=n ANSI B31.3: 341.4 Extent of Required Examination Piping Class
Description
Clause
Normal Fluid Service.
Process
341.4.1 Examination — Normal Fluid Service.
Category D Fluid Service.
Utility
Severe Cyclic Conditions.
Cyclic conditions defined by Engineering
341.4.3 Examination — Severe Cyclic Conditions. (b) Other
Highly toxic
M341.4 Extent of Required Examination
Cat. M
(1) Not less than 5% of circumferential butt and miter groove welds shall be examined fully by random radiography in accordance with para. 344.5 or by random ultrasonic examination in accordance with para. 344.6.
341.4.2 Examination — Category D Fluid Service. 341.4.2 Examination — Category D Fluid Service. Piping and piping elements for Category D Fluid Service as designated in the engineering design shall be visually examined in accordance with para. 344.2 to the extent necessary................
Examination. All circumferential butt and miter groove welds and all fabricated branch connection welds comparable to those shown in Fig. 328.5.4E shall be examined by 100% radiography in accordance with para. 344.5, or (if specified in the engineering design) by 100% ultrasonic examination in accordance with para. 344.6.
(1) The random radiography/ultrasonic examination requirements of para. 341.4.1(b)(1) apply except that at least 20% of circumferential butt and miter welds and of fabricated lap and branch connection welds comparable to those shown in Figs. 328.5.4E and 328.5.5 sketches (d) and (e) shall be examined.
Cat. K
High Pressure
K341.4.2 Radiographic and Ultrasonic Examination (a) All girth, longitudinal, and branch connection welds shall be 100% radiographically examined, except as permitted in (b) below. (b) When specified in the engineering design and with the owner’s approval, ultrasonic examination of welds may be substituted for radiographic examination where Tw ≥ 13 mm (1⁄2 in.). (c) In-process examination (see para. 344.7) shall not be substituted for radiographic or ultrasonic examination of welds.
Extend 0f Volumetric NDE 5%
RT
0%
No requirement
UT
Visual only Not applicable
No requirement
Not applicable
100% or (if specified in the engineering design)
20%
Not applicable
100%
Not applicable
When specified in the engineering design and with the owner’s approval