC FURNITURE/EQUIPMENT Moveable Yes Fixed RT60 & Shaping 0 TBD
TBD
Floor Level 0 Room Length,
Open
SUSTAINABILITY FEATURES Adjacencies Accessibility Requirement:
Width, Shape
vs. Private

This room data sheet is not comprehensive in nature. Information regarding specific

Compliance with ADA/ABAAG (2004) citations is required for accessibility. SI also requires compliance with SI Accessibility Guidelines and the IBC. Comparisons should be made and the more stringent requirement followed for design purposes. An accessible route including a minimum clear width of 36" (except through doors, which must be at least 32" clear) is required. Refer to ADA/ABAAG (2004) for specifications regarding clear floor spaces at desks, files and equipment for individuals using wheelchairs.See Accessibility Narrative for additional information.

CRITICAL DIMENSIONS

Please refer to structural narrative for more information on structural requirements.

225 Room Data Sheets | FREELON BOND Infrastructure Only 0 Other Amenities Deionized Water Vacuum Yes Speakers LH 225 SF/SF FIRE ALARM Smoke Detection Yes Wet Sprinkler Special Waste Dry Sprinkler Pre-Action Sprinkler No FIRE PROTECTION No Considerations for Water 0 No Floor Drains Floor Sink Grey/Blackwater Piping 0 No No No Protected Hot/Cold No No Recycled Water Supply (treated) 0 No Public Address Audio Compressed Air Audio Visual Requirements No Hot/Cold Water Task Light To Be Considered No 0 Plant/Clean Steam No Acoustic Sensitivity NC 40 Vibration Sensitivity Special Equipment/Artifact Sensitivity PLUMBING Target Illuminance (IES 9th Edition) Daylight Sensor 30 FC Exhibit Light No Power Density (AHSRAE 2004) 1.5 W/ft² Temperature Deviations (+/-) No No Process Water UPS Switched Receptacles Dimming To Be Considered Humidity 0 Yes Other Humidity Deviation (+/-) As required by load No No Outside Air Single/Multi-Level Switching 0 Emergency/Standby Power As required by code 30/85 Single Occupancy Sensor Special Exhaust Sub-metering & Feedback Displays Filtration (Pre/Final/Other) Voice/Data DATA/TELECOMMUNICATIONS Yes 0 SECURITY 0 5.0 kPa/8.9 kN Floor Loading/Point Loads DAYLIGHTING 0 0 Shading Considerations Top/Side Lighting None No STRUCTURAL 0 0 Refer to information indicated in Volume IV, Section E Full 0 Technical Comment: Lost and Found Assignable Square Feet (ASF) OFEO Space Dimensions 0 Organizational Unit Other Interior Glazing 0 0 Yes Yes 0 Ceiling CRITICAL FINISHES 0 0
ELECTRICAL ARCHITECTURAL
room features may not have been available and was intentionally left blank. Zone Room ID D3.47 Room Name 0 Functional Description Lockable room accomodating safe and storage cabinets for public lost and found items. Will also inulude a workstation for one staff member. Must be located within the unit
Non Public-Non Collection Space 100 Number of Occupants NA Visual Privacy (full, partial, open) Zone Designation Zone D Room Height 0 LEED NC Regurlarly Occupied Space 0 Base ACOUSTICS Equipment Hardware/STC Rating None NRCSTC 45 0 Plug Loads Air Change/ HR Walls HVAC ENGINEERING CRITERIA Temperature Lighting No Control ±2ºF 110v, 20a, 1ph Yes 0 Power Yes 0 Pressure (+/-) 78ºF Summer, 70ºF Winter Floor Operable Windows Separation/STC FURNITURE/EQUIPMENT Moveable Yes Fixed RT60 & Shaping 0 TBD
security suite.
Located
Unit Security Suite
Floor Level 0 Room Length,
Shape Open
within the
SUSTAINABILITY FEATURES Adjacencies Accessibility Requirement:
Width,
vs. Private

This

data sheet is not comprehensive in nature. Information regarding specific room features may not have been available and was intentionally left

Accessibility Requirement:

Adjacencies

Compliance with ADA/ABAAG (2004) citations is required for accessibility. SI also requires compliance with SI Accessibility Guidelines and the IBC. Comparisons should be made and the more stringent requirement followed for design purposes. An accessible route including a minimum clear width of 36" (except through doors, which must be at least 32" clear) is required. Refer to ADA/ABAAG (2004) for specifications regarding clear floor spaces at desks, files and equipment for individuals using wheelchairs.See Accessibility Narrative for additional information. Located within the Unit Security Suite SUSTAINABILITY FEATURES

office and landscape office space with two workstations for Security shift supervisors, with each individual allocated 50 sf with office partitioning, desk/computer workstation, computer operator chair, in-desk file drawer, waste baskets, telephones, wall-mounted bookshelves. This room oversees fire protection for the museum. It monitors all fire alarm and sprinkler systems.

CRITICAL DIMENSIONS

Absorptive finish on the ceiling with an NRC of 0.70 or higher

Please refer to structural narrative for more information on structural requirements.

Smithsonian Institution National Museum of African American History and Culture 226 Infrastructure Only 0 Other Amenities Deionized Water Vacuum Yes Speakers LH 225 SF/HD FIRE ALARM Smoke Detection Yes Wet Sprinkler Special Waste Dry Sprinkler Pre-Action Sprinkler No FIRE PROTECTION No Considerations for Water 0 No Floor Drains Floor Sink Grey/Blackwater Piping 0 No No No Protected Hot/Cold No No Recycled Water Supply (treated) 0 No Public Address Audio Compressed Air Audio Visual Requirements No Hot/Cold Water Task Light To Be Considered No 0 Plant/Clean Steam No Acoustic Sensitivity NC 40 Vibration Sensitivity Special Equipment/Artifact Sensitivity PLUMBING Target Illuminance (IES 9th Edition) Daylight Sensor 30 FC Exhibit Light No Power Density (AHSRAE 2004) 1.5 W/ft² Temperature Deviations (+/-) No No Process Water UPS Switched Receptacles Dimming To Be Considered Humidity 0 Yes Other Humidity Deviation (+/-) As required by load No No Outside Air Single/Multi-Level Switching 0 Emergency/Standby Power As required by code 30/85 Single Occupancy Sensor Special Exhaust Sub-metering & Feedback Displays Filtration (Pre/Final/Other) Voice/Data DATA/TELECOMMUNICATIONS Yes 0 SECURITY 0 5.0 kPa/8.9 kN Floor Loading/Point Loads DAYLIGHTING 0 0 Shading Considerations Top/Side Lighting Location for Push to Talk microphone for building. Public Address System override. No STRUCTURAL 0 0 Refer to information
E Full 0 Technical Comment: Unit Control Room Assignable Square Feet
OFEO Space Dimensions 0 Organizational Unit Other Interior Glazing 0 0 Yes Yes 0 Ceiling CRITICAL FINISHES 0 0
indicated in Volume IV, Section
(ASF)
ELECTRICAL ARCHITECTURAL
blank. Zone Room ID D3.48 Room Name 0 Functional
Non Public-Non Collection Space 400 Number of Occupants NA Visual Privacy (full, partial, open) Zone Designation Zone D Room Height 0 LEED NC Regurlarly Occupied Space 0 Base ACOUSTICS Equipment Hardware/STC Rating None NRC
STC 45 0 Plug Loads Air Change/ HR Walls HVAC ENGINEERING CRITERIA Temperature Lighting No Control ±2ºF 110v, 20a, 1ph Yes 0 Power Yes 0 Pressure (+/-) 78ºF Summer, 70ºF Winter Floor Operable Windows Separation/STC FURNITURE/EQUIPMENT Moveable Yes Fixed RT60 & Shaping 0 TBD
room
Description Private
Floor Level 400 S.F.
Room
(min)
Length, Width, Shape Open vs. Private

This room data sheet is not comprehensive in nature.

Compliance with ADA/ABAAG (2004) citations is required for accessibility. SI also requires compliance with SI Accessibility Guidelines and the IBC. Comparisons should be made and the more stringent requirement followed for design purposes. An accessible route including a minimum clear width of 36" (except through doors, which must be at least 32" clear) is required. Refer to ADA/ABAAG (2004) for specifications regarding clear floor spaces at desks, files and equipment for individuals using wheelchairs.See Accessibility Narrative for additional information.

CRITICAL DIMENSIONS

Please refer to structural narrative for more information on structural requirements.

227 Room Data Sheets | FREELON BOND Infrastructure Only 0 Other Amenities Deionized Water Vacuum Yes Speakers LH 225 SF/HD FIRE ALARM Smoke Detection Yes Wet Sprinkler Special Waste Dry Sprinkler Pre-Action Sprinkler No FIRE PROTECTION No Considerations for Water 0 No Floor Drains Floor Sink Grey/Blackwater Piping 0 No No No Protected Hot/Cold No No Recycled Water Supply (treated) 0 No Public Address Audio Compressed Air Audio Visual Requirements No Hot/Cold Water Task Light To Be Considered No 0 Plant/Clean Steam No Acoustic Sensitivity NC 40 Vibration Sensitivity Special Equipment/Artifact Sensitivity PLUMBING Target Illuminance (IES 9th Edition) Daylight Sensor 30 FC Exhibit Light No Power Density (AHSRAE 2004) 1.5 W/ft² Temperature Deviations (+/-) No No Process Water UPS Switched Receptacles Dimming To Be Considered Humidity 0 Yes Other Humidity Deviation (+/-) As required by load No No Outside Air Single/Multi-Level Switching 0 Emergency/Standby Power As required by code 30/85 Single Occupancy Sensor Special Exhaust Sub-metering & Feedback Displays Filtration (Pre/Final/Other) Voice/Data DATA/TELECOMMUNICATIONS Yes 0 SECURITY 0 5.0 kPa/8.9 kN Floor Loading/Point Loads DAYLIGHTING 0 0 Shading Considerations Top/Side Lighting None No STRUCTURAL 0 0 Refer to information indicated in Volume IV, Section E Full 0 Technical Comment: Key/ Weapons/ Radio Room Assignable Square Feet (ASF) OFEO Space Dimensions 0 Organizational Unit Other Interior Glazing 0 0 Yes Yes 0 Ceiling CRITICAL FINISHES 0 0
ELECTRICAL ARCHITECTURAL
Information regarding specific room features may not have been available and was intentionally left blank. Zone Room ID D3.49 Room Name 0 Functional Description Lockable storage space to accommodate radio chargers and weapons. Also will have shelving and counter space for other items. This room must be located within the Unit Security Suite. Non Public-Non Collection Space 100 Number of Occupants NA Visual Privacy (full, partial, open) Zone Designation Zone D Room Height 0 LEED NC Regurlarly Occupied Space 0 Base ACOUSTICS Equipment Hardware/STC Rating None NRCSTC 45 0 Plug Loads Air Change/ HR Walls HVAC ENGINEERING CRITERIA Temperature Lighting No Control ±2ºF 110v, 20a, 1ph Yes 0 Power Yes 0 Pressure (+/-) 78ºF Summer, 70ºF Winter Floor Operable Windows Separation/STC FURNITURE/EQUIPMENT Moveable Yes Fixed RT60 & Shaping 0 TBD
Located
Unit Security Suite
Floor Level 80 S.F. (min) Room Length,
Open
within the
SUSTAINABILITY FEATURES Adjacencies Accessibility Requirement:
Width, Shape
vs. Private

Accessibility Requirement:

Adjacencies

SUSTAINABILITY FEATURES

Open vs. Private

Compliance with ADA/ABAAG (2004) citations is required for accessibility. SI also requires compliance with SI Accessibility Guidelines and the IBC. Comparisons should be made and the more stringent requirement followed for design purposes. An accessible route including a minimum clear width of 36" (except through doors, which must be at least 32" clear) is required. Refer to ADA/ABAAG (2004) for specifications regarding clear floor spaces at desks, files and equipment for individuals using wheelchairs.See Accessibility Narrative for additional information. Unit Control Room, Security Rack Room (Security Equipment)

CRITICAL DIMENSIONS

Smithsonian Institution National Museum of African American History and Culture 228 Infrastructure Only 0 Other Amenities Deionized Water Vacuum 0 Speakers 0 FIRE ALARM Smoke Detection 0 Wet Sprinkler Special Waste Dry Sprinkler Pre-Action Sprinkler 0 FIRE PROTECTION 0 Considerations for Water 0 0 Floor Drains Floor Sink Grey/Blackwater Piping 0 0 0 0 Protected Hot/Cold 0 0 Recycled Water Supply (treated) 0 0 Public Address Audio Compressed Air Audio Visual Requirements 0 Hot/Cold Water Task Light 0 0 0 Plant/Clean Steam 0 Acoustic Sensitivity 0 Vibration Sensitivity Special Equipment/Artifact Sensitivity PLUMBING Target Illuminance (IES 9th Edition) Daylight Sensor 0 Exhibit Light 0 Power Density (AHSRAE 2004) 0 Temperature Deviations (+/-) 0 0 Process Water UPS Switched Receptacles Dimming 0 Humidity 0 0 Other Humidity Deviation (+/-) 0 0 0 Outside Air Single/Multi-Level Switching 0 Emergency/Standby Power 0 0 0 Occupancy Sensor Special Exhaust Sub-metering & Feedback Displays Filtration (Pre/Final/Other) Voice/Data DATA/TELECOMMUNICATIONS Data 0 SECURITY 0 0 Floor Loading/Point Loads DAYLIGHTING 0 0 Shading Considerations Top/Side Lighting 0 0 STRUCTURAL 0 0 0 0 0 Technical Comment: Security Utility Closet Assignable Square Feet (ASF) OFEO Space Dimensions 0 Organizational Unit Other Interior Glazing 0 0 0 0 0 Ceiling CRITICAL FINISHES 0 0 0 ELECTRICAL ARCHITECTURAL 0 Zone Room ID D3.50 Room Name 0 Functional Description Utility closet dedicated to security equipment. Min size of 40sf. Located within 250ft of all security equipment. Non Public-Non Collection Space 0 Number of Occupants NA Visual Privacy (full, partial, open) Zone Designation Zone D Room Height 0 LEED NC Regurlarly Occupied Space 0 Base ACOUSTICS Equipment Hardware/STC Rating 0 NRC 0 0 0 Plug Loads Air Change/ HR Walls HVAC ENGINEERING CRITERIA Temperature Lighting 0 0 110v, 20a, 1ph 0 0 Power 0 0 Pressure (+/-) 0 Floor Operable Windows Separation/STC FURNITURE/EQUIPMENT Moveable 0 Fixed RT60 & Shaping 0 0
Floor Level 40 S.F. (min) Room
Length, Width, Shape

Accessibility Requirement:

Adjacencies

SUSTAINABILITY FEATURES

vs. Private

Compliance with ADA/ABAAG (2004) citations is required for accessibility. SI also requires compliance with SI Accessibility Guidelines and the IBC. Comparisons should be made and the more stringent requirement followed for design purposes. An accessible route including a minimum clear width of 36" (except through doors, which must be at least 32" clear) is required. Refer to ADA/ABAAG (2004) for specifications regarding clear floor spaces at desks, files and equipment for individuals using wheelchairs.See Accessibility Narrative for additional information.

