TECHNICAL DATA: 10-2014
LED Module & Arrays Emergency Equipment LD-CO Range The ELP LD-CO emergency LED control gear allows maintained operation of high power LED modules or arrays, such as the Philips Fortimo DLM & SLM, Xicato XSM range, Bridgelux ES range, Citizen CL range and the Osram PrevaLED2 range when utilizing the standard mains voltage LED control gear in-line with the emergency LED control gear. The emergency gear incorporates an emergency LED driver module/charger and a high temperature Nickel Cadmium or Nickel Metal Hydride battery. In the event of a mains failure, an integral relay disconnects the LED lighting load from the mains control gear and then connects it to the emergency control gear, which operates the LED module/array at a reduced light output for a duration of 3 hours. The various high power LED modules utilise different arrays of LEDs connected in series or a combination of series and parallel, and the LD-CO range can be configured to suit any of these. It is important to note that some of the LED module/array mains drivers should not be operated with an open circuit load, to overcome this problem when first powering up or when switching between emergency and mains operations the LD-CO range features a live in/ live out relay which ensures the load is in place before the mains driver is powered up. NB: The LD-CO range is available with fully interoperable Dali control and reporting fuction. These /DALI versions provide automatic Self-Test if no Dali signal is connected.
ORDER CODES FOR KITS To ensure the correct operation of each type of high power LED module/array the correct LD-CO equipment should be selected. The following codes should be used to order the appropriate module and battery for the following LED Modules and Arrays: Philips Fortimo
3000 & 2000 lumen DLM & SLM 1100 lumen DLM & SLM
LD22CO50DLMK LD9CO100DLMK
Xicato XSM Range 400-1300 lumen 2000- 3000 lumen
LD9CO100K & LD8CO300K (High-output) LD16CO100K
Bridgelux ES Range & Citizen CL Range
LD9CO100K
Osram PrevaLED2
LD24CO50K
ALL LD-CO UNITS REQUIRE MAINS LED CONTROL GEAR FOR MAINTAINED OPERATION
Emergency Lighting Products Limited Unit 9 Gillmans Industrial Estate, Natts Lane Billingshurst, West Sussex RH14 9EZ Telephone: +44 (0)1403 786601 Fax: +44 (0)1403 786602 e-mail:sales@elp.uk.com www.elp.uk.com
SPECIFICATION
LED Module & Arrays Emergency Equipment Section
Subject Protection against electric shock Ingress protection
Environmental
-20 to 50째C
Battery rated operating ambient temperature
0 - 50째C
Rated voltage supply Mains frequency
60째C 220/240 VAC 50/60 Hz
Mains supply current
15mA
Mains supply power
3.6W 0.6
Power factor Indicator LED Maximum power that can be switched via relay contacts contacts current that can be switched via relay contacts Maximum
2 wire green colour
Maximum voltage that can be switched via relay contacts Emergency duration
250V 1 or 3 hours
Battery chemistry type Number and type of cells LD22CO50DLMK, LD9CO100DLMK & LD9CO100K LD16CO100K LD24CO50K LD8CO300K, Battery recharge period
Emergency operation
IP20
Module rated operating ambient temperature Maximum case temperature
Mains operation
Plastic housed module Secondary outputs SELV equivalent
60W 2A
NiCad or NiMH
5 x 2Ah NiCad sub-C cells 5 x 4Ah NiMH C or 4Ah NiCad D cells 6 x 2Ah NiCad sub-C cells 6 x 4Ah NiMH C or 4Ah NiCad D cells <24 hours
Battery charge current LD22CO50DLMK, LD9CO100DLMK & LD9CO100K LD16CO100K, LD8CO300K & LD24CO50K
100mA 160mA
Battery discharge current LD22CO50DLMK, LD9CO100DLMK & LD9CO100K LD16CO100K, LD8CO300K & LD24CO50K
500mA 1000mA
Module output current LD22CO50DLMK & LD24CO50K LD16CO100K, LD9CO100DLMK & LD9CO100K LD8CO300K Module output voltage LD8CO300K LD9CO100DLMK & LD9CO100K LD16CO100K LD22CO50DLMK LD24CO50K BLF/EBLF - dependant on LED module type Mechanical
Standards compliance
Outside dimensions Fixing centres Electrical connections
50mA 100mA 300mA 11.5V to <23.5V 9V to <33V 9V to <56V 9V to <56V 11.5V to <64V 0.12 to 0.25 L178mm x W30mm x H21mm 174mm Push wire terminals
EN61347-1, EN61347-2-7 & EN61347-2-13 EN62384
Yes
EN55015
Yes
EN61547
Yes
Marks CE
Yes
Note: Values are subject to change
Emergency Lighting Products Limited Unit 9 Gillmans Industrial Estate, Natts Lane Billingshurst, West Sussex RH14 9EZ Telephone: +44 (0)1403 786601 Fax: +44 (0)1403 786602 e-mail:sales@elp.uk.com www.elp.uk.com