3.3.2 Production Spaces
Figure 3.3.4 Requirements for rescue routes in production spaces
Every production space or storage room with more than 200 m² requires two exits
For multistory industrial buildings with a floor area of more than 1,600 m², a minimum of two physical rescue routes must be present in each story, preferably opposite each other
Figure 3.3.5 Options for heating production halls
From every point within a production space or storage room, at least one exit to the exterior, a compulsory stairwell, another fire compartment, or a firefighting section must be reachable: − within a maximum distance of 35 m for rooms with an average clear ceiling height of up to 5 m – within a maximum distance of 50 m for rooms with an average clear ceiling height of 10 m or more
Rescue routes for industrial buildings
Includes: Main aisles in production spaces and storage rooms; exits from these spaces to the exterior; compulsory stairs and corridors
At least one main aisle must be within 15 m of any point within every space
Radiant heaters
Ambient air heaters
Underfloor radiant heat