Support Area

for roll call/check-in for each shift, radio pickup and charging, bulletin boards.

CRITICAL DIMENSIONS

Length, Width, Shape

Recommend W&V and sink under Plumbing. Please refer to structural narrative for more information on structural requirements.

229 Room Data Sheets | FREELON BOND Infrastructure Only 0 Other Amenities Deionized Water Vacuum Yes Speakers LH 225 SF/HD FIRE ALARM Smoke Detection Yes Wet Sprinkler Special Waste Dry Sprinkler Pre-Action Sprinkler No FIRE PROTECTION No Considerations for Water 0 No Floor Drains Floor Sink Grey/Blackwater Piping 0 No No No Protected Hot/Cold No No Recycled Water Supply (treated) 0 No Public Address Audio Compressed Air Audio Visual Requirements Yes Hot/Cold Water Task Light No No 0 Plant/Clean Steam No Acoustic Sensitivity NC 40 Vibration Sensitivity Special Equipment/Artifact Sensitivity PLUMBING Target Illuminance (IES 9th Edition) Daylight Sensor 10 FC Exhibit Light To Be Considered Power Density (AHSRAE 2004) 1.2 W/ft² Temperature Deviations (+/-) No No Process Water UPS Switched Receptacles Dimming To Be Considered Humidity 0 Yes Other Humidity Deviation (+/-) As required by load No No Outside Air Single/Multi-Level Switching 0 Emergency/Standby Power As required by code 30/85 Single Occupancy Sensor Special Exhaust Sub-metering & Feedback Displays Filtration (Pre/Final/Other) Voice/Data DATA/TELECOMMUNICATIONS Yes 0 SECURITY 0 5.0 kPa/8.9 kN Floor Loading/Point Loads DAYLIGHTING 0 0 Shading Considerations Top/Side Lighting None No STRUCTURAL 0 0 Refer to information indicated in Volume IV, Section E Full 0 Technical Comment: Security Duty Room/Break Room Assignable Square Feet (ASF) OFEO Space Dimensions 0 Organizational Unit Other Interior Glazing 0 0 Yes Yes 0 Ceiling CRITICAL FINISHES 0 0
ELECTRICAL ARCHITECTURAL
room
nature.
blank. Zone Room ID D3.51 Room Name 0 Functional Description Break Room and Ready Room for Security staff, with coffee/microwave facilities, and lunch table and chairs. Used
Non Public-Non Collection Space 200 Number of Occupants TBD Visual Privacy (full, partial, open) Zone Designation Zone D Room Height 0 LEED NC Regurlarly Occupied Space 0 Base ACOUSTICS Equipment Hardware/STC Rating None NRC Absorptive finish on the ceiling with an NRC of 0.70 or higher STC 45 0 Plug Loads Air Change/ HR Walls HVAC ENGINEERING CRITERIA Temperature Lighting No Control ±2ºF 110v, 20a, 1ph Yes 0 Power No 0 Pressure (+/-) 78ºF Summer, 70ºF Winter Floor Operable Windows Separation/STC FURNITURE/EQUIPMENT Moveable Yes Fixed RT60 &
0 TBD
This
data sheet is not comprehensive in
Information regarding specific room features may not have been available and was intentionally left
Shaping
Building
Floor Level 0 Room
Open

This room data sheet is not comprehensive in nature. Information regarding specific room features may not have been available and was intentionally left blank.

Compliance with ADA/ABAAG (2004) citations is required for accessibility. SI also requires compliance with SI Accessibility Guidelines and the IBC. Comparisons should be made and the more stringent requirement followed for design purposes. An accessible route including a minimum clear width of 36" (except through doors, which must be at least 32" clear) is required. Refer to ADA/ABAAG (2004) for specifications regarding clear floor spaces at desks, files and equipment for individuals using wheelchairs.See Accessibility Narrative for additional information.

Building Support Area

CRITICAL DIMENSIONS

Smithsonian Institution National Museum of African American History and Culture 230 Infrastructure Only 0 Other Amenities Deionized Water Vacuum Yes Speakers OH Gr. 2, 130 SF/HD FIRE ALARM Smoke Detection Yes Wet Sprinkler Special Waste Dry Sprinkler Pre-Action Sprinkler No FIRE PROTECTION 0 Considerations for Water 0 No Floor Drains Floor Sink Grey/Blackwater Piping 0 0 0 0 Protected Hot/Cold 0 0 Recycled Water Supply (treated) 0 0 Public Address Audio Compressed Air Audio Visual Requirements 0 Hot/Cold Water Task Light 0 0 0 Plant/Clean Steam 0 Acoustic Sensitivity 0 Vibration Sensitivity Special Equipment/Artifact Sensitivity PLUMBING Target Illuminance (IES 9th Edition) Daylight Sensor 0 Exhibit Light 0 Power Density (AHSRAE 2004) 1.1 W/ft² Temperature Deviations (+/-) 0 0 Process Water UPS Switched Receptacles Dimming 0 Humidity 0 0 Other Humidity Deviation (+/-) 0 0 0 Outside Air Single/Multi-Level Switching 0 Emergency/Standby Power 0 0 0 Occupancy Sensor Special Exhaust Sub-metering & Feedback Displays Filtration (Pre/Final/Other) Voice/Data DATA/TELECOMMUNICATIONS 0 0 SECURITY 0 5.0 kPa/8.9 kN Floor Loading/Point Loads DAYLIGHTING 0 0 Shading Considerations Top/Side Lighting 0 0 STRUCTURAL 0 0 Refer to information indicated in Volume IV, Section E 0 0 Technical Comment: Security Locker Room (Men/ Women) Assignable Square Feet (ASF) OFEO Space Dimensions 0 Organizational Unit Other Interior Glazing 0 0 0 0 0 Ceiling CRITICAL FINISHES 0 0 0 ELECTRICAL ARCHITECTURAL
Zone Room ID D3.53 Room Name 0 Functional Description Final size will be determinied by staffing requirements. Separate Male and Female space will be provided. Spaces will include benches, showers, and lockers. Non Public-Non Collection Space 290 Number of Occupants NA Visual Privacy (full, partial, open) Zone Designation Zone D Room Height 0 LEED NC Regurlarly Occupied Space 0 Base ACOUSTICS Equipment Hardware/STC Rating 0 NRC0 0 Plug Loads Air Change/ HR Walls HVAC ENGINEERING CRITERIA Temperature Lighting 0 0 110v, 20a, 1ph 0 0 Power 0 0 Pressure (+/-) 0 Floor Operable Windows Separation/STC FURNITURE/EQUIPMENT Moveable 0 Fixed RT60 & Shaping 0 TBD
Adjacencies
Floor Level 0 Room
Open
SUSTAINABILITY FEATURES
Accessibility Requirement:
Length, Width, Shape
vs. Private

This room data sheet is not comprehensive in nature. Information regarding specific room features may not have been available and was intentionally left

Accessibility Requirement:

Adjacencies

Description

SUSTAINABILITY FEATURES

Open vs. Private

Compliance with ADA/ABAAG (2004) citations is required for accessibility. SI also requires compliance with SI Accessibility Guidelines and the IBC. Comparisons should be made and the more stringent requirement followed for design purposes. An accessible route including a minimum clear width of 36" (except through doors, which must be at least 32" clear) is required. Refer to ADA/ABAAG (2004) for specifications regarding clear floor spaces at desks, files and equipment for individuals using wheelchairs.See Accessibility Narrative for additional information.

Located within the Unit Security Suite

CRITICAL DIMENSIONS

Length, Width, Shape

(min)

231 Room Data Sheets | FREELON BOND Infrastructure Only 0 Other Amenities Deionized Water Vacuum Yes Speakers OH Gr. 2, 130 SF/HD FIRE ALARM Smoke Detection Yes Wet Sprinkler Special Waste Dry Sprinkler Pre-Action Sprinkler No FIRE PROTECTION 0 Considerations for Water 0 No Floor Drains Floor Sink Grey/Blackwater Piping 0 0 0 0 Protected Hot/Cold 0 0 Recycled Water Supply (treated) 0 0 Public Address Audio Compressed Air Audio Visual Requirements 0 Hot/Cold Water Task Light 0 0 0 Plant/Clean Steam 0 Acoustic Sensitivity 0 Vibration Sensitivity Special Equipment/Artifact Sensitivity PLUMBING Target Illuminance (IES 9th Edition) Daylight Sensor 0 Exhibit Light 0 Power Density (AHSRAE 2004) 0 Temperature Deviations (+/-) 0 0 Process Water UPS Switched Receptacles Dimming 0 Humidity 0 0 Other Humidity Deviation (+/-) 0 0 0 Outside Air Single/Multi-Level Switching 0 Emergency/Standby Power 0 0 0 Occupancy Sensor Special Exhaust Sub-metering & Feedback Displays Filtration (Pre/Final/Other) Voice/Data DATA/TELECOMMUNICATIONS Yes 0 SECURITY 0 7.5 kPa/17.8 kN Floor Loading/Point Loads DAYLIGHTING 0 0 Shading Considerations Top/Side Lighting 0 0 STRUCTURAL 0 0 Refer to information indicated in Volume IV, Section E 0 0 Technical Comment: Security Rack Room (Security Equipment) Assignable Square Feet (ASF) OFEO Space Dimensions 0 Organizational Unit Other Interior Glazing 0 0 0 0 0 Ceiling CRITICAL FINISHES 0 0 0 ELECTRICAL ARCHITECTURAL
Zone Room ID D3.54 Room Name 0 Functional
Where all the security head-end equipment will reside (i.e., DVRs, switches, etc.). Non Public-Non Collection Space 200 Number of Occupants NA Visual Privacy (full, partial, open) Zone Designation Zone D Room Height 0 LEED NC Regurlarly Occupied Space 0 Base ACOUSTICS Equipment Hardware/STC Rating 0 NRC0 0 Plug Loads Air Change/ HR Walls HVAC ENGINEERING CRITERIA Temperature Lighting 0 0 110v, 20a, 1ph 0 0 Power 0 0 Pressure (+/-) 0 Floor Operable Windows Separation/STC FURNITURE/EQUIPMENT Moveable 0 Fixed RT60 & Shaping 0 TBD
blank.
Floor Level 200 S.F.
Room

This room data sheet is not comprehensive in nature. Information regarding specific room features may not have been

