ELP LD-CO Range

Page 1

TECHNICAL DATA: 10-2014

LED Module & Arrays Emergency Equipment LD-CO Range The ELP LD-CO emergency LED control gear allows maintained operation of high power LED modules or arrays, such as the Philips Fortimo DLM & SLM, Xicato XSM range, Bridgelux ES range, Citizen CL range and the Osram PrevaLED2 range when utilizing the standard mains voltage LED control gear in-line with the emergency LED control gear. The emergency gear incorporates an emergency LED driver module/charger and a high temperature Nickel Cadmium or Nickel Metal Hydride battery. In the event of a mains failure, an integral relay disconnects the LED lighting load from the mains control gear and then connects it to the emergency control gear, which operates the LED module/array at a reduced light output for a duration of 3 hours. The various high power LED modules utilise different arrays of LEDs connected in series or a combination of series and parallel, and the LD-CO range can be configured to suit any of these. It is important to note that some of the LED module/array mains drivers should not be operated with an open circuit load, to overcome this problem when first powering up or when switching between emergency and mains operations the LD-CO range features a live in/ live out relay which ensures the load is in place before the mains driver is powered up. NB: The LD-CO range is available with fully interoperable Dali control and reporting fuction. These /DALI versions provide automatic Self-Test if no Dali signal is connected.

ORDER CODES FOR KITS To ensure the correct operation of each type of high power LED module/array the correct LD-CO equipment should be selected. The following codes should be used to order the appropriate module and battery for the following LED Modules and Arrays: Philips Fortimo

3000 & 2000 lumen DLM & SLM 1100 lumen DLM & SLM

LD22CO50DLMK LD9CO100DLMK

Xicato XSM Range 400-1300 lumen 2000- 3000 lumen

LD9CO100K & LD8CO300K (High-output) LD16CO100K

Bridgelux ES Range & Citizen CL Range

LD9CO100K

Osram PrevaLED2

LD24CO50K

ALL LD-CO UNITS REQUIRE MAINS LED CONTROL GEAR FOR MAINTAINED OPERATION

Emergency Lighting Products Limited Unit 9 Gillmans Industrial Estate, Natts Lane Billingshurst, West Sussex RH14 9EZ Telephone: +44 (0)1403 786601 Fax: +44 (0)1403 786602 e-mail:sales@elp.uk.com www.elp.uk.com


SPECIFICATION

LED Module & Arrays Emergency Equipment Section

Subject Protection against electric shock Ingress protection

Environmental

-20 to 50째C

Battery rated operating ambient temperature

0 - 50째C

Rated voltage supply Mains frequency

60째C 220/240 VAC 50/60 Hz

Mains supply current

15mA

Mains supply power

3.6W 0.6

Power factor Indicator LED Maximum power that can be switched via relay contacts contacts current that can be switched via relay contacts Maximum

2 wire green colour

Maximum voltage that can be switched via relay contacts Emergency duration

250V 1 or 3 hours

Battery chemistry type Number and type of cells LD22CO50DLMK, LD9CO100DLMK & LD9CO100K LD16CO100K LD24CO50K LD8CO300K, Battery recharge period

Emergency operation

IP20

Module rated operating ambient temperature Maximum case temperature

Mains operation

Plastic housed module Secondary outputs SELV equivalent

60W 2A

NiCad or NiMH

5 x 2Ah NiCad sub-C cells 5 x 4Ah NiMH C or 4Ah NiCad D cells 6 x 2Ah NiCad sub-C cells 6 x 4Ah NiMH C or 4Ah NiCad D cells <24 hours

Battery charge current LD22CO50DLMK, LD9CO100DLMK & LD9CO100K LD16CO100K, LD8CO300K & LD24CO50K

100mA 160mA

Battery discharge current LD22CO50DLMK, LD9CO100DLMK & LD9CO100K LD16CO100K, LD8CO300K & LD24CO50K

500mA 1000mA

Module output current LD22CO50DLMK & LD24CO50K LD16CO100K, LD9CO100DLMK & LD9CO100K LD8CO300K Module output voltage LD8CO300K LD9CO100DLMK & LD9CO100K LD16CO100K LD22CO50DLMK LD24CO50K BLF/EBLF - dependant on LED module type Mechanical

Standards compliance

Outside dimensions Fixing centres Electrical connections

50mA 100mA 300mA 11.5V to <23.5V 9V to <33V 9V to <56V 9V to <56V 11.5V to <64V 0.12 to 0.25 L178mm x W30mm x H21mm 174mm Push wire terminals

EN61347-1, EN61347-2-7 & EN61347-2-13 EN62384

Yes

EN55015

Yes

EN61547

Yes

Marks CE

Yes

Note: Values are subject to change