Compliance with ADA/ABAAG (2004) citations is required for accessibility. SI also requires compliance with SI Accessibility Guidelines and the IBC. Comparisons should be made and the more stringent requirement followed for design purposes. An accessible route including a minimum clear width of 36" (except through doors, which must be at least 32" clear) is required. Refer to ADA/ABAAG (2004) for specifications regarding clear floor spaces at desks, files and equipment for individuals using wheelchairs.See Accessibility Narrative for additional information. Located within the Unit Security Suite SUSTAINABILITY FEATURES Adjacencies

vs. Private

CRITICAL DIMENSIONS

Length, Width, Shape

Smithsonian Institution National Museum of African American History and Culture 232 Infrastructure Only 0 Other Amenities Deionized Water Vacuum Yes Speakers OH Gr. 2, 130 SF/HD FIRE ALARM Smoke Detection Yes Wet Sprinkler Special Waste Dry Sprinkler Pre-Action Sprinkler No FIRE PROTECTION 0 Considerations for Water 0 No Floor Drains Floor Sink Grey/Blackwater Piping 0 0 0 0 Protected Hot/Cold 0 0 Recycled Water Supply (treated) 0 0 Public Address Audio Compressed Air Audio Visual Requirements 0 Hot/Cold Water Task Light 0 0 0 Plant/Clean Steam 0 Acoustic Sensitivity 0 Vibration Sensitivity Special Equipment/Artifact Sensitivity PLUMBING Target Illuminance (IES 9th Edition) Daylight Sensor 0 Exhibit Light 0 Power Density (AHSRAE 2004) 0 Temperature Deviations (+/-) 0 0 Process Water UPS Switched Receptacles Dimming 0 Humidity 0 0 Other Humidity Deviation (+/-) 0 0 0 Outside Air Single/Multi-Level Switching 0 Emergency/Standby Power 0 0 0 Occupancy Sensor Special Exhaust Sub-metering & Feedback Displays Filtration (Pre/Final/Other) Voice/Data DATA/TELECOMMUNICATIONS Yes 0 SECURITY 0 5.0 kPa/8.9 kN Floor Loading/Point Loads DAYLIGHTING 0 0 Shading Considerations Top/Side Lighting 0 0 STRUCTURAL 0 0 Refer to information indicated in Volume IV, Section E 0 0 Technical Comment: Assistant Security Manager Office Assignable Square Feet (ASF) OFEO Space Dimensions 0 Organizational Unit Other Interior Glazing 0 0 0 0 0 Ceiling CRITICAL FINISHES 0 0 0 ELECTRICAL ARCHITECTURAL
Zone Room ID D3.55 Room Name 0
security badges for staff & visitors, should be connected to key card entry system to determine access to restricted areas. Assistant Manager of security is here, a duty list and security staff bulletin board should also be provided outside this office for security personnel. Non Public-Non Collection Space 100 Number of Occupants NA Visual Privacy (full, partial, open) Zone Designation Zone D Room Height 0 LEED NC Regurlarly Occupied Space 0 Base ACOUSTICS Equipment Hardware/STC Rating 0 NRC0 0 Plug Loads Air Change/ HR Walls HVAC ENGINEERING CRITERIA Temperature Lighting 0 0 110v, 20a, 1ph 0 0 Power 0 0 Pressure (+/-) 0 Floor Operable Windows Separation/STC FURNITURE/EQUIPMENT Moveable 0 Fixed RT60 & Shaping 0 TBD
available and was intentionally left blank.
Functional Description Space to produce
Floor Level 0 Room
Accessibility Requirement:
Open

room data sheet is not comprehensive in nature. Information regarding specific room features may not have been available and was intentionally left

Compliance with ADA/ABAAG (2004) citations is required for accessibility. SI also requires compliance with SI Accessibility Guidelines and the IBC. Comparisons should be made and the more stringent requirement followed for design purposes. An accessible route including a minimum clear width of 36" (except through doors, which must be at least 32" clear) is required. Refer to ADA/ABAAG (2004) for specifications regarding clear floor spaces at desks, files and equipment for individuals using wheelchairs.See Accessibility Narrative for additional information. Located within the Unit Security Suite

CRITICAL DIMENSIONS

233 Room Data Sheets | FREELON BOND Infrastructure Only 0 Other Amenities Deionized Water Vacuum Yes Speakers OH Gr. 2, 130 SF/HD FIRE ALARM Smoke Detection Yes Wet Sprinkler Special Waste Dry Sprinkler Pre-Action Sprinkler No FIRE PROTECTION 0 Considerations for Water 0 No Floor Drains Floor Sink Grey/Blackwater Piping 0 0 0 0 Protected Hot/Cold 0 0 Recycled Water Supply (treated) 0 0 Public Address Audio Compressed Air Audio Visual Requirements 0 Hot/Cold Water Task Light 0 0 0 Plant/Clean Steam 0 Acoustic Sensitivity 0 Vibration Sensitivity Special Equipment/Artifact Sensitivity PLUMBING Target Illuminance (IES 9th Edition) Daylight Sensor 0 Exhibit Light 0 Power Density (AHSRAE 2004) 0 Temperature Deviations (+/-) 0 0 Process Water UPS Switched Receptacles Dimming 0 Humidity 0 0 Other Humidity Deviation (+/-) 0 0 0 Outside Air Single/Multi-Level Switching 0 Emergency/Standby Power 0 0 0 Occupancy Sensor Special Exhaust Sub-metering & Feedback Displays Filtration (Pre/Final/Other) Voice/Data DATA/TELECOMMUNICATIONS Yes 0 SECURITY 0 5.0 kPa/8.9 kN Floor Loading/Point Loads DAYLIGHTING 0 0 Shading Considerations Top/Side Lighting 0 0 STRUCTURAL 0 0 Refer to information indicated in Volume IV, Section E 0 0 Technical Comment: Security Manager Office Assignable Square Feet (ASF) OFEO Space Dimensions 0 Organizational Unit Other Interior Glazing 0 0 0 0 0 Ceiling CRITICAL FINISHES 0 0 0 ELECTRICAL ARCHITECTURAL
blank. Zone Room ID D3.56 Room Name 0 Functional Description Manager of security is here, a duty list and security staff bulletin board should be provided outside this office for security personnel. Non Public-Non Collection Space 120 Number of Occupants NA Visual Privacy (full, partial, open) Zone Designation Zone D Room Height 0 LEED NC Regurlarly Occupied Space 0 Base ACOUSTICS Equipment Hardware/STC Rating 0 NRC0 0 Plug Loads Air Change/ HR Walls HVAC ENGINEERING CRITERIA Temperature Lighting 0 0 110v, 20a, 1ph 0 0 Power 0 0 Pressure (+/-) 0 Floor Operable Windows Separation/STC FURNITURE/EQUIPMENT Moveable 0 Fixed RT60 & Shaping 0 TBD
This
SUSTAINABILITY
Floor Level 0 Room Length,
Open
FEATURES Adjacencies Accessibility Requirement:
Width, Shape
vs. Private

room data sheet is not comprehensive in nature. Information regarding specific room features may not have been available and was intentionally left

Accessibility Requirement:

SUSTAINABILITY FEATURES Adjacencies

Compliance with ADA/ABAAG (2004) citations is required for accessibility. SI also requires compliance with SI Accessibility Guidelines and the IBC. Comparisons should be made and the more stringent requirement followed for design purposes. An accessible route including a minimum clear width of 36" (except through doors, which must be at least 32" clear) is required. Refer to ADA/ABAAG (2004) for specifications regarding clear floor spaces at desks, files and equipment for individuals using wheelchairs.See Accessibility Narrative for additional information.

Located within the Unit Security Suite

CRITICAL DIMENSIONS

Length, Width, Shape Open vs. Private

Smithsonian Institution National Museum of African American History and Culture 234 Infrastructure Only 0 Other Amenities Deionized Water Vacuum Yes Speakers OH Gr. 2, 130 SF/HD FIRE ALARM Smoke Detection Yes Wet Sprinkler Special Waste Dry Sprinkler Pre-Action Sprinkler No FIRE PROTECTION 0 Considerations for Water 0 No Floor Drains Floor Sink Grey/Blackwater Piping 0 0 0 0 Protected Hot/Cold 0 0 Recycled Water Supply (treated) 0 0 Public Address Audio Compressed Air Audio Visual Requirements 0 Hot/Cold Water Task Light 0 0 0 Plant/Clean Steam 0 Acoustic Sensitivity 0 Vibration Sensitivity Special Equipment/Artifact Sensitivity PLUMBING Target Illuminance (IES 9th Edition) Daylight Sensor 0 Exhibit Light 0 Power Density (AHSRAE 2004) 0 Temperature Deviations (+/-) 0 0 Process Water UPS Switched Receptacles Dimming 0 Humidity 0 0 Other Humidity Deviation (+/-) 0 0 0 Outside Air Single/Multi-Level Switching 0 Emergency/Standby Power 0 0 0 Occupancy Sensor Special Exhaust Sub-metering & Feedback Displays Filtration (Pre/Final/Other) Voice/Data DATA/TELECOMMUNICATIONS Yes 0 SECURITY 0 5.0 kPa/8.9 kN Floor Loading/Point Loads DAYLIGHTING 0 0 Shading Considerations Top/Side Lighting 0 Yes STRUCTURAL 0 0 Refer to information indicated in Volume IV, Section E 0 0 Technical Comment: Work Area (Security Suite) Assignable Square Feet (ASF) OFEO Space Dimensions 0 Organizational Unit Other Interior Glazing 0 0 0 0 0 Ceiling CRITICAL FINISHES 0 0 0 ELECTRICAL ARCHITECTURAL
blank. Zone Room ID D3.58 Room Name 0 Functional Description Non-enclosed administrative work area including counter, storage cabinets, over-counter mail slots, and task lighting as required. Non Public-Non Collection Space 100 Number of Occupants NA Visual Privacy (full, partial, open) Zone Designation Zone D Room Height 0 LEED NC Regurlarly Occupied
0 Base ACOUSTICS Equipment Hardware/STC Rating 0 NRC0 0 Plug Loads Air Change/ HR Walls HVAC ENGINEERING CRITERIA Temperature Lighting 0 0 110v, 20a, 1ph 0 0 Power 0 0 Pressure (+/-) 0 Floor Operable Windows Separation/STC FURNITURE/EQUIPMENT Moveable 0 Fixed RT60 & Shaping 0 TBD
This
Space
Floor Level 0 Room

This room data sheet is not comprehensive in nature. Information regarding specific room features may not have been available and was intentionally left

SUSTAINABILITY FEATURES

vs. Private

Compliance with ADA/ABAAG (2004) citations is required for accessibility. SI also requires compliance with SI Accessibility Guidelines and the IBC. Comparisons should be made and the more stringent requirement followed for design purposes. An accessible route including a minimum clear width of 36" (except through doors, which must be at least 32" clear) is required. Refer to ADA/ABAAG (2004) for specifications regarding clear floor spaces at desks, files and equipment for individuals using wheelchairs.See Accessibility Narrative for additional information.

Main Public Entrance, Group Public Entrance, VIP/Staff Entrance, Public Vehicular Entrance

and location of posts to be determined.

CRITICAL DIMENSIONS

235 Room Data Sheets | FREELON BOND Infrastructure Only 0 Other Amenities Deionized Water Vacuum Yes Speakers OH Gr. 2, 130 SF/HD FIRE ALARM Smoke Detection Yes Wet Sprinkler Special Waste Dry Sprinkler Pre-Action Sprinkler No FIRE PROTECTION 0 Considerations for Water 0 No Floor Drains Floor Sink Grey/Blackwater Piping 0 0 0 0 Protected Hot/Cold 0 0 Recycled Water Supply (treated) 0 0 Public Address Audio Compressed Air Audio Visual Requirements 0 Hot/Cold Water Task Light 0 0 0 Plant/Clean Steam 0 Acoustic Sensitivity 0 Vibration Sensitivity Special Equipment/Artifact Sensitivity PLUMBING Target Illuminance (IES 9th Edition) Daylight Sensor 0 Exhibit Light 0 Power Density (AHSRAE 2004) 0 Temperature Deviations (+/-) 0 0 Process Water UPS Switched Receptacles Dimming 0 Humidity 0 0 Other Humidity Deviation (+/-) 0 0 0 Outside Air Single/Multi-Level Switching 0 Emergency/Standby Power 0 0 0 Occupancy Sensor Special Exhaust Sub-metering & Feedback Displays Filtration (Pre/Final/Other) Voice/Data DATA/TELECOMMUNICATIONS Yes 0 SECURITY 0 0 Floor Loading/Point Loads DAYLIGHTING 0 0 Shading Considerations Top/Side Lighting 0 0 STRUCTURAL 0 0 Refer to information indicated in Volume IV, Section E 0 0 Technical Comment: Guard Post Assignable Square Feet (ASF) OFEO Space Dimensions 0 Organizational Unit Other Interior Glazing 0 0 0 0 0 Ceiling CRITICAL FINISHES 0 0 0 ELECTRICAL ARCHITECTURAL
blank. Zone Room ID D3.59 Room Name 0
mail rooms.
number
Non Public-Non Collection Space 0 Number of Occupants TBD Visual Privacy (full, partial, open) Zone Designation Zone D Room Height 0 LEED NC Regurlarly Occupied Space 0 Base ACOUSTICS Equipment Hardware/STC Rating 0 NRC0 0 Plug Loads Air Change/ HR Walls HVAC ENGINEERING CRITERIA Temperature Lighting 0 0 110v, 20a, 1ph 0 0 Power 0 0 Pressure (+/-) 0 Floor Operable Windows Separation/STC FURNITURE/EQUIPMENT Moveable 0 Fixed RT60 & Shaping 0 TBD
Functional Description Security monitoring point for primary and secondary entrances to the public. This includes loading docks and
Final
Floor Level 0 Room
Adjacencies Accessibility Requirement:
Length, Width, Shape Open

Compliance with ADA/ABAAG (2004) citations is required for accessibility. SI also requires compliance with SI Accessibility Guidelines and the IBC. Comparisons should be made and the more stringent requirement followed for design purposes. An accessible route including a minimum clear width of 36" (except through doors, which must be at least 32" clear) is required. Refer to ADA/ABAAG (2004) for specifications regarding clear floor spaces at desks, files and equipment for individuals using wheelchairs.See Accessibility Narrative for additional information.

Control Room SUSTAINABILITY FEATURES

vs. Private

CRITICAL DIMENSIONS

Length, Width, Shape

Smithsonian Institution National Museum of African American History and Culture 236 Infrastructure Only 0 Other Amenities Deionized Water Vacuum Yes Speakers OH Gr. 2, 130 SF/HD FIRE ALARM Smoke Detection Yes Wet Sprinkler Special Waste Dry Sprinkler Pre-Action Sprinkler No FIRE PROTECTION 0 Considerations for Water 0 No Floor Drains Floor Sink Grey/Blackwater Piping 0 0 0 0 Protected Hot/Cold 0 0 Recycled Water Supply (treated) 0 0 Public Address Audio Compressed Air Audio Visual Requirements 0 Hot/Cold Water Task Light 0 0 0 Plant/Clean Steam 0 Acoustic Sensitivity 0 Vibration Sensitivity Special Equipment/Artifact Sensitivity PLUMBING Target Illuminance (IES 9th Edition) Daylight Sensor 0 Exhibit Light 0 Power Density (AHSRAE 2004) 0 Temperature Deviations (+/-) 0 0 Process Water UPS Switched Receptacles Dimming 0 Humidity 0 0 Other Humidity Deviation (+/-) 0 0 0 Outside Air Single/Multi-Level Switching 0 Emergency/Standby Power 0 0 0 Occupancy Sensor Special Exhaust Sub-metering & Feedback Displays Filtration (Pre/Final/Other) Voice/Data DATA/TELECOMMUNICATIONS Yes 0 SECURITY 0 0 Floor Loading/Point Loads DAYLIGHTING 0 0 Shading Considerations Top/Side Lighting 0 0 STRUCTURAL 0 0 Refer to information indicated in Volume IV, Section E 0 0 Technical Comment: Reception Area (Security Suite) Assignable Square Feet (ASF) OFEO Space Dimensions 0 Organizational Unit Other Interior Glazing 0 0 0 0 0 Ceiling CRITICAL FINISHES 0 0 0 ELECTRICAL ARCHITECTURAL This room data sheet
not comprehensive in nature.
specific room features may not have been available and was intentionally left blank. Zone Room ID D3.60 Room Name 0 Functional Description Main reception area for unit security suite. Separate reception area from Unit Security Suite with countertops and swinging door. Non Public-Non Collection Space 100 Number of Occupants TBD Visual Privacy (full, partial, open) Zone Designation Zone D Room Height 0 LEED NC Regurlarly Occupied Space 0 Base ACOUSTICS Equipment Hardware/STC Rating 0 NRC0 0 Plug Loads Air Change/ HR Walls HVAC ENGINEERING CRITERIA Temperature Lighting 0 0 110v, 20a, 1ph 0 0 Power 0 0 Pressure (+/-) 0 Floor Operable Windows Separation/STC FURNITURE/EQUIPMENT Moveable 0 Fixed RT60 & Shaping 0 TBD
is
Information regarding
Adjacencies
Floor Level 0 Room
Security
Accessibility Requirement:
Open

This room data sheet is not comprehensive in nature. Information regarding specific room features may not have been available and was intentionally left blank.

Accessibility Requirement:

Adjacencies

SUSTAINABILITY FEATURES

Open vs. Private

Compliance with ADA/ABAAG (2004) citations is required for accessibility. SI also requires compliance with SI Accessibility Guidelines and the IBC. Comparisons should be made and the more stringent requirement followed for design purposes. An accessible route including a minimum clear width of 36" (except through doors, which must be at least 32" clear) is required. Refer to ADA/ABAAG (2004) for specifications regarding clear floor spaces at desks, files and equipment for individuals using wheelchairs.See Accessibility Narrative for additional information.

Located within the Unit Security Suite

CRITICAL DIMENSIONS

Length, Width, Shape

(min)

237 Room Data Sheets | FREELON BOND Infrastructure Only 0 Other Amenities Deionized Water Vacuum Yes Speakers OH Gr. 2, 130 SF/HD FIRE ALARM Smoke Detection Yes Wet Sprinkler Special Waste Dry Sprinkler Pre-Action Sprinkler No FIRE PROTECTION 0 Considerations for Water 0 No Floor Drains Floor Sink Grey/Blackwater Piping 0 0 0 0 Protected Hot/Cold 0 0 Recycled Water Supply (treated) 0 0 Public Address Audio Compressed Air Audio Visual Requirements 0 Hot/Cold Water Task Light 0 0 0 Plant/Clean Steam 0 Acoustic Sensitivity 0 Vibration Sensitivity Special Equipment/Artifact Sensitivity PLUMBING Target Illuminance (IES 9th Edition) Daylight Sensor 0 Exhibit Light 0 Power Density (AHSRAE 2004) 0 Temperature Deviations (+/-) 0 0 Process Water UPS Switched Receptacles Dimming 0 Humidity 0 0 Other Humidity Deviation (+/-) 0 0 0 Outside Air Single/Multi-Level Switching 0 Emergency/Standby Power 0 0 0 Occupancy Sensor Special Exhaust Sub-metering & Feedback Displays Filtration (Pre/Final/Other) Voice/Data DATA/TELECOMMUNICATIONS 0 0 SECURITY 0 7.5 kPa/17.8 kN Floor Loading/Point Loads DAYLIGHTING 0 0 Shading Considerations Top/Side Lighting 0 0 STRUCTURAL 0 0 Refer to information indicated in Volume IV, Section E 0 0 Technical Comment: Security System Storage Closet Assignable Square Feet (ASF) OFEO Space Dimensions 0 Organizational Unit Other Interior Glazing 0 0 0 0 0 Ceiling CRITICAL FINISHES 0 0 0 ELECTRICAL ARCHITECTURAL
Zone Room ID D3.61 Room Name 0
for security uniforms, handheld searching equipement, may contain a secure weapons locker. Shelving to be provided. Non Public-Non Collection Space 100 Number of Occupants NA Visual Privacy (full, partial, open) Zone Designation Zone D Room Height 0 LEED NC Regurlarly Occupied Space 0 Base ACOUSTICS Equipment Hardware/STC Rating 0 NRC0 0 Plug Loads Air Change/ HR Walls HVAC ENGINEERING CRITERIA Temperature Lighting 0 0 110v, 20a, 1ph 0 0 Power 0 0 Pressure (+/-) 0 Floor Operable Windows Separation/STC FURNITURE/EQUIPMENT Moveable 0 Fixed RT60 & Shaping 0 TBD
Functional Description Storage
Floor
100 S.F.
Level
Room

Accessibility Requirement: Floor Level

Adjacencies

SUSTAINABILITY FEATURES

Compliance with ADA/ABAAG (2004) citations is required for accessibility. SI also requires compliance with SI Accessibility Guidelines and the IBC. Comparisons should be made and the more stringent requirement followed for design purposes. An accessible route including a minimum clear width of 36" (except through doors, which must be at least 32" clear) is required. Refer to ADA/ABAAG (2004) for specifications regarding clear floor spaces at desks, files and equipment for individuals using wheelchairs.See Accessibility Narrative for additional information.

Security Check Area

CRITICAL DIMENSIONS

Length, Width, Shape Open vs. Private

Smithsonian Institution National Museum of African American History and Culture 238 Infrastructure Only 0 Other Amenities Deionized Water Vacuum Yes Speakers OH Gr. 2, 130 SF/HD FIRE ALARM Smoke Detection Yes Wet Sprinkler Special Waste Dry Sprinkler Pre-Action Sprinkler No FIRE PROTECTION 0 Considerations for Water 0 No Floor Drains Floor Sink Grey/Blackwater Piping 0 0 0 0 Protected Hot/Cold 0 0 Recycled Water Supply (treated) 0 0 Public Address Audio Compressed Air Audio Visual Requirements 0 Hot/Cold Water Task Light 0 0 0 Plant/Clean Steam 0 Acoustic Sensitivity 0 Vibration Sensitivity Special Equipment/Artifact Sensitivity PLUMBING Target Illuminance (IES 9th Edition) Daylight Sensor 0 Exhibit Light 0 Power Density (AHSRAE 2004) 0 Temperature Deviations (+/-) 0 0 Process Water UPS Switched Receptacles Dimming 0 Humidity 0 0 Other Humidity Deviation (+/-) 0 0 0 Outside Air Single/Multi-Level Switching 0 Emergency/Standby Power 0 0 0 Occupancy Sensor Special Exhaust Sub-metering & Feedback Displays Filtration (Pre/Final/Other) Voice/Data DATA/TELECOMMUNICATIONS Yes 0 SECURITY 0 0 Floor Loading/Point Loads DAYLIGHTING 0 0 Shading Considerations Top/Side Lighting 0 0 STRUCTURAL 0 0 Refer to information indicated in Volume IV, Section E 0 0 Technical Comment: Staff Entrance Lobby Assignable Square Feet (ASF) OFEO Space Dimensions 0 Organizational Unit Other Interior Glazing 0 0 0 0 0 Ceiling CRITICAL FINISHES 0 0 0 ELECTRICAL ARCHITECTURAL
left blank. Zone Room ID D3.62 Room Name 0 Functional Description Secure staff entry, separate from
entry,
back-of-house via a security sign-in
digital access card. Non Public Non-Collection Space 200 Number of Occupants NA Visual Privacy (full, partial, open) Zone Designation Zone D Room Height 0 LEED NC Regurlarly Occupied Space 0 Base ACOUSTICS Equipment Hardware/STC Rating 0 NRC 0 0 0 Plug Loads Air Change/ HR Walls HVAC ENGINEERING CRITERIA Temperature Lighting 0 0 110v, 20a, 1ph 0 0 Power 0 0 Pressure (+/-) 0 Floor Operable Windows Separation/STC FURNITURE/EQUIPMENT Moveable 0 Fixed RT60 & Shaping 0 0
This room data sheet is not comprehensive in nature. Information regarding specific room features may not have been available and was intentionally
visitor
direct access to
or
0
Room

This room data sheet is not comprehensive in nature. Information regarding specific room features may not have been available and was intentionally left blank.

Accessibility Requirement:

Adjacencies

SUSTAINABILITY FEATURES

Compliance with ADA/ABAAG (2004) citations is required for accessibility. SI also requires compliance with SI Accessibility Guidelines and the IBC. Comparisons should be made and the more stringent requirement followed for design purposes. An accessible route including a minimum clear width of 36" (except through doors, which must be at least 32" clear) is required. Refer to ADA/ABAAG (2004) for specifications regarding clear floor spaces at desks, files and equipment for individuals using wheelchairs.See Accessibility Narrative for additional information.

Security, Employee/Visitor/Package Entrance/ Control Room, Loading Dock Security Booths and Washroom, Adjacent but separate to Enclosed Collections Loading Bay

CRITICAL DIMENSIONS

Length, Width, Shape Open vs. Private

Recommend hose bibs under Plumbing. Please refer to structural narrative for more information on structural requirements.

239 Room Data Sheets | FREELON BOND Infrastructure Only 0 Other Amenities Deionized Water Vacuum Yes Speakers OH Gr. 2, 130 SF/HD FIRE ALARM Smoke Detection Yes Wet Sprinkler Special Waste Dry Sprinkler Pre-Action Sprinkler No FIRE PROTECTION No Considerations for Water 0 No Floor Drains Floor Sink Grey/Blackwater Piping 0 No No No Protected Hot/Cold No No Recycled Water Supply (treated) 0 No Public Address Audio Compressed Air Audio Visual Requirements Yes Hot/Cold Water Task Light To Be Considered No 0 Plant/Clean Steam No Acoustic Sensitivity 0 Vibration Sensitivity Special Equipment/Artifact Sensitivity PLUMBING Target Illuminance (IES 9th Edition) Daylight Sensor 10 FC Exhibit Light No Power Density (AHSRAE 2004) 1.25 W/ft² Temperature Deviations (+/-) No No Process Water UPS Switched Receptacles Dimming To Be Considered Humidity 0 No Other Humidity Deviation (+/-) As required by load No No Outside Air Single/Multi-Level Switching 0 Emergency/Standby Power As required by code 30/85 Single Occupancy Sensor Special Exhaust Sub-metering & Feedback Displays Filtration (Pre/Final/Other) Voice/Data DATA/TELECOMMUNICATIONS Yes 0 SECURITY 0 12.0 kPa/26.7 kN Floor Loading/Point Loads DAYLIGHTING 0 0 Shading Considerations Top/Side Lighting None No STRUCTURAL 0 0 Refer to information indicated in Volume IV, Section E Full 0 Technical Comment: Loading Bay, Non Collections Assignable Square Feet (ASF) OFEO Space Dimensions 0 Organizational Unit Other Interior Glazing 0 0 Yes Yes 0 Ceiling CRITICAL FINISHES 0 0
ELECTRICAL ARCHITECTURAL
Zone Room ID D3.63 Room Name 0 Functional Description One secure Non-Collections loading bay for deliveries of food and supplies,
bay
Non Public-Non Collection Space 1,000 Number of Occupants NA Visual Privacy (full, partial, open) Zone Designation Zone D Room Height 0 LEED NC Regurlarly Occupied Space 0 Base ACOUSTICS Equipment Hardware/STC Rating None NRC0 0 Plug Loads Air Change/ HR Walls HVAC ENGINEERING CRITERIA Temperature Lighting No Control ±2ºF 110v, 20a, 1ph Yes 0 Power No 0 Pressure (+/-) 78ºF Summer, 70ºF Winter Floor Operable Windows Separation/STC FURNITURE/EQUIPMENT Moveable Yes Fixed RT60 &
0 Lower
and another
for removal of garbage and recycling.
Shaping
Floor Level 0 Room

This room data sheet is not comprehensive in nature. Information regarding specific room features may not have been available and was intentionally left blank.

Accessibility Requirement: Floor Level

Adjacencies

SUSTAINABILITY FEATURES

Open vs. Private

LEED NC Regurlarly Occupied Space

Recommend Hose Bibs under Plumbing. Please refer to structural narrative for more information on structural requirements. ELECTRICAL ARCHITECTURAL

CRITERIA

Compliance with ADA/ABAAG (2004) citations is required for accessibility. SI also requires compliance with SI Accessibility Guidelines and the IBC. Comparisons should be made and the more stringent requirement followed for design purposes. An accessible route including a minimum clear width of 36" (except through doors, which must be at least 32" clear) is required. Refer to ADA/ABAAG (2004) for specifications regarding clear floor spaces at desks, files and equipment for individuals using wheelchairs.See Accessibility Narrative for additional information.

Adjacent but separate to Enclosed Collections Loading Dock

CRITICAL DIMENSIONS

Room Length, Width, Shape

Smithsonian Institution National Museum of African American History and Culture 240 Infrastructure Only 0 Other Amenities Deionized Water Vacuum Yes Speakers OH Gr. 2, 130 SF/HD FIRE ALARM Smoke Detection 0 Wet Sprinkler Special Waste Dry Sprinkler Pre-Action Sprinkler No FIRE PROTECTION No Considerations for Water 0 No Floor Drains Floor Sink Grey/Blackwater Piping 0 No No No Protected Hot/Cold No No Recycled Water Supply (treated) 0 No Public Address Audio Compressed Air Audio Visual Requirements Yes Hot/Cold Water Task Light No No 0 Plant/Clean Steam No Acoustic Sensitivity No Vibration Sensitivity Special Equipment/Artifact Sensitivity PLUMBING Target Illuminance (IES 9th Edition) Daylight Sensor 0 Exhibit Light No Power Density (AHSRAE 2004) 0 Temperature Deviations (+/-) No No Process Water UPS Switched Receptacles Dimming No Humidity 0 No Other Humidity Deviation (+/-) As required by load No No Outside Air Single/Multi-Level Switching 0 Emergency/Standby Power As required by code 30/85 Yes Occupancy Sensor Special Exhaust Sub-metering & Feedback Displays Filtration (Pre/Final/Other) Voice/Data DATA/TELECOMMUNICATIONS Yes 0 SECURITY 0 0 Floor Loading/Point Loads DAYLIGHTING 0 0 Shading Considerations Top/Side Lighting 0 0 STRUCTURAL 0 0 Refer to information indicated in Volume IV, Section E 0 0 Technical Comment: Loading Dock, Non-Collections Assignable Square Feet (ASF) OFEO Space Dimensions 0 Organizational Unit Other Interior Glazing 0 0 0 0 0 Ceiling
FINISHES 0 0
CRITICAL
Zone Room ID D3.64 Room Name 0 Functional
food
supplies
removal
garbage
Non Public Non-Collection Space 1,000 Number of Occupants NA Visual Privacy (full, partial, open) Zone Designation Zone D Room Height 0
0 Base ACOUSTICS Equipment Hardware/STC Rating None NRC 0 0 0 Plug Loads Air Change/ HR Walls HVAC ENGINEERING
Temperature Lighting No Control ±2ºF 110v, 20a, 1ph Yes 0 Power No 0 Pressure (+/-) 78ºF Summer, 70ºF Winter Floor Operable Windows
FURNITURE/EQUIPMENT Moveable 0 Fixed RT60 & Shaping 0 0
Description Dock for deliveries of
and
and
of
and recycling.
Separation/STC
0

This room data sheet is not comprehensive in nature. Information regarding specific room features may not have been available and was intentionally left

Compliance with ADA/ABAAG (2004) citations is required for accessibility. SI also requires compliance with SI Accessibility Guidelines and the IBC. Comparisons should be made and the more stringent requirement followed for design purposes. An accessible route including a minimum clear width of 36" (except through doors, which must be at least 32" clear) is required. Refer to ADA/ABAAG (2004) for specifications regarding clear floor spaces at desks, files and equipment for individuals using wheelchairs.See Accessibility Narrative for additional information.

Docks

CRITICAL DIMENSIONS

Recommend W&V, hose bibs and drinking fountain under Plumbing. Please refer to structural narrative for more information on structural requirements.

241 Room Data Sheets | FREELON BOND Infrastructure Only 0 Other Amenities Deionized Water Vacuum Yes Speakers OH Gr. 2, 130 SF/HD FIRE ALARM Smoke Detection Yes Wet Sprinkler Special Waste Dry Sprinkler Pre-Action Sprinkler No FIRE PROTECTION No Considerations for Water 0 No Floor Drains Floor Sink Grey/Blackwater Piping 0 No No Yes Protected Hot/Cold No No Recycled Water Supply (treated) 0 Yes Public Address Audio Compressed Air Audio Visual Requirements Yes Hot/Cold Water Task Light No No 0 Plant/Clean Steam No Acoustic Sensitivity NC 40 Vibration Sensitivity Special Equipment/Artifact Sensitivity PLUMBING Target Illuminance (IES 9th Edition) Daylight Sensor 5 FC Exhibit Light No Power Density (AHSRAE 2004) 0.9 W/ft² Temperature Deviations (+/-) No No Process Water UPS Switched Receptacles Dimming To Be Considered Humidity 0 No Other Humidity Deviation (+/-) As required by load No No Outside Air Single/Multi-Level Switching 0 Emergency/Standby Power As required by code 30/85 Single Occupancy Sensor Special Exhaust Sub-metering & Feedback Displays Filtration (Pre/Final/Other) Voice/Data DATA/TELECOMMUNICATIONS 0 0 SECURITY 0 5.0 kPa/8.9 kN Floor Loading/Point Loads DAYLIGHTING 0 0 Shading Considerations Top/Side Lighting None No STRUCTURAL 0 0 Refer to information indicated in Volume IV, Section E Full 0 Technical Comment: Trucker Washroom, Unisex Assignable Square Feet (ASF) OFEO Space Dimensions 0 Organizational Unit Other Interior Glazing Cleanable 0 No Yes Cleanable Ceiling CRITICAL FINISHES Cleanable 0
ELECTRICAL ARCHITECTURAL
Zone Room ID D3.65 Room Name 0 Functional Description Washroom facility for
outside
secured
Non Public-Non Collection Space 200 Number of Occupants NA Visual Privacy (full, partial, open) Zone Designation Zone D Room Height 0 LEED NC Regurlarly
Space 0 Base ACOUSTICS Equipment Hardware/STC Rating None NRCSTC 55 0 Plug Loads Air Change/ HR Walls HVAC ENGINEERING CRITERIA Temperature Lighting No Control ±2ºF 110v, 20a, 1ph Yes 0 Power No Cleanable Pressure (+/-) 78ºF Summer, 70ºF Winter Floor Operable Windows Separation/STC FURNITURE/EQUIPMENT Moveable Yes Fixed RT60 & Shaping 0 TBD
blank.
truckers to use, this is
the Conditioned Zone, so the delivery personell do not enter the
collections area.
Occupied
Loading
Floor Level 0 Room Length,
Open
SUSTAINABILITY FEATURES Adjacencies Accessibility Requirement:
Width, Shape
vs. Private

This room data sheet is not comprehensive in nature. Information regarding specific room features may not have been available and was intentionally left blank.

SUSTAINABILITY FEATURES Adjacencies Accessibility Requirement:

Compliance with ADA/ABAAG (2004) citations is required for accessibility. SI also requires compliance with SI Accessibility Guidelines and the IBC. Comparisons should be made and the more stringent requirement followed for design purposes. An accessible route including a minimum clear width of 36" (except through doors, which must be at least 32" clear) is required. Refer to ADA/ABAAG (2004) for specifications regarding clear floor spaces at desks, files and equipment for individuals using wheelchairs.See Accessibility Narrative for additional information.

Docks

Please refer to structural narrative for more information on structural requirements.

CRITICAL DIMENSIONS

Smithsonian Institution National Museum of African American History and Culture 242 Infrastructure Only 0 Other Amenities Deionized Water Vacuum 0 Speakers No FIRE ALARM Smoke Detection 0 Wet Sprinkler Special Waste Dry Sprinkler Pre-Action Sprinkler No FIRE PROTECTION No Considerations for Water 0 No Floor Drains Floor Sink Grey/Blackwater Piping 0 No No No Protected Hot/Cold No No Recycled Water Supply (treated) 0 No Public Address Audio Compressed Air Audio Visual Requirements No Hot/Cold Water Task Light No No 0 Plant/Clean Steam No Acoustic Sensitivity No Vibration Sensitivity Special Equipment/Artifact Sensitivity PLUMBING Target Illuminance (IES 9th Edition) Daylight Sensor 30 FC Exhibit Light No Power Density (AHSRAE 2004) 0.9 W/ft² Temperature Deviations (+/-) No No Process Water UPS Switched Receptacles Dimming To Be Considered Humidity 0 No Other Humidity Deviation (+/-) As required by load No No Outside Air Single/Multi-Level Switching 0 Emergency/Standby Power As required by code 30/85 Single Occupancy Sensor Special Exhaust Sub-metering & Feedback Displays Filtration (Pre/Final/Other) Voice/Data DATA/TELECOMMUNICATIONS 0 0 SECURITY 0 7.5 kPa/17.8 kN Floor Loading/Point Loads DAYLIGHTING 0 0 Shading Considerations Top/Side Lighting None No STRUCTURAL 0 0 Refer to information indicated in Volume IV, Section E Full 0 Technical Comment: Operations Yard Assignable Square Feet (ASF) OFEO Space Dimensions 0 Organizational Unit Other Interior Glazing 0 0 No Yes 0 Ceiling CRITICAL FINISHES 0 0
ELECTRICAL ARCHITECTURAL
Zone Room ID D3.66 Room Name 0 Functional Description Outdoor staging area for building operations. Non Public-Non Collection Space 0 Number of Occupants NA Visual Privacy (full, partial, open) Zone Designation Zone D Room Height 0 LEED NC Regurlarly Occupied Space 0 Base ACOUSTICS Equipment Hardware/STC Rating None NRC0 0 Plug Loads Air Change/ HR Walls HVAC ENGINEERING CRITERIA Temperature Lighting No Control ±2ºF 110v, 20a, 1ph Yes 0 Power No 0 Pressure (+/-) 78ºF Summer, 70ºF Winter Floor Operable Windows Separation/STC FURNITURE/EQUIPMENT Moveable No Fixed RT60 & Shaping 0 Ground
Loading
Floor Level 0 Room Length,
Open
Width, Shape
vs. Private

This room data sheet is not comprehensive in nature. Information regarding specific room features may not have been available and was intentionally left blank.

Accessibility Requirement:

Adjacencies

SUSTAINABILITY FEATURES

Compliance with ADA/ABAAG (2004) citations is required for accessibility. SI also requires compliance with SI Accessibility Guidelines and the IBC. Comparisons should be made and the more stringent requirement followed for design purposes. An accessible route including a minimum clear width of 36" (except through doors, which must be at least 32" clear) is required. Refer to ADA/ABAAG (2004) for specifications regarding clear floor spaces at desks, files and equipment for individuals using wheelchairs.See Accessibility Narrative for additional information.

Services Shipping/Receiving, Garbage Bins and Recycling Bins, Loading Dock (Non-Collections)

area. Accessible to garbage trucks. Cold water hose bib for cleanup.

CRITICAL DIMENSIONS

Length, Width, Shape Open vs. Private

Recommend Hose Bibs under Plumbing.Please refer to structural narrative for more information on structural requirements.

243 Room Data Sheets | FREELON BOND Infrastructure Only 0 Other Amenities Deionized Water Vacuum Yes Speakers OH Gr. 2, 130 SF/HD FIRE ALARM Smoke Detection Yes Wet Sprinkler Special Waste Dry Sprinkler Pre-Action Sprinkler No FIRE PROTECTION No Considerations for Water 0 No Floor Drains Floor Sink Grey/Blackwater Piping 0 No No No Protected Hot/Cold No No Recycled Water Supply (treated) 0 Yes Public Address Audio Compressed Air Audio Visual Requirements Yes Hot/Cold Water Task Light No No 0 Plant/Clean Steam No Acoustic Sensitivity No Vibration Sensitivity Special Equipment/Artifact Sensitivity PLUMBING Target Illuminance (IES 9th Edition) Daylight Sensor 10 FC Exhibit Light No Power Density (AHSRAE 2004) 0.9 W/ft² Temperature Deviations (+/-) No No Process Water UPS Switched Receptacles Dimming To Be Considered Humidity 0 No Other Humidity Deviation (+/-) As required by load No No Outside Air Single/Multi-Level Switching 0 Emergency/Standby Power As required by code 30/85 Single Occupancy Sensor Special Exhaust Sub-metering & Feedback Displays Filtration (Pre/Final/Other) Voice/Data DATA/TELECOMMUNICATIONS 0 0 SECURITY 0 7.5 kPa/26.7 kN Floor Loading/Point Loads DAYLIGHTING 0 0 Shading Considerations Top/Side Lighting None No STRUCTURAL 0 0 Refer to information indicated in Volume IV, Section E 0 0 Technical Comment: Garbage Bins and Recycling Bins Assignable Square Feet
OFEO Space Dimensions 0 Organizational Unit Other Interior Glazing 0 0 Yes No 0 Ceiling CRITICAL FINISHES 0 0
(ASF)
ELECTRICAL ARCHITECTURAL
Zone Room ID D3.67 Room Name 0
garbage
access
dumpster
dumpster
Non Public-Non Collection Space 300 Number of Occupants NA Visual Privacy (full, partial, open) Zone Designation Zone D Room Height 0 LEED NC Regurlarly Occupied Space 0 Base ACOUSTICS Equipment Hardware/STC Rating None NRC0 0 Plug Loads Air Change/ HR Walls HVAC ENGINEERING CRITERIA Temperature Lighting No Control ±2ºF 110v, 20a, 1ph No 0 Power No 0 Pressure (+/-) 78ºF Summer, 70ºF Winter Floor Operable Windows Separation/STC FURNITURE/EQUIPMENT Moveable Yes Fixed RT60
0 Varies
Functional Description Indoor temporary
and recycling center with
to
area outside or an exterior, enclosed
& Shaping
Floor Level 0 Room

This room data sheet is not comprehensive in nature. Information regarding specific room features may not have been available and was intentionally left blank.

Accessibility Requirement:

Compliance with ADA/ABAAG (2004) citations is required for accessibility. SI also requires compliance with SI Accessibility Guidelines and the IBC. Comparisons should be made and the more stringent requirement followed for design purposes. An accessible route including a minimum clear width of 36" (except through doors, which must be at least 32" clear) is required. Refer to ADA/ABAAG (2004) for specifications regarding clear floor spaces at desks, files and equipment for individuals using wheelchairs.See Accessibility Narrative for additional information.

Services Shipping/Receiving, Garbage Bins and Recycling Bins, Loading Dock (Non-Collections) SUSTAINABILITY FEATURES Adjacencies

CRITICAL DIMENSIONS

Please refer to structural narrative for more information on structural requirements.

Smithsonian Institution National Museum of African American History and Culture 244 Infrastructure Only 0 Other Amenities Deionized Water Vacuum Yes Speakers OH Gr. 2, 130 SF/HD FIRE ALARM Smoke Detection Yes Wet Sprinkler Special Waste Dry Sprinkler Pre-Action Sprinkler No FIRE PROTECTION No Considerations for Water 0 No Floor Drains Floor Sink Grey/Blackwater Piping 0 No No No Protected Hot/Cold No No Recycled Water Supply (treated) 0 No Public Address Audio Compressed Air Audio Visual Requirements No Hot/Cold Water Task Light To Be Considered No 0 Plant/Clean Steam No Acoustic Sensitivity No Vibration Sensitivity Special Equipment/Artifact Sensitivity PLUMBING Target Illuminance (IES 9th Edition) Daylight Sensor 10 FC Exhibit Light To Be Considered Power Density (AHSRAE 2004) 1.1 W/ft² Temperature Deviations (+/-) No No Process Water UPS Switched Receptacles Dimming To Be Considered Humidity 0 No Other Humidity Deviation (+/-) As required by load No No Outside Air Single/Multi-Level Switching 0 Emergency/Standby Power As required by code 30/85 Single Occupancy Sensor Special Exhaust Sub-metering & Feedback Displays Filtration (Pre/Final/Other) Voice/Data DATA/TELECOMMUNICATIONS Yes 0 SECURITY 0 12.0 kPa/26.7 kN Floor Loading/Point Loads DAYLIGHTING 0 0 Shading Considerations Top/Side Lighting None No STRUCTURAL 0 0 Refer to information indicated in Volume IV, Section E Open 0 Technical Comment: Shipping/ Receiving Assignable Square Feet (ASF) OFEO Space Dimensions 0 Organizational Unit Other Interior Glazing 0 0 Yes Yes 0 Ceiling CRITICAL FINISHES 0 0
ELECTRICAL ARCHITECTURAL
Zone Room ID D3.68 Room Name 0 Functional Description The area
food
Non Public-Non Collection Space 400 Number of Occupants NA Visual Privacy (full, partial, open) Zone
Room Height 0 LEED NC Regurlarly Occupied Space 0 Base ACOUSTICS Equipment Hardware/STC Rating None NRC0 0 Plug Loads Air Change/ HR Walls HVAC ENGINEERING CRITERIA Temperature Lighting No Control ±2ºF 110v, 20a, 1ph Yes 0 Power No 0 Pressure (+/-) 78ºF Summer, 70ºF Winter Floor Operable Windows Separation/STC FURNITURE/EQUIPMENT Moveable Yes Fixed RT60 & Shaping 0 TBD
designated for receiving deliveries of
and supplies.
Designation Zone D
Floor Level 0 Room
Open
Length, Width, Shape
vs. Private

room data sheet is not comprehensive in nature.

Compliance with ADA/ABAAG (2004) citations is required for accessibility. SI also requires compliance with SI Accessibility Guidelines and the IBC. Comparisons should be made and the more stringent requirement followed for design purposes. An accessible route including a minimum clear width of 36" (except through doors, which must be at least 32" clear) is required. Refer to ADA/ABAAG (2004) for specifications regarding clear floor spaces at desks, files and equipment for individuals using wheelchairs.See Accessibility Narrative for additional information.

Services Shipping/Receiving, Garbage Bins and Recycling Bins, Loading Dock (Non-Collections) SUSTAINABILITY FEATURES Adjacencies

CRITICAL DIMENSIONS

Please refer to structural narrative for more information on structural requirements.

245 Room Data Sheets | FREELON BOND Infrastructure Only 0 Other Amenities Deionized Water Vacuum Yes Speakers OH Gr. 2, 130 SF/HD FIRE ALARM Smoke Detection Yes Wet Sprinkler Special Waste Dry Sprinkler Pre-Action Sprinkler No FIRE PROTECTION No Considerations for Water 0 No Floor Drains Floor Sink Grey/Blackwater Piping 0 No No No Protected Hot/Cold No No Recycled Water Supply (treated) 0 No Public Address Audio Compressed Air Audio Visual Requirements No Hot/Cold Water Task Light No No 0 Plant/Clean Steam No Acoustic Sensitivity No Vibration Sensitivity Special Equipment/Artifact Sensitivity PLUMBING Target Illuminance (IES 9th Edition) Daylight Sensor 10 FC Exhibit Light No Power Density (AHSRAE 2004) 0.8 W/ft² Temperature Deviations (+/-) No No Process Water UPS Switched Receptacles Dimming To Be Considered Humidity 0 No Other Humidity Deviation (+/-) As required by load No No Outside Air Single/Multi-Level Switching 0 Emergency/Standby Power As required by code 30/85 Single Occupancy Sensor Special Exhaust Sub-metering & Feedback Displays Filtration (Pre/Final/Other) Voice/Data DATA/TELECOMMUNICATIONS 0 0 SECURITY 0 12.0 kPa/26.7 kN Floor Loading/Point Loads DAYLIGHTING 0 0 Shading Considerations Top/Side Lighting None No STRUCTURAL 0 0 Refer to information indicated in Volume IV, Section E Full 0 Technical Comment: Shipping Cages/Holding Area Assignable Square Feet (ASF) OFEO Space Dimensions 0 Organizational Unit Other Interior Glazing 0 0 Yes Yes 0 Ceiling CRITICAL FINISHES 0 0
ELECTRICAL ARCHITECTURAL
left blank. Zone Room ID D3.69 Room Name 0 Functional Description The secure holding area designated for receiving deliveries of food and supplies Non Public-Non Collection Space 400 Number of Occupants NA Visual Privacy (full, partial, open) Zone
Room Height 0 LEED NC Regurlarly Occupied Space 0 Base ACOUSTICS Equipment Hardware/STC Rating None NRC0 0 Plug Loads Air Change/ HR Walls HVAC ENGINEERING CRITERIA Temperature Lighting No Control ±2ºF 110v, 20a, 1ph No 0 Power No 0 Pressure (+/-) 78ºF Summer, 70ºF Winter Floor Operable Windows Separation/STC FURNITURE/EQUIPMENT Moveable Yes Fixed RT60 & Shaping 0 TBD
This
Information regarding specific room features may not have been available and was intentionally
Designation Zone D
Floor Level 0 Room Length,
Open
Accessibility Requirement:
Width, Shape
vs. Private

This room data sheet is not comprehensive in nature. Information regarding specific room features may not have been available and was intentionally left blank.

Accessibility Requirement:

Adjacencies

SUSTAINABILITY FEATURES

Compliance with ADA/ABAAG (2004) citations is required for accessibility. SI also requires compliance with SI Accessibility Guidelines and the IBC. Comparisons should be made and the more stringent requirement followed for design purposes. An accessible route including a minimum clear width of 36" (except through doors, which must be at least 32" clear) is required. Refer to ADA/ABAAG (2004) for specifications regarding clear floor spaces at desks, files and equipment for individuals using wheelchairs.See Accessibility Narrative for additional information.

Services Shipping/Receiving, Garbage Bins and Recycling Bins, Loading Dock (Non-Collections)

CRITICAL DIMENSIONS

Length, Width, Shape Open vs. Private

CRITERIA

Please refer to structural narrative for more information on structural requirements.

Smithsonian Institution National Museum of African American History and Culture 246 Infrastructure Only 0 Other Amenities Deionized Water Vacuum Yes Speakers Yes (in shaft) FIRE ALARM Smoke Detection Yes (in shaft) Wet Sprinkler Special Waste Dry Sprinkler Pre-Action Sprinkler No FIRE PROTECTION No Considerations for Water 0 No Floor Drains Floor Sink Grey/Blackwater Piping 0 No No No Protected Hot/Cold No No Recycled Water Supply (treated) 0 No Public Address Audio Compressed Air Audio Visual Requirements No Hot/Cold Water Task Light No No 0 Plant/Clean Steam No Acoustic Sensitivity No Vibration Sensitivity Special Equipment/Artifact Sensitivity PLUMBING Target Illuminance (IES 9th Edition) Daylight Sensor 5 FC Exhibit Light No Power Density (AHSRAE 2004) 0.6 W/ft² Temperature Deviations (+/-) No No Process Water UPS Switched Receptacles Dimming To Be Considered Humidity 0 No Other Humidity Deviation (+/-) As required by load No No Outside Air Single/Multi-Level Switching 0 Emergency/Standby Power As required by code 30/85 Single Occupancy Sensor Special Exhaust Sub-metering & Feedback Displays Filtration (Pre/Final/Other) Voice/Data DATA/TELECOMMUNICATIONS Voice 0 SECURITY 0 5.0 kPa/8.9 kN Floor Loading/Point Loads DAYLIGHTING 0 0 Shading Considerations Top/Side Lighting 0 No STRUCTURAL 0 0 Refer to information indicated in Volume IV, Section E Full Included in Grossing Factor. Technical Comment: Staff/ Service Elevator(s) Assignable Square Feet
OFEO Space Dimensions 0 Organizational Unit Other Interior Glazing 0 0 No Yes 0 Ceiling CRITICAL FINISHES 0 0
(ASF)
ELECTRICAL ARCHITECTURAL
Zone Room ID D3.70 Room Name 0
Non Public-Non Collection Space 0 Number of Occupants NA Visual Privacy (full, partial, open) Zone Designation Zone D Room Height 0 LEED NC Regurlarly Occupied Space 0 Base ACOUSTICS Equipment Hardware/STC Rating None NRC0 0 Plug Loads Air Change/ HR Walls HVAC ENGINEERING
Temperature Lighting No Control ±2ºF 110v, 20a, 1ph Yes 0 Power No 0 Pressure (+/-) 78ºF Summer, 70ºF Winter Floor Operable Windows Separation/STC FURNITURE/EQUIPMENT Moveable No Fixed RT60
0 Multiple
Functional Description Elevators for Staff, access to all staff areas on every floor. Key card secured and operated.
& Shaping
Floor Level 0 Room

This room data sheet is not comprehensive in nature. Information regarding specific room features may not have been available and was intentionally left blank.

Accessibility Requirement:

Adjacencies

SUSTAINABILITY FEATURES

vs. Private

Compliance with ADA/ABAAG (2004) citations is required for accessibility. SI also requires compliance with SI Accessibility Guidelines and the IBC. Comparisons should be made and the more stringent requirement followed for design purposes. An accessible route including a minimum clear width of 36" (except through doors, which must be at least 32" clear) is required. Refer to ADA/ABAAG (2004) for specifications regarding clear floor spaces at desks, files and equipment for individuals using wheelchairs.See Accessibility Narrative for additional information.

CRITICAL DIMENSIONS

Length, Width, Shape

finish on the ceiling with an NRC of 0.70 or higher

CRITERIA

Recommend hand sink and emergency shower under Plumbing. Please refer to structural narrative for more information on structural requirements.

247 Room Data Sheets | FREELON BOND Infrastructure Only 0 Other Amenities Deionized Water Vacuum Yes Speakers OH Gr. 2, 130 SF/HD FIRE ALARM Smoke Detection Yes Wet Sprinkler Special Waste Dry Sprinkler Pre-Action Sprinkler No FIRE PROTECTION No Considerations for Water 0 No Floor Drains Floor Sink Grey/Blackwater Piping 0 No No No Protected Hot/Cold Yes Yes Recycled Water Supply (treated) 0 No Public Address Audio Compressed Air Audio Visual Requirements Yes Hot/Cold Water Task Light Yes No 0 Plant/Clean Steam No Acoustic Sensitivity NC 35-40 Vibration Sensitivity Special Equipment/Artifact Sensitivity PLUMBING Target Illuminance (IES 9th Edition) Daylight Sensor 30-100 FC Exhibit Light To Be Considered Power Density (AHSRAE 2004) 1.9 W/ft² Temperature Deviations (+/-) No No Process Water UPS Switched
Dimming To Be Considered Humidity 0 Yes Other Humidity Deviation (+/-) As required by load No No Outside Air Single/Multi-Level Switching 0 Emergency/Standby Power As required by code 30/85 Single Occupancy Sensor Special Exhaust Sub-metering & Feedback Displays Filtration (Pre/Final/Other) Voice/Data DATA/TELECOMMUNICATIONS Yes 0 SECURITY 0 5.0 kPa/8.9 kN Floor Loading/Point Loads DAYLIGHTING 0 0 Shading Considerations Top/Side Lighting None No STRUCTURAL 0 0 Refer
Full 0 Technical Comment: Technical, Maintenance and Electrical Workshops Assignable Square Feet
OFEO Space Dimensions 0 Organizational Unit Other Interior Glazing 0 Solid wood core or insulated metal with neoprene strip seals max 1/4" undercut Yes Yes 0 Ceiling CRITICAL FINISHES 0 0
Receptacles
to information indicated in Volume IV, Section E
(ASF)
ELECTRICAL ARCHITECTURAL
Zone Room ID D3.71 Room Name 0 Functional Description Workshops that service the techincal needs of the museum. This is the in-house maintenance facility for the museum. Will need metal shelving for small equipment /parts for in-house repairs. Non Public-Non Collection Space 400 Number of Occupants NA Visual Privacy (full, partial, open) Zone Designation Zone
Room Height 0 LEED NC Regurlarly Occupied Space 0 Base ACOUSTICS Equipment Hardware/STC Rating None NRC
STC 50 0 Plug Loads Air Change/ HR Walls HVAC ENGINEERING
Temperature Lighting No Control ±2ºF 110v, 20a, 1ph Yes 0 Power No 0 Pressure (+/-) 78ºF Summer, 70ºF Winter Floor Operable Windows Separation/STC FURNITURE/EQUIPMENT Moveable Yes Fixed RT60
0 TBD
D
Absorptive
& Shaping
Protective Services Area
Floor Level 0 Room
Open

This room data sheet is not comprehensive in nature. Information regarding specific room features may not have been available and was intentionally left blank.

Accessibility Requirement:

Compliance with ADA/ABAAG (2004) citations is required for accessibility. SI also requires compliance with SI Accessibility Guidelines and the IBC. Comparisons should be made and the more stringent requirement followed for design purposes. An accessible route including a minimum clear width of 36" (except through doors, which must be at least 32" clear) is required. Refer to ADA/ABAAG (2004) for specifications regarding clear floor spaces at desks, files and equipment for individuals using wheelchairs.See Accessibility Narrative for additional information.

SUSTAINABILITY FEATURES Adjacencies

Functional Description BMS computer system control room. Work station for Facilities Manager, with monitoring instrumentation for building and security systems, storage for plan files and other building documentation.

CRITICAL DIMENSIONS

vs. Private

Please refer to structural narrative for more information on structural requirements.

Length, Width, Shape

Smithsonian Institution National Museum of African American History and Culture 248 Infrastructure Only 0 Other Amenities Deionized Water Vacuum Yes Speakers OH Gr. 2, 130 SF/HD FIRE ALARM Smoke Detection Yes Wet Sprinkler Special Waste Dry Sprinkler Pre-Action Sprinkler No FIRE PROTECTION No Considerations for Water 0 No Floor Drains Floor Sink Grey/Blackwater Piping 0 No No No Protected Hot/Cold No No Recycled Water Supply (treated) 0 No Public Address Audio Compressed Air Audio Visual Requirements No Hot/Cold Water Task Light To Be Considered No 0 Plant/Clean Steam No Acoustic Sensitivity NC 40 Vibration Sensitivity Special Equipment/Artifact Sensitivity PLUMBING Target Illuminance (IES 9th Edition) Daylight Sensor 30 FC Exhibit Light No Power Density (AHSRAE 2004) 1.5 W/ft² Temperature Deviations (+/-) No No Process Water UPS Switched Receptacles Dimming To Be Considered Humidity 0 Yes Other Humidity Deviation (+/-) As required by load No No Outside Air Single/Multi-Level Switching 0 Emergency/Standby Power As required by code 30/85 Single Occupancy Sensor Special Exhaust Sub-metering & Feedback Displays Filtration (Pre/Final/Other) Voice/Data DATA/TELECOMMUNICATIONS Yes 0 SECURITY 0 5.0 kPa/8.9 kN Floor Loading/Point Loads DAYLIGHTING 0 0 Shading Considerations Top/Side Lighting None No STRUCTURAL 0 0 Refer to information indicated in Volume IV, Section E Full 0 Technical Comment: Facilities Maintenance Control Rooms (BMS) Assignable Square Feet
OFEO Space Dimensions 0 Organizational Unit Other Interior Glazing 0 0 Yes No 0 Ceiling CRITICAL FINISHES 0 0
(ASF)
ELECTRICAL ARCHITECTURAL
Zone Room ID D3.72 Room Name 0
Non Public-Non Collection Space 200 Number of Occupants NA Visual Privacy (full, partial, open) Zone Designation Zone D Room Height 0 LEED NC Regurlarly Occupied Space 0 Base ACOUSTICS Equipment Hardware/STC Rating None NRCSTC 55 0 Plug Loads Air Change/ HR Walls HVAC ENGINEERING CRITERIA Temperature Lighting No Control ±2ºF 110v, 20a, 1ph Yes 0 Power No 0 Pressure (+/-) 78ºF Summer, 70ºF Winter Floor Operable Windows Separation/STC FURNITURE/EQUIPMENT Moveable Yes Fixed RT60
0 TBD
& Shaping
Protective Services Area
Floor Level 0 Room
Open

This room data sheet is not comprehensive in nature. Information regarding specific room

Accessibility Requirement:

Adjacencies

Compliance with ADA/ABAAG (2004) citations is required for accessibility. SI also requires compliance with SI Accessibility Guidelines and the IBC. Comparisons should be made and the more stringent requirement followed for design purposes. An accessible route including a minimum clear width of 36" (except through doors, which must be at least 32" clear) is required. Refer to ADA/ABAAG (2004) for specifications regarding clear floor spaces at desks, files and equipment for individuals using wheelchairs.See Accessibility Narrative for additional information.

SUSTAINABILITY FEATURES

vs. Private

Please refer to structural narrative for more information on structural requirements.

CRITICAL DIMENSIONS

Length, Width, Shape

249 Room Data Sheets | FREELON BOND Infrastructure Only 0 Other Amenities Deionized Water Vacuum Yes Speakers OH Gr. 2, 130 SF/HD FIRE ALARM Smoke Detection Yes Wet Sprinkler Special Waste Dry Sprinkler Pre-Action Sprinkler No FIRE PROTECTION No Considerations for Water 0 No Floor Drains Floor Sink Grey/Blackwater Piping 0 No No No Protected Hot/Cold No No Recycled Water Supply (treated) 0 No Public Address Audio Compressed Air Audio Visual Requirements No Hot/Cold Water Task Light No No 0 Plant/Clean Steam No Acoustic Sensitivity No Vibration Sensitivity Special Equipment/Artifact Sensitivity PLUMBING Target Illuminance (IES 9th Edition) Daylight Sensor 10 FC Exhibit Light No Power Density (AHSRAE 2004) 0.8 W/ft² Temperature Deviations (+/-) No No Process Water UPS Switched Receptacles Dimming To Be Considered Humidity 0 No Other Humidity Deviation (+/-) As required by load No No Outside Air Single/Multi-Level Switching 0 Emergency/Standby Power As required by code 30/85 Single Occupancy Sensor Special Exhaust Sub-metering & Feedback Displays Filtration (Pre/Final/Other) Voice/Data DATA/TELECOMMUNICATIONS 0 0 SECURITY 0 7.5 kPa/17.8 kN Floor Loading/Point Loads DAYLIGHTING 0 0 Shading Considerations Top/Side Lighting None No STRUCTURAL 0 0 Refer to information indicated in Volume IV, Section E Full 0 Technical Comment: Operations Storage Assignable Square Feet (ASF) OFEO Space Dimensions 0 Organizational Unit Other Interior Glazing 0 0 Yes Yes 0 Ceiling CRITICAL FINISHES 0 0
ELECTRICAL ARCHITECTURAL
features may not have been available and was intentionally left blank. Zone Room ID D3.73 Room Name 0 Functional Description Storage areas for maintenance tools and equipment, with utility finish and building systems, and industrial metal shelving or racking. Non Public-Non Collection Space 200 Number of Occupants NA Visual Privacy (full, partial, open) Zone Designation Zone D Room Height 0 LEED NC Regurlarly Occupied Space 0 Base ACOUSTICS Equipment Hardware/STC Rating None NRC0 0 Plug Loads Air Change/ HR Walls HVAC ENGINEERING CRITERIA Temperature Lighting No Control ±2ºF 110v, 20a, 1ph Yes 0 Power No 0 Pressure (+/-) 78ºF Summer, 70ºF Winter Floor Operable Windows
Moveable Yes Fixed RT60 & Shaping 0 TBD
Separation/STC FURNITURE/EQUIPMENT
Protective Services Area
Floor Level 0 Room
Open

This room data sheet is not comprehensive in nature. Information regarding specific room features may not have been available and was intentionally left

Accessibility Requirement:

Adjacencies

Compliance with ADA/ABAAG (2004) citations is required for accessibility. SI also requires compliance with SI Accessibility Guidelines and the IBC. Comparisons should be made and the more stringent requirement followed for design purposes. An accessible route including a minimum clear width of 36" (except through doors, which must be at least 32" clear) is required. Refer to ADA/ABAAG (2004) for specifications regarding clear floor spaces at desks, files and equipment for individuals using wheelchairs.See Accessibility Narrative for additional information.

SUSTAINABILITY FEATURES

etc.) should not contain any liquid cleansers or solvents that could potentially off-gas into gallery or public areas.

CRITICAL DIMENSIONS

Please refer to structural narrative for more information on structural requirements.

Smithsonian Institution National Museum of African American History and Culture 250 Infrastructure Only 0 Other Amenities Deionized Water Vacuum Yes Speakers OH Gr. 2, 130 SF/HD FIRE ALARM Smoke Detection Yes Wet Sprinkler Special Waste Dry Sprinkler Pre-Action Sprinkler No FIRE PROTECTION No Considerations for Water 0 No Floor Drains Floor Sink Grey/Blackwater Piping 0 No No No Protected Hot/Cold No No Recycled Water Supply (treated) 0 Yes Public Address Audio Compressed Air Audio Visual Requirements Yes Hot/Cold Water Task Light No No 0 Plant/Clean Steam No Acoustic Sensitivity No Vibration Sensitivity Special Equipment/Artifact Sensitivity PLUMBING Target Illuminance (IES 9th Edition) Daylight Sensor 10 FC Exhibit Light No Power Density (AHSRAE 2004) 0.8 W/ft² Temperature Deviations (+/-) No No Process Water UPS Switched Receptacles Dimming To Be Considered Humidity 0 No Other Humidity Deviation (+/-) As required by load No No Outside Air Single/Multi-Level Switching 0 Emergency/Standby Power As required by code 30/85 Single Occupancy Sensor Special Exhaust Sub-metering & Feedback Displays Filtration (Pre/Final/Other) Voice/Data DATA/TELECOMMUNICATIONS 0 0 SECURITY 0 5.0 kPa/8.9 kN Floor Loading/Point Loads DAYLIGHTING 0 0 Shading Considerations Top/Side Lighting None No STRUCTURAL 0 0 Refer to information indicated in Volume IV, Section E Full/Partial 0 Technical Comment: Custodials/Janitorials Assignable Square Feet
OFEO Space Dimensions 0 Organizational Unit Other Interior Glazing 0 0 Yes Yes 0 Ceiling CRITICAL FINISHES 0 0
(ASF)
ELECTRICAL ARCHITECTURAL
Zone Room ID D3.74 Room Name 0 Functional
Janitorial
distributed throughout building, used
vacuums,
Non Public-Non Collection Space 450 Number of Occupants NA Visual Privacy (full, partial, open) Zone Designation Zone D Room Height 0 LEED NC Regurlarly Occupied Space 0 Base ACOUSTICS Equipment Hardware/STC Rating None NRCSTC 55 0 Plug Loads Air Change/ HR Walls HVAC ENGINEERING
Temperature Lighting No Control ±2ºF 110v, 20a, 1ph Yes 0 Power No 0 Pressure (+/-) 78ºF Summer, 70ºF Winter Floor Operable Windows Separation/STC
Moveable Yes Fixed RT60 &
0 TBD
blank.
Description
Closets
for the storage of cleaning supplies (floor cleaners/polishers,
CRITERIA
FURNITURE/EQUIPMENT
Shaping
Distributed
Floor Level Sizable Room
Open
Length, Width, Shape
vs. Private

This room data sheet is not comprehensive in nature. Information regarding specific room features may not have been available and was intentionally left blank.

Accessibility Requirement:

Adjacencies

Compliance with ADA/ABAAG (2004) citations is required for accessibility. SI also requires compliance with SI Accessibility Guidelines and the IBC. Comparisons should be made and the more stringent requirement followed for design purposes. An accessible route including a minimum clear width of 36" (except through doors, which must be at least 32" clear) is required. Refer to ADA/ABAAG (2004) for specifications regarding clear floor spaces at desks, files and equipment for individuals using wheelchairs.See Accessibility Narrative for additional information.

SUSTAINABILITY FEATURES

vs. Private

Please refer to structural narrative for more information on structural requirements.

CRITICAL DIMENSIONS

Length, Width, Shape

251 Room Data Sheets | FREELON BOND Infrastructure Only 0 Other Amenities Deionized Water Vacuum Yes Speakers OH Gr. 2, 130 SF/HD FIRE ALARM Smoke Detection Yes Wet Sprinkler Special Waste Dry Sprinkler Pre-Action Sprinkler No FIRE PROTECTION No Considerations for Water 0 No Floor Drains Floor Sink Grey/Blackwater Piping 0 No No No Protected Hot/Cold No No Recycled Water Supply (treated) 0 No Public Address Audio Compressed Air Audio Visual Requirements No Hot/Cold Water Task Light To Be Considered No 0 Plant/Clean Steam No Acoustic Sensitivity No Vibration Sensitivity Special Equipment/Artifact Sensitivity PLUMBING Target Illuminance (IES 9th Edition) Daylight Sensor 30 FC Exhibit Light No Power Density (AHSRAE 2004) 1.5 W/ft² Temperature Deviations (+/-) No No Process Water UPS Switched Receptacles Dimming To Be Considered Humidity 0 Yes Other Humidity Deviation (+/-) As required by load No No Outside Air Single/Multi-Level Switching 0 Emergency/Standby Power As required by code 30/85 Single Occupancy Sensor Special Exhaust Sub-metering & Feedback Displays Filtration (Pre/Final/Other) Voice/Data DATA/TELECOMMUNICATIONS Yes 0 SECURITY 0 5.0 kPa/8.9 kN Floor Loading/Point Loads DAYLIGHTING 0 0 Shading Considerations Top/Side Lighting None No STRUCTURAL 0 0 Refer to information indicated in Volume IV, Section E Full Included in Grossing Factor. Technical Comment: Telephone/Electrical Closets Assignable Square Feet (ASF) OFEO Space Dimensions 0 Organizational Unit Other Interior Glazing 0 0 Yes Yes 0 Ceiling CRITICAL FINISHES 0 0
ELECTRICAL ARCHITECTURAL
Zone Room ID D3.75 Room Name 0 Functional Description Utility closet for specialty equipment and services Non Public-Non Collection Space 0 Number of Occupants NA Visual Privacy (full, partial, open) Zone Designation Zone
Room Height 0 LEED NC Regurlarly Occupied Space 0 Base ACOUSTICS Equipment Hardware/STC Rating None NRCSTC 55 0 Plug Loads Air Change/ HR Walls HVAC ENGINEERING CRITERIA Temperature Lighting No Control ±2ºF 110v, 20a, 1ph Yes 0 Power Yes 0 Pressure (+/-) 78ºF Summer, 70ºF Winter Floor Operable Windows
Moveable Yes Fixed RT60 & Shaping 0 TBD
D
Separation/STC FURNITURE/EQUIPMENT
Distributed
Floor Level 0 Room
Open

This room data sheet is not comprehensive in nature. Information regarding specific room features may not have been available and was intentionally left blank.

Accessibility Requirement:

Adjacencies

SUSTAINABILITY FEATURES

Compliance with ADA/ABAAG (2004) citations is required for accessibility. SI also requires compliance with SI Accessibility Guidelines and the IBC. Comparisons should be made and the more stringent requirement followed for design purposes. An accessible route including a minimum clear width of 36" (except through doors, which must be at least 32" clear) is required. Refer to ADA/ABAAG (2004) for specifications regarding clear floor spaces at desks, files and equipment for individuals using wheelchairs.See Accessibility Narrative for additional information.

CRITICAL DIMENSIONS

Length, Width, Shape Open vs. Private

Please refer to structural narrative for more information on structural requirements.

Smithsonian Institution National Museum of African American History and Culture 252 Infrastructure Only 0 Other Amenities Deionized Water Vacuum Yes Speakers OH Gr. 2, 130 SF/HD FIRE ALARM Smoke Detection Yes Wet Sprinkler Special Waste Dry Sprinkler Pre-Action Sprinkler No FIRE PROTECTION No Considerations for Water 0 No Floor Drains Floor Sink Grey/Blackwater Piping 0 No No No Protected Hot/Cold No No Recycled Water Supply (treated) 0 No Public Address Audio Compressed Air Audio Visual Requirements No Hot/Cold Water Task Light To Be Considered No 0 Plant/Clean Steam No Acoustic Sensitivity No Vibration Sensitivity Special Equipment/Artifact Sensitivity PLUMBING Target Illuminance (IES 9th Edition) Daylight Sensor 30 FC Exhibit Light No Power Density (AHSRAE 2004) 1.5 W/ft² Temperature Deviations (+/-) No No Process Water UPS Switched Receptacles Dimming To Be Considered Humidity 0 Yes Other Humidity Deviation (+/-) As required by load No No Outside Air Single/Multi-Level Switching 0 Emergency/Standby Power As required by code 30/85 Single Occupancy Sensor Special Exhaust Sub-metering & Feedback Displays Filtration (Pre/Final/Other) Voice/Data DATA/TELECOMMUNICATIONS Yes 0 SECURITY 0 5.0 kPa/8.9 kN Floor Loading/Point Loads DAYLIGHTING 0 0 Shading Considerations Top/Side Lighting None No STRUCTURAL 0 0 Refer to information indicated in Volume IV, Section E Full Included in Grossing Factor. Technical Comment: Hub Closet Assignable Square Feet (ASF) OFEO Space Dimensions 0 Organizational Unit Other Interior Glazing 0 0 Yes Yes 0 Ceiling CRITICAL FINISHES 0 0
ELECTRICAL ARCHITECTURAL
Zone Room ID D3.76 Room Name 0 Functional Description Utility closet for specialty equipment and services Non Public-Non Collection Space 0 Number of Occupants NA Visual Privacy (full, partial, open) Zone
Room Height 0 LEED NC Regurlarly Occupied Space 0 Base ACOUSTICS Equipment Hardware/STC Rating None NRCSTC 55 0 Plug Loads Air Change/ HR Walls HVAC ENGINEERING CRITERIA Temperature Lighting No Control ±2ºF 110v, 20a, 1ph Yes 0 Power Yes 0 Pressure (+/-) 78ºF Summer, 70ºF Winter Floor Operable Windows Separation/STC FURNITURE/EQUIPMENT Moveable Yes Fixed RT60 & Shaping 0 TBD
Designation Zone D
Distributed
Floor Level 0 Room

This room data sheet is not comprehensive in nature. Information regarding specific room features may not have been available and was intentionally left blank.

FEATURES

Compliance with ADA/ABAAG (2004) citations is required for accessibility. SI also requires compliance with SI Accessibility Guidelines and the IBC. Comparisons should be made and the more stringent requirement followed for design purposes. An accessible route including a minimum clear width of 36" (except through doors, which must be at least 32" clear) is required. Refer to ADA/ABAAG (2004) for specifications regarding clear floor spaces at desks, files and equipment for individuals using wheelchairs.See Accessibility Narrative for additional information.

CRITICAL DIMENSIONS

Length, Width, Shape Open vs. Private

253 Room Data Sheets | FREELON BOND Infrastructure Only 0 Other Amenities Deionized Water Vacuum Yes Speakers OH Gr. 2, 130 SF/HD FIRE ALARM Smoke Detection Yes Wet Sprinkler Special Waste Dry Sprinkler Pre-Action Sprinkler 0 FIRE PROTECTION 0 Considerations for Water 0 0 Floor Drains Floor Sink Grey/Blackwater Piping 0 0 0 0 Protected Hot/Cold 0 0 Recycled Water Supply (treated) 0 0 Public Address Audio Compressed Air Audio Visual Requirements 0 Hot/Cold Water Task Light 0 0 0 Plant/Clean Steam 0 Acoustic Sensitivity 0 Vibration Sensitivity Special Equipment/Artifact Sensitivity PLUMBING Target Illuminance (IES 9th Edition) Daylight Sensor 0 Exhibit Light 0 Power Density (AHSRAE 2004) 0 Temperature Deviations (+/-) 0 0 Process Water UPS Switched Receptacles Dimming 0 Humidity 0 0 Other Humidity Deviation (+/-) 0 0 0 Outside Air Single/Multi-Level Switching 0 Emergency/Standby Power 0 0 0 Occupancy Sensor Special Exhaust Sub-metering & Feedback Displays Filtration (Pre/Final/Other) Voice/Data DATA/TELECOMMUNICATIONS Yes 0 SECURITY 0 5.0 kPa/8.9 kN Floor Loading/Point Loads DAYLIGHTING 0 0 Shading Considerations Top/Side Lighting 0 0 STRUCTURAL 0 0 Refer to information indicated in Volume IV, Section E Full With Views/Windows Technical Comment: Custodial Lounge/Break Room Assignable Square Feet (ASF) OFEO Space Dimensions 0 Organizational Unit Other Interior Glazing 0 0 Yes Yes 0 Ceiling CRITICAL FINISHES 0 0 0 ELECTRICAL ARCHITECTURAL
Zone Room ID D3.77 Room Name 0 Functional Description Break Room for Custodial staff, with coffee/microwave facilities, and lunch table and chairs. Used for roll call/check in for each shift, radio pickup and charging, bulletin boards. Non Public-Non Collection Space 500 Number of Occupants TBD Visual Privacy (full, partial, open) Zone Designation Zone D Room Height 0 LEED NC Regurlarly Occupied Space 0 Base ACOUSTICS Equipment Hardware/STC Rating 0 NRC0 0 Plug Loads Air Change/ HR Walls HVAC ENGINEERING CRITERIA Temperature Lighting 0 0 110v, 20a, 1ph 0 0 Power 0 0 Pressure (+/-) 0 Floor Operable Windows Separation/STC FURNITURE/EQUIPMENT Moveable Yes Fixed RT60 & Shaping 0 TBD
Distributed
Floor Level 0 Room
SUSTAINABILITY
Adjacencies Accessibility Requirement:

This room data sheet is not comprehensive in nature. Information regarding specific room features may not have been available and was intentionally left blank.

Accessibility Requirement:

Adjacencies

SUSTAINABILITY FEATURES

Compliance with ADA/ABAAG (2004) citations is required for accessibility. SI also requires compliance with SI Accessibility Guidelines and the IBC. Comparisons should be made and the more stringent requirement followed for design purposes. An accessible route including a minimum clear width of 36" (except through doors, which must be at least 32" clear) is required. Refer to ADA/ABAAG (2004) for specifications regarding clear floor spaces at desks, files and equipment for individuals using wheelchairs.See Accessibility Narrative for additional information.

CRITICAL DIMENSIONS

Length, Width, Shape

Please refer to structural narrative for more information on structural requirements.

Smithsonian Institution National Museum of African American History and Culture 254 Infrastructure Only 0 Other Amenities Deionized Water Vacuum Yes Speakers OH Gr. 2, 130 SF/HD FIRE ALARM Smoke Detection Yes Wet Sprinkler Special Waste Dry Sprinkler Pre-Action Sprinkler No FIRE PROTECTION No Considerations for Water 0 No Floor Drains Floor Sink Grey/Blackwater Piping 0 No No No Protected Hot/Cold No No Recycled Water Supply (treated) 0 No Public Address Audio Compressed Air Audio Visual Requirements No Hot/Cold Water Task Light No No 0 Plant/Clean Steam No Acoustic Sensitivity No Vibration Sensitivity Special Equipment/Artifact Sensitivity PLUMBING Target Illuminance (IES 9th Edition) Daylight Sensor 10 FC Exhibit Light No Power Density (AHSRAE 2004) 0.8 W/ft² Temperature Deviations (+/-) No No Process Water UPS Switched Receptacles Dimming To Be Considered Humidity 0 No Other Humidity Deviation (+/-) As required by load No No Outside Air Single/Multi-Level Switching 0 Emergency/Standby Power As required by code 30/85 Single Occupancy Sensor Special Exhaust Sub-metering & Feedback Displays Filtration (Pre/Final/Other) Voice/Data DATA/TELECOMMUNICATIONS 0 0 SECURITY 0 7.5 kPa/17.8 kN Floor Loading/Point Loads DAYLIGHTING 0 0 Shading Considerations Top/Side Lighting None No STRUCTURAL 0 0 Refer to information indicated in Volume IV, Section E Full Storage area for maintenance tools and equipment with utility finish and building systems, and industrial metal shelving or racking.
Horticultural Space Assignable Square Feet (ASF) OFEO Space Dimensions 0 Organizational Unit Other Interior Glazing 0 0 Yes Yes 0 Ceiling CRITICAL FINISHES 0 0
Technical Comment:
ELECTRICAL ARCHITECTURAL
Zone Room ID D3.78 Room Name 0 Functional
Storage area for maintenance tools
equipment
utility finish
building
industrial metal shelving or racking Non Public-Non Collection Space 150 Number of Occupants NA Visual Privacy (full, partial, open) Zone Designation Zone D Room Height 0 LEED NC Regurlarly Occupied Space 0 Base ACOUSTICS Equipment Hardware/STC Rating None NRC0 0 Plug Loads Air Change/ HR Walls HVAC ENGINEERING CRITERIA Temperature Lighting No Control ±2ºF 110v, 20a, 1ph Yes 0 Power No 0 Pressure (+/-) 78ºF Summer, 70ºF Winter Floor Operable Windows Separation/STC FURNITURE/EQUIPMENT Moveable Yes Fixed RT60
0 TBD
Description
and
with
and
systems, and
& Shaping
Loading
Bay
Floor Level 0 Room
Open vs. Private

NMAAHC Pre-design and Programming Team

Owner

Smithsonian Institution

Architecture, Master Planning & Facility Programming

Freelon Bond

Master Planning, Museum Planning, Space Programming, Visitation Studies, Collections & Archive Management

Lord Cultural Resources

Exhibit Design

Amaze Design

Visitation Studies

Institute for Learning Innovation

Landscape Design

Peter Walker & Partners

Structural Engineer

Robert Silman Associates

MEP

SEI Company

Sustainable Design

Rocky Mountain Institute (RMI)

Civil Engineer

Delon Hampton & Associates

Traffic Studies

Gorove Slade

Geotechnical & Environmental Engineering

Froehling & Robertson, Inc.

IT/AV/Data Management/ Telecommunications

Shen Milsom Wilke

Multi-Media Performance

Fisher Dachs Associates

Code / Fire Protection

Rolf Jensen & Associates

Accessibility

Access-Andrews Consulting

Vertical Transportation

Lerch Bates

Lighting Design

Fisher Marantz Stone

Estimating

Faithful + Gould

Security

Ducibella Venture & Santore

Turn static files into dynamic content formats.

Create a flipbook
Issuu converts static files into: digital portfolios, online yearbooks, online catalogs, digital photo albums and more. Sign up and create your flipbook.